Trio
Trio
Trio
2903159
https://www.phoenixcontact.com/de/produkte/2903159
Please be informed that the data shown in this PDF document is generated from our Online Catalog. Please find the complete data in the user
documentation. Our General Terms of Use for Downloads are valid.
Primary-switched TRIO power supply for DIN rail mounting, input: 1-phase, output: 48 V DC / 5
A, dynamic boost, tool-free fast connection technology for solid and stranded conductors with
ferrule
Product Description
TRIO POWER power supplies with standard functionality
The TRIO POWER power supply range with push-in connection has been perfected for use in machine building. All functions and the space-saving
design of the single and three-phase modules are optimally tailored to the stringent requirements. Under challenging ambient conditions, the power
supply units, which feature an extremely robust electrical and mechanical design, ensure the reliable supply of all loads.
Your advantages
• Save time and costs, thanks to the Push-in connection and narrow design
• Increase system availability, thanks to dynamic boost with 150% of the nominal current for five seconds
• Maximum flexibility due to the wide temperature range from -25°C to +70°C and device startup at -40°C
• Electrically robust, thanks to high electric strength
• Mechanically robust, thanks to high vibration and shock resistance
Commercial Data
Item number 2903159
Packing unit 1 pc
Minimum order quantity 1 pc
Sales Key H1 - Stromversorgungen
Product Key CMPO14
Catalog Page Page 261 (C-4-2019)
GTIN 4055626255422
Weight per Piece (including packing) 1.165 g
Weight per Piece (excluding packing) 914 g
Customs tariff number 85044083
Country of origin CN
Technical Data
Input data
AC operation
Network type Star network
Nominal input voltage range 100 V AC ... 240 V AC
Input voltage range 100 V AC ... 240 V AC -15 % ... +10 %
Electric strength, max. ≤ 300 V AC 15 s
Typical national grid voltage 120 V AC
230 V AC
Voltage type of supply voltage AC/DC
2
Inrush current integral (I t) < 0.3 A2s
Inrush current limitation 15 A (after 1 ms)
AC frequency range 50 Hz ... 60 Hz ±10 %
Frequency range (fN) 50 Hz ... 60 Hz ±5 Hz
Mains buffering time typ. 15 ms (120 V AC)
typ. 15 ms (230 V AC)
Current consumption 2.9 A (100 V AC)
2.3 A (120 V AC)
1.2 A (230 V AC)
1.2 A (240 V AC)
Nominal power consumption 285.7 VA
Power factor (cos phi) 0.91
Input fuse 6.3 A (internal (device protection))
Recommended breaker for input protection 6 A ... 16 A (Characteristics B, C, D, K)
Discharge current to PE < 3.5 mA
< 1.7 mA (264 V AC, 60 Hz)
POWER factor > 0.9 (120 V AC)
> 0.9 (230 V AC)
DC operation
Nominal input voltage range 110 V DC ... 250 V DC
Input voltage range 110 V DC ... 250 V DC ±10 %
Extended input voltage range in operation > 88 V DC (Derating <99 V DC: 2 %/V)
Derating < 99 V DC (2 %/V)
Switch-on voltage 90 V DC
Shut-down voltage 70 V DC
Voltage type of supply voltage AC/DC
Mains buffering time > 20 ms (230 V AC)
Current consumption 2.5 A (110 V DC)
1.1 A (250 V DC)
Output data
Signal: DC OK
Continuous load current 100 mA
Connection data
Input
Connection method Push-in connection
Conductor cross section solid min. 0.2 mm²
Conductor cross section solid max. 4 mm²
Conductor cross section flexible min. 0.2 mm²
Conductor cross section flexible max. 2.5 mm²
Output
Connection method Push-in connection
Conductor cross section solid min. 0.2 mm²
Conductor cross section solid max. 4 mm²
Conductor cross section flexible min. 0.2 mm²
Conductor cross section flexible max. 2.5 mm²
Single conductor/terminal point, stranded, with ferrule, min. 0.2 mm²
Single conductor/terminal point, stranded, with ferrule, max. 2.5 mm²
Conductor cross section AWG min. 24
Conductor cross section AWG max. 12
Stripping length 8 mm
Signal
Connection method Push-in connection
Conductor cross section solid min. 0.2 mm²
Conductor cross section solid max. 1.5 mm²
Conductor cross section flexible min. 0.2 mm²
Conductor cross section flexible max. 1.5 mm²
Single conductor/terminal point, stranded, with ferrule, min. 0.2 mm²
Single conductor/terminal point, stranded, with ferrule, max. 1.5 mm²
Conductor cross section AWG min. 24
Conductor cross section AWG max. 16
Stripping length 8 mm
LED signaling
Types of signaling LED
Floating signal contact
Electrical properties
Number of phases 1.00
Insulation voltage input/output 3 kV AC (type test)
1.5 kV AC (routine test)
Product properties
Product type Power supply
Product family TRIO POWER
MTBF (IEC 61709, SN 29500) > 2000000 h (25 °C)
> 1200000 h (40 °C)
> 620000 h (60 °C)
Insulation characteristics
Protection class I (in closed control cabinet)
Degree of pollution 2
Dimensions
Width 42 mm
Height 130 mm
Depth 160 mm
Installation dimensions
Installation distance right/left 0 mm / 0 mm
Installation distance top/bottom 50 mm / 50 mm
Mounting
Mounting type DIN rail mounting
Assembly instructions alignable: horizontally 0 mm (≤ 40 °C) 10 mm (≤ 70 °C), vertically
50 mm
Mounting position horizontal DIN rail NS 35, EN 60715
With protective coating No
Material specifications
Flammability rating according to UL 94 (housing / terminal V0
blocks)
Housing material Metal
Type of housing Aluminum (AlMg3)
Hood version Polycarbonate
Ambient conditions
Degree of protection IP20
Ambient temperature (operation) -25 °C ... 70 °C (> 60 °C Derating: 2,5 %/K)
Ambient temperature (storage/transport) -40 °C ... 85 °C
Ambient temperature (start-up type tested) -40 °C
Maximum altitude ≤ 5000 m (> 2000 m, Derating: 10 %/1000 m)
Climatic class 3K3 (in acc. with EN 60721)
Max. permissible relative humidity (operation) ≤ 95 % (at 25 °C, non-condensing)
Shock 18 ms, 30g, in each space direction (according to IEC 60068-2-
27)
Overvoltage category
EN 60950-1 II
EN 62477-1 III
Approval data
UL approvals UL Listed UL 508
UL/C-UL Recognized UL 60950-1
UL ANSI/ISA-12.12.01 Class I, Division 2, Groups A, B, C, D
(Hazardous Location)
Conformity/Approvals
SIL in accordance with IEC 61508 0
EMC data
Low Voltage Directive Conformance with Low Voltage Directive 2014/35/EC
Electromagnetic compatibility Conformance with EMC Directive 2014/30/EU
EMC requirements for noise emission EN 61000-6-3
EN 61000-6-4
EMC requirements for noise immunity EN 61000-6-1
EN 61000-6-2
Conducted noise emission EN 55016
EN 61000-6-3 (Class B)
Interference emission Interference emission in accordance with EN 61000-6-3
(residential and commercial) and EN 61000-6-4 (industrial)
Noise emission EN 55011 (EN 55022)
Noise emission EN 55016
EN 61000-6-3 (Class B)
Noise immunity Immunity in accordance with EN 61000-6-1 (residential),
EN 61000-6-2 (industrial)
Harmonic currents
Frequency range Class A
Flicker
Electrostatic discharge
Standards/regulations EN 61000-4-2
Electrostatic discharge
Contact discharge 6 kV (Test Level 4)
Discharge in air 8 kV (Test Level 4)
Comments Criterion A
Electromagnetic HF field
Standards/regulations EN 61000-4-3
Electromagnetic HF field
Frequency range 80 MHz ... 1 GHz
Test field strength 10 V/m (Test Level 3)
Frequency range 1 GHz ... 2 GHz
Test field strength 10 V/m (Test Level 3)
Frequency range 2 GHz ... 6 GHz
Test field strength 10 V/m (Test Level 3)
Comments Criterion A
Conducted interference
Standards/regulations EN 61000-4-6
Conducted interference
I/O/S asymmetrical
Frequency range 0.15 MHz ... 80 MHz
Comments Criterion A
Voltage 10 V (Test Level 3)
Voltage dips
Standards/regulations EN 61000-4-11
Voltage 230 V AC
Frequency 50 Hz
Voltage dip 70 %
Number of periods 25 periods
Additional text Test Level 2
Comments Criterion A
Voltage dip 40 %
Number of periods 10 periods
Additional text Test Level 2
Comments Criterion A
Voltage dip 0%
Number of periods 1 period
Additional text Test Level 2
Comments Criterion A
Emitted interference
Standards/regulations EN 61000-6-3
Radio interference voltage in acc. with EN 55011 EN 55011 (EN 55022) Class B, area of application: Industry and
residential
Emitted radio interference in acc. with EN 55011 EN 55011 (EN 55022) Class B, area of application: Industry and
residential
Criteria
Criterion A Normal operating behavior within the specified limits.
Criterion B Temporary impairment to operational behavior that is corrected
by the device itself.
Criterion C Temporary adverse effects on the operating behavior, which the
device corrects automatically or which can be restored by
actuating the operating elements.
Drawings
Block diagram
+
L/+
active
+
N/- PFC -
-
-
13
14
Approvals
cUL Recognized
Approval ID: FILE E 211944
UL Recognized
Approval ID: FILE E 211944
EAC
Approval ID: RU S-DE.BL08.W.00764
UL Listed
Approval ID: FILE E 123528
cUL Listed
Approval ID: FILE E 123528
EAC
Approval ID: RU S-DE.BL08.W.00764
cUL Listed
Approval ID: FILE E 199827
UL Listed
Approval ID: FILE E 199827
cULus Recognized
cULus Listed
cULus Listed
Classifications
ECLASS
ECLASS-9.0 27040701
ECLASS-10.0.1 27040701
ECLASS-11.0 27040701
ETIM
ETIM 8.0 EC002540
UNSPSC
UNSPSC 21.0 39121000
Accessories
2866527
https://www.phoenixcontact.com/de/produkte/2866527
2315269
https://www.phoenixcontact.com/de/produkte/2315269
VARIOFACE module, with two equipotential busbars (P1, P2) for potential
distribution, for mounting on NS 35 rails. Module width: 70.4 mm
2903798
https://www.phoenixcontact.com/de/produkte/2903798
VARIOFACE module with push-in connection and two equipotential busbars (P1,
P2) for potential distribution, for mounting on NS 35 rails. Module width: 57.1 mm
2907928
https://www.phoenixcontact.com/de/produkte/2907928
Type 2/3 surge protection, consisting of protective plug and base element with
Push-in connection. For single-phase power supply network with integrated
status indicator and remote signaling. Nominal voltage: 230 V AC/DC
2907925
https://www.phoenixcontact.com/de/produkte/2907925
Type 3 surge protection, consisting of protective plug and base element, with
integrated status indicator and remote signaling for single-phase power supply
networks. Nominal voltage: 24 V AC/DC