HYpact Compact Hybrid
HYpact Compact Hybrid
HYpact Compact Hybrid
Alstom Grid has been manufacturing high voltage air insulated switchgear for over 100 years. More than 120 000 products have been installed and are in service worldwide. Our investments in R&D are significant, allowing users of our equipment to benefit from the latest technologies and innovations.
COMPACT SWITCHGEAR
l HYpact
Quality
Our markets and customers are changing fast - and so are we! We are committed to achieving excellence in quality, which is our number one priority. We strive for customer satisfaction through the improvement of all processes whether in terms of quality, cost or lead times. This applies to projects and administrative procedures throughout the entire business process, from tender to final delivery of our products, systems and services. An ISO 9001-certified quality management system, ISO 14001-certified environmental management system as well as OHSAS 18001- certified occupational health and safety management systems govern the entire development and production processes for our high voltage products and ensure through regularly conducted audits the highest standards of quality for all our products and services.
COMPACT SWITCHGEAR
l HYpact
Advantages
Compact switchgear assemblies save space as their name suggests. A switchyard based on hybrid compact switchgear gains more than 50 % in space savings compared to conventional open-type substations
But space savings is only one advantage. Increasingly, operators choose HYpact even where space is ample, just to benefit from the long periods between maintenance of circuit-breakers and gas insulated disconnectors and earthing switches. Compared to conventional air insulated substations, the maintenance-free periods of substations using HYpact are considerably prolonged. Besides savings in space and maintenance, HYpact largely reduces the switchgears exposure to environmental influences, thus providing an economical alternative to gas insulated substations in places that are heavily polluted, or suffer extreme weather conditions.
Due to the reduced number of single components the substations civil works requirements, such as foundations, steel supports, cable trenches and high voltage connections are simplified. Installation works are limited to only one to two days per bay, which can often be executed without our specialised supervisors.
COMPACT SWITCHGEAR
l HYpact
Hybrid compact switchgear assemblies allow optimised substation designs that differ from conventional air or gas insulated substation designs. Substation layouts are defined by the nature of the assembly as one unit and by the operational and maintenance requirements of the entire substation and the surrounding grid. Our experienced specialists are happy to advise you in defining your most preferred solution! The main versions of HYpact, described in the next pages of this document, can be integrated into the following substation types (examples only):
COMPACT SWITCHGEAR
l HYpact
H-schemes with three circuit-breakers (switchable busbar) Extendable to larger single busbar applications
COMPACT SWITCHGEAR
l HYpact
COMPACT SWITCHGEAR
l HYpact
Bus section with bus coupler circuit-breaker (incoming/outgoing feeder and transformer feeder, within one bay section)
COMPACT SWITCHGEAR
l HYpact
H-schemes with five circuit-breakers (switchable busbar) Extendable to larger single busbar applications
COMPACT SWITCHGEAR
l HYpact
Components overview
10
COMPACT SWITCHGEAR
l HYpact
11
COMPACT SWITCHGEAR
l HYpact
The inter-phase linkages as well as linkages between drive mechanisms and switchgear can be fully covered when necessary due to environmental conditions or due to safety regulations.
Bushings can be supplied either as porcelain or composite bushings. The creepage distance is designed for very heavily polluted areas. (Pollution level IV according to IEC 60815.)
12
COMPACT SWITCHGEAR
l HYpact
The three-position switch provides a closed disconnector switch with open earthing switch, an open disconnector switch with open earthing switch and an open disconnector switch with closed earthing switch. The disconnector and earthing switches are intrinsically interlocked. Where substation design and operational requirements do not allow for integral earthing, a direct disconnector/earthing switch is provided. Here, the earthing switch operates independently of the circuit-breaker. Induced currents can be switched according to IEC 62271-102, annex C, class B.
When required, the disconnectors of both integral and direct disconnector/earthing switches can be reinforced with pre-arcing contacts, enabling the disconnector to switch bus-transfer currents occurring in large air insulated substations (1600 A - 100 V in accordance with IEC 62271-102, annex B, class B).
13
COMPACT SWITCHGEAR
l HYpact
Epoxy cast resin toroidal current transformers (with or without metal covers) are placed around disconnector/earthing switches so that they do not need extra space. Their large diameter ensures they can be slipped over bushings and gas works are not required in case these current transformers need to be replaced. At positions without disconnector/earthing switches, or for particular requirements concerning the position of the current transformers, either cast resin or slimmer tape-air insulated current transformers are available. Each current transformer can consist of up to five cores. As the number of cores depends on the current transformers ratio, number of taps, accuracy and power, current transformers are always defined by particular requirements.
Current transformers terminate into a separate measuring transformer wiring box serving as convenient interface with the substations secondary wiring. (To be omitted on request.)
The position of circuit -breaker and disconnector/ear -thing switches is displayed in a mechanically linked mimic diagram, conveniently visible from the HYpacts front side. Additional precision indicators show the exact position of disconnector/earthing switches, including tolerances permitted.
Circuit-breakers are powered by springoperated mechanisms from Alstom Grids FK 3-1 series. These drive mechanisms use the most reliable helical compression springs and are present in more than a hundred thousand live and dead tank circuit-breakers, gas insulated switchgear and compact switchgear assemblies worldwide.
Disconnector/earthing switches are operated by a three-position motor drive, allowing for emergency manual operation too. All drive mechanisms are mounted on the steel supports and readily adjusted when dispatched.
14
A central bay control is integrated either into the circuit-breaker drive mechanism or into a separate central control cubicle mounted on the HYpact. The bay control is equipped with conventional relays and contactors or by programmable logic controller. If the bay control is integrated into the substation protection and control scheme, the switchgear control at bay level can also be avoided.
Pluggable current contact Stresscone in silicone rubber Insulator in epoxy resin Inlet with inner spring assembly Clamp support Screen connection
Inductive voltage transformers may be integrated. These gas insulated voltage transformers are equipped with gas barriers to form separate gas zones. Integrated cable connectors are optionally available for several types of the most common cable connector manufacturers, either for dry or liquid type connectors.
15
COMPACT SWITCHGEAR
l HYpact
Main versions
HYpact's modular concept facilitates a variety of configurations suitable for most substation designs, of which the most prominent are shown below.
Single busbar versions:
HYpact for line and transformer bays: - one circuit-breaker - one integral disconnector/earthing switch - current transformers on either, or on both sides
Optionally available: - second disconnector/earthing switch (recommended for switched busbar application and bus coupler application) - either disconnector/earthing switch with direct earthing - integrated voltage transformers - integrated cable connectors
16
COMPACT SWITCHGEAR
l HYpact
17
The modular concept of HYpact allows its use in almost all substation layouts including single and double busbar applications, cable connectors and single- and three-phase operation for indoor and outdoor installations.
Spring-operated mechanism FK 3-1 Rated operating sequence of circuit-breaker O-0.3s-CO-3 min-CO resp. CO-15s-CO Rated supply voltage From 48 up to 250 Vdc/ac Maximum ambient temperature From -60 C up to +40 C (with pure SF6)
Type tests
The IEC standard for compact switchgear assemblies, IEC 62271-205 2008, requires not only the performance of type test for each individual device, but also the need to demonstrate the characteristics of the assembly in its entirety. Consequently, the complete HYpact consisting of circuitbreaker, disconnector, earthing switch and current transformer has undergone an extensive type test series, including, but not limited to power tests, dielectric tests, mechanical and environmental tests. Completive devices and functions, e.g. cable connectors or voltage transformers, have been tested according to their individual applicable standards also as part of the HYpact, to demonstrate that interactions between the devices and the HYpact do not limit their individual ratings or those of the entire assembly. HYpact type tests have been carried out in accredited and certified test laboratories.
18
19
Seismic qualification
Due to the low center of gravity and the compactness particularly of the encapsulated disconnectors and earthing switches, HYpact is the ideal switchgear for areas exposed to high seismic activity. To optimise the HYpact for use under very heavy seismic conditions, finite element method calculations have been carried out. As a result, HYpacts to be used in earthquake-prone areas are equipped with supports made of high yield-strength steel. For verification of the calculations, the HYpact was exposed to additional shaking table tests based on IEEE Std 693TM-2005 High Level, equalling to seismic accelerations of 0.7 g, which it passed without fail. HYpact under shaking table test
Seismic calculation
20
Container transport
Transport by truck
The two delivery units two steel stands with drive mechanisms and control cubicle mounted and the switchgear module containing the circuitbreaker, disconnector/earthing switches, current transformers, voltage transformers and bushings can be easily installed and commissioned in only one to three days per bay, without need for time-consuming evacuation and SF6-refilling works and without special tools.
Monitoring
In addition to standard product components, we develop optional systems to optimise the monitoring and maintenance of high voltage equipment.
CBWatch-2 monitoring system
The CBWatch-2 is a combination of new monitoring and maintenance optimisation tools accessible via web-based technology. The CBWatch-2 is installed in the control panel and maintains a constant, monitored link with a local or remote database via CBWatch Tool software. The monitoring system records information coming from the sensors installed on the breaker, then analyses the information, comparing it with standard operational parameters programmed into the system. CBWatch-2
21
22
23