Power Supply Unit - QUINT-PS/1AC/24DC/10 - 2866763: Product Description
Power Supply Unit - QUINT-PS/1AC/24DC/10 - 2866763: Product Description
Power Supply Unit - QUINT-PS/1AC/24DC/10 - 2866763: Product Description
com/us/products/2866763
Primary-switched QUINT POWER supply for DIN rail mounting with SFB (selective fuse breaking) technology,
input: 1-phase, output: 24 V DC/10 A
Product Description
QUINT POWER power supplies with maximum functionality
QUINT POWER circuit breakers magnetically and therefore quickly trip at six times the nominal current, for selective and therefore cost-effective system
protection. The high level of system availability is additionally ensured, thanks to preventive function monitoring, as it reports critical operating states
before errors occur.
Reliable starting of heavy loads takes place via the static power reserve POWER BOOST. Thanks to the adjustable voltage, all ranges between 5 V
DC ... 56 V DC are covered.
Reliable starting of difficult loads with the static POWER BOOST power reserve with up to 1.5 times the nominal current permanently
Technical data
Dimensions
Width 60 mm
Height 130 mm
Depth 125 mm
08/17/2016Page1/13
https://www.phoenixcontact.com/us/products/2866763
Ambient conditions
Degree of protection IP20
Ambient temperature (operation) -25 C ... 70 C (> 60 C Derating: 2,5 %/K)
Ambient temperature (storage/transport) -40 C ... 85 C
Max. permissible relative humidity (operation) 95 % (at 25 C, non-condensing)
Noise immunity EN 61000-6-2:2005
Maximum altitude 5000 m
Input data
Nominal input voltage range 100 V AC ... 240 V AC
110 V DC ... 250 V DC
Input voltage range 85 V AC ... 264 V AC
90 V DC ... 350 V DC (UL 508: 300 V DC)
Dielectric strength maximum 300 V AC
AC frequency range 45 Hz ... 65 Hz
Frequency range DC 0 Hz
Discharge current to PE < 3.5 mA
Current consumption 2.2 A (120 V AC)
1.3 A (230 V AC)
2.5 A (110 V DC)
1.2 A (220 VDC)
Inrush surge current < 15 A (typical)
Power failure bypass > 36 ms (120 V AC)
> 36 ms (230 V AC)
Input fuse 10 A (slow-blow, internal)
Choice of suitable circuit breakers 10 A ... 20 A (AC: Characteristics B, C, D, K)
Type of protection Transient surge protection
Protective circuit/component Varistor, gas-filled surge arrester
Output data
Nominal output voltage 24 V DC 1%
Setting range of the output voltage (USet) 18 V DC ... 29.5 V DC (> 24 VDC, constant capacity restricted)
Nominal output current (IN) 10 A (-25C ... 60C, UOUT = 24 V DC)
POWER BOOST (IBoost) 15 A (-25C...40C permanent, UOUT = 24VDC )
Selective Fuse Breaking (ISFB) 60 A (12 ms)
08/17/2016Page2/13
https://www.phoenixcontact.com/us/products/2866763
General
Net weight 1.1 kg
Efficiency > 92.5 % (for 230 V AC and nominal values)
Insulation voltage input/output 4 kV AC (type test)
2 kV AC (routine test)
Protection class I
MTBF (IEC 61709, SN 29500) > 940000 h (25 C)
> 530000 h (40C)
> 230000 h (60C)
Mounting position horizontal DIN rail NS 35, EN 60715
Alignable: 5 mm horizontally, 15 mm next to active components, 50 mm
Assembly instructions
vertically
08/17/2016Page3/13
https://www.phoenixcontact.com/us/products/2866763
Drawings
Block diagram
L (+)
active
N (-) PFC
DC OK
I < IN
13
14
08/17/2016Page5/13
https://www.phoenixcontact.com/us/products/2866763
08/17/2016Page6/13
https://www.phoenixcontact.com/us/products/2866763
08/17/2016Page7/13
https://www.phoenixcontact.com/us/products/2866763
A1 Y1 13 23 31
B1 on B2 error K1
F1 F2 F3 F4
S1 CB E1 Logic
K2
2A 2A 6A 6A
SFB SFB
CB TM1 r r
e e
X31 on s
e
on s
e
off t off t
A2 Y2 14 24 32
33 33 33 33
X21 DC24V/60A 34 34 34 34
1+ 1+ 1+ 1+
1+
2+ 2+ 2+ 2+
3+ 3+ 3+ 3+
2+
4+ 4+ 4+ 4+
1- 1- 1- 1-
1-
2- 2- 2- 2-
3- 3- 3- 3-
2-
4- 4- 4- 4-
Classifications
eCl@ss
ETIM
UNSPSC
Approvals
Approvals
Approvals
CSA / UL Recognized / UL Listed / cUL Recognized / LR / BV / ABS / NK / RINA / BSH / IECEE CB Scheme / SEMI F47 / Bauartgeprft / EAC /
DeviceNet / EAC / DNV GL / cULus Recognized
Ex Approvals
Approvals submitted
Approval details
CSA
UL Recognized
UL Listed
08/17/2016Page9/13
https://www.phoenixcontact.com/us/products/2866763
cUL Recognized
LR
BV
ABS
NK
RINA
BSH
IECEE CB Scheme
SEMI F47
Bauartgeprft
EAC
DeviceNet
EAC
DNV GL
cULus Recognized
08/17/2016Page10/13
https://www.phoenixcontact.com/us/products/2866763
Assembly adapters-QUINT-PS-ADAPTERS7/2-2938206
Fan
Fan-QUINT-PS/FAN/4-2320076
The fan for QUINT-PS/1AC and .../3AC can be mounted without the need for tools or other accessories. By using the fan,
optimum cooling is ensured at high ambient temperatures or if the mounting position is rotated.
Redundancy module
08/17/2016Page11/13
https://www.phoenixcontact.com/us/products/2866763
Diode-QUINT-DIODE/12-24DC/2X20/1X40-2320157
DIN rail diode module 12-24 V DC/2x20 A or 1x40 A. Uniform redundancy up to the consumer.
Active QUINT redundancy module for DIN rail mounting with ACB (auto current balancing) technology and monitoring
functions, input: 24 V DC, output: 24 V DC/2 x 10 A or 1 x 20 A, including mounted UTA 107/30 universal DIN rail adapter
Redundancy module-TRIO-DIODE/12-24DC/2X10/1X20-2866514
Thermomagnetic device circuit breaker, 1-pos., tripping characteristic SFB, 1 PDT contact, plug for base element.
Thermomagnetic device circuit breaker, 1-pos., tripping characteristic SFB, 1 PDT contact, plug for base element.
08/17/2016Page12/13
https://www.phoenixcontact.com/us/products/2866763
Thermomagnetic device circuit breaker, 1-pos., tripping characteristic SFB, 1 PDT contact, plug for base element.
Thermomagnetic device circuit breaker, 1-pos., tripping characteristic SFB, 1 PDT contact, plug for base element.
Thermomagnetic device circuit breaker, 1-pos., tripping characteristic SFB, 1 PDT contact, plug for base element.
08/17/2016Page13/13