Guide 1 en
Guide 1 en
Guide 1 en
of busbar distribution
Coordination
and protection
M
M
M
M
M
M
M
M
Contents
5
7
8
26
26
26
26
27
27
27
27
In short
Busbar distribution
system
Design and production of a busbar distribution installation for
industrial and commercial buildings must meet 3 main
requirements: progressive upgradeability of the installation,
simplicity and dependability. Busbar distribution ensures
these requirements are fully met.
Three performance
criteria for a busbar
distribution installation:
upgradeability
simplicity
dependability
3. Dependability
Dependable electrical distribution is optimized as a means of guaranteeing:
v safety of persons and equipment
v continuity of service (choice of grounding system, implementation of
discrimination techniques, breaking not required when making changes to the
installation....)
v reliability (reliable switchgear, factory-mounted subassemblies...)
v easy maintenance (simple, rapid modifications).
Dependability also guarantees an economic operating solution.
Busbar distribution fully meets these criteria.
To be
noticed
Busbar distribution
system
In large sites
Buildings in excess of 5 000 m2
The following diagrams represent standard installations which cover most cases
encountered in practice.
T transmission
MSB
Isc 30 to 80 kA
workwhop 1
T1 transmission supply
with a small
1000 to 5000 A
quantity of
tap points
workshop 2 supply
hall 2
supply
hall 1
supply
hall 3
supply
Isc 20 to 70 kA
Isc 20 to 50 kA
distribution
with a large
quantity of tap
points
i 400 A
i 800 A
bay 2
supply
bay 1
supply
100 to 250 A
Isc 10 to 40 kA
automation
enclosure
socket
enclosure
i 5 to
10 kA
i 40 A
i 40/
63 A
i 10 to 16 kA
Icc 10 to
15 kA
automation
lighting
enclosure
i 25 A
(40 A)
i 400 A
i 160 A
15 to 25 kA
i 400 A
20 to 70 kA
E 36283E
use
lighting
Systme de distribution
rpartie
In medium-sized and small sites
Buildings smaller than 5 000 m2
Level A
Transmission and
distribution
with a small
quantity of
tap points.
NB : does not concern
medium-sized
and small sites .
400 A
15 kA
10 to 15 kA
Level B
Distribution
with a large
quantity of
tap points.
100 to 250 A
warehouse
storage
i 5 kA
< 63 A
10 to 15 kA
Level C
Energy utilisation.
25 to 40 A
ID63 s
60 A
10 kA
30 mA
homogeneous load,
offices
final distribution
M
purpose of building
lighting
E 36853E
PC
In short
BBT in transmission and
distribution with a small
quantity of tap points
high current ratings from
1000A to 5000 A
high short-circuit withstand
up to 150 kA
technological continuity
flexibility
BBT in Distribution with a
large quantity of tap points:
numerous tap off sockets
box positioning flexibility
safe, easy handling
Final distribution:
on-load opening
(emergency breaking)
local disconnection.
Busbar distribution
system
1.2 Functions
Level A: transmission and distribution
with a small quantity of tap points
Requirements
This level corresponds to Transformer/Main Switchboard (MSB) supply and
main distribution downstream from the Main Switchboard (MSB).
The requirements of this level as far as performance criteria are concerned
(see p. 3) are summarized in the table below:
Performance
criteria
Requirement
Upgradeability
**
Simplicity
***
Comments
modifications at this level of the
installation although rare are important;
new layouts do not affect main
distribution
Power is available at all points of the
installation as from the design stage.
Implementation simplified by the
factory-built BBT concept.
Dependability
continuity of service
safety
* : minor requirement
***
**
** : average requirement
Systme de distribution
rpartie
Level B: distribution with a large
quantity of tap points
Requirements
Two types of loads must be supplied downstream from the distribution BBTs:
v workshops and large machines (automation cubicle). In this case the short-circuit
and current levels may still be high (20 to 70 kA respectively and up to 800 A) (see
large sites on page 4).
v bays and small machines (switchboard, automation enclosure, lighting circuit...).
Short-circuit and power levels are lower, 10 to 40 kA respectively and up to 400 A.
Performance criteria are summarized in the table below
Performance
criteria
Requirement
Comments
Upgradeability
***
Simplicity
***
continuity of service
***
safety
***
Dependability
bnrbirrgo
jk,,
Level C : the final distribution
Requirements
Downstream final distribution is often linked to the load. The performance criteria
requirements are:
Performance
criteria
Requirement
Upgradeability
***
**
Simplicity
Dependability
Comments
continuity of service
***
safety
***
BBT
BBT
tap off
circuit-breaker
tap off
circuit-breaker
connecting
cable
connecting
cable
automation
cubicle
final distribution
enclosure
industrial
control
circuit-breaker
isolating
switch
E 39731E
E 36282E
isolating
switch
final distribution
circuit-breaker
In short
IEC 439-1 :
LV switchgear assemblies
IEC 439-2 :
second part : specific busbar
trunking rules.
General
Area of application:
busbar trunkings for power
and lighting distribution.
Factory quality :
Manufacturers guarantee
characterizing the product.
Product quality and
dependability guaranteed by a
series of factory tests.
Busbar distribution
system
1.3 IEC 439.2 standards
This standard concerns LV switchgear assemblies.
Busbar trunkings must comply with the rules
laid down in publications 439-1 and 2.
Dfinitions
Busbar trunking:
Switchgear type tested assembly in the form of a conductive network concerning,
in a duct, cableway or similar enclosure, busbars which are supported
by insulating materials.
This assembly can be made up of:
- busbar parts with or without tap off points,
- power supply, flexible links,
- branch busbar parts.
Construction arrangements
Busbar trunkings must be designed as type tested LV switchgear assemblies (TTA).
According to the manufacturers instructions, BBTs are designed to withstand
mechanical loads.
For safety reasons, an BBT equipped with tap off points must be designed
in such a way as to prevent incorrect connection of the tap off parts.
If three-phase ac is used, phase order must be constant throughout the BBT.
Temperature rise limits are defined on the enclosures and connection terminals.
Test specifications
Type tests are designed to check compliance with the specifications laid down for a
given BBT type.
Type tests are carried out on a copy of an BBT or on an BBT type produced using
the same or similar drawings.
Type tests consist of:
- checking temperature rise limits, dielectric properties, short-circuit withstand,
electrical continuity of the protection circuit, clearances and creepage distances,
mechanical operation, degree of protection, resistance, reactance and impedance,
and sturdiness of the construction.
The standard describes all the conditions and provisions of the tests laid down and,
if necessary, the results to be obtained.
To be
noticed
Systme de distribution
rpartie
1.4 BBT protection
This must be provided in accordance with installation standards.
Overload protection
t(s)
The busbar trunking supplies loads: the total load current is lr.
Sizing characteristics for choice of BBT and overload protection are:
current rating lb = k1 x IT (k1 is the concentrationfactor)
rated busbar trunking current lnc > lb
permissible current as a function of temperature lz = f1 x lnc
(f1 is the temperature factor)
derating factor k2 linked to the type of switchgear:
- fuse
k2 = 1.1
- circuit-breaker
k2 = 1
1,25 to 1,6 In
For extension purposes, busbar trunking is normally protected for its rated current
lnc (or for their permissible current lz if the temperature factor f1 is applied).
E 39595E
In order to take account of busbar trunking thermal overload protection, the various
protection switchgear technologies and the maximum opening currents for
protection devices in overload conditions must be considered.
Calibration of thermal asymptotes
fuse
In
Iz = 1,1 In 1,45 Iz
Iz = Inc if fz = 1
1,05 to 1,3 In
t(s)
v the distribution fuse is calibrated to trip on overloads of between 1.25 and 1.6
1000
v Circuit-breaker protection:
E 39594E
In
Iz = In 1,45 Iz
circuit-breaker
10
Setting circuit-breakers
equipped with electronic
trip units:
thermal protection lr
adjustable from 0.4 ln to ln
short-circuit protection from
2 lr to 10 lr
increased flexibility and
upgradeability.
v the fuse is given a fixed rating. Current changes in the device to be protected
require fuse replacement.
The difference between 2 fuse ratings is approximately 25%. Standard ratings
are given according to the series of characteristic numbers of the Renard series.
For example: 40 - 50 - 63 - 80 - 100 - 125 - 160 - 200 - etc.
v the circuit-breaker offers a setting fineness of:
- 5% for circuit-breakers equipped with conventional thermal-magnetic trip units,
- 3% for circuit-breakers equipped with electronic trip units.
For example: a circuit-breaker with a nominal rating of 100 A can easily be set to
values of lr = 100A, 95A, 90A, 85A, 80A.
For example: a circuit-breaker with a nominal rating of 100 A set at 90 A will be used
to protect a KSA10 busbar trunking (lnc = 100 A) which is used for an ambient
temperature of 50C (see table of maximum permissible temperatures
as a function of operating temperature).
Io
.8
Ir
.9
.7
.9
1
.63
.88
Im
.93
.95
.98
.85
.5
x In
.8
x Io
6
7
8
10
x Ir
E 39749E
In short
If operating conditions are
different from rated conditions
of use, the circuit-breaker
offers enhanced optimization
of busbar trunking protection.
(e.g. operation at high
ambient temperatures of
45/50C).
Systme de distribution
rpartie
11
In short
BBT sizing is determined
by 3 types of
characteristics:
the maximum peak
current, peak l
the maximum short-term
rms current, lcw
the thermal stress
(in A2s).
Systme de distribution
rpartie
Short-circuit protection by circuitbreaker
Circuit-breaker characteristics
circuit-breaker
Isc at point A
E 36854E
BBT
Applications
Directly protected BBT
E 36855E
BBT
12
Systme de distribution
rpartie
Circuit-breaker/busbar trunking coordination
busbar trunking
peak I
asymm
Isc
Isc
E 38884E
Ipeak (kA)
250
assymetric factor
k
4,5 I 6
6 < I 10
10 < I 20
20 < I 50
50 < I
1,5
1,7
2,0
2,1
2,2
For example: for a circuit with a assumed short-circuit current of 50 kA rms, the first
peak reaches 105 kA (50 kA x 2.1): see figure opposite.
200
v the short-term short-circuit current, lcw, of the BBT, must be greater than the
150
current flowing through the installation for the duration of the short-circuit Isc
(duration T - total breaking time - including the time delay if any -).
For example: a KTA16 BBT has an lcw characteristic of 60 kA for T = 1 second, i.e. a
thermal stress withstand expressed in A2s equal to 3.6x109 A2s.
E 38885E
105 kA
100
50
rms Isc
0
4,5
10
20
50
100
If one of these relationships is not verified, a suitable higher rating must be chosen
for the BBT.
13
Systme de distribution
rpartie
limiting circuit-breaker
This mainly concerns protection of BBTs by moulded case type circuit-breakers
(< 1250 A).
In this case it is ensured that the BBT withstands the peak current limited
by the protection device and the corresponding thermal stress.
v the current limited (peak l) by the circuit-breaker is < the peak current permissible
to the BBT.
v the thermal stress limited by the circuit-breaker is < the thermal stress permissible
to the BBT.
Checking BBT withstand in peak l
Ipeak (kA)
non-limiting
peak current
Isc
Ipeak
maximum current
permissible to the
busbar trunking
IL
current limitation
curve
E 38881E
peak current
limited in the
busbar trunking
Icc
assumed short-circuit
current
thermal stress
limitation curve
E 38882E
thermal stress
limited in the
busbar trunking
assumed short-circuit
current
If either of these conditions is not met, oversizing of the BBT will be required.
14
Icc
Systme de distribution
rpartie
BBT protection summarizing table
Network characteristics
Isc
Circuit-breaker characteristics / Short-circuit constraints
Icu Isc at point A
BBT characteristics / Short-circuit constraints (1)
peak l
Icw for T (3)
A2s
BBT withstand
permissible
instantaneous
at peak current
short-term current
thermal withstand
k
kA rms x f(T)
kA2s
peak l Isc x k (2)
Icw Icc
time-delayed non-limiting
circuit-breaker
limiting breaker-circuit
(1)
peak l IL limited
by the circuit-breaker
kA 2s (BBT) kA 2s limited
by the circuit-breaker
circuit-breaker
'A
circuit-breaker
cable
Isc at point A
E 36855E
E 36854E
BBT
BBT
the busbar trunking short-circuit protection level can be either total or partial:
v total protection: the busbar trunking is protected up to the ultimate breaking
capacity of the circuit-breaker
v partial protection: the busbar trunking is protected up to a high short-circuit
current level (e.g. 55 kA) but less than circuit-breaker ultimate breaking capacity
(lcu) (e.g. lcu = 70 kA).
Ipeak ()
Ipeak ()
total protection
total protection
BBT 1
BBT 1
partial
protection
partial
protection
BBT 2
BBT 2
E 39593E
E 39592E
circuit-breaker
curve
Non-limiting circuit-breaker
Isc
limiting
circuit-breaker
curve
I (25 kA)
BBT2
protection
limit
Icu Isc
(150 kA)
Limiting circuit-breaker
15
To be
noticed
Systme de distribution
rpartie
Protection device
coordination:
System performance is
guaranteed by
standardization of circuitbreaker protection and BBT
busbar distribution.
The performance of a busbar
distribution system depends
on the specific characteristics
of each of its component
parts.
This performance will be
optimized by providing proper
coordination, obtained by a
system type design.
Criteria
relevant functions
upgradeability
simplicity
continuity of service
safety
Level A
Level B
transmission and Distribution
distribution with with a large
a small quantity quantity of
of tap points
tap points
v
v
v
16
Level C
final
distribution
v
v
17
aa
The Schneider busbar
distribution System
In large sites
Buildings in excess of 5 000 m2
KT20
1600A
55kA
400A
45kA
400A
40kA
160A
30kA
push
to
trip
push
to
trip
35kA
10kA
a
a
E 40139E
25A
15 kA
KSA40
Level A
KT20
.4
.2
.1
push
to
trip
KSA16
level B
push
push
to
trip
KBB
.4
.2
.1
18
E 39733E
Level C
Systme Schneider
de distribution rpartie
In medium-sized and small sites
Buildings smaller than 5 000 m2
400A
15kA
160A
10kA
,,,
,,,
,,,,
,,,,
push
to
trip
63A
8kA
E 40140E
25A
5kA
KSA16
push
to
trip
Level B
,
,
,
,,
,,
KNA63
Mg
multi
DPN
C40
N 1
230Va
4500
3
20750
T
OFF
KBA
Level C
Example of a supermarket
E 38790E
OFF
19
To be
noticed
Systme de distribution
rpartie
2.1 Telemecanique BBT/Merlin Gerin
circuit-breaker coordination
The approach used in the study examined earlier, applied to Merlin Gerin and
Telemecanique products, enhances the Schneider System.
Isc = 55 kA
A
MSB
E 36856E
The following table lists the various constraints and characteristics of the circuitbreaker and busbar trunking.
Isc = 55 kA
MSB
A
E 39591E
transmission
BBT
non-limiting circuit-breaker
distribution
BBT
20
Systme de distribution
rpartie
Protection of an BBT by an NS400N
limiting circuit-breaker
Limiting capacity
The circuit-breakers in the Compact NS range are limiting circuit-breakers
with a high limiting capacity.
A circuit-breakers limiting capacity expresses its ability only to let a limited
current IL lower than the assumed Isc asymmetrical peak short-circuit current,
through on a short-circuit.
The consequence is a considerable reduction in electrodynamic and thermal
stresses in the installation requiring protection.
NS400N
assumed Isc
at "B" 40 kA
KSA40
E 36857E
assumed Isc
at "A" 45 kA
This fault current limitation means that BBT protection level is extremely high.
With present-day circuit-breakers (Compact NS type), a 10% limitation
(IL /asymmetrical Isc) reduces to less than 1% the fault current flowing through
the installation.
The diagram opposite shows protection of the KSA40 distribution busbar trunking
by an NS400N limiting circuit-breaker. In this diagram:
the Isc is 45 kA at point A
A study of the various limitation curves shows that:
in B, the limited Isc is only 26 kA (instead of nearly 84 kA without limitation)
the energy limited in A2s is far lower than BBT withstand.
kA peak
48 k
E 38936E
26 k
40 kA
Isc
a. current limitation NS
A2s
354 x 106
E 38937E
1,6 x 106
40 kA
Isc
b. energy limitation NS
21
Systme de distribution
rpartie
The following table lists the various constraints and characteristics of the circuitbreaker and BBT.
Network characteristics
Isc = 45 kA at point A
Isc = 40 kA at point B
Circuit-breaker characteristics / Short-circuit constraints
Icu = 45 kA 45 kA at point A
BBT characteristics / Short-circuit constraints (at point B)
peak l = 48 k
Icw for Ts
A2s = 354 x 106 A2s
BBT withstand
permissible short-term
instantaneous
at peak current
current
thermical withstand
k
kA rms
kA2s
48 k IL = 28 k
354 x 106 1,6 x 106 A2s
limiting circuit-breaker
unapplicable characteristics
This table shows that the limitation performance of the Compact NS is vital to reduce
the stresses to which the busbar trunkings are subjected and in particular the
thermal stress.
The exceptional limitation of the peak current means that monitoring of the BBT
thermal stress criterion can be ignored (limited I2t << BBT withstand I 2t).
The following limitation curves immediately show the coordination characteristics.
106 x A2s
KSA63 (630 A)
1100
KSA40 (400 A)
Ipeak
k
354
KSA25 (250 A)
100
KSA63
67,5
49,2
NS630
NS400
KSA40
KSA16 (160 A)
20,2
KSA25
28
NS160
KSA16
E 38938E
L
13,6
6,8
H
KSA10
N
25
NS100
70100 150
Isc
E 38939E
22
KSA10 (100 A)
NS250
H L NS630
NS400
H L
0,55
N
NS250
NS160
L NS100
Isc
These diagrams show that protection is provided in excess of the maximum Isc
encountered on installations.
22
sjort
Im
Enhanced coordination has
many advantages:
Exclusive features of the
Schneider System
possibility of installing
circuit-breakers with standard
breaking capacity (anywhere
on the tap off BBT) downstream
from an BBT protected
by a Compact NS.
standard guarantee of total
distribution discrimination.
Systme de distribution
rpartie
2.2 Exclusive Features of the Schneider
System: Enhanced busbar distribution
coordination
Coordination between a Compact NS circuit-breaker (D1 placed upstream)
and a downstream circuit-breaker (D2) from the Merlin Gerin ranges protecting
an BBT, enhances the Isc withstand performance of this BBT.
Enhancement depends on the limitation performances and breaking technique
of the Merlin Gerin circuit-breakers.
E 38883E
D1
Coordination
23
Systme de distribution
rpartie
Application: enhanced BBT protection
D1
NS400N
without coordination, the very high limiting capacity of the NS160N alone already
protects the KSA16 up to its ultimate breaking capacity Icu, i.e. 35 kA.
KSA40
E 36972E
D2
NS160N
KSA16
45 kA
protection limit
KSA16
descrimination limit
KSA16 characteristic
peak l = 22 k
A2 s = 20,2 106
24
protected by
limiting D2
NS 160 N Icu = 35 kA
Icc = 35 kA
up to max. Isc = 35 kA
according to upstream
protection
Maximum stresses
on BBT if a
short-circuit occurs
Isc = 35 kA
IL = 19 k
A2s = 0,52 10 6
BBT protection
in coordination
protected by limiting D2
NS 160 N Icu = 35 kA
coordinated upstream
with D1
NS400 N Icu = 45 kA
Icc = 45 kA
up to max. Isc = 45 kA
guaranteed
Isc = 45 kA
I L = 20 k
A2s = 0,6 106
Systme de distribution
rpartie
2.3 Final distribution
The following diagrams optimize all the functions required for all industrial and
commercial building applications.
Protection:
v switchboard overcurrent protection is provided by the protection circuit-breaker
(DD) installed in the tap off box.
v feeder protection is provided by the circuit-breakers (DCI) installed at each feeder.
Continuity of service is optimum at feeder level:
v thanks to enhanced total discrimination between the protection devices
v thanks to easy access and resetting of the protection devices.
Maintenance: the switchboard incoming switch (IS) guarantees disconnection and
thus safety for maintenance, servicing and upgrading of the installation.
On-load opening: this function is performed by a switch. The incoming switch
places the installation out of operation should a problem arise, either by manual
control or automatically using an emergency punch button. This safety function
requires a high degree of reliability should a fault occur on the electrical installation.
Canalis
Canalis
tap off
circuit-breaker
tap off
circuit-breaker
DD
connecting
cable
connecting
cable
automation
cubicle
final distribution
enclosure
isolating
switch
IS
Industrial
DCI
control
circuit-breaker
E 41500E
E 39735E
isolating
switch
final distribution
circuit-breaker
25
Systme de distribution
rpartie
2.4 Advantages of the Schneider System
BBT protection
E42 563E
E42563E - 2
Final distribution
52125E
Automation enclosure
Prisma enclosure
automation cubicle
Switch
26
Systme de distribution
rpartie
2.5 Advantages and exclusive features
of the Schneider System
Total coordination of the Schneider System guarantees and enhances safety
of persons and equipment, continuity of service and installation upgradeability
and simplicity.
Total coordination is materialized by:
27
Level A
transmission and
distribution with a small
quantity of tap points
Criteria
Relevant functions
upgradeabilityone tap off connection every meter
extensive setting range of protection devices
easy installation
standard performance circuit-breakers
for all Isc 70 kA
simplicity
CB
BBT
BBT,CB
continuty
of
service
safety of
Level B
distribution with
a large quantity
of tap points
BBT
CB
BBT
Level C
final distribution
CB
CB
BBT,CB
BBT,CB
CB
CB
BBT
BBT
BBT
BBT, CB
BBT
BBT
BBT
BBT, CB
BBT
CB
BBT
CB
CB
BBT, CB
BBT, CB
CB
CB
CB
BBT
CB
CB
BBT
CB
CB
CB
28
041624E
54511E
053192E
86010E
54512E
049575E
035928E
Ta b l e s
Compact C amont - 1200 1350 A, 1000 A, 800 A Compact NS / Canalis KSA, KVA, KVC ....................................... p 39
Compact NS amont - 630 160 A Compact NS, Multi 9 / Canalis KSA, KLE, KBA, KBB ................ p 43
lis
052168E
cana
lis
025125E
054104E
036430E
cana
29
Installation example
Example
Consider two 630 kVA/400 V transformer
(Usc 4 %) supplying a main LV switchboard
for which the prospective short-circuit
current on the busbars is 44 kA.
From the switchboard, a 30-metre long
Canalis KVA63 transmission busbar
trunking system (630A) supplies a Canalis
KSA63 trunking system (630A) for
distribution with high-density tap-offs.
A tap-off on the KSA63 trunking supplies a
Canalis KSA16 trunking system.
The short-circuit level are respectively:
c 44 kA downstream of circuit-breaker CB1
and at the upstream connection of the
KVA63 trunking.
c 33 kA at the junction between the KVA63
transmission trunking and the KSA63
trunking for high-density tap-offs.
Coordination tables
The tables for coordinating Merlin Gerin
E40700E
E40701E
CB1
CB1 = NS400H
(Breaking
capacity = 70 kA)
Isc = 65 kA
Ib = 360 A
CB2
CB2 = NS160H
(Breaking
capacity = 70 kA)
Isc = 65 kA
Ib = 140 A
E39613E
CB1
44 kA
NS630N (45 kA breaking
capacity)
45 kA
CB2
33 kA
NS160N (35 kA breaking
capacity)
45 kA
35 kA
630 kVA
400 V
630 kVA
400 V
prospective Isc
44 kA
LV main
swichboard
D1 Disconnector
prospective Isc
44 kA
prospective Isc
33 kA
Canalis KSA 63
a 30-meter KVA63
transmission BBT
systems
D2 Disconnector
Canalis KSA
30
Low power
Medium power
KVA 200 to 800 A
KVC 200 to 800 A
(380/415 V - 660/690 V)
KSA 100 to 800 A
(380/415 V - 660/690 V)
KN 40 to 100 A
(380/415 V)
KLE, KBA, KBB
K System
(380/415 V)
High power
KTA 1000 to 4000 A
KTC 1000 to 4000 A
(380/415 V - 660/690 V)
KHF 1000 to 4500 A
(380/415 V - 660/690 V)
Coordination tables between Merlin Gerin circuit breakers and Telemecanique Canalis
busbar trunking
Voltage : 380/415 V
type of Canalis busbar trunking
trunking rating (in A at 35C)
type of circuit breaker
Multi 9
Isc max. in kA ms.
16/20
C60N16/20
C60H16/20
C60L16/20
C60N25
C60H25
C60L25
NC100LH25
C60N40
C60H40
C60L40
NC100LH40
C60N63
C60H63
C60L63
NC100LH63
NS100N (1)
NS100H (1)
NS100L (1)
KLE-16/20
25
10
15
25
KBA-25
25
KBB-25
40
10
15
25
50
10
15
25
50
KBA-40
40
KBB-40
40
KN-04
63
10
15
25
50
10
15
25
50
10
15
25
50
25
25
25
KN-06
100
10
15
15
50
25
25
25
KN-10
25
25
25
(1) TM-D trip unit, rating 40 or 63 or 100 A and STR22SE rating 40 or 100 A
Masterpact
NS100N
NS100H
NS100L
NS160N
NS160H
NS160L
NS250N
NS250H
NS250L
NS400N
NS400H
NS400L
NS630N
NS630H
NS630L
C801N
C801H
C801L
C1001N
C1001H
C1001L
C1251N
C1251H
CMN
M08N1
M10N1
M12N1
M08H1
M10H1
M12H1
M08H2
M10H2
M12H2
M08L1
M10L1
M12L1
100
25
25
25
20
20
20
17
17
17
KSA-10
160
25
70
90
36
70
70
36
55
55
30
30
30
KSA-16
250
36
70
150
36
70
150
45
45
45
30
30
30
KSA-25
400
KSA-40
500
KSA-50
630
KSA-63
800
45
70
150
45
70
150
26
26
30
45
70
150
30
30
40
45
70
150
40
40
55
40
40
55
24
24
24
24
24
24
24
24
24
24
24
24
24
26
26
26
26
26
26
26
26
26
26
32
32
32
32
32
32
32
32
32
32
32
32
32
40
40
40
45
70
150
50
50
80
50
50
80
50
50
38
38
38
38
38
38
38
38
38
38
50
50
50
KSA-80
31
voltage : 380/415 V
type of Canalis busbar trunking
trunking rating (in A at 35C)
type of circuit breaker
Compact
Isc max. in kA ms.
Masterpact
Masterpact
Masterpact
32
200
NS250N
NS250H
NS250L
NS400N
NS400H
NS400L
NS630N
NS630H
NS630L
C801N
C801H
C801L
C1001N
C1001H
C1001L
M08N1
M10N1
M08H1
M10H1
M08H2
M10H2
M08L1
M10L1
NS250N
NS250H
NS250L
NS400N
NS400H
NS400L
NS630N
NS630H
NS630L
C801N
C801H
C801L
C1001N
C1001H
C1001L
M08N1
M10N1
M08H1
M10H1
M08H2
M10H2
M08L1
M10L1
C1001N
C1001H
C1001L
C1251N
C1251H
M10N1
M12N1
M16N1
M20N1
M25N1
M10H1
M12H1
M16H1
M20H1
M25H1
M32H1
M40H1
M50H1
M10H2
M12H2
M16H2
M20H2
M25H2
M32H2
M40H2
M50H2
M10L1
M12L1
M16L1
M20L1
M25L1
KVA-20
315
35
70
100
35
35
35
KVC-20
200
35
70
100
35
35
35
KTA-10
1000
50
55
100
50
55
40
40
40
40
40
40
40
40
40
55
55
KVA-31
400
KVA-40
500
KVA-50
630
KVA-63
800
45
70
150
45
70
150
45
70
150
45
70
150
45
70
150
45
70
150
45
70
150
45
70
150
40
40
70
40
40
70
33
33
33
33
33
33
40
40
KVC-31
315
KVC-40
400
KVC-63
630
KVC-80
800
45
70
150
45
70
150
45
70
150
45
70
150
45
70
150
45
70
150
40
40
70
40
40
70
36
36
36
36
36
36
40
40
50
60
110
50
60
110
40
40
40
40
40
40
55
55
KTA-12
1200
50
70
150
50
70
40
40
40
50
50
50
50
50
50
85
85
65
65
65
KTA-16
1600
KTA-20
2000
40
40
40
55
55
60
60
60
60
60
40
40
40
55
55
65
65
65
73
73
60
60
60
60
60
130
130
105
105
105
73
73
73
73
73
130
130
130
KTA-25
2500
KTA-30
3000
55
55
55
55
75
75
75
75
75
75
75
75
80
80
80
80
86
86
86
86
130
130
130
KVA-80
50
60
110
50
60
110
40
40
40
40
40
40
55
55
KTA-40
4000
75
75
90
90
90
90
voltage : 380/415 V
type of Canalis busbar trunking
trunking rating (in A at 35C)
type of circuit breaker
Compact
Isc max. in kA ms.
Masterpact
Masterpact
KTC-10
1000
50
55
100
50
55
40
40
40
C1001N
C1001H
C1001L
C1251N
C1251H
M10N1
M12N1
M16N1
M20N1
M25N1
M10H1
M12H1
M16H1
M20H1
M25H1
M32H1
M40H1
M50H1
M63H1
M10H2
M12H2
M16H2
M20H2
M25H2
M32H2
M40H2
M50H2
M63H2
M10L1
M12L1
M16L1
M20L1
M25L1
C801N
C801H
C801L
C1001N
C1001H
C1001L
C1251N
C1251H
CMN
CMH
M08N1
M10N1
M12N1
M16N1
M20N1
M25N1
M08H1
M10H1
M12H1
M16H1
M20H1
M25H1
M32H1
M40H1
M50H1
M63H1
M08H2
M10H2
M12H2
M16H2
M20H2
M25H2
M32H2
M40H2
M50H2
M63H2
M08L1
M10L1
M12L1
M16L1
M20L1
M25L1
KTC-13
1350
50
70
150
50
70
40
40
40
40
40
40
50
50
50
40
40
40
50
50
50
55
55
KHF
1000
28
28
45
28
28
45
28
28
28
28
28
28
28
28
28
28
28
28
28
28
28
28
KTC-16
1600
KTC-20
2000
40
40
40
55
55
60
60
60
60
60
40
40
40
55
55
65
65
65
73
73
60
60
60
60
60
85
85
65
65
65
73
73
73
73
73
130
130
105
105
105
KTC-25
2500
KTC-30
3000
55
55
55
55
75
75
75
75
75
75
75
75
82
82
82
82
130
130
130
130
130
130
82
82
82
82
KTC-40
4000
KTC-50
5000
75
75
90
90
95
95
90
90
90
90
95
95
130
130
130
KHF
KHF
KHF
KHF
1200/1450 2200/2500 3000/3400 4000/4500
50
50
80
50
50
38
38
38
38
38
38
38
38
38
38
38
38
38
38
28
28
28
28
28
28
28
38
38
38
38
38
38
38
35
35
35
28
28
28
50
50
50
42
42
42
70
85
70
85
40
55
55
55
55
65
75
75
75
75
90
90
75
75
75
75
100
100
75
75
100
100
90
90
90
90
90
90
90
100
100
100
100
120
120
100
100
125
125
130
130
130
130
130
33
voltage: 660/690 V
type of Canalis busbar trunking
trunking rating (in A at 35C)
type of circuit breaker
Compact
Isc max. in kA ms.
Masterpact
Masterpact
34
NS100N
NS100H
NS100L
NS160N
NS160H
NS160L
NS250N
NS250H
NS250L
NS400N
NS400H
NS400L
NS630N
NS630H
NS630L
C801N
C801H
C801L
C1001N
C1001H
C1001L
C1251N
C1251H
CMN
M08N1
M10N1
M12N1
M08H1
M10H1
M12H1
M08H2
M10H2
M12H2
M08L1
M10L1
M12L1
NS250N
NS250H
NS250L
NS400N
NS400H
NS400L
NS630N
NS630H
NS630L
C801N
C801H
C801L
C1001N
C1001H
C1001L
M08N1
M10N1
M08H1
M10H1
M08H2
M10H2
M08L1
M10L1
KSA-10
100
8
10
20
8
10
20
8
10
15
KVA-20
200
8
10
20
10
20
20
KSA-16
160
8
10
75
8
10
75
8
10
20
10
17
14
KSA-25
250
8
10
75
8
10
20
10
20
28
KSA-40
400
KSA-50
500
KSA-63
630
KSA-80
800
10
20
35
10
20
35
25
26
26
10
20
35
25
29
30
10
20
35
25
35
45
25
35
45
24
24
24
24
24
24
24
24
24
24
24
24
24
26
26
26
26
26
26
26
26
26
26
26
26
26
32
32
32
32
32
32
32
32
32
32
32
32
32
20
20
35
25
40
60
25
40
60
25
40
38
38
38
38
38
38
38
38
38
38
38
38
38
KVA-31
315
KVA-40
400
KVA-50
500
KVA-63
630
KVA-80
800
10
20
75
10
20
35
10
20
75
10
20
35
10
20
75
10
20
35
10
20
75
10
20
35
33
33
50
33
33
50
33
33
33
33
33
33
33
33
25
40
60
25
40
60
40
40
40
40
40
40
40
40
voltage: 660/690 V
type of Canalis busbar trunking
trunking rating (in A at 35C)
type of circuit breaker
Compact
Isc max. in kA ms.
Masterpact
Masterpact
NS250N
NS250H
NS250L
NS400N
NS400H
NS400L
NS630N
NS630H
NS630L
C801N
C801H
C801L
C1001N
C1001H
C1001L
M08N1
M10N1
M08H1
M10H1
M08H2
M10H2
M08L1
M10L1
C1001N
C1001H
C1001L
C1251N
C1251H
M10N1
M12N1
M16N1
M20N1
M25N1
M10H1
M12H1
M16H1
M20H1
M25H1
M32H1
M40H1
M50H1
M10H2
M12H2
M16H2
M20H2
M25H2
M32H2
M40H2
M50H2
M10L1
M12L1
M16L1
M20L1
M25L1
KVC-20
200
8
10
20
10
20
20
KTA-10
1000
25
40
60
25
40
40
40
40
40
40
40
40
40
40
40
40
KVC-31
315
KVC-40
400
KVC-63
630
KVC-80
800
10
20
75
10
20
35
10
20
75
10
20
35
10
20
75
10
20
35
25
36
60
25
36
60
36
36
36
36
36
36
36
36
25
40
60
25
40
60
40
40
40
40
40
40
40
40
KTA-12
1200
25
40
60
25
40
40
40
40
50
50
50
50
50
50
50
50
50
50
50
KTA-16
1600
KTA-20
2000
40
40
40
40
40
60
60
60
60
60
40
40
40
40
40
65
65
65
65
65
60
60
60
60
60
65
65
65
65
65
73
73
73
73
73
65
65
65
KTA-25
2500
KTA-30
3000
40
40
55
55
65
65
75
75
75
75
75
75
80
80
80
80
85
85
85
85
KTA-40
4000
75
75
85
85
85
85
65
65
65
35
voltage: 660/690 V
type of Canalis busbar trunking
trunking rating (in A at 35 C)
type of circuit breaker
Compact
Isc max. in kA ms.
Masterpact
Masterpact
36
C1001N
C1001H
C1001L
C1251N
C1251H
M10N1
M12N1
M16N1
M20N1
M25N1
M10H1
M12H1
M16H1
M20H1
M25H1
M32H1
M40H1
M50H1
M63H1
M10H2
M12H2
M16H2
M20H2
M25H2
M32H2
M40H2
M50H2
M63H2
M10L1
M12L1
M16L1
M20L1
M25L1
C801N
C801H
C801L
C1001N
C1001H
C1001L
C1251N
C1251H
CMN
CMH
M08N1
M10N1
M12N1
M16N1
M20N1
M25N1
M08H1
M10H1
M12H1
M16H1
M20H1
M25H1
M32H1
M40H1
M50H1
M63H1
M08H2
M10H2
M12H2
M16H2
M20H2
M25H2
M32H2
M40H2
M50H2
M63H2
M08L1
M10L1
M12L1
M16L1
M20L1
M25L1
KTC-10
1000
25
40
60
25
40
40
40
40
KTC-13
1350
25
40
60
25
40
40
40
40
40
40
40
50
50
50
40
40
40
50
50
50
55
55
KHF
1000
28
28
45
28
28
30
28
28
28
28
28
28
28
28
28
28
28
28
28
28
28
28
KTC-16
1600
KTC-20
2000
40
40
40
40
40
60
60
60
60
60
40
40
40
40
40
65
65
65
65
65
60
60
60
60
60
65
65
50
50
50
73
73
73
73
73
65
65
65
65
65
KTC-25
2500
KTC-30
3000
40
40
55
55
65
65
75
75
75
75
75
75
80
80
80
80
65
65
65
65
65
65
KHF
KHF
KHF
KHF
1200/1450 2200/2500 3000/3400 4000/4500
28
40
60
28
40
38
38
38
38
38
38
38
38
38
38
38
38
38
38
28
28
28
28
28
28
28
38
38
38
38
38
38
38
28
28
28
28
28
28
38
38
38
38
38
38
50
50
50
50
65
75
75
75
75
85
85
75
75
75
75
85
85
75
75
85
85
85
85
85
85
85
85
85
85
85
85
85
85
85
85
85
85
85
65
65
65
65
65
82
82
82
82
KTC-40
4000
KTC-50
5000
75
75
85
85
85
85
85
85
85
85
85
85
Cascading
The use of a current-limiting circuit breaker
upstream to reinforce the breaking capacity
of a downstream circuit breaker.
Principle
Cascading
Cascading
E40702E
E40703E
CB1
CB1 = NS400H
Renforced
break. cap.
70 kA
CB2 = NS160N
(Breaking
cap. = 35 kA)
CB2
Isc = 65 kA
Principle
E40702E
Discrimination
In the event of an electrical fault on one
outgoing circuit, discrimination is the ability
of the electrical installation to maintain the
continuity of electrical power supplied to the
other circuits not concerned by the fault.
As a general rule, cascading and
discrimination techniques are applied
independently.
Schneider has developed an exclusive
system to conciliate cascading and
discrimination.
This system ensures discrimination up to the
reinforced breaking capacity of the
association of circuit breakers CB1 and CB2 .
CB1 = NS400H
CB1
Break. cap. +
discrimination
reinforced 70 kA
CB2
Isc = 65 kA
CB2 = NS160N
Isc = 65 kA
CB 2 breaking capacity
Discrimination ensured up to the reinforced
breaking capacity of CB2
37
CB1 = NS400H
KSA40 (400 A)
CB2 = NS160N
KSA16 (160 A)
70 kA
38
NS400N
STR23SE/STR53UE
KSA / KVA / KVC
315 and 400 A
45
NS400H
NS400H
STR23SE/STR53UE
KSA / KVA / KVC
315 and 400 A
70
NS400L
STR23SE/STR53UE
STR23SE/STR53UE
KSA / KVA / KVC
KSA
/ KVA
/ KVC
315 and
400
A
315 and 400 A
70
150
NS160N
NS160H
KSA
160 A
NS100N
NS100H
TMD/STR22SE
KSA
KSA
100
100 A
A
70
70
150
70
150
70
45
70
70
150
70
150
70
45
70
70
25
70
70
NS100N
TMD/STR22SE
KSA
100 A
NS160N
NS160N
KSA
160 A
NS100N
TMD/STR22SE
KSA
100 A
45
45
45
45
KSA
KSA
160
160 A
A
E39614E
voltage: 380/415 V
upstream
circuit-breaker
level of protection
of the upstream
busbar trunking
upstream busbar
canalisation
reinforced cascading
and discrimination
between the 2 circuitbreakers
downstream
circuit-breaker
reinforced protection
of the downstream
busbar trunking
downstream
busbar trunking
C1251N
STR35SE / STR55UE
KTA-12 / KTC-13
1200 and 1350 A
50
NS100N
NS160N
TMD / STR22SE
KSA
KSA
100 A
160 A
C1251N
STR45AE
KTA-12 / KTC-13
1200 and 1350 A
50
NS250N
NS100N
NS160N
TMD / STR22SE
KSA
KSA
100 A
160 A
NS250N
KSA
250 A
NS400N
NS630N
STR23SE / STR53UE
KSA / KVA / KVC
315 - 400 A 500 - 630 A
KSA
250 A
NS400N
NS630N
STR23SE / STR53UE
KSA / KVA / KVC
315 - 400 A 500 - 630 A
50
50
45
40
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
25
50
50
50
50
C1251N
STR35SE / STR55UE
KTA-12 / KTC-13
1200 and 1350 A
50
NS100N TMD / STR22SE
40 A
63 A
KN
KN
40 A
63 A
C1251N
STR45AE
KTA-12 / KTC-13
1200 and 1350 A
50
100 A
KN
100 A
100 A
KN
100 A
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
39
C1251H
STR35SE / STR55UE
KTA-12 / KTC-13
1200 and 1350 A
70
NS100N
NS160N
TMD / STR22SE
KSA
KSA
100 A
160 A
NS250N
NS100N
NS160N
TMD / STR22SE
KSA
KSA
100 A
160 A
NS250N
KSA
250 A
NS400N
NS630N
STR23SE / STR53UE
KSA / KVA / KVC
315 - 400 A 500 - 630 A
KSA
250 A
NS400N
NS630N
STR23SE / STR53UE
KSA / KVA / KVC
315 - 400 A 500 - 630 A
70
70
45
40
70
70
70
70
70
70
70
70
70
70
70
70
70
70
70
70
70
70
70
70
70
70
70
C1251H
STR35SE / STR55UE
KTA-12 / KTC-13
1200 and 1350 A
70
NS100N TMD / STR22SE
40 A
63 A
KN
KN
40 A
63 A
40
C1251H
STR45AE
KTA-12 / KTC-13
1200 and 1350 A
70
C1251H
STR45AE
KTA-12 / KTC-13
1200 and 1350 A
70
100 A
KN
100 A
100 A
KN
100 A
70
70
70
70
70
70
70
70
70
70
50
50
50
50
50
C1001N
STR35SE / STR55UE
KTA-10 / KTC-10
1000 A
50
NS100N
NS160N
TMD / STR22SE
KSA
KSA
100 A
160 A
NS100N
NS160N
TMD / STR22SE
KSA
KSA
100 A
160 A
NS250N
KSA
250 A
NS400N
NS630N
STR23SE / STR53UE
KSA / KVA / KVC
315 - 400 A 500 - 630 A
KSA
250 A
NS400N
NS630N
STR23SE / STR53UE
KSA / KVA / KVC
315 - 400 A 500 - 630 A
50
50
45
40
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
C1001N
STR45AE
KTA-10 / KTC-10
1000 A
50
100 A
KN
100 A
100 A
KN
100 A
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
C1001H
STR35SE / STR55UE
KTA-10 / KTC-10
1000 A
55
NS100N
NS160N
TMD / STR22SE
KSA
KSA
100 A
160 A
NS250N
C1001N
STR35SE / STR55UE
KTA-10 / KTC-10
1000 A
50
C1001N
STR45AE
KTA-10 / KTC-10
1000 A
50
C1001H
STR45AE
KTA-10 / KTC-10
1000 A
55
NS250N
NS100N
NS160N
TMD / STR22SE
KSA
KSA
100 A
160 A
NS250N
KSA
250 A
NS400N
NS630N
STR23SE / STR53UE
KSA / KVA / KVC
315 - 400 A 500 - 630 A
KSA
250 A
NS400N
NS630N
STR23SE / STR53UE
KSA / KVA / KVC
315 - 400 A 500 - 630 A
70
70
45
40
70
70
70
70
70
70
70
70
70
70
70
70
70
70
55
55
55
55
55
55
55
55
55
C1001H
STR35SE / STR55UE
KTA-10 / KTC-10
1000 A
55
NS100N TMD / STR22SE
40 A
63 A
KN
KN
40 A
63 A
C1001H
STR45UE
KTA-10 / KTC-10
1000 A
55
100 A
KN
100 A
100 A
KN
100 A
70
70
70
70
70
70
70
70
70
70
50
50
50
50
50
41
C801N
STR35SE / STR55UE
KVA-80 / KVC-80
800 A
50
NS100N
NS160N
TMD / STR22SE
KSA
KSA
100 A
160 A
NS100N
NS160N
TMD / STR22SE
KSA
KSA
100 A
160 A
NS250N
KSA
250 A
NS400N
STR23SE / STR53UE
KSA / KVA / KVC
315 - 400 A
KSA
250 A
NS400N
STR23SE / STR53UE
KSA / KVA / KVC
315 - 400 A
50
50
35
50
50
50
35
50
50
50
50
50
50
50
50
50
50
50
50
50
50
100 A
KN
100 A
100 A
KN
100 A
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
C801H
STR35SE / STR55UE
KVA-80 / KVC-80
800 A
60
NS100N
NS160N
TMD / STR22SE
KSA
KSA
100 A
160 A
C801H
STR45AE
KVA-80 / KVC-80
800 A
60
NS250N
NS100N
NS160N
TMD / STR22SE
KSA
KSA
100 A
160 A
NS250N
KSA
250 A
NS400N
STR23SE / STR53UE
KSA / KVA / KVC
315 - 400 A
KSA
250 A
NS400N
STR23SE / STR53UE
KSA / KVA / KVC
315 - 400 A
70
70
35
70
70
70
35
70
70
70
70
70
70
70
60
60
60
60
60
60
60
C801H
STR35SE / STR55UE
KVA-80 / KVC-80
800 A
60
NS100N TMD / STR22SE
40 A
63 A
KN
KN
40 A
63 A
42
C801N
STR45AE
KVA-80 / KVC-80
800 A
50
NS250N
C801N
STR35SE / STR55UE
KVA-80 / KVC-80
800 A
50
C801N
STR45AE
KVA-80 / KVC-80
800 A
50
C801H
STR45AE
KVA-80 / KVC-80
800 A
60
100 A
KN
100 A
100 A
KN
100 A
70
70
70
70
70
70
70
70
70
70
50
50
50
50
50
NS630N
STR23SE/STR53UE
KSA / KVA / KVC
500 and 630 A
45
NS100N
NS160N
TMD / STR22SE
KSA
KSA
100 A
160 A
NS630H
STR23SE/STR53UE
KSA / KVA / KVC
500 and 630 A
70
NS250N
NS630L
STR23SE/STR53UE
KSA / KVA / KVC
500 and 630 A
150
NS250N
KSA
250 A
NS100N
NS160N
TMD / STR22SE
KSA
KSA
100 A
160 A
NS250H
KSA
250 A
NS100H
NS160H
TMD / STR22SE
KSA
KSA
100 A
160 A
45
45
70
70
70
150
150
150
45
45
70
70
70
150
150
150
45
45
70
70
70
70
70
70
KSA
250 A
NS630N
STR23SE/STR53UE
KSA / KVA / KVC
500 and 630 A
45
NS630H
STR23SE/STR53UE
KSA / KVA / KVC
500 and 630 A
70
NS630L
STR23SE/STR53UE
KSA / KVA / KVC
500 and 630 A
150
45
45
70
70
70
150
150
150
45
45
70
70
70
150
150
150
45
45
50
50
50
50
50
50
NS400N
STR23SE/STR53UE
KSA / KVA / KVC
315 and 400 A
45
NS100N
TMD / STR22SE
KSA
100 A
NS400H
STR23SE/STR53UE
KSA / KVA / KVC
315 and 400 A
70
NS160N
NS400L
STR23SE/STR53UE
KSA / KVA / KVC
315 and 400 A
150
NS160N
KSA
160 A
NS100N
TMD / STR22SE
KSA
100 A
NS160H
KSA
160 A
NS100H
TMD / STR22SE
KSA
100 A
45
70
70
150
150
45
70
70
150
150
45
70
70
70
70
KSA
160 A
NS400N
STR23SE/STR53UE
KSA / KVA / KVC
315 and 400 A
45
NS400H
STR23SE/STR53UE
KSA / KVA / KVC
315 and 400 A
70
NS400L
STR23SE/STR53UE
KSA / KVA / KVC
315 and 400 A
150
45
45
70
70
70
150
150
150
45
45
70
70
70
150
150
150
45
45
50
50
50
50
50
50
43
NS250N
TMD / STR22SE
KSA / KVA / KVC
200 and 250 A
36
NS250H
TMD / STR22SE
KSA / KVA / KVC
200 and 250 A
70
NS250L
TMD / STR22SE
KSA / KVA / KVC
200 and 250 A
150
NS100N
TMD / STR22SE
KSA-10
100 A
NS100N
TMD / STR22SE
KSA-10
100 A
NS100H
TMD / STR22SE
KSA-10
100 A
36
36
70
150
70
70
NS250N
TMD / STR22SE
KSA / KVA / KVC
200 and 250 A
36
NS250H
TMD / STR22SE
KSA / KVA / KVC
200 and 250 A
70
NS250L
TMD / STR22SE
KSA / KVA / KVC
200 and 250 A
150
C60N
16
KLE
16 A
36
36
36
36
36
36
36
36
70
70
70
150
150
150
36
36
50
50
50
50
50
50
NS250H
TMD / STR22SE
KSA / KVA / KVC
200 and 250 A
70
C60N
25/40
KBA / KBB
25 - 40 A
NC100L
25/40
KBA / KBB
25 - 40 A
C60H
16
KLE
16 A
C60H
25/40
KBA / KBB
25 - 40 A
NC100L
25/40
KBA / KBB
25 - 40 A
NC100LH
25/40
KBA / KBB
25 - 40 A
25
36
40
40
50
70
25
36
40
40
50
70
25
36
40
40
50
50
NS250N
TMD / STR22SE
KSA / KVA / KVC
200 and 250 A
36
C60N
40 A
KN
40 A
44
36
NS250N
TMD / STR22SE
KSA / KVA / KVC
200 and 250 A
36
36
NS250H
TMD / STR22SE
KSA / KVA / KVC
200 and 250 A
70
C60N
63 A
KN
63 A
NC100L
40 A
KN
40 A
NC100L
63 A
KN
63 A
C60H
40 A
KN
40 A
C60H
63 A
KN
63 A
NC100L
40 A
KN
40 A
NC100L
63 A
KN
63 A
NC100LH
40 A
KN
40 A
NC100LH
63 A
KN
63 A
25
36
36
40
30
50
50
70
70
25
36
36
40
30
50
50
70
70
25
36
36
40
30
50
50
50
50
NS160N
TMD / STR22SE
KSA
160 A
36
C60N
16
KLE
16 A
NS160H
TMD / STR22SE
KSA
160 A
70
C60N
25/40
KBA / KBB
25 - 40 A
NC100L
25/40
KBA / KBB
25 - 40A
C60H
16
KLE
16 A
C60H
25/40
KBA / KBB
25 - 40 A
NC100L
25/40
KBA / KBB
25 - 40 A
NC100LH
25/40
KBA / KBB
25 - 40 A
25
36
40
40
50
70
25
36
40
40
50
70
25
36
40
40
50
50
NS160N
TMD / STR22SE
KSA
160 A
36
C60N
40 A
KN
40 A
NS160H
TMD / STR22SE
KSA
160 A
70
C60N
63 A
KN
63 A
NC100L
40 A
KN
40 A
NC100L
63 A
KN
63 A
C60H
40 A
KN
40 A
C60H
63 A
KN
63 A
NC100L
40 A
KN
40 A
NC100L
63 A
KN
63 A
NC100LH
40 A
KN
40 A
NC100LH
63 A
KN
63 A
25
36
36
40
40
50
50
70
70
25
36
36
40
40
50
50
70
70
25
36
36
40
40
50
50
50
50
45
Adresse postale
38050 Grenoble cedex 09
France
Schneider Electric SA
As standards, specifications and designs change from time to time, please ask for confirmation
of the information given in this publication.
This document has been pinted on ecological paper.
http://www.schneiderelectric.com
DBPT 118GUI/E
Print : LIPS
01-98