Sepam Protection 20 and 40
Sepam Protection 20 and 40
Sepam Protection 20 and 40
Protection functions
Selection table
Protection functions
Series 20
07_C3213_En_protection_ind-B_04-2002.ppt
Selection table
Protection functions
Series 40
07_C3213_En_protection_ind-B_04-2002.ppt
Series 20
1 B
2 B
2 A
07_C3213_En_protection_ind-B_04-2002.ppt
1 A
1 B
2
2 A
Series 20
07_C3213_En_protection_ind-B_04-2002.ppt
Series 20
t
1 B
2 A
1 A
2 B
I
07_C3213_En_protection_ind-B_04-2002.ppt
Series 20
Series 20
07_C3213_En_protection_ind-B_04-2002.ppt
Series 40
2 groups of 4 elements :
functions(1A/2A/3A/4A)
group A, elements 1, 2, 3
and 4
functions(1A/2A/3A/4A)gr
oup B, elements 1, 2, 3
and 4
enabling/disabling :
group A OR group B
possibility to switch from
one group to the other
possibility to use group
switching AND logic
discriminition
07_C3213_En_protection_ind-B_04-2002.ppt
Series 40
07_C3213_En_protection_ind-B_04-2002.ppt
10
50/51 functions
Series 40
In the advanced parameters menu its possible to choose for each element
to have a confirmation of operation by using negative sequence overvoltage
protection (47) or undervoltage protection (27)
07_C3213_En_protection_ind-B_04-2002.ppt
11
50N/51N functions
Series 40
The choice between Io
(measured) and Io
(calculated by the sum of
the phase currents) can be
set for each element
by mixing these 2
possibilities it allows user:
to have different
dynamic set points
to have different
applications, e.g.
line zero sequence
protection and tank
earth leakage protection
07_C3213_En_protection_ind-B_04-2002.ppt
12
Series 20
Series 40
Definitions :
Reset time (of a protection) = time to return to the
initial state after the fault disappearance. (< 50ms)
Adjustable reset time (timer hold) = time added to the
reset time to delay the return to initial state and
bringing a memory into operation to enable the
function to be activated with intermittent faults.
07_C3213_En_protection_ind-B_04-2002.ppt
13
Series 20
Series 40
Applications :
definite time : detection of recurrent faults in network
grounded by Petersen coil (67NC)
IDMT : to allow the relay to have the same reset time
than an electromechanical relay in order to obtain a
better discrimination (when this relay is upstream)
07_C3213_En_protection_ind-B_04-2002.ppt
14
Reset characteristics
100%
tripping
time delay
I > Is
Timer hold
Tripping
time
15
16
0.1
0.2
0.3
0.4
0.5
figure 2
0.6
0.7
0.8
0.9
07_C3213_En_protection_ind-B_04-2002.ppt
17
-1
-2
0.1
0.2
0.3
0.4
0.5
figure 3
0.6
0.7
0.8
0.9
07_C3213_En_protection_ind-B_04-2002.ppt
18
50/51V function
Series 40
07_C3213_En_protection_ind-B_04-2002.ppt
19
50BF function
Series 40
This function is designed to
detect the failure of breakers
that do not open when a
tripping order is sent.
The failure to trip is detected
by a level of current or by the
close position of the circuit
breaker after a time delay.
07_C3213_En_protection_ind-B_04-2002.ppt
20
50BF function
Series 40
Example :
50/51 = inst. 40ms
output O1 = 10ms
CB = 60ms
time delay setting T :
output O1 = 10ms
CB = 60ms
overshoot time
50BF=20ms
safety margin = 20ms
==> T = 110ms
07_C3213_En_protection_ind-B_04-2002.ppt
21
67 function
Series 40
2 groups of 2 elements:
Functions 1A/2A :
group A, el. 1and 2
Functions 1B/2B :
group B, el.1 and 2
enabling/disabling
group A OR group B
possibility to switch
from one group to the
other
possibility to use
group switching AND
logic discrimination
07_C3213_En_protection_ind-B_04-2002.ppt
22
Protection 67
Series 40
23
Directional phase
overcurrent
V2
I1
V1
No fault
V3
feeder
feeder
51
51
P1
P1
P2
P2
P2
P2
P1
incomer
P1
incomer
U32
V2
V1
I1
+270
67
67
51
51
V3
V2
feedert
I1
V1
P1
V3
P2
07_C3213_En_protection_ind-B_04-2002.ppt
24
Directional
phase
overcurrent
Phase fault
on one line
Icc1
V2
feeder
I1
51
V1
V3
67
U32
Icc1
+45
V1
51
51
P1
P1
P2
P2
P2
P2
V2
P1
incomer
P1
incomer
I1
+270
feeder
67
67
51
51
V3
67
U32
+45
P1
P2
V1
V2
I1
V3
Icc1
07_C3213_En_protection_ind-B_04-2002.ppt
25
67N/67NC function
Series 40
2 groups of 2 elements :
functions 1A/2A
group A, elements 1
and 2
functions 1A/2A group
B, elements 1
and 2
enabling/disabling :
group A OR group B
possibility to switch from one
group to the other
possibility to use group
switching AND logic
discriminition
07_C3213_En_protection_ind-B_04-2002.ppt
26
67N/67NC function
Series 40
2 characteristics :
type 1 : projection
- definite time
- input Io (measured)
type 2 : according to Io
magnitude
- IDMT or definite time
- input Io (measured) or
sum of the 3 phases
possibility to mix these 2
characteristics
the tripping direction can
be set (line or busbar)
07_C3213_En_protection_ind-B_04-2002.ppt
27
67N/67NC function
Series 40
Type 1 :
the protection function calculates
the projection of the residual
current Io on the characteristic line
which is fixed by the characteristic
angle o in relation to the residual
voltage and compares this value to
Iso set point.
the projection method is suitable
for resistive, isolated or
compensated neutral systems.
the function is inhibited if the
residual voltage is below Vso set
point.
07_C3213_En_protection_ind-B_04-2002.ppt
28
67N/67NC function
Series 40
29
67N/67NC function
Series 40
Type 2 :
the protection function operates
like an earth fault protection
function with an added direction
criterion.
this characteristic allows a better
coordination with 50N/51N
protection functions.
this function is suitable for
closed ring distribution networks
or for incomings in parallel with
directly earthed neutral.
usual setting o = - 45
07_C3213_En_protection_ind-B_04-2002.ppt
30
67N/67NC Applications
Capacitive currents
aV
N
aV
V
VT2
3
VT3
V1
V2
N
Vrsd
VT2
1
VT1
VT3
C1
C2
C3
IC3
IC2
ICT
ICT
Examples :
for 6kV, non radial cable :
for 20kV, radial cable :
V3
07_C3213_En_protection_ind-B_04-2002.ppt
31
67N/67NC Applications
Residual currents
3
aV
N
residual current in a
fault-free feeder :
Irsd,s = Ic fault-free
feeder
aV
2
1
Cd
Cs
ID
IZn
ICd
ICs
07_C3213_En_protection_ind-B_04-2002.ppt
32
Vr
Ir = Ic
Ir
Ira
Ir
Vr
Series 40
radial networks
installation on each
feeder
Ic > ~10% I neutral
advantage of a type 1
function (projection) :
totally insensitive to
capacitive currents.
Vr
Ic
Ir
Faulted
feeder
Sound
feeder
07_C3213_En_protection_ind-B_04-2002.ppt
33
Vr
Ir = Ic
Ir
Ir
Vr
Vr
Series 40
radial networks
installation on each
feeder for location
since the first fault
used for alarm or
tripping
the high sensitivity
with the CSH120 core
balance CT is the
main advantage
Ir
Faulted
feeder
Sound
feeder
07_C3213_En_protection_ind-B_04-2002.ppt
34
Vr
Ir
Irr
Ir = Ic
Ir
Ira
Ir
Vr
Vr
Faulted
feeder
Series 40
radial networks
installation on each
feeder
only a type 1
protection, using
projection, is suitable
protection studied to
allow detection of
recurrent faults
(memory time)
Sound
feeder
07_C3213_En_protection_ind-B_04-2002.ppt
35
Series 40
closed ring networks
installation on
incomings
advantage of a type 2
protection, Io
magnitude : easy to
coordinate with 50N/51N
Ir
Vr
-45
Vr
-45
Ir
Faulted
incoming
Vr
Ir
Sound
incoming
Ir
07_C3213_En_protection_ind-B_04-2002.ppt
36
32P function
Series 40
07_C3213_En_protection_ind-B_04-2002.ppt
37
32Q function
Series 40
07_C3213_En_protection_ind-B_04-2002.ppt
38
79 function - recloser
Series 20
Series 40
Recloser is a function which recloses the circuit breaker after a tripping due to
a fugitive or semi-permanent single phase or phase-to-phase fault.
setting 1 to 4 cycles
possibility to choose the protection functions which activate the different
cycles.
time delays :
inhibition : starts when a voluntary close or trip command is given
(detection by the change of the CB position input states)
isolation : 1 per cycle. Waiting time before reclosing.
disengagement : starts when the CB is closed by the recloser
if a fault occurs during this time delay, the next reclosing
cycle is activated or a permanent trip order is given if it was
the last cycle.
If there is no fault during this time delay the recloser
reinitializes.
07_C3213_En_protection_ind-B_04-2002.ppt
39
79 function - recloser
Series 20
07_C3213_En_protection_ind-B_04-2002.ppt
40
79 function - recloser
Series 40
41
79 recloser - example
I (A)
Id
1 cycle
2 cycle
3 cycle
Permanent fault
In
Inst.
0.3
Inhibition
0.5
15 to 30
0.5
15 to 30
0.5
T (s)
isolation
isolation
isolation
Disengagement Disengagement
Disengagement
10s
10s
10s
10s
07_C3213_En_protection_ind-B_04-2002.ppt
42
79 recloser - example
Different types of faults:
Fugitive : confirmed instantaneous tripping (35ms<t<50ms)
fast cycle (300ms) to allow the arc de-ionization.
Semi-permanent : time delayed tripping (0.5s) to avoid to trip
because of the transient currents due to the
re-energization of the load and to ensure a correct
discrimination regarding downstream protection
devices.
slow cycle (15 to 30s) to allow fault instinguishing
when there is no arc (ex: tree branch) mini 10s
charging time of CB motor.
Permanent : end of cycle.
07_C3213_En_protection_ind-B_04-2002.ppt
43
79 Recloser
Series 20
Series 40
07_C3213_En_protection_ind-B_04-2002.ppt
44
45
07_C3213_En_protection_ind-B_04-2002.ppt
46
49 thermal overload
Series 20
With I=Ib
Hot curve: time for E to
go from 100% to trip
value.
With I=0
07_C3213_En_protection_ind-B_04-2002.ppt
47
Series 20
49 thermal overload
CB tripping
E=120%
E=100%
E= 63%
T1
E=100% when I=Ib
during an infinite time
t
Curve depending
t=Tripping time from the hot
on T2. ( I=0 )
curve(E=100%) depending on
T1 and on the value of the current
07_C3213_En_protection_ind-B_04-2002.ppt
48
49 thermal overload
Series 20
T max 40
70 40 30
1 .5
T max Tambient 70 50 20
07_C3213_En_protection_ind-B_04-2002.ppt
49
Series 20
49 thermal overload
Accounting for negative sequence current
s n 1500 1485
0.01
s
1500
Cd
2
Cn
Id
8
In
0.015>g>0.005
k 2.
Cd
1
.
Cn Id
g .
Ib
1 2.1.
1
1 4.55
0.01.6 2
07_C3213_En_protection_ind-B_04-2002.ppt
50
49 thermal overload
Series 20
120%
07_C3213_En_protection_ind-B_04-2002.ppt
51
49 thermal overload
Series 20
52
49 thermal overload
Series 20
1.1
07_C3213_En_protection_ind-B_04-2002.ppt
53
49 Thermal overload
Series 40
07_C3213_En_protection_ind-B_04-2002.ppt
54
Series 20
07_C3213_En_protection_ind-B_04-2002.ppt
55
Series 20
ST
LTS
Excessive
starting time
Locked rotor
during start
07_C3213_En_protection_ind-B_04-2002.ppt
56
Series 20
Motor re-acceleration
When the motor re-accelerates (after loss of mains, change over for
example) it consumes a current close to the starting current whithout
passing through a value less than 10% of Ib.
In that case the starting is not detected by sepam and there is a possibily
to trip on locked rotor time delay.
Its possible to reinitialize the excessive starting time protection by using
logic input I22
07_C3213_En_protection_ind-B_04-2002.ppt
57
Series 20
This function picks up when the number
of starts reaches the following limits :
-Nt- maximum number of starts allowed per
period of time P (from 1 to 6 hours)
-Nh-maximum allowed number of
consecutive hot starts
-Nc-maximum allowed number of
consecutive cold starts
motor hot state : 50% heat rise (70% Ib)
07_C3213_En_protection_ind-B_04-2002.ppt
58
Series 40
Use of circuit breaker closed data :
detection of starts for synchronous
motors
When a synchronous motor starts
without load, often the current
decreases lower than 10% of Ib
during a certain time. In that case
sepam counts a second start.
To avoid that problem it s possible to
take into account the closed position
of the circuit breaker.
07_C3213_En_protection_ind-B_04-2002.ppt
59
Series 20
Series 40
Examples :
4 starts per day. Settings: P=6 Nt=1 Nh=1 Nc=1
6h
6h
6h
6h
blocking
blocking
blocking
blocking
24h
1 start
3 starts every 2 hours and 2 consecutive starts. Settings : P=2 Nt=3 Nh=2 Nc=2
40mn (P/Nt)
0
1 start
allowed
1 start allowed
Blocking
time
2 hot or cold
consecutive
starts
2h
Blocking time
40mn (P/Nt)
40mn (P/Nt)
1 start
allowed
2 start
allowed
07_C3213_En_protection_ind-B_04-2002.ppt
60
Series 20
Series 40
Examples :
3 starts every 2 hours and 2 consecutive cold starts or 1 consecutive hot start.
Settings : P=2 Nt=3 Nh=1 Nc=2
2h
40mn (P/Nt)
1 cold or 1 hot
start allowed
Blocking
time
Blocking time
1 cold start
allowed
07_C3213_En_protection_ind-B_04-2002.ppt
61
Series 20
Series 40
Examples :
1h
Blocking time
15mn
15mn
15mn
15mn
15mn
1h
15mn
15mn
15mn
T
15mn
T
15mn
15mn
T
15mn
15mn
T
1h
T
15mn
07_C3213_En_protection_ind-B_04-2002.ppt
62
37 undercurrent
Series 20
Series 40
Use :
protection of pumps against the
consequences of a loss of
priming.
Detection of breaking in
transmission.
07_C3213_En_protection_ind-B_04-2002.ppt
63
Phase-to-phase undervoltage 27
phase-to-neutral undervoltage 27S
Series 20
Series 40
Use :
27 : detection of a general voltage drop : motor protection
27S : detection of 1 phase-to-earth fault : isolated neutral system
27 : information used in automated functions : changeover, load
shedding
64
Overvoltage 59
Series 20
Series 40
Use :
detection of an abnormally high voltage
checking that there is sufficient voltage for power supply changeover
65
Series 20
Series 40
a
N
b
c
Va
V0
Vc
In case of solid fault, the voltage Va becomes zero, there is a displacement of the
neutral point and the voltages of the sound phases Vb and Vc are equal to phaseto-phase voltages.
The residual voltage is the same everywhere in the network and is equal to 3 times
the phase-to-neutral voltage.
Disadvantage : equipment must be designed for these overvoltages.
07_C3213_En_protection_ind-B_04-2002.ppt
66
Series 20
Series 40
a
b
N
Va
V0
Vc
In case of solid fault, at fault, the voltage Va becomes zero, there is a very
short voltage displacement, the sound phases dont change and the
residual voltage is equal to a phase-to-neutral voltage.
At source, there is a voltage Va (and then a drop in residual voltage) which
depends on the values of the link impedances between fault and source for
the faulted phase.
07_C3213_En_protection_ind-B_04-2002.ppt
67
Series 20
Series 40
Vb
Vb
b
c
N
Va
Va
N
Z
Voltage diagram
at source
Vc
V0
V0
Voltage diagram
at fault
Vc
In case of solid fault, at fault, the voltage diagram is the same as the isolated
neutral one. Residual voltage is equal to 3 times phase-to-neutral voltage.
At source, the displacement of the neutral point (and then the values of Vo
and the other voltages) depends on the values of the link impedances
between fault and source for the faulted phase.
07_C3213_En_protection_ind-B_04-2002.ppt
68
Series 20
Series 40
Use :
generally, in isolated grounding systems on transformer incomings or
on busbar (alarm or tripping).
possibly, in the other grounding systems for back up protection.
07_C3213_En_protection_ind-B_04-2002.ppt
69
Series 20
Series 40
Parameter settings :
according the measurement method : 3V, external VTs Uns/3 or Uns/3
Uns/3
20KV
Uns/3
20KV
20KV
20KV
20KV/3
/ 100V/3
0
100V
20KV/3
/ 100V/3
100V
173V
57V
57V
100V
Va
3Vns (3Uns)
Vb
V0
3Vns (Uns)
Vc
Vo = 3V = 3U
07_C3213_En_protection_ind-B_04-2002.ppt
70
Series 20
Series 40
Motor protection
27D : the positive sequence voltage is the exact image of the motor torque.
Consequences of a positive sequence voltage drop :
during energizing, increase in starting torque and maximum torque, then
increase in starting current (overheating, loss) and even rotor stalling.
In normal operation, increase in consumed current to maintain the power.
47 : detection of phase rotation direction (wrong connection)
protection of the load
usual settings : 75 to 80% of Un
07_C3213_En_protection_ind-B_04-2002.ppt
71
Series 40
07_C3213_En_protection_ind-B_04-2002.ppt
72
Series 20
Series 40
07_C3213_En_protection_ind-B_04-2002.ppt
73
Overfrequency 81H
Underfrequency 81L
Series 20
Series 40
07_C3213_En_protection_ind-B_04-2002.ppt
74
Underfrequency 81L
Series 40
07_C3213_En_protection_ind-B_04-2002.ppt
75
Series 20
Advantages of 81R
compared to 81L
Faster
fast tripping with low
frequency variations
More selective
precise setting of tripping time
protection used for fast
disconnection of a source
transmitting power into a
network when a fault occurs or
to monitor load shedding
07_C3213_En_protection_ind-B_04-2002.ppt
76
Series 20
49.5 Hz
07_C3213_En_protection_ind-B_04-2002.ppt
77
Series 20
Example: disconnection
50 Hz
49.5 Hz
Underfrequency (81L) settings: 49.5 Hz 0.1 s
the protection trips in 0.1 s + 0.1 s (time delay) = 0.2 s
df/dt (81R) settings: 0.15 Hz/s 0.5 s
the protection trips in 0.5 s
07_C3213_En_protection_ind-B_04-2002.ppt
78
Series 20
Series 40
RTD
connection
U
r
U=rI
R
V
A
E - 2U
I
Sepam
07_C3213_En_protection_ind-B_04-2002.ppt
79
Temperature monitoring
Series 20
Series 40
07_C3213_En_protection_ind-B_04-2002.ppt
80