Bus Bar
Bus Bar
Bus Bar
Bus bar
A bus bar (also spelled busbar, buss bar or busbar), is a strip or bar of copper, brass or aluminum
that conducts electricity within a switchboard, distribution board, substation, battery bank or
other electrical apparatus. Its main purpose is to conduct electricity, not to function as a
structural member.
Busbars are typically either flat strips or hollow tubes as these shapes allow heat to dissipate
more efficiently due to their high surface area to cross-sectional area ratio. A hollow section has
higher stiffness than a solid rod of equivalent current-carrying capacity, which allows a greater
span between busbar supports in outdoor switch yards.
A busbar may either be supported on insulators, or else insulation may completely surround it.
Busbars are protected from accidental contact either by a metal earthed enclosure or by elevation
out of normal reach. Power Neutral busbars may also be insulated. Earth (safety grounding)
busbars are typically bare and bolted directly onto any metal chassis of their enclosure. Busbars
may be enclosed in a metal housing, in the form of bus duct or busway, segregated-phase bus, or
isolated-phase bus.
Busbars may be connected to each other and to electrical apparatus by bolted, clamp, or welded
connections. Often joints between high-current bus sections have matching surfaces that are
silver-plated to reduce the contact resistance. At extra-high voltages (more than 300 kV) in
outdoor buses, corona around the connections becomes a source of radio-frequency interference
and power loss, so connection fittings designed for these voltages are used.
Busbars are typically contained inside switchgear, panel boards, or busway. Distribution boards
split the electrical supply into separate circuits at one location. Busways, or bus ducts, are long
busbars with a protective cover. Rather than branching the main supply at one location, they
allow new circuits to branch off anywhere along the route of the busway.
Advantages
Following are some advantages of Bus bar trunking system over normal cabling system:1. On-site installation times are reduced compared to hard-wired systems, thus leading to cost
savings.
2. It provides increased flexibility in design and versatility with regard to future modifications.
3. Greater safety and peace of mind for specifiers, contractors and end-users.
4. Because of the simplicity of busbar, it is easy to estimate costs from the design/estimating stage
through to installation on site. This is because the technical characteristics and price of each
component are always known.
5. It is short sighted to compare the cost of busbar against that of a length of cable and not the
real cost of a cable installation to include multiple runs of cable, tray and fixing, let alone the
protracted time and effort of pulling cables.
6. Distribution busbar distributes power along its length through tap-off points along the busbar at
typically at 0.5 or 1 m centers. Tap-off units are plugged in along the length of the busbar to
supply a load; this could be a sub distribution board or, in a factory, to individual machines. Tapoffs can normally be added or removed with busbar live, eliminating production down time.
7. Installed vertically the same systems can be used for rising-mains applications, with tap-offs
feeding individual floors. Certified fire barriers are available at points where the busbar passes
through a floor slab. Protection devices such as fuses, switchfuses or circuit breakers are located
along the busbar run, reducing the need for large distribution boards and the large quantities of
distribution cables running to and from installed equipment.
8. Very compact so provides space savings.
9. Where aesthetics have to be considered, busbar trunking can be installed with natural
galvanized, aluminium, or painted finish. Special colours to match switchboards or a specific
colour scheme are also available on request.
10. Busbar trunking has several key advantages over conventional forms of power distribution
including: 11. (a) Reduced, onsite installation times when compared to hard-wired systems thus leading to cost
savings.
a. Increased flexibility in design and versatility with regard to future modifications.
b. Increased safety features brought about by the use of high quality, manufactured components,
which provide greater safety and peace of mind for specifies, contractors and end-users.
12. Uneven distribution of current takes place where multiple runs of cables are used in parallel.
13. Busbar trunking has tap-off points at regular intervals along each length to allow power to be
taken off and distributed to where it is needed. Because it is fully self-contained it needs only to
be mechanically mounted and electrically connected to be operational.
14. For higher ratings of power distribution we need to have multiple runs of cable. In such
conditions unbalanced distribution of current takes place and causing overheating of some cable.
This is completely avoided in the BTS systems.
15. When multiple runs of cables are used it often leads to improper end connections thereby
causing overheating of contacts, burning of cables ends, and is a major cause of fire. This is
completely avoided in Bus Bar Trunking systems.
5 Future
expansion
6 Fault
withstand
levels
7 Installation
time
8 Voltage drop
Limited by conductor
size of each circuit.
Much longer
High impedance if you
choose cable size based
on each floor current
rating.
busbar
Just one circuit can cover all floors.
Typical example
Rating Current: 3200Amp.
System:415Vac, TPN, 50Hz.
Fault Level: 50KA. For 1 Sec.
Operation Temp:40 C rise over 45 C ambient.
CONSIDERATION
Enclosure size: 1400 mm. wide X 400mm. height
Bus bar Size: 2:200x10 per Ph., 1:200x10 for Neutral.
Bus bar material: Electrolytic gr. Al. (IS 63401/AA6101)
Short Circuit Rating
-upto 400A rated current:
-600 to 1000A rated current:
-1250 to 2000A rated current:
-2500 to 5000A rated current:
The minimum cross section needed in sqmm for busbar in various common cases can be listed as
belowMaterial
Aluminium
Copper
Fault level
(KA)
35
50
65
35
50
65
Withstand time
1 sec.
443
633
823
285
407
528
200 msec.
198
283
368
127
182
236
40 ms.
89
127
165
57
81
106
10 ms.
44
63
82
28
41
53
Thus, by using the above formula and table, we can easily select busbars for our switchboards.
Size in
mm
Area
sqmm
Weight/
km
12X2
15X2
15X3
20X2
20X3
20X5
25X3
25X5
30X3
30X5
40X3
40X5
40X10
50X5
50X10
60X5
60X10
80X5
80X10
100X5
100X10
120X10
160X10
200X10
24
30
75
40
60
100
75
125
90
150
120
200
400
250
500
300
600
400
800
500
1000
1200
1600
2000
0.209
0.262
0.396
0.351
0.529
0.882
0.663
1.11
0.796
1.33
1.06
1.77
3.55
2.22
4.44
2.66
5.33
3.55
7.11
4.44
8.89
10.7
14.2
17.8
I
110
140
170
185
220
295
270
350
315
400
420
520
760
630
920
760
1060
970
1380
1200
1700
2000
2500
3000
II II
2500
3600
3200
4800
4050
5800
6700
9000
10000
Temperature rise
During the short circuiting, the bus bar should be able to withstand the thermal as well as
mechanical stress. When a sort circuiting takes place, the temperature rise is directly proportional
to the squire of the rms value of the fault current. The duration of short circuiting is very small
i.e. one second till the breakers opens and clears the fault. The heat dissipation through
convection and radiation during this short duration is negligible and all the heat is observed by
the busbar itself. The temperature rise due to the fault can be calculated by applying the
formulae.
T = K (I/A) 2 (1+) 10-2
T=temperature rise per second
A= conductor cross section area
= temperature coefficient of resistivity at 20 deg.C/deg.C
= 0 .00393 for copper
= 0 .00386 for aluminium
K = constant
=0.52 for copper
=1.166 for aluminium
= temperature of the conductor at the instant at which the temperature rise is being calculated.
Typical calculation
Rated current = 1000A
Fault current = 50KA for 1 sec
Permissible temperature rise= 40 deg.C
Busbar material =aluminium ally E91E
De-rating factor due to material =1
De-rating factor due to temperature rise =0.86
De-rating factor due to enclosure =0.75
Total de-rating factor = 1x0.75x0.86=0.66
Minimum cross section area required to withstand short circuit for 1 sec.
= (Ifc xt )/0.08
Where, Ifc = fault level current in KA
t= 1 second
Area A = (50x1 )/0.08 = 625 sqmm
Considering all de-rating factor, A = 625/0.66 =946.97
Say, cross sectional area per phase = 1000 sqmm
For neutral, cross sectional area per phase = 500 sqmm