Location via proxy:   [ UP ]  
[Report a bug]   [Manage cookies]                

Protect 8.inv: Industrial Inverters

Download as pdf or txt
Download as pdf or txt
You are on page 1of 4

protect

8.INv Industrial inverters


Protect 8.INV1 Industrial Inverter
Single Phase Output
230 V, 10 – 120 kVA

Protect 8.INV3 Industrial Inverter


Three Phase Output
400 V, 10 – 120 kVA

Engineering is our business Protect 8. industrial applications


Inverter and UPS solutions engineered by AEG Power Solutions »»Oil and gas (petrochemicals, offshore, onshore, pipelines)
have been protecting oil and gas infrastructure, power stations »»Energy and electricity generation
and other industrial applications for more than 60 years. (power generation, transmission, distribution)
»»Water (desalination, treatment)
Designed for all industrial applications
»»Instrumentation and process control
Protect 8.INV, the latest generation of our Protect Inverter product (chemicals, mining, steel, paper)
range is extremely robust, both electrically and mechanically. »»Emergency lighting
It is custom-designed for use in harsh industrial environments
to meet the toughest product customization requirements: »»All industrial applications
»»Specific mechanical protection degree
»»Specific input and output voltage
»»Customized documentation
Protect 8.INV is just a part of the Protect product range of
inverters and UPS’s suitable for industrial applications. See
also our Protect 3., Protect 4. and Protect 8. range of UPS’s.
2

Protect 8.INV1
Specification

Single Phase Output


Model P8.INV1-10 P8.INV1-20 P8.INV1-30 P8.INV1-40 P8.INV1-60 P8.INV1-80 P8.INV1-100 P8.INV1-120
Nominal Rating (at cos ϕ 0.8 lag) 10 kVA 20 kVA 30 kVA 40 kVA 60 kVA 80 kVA 100 kVA 120 kVA
INVERTER UNIT
DC input 216 V ±20 %
Nominal AC voltage 230 V (220 V,240 V)
Output voltage static response <±1 %
Output voltage dynamic response <±2 %
Recovery time 1 ms
Frequency 50 Hz / 60 Hz
Frequency tolerance without mains ±0.1 %
Frequency synchronization range ±1 % (±2 %, ±3 %)
Allowable load power factor 0.0 lag to 0.0 lead
Output phase current in A 43 87 130 174 261 348 435 522
Voltage wave form sinusoidal
Voltage distortion <3 %
Crest factor max. 3
Overload response 1 min. 150 %
Overload response 10 min. 125 %
Max short circuit current >3 x Inom
STATIC BYPASS SWITCH
AC voltage 230 V (220 V, 240 V)
Frequency 50 Hz / 60 Hz
Nominal power in kVA 10 20 30 40 60 80 100 120
GENERAL DATA
Efficiency – typical up to 92 %
Noise level depending on rating <55 – 70 dB(A)
EMC compatability EN 62040-2
Air cooling with redundant and Yes
monitoring fans
Operating temperature range min./max. -5 ˚C – 40 ˚C
(without de-rating)
Storage temperature range min./max. -30 ˚C – 75 ˚C
Maximum altitude without de-rating 1000 m
Protection degree per IEC 529/EN IP20 (IP21 & IP43 ; >IP43 engineered)
60529 standard system (as option)
Equipment color RAL 7035
WEIGHT AND DIMENSIONS
Height standard inverter (mm) 1810 1810 1810 1810 1810 1810 1810 1810
Height with max. options (mm) 1915 1915 1915 1915 2015 2015 2015 2015
Width (mm) 600 900 900 900 1200 1500 1800 1800
Depth (mm) 860 860 860 860 860 860 860 860
Weight (kg) 270 400 580 580 900 1000 1100 1100
3

Protect 8.INV3
Specification

Three Phase Output


Model P8.INV3-10 P8.INV3-20 P8.INV3-30 P8.INV3-40 P8.INV3-60 P8.INV3-80 P8.INV3-100 P8.INV3-120
Nominal Rating (at cos ϕ 0.8 lag) 10 kVA 20 kVA 30 kVA 40 kVA 60 kVA 80 kVA 100 kVA 120 kVA
INVERTER UNIT
DC input 216 V±20 %
Nominal AC voltage 3 x 400 V (3 x 380 V, 3 x 415 V)
Output voltage static response <±1 %
Output voltage dynamic response <±2 %
Recovery time 1 ms
Frequency 50 Hz / 60 Hz
Frequency tolerance without mains ±0.1 %
Frequency synchronization range ±1 % (±2 %, ±3 %)
Allowable load power factor 0.0 lag to 0.0 lead
Output phase current in A 14 29 43 58 87 116 145 173
Voltage wave form sinusoidal
Voltage distortion <3 %
Crest factor max. 3
Overload response 1 min. 150 %
Overload response 10 min. 125 %
Max short circuit current >3 x Inom
STATIC BYPASS SWITCH
AC voltage 3 x 400 V (3 x 380 V, 3 x 415 V)
Frequency 50 Hz / 60 Hz
Nominal power in kVA 10 20 30 40 60 80 100 120
GENERAL DATA
Efficiency – typical up to 92 %
Noise level depending on rating <55 – 70 dB(A)
EMC compatability EN 62040-2
Air cooling with redundant and Yes
monitoring fans
Operating temperature range min./max. -5 ˚C – 40 ˚C
(without de-rating)
Storage temperature range min./max. -30 ˚C – 75 ˚C
Maximum altitude without de-rating 1000 m
Protection degree per IEC 529/EN IP20 (IP21 & IP43 ; >IP43 engineered)
60529 standard system (as option)
Equipment color RAL 7035
WEIGHT AND DIMENSIONS
Height standard inverter (mm) 1810 1810 1810 1810 1810 1810 1810 1810
Height with max. options (mm) 1915 1915 1915 1915 2015 2015 2015 2015
Width (mm) 900 900 900 900 1200 1500 1800 1800
Depth (mm) 860 860 860 860 860 860 860 860
Weight (kg) 500 500 600 600 1000 1000 1600 1600
AEG Power
Solutions

Batteries Services
Protect 8.INV highlights
»»The new generation AEG Power Solutions has With over 60 years of expertise You can also benefit from
of AEG Power considerable in-house in power systems and solutions, a full range of professional
Solutions inverters knowledge in battery AEG Power Solutions is services that will protect and
technology and is able to renowned for its unparalleled ensure the durability of your
»»More than 60 years of offer expert advice on the services and technical investment and will take over
experience in the UPS specifying, selection, operation support in critical application when you need it most:
business incorporated and testing of batteries. Our environments. As a world
into Protect.8 INV total systems solutions include class system provider, you can
»»Pro CareTM preventive
maintenance options

AEGPS - Protect 8.INV - EN - 03/2012 V1 - Due to our policy of continuous development, the data in this document is subject to change without notice.
»»Modern modular a wide range of products using rely on a global network of 20
“building block” to lead acid and nickel-cadmium services centers supported by »»Turnkey solutions
meet all customization batteries in vented and gas over 150 field engineers and »»Installation and
requirements recombination technologies. more than 100 certified service commissioning
Replacement batteries can partners around the world.
»»Inverters designed for be supplied and installed by From power solution selection »»Maintenance services
industrial applications our global service team. to your process installation and »»E-Service /remote monitoring
»»Short lead times commissioning, our certified »»24 /7 hotline
»»High robustness experts go beyond your
for harsh working expectations by offering service »»Onsite training
environments excellence that will ensure the »»Hot swapping
lowest operational cost for your
»»Redundant controls mission-critical equipment. »»Onsite battery replacement
for high reliability The reliability of your installed »»Battery monitoring
»»Small footprint power solution is supported »»Facility and equipment
by a global service team
»»High efficiency even renowned for its short response
management
at low output power time and trouble shooting »»24 /7 global onsite contracts

AEG is a registered trademark used under licence from AB Electrolux.


»»Compatible with efficiency. Choosing one of »»Power quality assessment
every type of battery the Pro CareTM preventive
maintenance options gives »»Load bank and
»»Full digital control you the ultimate peace of site capacity analysis
»»Top class mind reassuring complete »»Trouble shooting and repair
communication cost control, security and
platform uninterrupted power supply
in utmost critical situations.

AEG Power Solutions


Approach your local AEG Power Solutions
representative for further support.
Contact details can be found on:
www.aegps.com

You might also like