Location via proxy:   [ UP ]  
[Report a bug]   [Manage cookies]                

Sepam

Download as pdf or txt
Download as pdf or txt
You are on page 1of 202

Square D SEPAM Digital Relay Catalog

Square D Electrical Protection And Monitoring

HAZARD CATEGORIES AND SPECIAL SYMBOLS


Read these instructions carefully and look at the equipment to become familiar with the device before trying to install, operate, service or maintain it. The following special messages may appear throughout this bulletin or on the equipment to warn of potential hazards or to call attention to information that claries or simplies a procedure. The addition of either symbol to a Danger or Warning safety label indicates that an electrical hazard exists which will result in personal injury if the instructions are not followed. This is the safety alert symbol. It is used to alert you to potential personal injury hazards. Obey all safety messages that follow this symbol to avoid possible injury or death.

DANGER
DANGER indicates an imminently hazardous situation which, if not avoided, will result in death or serious injury.

WARNING
WARNING indicates a potentially hazardous situation which, if not avoided, can result in death or serious injury.

CAUTION
CAUTION indicates a potentially hazardous situation which, if not avoided, can result in minor or moderate injury.

CAUTION
CAUTION, used without the safety alert symbol, indicates a potentially hazardous situation which, if not avoided, can result in property damage.

Note: Provides additional information to clarify or simplify a procedure.

PLEASE NOTE
Electrical equipment should be installed, operated, serviced, and maintained only by qualied personnel. No responsibility is assumed by Schneider Electric for any consequences arising out of the use of this material.

FCC NOTICE
This equipment has been tested and found to comply with the limits for a Class A digital device, pursuant to part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference when the equipment is operated in a commercial environment. This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with the instruction manual, may cause harmful interference to radio communications. Operation of this equipment in a residential area is likely to cause harmful interference in which case the user will be required to correct the interference at his own expense. This Class A digital apparatus complies with Canadian ICES-003.

Sepam Series 20 Sepam Series 40 Sepam Series 80

General Content

Introduction

1 2 3 4 5

Sepam Series 20 and Sepam Series 40

Sepam Series 80

Additional Modules and Accessories

Ordering Sepam Relays

Sepam Series 20 Sepam Series 40 Sepam Series 80

Introduction

Sepam for Greater Simplicity Sepam Network Protection for Your Peace of Mind Sepam Offers Flexibility to Match Your Needs Sepam Boosts Productivity Overview of Sepam Applications Selection Guide for All Applications Substation Applications
Feeder Protection Main Protection

4 5 6 7 8 9 10
11 12

Bus Applications Transformer Applications


Transformer Feeder Protection Transformer Main Protection

13 14
15 17

Motor Applications Generator Applications Capacitor Applications Communication Networks and Protocols Implementation Examples of Architectures Available Sepam Data
Selection Table Description Sepam Series 20 and Sepam Series 40 Sepam Series 80 Additional Modules and Accessories Ordering Sepam Relays
0

20 24 28 30 32 33 36
36 37 41 77 129 195

Introduction

Sepam for Greater Simplicity

PE50478

A consistent range of protection relays


The Sepam range of protection relays is designed for all protection applications on medium-voltage commercial and industrial distribution networks. There are three series of relays: b Sepam Series 20 for common applications b Sepam Series 40 for demanding applications b Sepam Series 80 for custom applications

Sepam, a consistent range of protection relays.

PE50539

A multi-functional range of digital relays


Each Sepam series offers all the functions required for the intended application: b effective protection of life and property b accurate measurements and detailed diagnosis b integral equipment control b local or remote indications and operation

Integral equipment control by Sepam.

PE50480

A Sepam solution for every application


For each electrotechnical application, Sepam offers the relay suited to the protection needs of your electrical network. The Sepam range covers the following applications: b substations (main or feeder type) b transformers b motors b generators b buses b capacitors

A Sepam solution for every application.

Introduction

Sepam Network Protection for Your Peace of Mind


Schneider Electrics global product line

PE50528

World leader in Power & Control


The future will call increasingly on electricity with growing needs for new modes of production and new applications. The world leader in electric distribution and automation & control, Schneider Electric makes electricity safe, as well as facilitating and improving its use.

World-wide presence
Schneider Electric, by your side in over 130 countries.

With sites on every continent, Schneider Electric contributes to customer performance through its unique selection of products, solutions and services, as well as its dynamic policy of innovation. Continuous, worldwide availability With over 5000 points of sale in 130 countries, you can be sure to nd the range of products that meets your needs and complies perfectly with local standards. Technical assistance around the globe Our technicians are always on hand to provide solutions tailored to your needs. Schneider Electric provides all the technical assistance you require, wherever you may be. Visit the www.powerlogic.com site to nd contact information about Schneider Electric in your country.

PE50529

Schneider Electrics manufacturing of protection relays


Sepam, over 25 years of experience
Schneider Electric broke new ground in 1982 by marketing the rst multi-functional digital protection relay, the Sepam 10. Today, with the Sepam range, you benet from more than 25 years of experience on the part of our R&D teams.

Installed base
b 200,000 Sepam relays in over 90 countries b presence in every sector of activity: v energy: production and distribution v infrastructures: airports, tunnels, public transport, water treatment v industry: automobiles, mines, semi-conductors, metallurgy, petrochemicals v commercial sector: shopping centers, hospitals.

Sepams guaranteed quality


Protection relays must be totally reliable. That level of reliability is obtained by total quality at every step, from design through operation. b design based on dependability studies and complying with the functional requirements of standard IEC 61508 b development and production certied ISO 9001 b environment-friendly production, certied ISO 14001 b service quality ensured by decentralized logistics and support b compliance with international standards and local certication b compliance with applicable ANSI C37 standard, UL 508 standard, CSA C22 standard
DE51860 DE51861 DE51862

Introduction

Sepam Offers Flexibility to Meet Your Needs


Enhancement through the addition of optional modules to keep pace with your everchanging installation
To adapt to as many situations as possible and allow for future installation upgrades, optional modules may be added to Sepam at any time for new functions: b plug & play modules, easy to install and connect b complete setup using software

1 2 3 4 5 6 7 8

Base unit Parameter and protection settings saved on removable memory cartridge 42 logic inputs and 23 relay outputs with 3 optional modules Connection to communication networks Temperature sensors Low-level analog output Synchro-check module Software tools
PE50483

Sepam Series 80 and its optional modules.

A choice of user-machine interfaces (UMI) to meet your operating needs


b advanced UMI for all Sepam relays: v on front panel v or remote UMI installed in the most convenient location for the facility manager b mimic-based UMI for Sepam series 80, offering local switchgear control

PE50041

A software tool for all Sepam relays


The SFT2841 software is the setting and operating tool for Sepam Series 20, Series 40 and Series 80. b the ergonomics are designed to guide you in setting up Sepam b future compatibility is ensured with all Sepam versions.

SFT2841: a single software tool for all Sepam relays.

Introduction

Sepam Boosts Productivity

Easy operation
To ensure fast and effective servicing, thereby reducing the operating and maintenance costs of your electric installation, all operating and maintenance information is available: b locally and remotely b in your language

Local operation
PE50127

All the data required for local equipment operation are clearly displayed on the LCD screen of the UMI (User-Machine Interface). b UMI screens are shipped with English as the default, but can be translated to your language b alarms and operating messages can be personalized

Customized advanced UMI.

PE50765

Remote operation
All Sepam relays can be connected to two types of communication networks: b an S-LAN (supervisory local area network) to remotely control and monitor Sepam relays connected to a supervisory system (SCADA or RTU) b an E-LAN (engineering local area network), reserved for Sepam remote parameter setting and centralized installation diagnosis using the SFT2841 software.

Sepam Series 20

Sepam Series 40

Sepam Series 80

Sepam connection to two communication networks.

Improved continuity of service


With Sepam, all data is available for optimum management and use of the electric installation. b The clear and complete information supplied by Sepam following a fault trip enables the operator to restore power as quickly as possible. b Preventive maintenance of switchgear is made easier by the diagnosis functions provided by Sepam. b The predictive information supplied by the motor-protection functions optimizes process control.

PE50637

Reduced maintenance costs


The Sepam range is designed to reduce maintenance time and cost for your protection system. b Sepam modules and connectors may be removed. b The optional modules are the same for the entire Sepam range, thus reducing the stock of replacement parts. b Sepam series 80 has a removable memory cartridge to simplify maintenance operations.

Sepam series 80 memory cartridge.

Selection Guide for All Applications

Overview of Sepam Applications

The selection guide proposes Sepam Series 20 For applications the Sepam types suited to your Characteristics b 10 logic inputs protection needs, based on the b 8 relay outputs b 1 communication port characteristics of your application. b 8 temperature-sensor
PE50465

DE51730 DE51732 DE51733 DE51734 DE51731

NO

inputs

The most typical applications are presented with the corresponding Sepam and each application example is described by: a single-line diagram indicating: equipment to be protected network conguration position of measurement sensors standard and specic Sepam functions to be implemented to protect the application. The list of functions is given for information purposes. Grounding, whether direct or via an impedance, is represented by the same pictogram, i.e. the pictogram corresponding to a direct connection.

NO

Sepam Series 40
For demanding applications Characteristics b 10 logic inputs b 8 relay outputs b logical equation editor b 1 communication port b 16 temperature-sensor inputs
PE50465

NO

Sepam Series 80
For custom applications Characteristics b 42 logic inputs b 23 relay outputs b logical equation editor b 2 communication ports for multi-master or redundant architectures b 16 temperature-sensor inputs b removable memory cartridge with parameter and protection settings for fast return to service following replacement b battery backup to save historical and disturbance-recording data b mimic-based UMI for local device control b optional Logipam programming software to program specic functions
PE50463

NO

PE50464

NO

DE51735

NO

NO

NO
NO

DE51736

Selection Guide for All Applications

Selection Guide for All Applications

Protection Functions
Basic Specic

Applications
Substation Bus Transformer Motor Generator Capacitor

current protection Breaker failure

S20 S23

T20 T23

M20

voltage and frequency protection disconnection by rate of change of frequency

B21 B22
Page 41

current, voltage and frequency protection directional ground fault directional ground fault and phase overcurrent

S40 S41 S42

T40 M41 T42

G40

current, voltage and frequency protection directional ground fault directional ground fault and phase overcurrent disconnection by rate of change of frequency current, voltage and transformer and frequency protection transformermachine unit differential machine differential current, voltage and voltage and frequency protection frequency protection for two sets of bus

S80 S81 S82 S84

B80 T81 T82 M81 G82

T87

M88

G88

M87 B83

G87

Page 77

current, voltage and capacitor-bank frequency protection unbalance

C86

Page 10

Page 12

Page 14

Page 20

Page 24

Page 28

Selection Guide for All Applications

Substation Applications Feeder Protection

Protection Functions
Phase overcurrent (1) Ground fault / Sensitive ground fault (1) Breaker failure Negative sequence / unbalance Thermal overload for cables Directional phase overcurrent (1) Directional ground fault (1) Directional active overpower Directional active underpower Positive sequence undervoltage Remanent undervoltage Undervoltage (LL or Ln) Overvoltage (LL or Ln) Neutral voltage displacement Negative sequence overvoltage Overfrequency Underfrequency Rate of change of frequency Recloser (4 shots) (2) Synchro-check (3)

ANSI code
50/51 50N/51N 50G/51G 50BF 46 49RMS 67 67N/67NC 32P 37P 27D 27R 27 59 59N 47 81H 81L 81R 79 25

S20
4 4

S23
4 4 1 1

B22

S40
4 4 1 2

S41
4 4 1 2

S42
4 4 1 2 2 2 1

S80
8 8 1 2

S81
8 8 1 2 2 2 2

S82
8 8 1 2 2 2 2 2 2 2 4 4 2 2 2 4 v v

S84
8 8 1 2 2 2 2 2 2 2 2 4 4 2 2 2 4 2 v v

2 1 2 1 2/1 (4) 2 2 1 2 1 v v

2 2 2 1 2 4 v

2 2 2 1 2 4 v

2 2 2 1 2 4 v

2 2 4 4 2 2 2 4 v v

2 2 4 4 2 2 2 4 v v

standard options. (1) Protection functions with 2 groups of settings. (2) According to parameter setting and optional input/output modules. (3) With optional MCS025 synchro-check module. (4) 2 undervoltage (LL) and 1 undervoltage (Ln). (5) The digits in the matrix to the right of the ANSI code indicate the number of units available for each protection function.

Feeder Protection
b feeder short-circuit and overload protection. Protection of low-capacitance feeders in impedance grounded or solidly grounded neutral systems: Sepam S20, S23, S40 or S80 b no voltage and frequency monitoring. b voltage and frequency monitoring.
DE52581

NO

DE51686

NO

Protection of high-capacitance feeders in impedance grounded or compensated or isolated neutral systems: Sepam S41 or S81 b specic feeder protection: 67N/67NC.
DE51687

NO

10

Selection Guide for All Applications


Main Protection
b bus short-circuit protection. Main protection: Sepam S20, S23, S40 or S80 b no voltage and b bus voltage and frequency monitoring. frequency monitoring.
DE52582 DE51688

Substation Applications Main Protection

b line voltage and frequency monitoring.


DE51689

Protection of 2 mains: Sepam S80 b with automatic source transfer (ATS) and synchrocheck (ANSI 25).
DE51690

NO

NO

NO

NC

NC

NO

Parallel main protection: Sepam S42 or S82 b specic line or source protection: 67, 67N/67NC.

Parallel-main protection with disconnection function: Sepam S20 + B22 or Sepam S84 b disconnection-specic functions: b disconnection-specic functions: 27,59, 59N, 81L, 81R. 27,59, 59N, 81L, 81R, 32P, 37P.
DE52583 DE51692

DE51691

NO

NO

NO

NO

NO

NO

NO

NO

Protection of any main or tie breaker circuit breaker with load shedding based on frequency variations: Sepam S84 b load-shedding-specic functions: 81L, 81R.
DE51693 DE51694

NO
NO

Ring-main protection: Sepam S42 or S82 b line or source protection: 67, 67N/67NC b directional Zone Sequence Interlocking (ZSI).

DE51695

NO

NO

NO

NO

NO

NO

11

Selection Guide for All Applications

Bus Applications

Protection Functions
Phase overcurrent (1) Ground fault / Sensitive ground fault (1) Breaker failure Negative sequence / unbalance Positive sequence undervoltage Remanent undervoltage Undervoltage (LL or Ln) Overvoltage (LL or Ln) Neutral voltage displacement Negative sequence overvoltage Overfrequency Underfrequency Rate of change of frequency Synchro-check (2)

ANSI code
50/51 50N/51N 50G/51G 50BF 46 27D 27R 27 59 59N 47 81H 81L 81R 25

B21

B22

B80
8 8 1 2 2 2 4 4 2 2 2 4 v

B83
8 8 1 2 2 2 4 4 2 2 2 4 v

2 1 2/1 (3) 2 2 1 2

2 1 2/1 (3) 2 2 1 2 1

standard v options. (1) Protection functions with 2 groups of settings. (2) With optional MCS025 synchro-check module. (3) 2 undervoltage (LL) and 1 undervoltage (Ln). (4) The digits in the matrix to the right of the ANSI code indicate the number of units available for each protection function.

12

Selection Guide for All Applications

Bus Applications

Voltage Monitoring
b voltage and frequency monitoring. Monitoring of the 3 phase voltages and the residual voltage on buses: Sepam B21 or B22 b load-shedding-specic function: 81L. b load-shedding-specic functions: 81L, 81R.
DE51722 DE51723

Tie Breaker Circuit-Breaker Protection


b bus short-circuit protection b voltage and frequency monitoring. Monitoring of the 3 phase voltages and the residual voltage on 2 buses: Sepam B83
DE51696

NO NO

NO

Main Protection with Additional Bus Voltage Monitoring


b bus short-circuit protection b line voltage and frequency monitoring. Additional bus voltage monitoring: Sepam B80
DE51697

NO

13

Selection Guide for All Applications

Transformer Applications

Standard transformer application diagrams do not take voltage levels into account: b the transformer primary winding is always at the top b the transformer secondary winding is always at the bottom. b the transformer primary and secondary windings need to be protected. b the Sepam relay can be installed on either the primary or secondary winding of the transformer. b the other winding can be protected by a main or feeder type substation application.

Protection Functions ANSI code


Phase overcurrent (1) Ground fault / Sensitive ground fault (1) Breaker failure Negative sequence / unbalance Thermal overload for machines (1) Restricted ground fault differential Two-winding transformer differential Directional phase overcurrent (1) Directional ground fault (1) Directional active overpower Overexcitation (V / Hz) Positive sequence undervoltage Remanent undervoltage Undervoltage (LL or Ln) Overvoltage (LL or Ln) Neutral voltage displacement Negative sequence overvoltage Overfrequency Underfrequency Thermostat / Buchholz (2) Temperature monitoring (16 RTDs) (3) Synchro-check (4) 50/51 50N/51N 50G/51G 50BF 46 49RMS 64REF 87T 67 67N/67NC 32P 24 27D 27R 27 59 59N 47 81H 81L 26/63 38/49T

T20
4 4

T23
4 4 1 1 2

T40
4 4 1 2 2

T42
4 4 1 2 2

T81
8 8 1 2 2 2

T82
8 8 1 2 2 2

T87
8 8 1 2 2 2 1

1 2

2 2 2 2

2 2 2

2 2 2 2 2 2 4 4 2 2 2 4 v v 16 RTDs v

2 2 4 4 2 2 2 4 v v 16 RTDs v

2 2 4 4 2 2 2 4 v v 16 RTDs v

2 2 2 1 2 4 v v v v v v 8 8 16 RTDs RTDs RTDs

2 2 2 1 2 4 v v 16 RTDs

25

standard v options. (1) Protection functions with 2 groups of settings. (2) According to parameter setting and optional input/output modules. (3) With optional MET1482 temperature input modules. (4) With optional MCS025 synchro-check module. (5) The digits in the matrix to the right of the ANSI code indicate the number of units available for each protection function.

14

Selection Guide for All Applications

Transformer Applications Transformer Feeder Protection


Transformer Feeder Protection
b transformer short-circuit and overload protection b internal transformer protection: Thermostat / Buchholz (ANSI 26/63) b RTD temperature monitoring (ANSI 49T). Transformer feeder protection without voltage monitoring: Sepam T20, T23 Ground fault protection: Ground fault protection: b primary: 50G/51G. b neutral point: 50G/51G.
DE52584 DE52585

NO

NO

NO

NO

Transformer feeder protection with voltage monitoring: Sepam T40 or T81 Ground fault protection: b primary: 50G/51G.
DE51698

NO

NO

Note: for long feeders, the 50G/51G function may be replaced by the 67N/67NC.

15

Selection Guide for All Applications

Transformer Applications Transformer Feeder Protection

Transformer feeder protection with voltage monitoring and additional current measurement: Sepam T81 Ground fault protection: Ground fault protection: b primary: 50G/51G b primary: 50G/51G b tank ground leakage: b secondary: 50G/51G. 50G/51G.
DE51699

NO

DE51700 DE51702

NO

NO

NO

Note: for long feeders, the 50G/51G function may be replaced by the 67N/67NC.

Transformer feeder differential protection: Sepam T87 Transformer differential protection: 87T Ground fault protection: Ground fault protection: Ground fault protection: b primary: 50G/51G. b primary: 50G/51G b primary: b secondary: v 64REF v 64REF v 50G/51G v 50G/51G. b secondary: v 64REF v 50G/51G.
DE51701

NO

NO

DE51703

NO

Y Y

NO

NO

NO

16

Selection Guide for All Applications

Transformer Applications Transformer Main Protection


Transformer Main Protection
b transformer short-circuit and overload protection b internal transformer protection: Thermostat / Buchholz (ANSI 26/63) b RTD temperature monitoring (ANSI 49T). Transformer main protection without voltage monitoring: Sepam T20, T23 Ground fault protection: Ground fault protection: b secondary: 50G/51G. b neutral point: 50G/51G.
DE52586

NO

DE52587 DE51705

NO

NO

NO

Transformer main protection with voltage monitoring: Sepam T40 or T81 Ground fault protection: Ground fault protection: b secondary: 50G/51G. b secondary: v 64REF v 50G/51G.
DE51704

NO

NO

NO

NO

17

Selection Guide for All Applications

Transformer Applications Transformer Main Protection

Transformer main differential protection: Sepam T87 Transformer differential protection: 87T Ground fault protection: Ground fault protection: Ground fault protection: b primary: 50G/51G b primary: 50G/51G b primary: 50G/51G b secondary: 50G/51G. b secondary: b secondary: v 64REF v 64REF v 50G/51G. v 50G/51G.

Ground fault protection: b primary: v 64REF v 50G/51G b secondary: 50G/51G.

Ground fault protection: b primary: v 64REF v 50G/51G b secondary: v 64REF v 50G/51G.


DE51711

DE51707

DE51708

DE51709

DE51710

NO

NO

NO

NO

NO

Y Y

NO

NO

NO

NO

NO

Protection of 2 non-coupled transformer mains: Sepam T81 b automatic source transfer (ATS) b synchro-check (ANSI 25).
DE51706

18

Selection Guide for All Applications

Transformer Applications Transformer Main Protection


Parallel transformer main protection: Sepam T42 or T82 b transformer directional phase overcurrent protection: 67 b transformer secondary ground fault protection: 50G/51G, 59N.
DE51712

NO

NO

NO

NO

b transformer directional phase overcurrent protection: 67 b transformer secondary ground fault protection: 67N/67NC, 64REF b with synchro-check (ANSI 25).
DE51718

NO

NO

NO

NO

NO

Parallel main differential protection: Sepam T87 b transformer differential protection: 87T b directional transformer protection: 67 b transformer secondary ground fault protection: 50G/51G, 67N/67NC 64REF.
DE51713

NO

NO

NO

NO

NO

19

Selection Guide for All Applications

Motor Applications

Protection Functions

ANSI code
50/51 50N/51N 50G/51G 50BF 46 49RMS 87T 87M 67N/67NC 32P 32Q/40 40 37 48/51LR/14 66 78PS 12 14 27D 27R 27 59 59N 47 81H 81L 26/63 38/49T

M20
4 4

M41
4 4 1 2 2

M81
8 8 1 2 2

M87
8 8 1 2 2

M88
8 8 1 2 2 1

Phase overcurrent (1) Ground fault / Sensitive ground fault (1) Breaker failure Negative sequence / unbalance Thermal overload for machines (1) Two-winding transformer differential Machine differential Directional ground fault (1) Directional active overpower Directional reactive overpower Field loss (underimpedance) Phase undercurrent Excessive starting time, locked rotor Starts per hour Loss of synchronization Overspeed (2 set points) (2) Underspeed (2 set points) (2) Positive sequence undervoltage Remanent undervoltage Undervoltage (LL or Ln) Overvoltage (LL or Ln) Neutral voltage displacement Negative sequence overvoltage Overfrequency Underfrequency Thermostat / Buchholz Temperature monitoring (16 RTDs) (3)

1 2

2 1 1 1 1 1 1 1 1

2 2 1 1 1 1 1 1 v v 2 2 4 4 2 2 2 4 v v 16 RTDs

1 2 2 1 1 1 1 1 1 v v 2 2 4 4 2 2 2 4 v 16 RTDs

2 2 1 1 1 1 1 1 v v 2 2 4 4 2 2 2 4 v v 16 RTDs

2 1 2 2 2 1 2 4 v 8 RTDs v 16 RTDs

standard v options. (1) Protection functions with 2 groups of settings. (2) According to parameter setting and optional input/output modules. (3) With optional MET1482 temperature input modules. (4) The digits in the matrix to the right of the ANSI code indicate the number of units available for each protection function.

20

Selection Guide for All Applications

Motor Applications

Motor Protection
b b b b internal motor fault protection power supply fault protection driven load fault protection RTD temperature monitoring (ANSI 38/49T).

Motor protection without voltage monitoring: Sepam M20 b direct starting. b auto-transformer b two-way. starting.
DE51724 DE51737 DE51738

NO

NO

NO

NO

NO

NO

Motor protection with voltage monitoring: Sepam M41 or M81 b direct starting. b auto-transformer b two-way. starting.
DE51725 DE51739

NO

DE51740

NO

NO

NO

NO

NO

Motor differential protection: Sepam M87 Motor differential protection: 87M.

b direct starting.

b auto-transformer starting.
DE51742

Phase protection by self-balancing-differential scheme: 50/51. b direct starting.

DE51741

NO

DE51743

NO

NO

NO

NO

21

Selection Guide for All Applications

Motor Applications

Motor-Transformer Unit Protection

b b b b b

motor and transformer protection against internal faults power supply fault protection driven load fault protection internal transformer protection: Thermostat / Buchholz (ANSI 26/63) RTD temperature monitoring (ANSI 38/49T).

Motor-transformer unit protection without voltage monitoring: Sepam M20 b transformer primary ground fault protection: 50G/51G.
Note: monitoring of motor insulation must be ensured by another device.
DE51744

NO

Motor-transformer unit protection with voltage monitoring: Sepam M41 b motor ground fault protection: 59N b transformer primary ground fault protection: 50G/51G.
DE51745

NO

Motor-transformer unit protection with voltage and transformer monitoring: Sepam M81 b motor ground fault protection: 59N b motor ground fault protection: 50G/51G b transformer primary ground fault b transformer primary ground fault protection: 50G/51G protection: 50G/51G b transformer monitoring: Buchholz, b transformer monitoring: Buchholz, thermostat, temperature measurement. thermostat, temperature measurement.
DE51747

NO

22

DE51746

NO

Selection Guide for All Applications

Motor Applications

Motor-transformer unit differential protection: Sepam M88 Motor-transformer unit differential protection: 87T. b motor ground fault protection: 50G/51G b motor ground fault protection: 59N b transformer primary ground fault b transformer primary ground fault protection: 50G/51G. protection: 50G/51G.
DE51748

NO

DE51749

NO

23

Selection Guide for All Applications

Generator Applications

Protection Functions
Phase overcurrent (1) Ground fault / Sensitive ground fault (1) Breaker failure Negative sequence / unbalance Thermal overload for machines (1) Restricted ground fault differential Two-winding transformer differential Machine differential Directional phase overcurrent (1) Directional ground fault (1) Directional active overpower Directional reactive overpower Directional active underpower Field loss (underimpedance) Loss of synchronization Overspeed (2 set points) (2) Underspeed (2 set points) (2) Voltage-restrained phase overcurrent Underimpedance Inadvertent energization Third harmonic undervoltage / 100% stator ground fault Overexcitation (V / Hz) Positive sequence undervoltage Remanent undervoltage Undervoltage (LL or Ln) Overvoltage (LL or Ln) Neutral voltage displacement Negative sequence overvoltage Overfrequency Underfrequency Thermostat / Buchholz Temperature monitoring (16 RTDs) (3) Synchro-check (4)

ANSI code
50/51 50N/51N 50G/51G 50BF 46 49RMS 64REF 87T 87M 67 67N/67NC 32P 32Q/40 37P 40 78PS 12 14 50V/51V 21B 50/27 27TN/64G2 64G 24 27D 27R 27 59 59N 47 81H 81L 26/63 38/49T 25

G40
4 4 1 2 2

G82
8 8 1 2 2 2

G87
8 8 1 2 2

G88
8 8 1 2 2 2 1

1 1

2 2 2 1 2 1 1 v v 2 1 1 2

1 2 2 2 1 1 1 v v 2 1 1 2

2 2 2 1 1 1 v v 2 1 1 2

2 2 2 1 2 4 v 16 RTDs

2 2 2 4 4 2 2 2 4 v v 16 RTDs v

2 2 2 4 4 2 2 2 4 v 16 RTDs v

2 2 2 4 4 2 2 2 4 v v 16 RTDs v

standard v options. (1) Protection functions with 2 groups of settings. (2) According to parameter setting and optional input/output modules. (3) With optional MET1482 temperature input modules. (4) With optional MCS025 synchro-check module. (5) The digits in the matrix to the right of the ANSI code indicate the number of units available for each protection function.

24

Selection Guide for All Applications

Generator Applications

Generator Protection
b b b b b internal generator fault protection network fault protection driving machine fault protection RTD temperature monitoring (ANSI 38/49T) voltage and frequency monitoring.

Protection of a separate generator: Sepam G40 Ground fault protection: Ground fault protection: b 50G/51G b 50G/51G. b 59N.
DE51750 DE51751

NO
NO

Protection of a generator coupled to other generators or to a network: Sepam G82 Short-circuit detection on generator side: 67. Control fault protection. Ground fault protection: Ground fault protection: Ground fault protection: b 50G/51G b 100 % stator ground fault b 64REF and 50G/51G b 59N. 64G. b 50N/51N.
DE51752 DE51753 DE51754

NO
NO

NO

25

Selection Guide for All Applications

Generator Applications

1
DE51755

Generator Differential protection: Sepam G87 Phase protection by self-balancing differential scheme: Generator differential protection: 87M. 50/51. Ground fault protection: 50G/51G. Ground fault protection: Ground fault protection: b 50G/51G b 100 % stator ground b 59N. fault 64G.
DE51756 DE51757

Ground fault protection: b 50N/51N.

NO

DE51758

NO

NO

NO

Generator-Transformer Unit Protection


b b b b b generator and transformer protection against internal faults network fault protection driving machine fault protection RTD temperature monitoring (ANSI 38/49T) voltage and frequency monitoring.

Separate generator-transformer unit protection. Sepam G40 Ground fault protection: b 50G/51G.
Note: monitoring of generator insulation must be ensured by another device.

DE51759

NO

26

Selection Guide for All Applications

Generator Applications

Protection of a generator-transformer unit coupled to other generators or to a network: Sepam G82 Short-circuit detection on generator side: 67. Control fault protection. Internal transformer protection: Thermostat / Buchholz (ANSI 26/63). b generator ground fault protection: b generator ground fault protection: 50G/51G 100 % stator ground fault 64G b transformer secondary ground fault b transformer secondary ground fault protection: protection: v 50G/51G v 50G/51G v 59N. v 59N.
DE51760 DE51761

NO

NO

Generator-transformer unit differential protection: Sepam G88 Generator-transformer unit differential protection: 87T. b generator ground fault protection: b generator ground fault protection: 50G/51G 100% stator ground fault 64G b transformer secondary ground fault b transformer secondary ground fault protection: protection: v 50G/51G. v 50G/51G v 64REF.
DE51762 DE51763

NO

NO

27

Selection Guide for All Applications

Capacitor Applications

Protection Functions

ANSI code
50/51 50N/51N 50G/51G 50BF 46 49RMS 51C 27D 27R 27 59 59N 47 81H 81L 38/49T

S20
4 4

S23
4 4 1 1

S40
4 4 1 2

C86
8 8 1 2 2 8 2 2 4 4 2 2 2 4 v 16 RTDs

Phase overcurrent (1) Ground fault / Sensitive ground fault (1) Breaker failure Negative sequence / unbalance Thermal overload for capacitors (1) Capacitor-bank unbalance Positive sequence undervoltage Remanent undervoltage Undervoltage (LL or Ln) Overvoltage (LL or Ln) Neutral voltage displacement Negative sequence overvoltage Overfrequency Underfrequency Temperature monitoring (16 RTDs) (2)

2 2 2 1 2 4

standard v options. (1) Protection functions with 2 groups of settings. (2) With optional MET1482 temperature input modules. (3) The digits in the matrix to the right of the ANSI code indicate the number of units available for each protection function.

28

Selection Guide for All Applications

Capacitor Applications

Capacitor Bank Protection


Protection of a capacitor bank (delta connection) without voltage monitoring: Sepam S20, S23 b capacitor bank short-circuit protection.
DE52588

NO

Protection of a capacitor bank (delta connection) with voltage monitoring: Sepam S40 or C86 b capacitor bank short-circuit protection b voltage and frequency monitoring b overload protection: ANSI 49RMS (Sepam C86 only).
DE51765 DE51766
NO

NO

Protection of a double-wye connected capacitor bank with 1 to 4 steps: Sepam C86 b capacitor bank short-circuit protection b voltage and frequency monitoring b specic overload protection, self-adapted to the number of connected steps b unbalance protection: 51C.

29

Communication

Communication Networks and Protocols


Two Types of Communication Network
Sepam relays can be connected to two types of networks, thus providing access to different types of information: b a supervisory local area network or S-LAN b an engineering local area network or E-LAN. Examples of communication architectures are presented on pages 30 and 31.

All Sepam relays communicate and can be integrated into communication architecture. All Sepam information can be accessed remotely.

DE53103

Supervisory local area network (S-LAN)


An S-LAN is used for supervision functions concerning the installation and the electric network. It can be used to connect a set of communicating devices using the same communication protocol to a centralized supervision system. Sepam can be connected to an S-LAN using one of the following communication protocols: b Modbus RTU b Modbus TCP/IP b DNP3 b IEC 60870-5-103 b IEC 61850

Engineering local area network (E-LAN)


An E-LAN is intended for Sepam parameter-setting and operating functions. It can be used to connect a set of Sepam units to a PC running the SFT2841 software. In this conguration, the operator has remote and centralized access to all Sepam information, with no need to develop any special communication software. The Sepam connection to two communication networks (S-LAN and operator can easily: E-LAN). b set up the Sepam general parameters and functions b collect all Sepam operating and diagnostics information b manage the protection system for the electric network b monitor the status of the electric network b run diagnostics on any incidents affecting the electric network.
Sepam Series 20 Sepam Series 40 Sepam Series 80

Communication Protocols
Modbus RTU
Modbus RTU is a data-transmission protocol, a de facto standard since 1979 widely used in industry and accepted by many communicating devices. For more information on the Modbus RTU protocol, visit www.modbus.org.

Modbus TCP/IP
The Modbus TCP/IP Ethernet communication protocol offers the same functions as Modbus RTU as well as compatibility with multi-master architectures

DNP3
DNP3 is a data-transmission protocol specially suited to the needs of utilities for remote control/monitoring of substations in the electric network. For more information on the DNP3 protocol, visit www.dnp.org.

IEC 60870-5-103
IEC 60870-5-103 is an accompanying standard for the standards in the IEC 60870-5 series. It denes communication between protection devices and the various devices in a control system (supervisor or RTU) in a substation. For more information on the IEC 60870-5-103 protocol, visit www.iec.ch.

IEC 61850
The standards in the IEC 61850 series dene a protocol for communication in electrical substations. This Ethernet-based protocol offers advanced characteristics and interoperability between multi-vendor devices. The Sepam relay handles the station bus, in compliance with standards IEC 61850-6, 7-1, 7-2, 7-3, 7-4 and 8-1. For more information on the IEC 61850 protocol, visit www.iec.ch.

30

Communication

Communication Networks and Protocols

Other protocols
A gateway / protocol converter must be used to connect Sepam to a communication network based on other protocols. IEC 60870-5-101 The CN1000 gateway developed by EuroSystem enables Sepam connection to IEC 60870-5-101 networks. This gateway is quick and simple to implement using the supplied conguration software integrating all Sepam parameters. For more information on the CN1000 gateway, visit www.euro-system.fr.

31

Communication

Implementation

Sepam Communication Interfaces

PE50530

A complete range of accessories


Sepam connects to a communication network via a communication interface. Selection of the interface depends on the communication architecture: b number of networks to be connected: v 1 network, S-LAN or E-LAN v 2 networks, S-LAN and E-LAN b communication protocol selected for the S-LAN: Modbus RTU, DNP3, IEC 60870-5-103 or IEC 61850 b network physical interface: v 2-wire or 4-wire RS485 v Ethernet v ber optic, with wye or ring architecture. Sepam communication interfaces are presented in detail on page 158.

Direct Sepam connection to the Ethernet network


Sepam series 40 and Sepam series 80 units can be directly connected to the Ethernet network via the ACE 850 communication interface. In this way they make full use of Ethernet network performance and all IEC 61850 functions. b Compatible communication protocols: v Modbus TCP/IP v IEC 61850 b Network physical interface: v 10 baseT /100 base TX (wye architecture) v 100 base FX (wye architecture).

A complete range of Sepam communication interfaces


PE80033-36

Easy implementation
The communication interfaces are remote modules that are easy to install and connect. The SFT2841 software is used for complete setup of the communication interfaces: b protocol selection and setup of the functions specic to each protocol b setup of the physical interface.

Advanced conguration of IEC 61850 protocol


The SFT850 software is used for advanced conguration of the IEC 61850 protocol for both the ECI850 server and the ACE850 communication interface: b complete Sepam-conguration database (.icd) b processing of system-conguration les (.scd) b creation and processing of ECI850 and ACE850 conguration les (.cid).
PE50161

Sepam IEC 61850 server


The entire Sepam range can be connected to an IEC 61850 system via the Sepam ECI850 server, representing the most economical solution. The server also ensures compatibility with the E-LAN network.

Ethernet Gateways in a Modbus Environment


Sepam can be connected to an Ethernet TCP/IP network in a totally transparent manner via the EGX100 gateway or the EGX400 server.

EGX100 gateway
Access to Sepam information via a web browser.

The EGX100 offers access to enhanced communication and multi-master architectures. It provides IP (Internet Protocol) connection for communication on all types of networks, notably intranets and internet.

EGX400 server
In addition to Ethernet TCP/IP connection, the EGX400 offers a web server and HTML pages designed specially to present the essential Sepam information. This information may be accessed in clear text and at no risk on any PC connected to the intranet/ internet and equipped with a web browser.

32

Communication

Examples of Architectures

Seven typical communication architectures are presented in the examples below. Each architecture is presented with: b a simplied diagram b the characteristics of the implemented networks. The physical architecture of the communication networks and the connection to networks depends on the type of network (RS485 or ber optic) and the communication interfaces used. Sepam communication interfaces are presented in detail on page 158.

Example 1. Single S-LAN network


S-LAN characteristics
DE53249

Protocol

Physical medium

Modbus RTU DNP3 or IEC 60870-5-103 Twisted-pair (2-wire or 4-wire RS485) or ber optic

Sepam Series 20

Sepam Series 40

Sepam Series 80

Example 2. Single E-LAN network


E-LAN characteristics
DE53250

Protocol Physical medium

Modbus RTU Twisted-pair (2-wire or 4-wire RS485) or ber optic

Sepam Series 80

Sepam Series 80

Sepam Series 80

Example 3. Parallel S-LAN and E-LAN networks


S-LAN characteristics
DE53251

Protocol

Physical medium

Modbus RTU DNP3 or IEC 60870-5-103 2-wire RS485 (twisted-pair) or ber optic

E-LAN characteristics
Protocol Physical medium Modbus RTU 2-wire RS485 (twisted-pair)

Sepam Series 20

Sepam Series 40

Sepam Series 80

33

Communication

Examples of Architectures

Protocol Physical medium

Modbus RTU Twisted-pair (2-wire or 4-wire RS485)

Characteristics of Ethernet network


Protocol Physical medium Functions of EGX100 or EGX400 gateway Modbus TCP/IP Ethernet 10/100 BaseTx or 100 Base Fx Modbus TCP / Modbus RTU conversion Multiplexing between S-LAN and E-LAN networks

DE53106

Example 4. S-LAN and E-LAN networks over Ethernet TCP/IP


Characteristics of Modbus network between Sepam relays (S-LAN and E-LAN)

Sepam Series 20

Sepam Series 40

Sepam Series 80

Example 5. Two parallel S-LAN networks (Sepam series 80)


S-LAN characteristics
Modbus RTU DNP3 or IEC 60870-5-103 Physical medium Twisted-pair (2-wire or 4-wire RS485) or ber optic Note: the two communication ports on Sepam series 80 can also be used to create two redundant S-LANs connected to a single supervisor/RTU. An E-LAN can be added to the two S-LANs.
DE53107

Protocol

Sepam Series 80

Sepam Series 80

Sepam Series 80

34

Communication

Examples of Architectures

Example 6: S-LAN over IEC 61850 and E-LAN over Ethernet TCP/IP
Protocol Physical medium Modbus RTU Twisted-pair (2-wire or 4-wire RS485)
DE53104

Characteristics of Modbus network between Sepam relays (S-LAN and E-LAN)

Characteristics of Ethernet network


Protocol Support physique Sepam ECI850 server functions IEC 61850 Ethernet 10/100 BaseTx Modbus RTU / IEC 61850 conversion Multiplexing between S-LAN and E-LAN networks

Sepam Series 20

Sepam Series 40

Sepam Series 80

Example 7: S-LAN over IEC 61850 and E-LAN over Ethernet TCP/IP (Sepam series 80)
Characteristics of Ethernet network
Physical medium Ethernet 10/100 BaseTx or 100 Base Fx
DE53105

Protocol

IEC 61850

Note: for the best performance of the protection system when involving peer-to-peer communication through GOOSE messages, we strongly recommend : b to use ber-optic links b to build a fault-tolerant backbone ber-optic ring, as shown in the example b to use 61850 compatible managed switches.

Sepam Series 80

Sepam Series 80

Sepam Series 80

35

Communication

Available Sepam Data Selection Table

1
Measurements Energy Network diagnosis Machine diagnosis Switchgear diagnosis Sepam diagnosis Logipam counters

Modbus RTU

DNP3

IEC 60870-5-103

IEC 61850 (ECI850)

Series 20 Series 40 Series 80 Series 20 Series 40 Series 80 Series 20 Series 40 Series 80 Series 20 Series 40 Series 80

Data transmitted from Sepam to the supervisor


Metering and diagnosis
b b b b b b b b b b b b b b b b b b b b b b b b b b b b b b b b b b b b b b b b b b b b b b b b b b b b b (1) (1) (1) b b (1) (1) (1) b b b (1) (1) (1) b b (1) (1) (1) b b b (1) (1) (1) b b (1) (1) (1) b

Remote indications
Alarms and internal status conditions Logic inputs Logic outputs Logic equations b b b b b b b b b b b b b b b b b b b b b b b b b b b

Data transmitted from the supervisor to Sepam


b Pulse-type remote-control commands, in direct mode b Pulse-type remote-control commands, in Select Before Operate mode Maintained remote-control commands (for Logipam) Remote control security (1) (1) b b (1) (1) b b (1) (1) b b

b b

Data accessible via special functions


Time-stamping
Time-stamped events Unsolicited events Time-setting and synchronization b b b b b b b b b b b b b b b b b b b b b b b b b b b b b b

Remote setting
Selection of the protectionsetting group Reading/writing of protection settings Reading of general parameters Reading/writing of analog output (MSA141) b b b b b b b b b b b b b b b b b b b b b b b b b b b

Network diagnosis
Transfer of disturbancerecording data Tripping contexts Out-of-sync context b b b b b b b b b b b b b b b b b b (1) (1) b (1) (1) b (1) (1) b

Miscellaneous
Identication of Sepam b b b b b b

Peer-to-peer data
Protection related
Zone Sequence Interlocking (ZSI) Inter-tripping Fast load-shedding b b b b

User-dened
Logipam contacts * To or from the Sepam series 80, series 40 and series 20 units, depending on the case. (1) Depending on the modelling of the IEC 61850 logic nodes.

36

Communication

Available Sepam Data Description

Data Transmitted from Sepam to the Supervisor


Metering and Diagnosis
The values measured by Sepam that may be remotely accessed are divided into the following categories: b measurements: currents, voltages, frequency, power, temperatures, etc. b energy: calculated or pulse-type energy counters b network diagnosis: phase displacement, tripping currents, unbalance ratio, etc. b machine diagnosis: temperature rise, motor starting time, remaining operating time before overload tripping, waiting time after tripping, etc. b switchgear diagnosis: cumulative breaking current, operating time and number of operations, circuit breaker charging time, etc. b Sepam diagnosis: partial or major fault, etc. b Logipam SFT2885 counters.

Remote Indications
The logic-state information that may be remote accessed is divided into the following categories: b alarms and internal status conditions b status of logic inputs b status of logic outputs b status of nine LEDs on the front panel of Sepam b status of logic-equation output bits. Alarms and internal status conditions The alarms and internal status conditions are remote indications (TS) pre-assigned to protection and control functions. Remote indications depend on the type of Sepam application and can be re-assigned by Logipam. The remote indications that can be accessed via the communication link include: b all protection-function alarms b monitoring-function alarms: CT or VT fault, control fault b Sepam status data: v Sepam not reset v remote setting blocked, remote-control commands blocked b status data on the following functions: v recloser: in service / blocked, reclosing in progress / successful, permanent trip v disturbance recording: records blocked / stored.

Data Transmitted from the Supervisor to Sepam


Pulse-type remote-control commands
Pulse-type remote-control commands (TC) may be carried out in two modes (selected by parameter setting): b direct mode b conrmed SBO (select before operate) mode. Remote-control commands are reassigned to metering, protection and control functions and depend on the type of Sepam. They are used for the following, in particular: b to control breaking device opening and closing b to reset Sepam and initialize maximum demand measurements b to select the active group of settings by enabling group A or B b to block or enable the following functions: recloser, thermal overload protection, disturbance recording. Remote-control commands can be re-assigned by Logipam.

Remote-control security
Transmission of Sepam series 80 remote controls and settings over a Modbus S-LAN can be password protected.

37

Communication

Available Sepam Data Description


IEC 61850 logical nodes

1
Nodes
L: system logical nodes
LPHD LLN0 PDIF PDOP PDUP PFRC PHIZ PMRI PMSS PSDE PTOC PTOF PTOV PTRC PTTR PTUC PTUV PTUF PVOC PVPH PZSU RBRF RREC RSYN CSWI GGIO MHAI MMTR MMXU MSQI MSTA XCBR ZCAP Physical device information Logical node zero Differential Directional overpower Directional underpower Rate of change of frequency Ground detector Motor restart blocking Motor starting time supervision Sensitive directional ground fault Time overcurrent Overfrequency Overvoltage Protection trip conditioning Thermal overload Undercurrent Undervoltage Underfrequency Voltage controlled time overcurrent Volts per Hz Zero speed or underspeed Breaker failure Autoreclosing Synchronism-check or synchronizing Switch controller Generic process I/O Harmonics or interharmonics Metering Measurement Sequence and imbalance Metering statistics Circuit breaker Capacitor bank

Sepam supports IEC 61850 logical nodes as indicated in the following table. Note that the actual instantiation of each logical node depends on the application.

Sepam Series 20
Bus
b b

Sepam Series 20
Others
b b

Sepam Series 40
b b

Sepam Series 80
b b b

P: logical nodes for protection functions


b b b b b b b b b b b b b b b b b b b b b b b b b b b b b b b b b b b b b b b b b b b b b b b b b b b b b b b b b b b b b b b b b b b b b b b b b b b b b

R: logical nodes for protection related functions

C: logical nodes for control GG: logical nodes for generic references M : logical nodes for metering and measurement

X: logical nodes for switchgear Z: logical nodes for further power system equipment b

38

Communication

Available Sepam Data Description


IEC 61850 GOOSE messages
GOOSE messages allows peer-to-peer communication between protection devices in a standardized way. Sepam series 80 with ACE850 communication module supports GOOSE messages for: b improved system protection: v Zone Sequence Interlocking (ZSI) v inter-tripping b improved system control: v user-dened Logipam contacts. High level of performance and security of these messages is ensured by: b use of ber optic data link b use of IEC 61850 compatible managed Ethernet switches b selection of a fault-tolerant communication architecture

Time-Stamping
Time-stamped events
The time-stamping function assigns a date and precise time to status changes (events) so that they can be accurately organized over time. Sepam systematically time-stamps the following events: b status changes of all logic inputs b status changes of all remote indications (TS - alarms and internal status conditions). Each event is time-stamped to within one millisecond. The number of stacks of time-stamped events managed by Sepam on each communication port and the volume of each stack in terms of the numbers of events depend on the communication protocol used. Modbus RTU DNP3
Number of event stacks for each Sepam communication port Number of events per stack 2 1

IEC 60870-5-103 IEC 61850


1 Depending on conguration Depending on conguration

64

100

100

Whatever the communication protocol used, Modbus RTU, DNP3, IEC 60870-5-103 or IEC 61850 events may be used by a remote monitoring and control system for data logging and histories, for example.

Unsolicited events
Using the DNP3 and IEC 61850 protocols, Sepam can spontaneously transmit timestamped events to the supervisor. The transmission of unsolicited events must be activated during setup.

Time-setting and synchronization


The Sepam internal clock manages the date and time. Time-setting is possible: b via the Sepam display b using the SFT2841 software b via the communication link. To ensure long-term time stability or to coordinate a number of devices, Sepam units can be synchronized: b by an external pulse to a dedicated logic input b via the communication link.

39

Communication

Available Sepam Data Description


Remote Setting

Sepam parameter and protection settings


The following remote-setting functions are available: b selection of the protection-setting group b reading of general parameters b reading of protection settings (remote reading) b writing of protection settings (remote setting). The writing of protection settings may be blocked by parameter setting.

S-LAN and E-LAN networks


The availability of remote-setting functions over the S-LAN depends on the communication protocol used. All remote-setting functions are available over the E-LAN using the SFT2841 software.

Other Data Accessible via Special Functions


Network diagnosis
The network diagnostic information recorded in les by Sepam can also be transmitted over the communication link: b disturbance-recording records in COMTRADE format b tripping contexts b Out-of-sync context.

Identication of Sepam
The identication function enables the supervisor to clearly identify the device connected to the S-LAN, based on the following elements of information: b manufacturer identication b Sepam type. This function is available for all Sepam relays, whatever the protocol used.

40

Sepam Series 20 Sepam Series 40

Sepam Series 20 and Sepam Series 40

Sepam Series 20 - Sepam Series 40


Selection Table Sepam Series 20 Selection Table Sepam Series 40 Sensor Inputs General Settings Metering and Diagnosis
Description Characteristics

42
42 43 44 45 46
46 49

Protection
Description Main Characteristics Setting Ranges

50
50 54 55

Control and Monitoring


Description Description of Predened Functions Adaptation of Predened Functions Using the SFT2841 Software

58
58 59 61

Characteristics
Base Unit
Presentation Dimensions Description Technical Characteristics Environmental Characteristics

62
62
62 65 66 68 69

Connection Diagrams
Base Unit
Sepam Series 20 Sepam Series 40 Other Phase Current Input Connection Schemes Other Residual Current Input Connection Schemes

70
70
70 71 72 73

Voltage Inputs
Sepam Series 20 Sepam Series 40

75
75 76

41

Sepam Series 20 Sepam Series 40

Selection Table Sepam Series 20

Substation

Transformer

Motor

Bus

Protection
Phase overcurrent Ground fault / Sensitive ground fault Breaker failure Negative sequence / unbalance Thermal overload Phase undercurrent Excessive starting time, locked rotor Starts per hour Positive sequence undervoltage Remanent undervoltage Line-to-line undervoltage Line-to-neutral undervoltage Line-to-line overvoltage Neutral voltage displacement Overfrequency Underfrequency Rate of change of frequency Recloser (4 shots) Thermostat / Buchholz Temperature monitoring (8 RTDs)

ANSI code
50/51 50N/51N 50G/51G 50BF 46 49RMS 37 48/51LR/14 66 27D/47 27R 27 27S 59 59N 81H 81L 81R 79 26/63 38/49T

S20
4 4

S23
4 4 1 1

T20
4 4

T23
4 4 1 1 2

M20
4 4

B21 (3)

B22

1 2

1 2 1 1 1 2 1 2 1 2 2 1 2 2 1 2 1 2 2 1 2 1

v v v v v b b v b b b b b v v b b b b b b b v b b b b b b b b b b b b

Metering
Phase current Ia, Ib, Ic RMS, residual current Ir Demand current Ia, Ib, Ic, maximum demand current Iamax, Ibmax, Icmax Voltage Vab, Vbc, Vca, Van, Vbn, Vcn, residual voltage Vr Positive sequence voltage V1 / rotation direction Frequency Temperature b b b b b b

Network and machine diagnosis


Tripping current TripIa, TripIb, TripIc, TripIr Unbalance ratio / negative sequence current I2 Disturbance recording Thermal capacity used Remaining operating time before overload tripping Waiting time after overload tripping Running hours counter / operating time Starting current and time Start block time Number of starts before blocking b b b b b b b b b b b b b

Switchgear diagnosis
Cumulative breaking current Trip circuit supervision Number of operations, operating time, charging time b v v v b v b b
(2)

b v v v b v b b
(2)

b v v v b v b b
(2)

b v v v b v b b
(2)

b v v v b v b (2) b

Control and monitoring


Circuit breaker / contactor control (1) Latching / acknowledgement Zone Sequence Interlocking (ZSI) Switching of groups of settings Annunciation

ANSI code
94/69 86 68 30 v b v b

Additional modules
8 temperature sensor inputs - MET1482 module v v v 1 low level analog output - MSA141 module v v v v v v Logic inputs/outputs v v v v v v MES114/MES114E/MES114F (10I/4O) module Communication interface v v v v v v ACE9492, ACE959, ACE937, ACE969TP or ACE969FO b standard v according to parameter setting and MES114/MES114E/MES114F or MET1482 input/output module options. (1) For NO or NC trip contacts. (2) Exclusive choice between Zone Sequence Interlocking (ZSI) and switching from one 2-relay group of settings to another 2-relay group. (3) Performs Sepam B20 functions. (4) the digits in the matrix to the right of the ANSI code indicate the number of units available for each protection function. v v v

42

Sepam Series 20 Sepam Series 40

Selection Table Sepam Series 40


Substation Transformer Motor Generator

Protection
Phase overcurrent Voltage-restrained overcurrent Ground fault / Sensitive ground fault Breaker failure Negative sequence / unbalance Directional phase overcurrent Directional ground fault Directional active overpower Directional reactive overpower Thermal overload Phase undercurrent Excessive starting time, locked rotor Starts per hour Positive sequence undervoltage Remanent undervoltage Undervoltage (3) Overvoltage (3) Neutral voltage displacement Negative sequence overvoltage Overfrequency Underfrequency Recloser (4 shots) Temperature monitoring (8 or 16 RTDs) Thermostat / Buchholz

ANSI code
50/51 50V/51V 50N/51N 50G/51G 50BF 46 67 67N/67NC 32P 32Q/40 49RMS 37 48/51LR/14 66 27D 27R 27/27S 59 59N 47 81H 81L 79 38/49T 26/63

S40
4 4 1 2

S41
4 4 1 2 2 1

S42
4 4 1 2 2 2 1

T40
4 4 1 2

T42
4 4 1 2 2 2

M41
4 4 1 2 2 1 1 2 1 1 1 2 1 2 2 2 1 2 4 v

G40
4 1 4 1 2

1 1 2

2 2 2 1 2 4 v

2 2 2 1 2 4 v

2 2 2 1 2 4 v

2 2 2 1 2 4 v v

2 2 2 1 2 4 v v b b b b b b b v v b b b b b b b b b

2 2 2 1 2 4 v

Metering
Phase current Ia, Ib, Ic RMS, residual current Ir Demand current Ia, Ib, Ic, maximum demand current Iamax, Ibmax, Icmax Voltage Vab, Vbc, Vca, Van, Vbn, Vcn, residual voltage Vr Positive sequence voltage V1 / rotation direction Negative sequence voltage V2 Frequency Active, reactive and apparent power P, Q, S Maximum demand power Pmax, Qmax, power factor Calculated active and reactive energy (W.h, var.h) Active and reactive energy by pulse counting (W.h, .varh) Temperature b b b b b b b v b b b b b b b v b b b b b b b v b b b b b b b v v b b b b b b b b b b b b b b b b v v b b b b b b b b b b b b v v b b b v b b b v v v v b b b b b b b v v b b b b b b b b b

Network and machine diagnosis


Tripping context Tripping current TripIa, TripIb, TripIc, TripIr Unbalance ratio / negative sequence current I2 Phase displacement 0, a, b, c Disturbance recording Thermal capacity used Remaining operating time before overload tripping Waiting time after overload tripping Running hours counter / operating time Starting current and time Start block time, number of starts before blocking b b b b b b b b b b b b b b b

Switchgear diagnosis
Cumulative breaking current Trip circuit supervision Number of operations, operating time, charging time CT / VT supervision b v v b b b v b b b b v v b b b v b b b b v v b b b v b b b b v v b b b v b b b v v v v b v v b b b v b b b v v v v b v v b b b v b b b v v v v

60FL

Control and monitoring


Circuit breaker / contactor control (1) Latching / acknowledgement Zone Sequence Interlocking (ZSI) Switching of groups of settings Annunciation Logic equation editor

ANSI code
94/69 86 68 30

8 temperature sensor inputs - MET1482 module (2) 1 low level analog output - MSA141 module Logic inputs/outputs MES114/MES114E/MES114F (10I/4O) module Communication interface ACE9492, ACE959, ACE937, ACE969TP, ACE969FO or ECI850

Additional modules

v v v

v v v

v v v

b standard v according to parameter setting and MES114/MES114E/MES114F or MET1482 input/output module options. (1) For NO or NC trip contacts. (2) 2 modules possible. (3) Exclusive choice, line-to-neutral voltage or line-to-line voltage for each of the 2 relays. (4) the digits in the matrix to the right of the ANSI code indicate the number of units available for each protection function.

43

Sepam Series 20 Sepam Series 40

Sensor Inputs

DE51809

Each Sepam series 20 or Sepam series 40 has analog inputs that are connected to the measurement sensors required for the application.

Sepam Series 20 Sensor Inputs


NO

Sepam T20

IN INr Ir

S20, S23
Phase current inputs Residual current input Phase voltage inputs Residual voltage input Temperature inputs (on MET1482 module) 3 1 0 0 0

T20, T23, M20 B21, B22


3 1 0 0 8 0 0 3 1 0

IB

Sepam T20 sensor inputs.

DE51810

NO

VLnP VLnS

Sepam Series 40 Sensor Inputs


Sepam M41

IN INr Ir

S40, S41, S42


Phase current inputs Residual current input Phase voltage inputs Residual voltage input Temperature inputs (on MET1482 module) 3 1 2 1 0 3 0

T40, T42, M41, G40


3 1 2 1 2x8

3 0

IB

Sepam M41 sensor inputs.

44

Sepam Series 20 Sepam Series 40

General Settings

The general settings dene the characteristics of the measurement sensors connected to Sepam and determine the performance of the metering and protection functions used. They are accessed via the SFT2841 setting software General Characteristics, CT-VT Sensors and Particular characteristics tabs.

General settings
IN IB INr Rated phase current (sensor primary current) Base current, according to rated power of equipment Rated residual current

Selection
2 or 3 CT 1 A / 5 A 3 LPCTs

Sepam Series 20
1 A to 6250 A 25 A to 3150 A (1) 0.4 to 1.3 IN See IN rated phase current 2 A or 20 A rating 1 A to 6250 A -

Sepam Series 40
1 A to 6250 A 25 A to 3150 A (1) 0.4 to 1.3 IN See IN rated phase current 2 A, 5 A or 20 A rating 1 A to 6250 A (INr = IN) 1 A to 6250 A (INr = IN/10)

Sum of 3-phase currents CSH120 or CSH200 zero sequence CT 1 A/5 A CT + CSH30 interposing ring CT 1 A/5 A CT + CSH30 interposing ring CT Sensitivity x10 Zero sequence CT + ACE990 (the zero sequence CT ratio 1/n must be such that 50 y n y 1500)

According to current monitored and use of ACE990

According to current monitored and use of ACE990

VLLp VLLs

Rated primary line-to-line voltage (VLnp: rated primary line-to-neutral voltage VLnp = VLLp/3) Rated secondary line-to-line voltage

220 V to 250 kV

220 V to 250 kV

3 VTs: Van, Vbn, Vcn 2 VTs: Vab, Vbc 1 VT: Van

VLLsr

Secondary zero sequence voltage relative to primary zero sequence voltage VLLnp/3 Rated frequency Demand interval (for demand current and maximum demand current and power) Pulse-type accumulated energy meter

100, 110, 115, 120, 200, 230 V 100, 110, 115, 120 V 100, 110, 115, 120 V VLLns/3 or VLLns/3 50 Hz or 60 Hz 5, 10, 15, 30, 60 min

100, 110, 115, 120, 200, 230 V 100, 110, 115, 120 V 100, 110, 115, 120 V VLLns/3 or VLLns/3 50 Hz or 60 Hz 5, 10, 15, 30, 60 min 0.1 kW.h to 5 MW.h 0.1 kvar.h to 5 Mvar.h

Increments active energy Increments reactive energy

(1) IN values for LPCT, in Amps: 25, 50, 100, 125, 133, 200, 250, 320, 400, 500, 630, 666, 1000, 1600, 2000, 3150.

45

Sepam Series 20 Sepam Series 40

Metering and Diagnosis Description


Metering
Sepam is a precision metering unit. All the metering and diagnosis data used for commissioning and required for the operation and maintenance of your equipment are available locally or remotely, expressed in the units concerned (A, V, W, etc.).

Phase current
RMS current for each phase, taking into account harmonics up to number 13. Different types of sensors may be used to meter phase current: b 1 A or 5 A current transformers b LPCT type current sensors.

Residual current
Two residual current values are available depending on the type of Sepam and sensors connected to it: b residual currents Ir, calculated by the vector sum of the 3-phase currents b measured residual current Ir. Different types of sensors may be used to measure residual current: b CSH120 or CSH200 specic zero sequence CT b conventional 1 A or 5 A current transformer b any zero sequence CT with an ACE990 interface.

Demand current and maximum demand currents


Demand current and maximum demand currents are calculated according to the 3-phase currents Ia, Ib and Ic: b demand current is calculated over an adjustable period of 5 to 60 minutes b maximum demand current is the greatest demand current and indicates the current drawn by maximum loads. Maximum demand currents may be cleared.

Voltage and frequency


The following measurements are available according to the voltage sensors connected: b line-to-neutral voltages Van, Vbn, Vcn b line-to-line voltages Vab, Vbc, Vca b residual voltage Vr b positive sequence voltage V1 and negative sequence voltage V2 b frequency f.

Power
Powers are calculated according to the phase currents Ia, Ib and Ic: b active power b reactive power b apparent power b power factor (pf). Power calculation is based on the 2 wattmeter method. The 2 wattmeter method is only accurate when there is no residual current and it is not applicable if the neutral is distributed.

Maximum demand powers


The greatest demand active and reactive power values calculated over the same period as the demand current. The maximum demand powers may be cleared.

Energy
b 4 accumulated energies calculated according to voltages and phase currents measured: active energy and reactive energy in both directions b 1 to 4 additional accumulated energy meters for the acquisition of active or reactive energy pulses from external meters.

Temperature
Accurate measurement of temperature inside equipment tted with Pt100, Ni100 or Ni120 type RTDs, connected to the optional remote MET1482 module.

46

Sepam Series 20 Sepam Series 40

Metering and Diagnosis Description


Network Diagnosis Assistance
Sepam provides network power quality metering functions, and all the data on network disturbances detected by Sepam are recorded for analysis purposes.

Machine Diagnosis Assistance


Sepam assists facility managers by providing: b data on the operation of their machines b predictive data to optimize process management b useful data to facilitate protection function setting and implementation.

Tripping context
Storage of tripping currents and Ir, I2, Vab, Vbc, Vca, Vr, V2, V1, f, P and Q values when tripping occurs. The values for the last ve trips are stored.

Thermal capacity used


Equivalent temperature buildup in the machine, calculated by the thermal overload protection function. Displayed as a percentage of rated thermal capacity.

Tripping current
Storage of the 3-phase currents and ground fault current at the time of the last Sepam trip command, to indicate fault current. The values are stored in the tripping contexts.

Negative sequence / unbalance


Negative sequence component of phase currents Ia, Ib and Ic, indicating the degree of unbalance in the power supplied to the protected equipment.

Remaining operating time before overload tripping


Predictive data calculated by the thermal overload protection function. The time is used by facility managers to optimize process management in real time by deciding to: b interrupt according to procedures b continue operation with blocking of thermal protection on overloaded machine.

Phase displacement
b phase displacement a, b, c between phase currents l1, l2, l3 and voltages Van, Vbn, Vcn respectively b phase displacement r between residual current and residual voltage.

Disturbance recording
Recording triggered by user-set events: b all sampled values of measured currents and voltages b status of all logic inputs and outputs b logic data: instantaneous, etc. Characteristics
Number of recordings in COMTRADE format Total duration of a recording

Waiting time after overload tripping


Predictive data calculated by the thermal overload protection function. Waiting time to avoid further tripping of thermal overload protection by premature re-energizing of insufciently cooled down equipment.

Sepam Series 20
2 86 periods (1.72 s at 50 Hz, 1.43 s at 60 Hz) 12 Adjustable from 0 to 86 periods b currents or voltages b logic inputs b pick up b logic output O1.

Sepam Series 40
Adjustable from 1 to 19 Adjustable from 1 to 10 s. The total of all the records plus one must not be more than 20 s at 50 Hz and 16 s at 60 Hz 12 Adjustable from 0 to 99 periods b currents and voltages b logic inputs b pick up b logic outputs O1 to O4.

Running hours counter / operating time


Equipment is considered to be running whenever a phase current is over 0.1 IB. Cumulative operating time is given in hours.

Motor starting / overload current and time


A motor is considered to be starting or overloaded when a phase current is over 1.2 IB. For each start / overload, Sepam stores: b maximum current drawn by the motor b starting / overload time. The values are stored until the next start / overload operation.

Number of samples per period Duration of recording before occurrence of the event Recorded data

Number of starts before blocking/start block time


Indicates the number of starts still allowed by the starts per hour protection function. If the number is zero, it indicates only one start is allowed.

47

Sepam Series 20 Sepam Series 40

Metering and Diagnosis Description


Switchgear Diagnosis Assistance

Sepam Self-Diagnosis

Sepam includes a number of self-tests carried out in the base unit and optional modules. The purpose of the self-tests is to: b detect internal failures that may cause nuisance tripping or failed fault tripping b put Sepam in fail-safe position to avoid any unwanted operation b alert the facility manager of the need for maintenance operations.

Switchgear diagnosis data give facility managers information on: b mechanical condition of breaking device b Sepam auxiliaries and assist them for preventive and curative switchgear maintenance actions. The data are to be compared to switchgear manufacturer data.

ANSI 60/60FL - CT/VT supervision


Used to monitor the entire metering chain: b CT and VT sensors b connection b Sepam analog inputs. Monitoring includes: b consistency checking of currents and voltages measured b acquisition of phase or residual voltage transformer protection fuse blown contacts. In the event of a loss of current or voltage measurement data, the assigned protection functions may be blocked to avoid nuisance tripping.

Internal failure
Two categories of internal failures are monitored: b major failures: Sepam shutdown (to fail-safe position). The protection functions are blocked, the output relays are forced to drop out and the Watchdog output indicates Sepam shutdown b minor failures: downgraded Sepam operation. Sepams main functions are operational and equipment protection is ensured.

ANSI 74 - Trip circuit supervision


To determine the health of the trip circuit, Sepam monitors: b shunt trip coil connection b matching of breaking device open/closed position contacts b execution of breaking device open and close commands. The trip circuit is only supervised when connected as shown below.

Detection of plugged connectors


The system checks that the current or voltage sensors are plugged in. A missing connector is a major failure.

Conguration checking
The system checks that the optional modules congured are present and working correctly. The absence or failure of a remote module is a minor failure, the absence or failure of a logic input/output module is a major failure.

DE51812

DE51813

NO

NO

Connection for shunt trip coil monitoring.

Connection for undervoltage trip coil monitoring.

Cumulative breaking current


Six cumulative currents are proposed to assess the pole condition of the breaking device: b total cumulative breaking current b cumulative breaking current between 0 and 2 IN b cumulative breaking current between 2 IN and 5 IN b cumulative breaking current between 5 IN and 10 IN b cumulative breaking current between 10 IN and 40 IN b cumulative breaking current > 40 IN. Each time the breaking device opens, the breaking current is added to the cumulative total and to the appropriate range of cumulative breaking current. Cumulative breaking current is given in (kA).

Number of operations
Cumulative number of opening operations performed by the breaking device.

Circuit breaker operating time and charging time


Used to assess the condition of the operating mechanism of the breaking device.

48

Sepam Series 20 Sepam Series 40

Metering and Diagnosis Characteristics


Measurement Range Accuracy (1) Sepam Series 20
1 % 1 % 1 % 1 % 1 % 1 % 1 % 1 % 5 % 0.05 Hz 1 C from +20 to +140 C 1 F from +68 to +284 F

Functions
Metering
Phase current Residual current Calculated Measured

Accuracy (1) Sepam Series 40


0.5 % 1 % 1 % 0.5 % 0.5 % 0.5 % 0.5 % 1 % 2 % 2 % 0.02 Hz 1 % 1 % 1 % 1 % 1 % 1 % 1 % 1 digit 1 % 1 digit 1 C from +20 to +140 C 1 F from +68 to +284 F

MSA141

Saving

Demand current Maximum demand current Line-to-line voltage Line-to-neutral voltage Residual voltage Positive sequence voltage Negative sequence voltage Frequency Sepam series 20 Frequency Sepam series 40 Active power Reactive power Apparent power Maximum demand active power Maximum demand reactive power Power factor Calculated active energy Calculated reactive energy Temperature

0.1 to 40IN(3) 0.1 to 40 IN 0.1 to 20 INr 0.1 to 40 IN 0.1 to 40 IN 0.05 to 1.2 VLLp 0.05 to 1.2 VLnp 0.015 to 3 VLnp 0.05 to 1.2 VLnp 0.05 to 1,2 VLnp 50 5 Hz or 60 5 Hz 25 to 65 Hz 0.015 Sn(2) to 999 MW 0.015 Sn(2) to 999 Mvar 0.015 Sn(2) to 999 MVA 0.015 Sn(2) to 999 MW 0.015 Sn(2) to 999 Mvar -1 to +1 (CAP/IND) 0 to 2.1.108 MW.h 0 to 2.1.108 Mvar.h -30 to +200 C or -22 to +392 F

b b b v b b

b b b b b v v v v b v v v

Network diagnosis assistance


Tripping context Phase tripping current Ground fault tripping current Negative sequence / unbalance Phase displacement 0 (between Vr and Ir) Phase displacement 1, 2, 3 (between V and I) 0.1 to 40 IN 0.1 to 20 INr 10 to 500 % of IB 0 to 359 0 to 359 5 % 5 % 2 % 5 % 5 % 2 % 2 2

Machine operating assistance


Thermal capacity used Remaining operating time before overload tripping Waiting time after overload tripping Running hours counter / operating time Starting current Starting time Number of starts before blocking Start block time Cooling time constant 0 to 800 % (100 % for I phase = IB) 0 to 999 min 0 to 999 min 0 to 65535 hours 1.2 IB to 24 IN 0 to 300 s 0 to 60 0 to 360 min 5 to 600 min 1 % 1 min 1 min 1 % or 0.5 h 5 % 300 ms 1 1 min 1 % 1 min 1 min 1 % or 0.5 h 5 % 300 ms 1 1 min 5 min 10 % 1 1 ms 0.5 s b v

v v v

Switchgear diagnosis assistance


Cumulative breaking current 0 to 65535 kA 10 % 1 Number of operations 0 to 4.109 Operating time 20 to 100 ms 1 ms Charging time 1 to 20 s 0.5 s b available on MSA141 analog output module, according to setup. v saved in the event of auxiliary supply outage. (1) Under reference conditions (IEC 60255-6), typical accuracy at IN or VLLp, pf > 0.8. (2) Sn: apparent power, = 3.VLLp.IN. (3) Measurement up to 0.02 IN for information purpose. v v v v

49

Sepam Series 20 Sepam Series 40

Protection Description

Current Protection Functions

ANSI 50/51 - Phase overcurrent


Line-to-line short-circuit protection, sensitive to the highest phase current measured. Characteristics b 2 groups of settings b instantaneous or time-delayed tripping b denite time (DT) or IDMT curve (choice of 16 standardized IDMT curves) b with or without timer hold With Sepam series 40, tripping can be conrmed or unconrmed, according to parameter setting: b unconrmed tripping: standard b tripping conrmed by negative sequence overvoltage protection (ANSI 47, unit 1), as backup for distant 2-phase short-circuits b tripping conrmed by undervoltage protection (ANSI 27, unit 1), as backup for line-to-line shortcircuits in networks with low short-circuit power.

ANSI 46 - Negative sequence / unbalance


Protection against phase unbalance, detected by the measurement of negative sequence current: b sensitive protection to detect 2-phase faults at the ends of long lines b protection of equipment against temperature build-up, caused by an unbalanced power supply, phase inversion or loss of phase, and against phase current unbalance. Characteristics b Sepam series 20: v 1 denite time (DT) curve v 1 specic Schneider IDMT curve. b Sepam series 40: v 1 denite time (DT) curve v 7 IDMT curves: 3 IEC curves, 3 IEEE curves and 1 specic Schneider curve.

ANSI 49RMS - Thermal overload


Protection against thermal damage caused by overloads on machines (transformers, motors or generators). The thermal capacity used is calculated according to a mathematical model which takes into account: b current RMS values b ambient temperature b negative sequence current, a cause of motor rotor temperature rise. The thermal capacity used calculations may be used to calculate predictive data for process control assistance. The protection may be blocked by a logic input when required by process control conditions. Characteristics b 2 groups of settings b 1 adjustable alarm set point b 1 adjustable tripping set point b adjustable initial thermal capacity used setting, to adapt protection characteristics to t manufacturers thermal withstand curves b equipment heating and cooling time constants. With Sepam series 40, the cooling time constant may be calculated automatically based on measurement of the equipment temperature by a sensor.

ANSI 50N/51N or 50G/51G - Ground fault


Ground fault protection based on measured or calculated residual current values: b ANSI 50N/51N: residual current calculated or measured by 3-phase current sensors b ANSI 50G/51G: residual current measured directly by a specic sensor. Characteristics b 2 groups of settings b Denite time (DT) or IDMT curve (choice of 16 standardized IDMT curves) b with or without timer hold b second harmonic restraint to ensure stability during transformer energizing, activated by parameter setting.

ANSI 50BF - Breaker failure


If a breaker fails to be triggered by a tripping command, as detected by the non-extinction of the fault current, this backup protection sends a tripping command to the upstream or adjacent breakers.

Recloser
ANSI 79
Automation device used to limit down time after tripping due to transient or semipermanent faults on overhead lines. The recloser automatically recloses the breaking device after the insulation restoring time delay. Recloser operation is easy to adapt for different operating modes by parameter setting. Characteristics b 1 to 4 reclosing shots, each shot has an adjustable dead time; and adjustable independent reclaim time and blocking time until recloser ready b shot activation linked to instantaneous or time-delayed short-circuit protection function (ANSI 50/51, 50N/51N, 67, 67N/67NC) outputs by parameter setting b blocking/lockout of recloser by logic input.

50

Sepam Series 20 Sepam Series 40

Protection Description

Directional Current Protection


ANSI 67 - Directional phase overcurrent
Line-to-line short-circuit protection, with selective tripping according to fault current direction. It comprises a phase overcurrent function associated with direction detection, and picks up if the phase overcurrent function in the chosen direction (line or bus) is activated for at least one of the 3 phases. Characteristics b 2 groups of settings b instantaneous or time-delayed tripping b choice of tripping direction b denite time (DT) or IDMT curve (choice of 16 standardized IDMT curves) b with voltage memory to make the protection insensitive to loss of polarization voltage at the time of the fault b with or without timer hold.

ANSI 67N/67NC - Directional ground fault


Ground fault protection, with selective tripping according to fault current direction. 3 types of operation: b type 1: the protection function uses the projection of the Ir vector b type 2: the protection function uses the Ir vector magnitude with half-plane tripping zone b type 3: the protection function uses the Ir vector magnitude with angular sector tripping zone ANSI 67N/67NC type 1 Directional ground fault protection for impedance, isolated or compensated neutral systems, based on the projection of measured residual current. Type 1 characteristics b 2 groups of settings b instantaneous or time-delayed tripping b denite time (DT) curve b choice of tripping direction b characteristic projection angle b no timer hold b with voltage memory to make the protection insensitive to recurrent faults in compensated neutral systems. ANSI 67N/67NC type 2 Directional overcurrent protection for impedance and solidly grounded systems, based on measured or calculated residual current. It comprises a ground fault function associated with direction detection, and picks up if the ground fault function in the chosen direction (line or bus) is activated. Type 2 characteristics b 2 groups of settings b instantaneous or time-delayed tripping b denite time (DT) or IDMT curve (choice of 16 standardized IDMT curves) b choice of tripping direction b with or without timer hold.
Tripping characteristic of ANSI 67N/67NC type 2 protection (characteristic angle r 0).
DE52062

Tripping characteristic of ANSI 67N/67NC type 1 protection (characteristic angle r 0).

DE52063

ANSI 67N/67NC type 3 Directional overcurrent protection for distribution networks in which the neutral grounding system varies according to the operating mode, based on measured residual current. It comprises a ground fault function associated with direction detection (angular sector tripping zone dened by 2 adjustable angles), and picks up if the ground fault function in the chosen direction (line or bus) is activated. This protection function complies with the Enel DK5600 specication. Type 3 characteristics b 2 groups of settings b instantaneous or time-delayed tripping b denite time (DT) curve b choice of tripping direction b no timer hold

DE52064

Tripping characteristic of ANSI 67N/67NC type 3 protection.

51

Sepam Series 20 Sepam Series 40

Protection Description

Directional Power Protection Functions


ANSI 32P - Directional active overpower
Two-way protection based on calculated active power, for the following applications: b active overpower protection to detect overloads and allow load shedding b reverse active power protection: v against generators running like motors when the generators consume active power v against motors running like generators when the motors supply active power.

Machine Protection Functions


ANSI 37 - Phase undercurrent
Protection of pumps against the consequences of a loss of priming by the detection of motor no-load operation. It is sensitive to a minimum of current in phase 1, remains stable during breaker tripping and may be blocked by a logic input.

ANSI 48/51LR/14 - Locked rotor / excessive starting time


Protection of motors against overheating caused by: b excessive motor starting time due to overloads (e.g. conveyor) or insufcient supply voltage. The reacceleration of a motor that is not shut down, indicated by a logic input, may be considered as starting. b locked rotor due to motor load (e.g. crusher): v in normal operation, after a normal start v directly upon starting, before the detection of excessive starting time, with detection of locked rotor by a zero speed detector connected to a logic input, or by the underspeed function.

ANSI 32Q/40 - Directional reactive overpower


Two-way protection based on calculated reactive power to detect eld loss on synchronous machines: b reactive overpower protection for motors which consume more reactive power with eld loss b reverse reactive overpower protection for generators which consume reactive power with eld loss.

ANSI 66 - Starts per hour


Protection against motor overheating caused by: b too frequent starts: motor energizing is blocked when the maximum allowable number of starts is reached, after counting of: v starts per hour (or adjustable period) v consecutive motor hot or cold starts (reacceleration of a motor that is not shut down, indicated by a logic input, may be counted as a start) b starts too close together in time: motor re-energizing after a shutdown is only allowed after an adjustable waiting time.

ANSI 50V/51V - Voltage-restrained overcurrent


Line-to-line short-circuit protection for generators. The current tripping set point is voltage-adjusted in order to be sensitive to faults close to the generator which cause voltage drops and lowers the short-circuit current. Characteristics b instantaneous or time-delayed tripping b denite time (DT) or IDMT curve (choice of 16 standardized IDMT curves) b with or without timer hold.

ANSI 26/63 - Thermostat/Buchholz


Protection of transformers against temperature rise and internal faults via logic inputs linked to devices integrated in the transformer.

ANSI 38/49T - Temperature monitoring


Protection that detects abnormal temperature build-up by measuring the temperature inside equipment tted with sensors: b transformer: protection of primary and secondary windings b motor and generator: protection of stator windings and bearings. Characteristics b Sepam series 20: 8 Pt100, NI100 or Ni120 type RTDs b Sepam series 40: 16 Pt100, NI100 or Ni120 type RTDs b 2 adjustable independent set points for each RTD (alarm and trip).

52

Sepam Series 20 Sepam Series 40

Protection Description

Voltage Protection Functions


ANSI 27D - Positive sequence undervoltage
Protection of motors against faulty operation due to insufcient or unbalanced network voltage, and detection of reverse rotation direction.

Frequency Protection Functions


ANSI 81H - Overfrequency
Detection of abnormally high frequency compared to the rated frequency, to monitor power supply quality.

ANSI 81L - Underfrequency


Detection of abnormally low frequency compared to the rated frequency, to monitor power supply quality. The protection may be used for overall tripping or load shedding. Protection stability is ensured in the event of the loss of the main source and presence of remanent voltage by a continuous decrease of the frequency, which is activated by parameter setting.

ANSI 27R - Remanent undervoltage


Protection used to check that remanent voltage sustained by rotating machines has been cleared before allowing the bus supplying the machines to be reenergized, to avoid electrical and mechanical transients.

ANSI 81R - Rate of change of frequency


Protection function used for fast disconnection of a generator or load shedding control. Based on the calculation of the frequency variation, it is insensitive to transient voltage disturbances and therefore more stable than a phase-shift protection function. Disconnection In installations with autonomous production means connected to a utility, the rate of change of frequency protection function is used to detect loss of the main system in view of opening the incoming circuit breaker to: b protect the generators from a reconnection without checking synchronization b avoid supplying loads outside the installation. Load shedding The rate of change of frequency protection function is used for load shedding in combination with the underfrequency protection to: b either accelerate shedding in the event of a large overload b or block shedding following a sudden drop in frequency due to a problem that should not be solved by shedding.

ANSI 27 - Undervoltage
Protection of motors against voltage sags or detection of abnormally low network voltage to trigger automatic load shedding or source transfer. Works with line-to-line voltage (Sepam series 20 and Sepam series 40) or lineto-neutral voltage (Sepam series 40 only), each voltage being monitored separately.

ANSI 59 - Overvoltage
Detection of abnormally high network voltage or checking for sufcient voltage to enable source transfer. Works with line-to-line or line-to-neutral voltage, each voltage being monitored separately.

ANSI 59N - Neutral voltage displacement


Detection of insulation faults by measuring residual voltage in isolated neutral systems.

ANSI 47 - Negative sequence overvoltage


Protection against phase unbalance resulting from phase inversion, unbalanced supply or distant fault, detected by the measurement of negative sequence voltage.

53

Sepam Series 20 Sepam Series 40

Protection Main Characteristics

Current IDMT Tripping Curves


Multiple IDMT tripping curves are offered, to cover most applications: b IEC curves (SIT, VIT/LTI, EIT) b IEEE curves (MI, VI, EI) b usual curves (UIT, RI, IAC). The curve equations are given page 94.

Setting of IDMT Tripping Curves, Time Delay T or TMS Factor


The time delays of current IDMT tripping curves (except for customized and RI curves) may be set as follows: b time T, operating time at 10 x Is b TMS factor, factor shown as T/ (see curve equation page 94).

Timer Hold
The adjustable timer hold T1 is used for: b detection of restriking faults (DT curve) b coordination with electromechanical relays (IDMT curve). Timer hold may be blocked if necessary.
DE50275

2 Groups of Settings
Line-to-line and line-to-ground short-circuit protection
Each unit has 2 groups of settings, A and B, to adapt the settings to suit the network conguration. The active group of settings (A or B) is set by a logic input or the communication link. Example of use: normal / backup mode network b group A for network protection in normal mode, when the network is supplied by the utility b group B for network protection in backup mode, when the network is supplied by a backup generator.
Detection of restriking faults with adjustable timer hold.

Thermal overload for machines


Each unit has 2 groups of settings to protect equipment that has two operating modes. Examples of use: b transformers: switching of groups of settings by logic input, according to transformer ventilation operating mode, natural or forced ventilation (ONAN or ONAF) b motors: switching of groups of settings according to current set point, to take into account the thermal withstand of motors with locked rotors.

Summary Table
Characteristics
2 groups of settings A and B 2 groups of settings, operating modes 1 and 2 IEC IDMT curves IEEE IDMT curves Usual IDMT curves Timer hold

Protection Functions
50/51, 50N/51N, 67, 67N/67NC 49RMS Machine 50/51, 50N/51N, 50V/51V, 67, 67N/67NC type 2, 46 50/51, 50N/51N, 50V/51V, 67, 67N/67NC type 2, 46 50/51, 50N/51N, 50V/51V, 67, 67N/67NC type 2 50/51, 50N/51N, 50V/51V, 67, 67N/67NC type 2

54

Sepam Series 20 Sepam Series 40

Protection Setting Ranges

Functions

Settings
5 to 100 % of VLLp

Time Delays
0.05 s to 300 s 0.05 s to 300 s 0.05 s to 300 s 0.05 s to 300 s 0.1 s to 300 s 0.1 s to 300 s 0.05 s to 300 s

ANSI 27 - Line-to-line undervoltage ANSI 27D/47 - Positive sequence undervoltage


15 to 60 % of VLLp

ANSI 27R - Remanent undervoltage


5 to 100 % of VLLp

ANSI 27S - Line-to-neutral undervoltage


5 to 100 % of VLnp

ANSI 32P - Directional active overpower


1 to 120 % of Sn (3)

ANSI 32Q/40 - Directional reactive overpower


5 to 120 % of Sn (3)

ANSI 37 - Phase undercurrent


0.15 to 1 IB

ANSI 38/49T - Temperature monitoring (8 or 16 RTDs)


Alarm and trip set points Denite time IDMT Tripping curve 0 to 180 C (or 32 to 356 F) 0.1 to 5 IB 0.1 to 0.5 IB (Schneider Electric) 0.1 to 1 IB (IEC, IEEE) Schneider Electric IEC: SIT/A, LTI/B, VIT/B, EIT/C (2) IEEE: MI (D), VI (E), EI (F) (2) 1 to 50 % of VLLp 0.1 s to 300 s 0.1 s to 1 s

ANSI 46 - Negative sequence / unbalance

ANSI 47 - Negative sequence overvoltage


0.05 s to 300 s ST starting time LT and LTS time delays 0.5 s to 300 s 0.05 s to 300 s

ANSI 48/51LR/14 - Excessive starting time, locked rotor


0.5 IB to 5 IB

ANSI 49RMS - Thermal overload


Accounting for negative sequence component Time constant Heating Cooling Alarm and tripping set points Cold curve modication factor Switching of thermal settings conditions Maximum equipment temperature

Rate 1 and Rate 2


0 - 2,25 - 4,5 - 9 Sepam series 20 T1: 1 to 120 min Sepam series 40 T1: 1 to 600 min Sepam series 20 T2: 1 to 600 min Sepam series 40 T2: 5 to 600 min 50 to 300 % of rated thermal capacity 0 to 100 % By logic input By Is set point adjustable from 0.25 to 8 IB 60 to 200 C (140 F to 392 F) Timer hold DT DT DT DT or IDMT DT or IDMT DT or IDMT Denite time IDMT

ANSI 50/51 - Phase overcurrent


Tripping curve Tripping time delay Denite time SIT, LTI, VIT, EIT, UIT (1) RI IEC: SIT/A, LTI/B, VIT/B, EIT/C IEEE: MI (D), VI (E), EI (F) IAC: I, VI, EI 0.1 to 24 IN 0.1 to 2.4 IN Denite time (DT ; timer hold) IDMT (IDMT ; reset time) None By negative sequence overvoltage By line-to-line undervoltage 0.2 to 2 IN 0.05 s to 300 s

Is set point Timer hold Conrmation (2)

Inst ; 0.05 s to 300 s 0.1 s to 12.5 s at 10 Is Inst ; 0.05 s to 300 s 0.5 s to 20 s

ANSI 50BF - Breaker failure


Presence of current Operating time (1) Tripping as of 1.2 Is. (2) Sepam series 40 only. (3) Sn = 3.IN.VLLp.

55

Sepam Series 20 Sepam Series 40

Protection Setting Ranges

Functions
Tripping curve

Settings
Tripping time delay Denite time SIT, LTI, VIT, EIT, UIT (1) RI IEC: SIT/A, LTI/B, VIT/B, EIT/C IEEE: MI (D), VI (E), EI (F) IAC: I, VI, EI 0.1 to 15 INr 0.1 to 1 INr Denite time (DT ; timer hold) IDMT (IDMT ; reset time) Tripping time delay Denite time SIT, LTI, VIT, EIT, UIT (1) RI IEC: SIT/A, LTI/B, VIT/B, EIT/C IEEE: MI (D), VI (E), EI (F) IAC: I, VI, EI 0.5 to 24 IN 0.5 to 2,4 IN Denite time (DT ; timer hold) IDMT (IDMT ; reset time) Timer hold DT DT DT DT or IDMT DT or IDMT DT or IDMT Denite time IDMT

Time Delays

ANSI 50N/51N or 50G/51G - Ground fault / Sensitive ground fault

Is r set point Timer hold

Inst ; 0.05 s to 300 s 0.1 s to 12.5 s at 10 Is0 Inst ; 0.05 s to 300 s 0.5 s to 20 s

ANSI 50V/51V - Voltage-restrained overcurrent


Tripping curve Timer hold DT DT DT DT or IDMT DT or IDMT DT or IDMT Denite time IDMT

Is set point Timer hold

Inst ; 0.05 s to 300 s 0.1 s to 12.5 s at 10 Is Inst ; 0.05 s to 300 s 0.5 s to 20 s 0.05 s to 300 s 0.05 s to 300 s

ANSI 59 - Overvoltage

Line-to-line
50 to 150 % of VLLp

Line-to-neutral (2)
50 to 150 % of VLnp

ANSI 59N - Neutral voltage displacement


2 to 80 % of VLLp

ANSI 66 - Starts per hour


Starts per period Consecutive starts 1 to 60 1 to 60 Tripping time delay Denite time SIT, LTI, VIT, EIT, UIT (1) RI IEC: SIT/A, LTI/B, VIT/B, EIT/C IEEE: MI (D), VI (E), EI (F) IAC: I, VI, EI 0.1 to 24 IN 0.1 to 2,4 IN Denite time (DT ; timer hold) IDMT (IDMT ; reset time) 30, 45, 60 Period Time between starts Timer hold DT DT DT DT or IDMT DT or IDMT DT or IDMT Denite time IDMT 1 to 6 hr 0 to 90 min

ANSI 67 - Directional phase overcurrent


Tripping curve

Is set point Timer hold Characteristic angle (1) Tripping as of 1.2 Is. (2) Sepam series 40 only.

Inst ; 0.05 s to 300 s 0.1 s to 12.5 s at 10 Is Inst ; 0.05 s to 300 s 0.5 s to 20 s

56

Sepam Series 20 Sepam Series 40

Protection Setting Ranges

Functions
Characteristic angle Isr set point Vsr set point Memory time

Settings
-45, 0, 15, 30, 45, 60, 90 0.1 to 15 INr 2 to 80 % of Un T0mem time Vrmem validity set point -45, 0, 15, 30, 45, 60, 90 Tripping time delay Denite time SIT, LTI, VIT, EIT, UIT (1) RI IEC: SIT/A, LTI/B, VIT/B, EIT/C IEEE: MI (D), VI (E), EI (F) IAC: I, VI, EI 0.5 to 15 INr 0.5 to 1 INr 2 to 80 % of VLLp Denite time (DT ; timer hold) IDMT (IDMT ; reset time) 0 to 359 0 to 359 0.1 A to 30 A 0.05 to 15 INr (min. 0.1 A) 0.05 to 15 INr (min. 0.1 A) Calculated Vr (sum of 3 voltages) Measured Vr (external VT) 50 to 53 Hz or 60 to 63 Hz 50 to 55 Hz or 60 to 65 Hz 45 to 50 Hz or 55 to 60 Hz 40 to 50 Hz or 50 to 60 Hz 0.1 to 10 Hz/s 2 to 80 % of VLLp 0.6 to 80 % of VLLp Denite time 0 ; 0.05 s to 300 s 0 ; 2 to 80 % of VLLp

Time Delays
Inst ; 0.05 s to 300 s

ANSI 67N/67NC type 1 - Directional ground fault, according to Ir projection

ANSI 67N/67NC type 2 - Directional ground fault, according to Ir magnitude with half-plan tripping zone
Characteristic angle Tripping curve Timer hold DT DT DT DT or IDMT DT or IDMT DT or IDMT Denite time IDMT

Isr set point Vsr set point Timer hold

Inst ; 0.05 s to 300 s 0.1 s to 12.5 s at 10 Is0 Inst ; 0.05 s to 300 s 0.5 s to 20 s

ANSI 67N/67NC type 3 - Directional ground fault, according to Ir magnitude with angular sector tripping zone
Angle at start of tripping zone Angle at end of tripping zone Isr set point CSH zero sequence CT (2 A rating) 1 A CT (sensitive, INr = 0.1 CT IN) Zero sequence CT + ACE990 (range 1) Vsr set point

Denite time

Inst ; 0.05 to 300 s

ANSI 81H - Overfrequency


Sepam series 20 Sepam series 40 0.1 s to 300 s 0.1 s to 300 s 0.1 s to 300 s 0.1 s to 300 s Inst ; 0.15 s to 300 s

ANSI 81L - Underfrequency


Sepam series 20 Sepam series 40

ANSI 81R - Rate of change of frequency


(1) Tripping as of 1.2 Is.

57

Sepam Series 20 Sepam Series 40

Control and Monitoring Description


Sepam performs all the control and monitoring functions required for electrical network operation: b the main control and monitoring functions are predened and t the most frequent cases of use. They are ready to use and are implemented by simple parameter setting after the necessary logic inputs / outputs are assigned. b the predened control and monitoring functions can be adapted for particular needs using the SFT2841 software, which offers the following customization options: v customization of the control matrix by changing the assignment of output relays, LEDs, and annunciation messages v logic equation editor, to adapt and complete the predened control and monitoring functions (Sepam series 40 only) v creation of personalized messages for local annunciation (Sepam series 40 only).

Operating principle
The processing of each control and monitoring function may be broken down into 3 phases: b acquisition of input data: v results of protection function processing v external logic data, connected to the logic inputs of an optional MES114 input / output module v remote control commands (TC) received via the Modbus communication link b actual processing of the control and monitoring function b utilization of the processing results: v activation of output relays to control a device v information sent to the facility manager: - by message and/or LED on the Sepam display and SFT2841 software - by remote indication (TS) via the Modbus communication link.

DE52789

Logic inputs and outputs


The number of Sepam inputs / outputs must be adapted to t the control and monitoring functions used. The 4 outputs included in the Sepam base unit (series 20 or series 40) may be extended by adding one MES114 module with 10 logic inputs and 4 output relays. After selecting the MES114 type required by an application, the logic inputs must be assigned to functions. The functions are chosen from a list which covers the whole range of possible uses. The functions are adapted to meet needs within the limits of the logic inputs available. The inputs may also be inverted for undervoltage type operation. A default input / output assignment is proposed for the most frequent uses.

58

Sepam Series 20 Sepam Series 40

Control and Monitoring Description of Predened Functions


Each Sepam contains the appropriate predened control and monitoring functions for the chosen application.

ANSI 94/69 - Circuit Breaker/Contactor Control


Control of interrupting devices equipped with different types of closing and tripping coils: b circuit breakers with NO or NC trip contacts b latching contactors with NO contacts The function processes all interrupting device closing and tripping conditions, based on: b protection functions b interrupting device status data b remote control commands b specic control functions for each application (e.g. recloser). The function also blocks interrupting device closing, according to the operating conditions. With Sepam series 20, it is necessary to use an MES114 module in order to have all the required logic inputs.

ANSI 86 - Latching / acknowledgement


The tripping outputs for all the protection functions and all the logic inputs can be latched individually. The latched information is saved in the event of an auxiliary power outage. (The logic outputs cannot be latched.) All the latched data may be acknowledged: reset key b locally, with the b remotely via a logic input b or via the communication link. The Latching/acknowledgement function, when combined with the circuit breaker/ contactor control function, can be used to create the ANSI 86 Lockout relay function.

ANSI 68 - Zone Selective Interlocking (ZSI)


This function provides: b perfect tripping coordination with line-to-line and line-to-ground short-circuits, on all types of networks b faster tripping of the breakers closest to the fault (solving the drawback of conventional time coordination). Each Sepam is capable of: b sending a blocking input when a fault is detected by the phase overcurrent and ground fault protection functions, which may or may not be directional (ANSI 50/51, 50N/51N, 67 or 67N/67NC) b and receiving blocking inputs which block protection tripping. A control logic ensures continued operation of the protection in the event that a blocking link malfunctions or is lost.

Output relay testing


Each output relay is activated for 5 seconds, to make it simpler to check output connections and connected switchgear operation.

59

Sepam Series 20 Sepam Series 40

Control and Monitoring Description of Predened Functions

PE50287

ANSI 30 - Local annunciation


LED indication on the Sepam front panel b 2 LEDs indicate the unit operating status: v green LED ON: Sepam on v red key LED: Sepam unavailable (initialization phase or detection of an internal failure) b 9 yellow LEDs: v pre-assigned and identied by standard removable labels v the SFT2841 software tool may be used to assign LEDs and personalize labels. Local annunciation on Sepams advanced UMI Events and alarms may be indicated locally on Sepams advanced UMI by: b messages on the display unit, available in 2 languages: v English, factory-set messages, not modiable v local language, according to the version delivered (the language version is chosen when Sepam is set up) b the lighting up of one of the 9 yellow LEDs, according to the LED assignment, which is set using SFT2841. Alarm processing b when an alarm appears, the related message replaces the current display and the related LED goes on. The number and type of messages depend on the type of Sepam. The messages are linked to Sepam functions and may be viewed on the front-panel display and in the SFT2841 Alarms screen. b to clear the message from the display, press the b after the fault has disappeared, press the reset pressing the
clear reset clear

Local indications on the Sepam front panel.

key

key: the light goes off and Sepam is key) and may be cleared by

b the list of alarm messages remains accessible ( key.

60

Sepam Series 20 Sepam Series 40

Control and Monitoring Adaptation of Predened Functions Using the SFT2841 Software
The predened control and monitoring functions can be adapted for particular needs using the SFT2841 software, which offers the following customization options: b customization of the control matrix by changing the assignment of output relays, LEDs and annunciation messages b logic equation editor, to adapt and complete the predened control and monitoring functions (Sepam series 40 only) b creation of personalized messages for local annunciation (Sepam series 40 only).

Control matrix
The control matrix is a simple way to assign data from: b protection functions b control and monitoring functions b logic inputs b logic equations to the following output data: b output relays b 9 LEDs on the front panel of Sepam b messages for local annunciation b triggering of disturbance recording.
PE50133

SFT2841: control matrix.

Logic equation editor (Sepam series 40)


The logic equation editor included in the SFT2841 software can be used to: b complete protection function processing: v additional interlocking v conditional blocking/validation of functions etc. b adapt predened control functions: particular circuit breaker or recloser control sequences, etc. A logic equation is created by grouping logic input data received from: b protection functions b logic inputs b remote control commands using the Boolean operators AND, OR, XOR, NOT, and automation functions such as time delays, bi-stables and time programmer. Equation input is assisted and syntax checking is done systematically. The result of an equation may then be: b assigned to a logic output, LED or message via the control matrix b transmitted by the communication link, as a new remote indication b utilized by the circuit breaker/contactor control function to trip, close or block interrupting device closing b used to block or reset a protection function.

Personalized alarm and operating messages (Sepam series 40)


The alarm and operating messages may be personalized using the SFT2841 software tool. The new messages are added to the list of existing messages and may be assigned via the control matrix for display: b on the Sepam display b in the SFT2841 Alarms and Alarm History screens.

61

Characteristics Sepam Series 20 Sepam Series 40


Base units are dened according to the following characteristics: b type of User-Machine Interface (UMI) b working language b type of base unit connector b type of current sensor connector.
PE50492

Base Unit Presentation

User-Machine Interface
Two types of User-Machine Interfaces (UMI) are available for Sepam base units (series 20 or series 40): b advanced UMI b basic UMI. The advanced UMI can be integrated in the base unit or installed remotely on the cubicle. Integrated and remote advanced UMIs offer the same functions. A Sepam (series 20 or series 40) with a remote advanced UMI is made up of : b a base unit with basic UMI, for mounting inside the LV compartment b a remote advanced UMI (DSM303) v for ush mounting on the front panel of the cubicle in the location most suitable for the facility manager v for connection to the Sepam base unit using a prefabricated CCA77x cord. The characteristics of the remote advanced UMI module (DSM303) are presented in the DSM303 section of Chapter 4.

Advanced UMI
Comprehensive data for facility managers All the data required for local equipment operation may be displayed on demand: b display of all measurement and diagnosis data in numerical format with units and/or in bar graphs b display of operating and alarm messages, with alarm acknowledgment and Sepam resetting b display and setting of all the Sepam parameters b display and setting of all the parameters of each protection function b display of Sepam and remote module versions b output testing and logic input status display b entry of 2 passwords to protect parameter and protection settings. Ergonomic data presentation b keypad keys identied by pictograms for intuitive navigation b menu-guided access to data. b graphical LCD screen to display any character or symbol b excellent display quality under all lighting conditions: automatic contrast setting and backlit screen (user activated).

Sepam base unit (series 20 or series 40) with integrated advanced UMI.

PE50493

Basic UMI
A Sepam with basic UMI offers an economical solution suited to installations that do not require local operation (managed by a remote monitoring and control system) or to replace electromechanical or analog electronic protections units with no additional operating needs. The basic UMI includes: b 2 signal lamps indicating Sepam operating status: b 9 parameterizable yellow signal lamps equipped with a standard label reset button for clearing faults and resetting. b

Working language
Sepam base unit (series 20 or series 40) with basic UMI.

All the texts and messages displayed on the advanced UMI are available in 2 languages: b English (IEC), the default working language b and a second language, which may be v French v Spanish v U.S. English (ANSI) v another local language. Please contact us regarding local language customization.

PE50127

Setting and operating software


SFT2841 setting and operating software can be used for easy setting of Sepam parameters and protection functions. A PC containing the SFT2841 software is connected to the communication port on the front of the unit.

Customized advanced UMI.

62

Characteristics Sepam Series 20 Sepam Series 40

Base Unit Presentation

Selection Guide
Base Unit With Basic UMI With Integrated Advanced UMI
PE50466 PE50467

With Remote Advanced UMI

Functions
Local indication Metering and diagnosis data Alarms and operating messages Sepam parameter setting Protection setting Version of Sepam and remote modules Status of logic inputs Local control Alarm acknowledgement Sepam reset Output testing b b b b b b b b b b b b b b b b b b b b

Characteristics
Screen Size Automatic contrast setting Backlit screen Keypad Number of keys LEDs Sepam operating status 128 x 64 pixels b b 1 2 LEDs on front 9 2 LEDs on front 128 x 64 pixels b b 9 b base unit: 2 LEDs on front b remote advanced UMI: 2 LEDs on front 9 LEDs on remote advanced UMI b base unit with basic UMI, mounted at the back of the compartment using the AMT840 mounting plate b DSM303 remote advanced UMI module ,ush mounted on the front of the cubicle and connected to the base unit with the CCA77x prefabricated cord

Indication LEDs

PE50493

9 LEDs on front Flush mounted on front of cubicle

9 LEDs on front Flush mounted on front of cubicle

Mounting

63

Characteristics Sepam Series 20 Sepam Series 40

Base Unit Presentation

Hardware Characteristics
Auxiliary power supply
Sepam series 20 and Sepam series 40 can be supplied by either of the following voltages: b 24 to 250 V DC b 110 to 240 V AC.

Four relay outputs


The 4 relay outputs O1 to O4 on the base unit must be connected to connector A . Each output can be assigned to a predetermined function using the SFT2841 software. O1, O2 and O3 are 3 control outputs with one NO contact. O1 and O2 are used by default for the switchgear control function: b O1: switchgear tripping b O2: switchgear closing blocked. O4 is an indication output with one NO contact and one NC contact. It is used by default for the watchdog function.

Main connector A
A choice of 2 types of removable, screw-lockable 20-pin connectors: b CCA620 screw-type connector b CCA622 ring lug connector.

Phase current input connector


Current sensors connected to removable, screw-lockable connectors according to type of sensors used: b CCA630 or CCA634 connector for 1 A or 5 A current transformers or b CCA670 connector for LPCT sensors. The presence of these connectors is monitored.

Voltage input connector


Sepam B21 and B22 Voltage sensors connected to the removable, screw-lockable CCT640 connector. The presence of the CCT640 connector is monitored. Sepam Series 40 Voltage sensors connected to the 6-pin connector E . A choice of 2 types of removable, screw-lockable 6-pin connectors: b CCA626 screw-type connector or b CCA627 ring lug connector. The presence of the E connector is monitored.

PE50468

Mounting Accessories
AMT840 mounting plate
It is used to mount a Sepam with basic UMI inside the compartment with access to connectors on the rear panel. Mounting used with remote advanced UMI module (DSM303).

AMT852 lead sealing accessory


The AMT852 lead sealing accessory can be used to prevent unauthorized modication of the settings of Sepam series 20 and Sepam series 40 units with integrated advanced UMIs. The accessory includes: b a lead-sealable cover plate b the screws required to secure the cover plate to the integrated advanced UMI of the Sepam unit.
Note: the AMT852 lead sealing accessory can secured only to the integrated advanced UMIs of Sepam series 20 and Sepam series 40 units with serial numbers higher than 0440000. Sepam unit with integrated advanced UMI and lead sealing accessory AMT852.

64

Characteristics Sepam Series 20 Sepam Series 40

Base Unit Dimensions

DE80030

in. (mm)

Dimensions
DE52847 DE52756

in. (mm) 1.57 (40)

in. (mm)

6.30 (160) 2.05 (52) 3.86 (98)

8.74 (222)

7.72 (196)

8.74 (222)

6.93 (176)

1.22 (31)

6.93 (176)
Front view of Sepam.
1.57 (40) 1.57 (40) 3.86 (98) 1.22 (31)

Sepam with advanced UMI and MES114, ush-mounted in front panel. (1) With basic UMI: 23 mm (0.91 in).

Sepam with advanced UMI and MES114, ush-mounted in front panel.

Clearance for Sepam assembly and wiring.

Cut-Out
Cut-out accuracy must be complied with to ensure proper t. For mounting plate between 1.5 mm (0.059 in) and 3 mm (0.12 in) thick
DE80028 DE80044

For mounting plate 3.17 mm (0.125 inch) thick


in. (mm)

in. (mm)

7.95 0.2 (202 0.2)

7.95 0.2 (202 0.2) 2.91 (74) 0.47 (12)

0.26 (6.5)
DE52759

in. (mm)

1.57 (40) 1.57 (40) 7.95 (202) 1.57 (40) 1.57 (40) 1.57 (40) 9.06 (230)

6.38 0.2 (162 0.2)

6.38 0.2 (162 0.2)

0.08 (2)

Assembly with AMT840 Mounting Plate


Used to mount Sepam with basic UMI at the back of the compartment with access to the connectors on the rear panel. Mounting associated with the use of the remote advanced UMI (DSM303).
DE52756

6.38 (162)

8.50 (216) 9.29 (236)

0.39 (10)

0.59 (15)

in. (mm)

6.30 (160) 2.05 (52) 3.86 (98)

AMT840 mounting plate.


6.93 (176) 1.22 (31)

Sepam with basic UMI and MES114, mounted with AMT840 plate. Mounting plate thickness: 2 mm (0.079 in).

65

Characteristics Sepam Series 20 Sepam Series 40

Base Unit Description

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15

Green LED: Sepam on. Red LED: Sepam unavailable. 9 yellow indication LEDs. Label identifying the indication LEDs. Graphical LCD screen. Display of measurements. Display of switchgear, network and machine diagnosis data. Display of alarm messages. Sepam reset (or conrm data entry). Acknowledgement and clearing of alarms (or move cursor up). LED test (or move cursor down). Access to protection settings. Access to Sepam parameter setting. Entry of 2 passwords. PC connection port.

Front Panel with Advanced UMI


DE51817

The , , keys (9, 10, 11) are used to browse through the menus and to scroll through and accept the values displayed.
SEPAM
DIGITAL RELAY

1 2 3 4 5 6

Green LED: Sepam on. Red LED: Sepam unavailable. 9 yellow indication LEDs. Label identifying the indication LEDs. Acknowledgement / clearing of alarms and Sepam reset. PC connection port.

Front Panel with Basic UMI


DE51818

SEPAM
DIGITAL RELAY

66

Characteristics Sepam Series 20 Sepam Series 40

Base Unit Description

Base unit. b auxiliary power supply b 4 relay outputs b 1 residual current input (used only with CCA630 CT connector).
B b Sepam S20, S23, T20, T23, M20:
DE51819

Rear Panel - Sepam Series 20

A 20-pin connector for:

connector for 3-phase current Ia, Ib, Ic inputs and residual current b Sepam B21 and B22: connector for 3-phase voltage Van, Vbn, Vcn inputs and 1 residual voltage Vr input.
C Communication port. D Remote module connection port.

2 3 4

Connector for MES114 input/output module. 2 mounting clips. 2 locating nibs in ush-mounted position.

Rear Panel - Sepam Series 40


1 Base unit. b auxiliary power supply b 4 relay outputs b 1 residual current input (used only with CCA630 CT connector).
B b Sepam S20, S23, T20, T23, M20:
DE51820

A 20-pin connector for:

connector for 3-phase current Ia, Ib, Ic inputs and residual current b Sepam B21 and B22: connector for 3-phase voltage Van, Vbn, Vcn inputs and 1 residual voltage Vr input.
C Communication port. D Remote module connection port. E 6-pin connector for 3-phase voltage Van, Vbn, Vcn

inputs. 2 3 4 Connector for MES114 input/output module. 2 mounting clips. 2 locating nibs in ush-mounted position.

67

Characteristics Sepam Series 20 Sepam Series 40


Weight
Sepam series 20

Base Unit Technical Characteristics


Minimum weight (base unit with basic UMI and without MES114) Maximum weight (base unit with advanced UMI and MES114) Minimum weight (base unit with basic UMI and without MES114) Maximum weight (base unit with advanced UMI and MES114) Input impedance Consumption Rated thermal withstand 1-second overload Input impedance Input voltage Rated thermal withstand 1-second overload Pt 100 None 4 mA 1 km (0.62 mi) 1.2 kg (2.6 lb) 1.7 kg (3.7 lb) 1.4 kg (3.1 lb) 1.9 kg (4.2 lb) < 0.02 W < 0.02 VA at 1 A < 0.5 VA at 5 A 4 IN 100 IN > 100 kW 100 to 230/3 V 240 V 480 V Ni 100 / 120 None 4 mA

Sepam series 40

Analog Inputs
Current transformer 1 A or 5 A CT (with CCA630 or CCA634) 1 A to 6250 A ratings

Voltage transformer 220 V to 250 kV ratings

Temperature Sensor Input (MET1482 module)


Type of sensor Isolation from ground Current injected in sensor Maximum distance between sensor and module

Logic Inputs
Voltage Range Frequency Typical consumption Typical switching threshold Input limit voltage

MES114
24 to 250 V DC 19.2 to 275 V DC 3 mA 14 V DC u 19 V DC y 6 V DC Enhanced

MES114E
110 to 125 V DC 88 to 150 V DC 3 mA 82 V DC u 88 V DC y 75 V DC Enhanced 110 V AC 88 to 132 V AC 47 to 63 Hz 3 mA 58 V AC u 88 V AC y 22 V AC Enhanced

MES114F
220 to 250 V DC 176 to 275 V DC 3 mA 154 V DC u 176 V DC y 137 V DC Enhanced 220 to 240 V AC 176 to 264 V AC 47 to 63 Hz 3 mA 120 V AC u 176 V AC y 48 V AC Enhanced

At state 1 At state 0 Isolation of inputs in relation to other isolated groups

Relays Outputs
Control relay outputs (O1, O2, O3, O11 contacts) (2)

Voltage Continuous current Breaking capacity

DC AC (47.5 to 63 Hz) Resistive load L/R load < 20 ms L/R load < 40 ms Resistive load pf load > 0.3

Making capacity Isolation of outputs in relation to other isolated groups Voltage Continuous current Breaking capacity DC AC (47.5 to 63 Hz)

24 / 48 V DC 8A 8 / 4A 6 / 2A 4 / 1A < 15 A for 200 ms Enhanced 24 / 48 V DC 2A 2 / 1A Enhanced

127 V DC 8A 0.7 A 0.5 A 0.2 A -

220 V DC 8A 0.3 A 0.2 A 0.1 A -

100 to 240 V AC 8A

8A 5A

Annunciation relay output (O4, O12, O13, O14 contacts)


127 V DC 2A 0.5 A 220 V DC 2A 0.15 A 100 to 240 V AC 2A 1A

L/R load < 20 ms pf load > 0.3 Isolation of outputs in relation to other isolated groups

Power Supply
Voltage Range Deactivated consumption (1) Maximum consumption (1) Inrush current Acceptable momentary outages 24 / 250 V DC -20 % +10 % < 4.5 W <6W <8W < 11 W < 10 A for 10 ms, < 28 A for 100 s 10 ms 10 ms 110 / 240 V AC -20 % +10 % (47.5 to 63 Hz) < 6 VA < 6 VA < 15 VA < 25 VA < 15 A for rst half-period 10 ms 10 ms

Sepam series 20 Sepam series 40 Sepam series 20 Sepam series 40 Sepam series 20, series 40 Sepam series 20 Sepam series 40

Analog Output (MSA141 module)


Current 4 - 20 mA, 0 - 20 mA, 0 - 10 mA Load impedance < 600 W (wiring included) Accuracy 0.50 % (1) According to conguration. (2) Relay outputs comply with clause 6.7 of standard C37.90 (30 A, 200 ms, 2000 operations).

68

Characteristics Sepam Series 20 Sepam Series 40


Electromagnetic Compatibility
Disturbing eld emission Conducted disturbance emission
Immunity tests Radiated disturbances Emission tests

Base Unit Environmental Characteristics


Standard
IEC 60255-25 EN 55022 IEC 60255-25 EN 55022 IEC 60255-22-3 IEC 61000-4-3 ANSI C37.90.2 (1995) IEC 60255-22-2 ANSI C37.90.3 IEC 61000-4-8 IEC 60255-22-6 IEC 60255-22-4 IEC 61000-4-4 ANSI C37.90.1 IEC 60255-22-1 ANSI C37.90.1 IEC 61000-4-12 IEC 61000-4-5 IEC 60255-11

Level / Class
A B

Value

2
10 V/m ; 80 MHz - 1 GHz 10 V/m ; 80 MHz - 2 GHz 35 V/m ; 25 MHz - 1 GHz 8 kV air ; 6 kV contact 8 kV air ; 4 kV contact 30 A/m (continuous) - 300 A/m (13 s) 10 V 4 kV ; 2.5 kHz / 2 kV ; 5 kHz 4 kV ; 2.5 kHz 4 kV ; 2.5 kHz 2.5 kV MC ; 1 kV MD 2.5 kV MC and MD 2.5 kV MC ; 1 kV MD 2 kV MC ; 1 kV MD Series 20: 100 %, 10 ms Series 40: 100 %, 20 ms

Immunity to radiated elds

III

Electrostatic discharge Immunity to magnetic elds at network frequency


Immunity tests Conducted disturbances

IV

Immunity to conducted RF disturbances Fast transient bursts

A or B IV III

1 MHz damped oscillating wave 100 kHz damped oscillating wave Surges Voltage interruptions

III

Mechanical Robustness
In operation

Standard
IEC 60255-21-1 IEC 60068-2-6 IEC 60255-21-2 IEC 60255-21-3 IEC 60255-21-1 IEC 60255-21-2 IEC 60255-21-2

Level / Class
2 Fc 2 2 2 2 2

Value
1 Gn ; 10 Hz - 150 Hz 2 Hz - 13.2 Hz ; a = 1 mm 10 Gn / 11 ms 2 Gn (horizontal axes) 1 Gn (vertical axes) 2 Gn ; 10 Hz - 150 Hz 30 Gn / 11 ms 20 Gn / 16 ms

Vibrations Shocks Earthquakes


De-energized

Vibrations Shocks Jolts

Climatic Withstand
In operation

Standard
IEC 60068-2-1 IEC 60068-2-2 IEC 60068-2-3 IEC 60068-2-14 IEC 60068-2-52 IEC 60068-2-60 IEC 60068-2-60

Level / Class
Series 20: Ab Series 40: Ad Series 20: Bb Series 40: Bd Ca Nb Kb/2 C

Value
-25 C (-13 F) +70 C (+158 F) 10 days ; 93 % RH ; 40 C (104 F) 25 C to +70 C (-13 F to +158 F) 5 C/min (41 F/min) 21 days ; 75 % RH ; 25 C (-13 F); 0.5 ppm H2S ; 1 ppm SO2 21 days ; 75 % RH ; 25 C ; 0.01 ppm H2S ; 0.2 ppm SO2 ; 0.02 ppm NO2; ; 0.01 ppm Cl2 -25 C (-13 F) +70 C (+158 F) 56 days ; 93 % RH ; 40 C (104 F)

Exposure to cold Exposure to dry heat Continuous exposure to damp heat Temperature variation with specied variation rate Salt mist Inuence of corrosion/gaz test 2 Inuence of corrosion/gaz test 4
In storage (3)

Exposure to cold Exposure to dry heat Continuous exposure to damp heat

IEC 60068-2-1 IEC 60068-2-2 IEC 60068-2-3

Ab Bb Ca

Safety
Enclosure safety tests

Standard
IEC 60529 NEMA IEC 60695-2-11 IEC 60255-5 IEC 60255-5 Harmonized standard: EN 50263

Level / Class
IP52 Type 12 with gasket supplied

Value
Other panels closed, except for rear panel IP20 650 C with glow wire (1562 F) 5 kV (1) 2 kV 1 min (2)

Front panel tightness

Fire withstand
Electrical safety tests

1.2/50 s pulse wave Power frequency dielectric withstand

European directives: b 89/336/CEE Electromagnetic Compatibility (EMC) Directive v 92/31/CEE Amendment v 93/68/CEE Amendment b 73/23/CEE Low Voltage Directive v 93/68/CEE Amendment UL UL508 - CSA C22.2 n 14-95 File E212533 CSA CSA C22.2 n 14-95 / n 94-M91 / n 0.17-00 File 210625 (1) Except for communication: 3 kV in common mode and 1kV in differential mode (2) Except for communication: 1 kVrms (3) Sepam must be stored in its original packing.

Certication

69

Characteristics Sepam Series 20 Sepam Series 40

Base Unit Sepam Series 20


Sepam B21 and B22
a
DE51822

Sepam S20, S23, T20, T23 and M20


DE52168

a b c

b c

CCA634

Ia Ib Ic Ir

Van Vbn Vcn Vr

(1) This type of connection allows the calculation of residual voltage.

! DANGER
HAZARD OF ELECTRIC SHOCK, ELECTRIC ARC OR BURNS b Only qualied personnel should install this equipment. Such work should be performed only after reading this entire set of instructions and checking the technical characteristics of the device b NEVER work alone. b Turn off all power supplying this equipment before working on or inside it. Consider all sources of power, including the possibility of backfeeding b Always use a properly rated voltage sensing device to conrm that all power is off b Screw tight all terminals, even those not in use Failure to follow these instructions will result in death or serious injury.

Connector

Type
Screw-type

Reference
CCA620

Wiring

6.35 mm ring lugs

CCA622

For Sepam S20, S23, T20, T23 and M20 For Sepam B21 and B22

4 mm ring lugs RJ45 plug Screw-type Green RJ45 plug Black RJ45 plug

CCA630, CCA634 for connection of 1 A or 5 A CTs CCA670, for connection of 3 LPCT sensors CCT640

b wiring with no ttings: v 1 wire with max. cross-section 0.2 to 2.5 mm (u AWG 24-12) or 2 wires with max. cross-section 0.2 to 1 mm (u AWG 24-16) v stripped length: 8 to 10 mm b wiring with ttings: v recommended wiring with Telemecanique ttings: - DZ5CE015D for 1 x 1.5 mm wire - DZ5CE025D for 1 x 2.5 mm wire - AZ5DE010D for 2 x 1 mm wires v wire length: 8.2 mm v stripped length: 8 mm b 6.35 mm ring or spade lugs (1/4 in) b maximum wire cross-section of 0.2 to 2.5 mm (u AWG 24-12) b stripped length: 6 mm b use an appropriate tool to crimp the lugs on the wires b maximum of 2 ring or spade lugs per terminal b tightening torque: 0.7 to 1 Nm b wire cross-section of 1.5 to 6 mm (AWG 16-10) b tightening torque: 1.2 Nm (13.27 IB-in) Integrated with LPCT sensor

Same as wiring for the CCA620 CCA612 CCA770: L = 0.6 m (2 ft) CCA772: L = 2 m (6.6 ft) CCA774: L = 4 m (13 ft)

70

Characteristics Sepam Series 20 Sepam Series 40

Base Unit Sepam Series 40


a
DE52169

b c

2
CCA634

Ia

Van Vbn Vcn

! DANGER
HAZARD OF ELECTRIC SHOCK, ELECTRIC ARC OR BURNS b Only qualied personnel should install this equipment. Such work should be performed only after reading this entire set of instructions and checking the technical characteristics of the device b NEVER work alone. b Turn off all power supplying this equipment before working on or inside it. Consider all sources of power, including the possibility of backfeeding b Always use a properly rated voltage sensing device to conrm that all power is off b Screw tight all terminals, even those not in use Failure to follow these instructions will result in death or serious injury.

Ib Ic Ir

(1) This type of connection allows the calculation of residual voltage. (2) Accessory for bridging terminals 3 and 5 supplied with CCA626 and CCA627 connector.

Connector

Type
Screw-type

Reference
CCA620

Wiring
b wiring with no ttings: v 1 wire with max. cross-section 0.2 to 2.5 mm (u AWG 24-12) or 2 wires with max. cross-section 0.2 to 1 mm (u AWG 24-16) v stripped length: 8 to 10 mm b wiring with ttings: v recommended wiring with Telemecanique ttings: - DZ5CE015D for 1 x 1.5 mm wire - DZ5CE025D for 1 x 2.5 mm wire - AZ5DE010D for 2 x 1 mm wires v wire length: 8.2 mm v stripped length: 8 mm b 6.35 mm ring or spade lugs (1/4 in) b maximum wire cross-section of 0.2 to 2.5 mm (u AWG 24-12) b stripped length: 6 mm b use an appropriate tool to crimp the lugs on the wires b maximum of 2 ring or spade lugs per terminal b tightening torque: 0.7 to 1 Nm b wire cross-section of 1.5 to 6 mm (AWG 16-10) b tightening torque: 1.2 Nm (13.27 IB-in) Integrated with LPCT sensor CCA612 CCA770: L = 0.6 m (2 ft) CCA772: L = 2 m (6.6 ft) CCA774: L = 4 m (13 ft) Same as wiring for the CCA620 Same as wiring for the CCA622

6.35 mm ring lugs

CCA622

4 mm ring lugs RJ45 plug Green RJ45 plug Black RJ45 plug

CCA630, CCA634, for connection of 1 A or 5 A CTs CCA670, for connection of 3 LPCT sensors

Screw-type 6.35 mm ring lugs

CCA626 CCA627

71

Characteristics Sepam Series 20 Sepam Series 40

Base Unit Other Phase Current Input Connection Schemes

2
DE80144

Variant 1: phase current measurements by 3 x 1 A or 5 A CTs (standard connection)


a b c
CCA630/ CCA634

Description Connection of 3 x 1 A or 5 A sensors to the CCA630 or CCA634 connector.


Ia Ib Ic

The measurement of the 3-phase currents allows the calculation of residual current. Parameters
Sensor type Number of CTs Rated current (IN) 5 A CT or 1 A CT Ia, Ib, Ic 1 A to 6250 A

Variant 2: phase current measurement by 2 x 1 A or 5 A CTs


a
DE80145

c
CCA630/ CCA634

Description Connection of 2 x 1 A or 5 A sensors to the CCA630 or CCA634 connector.


Ia Ib Ic

The measurement of phase currents 1 and 3 is sufcient to ensure all the phase current-based protection functions. The phase current IB is only assessed for metering functions, assuming that Ir = 0. This arrangement does not allow the calculation of residual current. Parameters
Sensor type Number of CTs Rated current (IN) 5 A CT or 1 A CT Ia, Ic 1 A to 6250 A

Variant 3: phase current measurement by 3 LPCT type sensors


a
DE51826

c
CCA670

a b c

Description Connection of 3 Low Power Current Transducer (LPCT) type sensors to the CCA670 connector. The connection of only one or two LPCT sensors is not allowed and causes Sepam to go into fail-safe position.
Ia Ib Ic

The measurement of the 3-phase currents allows the calculation of residual current. Parameters
Sensor type Number of CTs Rated current (IN) LPCT Ia, Ib, Ic 25, 50, 100, 125, 133, 200, 250, 320, 400, 500, 630, 666, 1000, 1600, 2000 or 3150 A Note: Parameter IN must be set 2 twice:

b Software parameter setting using the advanced UMI or the SFT2841 software tool b Hardware parameter setting using microswitches on the CCA670 connector

72

Characteristics Sepam Series 20 Sepam Series 40

Base Unit Other Residual Current Input Connection Schemes

Variant 1: residual current calculation by sum of 3-phase currents


Description Residual current is calculated by the vector sum of the 3-phase currents Ia, Ib and Ic, measured by 3 x 1 A or 5 A CTs or by 3 LPCT type sensors. See current input connection diagrams. Parameters
Residual current Sum of 3 Is Rated residual current INr = IN, CT primary current Measuring range 0.1 to 40 INr

Variant 2: residual current measurement by CSH120 or CSH200 zero sequence CT (standard connection)
a
DE80061

Description Arrangement recommended for the protection of isolated or compensated neutral systems, in which very low fault currents need to be detected.
Ir

Parameters
Residual current 2 A rating CSH 5 A rating CSH (Sepam series 40) 20 A rating CSH Rated residual current I Nr = 2 A INr = 5 A INr = 20 A Measuring range 0.2 to 40 A 0.5 to 100 A 2 to 400 A

Variant 3: residual current measurement by 1 A or 5 A CTs and CCA634


DE52520

Ia Ib Ic Ir

Description Residual current measurement by 1 A or 5 A CTs. b Terminal 7: 1 A CT b Terminal 8: 5 A CT Parameters


Residual current 1 A CT 1 A CT sensitive 5 A CT 5 A CT sensitive Rated residual current INr = IN, CT primary current INr = IN/10 (Sepam series 40) INr = IN, CT primary current INr = IN/10 (Sepam series 40) Measuring range 0.1 to 20 INr 0.1 to 20 INr 0.1 to 20 INr 0.1 to 20 INr

a
DE80048

c Ia Ib Ic Ir

73

Characteristics Sepam Series 20 Sepam Series 40

Base Unit Other Residual Current Input Connection Schemes


Description The CSH30 interposing ring CT is used to connect 1 A or 5 A CTs to Sepam to measure residual current: b connection of CSH30 interposing ring CT to 1 A CT: make 2 turns through CSH primary b connection of CSH30 interposing ring CT to 5 A CT: make 4 turns through CSH primary. b for Sepam series 40, the sensitivity can be multiplied by 10 using the "sensitive" setting with INr = IN/10. Parameters

DE80115

Variant 4: residual current measurement by 1 A or 5 A CTs and CSH30 interposing ring CT


a b c

turns turns

Residual current 1 A CT 1 A CT sensitive 5 A CT 5 A CT sensitive

Rated residual current INr = IN, CT primary current INr = IN/10 (Sepam series 40) INr = IN, CT primary current INr = IN/10 (Sepam series 40)

Measuring range 0.1 to 20 INr 0.1 to 20 INr 0.1 to 20 INr 0.1 to 20 INr

DE80116

c Ia Ib Ic

Ir CT 1 A : 2 turns CT 5 A : 4 turns

Variant 5: residual current measurement by zero sequence CT with ratio of 1/n (n between 50 and 1500)
a
DE51830

Ir

Description The ACE990 is used as an interface between an MV zero sequence CT with a ratio of 1/n (50 < n < 1500) and the Sepam residual current input. This arrangement allows the continued use of existing zero sequence CTs on the installation.

Parameters
Residual current Rated residual current Measuring range 0.1 to 20 INr ACE990 - range 1 INr = Ik.n(1) (0.00578 y k y 0.04) 0.1 to 20 INr ACE990 - range 2 INr = Ik.n(1) (0.0578 y k y 0.26316) (1) n = number of zero sequence CT turns k = factor to be determined according to ACE990 wiring and setting range used by Sepam

74

Characteristics Sepam Series 20 Sepam Series 40

Voltage Inputs Sepam Series 20


The phase and residual voltage transformer secondary circuits are connected to the CCT640 connector (item B ) on Sepam series 20 type B units. The CCT640 connector contains 4 transformers which perform isolation and impedance matching of the VTs and Sepam input circuits.

Variant 1: measurement of 3 line-to-neutral voltages (standard connection)


a b c

Parameters
Voltages measured by VTs Residual voltage
Van Vbn Vcn Vr

DE51831

Van, Vbn, Vcn Sum of 3Vs

Functions available
Voltages measured Values calculated Measurements available Protection functions available (according to type of Sepam) Van, Vbn, Vcn Vab, Vbc, Vca, Vr, V1, f All All

Variant 2: measurement of 3 line-to-neutral voltages and residual voltage


DE51832

a b c

Parameters
Voltages measured by VTs Residual voltage
Van Vbn Vcn Vr

Van, Vbn, Vcn External VT

Functions available
Voltages measured Values calculated Measurements available Protection functions available (according to type of Sepam) Van, Vbn, Vcn, Vr Vab, Vbc, Vca, V1, f All All

DE51833

a b c

Variant 3: measurement of 2 line-to-line voltages Parameters


Voltages measured by VTs Residual voltage
Van Vbn Vcn Vr

Vab, Vbc None

Functions available
Voltages measured Values calculated Measurements available Protection functions available (according to type of Sepam) Van, Vbn, Vcn Vca, V1, f Vab, Vbc, Vca, V1, f All except 59N, 27S

Variant 4: measurement of 1 line-to-line voltage and residual voltage


DE51834

a b c

Parameters
Voltages measured by VTs Residual voltage
Van Vbn Vcn Vr

Vab External VT

Functions available
Voltages measured Values calculated Measurements available Protection functions available (according to type of Sepam) Vab, Vr f Vab, Vr, f All except 47, 27D, 27S

Variant 5: measurement of 1 line-to-line voltage


DE51835

a b c

Parameters
Voltages measured by VTs Residual voltage
Van Vbn Vcn Vr

Vab None

Functions available
Voltages measured Values calculated Measurements available Protection functions available (according to type of Sepam) Vab f Vab, f All except 47, 27D, 59N, 27S

75

Characteristics Sepam Series 20 Sepam Series 40

Voltage Inputs Sepam Series 40


The phase and residual voltage transformer secondary circuits are connected directly to the connector marked E . The 3 impedance matching and isolation transformers are integrated in the Sepam series 40 base unit.

2
a b
DE51836

Variant 1: measurement of 3 line-to-neutral voltages (standard connection)


c

Phase voltage sensor parameter setting Residual voltage sensor parameter setting Voltages measured Values calculated
Van Vbn Vcn

3V 3V sum Van, Vbn, Vcn Vab, Vbc, Vca, Vr, V1, V2, f None None

Measurements unavailable Protection functions unavailable (according to type of Sepam)

Variant 2: measurement of 2 line-to-line voltages and residual voltage


a b
DE51837

Phase voltage sensor parameter setting Residual voltage sensor parameter setting Voltages measured Values calculated
Van Vbn Vcn

Vab, Vbc External VT Vab, Vbc, Vr Vca, Van, Vbn, Vcn, V1, V2, f None None

Measurements unavailable Protection functions unavailable (according to type of Sepam)

Variant 3: measurement of 2 line-to-line voltages


a b
DE51838

Phase voltage sensor parameter setting Residual voltage sensor parameter setting Voltages measured Values calculated
Van Vbn Vcn

Vab, Vbc None Vab, Vbc Vca, V1, V2, f Van, Vbn, Vcn, Vr 67N/67NC, 59N

Measurements unavailable Protection functions unavailable (according to type of Sepam)

Variant 4: measurement of 1 line-to-line voltage and residual voltage


a b
DE51839

Phase voltage sensor parameter setting Residual voltage sensor parameter setting Voltages measured Values calculated
Van Vbn Vcn

Vab External VT Vab, Vr f Vbc, Vca, Van, Vbn, Vcn, V1, V2 67, 47, 27D, 32P, 32Q/40, 27S

Measurements unavailable Protection functions unavailable (according to type of Sepam)

Variant 5: measurement of 1 line-to-line voltage


a b
DE51840

Phase voltage sensor parameter setting Residual voltage sensor parameter setting Voltages measured Values calculated
Van Vbn Vcn

Vab None Vab f Vbc, Vca, Van, Vbn, Vcn, Vr, V1, V2 67, 47, 27D, 32P, 32Q/40, 67N/67NC, 59N, 27S

Measurements unavailable Protection functions unavailable (according to type of Sepam)

76

Sepam Series 80

Sepam Series 80

Sepam Series 80
Selection Table

78
78

Functions
Sensor Inputs General Settings Metering and Diagnosis
Description Characteristics

80
80 81 82
82 87

Protection
Description Trip Curves Main Characteristics Setting Ranges

88
88 94 96 97

Control and Monitoring


Description Description of Predened Functions Adaptation of Predened Functions Using the SFT2841 Software Customized Functions Using Logipam

101
101 102 106 108

Characteristics
Base Unit
Presentation Description Technical Characteristics Environmental Characteristics Dimensions

109
109
109 113 115 116 117

Connection Diagrams
Base Unit
Sepam Series 80 Connection Sepam B83 Sepam C86 Phase Current Inputs Residual Current Inputs

118
118
118 119 120 121 122 123

Phase Voltage Inputs - Residual Voltage Input


Main Channels Additional Channels for Sepam B83 Additional Channel for Sepam B80 Available Functions

125
125 126 127 128

77

Sepam Series 80

Selection Table

Substation

Transformer

Motor

Generator

Bus

Cap.

Protection

ANSI Code
50/51 50N/51N 50G/51G 50BF 46 49RMS 49RMS 49RMS 51C 64REF 87T 87M 67 67N/67NC 32P 32Q 37P 37 48/51LR 66 40 78PS 12 14 50V/51V 21B 50/27 27TN/64G2 64G 24 27D 27R 27 59 59N 47 81H 81L 81R 79 26/63 38/49T 25

S80 S81 S82 S84 T81 T82 T87 M81 M87 M88 G82 G87 G88 B80 B83 C86
8 8 1 2 8 8 1 2 2 8 8 1 2 2 8 8 1 2 2 8 8 1 2 2 8 8 1 2 2 8 8 1 2 2 8 8 1 2 2 8 8 1 2 2 8 8 1 2 2 8 8 1 2 2 8 8 1 2 2 8 8 1 2 2 2 8 2 2 2 1 1 2 2 2 2 2 2 2 2 2 1 1 1 1 1 v v 1 1 1 1 1 v v 1 1 1 1 1 v v 2 2 2 2 2 2 2 2 2 2 1 2 2 1 2 2 1 2 2 2 1 2 2 1 1 2 2 2 1 2 1 8 8 1 2 8 8 1 2 8 8 1 2

Phase overcurrent (1) Ground fault/Sensitive ground fault (1) Breaker failure Negative sequence/unbalance Thermal overload for cables Thermal overload for machines (1) Thermal overload for capacitors Capacitor bank unbalance Restricted ground fault Two-winding transformer differential Machine differential Directional phase overcurrent (1) Directional ground fault (1) Directional active overpower Directional reactive overpower Directional active underpower Phase undercurrent Excessive starting time, locked rotor Starts per hour Field loss (underimpedance) Pole slip Overspeed (2 set points) (2) Underspeed (2 set points) (2) Voltage-restrained overcurrent Underimpedance Inadvertent energization Third harmonic undervoltage / 100 % stator ground fault Overexcitation (V / Hz) Positive sequence undercurrent Remanent undervoltage Undervoltage (LL or Ln) Overvoltage (LL or Ln) Neutral voltage displacement Negative sequence overvoltage Overfrequency Underfrequency Rate of change of frequency Recloser (4 shots) (2) Thermostat / Buchholz (2) Temperature monitoring (16 RTDs) (3) Synchro-check (4)

2 2 2 1

1 1 v v 2 1 1 2 2 2 2 4 4 2 2 2 4

1 1 v v 2 1 1 2 2 2 2 4 4 2 2 2 4

1 1 v v 2 1 1 2 2 2 2 4 4 2 2 2 4

2 2 4 4 2 2 2 4 v

2 2 4 4 2 2 2 4 v

2 2 4 4 2 2 2 4 v

4 2 2 4 2 2 2 4 2 v

2 2 4 4 2 2 2 4

2 2 4 4 2 2 2 4

2 2 2 4 4 2 2 2 4

2 2 4 4 2 2 2 4

2 2 4 4 2 2 2 4

2 2 4 4 2 2 2 4

4 2 2 4 2 2 2 4

4 2 2 4 2 2 2 4

4 2 2 4 2 2 2 4

v v v v v v v

v v v v v

v v v v v

v v

v v

v v v

v v v v b b v b b b b v

v v v v v b b v b b b b v v b b b b v v b b b b v v v v v v v

v v v v v Circuit breaker / contactor control 94/69 v v v v Automatic transfer (AT) (2) v Load shedding / automatic restart De-excitation Genset shutdown Capacitor step control (2) v v v Zone sequence interlocking (2) 68 v v b b b b b Latching / acknowledgement 86 b b b b b Annunciation 30 b b b b b Switching of groups of settings b b b b b Adaptation using logic equations v v v v Logipam programming (Ladder language) v The numbers indicate the number of relays available for each protection function. b standard v options. (1) Protection functions with two groups of settings. (2) According to parameter setting and optional MES120 input/output modules. (3) With optional MET1482 temperature input modules. (4) With optional MCS025 synchro-check module.

Control and Monitoring

v b

v b

v b

v v b b

v b b b b v

v b b b b v

v b b b b v

v b b b b v

v b b b b v

v b b b b v

v v b b b b v

78

Sepam Series 80

Selection Table

Substation

Transformer

Motor

Generator

Bus

Metering
Phase current Ia, Ib, Ic RMS Measured residual current Ir, calculated Ir Demand current Ia, Ib, Ic Maximum demand current Iamax, Ibmax, Icmax Measured residual current Ir Voltage Vab, Vbc, Vac, Van, Vbn, Vcn Residual voltage Vr Positive sequence voltage V1 / rotation direction Negative sequence voltage V2 Frequency Active power P, Pa, Pb, Pc Reactive power Q, Qa, Qb, Qc Apparent power S, Sa, Sb, Sc Maximum demand power Pmax, Qmax Power factor (pf) Calculated active and reactive energy (Wh, VARh) Active and reactive energy by pulse counting (2) ( Wh, VARh) Phase current Ia, Ib, Ic RMS Calculated residual current Ir Voltage Vab, Va and frequency Voltage Vab, Vbc, Vac, Van, Vbn, Vcn, Va, Vb and frequency Residual voltage Vr Temperature (16 RTDs) (3) Rotation speed (2) Neutral point voltage VLnt

S80 S81 S82 S84 T81 T82 T87 M81 M87 M88 G82 G87 G88 B80 B83
b b b b b b b b b b b b b b b b v b b b b b b b b b b b b b b b b v b b b b b b b b b b b b b b b b v b b b b b b b b b b b b b b b b v b b b b b b b b b b b b b b b b v b b b b b b b b b b b b b b b b v b b b b b b b b b b b b b b b b v b b b b b b b b b b b b b b b b b b v b b b b b b b b b b b b b b b b v b b b b b b b b b b b b b b b b b b v b b b b b b b b b b b b b b b b b b v b b b b b b b b b b b b b b b b v b b b b b b b b b b b b b b b b b b v b b b b b v v v v v b b b b b b b b b b b b b b b b v v b b b b b b b b b b b b b b b b b b b b b b v v b b b b b b b b b b b b b b b b b b b b b b v v b b b b b b b b b b b b b v v b b b b b b b b b b b b b v v b b b b b b b b b b b b b b b b b b b b b b b b b b b b b b b b b b b b b b b b b b b b b v b b b b

b b b b b b b b b b b v

Network and Machine Diagnosis


Tripping context Tripping current TripIa, TripIb, TripIc Phase fault and ground fault trip counters Unbalance ratio / negative sequence current I2 Harmonic distortion (thd), current and voltage Ithd, Vthd Phase displacement r, r, r Phase displacement a, b, c Disturbance recording Thermal capacity used Remaining operating time before overload tripping Waiting time after overload tripping Running hours counter / operating time Starting current and time Start block time Number of starts before block Unbalance ratio / negative sequence current I2 Differential current Idiffa, Idiffb, Idiffc Through current Ita, Itb, Itc Current phase displacement Apparent positive sequence impedance Z1 Apparent line-to-line impedances Zab, Zbc, Zac Third harmonic voltage, neutral point or residual Difference in amplitude, frequency and phase of voltages compared for synchro-check (4) Capacitor unbalance current and capacitance

b b b b b b b b

b b b b b b b b b b b

b b b b b b b b b b b

b b b b b b b b b b b

b b b b b b b b b b b b

b b b b b b b b b b b b

b b b b b b b b b b b b

b b v v

b b v

b b v

b b v

b b v

b b b b b b v

b b

b b b v

b b b b b b b v

b b b b b b b v

b b v

b b v

Switchgear Diagnosis

ANSI Code

CT / VT supervision 60/60FL Trip circuit supervision (2) 74 Auxiliary power supply monitoring Cumulative breaking current Number of operations, operating time, charging time, number of racking out operations (2)

b v b b v

b v b b v

b v b b v

b v b b v

b v b b v

b v b b v

b v b b v

b v b b v v v v v v

b v b b v v v v v v

b v b b v v v v v v

b v b b v v v v v v

b v b b v v v v v v

b v b b v v v v v v

b v b b v v v v v v

b v b b v v v v v v

v v v v v v v Measurement readout (4) v v v v v v v Remote indication and events time tagging(4) v v v v v v v Remote control commands (4) v v v v v v v Remote protection setting (4) v v v v v v v Disturbance recording data transfer (4) b standard v options. (2) According to parameter setting and optional MES120 input/output modules. (3) With optional MET1482 temperature input modules. (4) With optional MCS025 synchro-check module. (5) With ACE9492, ACE959, ACE937, ACE969TP, ACE969FO or ECI850 communication interface.

Modbus Communication, IEC 60 870-5-103, DNP3 or IEC 850

79

Functions Sepam Series 80

Sensor Inputs

DE50583

NO

VLLp VLLs

Sepam G88 3VLN/2VLL

IN

VLLN1 VLLN2

INr

Ir

Sepam Series 80 has analog inputs that are connected to the measurement sensors required for applications: b main analog inputs, available on all types of Sepam Series 80: v 3 phase current inputs la, lb, lc v 1 residual current input lr v 3 phase voltage inputs Van, Vbn, Vcn v 1 residual voltage input Vr b additional analog inputs, dependent on the type of Sepam: v 3 additional phase current inputs la, lb, lc v 1 additional residual current input lr v 3 additional phase voltage inputs Van, Vbn, Vcn v 1 additional residual voltage input Vr The table below lists the analog inputs available according to the type of Sepam Series 80.

IB

IN VLnp VLns VLnt INr Ir

Sepam G88 sensor inputs

S80, S81, T81, T82, T87, M87, S82, S84 M81, G82 M88, G87, G88
Phase current inputs Residual current inputs Unbalance current inputs for capacitor steps Phase voltage inputs Main channel Additional channels Main channel Additional channels Ia, Ib, lc lr lr Ia, lb, lc lr lr Ia, lb, lc la, lb, lc lr lr

B80

B83

C86

Ia, lb, lc lr lr

Ia, lb, lc lr

Ia, lb, lc lr la, lb, lc, lr

Main channel

Van, Vbn, Vcn or Vab, Vbc

Van, Vbn, Vcn or Vab, Vbc

Van, Vbn, Vcn or Vab, Vbc

Van, Vbn, Vcn or Vab, Vbc Van or Vab

Van, Vbn, Vcn or Vab, Vbc Van, Vbn, Vcn or Vab, Vbc Vr Vr

Van, Vbn, Vcn or Vab, Vbc

Additional channels Residual voltage inputs Main channel Additional channel Vr Vr Vr

Vr (1)

Vr T1 to T16

Temperature inputs T1 to T16 T1 to T16 (on MET1482 module) Note: by extension, an additional measurement (current or voltage) is a value measured via an additional analog channel. (1) Available with phase voltage Vab, Vbc.

80

Functions Sepam Series 80

General Settings

The general settings dene the characteristics of the measurement sensors that are connected to Sepam. They determine the performance of the metering and protection functions used. They are accessed via the SFT2841 setting software General Characteristics, CT-VT Sensors and Particular characteristics tabs.

General Settings
IN, IN IN IB IB INr, INr Rated phase current (sensor primary current)

Selection

Value
1 A to 6250 A 25 A to 3150 A (1) 1 A to 30 A 0.2 to 1.3 IN IB = IB x VLna/VLnb IB = IB See IN(IN) rated phase current 2 A or 20 A rating 1 A to 6250 A According to current monitored and use of ACE990 220 V to 250 kV 90 to 230 V 90 to 120 V 90 to 120 V 90 to 230 V VLns/3 or VLns/3 220 V to 250 kV 57.7 V to 133 V 50 Hz or 60 Hz 1-2-3 oru 1-3-2 5, 10, 15, 30, 60 min

VLLp, VLLp VLLs, VLLs

2 or 3 1 A / 5 A CTs 3 LPCTs Unbalance current sensor rating (capacitor application) CT 1 A / 2 A / 5 A Base current, according to rated power of equipment Base current on additional channels Applications with transformer (not adjustable) Other applications Rated residual current Sum of 3 phase currents CSH120 or CSH200 zero sequence CT 1 A/5 A CT + CSH30 interposing ring CT Zero sequence CT + ACE990 (the zero sequence CT ratio 1/n must be such that 50 y n y 1500) Rated primary line-to-line voltage (VLnp: rated primary line-to-neutral voltage VLnp = VLLp/3) Rated secondary line-to-line voltage 3 VTs: Van, Vbn, Vcn 2 VTs: Vab, Vbc 1 VT: Vab 1 VT: Van

VLLsr, VLLsr VLnp VLns fN

Secondary zero sequence voltage relative to primary zero sequence voltage VLLp/3 Neutral point voltage transformer primary voltage (generator application) Neutral point voltage transformer secondary voltage (generator application) Rated frequency Phase rotation direction Demand interval (for demand current and maximum demand current and power) Pulse-type accumulated energy meter Rated transformer power Rated winding 1 voltage (main channels: I) Rated winding 2 voltage (additional channels: I) Rated winding 1 current (not adjustable) Rated winding 2 current (not adjustable) Transformer vector shift Rated speed (motor, generator) Number of pulses per rotation (for speed acquisition) Zero speed set point Number of capacitor steps Connection of capacitor steps Capacitor step ratio

Increments active energy Increments reactive energy

P VLn1 VLn2 I N1 I N2 N R

0.1 kWh to 5 MWh 0.1 kVARh to 5 MVARh 100 kVA to 999 MVA 220 V to 220 kV 220 V to 400 kV IN1 = P/(3 VLn1) IN2 = P/(3 VLn2) 0 to 11 100 to 3600 rpm 1 to 1800 (N x R/60 y 1500) 5 to 20 % of N 1 to 4 Wye / Delta 1 1, 2 1, 2, 3, 4 1, 2, 3, 4, 6, 8

Step 1 Step 2 Step 3 Step 4 (1) IN values for LPCT, in Amps: 25, 50, 100, 125, 133, 200, 250, 320, 400, 500, 630, 666, 1000, 1600, 2000, 3150.

81

Functions Sepam Series 80

Metering and Diagnosis Description


Maximum Demand Powers
The greatest demand active and reactive power values are calculated over the same period as the demand current. The maximum demand powers may be cleared.

Metering
Sepam is a precision metering unit. All the metering and diagnosis data used for commissioning and required for the operation and maintenance of your equipment are available locally or remotely, expressed in the units concerned (A, V, W, etc.).

Energy
b Four accumulated energies are calculated by using voltages and phase currents Ia, Ib, and Ic. They are used to measure active energy and reactive energy in both directions b 1 to 4 additional accumulated energy meters can be used to acquire active or reactive energy pulses from external meters

Phase Current
RMS current for each phase, factoring harmonics up to the 13th level. Different types of sensors may be used to meter phase current: b 1 A or 5 A current transformers b LPCT type current sensors

Temperature
Accurate measurement of temperature inside equipment tted with Pt100, Ni100 or Ni120 type RTDs, connected to the optional remote MET1482 module.

Residual Current
Four types of residual current values are available depending on the type of Sepam and sensors connected to it: b two residual currents Ir and Ir, calculated by the vector sum of the 3 phase currents b two measured residual currents Ir and Ir. Different types of sensors may be used to measure residual current: b CSH120 or CSH200 specic zero sequence CT b conventional 1 A or 5 A current transformer with CSH30 interposing ring CT b any zero sequence CT with an ACE990 interface

Rotation Speed
Rotation speed is calculated by counting the pulses transmitted by a proximity sensor at each passage of a cam driven by the rotation of the motor or generator shaft. Acquisition of pulses on a logic input.

Phasor Diagram
A phasor diagram is displayed by SFT2841 software and the mimic-based UMI to check cabling and assist in the setting and commissioning of directional and differential protection functions. According to the connected sensors, all current and voltage information can be selected for display in vector form.

Demand Current and Maximum Demand currents


Demand and maximum demand currents are calculated according to the three phase currents Ia, Ib, and Ic: b demand current is calculated over an adjustable period of 5 to 60 minutes b maximum demand current is the greatest demand current and indicates the current drawn by maximum loads. Maximum demand currents can be cleared

Voltage and Frequency


The following measurements are available according to the voltage sensors connected: b line-to-neutral voltages Van, Vbn, Vcn and Van, Vbn, Vcn b line-to-line voltages Vab, Vbc, Vca and Vab, Vbc, Vca b residual voltage Vr, Vr or neutral point voltage VNt b positive sequence voltage V1, V1 and negative sequence voltage V2, V2 b frequency measured on the main and additional voltage channels.

Power
Powers are calculated according to the phase currents Ia, Ib and Ic: b active power b reactive power b apparent power b power factor (pf). According to the sensors used, power calculations may be based on the two or three wattmeter method. The two wattmeter method is only accurate when there is no residual current and it is not applicable if the neutral is distributed. The three wattmeter method accurately calculates 3-phase and phase by phase powers in all cases, regardless of whether or not the neutral is distributed. 82

Functions Sepam Series 80

Metering and Diagnosis Description


Network Diagnosis Assistance
Sepam provides network power quality metering functions, and all the data on network disturbances detected by Sepam. The data are recorded for analytical purposes.

Tripping Context
Storage of tripping currents and Ir, I2, Vab, Vbn, Vca, Van, Vbn, Vcn, Vr, V1, V2, F, P, Q, Idiff, It and VNt values when tripping occurs. The values for the last ve trips are stored.

Tripping Current
Storage of the 3 phase currents and ground fault current at the time of the last Sepam trip command, to indicate fault current. The values are stored in the tripping contexts.

Number of Trips
2 trip counters: b number of phase fault trips, incremented by each trip triggered by ANSI 50/51, 50V/51V and 67 protection functions b number of ground fault trips, incremented by each trip triggered by ANSI 50N/51 and 67N/67NC protection functions.

Negative Sequence/Unbalance
Negative sequence component of phase currents Ia, Ib, and Ic (and Ia, Ib and Ic), indicating the degree of unbalance in the power supplied to the protected equipment.

Total harmonic Distortion


Two THD values calculated to assess network power quality, taking into account harmonics up to number 13: b current THD, calculated according to Ia b voltage THD, calculated according to Van or Vab.

Phase Displacement
b phase displacement a, b, c between phase currents la, lb, lc and voltages Van, Vbn, Vcn respectively b phase displacement r between residual current and residual voltage.

Disturbance Recording
Recording triggered by user-set events: b all sampled values of measured currents and voltages b status of all logic inputs and outputs logic data: instantaneous, etc. Recording Characteristics
Number of recordings in COMTRADE format Total duration of a recording Number of samples per period Duration of recording prior to occurrence of the event Adjustable from 1 to 19 Adjustable from 1 to 11 s 12 or 36 Adjustable from 0 to 99 periods 36 Samples per Period 7s 6s

Maximum Recording Capability


Network Frequency 50 Hz 60 Hz 12 Samples per Period 22 s 18 s

Voltage Comparison for Synchro-Check


For the synchro-check function, the MCS025 module continuously measures the amplitude, frequency and phase differences between the 2 voltages to be checked.

Out-of-Sync Context
Storage of amplitude, frequency and phase differences between the 2 voltages measured by the MCS025 module when a closing command is blocked by the synchrocheck function.

83

Functions Sepam Series 80

Metering and Diagnosis Description


Machine Diagnosis Assistance
Sepam assists facility managers by providing: b data on the operation of their machines b predictive data to optimize process management b useful data to facilitate protection function setting and implementation

Thermal Capacity Used


Equivalent temperature buildup in the machine is calculated by the thermal overload protection function. This value is displayed as a percentage of rated thermal capacity.

Remaining Operating Time before Overload Tripping


Predictive data is calculated by the thermal overload protection function. The time is used by facility managers to optimize process management in real time by deciding to: b interrupt according to procedures b continue operation with blocking of thermal protection on overloaded machine.

Waiting Time after Overload Tripping


Predictive data is calculated by the thermal overload protection function. The purpose of waiting time is to avoid further tripping of thermal overload protection that is caused by premature re-energizing of insufciently cooled down equipment.

Running Hours Counter/Operating Time


Equipment is considered to be running whenever a phase current is over 0.1 IB. Cumulative operating time is given in hours.

Motor Starting/Overload Current and Time


A motor is considered to be starting or overloaded when a phase current is over 1.2 IB. For each start / overload, Sepam stores: b maximum current drawn by the motor b starting / overload time. The values are stored until the following start / overload.

Number of Starts before Block/Start Block Time


This indicates the number of starts still allowed by the starts per hour protection function. If the number is zero, there is only one start per hour allowed.

Differential and Through Current


Values calculated to facilitate the implementation of ANSI 87T and 87M differential protection functions.

Current Phase Displacement


Phase shift between the main phase currents and additional phase currents to facilitate implementation of ANSI 87T differential protection function.

Apparent Positive Sequence Impedance Z1


This value is calculated to facilitate implementing the underimpedance eld loss protection (ANSI 40).

Apparent Line-to-line Impedances Zab, Zbc, Zac


Values calculated to facilitate the implementation of the backup underimpedance protection function (ANSI 21B).

Third Harmonic Neutral Point or Residual Voltage


Values measured to facilitate the implementation of the third harmonic undervoltage / 100 % stator ground fault protection function (ANSI 27TN/64G2).

Capacitance
Measurement, for each phase, of the total capacitance of the connected capacitor bank steps. This measurement is used to monitor the condition of the capacitors.

Capacitor Unbalance Current


Measurement of the unbalance current for each capacitor bank step. This measurement is possible when the steps are connected in a double wye arrangement.

84

Functions Sepam Series 80

Metering and Diagnosis Description


ANSI 74 - Trip/Closing Circuit Supervision
To detect the health of the trip and close circuits, Sepam monitors: b shunt trip coil connection b closing coil connection b matching of breaking device open/closed position contacts b execution of breaking device open and close commands The trip and closing circuits are only supervised when connected as shown below.
NO
DE51773

Switchgear Diagnosis Assistance

Switchgear diagnosis data give facility managers information on: b mechanical condition of breaking device b Sepam auxiliaries and assist them for preventive and curative switchgear maintenance actions The data are to be compared to switchgear manufacturer data.

NO

ANSI 60/60FL - CT/VT Supervision


Used to monitor the entire metering chain: b CT and VT sensors b connection b Sepam analog inputs Monitoring includes: b consistency checking of currents and voltages measured b blown fuse indication of phase or residual voltage transformer. If current or voltage measurement data is lost, the assigned protection functions can be blocked to avoid nuisance tripping.

NO

Connection for shunt trip coil monitoring.

Connection for undervoltage trip coil monitoring.

Connection for closing circuit supervision

Auxiliary Power Supply Monitoring


The voltage rating of Sepams auxiliary supply should be set between 24 V DC and 250 V DC. If the auxiliary supply drifts, two alarms may be triggered: b high set point alarm, adjustable from 105 % to 150 % of rated supply (maximum 275 V) b low set point alarm, adjustable from 60 % to 95 % of rated supply (minimum 20 V).

Cumulative Breaking Current Monitoring


Six cumulative currents are proposed to assess interrupting device pole condition: b total cumulative breaking current b cumulative interrupting current between 0 and 2 IN b cumulative interrupting current between 2 IN and 5 IN b cumulative interrupting current between 5 IN and 10 IN b cumulative interrupting current between 10 IN and 40 IN b cumulative interrupting current > 40 IN. Each time the interrupting device opens, the interrupting current is added to the cumulative total and to the appropriate range of cumulative interrupting current. Cumulative interrupting current is given in (kA). An alarm can be generated when the total cumulative interrupting current exceeds a set point.

Number of Operations
Cumulative number of opening operations performed by the interrupting device.

Circuit Breaker Operating Time and Charging Time Number of Rackouts


Used to assess the condition of the interrupting device operating mechanism.

85

Functions Sepam Series 80

Metering and Diagnosis Description


Sepam Self-Diagnosis
Sepam includes a number of self-tests carried out in the base unit and optional modules. The purpose of the self-tests is to: b detect internal problems that may cause nuisance tripping or not tripping when required b put Sepam in fail-safe position to avoid any unwanted operation b alert the facility manager of the need for maintenance operations

Internal Failure
Two categories of internal failures are monitored: b major failures: Sepam shutdown (to fail-safe position). The protection functions are blocked, the output relays are forced to drop out and the Watchdog output indicates Sepam shutdown b minor failures: downgraded Sepam operation Sepams main functions are operational and equipment protection is ensured.

Battery Monitoring
Monitoring of battery voltage to guarantee data is saved in the event of an outage. A battery with low charge generates an alarm.

Detection of Plugged Connectors


The system checks that the current or voltage sensors are plugged in. A missing connector is a major failure.

Conguration Checking
The system checks that the optional modules congured are present and working correctly. The absence or malfunction of a remote module is considered a minor failure. The absence or failure of a logic input/output module is considered a major failure.

86

Functions Sepam Series 80


Functions
Metering

Metering and Diagnosis Characteristics


Measurement range Accuracy (1)
0.5 % 1 % 1 % 0.5 % 0.5 % 0.5 % 1 % 0.5 % 1 % 1 % 1 % 2 % 2 % 0.01 Hz 0.05 Hz 1 % 1 % 1 % 1 % 1 % 0.01 1 % 1 digit 1 % 1 digit 1.8 F from +68 to +384 F 1 C from +20 to +140 C 1 rpm b

MSA141
b b b

Saving

Phase current Residual current Demand current Maximum demand current Line-to-line voltage Line-to-neutral voltage Residual voltage Neutral point voltage Positive sequence voltage Negative sequence voltage Frequency

Calculated Measured

Main channels (VLL) Additional channels (VLL) Main channels (VLn) Additional channels (VLn)

0.02 to 40 IN 0.005 to 40 IN 0.005 to 20 INr 0.02 to 40 IN 0.02 to 40 IN 0.05 to 1.2 VLLp 0.05 to 1.2 VLLp 0.05 to 1.2 VLnp 0.05 to 1.2 VLnp 0.015 to 3 VLnp 0.015 to 3 VLnp 0.05 to 1.2 VLnp 0.05 to 1.2 VLnp 25 to 65 Hz 45 to 55 Hz (fn = 50 Hz) 55 to 65 Hz (fn = 60 Hz) 0.008 Sn to 999 MW 0.008 Sn to 999 MVAR 0.008 Sn to 999 MVA 0.008 Sn to 999 MW 0.008 Sn to 999 MVAR -1 to + 1 (CAP/IND) 0 to 2.1 x 108 MWh 0 to 2.1 x 108 MVARh -22 F to +392 F -30 C to +200 C 0 to 7200 rpm

3
v

Main channels (f) Additional channels (f)

Active power (total or per phase) Reactive power (total or per phase) Apparent power (total or per phase) Maximum demand active power Maximum demand reactive power Power factor Calculated active energy Calculated reactive energy Temperature Rotation speed
Network Diagnosis Assistance

b b b v v b vv vv b

Tripping context Tripping current Number of trips Negative sequence / unbalance Total harmonic distortion, current Total harmonic distortion, voltage Phase displacement r (between Vr and Ir) Phase displacement a, b, c (between V and I) Disturbance recording Amplitude difference Frequency difference Phase difference Out-of-sync context
Machine Operating Assistance

0.02 to 40 In 0 to 65535 1 to 500 % of IB 0 to 100 % 0 to 100 % 0 to 359 0 to 359 0 to 1.2 VLLsync1 0 to 10 Hz 0 to 359 0 to 800 % (100 % for phase I = IB) 0 to 999 min 0 to 999 min 0 to 65535 hours 1.2 IB to 40 IN 0 to 300 s 0 to 60 0 to 360 min 0.015 to 40 IN 0.015 to 40 IN 0 to 359 0 to 200 kw 0.2 to 30 % of VLnp 0.2 to 90 % of VLnp 0 to 30 F 0.02 to 40 IN

5 % 2 % 1 % 1 % 2 2 1 % 0.5 Hz 2 1 % 1 min 1 min 1 % or 0.5 h 5 % 300 ms 1 min 1 % 1 % 2 5 % 1 % 1 % 5 % 5 % 10 % 4 V or 10 % 1 ms 0.5 s b

v v vv

v vv

Thermal capacity used Remaining operating time before overload tripping Waiting time after overload tripping Running hours counter / operating time Starting current Starting time Number of starts before blocking Start block time Differential current Through current Phase displacement a, b, c (between I and I) Apparent impedance Z1, Zab, Zbc, Zac Third harmonic neutral point voltage Third harmonic residual voltage Capacitance Capacitor unbalance current
Switchgear Diagnosis Assistance

vv v v

Cumulative breaking current 0 to 65535 kA Auxiliary supply 24 V DC to 250 V DC Number of operations 0 to 4 x 109 Operating time 20 to 100 s Charging time 1 to 20 s Number of rackouts 0 to 65535 b available on MSA141 analog output module, according to setup v saved in the event of auxiliary supply outage, even without battery v saved by battery in the event of auxiliary supply outage. (1) Under reference conditions (IEC 60255-6), typical accuracy at IN or VLLp, pf > 0.8.

v v v v v v

v v v v v v

87

Functions Sepam Series 80

Protection Description

Current Protection Functions


ANSI 50/51 - Phase Overcurrent
This function provides line-to-line short-circuit protection. There are two modes: b overcurrent protection sensitive to the highest phase current measured b machine differential protection sensitive to the highest differential phase currents obtained in self-balancing schemes Characteristics b two groups of settings b instantaneous or time-delayed tripping b denite time (DT), IDMT (choice of 16 standardized IDMT curves) or customized curve b with or without timer hold b tripping conrmed or unconrmed, according to parameter setting: v unconrmed tripping: standard v tripping conrmed by negative sequence overvoltage protection (ANSI 47, unit 1), as backup for distant 2-phase short-circuits b tripping conrmed by undervoltage protection (ANSI 27, unit 1), as backup for line-to-line shortcircuits in networks with low short-circuit power.

ANSI 49RMS - Thermal Overload


This is protection against thermal damage caused by overloads on: b machines (transformers, motors or generators) b cables b capacitors The thermal capacity used is calculated according to a mathematical model which takes into account: b current RMS values b ambient temperature b negative sequence current, a cause of motor rotor temperature rise. The thermal capacity used calculations may be used to determine predictive data for process control assistance. The protection may be blocked by a logic input when required by process control conditions. Thermal Overload for Machines - Characteristics b two groups of settings (e.g. for alarm / trip for two speed motor) v one adjustable alarm set point for each group v one adjustable tripping set point for each group b adjustable initial thermal capacity used setting, to adapt protection characteristics to t manufacturers thermal withstand curves b equipment heating and cooling time constants. The cooling time constant may be calculated automatically based on measurement of the equipment temperature by a sensor. Thermal Overload for Cables - Characteristics b one group of settings b cable current carrying capacity, which determines alarm and trip set points b cable heating and cooling time constants. Thermal Overload for Capacitors - Characteristics b one group of settings b alarm current, which determines the alarm set point b overload current, which determines the tripping set point b hot tripping time and current setting, which determine a point on the tripping curve.

ANSI 50N/51N or 50G/51G - Ground Fault


Ground fault protection is based on measured or calculated residual current values: b ANSI 50N/51N: residual current calculated or measured by 3 phase current sensors b ANSI 50G/51G: residual current measured directly by a specic sensor Characteristics b two groups of settings b denite time (DT), IDMT (choice of 17 standardized IDMT curves) or customized curve b with or without timer hold b second harmonic restraint to ensure stability during transformer energizing, activated by parameter setting

ANSI 51C - Capacitor Bank Unbalance


Detection of capacitor step internal faults by measuring the unbalance current owing between the two neutral points of a step connected in a double wye arrangement. Four unbalance currents can be measured to protect up to 4 steps. Characteristics b two set points per step b denite time (DT) curve.

ANSI 50BF - Breaker Failure


If breaker fails to trip when signaled, as detected by the fault current persisting, this backup protection sends a tripping command to the upstream (radial) or adjacent (bi-directional) breaker(s).

ANSI 46 - Negative Sequence/Unbalance


This function provides protection against phase unbalance detected by measuring negative sequence current. b sensitive protection to detect 2-phase faults at the ends of long lines b protection of equipment against temperature buildup, caused by an unbalanced power supply, phase inversion or loss of phase, and against phase current unbalance Characteristics b 1 denite time (DT) curve b 9 IDMT curves: 4 IEC curves and 3 IEEE curves, 1 ANSI curve in RI and 1 specic Schneider curve

88

Functions Sepam Series 80

Protection Description
Differential Protection Functions
ANSI 64REF - Restricted Ground Fault Differential
Detection of line-to-ground faults on 3-phase windings with grounded neutral, by comparison of residual current calculated from the 3 phase currents and residual current measured at the neutral point.
DE51774

Recloser
ANSI 79
Automation device used to limit down time after tripping due to transient or semi-permanent faults on overhead lines. The recloser commands automatic reclosing of the interrupting device after the time delay required to restore the insulation has elapsed. Recloser operation is easy to adapt for different operating modes by parameter setting. Characteristics b 1 to 4 reclosing shots, each shot has an adjustable delay before closing time b adjustable, independent reclose time and blocking reclosing operation until delay time as expired. b shot activation linked to instantaneous or timedelayed short-circuit protection function (ANSI 50/51, 50N/51N, 67, 67N/67NC) outputs by parameter setting b blocking/locking out of recloser by logic input.

Ia Ib Ic

INt

Characteristics b instantaneous tripping b percentage-based characteristic with xed slope and adjustable low set point b more sensitive than transformer or machine differential protection.

Synchro-Check
ANSI 25
This function checks the voltages upstream and downstream of a circuit breaker and allows closing when the differences in amplitude, frequency and phase are within authorized limits. Characteristics b adjustable and independent set points for differences in voltage, frequency and phase b adjustable lead time to take into account the circuitbreaker closing time b 5 possible operating modes to take no-voltage conditions into account.

ANSI 87T - Transformer and Transformer- Machine Unit Differential (two windings)
Line-to-line short-circuit protection of two-winding transformers or transformermachine units. Protection based on phase by phase comparison of the primary and secondary currents with: b amplitude and phase correction of the currents in each winding according to the transformer vector shift and the voltage values set b clearance of zero sequence current from the primary and secondary windings (suitable for all grounding systems). Characteristics b instantaneous tripping b adjustable high set point for fast tripping for high level faults, with no restraint b percentage-based characteristic with two adjustable slopes and adjustable low set point b restraint based on percentage of harmonics. These restraints prevent nuisance tripping during transformer energizing, during faults outside the zone that provoke saturation of the current transformers and during operation of a transformer supplied with excessive voltage (overexcitation). v self-adapting neural network restraint: this restraint analyzes the percentage of the 2nd and 5th harmonics as well as differential and through currents v restraint based on the percentage of the 2nd harmonic per phase or total v restraint based on the percentage of the 5th harmonic per phase or total. Self-adapting restraint is exclusive with respect to restraints on the percentage of the 2nd harmonic or on the percentage of the 5th harmonic. b restraint on energization. This restraint, based on the magnetizing current of the transformer or on a logic equation or Logipam, ensures stability of transformers that have low harmonic percentages on energization b fast restraint upon loss of sensor.

ANSI 87M - Machine Differential


Line-to-line short-circuit protection, based on phase by phase comparison of the currents on motor and generator windings. Characteristics b instantaneous tripping b xed high set point for fast tripping for high level faults, with no restraint b percentage-based characteristic with xed slope and adjustable low set point b tripping restraint according to percentage characteristic activated by detection of: v external fault or machine starting v sensor saturation or disconnection v transformer energizing (2nd harmonic restraint)

89

Functions Sepam Series 80

Protection Description
Directional Current Protection
ANSI 67 - Directional Phase Overcurrent
This function provides line-to-line short-circuit protection, with selective tripping according to fault current direction. It comprises a phase overcurrent function associated with direction detection, and picks up if the phase overcurrent function in the chosen direction (line or bus) is activated for at least one of the three phases. Characteristics b two groups of settings b instantaneous or time-delayed tripping b choice of tripping direction b denite time (DT), IDMT (choice of 16 standardized IDMT curves) or customized curve b with voltage memory to make the protection insensitive to loss of polarization voltage at the time of the fault b with or without timer hold

DE51841

ANSI 67N/67NC - Directional Ground Fault


This function provides ground fault protection, with selective tripping according to fault current direction. There are two types of operation: b type 1, projection b type 2, according to the magnitude of the residual current phasor ANSI 67N/67NC Type 1 Directional ground fault protection for impedance, isolated or compensated neutral systems, based on the projection of measured residual current. Type 1 Characteristics There are two groups of settings b instantaneous or time-delayed tripping b denite time (DT) curve b choice of tripping direction b characteristic projection angle b no timer hold b with voltage memory to make the protection insensitive to recurrent faults in compensated neutral systems ANSI 67N/67NC Type 2 Directional overcurrent protection for impedance and solidly grounded systems, based on measured or calculated residual current. It comprises an ground fault function associated with direction detection, and picks up if the ground fault function in the chosen direction (line or bus) is activated. Type 2 Characteristics b two groups of settings b instantaneous or time-delayed tripping b denite time (DT), IDMT (choice of 16 standardized IDMT curves) or customized curve b choice of tripping direction b with or without timer hold

Tripping characteristic of ANSI 67N/67NC type 1 protection (characteristic angle q0 0).


DE51842

Tripping characteristic of ANSI 67N/67NC type 2 protection (characteristic angle q0 0).


DE52064

ANSI 67N/67NC Type 3 Directional overcurrent protection for distribution networks in which the neutral grounding system varies according to the operating mode, based on measured residual current. It comprises an ground fault function associated with direction detection (angular sector tripping zone dened by 2 adjustable angles), and picks up if the ground fault function in the chosen direction (line or bus) is activated. This protection function complies with the Enel DK5600 specication. Type 3 Characteristics b two groups of settings b instantaneous or time-delayed tripping b denite time (DT) curve b choice of tripping direction b no timer hold

Tripping characteristic of ANSI 67N/67NC type 3 protection.

90

Functions Sepam Series 80

Protection Description
Machine Protection Functions
ANSI 37 - Phase Undercurrent
Protection of pumps against the consequences of a loss of priming by the detection of motor no-load operation. It is sensitive Ia below set point, remains stable during breaker tripping and may be blocked by a logic input.

Directional Power Protection Functions


ANSI 32P - Directional Active Overpower
Two-way protection based on calculated active power, for the following applications: b active overpower protection to detect overloads and allow load shedding b reverse active power protection: v against generators running like motors when the generators consume active power v against motors running like generators when the motors supply active power.

ANSI 48/51LR - Locked Rotor/Excessive Starting Time


Protection of motors against overheating caused by: b excessive motor starting time due to overloads (conveyor) or insufcient supply voltage. The reacceleration of a motor that is not shut down, indicated by a logic input, may be considered as starting. b locked rotor due to motor load (e.g. crusher): v in normal operation, after a normal start v directly upon starting, before the detection of excessive starting time, with detection of locked rotor by a zero speed detector connected to a logic input, or by the underspeed function.

ANSI 32Q - Directional Reactive Overpower


Two-way protection based on calculated reactive power to detect eld loss on synchronous machines: b reactive overpower protection for motors which consume more reactive power with eld loss b reverse reactive overpower protection for generators which consume reactive power with eld loss.

ANSI 66 - Starts per Hour


Protection against motor overheating caused by: b too frequent starts: motor energizing is blocked when the maximum allowable number of starts is reached, after counting of: v starts per hour (or adjustable period) v consecutive motor hot or cold starts (reacceleration of a motor that is not shut down, indicated by a logic input, may be counted as a start) b starts too close together in time: motor re-energizing after a shutdown is only allowed after an adjustable waiting time.

ANSI 37P - Directional Active Underpower


Two-way protection based on calculated active power Checking of active power ows: b to adapt the number of parallel sources to t the network load power demand b to create an isolated system in an installation with its own generating unit.

ANSI 40 - Field Loss (Underimpedance)


Protection of synchronous machines against eld loss, based on the calculation of positive sequence impedance on the machine terminals or transformer terminals in the case of transformer-machine units. Characteristics b two circular characteristics dened by reactances Xa, Xb and Xc
DE51843

2 circular tripping characteristics of ANSI 40 protection.

b tripping when the machines positive sequence impedance enters one of the circular characteristics. b denite (DT) time delay for each circular characteristic b setting assistance function included in SFT2841 software to calculate the values of Xa, Xb and Xc according to the electrical characteristics of the machine (and transformer, when applicable).

91

Functions Sepam Series 80

Protection Description

ANSI 78PS - Pole Slip


Protection against loss of synchronism on synchronous machines, based on calculated active power. There are two types of operation: b tripping according to the equal-area criterion, time-delayed b tripping according to power swing (number of active power swings): v suitable for generators capable of withstanding high electrical and mechanical constraints v to be set as a number of rotations. The two types of operation may be used independently or at the same time.
DE51844

Characteristics b circular characteristic centered at origin dened by adjustable set point Zs

ANSI 12 - Overspeed
Detection of machine overspeed, based on the speed calculated by pulse-counting, to detect synchronous generator racing due to loss of synchronism, or for process monitoring, for example.
Circular tripping characteristic of ANSI 21B protection.

b time-delayed denite time (DT) tripping when one of the three apparent impedances enters the circular tripping characteristic

ANSI 14 - Underspeed
Machine speed monitoring based on the speed calculated by pulse-counting: b detection of machine underspeed after starting, for process monitoring, for example b zero speed data for detection of locked rotor upon starting.

ANSI 50/27 - Inadvertent Energization


This function provides for checking the generator starting sequence in order to detect the inadvertent energization of generators that are shut down (a generator which is energized when shut down runs like a motor). This consists of instantaneous phase overcurrent protection conrmed by a time-delayed undervoltage protection function.

ANSI 64G - 100 % Stator Ground Fault


This function provides protection of generators with grounded neutral against lineto-ground insulation faults in stator windings. This function can be used to protect generators connected to step-up transformers. 100 % stator ground fault is a combination of two protection functions: b ANSI 59N/64G1: neutral voltage displacement, protection of 85 % to 90 % of the stator winding, terminal end. b ANSI 27TN/64G2: third harmonic undervoltage, protection of 10 % to 20 % of the stator winding, neutral point end.
DE50099

ANSI 50V/51V - Voltage-Restrained Overcurrent


Line-to-line short-circuit protection, for generators. The current tripping set point is voltage-adjusted in order to be sensitive to faults close to the generator which cause voltage drops and lowers the short-circuit current. Characteristics b instantaneous or time-delayed tripping b denite time (DT), IDMT (choice of 16 standardized IDMT curves) or customized curve b with or without timer hold.

ANSI 21B - Underimpedance


Line-to-line short-circuit protection, for generators, based on the calculation of apparent line-to-line impedance.
Zab = Vab Ib - Ia Area of the generators stator winding associated with the ANSI 59N and ANSI 27TN functions.

ANSI 27TN/64G2 - Third Harmonic Undervoltage


Protection of generators with grounded neutral against line-to-ground insulation faults, by the detection of a reduction of third harmonic residual voltage. Protects the 10 to 20 % of the stator winding, neutral point end, not protected by the ANSI 59N/64G1 function, neutral voltage displacement. Characteristics b choice of two tripping principles, according to the sensors used: v xed third harmonic undervoltage set point v adaptive neutral and terminal third harmonic voltage comparator set point b time-delayed denite time (DT) tripping.

apparent impedance between phases a and b.

ANSI 26/63 - Thermostat/Buchholz


Protection of transformers against temperature rise and internal faults via logic inputs linked to devices integrated in the transformer.

ANSI 38/49T - Temperature Monitoring


This protection detects abnormal temperature build-up by measuring the temperature inside equipment tted with sensors: b transformer: protection of primary and secondary windings b motor and generator: protection of stator windings and bearings. Characteristics b 16 Pt100, NI100 or Ni120 type RTDs 92

Functions Sepam Series 80

Protection Description
Frequency Protection Functions
ANSI 81H - Overfrequency
Detection of abnormally high frequency compared to the rated frequency, to monitor power supply quality.

Voltage Protection Functions


ANSI 24 - Overexcitation (V/Hz)
Protection which detects overexcitation of transformer or generator magnetic circuits by calculating the ratio between the greatest line-to-neutral or line-to-line voltage divided by the frequency. Characteristics b machine tie breaker to be set up b denite time (DT) or IDMT time delays (choice of three curves)

ANSI 81L - Underfrequency


This function allows for detecting abnormally low frequency compared to the rated frequency, to monitor power supply quality. It is activated by parameter setting. This protection can be used for overall tripping or load shedding. Protection stability is ensured if the main source is lost and there is a presence of remnant voltage. This is accomplished by a restraint in the event of a continuous frequency decrease.

ANSI 27D - Positive Sequence Undervoltage


Protection of motors against faulty operation due to insufcient or unbalanced network voltage, and detection of reverse rotation direction.

ANSI 81R - Rate of Change of Frequency (df/dt)


This protection function is used for fast disconnect of a generator or load shedding control. It is based on the frequency variation calculation. It is insensitive to transient voltage disturbances and therefore more stable than a phase-shift protection function. Disconnection In installations with autonomous production means connected to a utility, the "rate of change of frequency" protection function is used to detect loss of the main system in view of opening the incoming circuit breaker to: b protect the generators from a reconnection without checking synchronization b avoid supplying loads outside the installation. Load Shedding The "rate of change of frequency" protection function is used for load shedding in combination with the underfrequency protection to: b either accelerate shedding in the event of a large overload b or block shedding following a sudden drop in frequency due to a problem that should not be solved by shedding

ANSI 27R - Remnant Undervoltage


Protection used to check that remnant voltage sustained by rotating machines has been cleared before allowing the bus supplying the machines to be re-energized, to avoid electrical and mechanical transients.

ANSI 27 - Undervoltage
Protection of motors against voltage sags or detection of abnormally low network voltage to trigger automatic load shedding or source transfer. Works with line-to-line or line-to-neutral voltage, each voltage being monitored separately. Characteristics b denite time (DT) curve b IDMT curve

ANSI 59 - Overvoltage
Detection of abnormally high network voltage or checking for sufcient voltage to enable source transfer. Works with line-to-line or line-to-neutral voltage, each voltage being monitored separately.

ANSI 59N - Neutral Voltage Displacement


Detection of insulation faults by measuring residual voltage b ANSI 59N: in isolated neutral systems b ANSI 59N/64G1: in stator windings of generators with grounded neutral. Protects the 85 % to 90 % of the winding, terminal end, not protected by the ANSI 27TN/64G2 function, third harmonic undervoltage Characteristics b denite time (DT) curve b IDMT curve

ANSI 47 - Negative Sequence Overvoltage


Protection against phase unbalance resulting from phase inversion, unbalanced supply or distant fault, detected by the measurement of negative sequence voltage. b 2 adjustable independent set points for each RTD (alarm and trip).

93

Functions Sepam Series 80

Protection Trip Curves


Customized Trip Curve

PE50551

Dened point by point using the SFT2841 setting and operating software tool, this curve can be used to solve all special cases involving protection coordination or revamping.

IDMT Trip Curves


Current IDM T Trip Curves
Multiple IDMT tripping curves are offered, to cover most applications: b IEC curves (SIT, VIT/LTI, EIT) b IEEE curves (MI, VI, EI) b usual curves (UIT, RI, IAC).

Customized trip curve set using SFT2841 software.

IEC Curves
Equation Curve Type
Standard inverse / A
k T t d( I) = ----------- I -- 1 Is

Coefcient Values
k 0.14 13.5 120 80 315.2 a 0.02 1 1 2 2.5 b 2.97 1.50 13.33 0.808 1

Very inverse / B Long time inverse / B Extremely inverse / C Ultra inverse RI curve Equation:

1 T ------------------- ------td ( I ) = -1 3 ,1706 I 0 ,339 0,236 - Is

IEEE Curves
Equation Curve Type
Moderately inverse Very inverse Extremely inverse

Coefcient Values
A B 0.023 0.098 0.0243 p 0.02 2 2 b 0.241 0.138 0.081 0.010 3.922 5.64

T A -------- + B -td ( I ) = I p 1 - Is

IEEE Curves
Equation Curve Type
Inverse Very inverse Extremely inverse

Coefcient Values
A B 0.863 0.795 0.638 C 0.800 0.100 0.620 D -0.418 -1.288 1.787 E 0.195 7.958 0.246 b 0.297 0.165 0.092 0.208 0.090 0.004

T B D E td ( I ) = A + -------+ -------- + -------- x -2 3 I I I -- C -- C -- C Is Is Is

94

Functions Sepam Series 80

Protection Trip Curves


Equation for EPATRB, EPATRC
EPATRB For 0,6 A Ir 6,4 A

DB52590

101.21

85 ,386 T td ( I0 ) = ------- x--I0 0, 975 0, 8

For 6,4 A Ir 200,0 A


140 ,213 T td ( I0 ) = -------- x--0, 8 I0 0, 975

T = 2.10 Ir (A)

For Ir > 200,0 A td (Ir) = T


0.6 Ir0

EPATR-C Standard curve (logarithmic scale).

EPATRC For 0,6 A Ir 200,0 A


T td ( I0 ) = 72 I0 2 /3 x ---2 ,10

DB52591

For Ir > 200,0 A td (Ir) = T

EPATR-B Standard curve (logarithmic scale).

Voltage IDMT Trip Curves


Equation for ANSI 27 - Undervoltage
T td ( I ) = -------V --- 1 Vs

Equation for ANSI 59N - Neutral Voltage Displacement


T td ( I ) = -------V --1 Vs

Voltage/Frequency Ratio IDMT Trip Curves


Equation for ANSI 27 - Undervoltage
With G = VLn/f or VLL/f
1 td ( G ) = ---------x T p G --- 1 Gs

Curve Type
A B C

P 0.5 1 2

95

Functions Sepam Series 80

Protection Main Characteristics


Setting IDMT Trip Curves, Time Delay, or TMS Factor
The time delays of current IDMT tripping curves (except for customized and RI curves) may be set as follows: b time T, operating time at 10 x Is b TMS factor, factor shown as T/b in the equations on the left

DE50275

Timer Hold
The adjustable timer hold T1 is used for: b detection of restriking faults (DT curve) b coordination with electromechanical relays (IDMT curve). Timer hold may be blocked, if necessary.

Two Groups of Settings


Line-to-line and Line-to-Ground Short-Circuit Protection
Detection of restriking faults with adjustable timer hold.

Each unit has two groups of settings, A and B, to adapt the settings to suit the network conguration. The active group of settings (A or B) is set by a logic input or the communication link. Example: normal / backup mode network b group A for network protection in normal mode, when the network is supplied by the utility b group B for network protection in backup mode, when the network is supplied by a backup generator

Thermal Overload for Machines


Each unit has two groups of settings to protect equipment that has two operating modes. Examples: b transformers: switching of groups of settings by logic input, according to transformer ventilation operating mode, natural or forced ventilation (ONAN or ONAF) b motors: switching of groups of settings according to current set point, to take into account the thermal withstand of motors with locked rotors
Ir Y Y
DE51775

NO

Ir

Measurement Origin
The measurement origin needs to be indicated for each unit of the protection functions that may use measurements of different origins. The setting links a measurement to a protection unit and allows the protection units to be distributed optimally among the measurements available according to the sensors connected to the analog inputs. Example: distributing ANSI 50N/51N function units for transformer ground fault protection: b two units linked to measured Ir for transformer primary protection b two units linked to measured I'r for transformer secondary protection b two units linked to Ir for protection upstream of the transformer b two units linked to I'r for protection downstream of the transformer

Ir Ir

NO

Measurement origin: example.

Summary Table
Characteristics
2 groups of settings A or B 2 groups of settings, operating modes 1 and 2 IEC IDMT curves IEEE IDMT curves Usual IDMT curves EPATR curves Voltage IDMT curves Customized curve Timer hold

Protection Functions
50/51, 50N/51N, 67, 67N/67NC 49RMS Machine 50/51, 50N/51N, 50V/51V, 67, 67N/67NC type 2, 46 50/51, 50N/51N, 50V/51V, 67, 67N/67NC type 2, 46 50/51, 50N/51N, 50V/51V, 67, 67N/67NC type 2 50N/51N 27, 59N, 24 50/51, 50N/51N, 50V/51V, 67, 67N/67NC type 2 50/51, 50N/51N, 50V/51V, 67, 67N/67NC type 2

96

Functions Sepam Series 80


Functions
ANSI 12 - Overspeed ANSI 14 - Underspeed

Protection
Setting Ranges
Settings
100 to 160 % of n 10 to 100 % of n

Time Delays
1 to 300 s 1 to 300 s

ANSI 21B - Underimpedance

Impedance Zs
ANSI 24 - Overexcitation (V/Hz)

0.05 to 2.00 VLn/IB Denite time IDMT type A, B or C 1.03 to 2 pu

Tripping curve Gs set point


ANSI 25 - Synchro-Check

Denite time IDMT Line-to-neutral 220 V to 250 kV 220 V to 250 kV 90 V to 230 V 90 V to 230 V 3 % to 30 % of VLnp sync1 0,05 to 0,5 Hz 5 to 80 70 % to 110 % VLnp sync1 10 % to 70 % VLnp sync1 0 to 0.5 s Dead1 AND Live2 Live1 AND Dead2 Dead1 XOR Dead2 Dead1 OR Dead2 Dead1 AND Dead2

0.1 to 20000 s 0.1 to 1250 s

Measured voltages Rated Primary Line-to-line Voltage VLLp sync1 (VLnp sync1 = VLLp sync1/3) VLLp sync2 (VLnp sync2 = VLLp sync2/3) Rated Secondary Line-to-line Voltage VLns sync1 VLns sync2 Synchro-Check Setpoints dUs set point dfs set point dPhi set point VLLs high set point VLLs low set point Other Settings Lead time Operating modes: no-voltage conditions for which a tie breaker is allowed

Line-to-line 220 V to 250 kV 220 V to 250 kV 90 V to 120 V 90 V to 120 V 3 % to 30 % of VLLp sync1 0.05 to 0.5 Hz 5 to 80 70 % to 110 % VLLp sync1 10 % to 70 % VLLp sync1 0 to 0.5 s Dead1 AND Live2 Live1 AND Dead2 Dead1 XOR Dead2 Dead1 OR Dead2 Dead1 AND Dead2

ANSI 27 - Undervoltage (LL) or (Ln)

Trip curve Set point Measurement origin


ANSI 27D - Positive Sequence Undervoltage

Denite time IDMT 5 to 100 % of VLLp Main channels (VLL) or additional channels (VLL) 15 to 60 % of VLLp Main channels (VLL) or additional channels (VLL) 5 to 100 % of VLLp Main channels (VLL) or additional channels (VLL) 0.2 to 20 % of VLnp 0.1 to 0.2 50 to 100 % of VLLp 1 to 90 % of Sb (Sb = 3.VLL IB) 1 to 120 % of Sn (1)

0.05 to 300 s

Set point and time delay Measurement origin


ANSI 27R - Remnant Undervoltage

0.05 to 300 s

Set point and time delay Measurement origin Vs set point (xed) K set point (adaptive) Positive sequence undervoltage Minimum apparent power
ANSI 32P - Directional Active Overpower

0.05 to 300 s

ANSI 27TN/64G2 - Third Harmonic Undervoltage

0.05 to 300 s 0.05 to 300 s

0.1 s to 300 s 0.1 s to 300 s 0.05 to 300 s 0.1 s to 300 s

ANSI 32Q - Directional Reactive Overpower

5 to 120 % of Sn (1)
ANSI 37 - Phase Undercurrent

0.05 to 1 IB
ANSI 37P - Directional Active Underpower

5 to 100 % of Sn (1)
ANSI 38/49T - Temperature Monitoring

Alarm set point TS1 Trip set point TS2


ANSI 40 - Field Loss (underimpedance)

32 F to 356 F or 0 C to 180 C 32 F to 356 F or 0 C to 180 C 0.02 VLn/IB to 0.2 VLn/IB + 187.5 kW 0.2 VLn/IB to 1.4 VLn/IB + 187.5 kW 0.6 VLn/IB to 3 VLn/IB + 187.5 kW

Common point: Xa Circle 1: Xb Circle 2: Xc

0.05 to 300 s 0.1 s to 300 s

(1) Sn = 3.IN.VLLp. 97

Functions Sepam Series 80

Protection
Setting Ranges

Functions
ANSI 46 - Negative Sequence/Unbalance

Settings
Denite time Schneider Electric IEC: SIT/A, LTI/B, VIT/B, EIT/C IEEE: MI (D), VI (E), EI (F) RI (setting constant from 1 to 100) Denite time 0.1 to 5 IB IDMT 0.1 to 5 IB (Schneider Electric) 0.1 to 1 IB (IEC, IEEE) 0.03 to 0.2 IB (RI) Main channels (I) or additional channels (I) 1 to 50 % of VLLp Main channels (I) or additional channels (I) 0.5 IB to 5 IB ST starting time LT and LTS time delays

Time Delays

Tripping curve

Is set point

0.1 to 300 s 0.1 to 1s

Measurement origin
ANSI 47 - Negative Sequence Overvoltage

Set point and time delay Measurement origin Is set point


ANSI 49RMS - Thermal Overload for Cables

0.05 to 300 s

ANSI 48/51LR -Locked Rotor/Excessive Starting Time

0.5 to 300 s 0.05 to 300 s

Admissible current Time constant T1 Alarm current Trip current Positioning of the hot tripping curve

1 to 1.73 IB 1 to 600 min 1.05 to 1.70 IB 1.05 to 1.70 IB 1.02 x trip current to 2 IB 1 to 2000 minutes (variable range depending on the trip current and current setting)
Mode 1 Mode 2

ANSI 49RMS - Thermal Overload for Capacitors

Current setting Time setting

ANSI 49RMS - Thermal Overload for Machines

Accounting for negative sequence component Time constant Heating Cooling Alarm and tripping set points (Es1 and Es2) Initial thermal capacity used (Es0) Switching of thermal settings condition Maximum equipment temperature Measurement origin
ANSI 50BF - Breaker Failure

0 - 2.25 - 4.5 - 9 T1: 1 to 600 min T2: 5 to 600 min T1: 1 to 600 min T2: 5 to 600 min

0 to 300 % of rated thermal capacity 0 to 100 % by logic input by Is set point adjustable from 0.25 to 8 IB 140 F to 392 F (60 to 200 C) Main channels (I) or additional channels (I)

Presence of current Operating time


ANSI 50/27 - Inadvertent Energization

0.2 to 2 IN 0.05 s to 3 s 0.05 to 4 IN 10 to 100 % VLLp

Is set point Vs set point


ANSI 50/51 - Phase Overcurrent

T1: 0 to 10 s T2: 0 to 10 s

Trip curve

Is set point Timer hold Measurement origin Conrmation

Tripping Time Delay Timer Hold Denite time DT DT SIT, LTI, VIT, EIT, UIT (1) RI DT IEC: SIT/A, LTI/B, VIT/B, EIT/C DT or IDMT IEEE: MI (D), VI (E), EI (F) DT or IDMT IA : I, VI, EI DT or IDMT Customized DT Denite time 0.05 to 24 IN IDMT 0.05 to 2.4 IN Denite time (DT; timer hold) IDMT (IDMT; reset time) Main channels (I) or additional channels (I) None By negative sequence overvoltage By line-to-line undervoltage

Inst; 0.05 s to 300 s 0.1 s to 12.5 s at 10 Is Inst; 0.05 s to 300 s 0.5 s to 20 s

(1) Tripping as of 1.2 Is.

98

Functions Sepam Series 80


Functions
ANSI 50N/51N or 50G/51G - Ground Fault

Protection
Setting Ranges
Settings
Tripping Time Delay Denite time SIT, LTI, VIT, EIT, UIT (1) RI IEC: SIT/A, LTI/B, VIT/B, EIT/C IEEE: MI (D), VI (E), EI (F) IAC: I, VI, EI EPATR-B, EPATR-C Customized 0.6 to 5 A 0.6 to 5 A 0.01 to 15 INr (min. 0.1 A) 0.01 to 1 INr (min. 0.1 A) Denite time (DT; timer hold) IDMT (IDMT; reset time) Timer Hold DT DT DT DT or IDMT DT or IDMT DT or IDMT DT DT EPATR-B EPATR-C Denite time IDMT

Time Delays

Trip curve

3
0.5 to 1 s 0.1 to 3 s Inst; 0.05 s to 300 s 0.1 s to 12.5 s at 10 Is0 Inst; 0.05 s to 300 s 0.5 s to 20 s

Isr set point Timer hold Measurement origin

Ir input, Ir input, sum of phase currents Ir or sum of phase currents Ir Tripping Time Delay Timer Hold Denite time DT DT SIT, LTI, VIT, EIT, UIT (1) RI DT IEC : SIT/A, LTI/B, VIT/B, EIT/C DT or IDMT IEEE : MI (D), VI (E), EI (F) DT or IDMT IAC : I, VI, EI DT or IDMT Customized DT Denite time 0.5 to 24 IN IDMT 0.5 to 2.4 IN Denite time (DT; timer hold) IDMT (IDMT; reset time) Main channels (I) or additional channels (I) 0.05 A to 2 IN Denite time

ANSI 50V/51V - Voltage-Restrained Overcurrent

Tripping curve

Is set point Timer hold Measurement origin


ANSI 51C - Capacitor Bank Unbalance

Inst; 0.05 s to 300 s 0.1 s to 12.5 s at 10 Isr Inst; 0.05 s to 300 s 0.5 s to 20 s

Is set point
ANSI 59 - Overvoltage (LL) or (LN)

0.1 to 300 s 0.05 to 300 s

Set point and time delay Measurement origin


ANSI 59N - Neutral Voltage Displacement

50 to 150 % of VLLp or VLnp Main channels (VLL) or additional channels (VLL) Denite time IDMT Denite time 2 to 80 % of VLLp IDMT 2 to 10 % of VLLp Main channels (VLL), additional channels (VLL) or neutral-point voltage VLnt 0.05 to 0.8 IN (IN 20 A) 0.1 to 0.8 IN (IN < 20 A) Main channels (I, Ir) or additional channels (I, Ir) 1 to 60 1 to 60 Period T time delay stop/start

Tripping curve Set point Measurement origin Isr set point Measurement origin
ANSI 66 - Starts per Hour

0.05 to 300 s 0.1 to 100 s

ANSI 64REF - Restricted Ground Fault Differential

Total number of starts Number of consecutive starts (1) Tripping as of 1.2 Is.
ANSI 67 - Directional Phase Overcurrent

1 to 6 h 0 to 90 min

Characteristic angle Tripping curve

Is set point Timer hold (1) Tripping as of 1.2 Is.

30, 45, 60 Tripping Time Delay Denite time SIT, LTI, VIT, EIT, UIT (1) RI IEC: SIT/A, LTI/B, VIT/B, EIT/C IEEE: MI (D), VI (E), EI (F) IAC: I, VI, EI Customized 0.1 to 24 IN 0.1 to 2.4 IN Denite time (DT; timer hold) IDMT (IDMT; reset time)

Timer Hold DT DT DT DT or IDMT DT or IDMT DT or IDMT DT Denite time IDMT

Inst; 0.05 s to 300 s 0.1 s to 12.5 s at 10 Isr Inst; 0.05 s to 300 s 0.5 s to 20 s

99

Functions Sepam Series 80


Functions

Protection
Setting Ranges
Settings
-45, 0, 15, 30, 45, 60, 90 0.01 to 15 INr (mini. 0,1 A) 2 to 80 % of VLLp T0mem time Vrmem validity set point Ir input, Ir input -45, 0, 15, 30, 45, 60, 90 Tripping Time Delay Denite time SIT, LTI, VIT, EIT, UIT (1) RI IEC: SIT/A, LTI/B, VIT/B, EIT/C IEEE: MI (D), VI (E), EI (F) IAC: I, VI, EI Customized 0.1 to 15 INr (min. 0.1 A) 0.01 to 1 INr (min. 0.1 A) 2 to 80 % of VLLp Denite time 0; 0.05 s to 300 s 0; 2 to 80 % of VLLp

Time
Inst; 0.05 s to 300 s

ANSI 67N/67NC - Directional Ground Fault, Projection (Type 1)

Characteristic angle Isr set point Vsr set point Memory time Measurement origin Characteristic angle Tripping curve

ANSI 67N/67NC - Directional Ground Fault, According to Ir Vector Magnitude (Type 2)

Isr set point Vsr set point Timer hold Measurement origin Tripping sector start angle Tripping sector end angle Isr set point CSH Zero Sequence CT (2 A rating) 1 A CT ZSCT + ACE990 (range 1) Vsr set point Measurement origin
ANSI 78PS - Pole Slip

Timer Hold Delay DT DT DT DT or IDMT DT or IDMT DT or IDMT DT Denite time IDMT

Inst; 0.05 s to 300 s 0.1 s to 12.5 s at 10 Isr Inst; 0.05 s to 300 s 0.5 s to 20 s

Denite time (DT; timer hold) IDMT (IDMT; reset time) Ir input, Ir input or sum of phase currents Ir 0 to 359 0 to 359 0.1 A to 30 A 0.005 to 15 INr (min. 0.1 A) 0.01 to 15 INr (min. 0.1 A) Calculated Vr (sum of 3 voltages) Measured Vr (external VT) Ir input or Ir input 0.1 to 300 s 1 to 30 1 to 300 s 50 to 55 Hz or 60 to 65 Hz Main channels (V) or additional channels (V) 40 to 50 Hz or 50 to 60 Hz Main channels (VLn) or additional channels (VLn) 0.1 to 10 Hz/s

ANSI 67N/67NC Type 3 - Directional Ground Fault, According to Ir Vector Magnitude Directionalized on a Tripping Sector

Denite time

Inst; 0.05 s to 300 s

2 to 80 % of VLLp 0.6 to 80 % of VLLp

Time delay of the equal-area criterion Maximum number of power swings Time between 2 power swings
ANSI 81H - Overfrequency

Set point and time delay Measurement origin


ANSI 81L - Underfrequency

0.1 to 300 s

Set point and time delay Measurement origin


ANSI 81R - Rate of Change of Frequency

0.1 to 300 s

0.15 to 300 s

ANSI 87M - Machine Differential

Ids set point


ANSI 87T - Transformer Differential

0.05 to 0.5 IN (IN < 20 A) 0.1 to 0.5 IN (IN < 20 A) 3 to 18 IN1 30 to 100 % IN1 15 to 50 % without, 50 to 100 % 1 to 18 IN1 1 to 10 % 0 to 300 s On / Off Classic Classic On off, 5 to 40 % per phase / total off, 5 to 40 % per phase / total

High set point Percentage-Based Curve Ids set point Slope Id/It Slope I1/It2 Slope change point Restraint on Energization Current threshold Delay Restraint on CT loss Activity Restraint on Harmonics Percentage Choice of restraint High set point Harmonic 2 percentage set point Harmonic 2 restraint Harmonic 5 percentage set point Harmonic 5 restraint

Self-Adapting Self-adapting On / Off

100

Functions Sepam Series 80

Control and Monitoring Description


Sepam performs all the control and monitoring functions required for electrical network operation: b the main control and monitoring functions are predened and t the most frequent cases of use. They are ready to use and are implemented by simple parameter setting after the necessary logic inputs / outputs are assigned. b the predened control and monitoring functions can be adapted for particular needs using the SFT2841 software, which offers the following customization options: v logic equation editor, to adapt and complete the predened control and monitoring functions v creation of personalized messages for local annunciation v creation of personalized mimic diagrams corresponding to the controlled devices v customization of the control matrix by changing the assignment of output relays, LEDs and annunciation messages b with the Logipam option, Sepam can provide the most varied control and monitoring functions, programmed using the SFT2885 programming software that implements the Logipam ladder language

Operating Principle
Processing control and monitoring functions can be broken down into three phases: b acquisition of input data: v results of protection function processing v external logic data, connected to the logic inputs of an optional MES120 input / output module v local control commands transmitted by the mimic-based UMI v remote control commands (TC) received via the Modbus communication link b actual processing of the control and monitoring function b utilization of the processing results: v activation of output relays to control a device v information sent to the facility manager: - by message and/or LED on the Sepam display and SFT2841 software - by remote indication (TS) via the Modbus communication link - by real-time indications on device status on the animated mimic diagram
PE50249

Logic Inputs and Outputs


The number of Sepam inputs/outputs must be adapted to t the control and monitoring functions used. The ve outputs included in the Sepam Series 80 base unit may be extended by adding one, two, or three MES120 modules with 14 logic inputs and 6 output relays. After the number of MES120 modules required for the needs of an application is set, the logic inputs are assigned to functions. The functions are chosen from a list which covers the whole range of possible uses. The functions are adapted to meet needs within the limits of the logic inputs available. The inputs may also be inverted for undervoltage type operation. A default input / output assignment is proposed for the most frequent uses.

Maximum Sepam Series 80 conguration with 3 MES120 modules: 42 inputs and 23 outputs.

101

Functions Sepam Series 80

Control and Monitoring Description of Predened Functions


Each Sepam contains the appropriate predened control and monitoring functions for the chosen application.

ANSI 94/69 - Circuit Breaker/Contactor Control


This function provides control of breaking devices equipped with different types of closing and tripping coils: b circuit breakers with shunt or undervoltage trip coils b latching contactors with NO contacts b contactors with latched commands. The function processes all interrupting device closing and tripping conditions, based on: b protection functions b interrupting device status data b remote control commands b specic control functions for each application (e.g. recloser, synchro-check) The function also blocks interrupting device closing according to the operating conditions.

Automatic Transfer (AT)


This function transfers bus supply from one source to another. It concerns substations with two mains, with or without tie breakers. The function carries out: b automatic transfer with a break if there is a loss of voltage or a fault b manual transfer and return to normal operation without a break, with or without synchro-check b control of the tie breaker circuit breaker (optional) b selection of the normal operating mode b the necessary logic to ensure that at the end of the sequence, only one circuit breaker out of two or two out of three are closed.
NO NO

DE51889

NO NO NO NO

The function is distributed between the two Sepam units protecting the two mains. The synchro-check function (ANSI 25) is carried out by the optional MCS025 module, in conjunction with one of the two Sepam units. Load shedding - Automatic restart Automatic load regulation on electrical networks by load shedding followed by automatic restarting of motors connected to the network

Automatic transfer with synchro-check controlled by Sepam Series 80.

Load Shedding
The interrupting device opens to stop motors in case of: b detection of a network voltage sag by the positive sequence undervoltage protection function ANSI 27D b receipt of a load shedding command on a logic input. Automatic Restart The motors disconnected as a result of the network voltage sag are automatically restarted: b after the return of network voltage is detected by the positive sequence undervoltage protection function ANSI 27D b and a time delay has run out, so as to stagger motor restarts.

De-Excitation
Interruption of a synchronous generators excitation supply and tripping of the generator interrupting device in case of: b detection of an internal generator fault b detection of an excitation system fault b receipt of a de-excitation command on a logic input or via the communication link.

102

Functions Sepam Series 80

Control and Monitoring Description of Predened Functions


Genset Shutdown
Shutdown of the driving machine, tripping of the interrupting device and interruption of the generator excitation supply in case of: b detection of an internal generator fault b receipt of a genset shutdown command on a logic input or via the communication link.

Control of Capacitor Banks


This function controls 1 to 4 switches for capacitor steps, taking into account all the closing and tripping conditions determined by the ANSI 94/69 function for control of the switchgear. Manual or automatic control, controlled by an external reactive-energy regulator.

ANSI 68 - Zone Sequence Interlocking (ZSI)


This function provides: b perfect tripping coordination with line-to-line and line-to-ground short-circuits, on all types of network b faster tripping of the breakers closest to the source (solving the drawback of conventional time coordination). Each Sepam is capable of: b sending a blocking input when a fault is detected by the phase overcurrent and ground fault protection functions, which may or may not be directional (ANSI 50/51, 50N/51N, 67 or 67N/67NC) b and receiving blocking inputs which block protection tripping. A saving mechanism ensures continued operation of the protection in the event of a blocking link malfunction.

ANSI 86 - Latching/Acknowledgement
The tripping outputs for all the protection functions and all the logic inputs can be latched individually. The latched information is saved in the event of an auxiliary power outage. (The logic outputs cannot be latched.) All the latched data may be acknowledged: b locally, with the key reset b remotely via a logic input b or via the communication link The Latching/acknowledgement function, when combined with the circuit breaker/ contactor control function, can be used to create the ANSI 86 "Lockout relay" function.

Output Relay Testing


Each output relay is activated for 5 seconds, to make it simpler to check output connections and connected switchgear operation.

103

Functions Sepam Series 80

Control and Monitoring Description of Predened Functions


ANSI 30 - Local Annunciation
LED Indication b 2 LEDs, on the front and back of Sepam, indicate the unit operating status, and are visible when a Sepam without a UMI is mounted inside the LV compartment, with access to connectors: v green LED ON: Sepam on v red "key" LED: Sepam unavailable (initialization phase or detection of an internal failure) b 9 yellow LEDs on the Sepam front panel: v pre-assigned and identied by standard removable labels v the SFT2841 software tool may be used to assign LEDs and personalize labels. Local Annunciation on Sepam Display Events and alarms may be indicated locally on Sepams advanced UMI or on the mimic-based UMI by: b messages on the display unit, available in 2 languages: v English, factory-set messages, not modiable v local language, according to the version delivered (the language version is chosen when Sepam is set up) b one of the 9 yellow LEDs lights up, according to the LED assignment, which is set using SFT2841 Alarm Processing When an alarm appears, the related message replaces the current display and the related LED goes on. The number and type of messages depend on the type of Sepam. The messages are linked to Sepam functions and may be viewed on the front-panel display and in the SFT2841 "Alarms" screen. b to clear the message from the display, press the key b after the fault has disappeared, press the key: the light goes off and Sepam is reset

PE50287

Local indications on the Sepam front panel.

PE50274

SFT2841: alarm history.

b the list of alarm messages remains accessible ( pressing the clear key

key) and may be cleared by

104

Functions Sepam Series 80

Control and Monitoring Description of Predened Functions


Local Control Using the Mimic-Based UMI
Sepam Control Mode A key-switch on the mimic-based UMI is used to select the Sepam control mode. Three modes are available : Remote, Local or Test. In Remote mode: b remote control commands are taken into account b local control commands are disabled, with the exception of the circuit-breaker open command. In Local mode: b remote control commands are disabled, with the exception of the circuit-breaker open command b local control commands are enabled. Test mode should be selected for tests on equipment, e.g. during preventivemaintenance operations: b all functions enabled in Local mode are available in Test mode b no remote indications (TS) are sent via the communication link.

PE50486

Local control using the mimic-based UMI.

The Logipam programming software can be used to customize control-mode processing. View Device Status on the Animated Mimic Diagram For local control of devices, all information required by operators can be displayed simultaneously on the mimic-based UMI: b single-line diagram of the equipment controlled by Sepam, with an animated, graphic indication of device status in real time b the desired current, voltage and power measurements. The local-control mimic diagram can be customized by adapting one of the supplied, predened diagrams or by creating a diagram from scratch. Local control of devices All the devices for which opening and closing are controlled by Sepam can be controlled locally using the mimic-based UMI. The most common interlock conditions can be dened be logic equations or by Logipam. The sure and simple operating procedure is the following: b select the device to be controlled by moving the selection window using the keys or . Sepam checks whether local control of the selected device is authorized and informs the operator (selection window with a solid line) b selection conrmation for the device to be controlled by pressing the key (the selection window ashes) b device control by pressing: : open command v key : close command. v or key

105

Functions Sepam Series 80

Control and Monitoring Adaptation of Predened Functions Using the SFT2841 Software
The predened control and monitoring functions can be adapted for particular needs using the SFT2841 software, which offers the following customization options: b logic equation editor, to adapt and complete the predened control and monitoring functions b creation of personalized messages for local annunciation b creation of custom mimic diagrams corresponding to the controlled devices b customization of the control matrix by changing the assignment of output relays, LEDs and annunciation messages

Operating Principle
DE51890

PE50277

Logic Equation Editor


The logic equation editor included in the SFT2841 software can be used to: b complete protection function processing: v additional interlocking v conditional blocking/validation of functions b adapt predened control functions: particular circuit breaker or recloser control sequences Note that the use of the logic equation editor excludes the possibility of using the Logipam programming software.
SFT2841: logic equation editor.

A logic equation is created by grouping logic input data received from: b protection functions b logic inputs b local control commands transmitted by the mimic-based UMI b remote control commands using the Boolean operators AND, OR, XOR, NOT, and automation functions such as time delays, bistables and time programmer. Equation input is assisted and syntax checking is done systematically. The result of an equation may then be: b assigned to a logic output, LED or message via the control matrix b transmitted by the communication link, as a new remote indication b utilized by the circuit breaker/contactor control function to trip, close or block interrupting device closing b used to block or reset a protection function

106

Functions Sepam Series 80

Control and Monitoring Adaptation of Predened Functions Using the SFT2841 Software
Personalized Alarm and Operating Messages
The alarm and operating messages may be personalized using the SFT2841 software tool. The new messages are added to the list of existing messages and may be assigned via the control matrix for display: b on the Sepam display b in the SFT2841 "Alarms" and "Alarm History" screens.

PE50492

Local-Control Mimic Diagram


Main #2

52

Ia = 175 A Vab = 6.61 kV P = 1.81 MW Q = 860 kvar

The mimic-diagram editor in the SFT2841 software can be used to create a singleline diagram corresponding exactly to the equipment controlled by Sepam. Two procedures are available: b rework a diagram taken from the library of standard diagrams in the SFT2841 software b creation of an original diagram : graphic creation of the single-line diagram, positioning of symbols for the animated devices, insertion of measurements, text, etc. Creation of a customized mimic diagram is made easy: b library of predened symbols: circuit breakers, grounding switch, etc. b creation of personalized symbols.

SFT2841: mimic-diagram editor.

PE50490

Control Matrix
The control matrix is a simple way to assign data from: b protection functions b control and monitoring functions b logic inputs b logic equations or Logipam program to the following output data: b output relays b 9 LEDs on the front panel of Sepam b messages for local annunciation b triggering of disturbance recording.

SFT2841: control matrix.

107

Functions Sepam Series 80

Control and Monitoring Customized Functions Using Logipam


The SFT2885 programming software (Logipam) can be used to enhance Sepam by programming specic control and monitoring functions. Only the Sepam Series 80 with a cartridge containing the Logipam SFT080 option can run the control and monitoring functions programmed by Logipam.

3
DE51891

Operating Principle

PE50257

Logipam Programming Software


The Logipam SFT2885 programming software can be used to: b adapt predened control and monitoring functions b program specic control and monitoring functions, either to replace the predened versions or to create completely new functions, to provide all the functions required by the application It is made up of: b a ladder-language program editor used to address all Sepam data and to program complex control functions b a simulator for complete program debugging b a code generator to run the program on Sepam The ladder-language program and the data used can be documented and a complete le can be printed. Offering more possibilities than the logic-equation editor, Logipam can be used to create the following functions : b specic automatic transfer functions b motor starting sequences. It is not possible to combine the functions programmed by Logipam with functions adapted by the logic-equation editor in a given Sepam. The Logipam program uses the input data from: b protection functions b logic inputs b remote control commands b local control commands transmitted by the mimic-based UMI The result of Logipam processing may then be: b assigned to a logic output, directly or via the control matrix b assigned to a LED or message via the control matrix b transmitted by the communication link, as a new remote indication b used by the predened control and monitoring functions b used to block or reset a protection function 108

SFT2885: Logipam programming software.

Characteristics Sepam Series 80

Base Unit Presentation


User-Machine Interface
Two types of User-Machine Interfaces (UMI) are available for Sepam Series 80 base units: b mimic-based UMI b advanced UMI The advanced UMI can be integrated in the base unit or installed remotely on the enclosure. Integrated and remote advanced UMIs offer the same functions. A Sepam Series 80 with a remote advanced UMI is made up of: b a base unit without any UMI, for mounting inside the LV compartment b a remote advanced UMI (DSM303) v for ush mounting on the front panel of the cubicle in the location most suitable for the facility manager v for connection to the Sepam base unit using a prefabricated CCA77x cable The characteristics of the remote advanced UMI module (DSM303) are presented on page 152.

Base units are dened according to the following characteristics: b type of User-Machine Interface (UMI) b working language b type of base unit connector b type of current sensor connector b type of voltage sensor connector

PE50472

Comprehensive Data for Facility Managers


All the data required for local equipment operation may be displayed on demand: b display of all measurement and diagnosis data in numerical format with units and/or in bar graphs b display of operating and alarm messages, with alarm acknowledgment and Sepam resetting b display of the list of activated protection functions and the main settings of major protection functions b adaptation of activated protection function set points or time delays in response to new operating constraints b display of Sepam and remote module versions b output testing and logic input status display b display of Logipam data: status of variables, timers b entry of two passwords to protect parameter and protection settings
Sepam Series 80 base unit with integrated advanced UMI.

Local Control of Devices Using the Mimic-Based UMI


The mimic-based UMI provides the same functions as the advanced UMI as well as local control of devices: b selection of the Sepam control mode b view device status on the animated mimic diagram b local opening and closing of all the devices controlled by Sepam

PE50473

Ergonomic Data Presentation


b b b b keypad keys identied by pictograms for intuitive navigation menu-guided access to data graphical LCD screen to display any character or symbol excellent display quality under all lighting conditions, such as automatic contrast setting and backlit screen (user activated)

Working Language
Sepam Series 80 base unit with mimic-based UMI.

All the texts and messages displayed on the advanced UMI or on the mimic-based UMI are available in two languages: b English, the default working language b and a second language, which may be v French v Spanish v U.S. English (ANSI) v another "local" language Please contact a representative about local language customization.

PE50127

Connecting Sepam to the Parameter Setting Tool


The SFT2841 parameter setting tool is required for Sepam protection and parameter setting. A PC containing the SFT2841 software is connected to the RS232 communication port on the front of the unit.
Customized advanced UMI.

109

Characteristics Sepam Series 80

Base Unit Presentation

Selection Guide
Base Unit
PE50260

With Remote Advanced UMI


PE50262

With Integrated Advanced UMI


PE50475

With Mimic-Based UMI

Functions
Local Indication Metering and diagnosis data Alarms and operating messages List of activated protection functions Main protection settings Version of Sepam and remote modules Status of logic inputs Logipam data Switchgear status on the animated mimic diagram Phasor diagram of currents or voltages Local Control Alarm acknowledgement Sepam reset Output testing Selection of Sepam control mode Device open/close command b b b b b b b b b b b b b b b b b b b b b b b b b b b b b b b b b b

Characteristics
Screen Size Automatic contrast setting Backlit screen Keypad Number of keys Control-mode switch LEDs Sepam operating status b base unit: 2 LEDs visible on back b remote advanced UMI: 2 LEDs visible on front 9 LEDs on remote advanced UMI b bare base unit, mounted at the back of the compartment using the AMT880 mounting plate b DSM303 remote advanced UMI module , ush mounted on the front of the cubicle and connected to the base unit with the CCA77x prefabricated cable 2 LEDs, visible from front and back 2 LEDs, visible from front and back 9 9 14 Remote / Local / Test 128 x 64 pixels b b 128 x 64 pixels b b 128 x 240 pixels b b

Indication LEDs

9 LEDs on front Flush mounted on front of cubicle

9 LEDs on front Flush mounted on front of cubicle

Mounting

110

Characteristics Sepam Series 80

Base Unit Presentation


Hardware Characteristics
Removable Memory Cartridge
The cartridge contains all the Sepam characteristics: b all Sepam protection and parameter settings b all the metering and protection functions required for the application b predened control functions b functions customized by control matrix or logic equations b functions programmed by Logipam (optional) b personalized local-control mimic diagram b accumulated energies and switchgear diagnosis values b working languages, customized and otherwise It may be made tamper-proof by lead sealing. It is removable and easy to access on the front panel of Sepam to reduce maintenance time. If a base unit malfunctions, simply: b switch off Sepam and unplug connectors b retrieve original cartridge b replace the faulty base unit by a spare base unit (without cartridge) b load the original cartridge into the new base unit b plug in the connectors and switch Sepam on again Sepam is operational, with all its standard and customized functions, without requiring any reloading of protection and parameter settings.

PE50663

Sepam Series 80 memory cartridge and backup battery.

Backup Battery
Standard lithium battery, 1/2 AA format, 3.6 Volts. It allows the following data to be stored in the event of an auxiliary power outage: b time-stamped event tables b disturbance recording data b maximum demands, tripping context, etc b date and time The battery presence and charge are monitored by Sepam. The main data (protection and parameter settings) are saved in the event of an auxiliary power outage, regardless of the state of the battery.

Auxiliary Power Supply


DC power supply voltage from 24 to 250 V DC.

Five Relay Outputs


The ve relay outputs O1 to O5 on the base unit must be connected to connector A . Each output can be assigned to a predetermined function using the SFT2841 software. O1 to O4 are 4 control outputs with one NO contact, used by default for the switchgear control function: b O1: switchgear tripping b O2: switchgear closing blocking b O3: switchgear closing b O4: available O5 is an indication output used by default for the watchdog function and has two contacts, one NC and one NO.

111

Characteristics Sepam Series 80

Base Unit Presentation


Main Connector, Voltage, and Residual Current Input Connectors
A choice of two types of removable, screw-lockable 20-pin connectors: b CCA620 screw-type connectors b or CCA622 ring lug connectors The presence of the connector is monitored.

PE50666

Connector for Additional Voltage Inputs (Sepam B83)


CCT640 connector, removable and screw-lockable. The presence of the CCT640 connector is monitored.

Phase Current Input Connectors


Current sensors connected to removable, screw-lockable connectors according to type of sensors used: b CCA630 or CCA634 connector for 1 A or 5 A current transformers b or CCA671 connector for LPCT sensors The presence of these connectors is monitored.

Mounting Accessories
Spring Clips
8 spring clips are supplied with the base unit to ush-mount Sepam in mounting plates 0.059 to 0.236 in (1.5 to 6 mm) thick. Simple, tool-free installation.

AMT880 Mounting Plate


It is used to mount a Sepam without UMI inside the compartment with access to connectors on the rear panel. Mounting used with remote advanced UMI module (DSM303).

AMT820 Blanking Plate


It lls in the space left when a standard model Sepam 2000 is replaced by a Sepam Series 80.

Spare Base Units

The following spares are available to replace faulty base units: b base units with or without UMI, without cartridge or connectors b all types of standard cartridges, with or without the Logipam option.

AMT852 Lead Sealing Accessory


The AMT852 lead sealing accessory can be used to prevent unauthorized modication of the settings of Sepam Series 80 units with integrated advanced UMIs. The accessory includes: b a lead-sealable cover plate b the screws required to secure the cover plate to the integrated advanced UMI of the Sepam unit.
Note: The AMT852 lead sealing accessory can secured only to the integrated advanced UMIs of Sepam Series 80 units Contact us to determine the serial number of the device on which you can t the lead sealing accessory.

112

Characteristics Sepam Series 80

Base Unit Description


Front Panel with Advanced UMI

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15

Green LED: Sepam on. Red LED: Sepam unavailable. 9 yellow indication LEDs. Label identifying the indication LEDs. Graphical LCD screen. Display of measurements. Display of switchgear, network and machine diagnosis data. Display of alarm messages. Sepam reset (or conrm data entry). Acknowledgement and clearing of alarms (or move cursor up). LED test (or move cursor down). Display and adaptation of activated protection settings. Display of Sepam and Logipam data. Entry of 2 passwords. RS232 PC connection port.

16 Backup battery. 17 Memory cartridge. 18 Door.

DE52687

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22

Graphical LCD screen. Green LED: Sepam on. Red LED: Sepam unavailable. Local close command. Local open command. Label identifying the indication LEDs. 9 yellow indication LEDs. Move cursor up. Conrm data entry. Move cursor down. RS232 PC connection port. Transparent door. Entry of 2 passwords. Mimic-based UMI display. Sepam reset. Display of alarm messages. Acknowledgement and clearing of alarms. Display of switchgear and network diagnosis data (or LED test). Display and adaptation of activated protection settings. Display of measurements. Display of Sepam and Logipam data. Three-position key switch to select Sepam control mode.

Front Panel with Mimic-Based UMI


DE52688

52

Ia = 175 A Vab = 6.61 kV P = 1.81 MW Q = 860 kvar

23 Backup battery. 24 Memory cartridge. 25 Door. 113

Characteristics Sepam Series 80

Base Unit Description

A 20-pin connector for:

b 24 V DC to 250 V DC auxiliary supply b 5 relay outputs.


B1 Connector for 3 phase current Ia, Ib, Ic inputs. B2 Sepam T87, M87, M88, G87, G88:

b connector for 3-phase current I'a, I'b, I'c inputs Sepam B83: b connector for v 3 phase voltage V'an, V'bn, V'cn inputs v 1 residual voltage Vr input. Sepam C86: b connector for capacitor unbalance current inputs.

C1 Modbus communication port 1. C2 Modbus communication port 2. D1 Remote module connection port 1. D2 Remote module connection port 2. E 20-pin connector for:

b phase voltage Van, Vbn, Vcn inputs b 1 residual voltage Vr input. b 2 residual current Ir, I'r inputs.
F Spare port. H1 Connector for 1st MES120 input/output module. H2 Connector for 2nd MES120 input/output module. H3 Connector for 3rd MES120 input/output module. Functional ground.

114

DE51781

1 2 3 4 5

Base unit. 8 xing points for 4 spring clips. Red LED: Sepam unavailable. Green LED: Sepam on. Gasket.

Rear Panel

Characteristics Sepam Series 80

Base Unit Technical Characteristics

Weight
Base Unit with Advanced UMI
Minimum weight (base unit without MES120) Maximum weight (base unit with 3 MES120) 5.29 lb (2.4 kg) 8.82 lb (4.0 kg)

Base Unit with Mimic-Based UMI


6.61 lb (3.0 kg) 10.1 lb (4.6 kg)

Sensor Inputs
Phase Current Inputs
Input impedance Consumption Continuous thermal withstand 1 second overload

1 A or 5 A CT
< 0.02 W < 0.02 VA (1 A CT) < 0.5 VA (5 A CT) 4 In 100 In

Voltage Inputs
Input impedance Consumption Continuous thermal withstand 1-second overload Isolation of inputs in relation to other isolated groups

Phase
> 100 k W < 0.015 VA (100 V VT) 240 V 480 V Enhanced

Residual
> 100 k W < 0.015 VA (100 V VT) 240 V 480 V Enhanced

Relay Outputs
Control Relay Outputs O1 to O4 and O x 01 (1)
Voltage Continuous current Breaking capacity DC AC (47.5 to 63 Hz) Resistive load Load L/R < 20 ms Load L/R < 40 ms Resistive load Load pf > 0.3 24/48 V DC 8A 8A/ 4A 6A/ 2A 4A/ 1A 127 V DC 8A 0.7 A 0.5 A 0.2 A 220 V DC 8A 0.3 A 0.2 A 0.1 A 100 to 240 V AC 8A

8A 5A < 15 A for 200 ms Enhanced

Making capacity Isolation of outputs in relation to other isolated groups

Annunciation Relay Output O5


Voltage Continuous current Breaking capacity Isolation of outputs in relation to other isolated groups DC AC (47.5 to 63 Hz) Load L/R < 20 ms Load pf > 0.3 24/48 V DC 2A 2A/ 1A Enhanced 127 V DC 2A 0.5 A 220 V DC 2A 0.15 A 100 to 240 V AC 2A 1A

Power Supply
Voltage Maximum consumption Inrush current Acceptable ripple content Acceptable momentary outages 24 to 250 V DC < 16 W < 10 A 10 ms 12 % 100 ms -20 % / +10 %

Battery
Format Service life 1/2 AA lithium 3.6 V 10 years Sepam energized 8 years Sepam not energized (1) Relay outputs complying with clause 6.7 of standard C 97.90 (30 A, 200 ms, 2000 operations)

115

Characteristics Sepam Series 80


Electromagnetic Compatibility
Emission Tests

Base Unit Environmental Characteristics


Standard
IEC 60255-25 EN 55022 IEC 60255-25 EN 55022 ANSI C37.90.2 IEC 60255-22-3 IEC 61000-4-3 ANSI C37.90.3 IEC 60225-22-2 IEC 61000-4-8 IEC 60255-22-6 ANSI C37.90.1 IEC 60255-22-4 IEC 61000-4-4 ANSI C37.90.1 IEC 60255-22-1 IEC 61000-4-12 IEC 61000-4-5 IEC 60255-11

Level/Class
A A

Value

Disturbing eld emission Conducted disturbance emission


Immunity Tests Radiated Disturbances

Immunity to radiated elds

III

Electrostatic discharge Immunity to magnetic elds at network frequency


Immunity Tests Conducted Disturbances

4 III A and B IV

35 V/m; 25 MHz - 1GHz 10 V/m; 80 MHz - 1 GHz 10 V/m; 80 MHz - 2 GHz 8 kV air; 4 kV contact 8 kV air; 6 kV contact 30 A/m (continuous) - 300 A/m (1-3 s) (4) 10 V 4 kV; 2.5 kHz 4 kV; 2.5 kHz/2 kV, 5 kHz 4 Kv; 2.5 KHz 2.5 kV CM; 2.5 kV DM 2.5 kV CM; 1 kV DM 2.5 kV CM; 1 kV DM 2 kV CM; 1 kV DM 100 % during 100 ms

Immunity to conducted RF disturbances Fast transient bursts

1 MHz damped oscillating wave 100 MHz damped oscillating wave Surges Voltage interruptions

III

Mechanical Robustness
In Operation

Standard
IEC 60255-21-1 IEC 60068-2-6 IEC 60255-21-2 IEC 60255-21-3 IEC 60255-21-1 IEC 60255-21-2 IEC 60255-21-2

Level/Class
2 Fc 2 2 2 2 2

Value
1 Gn; 10 Hz - 150 Hz 2 Hz - 13.2 Hz; a = 1 mm 10 Gn / 11 ms 2 Gn (horizontal axes) 1 Gn (vertical axes) 2 Gn; 10 Hz - 150 Hz 27 Gn / 11 ms 20 Gn / 16 ms

Vibrations Shocks Earthquakes


De-Energized

Vibrations Shocks Jolts

Climatic Withstand
In Operation

Standard
IEC 60068-2-1 IEC 60068-2-2 IEC 60068-2-78 IEC 60068-2-52 IEC 60068-2-60 IEC 60068-2-60

Level/Class
Ad Bd Cab Kb/2

Value
-25 C +70 C 10 days; 93 % RH ; 40 C 6 days 21 days; 75 % RH; 25 C; 0.5 ppm H2S; 1 ppm SO2 21 days; 75 % HR; 25 C; 0.01 ppm H2S; 0.2 ppm SO2; 0.2 ppm NO2; 0.01 ppm Cl2 -25 C at +70 C; 5 C/min -25 C +70 C 56 days; 93 % RH; 40 C 6 days; 95 % RH; 55 C

Exposure to cold Exposure to dry heat Continuous exposure to damp heat Salt mist Inuence of corrosion/Gas test 2 Inuence of corrosion/Gas test 4
In Storage (3)

Temperature variation with specied variation rate Exposure to cold Exposure to dry heat Continuous exposure to damp heat

IEC 60068-2-14 IEC 60068-2-1 IEC 60068-2-2 IEC 60068-2-78 IEC 60068-2-30

Nb Ab Bb Cab Db

Safety
Enclosure Safety Tests

Standard
IEC 60529 NEMA IEC 60695-2-11 IEC 60255-5 ANSI C37.90 IEC 60255-5 EN 50263 harmonized standard

Level/Class
IP52 Type 12

Value
Other panels IP20 650 C with glow wire 5 kV (1) 1 kV 1 mn (indication output) 1.5 kV 1 mn (control output) 2 kV 1 mn(2)

Front panel tightness Fire Resistance


Electrical Safety Tests

1.2/50 s pulse wave Power frequency dielectric withstand

Certication
e

European directives: b 89/336/EEC Electromagnetic Compatibility (EMC) Directive 92/31/EEC Amendment 93/68/EEC Amendment b 73/23/EEC Low Voltage Directive 93/68/EEC Amendment UL UL508 - CSA C22.2 n 14-95 File E212533 CSA CSA C22.2 n 14-95 / n 94-M91 / n 0.17-00 File 210625 (1) Except for communication: 3 kV in common mode and 1 kV in differential mode. (2) Except for communication: 1 kVrms. (3) Sepam must be stored in its original packing. (4) Iso > 0.1 INr for the 50N/51N and 67N protection functions, with Ir calculated as the sum of the phase currents.

116

Connection Diagrams Sepam Series 80

Base Unit Dimensions

DE80070

in. (mm)
DE52760

Dimensions
in. (mm) 1.57 (40)

8.74 (222)
9.49 7.87 (241) (200)

10.39 (264)

Front view of Sepam

1.57 (40) 1.57 (40) 7.28 (185)

Side view of Sepam with MES120, ush-mounted in front panel with spring clips. Front panel: 0.05 in to 0.23 in (1.5 mm to 6 mm) thick Clearance for Sepam assembly and wiring.

DE52761

in. (mm)
DE52762

in. (mm)

9.80 (249)

7.95 (202)
7.28 (185) 4.41 (112) 2.53 (64.2)

9.84 (250)

Cut-out.

10.39 (264)

1.00 (25.5)

Top view of Sepam with MES120, ush-mounted in front panel with spring clips. Front panel: 0.05 in to 0.23 in (1.5 mm to 6 mm) thick

Assembly with AMT880 Mounting Plate


0.26 (6.5)
DE52763

1.57 (40) 1.57 (40) 7.95 (202) 1.57 (40) 1.57 (40) 1.57 (40) 9.69 (246)

DE80075

in. (mm)

in. (mm)

8.43 (214) 5.55 (141)

9.84 (250)

11.97 (304)

0.39 (10)

0.91 (23)

12.76 (324)

Top view of Sepam with MES120, ush-mounted in front panel with spring clips. Mounting plate: 0.11 in (3 mm) thick.

AMT880 mounting plate

117

Connection Diagrams Sepam Series 80

Base Unit Sepam Series 80

DE52813

a b c

CCA634

Ia Ib Ic

Van Vbn Vcn

(<11.8 ft, 3 m)

CCA634

Ia Ib Ic Ir
Functional ground

118

Connection Diagrams Sepam Series 80

Base Unit Connection


Connection Characteristics

Connector
A , E

Type
Screw-type

Reference
CCA620

Wiring
b wiring with no ttings : v 1 wire with max. cross-section 0.2 to 2.5 mm ( AWG 24-12) or 2 wires with max. cross-section 0.2 to 1 mm ( AWG 24-16) v stripped length: 8 to 10 mm (.31 in to .39 in) b wiring with ttings: v recommended wiring with Telemecanique ttings: - DZ5CE015D for 1 x 1.5 mm wire (AWG 16) - DZ5CE025D for 1 x 2.5 mm wire (AWG 12) - AZ5DE010D for 2 x 1 mm wires (AWG 18) v wire length: 8.2 mm (0.32 in) v stripped length: 8 mm (0.31 in) b 6.35 mm ring or spade lugs (1/4) b maximum wire cross-section of 0.2 to 2.5 mm ( AWG 24-12) b stripped length: 6 mm (.24 in) b use an appropriate tool to crimp the lugs on the wires b maximum of 2 ring or spade lugs per terminal b tightening torque: 1.2 nm (13.27 lb-in) CCA612 CCA770: L = 0.6 m (2 ft) CCA772: L = 2 m (6.6 ft) CCA774: L = 4 m (13.1 ft) CCA785 for MCS025 module: L = 2 m (6.6 ft) Grounding braid, to be connected to cubicle grounding: b at copper braid with cross-section u 9 mm b maximum length: 300 mm (11.8 in) b wire cross-section 1.5 to 6 mm (AWG 16-10) b tightening torque: 1.2 Nm (13.27 lb-in) Integrated with LPCT sensor

6.35 mm ring lugs

CCA622

C1 , C2 D1 , D2

Green RJ45 plug Black RJ45 plug

DE51845

Ring lug Functional ground B1 , B2 4 mm ring lugs RJ45 plug CCA630, CCA634 for connection of 1 A or 5 A CTs CCA671, for connecting three LPCT sensors

CAUTION
LOSS OF PROTECTION OR RISK OF NUISANCE TRIPPING If the Sepam is no longer supplied with power or is in fail-safe position, the protection functions are no longer active and all the Sepam output relays are dropped out. Check that this operating mode and the watchdog relay wiring are compatible with your installation. Failure to follow this instruction can result in equipment damage and unwanted shutdown of the electrical installation.

DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION OR ARC FLASH b Only qualied personnel should install this equipment. Such work should be performed only after reading this entire set of instructions b NEVER work alone b Before performing visual inspections, tests, or maintenance of this equipment, disconnect all sources of electric power. Assume that all circuits are live until they have been completely de-energized, tested, and tagged. Pay particular attention to the design of the power system. Consider all sources of power, including the possibility of backfeeding b Always use a properly rated voltage sensing device to conrm that all power is off b Start by connecting the device to the protective ground and to the functional ground b Screw tight all terminals, even those not in use Failure to follow these instructions will result in death or serious injury.

119

Connection Diagrams Sepam Series 80

Base Unit Sepam B83

DE52814

a b c

Ia Ib Ic

Van Vbn Vcn

(<11.8 ft, 3 m)

Va Vb Vc
a b c

Vr
Functional ground

Connection Characteristics
Connector
B1 B2

Type
4 mm ring lugs Screw-type

Reference
CCA630, for connection of 1 A or 5 A CTs CCT640 : see Page 126.

Wiring
1.5 to 6 mm (AWG 16-10) VT wiring: same as wiring for the CCA620 Grounding connection: by 4 mm ring lug

For connectors A , E , C1 , C2 , D1 , D2 ,

CAUTION
LOSS OF PROTECTION OR RISK OF NUISANCE TRIPPING If the Sepam is no longer supplied with power or is in fail-safe position, the protection functions are no longer active and all the Sepam output relays are dropped out. Check that this operating mode and the watchdog relay wiring are compatible with your installation. Failure to follow this instruction can result in equipment damage and unwanted shutdown of the electrical installation.

DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION OR ARC FLASH b Only qualied personnel should install this equipment. Such work should be performed only after reading this entire set of instructions. b NEVER work alone. b Before performing visual inspections, tests, or maintenance of this equipment, disconnect all sources of electric power. Assume that all circuits are live until they have been completely de-energized, tested, and tagged. Pay particular attention to the design of the power system. Consider all sources of power, including the possibility of backfeeding b Always use a properly rated voltage sensing device to conrm that all power is off. b Start by connecting the device to the protective ground and to the functional ground. b Screw tight all terminals, even those not in use. Failure to follow these instructions will result in death or serious injury.

120

Connection Diagrams Sepam Series 80

Base Unit Sepam C86

a
DE52815

b c

3
CCA634

Ia Ib Ic Ir

Van Vbn Vcn Vr


(<11.8 ft, 3 m)

CCA634

Ia Ib Ic Ir
Functional ground

Connector
B1

Type
4 mm ring lugs RJ45 plug

Reference
CCA630, for connection of 1 A or 5 A CTs CCA671, for connection of 3 LPCT sensors CCA630, for connection of 1 A, 2A or 5 A CTs

Wiring
1.5 to 6 mm (AWG 16-10) Integrated with LPCT sensor 1.5 to 6 mm (AWG 16-10) Grounding braid, to be connected to cubicle grounding: b at copper braid with cross-section 9 mm b maximum length: 300 mm

B2 Functional ground

4 mm ring lugs Ring lugs

For connectors A , E , C1 , C2 , D1 , D2 ,

: see Page 127.

121

Connection Diagrams Sepam Series 80

Base Unit Phase Current Inputs

3
DE80089

Variant 1: Phase Current Measurement by 3 x 1 A or 5 A CTs (standard connection)


a b c
CCA630/ CCA634

Connection of 3 x 1 A or 5 A sensors to the CCA630 connector. Measuring the three phase currents allows the calculation of residual current.
Ia Ib Ic

Parameters
Sensor type Number of CTs Rated current (In) 5 A CT or 1 A CT Ia, Ib, Ic 1 A to 6250 A

Variant 2: Phase Current Measurement by 2 x 1 A or 5 A CTs


a
DE52773

Connection of two 1 A or 5 A sensors to the CCA630 connector. Measuring phase a and c currents is sufcient for all protection functions based on phase current. This arrangement does not allow the calculation of residual current, nor use of ANSI 87T and 87M differential protection functions on the Sepam T87, M87, M88, G87 and G88. Parameters
Sensor type Number of CTs Rated current (In) 5 A CT or 1 A CT Ia, Ic 1 A to 6250 A

Ia Ib Ic

Variant 3: Phase Current Measurement by three LPCT type sensors


a
DE51790

c a Ia b Ib c Ic

Connecting three Low Power Current Transducer (LPCT) type sensors to the CCA671 connector. Sepam goes into fail-safe position if less than three sensors are connected. Measuring the three phase currents allows the calculation of residual current. The IN parameter, primary rated current measured by an LPCT, is to be chosen from the following values, in Amps: 25, 50, 100, 125, 133, 200, 250, 320, 400, 500, 630, 666, 1000, 1600, 2000, 3150. The parameter is set in the SFT2841 software. It is completed by hardware setting of the microswitches on the CCA671 connector. It is not possible to use LPCT sensors for the following measurements: b phase-current measurements for Sepam T87, M88 and G88 with ANSI 87T transformer differential protection (connectors B1 and B2 ) b phase-current measurements for Sepam B83 (connector B1 ) b unbalance-current measurements for Sepam C86 (connector B2 ). Parameters
Sensor type Number of CTs Rated current (In) LPCT Ia, Ib, Ic 25, 50, 100, 125, 133, 200, 250, 320, 400, 500, 630, 666, 1000, 1600, 2000 or 3150 A

Note: Parameter IN must be set twice: b Software parameter setting using the advanced UMI or the SFT2841 software tool b Hardware parameter setting using microswitches on the CCA671 connector

122

Connection Diagrams Sepam Series 80

Base Unit Residual Current Inputs

Variant 1: Residual Current Calculation by Sum of Three Phase Currents


Description Residual current is calculated by the vector sum of the three phase currents Ia, Ib, and Ic, measured by three 1 A or 5 A CTs or by three LPCT type sensors. See current input connection diagrams. Parameters
Residual Current Sum of three Is Rated Residual Current INr = IN, CT primary current Measuring Range 0.01 to 40 INr (minimum 0.1 A)

Variant 2: Residual Current Measurement by CSH120 or CSH200 Zero Sequence CT (standard connection)
a
DE80083

Description Arrangement recommended for the protection of isolated or compensated neutral systems, in which very low fault currents need to be detected. Parameters
Residual Current 2 A rating CSH 20 A rating CSH Rated Residual Current INr = 2 A INr = 20 A Measuring Range 0.1 to 40 A 0.2 to 400 A

Variant 3: Residual Current Measurement by 1 A or 5 A CTs and CCA634


a
DE80086

c Ia Ib Ic

Description Residual current measurement by 1 A or 5 A CTs b Terminal 7: 1 A CT b Terminal 8: 5 A CT Parameters


Residual Current 1 A CT 5 A CT Rated Residual Current INr = IN, CT primary current INr = IN, CT primary current Measuring Range 0.01 to 20 INr (minimum 0.1 A) 0.01 to 20 INr (minimum 0.1 A)

a
DE80087

Ia Ib Ic

123

Connection Diagrams Sepam Series 80

Base Unit Residual Current Inputs

3
DE52848

Variant 4: Residual Current Measurement by 1 A or 5 A CTs and CSH30 Interposing Ring CT


a b c

Description The CSH30 interposing ring CT is used to connect 1 A or 5 A CTs to Sepam to measure residual current: b CSH30 interposing ring CT connected to 1 A CT: make 2 turns through CSH primary b CSH30 interposing ring CT connected to 5 A CT: make 4 turns through CSH primary.
Ir Ir

Parameters
Residual Current 1 A CT 5 A CT Rated Residual Current INr = IN, CT primary current INr = IN, CT primary current Measuring Range 0.01 to 20 INr (minimum 0.1 A) 0.01 to 20 INr (minimum 0.1 A)

a
DE52849

Ia Ib Ic

Ir Ir

Variant 5: Residual Current Measurement by Zero Sequence CT with Ratio of 1/n (n between 50 and 1500)
DE80102

Description The ACE990 is used as an interface between a MV zero sequence CT with a ratio of 1/n (50 y n y 1500) and the Sepam residual current input. This arrangement allows the continued use of existing zero sequence CTs on the installation. Parameters
Residual Current Rated Residual Current Measuring Range 0.01 to 20 INr (minimum 0.1 A) ACE990 - range 1 INr = Ik.n (1) (0.00578 k 0.04) ACE990 - range 2 INr = Ik.n (1) 0.01 to 20 INr (minimum 0.1 A) (0.00578 k 0.26316) (1) n = number of zero sequence CT turns k = factor to be determined according to ACE990 wiring and setting range used by Sepam

124

Connection Diagrams Sepam Series 80

Phase Voltage Inputs Residual Voltage Input Main Channels


Phase Voltage Input Connection Cariants

Variant 1: Measuring three line-to-neutral voltages (3 VLn, standard connection)


a
DE51795 DE51796

Variant 2: Measuring two line-to-line voltages (2 VLL)

a b c

b c

Van Vbn Vcn

Van Vbn Vcn

Measurement of the three line-to-neutral voltages allows the calculation of residual voltage, Vr

This variant does not allow the calculation of residual voltage

Variant 3: Measuring one line-to-line voltage (1 VLL)


a
DE51797

Variant 4: Measuring one line-to-neutral voltage (1 VLn)


a
DE51798

b c

b c

Van Vbn Vcn

Van Vbn Vcn

This variant does not allow the calculation of residual voltage

This variant does not allow the calculation of residual voltage

Residual Voltage Input Connection Variants


Variant 5: Measuring residual voltage Vr
a
DE51799 DE51800

Variant 6: Measuring residual voltage VLnt in generator neutral point


a b c

b c

Van Vbn Vcn

Van Vbn Vcn

125

Connection Diagrams Sepam Series 80

Phase Voltage Inputs Residual Voltage Input Additional Channels for Sepam B83
Additional Phase Voltage Input Connection Variants

3
Variant 1: Measuring three line-to-neutral voltages (3 VLn, standard connection)
a
DE51801

Variant 2: Measuring two line-to-line voltages (2 VLL)

c
DE51802

Van Vbn Vcn

Van Vbn Vcn

Measurement of the 3 line-to-neutral voltages allows the calculation of residual voltage, Vr

This variant does not allow for calculating residual voltage

Variant 3: Measuring one line-to-line voltage (1 VLL)


a
DE51803

Variant 4: Measuring one line-to-neutral voltage (1 VLn)


a
DE51804

Van Vbn Vcn

Van Vbn Vcn

This variant does not allow for calculating residual voltage.

This variant does not allow for calculating residual voltage.

Additional Residual Voltage Input Connection


Variant 5: Measuring Residual Voltage Vr
a
DE51805

Van Vbn Vcn

126

Connection Diagrams Sepam Series 80

Phase Voltage Inputs Residual Voltage Input Additional Channel for Sepam B80
Connecting to Measure One Additional Voltage
a
DE51899

b c

Van Vbn Vcn

This connection should be used to measure: b three line-to-neutral voltages Van, Vbn, Vcn on bus number 1 b one additional line-to-neutral voltage Van (or one additional line-to-line voltage V'ab) on bus number 2

a
DE51898

b c

Van Vbn Vcn

This connection should be used to measure: b two line-to-line voltages Vab, Vbc, and one residual voltage Vr on bus number 1 b one additional line-to-line voltage V'ab (or one additional line-to-neutral voltage Van) on bus number 2.

127

Connection Diagrams Sepam Series 80

Phase Voltage Inputs Residual Voltage Input Available Functions


The availability of certain protection and metering functions depends on the phase and residual voltages measured by Sepam. The table below gives the voltage input connection variants for which for each protection and metering function dependent on measured voltages is available. For example, the directional overcurrent protection function (ANSI 67N/67NC) uses residual voltage Vr as a polarization value. It is therefore operational in the following cases: b measuring the three line-to-neutral voltages and calculating Vr (3 V + Vr, variant 1) b measuring residual voltage Vr (variant 5). The protection and metering functions which do not appear in the table below are available regardless of the voltages measured.

Phase Voltages Measured (Connection Variant) Residual Voltage Measured (Connection Variant) Protection Functions Dependent on Voltages Measured

3 V + Vr (var. 1) Vr (v. 5) VLnt (v. 6)

2 VLL (var. 2) Vr (v. 5) VLnt (v. 6)

1 VLL (var. 3) Vr (v. 5) VLnt (v. 6)

1 VLn (var. 4) Vr (v. 5) VLnt (v. 6)

Directional phase overcurrent Directional ground fault Directional active overpower Directional reactive active overpower Directional active underpower Field loss (underimpedance) Pole slip, phase shift Voltage-restrained overcurrent Underimpedance Inadvertent energization 100 % stator ground fault Overexcitation (V/Hz) Positive sequence undervoltage Remanent undervoltage Undervoltage (LL or LN) Overvoltage (LL or LN) Neutral voltage displacement Negative sequence overvoltage Overfrequency Underfrequency Rate of change of frequency
Measurements Dependent on Voltages Measured

67 67N/67NC 32P 32Q 37P 40 78PS 50V/51V 21B 50/27 64G2/27TN 24 27D 27R 27 59 59N 47 81H 81L 81R

b b b b b b b b b b b bv bv bv bv bv bv bv bv b bv bv

b b b b b b b b b b b bv bv bv bv bv bv bv bv b bv bv

b b b b b b b b b b b b b b b b b b b b b b b

b b b b b b b b b b bv bv bv bv b bv bv b bv

b b b b b b b b b b b bv bv bv bv bv bv bv bv b bv b

b b b b b b b b b b b b b b b b b b b b b bv b

b bvU bvU bvU

b b b b b v v v v

b b b b b b b

b bvU bvU bvU

b b b b b b b b v v v v v v v

b b b b b b b

bvU bvU

bv bv

bvU bvU

Line-to-line voltage Vab, Vbc, Vac or V'ab, V'bc, V'ac Line-to-neutral voltage Van, Vbn, Vcn, or Van, Vbn, Vcn Residual voltage Vr or Vr

Vab, V'ab

Vab

Vab Van, Van Van, Van bv Van

bv bv b bv b b Neutral point voltage VLnt b b Third harmonic neutral point or residual voltage bv bv b bv bv b Positive sequence voltage V1 or V1 / negative sequence voltage V2 or V2 bv bv bv bv bv bv bvU Frequency b b b b b b b Active/reactive/apparent power: P, Q, S b b b b b b b Maximum demand power Pmax, Qmax Active / reactive / apparent power per phase : b (1) b (1) b (1) b (1) Pa/Pb/Pc, Qa/Qb/Qc, Sa/Sb/Sc b b b b b b b Power factor b b b b b b b Calculated active and reactive energy (Wh, VARh) b b b b b b b Total harmonic distortion, voltage Vthd b b b b Phase displacement r, r b b b b b b Phase displacement a, b, c b b b b b b Apparent positive sequence impedance Z1 b b b b b b Apparent line-to-line impedances Zab, Zbv, Zac b Function available on main voltage channels. v Function available on Sepam B83 additional voltage channels. U Function available on Sepam B80 additional voltage channel, according to the type of the additional voltage measured. (1) If all three phase currents are measured

bv b b bv b b bv b b bvU

b b bv bv

Pa/ Qa/Sa b b b b b b b

Pa/ Qa/Sa

Pa/ Qa/Sa

128

Sepam Series 20 Sepam Series 40 Sepam Series 80

Additional Modules and Accessories

Software
Sepam Software SFT2841 Setting and Operating Software
Function SFT2841 Connection to Sepam Adapting the Predened Functions

131
131 132
132 134 135

SFT2826 Disturbance Recording Data Display Software SFT850 Conguration Software for IEC 61850 Protocol SFT2885 Programming Software - Logipam

136 137 138

Logic Input/Output Modules


MES114 Modules Logic Input/Output Assignment of Sepam Series 20 Logic Input/Output Assignment of Sepam Series 40 MES120, MES120G, MES120H 14 Input/6 Output Module
Presentation Installation Logic Input/Output Assignment

140
140 142 143 144
144 145 146

Remote Modules
Selection Guide and Connection MET1482 Temperature Sensor Module MSA141 Analog Output Module DSM303 Remote Advanced UMI Module MCS025 Synchro-Check Module

148
148 149 151 152 154

Communication Accessories
Selection Guide

158
158

Communication Interfaces
Communication Interface Connection ACE9492 2-wire RS485 Network Interface ACE959 4-wire RS485 Network Interface ACE937 Fiber Optic Interface ACE969TP and ACE969FO Interfaces Network
Description Connection

159
159 160 161 162 163
165 166

129

Sepam Series 20 Sepam Series 40 Sepam Series 80

Additional Modules and Accessories


Converters
ACE9092 RS232 / RS485 Converter ACE919CA and ACE919CC RS485 / RS485 Converters Sepam ECI850 Server for IEC 61850 Ethernet EGX100 Gateway Ethernet EGX400 Server WPG Software Tool HTML Page Generator

168
168 170 172 176 177 180

Sensors
Selection Guide Voltage Transformers 1 A / 5 A Current Transformers LPCT Type Current Sensors
Test Accessories

181
181 182 183 186
187

CSH120 and CSH200 Zero Sequence CTs CSH30 Interposing Ring CT ACE990 Zero Sequence CT Interface

189 191 192

130

Software

Sepam Software

Presentation

Four types of Sepam PC software are available: b SFT2841 setting and operating software b SFT2826 disturbance recording data display software b SFT2885 programming software for the Sepam Series 80 (Logipam) b SFT850 advanced-conguration software for IEC 61850 protocol

SFT2841 and SFT2826 Software


SFT2841 and SFT2826 software is provided on the same CD-ROM as the Sepam documentation in PDF format.

PC Connection Cable
The CCA783 PC connection cable (ordered separately) is designed to connect a PC to the RS232 port on the front panel of a Sepam unit in order to use the SFT2841 software in point-to-point connected mode. The USB/RS232 TSXCUSB232 converter may be used with the CCA783 connection cable for connection to a USB port.

SFT2885 Software
SFT2885 is available on a separate CD-ROM.

SFT850 Software
SFT850 is available on a separate CD-ROM

Minimum Conguration Required


SFT2841 and SFT2826 Software
Operating systems RAM Space on disk Microsoft 2000/XP 128 MB (32 MB for Windows 98) 120 MB

SFT2885
Operating systems RAM Space on disk Microsoft 2000/XP 64 MB 20 MB

SFT850
Operating systems RAM Space on disk Microsoft 2000/XP 64 MB 40 MB

131

Software

SFT2841 Setting and Operating Software Function


The SFT2841 software is the setting and operating tool for Sepam Series 20, Series 40, and Series 80. It may be used: b prior to commissioning and without connection to Sepam, to prepare Sepam protection and parameter settings b during commissioning, on a PC connected point-to-point to the front panel Sepam: v to load, unload and modify Sepam protection and parameter settings v to obtain all measurements and useful information during commissioning b during operation, on a PC connected to a set of Sepam relays via an E-LAN multipoint communication network: v to manage the protection system v to monitor the status of the electrical network v to run diagnostics on any incidents affecting the electrical network

PE50540

Preparation of Sepam Parameter and Protection Settings in Unconnected Mode


b b b b conguration of Sepam and optional modules, and entry of general settings enabling/disabling of functions and entry of protection settings adaptation of predened control and monitoring functions creation of personalized mimic diagrams for local display

Sepam Commissioning via a Point-to-Point Connection to the Front Panel


b access to all functions available in unconnected mode, after entering the protectionsetting or parameter-setting password b transfer of Sepam parameter and protection setting le, prepared in unconnected mode (downloading function), protected by the parameter-setting password b display of all measurements and useful information during commissioning b display of logic input, logic output and LED status b test of logic outputs b display of Logipam variables b setting of Logipam parameters (conguration bits, timers, etc.) b modication of passwords

SFT2841: Sepam Series 80 hardware conguration.

PE50304

Management of Protection Functions and Network Diagnostics with an E-LAN Multipoint Network Connection
b reading all Sepam protection and parameter settings, with modications following entry of the protection-setting or parameter-setting password b display of all the Sepam measurement data b display of Sepam, switchgear and network diagnosis data b display of time-stamped alarm messages b retrieval of disturbance recording data

SFT2841: output testing.

Efcient, Easy-to-Use Software


b b b b b menus and icons for fast, direct access to the data required guided navigation to go through all the data input screens in the natural order all data on the same function together in the same screen trilingual software: English, French, Spanish on-line help, with all the technical information needed to use and implement Sepam b familiar le management in Microsoft Windows environment: v all le management services included: copy / paste, save, etc. v printing parameter and protection settings in standard layout

PE50274

SFT2841: alarm history.

132

Software

SFT2841 Setting and Operating Software Function


The table below gives the SFT2841 functions available for the Sepam Series: Sepam Series 20, Series 40, and Series 80. NC: function available in unconnected mode. S: function available with SFT2841 connected via Sepam front panel. E: function available with SFT2841 connected to Sepam via E-LAN communication network.

PE50302

Functions
Management
On-line help Managing parameter and protection setting les: creation, saving, downloading and uploading Downloading and uploading parameter and protection setting les Exporting parameter and protection settings in a text le Printing parameter and protection settings Modifying passwords, one for parameter setting and one for protection setting

Series 20 Series 40 Series 80


NC
b b

S
b b

E
b b

NC
b b

S
b b

E
b b

NC
b b

S
b b

E
b b

b b b b b b

b b b b b

b b b b

b
(1)

SFT2841: Sepam Series 80 sensor parameter setting.

b b

PE50541

Sepam Parameter Setting


Displaying parameter settings Hardware conguration and parameter entry protected by parameter setting password Graphical parameter setting assistance Standard conguration for IEC 61850 network b b b b b b b b b b b b b b b b b b b b b b b 100 10 b b b b b b b 30 b b b b b b b b b b b 200 20 b b b b b b b b b b b b b b b b b b b b b b b b b b b b b b b b b b b b b b

b b b

b b b

b b b

b b b

b b b

b b b

Protection Setting
Displaying protection settings Entry of protection settings, protected by protection setting password Dening customized tripping curve

Adapting Predened Functions


SFT2841: Sepam Series 80 application, with protection function measurement origin. Display and modication of the control matrix Logic equation editing Number of instructions Number of dedicated remote indications Display of logic equations Load the Logipam program Setting of Logipam parameters Assignment of LEDs on front Editing user messages Number of user messages Editing of personalized mimic diagram Display of all Sepam measurement data Display of switchgear diagnosis assistance data Display of machine operating assistance data Display of time-stamped alarm messages
PE50276

PE50275

100 b b b b b b b b b b b b b b b b b b b b b b b b b b b b b b b b

Assistance in Commissioning and Operating the Installation


b b b b b b b b b b b b b b b b b b b b

SFT2841: protection settings.

Tripping context Retrieval of disturbance recording les Display of Logipam variables Display of logic input/output status Output testing Sepam diagnosis

(1) Except for logic equations and personalized messages.

SFT2841: Sepam diagnosis.

133

Software

SFT2841 Setting and Operating Software SFT2841 Connection to Sepam


SFT2841 Connection to the Front Panel of a Sepam
Connection of the PC RS232 serial port to the communication port on the front panel of Sepam Series 20, Series 40, or Series 80 using the CCA783 cable or the USB/RS232 (TSXCUSB232) converter + CCA783.
Sepam Series 80
DE52069 DE53111

SFT2841 Connection to a Set of Sepam Relays


The SFT2841 can be connected to a set of Sepam relays, themselves connected to a E-LAN communication network in one of the three architectures presented below. These connections do not require any further software development work. Ethernet Connection b connection a set of Sepam to a Modbus RS485 network b Ethernet RS485 link via the EGX100 or EGX400 gateway or the ECI850 server b connection of the PC via its Ethernet port. RS485 Serial Connection b connection a set of Sepam to a Modbus RS485 network b connection of the PC via its RS232 port, using the ACE9092 interface. Telephone-Line Connection b connection a set of Sepam to a Modbus RS485 network b RS485-RTC link via an RS485 modem (Wertermo TD-34 for example) b connection of the PC via its modem port.

DE53108

DE53109

Sepam Series 20

Sepam Series 20

Sepam Series 20

DE53110

Sepam Series 20

Sepam Series 40

Sepam Series 40

Sepam Series 40

Sepam Series 40

Sepam Series 80

Sepam Series 80

Sepam Series 80

Sepam Series 80

134

Software

SFT2841 Setting and Operating Software Adapting the Predened Functions


Logic Equation Editor (Sepam Series 40 and Series 80)
The logic equation editor included in the SFT2841 software can be used to: b complete protection function processing: v additional interlocking v conditional blocking/validation of functions b adapt predened control functions: particular circuit breaker or recloser control sequences
Note: the use of the logic equation editor excludes the possibility of using the Logipam programming software.

PE50277

SFT2841: logic equation editor.

A logic equation is created by grouping logic input data received from: b protection functions b logic inputs b local control commands transmitted by the mimic-based UMI b remote control commands This grouping is accomplished by using the Boolean operators AND, OR, XOR, NOT, and automation functions such as time delays, bi-stables and time programmer. Equation input is assisted and syntax checking is done systematically. The result of an equation may then be: b assigned to a logic output, LED or message from the control matrix b transmitted by the communication link, as a new remote indication b utilized by the circuit breaker/contactor control function to trip, close or block breaking device closing b used to block or reset a protection function

Alarms and Operating Messages (Sepam Series 40 and Series 80)


New alarm and operating messages may be created using the SFT2841 software. The new messages are added to the list of existing messages and may be assigned via the control matrix for display: b on Sepams advanced UMI b in the SFT2841 Alarms and Alarm History screens

Local-Control Mimic Diagram (Sepam Series 80)


Main #2

52

Ia = 175 A Vab = 6.61 kV P = 1.81 MW Q = 860 kvar

The local-control mimic diagram displayed on the UMI can be personalized by adapting one of the supplied, predened mimic diagrams or by creating a diagram from scratch. The mimic-diagram editor can be used to: b create a xed, bitmap background (128 x 240 pixels) using a standard drawing tool b create animated symbols or use predened animated symbols to represent the electrotechnical devices or other objects b assign the logic inputs or internal status conditions that modify the animated symbols. For example, the logic inputs for the circuit-breaker position must be linked to the circuit-breaker symbol to enable the display of the open and closed conditions b assign the logic outputs or internal status conditions that are activated when an opening or closing command are issued for the symbol b display the current, voltage and power measurements on the mimic diagram

PE50542

SFT2841: mimic-diagram editor.

Control Matrix
PE50305

The control matrix is used for simple assignment of data from: b protection functions b control and monitoring functions b logic inputs b logic equations or the Logipam program to the following output data: v logic outputs v 9 LEDs on the front of Sepam v messages for local display v triggering of disturbance recording

SFT2841: control matrix.

135

Software

SFT2826 Disturbance Recording Data Display Software


Function

The SFT2826 software is used to display, analyze, and print disturbance data recorded by Sepam. It uses COMTRADE (IEEE standard: Common format for transient data exchange for power systems) les.

Mt10623

Transferring Disturbance Recording Data


Before they are analyzed by SFT2826, the disturbance recording data must be transferred from Sepam to the PC: b by the SFT2841 software b or by the Modbus communication link

Analysis of Disturbance Recording Data


SFT2826: analysis of a disturbance data record.

b b b b b

selection of analog signals and logic data for display zoom and measurement of time between events display of all numerical values recorded exporting of data in le format printing of curves and/or numerical values recorded

Characteristics

The SFT2826 software comes with the SFT2841 software: b four languages: English, French, Spanish, Italian b on-line help with description of software functions

136

Software

SFT850 Conguration Software for IEC 61850 Protocol


Function

The SFT850 software is used to easily create, modify and consult the SCL (Substation Conguration Language) conguration les for the IEC 61850 communication protocol: b CID (Congured IED Description) le for conguration of a device connected to an IEC 61850 network b SCD (Substation Conguration Description) le for IEC 61850 conguration of substation equipment. The SFT850 software supplements the standard IEC 61850 conguration created with the SFT2841 software in cases where the conguration must be precisely adapted to system requirements. Adding or Deleting Equipment The SFT850 software can be used to add or delete connected equipment in the IEC 61850 conguration. If a Sepam unit is added, the software uses the supplied ICD (IED Capability Description) le to start conguration. Equipment Connection The SFT850 software describes the data for equipment connection to the network. Editing the Equipment Conguration The conguration of a given device described in a CID or SCD le can be modied in the following ways: b add, modify or delete datasets. A dataset is used to group data and optimized communication b add, modify or delete RCBs (Report Control Block). A Report Control Block denes dataset transmission conditions b add, modify or delete GCBs (Goose Control Block). A Goose Control Block denes how data is exchanged between Sepam units b modify dead measurement bands. This parameter is used to optimize communication in that measurements are transmitted only if they have changed signicantly Generating CID les The SFT850 software can generate the CID le for each device on the basis of an SCD le.

137

Software

SFT2885 Programming Software Logipam


Function
The SFT2885 programming software (called Logipam) is a special option intended exclusively for the Sepam Series 80 and can be used to: b adapt predened control and monitoring functions b program specic control and monitoring functions, either to replace the predened versions or to create completely new functions, to provide all the functions required by the application. It is made up of: b a ladder-language program editor used to address all Sepam data and to program complex control functions b a simulator for complete program debugging b a code generator to run the program on Sepam The ladder-language program and the data used can be documented and a complete le can be printed. Only the Sepam Series 80 with a cartridge containing the Logipam SFT080 option can run the control and monitoring functions programmed by the Logipam SFT2885 software. The complete Logipam software is made up of the executable program run by Sepam and the source program that can be modied by the Logipam SFT2885 programming software. The SFT2841 setting and operating software, required for implementation of the Logipam program, offers the following functions: b association of the complete Logipam program with the Sepam parameter and protection settings b loading and unloading of Logipam program, parameters and settings in the Sepam cartridge b running functions programmed with Logipam: v display of the status of Logipam internal bits v setting Logipam parameters: conguration bits, timers

Operating Principle
DE52073

138

Software

SFT2885 Programming Software Logipam


Characteristics

PE50257

Program Structure
A ladder-language program is made up of a series of rungs executed sequentially: b maximum 1000 lines with 9 contacts and 1 coil maximum per line b with a maximum total number of 5000 contacts and coils Comments can be made for each line. Sections The program can be broken down into sections and subsections to clarify the structure and facilitate reading. It is possible to set up three levels of sections. Comments can be added for each section, and execution of each section can be subjected to conditions. Variable Editor Each variable is dened by a xed identier and can be linked to a name or a comment. The programmer can decide to work directly with the identiers or with the linked names. The list of the variables used and the cross references can be consulted during programming.

SFT2885: ladder-language program, structured in sections

PE50265

Graphic Elements in the Ladder Language


The graphic elements are the instructions in the ladder language: b NO and NC contacts b rising and falling-edge detection contacts b direct or negated coils b set and reset coils b coils and contacts linked to timers, counters and clocks

Available Resources
Sepam Variables All the data used by Sepam functions can be addressed by Logipam: b all logic inputs and outputs b all remote-control commands and remote indications (the remote-control commands and remote indication used in the Logipam program are no longer used by the predened functions) b all protection-function inputs and outputs b all inputs and outputs for the predened control and monitoring functions b all inputs and outputs for symbols in the mimic-based UMI b all system data Logipam Internal Variables b 64 conguration bits to parameter program processing, settable via the SFT2841 software and the display b 128 bits used by the control matrix to control LEDs, messages and logic outputs b 128 internal bits that are saved b 512 internal bits that are not saved Logipam Functions b 60 timers that can be set for a rising edge (TON) or a falling edge (TOF) b 24 incremental counters with adjustable thresholds b 4 clocks for a given week
PE50266

SFT2885: variable editor

Debugging Tools
The Logipam software offers a complete set of tools for program debugging: b step-by-step or continuous program execution to simulate the programmed functions b color animation of the rungs and all program variables b grouping in a table of all program variables requiring monitoring

Documentation
The application le can be printed in part or in whole. It can also be personalized with such items as a front page, title block, and general description of the program.
SFT2885: program debugging

139

Logic Input/Output Modules

MES114 Modules

PE50476

Function
The four outputs included on the Sepam Series 20 and 40 may be extended by adding an optional MES114 module with 10 inputs and 4 outputs, available in three versions: b MES114: 10 DC inputs voltage from 24 V DC to 250 V DC b MES114E: 10 inputs, voltage 110-125 V AC or V DC b MES114F: 10 inputs, voltage 220-250 V AC or V DC.

Characteristics
MES114 Module
Weight Operating temperature Environmental characteristics 0.28 kg (0.617 lb) -13 F to +158 F (-25 C to +70 C) Same characteristics as Sepam base units

Logical Inputs
Voltage Range

MES114
24 to 250 V DC 19.2 to 275 V DC / 3 mA 14 V DC

MES114E
110 to 125 V DC 88 to 150 VV DC / 3 mA 82 V DC 88 V DC 75 V DC Enhanced Enhanced 110 V AC

MES114F
220 to 240 V AC 176 to 264 V AC 47 to 63 Hz 3 mA 120 V AC 88 V AC 176 V DC 176 V AC 22 V AC 137 V DC 48 V AC Enhanced Enhanced Enhanced Enhanced Enhanced Enhanced 220 to 250 V DC 88 to 176 to 132 V AC 275 V DC 47 to 63 Hz / 3 mA 3 mA 58 V AC 154 V DC

10 input/4 output MES114 module.

Frequency Typical consumption Typical switching threshold Input limit At state 0 19 V DC voltage At state 1 6 V DC Isolation of inputs from Enhanced other isolated groups Isolation between inputs Voltage Enhanced

O11 Control Relay Output


DC AC (47.5 to 63 Hz) Resistive load Load L/R < 20 ms Load L/R < 40 ms Load cos j > 0.3 Enhanced 24 / 48 V DC 127 V DC 8A 8 / 4A 6 / 2A 4 / 1A 8A 0.7 A 0.5 A 0.2 A 220 V DC 8A 0.3 A 0.2 A 0.1 A 250 V CC 100 to 240 V AC 8A 0.2 A 8A 8A 5A

Continuous current Breaking capacity

Making capacity Isolation of outputs from other isolated groups Isolation between outputs Voltage

< 15 A for 200 ms

Enhanced

O12 to O14 Indication Relay Output


DC AC (47.5 to 63 Hz) 24 / 48 V DC 127 V DC 220 V DC 2A 0.3 A 0.15 A 250 V DC 100 to 240 V AC 2A 0.2 A 2A 1A

Continuous current Breaking capacity

Making capacity Isolation of outputs in relation to other isolated groups Isolation between outputs

2A 2A Resistive 2 / 1A 0.6 A load Load 2 / 1A 0.5 A L/R < 20 ms Load cos j > 0.3 < 15 A for 200 ms Enhanced

Enhanced

140

Logic Input/Output Modules

MES114 Modules

Description
DE52153

L , M and K : 3 removable, lockable screw-type connectors L : connectors for 4 relay outputs:

b O11: 1 control relay output b O12 to O14: 3 annunciation relay outputs M : connectors for 4 independent logic inputs I11 to I14 K : connectors for 6 logic inputs: b I21: 1 independent logic input b I22 to I26: 5 common point logic inputs. 1 25-pin sub-D connector to connect the module to the base unit. 2 Voltage selector switch for MES114E and MES114F module inputs, to be set to: b V DC for 10 DC voltage inputs (default setting) b V AC for 10 AC voltage inputs. 3 Label to be lled in to indicate the chosen parameter setting for MES114E and MES114F input voltages. The parameter setting status can be accessed in the Sepam Diagnosis screen of the SFT2841 software tool. Parameter setting of the inputs for AC voltage (V AC setting) blocks the operating time measurement function.

Assembly
DE51683

1. Insert the 2 pins on the MES module into the slots 1 on the base unit. 2. Flatten the module up against the base unit to plug it into the connector 2. 3. Tighten the mounting screw 3.

Connection
The inputs are potential-free and the DC power supply source is external.

! DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION OR ARC FLASH b Only qualied personnel should install this equipment. Such work should be performed only after reading this entire set of instructions and checking the technical characteristics of the device b NEVER work alone. b Turn off all power supplying this equipment before working on or inside it. Consider all sources of power, including the possibility of backfeeding b Always use a properly rated voltage sensing device to conrm that all power is off b Screw tight all terminals, even those not in use Failure to follow these instructions will result in death or serious injury. Wiring for connectors L , M and K : b Wiring with no ttings: v 1 wire with maximum cross-section AWG 24-12 (0.2 to 2.5 mm2) v or 2 wires with maximum cross-section AWG 24-18 (0.2 to 1 mm2) v stripped length: 0.315 to 0.39 in (8 to 10 mm) b Wiring with ttings: v terminal 5, recommended wiring with Telemecanique tting: - DZ5CE015D for 1 wire 1.5 mm2 (AWG 16) - DZ5CE025D for 1 wire 2.5 mm2 (AWG 12) - AZ5DE010D for 2 wires 1 mm2 (AWG 18) v wire length: 0.32 in (8.2 mm) v stripped length: 0.31 in (8 mm) 141

DE51685

Logic Input/Output Modules

Logic Input/Output Assignment of Sepam Series 20


Using preset control and monitoring functions requires exclusive parameter setting and particular wiring of the inputs according to their application and the type of Sepam. The advanced UMI or the SFT2841 software may be used to assign inputs and set the control and monitoring function parameters. Since an input may only be assigned to a single function, not all the functions are available at the same time. For example, if the zone selective interlocking function is used, the switching of groups of settings function can not be used.

Input/Output Assignment by Application


Functions
Logic Inputs Open position Closed position Zone selective interlocking, receive blocking input Switching groups of settings A/B External reset External tripping 4 (1) External tripping 1 (1) External network synchronization External tripping 2 (1) Motor re-acceleration External tripping 3 (1) Buchholz alarm (1) (Buchholz alarm message) Rotor rotation detection Thermistor tripping (1) Block ground fault protection End of charging position Thermostat alarm (1) (thermostat alarm message) Thermistor alarm (1) External tripping 5 and 50BF activation (1) Block remote control, excluding TC1 (1) Block remote control, including TC1 (1) SF6-1 SF6-2 Change of thermal settings Block thermal overload Block recloser Logic Outputs Tripping Block closing Watchdog Close command

S20 b b b b b b b b b b

S23 b b b b b b b b b b

T20 b b b b b b b (2) b b (3) b (4) b b b b b b b b b b b

T23 b b b b b b b (2) b b (3) b (4) b b b b b b b b b b b b

M20 b b b b b b b b b b b b b b b b b b b b

B21 - B22 b b

Assignment
I11 I12 I13

b b b b b b

I14 I21 I22 I23

b b

I24

b b b b

b b b b b

b b b b

I25

I26

b b b b b

b b b b b b b b b b b b b b b b b b b b b
O1 O2 O4 O11

Note: all of the logic inputs are available via the communication link and are accessible in the SFT2841 control matrix for other non predened applications. (1) These inputs have parameter setting with the prex NEG (negative) for undervoltage type operation. (2) Buchholz/Gas trip message. (3) Thermostat trip message. (4) Pressure trip message.

142

Logic Input/Output Modules

Logic Input/Output Assignment of Sepam Series 40


Inputs and outputs may be assigned to predened control and monitoring functions using the SFT2841 software, according to the uses listed in the table below. b all the logic inputs, whether or not assigned to predened functions, may be used for the SFT2841 customization functions according to specic application needs: v in the control matrix, to link inputs to output relays, LED indications or display messages v in the logic equation editor, as logic equation variables b the control logic of each input may be inverted for undervoltage type operation.

Functions
Logic Inputs
Open position Closed position Zone selective interlocking, receive blocking input 1 Zone selective interlocking, receive blocking input 2 Switching of groups of settings A/B External reset External tripping 1 External tripping 2 External tripping 3 Buchholz/gas tripping Thermostat tripping Pressure tripping Thermistor tripping Buchholz/gas alarm Thermostat alarm Pressure alarm Thermistor alarm End of charging position Block remote control SF6 Block recloser External synchronization Block thermal overload Switching of thermal settings Motor re-acceleration Rotor rotation detection Block undercurrent Block closing Open command Close command Phase voltage transformer fuse melting Residual voltage transformer fuse melting External positive active energy counter External negative active energy counter External positive reactive energy counter External negative reactive energy counter

S40, S41
b b b b b b b b

Assignment: Logic Inputs by Application S42 T40, T42 M41 G40 Assignment
b b b b b b b b b b b b b b b b b b b b b b b b b b b b b b b b b b b b b b b b b
I11 I12 Free Free I13 Free Free Free Free Free Free Free

b b b b b

Free Free Free Free

b b b b b

b b b b b

b b b b b b b b b b b b b b b b b b b b b b b b b b b

b b b b b b b

Free Free Free Free Free I21 Free Free Free Free Free

b b b b b b b b b b b b b

b b b b b b b b b b b b b b b b b

b b b b b b b b b

b b b b b b b b b

Free Free Free Free Free Free Free Free Free O1 O2 O4 O11

Logic Outputs
Tripping Block closing Watchdog Close command

Note: The logic inputs are available via the communication link and are accessible in the SFT2841 matrix for other non predened applications.

143

Logic Input/Output Modules

MES120, MES120G, MES120H 14 Input/6 Output Module Presentation


Function
The ve output relays included on the Sepam Series 80 base unit can be extended by adding one, two, or three MES120 modules with 14 DC logic inputs and 6 outputs relays, 1 control relay output and 5 indication relay outputs. Two modules are available for the different input supply voltage ranges and offer different switching thresholds: b MES120, 14 inputs 24 V DC to 250 V DC with a typical switching threshold of 14 V DC b MES120G, 14 inputs 220 V DC to 250 V DC with a typical switching threshold of 155 V DC b MES120H, 14 inputs 110 V DC to 125 V DC with a typical switching threshold of 82 V DC.

PE50020

MES120 14 input / 6 output module.

Characteristics
0,38 kg (0,83 lb) -25 C to +70 C (-13 F to +158 F) Same characteristics as Sepam base units

MES120 / MES120G / MES120H Modules


Weight Operating temperature Environmental characteristics

Logic Inputs

MES120

MES120G

MES120H
110 to 125 V DC 88 to 150 V DC 3 mA 82 V DC < 75 V DC > 88 V DC Enhanced 250 V DC 8A 0.2 A -

At state 0 At state 1 Isolation of inputs from other isolated groups

Voltage Range Typical consumption Typical switching threshold Input limit voltage

Control Relay Output Ox01

24 250 V DC 19.2 275 V DC 3 mA 14 V DC < 6 V DC > 19 V DC Enhanced 24/48 V DC 8A 8 / 4A 6 / 2A 4 / 1A < 15 A for 200 ms Enhanced 24/48 V DC 2A 2 / 1A Enhanced

220 to 250 V DC 170 to 275 V DC 3 mA 155 V DC < 144 V DC > 170 V DC Enhanced 127 V DC 8A 0.7 A 0.5 A 0.2 A 220 V DC 8A 0.3 A 0.2 A 0.1 A -

Voltage Continuous current Breaking capacity

DC AC (47.5 to 63 Hz) Resistive load Load L/R < 20 ms Load L/R < 40 ms Load p.f > 0.3

100 240 V AC 8A 8A 5A

Making capacity Isolation of inputs from other isolated groups Tension Continuous current Breaking capacity

Annunciation Relay Input Ox02 to Ox06


Continue Alternative (47.5 63 Hz)

Load L/R < 20 ms Load p.f > 0.3 Isolation of inputs from other isolated groups
in. (mm)

127 V DC 2A 0.5 A -

220 V DC 2A 0.15 A -

250 V DC 2A 0.2 A -

100 to 240 V AC 2A 1A

Description
3 removable, lockable screw-type connectors. 1 20-pin connector for 9 logic inputs: b Ix01 to Ix04: 4 independent logic inputs b Ix05 to Ix09: 5 common point logic inputs. 2 7-pin connector for 5 common point logic inputs Ix10 Ix14. 3 17-pin connector for 6 relay outputs: b Ox01: 1 control relay output b Ox02 to Ox06 : 5 indication relay outputs. Addressing of MES120 module inputs / outputs: b x = 1 for the module connected to H1 b x = 2 for the module connected to H2 b x = 3 for the module connected to H3. 4 MES120G, MES120H identication label (MES120 modules have no labels).

6.69 (170)

4.72 (120)

1.57 (40)

144

Logic Input/Output Modules

MES120, MES120G, MES120H 14 Input/6 Output Module Installation


Assembly
Installing an MES120 Module on the Base Unit b insert the two pins on the MES module into the slots (1) on the base unit b push the module at up against the base unit to plug it into the connector H2 b partially tighten the two mounting screws (2) before locking them. MES120 modules must be mounted in the following order: b if only one module is required, connect it to connector (H1) b if two modules are required, connect them to connectors (H1) and (H2) b if three modules are required (maximum conguration), the three connectors (H1, H2, and H3) are used.

PE50026

Installation of the second MES120 module, connected to base unit connector H2.

Connection

The inputs are potential-free and the DC power supply source is external.

! DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION OR ARC FLASH b Only qualied personnel should install this equipment. Such work should be performed only after reading this entire set of instructions and checking the technical characteristics of the device. b NEVER work alone. b Turn off all power supplying this equipment before working on or inside it. Consider all sources of power, including the possibility of backfeeding. b Always use a properly rated voltage sensing device to conrm that all power is off. b Screw tight all terminals, even those not in use. Failure to follow these instructions will result in death or serious injury.

Wiring Connectors b wiring without ttings: v 1 wire with maximum cross-section AWG 24-12 (0.2 to 2.5 mm) v or 2 wires with maximum cross-section AWG 24-16 (0.2 to 1 mm) v stripped length: 0.31 to 0.39 in (8 to 10 mm) b wiring with ttings: v recommended wiring with Telemecanique ttings:
- DZ5CE015D for one AWG 16 (1.5 mm) wire - DZ5CE025D for one AWG 12 (2.5 mm) wire - AZ5DE010D for two AWG 18 (1 mm) wires

DE51645

v wire length: 0.32 in (8.2 mm) v stripped length: 0.31 in (8 mm).

145

Logic Input/Output Modules

MES120, MES120G, MES120H 14 Input/6 Output Module Logic Input/Output Assignment


Inputs and outputs may be assigned to predened control and monitoring functions using the SFT2841 software, according to the uses listed in the table below. The control logic of each input may be inverted for undervoltage type operation. All the logic inputs, whether or not assigned to predened functions, may be used for the customization functions according to specic application needs: b in the control matrix (SFT2841 software), to connect an input to a logic output, a LED on the front of Sepam or a message for local indication on the display b in the logic equation editor (SFT2841 software), as logic equation variables b in Logipam (SFT2885 software) as input variables for the program in ladder language

Logic Output Assignment Table


Functions
Tripping / contactor control Block closing Closing Watchdog Zone selective interlocking, blocking send 1 Zone selective interlocking, blocking send 2 Genset shutdown De-excitation Load shedding AT, closing of NO circuit breaker AT, closing of tie breaker AT, opening of tie breaker Tripping of capacitor step (1 to 4) Tripping of capacitor step (1 to 4) b b b b b b b b b b b b b b b b b b b b b b b b b b b b b b b b b b

S80
b b b b b

S81
b b b b b

S82
b b b b b b

S84
b b b b b b

T81
b b b b b

T82 T87
b b b b b b

M87 M81 M88


b b b b b b b b b b

G87 G82 G88


b b b b b b b b b b b b b b b b

B80
b b b b b

B83
b b b b b

C86
b b b b b

Assignment
O1 O2 by default O3 by default O5 O102 by default O103 by default Free Free Free Free Free Free Free Free

Note: The logic outputs assigned by default may be freely reassigned.

Assignment Table for Logic Inputs Common to all Applications


Functions
Closed circuit breaker Open circuit breaker Synchronization of Sepam internal clock via external pulse Switching of groups of settings A/B External reset Grounding switch closed Grounding switch open External trip 1 External trip 2 External trip 3 End of charging position Block remote control (Local) SF6 pressure default Block closing Open command Close command Phase VT fuse blown Vr VT fuse blown External positive active energy meter External negative active energy meter External positive reactive energy meter External negative reactive energy meter Racked out circuit breaker Switch A closed Switch A open Switch B closed Switch B open Closing-coil monitoring

S80
b b b b b b b b b b b b b b b b b b b b b b b b b b b b

S81
b b b b b b b b b b b b b b b b b b b b b b b b b b b b

S82
b b b b b b b b b b b b b b b b b b b b b b b b b b b b

S84
b b b b b b b b b b b b b b b b b b b b b b b b b b b b

T81
b b b b b b b b b b b b b b b b b b b b b b b b b b b b

b b b b b b b b b b b b b b b b b b b b b b b b b b b b

T82 T87

M87
b b b b b b b b b b b b b b b b b b b b b b b b b b b b

b b b b b b b b b b b b b b b b b b b b b b b b b b b b

M81 M88

G87
b b b b b b b b b b b b b b b b b b b b b b b b b b b b

b b b b b b b b b b b b b b b b b b b b b b b b b b b b

G82 G88

B80
b b b b b b b b b b b b b b b b b b b b b b b b b b b b

B83
b b b b b b b b b b b b b b b b b b b b b b b b b b b b

C86
b b b b b b b b b b b b b b b b b b b b b b b b b b b b

Assignment
I101 I102 I103 Free Free Free Free Free Free Free Free Free Free Free Free Free Free Free Free Free Free Free Free Free Free Free Free Free

146

Logic Input/Output Modules

MES120, MES120G, MES120H 14 Input/6 Output Module Logic Input/Output Assignment


S80
b b

Functions
Block recloser Block thermal overload Switching of thermal settings Blocking reception 1 Blocking reception 2 Buchholz trip Thermostat trip Pressure trip Thermistor trip Buchholz alarm Thermostat alarm Pressure alarm Thermistor alarm Rotor speed measurement Rotor rotation detection Motor re-acceleration Load shedding request Block undercurrent Priority genset shutdown De-excitation Close enable (ANSI 25) Block opposite-side remote control (local) Block remote-control tie breaker (local) Tie breaker open Tie breaker closed Opposite side open Opposite side closed Selector set to Manual (ANSI 43) Selector set to Auto (ANSI 43) Selector set to Circuit breaker (ANSI 10) Selector set to Tie Breaker (ANSI 10) Opposite-side circuit breaker disconnected Tie breaker circuit breaker disconnected Tie breaker close command Opposite-side voltage OK Block closing of tie breaker Automatic closing command External closing command 1 External closing command 2 Additional phase voltage transformer fuse blown Additional Vr voltage transformer fuse blown Capacitor step 1 open Capacitor step 1 closed Capacitor step 2 open Capacitor step 2 closed Capacitor step 3 open Capacitor step 3 closed Capacitor step 4 open Capacitor step 4 closed Step 1 opening command Step 2 opening command Step 3 opening command Step 4 opening command Step 1 closing command Step 2 closing command Step 3 closing command Step 4 closing command Step 1 external trip Step 2 external trip Step 3 external trip Step 4 external trip Capacitor step 1 VAR control Capacitor step 2 VAR control Capacitor step 3 VAR control Capacitor step 4 VAR control External capacitor step control block Manual capacitor step control Automatic capacitor step control

S81
b b b

S82
b b b b

Assignment of Logic Inputs by Application S84 T81 T82 M87 M81 G87 G82 B80 T87 M88 G88
b b b b b b b b b b b b b b b b b b b b b b b b b b b b b b b b b b b b b b b b b b b b b b b b b b b b b b b b b b b

B83

C86
b

Assignment
Free Free Free Free Free Free Free Free Free Free Free Free Free I104 Free Free Free Free Free Free Free Free Free Free Free Free Free Free Free Free Free Free Free Free Free Free Free Free Free Free Free Free Free Free Free Free Free Free Free Free Free Free Free Free Free Free Free Free Free Free Free Free Free Free Free Free Free Free

b b

b b b b b b

b b

b b b b b b b b b b b b b b b b b

b b b b b b b b b b b b b b b b b

b b b b b b b b b b b b b b b b b

b b b b b b b b b b b b b b b b b

b b b b b b b b b b b b b b b b b

b b b b b b b b b b b b b b b b b

b b b b b b b b b b b b b b b b b b b

b b b b b b b b b b b b b b b b b b b

b b b b b b b b b b b b b b b b b b b b

b b b b b b b b b b b b b b b b b b b b b b b b b b b b b b b b b b b b b b b b b b b b b b b b

147

Remote Modules

Selection Guide and Connection

Selection Guide

Four remote modules are proposed as options to enhance the Sepam base unit functions: b the number and type of remote modules compatible with the base unit depend on the Sepam application b the DSM303 remote advanced UMI module is only compatible with base units that do not have integrated advanced UMIs

Sepam Series 20 Sepam Series 40 Sepam Series 80


S2x, B2x
MET1482 Temperature sensor module See page 149 MSA141 Analog output module See page 151 DSM303 Remote advanced UMI module See page 152 MCS025 Synchro-check module See page 154 Number of sets of interlinked modules / maximum number of remote modules

T2x, M2x

S4x

T4x, M4x, G4x S8x, B8x

T8x, G8x

M8x, C8x

0 1 1 1 1 1 0 0 1 set of 3 interlinked modules

0 2 1 1 1 1 0 0 1 set of 3 interlinked modules

0 2 2 1 1 1 1 1 1 1 1 0 5 modules split between 2 sets of interlinked modules

CAUTION
HAZARD OF NON-OPERATION The MCS025 module must ALWAYS be connected with the special CCA785 cable that is supplied with the module and equipped with an orange RJ45 plug and a black RJ45 plug. Failure to follow this instruction can cause equipment damage.

Connection
Connection Cables
Different combinations of modules may be connected using cables tted with two black RJ45 connectors, which come in three lengths: b CCA770: length = 2 ft (0.6 m) b CCA772: length = 6.6 ft (2 m) b CCA774: length = 13.1 ft (4 m)
The modules are linked by cables which provide the power supply and act as functional links with the Sepam unit (connector D to connector Da , Dd to Da , ).

Rules on Inter-Module Linking


DE51646

b Link three modules maximum b DSM303 and MCS025 modules may only be connected at the end of the link

Maximum Advisable Congurations


Sepam Series 20 and Sepam Series 40 with One set of Interlinked Modules
Base
DE51770

Cable

Module 1 Cable

Module 2

Cable

Module 3

Ia Ib Ic

Series 20 Series 40 Series 40 Series 40

CCA772 CCA772 CCA772 CCA772

MSA141 MSA141 MSA141 MET1482

CCA770 CCA770 CCA770 CCA770

MET1482 MET1482 MET1482 MET1482

CCA774 CCA774 CCA772 CCA774

DSM303 DSM303 MET1482 DSM303

Sepam Series 80 with Two sets of Interlinked Modules Sepam Series 80 has 2 connection ports for remote modules, D1 and D2 . Modules may be connected to either port.
Base Set 1 D1
DE51647

Cable CCA772

Module 1 MET1482

Cable CCA770

Module 2 MET1482

Cable CCA774

Module 3 DSM303

A RMS Ia = 165 RMS A Ib = 166 RMS A Ic = 167

a b c

Example of inter-module linking on Sepam Series 20

Set 2 D2

CCA772

MSA141

CCA785

MCS025

148

Remote Modules

MET1482 Temperature Sensor Module


Function

MET1482 Temperature sensor module.

The MET1482 module can be used to connect eight temperature sensors (RTDs) of the same type: b Pt100, Ni100 or Ni120 type RTDs, according to parameter setting b 3-wire temperature sensors b A single module for each Sepam Series 20 base unit, connected by a CCA770 (2 ft or 0.6 m), CCA772 (6.6 ft or 2 m) or CCA774 (13.1 ft or 4 m) cable b two modules for each Sepam Series 40 or Series 80 base units, connected by a CCA770 (2 ft or 0.6 m), CCA772 (6.6 ft or 2 m) or CCA774 (13.1 ft or 4 m) cable The temperature measurement as in a transformer or motor winding is used by the following protection functions: b Thermal overload (to account for ambient temperature) b Temperature monitoring

PE50021

Characteristics
MET1482 Module
Weight Assembly Operating temperature Environmental characteristics 0.441 lb (0.2 kg) On symmetrical DIN rail -13 F to +158 F (-25 C to +70 C) Same characteristics as Sepam base units

Temperature Sensors
Isolation from ground Current injected in RTD

Pt100
None 4 mA

Ni100 / Ni120
None 4 mA

DE80031

Description and Dimensions


A Terminal block for RTDs 1 to 4.
in. (mm)

B Terminal block for RTDs 5 to 8.


(88)
3.46

Da RJ45 connector to connect the module to the base unit with a CCA77x cable Dd RJ45 connector to link up the next remote module with a CCA77x cable (according to application).

Grounding/grounding terminal. 1
1.18(1) (30)

(144)

5.67

(1) 70 mm (2.8 in) with CCA77x cable connected.

Jumper for impedance matching with load resistor (Rc), to be set to: b Rc , if the module is not the last interlinked module (default position) b Rc, if the module is the last interlinked module. 2 Jumper used to select module number, to be set to: b MET1: 1st MET1482 module, to measure temperatures T1 to T8 (default position) b MET2: 2nd MET1482 module, to measure temperatures T9 to T16 (for Sepam Series 40 and Series 80 only).

149

Remote Modules

MET1482 Temperature Sensor Module


Connection
! DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION OR ARC FLASH b Only qualied personnel should install this equipment. Such work should be performed only after reading this entire set of instructions and checking the technical characteristics of the device. b NEVER work alone. b Check that the temperature sensors are isolated from all voltages. Failure to follow these instructions will result in death or serious injury.

DE51649

Connecting the Grounding Terminal Connecting the grounding terminal is accomplished by using a tinned copper braid with cross-section u AWG 10 (6 mm) or cable with cross-section u AWG 12 (2.5 mm) and length y 7.9 in (200 mm), tted with a 0.16 in (4 mm) ring lug. Check the tightness (maximum tightening torque 19.5 lb-in or 2.2 Nm). Connecting RTDs to Screw-Type Connectors b 1 wire with cross-section AWG 24-12 (0.2 to 2.5 mm) Recommended cross-sections according to distance: b Up to 330 ft (100 m) AWG 18 (1 mm) b Up to 990 ft (300 m) AWG 16 (1.5 mm) b Up to 0.62 mi (1 km) AWG 12 (2.5 mm) Maximum distance between sensor and module: 0.62 mi (1 km). Wiring Precautions b Shielded cabling is preferred. Using unshielded cables can cause measurement errors which vary according to the level of surrounding electromagnetic disturbance b Only connect the shielding at the MET1482 end, in the shortest manner possible, to the corresponding terminals of connectors A and B b Do not connect the shielding at the RTD end Accuracy derating according to wiring The error Dt is proportional to the length of the cable and inversely proportional to the cable cross-section:
L km ( ) -------t ( C ) = 2 S ( m m2 )

b 2.1C/km for 0.93 mm cross-section (AWG 18) b 1C/km for 1.92 mm cross-section (AWG 14)

150

Remote Modules

MSA141 Analog Output Module


Function

MSA141 Analog Output Module

The MSA141 module converts one of the Sepam measurements into an analog signal: b selection of the measurement to be converted by parameter setting b 0-10 mA, 4-20 mA, or 0-20 mA analog signal according to parameter setting b scaling the analog signal by setting minimum and maximum values of the converted measurement. Example: the setting used to have phase current 1 as a 0-10 mA analog output with a dynamic range of 0 to 300 A is: v minimum value = 0 v maximum value = 3000 b a single module for each Sepam base unit, to be connected by one of the CCA770 (2 ft or 0.6m), CCA772 (6.6 ft or 2m) or CCA774 (13.1 ft or 4m) cables. The analog output can also be remotely managed via the communication network.

Mt11009

Characteristics
MSA141 Module
Weight Assembly Operating temperature Environmental characteristics 0.441 lb (0.2 kg) On symmetrical DIN rail -13 F to +158 F (-25 C to +70 C) Same characteristics as Sepam base units 4-20 mA, 0-20 mA, 0-10 mA Minimum value Maximum value < 600 W (including wiring) 0.5 %

Analog Output
Current Scaling (no data input checking) Load impedance Accuracy

Available Measurements
Phase and residual currents Line-to-neutral and line-to-line voltages Frequency Thermal capacity used Temperatures Active power Reactive power Apparent power Power factor Remote setting via communication link
in. (mm) (88)
3.46

Unit
0.1 A 1V 0.01 Hz 1% 1 C 0.1 kW 0.1 kvar 0.1 kVAR 0.01

Series 20
b b b b b

Series 40
b b b b b b b b b

Series 80
b b b b b b b b b b

DE80032

Description and Dimensions


A Terminal block for analog output. Da RJ45 socket to connect the module to the base unit with a CCA77x cable. Dd RJ45 socket to link up the next remote module with a CCA77x cable

(according to application). Grounding terminal. 1


1.18(1) (30) (144)
5.67

Jumper for impedance matching with load resistor (Rc), to be set to: b Rc , if the module is not the last interlinked module (default position) b Rc, if the module is the last interlinked module.

Connection
(1) 70 mm (2.8 in) with CCA77x cable connected
DE52182

Connecting the Grounding Terminal Use a tinned copper braid with cross-section u AWG 10 (6 mm) or cable with cross-section u AWG 12 (2.5 mm) and length y 7.9 in (200 mm), equipped with a 0.16 in (4 mm) ring lug. Check the tightness (maximum tightening torque 19.5 lb-in or 2.2 Nm). Connection of Analog Output to Screw-Type Connector b 1 wire with cross-section AWG 24-12 (0.2 to 2.5 mm) b or 2 wires with cross-section AWG 24-18 (0.2 to 1 mm). Wiring Precautions b Shielded cables are preferred b Use tinned copper braid to connect the shielding at least at the MSA141 end 151

Remote Modules

DSM303 Remote Advanced UMI Module


Function

PE50127

When associated with a Sepam that does not have its own advanced user-machine interface, the DSM303 offers all the functions available on a Sepam integrated advanced UMI. It can be installed on the front panel of a room in the most suitable operating location: b reduced depth < 1.2 in (30 mm) b a single module for each Sepam, to be connected by one of the CCA772 (6.6 ft or 2 m) or CCA774 (13.1 ft or 4 m) cables The module cannot be connected to Sepam units with integrated advanced UMIs.

Characteristics
DSM303 Module
DSM303 remote advanced UMI module. Weight Assembly Operating temperature Environmental characteristics 0.3 kg (0.661 lb) Flush-mounted -25 C to +70 C (-13 F to +158 F) Same characteristics as for Sepam base units

152

Remote Modules

DSM303 Remote Advanced UMI Module


Description and Dimensions
Front view
DE80033

The module is simply ush-mounted and secured by its clips. No additional screw-type fastening is required. Side view
DE80034

in. (mm)

in. (mm)

16

17

4.61 (117)

3.78 (96)

5.98 (152)

0.98 (25) 0.59 (15)

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17

Green LED: Sepam on. Red LED: - steadily on: module unavailable - ashing: Sepam link unavailable. 9 yellow LEDs. Label identifying the LEDs. Graphic LCD screen. Display of measurements. Display of switchgear, network and machine diagnosis data. Display of alarm messages. Sepam reset (or conrm data entry). Alarm acknowledgment and clearing (or move cursor up). LED test (or move cursor down). Access to protection settings. Access to Sepam parameters. Entry of 2 passwords. PC connection port. Mounting clip. Gasket to ensure NEMA 12 tightness (gasket supplied with the DSM303 module, to be installed if necessary). a CCA77x cable.

Da RJ45 lateral output connector to connect the module to the base unit with

Cut-out for ush-mounting (mounting plate thickness < 3 mm or 0.12 in)


in. (mm)

DE80060

3.88 0.5 (98.5 0.5)

5.67 0.2 (144 0.2)


DE53033

Connection

Da RJ45 socket to connect the module to the base unit with a CCA77x cable.

The DSM303 module is always the last interlinked remote module and it systematically ensures impedance matching by load resistor (Rc). 153

Remote Modules

MCS025 Synchro-Check Module


Function

PE50285

The MCS025 module checks the voltages upstream and downstream of a circuit breaker to verify that the two voltages are in sync before the circuit breaker closes (ANSI 25). It checks the differences in amplitude, frequency, and phase between the two measured voltages, taking into account dead line/bus conditions. Three relay outputs may be used to send the close enable command to several Sepam Series 80 units. The circuit-breaker control function of each Sepam Series 80 unit will take this close enable into account. The settings for the synchro-check function and the measurements carried out by the module may be accessed by the SFT2841 setting and operating software, similar to the other settings and measurements for the Sepam Series 80. The MCS025 module is supplied ready for operation with: b the CCA620 connector for connection of the relay outputs and the power supply b the CCT640 connector for voltage connection b the CCA785 cable for connection between the module and the Sepam Series 80 base unit
MCS025 synchro-check module.

Characteristics
2.98 lb (1.35 kg) With the AMT840 accessory -13 F to +158 F (-25 C to +70 C) Same characteristics as Sepam base units > 100 kW < 0.015 VA (VT 100 V) 240 V 480 V

MCS025 Module
Weight Assembly Operating temperature Environmental characteristics

Voltage Inputs
Input impedance Burden Continuous thermal withstand 1-second overload

Relay Outputs
Relay Outputs O1 and O2
Voltage Continuous current Breaking capacity DC AC (47.5 to 63 Hz) Resistive load Load L/R < 20 ms Load L/R < 40 ms Resistive load Load pf > 0.3 24/48 V DC 8A 8A/ 4A 6A/ 2A 4A/ 1A 127 V DC 8A 0.7 A 0.5 A 0.2 A 220 V DC 8A 0.3 A 0.2 A 0.1 A 100 to 240 V AC 8A

8A 5A < 15 ms for 200 ms Enhanced

Making capacity Isolation of outputs from other isolated groups

Relay Outputs O3 and O4 (O4 not used)


Voltage Continuous current Breaking capacity Isolation of outputs from other isolated groups DC AC (47.5 to 63 Hz) Load L/R < 20 ms Load pf > 0.3 24/48 V DC 2A 2A/ 1A Enhanced 127 V DC 2A 0.5 A 220 V DC 2A 0.15 A 100 to 240 V AC 2A 5A

Power Supply
Voltage Maximum consumption Inrush current Acceptable momentary outages 24 to 250 V DC, -20 % / +10 % 6W < 10 A for 10 ms 10 ms 110 to 240 V AC, -20 % / + 0 % 47.5 to 63 Hz 9 VA < 15 A for one half period 10 ms

154

Remote Modules

MCS025 Synchro-Check Module


Description

MCS025 module

A CCA620 20-pin connector for:

B CCT640 connector (line-to-neutral or phase-to-

phase) for the two input voltages to be synchronized


C RJ45 connector, not used D RJ45 connector for module connection to the

Sepam Series 80 base unit, either directly or via another remote module. 2 3 4 Two mounting clips Two holding pins for the ush-mount position CCA785 connection cable

DE51654

b auxiliary power supply b 4 relay outputs: v O1, O2, O3: close enable. v O4: not used

155

Remote Modules

MCS025 Synchro-Check Module


Dimensions

4
in. (mm)
DE80079

DE52816

in. (mm) 1.57 (40)

8.74 (222)

7.72 (196)

8.74 (222)

6.93 (176)

1.57 (40) 1.57 (40) 3.86 (98) 0.91 (23)

MCS025.

0.26 (6.5)
DE52759

in. (mm)

Assembly with AMT840 Mounting Plate


1.57 (40) 1.57 (40)

The MCS025 module should be mounted at the back of the compartment using the AMT840 mounting plate.
9.06 (230)
DE80081

7.95 (202)

in. (mm) 4.84 (123)

1.57 (40) 1.57 (40) 1.57 (40)

6.38 (162)

8.50 (216) 9.29 (236)

0.39 (10)

0.59 (15)

AMT840 mounting plate.

Connection Characteristics
Connector
A

Type
Screw-type

Reference
CCA620

Wiring
b Wiring with no ttings: v 1 wire with maximum cross-section 0.2 to 2.5 mm (> AWG 24-12) or 2 wires with cross-section 0.2 to 1 mm (>AWG 24-16) v stripped length: 8 to 10 mm (0.31 0.39 in) b Wiring with ttings: v recommended wiring with Telemecanique ttings: - DZ5CE015D for 1 wire 1.5 mm2 (AWG 16) - DZ5CE025D for 1 wire 2.5 mm2 (AWG 12) - AZ5DE010D for 2 x 1 mm wires (AWG 18) v wire length: 8.2 mm (0.32 in) v stripped length: 8 mm (0.31 in) VT wiring: same as wiring of the CCA620 Grounding connection: by 4 mm (0.15 in) ring lug CCA785, special prefabricated cable supplied with the MCS025 module: b orange RJ45 connector for connection to port D on the MCS025 module b black RJ45 connector for connection to the Sepam Series 80 base unit, either directly or via another remote module.

B D

Screw-type Orange RJ45 connector

CCT640

156

Remote Modules

MCS025 Synchro-Check Module

a b c

4
VT VT

DE52075

Sepam Series 80

I/O Mod

(1) Line-to-line or line-to-neutral connection.

CAUTION
HAZARD OF NON-OPERATION The MCS025 module must ALWAYS be connected with the special CCA785 cable, supplied with the module and equipped with an orange RJ45 plug and a black RJ45 plug. Failure to follow this instruction can cause equipment damage.

! DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION OR ARC FLASH b Only qualied personnel should install this equipment. Such work should be performed only after reading this entire set of instructions and checking the technical characteristics of the device. b NEVER work alone. b Turn off all power supplying this equipment before working on or inside it. Consider all sources of power, including the possibility of backfeeding. b Always use a properly rated voltage sensing device to conrm that all power is off. b Screw tight all terminals, even those not in use. Failure to follow these instructions will result in death or serious injury.

157

Communication Accessories

Selection Guide

4
ACE9492
Type of Network
S-LAN or E-LAN (1) S-LAN or E-LAN (1) b

There are two types of Sepam communication accessories: b communication interfaces, which are essential for connecting Sepam to the communication network b converters and other accessories, as options, which are used for complete implementation of the communication network.

Communication-Interface Selection Guide


ACE959 ACE937
S-LAN or E-LAN (1) b

ACE969TP ACE969FO ACE850TP (4) ACE850FO (4)


S-LAN E-LAN S-LAN E-LAN S-LAN and E-LAN b S-LAN and E-LAN

Protocol
Modbus RTU DNP3 IEC 60870-5-103 Modbus TCP/IP IEC 61850 b b b b
(3) (3) (3)

b b b

(3) (3) (3)

b b 2-wire 4-wire Star Ring 1 port 1 port b b b b b


(2)

(3) (3)

b b

(3) (3)

Physical Interface
RS485 Fiber optic ST 10/100 base T 100 base FX b b b

b b Supplied by Sepam Supplied by Sepam Supplied by Sepam 24 to 250 V 110 to 240 V 24 to 250 V 110 to 240 V 24 to 250 V 110 to 240 V 24 to 250 V 110 to 240 V

Power Supply
CC CA

See details on page

160

161

162

163

163

(1) Only one connection possible, S-LAN or E-LAN. (2) Except with the Modbus protocol. (3) Not simultaneously (1 protocol per application). (4) Soon available for Sepam Series 40 and series 80.

Converter Selection Guide


ACE919CA
1 port RS485 port 2-wire b b b
(1) (1) (1)

ACE9092
Converter
Physical interface 1 port RS232

ACE919CC
1 port RS485 port 2-wire b b b
(1) (1) (1)

EGX100
1 Ethernet port 10/100 base T

EGX400
2 Ethernet ports 10/100 base T 100 base F

ECI850
1 Ethernet port 10/100 base T

Modbus RTU IEC 60870-5-103 DNP3 Modbus TCP/IP IEC 61850

b b b

(1) (1) (1)

b b

To Sepam
Physical interface 1 port RS485 2-wire b b b b
(1) (1) (1)

1 port RS485 2-wire b b b b


(1) (1) (1)

1 port RS485 2-wire b b b b


(1) (1) (1)

1 port RS485 2-wire or 4-wire

2 ports RS485 2-wire or 4-wire

1 port RS485 2-wire or 4-wire

Distributed power supply RS485 Modbus RTU IEC 60870-5-103 DNP3

Power Supply
DC AC 24 to 48 V 110 to 220 V AC 11to 220 V AC 24 V 24 V 100 to 240 V AC (with adapter) 24 V

See details on page

168

170

170

176

177

(1) The supervisor protocol is the same as the Sepam protocol. Note: All these interfaces accept the E-LAN protocol.

158

Communication Interfaces

Communication Interface

CCA612 Connection Cable


Plugging into Sepam
Cable used to connect a communication interface to a Sepam base unit: b Length = 9.8 ft (3 m) b Fitted with two green RJ45 plugs.

Sepam Series 20 and Series 40


DE51659 DE51660

Sepam Series 80

Sepam Series 20 and Sepam Series 40: 1 communication port

Sepam Series 80: 2 communication ports.

Connecting to the Communication Network


RS485 Network Cable
RS485 medium Distributed power supply Shielding Characteristic impedance Gauge Resistance per unit length Capacitance between conductors Capacitance between conductor and shielding Maximum length

2-wire

4-wire

1 shielded twisted pair 2 shielded twisted pairs 1 shielded twisted pair 1 shielded twisted pair Tinned copper braid, coverage > 65% 120 W AWG 24 < 62.1 W/mi (100 W/km) < 18.3 pF/ft (60 pF/m) < 30.5 pF/ft (100 pF/m) 4270 ft (1300 m)

Fiber Optic
Fiber type Wavelength Type of connector Graded-index multimode silica 820 nm (invisible infrared) ST (BFOC bayonet ber optic connector)

Fiber Optic Diameter (m)


50/125 62.5/125 100/140 200 (HCS)

Numerical Aperture (NA)


0.2 0.275 0.3 0.37

Maximum Attenuation (dBm/km)


2.7 3.2 4 6

Minimum Optical Power Available (dBm)


5.6 9.4 14.9 19.2

Maximum Fiber Length


2300 ft (700 m) 5900 ft (1800 m) 9200 ft (2800 m) 8500 ft (2600 m)

159

Communication Interfaces

ACE9492 2-wire RS485 Network Interface


Function

PE50029

The ACE9492 interface performs two functions: b Electrical interface between Sepam and a 2-wire RS485 communication network b Main network cable branching box for the connection of a Sepam with a CCA612 cable.

Characteristics
ACE9492 Module
ACE9492 2-wire RS485 network connection interface Weight Assembly Operating temperature Environmental characteristics Standard Distributed power supply Power consumption 0.22 lb (0.1 kg) On symmetrical DIN rail -13F to +158F (-25C to +70C) Same characteristics as Sepam base units EIA 2-wire RS485 differential External, 12 V DC or 24 V DC 10% 16 mA in receiving mode 40 mA maximum in sending mode

2-wire RS485 Electrical Interface

Maximum Length of 2-wire RS485 Network with Standard Cable


DE80035

in. (mm) 3.46 (88)

Number of Sepam Units


5 10 20 25

Maximum Length with 12 V DC Power Supply


1000 ft (320 m) 590 ft (180 m) 520 ft (160 m) 410 ft (125 m)

Maximum Length with 24 V DC Power Supply


3300 ft 2500 ft 1500 ft 1200 ft (1000 m) (750 m) (450 m) (375 m)

Description and Dimensions


A and B Terminal blocks for network cable C RJ45 socket to connect the interface to the base unit with a CCA612 cable

1.18(1) (30) 2.83 (72)


(1) 2.8 in (70 mm) with CCA612 cable connected

t Grounding terminal

DE80127

2-wire RS485 network

Power supply or 24 V DC

1 Link activity LED, ashes when communication is active (sending or receiving in progress). 2 Jumper for RS485 network line-end impedance matching with load resistor (Rc = 150 W), to be set to: b Rc , if the module is not at one end of the network (default position) b Rc, if the module is at one end of the network. 3 Network cable clamps (inner diameter of clamp = 0.24 in or 6 mm).

Connection
b Connection of network cable to screw-type terminal blocks A and B b Connection of the grounding terminal by tinned copper braid with cross-section AWG 10 (6 mm) or cable with cross-section AWG 12 (2.5 mm) and length 7.9 in (200 mm), tted with a 0.16 in (4 mm) ring lug. Check the tightness (maximum tightening torque 19.5 lb-in (2.2 Nm). b The interfaces are tted with clamps to hold the network cable and recover shielding at the incoming and outgoing points of the network cable: v the network cable must be stripped v the cable shielding braid must be around and in contact with the clamp b The interface is to be connected to connector C on the base unit using a CCA612 cable (length = 9.8 ft or 3 m, green ttings) b The interfaces are to be supplied with 12 V DC or 24 V DC.
2-wire

RS485 network

Power supply or 24 V DC

Note: The shield connection should be grounded at only one end of the serial daisy chain.

160

Communication Interfaces

ACE959 4-wire RS485 Network Interface


Function

The ACE959 interface performs two functions: b Electrical interface between Sepam and a 4-wire RS485 communication network b Main network cable branching box for the connection of a Sepam with a CCA612 cable.

PE50023

Characteristics
ACE959 Module
Weight ACE959 4-wire RS485 network connection interface. Assembly Operating temperature Environmental characteristics Standard Distributed power supply Power consumption 0.441 lb (0.2 kg) On symmetrical DIN rail -13F to +158F (-25C to +70C) Same characteristics as Sepam base units EIA 4-wire RS485 differential External, 12 V DC or 24 V DC 10% 16 mA in receiving mode 40 mA maximum in sending mode

4-wire RS485 Electrical Interface


in. (mm)
DE80036

3.46 (88)

Maximum Length of 4-wire RS485 Network with Standard Cable


Number of Sepam units
1.18(1) (30) (144)
5.67

Maximum length with 12 V DC power supply


1000 ft (320 m) 590 ft (180 m) 520 ft (160 m) 410 ft (125 m)

Maximum length with 24 V DC power supply


3300 ft 2500 ft 1500 ft 1200 ft (1000 m) (750 m) (450 m) (375 m)

5 10 20 25

(1) 70 mm (2.8 in) with CCA612 cable connected


Power supply or

Description and Dimensions


A and B Terminal blocks for network cable C RJ45 socket to connect the interface to the base unit with a CCA612 cable D Terminal block for a separate auxiliary power supply (12 V DC or 24 V DC) t Grounding terminal

-wire RS485 networks

Power supply or

1 Link activity LED, ashes when communication is active (sending or receiving in progress). 2 Jumper for 4-wire RS485 network line-end impedance matching with load resistor (Rc = 150 W), to be set to: b Rc , if the module is not at one end of the network (default position) b Rc, if the module is at one end of the network. 3 Network cable clamps (inner diameter of clamp = 0.24 in or 6 mm).

DE80129

Connection
b Connection of network cable to screw-type terminal blocks A and B b Connection of the grounding terminal by tinned copper braid with cross-section AWG 10 (6 mm) or cable with cross-section AWG 12 (2.5 mm) and length 7.9 in (200 mm), tted with a 0.16 in (4 mm) ring lug. Check the tightness (maximum tightening torque 19.5 lB-in or 2.2 Nm). b The interfaces are tted with clamps to hold the network cable and recover shielding at the incoming and outgoing points of the network cable: v the network cable must be stripped v the cable shielding braid must be around and in contact with the clamp b The interface is to be connected to connector C on the base unit using a CCA612 cable (length = 9.8 ft or 3 m, green ttings) b The interfaces are to be supplied with 12 V DC or 24 V DC b The ACE959 can be connected to a separate distributed power supply (not included in shielded cable). Terminal block D is used to connect the distributed power supply module. 161

networks RS485 -wire

Power supply or

(1) Distributed power supply with separate wiring or included in the shielded cable (3 pairs). (2) Terminal block for connection of the distributed power supply module. Note: The shield connection should be grounded at only one end of the serial daisy chain.

Communication Interfaces

ACE937 Fiber Optic Interface


Function

PE50024

The ACE937 interface is used to connect Sepam to a ber optic communication wye system. This remote module is connected to the Sepam base unit by a CCA612 cable.

Characteristics
ACE937 Module
Weight Assembly Power supply Operating temperature Environmental characteristics 0.22 lb (0.1 kg) On symmetrical DIN rail Supplied by Sepam -13F to +158F (-25C to +70C) Same characteristics as Sepam base units Graded-index multimode silica 820 nm (invisible infrared) ST (BFOC bayonet ber optic connector)

ACE937 ber optic connection interface.

Fiber Optic Interface


Fiber type Wavelength Type of connector

Fiber Optic Diameter (m) HAZARD OF BLINDING Never look directly into the end of the ber optic. Failure to follow this instruction can cause serious injury.

Numerical Aperture (NA)


0.2 0.275 0.3 0.37

Maximum Attenuation (dBm/km)


2.7 3.2 4 6

Minimum Optical Power Available (dBm)


5.6 9.4 14.9 19.2

Maximum Fiber Length


2300 ft (700 m) 5900 ft (1800 m) 9200 ft (2800 m) 8500 ft (2600 m)

CAUTION

50/125 62.5/125 100/140 200 (HCS)

Maximum length calculated with: b Minimum optical power available b Maximum ber attenuation b Losses in two ST connectors: 0.6 dBm b Optical power margin: 3 dBm (according to IEC 60870 standard) Example for a 62.5/125 m Fiber Lmax = (9.4 - 3 - 0.6)/3.2 = 1.8 km (1.12 mi)

DE80037

in. (mm)

Description and Dimensions


C RJ45 socket to connect the interface to the base unit with a CCA612 cable.
3.46 (88)

1 Link activity LED, ashes when communication is active (sending or receiving in progress). 2 Rx, female ST type connector (Sepam receiving). 3 Tx, female ST type connector (Sepam sending).

1.18(1) (30) 2.83 (72)

(1) 70 mm (2.8 in) with CCA612 cable connected.

Connection
b The sending and receiving ber optic bers must be equipped with male ST type connectors b Fiber optics screw-locked to Rx and Tx connectors The interface is to be connected to connector C on the base unit using a CCA612 cable (length = 3 m or 9.8 ft, green ttings).
DE51666

162

Communication Interfaces

ACE969TP and ACE969FO Interfaces Network


Function

PE50470

ACE969TP communication interface

The ACE969 multi-protocol communication interfaces are for Sepam Series 20, Series 40, and Series 80. They have two communication ports to connect a Sepam to two independent communication networks: b The S-LAN (Supervisory Local Area Network) port is used to connect Sepam to a communication network dedicated to supervision, using one of the three following protocols: v IEC 60870-5-103 v DNP3 v Modbus RTU The communication protocol is selected at the time of Sepam parameter setting. b The E-LAN (Engineering Local Area Network) port, reserved for Sepam remote parameter setting and operation using the SFT2841 software There are two versions of the ACE969 interfaces that are identical except for the S-LAN port: b ACE969TP (Twisted Pair), for connection to an S-LAN network using a 2-wire RS485 serial link b ACE969FO (Fiber Optic), for connection to an S-LAN network using a ber-optic connection (wye or ring) The E-LAN port is always a 2-wire RS485 type port.

PE50471

ACE969FO communication interface

163

Communication Interfaces

ACE969TP and ACE969FO Interfaces Network


Characteristics
ACE969 Module
Technical Characteristics
Weight Assembly Operating temperature Environmental characteristics 0.628 lb (0.285 kg) On symmetrical DIN rail -13F to +158F (-25C to +70C) Same characteristics as Sepam base units 24 to 250 V DC -20%/+10% 2W < 10 A 100 ms 12% 20 ms 110 to 240 V AC -20%/+10% 3 VA

Power Supply
Voltage Range Maximum consumption Inrush current Acceptable ripple content Acceptable momentary outages

2-wire RS485 Communication Ports


Electrical Interface
Standard Distributed power supply Power consumption Max. number of Sepam units
Number of Sepam Units

EIA 2-wire RS485 differential External, 12 V DC or 24 V DC 10% 16 mA in receiving mode 40 mA in sending mode 25
With Distributed Power Supply 12 V DC 24 V DC

Maximum Length of 2-wire RS485 Network


5 10 20 25 1000 ft (320 m) 590 ft (180 m) 430 ft (130 m) 410 ft (125 m) 3300 ft (1000 m) 2500 ft (750 m) 1500 ft (450 m) 1200 ft (375 m)

Fiber Optic Communication Port


Fiber Optic Interface
Fiber type Wavelength Type of connector
Fiber Diameter (m) Numerical Aperture (NA)

Graded-index multimode silica 820 nm (invisible infrared) ST (BFOC bayonet ber optic connector)
Attenuation (dBm/km) Minimum Optical Power Available (dBm) Maximum Fiber Length

Maximum Length of Fiber Optic Network

50/125 62.5/125 100/140 200 (HCS)

Maximum length calculated with: b Minimum optical power available b Maximum ber attenuation b Losses in two ST connectors: 0.6 dBm b Optical power margin: 3 dBm (according to IEC 60870 standard). Example for a 62.5/125 m Fiber Lmax = (9.4 - 3 - 0.6)/3.2 = 1.8 km (1.12 mi).

0.2 0.275 0.3 0.37

2.7 3.2 4 6

5.6 9.4 14.9 19.2

2300 ft (700 m) 5900 ft (1800 m) 9200 ft (2800 m) 8500 ft (2600 m)

Dimensions
in. (mm)
DE80043

3.54 (90)

5.67 (144)

2.05 (52)

164

Communication Interfaces

ACE969TP and ACE969FO Interfaces Network Description


ACE969 Communication Interfaces
ACE969TP
DE51855 DE51856

1 Grounding/grounding terminal using supplied braid 2 Power-supply terminal block 3 RJ45 connector to connect the interface to the base unit with a CCA612 cable 4 Green LED: ACE969 energized 5 Red LED: ACE969 interface status b LED off = ACE969 set up and communication operational b LED ashing = ACE969 not set up or setup incorrect b LED remains on = ACE969 has faulted 6 Service connector: reserved for software upgrades 7 E-LAN 2-wire RS485 communication port (ACE969TP and ACE969FO) 8 S-LAN 2-wire RS485 communication port (ACE969TP) 9 S-LAN ber-optic communication port (ACE969FO).

ACE969FO
3 4 5 6

Rx Rx Tx on

Tx

N S-LA

V+ V-

N E-LA B A

O 969F ACE

1 2-wire RS485 network terminal block: b 2 black terminals: connection of RS485 twisted-pair (2 wires) b 2 green terminals: connection of twisted-pair for distributed power supply 2 Indication LEDs: b ashing Tx LED: Sepam sending b ashing Rx LED: Sepam receiving. 3 Clamps and recovery of shielding for two network cables, incoming and outgoing (inner diameter of clamp = 0.236 in or 6 mm) 4 Fixing stud for network cable ties 5 Jumper for RS485 network line-end impedance matching with load resistor (Rc = 150 W), to be set to: b Rc, if the interface is not at the line end (default position) b Rc, if the interface is at the line end.

2-wire RS485 Communication Ports


Port S-LAN (ACE969TP) Port E-LAN (ACE969TP or ACE969FO)

DE51863

Rx

Tx

on

Rx

Tx

DE51864

serv

Rx

S-LAN V+ V- A B

E-LAN V+ V - A B

Rc Rc

Rc Rc

Fiber-Optic Communication Port


1 Indication LEDs: b ashing Tx LED: Sepam sending b ashing Rx LED: Sepam receiving. 2 Rx, female ST-type connector (Sepam receiving) 3 Tx, female ST-type connector (Sepam sending). Port S-LAN (ACE969FO)
DE51865

Rx

Tx S-LAN

on

serv
Rx

Tx

E-LAN V+ V - A B

Rc Rc

Tx

Rx

165

Communication Interfaces

ACE969TP and ACE969FO Interfaces Network Connection


Power Supply and Sepam
b The ACE969 interface connects to connector C on the Sepam base unit using a CCA612 cable (length = 9.84 ft or 3 m, green RJ45 ttings) b The ACE969 interface must be supplied with 24 to 250 V DC or 110 to 230 V AC.

HAZARD OF ELECTRIC SHOCK, EXPLOSION OR ARC FLASH b Only qualied personnel should install this equipment. Such work should be performed only after reading this entire set of instructions and checking the technical characteristics of the device. b NEVER work alone. b Turn off all power supplying this equipment before working on or inside it. Consider all sources of power, including the possibility of backfeeding. b Always use a properly rated voltage sensing device to conrm that all power is off. b Start by connecting the device to the protective ground and to the functional ground. b Screw tight all terminals, even those not in use. Failure to follow these instructions will result in death or serious injury.

DANGER

Terminals
e1-e2 - supply
DE51727

Type
Screw terminals

Wiring
b Wiring with no ttings: v 1 wire with maximum cross-section 0.2 to 2.5mm ( AWG 24-12) v or 2 wires with maximum cross-section 0.2 to 1 mm ( AWG 24-18) v stripped length: 8 to 10 mm (0.31 to 0.39 in) b Wiring with ttings: v recommended wiring with Telemecanique tting: - DZ5CE015D for 1 wire 1.5 mm (AWG 16) - DZ5CE025D for 1 wire 2.5 mm (AWG 12) - AZ5DE010D for 2 wires 1 mm (AWG 18) v wire length: 8.2 mm (0.32 in) v stripped length: 8 mm (0.31 in). 1 green/yellow wire, max. length 9.8 ft (3 m) and max. cross-section AWG 12 (2.5 mm) Grounding braid, supplied for connection to cubicle grounding

DE51845 DE51962

Protective ground Functional ground

Screw terminal 0.16 in (4 mm) ring lug

166

Communication Interfaces

ACE969TP and ACE969FO Interfaces Network Connection


2-wire RS485 Communication Ports (S-LAN or E-LAN)
b Connection of RS485 twisted pair (S-LAN or E-LAN) to black terminals A and B b Connection of twisted pair for distributed power supply to green terminals V+ and Vb The interfaces are tted with clamps to hold the network cable and recover shielding at the incoming and outgoing points of the network cable: v the network cable must be stripped v the cable shielding must be around and in contact with the clamp v shielding continuity of incoming and outgoing cables is ensured by the electrical continuity of the clamps b All cable clamps are linked by an internal connection to the grounding terminals of the ACE969 interface (protective and functional grounding), that is, the shielding of the RS485 cables is grounded as well b On the ACE969TP interface, the cable clamps for the S-LAN and E-LAN RS485 networks are grounded
Note: The shield connection should be grounded at only one end of the serial daisy chain.

Control Power
DE52078

AC/DC + AC/DC

ACE969TP

Not Connected

Common Ground

Shield (Typical)

Chassis Common Ground

DE52165

Fiber Optic Communication Port (S-LAN) CAUTION


HAZARD OF BLINDING Never look directly into the ber optic. Failure to follow this instruction can cause serious injury. The ber optic connection can be made: b point-to-point to an optic wye system b in a ring system (active echo) The sending and receiving ber optic bers must be equipped with male ST type connectors. The ber optics are screw-locked to Rx and Tx connectors.

167

Converters

ACE9092 RS232/RS485 Converter


Function

PE50035

The ACE9092 converter is used to connect a master/central computer equipped with a V24/RS232 type serial port as a standard feature to stations connected to a 2-wire RS485 network. After the parameters are set, the ACE9092 converter performs conversion and network polarization. It also automatically dispatches frames between the master and the stations by two-way simplex (half-duplex, single-pair) transmission. This is all done without requiring any ow control signals. The ACE9092 converter also provides a 12 V DC or 24 V DC supply for the distributed power supply of the Sepam ACE9492, ACE959 or ACE969 interfaces. The communication settings should be the same as the Sepam and supervisor communication settings.
ACE9092 RS232/RS485 converter.

HAZARD OF ELECTRIC SHOCK, EXPLOSION OR ARC FLASH b Only qualied personnel should install this equipment. Such work should be performed only after reading this entire set of instructions and checking the technical characteristics of the device. b NEVER work alone. b Turn off all power supplying this equipment before working on or inside it. Consider all sources of power, including the possibility of backfeeding. b Always use a properly rated voltage sensing device to conrm that all power is off. b Start by connecting the device to the protective ground and to the functional ground. b Screw tight all terminals, even those not in use. Failure to follow these instructions will result in death or serious injury.

DANGER

Characteristics
Mechanical Characteristics
Weight Assembly 0.617 lb (0.280 kg) On symmetrical or asymmetrical DIN rail 110 to 220 V AC 10%, 47 to 63 Hz 2000 Vrms, 50 Hz, 1 min

Electrical Characteristics
Power supply Galvanic isolation between ACE power supply and frame, and between ACE power supply and interface supply Galvanic isolation between RS232 and RS485 interfaces Protection by time-delayed fuse 5 mm x 20 mm (0.2 in x 0.79 in) Data format Transmission delay Distributed power supply for Sepam interfaces Maximum number of Sepam interfaces with distributed supply

1000 Vrms, 50 Hz, 1 min 1 A rating

Communication and Sepam Interface Distributed Supply


11 bits: 1 start, 8 data, 1 parity, 1 stop < 100 ns 12 V DC or 24 V DC 12

Environmental Characteristics
Operating temperature +23F to +131F (-5C to +55C)

Electromagnetic Compatibility
Fast transient bursts, 5 ns

IEC standard
60255-22-4

Value
4 kV with capacitive tie breaker in common mode 2 kV with direct tie breaker in common mode 1 kV with direct tie breaker in differential mode 1 kV common mode 0.5 kV differential mode 3 kV common mode 1 kV differential mode

1 MHz damped oscillating wave 1.2/50 s pulse waves

60255-22-1 60255-5

168

Converters

ACE9092 RS232/RS485 Converter


Description and Dimensions
A Terminal block for RS232 link limited to 33 ft (10 m).
B Female 9-pin sub-D connector to connect to the 2-wire RS485 network, with
3.35 (85) 4.13 (105)

DE80038

in. (mm)

distributed power supply. 1 screw-type male 9-pin sub-D connector is supplied with the converter. C Power-supply terminal block 1 Distributed power supply voltage selector switch, 12 V DC or 24 V DC. 2 Protection fuse, unlocked by a 1/4 turn. 3 LEDs: b ON/OFF: on if ACE9092 is energized b Tx: on if RS232 sending by ACE9092 is active b Rx: on if RS232 receiving by ACE9092 is active. 4 SW1, parameter setting of 2-wire RS485 network polarization and line impedance matching resistors. Function
Polarization at 0 V via Rp -470 W Polarization at 5 V via Rp +470 W 2-wire RS485 network impedance matching by 150 W resistor

4.13 (105)

1.77 (45) 2.56 (65)

DE80022

in. (mm) 2.22 (56.4)

1.75 (44.5)

SW1/1
ON

SW1/2
ON

SW1/3

1.42 (36)

ON

0.63 (16)

5 SW2, parameter setting of asynchronous data transmission rate and format (same parameters as for RS232 link and 2-wire RS485 network). Rate (baud) SW2/1 SW2/2 SW2/3
1200 2400 4800 9600 19200 38400 1 0 1 0 1 0 1 1 0 0 1 1 1 1 1 1 0 0

Male 9-pin sub-D connector supplied with the ACE9092.

DE51668

Format
With parity check Without parity check 1 stop bit (compulsory for Sepam) 2 stop bits

SW2/4
0 1

SW2/5

0 1

Converter Conguration when Delivered b 12 V DC distributed power supply b 11-bit format, with parity check b 2-wire RS485 network polarization and impedance matching resistors activated.

Connection
RS232 Link b b b b To AWG 12 (2.5 mm) screw-type terminal block A Maximum length 33 ft (10 m) Rx/Tx: RS232 receiving/sending by ACE9092 0V: Rx/Tx common, do not ground.

2-wire RS485 Link with Distributed Power Supply b To connector B female 9-pin sub-D b 2-wire RS485 signals: L+, Lb Distributed power supply: V+ = 12 V DC or 24 V DC, V- = 0 V. Power Supply b To AWG 12 (2.5 mm) screw-type terminal block C b Reversible phase and neutral b Grounded via terminal block and metal case (ring lug on back of case).

169

Converters

ACE919CA and ACE919CC RS485/RS485 Converters


Function

PE50036

The ACE919 converters are used to connect a master/central computer equipped with an RS485 type serial port as a standard feature to stations connected to a 2-wire RS485 network. The ACE919 converters perform network polarization and impedance matching without requiring any ow control signals. The ACE919 converters also provide a 12 V DC or 24 V DC supply for the distributed power supply of the Sepam ACE9492, ACE959 or ACE969 interfaces. There are two types of ACE919 converter: b ACE919CC, DC-powered b ACE919CA, AC-powered.
ACE919CC RS485/RS485 converter.

HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH b Only qualied personnel should install this equipment. Such work should be performed only after reading this entire set of instructions and checking the technical characteristics of the device. b NEVER work alone. b Turn off all power supplying this equipment before working on or inside it. Consider all sources of power, including the possibility of backfeeding. b Always use a properly rated voltage sensing device to conrm that all power is off. b Start by connecting the device to the protective ground and to the functional ground. b Screw tight all terminals, even those not in use. Failure to follow these instructions will result in death or serious injury.

DANGER

Characteristics
Mechanical Characteristics
Weight Assembly 0.617 lb (0.280 kg) On symmetrical or asymmetrical DIN rail

Electrical Characteristics
Power supply Protection by time-delayed fuse 0.2 in x 0.79 in (5 mm x 20 mm) Galvanic isolation between ACE power supply and frame, and between ACE power supply and interface supply Data format Transmission delay Distributed power supply for Sepam interfaces Maximum number of Sepam interfaces with distributed supply

ACE919CA
110 to 220 V AC 10%, 47 to 63 Hz 1 A rating

ACE919CC
24 to 48 V DC 20% 1 A rating 2000 Vrms, 50 Hz, 1 min

Communication and Sepam Interface Distributed Supply


11 bits: 1 start, 8 data, 1 parity, 1 stop < 100 ns 12 V DC or 24 V DC 12

Environmental Characteristics
Operating temperature Fast transient bursts, 5 ns +23F to +131F (-5C to +55C)

Electromagnetic Compatibility IEC standard


60255-22-4

Value
4 kV with capacitive tie breaker in common mode 2 kV with direct tie breaker in common mode 1 kV with direct tie breaker in differential mode 1 kV common mode 0.5 kV differential mode 3 kV common mode 1 kV differential mode

1 MHz damped oscillating wave

60255-22-1

1.2/50 s pulse waves

60255-5

170

Converters

ACE919CA and ACE919CC RS485/RS485 Converters


Description and Dimensions

DE80039

in. (mm)

3.35 (85) 4.13 (105)

A Terminal block for 2-wire RS485 link without distributed power supply. B Female 9-pin sub-D connector to connect to the 2-wire RS485 network, with distributed power supply. 1 screw-type male 9-pin sub-D connector is supplied with the converter. C Power supply terminal block. 1 2 3 4 Distributed power supply voltage selector switch, 12 V DC or 24 V DC. Protection fuse, unlocked by a 1/4 turn. ON/OFF LED: ON if ACE919 is energized. SW1, parameter setting of 2-wire RS485 network polarization and line impedance matching resistors. Function SW1/1
ON ON ON

1.77 (45) 4.13 (105) 2.56 (65)

SW1/2

SW1/3

DE80022

in. (mm) 2.22 (56.4)

1.75 (44.5)

Polarization at 0 V via Rp -470 W Polarization at 5 V via Rp +470 W 2-wire RS485 network impedance matching by 150 W resistor
1.42 (36)

Converter Conguration when Delivered b 12 V DC distributed power supply b 2-wire RS485 network polarization and impedance matching resistors activated.

0.63 (16)

Connection
Male 9-pin sub-D connector supplied with the ACE919

2-wire RS485 Link without Distributed Power Supply b To 2.5 mm (AWG 12) screw-type terminal block A b L+, L-: 2-wire RS485 signals b Shielding. 2-wire RS485 Link with Distributed Power Supply b To connector B female 9-pin sub-D b 2-wire RS485 signals: L+, Lb Distributed power supply: V+ = 12 V DC or 24 V DC, V- = 0 V. Power supply b To AWG 12 (2.5 mm) screw-type terminal block C b Reversible phase and neutral (ACE919CA) b Grounded via terminal block and metal case (ring lug on back of case).

DE51670

171

Converters

Sepam ECI850 Server for IEC 61850


Function

PE80033-36

The ECI850 connects Sepam Series 20, Series 40, and Series 80 units to an Ethernet network using the IEC 61850 protocol. It acts as the interface between the Ethernet/ IEC 61850 network and a Sepam RS485/Modbus network. Two PRI surge arresters (catalog number 16595) are supplied with the ECI850 to protect its power supply.

Characteristics
ECI850 Module
Technical Characteristics
Weight Sepam ECI850 server for IEC 61850. Assembly 0,37 lb (0.17 kg) On symmetrical DIN rail 24 V DC (10 %) supplied by a class 2 supply 4W 1.5 kV -13 F to +158 F (-25 C to +70 C) -40 F to +185 F (-40 C to +85 C) 5 to 95 % (without condensation) at 131 F (+55 C) Class 2 IP30

Power Supply
Voltage Maximum consumption Dielectric strength Operating temperature Storage temperature Relative humidity Pollution degree Degree of protection

Environmental Characteristics

Electromagnetic Compatibility
Emission Tests
Emission (radiated and conducted) Electrostatic discharge Radiated radio-frequency elds Magnetic elds at power frequency Fast transient bursts Surges Conducted disturbances, induced by radiofrequency elds EN 55022/EN 55011/FCC Class A EN 61000-4-2 EN 61000-4-3 EN 61000-4-8 EN 61000-4-4 EN 61000-4-5 EN 61000-4-6

Immunity Tests Radiated Disturbances

Immunity Tests Conducted Disturbances

Standards
International United States Canada Australia / New Zealand IEC 60950 UL 508/UL 60950 cUL (in compliance with CSA C22.2, no. 60950) AS/NZS 60950 e

Certication
Europe

2-wire/4-wire RS485 Communication Ports


Electrical interface
Standard Max. number of Sepam units Number of Sepam Units 5 8 Number of ports Type of port Protocols Transmission rate EIA 2-wire/4-wire RS485 differential 8 Maximum Length 3300 ft (1000 m) 2500 ft (750 m)

Maximum Length of 2-wire/4-wire RS485 Network

Ethernet Communication Port


1 10/100 Base Tx HTTP, FTP, SNMP, SNTP, ARP, SFT, IEC 61850 TCP/IP 10/100 Mbits/s

172

Converters

Sepam ECI850 Server for IEC 61850


Characteristics
PRI Surge Arrester
Electrical Characteristics
Utilisation voltage Full discharge current Rated discharge current Level of protection Response time 12 to 48 V 10 kA (8/20 s wave) 5 kA (8/20 s wave) 70 V < 25 ms Normal operation Arrester must be replaced Wires with maximum cross-section of AWG 24-12 (0.5 to 2.5 mm)

Mechanical Operation Indicator


White Red

Connection
Tunnel terminals

Description
1 / LED: Power on and maintenance 2 Serial-link LEDs: b RS485 LED: link to network activated v On: RS485 mode v Off: RS232 mode v ashing TX LED: ECI850 sending v ashing RX LED: ECI850 receiving 3 Ethernet LEDs: b green LK LED on: link to network activated b ashing green Tx LED: ECI850 sending b ashing green Rx LED: ECI850 receiving b green 100 LED: b On: transmission rate = 100 Mbit/s b Off: transmission rate = 10 Mbit/s 4 10/100 Base Tx port for Ethernet connection via RJ45 connector 5 24 V DC connection 6 Reset button 7 RS485 connector 8 RS485 setup switches 9 RS232 connector
PE80063

RS485 Network Setup


The RS485 setup switches are used to select the network-polarization (bias) and line-impedance matching resistors and the type of RS485 network (2-wire/4-wire). The default settings are for a 2-wire RS485 with network-polarization and line-impedance matching resistors.

Recommended settings

Line-Impedance Matching using Resistors


2-wire RS485 4-wire RS485

DE53201

SW1
OFF ON

SW2
ON ON

SW3

SW4

SW5

SW6

Polarization (bias)
at 0 V at 5 V

SW1

SW2

SW3
ON

SW4
ON

SW5

SW6

2 wires (default)

RS485 Network Type


2-wire 1 2 3 4 5 6 4-wire 4 wires

SW1

SW2

SW3

SW4

SW5
ON OFF

SW6
ON OFF

Ethernet Link Set-up


The TCSEAK0100 conguration kit can be used to connect a PC to the ECI850 to set up the Ethernet link. 173

RS485 network setup

Converters

Sepam ECI850 Server for IEC 61850


Dimensions
DE80153

in. (mm) 2.28 (57.9) 3.18 (80.8) 3.57 (90.7)

2.59 (65.8)

1.38 (35)

1.78 (45.2)

2.83 (72)

1.95 (49.5) 2.69 (68.3)

0.10 (2.5)

CAUTION
HAZARD OF HIGH VOLTAGE SURGE DAMAGE b Connect the two PRI surge arresters as indicated in the diagrams below. b Check the quality of the grounding conductors connected to the surge arresters. The equipment may be damaged if these instructions are not followed.

b Connect the supply and the RS485 twisted pair using the 2.5 mm cable ( AWG 12). b Connect the 24 V DC supply and ground to inputs 1, 5 and 3 on the PRI surge arresters supplied with the ECI850. b Connect outputs 2 and 6 of PRI surge arresters (catalog number 16595) to the - and + terminals on the terminal block with black screws. b Connect the RS485 twisted pair (2 or 4 wires) to the terminals (RX+ RX- or RX+ RXTX+ TX-) on the terminal block with black screws. b Connect the shielding of the RS485 twisted pair to the terminal on the terminal block with black screws. b Connect the Ethernet cable to the green RJ45 connector. 2-Wire RS485 Network
DE80156

Connection

+ +24 V (1)(3)(5) PRI (2) (6) (1)(3)(5) PRI (2) (6) ECI850 (7) V+ (6) VRx+ (3) Rx- (4) (5) A B A B ACE9492 V+ VL+ LACE9492 A V+ VL+ L-

4-Wire RS485 Network


DE80157

+ +24 V (1)(3)(5)
PRI

(1)(3)(5)
PRI

(2) (6)

(2) (6)

ECI850 (7) V+ (6) VRx+ (3) Rx- (4) Tx+ (1) Tx- (2) (5)

ACE959 V+ VTx+ TxRx+ Rx-

ACE959 V+ VTx+ TxRx+ Rx-

174

Converters

Sepam ECI850 Server for IEC 61850


Architecture Example
DE53202

The diagram below shows an example of a communication architecture using the ECI850.
Supervisor or RTU

Ethernet TCP/IP/IEC 61850 ECI850 S-LAN and E-LAN Rc RS 485/Modbus ACE9492 Rc Up to 8 Sepam units ACE9492 Rc ACE9492

Sepam Series 20 Note: Rc = line-impedance matching resistor.

Sepam Series 40

Sepam Series 80

175

Converters

Ethernet EGX100 Gateway

Function
The EGX100 serves as an Ethernet gateway for PowerLogic System devices and for any other communicating devices utilizing the Modbus protocol. The EGX100 gateway offers complete access to status and measurement information provided by the connected devices, for example, via the System ManagerTM Software (SMS) installed on a PC.
E90463 PB101556

Architecture
DE52790

EGX100 Gateway

PM700 Micrologic PM800 Power Trip Unit Power

Sepam Series 20

Sepam Series 40

Sepam Series 80

Setup
Setup via an Ethernet Network Once connected to an Ethernet network, the EGX100 gateway can be accessed by a standard internet browser via its IP address to: b specify the IP address, subnet mask, and gateway address of the EGX gateway b congure the serial port parameters (baud rate, parity, protocol, mode, physical interface, and timeout value) b create user accounts b create or update the list of the connected products with their Modbus communication parameters b congure IP ltering to control access to serial devices b access Ethernet and serial port diagnostic data b update the rmware Setup via a Serial Connection Serial setup is carried out using a PC connected to the EGX100 via an RS232 link. This setup: b species the IP address, subnet mask, and gateway address of the EGX gateway b species the language used for the setup session

176

Converters

Ethernet EGX400 Server

Function
PE50538

The EGX400 server is used as an Ethernet coupler for Sepam relays, PowerLogic devices, and any other communicating devices operating under the Modbus RS485 protocol. The EGX400 contains HTML pages (set up using the WPG software tool) that can be accessed using a standard internet browser. The HTML pages are used to display the information provided by the devices connected to the server. Supervisor and Internet Browser The EGX400 server makes it possible to implement two types of user interface: b supervision software b a standard internet browser providing access to the main information organized in predened HTML pages
Ethernet EGX400 gateway

PE50270

These two approaches, supervisor and internet browser, are complementary: b the supervisor offers complete access to all information, but requires specic software b the HTML pages offer partial access to the main information via any PC connected to the network

Architecture
DE52081

Sepam Series 80

Sepam Series 20

Sepam Series 40

Setup
Initial Setup The initial setup is carried out using a PC connected to the EGX400 via an RS232 link. This setup: b species the IP address of the EGX gateway b selects the type of Ethernet port (wire or optic ber) b lists the connected products with their Modbus communication parameters Setup via the Ethernet Network Once connected to the Ethernet network, the EGX400 server can be accessed by a standard internet browser via its IP address to: b create or update the list of the connected products with their Modbus communication parameters b update the rmware

177

Converters

Ethernet EGX100 Gateway Ethernet EGX400 Server

4
DB109282

EGX100

Characteristics
EGX100
Weight Dimensions (H x W x D) Mounting 6 oz (170 g) 2.58 x 2.83 x 2.68 in (91 x 72 x 68 mm) DIN rail

EGX400
24.7 oz (700 g) 0.98 x 7.48 x 4.53 in. (25 x 190 x 115 mm) Symmetrical or asymmetrical DIN rail Front or side position None 24 V DC 100-240 V AC/24 V DC adapter supplied -22 F to 176 F -30 C to +80C 5 % to 95 % relative humidity (without condensation) at 104 F (+40 C) EN 55022/FCC class A EN 61000-6-2 EN 61000-4-2 EN 61000-4-3 EN 61000-4-4 EN 61000-4-5 EN 61000-4-8 EN 61000-4-11

Power-over-Ethernet (PoE) Power supply

Class 3 24 V DC if not using PoE

Operating temperature Humidity rating

-13 F to 158 F (-25 C to +70C) 5 % to 95 % relative humidity (without condensation) at 131 F (+55 C) EN 55022/EN 55011/ FCC class A EN 61000-6-2 EN 61000-4-2 EN 61000-4-3 EN 61000-4-4 EN 61000-4-5 EN 61000-4-6 EN 61000-4-8

Regulatory/Standards Compliance for Electromagnetic Interference


1 2 3 4 5 6 7 8 24 Vbc power connection. 10/100 Base TX (802.3af) port for connection to Ethernet via an RJ45 connector. Ethernet and serial indication LEDs. Power/Status LED. Reset button. RS485 connection. Dip switches for biasing, termination, and 2-wire/4-wire jumpers. RS232 connection. Emissions (radiated and conducted) Immunity for industrial environments: - electrostatic discharge - radiated RF - electrical fast transients - surge - conducted RF - power frequency magnetic eld International (CB scheme) USA Canada Europe Australia/New Zealand

EGX400

Regulatory/Standards Compliance for Safety


IEC 60950 UL508/UL60950 cUL (complies with CSA C22.2, no. 60950) EN 60950 AS/NZS25 60950 1 RS232 or RS485 (2-wire or 4-wire), depending on settings UL508 cUL (complies with CSA C22.2, no. 14-M91)

Serial Ports
Number of ports Types of ports
DB100978

Power connector. Ethernet indication LEDs. 10/100 Base TX port for connection to Ethernet via an RJ45 connector. 4 100 Base FX port for connection to Ethernet via ber optic cable (LC connector). 5 COM1: terminal block for RS485 serial link. 6 COM1 indication LEDs. 7 COM2: terminal block for RS485 serial link. 8 COM2 indication LEDs. 9 Dip-switches for setup of COM1 and COM2 ports bias and termination. 10 COM2: Sub D-9 connector for the RS232 serial link.

1 2 3

Protocol Maximum baud rate Maximum number of directly connected devices

Modbus RTU/ASCII PowerLogic (SY/MAX) 38400 or 57600 baud depending on settings 32

2 COM1: RS485 (2-wire or 4-wire) COM2: RS232 or RS485 (2-wire or 4-wire), depending on settings Modbus RTU/ASCII PowerLogic (SY/MAX) 38400 baud 32 per port, 64 in all

Ethernet Port
Number of ports Types of ports 1 One 10/100 base TX (802.3af) port HTTP, SNMP, FTP, Modbus TCP/IP 10/100 MB None 2 One 10/100 base TX port One 100 base FX port (multimode optic ber) HTTP, SNMP, SMTP, SNTP, FTP, Modbus TCP/IP 10/100 MB 16 MB

Protocol Baud rate

Web Server
Memory for custom HTML pages

178

Converters

Ethernet EGX100 Gateway Ethernet EGX400 Server

Installation DIN Rail Mounting (EGX100)


DE52765 DE52766

in. (mm) 2.26 (57.29)

in. (mm)

4
2.59 (65.8)

1.38 (35)

3.18 (80.8) 3.57 (90.7)

1.78 (45.2)

2.83 (72)

1.95 (49.5) 2.69 (68.3)

0.10 (2.5)

Side Mounting on DIN Rail (EGX400)


DE52767 DE52768

in. (mm) 1.38 (35) 4.84 (123) 2.36 (60) 7.91 (201) 8.70 (221)

in. (mm)

0.59 (15)

1.10 (28)

Front Mounting on DIN Rail (EGX400)


DE52769 DE52770

in. (mm)

in. (mm)

1.38 (35)

7.91 (201) 3.94 (100)

1.10 (28) 1.93 (49)

0.43 (11)

0.59 (15)

4.84 (123)

179

Converters

WPG Software Tool HTML Page Generator


Function
Easy to use, the WPG software tool generates HTML pages for the EGX400 server. It is used to: b select the devices connected to the server b transfer the HTML pages corresponding to the selected devices to the server. The WPG tool can set up HTML pages for the following devices: b Sepam Series 20, Sepam Series 40, Sepam Series 80 b Masterpact equipped with Micrologic A, P and H control units b Power Meter PM700 and PM800 b Circuit Monitor Series 2000, 3000 and 4000 The WPG software is available in English, French, and Spanish. To obtain WPG, contact your Schneider Electric representative.

PE50271

HTML page with summary information on all the equipment in a switchboard.

HTML Pages
Following transfer, the EGX400 contains HTML pages that can be used to remotely monitor equipment under secure conditions. b 1st service level based on the summary pages. b 2nd service level based on specic pages for each type of device. Summary Pages Five summary pages are available for overall monitoring of the switchboard. They present the main measurements input by the devices connected to the server. b Page 1 v 3-phase average rms current v active power v power factor v circuit-breaker position b Page 2 v rms current per phase b Page 3 v demand current per phase b Page 4 v demand power v maximum power v time-stamping data b Page 5 v active power v reactive power v date and time of last reset of energy meters Specic Pages for each Device A number of specic pages present detailed information on each device for in-depth analysis, such as: b operating information: v instantaneous current per phase v demand current per phase v active and reactive power v average voltage (line-to-neutral and line-to-line) v maximum unbalance v power factor v frequency b event information: v minimum and maximum current values v maximum demand current v date and time of last reset b historical data: v recording over 38 days of three user-selectable parameters (energy by default), every 15, 30 or 60 minutes, with graphic display and data export to an Excel le

PE50272

Single device operating information HTML page.

PE50273

Single device HTML page showing historical data.

180

Sensors

Selection Guide

Phase Current Sensors


Selection Guide

Two types of sensor may be used with Sepam to measure phase current: b 1 A or 5 A current transformers b LPCT (Low Power Current Transducer) type current sensors

1 A or 5 A current sensors are: b sized case by case: accuracy, electrical characteristics, etc. b dened according to the IEC 60044-1 standard The LPCT type current sensors are: b simple sizing: a given LPCT sensor is suitable for measuring different rated currents: for example, the CLP1 sensor measures rated currents of 25 to 1250 A b dened according to IEC 60044-8 standard (rated secondary voltage = 22.5 mV)

Residual Current Sensors

The residual current value can be obtained from different sensors and assemblies chosen according to the performance required (measurement accuracy and ground fault protection sensitivity). Residual current can be: b measured by a specic CSH120 or CSH200 zero sequence CT b measured by a zero sequence CT with a ratio of 1/n (50 n 1500), with an ACE990 adapter. b calculated by Sepam from the vector sum of the three phase currents

Selection Guide
Measurement Sensors
CSH120 or CSH200 Zero Sequence CT connected to CCA634 1 or 3 x 1 A or 5 A CT+ CSH30 Zero Sequence CT + ACE990 3-Phase CT (Ir calculated by Sepam)

Recommended Minimum Set Point


> 1A

0.10 INCT (DT) 0.05 INCT (IDMT) 0.10 INCT (DT) 0.05 INCT (IDMT) 0.30 INCT (DT) (1) 0.10 INCT (IDMT) (1)

(1) Recommended minimum set point for ANSI 50N/51N function with H2 restraint: 0.10 INCT (DT) or 0.05 INCT (IDMT).

It is recommended not to set the ground fault protection functions below the recommended minimum set point. This avoids any risk of unwanted tripping caused by oversensitive detection of residual current or false residual current due to CT saturation. Lower settings may be used to trigger alarms.

181

Sensors

Voltage Transformers

058734NSD

Function

Sepam can be connected to any standard voltage transformer with a rated secondary voltage of 100 V to 220 V. Schneider Electric offers a range of voltage transformers: b to measure line-to-neutral voltages: voltage transformers with one insulated MV terminal b to measure line-to-line voltages: voltage transformers with two insulated MV terminals b with or without integrated protection fuses
ANSI voltage transformer.

Consult us for more information.

Connection
The voltage transformers connect to Sepam: b directly, for Sepam Series 40 and Series 80 b or via the CCT640 connector for Sepam B21, B22 and the additional voltage inputs for Sepam B83 The table below presents the different connection possibilities for voltage transformers to Sepam. Sepam Sepam Sepam B21 and B22 Series 40 Series 80
Number of voltage inputs Intermediate connector Sepam connector (1) Sepam B83 only. 4 CCT640 B 3 E 4 main E 4 additional (1) CCT640 B2

When voltage transformers are connected directly to the E connector on Sepam, four transformers built into the Sepam base unit ensure matching and isolation between the VTs and the Sepam input circuits. When voltage transformers are connected via the CCT640 connector, the four transformers for matching and isolation between the VTs and the Sepam input circuits are contained in the CCT640.

182

Sensors

1A/5A Current Transformers

Function
120R302

Sepam can be connected to any standard 1A or 5A current transformer. Schneider Electric offers a range of current transformers to measure primary currents from 50 A to 2500 A. Consult a representative for more information.

Sizing Current Transformers


ANSI current transformer.

Current transformers are sized so as not to be saturated by the current values they are required to measure accurately (minimum 5 In).

For Overcurrent Protection Functions

b with DT tripping curve: the saturation current must be 1.5 times greater than the setting b with IDMT tripping curve: the saturation current must be 1.5 times greater than the highest working value on the curve. Practical solution when there is no information on the settings
Rated Secondary Current (IN) 1A 5A Accuracy Burden 2.5 VA 7.5 VA Accuracy Class 5P 20 5P 20 CT Secondary Resistance RCT <3 < 0.2 Wiring Resistance Rf < 0.075 < 0.075

183

Sensors

1A/5A Current Transformers

CCA630/CCA634 Connector
DE80051

c Ia Ib Ic

Function
The current transformers (1 A or 5 A) are connected to the CCA630 or CCA634 connector on the rear panel of Sepam: b The CCA630 connector is used to connect 3 phase current transformers to Sepam b The CCA634 connector is used to connect 3 phase current transformers and a residual current transformer to Sepam The CCA630 and CCA634 connectors contain interposing ring CTs with through primaries, which ensure impedance matching and isolation between the 1A or 5A circuits and Sepam when measuring phase and residual currents. The connectors can be disconnected with the power on since disconnection does not open the CT secondary circuit.

DE80059

CCA634

DANGER
Ia Ib Ic

HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH b Apply appropriate personal protective equipment (PPE) and follow safe electrical work practices. In the USA, see NFPA 70E b Only qualied personnel should install this equipment. Such work should be performed only after reading this entire set of instructions and checking the technical characteristics of the device b NEVER work alone. b Before performing visual inspections, tests, or maintenance of this equipment, disconnect all sources of electric power. Assume all circuits are live until they have been completely de-energized, tested, and tagged. Pay particular attention to the design of the power system. Consider all sources of power, including the possibility of backfeeding b Turn off all power supplying this equipment before working on or inside it. Consider all sources of power, including the possibility of backfeeding b Always use a properly rated voltage sensing device to conrm that all power is off b To remove current inputs to the Sepam unit, unplug the CCA630 or CCA634 connector without disconnecting the wires from it. The CCA630 and CCA634 connectors ensure continuity of the current transformer secondary circuits b Before disconnecting the wires connected to the CCA630 or CCA634 connector, short-circuit the current transformer secondary circuits Failure to follow these instructions will result in death or serious injury.

184

Sensors

1A/5A Current Transformers

Connecting and Assembling the CCA630 Connector


1. Open the two side shields for access to the connection terminals. The shields can be removed, if necessary, to make wiring easier. If removed, they must be replaced after wiring. 2. If necessary, remove the bridging strap linking terminals 1, 2 and 3. This strap is supplied with the CCA630. 3. Connect the wires using 0.16 in (4 mm) ring lugs and check the tightness of the six screws that guarantee the continuity of the CT secondary circuits. The connector accommodates wires with cross-sections of AWG 16-10 (1.5 to 6 mm). 4. Close the side shields. 5. Plug the connector into the 9-pin inlet on the rear panel (item B ). 6. Tighten the two CCA630 connector fastening screws on the Sepam rear panel.
MT10490

DE80068

DE80069

Connecting and Assembling the CCA634 Connector


1. Open the two side shields for access to the connection terminals. The shields can be removed, if necessary, to make wiring easier. If removed, they must be replaced after wiring. 2. According to the wiring required, remove or reverse the bridging strap. This is used to link either terminals 1, 2 and 3, or terminals 1, 2, 3 and 9 (see picture opposite). 3. Use terminal 7 (1 A) or 8 (5 A) to measure the residual current according to the CT secondary. 4. Connect the wires using 0.16 in (4 mm) ring lugs and check the tightness of the six screws that ensure the continuity of the CT secondary circuits. The connector accommodates wires with cross-sections of AWG 16-10 (1.5 to 6 mm). The wires only exit from the base. 5. Close the side shields. 6. Insert the connector pins into the slots on the base unit. 7. Flatten the connector against the unit to plug it into the 9-pin SUB-D connector (principle similar to that of the MES module). 8. Tighten the mounting screw.

Bridging of terminals 1, 2, 3 and 9

Bridging of terminals 1, 2 and 3

CAUTION
HAZARD OF IMPROPER OPERATION Sepam Series 20, Sepam Series 40 b Do not connect the connector A residual current input Ir (terminals 18 and 19) and the CCA634 residual current input (terminal 9 and 7 or 8) simultaneously. These two residual current input use the same Sepam analog channel. Sepam Series 80 b Do not use a CCA634 on connector B1 and residual current input Ir on connector E (terminals 14 and 15) simultaneously. Even if it is unconnected to a sensor, a CCA634 on connector B1 will disturb input Ir on connector E. b Do not use a CCA634 on connector B2 and residual current input Ir on connector E (terminals 17 and 18) simultaneously b Even if it is not connected to a sensor, a CCA634 on connector B2 will disturb input Ir on connector E. Failure to follow this instruction can cause equipment damage.

185

Sensors

LPCT Type Current Sensors

PE50031

Function

Low Power Current Transducer (LPCT) type sensors are voltage-output sensors, which are compliant with the IEC 60044-8 standard. The Schneider Electric range of LPCTs includes the following sensors: CLP1, CLP2, CLP3, TLP160 and TLP190.

CLP1 LPCT sensor

CCA670/CCA671 Connector
DE51674

Function
The three LPCT sensors are connected to the CCA670 or CCA671 connector on the rear panel of Sepam. Connecting fewer than three LPCT sensors is not allowed and causes Sepam to go into fail-safe position. The two CCA670 and CCA671 interface connectors serve the same purpose, the difference being the position of the LPCT sensor plugs: b CCA670: lateral plugs, for Sepam Series 20 and Series 40 b CCA671: radial plugs, for Sepam Series 80

Description
1 Three RJ45 plugs to connect the LPCT sensors. 2 Three blocks of microswitches to set the CCA670/CCA671 to the rated phase current value. 3 Microswitch setting/selected rated current equivalency table (2 IN values per position). 4 9-pin sub-D connector to connect test equipment (ACE917 for direct connector or via CCA613).

Rating of CCA670/CCA671 Connectors


The CCA670/CCA671 connector must be rated according to the rated primary current IN measured by the LPCT sensors. IN is the current value that corresponds to the rated secondary current of 22.5 mV. The possible settings for IN are (in A): 25, 50, 100, 125, 133, 200, 250, 320, 400, 500, 630, 666, 1000, 1600, 2000, 3150. The selected IN value should be: b entered as a Sepam general setting b congured by microswitch on the CCA670/CCA671 connector Operating Mode: 1. Use a screwdriver to remove the shield located in the LPCT settings zone; the shield protects three blocks of eight microswitches marked L1, L2, L3. 2. On the L1 block, set the microswitch for the selected rated current to 1 (2 IN values per microswitch). b The table of equivalencies between the microswitch settings and the selected rated current IN is printed on the connector b Leave the seven other microswitches set to 0. 3. Set the other two blocks of switches L2 and L3 to the same position as the L1 block and close the shield.

CAUTION
HAZARD OF NON-OPERATION b Set the microswitches for the CCA670/ CCA671 connector before commissioning the device. b Check that only one microswitch is in position 1 for each block L1, L2, L3 and that no microswitch is in the center position. b Check that the microswitch settings on all 3 blocks are identical. Failure to follow these instructions can cause incorrect operation. 186

Sensors

LPCT Type Current Sensors Test Accessories


Accessory Connection Principle DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH b Only qualied personnel should install this equipment. Such work should be performed only after reading this entire set of instructions. b NEVER work alone. b Turn off all power supplying this equipment before working on or inside it. Consider all sources of power, including the possibility of backfeeding. b Always use a properly rated voltage sensing device to conrm that all power is off. Failure to follow these instructions will result in death or serious injury.

DE51675

1 LPCT sensor, equipped with a shielded cable tted with a yellow RJ 45 plug which is plugged directly into the CCA670/CCA671 connector.
a b c

2 Sepam protection unit. 3 CCA670/CCA671 connector, LPCT voltage interface, with microswitch setting of rated current: b CCA670: lateral plugs for Sepam Series 20 and Series 40 b CCA671: radial plugs for Sepam Series 80 4 CCA613 remote test plug, ush-mounted on the front of the cubicle and equipped with a 9.84 ft (3-meter) cable to be plugged into the test plug of the CCA670/ CCA671 interface connector (9-pin sub-D). 5 ACE917 injection adapter, to test the LPCT protection chain with a standard injection box. 6 Standard injection box.

c b a

a b c

a b c

187

Sensors

LPCT Type Current Sensors Test Accessories


ACE917 Injection Adapter

DE80065

in. (mm)

Function
The ACE917 adapter is used to test the protection chain with a standard injection box, when Sepam is connected to LPCT sensors. The ACE917 adapter is inserted between: b The standard injection box b The LPCT test plug: v integrated in the Sepam CCA670/CCA671 interface connector v or transferred by means of the CCA613 accessory The following are supplied with the ACE917 injection adapter: b Power supply cable b 9.84 ft (3-meter) cable to connect the ACE917 to the LPCT test plug on CCA670/CCA671 or CCA613.

2.76 (70)

10.24 (260) 6.69 (170)

Characteristics
Power supply Protection by time-delayed fuse 5 mm x 20 mm (0.2 x 0.79 in ) 115/230 V AC 0.25 A rating

DE50564

CCA613 Remote Test Plug


Function
The CCA613 test plug, ush-mounted on the front of the cubicle, is equipped with a 9.84 ft (3-meter) cable to transfer data from the test plug integrated in the CCA670/ CCA671 interface connector on the rear panel of Sepam.

Dimensions
DE80045 DE80117

in. (mm)

in. (mm)

Mounting lug

Accessory connection principle


Cable

2.66 (67.5)

2.66 (67.5)

1.73 (44)

0.51 (13)

1.97 (50) 3.15 (80)

Front view with cover lifted


in. (mm)

Right side view

2.72 (69)

1.81 (46)

Cut-out

188

Sensors

CSH120 and CSH200 Zero Sequence CTs


Function

PE50032

The specically designed CSH120 and CSH200 zero sequence CTs are for direct residual current measurement. The only difference between them is the diameter. Due to their low voltage insulation, they can only be used on cables.

Characteristics
CSH120
Inner diameter Weight Accuracy

CSH200

CSH120 and CSH200 zero sequence CTs.

Transformation ratio Maximum permissible current Operating temperature Storage temperature

4.7 in (120 mm) 7.9 in (200 mm) 1.32 lb (0.6 kg) 3.09 lb (1.4 kg) 5% at 68F (20C) 6% max. from -13F to +158F (-25C to 70C) 1/470 20 kA - 1 s -13F to +158F (-25C to +70C) -40F to +185F (-40C to +85C)

Dimensions
DE10228

4 horizontal mounting holes 0.2 in. (5 mm)

4 vertical mounting holes 0.2 in. (5 mm)

Dimensions A
CSH120 (in) (mm) CSH200 (in) (mm) 4.75 (120) 7.87 (200)

B
6.46 (164) 10.1 (256)

D
1.73 (44) 1.81 (46)

E
7.48 (190) 10.8 (274)

F
2.99 (76) 4,72 (120)

H
1.57 (40) 2.36 (60)

J
6.54 (166) 10.1 (257)

K
2.44 (62) 4.09 (104)

L
1.38 (35) 1.46 (37)

189

Sensors

CSH120 and CSH200 Zero Sequence CTs


Assembly
Group the MV cable (or cables) in the middle of the zero sequence CT. Use non-conductive binding to hold the cables. Remember to insert the 3 medium voltage cable shielding grounding cables through the zero sequence CT. See below.
DE51678

DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION OR ARC FLASH b Only qualied personnel should install this equipment. Such work should be performed only after reading this entire set of instructions and checking the technical characteristics of the device. b NEVER work alone. b Turn off all power supplying this equipment before working on or inside it. Consider all sources of power, including the possibility of backfeeding. b Always use a properly rated voltage sensing device to conrm that all power is off. b Only CSH120, CSH200 and CSH280 zero sequence CTs can be used for direct residual current measurement. Other residual current sensors require the use of an intermediate device, CSH30, ACE990 or CCA634. b Install the zero sequence CTs on insulated cables. b Cables with a rated voltage of more than 1000 V must also have a grounded shielding. Failure to follow these instructions will result in death or serious injury.

E40465

Assembly on MV cables.

CAUTION
HAZARD OF NON-OPERATION Do not connect the secondary circuit of the CSH zero sequence CTs to ground. This connection is made in Sepam. Failure to follow this instruction can cause Sepam to operate incorrectly.

Connection
Connection to Sepam Series 20 and Series 40 To residual current Ir input, on connector A , terminals 19 and 18 (shielding). Connection to Sepam Series 80 b To residual current Ir input, on connector E , terminals 15 and 14 (shielding) b To residual current Ir input, on connector E , terminals 18 and 17 (shielding). Recommended cable b Sheathed cable, shielded by tinned copper braid b Minimum cable cross-section AWG 18 (0.93 mm) b Resistance per unit length < 30.5 m/ft (100 m/m) b Minimum dielectric strength: 1000 V (700 Vrms) b Connect the cable shielding in the shortest manner possible to Sepam b Flatten the connection cable against the metal frames of the cubicle The connection cable shielding is grounded in Sepam. Do not ground the cable by any other means. The maximum resistance of the Sepam connection wiring must not exceed 4 (66 ft maximum for 30.5 m/ft or 20 m maximum for 100 m/m).

a
DE80021

190

Sensors

CSH30 Interposing Ring CT


Function

E40468

E44717

The CSH30 interposing ring CT is used as an interface when the residual current is measured using 1 A or 5 A current transformers.

Characteristics
Weight Assembly 0.265 lb (0.12 kg) On symmetrical DIN rail In vertical or horizontal position

Vertical assembly of CSH30 interposing ring CT.

Horizontal assembly of CSH30 interposing ring CT.

Dimensions
DE80023

in. (mm)

2 0.18 (2 4.5)

0. (4

1.18 ( 30) 3.23 (82)

1.97 (50)

0.6 (16

2 (2
0.20 (5) 0.31 (8) 1.14 (29)

2.36 (60)

Connection

The CSH30 is adapted for the type of current transformer, 1 A or 5 A, by the number of turns of the secondary wiring through the CSH30 interposing ring CT: b 5 A rating - 4 turns b 1 A rating - 2 turns
a
DE80118

Connection to 5 A Secondary Circuit


PE50033 PE50034

Connection to 1 A Secondary Circuit

Ir CT 1 A : 2 turns CT 5 A : 4 turns

1. Plug into the connector. 2. Insert the transformer secondary wire through the CSH30 interposing ring CT four times.

1. Plug into the connector. 2. Insert the transformer secondary wire through the CSH30 interposing ring CT twice.

Connecting to Sepam Series 20 and Series 40 To residual current Ir input, on connector A , terminals 19 and 18 (shielding).
a
DE80119

Connection to Sepam Series 80 b To residual current Ir input, on connector E , terminals 15 and 14 (shielding) b To residual current Ir input, on connector E , terminals 18 and 17 (shielding).
Ia Ib Ic

Ir CT 1 A : 2 turns CT 5 A : 4 turns

Recommended Cable b Sheathed cable, shielded by tinned copper braid b Minimum cable cross-section AWG 18 (0.93 mm) (max. AWG 12, 2.5 mm) b Resistance per unit length < 30.5 m/ft (100 m/m) b Minimum dielectric strength: 1000 V (700 Vrms) b Maximum length: 6.6 ft (2 m). It is essential to install the CSH30 interposing ring CT near Sepam, because the Sepam - CSH30 link is less than 6.6 ft (2 m) long. Flatten the connection cable against the metal frames of the cubicle. The connection cable shielding is grounded in Sepam. Do not ground the cable by any other means. 191

Sensors

ACE990 Zero Sequence CT Interface


Function

PE50037

The ACE990 is used to adapt measurements between an MV zero sequence CT with a ratio of 1/n (50 n 1500), and the Sepam residual current input.

Characteristics
Weight Assembly Amplitude accuracy Phase accuracy Maximum permissible current 1.41 lB (0.64 kg) Mounted on symmetrical DIN rail 1% < 2 20 kA - 1 s (on the primary winding of an MV zero sequence CT with a ratio of 1/50 that does not saturate) +23F to +131F (-5C to +55C) -13F to +158F (-25C to +70C)

ACE990 zero sequence CT interface


1.97 (50) 0.43 (11)

Operating temperature Storage temperature

DE80040

in. (mm)

Description and Dimensions


E ACE990 input terminal block, for connection of the zero sequence CT. S ACE990 output terminal block, for connection of the Sepam residual current.

1.81 3.90 (46) (99)

0.79 (20) 3.03 (77)

0.98 (25) 2.83 (72)

0.43 (11)

192

Sensors

ACE990 Zero Sequence CT Interface


Connection
Sa Sb Ir

a
DE51682

Connecting a Zero Sequence CT Only one zero sequence CT can be connected to the ACE990 interface. The secondary circuit of the MV zero sequence CT is connected to two of the ve ACE990 interface input terminals. To dene the two input terminals, it is necessary to know the following: b Zero sequence CT ratio (1/n) b Zero sequence CT power b Close approximation of rated current INr (INr is a general setting in Sepam and denes the ground fault protection setting range between 0.1 INr and 15 INr). The table below can be used to determine: b The two ACE990 input terminals to be connected to the MV zero sequence CT secondary b The type of residual current sensor to set b The exact value of the rated residual current INr setting, given by the following formula: INr = k x number of zero sequence CT turns with k the factor dened in the table below. The zero sequence CT must be connected to the interface in the right direction for correct operation: the MV zero sequence CT secondary output terminal S1 must be connected to the terminal with the lowest index (Ex).

Example: Given a zero sequence CT with a ratio of 1/400 2 VA, used within a measurement range of 0.5 A to 60 A. How should it be connected to Sepam via the ACE990? 1. Choose a close approximation of the rated current INr (5 A). 2. Calculate the ratio: approx. INr/number of turns = 5/400 = 0.0125. 3. Find the closest value of k in the table opposite to k = 0.01136. 4. Check the minimum power required for the zero sequence CT: 2 VA zero sequence CT > 0.1 VA V OK. 5. Connect the zero sequence CT secondary to ACE990 input terminals E2 and E4. 6. Set Sepam up with: INr = 0.01136 x 400 = 4.5 A. This value of INr can be used to monitor current between 0.45 A and 67.5 A. Wiring the MV zero sequence CT secondary circuit:

K Value

ACE990 Input Terminals to be Connected


E1 - E5 E2 - E5 E1 - E4 E3 - E5 E2 - E4 E1 - E3 E4 - E5 E3 - E4 E2 - E3 E1 - E2 E1 - E5 E2 - E5 E1 - E4 E3 - E5 E2 - E4 E1 - E3 E4 - E5 E3 - E4 E2 - E3

Residual Current Sensor Setting


ACE990 - range 1 ACE990 - range 1 ACE990 - range 1 ACE990 - range 1 ACE990 - range 1 ACE990 - range 1 ACE990 - range 1 ACE990 - range 1 ACE990 - range 1 ACE990 - range 1 ACE990 - range 2 ACE990 - range 2 ACE990 - range 2 ACE990 - range 2 ACE990 - range 2 ACE990 - range 2 ACE990 - range 2 ACE990 - range 2 ACE990 - range 2

Min. MV Zero Sequence CT Power


0.1 VA 0.1 VA 0.1 VA 0.1 VA 0.1 VA 0.1 VA 0.1 VA 0.1 VA 0.1 VA 0.2 VA 2.5 VA 2.5 VA 3.0 VA 3.0 VA 3.0 VA 4.5 VA 4.5 VA 5.5 VA 7.5 VA

0.00578 0.00676 0.00885 0.00909 0.01136 0.01587 0.01667 0.02000 0.02632 0.04000 0.05780 0.06757 0.08850 0.09091 0.11364 0.15873 0.16667 0.20000 0.26316

b S1 output to ACE990 E2 input terminal b S2 output to ACE990 E4 input terminal.

Connection to Sepam Series 20 and Sepam Series 40 To residual current Ir input, on connector A , terminals 19 and 18 (shielding). Connection to Sepam Series 80 b To residual current Ir input, on connector E , terminals 15 and 14 (shielding) b To residual current Ir input, on connector E , terminals 18 and 17 (shielding). Recommended Cables b Cable between zero sequence CT and ACE990: less than 160 ft (50 m) long b Sheathed cable, shielded by tinned copper braid between the ACE990 and Sepam, maximum length 6.6 ft (2 m) b Cable cross-section between AWG 18 (0.93 mm) and AWG 12 (2.5 mm) b Resistance per unit length less than 30.5 m/ft (100 m/m) b Minimum dielectric strength: 100 Vrms Connect the connection cable shielding in the shortest manner possible (5.08 in or 2 cm maximum) to the shielding terminal on the Sepam connector. Flatten the connection cable against the metal frames of the cubicle. The connection cable shielding is grounded in Sepam. Do not ground the cable by any other means. 193

194

Sepam Series 20 Sepam Series 40 Sepam Series 80

Ordering Sepam Relays

Digital Protective Relay Selection Table Application and Accessory Lists Selection Example

196 197 198 199

195

Ordering Sepam Relays

Sepam Series 20, 40, and 80 Digital Protective Relay


Sepam Series 20 Relay Features

20, 40, and 80 Series

The Sepam family of digital protection units, Series 20, 40 and 80, is the newest generation of Sepam relay, a time tested product with a 20-year worldwide history. Modular relay design allows quick and easy future upgrades to communications, digital I/O, analog output or temperature acquisition. The 64x128 bit, graphic LCD display and keypad permit basic relay setting of Series 20 and 40 without a PC. Comprehensive self-testing provides assurance of readiness to protect. The Sepam family also has exceptional withstand to environmental electromagnetic disturbances. An optional 128 x 240 LCD display can show one-line or electrical vectors. Table 1: Quick Select Guide
Capacitor Bank Feeder or main (Substation) Transformer Generator Motor

Criteria Radial (51, 51N, 46) Long feeders (67N) Closed loop (67N, 67) Parallel mains [transf] [sources] (67N, 67) Sync-check required (25)(67N, 67) Solid or low/high impedance (51N) Ungrounded or compensated (67N/NC) Basic Feeder [Transf][Motor]

Selection S23 T23 M20 G40 B80 C86 S41 S42 S42 T42 S82 T82 G82 G82 B80 M41

Backlit LCD graphic bitmap display Compact standard footprint (< 4deep) for basic protection of Mains/Feeders, Transformer, Motor, Bus (Voltage) Applications 16 inverse time overcurrent characteristic curves Setting software with offline file creation and download to relay Two 86 cycle records of fault recording, last trip fault values, and last 64 time-tagged alarms retained Provides trip diagnostic information for analysis of faults Self-test diagnostic ensures correct operation of relay and integrity of protection Wide range of control power inputs Display operation minimal training required for operation. Application specific design for Main/Feeder, Transformer, Motor, Bus (Voltage) zones Zone selective interlocking (ZSI) improved protection coordination Rear communication port for interface to optional Modbus communications modules, plus dual port module, opt protocols DNP3 and IEC60870-5-103, and also F/O Modular architecture Breaker diagnostics

Bus

Network structure

Sepam Series 40 Relay Features


Compact standard footprint (< 4deep) for enhanced protection of Mains/Feeders, Transformer, Motor, Generator Applications Directional overcurrent protection for dual mains and ties and closed loop feeders Current and voltage inputs I, V, E, P, PF Setting software with Boolean logic equation assistance CT/VT and Trip Circuit supervision Sixteen seconds of fault recording, last 5 trip reports, and last 200 time-tagged alarms Rear communication port for interface to optional Modbus communications modules Includes all Series 20 features

Grounding system

S23 T23 M20 G40 S41 T42 M41 G82 S23 T23 M20 G40 S40 T40 M41 G40 B21 S84 B22 S41 T82 M81 G82 B83 S81 C86 T87 M87 G87 M88 G88 S23 T23 M20 B21 S40 T40 M41 G40 B80 B83 T87 M87 G87 S80 T81 M81 G82 B80 T23 M20 G40 T40 M41 G40 S23 S80 S23 S40 S80 S23 S80 T23 T81 T23 T40 T81 T23 T81 M20 M81 M20 M41 M81 M20 M81 G40 G82 G40 G40 G82 G40 G82 B21 B80 B21 B80 B80 B21 B80

Protection

Voltage/frequency (27/59/81) ROCOF (81R) Advanced Fdr/Main[Transf] [Motor][Gen] Thermal overload (49)cable Thermal O/L (49)- capacitor bank Differential (87T) Machine differential (87M) Machinetransformer unit differential

Sepam Series 80 Relay Features

I V, f I, V, f, P ,E Metering I, V, V, f, P, E I, I, V, F, P, E THD-I, THD-V <8 RTDs of same type Temperature > 8 RTDs (< 16) or 2 types of RTDs < 10 I / 8 O I/Os > 10 I / 8 O and < 42 I / 23 O Control matrix Program logic Logic equation editor customization Ladder-logic software 1 Modbus port Modbus communication 2 Modbus ports

Standard footprint for enhanced protection of Mains/Feeders, Transformer, Motor, Generator, Capacitor, Bus Applications Differential protection of transformer or machine transformer units Differential protection of motors and generators Protection for mains and ties and important feeders including pre-programmed transfer schemes Increased metering capabilities I, V, E, P, PF, THD, vector diagram Expanded logic equation capabilities (an option for Logipam PLC ladder logic) Setting software with graphical assistance, opt mimic-based display Battery backup for historical and fault waveform data retention, wide range DC control power Two rear communication interfaces Includes all Series 20 and Series 40 features

Note: Units in table depict least complex device types compliant with criterion.

196

Ordering Sepam Relays

Sepam Series 20, 40, and 80 Selection Table


S23 4 4 1 1 S40 4 4 1 2 S41 4 4 1 2 2 1 S42 4 4 1 2 2 2 1 T23 4 4 1 1 T40 4 4 1 2 T42 4 4 1 2 2 2 M20 4 4 1 M41 4 4 1 2 2 1 1 2 1 1 1 2 1 G40 4 1 4 1 2 B21 B22

Table 2:

Series 20/40 Applications


Protection Application ANSI Code

50/51 50V/51V 50N/51N Ground fault / Sensitive ground faulta 50G/51G Breaker failure 50BF Negative sequence / unbalance 46 Directional phase overcurrenta 67 Directional ground faulta 67N/67NC Directional active overpower 32P Directional reactive overpower 32Q/40 Thermal overloada 49RMS Phase undercurrent 37 Excessive starting time, locked rotor 48/51LR/14 Starts per hour 66 Positive sequence undervoltage 27D/47 Positive sequence undervoltage 27D Remanent undervoltage 27R Phase-to-phase undervoltage 27 Phase-to-neutral undervoltage 27S Undervoltagec 27/27S Overvoltagec 59 Neutral voltage displacement 59N Negative sequence overvoltage 47 Overfrequency 81H Underfrequency 81L Rate of change of frequency 81R Recloser (4 cycles) 79 Temperature monitoring (8 or 16 RTDs) 38/49T Thermostat / Buchholz 26/63 Note: Numerals in table indicate number of protection setpoints a Protection functions with 2 groups of settings b Requires MES120 I/O module c Requires MET1482 RTD Input module d Requires MCS025 synch check module e Option

Phase overcurrenta Voltage-restrained overcurrent

2 1 1 1

1 1 2

2 1 2 1 2 2 2 1 2 4 2 2 1 2

2 1 2 1 2 2 1 2 1

2 2 2 1 2 4 e e

2 2 2 1 2 4 e

2 2 2 1 2 4 e e e

2 2 2 1 2 4

2 2 2 1 2 4

2 2 2 1 2 4

e e

e e

Table 3:

Series 80 Applications
Protection Application ANSI Code 50/51 50N/51N 50G/51G 50BF 46 49RMS 49RMS 49RMS 51C 64REF 87T 87M 67 67N/67NC 32P 32Q 37P 37 48/51LR 66 40 78PS 12 14 50V/51V 21B 50/27 27TN/64G2/64G 24 27D 27R 27 59 59N 47 81H 81L 81R 79 26/63 38/49T 25 S80 8 8 1 2 S81 8 8 1 2 2 S82 8 8 1 2 2 S84 8 8 1 2 2 T81 8 8 1 2 2 T82 8 8 1 2 2 T87 8 8 1 2 2 M81 8 8 1 2 2 M87 8 8 1 2 2 M88 8 8 1 2 2 G82 8 8 1 2 2 G87 8 8 1 2 2 G88 8 8 1 2 2 2 8 2 2 2 1 1 2 2 2 2 2 2 2 2 2 1 1 1 1 1 e e 1 1 1 1 1 e e 1 1 1 1 1 e e 2 2 2 2 2 2 2 2 2 2 1 2 2 1 2 2 1 2 2 2 1 2 2 1 1 2 2 2 1 2 1 2 2 2 1 B80 8 8 1 2 B83 8 8 1 2 C86 8 8 1 2

Phase overcurrenta Ground fault / Sensitive ground faulta Breaker failure Negative sequence / unbalance Thermal overload for cables Thermal overload for machinesa Thermal overload for capacitors Capacitor bank unbalance Restricted ground fault Two-winding transformer differential Machine differential Directional phase overcurrenta Directional ground faulta Directional active overpower Directional reactive overpower Directional active underpower Phase undercurrent Excessive starting time, locked rotor Starts per hour Field loss (underimpedance) Pole slip Overspeed (2 set points)b Underspeed (2 set points)b Voltage-restrained overcurrent Underimpedance Inadvertent energization Third harmonic undervoltage/100% stator ground fault Overfluxing (V / Hz) Positive sequence undervoltage Remanent undervoltage Undervoltage (L-L or L-N) Overvoltage (L-L or L-N) Neutral voltage displacement Negative sequence overvoltage Overfrequency Underfrequency Rate of change of frequency Recloser (4 cycles)b Thermostat / Buchholzb Temperature monitoring (16 RTDs)c Synchronism-checkd

2 2 4 4 2 2 2 4 e

2 2 4 4 2 2 2 4 e

2 2 4 4 2 2 2 4 e

4 2 2 4 2 2 2 4 2 e

2 2 4 4 2 2 2 4

2 2 4 4 2 2 2 4

2 2 2 4 4 2 2 2 4

2 2 4 4 2 2 2 4

2 2 4 4 2 2 2 4

2 2 4 4 2 2 2 4

1 1 e e 2 1 1 2 2 2 2 4 4 2 2 2 4

1 1 e e 2 1 1 2 2 2 2 4 4 2 2 2 4 e e

1 1

2 1 1 2 2 2 2 4 4 2 2 2 4

4 2 2 4 2 2 2 4

4 2 2 4 2 2 2 4

4 2 2 4 2 2 2 4

e e e

e e e

e e e

e e

e e

e e e

e e

e e e

e e e

197

Ordering Sepam Relays

Sepam Series 20, 40 and 80 Application and Accessory Lists

Table 4:
Model

Application List by Catalog Number


Model Application S40 - Substation/feeder [current & voltage] S41 - Substation/feeder [directional grd O/C] S42 - Substation/feeder [directional ph & grd O/C] T40 - Transformer [current & voltage] T42 - Transformer [Dir. Ph & Grd O/C] M41 - Motor [Dir. Grd O/C] G40 - Generator [Dir. Real & Reac Power, Volt-Restr O/C] S23 - Substation/feeder [breaker failure] T23 - Transformer [breaker failure] M20 - Motor B21 - Bus (Voltage/Freq) B22 - Loss of Mains (Voltage/Freq/ROCOF) Catalog No. SQ1S40A SQ1S41A SQ1S42A SQ T40A SQ1T42A SQ1M41A SQ1G40A SQ1S23A SQ1T23A SQ1M20A SQ1B21A SQ1B22A

Application Catalog No. S80 - Substation/feeder [current & voltage] SQ1S80Aa S81 - Substation/feeder [directional grd O/C] SQ1S81A S82 - Substation/feeder [directional ph & grd O/C] SQ1S82A S84 - Substation/main [separation/ load shed] SQ1S84A T81 - Transformer [current & voltage] SQ1T81A T82 - Transformer [Dir. Ph & Grd O/C] SQ1T82A T87 - Transformer [Diff.-2 wdg) SQ1T87A M81- Motor [Dir. Grd O/C] SQ1M81A Series 80 M87- Motor [Mach. Diff.] SQ1M87A M88 - Motor [Transf. Diff.] SQ1M88A G82 - Generator [Dir. Watt & Var, Volt-Restr O/C] SQ1G82A G87 - Generator [Mach diff] SQ1G87A G88 - Generator [Transf diff] SQ1G88A B80 - Bus [Main+1ph volt] SQ1B80A B83 - Bus [Tie +3ph volt] SQ1B83A C86 - Capacitor [4 step 2xWye banks] SQ1C86A a Replace A suffix with P to select the Pro version mimic display.

Series 40

Series 20

Table 5:

Series 20+40+80 Accessory List


Series 20/40 Series 80 x x x Catalog No. MES120 MES120G MES120H MES114 MES114E MES114F ACE959 ACE9492 ACE937 ACE969TP ACE969FO MCS025 MET1482 MSA141 DSM303 SFT080 AMT840 CCA770 CCA772 CCA774 CSH30 CSH120 CSH200 ACE990 SFT2841KIT 2640KIT CCA634 CCT640 CCA612 CCA783 CCA785 CCA670 CCA671 Description 14 inputs + 6 outputs / 24-250Vdc 14 inputs + 6 outputs / 220-250Vdc/hi p.u. 14 inputs + 6 outputs / 110-125 Vdc/hi p.u. 10 Input / 4 output module 10 inputs + 4 outputs 110/125V 10 inputs + 4 outputs 220/250V RS485 4-wire Interface Module (requires. ext. 24VDC control pwr) RS485 2-wire Interface Module (requires. ext. 24VDC control pwr) Fiber optic Interface Module (2)RS485 2wire I/F (1) RS485 2wire + (1) F/O I/F Synch check module (includes cable CCA785) 8 temperature sensor input module Analog output module Remote advanced MMI (requires cable CCA77x see below) Logipam plc logic software Assembly plate for surface mounting of MCS module 2ft cable from remote display to base unit 2m cable from remote display to base unit 4m cable from remote display to base unit Interposing window CT for Residual current input Ground Sensor CT - 120 mm window Ground Sensor CT - 200 mm window Aux. CT for Ground Sensor CT Ratio Adjustment (for retrofit) Setting/operating software kit (including SFT2826 osc s/w+CCA783 cable) Terminal blocks for MES modules 1 or 5 A CT Current Connector Voltage Connector Cable for communication module to relay connection Cable for pc to relay connection MCS025 cable LPCT Current Connector LPCT Current Connector

Accessory Type

Digital I/O Module

x x x x x x x x x x x

Communication I/Fb Module

Analog I/O module

Analog I/O Cables

Ground Sensor CTs (mV out) Configure softwarec

x x x x x x x x x x x x x x

x x x x x x x x x x x x x x x x x x x x x x x x x x

Selected sparesd

b c d

Includes CCA612 cable to relay rear port One s/w kit required per Series 80 order and recommended per Series 40/20 order To be ordered as spare or replacement

198

Ordering Sepam Relays

Sepam Series 20, 40 and 80 Selection Example

Series 20 and Series 40

Series 80

Table 6:

Selection Example
Follow these steps: Example: Type Part Relay unit Memory module Digital I/O Communication module RTD Input Analog output Sync check (25) module Config S/W Cable for RTD I/F Modulle QTY 1 0 1 1 1 0 1 1 1 Catalog No. SP1T87A MMS020xxx MES120 ACE959 MET1482 MSA141 MCS025 SFT2841KIT CCA772 Description T87- Transformer [Diff.-2 wdg) Spare memory module 14 inputs + 6 outputs / 24-250Vdc RS485 4-wire Interface Module l 8 temperature sensor input module Analog output module (1 channel) Synch check module (includes cable CCA785) Setting / operating software kit 2m cable from remote display to base unit

[1] [2] [3] [4] [5] [6] [7] [8] [9]

Selection Sequence Select from Table 4 per system, features Table 1 & 2/3 Spare by application Select from Table 5 (as required) Select from Table 5 (as required) Select from Table 5 (as required) Select from Table 5 (as required) Select from Table 5 (as required) Select from Table 5 (as required) Select from Table 5 (as required)

199

Schneider Electric - North American Operating Division 295 Tech Park Drive LaVergne, TN 37086 Ph: 866-466-7627 Square D.com Powerlogic.com

As standards, specications and designs develop from time, always ask for conrmation of the information given in this publication. Square D, ION, ION Enterprise, MeterM@il and Modbus are either trademarks or registered trademarks of Schneider Electric or its afliates. Other marks used herein may be the property of their respective owners.

Document#3000CT07018/07 August 2007

08-2007

2007 - Schneider Electric - All rights reserved

You might also like