09 Busbar Holder Web 1
09 Busbar Holder Web 1
09 Busbar Holder Web 1
9/0
Busbars for low-voltage switchgear and controlgear assemblies General information Busbar connections General information Busbar systems and accessories Installation position busbar systems Technical specifications busbar holder
Page
9/2
Dynamic short-circuit withstand strength according to DIN EN 60439-1 (VDE 0660-500) Rating for Continuous current for copper busbars according to DIN 43671. Busbar drillings, screw fittings and busbars with square cross-section according to DIN43673 part 1.
9/1
Busbar systems
Busbars for low-voltage switchgear and controlgear assemblies General information Busbar systems in low-voltage switchgear and controlgear assemblies must be dimensioned and designed for safe and effective current distribution. In practice, the need for correct dimensioning, the required rated values and proper mounting is often underestimated and, therefore, not adequately met. To plan and implement busbars according to need and function, various DIN standards and VDE regulations must be applied, e.g., dimensioning the busbar system according to DIN 43771 depending on: Busbar cross section Number of busbars Rated current Untreated/coated Ambient temperature inside the enclosure Max. busbar temperature
In addition, there are other factors that need to be taken into account to attempt to present practical states in theory. Physical conditions that occur with modern switchgear controlgear assemblies can be covered only partially or not at all by this method. Realistic values can be determined only through type tests, e.g. according to DIN EN 60439-1 (currently valid until 2014-11) or the following DIN EN 61439-1/-2, and, in this way, they ensure the required safety. The type-tested results can be used, to a limited extent, for derivation. Generally, the method of derivation must be documented for the required verification. Such as: DIN VDE 0660 Part 507 Method for determining heat rise in partially type-tested assemblies (PTTA) through extrapolation VDE 0660 Part 509 Method for determining short-circuit withstand strength of partially type-tested assemblies (PTTA)
The geometric configuration of the busbars in the assembly can be analysed and rated in regard to the following: Greater personal safety Greater system safety Higher level of availability Greater electrical arc safety Higher dynamic resistance Rated currents Radiation of heat/influence of heat Number of main busbar systems Double-sided operation Cable entry Couplings Mounting Maintenance Economy
General information Profile selection and configuration for alternating current The profile form for busbars has a considerable influence not only on the mechanical bending strength, but also on the electrical rating. With direct current there is no skin effect. For this reason, the profile form is important only in regard to the surface emitting heat. Whereas with alternating current, resistance increases due to the skin effect and other effects; resistance can be minimized by selecting a favourable profile form. If the current strength permits it, one or two flat busbars can be mounted for each phase/N conductor in simple mounting. Two busbars are more favourable in terms of smaller losses and are, therefore, recommended. For larger current strengths (> 2,500 A), four flat busbars are a favourable and economical solution. This makes the eddy current smaller and the inductive voltage drop lower.
9/2
Busbar systems
The following standards should be taken into account. DIN 43671: Copper busbars Ratings for continuous current DIN 43673 part 1: Busbars drilling and screw fitting Busbars with square cross section Design of busbar connections:
For vibrations and the like, microencapsulated screws should be used as well. For direct and alternating currents up to 6300 A, connecting material (screws, washers) of torsional strength 8.8 or higher (DIN 267 part 3) can be used for indoor applications. Above 6300 A, connection material with a torsional strength of A2-70 or A4-70 (DIN ISO 3506) is recommended. Treatment of contact surfaces:
In general a torque wrench must be used on rust-resistant screws. In addition, spring elements that are designed to maintain the required contact pressure should be used. The strain washers sustain the tensional force within a certain range and can therefore also be recommended for screw locking. Adequate tensional force prevents the screws from loosening on their own. This principle allows the realization of maintenance free busbar connections. The surfaces should be smooth, but not polished. The contact resistance is actually smaller when the contact surfaces have average roughness (RA 1.6-3.2) since the oxides are overcome more easily. The contact surfaces should, however, be free of oxides and grease. If this is not the case, the contact surfaces must be cleaned.
12 to 50
b 2 b 2
25 to 60
b 2 b 2
60
e3 b e 3 2b W b e3 2 b 2 b W b 2 13,5 b 13,5 13,5 13,5
80 to 120
b 2
b 2
b 2
b 2
9
b e3 2 b Wb 2 2 b e3 b e3
W b
DIN 43673 Design width w 12 Drilling dimensions 15 20 25 30 40 Drilling dimensions 50 60 80 100 120 d 5.5 6.6 9.0 11 11 13.5 13.5 e1 6 7.5 10 12.5 15 20 25 d 11 11 13.5 13.5 13.5 e1 12.5 15 20 20 20 e2 30 30 40 40 40 e1 17 -
e2
e2 26 -
e3 26 -
e1 20 20 20
e2 80
b 2
e2 40 40 40
b 2
e1
e2
b 2
e1
13,5
e2 e1 e2 80e1 e2 e1 e180 80
e3
e1
e1
e2 e1 e2 e1 e2 e 1 e1 b
W b
W b
e2 e1 e2 e1 e2 e 1 e1 e3
e3 40 60 60
Dimensions in mm
9/3
Connection bracket
T-head bolt
Outgoing taps from the busbar system with cables or outgoing busbars can be connected as required to the busbar system without drilling at any point in the busbar system. In the case of cable feeders, a connection bracket must be placed over the subconductors under the cable lug in order to achieve a perfect contact. Retrofitting and repositioning the outgoing feeder is also possible without the need to make changes to the busbar system. The subconductor spacings of a phase are defined by the busbar holder in such a way that an M10 T-head bolt can be inserted between 2 subconductors (1). After a quarter turn, the T-head encircles both subconductors from the outside and also prevents them from coming into contact with one another in the event of a short circuit (2). The outgoing feeder busbar with the hole is now attached over the threaded bolt part of the T-head bolt and secured with a spring washer, flat washer and hexagon nut (3).
Busbar holder
Hexagon bolt
Cu cylindricalspacer
2 x Cu subconductor L/N
The main busbar system consists of two upright Cu flat busbars arranged above one another. The busbar outgoing feeders are connected via Cu spacers. No bending of the busbar outgoing feeders is needed due to the achieved spacing to the main busbars. Connecting hexagon bolts with conical spring washers and threaded plates.
Threaded plate
Hexagon bolt
Cu cylindricalspacer
4 x Cu subconductor L/N
The main busbar system consists of four upright/parallel Cu flat busbars arranged behind and above one another. The busbar outgoing feeders are connected via Cu cylindricalspacers. No bending of the busbar outgoing feeders is needed due to the achieved spacing to the main busbars. Connecting hexagon bolts with conical spring washers and threaded plates.
9/4
CU bars
Subconductor
CU spacer
Busbar outgoing feeders with Cu spacer Not necessary to bend the busbar outgoing feeders
CU bar
CU bar
CU spacer
9
CU bar CU busbar connection plates
CU bar
Connection without Cu connection plates, with an offset in the main busbar system
9/5
12 x 5 250 59,5 12 x 10 355 119,0 For technical specifications, see page 9/24 9/6
(Dimensions in mm)
ZX2P2
62489
ZX95P2 ED111
62638 39321
ZK81 ZK81P50
64881 62431
ZK150 ZK150P50
64860 62432
16-95 mm2 for Cu 12 x 5 mm 16-70 mm2 for Cu 12 x 10 mm 1 pc. 5 pcs. 50 pcs. 16-150 mm2 for Cu 12 x 5 mm 4 pcs.
Cover profile For snapping onto busbars 12 x 5 and 12 x 10 mm, by the metre Device carrier For snapping onto the busbar system, width 53 mm For Cu 12 x 5 mm Device carrier For snapping onto the busbar system, width 86 mm For Cu 12 x 5 mm For Cu 12 x 10 mm Busbar connector Panel-panel (with cover strip) 1 set 4-pole, 250 A 1 set 5-pole, 250 A 1 set 5-pole, 355 A
35-150 mm2 for Cu 12 x 5 mm 35-150 mm2 for Cu 12 x 5 mm 35-150 mm2 for Cu 25 x 5 mm 1 pc. 20 pcs. 1.5-16 mm2 for Cu 10 mm 1 pc. 50 pcs.
ZB1
39121
ZX100
39100
ZK154 ZK154P50
64864 62435
16-70 mm2 for Cu 5 mm 1 pc. 50 pcs. ZX90 ZX91 ZX106 39090 39091 39106
ZK178 ZK178P50
64978 62622
ZK157 ZK157P50
64867 62437
Weight (kg/m)
440 30 x 5* 30 x 10 630
149.0 299.0
1.330 2.66
* No
Deep-mounting bracket for WR frame For stepless depth adjustment of busbar holders Incl. fastening material 2 pcs. ZW142P2 40 pcs. ZW142P40
62454 62476
35-70 mm2 for Cu 10 mm 1 pc. 50 pcs. 16-70 mm2 for Cu 5 mm 1 pc. 50 pcs. 25-70 mm2 for Cu 30 x 5 mm 25-70 mm2 for Cu 30 x 10 mm 1 pc. 20 pcs.
T-head bolt For 2 x 10 mm Cu bars, parallel M 10 x 50 mm for Cu 30 mm M 10 x 60 mm for Cu 40 mm Connecting bracket for cable lugs For 2 x 10 mm Cu bars, parallel Accessories for ZX150, upright Spacer for busbar holder (Four spacers are required for each busbar holder) Cu bar 20 x 10 mm 30 x 10 mm 40 x 10 mm D x d x H (mm) 17 x 7 x 4 mm 17 x 7 x 14 mm 17 x 7 x 24 mm ZX192 ZX193 ZX194 44028 44029 44030 ZX197 ZX198 XAB10 60242 60243 44229
ZK161 ZK161P20
64871 62441
35-120 mm2 for Cu 30 x 5 mm 35-120 mm2 for Cu 30 x 10 mm 1 pc. 20 pcs. 95-185 mm2 for Cu 30 x 5 mm 95-185 mm2 for Cu 30 x 10 mm 1 pc. 20 pcs.
ZK162 ZK162P20
64872 62442
ZK163 ZK163P20
64873 62443
ZK302 ZK302P20
62645 62648
ZK303 ZK303P20
62646 62649
Busbar systems Busbar holder type ZX151/ZX157/ZX149/ZX518 Busbar holder type ZX146/ZX147 and accessories
Busbar holder type ZX151/ZX157
Fastening hole spacing 200 mm Busbar spacing 60 mm Continuous current 250-630 A Cu 12 x 5 to 30 x 10 mm Suitable for E-Cu busbars
Busbar holder 1-pole For series connection to ZX146 For Cu 12 x 5, 12 x 10, 20 x 5, 20 x 10, 30 x 5 and 30 x 10 mm Busbar holder 3-pole Busbar spacing 60 mm For Cu 12 x 5, 12 x 10, 20 x 5, 20 x 10, 30 x 5 and 30 x 10 mm
ZX147
ZX146
44010
End cover For busbar holder type ZX146 Mounting cross member For busbar holder type ZX146 (3-pole) For horizontal installation
ZX172
60232
ZW399
62972
Mounting cross member For busbar holder ZX146 (3-pole) For vertical installation on WR profile For technical specifications, see page 9/24 9/10
ZW403LR
62974
(Dimensions in mm)
Deep-mounting bracket for WR frame For stepless depth adjustment of busbar holders Incl. fastening material 2 pcs. ZW142P2 40 pcs. ZW142P40 Deep-mounting bracket for WR frame For depth adjustment of busbar holders in steps of 15 mm Incl. fastening material 2 pcs. ZW60P2 100 pcs. ZW60P100 Copper bars Cu bar 250 A 12 x 5 mm Cu bar 360 A 12 x 10 mm Cu bar 320 A 20 x 5 mm Cu bar 500 A 20 x 10 mm Cu bar 390 A 25 x 5 mm Cu bar 440 A 30 x 5 mm Cu bar 630 A 30 x 10 mm
62463 62477
ZK152 ZK152P20
64862 62444
62454 62476
ZK86 ZK86P20 ZK87 ZK87P50 ZK154 ZK154P50 ZK178 ZK178P50 ZK156 ZK156P50 ZK157 ZK157P50
64886 62434 64887 62430 64864 62435 64978 62622 64866 62438 64867 62437
Length 1 m Length 2 m Length 3 m Length 4 m Length 1 m Length 2 m Length 3 m Length 4 m Length 1 m Length 2 m Length 3 m Length 4 m Length 1 m Length 2 m Length 3 m Length 4 m Length 1 m Length 2 m Length 3 m Length 4 m Length 1 m Length 2 m Length 3 m Length 4 m Length 1 m Length 2 m Length 3 m Length 4 m
ZX400 ZX401 ZX402 ZX350 ZX403 ZX404 ZX405 ZX354 ZX406 ZX407 ZX408 ZX351 ZX362 ZX363 ZX364 ZX355 ZX365 ZX366 ZX367 ZX352 ZX409 ZX410 ZX411 ZX353 ZX412 ZX413 ZX414 ZX356
61400 61401 61402 61350 61403 61404 61405 61354 61406 61407 61408 61351 61362 61363 61364 61355 61365 61366 61367 61352 61409 61410 61411 61353 61412 61413 61414 61356
64872 62442
64873 62443
ZK152 ZK152P20
64862 62444
Cu spacer Dxdxs 20 x 8.5 x 11 mm 20 x 8.5 x 22 mm 20 x 8.5 x 33 mm 30 x 10.5 x 11 mm 30 x 10.5 x 22 mm 30 x 10.5 x 33 mm 40 x 10.5 x 11 mm 40 x 10.5 x 22 mm 40 x 10.5 x 33 mm Cross section 257 mm2 257 mm2 257 mm2 620 mm2 620 mm2 620 mm2 1170 mm2 1170 mm2 1170 mm2 ZX36 ZX37 ZX38 ZX39 ZX40 ZX41 ZX42 ZX43 ZX44 60210 60211 60212 60213 60214 60215 60216 60217 60218 16-120 mm2 For Cu 10 mm 1 pc. 50 Pcs. ZK154 ZK154P50 64864 62435
On bar terminals 25-70 mm2 For Cu 30 x 5 mm up to Cu 100 x 10 mm 1 pc. ZK161 20 Pcs. ZK161P20
64871 62441
Copper bars Cu bar 630 A 30 x 10 mm Cu bar 850 A 40 x 10 mm Cu bar 1000 A 50 x 10 mm Cu bar 1250 A 60 x 10 mm Cu bar 1450 A 80 x 10 mm Cu bar 1700 A 100 x 10 mm Length 1 m Length 2 m Length 3 m Length 4 m Length 1 m Length 2 m Length 3 m Length 4 m Length 1 m Length 2 m Length 3 m Length 4 m Length 1 m Length 2 m Length 3 m Length 4 m Length 1 m Length 2 m Length 3 m Length 4 m Length 1 m Length 2 m Length 3 m Length 4 m ZX412 ZX413 ZX414 ZX356 ZX415 ZX416 ZX417 ZX357 ZX418 ZX419 ZX420 ZX358 ZX421 ZX422 ZX423 ZX359 ZX424 ZX425 ZX426 ZX360 ZX427 ZX428 ZX429 ZX361 61412 61413 61414 61356 61415 61416 61417 61357 61418 61419 61420 61358 61421 61422 61423 61359 61424 61425 61426 61360 61427 61428 61429 61361
64872 62442
64873 62443
185-240 mm2 For Cu 40 x 10 mm up to Cu 100 x 10 mm 1 pc. ZK164 20 Pcs. ZK164P20 10-95 mm2 1 pc. 20 Pcs.
9
64874 62445
ZK302 ZK302P20
62645 62648
ZK303 ZK303P20
62646 62649
ZK304 ZK304P20
62647 62650
64871 62441
Deep-mounting bracket for WR frame For stepless depth adjustment of busbar holders ZX152 2 pcs. ZW143P2 Incl. fastening material Busbar holder Busbar centre spacing 60/100 mm 1 pc. 10 pcs. Busbar holder Busbar centre spacing 100-185 mm
62464
64872 62442
64873 62443
Deep-mounting bracket for WR frame ZW144LR For stepless depth adjustment of busbar holders ZX153 2 pcs. Incl. fastening material Busbar holder Busbar centre spacing 100-185 mm 1 pc. 10 pcs.
ZX522 ZX522P10
67909 62553
Deep-mounting bracket for WR frame For stepless depth adjustment of busbar holders ZX522 and ZX520 Incl. fastening material 2 pcs. ZW142P2 40 pcs. ZW142P40 Cu spacer D x d x s 20 x 8.5 x 11 mm 20 x 8.5 x 22 mm 20 x 8.5 x 33 mm 30 x 10.5 x 11 mm 30 x 10.5 x 22 mm 30 x 10.5 x 33 mm 40 x 10.5 x 11 mm 40 x 10.5 x 22 mm 40 x 10.5 x 33 mm Cross section 257 mm2 257 mm2 257 mm2 620 mm2 620 mm2 620 mm2 1170 mm2 1170 mm2 1170 mm2 ZX36 ZX37 ZX38 ZX39 ZX40 ZX41 ZX42 ZX43 ZX44
62463 62477
Copper bars Cu bar 630 A 30 x 10 mm Cu bar 850 A 40 x 10 mm Cu bar 1000 A 50 x 10 mm Cu bar 1250 A 60 x 10 mm Cu bar 1450 A 80 x 10 mm Cu bar 1700 A 100 x 10 mm Length 1 m Length 2 m Length 3 m Length 4 m Length 1 m Length 2 m Length 3 m Length 4 m Length 1 m Length 2 m Length 3 m Length 4 m Length 1 m Length 2 m Length 3 m Length 4 m Length 1 m Length 2 m Length 3 m Length 4 m Length 1 m Length 2 m Length 3 m Length 4 m ZX412 ZX413 ZX414 ZX356 ZX415 ZX416 ZX417 ZX357 ZX418 ZX419 ZX420 ZX358 ZX421 ZX422 ZX423 ZX359 ZX424 ZX425 ZX426 ZX360 ZX427 ZX428 ZX429 ZX361 61412 61413 61414 61356 61415 61416 61417 61357 61418 61419 61420 61358 61421 61422 61423 61359 61424 61425 61426 61360 61427 61428 61429 61361 9/15
Connection terminals 35-70 mm2 for Cu 10 mm 1 pc. 50 pcs. ZK156 ZK156P50 64866 62438
ZK152 ZK152P20
64862 62444
ZK154 ZK154P50
64864 62435
N/PE busbar holder 2 ZX154 pieces are needed for each support point.
ZX154
Busbar holder 2 ZX155 pieces are needed for each support point.
ZX155
44012
Busbar holder 2 ZX156 pieces are needed for each support point.
ZX156
44013
10/24 ff > For technical specifications, see page 9/24 9/16 (Dimensions in mm)
Length 1 m Length 2 m Length 3 m Length 4 m Length 1 m Length 2 m Length 3 m Length 4 m Length 1 m Length 2 m Length 3 m Length 4 m Length 1 m Length 2 m Length 3 m Length 4 m Length 1 m Length 2 m Length 3 m Length 4 m Length 1 m Length 2 m Length 3 m Length 4 m Length 1 m Length 2 m Length 3 m Length 4 m Length 1 m Length 2 m Length 3 m Length 4 m
ZX406 ZX407 ZX408 ZX351 ZX409 ZX410 ZX411 ZX353 ZX412 ZX413 ZX414 ZX356 ZX415 ZX416 ZX417 ZX357 ZX418 ZX419 ZX420 ZX358 ZX421 ZX422 ZX423 ZX359 ZX424 ZX425 ZX426 ZX360 ZX427 ZX428 ZX429 ZX361
61406 61407 61408 61351 61409 61410 61411 61353 61412 61413 61414 61356 61415 61416 61417 61357 61418 61419 61420 61358 61421 61422 61423 61359 61424 61425 61426 61360 61427 61428 61429 61361
ZX291P10
62537
T-head bolt For 2 x 5 mm Cu bars, parallel M 10 x 40 for Cu 20 mm M 10 x 50 for Cu 30 mm For 2 x 10 mm Cu bars, parallel M 10 x 50 for Cu 30 mm M 10 x 60 for Cu 40 mm M 10 x 70 for Cu 50 mm M 10 x 80 for Cu 60 mm M 10 x 100 for Cu 80 mm M 10 x 120 for Cu 100 mm Connecting bracket for cable lugs For 2 x 5 mm Cu bars parallel For 2 x 10 mm Cu bars parallel
ZX195 ZX196 ZX197 ZX198 ZX199 ZX200 ZX201 ZX202 RAB10 XAB10 ZX285P10 ZX290P10
60240 60241 60242 60243 60244 60245 60246 60247 44231 44229 62533 62536
Conical spring washer Two conical spring washers are required per support point with ZX154 and ZX155, and four conical spring washers with ZX156. 10 pcs. 12 mm ZX219P10 250 pcs. 12 mm ZX219P250 Sliding nuts Two sliding nuts are required per support point with ZX154 and ZX155, and four sliding nuts with ZX156. 1 pc. 25 x 25 x 10 M 12 ZX190
Washer 10 pcs. 10 mm Spring washer 10 pcs. 10 mm Conical spring washer 10 pcs. 10 mm 500 pcs. 10 mm Hexagon nut 10 pcs. M 10
Busbar holder, 3 pole ZX640 46077 Busbar centre spacing 200 mm Mounting bracket RZ42 see page 5-49 For Cu: 2 x 30 x 10 mm, 2 x 40 x 10 mm, 2 x 60 x 10 mm, 2 x 80 x 10 mm, 4 x 60 x 10 mm Busbar holder, 4 pole ZX641 46078 Busbar centre spacing 200 mm Mounting bracket RZ42 see page 5-49 For Cu: 2 x 30 x 10 mm, 2 x 40 x 10 mm, 2 x 60 x 10 mm, 2 x 80 x 10 mm, 4 x 60 x 10 mm Busbar holder intermediate piece 3-pole ZX642 Is required for assembly of Cu 4 x 60 x 10 mm Busbar holder intermediate piece 4-pole Is required for assembly of Cu 4 x 60 x 10 mm ZX643 46079 46080
Clamp for busbar holder ZX640/641 (One required per phase) for Cu 2 x 30 x 10 mm 1 pc. 20 pcs. Clamp for busbar holder ZX640/641 (One required per phase) for Cu: 2 x 40 x 10 mm 1 pc. 20 pcs. Clamp for busbar holder ZX640/641 (One required per phase) for Cu 2 x 60 x 10 mm, 4 x 60 x 10 mm 1 pc. 20 pcs. Clamp for busbar holder ZX640/641 (One required per phase) for Cu 2 x 80 x 10 mm 1 pc. 20 pcs. Cu intermediate piece For Cu: 4 x 60 x 10 mm Threaded plate M10 e.g. for cable tap (Assembly between busbars) 1 pc. 20 pcs. Threaded plate M12 For busbar tap (Assembly between busbars) 1 pc. 20 pcs. Cu spacer 30 x 10 mm, inside diameter 12.5 mm 30 x 20 mm, inside diameter 12.5 mm 30 x 30 mm, inside diameter 12.5 mm 30 x 40 mm, inside diameter 12.5 mm 30 x 45 mm, inside diameter 12.5 mm 30 x 50 mm, inside diameter 12.5 mm For technical specifications, see page 9/24 (Dimensions in mm)
ZX644 ZX644P20
46081 46600
ZX647 ZX647P20
46084 46603
ZX645 ZX645P20
46082 46601
ZX656 ZX656P20
46093 46302
9/19
Busbar Busbar Busbar Continuous current in A Cross section Weight holder spacing dimensions Number of busbars Type (mm) (mm) 1 2 3 (mm2) (kg/m) ZB5 40 12 x 5 250 A - - 59.5 40 12 x 10 360 A - - 119.0 40 20 x 5 320 A - - 99.1 ZX2 40 12 x 5 250 A - - 59.5 ZX95 40 12 x 10 360 A - - 119.0 ZX150 60 30 x 5 440 A - - 149.0 100 30 x 10 630 A - - 299.0 ZX150 60 20 x 10 500 A 850 A - 199.0 80 30 x 10 630 A 1,250 A - 299.0 100 40 x 10 850 A 1,500 A - 399.0 ZX151 60 12 x 5 250 A - - 59.5 60 20 x 5 320 A - - 99.1 60 25 x 5 390 A - - 124.0 60 30 x 5 440 A - - 149.0 60 12 x 10 360 A - - 119.0 60 20 x 10 500 A - - 199.0 60 30 x 10 630 A - - 299.0 ZX149 95 12 x 5 250 A - - 59.5 95 12 x 10 360 A - - 119.0 95 20 x 5 320 A - - 99.1 95 20 x 10 500 A - - 199.0 95 30 x 5 440 A - - 149.0 95 30 x 10 630 A - - 299.0 ZX518 40 40 40 12 x 5 250 A 20 x 5 320 A 30 x 5 440 A - - - - 59.5 - 99.1 - 149.0 0.532 1.064 0.882 0.532 1.064 1.33 2.66 1.77 2.66 3.55 0.532 0.882 1.110 1.330 1.064 1.770 2.660 0.532 1.064 0.882 1.770 1.330 2.660 0.532 0.882 1.330
ZX152 100 30 x 10 630 A - - 299.0 100 40 x 10 850 A - - 399.0 100 50 x 10 1,000 A - - 499.0 100 60 x 10 1,250 A - - 599.0 ZX520 60 30 x 10 630 A - - 299.0 ZX520 100 100 100 100 30 x 10 630 A 40 x 10 850 A 50 x 10 1,000 A 60 x 10 1,250 A - - - - - - - - 299.0 399.0 499.0 599.0 2.660 3.550 4.440 5.330 2.660
9/20
Busbar Busbar Busbar Continuous current in A Cross section Weight holder spacing dimensions Number of busbars Type (mm) (mm) 1 2 3 (mm2) (kg/m) ZX153 185 30 x 10 630 A 185 40 x 10 850 A 185 50 x 10 1,000 A 185 60 x 10 1,250 A 185 80 x 10 1,450 A 185 100 x 10 1,700 A - - - - - - - - - - - - 299.0 399.0 499.0 599.0 799.0 999.0 2.660 3.550 4.440 5.330 7.110 8.890
ZX522 100 100 100 100 30 x 10 630 A 40 x 10 850 A 50 x 10 1,000 A 60 x 10 1,250 A - - - - - - - - 299.0 399.0 499.0 599.0 2.660 3.550 4.440 5.330
ZX522 185 30 x 10 630 A 185 40 x 10 850 A 185 50 x 10 1,000 A 185 60 x 10 1,250 A 185 80 x 10 1,450 A 185 100 x 10 1,700 A - - - - - - - - - - - - 299.0 399.0 499.0 599.0 799.0 999.0 2.660 3.550 4.440 5.330 7.110 8.890
9/21
Busbar Busbar Busbar Continuous current in A Cross section Weight holder spacing dimensions Number of busbars Type (mm) (mm) 1 2 3 (mm2) (kg/m) ZX154 72 20 x 5 320 A 500 A 690 A 99.1 72 30 x 5 440 A 672 A 896 A 149.0 ZX154 72 30 x 10 630 A 1,250 A 72 40 x 10 850 A 1,500 A 72 50 x 10 1,000 A 1,700 A 72 60 x 10 1,250 A 2,000 A 72 80 x 10 1,450 A 2,400 A 72 100 x 10 1,700 A 2,750 A - 299.0 - 399.0 - 499.0 - 599.0 - 799.0 - 999.0 0.882 1.330 2.660 3.550 4.440 5.330 7.110 8.890 0.882 1.330 2.660 3.550 4.440 5.330 7.110 8.890 10.660 14.220 0.882 1.330
ZX155 100 20 x 5 320 A 500 A 690 A 99.1 100 30 x 5 440 A 672 A 896 A 149.0 ZX155 100 30 x 10 630 A 1,250 A - 299.0 100 40 x 10 850 A 1,500 A - 399.0 100 50 x 10 1,000 A 1,700 A - 499.0 100 60 x 10 1,250 A 2,000 A - 599.0 100 80 x 10 1,450 A 2,400 A - 799.0 100 100 x 10 1,700 A 2,750 A - 999.0 100 120 x 10 2,000 A 3,500 A - 1199.0 100 160 x 10 2,500 A 4,000 A - 1599.0 ZX156 125 20 x 5 320 A 125 30 x 5 440 A 500 A 672 A 690 A 99.1 896 A 149.0
ZX156
125 30 x 10 630 A 125 40 x 10 850 A 125 50 x 10 1,000 A 125 60 x 10 1,250 A 125 80 x 10 1,450 A 125 100 x 10 1,700 A 125 120 x 10 2,000 A 125 160 x 10 2,500 A
- - - - - - - -
9/22
Busbar Busbar Busbar Continuous current in A Cross section Weight holder spacing dimensions Number of busbars Type (mm) (mm) 1 2 4 (mm2) (kg/m) ZX561 - 80 x 10 1,450 A - - 100 x 10 1,700 A - ZX563 - 30 x 10 630 A - - 40 x 10 850 A - - 50 x 10 1,000 A - - 60 x 10 1,250 A - ZX640 200 200 200 200 200 30 x 10 40 x 10 60 x 10 80 x 10 60 x 10 - - - - - 1,250 A 1,600 A 2,000 A 2,500 A - - - - - - - - - - - 799.0 999.0 299.0 399.0 499.0 599.0 299.0 399.0 599.0 799.0 7.110 8.890 2.660 3.550 4.440 5.330 2.660 3.550 5.330 7.110 5.330
3,150 A 599.0
- - - -
9/23
40 40 40 40
Rated values ZX2 Cu busbars (mm) 12 x 5 12 x 10 Busbar holder spacing (max. in mm) 283 283 15 (0,3 sec.) 15 (0,3 sec.) 36 36 Icw/kA Ipk/kA
9
220 40 40 40 40
Rated values ZB5 Cu busbars (mm) 12 x 5 12 x 10 12 x 10 20 x 5 20 x 5 Busbar holder spacing (max. in mm) 240 240 480 240 480 35 35 22 35 24 56 56 42 56 47 Icw/kA Ipk/kA
9/24
120
160
210
210
(Dimensions in mm)
Rated values ZX95 Cu busbars (mm) 12 x 5 12 x 10 Busbar holder spacing (max. in mm) 220 220 14,5 14,5 29,1 29,1 Icw/kA Ipk/kA
10,5
5,6
140
115
125
50
40
12
4,5
40
10 15 27 14
Rated values for ZX387 Cu busbars (mm) 12 x 5 12 x 10 Busbar holder spacing (max. in mm) 220 220 20,8 20,8 46,8 46,8 Icw/kA Ipk/kA
(Dimensions in mm)
9/25
Rated values ZX150, upright For short-circuit current Ik Conversion factor according to DIN EN 60439-1 Icw = Ipk x 0.5 Icw = Ipk x 0.48 Icw = Ipk x 0.46
10 20 kA 20 50 kA > 50 kA
9
Short circuit strength diagram
Rated values ZX150 flat For short-circuit current Ik Conversion factor according to DIN EN 60439-1 Icw = Ipk x 0.5 Icw = Ipk x 0.48 Icw = Ipk x 0.46
10 20 kA 20 50 kA > 50 kA
9/26
(Dimensions in mm)
Rated values ZX149 Cu busbars (mm) 30 x 10 30 x 10 Busbar holder spacing (max. in mm) 240 480 15 15 33,4 33,4 Icw/kA Ipk/kA
155 92
16
75
9
40 58 34
Rated values ZX518 Cu busbars (mm) 12 x 5 12 x 5 20 x 5 20 x 5 30 x 5 30 x 5 Busbar holder spacing (max. in mm) 240 480 240 480 240 480 12,5 12,5 12,5 12,5 12,5 12,5 27,9 27,9 27,9 27,9 27,9 27,9 Icw/kA Ipk/kA
(Dimensions in mm)
9/27
220
ZX151 60 60 200
Rated peak withstand current
ZX157
30 x max.
92
Conversion factors for ZX151 / ZX157 For short-circuit current Ik Conversion factor according to DIN EN 60439-1 Icw = Ipk x 0,5 Icw = Ipk x 0,48 Icw = Ipk x 0,46
10 - 20 kA 20 - 50 kA > 50 kA
Rated values ZX146/ZX147 Cu busbars (mm) 12 x 5 20 x 5 12 x 10 20 x 10 30 x 5 30 x 10 Busbar holder spacing (max mm) Module width 250 mm Icw/kA 20,1 20,3 21,4 23,5 32,1 36,7 Ipk/kA 44,3 44,8 47,2 51,8 70,7 79,8
Busbar holder spacing (max mm) Module width 500 mm/750 mm Icw/kA 10,9 14,4 11,2 14,5 24,5 26,0 Ipk/kA 24,7 holder spacing (mm) Busbar 31,7 24,8 31,9 54,1 57,4
9/28
(Dimensions in mm)
Rated values ZX561 Cu busbars (mm) 80 x 10 100 x 10 Busbar holder spacing (max. in mm) 730 730 45,0 45,0 100,0 100,0 Icw/kA Ipk/kA
Rated values ZX563 Cu busbars (mm) 30 x 10 40 x 10 60 x 10 Busbar holder spacing (max. in mm) 730 730 730 26,3 45,0 45,0 59,2 100,0 100,0 Icw/kA Ipk/kA
(Dimensions in mm)
9/29
62 7 0 320 275
100 100
Rated values ZX152 For short-circuit current Ik Conversion factor according to DIN EN 60439-1 Icw = Ipk x 0.5 Icw = Ipk x 0.48 Icw = Ipk x 0.46
10 20 kA 20 50 kA > 50 kA
38
9
100 85
100 100
185
185
432
185
Conversion factor according to DIN EN 60439-1 Icw = Ipk x 0.5 Icw = Ipk x 0.48 Icw = Ipk x 0.46
10 20 kA 20 50 kA > 50 kA
9/30
(Dimensions in mm)
22
26
87,5
285
100
60
100
60
87,5
75
Rated values ZX520 For short-circuit current Ik Conversion factor according to DIN EN 60439-1 Icw = Ipk x 0.5 Icw = Ipk x 0.48 Icw = Ipk x 0.46
10 20 kA 20 50 kA > 50 kA
24
26
87,5
185
100
430
75
100
185
Conversion factor according to DIN EN 60439-1 Icw = Ipk x 0.5 Icw = Ipk x 0.48 Icw = Ipk x 0.46
10 20 kA 20 50 kA > 50 kA
(Dimensions in mm)
9/31
5 72 5,5 10 10 5,5
Short circuit strength diagram Rated peak withstand current Busbar holder spacing (mm)
Rated values ZX154 For short-circuit current Ik Conversion factor according to DIN EN 60439-1 Icw = Ipk x 0.5 Icw = Ipk x 0.48 Icw = Ipk x 0.46
10 20 kA 20 50 kA > 50 kA
9/32
(Dimensions in mm)
Rated values ZX155 For short-circuit current Ik Conversion factor according to DIN EN 60439-1 Icw = Ipk x 0.5 Icw = Ipk x 0.48 Icw = Ipk x 0.46
10 20 kA 20 50 kA > 50 kA
(Dimensions in mm)
9/33
Cu busbars Continuous current in A Cross section (mm) 1 bar 2 bars 3 bars (mm2) 20 x 5 320 A 500 A 690 A 99.1 30 x 5 440 A 672 A 896 A 149.0 30 x 10 630 A 1,250 A 299.0 40 x 10 850 A 1,500 A 399.0 50 x 10 1,000 A 1,700 A 499.0 60 x 10 1,250 A 2,000 A 599.0 80 x 10 1,450 A 2,400 A 799.0 100 x 10 1,700 A 2,750 A 999.0 120 x 10 3,500 A 160 x 10 4,000 A
Weight (kg/m) 0.882 1.330 2.660 3.550 4.440 5.330 7.110 8.890
9
Short circuit strength diagram
Rated values ZX156 For short-circuit current Ik Conversion factor according to DIN EN 60439-1 Icw = Ipk x 0.5 Icw = Ipk x 0.48 Icw = Ipk x 0.46
10 20 kA 20 50 kA > 50 kA
For rated currents 1,600 A, the use of antimagnetic fastening screws (stainless steel) is recommended; see page 9/17 9/34 (Dimensions in mm)
50
65
587
10
50
65
784
200
200
200
200
200
10
9
5
Rated values ZX640/ZX641 Cu busbars (mm) 30 x 10 40 x 10 60 x 10 80 x 10 60 x 10 Number per Rated current phase In 2 1,250 A 2 1,600 A 2 2,000 A 2 2,500 A 4 3,150 A Busbar holder spacing (max. in mm) 525 525 525 525 525 50.0 50.0 75.0 75.0 100.0 100.0 100.0 165.0 165.0 220.0 Icw/kA Ipk/kA
Rated values of degree of protection IP30 Type-tested according to DIN EN 60439-1 Cabinet depth < 2500 A min. 600 mm Cabinet depth > 2500 A min. 800 mm The busbar connections are to be installed as maintenance-free connections! (Dimensions in mm) 9/35