A
A
A
PDX Series
SERVICE MANUAL
Troubleshooting Guide and Instructions for Service
(To be performed ONLY by qualified service providers)
Manual 238-49770-00A
Table of Contents
Page Introduction How to use this manual Tool required for service Specifications Control Timings Sequence of Operation Troubleshooting Burner Inspection, Cleaning and Replacement Pilot Testing, Cleaning and Replacement Pressure Switch Testing and Replacement Blower Testing and Replacement Blower Temperature Switch Testing and Replacement Gas Control & Thermal well Testing & Replacement Flammable Vapor Sensor Testing & Replacement Safety Circuit Voltage Trace 115VAC Circuit Trace Dip Tube inspection and Replacement Anode Inspection and Replacement Flue Baffle Inspection and Replacement Inner Door Removal, Inspection & Replacement Glossary of Terms Parts List 4 5 5 6 9 10 13 15 17 18 20 22 24 28 29 30 31 32 33 34 38 39 PDX Service Procedure --------------I II III IV V VI VII VIII IX X XI XII XIII -----
Page 2
PDX Series
WARNING: If the information in these instructions is
not followed exactly, a fire or explosion may result causing property damage, personal injury, or death.
CAUTION
Incorrect operation of this appliance may create a hazard to life and property and will nullify the warranty.
DANGER Do not store or use gasoline or other flammable, combustible, or corrosive vapors and liquids in the vicinity of this or any other appliance.
IMPORTANT Before proceeding, please inspect the water heater and its components for possible damage. DO NOT install any water heater with damaged components. If damage is evident then please contact the supplier where the water heater was purchased or the manufacturer listed on the rating plate for replacement parts.
WARNING
Water heaters are heat producing appliances. To avoid damage or injury, do not store materials against the water heater or vent-air intake system. Use proper care to avoid unnecessary contact (especially by children) with the water heater and vent-air intake components. UNDER NO CIRCUMSTANCES MUST FLAMMABLE MATERIALS, SUCH AS GASOLINE OR PAINT THINNER BE USED OR STORED IN THE VICINITY OF THIS WATER HEATER, VENTAIR INTAKE SYSTEM OR IN ANY LOCATION FROM WHICH FUMES COULD REACH THE WATER HEATER OR VENT-AIR INTAKE SYSTEM.
WARNING
DO NOT ATTEMPT TO LIGHT ANY GAS APPLIANCE IF YOU ARE NOT CERTAIN OF THE FOLLOWING: Liquefied petroleum gases/propane gas and natural gas have an odorant added by the gas supplier that aids in the detection of the gas. Most people recognize this odor as a sulfur or rotten egg smell. Other conditions, such as odorant fade can cause the odorant to diminish in intensity, or fade, and not be as readily detectable. If you have a diminished sense of smell, or are in any way unsure of the presence of gas, immediately contact your gas supplier from a neighbor's telephone. Gas detectors are available. Contact your gas supplier, or plumbing professional, for more information.
CAUTION
If sweat fittings are to be used DO NOT apply heat to the nipples on top of the water heater. Sweat the tubing to the adapter before fitting the adapter to the water connections. It is imperative that heat is not applied to the nipples containing a plastic liner.
WARNING
FAILURE TO INSTALL AND MAINTAIN A NEW, LISTED 3/4 X 3/ 4 TEMPERATURE AND PRESSURE RELIEF VALVE WILL RELEASE THE MANUFACTURER FROM ANY CLAIM THAT MIGHT RESULT FROM EXCESSIVE TEMPERATURE AND PRESSURES.
WARNING
Hydrogen gas can be produced in an operating water heater that has not had water drawn from the tank for a long period of time (generally two weeks or more). Hydrogen gas is extremely flammable. To prevent the possibility of injury under these conditions, we recommend the hot water faucet to be open for several minutes at the kitchen sink before you use any electrical appliance which is connected to the hot water system. If hydrogen is present, there will be an unusual sound such as air escaping through the pipes as hot water begins to flow. Do not smoke or have open flame near the faucet at the time it is open.
CAUTION
Turn off or disconnect the electrical power supply to the water heater before servicing. Label all wires prior to disconnection when servicing controls. Wiring errors can cause improper and dangerous operation. Verify proper operation after servicing.
Page 3
PDX Series
Introduction
The new Bradford White PDX1, PDX2 and PDX4 water heaters are designed to provide reliable performance with enhanced standard features. New design features include reliable spark to pilot ignition system, enhanced diagnostics, simplified servicing, significantly quieter operation, additional vent lengths and certified FVIR technology. Spark to Pilot Ignition System - employing the spark to pilot ignition system promotes reliable and consistent pilot and main burner ignitions to provide hot water on demand. Integrated Immersion Thermostat/Gas Control Valve with LED - was developed for ease of troubleshooting by providing simple diagnostic codes to pinpoint an installation or component performance issue. New Powerful Blower - will eliminate problems with difficult venting situations. Quieter and Cooler Blower Operation - blower noise is significantly reduced for both interior and exterior environments. Cooler operation increases blower life by reducing bearing wear and noise. Rugged Wiring Connections - receptacle type connections promote error free wiring. Increased Vent Lengths - increased venting performance is achieved while maintaining Energy Factor & FHSR performance. The PDX1, PDX2, and PDX4 water heaters use a combustion system were flue gases are combined with dilution air to reduce the flue gas temperature in the blower, combustion air and dilution air are drawn from outside the building. The diluted flue gases are evacuated to the exterior through non metallic vent materials. The gas control maintains water temperature, ignition sequence and regulates gas flow. A safety circuit consisting of a pressure switch and blower temperature switch verifies proper conditions exist for safe and reliable operation. If a situation outside of normal operating parameters exists, the gas control diagnostic LED will flash a code to positively identify an operational issue. This service manual is designed to facilitate problem diagnosis and enhance service efficiency. To further promote quicker service times the new gas valve can be removed and replaced without draining the water heater. A special tool is required and will be provided with each gas valve kit shipped from our Service Parts department. Please read the service manual completely before attempting service on this new series of power vent models. How the Safety System Works
During normal operation, air for combustion is drawn into the water heater though the vent pipe from outside your building. The air travels into the closed combustion chamber. The air then mixes with in a normal manner with supplied gas and its efficiently combusted, producing very low NOx emissions. In the unlikely event trace amounts of flammable vapors are present in the area surrounding the water heater, the sealed combustion system prevents the flammable vapors from reaching the ignition source. In addition the flammable vapors sensor will stop the water heater from operating if a significant amount of flammable vapors are present.
Page 4
PDX Series
It is intended for this manual to be used by qualified service personal for the primary purpose of troubleshooting and repair of the Bradford White PDX Series water heaters. Understanding the sequence of operation section of this manual will contribute greatly to troubleshooting the water heater. The Honeywell WV4460E Electronic Gas Control will display error codes in the event of abnormal operation. Error codes are listed in the troubleshooting chart beginning on page 12 of this service manual. The troubleshooting chart will also indicate the probable cause for the error code and direct the service professional to a service procedure to properly diagnose the abnormal operation. In some difficult to diagnose conditions, it may be necessary to isolate the heater from the vent system to determine the problem. Contact the Bradford White technical support group immediately if diagnosis can not be made using the methods described in this service manual.
Electronic Probes:
Thermometer:
Water Pressure Gage: Used to measure water supply pressure. Also used to determine tank pressure by adapting to the drain valve of the heater. Gas Control Service Tool: BWC part number 239-45991-00. A specialized tool designed to remove the gas control from gas control thermal well. Available from your Bradford White parts supplier.
Various Hand Tools: Pipe wrench, channel locks, open end wrenchs (3/8",7/16","), 12" crescent wrench, Allen wrench set, screw drivers (common & Phillips), " nut driver, pliers (common & needle nose), socket set, side cutters wire cutters, wire strippers, wire crimpers, torpedo level, small shop vac, step ladder, and flashlight, 5 gallon pail.
Page 5
PDX Series
Specifications
Power supply Gas Supply Pipe Approved Gas Type Gas Pressure Venting System Approved Vent Materials Minimum Clearance for Servicing Water Supply Pressure Thermal well TCO Limit Residential Temperature Set Point Range Commercial Temperature Set Point Range
Dedicated 115VAC, 60 Hz, 15A Minimum 1/2" NPT (schedule 40 black iron pipe recommended) Natural or Propane. Unit must match gas type supplied. 5.0" W.C. min. for Nat gas, 11.0" W.C. min. for L.P. gas, 14.0" W.C. maximum (Nat. & L.P.) Power direct vent through the wall or vertical through the roof PVC, CPVC or ABS 18" from top, 24" from front, 4" sides and rear. 150 PSI maximum allowable working pressure. Check local codes for supply pressure Residential 188F (87C), Commercial 199F (93C) 60F (16C) to 160F (71C) (Approximate temperatures) 80F (27C) to 180F (82C) (Approximate temperatures)
Blower Temperature Switch Normally closed, opens @ 155F (68C), auto reset @ 128F (54C).
Standard Altitude-Normally open, closes at differential pressure of -.80. Pressure switch High Altitude-Normally open, closes at differential pressure of -.73.
Blower
Page 6
PDX Series
Venting Specifications for: 48 Gallon 65 Gallon 75 Gallon
Specifications
Vent Tables
This water heater is approved for installation with the following PVC, CPVC or ABS Schedule 40 venting material. The maximum and minimum vent lengths listed on this label are for the exhaust portion of the vent. The intake portion of the vent must be equal to or less than the length of the exhaust.
3" Diameter (7.6 cm) PVC Vent Connector Lengths Maximum 48, 65 gal. Terminating Through the Wall Through the Wall Through the Wall Through the Wall Through the Roof Through the Roof Through the Roof Through the Roof # of Elbows 1 2 3 4 0 1 2 3 Maximum Length ft (m) 55 (16.8) 50 (15.2) 45 (13.7) 40 (12.2) 60 (18.3) 55 (16.8) 50 (15.2) 45 (13.7) Minimum Length ft (m) 2 (.6) 2 (.6) 2 (.6) 2 (.6) 7 (2.1) 7 (2.1) 7 (2.1) 7 (2.1) Maximum 75 gal. Maximum Length ft (m) 45 (13.7) 40 (12.2) 35 (10.7) 30 (9.1) 50 (15.2) 45 (13.7) 40 (12.2) 35 (10.7) Minimum Length ft (m) 2 (.6) 2 (.6) 2 (.6) 2 (.6) 7 (2.1) 7 (2.1) 7 (2.1) 7 (2.1)
4" Diameter (10.2 cm) PVC Vent Connector Lengths Maximum 48, 65 gal. Terminating Through the Wall Through the Wall Through the Wall Through the Wall Through the Wall Through the Roof Through the Roof Through the Roof Through the Roof Through the Roof # of Elbows 1 2 3 4 5 0 1 2 3 4 Maximum Length ft (m) 95 (29.0) 90 (27.4) 85 (25.9) 80 (24.4) 75 (22.9) 100 (30.5) 95 (29.0) 90 (27.4) 85 (25.9) 80 (24.4) Minimum Length ft (m) 10 (3.1) 10 (3.1) 10 (3.1) 10 (3.1) 12 (3.6) 15 (4.6) 15 (4.6) 15 (4.6) 15 (4.6) 15 (4.6) Maximum 75 gal. Maximum Length ft (m) 85 (25.9) 80 (24.4) 75 (22.9) 70 (21.3) 65 (19.8) 90 (27.4) 85 (25.9) 80 (24.4) 75 (22.9) 70 (21.3) Minimum Length ft (m) 10 (3.1) 10 (3.1) 10 (3.1) 10 (3.1) 12 (3.6) 15 (4.6) 15 (4.6) 15 (4.6) 15 (4.6) 15 (4.6)
Page 7
PDX Series
Vent Tables
Part II-Venting Specifications for: 40 Gallon 50 Gallon
Specifications
IMPORTANT The minimum equivalent length for the exhaust portion of the vent is 7 feet. The maximum equivalent vent length for the exhaust is 35 feet for 2" diameter pipe and 85 feet for 3" diameter pipe. The intake portion of the vent must be equal to or less than the vent length of the exhaust. The tables below are provided for your quick reference, some installations may require a greater number of elbows. When calculating equivalent vent length, one 90 elbow is equivalent to 5 feet.
VENT CONNECTOR LENGTHS FOR 2" (5.1 cm) DIAMETER VENT PIPE Terminating Through the Wall Through the Wall Through the Wall Through the Wall Through the Roof Through the Roof Through the Roof Through the Roof
# of Elbows (excl. vent term.)
Maximum straight Length ft (m) 30 (9.1) 25 (7.6) 20 (6.1) 15 (4.6) 35 (9.1) 30 (9.1) 25 (7.6) 20 (6.1)
Minimum straight Length ft (m) 2 (.6) 2 (.6) 2 (.6) 2 (.6) 7 (2.1) 7 (2.1) 7 (2.1) 7 (2.1)
1 2 3 4 0 1 2 3
VENT CONNECTOR LENGTHS FOR 3" (7.6 cm) DIAMETER VENT PIPE Terminating Through the Wall Through the Wall Through the Wall Through the Wall Through the Roof Through the Roof Through the Roof Through the Roof Through the Roof Through the Roof
# of Elbows (excl. vent term.)
Maximum straight Length ft (m) 80 (24.4) 75 (22.9) 70 (21.3) 65 (19.8) 60 (18.3) 85 (29.9) 80 (24.4) 75 (22.9) 70 (22.3) 65 (19.8)
Maximum straight Length ft (m) 10 (3.1) 10 (3.1) 10 (3.1) 10 (3.1) 10 (3.1) 15 (4.6) 15 (4.6) 15 (4.6) 15 (4.6) 15 (4.6)
1 2 3 4 5 0 1 2 3 4
Page 8
PDX Series
Control Timings
Ignition State Pre-purge Trial for Ignition Flame Stabilization Period Inter-purge Flame Failure Response Time Post-purge PS Fault Delay (failed open/close) Soft Lockout TCO Limit Lockout Verify Resistive Delay Simulated Resistive Load Lockout Hardware Error Lockout 15 Seconds 90 Seconds 3 Seconds 15 Seconds Timing
Specifications
1.5 Seconds (2 second. Maximum; 1 second minimum.) 15 Seconds Retry after 2 Minutes Retry after 5 Minutes Indefinite (cycle power to restart) Retry after 2 Minutes (repeats 5 times) Indefinite (cycle power to restart) Indefinite (self clears if fault clears for at least 15 seconds)
Page 9
PDX Series
Sequence of Operation
Start Up.
Upon power up, the control runs a safe-start check with a typical start-up delay of 1-5 seconds.
Blower energizes. Blower pre-purge period (15 seconds) Differential pressure switch proves blower/vent system operation.
a) If the pressure switch does not close within 30 seconds, the control LED Flashes 3 times with 3 second pause. The blower runs for 30 seconds every 2 minutes trying to get the pressure switch or blower temperature switch to close. This cycle repeats as long as there is a call for heat.
Page 10
10
PDX Series
Sequence of Operation
During Steady State Operation the Control Monitors: Thermostat temperature sensor- When set point temperature is satisfied, gas valve is shut down and blower will post purge for 15 seconds. Control LED flashes a short flash once every 4 seconds (idle) status code. Pressure switch / Blower temperature switch- If either switch opens, pilot valve and main valve is shut down. The blower continues to run for 30 seconds attempting to close the circuit. The control LED Flashes 3 times with 3 second pause. Flame Sense- If flame is lost, pilot & main valve are shut down, blower runs for 15 seconds. Control attempts to re-light pilot 4 times. If unsuccessful, Blower is shut down and control proceeds to 5 minute lockout. Control re-attempts to light pilot starting at normal heating sequence #2.
10
11
PDX Series
Sequence of Operation
Page 12
12
PDX Series
Troubleshooting
Observe green LED indicator on Electronic gas control. Error flash codes are displayed with a three second pause before repeating. Check and repair the system as noted in the troubleshooting table below.
Service Procedure
Turn power on Normal operation. Adjust thermostat to temp level Normal operation. Adjust thermostat to temp level 1. Page 15 2-4. Page 17
LED Status
None, control LED not on or flashing Short flash, once every four seconds Heartbeat, alternates bright/dim
Control Status
No electrical power Stand-by mode, Waiting for call for heat (no fault). Thermostat calling for heat (no fault).
Probable Cause
Control power switch in OFF position. Supply voltage interrupted.
1. Unstable pilot. 2. Pilot tube block or restricted. Weak pilot signal 3. Oxidation build up on pilot electrode. on last call for heat. 4. Wire damage to pilot assembly or bad connection at gas valve. Pressure switch not working-closed position. 1. Pressure switch tubing kinked or blocked. 2. Blocked pressure tap on switch or blower. 3. Faulty pressure switch. 1. Vent blockage or improper vent configuration. 2. Pressure switch tubing kinked or blocked. 3. Faulty pressure switch. 4. Blower not spinning up to speed. 5. Blower temp or exhaust temp too high 6. Faulty blower temperature switch. 7. Intake vent length exceeds exhaust vent length. 8. Frozen intake or exhaust vent terminal. 1. Thermal well sensor out of calibration. 2. Faulty gas control. 3. Plumbing leak 1. Pilot valve stuck in open position.
Page 18
1. Check vent or vent tables. 2 & 3 Page 18 4. Page 20 5 & 6 Page 22 8. Page 37 1. Page 24 2. Replace gas control, page 26 Replace gas control, page 26
Pressure switch or Three flash, three second blower temp. pause switch not working -open position.
Excessive tank temperature. System must be reset. Undesired-false pilot flame present.
Page 13
13
PDX Series
LED Status Control Status Probable Cause
Troubleshooting
Service Procedure
1. Page 15 2-4. Page 17
1. Unstable pilot. 2. Pilot tube blocked or restricted. Failed to light pilot. 3. Oxidation build up on pilot electrode. System auto resets. 4. Wire damage to pilot assembly or bad connection at gas valve. 1. Vent blockage or improper vent configuration. Pressure switch 2. Pressure switch tubing kinked or blocked. or blower temp 3. Faulty pressure switch. switch opened 4. Vent termination being affected by wind during burner 5. Blower not spinning up to speed. operation. 6. Blower temp or exhaust temp too high System auto 7. Faulty blower temperature switch. resets. 8. Insufficient combustion air. 1. Unstable pilot. 2. Pilot tube blocked or restricted. 3. Oxidation build up on pilot electrode. 4. Wire damage to pilot assembly or bad connection at gas valve. 5. Insufficient combustion air. 6. Gas pressure is out of specification.
1. Check vent or vent tables. 2 & 3 Page 18 4. Refer to venting section of installation manual 5. Page 20 6 & 7 Page 22 8. Refer to installation manual.
WARNING: EXPLOSION HAZARD * Indicates gasoline vapors were detected at potentially explosive levels. Flammable Vapor * Verify no gasoline vapors are still present Seven flash, three second Sensor fault pause * Reset the control by cycling power to the appliance or detected by cycling the ON/OFF switch. * Replace the Flammable Vapors Sensor element if a gasoline spill event occurred. * Verify Flammable Vapor Sensor (FVS) resistance is Flammable Vapor not below 25 K Ohms. Sensor out of * Check wiring to FVS and insure it is not shorted. specification. * Replace control if everything above checks out OK. Thermal well sensor damaged or unplugged Gas valve electronics fault detected Gas valve fault detected. 1. Damage to thermal well wire. 2. Thermal well sensor resistance out of range. 1. Control needs to be reset. 2. Control is wet or physically damaged. 1. Control needs to be reset. 2. Control is wet or physically damaged.
Page 28
Page 28
Page 24
1. Interrupt power supply 2. Replace gas control, page 26 1. Interrupt power supply 2. Replace gas control, page 26
Page 14
14
PDX Series
PDX SERVICE PROCEDURE I Burner Operation Inspection, Adjustment, Cleaning and Replacement
Page 15
15
PDX Series
Burner Cleaning
Step 1. Step 2. Step 3. Step 4. Step 5. Step 6. Step 7. Step 8.
PDX SERVICE PROCEDURE I Burner Operation Inspection, Adjustment, Cleaning and Replacement
Position gas control power switch to the OFF position and unplug heater from wall outlet. Turn off gas supply to water heater. Remove outer jacket door and inner door per service procedure XIII on page 35. Disconnect pilot tube (7/16 wrench) and feedline ( wrench) from gas control.
Igniter/flame sense wire
Disconnect igniter/flame sensor wire from gas control. Remove burner assembly from combustion chamber. Thoroughly inspect burner surface area and burner port area and remove any loose debris. For cast iron burners, inspect for any debris build up inside burner casting.
Burner surface area
Feedline nut
Step 9.
Unscrew burner from main burner orifice. On cast iron burners, loosen air shutter nut and unscrew feedline from burner.
Step 10.
Remove main burner orifice from feedline (" wrench on steel burners, 3/8" wrench on cast iron) inspect orifice, clean or replace if necessary. Reassemble burner and reinstall into water heater. Restore gas supply and check for gas leaks. To resume operation follow the instruction located on the lighting instruction label or the lighting instruction located in the installation and operating manual.
Page 16
16
PDX Series
Disconnect pilot tube nut (7/16 wrench) and feedline nut ( wrench) from gas control. Disconnect igniter/flame sense wire from gas control. Remove burner assembly from combustion chamber. Remove pilot assembly from feedline (" nut driver). Visually inspect igniter/flame sense wire for damage. Replace pilot if damage is found. With a multi-meter set to the ohms setting, check continuity through igniter/flame sense wire. Replace pilot if no continuity. Visually inspect igniter/flame sense electrode for deterioration. Replace pilot as necessary. Electrode should not be in contact with pilot hood, If so, carefully adjust electrode to a gap distance of 3/32" (.09) from pilot hood. Visually inspect igniter/flame sense electrode for oxidation build up. Carefully clean any oxidation using very fine emery cloth. Visually inspect pilot tubing for kinks or cracks. If damage is found replace pilot. Inspect pilot tubing and pilot orifice for blockage: a) Remove ferrule nut from bottom of pilot assembly (7/16" wrench). b) Remove pilot tube and pilot orifice. c) Inspect pilot tubing and pilot orifice for blockage. Clean or replace as necessary.
Igniter/flame sense wire Ferrule nut Pilot tubing Pilot orifice
Feedline nut
Pilot hood
Step 11.
Reassemble pilot and install to feedline. Reinstall burner assembly to water heater. Restore gas supply and check for gas leaks. To resume operation follow the instruction located on the lighting instruction label or the lighting instruction located in the installation and operating manual.
Page 17
17
PDX Series
Pressure Switch Testing
Step 1. Step 2. Step 3. Position power switch on gas control to the OFF position.
WARNING 120 volt potential exposure. Use caution making voltage checks to avoid personal injury.
Remove the three screws (Phillips screw driver) from control access cover on blower assembly and remove cover (see photo 1). Carefully remove pressure switch from blower housing (see photo 2)
Exhaust pressure switch
1 2
Pressure Switch Pressure switch wire leads With steps 1,2 & 3 complete, disconnect wire leads from pressure switch. 3 Slide pressure switch in direction of arrow while tilting slightly away from blower housing.
Use a multi-meter set to the ohms setting. With blower off, check across pressure switch terminals. Are switch contacts open? (no electrical continuity) Y
``
N Check tubing and pressure tap N on switch for blockage. Is there blockage? Y Replace switch (see page 18)
Clear blockage Position gas valve power switch to the ON position and adjust thermostat to call for heat, this will start the blower. N Check with multi-meter, do pressure switch contacts close with blower running with the switch in the vertical postition? Y Switch contacts are OK. See safety circuit trace (page 30)
Y Check tubing and pressure tap on switch for blockage. Is there blockage? N
Page 18
18
PDX Series
Exhaust Pressure Switch Replacement
Step 1. Step 2. Position gas control power switch to OFF position.
WARNING 120 volt potential exposure. Use caution to avoid personal injury.
Remove the three screws (Phillips screw driver) from control access cover on blower assembly and remove cover (see photo 3).
Pressure Switch 4 5
Step 3.
Slide pressure switch in direction of arrow while tilting slightly away from blower housing.
Step 4.
Disconnect tubing from pressure switch. (see photo 5) Disconnect yellow wires from pressure switch (see photo 6)
Step 5.
Reconnect wires from step 5 to new pressure switch. Reconnect tubing to new pressure switch. Carefully position pressure switch into blower housing. Position gas control power switch to ON position and verify proper heater operation. Replace control access cover from step 2.
Page 19
19
PDX Series
Blower Testing
Step 1. Step 2.
WARNING 115 volt potential exposure. Use caution when making voltage checks to avoid personal injury.
Position gas control power switch to ON position and adjust control to call for heat.
8
Remove the three screws (Phillips Screw driver) from control access cover on blower assembly and remove cover (see photo 8).
Disconnect vent system from top of blower and remove exhaust vent adapter. (see photo 15) Remove exhaust adapter With blower running, and exhaust adapter removed from top of blower, is there a negative pressure of -2.30" to -2.60" W.C.? N Y
11
Pressure tap
Blower OK
Pressure switch tubing Determine voltage problem and correct. Does blower energize after 2 minutes, run for 30 seconds and shut down? N Y See pressure switch testing Page 18
Is there 115vac across blue and green wires (see photo 14)
Replace blower
12
13
Disconnect cord set shown in photo 9. Is there 115VAC across terminals shown in photo 12 N
Is there 115VAC across terminals shown in photo 13 ? N Incorrect supply voltage polarity
Y Reconnect cord set shown in photo 8, is there Y 115VAC between blue wire and green ground wire (see photo 14) N Does cord set have electrical continuity? Y Blue wire Green ground wire
Replace blower
Is there 115 VAC at wall outlet? Y Check power cord for damage. N Replace blower
14
Page 20
20
PDX Series
Blower removal
Step 1. Step 2. Step 3. Step 4. Step 5. Step 6. Step 7. Step 8. Step 9. Position gas control power switch to the OFF position. Unplug blower power cord from wall outlet. Disconnect vent system from exhaust adapter on top of blower. Remove exhaust adapter from blower (blade screw driver) and retain for use on new blower Unplug cord sets from blower. Remove vertical air intake bracket. Disconnect vertical air intake from blower. Remove the three blower mounting screws (" nut driver).
Remove exhaust adapter and retain for use on new blower. Blower Mounting Screws
Blower Installation
Step 10. Step 11. Clean any debris from jacket head of water heater. Set new blower with gasket in place using locating pins on blower flange to line up with location holes in jacket head. Be sure not to damage gasket. Secure blower in place using mounting screws from step 8. Slide vertical air intake tee onto blower. Re-install vertical air intake bracket. Re-install exhaust adapter from step 4. Reconnect vent system to exhaust adapter. Reconnect cord sets from step 5. Plug blower power cord into wall outlet. Position gas control power switch to the ON position. Verify proper blower operation.
Pin location holes in jacket head Locating Pins on blower flange
Step 12. Step 13. Step 14. Step 15. Step 16. Step 17. Step 18. Step 19. Step 20.
Page 21
21
PDX Series
Blower Temperature Switch Testing.
Step 1. Step 2. Step 3. Position power switch on gas control to the OFF position. Remove tubing from inlet pressure tap. Remove the three screws (Phillips screw driver) from control access cover on blower and remove cover (see photo 15). Locate blower temperature switch (see photo 16)
WARNING 120 volt potential exposure. Use caution to avoid personal injury.
15
Step 4.
Switch Setting Opens on rise @ approximately 155F Auto resets on fall @ approximately 128F
16
Blower temperature switch location Cool switch to below 125F Air mixing inlet
Disconnect wire leads to switch. Using a multi-meter set to the ohms setting, is there continuity between the switch terminals? Y
Reconnect wire leads and observe heater operation. Do exhaust gas temperatures rise to or above 175F? N
Common causes for high exhaust temperature 1. Vent length is below minimum allowable. 2. Vent diameter not to specification. 3. Restricted dilution air inlet. 4. Missing or deteriorated flue baffle. 5. Gas pressure is out of specification. 6. Excessively high ambient temperatures.
Switch OK
Page 22
22
PDX Series
Blower Temperature Switch Replacement.
WARNING 120 volt potential exposure. Use caution to avoid personal injury.
Step 1. Step 2.
Position gas control power switch to the OFF position and unplug heater from wall outlet. Remove the three screws (Phillips screw driver) from the control access cover on blower and remove cover. (see photo 17)
17
Locate blower temperature switch (see photo 18) Disconnect red and yellow wire leads from switch. With an appropriate tool such as side cutters, snip the retaining lug from the blower housing to allow removal of temperature switch (see photo 19). Remove switch from blower housing. Install new switch. Be sure switch is properly seated in mounting area. Reconnect red and yellows wires to new switch. Wires are interchangeable with either terminal. Position gas control power switch to the ON position and verify proper heater operation. Replace control access cover from step 2.
18
19
Page 23
23
PDX Series
Gas Control Testing
See pages 27 & 28 for gas control input & output testing.
Observe heater operation. If control continues to lockout due to excessive tank temperature, proceed to thermal well testing to determine cause.
20
21
Thermal well testing Position gas control power switch to the OFF position and disconnect thermal well harness from gas control.
CAUTION
DO NOT use standard multimeter probes for this test. Doing so will damage connector. Use special pin type electronic probes or small diameter wire pins inserted into connector.
Using a multi-meter set to the Ohms setting, determine the resistance of thermal well sensor (see caution photos 20 & 21)
Using a multi-meter set to the ohms setting, insert one meter probe (see caution) into center wire position of thermal well connector, insert the second probe (see caution) into either of the outside wire positions (see photo 20). Alternate the probe on the outside position to the opposite outside wire position (see photo 21).
Once the thermal well resistance values are known, the water temperature must also be known to determine if the resistance values are correct. See page 25 to obtain water temperature. Are thermal well resistance values correct? Y
Page 24
24
PDX Series
WARNING Stored water may be HOT when performing the following steps in this procedure. Take necessary precaution to prevent personal injury.
Step 1. Step 2.
Position gas control power switch to OFF position. Draw approximately 4 gallons of water from drain valve into a container and discard. Draw an additional gallon and immediately measure water temperature using an accurate thermometer. It may be necessary to open a hot water faucet to allow heater to drain. Using the chart below, determine correct resistance value for the water temperature from step 2. If temperature of water is 84F, then the resistance through the sensor would be 8449 (see shaded area). NOTE: Sensor resistance increases as the temperature falls. Sensor Resistance at Various Temperatures
F 40 50 60 70 80 90 100 110 120 130 140 150 160 170 180 190 200 0 26109 19906 15314 11884 9299 7333 5827 4663 3758 3048 2488 2043 1688 1402 1170 982 828 1 25400 19383 14925 11592 9078 7165 5697 4562 3679 2986 2439 2004 1656 1376 1150 965 814 2 24712 18876 14548 11308 8862 7000 5570 4464 3602 2925 2391 1966 1625 1351 1129 949 801 3 24045 18383 14180 11032 8653 6839 5446 4368 3527 2866 2344 1928 1595 1327 1110 933 788 In Degrees 4 23399 17905 13823 10763 8449 6683 5326 4274 3453 2808 2298 1891 1566 1303 1090 917 775 F 5 22771 17440 13477 10502 8250 6531 5208 4183 3382 2752 2253 1856 1537 1280 1071 901 762 6 22163 16990 13140 10248 8057 6383 5094 4094 3312 2697 2209 1820 1509 1257 1953 886 749 7 21573 16553 12812 1000 7869 6238 4982 4006 3244 2643 2166 1786 1481 1235 1035 871 737 8 21000 16128 12494 9760 7685 6098 4873 3922 3177 2590 2124 1753 1454 1213 1017 857 725 9 20445 15715 12185 9526 7507 5961 4767 3839 3112 2538 2083 1720 1427 1191 999 842 713
Step 3. Example:
Page 25
25
PDX Series
PDX SERVICE PROCEDURE VI Gas Control & Thermal Well Testing and Replacement
Position gas valve power switch to the OFF position and Unplug Heater from power supply. Drain heater to a point below the gas control level. Turn off gas supply to water heater and disconnect gas piping from gas control. Disconnect wire harnesses and burner assembly from gas control.
Thermal Well
Remove gas control & thermal well by rotating flats of Thermal Well counter clockwise (1-5/16"wrench).
Step 5.
Pivot tool towards heater as far as possible (see photo below). Lift straight up on gas control. The control should move about 1/8". Hold control in position and remove tool. Lift straight up on control to remove completely from Thermal Well.
With service tool inserted, pivot tool back towards water heater as far as possible. Lift straight up on control, control will move 1/8". Remove tool and continue to lift straight up on control to remove from Thermal Well. Page 26
26
PDX Series
Gas Control Assembly to Thermal Well
Step 1. Install threaded end of thermal well into tank. Be sure thermal well flange is positioned as shown in photo 22 for proper control alignment. Route wire leads back into relief opening. (see photo 23) Align slots located on thermal well flange with tabs located on back of gas control (see photo 22 & 23)
PDX SERVICE PROCEDURE VI Gas Control & Thermal Well Testing and Replacement
22
Step 2. Step 3.
Step 4.
Carefully push control back onto thermal well flange as far as possible towards water heater. Slide control down to lock into position. Install burner and connect pilot tubing and feedline nut to gas control.
23
Step 5.
Igniter/sensor connection
Step 6. Step 7.
Reconnect wire harnesses to gas control per the illustration. Reconnect gas piping to gas control. Restore gas supply and check for gas leaks. To resume operation, follow the instruction located on the lighting instruction label or the lighting instruction located in the installation and operation manual.
Step 8.
5 pin blower harness connection 3 pin thermal well connection
27
PDX Series
CAUTION
DO NOT use standard multimeter probes for this test. Doing so will damage connector. Use special electronic pin type probes or small diameter wire pins inserted into connector.
Page 28
28
PDX Series
Safety Circuit Voltage Trace
NOTE: This procedure assumes a cool tank.
WARNING 120 volt potential exposure. Use caution making voltage checks to avoid personal injury.
24
Step 2.
Remove three screws (Phillips Screw driver) from control access cover on blower and remove cover (see photo 24).
Position gas control switch to the ON position and adjust thermostat dial to call for heat, Is there 10 to 13 VAC between red wire leading to blower temperature switch N and green ground wire? Blower must be running during this voltage check. (see photo 25) Y
Is there 10 to 13 VAC between yellow wire leading from pressure switch and green ground wire? (see photo 25) Y
If burner does not light, observe LED flash code on gas valve and refer to troubleshooting section on page 13
Page 29
29
PDX Series
120 VAC Circuit Trace
WARNING 120 volt potential exposure. Use caution making voltage checks to avoid personal injury.
Step 1. Verify 120VAC and proper polarity at wall outlet. Step 2. With unit plugged in and control power switch in the ON position verify LED status.
LED status None, Control LED not on or flashing. LED status Short flash, once every four seconds. LED status Heartbeat, alternates bright/dim. LED status Various flashing error codes.
27
28
Using a volt meter set to volts AC, is there 120VAC N across terminals shown in photo 27 ? Y Is there 120VAC across terminals shown in photo 28 ? N Incorrect supply voltage polarity Disconnect wire harness from gas control (see photo 29). Y Reconnect cord set shown in photo 26.
Repair damage
29
Wire harness
Locate black & white wires at connector, It may be necessary to pull back wire sheath to identify wire colors. (see photo 30)
30
Wire sheath pulled back to identify wire colors Is there 120VAC across black & white wires as shown in photo 30? N
Check for 120VAC between black & white wires. -NOTEElectronic meter probes required. Use care not to damage connector during this check.
30
PDX Series
Step 1. Step 2.
Position on/off switch of gas control valve to OFF position and unplug water heater from wall outlet. Turn off cold water supply to water heater. Connect hose to drain valve of water heater and route to an open drain. Open a nearby hot water faucet to vent heater for draining. Open drain valve of water heater and allow heater to drain to a point below the inlet connection nipple. Disconnect inlet nipple from plumbing system. With an appropriate tool such as a pipe wrench, remove inlet nipple/dip tube from the water heater. Use caution not to damage pipe threads. Visually inspect inlet nipple/dip tube. Inlet nipple/dip tube should be free of cracks and any blockage. Hydro-jet slots should be open and free of any blockage. Any damage such as cracks, restriction due to deformation or unintentional holes are not field repairable and the inlet nipple/dip tube must be replaced.
Step 6. Step 7.
Upon completion of inspection or subsequent replacement, reinstall inlet nipple/dip tube into water heater. Connect nipple to plumbing system, resume water supply and refill with water. To resume operation follow the instructions located on the lighting instruction label or the lighting instructions located in the installation and operation manual.
Page 31
31
PDX Series
Step 6. Step 7.
Page 32
32
PDX Series
Remove blower to gain access to flue baffle
Step 1. Step 2. Step 3. Step 4. Step 5. Step 6. Step 7. Step 8.
Position gas control power switch to the OFF position and unplug blower from wall outlet. Disconnect vent system from exhaust adapter on top of blower. Disconnect intake air piping. Unplug cord sets from blower. (see photo 31). Remove the three blower mounting screws (" nut driver) (see photo 31). Remove blower with gasket from water heater. Remove flue baffle from Heater (see photo 33). Inspect baffle for deterioration, missing restrictors. Clean any scale or debris build up. Replace with new baffle as necessary. Reinstall baffle into flue tube. Be sure baffle hanger tabs are inserted into notch location at the top of the flue tube (see photos 34 & 35). Check Burner to insure no scale has accumulated during this operation. See burner cleaning procedure on page 15. Reinstall blower on water heater. Connect vent system and cords set to blower. Plug water heater into wall outlet. To resume operation follow the lighting instruction located on the lighting instruction label or the lighting instruction located in the installation and operation manual.
Flue Baffle Blower Cord Sets 32
Step 9.
Step 12.
33
34
Page 33
33
PDX Series
Inner Door Removal Procedure.
PDX SERVICE PROCEDURE XIII Inner Door/Gasket Removal, Inspection Replacement and Reinstallation
Step 1. Slide switch of the Electronic Gas Control to the OFF position and unplug from wall. Step 2. Remove outer jacket burner access door. Step 3. Disconnect wire connections from Electronic Gas Control. Step 4. Right side Inner Door Removal. a) Remove wire tie from feedline. b) Remove (2) 1/4" hex drive screws from right side inner door. c) Remove (2) 1/4" hex drive screws from flange section of inner door. d) Remove right side inner door and set aside. Be careful not to damage gasket material on inner door.
" Hex Drive Screws shown on Right Side Inner Door. " Hex Drive Screws at Flange section of Inner Door
Step 4. Fully inspect inner door gaskets for the following: >Tears >Other imperfection that will inhibit proper seal >Missing Material >Gasket adhesion to inner door >Cracks >Material left on combustion chamber (around opening) >Dirt or debris If the gasket is not effected by any of the above, gasket replacement is not required. If replacement is required, proceed to Inner Door Gasket Replacement Procedure.
34
PDX Series
PDX SERVICE PROCEDURE XIII Inner Door/Gasket Removal, Inspection Replacement and Reinstallation
WARNING Stripped fastener connections may allow for seal breach of inner door. A seal breach may result in a fire or explosion causing property damage, personal injury or death. Do not over tighten screws in steps 8, 10 and 11. If a fastener connection is stripped, contact the manufacturer listed on the water heater rating plate.
35
PDX Series
PDX SERVICE PROCEDURE XIII Inner Door/Gasket Removal, Inspection Replacement and Reinstallation
Align right side inner door to combustion chamber and verify the fastener holes of the combustion chamber are aligned with the right side inner door slotted opening. Verify seal integrity around combustion opening. Secure right side inner door using 1/4 hex drive screws from step 3b. DO NOT OVER TIGHTEN SCREWS. Verify both left and right sides of the inner door are properly positioned and sealed against the combustion chamber
Replace outer jacket burner access door. To resume operation follow the instructions located on the lighting instruction label or the lighting instructions located in the installation and operation manual.
Page 36
36
PDX Series
Frozen intake or exhaust vent terminal
If an intake or exhaust vent terminal is blocked with ice or snow due to severe conditions, the pressure switch and control will not allow the burner to operate. This will result in a three flash error code. Once the blockage is removed (through melting or other means) the controls will let the burner operate. The position of the vent terminals in relation to each other and terminals from other appliances can have an effect on the potential for blockage due to ice or snow. See the installation instructions for recommended positioning of the terminals. Testing under severe conditions has shown that the optional concentric vent terminal is resistant to ice blockage. Contact Bradford White or the supplier of the water heater for information about ordering the optional concentric vent terminal. Bradford White has also developed an air intake relief device that can be installed in the air intake near the water heater temporarily enabling the water heater to operate with a frozen intake terminal. Contact Bradford White or the supplier of the water heater for information about the air intake relief device.
Page 37
37
PDX Series
Glossary of Terms
BTU GPM Hz KW/h LED NPT Ohms PSI RPM TCO VAC W.C. C F
British Thermal Units Gallons per Minute Hertz Killo-watts per hour Light Emitting Diode National Pipe Thread Ohms of resistance Pounds per Square Inch Revolutions per Minute Temperature Cut Off Volts Alternating Current Inches of Water Column Degrees Centigrade Degrees Fahrenheit
NOTES
Page 38
38
PDX Series
Parts List
1. Blower Assembly 2. Blower Temp. Switch 3. Pressure Switch 4. Blower Gasket 5. Tee and Vent Pipe Assy. 6. Vent Adapter with Term. 7. Intake Terminal 8. Vent Terminal Elbow 9. Exhaust Adapter 10. Condensate Hose Kit 11. Flue Reducer 12. Heat Trap Insert (outlet) 13. Heat Trap Insert (inlet) 14. Hot Water Outlet Anode
15. Cold Water Inlet Diptube 16. Flue Baffle 17. Blower Harness 18. T&P Relief Valve 19. NPT PLUg 20. Direct Vent Boot Escutcheon 21. Air Intake Boot 22. Air Intake Boot Gasket 23. Outer Door 24. Right Side Inner Door 25. Left Side Inner Door 26. Screw-#10-12 x HWH 27. Screw-#8-18 x HWH
28. Brass Drain Valve 29. Flammable Vapor Sensor 30. Sensor Harness 31. Flammable Vapor Sensor Clip 32. Thermal Well 33. Gas Control Kit 34. Gas Control Service tool 35. Gas Control 36. Gas Burner Assy (Nat.) 37. Gas BN burner (Nat.) 38. Main Burner Orifice (Nat.) 39. Gas Pilot Assembly (Nat.) 40. Gas Pilot Orifice (Nat.)
41. Gas Feedline (Nat.) 42. Gas Burner Assy (L.P.) 43. Cast Iron Burner (L.P.) 44. Gas Pilot Assy (L.P.) 45. Gas Pilot Orifice (L.P.) 46. Air Shutter (L.P.) 47. LP Gas Feedline (L.P.) 48. Air Shutter Nut (L.P.) 49. Main Burner Orifice (L.P.) 50. Inner Door Gasket 51. Heat Trap Insert kit 52. Mixing Valve
Page 39
39