SM6
Modular units
Air insulated switchgear up to 36 kV
Your requirements
Safety
Operating safety through protection against electrical, mechanical and thermal effects of a fault (insulation of each compartment) All operations carried out from the front, door closed Voltage Presence Indicator System located on the front panel Position indicator linked to the devices physical position Protection in the event of internal arcing Interlocking devices Anti-reflex handles
Reliability
Type-tested solution which complies with the IEC62271-200 standard Design by the most accurate three-dimensional computer techniques Manufacturing & Testing according to ISO 9001:2000 quality standard
Simplicity
Easy installation - All cubicles with the same engineering dimensions On-site information retrieval Possibility of remote management Maintenance with power on (LSC2A), very simple Compartmentalization of MV parts (insulated partitions)
Our solutions
Schneider Electric has developed protection, monitoring and control solutions specifically dedicated to Medium Voltage networks for over 40 years. SM6 switchgear has been specifically designed on the basis of that extensive experience. It also incorporates some very new solutions, giving the best in terms of continuity of service and operators safety.
PE57150
A comprehensive solution
SM6 switchgear is fully compatible with PowerMeter metering units. Sepam multi-function protection relays - Protection - Measurements and diagnosis. VIP protection self powered relay for protection. SM6 swithchboards can thus be easily integrated into any monitoring and control system. - Local & remote indication and operation.
PM103193
SM6, a truly professional solution! More than 1,100,000 cubicles installed world-wide.
SM6
General contents
Presentation
General characteristics
11
47
Connections
83
Installation
91
101
AMTED398078EN
AMTED398078EN
Presentation
Contents
The experience of a world leader The ranges advantages Protecting the environment A full range of services The references of a leader Quality assurance
4 5 6 7 8 9
AMTED398078EN
Presentation
The Schneider Electric experiences extends over forty years in factorybuilt cubicles and over thirty years in SF6 breaking technology for Medium Voltage switchgear. This experience means that today Schneider Electric can propose a complementary range: vacuum type circuit breaker cubicles up to 24 kV and standard or enhanced internal arc withstand cubicles to reinforce the safety of people according to the IEC standard. This gives you the advantage of unique experience, that of a world leader, with over 2,500 000 SF6 Medium Voltage units installed throughout the world. Putting this experience at your service and remaining attentive to your requirements is the spirit of active partnership that we want to develop in offering you the SM6. The modular SM6 is a range of harmonised cubicles equipped with SF6 or vacuum breaking technology switchgear with 30 years life span. These cubicles allow you to produce all your Medium Voltage substation requirements up to 36 kV by superposing their various functions.The result of in-depth analysis of your requirements, both now and in the future, SM6 cubicles mean that you can take advantage of all the features of both a modern and proven technology.
PM103194
1975: innovation Sulphur hexauoride (SF6) is rst used in an MV switch for an MV/LV transformer substation, with the VM6. 1989: experience Over 300,000 VM6 cubicles equipped networks throughout the world. 1991: innovation and experience Cumulated with the second generation of SM6 modular SF6 cubicles. 2012: a leading position With over 1,100,000 SM6 cubicles installed around the world, Schneider Electric consolidates its position as uncontested leader in the Medium Voltage eld.
AMTED398078EN
Presentation
Upgradability
SM6, a comprehensive range
b b b b b A comprehensive offer covering your present and future requirements A design adapted to the extension of your installations A catalogue of functions for all your applications A product designed to be in compliance with standards constraints Options to anticipate the control and monitoring of your installations.
Compactness
SM6, an optimised range
b Compact units, with low increment cubicles b Rationalised space requirement for switchboard installation b Reduction of civil works costs b Easy integration in factory-built outdoor substations for which the SM6 is particularly well designed.
Maintenance
SM6, a range with reduced maintenance
b The active parts (breaking and earthing) are integrated in an SF6-lled, sealed for life unit b The control mechanisms, are intented to function with reduced maintenance under normal operating conditions b Enhanced electrical endurance when breaking.
Ease of installation
SM6, a simple range to incorporate
b b b b Reduced dimensions and weights Only one civil works layout A solution adapted to cable connection Simplied switchboard busbar design.
AMTED398078EN
Presentation
Schneider Electric is committed to a long term environmental approach. As part of this, the SM6 has been designed to be environmentally friendly, notably in terms of the products recycleability. The materials used, both conductors and insulators, are identied in product environmental prole analysis and easily separable. It was performed in conformity with ISO 14040 Environmental management: life cycle assessment - principle and framework. At the end of its life, SM6 can be processed, recycled and its materials recovered in conformity with the draft European regulations on the end-of-life of electronic and electrical products, and in particular withoutany gas being released to the atmosphere nor any polluting uids being discharged. SM6 is compliant with the RoHS directive. RoHS restricts the use of six hazardous materials in the manufacture of various types of electronic and electrical equipment.
61016N
Non-ferrous metal
4%
10.6%
8%
15% 2% 1%
The environmental management system adopted by Schneider Electric production sites that produce the SM6 have been assessed and judged to be in conformity with requirements in the ISO 14001 standard.
MT55145
01 ISO 140
AMTED398078EN
Presentation
Schneider Electric is capable of offering a full range of services either associated or not with the supply of the SM6 unit. To improve the quality of your electrical power: b Network study, harmonics study, etc. b Reactive energy compensation b Consumption monitoring b Optimisation of your electrical power supply contracts. To accompany the purchase and installation of your SM6 equipment: b Adaptation of our equipment to provide a better response to your requirements b On site assembly, testing and commissioning of your equipment b Customised nancing solutions b Warranty extension b Operator training. To accompany your installation throughout its life and upgrading your equipment: b Upgrading your existing equipment: functional adaptation, control motorisation, renovation of protections units, etc. b On site work b Supply of replacement parts b Maintenance contracts b End of life recycling. Fore more information on all the services proposed by Schneider Electric, please contact your Schneider Electric Sales Ofce.
PE57151
61052N
AMTED398078EN
Presentation
PE57234
Asia/Middle East
b Canal Electrical Distribution Company, Egypt b General Motors Holden, Australia b Pasteur Institute, Cambodia b Tian he City, China b Sanya Airport, China b Bank of China, Beijing, Jv Yanta, China b Plaza Hotel, Jakarta, Indonesia b Bali Airport, Indonesia b Wakasa Control Center, Japan b Otaru Shopping center, Japan b New City of Muang, Thong Than, Kanjanapas, Thailand b Danang and Quinhon Airport, Vanad, Vietnam b British Embassy, Oman b KBF Palace Riyadh, Saudi Arabia b Raka Stadium, Saudi Arabia b Bilkent University, Turkey b TADCO, BABOIL development, United Arab Emirates b Melbourne Tunnel City Link, Australia b Campus KSU Qassim Riyad, Saudi Arabia
Africa
b b b b b b b b b b ONAFEX, Hilton Hotel, Algeria Yaounde University, Cameroon Karoua Airport, Cameroon Libreville Airport, Gabon Ivarto Hospital, CORIF, Madagascar Central Bank of Abuja, ADEFEMI, Nigeria OCI Dakar, Oger international, CGE, Senegal Bamburi cement Ltd, Kenya Ivory Electricity Company, Ivory Coast Exxon, New Headquarters, Angola
South America/Pacic
b b b b b b b b b b b Lamentin Airport, CCIM, Martinique Space Centre, Kourou, Guyana Mexico City Underground System, Mexico Santiago Underground System, Chile Cohiba Hotel, Havana, Cuba Iberostar Hotel, Bavaro, Dominican Republic Aluminio Argentino Saic SA, Argentina Michelin Campo Grande, Rio de Janeiro, Brazil TIM Data Center, So Paulo, Brazil Light Rio de Janeiro, Brazil Hospital Oswaldo Cruz, So Paulo, Brazil
Europe
b b b b b b b b b b b b b b b b b b Stade de France, Paris, France EDF, France Eurotunnel, France Nestl company headquarters, France TLM Terminal , Folkestone, Great Britain Zaventem Airport, Belgium Krediebank Computer Centre, Belgium Bucarest Pumping station, Romania Prague Airport, Czech Republic Philipp Morris St Petersburg, Russia Kremlin Moscow, Russia Madrid airport, Spain Dacia Renault, Romania Lafarge cement Cirkovic, Czech Republic Caterpillar St Petersburg, Russia Ikea Kazan, Russia Barajas airport, Spain Coca-cola Zurich, Switzerland
AMTED398078EN
Presentation
Quality assurance
Quality certified to ISO 9001
A major advantage
Schneider Electric has integrated a functional organisation into each of its units. The main mission of this organisation is to check the quality and the compliance with standards. This procedure is: b Uniform throughout all departments b Recognised by many customers and approved organisations. But it is above all its strict application that has enabled recognition to be obtained by an independent organisation: The French Quality Assurance Association (FQAA).
The quality system for the design and manufacture of SM6 units has been certied in conformity with the requirements of the ISO 9001: 2000 quality assurance model.
MT55054 MT55055
ISO
900 1
ISO
9002
61002N
61003N
AMTED398078EN
10
AMTED398078EN
General characteristics
Contents
Field of application Units for switching function Units for protection function Units for metering function Units for other functions Operating conditions Standards Main characteristics Factory-built cubicles description Compartments description Safety of people
By switchgear By operating mechanism safety By internal arc protection
12 14 15 18 19 20 21 22 24 26 28 28 30 31 32 32 33 34 37 38 39 39 42 42 43 44 45 46
AMTED398078EN
11
General characteristics
Field of application
The SM6 is made up of modular units containing xed, disconnectable or withdrawable metal-enclosed switchgear, using sulphur hexauoride (SF6) or vacuum: b Switch-disconnector b SF1, SFset or Evolis circuit breaker b Rollarc 400 or 400 D contactor, or vacuum contactor b Disconnector. SM6 units are used for the MV section in MV/LV transformer substations in public distribution systems and MV consumer or distribution substations up to 36 kV.
IM
CM
DM2
QM
PM
IM
Substation GAM2 QM
Other standards
MV consumer substations (MV metering) IM
MT55146
IM
DM1-D
GBC-A
QM
DM1-S
Outgoing line toward other ring substations Incoming line of the main distribution switchboard
12
AMTED398078EN
General characteristics
Field of application
GBC-B
QM QM IM
IM
GBC-B
DM1-A
Incoming line
ATS
Incoming line
Unit denitions
Below is the list of SM6 units used in MV/LV transformer substations and industrial distribution substations: b IM, IMC, IMB switch b PM fused switch b QM, QMC, QMB fuse-switch combination b CRM, CVM contactor and contactor with fuses b DM1-A, DM1-D, DM1-S single-isolation disconnectable SF6 type circuit breaker b DMV-A, DMV-D, DMV-S single-isolation vacuum type circuit breaker frontal b DMVL-A, DMVL-D single-isolation disconnectable vacuum type circuit breaker lateral b DM1-W, DM1-Z withdrawable single-isolation SF6 type circuit breaker b DM2 double-isolation disconnectable SF6 type circuit breaker b DM2-W withdrawable double-isolation SF6 type circuit breaker only for 36 kV b CM, CM2 voltage transformers b GBC-A, GBC-B current and/or voltage measurements b NSM-cables for main incoming and standby b NSM-busbars for main incoming and cables for standby b GIM intermediate bus unit b GEM extension unit b GBM connection unit b GAM2, GAM incoming cable connection unit b SM disconnector b TM MV/LV transformer unit for auxiliaries b Other units, consult us b Special function EMB busbar earthing only for 24 kV.
QM NSM-busbarsGBM SM TM
Standby source
ATS
Incoming line
AMTED398078EN
13
General characteristics
Switching
DE59671 DE59672 DE59673
page
48
IMB Switch unit with earthing disconnector right or left outgoing line 24 kV: 375 mm 36 kV: 750 mm
49
NSM-cables Cables power supply for main incoming line and standby line 24 kV: 750 mm
DE59696 DE59697
NSM-busbars Busbars power supply for main incoming line on right or left and cables for standby line 24 kV: 750 mm
50
NSM-cables Cables power supply for main incoming line and standby line 36 kV: 1500 mm
NSM-busbars Busbars power supply for main incoming line on right or left and cables for standby line 36 kV: 1500 mm
14
AMTED398078EN
General characteristics
Fuse-switch
DE59674 DE59675 DE59676
page
51
QMB Fuse-switch combination unit right or left outgoing line 24 kV: 375 mm 36 kV: 750 mm
52
SF6 circuit-breaker
DE59678 DE59679
53
DM1-A Single-isolation, disconnectable circuit breaker unit 24 kV: 750 mm 36 kV: 1000 mm
DM1-D Single-isolation, disconnectable circuit breaker unit right or left outgoing line 24 kV: 750 mm 36 kV: 1000 mm
AMTED398078EN
15
General characteristics
SF6 circuit-breaker
DE59681 DE53487 DE53490
page
54 55
DM1-W Withdrawable single-isolation circuit breaker unit 24 kV: 750 mm 36 kV: 1000 mm
DE59680
DM1-S Single-isolation, disconnectable circuit breaker unit with autonomous protection 24 kV: 750 mm
DE59691
DM1-Z Withdrawable single-isolation circuit breaker unit right outgoing line 24 kV: 750 mm
54 55
DM2 Double-isolation, disconnectable circuit breaker unit right or left outgoing line 24 kV: 750 mm 36 kV: 1500 mm
DM2-W Withdrawable double-isolation circuit breaker unit right outgoing line 36 kV: 1500 mm
Vacuum circuit-breaker
DE53491 DE53492 DE53493
56
DMV-D Single-isolation circuit breaker unit right outgoing line 24 kV: 625 mm
DMV-S Single-isolation circuit breaker unit with autonomous protection 24 kV: 625 mm
16
AMTED398078EN
General characteristics
Vacuum circuit-breaker
DE53485 DE59694
page
57
DMVL-D Single-isolation, disconnectable circuit breaker unit right outgoing line 24 kV: 750 mm
58
59
AMTED398078EN
General characteristics
DE59863
60
CM Voltage transformers for mains with earthed neutral system 24 kV: 375 mm 36 kV: 750 mm
DE53496 DE53497
DE59684
page
CM2 Voltage transformers for mains with insulated neutral system 24 kV: 500 mm 36 kV: 750 mm
61
GBC-A Current and/or voltage measurement unit right or left outgoing line 24 and 36 kV: 750 mm
18
AMTED398078EN
General characteristics
DE59686
DE53498
62
GBM Connection unit right or left outgoing line 24 kV: 375 mm 36 kV: 750 mm
DE59687 DE59688
DE59685
page
63
GAM Incoming cable-connection unit with earthing 24 kV: 500 mm 36 kV: 750 mm
DE53504
DE59689
64
DE59690
AMTED398078EN
19
General characteristics
Operating conditions
In addition to its technical characteristics, SM6 meets requirements concerning safety of life and property as well as ease of installation, operation and protecting the environment.
PE57152
SM6 units are designed for indoor installations. Their compact dimensions are: b 375 to 1500 mm width b 1600 to 2250 mm height b 840 to 1400 mm depth this makes for easy installation in small rooms or prefabricated substations. Cables are connected via the front. All control functions are centralised on a front plate, thus simplifying operation. The units may be equipped with a number of accessories (relays, toroids, instrument transformers, surge arrester, control and monitoring, etc.).
20
AMTED398078EN
General characteristics
Standards
SM6 units meet all the following standards and specications: b IEC standards b UTE standards for 24 kV b EDF specications for 24 kV.
b IEC standards 62271-200 High-voltage switchgear and controlgear - Part 200: A.C. metalenclosed switchgear and controlgear for rated voltage above 1 kV and up to and including 52 kV. High-voltage switchgear and controlgear - Part 1: Common specications. High voltage switches - Part 1: switches for rated voltages above 1 kV and less or equal to 52 kV. High-voltage switchgear and controlgear - Part 105: High voltage alternating current switch-fuse combinations. Electrical relays. High-voltage switchgear and controlgear - Part 100: High-voltage alternating current circuit breakers. High-voltage switchgear and controlgear - Part 102: High-voltage alternating current disconnectors and earthing switches. Instrument transformers - Part 1: Current transformers. Instrument transformers - Part 2: Voltage transformers. Instrument transformers - Part 8: Low Power Current Transducers. High-voltage prefabricated switchgear and controlgear assemblies Voltage presence indicating systems. High-voltage prefabricated switchgear and controlgear assemblies Voltage presence indicating systems. Consumer substation installed inside a building and fed by a second category voltage public distribution system. High voltage electrical installations requirements. High voltage switches for rated voltage above 1 kV and less than 52 kV.
62271-1 62271-103 62271-105 60255 62271-100 62271-102 60044-1 60044-2 60044-8 61958 62271-206
NFC 64.160. Alternating current disconnectors and earthing switches EDF specications for 24 kV HN 64-S-41 HN 64-S-43 A.C. metal-enclosed swichgear and controlgear for rated voltages above 1 kV and up to and including 24 kV. Electrical independent-operating mechanism for switch 24 kV - 400 A.
AMTED398078EN
21
General characteristics
Main characteristics
PE57150
The hereunder values are for working temperatures from -5C up to +40C and for a setting up at an altitude below 1000 m.
Electrical characteristics
Rated voltage Ur Ud Ud Up Up kV 50/60 Hz, 1 min (kV rms) 50/60 Hz, 1 min (kV rms) 1.2/50 s (kV peak) 1.2/50 s (kV peak) A A Ir Ik/tk (2) A kA /1 s 25 20 (3) 16 12.5 Making capacity (50 Hz) Ima kA 62.5 50 40 31.25 7.2 20 23 60 70 16 31.5 400 - 630 -1250 630 - 1250 630 - 1250 630 - 1250 400 - 630 - 1250 630 630 630 400 - 630 630 - 800 (4) 25 25 10 25 6.3 25 25 20 DM1-S DM1-Z DM2 DM2-W Vacuum circuit breaker range DMV-A, DMV-D, DMV-S DMVL-A DMVL-D NA: Non Available (1) 60 kV peak for the CRM unit (2) 3 phases (3) In 20 kA / 3 s, consult us (4) In 800 A, consult us. kA kA kA 25 20 25 630-1250 630 630 NA NA NA kA kA kA 25 25 20 25 25 630-1250 630-1250 630 1250 630 630 NA 1250 1250 NA NA NA NA NA NA 1250 20 630 630 20 20 NA 630-1250 50 630-1250 1250 12 28 32 75 (1) 85 17.5 38 45 95 110 24 50 60 125 145 36 70 80 170 195
Insulation level
Insulation Isolation Insulation Isolation
Breaking capacity
Transformer off load Cables off load Rated current Short-time withstand current
22
AMTED398078EN
General characteristics
Main characteristics
PE57150
Endurance
Units
Units IM, IMC, IMB, PM, QM (5), QMC (5), QMB (5), NSM-cables, NSM-busbars CRM Disconnector Rollarc 400 Mechanical endurance IEC 62271-103 1 000 operations class M1 IEC 62271-102 1 000 operations IEC 60470 300 000 operations 100 000 operations IEC 62271-102 1 000 operations IEC 60470 250 000 breaks at Ir IEC 60470 100 000 breaks at 320 A 300 000 breaks at 250 A 100 000 breaks at 200 A Electrical endurance IEC 62271-103 100 breaks at Ir, p.f. = 0.7, class E3
Vacuum contactor IEC 60470 2 500 000 operations 250 000 with mechanical latching SF6 circuit breaker range DM1-A, DM1-D, DM1-W, DM1-Z, DM1-S, DM2 DM2-W Disconnector SF circuit breaker IEC 62271-102 1 000 operations IEC 62271-100 10 000 operations class M2
IEC 62271-100 30 breaks at 12.5 kA for 24 kV 25 breaks at 25 kA for 24 kV 40 breaks at 16 kA for 36 kV 15 breaks at 25 kA for 36 kV 10 000 breaks at Ir, p.f. = 0.7, class E2 IEC 62271-103 100 breaks at Ir, p.f. = 0.7, class E3 IEC 62271-100 10 000 breaks at Ir, p.f. = 0.7, class E2
Vacuum circuit breaker range DMV-A, DMV-D, DMV-S Switch IEC 62271-103 1 000 operations class M1 IEC 62271-100 10 000 operations class M2 IEC 62271-102 1 000 operations IEC 62271-100 10 000 operations class M2 IEC 62271-100 10 000 breaks at Ir, p.f. = 0.7, class E2
(5) As per recommendation IEC 62271-105, three breakings at p.f. = 0.2 800 A under 36 kV; 1400 A under 24 kV; 1730 A under 12 kV; 2600 A under 5.5 kV.
Internal arc withstand (in accordance with IEC 62271-200): b SM6 24 kV: v 12.5 kA 1 s, IAC: A-FL v 16 kA 1 s, IAC: A-FLR & IAC: A-FL v 20 kA 1 s, IAC: A-FLR & IAC: A-FL b SM6 36 kV: v 16 kA 1 s, IAC: A-FL. Protection index: b Classes: PI (insulating partition) b Loss of service continuity classes: LSC2A b Units in switchboard: IP3X b Between compartments: IP2X for 24 kV, IP2XC for 36 kV b Cubicle: IK08 for 24 kV, IK07 for 36 kV. Electro-magnetic compatibility: b Relays: 4 kV withstand capacity, as per recommendation IEC 60801.4 b Compartments: v electrical eld: - 40 dB attenuation at 100 MHz - 20 dB attenuation at 200 MHz v magnetic eld: 20 dB attenuation below 30 MHz. Temperatures: The cubicles must be stored and installed in a dry area free from dust and with limited temperature variations. b For stocking: from 40C to +70C b For working: from 5C to +40C b Other temperatures, consult us.
AMTED398078EN
23
General characteristics
DE58646
DE58647
24
AMTED398078EN
General characteristics
DE58648
2 1
5 4
1 switchgear: load break switch and earthing switch(es), in enclosure lled with SF6 and satisfying and one vacuum circuit breaker, sealed pressure system requirements. 2 busbars: all in the same horizontal plane, thus enabling later switchboard
extensions and connection to existing equipment.
3 connection and switchgear: accessible through front, connection to the downstream terminals of the circuit breaker. b Evolis: device associated with an electronic relay and standard sensors (with or without auxiliary source). 4 operating mechanism: contains the elements used to operate the disconnector(s), the circuit breaker and the earthing switch and actuate the corresponding indications. 5 low voltage: installation of compact relay devices (VIP) and test terminal boxes.
If more space is required, an additional enclosure may be added on top of the cubicle. Options: please, refer to the chapter Characteristics of the functional units.
DE58649
3 connection and switchgear: accessible through front, connection to the downstream terminals of the circuit breaker. b Evolis: device associated with an electronic relay and standard sensors (with or without auxiliary source). 4 operating mechanism: contains the elements used to operate the disconnector(s), the circuit breaker and the earthing switch and actuate the corresponding indications. 5 low voltage: installation of compact relay devices (VIP) and test terminal boxes.
If more space is required, an additional enclosure may be added on top of the cubicle. Options: please, refer to the chapter Characteristics of the functional units.
Contactor cubicles
DE58650
1 switchgear: disconnector and earthing switch and contactor in enclosures lled with SF6 and satisfying sealed pressure system requirements. 2 1 2 busbars: all in the same horizontal plane, thus enabling later switchboard 5 4
extensions and connection to existing equipment.
3 connection and switchgear: accessible through front. This compartment is also equipped with an earthing switch downstream. The contactor may be equipped with fuses. 4 types may be used: b R400 with magnetic holding b R400D with mechanical latching b Vacuum with magnetic holding b Vacuum with mechanical latching. 4 operating mechanism: contains the elements used to operate the disconnector(s), the contactor and the earthing switch and actuate the corresponding indications.
5 low voltage: installation of compact relay devices and test terminal boxes.
With basic equipment, an additional enclosure is added on top of the cubicle. Options: please, refer to the chapter Characteristics of the functional units.
AMTED398078EN
25
General characteristics
Compartments description
DE53507
61007N
Busbar compartment
The three insulated busbars are parallel-mounted. Connection is made to the upper pads of the enclosure using a eld distributor with integrated captive screws. Ratings 400 (for 24 kV only) - 630 - 1250 A.
DE53508
61006N
Switch compartment
This compartment is separated from the busbar compartment and the connection compartment by the enclosure surrounding the switch, the disconnector and the earthing switch.
DE57172
See in fonctional units characteristics chapter for each unit allowable section. The earthing switch must be closed before the cubicle may be accessed. The reduced depth of the cubicle makes for easy connection of all phases. A stud incorporated in the eld distributor makes it possible to position and secure the cable-end lug with a single hand.
DE53510
26
AMTED398078EN
General characteristics
Compartments description
DE57173
PE57230
Operating-mechanism cover
These covers contain the various operating functions for the: b switch and earthing switch b disconnector(s) b circuit breaker b contactor and the voltage presence indicator. The operating-mechanism cover may be accessed with the cables and busbars energised and without isolating the substation. It also enables easy installation of padlocks, locks and standard LV accessories (auxiliary contacts, trip units, motors, etc.).
C B A
A - LV cover h = 2250 mm
PE58270
1500 mm 1615 mm
AMTED398078EN
27
General characteristics
Safety of people
By switchgear
61010N
Switch-disconnector for 24 kV
PE57226
Switch-disconnector for 36 kV
Closed position
Open position
Earth position
b Insensitivity to the environment v parts are designed in order to obtain optimum electrical eld distribution. v the metallic structure of cubicles is designed to withstand and aggressive environment and to make it impossible to access any energised part when in operation.
61011N
Rollarc contactor
Contacts closed
Arcing period
Contacts open
28
AMTED398078EN
General characteristics
Safety of people
By switchgear
61012N
61058N
Contacts closed
Precompression
Arcing period
Contacts open
PE50798
AMTED398078EN
29
General characteristics
Safety of people
By operating mechanism safety
PE57230
PE57231
PE57166
PE56366
30
AMTED398078EN
General characteristics
Safety of people
By internal arc protection
Standard IEC 62271-200 appendix A indicates a method for testing switchgear in metal enclosures under internal arc conditions. The aim of this test is to show that an operator situated in front of a switchboard would be protected against the effects of an internal fault.
To enhance the safety of people, it is desirable to provide as high a degree of protection as possible by evacuating the effects of internal arc using: b Evacuation systems which direct gases towards the top or the bottom of the switchboard enabling over pressure to be limited in the case of an internal fault in the compartments b Channelling and evacuating hot gases towards an external area, which is not hazardous for the operator b Materials which are non-inammable in the cubicles b Reinforced panels.
Consequently:
The SM6 is designed to offer a good level of safety b Control of the architecture: v compartment type enclosure.
DE59732
b Technological control: v electrotechnical: modelling of electrical elds, v mechanical: parts produced using CAD systems. b Use of reliable components: v choice of materials, v earthing switch with closing capacity. b v v v
Example of installation of an SM6 switchboard installed against the wall downwards exhaust 12.5 kA 1 s and 16 kA 1 s, IAC: A-FL: 3-sides internal arc protection
Devices for total operating safety: voltage presence indicator on the front face, natural reliable interlocking, locking using keys or padlocks.
3 versions are available for SM6 24 kV: 12.5 kA 1 s, IAC: A-FL 16 kA 1 s, IAC: A-FLR & IAC: A-FL 20 kA 1 s, IAC: A-FLR & IAC: A-FL
Example of installation of an SM6 24 kV switchboard installed in the middle of a room downwards exhaust 16 kA 1 s, IAC: A-FLR: 4-sides internal arc protection
SM6 proposes several options to install a standard internal arc withstand switchboard
b 3-sides internal arc protection IAC: A-FL, 12,5 kA 1 s and 16 kA 1 s for 24 kV and 16 kA 1 s for 36 kV. SM6 switchboard positioned against the wall, access to the rear of the cubicles is impossible, internal arc protection on three sides is sufcient. b 4-sides internal arc protection IAC: A-FLR, 16 kA 1 s and 20 kA 1 s for 24 kV. For SM6 switchboards installed in the middle of a room, 4-sides internal arc protection is necessary in order to protect an operator moving around the switchboard. b Choice of exhaust: (Installation requirements manual to be considered) v downwards exhaust Civil engineering with an adequate volume is necessary. v upwards exhaust for 24 kV A ceiling height greater or equal than 2 150 mm is necessary, duct at the right or left side of the cubicle (not supplied).
DE57174
Example of installation of an SM6 24 kV switchboard installed in the middle of a room upwards exhaust 16 kA 1 s and 20 kA 1 s, IAC: A-FLR: 4-sides internal arc protection
AMTED398078EN
31
General characteristics
PE15074
Control command
PE15078
32
AMTED398078EN
General characteristics
PE56311
PE56421
PE56422
Polarized connectors
PE57787
Various combinations of voltage detection are possible: b 3 Ph-N and residual voltage: V1 + V2 + V3 + V0 b 3 Ph-N or Ph-Ph voltage: V1 + V2 + V3 or U12 + U13 + U23 b 1 Ph-N or Ph-Ph or residual voltage: V1, V2, V3, U12, U13, U23, V0. VD23 can display the MV network voltage (in % of service voltage), activate the relay output R1 to monitor a loss of voltage on 1 phase at least and active the relay output R2 to monitor a presence of voltage on 1 phase at least. b Auxilary power supply: from 24 to 48 Vdc b Assembly: compact DIN format, mounted in the same place as fault passage indicator (format DIN, integrated in switchgear), terminal connexion tted with VPIS-Voltage Output b Compatible with all neutral earthing systems.
AMTED398078EN
33
General characteristics
DE40552EN
Easergy T200 automation systems are factory predened. No on-site programming is required. b The automation systems can be switched on and off from the local operator panel and disabled using the congurator.
Voltage drop
b Switches can be controlled manually in the following circumstances: v automation system switched off v switch in local mode.
Sectionaliser (SEC)
Time b Congurable parameters: v Number of faults: from 1 to 4 v Execution time: from 20 s to 4 mins congurable in 5 s steps v Automation system valid/invalid.
DE59320EN
The sectionaliser automation system opens the switch after a predened number of faults (1 to 4) during the voltage dip in the reclosing cycle of the top circuit breaker. b The automation system counts the number of times a fault current followed by a voltage loss is detected. It sends an open order if: v the switch is closed v the fault has disappeared v the MV supply is absent. b The automation system is reset at the end of the execution time delay.
SW1 voltage
T1 TR
SW1
SW2
Network ATS - Semi-Auto Mode (without paralleling upon automatic return) TR: switch response time Vn O C O C O T1 TR SW1 T2 SW1 voltage
Operating modes
The operating mode is selected from the T200 Web server.
TR
TR
SW2
Mode SW1VSW2 or SW2VSW1 (or SWVSWG if Generator ATS): Automatic transfer system executes only one changeover from the priority channel to the backup channel. Automatic transfer system then remains on that channel. Semi-Auto mode SW1XVSW2 (or SWXVSWG if Generator ATS): In the event of a voltage loss on the active channel, automatic transfer system switches to the other channel after a time delay T1. Automatic transfer system executes no return, except in case of voltage loss on the new active channel. Auto SW1 or Auto SW2 mode (or Auto SW if Generator ATS): After a changeover, return to the priority channel occurs if the MV voltage on that channel is restored. The channel that has priority can be dened according to the state of a dedicated digital input.
Tg2
Network ATS - Auto Mode SW1 (with paralleling upon automatic return) TR: switch response time
DE59321EN
Vn 0 1 0 Vg 0 C O C O C O
SW1 voltage
T1
GE Command Tg1
6s
GE voltage
Changeover sequences:
Network ATS: in the event of voltage loss on the normal channel, changeover involves opening the normal channel after time delay T1 and then closing the backup channel. Note: in Auto mode, the sequence of return to the normal channel depends on conguration of the Paralleling upon auto return option (see below). Generator ATS: in the event of voltage loss on the network channel, changeover involves sending the order for opening the network channel and at the same time the Generator start-up order, after time delay T1. The remainder of the changeover sequence depends on the management of Generator channel closing (congurable option): b Case of Generator channel closing after start-up order: After the Generator start-up order, the closing order is given to the Generator channel, without waiting until the Generator is actually started. b Case of Generator closing after Generator power on: The Generator channel closing order is sent only when Generator voltage is detected.
TR
TR
SW
TR TR
T2 TR T2 TR
SWG
SWG
Generator ATS - Auto SW mode (Without paralleling upon Auto return) TR: Switch response time Tg1: Generator starting time (maximum 60 s) Tg2: Generator stopping time Case : Generator channel closing after Generator power on (congurable option) Case : Generator channel closing after Generator start-up command (congurable option)
34
AMTED398078EN
General characteristics
Congurable parameters: b Automatic transfer system ON/OFF b Operating mode: Semi-Auto, Auto SW1, Auto SW2, SW1 > SW2, SW2 > SW1 b T1: 0 ms to 2 min. in increments of 100 ms b T2: 0 s to 30 min. in increments of 5 s b Disabling/enabling transfer upon fault detection: b Choice of voltage presence detection: DI4 or VD23 b Channel connected to generator: SW1 or SW2 b Type of automatic transfer system: Network ATS or Generator ATS b Manual control enabled/disabled if ATS in operation b Paralleling enabled/disabled in auto and/or manual mode b Choice of type of changeover to Generator: immediately or after detection of Generator power on
Changeover conditions
Changeover takes place if the following conditions are met: b Automatic transfer system in operation b SW1 open and SW2 closed or SW1 closed and SW2 open b Absence of fault current on the two channels (only if locking by fault detection option activated) b Transfer locking absent b Earthing switch absent on the two channels b MV voltage absent on the active channel b MV voltage present on the other channel. Return to the main channel for the Auto modes occurs if: b The priority channel is open b The MV voltage on the priority channel is present during time delay T2.
DE59175
DI 1 DI 2 Priority channel Genset voltage presence Parallel connection input Genset forcing The DIs can be assigned for ATS automation (congurable options) DI 3 DI 4 DI 5 DI 6
1 2 3 4 5 6 7 8 9 10 11 12
DE56806
A dedicated digital input allows changeover to be locked if a problem occurs on one of the devices related to the changeover. This input is generally connected to the downstream circuit breaker. Local and remote controls are no longer possible in this case.
DE59173
b Upon transfer to the Generator, if the latter doesnt start, the automatic transfer system waits for a period of 60 s at most before stopping changeover, then: v in SW > SWG mode: the automatic transfer system is locked and must be reset (on the Control panel) to restart the device. v in SW <> SWG mode or in Auto mode: the automatic transfer system remains operational. If voltage returns to the network channel, the automatic transfer system requests return to the network channel.
1 2 3 4 +5 6
b When the automatic transfer system is congured with auto return on the network channel, Generator stoppage is requested 6 s after the changeover sequence is completed.
Lock connection (J1 terminal block on the 4-ways interface or J9 on the 2-ways interface)
AMTED398078EN
35
General characteristics
DE56655
SW1
SW3
SW2
The BTA (Bus Tie Automatism) is an automation system for switching sources between two incoming lines (SW1 and SW2) and a busbar coupling switch (SW3). It must be used in conjunction with VD23 type voltage presence detectors and the fault current detection function on the busbar incoming lines.
Operating mode
Normal position
SW1
SW3
SW2
Two operating modes can be congured: b Standard mode: If the voltage is lost on one busbar, the automation system opens the incoming line (SW1 or SW2) and closes the coupling switch SW3. Coupling is conditional upon the absence of a fault current on the main source. b Interlock on loss of voltage after switching mode: After execution of the automation system in standard mode, the voltage presence is checked for a congurable period. If the voltage is lost during this period, the coupling switch SW3 is opened and the automation system interlocked.
Coupling sequence
b Coupling takes place if the following conditions are met: v the automation system is switched on v the switches on incoming channels SW1 and SW2 are closed v the earthing switches SW1, SW2 and SW3 are open v there is no voltage on an incoming line SW1 or SW2 v there is no fault current detection on SW1 and SW2 v there is no transfer interlock v voltage is present on the other incoming line. b The coupling sequence in standard mode is as follows: v opening of the de-energised incoming line switch after a delay T1 v closing of the coupling switch SW3. b The coupling sequence in Interlock on loss of voltage after coupling mode i s completed as follows: v monitoring of the voltage stability for a delay T3 v opening of the coupling switch SW3 if this condition is not met v locking of BTA automation system. b The system returns to standard mode after coupling if: v the return to SW1 or SW2 option is activated v voltage on the channel has been normal for a delay T2 v the automation system is activated v the automation system is not locked v there is no coupling interlock.
Active coupling
DE59322EN
V2 V1 O C O C O
SW2 voltage
SW1 voltage
T1
SW1 T3 SW3 T2
Congurable parameters: b Operating mode: Standard/locking upon voltage loss b Automatic return: SW1/SW2 b Automation system: on/off b Delay before switching T1: 100 ms to 60 s in 100 ms steps b Delay before return T2: 5 s to 300 s in 1 s steps b Interlock delay on voltage loss T3: 100 ms to 3 s in 100 ms steps b Motorisation type: command time b Manual control: enabled/disabled in local and remote modes if automation system in operation b Paralleling: enabled/disabled in auto and (or) manual modes b Transfer locking upon fault detection.
Coupling interlock
A dedicated digital input allows changeover to be locked if a problem occurs on one of the devices related to the changeover. This input is generally connected to the downstream circuit breaker. Local and remote controls are no longer possible in this case. Locking the automation system The BTA automation system is locked if one of the following conditions is met during the coupling process: b Failure of a command to open or close a switch b Indication that an earthing switch has closed b Appearance of a fault current b Switch power supply fault b Appearance of the coupling interlock b Manual or remote ON/OFF command from the automation system.
36
AMTED398078EN
General characteristics
Fault indicators
Easergy MV underground network fault current passage indicators are a range of products adapted to all neutral earthing systems: insulated, impedant and direct earthing. b Easergy Flair 21D-22D-23DV, are self-powered with a liquid crystal display, with DIN dimensions for MV cubicle installation. b Easergy Flair 279 and 219, have a wall-mounted case for the MV cubicles substation or LV compartment and an external power supply which can be backed up (Li battery or LV supply + Li battery in LV compartment). b Easergy Flair 200C is a communicating Fault passage Indicator with advanced measurement functions and Modbus master port for data concentration.
PE57784
PE57922 PE57921
279 - 219
200C + compensated
Underground MV networks, isolated, impedant and solidly earthed Flush mounted Self-powered or dual power Led and LCD display + optional external light indicator Current, frequency Dry output contact Dry output contact Wall-mounted 230 Vac and / or Li battery External light indicator Wall-mounted 230 Vac and rechargeable battery External light indicator (option) Current, voltage, power Modbus, DNP3, IEC101&104, GMS, GPRS and others
Measurement Communication
PE57232
AMTED398078EN
37
General characteristics
Ammeter
b At the leading edge of technology, Amp 21D is suitable for Medium Voltage network load management. b Self-powered, it ensures a permanent display of currents. b Compact and in DIN format, it ts naturally into MV cubicles. b Cost efcient, it uses the CT optimised for Fault Passage Indicator. b Performant, it displays phase current and maximum of current.
Functions
b Display of 3 phase current: I1 , I2 , I3. Range: 3 A to 630 A b Display of 3 phase current maximeter: I1 , I2 , I3. Range: 3 to 630 A.
Display principle
b v b v v v Load curents are permanently displayed continuous scrolling of L1, then L2, then L3. Maximeter access to maximeter display by pressing a dedicated push button continuous scrolling of M1, then M2, then M3 reset of all maximeter by pressing a combination of two push buttons.
Connections, assembly
Small size enclosure b DIN format: 93 x 45 mm b Secured, extraction-proff mounting b Terminal connections.
PE57786
Technical data
Application Frequency Load current Measurement Range Amp 21D Reset of maximeter Power supply Self power Battery Auxiliary supply Display L1 L2 L3 Sensors Phase CTs Miscellaneous Test
PE57233
Minimum current Phase current Accuracy (I < 630 A) Manual from device From the current sensors
50 Hz and 60 Hz 3A 3 to 630 A (resolution 1 A) (2% + 2 digit) Yes I load 3 A No No 4 digits LCD Yes (resolution 1 A) Yes 3 split core CT Yes
DE58404
The SM6 can integrate ammeter Amp 21D on all incoming cubicles and the fuse-switch cubicles
38
AMTED398078EN
General characteristics
The Sepam range of protection and metering is designed for the operation of machines and electrical distribution networks of industrial installations and utility substations for all levels of voltage. It consists of complete, simple and reliable solutions, suited to following ve families: Sepam series 10, 20, 40, 60 and 80. A range adapted at your application
b Protection of substation (incoming, outgoing line and busbars). b Protection of transformers. b Protection of motors, and generators.
Series 10
Series 20
Protections
Current Voltage Frequency Specics b b b b b
Phase and earth fault overcurrent Breaker failure
Simplicity
Easy to install b Light, compact base unit. b Optional modules tted on a DIN rail, connected using prefabricated cords. b User friendly and powerful PC parameter and protection setting software to utilize all of Sepams possibilities. User-friendly b Intuitive User Machine Interface, with direct data access. b Local operating data in the users language.
b b
Disconnection by rate of change of frequency
Applications
Substation Busbar Transformer Motor Generator Capacitor 10A, 10B 10A, 10B S20 T20 M20 S24 B21 T24 B22
Characteristics
Logic inputs Logic outputs Temperature sensors Channel
Current Voltage LPCT (1) 4 7 0 to 10 4 to 8 0 to 8 3 I + Io 3 I + Io 3V + Vo 0 to 10 4 to 8 0 to 8
b
1 1 to 2 1 to 2
b b
b b
Other
Backup battery Front memory cartridge with settings (1) LPCT: low-power current transformer complying with standard IEC 60044-8. (2) Control matrix for simple assignment of information from the protection, control and monitoring functions. (3) Logipam ladder language (PC programming environment) to make full use of Sepam series 80 functions. (4) Standard lithium battery 1/2 AA format, 3.6 V, front face exchangeable. Lithium battery (4)
AMTED398078EN
39
General characteristics
Series 40
Series 60
Protections
Current Voltage Frequency Specics b b b b b b
Directional earth fault
b b b
Directional earth fault and phase overcurrent
b b b
b b b
Directional earth fault
b b b
Directional earth fault and phase overcurrent
Applications
Substation Busbar Transformer Motor Generator Capacitor S40 T40 M41 G40 G60 C60
0 to 28 4 to 16 0 to 16 3 I + Io 3V, 2U + Vo or Vnt
S41, S43
S42 T42
Characteristics
Logic inputs Logic outputs Temperature sensors Channel
Current Voltage LPCT (1) 0 to 10 4 to 8 0 to 16 3 I + Io 3V, 2U + Vo
b
1 to 2
b
1 to 2
b b b
b b b
Other
Backup battery Front memory cartridge with settings 48 hours Lithium battery (4)
(1) LPCT: low-power current transformer complying with standard IEC 60044-8. (2) Control matrix for simple assignment of information from the protection, control and monitoring functions. (3) Logipam ladder language (PC programming environment) to make full use of Sepam series 80 functions. (4) Standard lithium battery 1/2 AA format, 3.6 V, front face exchangeable.
40
AMTED398078EN
General characteristics
Series 80
Protections
Current Voltage Frequency Specics b b b b b b
Directional earth fault
b b b
Directional earth fault and phase overcurrent
b b b
Disconnection by rate of change of frequency
b b b
b b b
b b b
Voltage and frequency protection for 2 sets of busbars
b b b
Capacitor-bank unbalance
Applications
Substation Busbar Transformer Motor Generator Capacitor S80 B80 S81 T81 M81 S82 T82 G82 S84 B83 T87 M88 G88 M87 G87 C86
0 to 42 5 to 23 0 to 16 3 I + 2 x Io 3V + Vo 0 to 42 5 to 23 0 to 16 2 x 3 I + 2 x Io 3V + Vo 0 to 42 5 to 23 0 to 16 3 I + Io 2 x 3V + 2 x Vo 0 to 42 5 to 23 0 to 16 2 x 3 I + 2 x Io 3V + Vo
Characteristics
Logic inputs Logic outputs Temperature sensors Channel
Current Voltage LPCT (1)
b
2 to 4
b
2 to 4
b
2 to 4
b
2 to 4
b b b b
Lithium battery (4)
b b b b
Lithium battery (4)
b b b b
Lithium battery (4)
b b b b
Lithium battery (4)
Other
Backup battery Front memory cartridge with settings
(1) LPCT: low-power current transformer complying with standard IEC 60044-8. (2) Control matrix for simple assignment of information from the protection, control and monitoring functions. (3) Logipam ladder language (PC programming environment) to make full use of Sepam series 80 functions. (4) Standard lithium battery 1/2 AA format, 3.6 V, front face exchangeable.
AMTED398078EN
41
General characteristics
PE57159
Integrated in the DM1-S and DMV-S cubicles for SM6 24 kV The VIP 35 is an independent relay without an auxiliary power supply, powered by the current sensors, and actuating a Mitop release unit. VIP 35 provides protection against phase-to-phase faults and against earthing faults. Phase protection b phase protection is achieved by a denite time threshold which functions from 1.2 times the operating current (Is). Earthing protection b earthing fault protection functions with the residual current measurement taken from the sum of the secondary currents in the sensors. This is taken via a CRc, 8 A to 80 A gauge. b earthing protection is inverse denite time: its threshold and time delay can be set. Setting the VIP 35 relays Is: the phase operating current is adjusted directly in accordance with the transformer rating and the operating voltage. Io: the earth current threshold is adjusted according to the network characteristics. Setting values of the Is phase operating current for VIP 35
Operating Transformer rating (kVA) voltage (kV) 50 75 100 125 160 3 3.3 4.2 5.5 6 6.6 10 11 13.8 15 20 22 10 10 8 8* 8* 8* 8* 8* 8* 8* 8* 8* 15 15 12 8 8* 8* 8* 8* 8* 8* 8* 8* 20 18 15 12 10 10 8* 8* 8* 8* 8* 8* 25 22 18 15 12 12 8 8* 8* 8* 8* 8* 36 28 22 18 18 15 10 10 8 8* 8* 8* 200 45 36 28 22 20 18 12 12 10 8 8* 8* 250 55 45 36 28 25 22 15 15 12 10 8 8 315 68 56 45 36 36 28 20 18 15 15 10 10 400 80 70 55 45 45 36 25 22 18 18 12 12 500 115 90 70 55 55 45 30 28 22 20 15 15 630 140 115 90 68 68 56 37 36 28 25 20 18 800 170 140 115 90 80 70 55 45 36 36 25 22 1000 1250 1600 2000 2500 3150 4000 5000 6300 200 200 140 115 115 90 68 55 45 45 30 28 200 140 140 115 80 68 55 55 37 36 170 170 140 115 90 68 68 55 45 200 200 140 115 90 80 68 55 170 140 115 115 80 68 200 170 140 140 115 90 170 170 140 115 200 170 140 200 170
VIP 35
PE57160
VIP 300 LL
42
AMTED398078EN
General characteristics
Sepam series 10
AMTED398078EN
43
General characteristics
Three-phase overcurrent Zero-sequence overcurrent Directional zero-sequence current Undervoltage Overvoltage Thermal image Zero-sequence overvoltage Negative sequence overcurrent Long start-up and rotor blocking Maximum number of start-ups Single-phase undercurrent Communication
b b b b b b
(1) DT, EI, SI, VI and RI trip curves. (2) Inverse curve suited to transformer protection. (3) DT trip curve.
Current sensor for VIP 35 and VIP 300LL and Sepam series 10 for 24 kV
Type Dimensions (mm) External Internal Thickness (without fastening) 143.5 81 37.5 Weight (kg) Ratio of Class of precision transformation VIP 35 VIP 300LL Sepam 10
CRa
2.18
1/200
CRb CRc
143.5 143.5
81 81
37.5 37.5
1.26 2
2% from 10 A to 100 A On load 5.7 (cal. x 1) 1% from 100 A to 1600 A 1% from 10 A to 10 kA On load 0.67 (cal. x 4) 1% from 10 A to 11 kA On load 5.7 (cal. x 1) 1 % from 10 A to 25 kA On load 0.67 (cal. x 4) S1-S2: On load 0.6 5% from 10 A to 80 A 2.5 % from 80 A to 600 A S1-S3: 2% from 20 A to 2200 A
b b b
b b
DE58402
44
AMTED398078EN
General characteristics
Standard applications
PE88012
TLP130, TLP160, TLP190, CLP2 sensors for Sepam series 20, 40, 60, 80 protection units
LPCT sensors are voltage-output current sensors (Low Power Current Transformer) compliant with the IEC 60044-8 standard. These sensors are designed to measure rated current between 5 A and 630 A, with a ratio of 100 A / 22.5 mV. Sepam series 20, 40, 60 and 80 protection units are at the heart of the LPCT protection chain. Sepam series 20, 40, 60 and 80 performs the following functions: b acquisition of phase currents measured by the LPCT sensors b utilization of measurements by the protection functions b tripping of the breaking device in case of fault detection.
Sepam series 20
Advantages
Demanding applications
PE88011
Sepam series 40
DE58405EN
b Consistent protection chain with the same sensor measures phase currents from 5 A to 630 A b Simple to install and implement: v installation of LPCT sensors - TLP130, TLP160 and TLP190 are installed around MV cable - CLP2 is installed on the MV circuit v LPCT connected directly to Sepam series 20, 40, 60 and 80 v accessories available to test the LPCT protection chain by secondary current injection. b LPCTs range of use LPCT measuring and protection function guaranteeing the accuracy up to the short-time current. Following the range of use of LPCT: v from 5 A up to 1250 A respecting the error limits imposed by the accuracy class 0,5 v from 1250 A up to 50 kA respecting the error limits imposed by the accuracy class 5P.
5.00 4.75 4.50 4.25 4.00 3.75 3.50 3.25 3.00 2.75 2.50 2.25 2.00 1.75 1.50 1.25 1.00 0.75 0.50 0.25
Ratio error
Custom applications
PE88010
A
5 20 100 1000 1250 2000 3000 31500 40000 50000
MT11325
b Optimized integration of functions: v measurement of phase rated currents as of 25 A that is set by micro-switch v monitoring of LPCT sensor by Sepam series 20, 40, 60 and 80 (detection of phase loss).
Connections
1 LPCT sensor, equipped with a shielded cable tted with an RJ45 connector to be connected directly to the card 3 2 Sepam series 20, 40, 60 and 80 protection unit 3 Card interface that adapts the voltage delivered by the LPCT sensors, with microswitch setting of rated current. v CCA671 card for series 60 and 80 v CCA670 card for series 20 and 40.
AMTED398078EN
45
General characteristics
Backup solution for MV switchgear power needs in the event of micro outages and power interruptions. b Easy maintenance with only one battery b Remote battery monitoring b High level of insulation to protect the electronic devices in harsh MV environments b End-of-life alarm possible via Modbus communication b Compliant with standards IEC 60 255-5 (10 kV level).
PM100592
PS100 benets
Only one battery
Traditional backup power supplies require a set of 2 or 4 batteries to produce 24 V or 48 V, with complicated replacement and adjustment of the battery pack. The PS100 needs only one battery, simplifying replacement.
PS100
The battery is a standard sealed lead-acid 12 V battery with a 10-year service. It can be purchased easily, anywhere in the world.
Main features
b DIN rail mounting for easy integration in any LV cabinet or MV/LV substation b 2 power supply outputs: v 12 Vdc - 18 W continuous - 100 W 20 s (for modem, radio, RTU, etc.) v 48 Vdc or 24 Vdc - 300 W /1 minute (for switchgear operating mechanism motors) and 90 W / continuous for protection relays, electronic devices, etc. b RJ45 Modbus communication port b 2 output relays (AC supply ON, Battery ON) b Diagnosis with LEDs b 1 sealed lead-acid 12 V battery with a 10-year service life (from 7 Ah to 40 Ah) b Power supply paralleling available with a 2nd PS100 b - 40C to +70C operating temperature.
Range
b b b b PS100-48V PS100-24V Bat24AH Bat38AH 48 Vdc power supply and battery charger 24 Vdc power supply and battery charger 24 Ah long life battery 38 Ah long life battery.
46
AMTED398078EN
Contents
48 48 51 60 62 65 68 70 72 73 75 76 77 79
Operating mechanisms Auxiliaries Current transformers for 24 kV Current transformers for 36 kV Voltage transformers for 24 kV Voltage transformers for 36 kV Motors protection units Protection of transformers Interlocks
AMTED398078EN
47
IM Switch unit
DE59700 DE53518
Electrical characteristics
DE59710
kA 25
Ik/1s
DE59711
kA 62.5
Ima
20 Ir = 630 A 16
50 Ir = 630 A 40
12.5 7.2
Ur kV
31.25 7.2
Ur kV
Basic equipment:
b b b b b switch and earthing switch three-phase busbars CIT operating mechanism voltage presence indicator 150 W heating element for 36 kV b three-phase bottom busbars for outgoing lines (right or left) b one to three CTs for 24 kV b three CTs for 36 kV
Versions:
b CI2 operating mechanism b CI1 operating mechanism b in 800 A version for 24 kV, consult us b CI1 operating mechanism for 36 kV b CI1 operating mechanism
Optional accessories:
b b b b b b motor for operating mechanism auxiliary contacts key-type interlocks release units (coil) operation counter 1250 A three-phase upper busbars b b b b b b 630 A three-phase upper busbars for severe operating conditions for 24 kV visibility of main contacts pressure indicator device enlarged low-voltage control cabinet for 24 kV 50 W heating element for 24 kV cable connection by the top (no internal arc withstand if selected)
b fault indicators b Connection pads for two dry-type single-core cables for 36 kV b digital ammeter b surge arresters (for 36 kV and for 24 kV in 500 mm width cubicle) b 630 A busbars earthing switch cabinet for 24 kV (not available for internal arc IEC62271-200)
48
AMTED398078EN
NSM-cables Cables power supply for main incoming line (N) and standby line (S)
DE53559 DE58401
NSM-busbars Cables power supply for main incoming line on left (N) and busbars for standby line (S) on right
DE53561
NSM-busbars Busbars power supply for main incoming line on left (N) and cables for standby line (S) on right
Electrical characteristics
DE59212 DE59218
kA 25
Ik/1s
kA 62.5
Ima
20 Ir = 630 A 16
50 Ir = 630 A 40
12.5 7.2
Ur kV
31.25 7.2
Ur kV
Basic equipment:
b b b b b b b b switches and earthing switches three-phase busbars connection pads for dry-type cables voltage presence indicator mechanical interlocking motorised operating mechanism CI2 with open/close coils additional enclosure automatic-control equipment (T200 S)
Optional accessories:
b b b b b b b b auxiliary contacts key-type interlocks 50 W heating element control and monitoring visibility of main contacts pressure indicator device 1250 A three-phase upper busbars 630 A three-phase upper busbars for severe operating conditions
AMTED398078EN
49
NSM-cables Cables power supply for main incoming line (N) and standby line (S)
DE59706 DE59707
NSM-busbars Cables power supply for main incoming line on left (N) and busbars for standby line (S) on right
DE59708
NSM-busbars Busbars power supply for main incoming line on left (N) and cables for standby line (S) on right
Electrical characteristics
DE59720
kA 25
20
16
Ir = 630 A
12.5 36 kV
Basic equipment:
b b b b b b b b switches and earthing switches three-phase busbars 630 A connection pads for dry-type cables voltage presence indicator motorised operating mechanism CI2 with shunt trips additional enclosure automatic-control equipment 150 W heating element
Optional accessories:
b auxiliary contacts b key-type interlocks b control and monitoring
50
AMTED398078EN
Electrical characteristics
DE59712 DE59713
kA 25
Ik/1s
kA 25
Isc
20 Ir = 200 A 16 Ir = 63 A
20 Ir = 200 A 16 Ir = 63 A
Ur kV
Ur kV
Basic equipment:
b b b b b b b switch and earthing switch three-phase busbars CI1 operating mechanism voltage presence indicator equipment for three DIN striker fuses mechanical indication system for blown fuses 150 W heating element for 36 kV b three-phase bottom busbars for outgoing lines (right or left) b one to three CTs for 24 kV b three CTs for 36 kV
b connection pads for dry-type cables b downstream earthing switch 2 kA rms making capacity
Version:
b equipment for three UTE striker fuses for 24 kV b CI2 operating mechanism b CI2 operating mechanism for 36 kV
Optional accessories:
b b b b b b b b b b b b b b motor for operating mechanism auxiliary contacts key-type interlocks auxiliary contact for blown fuses DIN striker fuses release units (coil) digital ammeter 1250 A three-phase upper busbars cable connection by the top (no internal arc withstand if selected) visibility of main contacts pressure indicator device 630 A three-phase upper busbars for severe operating conditions for 24 kV enlarged low-voltage control cabinet for 24 kV 50 W heating element for 24 kV
AMTED398078EN
51
PM Fused-switch unit
DE53526
Electrical characteristics
DE59714
kA 25
20 Ir = 200 A 16 Ir = 63 A
Ur kV
Basic equipment:
b b b b b b b b switch and earthing switch three-phase busbars CIT operating mechanism voltage presence indicator connection pads for dry-type cables downstream earthing switch 2 kA rms making capacity equipment for three UTE (for 24 kV) or DIN striker fuses 150 W heating element for 36 kV
Version:
b CI1 operating mechanism b CI2 operating mechanism for 36 kV
Optional accessories:
b b b b b b b b b b b b b b motor for operating mechanism auxiliary contacts digital ammeter key-type interlocks mechanical indication system for blown fuses 1250 A three-phase upper busbars cable connection by the top (no internal arc withstand if selected) UTE (for 24 kV) or DIN striker fuses visibility of main contacts pressure indicator device 630 A three-phase upper busbars for severe operating conditions for 24 kV enlarged low-voltage control cabinet for 24 kV 50 W heating element for 24 kV Release units for 36 kV
52
AMTED398078EN
Electrical characteristics
DE59715
kA 25
20 Ir = 630 - 1250 A 16
12.5
Ur kV
Basic equipment:
b b b b b b b b b b SF1 disconnectable circuit breaker disconnector and earthing switch three-phase busbars circuit breaker operating mechanism RI disconnector operating mechanism CS voltage presence indicator three CTs auxiliary contacts on circuit breaker mechanical interlocking between circuit breaker and disconnector 150 W heating element for 36 kV b three-phase bottom busbars
b connection pads for dry-type cables b downstream earthing switch 2 kA rms making capacity at 630 A and 25 kA rms making capacity at 1250 A
Version:
b LPCT (only with Sepam series 20, 40, 60, 80) b SFset circuit breaker disconnectable (only for 400-630 A performances and 24 kV)
Optional accessories:
b cubicle: v auxiliary contacts on the disconnector v protection using Sepam programmable electronic unit v three voltage transformers v key-type interlocks v 1250 A three-phase upper busbars at Ir 630 A v cable connection by the top (no internal arc withstand if selected) v surge arresters v 630 A busbars earthing switch cabinet for 24 kV (not available for internal arc IEC62271-200) v v v v 630 A three-phase upper busbars for severe operating conditions for 24 kV enlarged low-voltage control cabinet for 24 kV 50 W heating element for 24 kV connection pads for two dry-type single-core cables for 36 kV
AMTED398078EN
53
Electrical characteristics
DE59212-Isc DE59721
kA 25
kA 25
20 Ir = 630 A 16
20 Ir = 630 16
12.5 7.2
Ur kV
12.5 7.2
Ur kV
Basic equipment:
b b b b b b b b b b b b SF1 disconnectable circuit breaker disconnector and earthing switch three-phase busbars circuit breaker operating mechanism RI disconnector operating mechanism CS auxiliary contacts on circuit breaker mechanical interlocking between circuit breaker and disconnector VIP relay three CR sensors for VIP relay protection voltage presence indicator connection pads for dry-type cables downstream earthing switch 2 kA rms making capacity b three CTs b 150 W heating element for 36 kV
Version:
b Sepam series 10 with auxiliary supply and three CR sensors
Optional accessories:
b cubicle: v three voltage transformers v key-type interlocks v 1250 A three-phase upper busbars at Ir 630 A v 630 A three-phase upper busbars for severe operating conditions for 24 kV v enlarged low-voltage control cabinet for 24 kV b v v v circuit breaker: motor for operating mechanism release units (coil) operation counter on manual operating mechanism b v v v cubicle: protection using Sepam programmable electronic unit auxiliary contacts on disconnectors 2 voltage transformers phase-to-phase or 3 voltage transformers phase-to-earth
54
AMTED398078EN
Electrical characteristics
DE59715 DE59226
kA 25
kA 25
DE59716
kA 25
20 Ir = 630 - 1250 A 16
20 Ir = 1250 A 16
20 Ir = 630 - 1250 A
16
12.5
Ur kV
Ur kV
12.5 36
Ur kV
Basic equipment:
b b b b b b b b b SF1 withdrawable circuit breaker disconnector and earthing switch three-phase busbars circuit breaker operating mechanism RI disconnector operating mechanism CS voltage presence indicator three CTs auxiliary contacts on circuit breaker 150 W heating element for 36 kV
b mechanical interlocking between circuit breaker and disconnector b earthing switch operating mechanism CC b connection pads for dry-type cables b downstream earthing switch 25 kA rms making capacity b three-phase busbars
Version:
b LPCT (only with Sepam series 20, 40 and 80)
Optional accessories:
b v v v v v v v cubicle: auxiliary contacts on the disconnector protection using Sepam programmable electronic unit key-type interlocks three voltage transformers for 24 kV connection enclosure for cabling from above for 24 kV 50 W heating element for 24 kV enlarged low-voltage control cabinet for 24 kV b circuit breaker: v motor for operating mechanism v release units (coil) v operation counter on manual operating mechanism b cubicle: v auxiliary contacts on the disconnector v key-type interlocks v protection using Sepam programmable electronic unit b circuit breaker: v motor for operating mechanism v operation counter on manual operating mechanism v opening and closing shunt trips
v 1250 A three-phase upper busbars at Ir 630 A v 630 A three-phase upper busbars for severe operating conditions for 24 kV v surge arresters (only for 630 A and 24 kV)
AMTED398078EN
55
Electrical characteristics
DE59227
kA 25
12.5
Ur kV
Basic equipment:
b b b b b b b b Evolis circuit breaker frontal switch and earthing switch for 400 - 630 A disconnector and earthing switch for 1250 A three-phase busbars circuit breaker operating mechanism P2 disconnector and switch operating mechanism CIT voltage presence indicator auxiliary contacts on circuit breaker b 3 CR sensors for VIP relay b VIP protection relay b connection pads for dry-type cables b downstream earthing switch 25 kA rms making capacity
b three CTs b Sepam series 20 programmable electronic unit b connection pads for dry-type cables b downstream earthing switch 25 kA rms making capacity
Optional accessories:
b v v v v v v v v cubicle: b circuit breaker: auxiliary contacts on the disconnector v motor for operating mechanism three voltage transformers v release units (coil) key-type interlocks v operation counter on manual operating mechanism 50 W heating element connection enclosure for cabling from above 1250 A three-phase upper busbars at Ir 630 A 630 A three-phase upper busbars for severe operating conditions enlarged low-voltage control cabinet
56
AMTED398078EN
Electrical characteristics
DE59228
kA 25
DE59717
kA 25
20
20 Ir = 630 A
16
Ir = 630 A
16
Ur kV
Ur kV
Basic equipment:
b b b b b b b b b b Evolis circuit breaker lateral disconnectable disconnector and earthing switch mechanical interlocking between circuit breaker and disconnector three-phase busbars circuit breaker operating mechanism RI disconnector operating mechanism CS voltage presence indicator auxiliary contacts on circuit breaker 3 CTs connection pads for dry-type cables
Optional accessories:
b v v v v v v v v v v cubicle: b circuit breaker: auxiliary contacts on the disconnector v motor for operating mechanism three voltage transformers v release units (coil) key-type interlocks v operation counter on manual operating mechanism 50 W heating element connection enclosure for cabling from above 1250 A three-phase upper busbars at Ir 630 A 630 A three-phase upper busbars for severe operating conditions enlarged low-voltage control cabinet Sepam relay protection surge arresters
AMTED398078EN
57
Electrical characteristics
DE59220 DE59221
kA
kA 25
Isc
10 8
20 Ir = 250 A 16
Basic equipment:
b b b b b b b b b b b b b vacuum contactor disconnector and earthing switch three-phase busbars contactor operating mechanism with magnetic holding or contactor with mechanical latching disconnector operating mechanism CS one to three current transformers auxiliary contacts on contactor connection pads for dry-type cables voltage presence indicator downstream earthing switch 2 kA rms making capacity operation counter on contactor enlarged low-voltage control cabinet mechanical interlocking between contactor and disconnector/earthing switch b equipment for three DIN striker fuses b mechanical indication system for blown fuses b auxiliary contact for blown fuses
Version:
b LPCT (only with Sepam series 20, 40, 60, 80)
Optional accessories:
b v v v v v v v cubicle: auxiliary contacts on the disconnector protection using Sepam programmable electronic unit one to three voltage transformers key-type interlocks 50 W heating element 1250 A three-phase upper busbars 630 A three-phase upper busbars for severe operating conditions
58
AMTED398078EN
Electrical characteristics
DE57175 DE59224
kA
kA 25
Isc
10 8 Ir = 400 A
20 Ir = 250 A 16
Ur 7.2 12 kV
12.5 7.2 12
Ur kV
Basic equipment:
b b b b b b b b b b b b SF6 contactor disconnector and earthing switch three-phase busbars contactor operating mechanism with magnetic holding or contactor with mechanical latching disconnector operating mechanism CS one to three current transformers auxiliary contacts on contactor connection pads for dry-type cables voltage presence indicator downstream earthing switch 2 kA rms making capacity operation counter on contactor enlarged low-voltage control cabinet b equipment for three DIN striker fuses
Optional accessories:
b v v v v v v v cubicle: auxiliary contacts on the disconnector protection using Sepam programmable electronic unit one to three voltage transformers key-type interlocks 50 W heating element 1250 A three-phase upper busbars 630 A three-phase upper busbars for severe operating conditions
AMTED398078EN
59
CM2 Voltage transformers unit for network with insulated neutral system
Electrical characteristics
DE59722
kA 25
Ik/1s
20 Ir = 50 A 16
Ur kV
Basic equipment:
b b b b b b b disconnector and earthing switch three-phase busbars operating mechanism CS LV circuit isolation switch LV fuses three 6.3 A UTE or DIN type fuses 150 W heating element for 36 kV b two voltage transformers (phase-to-phase)
Optional accessories:
b b b b b b b auxiliary contacts mechanical signalling and auxiliary contact for blown fuses 1250 A three-phase upper busbars cable connection by the top (no internal arc withstand if selected) 50 W heating element for 24 kV 630 A three-phase upper busbars for severe operating conditions for 24 kV enlarged low-voltage control cabinet for 24 kV
60
AMTED398078EN
Electrical characteristics
DE59709
kA 25
Ik/1s Ir = 1250 A
20 Ir = 630 - 1250 A 16
12.5
Ur kV
Basic equipment:
b b b b b one to three CTs for 24 kV three CTs for 36 kV connection bars three-phase busbars 150 W heating element for 36 kV
Optional accessories:
b b b b b 1250 A three-phase upper busbars at Ir 630 A for 24 kV enlarged low-voltage control cabinet for 24 kV three voltage transformers (phase-to-earth) or two voltage transformers (phase-to-phase) for 24 kV 50 W heating element for 24 kV cable connection by the top for 36 kV (no internal arc withstand if selected)
AMTED398078EN
61
Electrical characteristics
DE59709 DE59212
kA 25
Ik/1s Ir = 1250 A
kA 25
Ik/1s
DE59214
kA 25
Ik/1s
20 Ir = 630 - 1250 A 16
20 Ir = 630 A 16
20 Ir = 630 A 16
12.5
Ur kV
12.5 7.2
Ur kV
12.5 7.2
Ur kV
Basic equipment:
b connection bars b three-phase busbars for outgoing lines right or left b 150 W heating element for 36 kV b metallic envelop b three-phase busbars b metallic envelop
Optional accessories:
b 1250 A three-phase upper busbars at Ir 630 A b enlarged low-voltage control cabinet for 24 kV b cable connection by the top for 36 kV (no internal arc withstand if selected)
62
AMTED398078EN
Electrical characteristics
DE59719
kA 25
DE59709
kA 25
Ik/1s Ir = 1250 A
20
20 Ir = 630 - 1250 A 16
16
12.5 7.2
Ur kV
12.5
Ur kV
Basic equipment:
b b b b b three-phase busbars voltage presence indicator connection pads for dry-type cables connection bars 150 W heating element for 36 kV b downstream earthing switch 25 kA rms making capacity b operating mechanism CC for 24 kV b operating mechanism CS for 36 kV
Optional accessories:
b b b b b b fault indicator digital ammeter 1250 A three-phase upper busbars at Ir 630 A enlarged low-voltage control cabinet for 24 kV cable connection by the top (no internal arc withstand if selected) 50 W heating element for 24 kV b auxiliary contacts b key-type interlocks b surge arresters for 24 kV
AMTED398078EN
63
SM Disconnector unit
DE59704 DE53557
Electrical characteristics
DE59709
kA 25
Ik/1s Ir = 1250 A
DE59722
kA 25
Ik/1s
kA 25
Ik/1s
20 Ir = 630 - 1250 A 16
20 Ir = 50 A 16
20 Ir = 630 A 16
12.5
Ur kV
Ur kV
12.5 7.2
Ur kV
Basic equipment:
b b b b disconnector and earthing switch three-phase busbars operating mechanism CS 150 W heating element for 36 kV b two 6.3 A fuses, UTE (for 24 kV) or DIN type b LV circuit isolating switch b one voltage transformer (phase-to-phase) b earthing switch b connection bars three phase b operating mechanism CIT b installation on 630 A IM 375 mm or DM1-A units (not available for internal arc IEC 62271-200) b require a key-type interlocks adapted to the switchboard network
Optional accessories:
b b b b b b b auxiliary contacts key-type interlocks 1250 A three-phase upper busbars at Ir 630 A cable connection by the top (no internal arc withstand if selected) enlarged low-voltage control cabinet for 24 kV 50 W heating element for 24 kV 630 A three-phase upper busbars for severe operating conditions for 24 kV b mechanical indication system and auxiliary contacts for blown fuses b auxiliary contacts
64
AMTED398078EN
Operating mechanisms
The control devices required for the unit operating mechanisms are centralised on the front panel. The different types of operating mechanism are presented in the table opposite. Operating speeds do not depend on the operator, except for the CS.
Units
IM, IMB IMC PM QM QMC, QMB CM, CM2, CRM, CVM DM1-A, DM1-D, DM1-S, DM1-Z, DM2, DMVL-A, DMVL-D DM1-A (2), DM1-W, DM2-W DMV-A, DMV-D, DMV-S NSM-cables, NSM-busbars GAM 24 kV SM, TM, GAM 36 kV EMB
b b b
v v v b b
v v v (1) v v b b b b b b b b b b
CIT
Load-break switch Fused switch Closing Opening Hand lever Hand lever Motor Motor 1 to 2 s 1 to 2 s Remote control network management Closing Hand lever Opening Hand lever
CI1
Load-break switch Fuse switch combination Closing Opening Hand lever Push button Motor Coil 4 to 7 s 35 ms Remote control transformer protection Closing Hand lever Opening Hand lever
CI2
Load-break switch Fuse switch combination Mechanism Closing Opening charging Hand lever Push button Push button Motor Coil Coil 4 to 7 s 55 ms 35 ms Remote control network management, need of quick reconguration (generator source, loop) N/A Closing Opening Hand lever Hand lever Hand lever
CS
Disconnector Closing Hand lever N/A N/A N/A Opening Hand lever N/A N/A
AMTED398078EN
65
Operating mechanisms
61030N
61031N
61032N
66
AMTED398078EN
Operating mechanisms
Single-function operating mechanism for the SF circuit breakers 24 kV and 36 kV and Evolis 24 kV lateral
b Circuit-breaker function v independent-operation closing in two steps. First operating mechanism recharge by motor or lever, then release of the stored energy by push-button (I) or trip unit. v independent-operation opening by push-button (O) or trip units. b Auxiliary contacts v circuit breaker (4 O + 4 C), v mechanism charged (1 C). b Mechanical indications Operation counter. b Opening releases v Mitop (low energy), v shunt trip, v undervoltage. b Closing release v shunt trip b Motor option (option and installation at a later date possible). Possible combinations between opening releases SF1
Release type Mitop (low energy) Shunt trip Undervoltage Combinations 1 b 2 b b b 3 b b b b b 4 5 6
PE57163
SFset
Combinations 1 b 2 b b b 3 b 4
61035N
P2 stored energy operating mechanism for the Evolis circuit breaker 17.5 kV frontal
b Circuit-breaker function v independent-switching operating closing in two steps. First operating mechanism recharge by motor or lever, then release of the stored energy by push-button (I) or trip unit. v independent-operation opening by push-button (O) or trip units. v spring energy release. b Auxiliary contacts v circuit breaker (4 O + 4 C), v mechanism charged (1 C). b Mechanical indications Operation counter. b Opening releases v Mitop (low energy), v shunt trip, v undervoltage. b Closing release v shunt trip b Motor option (option and installation at a later date possible).
AMTED398078EN
67
Auxiliaries
61036N
Un
Power supply (V)
DC
24 200 1 to 2 (s) 4 to 7 (s) 200 35 160 250 300 300 300 48 110 125 220 (W) (VA) Operating time for CIT Charging time for CI1, CI2
AC (50 Hz)*
120 230
Motor option
200 1 to 2 (s) 4 to 7 (s)
Opening releases
Shunt trip Response time Undervoltage Pick-up Hold Response time (W) (VA) (ms) (W) (VA) (W) (VA) (ms) (W) (VA) (ms) 400 35 750
550 40
Closing release
Shunt trip Response time 750
Motor option and releases for SF6 type circuit breakers and Evolis 24 kV lateral
Operating mechanism RI may be equipped with the motor option for the recharging function.
PE57164
Un
Power supply (V) (W) (VA) (s) (W) (ms) (W) (VA) (ms) (W) (VA) (W) (VA) (ms) (W) (VA) (ms)
DC
24 300 48 110 125 220
AC (50 Hz)*
120 230
Motor option
380 15 3 30 85 45 160 280 10 55 85 180 65 65 50 55 40 550 15
Charging time
Opening releases
Mitop (low energy) Response time Shunt trip Response time Undervoltage Pick-up Hold Response time 30 180 45
Closing release
Shunt trip Response time
68
AMTED398078EN
Auxiliaries
Motor option and releases for Evolis circuit breakers 17.5 kV frontal
Charging motor and associated mechanism (P2)
Power supply Threshold Consumption Charging time Switching rate CH contact Power supply Threshold Response time to the circuit breaker at Ur (VA or W) Motor overcurrent (Vac 50/60 Hz) (Vdc) 24/30 0.85 to 1.1 Ur 180 2 to 3 Ir during 0.1 s 6 s max. 3 cycles per minute max. 10 A 240 V Direct current 0.6 A < I < 3 A 50 ms (protection relay setting) 48/60 48/60 100/130 100/125 200/240 200/250
61035N
PE57842
Open release characteristics Power supply (Vdc) 48 Consumption (W) 470 Response time (ms) 20-40
AMTED398078EN
69
b b b b b b b b b b b b b b b b b
Transformer ARJP1/N2F b characteristics according to IEC standard 60044-1 b single primary winding b double secondary winding for measurement and protection. Short-time withstand current Ith (kA)
I1n (A) Ith (kA) t (s) Measurement and protection 5A 5A 10 1.2 1 15 VA - class 0.5 2.5 VA - 5P20 20 2.4 30 3.6 50 6 75 10 100 10 150 10 200 10
61040N
Transformer ARJP1/N2F b characteristics according to IEC standard 60044-1 b single primary winding b double secondary winding for measurement and protection. Short-time withstand current Ith (kA)
I1n (A) Ith (kA) t (s) Measurement and protection 5A 5A 50 6 1 15 VA - class 0.5 2.5 VA - 5P20 100 10 150 200
61040N
Transformer ARM3/N2F b characteristics according to IEC standard 60044-1 b double primary winding b single secondary winding for measurement and protection. Short-time withstand current Ith (kA)
I1n (A) Ith (kA) t (s) Measurement and 5 A protection 1A 5A * For 5 A protection 10/20 5 1 20/40 12.5 0.8 50/100 12.5/21* 1 100/200 12.5/25* 200/400 12.5/25* 300/600 25
61041N
b characteristics according to IEC standard 60044-1 b double primary winding b double secondary winding for measurement and protection. Short-time withstand current Ith (kA)
I1n (A) Ith (kA) t (s) Measurement and protection 5A 5A 5A 50/100 14.5 1 30 VA - class 0.5 5 VA - 5P15 7.5 VA - 5P10 7.5 VA - 5P15 15 VA - 5P10 100/200 25 200/400 25 300/600 25
70
AMTED398078EN
Transformer ARJP2/N2F b characteristics according to IEC standard 60044-1 b single primary winding b double secondary winding for measurement and protection. Short-time withstand current Ith (kA)
I1n (A) Ith (kA) t (s) Measurement and protection 5A 5A 50 25 1 10 VA class 0.5 2.5 VA 5P20 15 VA class 0.5 2.5 VA 5P20 15 VA class 0.5 5 VA 5P20 15 VA class 0.5 5 VA 5P20 20 VA class 0.5 7.5 VA 5P20 100 200 400 600
61042N
Transformer ARJP3/N2F b characteristics according to IEC standard 60044-1 b single primary winding b double secondary winding for measurement and protection. Short-time withstand current Ith (kA)
I1n (A) Ith (kA) t (s) Measurement and protection Measurement and protection 1A 1A 5A 5A 1000 25 1 30 VA - class 0.5 10 VA - 5P20 30 VA - class 0.5 10 VA - 5P20 1250
PE55661
61044N
Low Power Current Transformer (LPCT) CLP2 b characteristics according to IEC standard 60044-8 b large primary current range b direct output voltage for measurement and protection b RJ45-8 pts secondary connector b insulation level 24 kV.
Minimum rated primary current Rated nominal primary current Rated extended primary current Rated nominal secondary output Accuracy class for measurement Accuracy class for protection Accuracy limit factor Rated short time thermal current Highest voltage (Um) Rated power-frequency withstand 5A 100 A 1250 A 22.5 mV 0.5 5P 400 40 kA 1 s 24 kV 50 kV
Low Power Current Transformer (LPCT) TLP130 b characteristics according to IEC standard 60044-8 b large primary current range b direct output voltage for measurement and protection b RJ45-8 pts secondary connector b insulation level 0.72 kV b internal diameter 130 mm.
Minimum rated primary current Rated nominal primary current Rated extended primary current Rated nominal secondary output Accuracy class for measurement Accuracy class for protection Accuracy limit factor Rated short time thermal current Highest voltage (Um) Rated power-frequency withstand 5A 100 A 1250 A 22.5 mV 0.5 5P 250 25 kA 1 s 0.72 kV 3 kV
PE57162
AMTED398078EN
71
PE57222
For units DM1-A, DM1-D, DM1-W, DM2, DM2-W, IMC, GBC-A, GBC-B
Transformer ARM6T/N1 or N2 b characteristics according to IEC standard 60044-1 b double primary winding b double secondary winding for measurement and protection. Short-time withstand current Ith (kA)
I1n (A) Ith (kA) t (s) Current transformer ARM6T Measurement and protection 5A 5A 50-100 16 - 20 1 7.5 VA - 15 VA - class 0.5 2.5 VA - 5 VA - 5P20 75-150 100-200 150-300 200-400 300/600 1000/1250 25 1 30 VA class 0.5 10 VA 5P20
PE57162
TLP 130
5A 1250 A 22.5 mV - 100 A 0.5 5P 250 25 kA 1 s 0.72 kV 3 kV
TLP 190
5A 2500 A 22.5 mV - 100 A 0.5 5P 400 40 kA 1 s 0.72 kV 3 kV
72
AMTED398078EN
Rated voltage (kV) Primary voltage (kV) Secondary voltage (V) Thermal power (VA) Accuracy class Rated output for single primary winding (VA) Rated output for double primary winding (VA)
61046N
PE55648
Transformer VRM3-n/S2 (phase-to-earth and protected by fuses 0.3 A) 50 or 60 Hz b characteristics according to IEC standard 60044-2.
Rated voltage (kV) Primary voltage (kV) Secondary voltage (V) First secondary Thermal power (VA) Accuracy class Rated output for single primary (VA) Second secondary Thermal power (VA) Accuracy class Rated output 12 10/3 200 0.5 30-50 100 3P 50 17.5 15/3 24 20/3
100/3 - 100/3
AMTED398078EN
73
DE53562
DE52402
DE58408
Surge arresters
For units IM500, DM1-A, DM1-W, GAM, DMV-A*, DMVL-A
In (A) Un (kV) 400/630 7.2 10 12 17.5 24
Note: the rated voltage of the surge arrester is according to units rated voltage. (*) limited up to 17.5 kV for DMV-A circuit breaker cubicles.
74
AMTED398078EN
PE57223
For units TM
Transformer VRC3/S1 (phase-to-phase) b single primary winding b single secondary
Rated voltage (kV) Primary voltage (kV) Secondary voltage (V) Thermal power (VA) 36 30 220 1000
DE58408
Surge arresters
For units IM, DM1-A, SM, GAM2
In (A) Un (kV) 630 36
AMTED398078EN
75
The current rating of fuses installed in units depends on: b motor current rating In b starting current Id b frequency of starts. The fuses rating is calculated such that a current equal to twice the starting current does not blow the fuse within period equal to the starting time. The adjacent table indicated the ratings which should be used, based on the following assumptions: b direct on-line startup b Id/In y 6 b pf = 0.8 (P y 500 kW) or 0.9 (P > 500 kW) b = 0.9 (P y 500 kW) or 0.94 (P > 500 kW). The indicated values are for Fusarc fuses (to DIN standard 43-625). Example: Consider a 950 kW motor at 5 kV.
In = P pf = 130 A
20
12
250 250 250 250 250 200 200 200 200 160 160 160 160 125 125 125 100
3.3
6.6
Id = 6 x In = 780 A Then select the next higher value, i.e. 790 A. For six 5-second starts per hour, select fuses rated 200 A.
Note: the same motor could not be protected for 12 starts per hour since the maximum service voltage for the required 250 A rated fuses is 3.3 kV.
11
5 3
250 250 200 160 160 125 125 100 100 100 80 50
10 6
250 250 200 160 160 160 125 125 100 100 100 50
30 6
250 200 200 160 160 160 125 100 100 100 80
Id = 6 x Ie
3.3 1100 942 785 6.6 628 565 502 439 377 314 251 188 126
Ie
183 157 131 105 94 84 73 63 52 42 31 21
3
250 250 200 160 160 160 125 100 100 100 100 63
3
250 200 200 160 160 160 125 100 100 100 80
6
250 250 200 160 160 160 160 125 100 100 80
Fuse selection method: b if Id 6 x Ie, use Id to select the fuses b if Id < 6 x Ie, use Ie to select the fuses.
Note: Fuses are 292 mm long (Fusarc fuses). Fuses are only for short circuit protection. For 250 A fuses, it is necessary to delay the opening of the contactor.
76
AMTED398078EN
Protection of transformers
Fuse ratings for SM6 protection units such as PM, QM, QMB and QMC depend, among other things, on the following criteria: b service voltage b transformer rating b fuse technology (manufacturer) Different types of fuses with medium loaded striker may be installed: v Solefuse fuses as per standard UTE NCF 64.210 v Fusarc CF fuses as per IEC 60.282.1 recommendation and dimensions are related to DIN 43.625 standard. For fuse-switch combination unit type QM, QMB, QMC, refer only to the selection table and reference list of fuses. For all other type of fuses, consult us. Example: for the protection of a 400 kVA transformer at 10 kV, select either Solefuse fuses rated 43 A or Fusarc CF fuses rated 50 A.
PE57161
Fuse selection table d Please consult us for overloads and operation over 40C for France Transfo oil immersed type transformers.
Type of fuse Service Transformer rating (kVA) Rated voltage 25 50 100 125 160 200 250 315 400 500 630 800 1000 1250 1600 2000 2500 voltage (kV) (kV) Solefuse (UTE NFC standards 13.100. 64.210) 5.5 6.3 16 31.5 31.5 63 63 63 63 63 7.2 10 6.3 6.3 16 16 31.5 31.5 31.5 63 63 63 63 15 6.3 6.3 16 16 16 16 16 43 43 43 43 43 63 20 6.3 6.3 6.3 6.3 16 16 16 16 43 43 43 43 43 63 24 Solefuse (general case, UTE NFC standard 13.200) 3.3 16 16 31.5 31.5 31.5 63 63 100 100 7.2 5.5 6.3 16 16 31.5 31.5 63 63 63 80 80 100 125 6.6 6.3 16 16 16 31.5 31.5 43 43 63 80 100 125 125 10 6.3 6.3 16 16 16 31.5 31.5 31.5 43 43 63 80 80 100 12 13.8 6.3 6.3 6.3 16 16 16 16 31.5 31.5 31.5 43 63 63 80 17.5 15 6.3 6.3 16 16 16 16 16 31.5 31.5 31.5 43 43 63 80 20 6.3 6.3 6.3 6.3 16 16 16 16 31.5 31.5 31.5 43 43 63 24 22 6.3 6.3 6.3 6.3 16 16 16 16 16 31.5 31.5 31.5 43 43 63 Fusarc CF and SIBA (1) (general case for QM, QMB and QMC cubicle according to IEC 62271-105) 3.3 16 25 40 50 50 80 80 100 125 125 160(1) 200(1) 7.2 5 10 16 31.5 40 40 50 63 80 80 125 125 160(1) 5.5 10 16 31.5 31.5 40 50 50 63 80 100 125 125 160(1) 160(1) 6 10 16 25 31.5 40 50 50 63 80 80 125 125 160(1) 160(1) 6.6 10 16 25 31.5 40 50 50 63 80 80 100 125 125 160(1) 10 6.3 10 16 20 25 31.5 40 50 50 63 80 80 100 100 125(1) 200(1) 12 11 6.3 10 16 20 25 25 31.5 40 50 50 63 80 100 100 125(1) 160(1) 13.8 6.3 10 16 16 20 25 31.5 31.5 40 50 50 63 80 80 100(1) 125(1) 125(1) 17.5 15 6.3 10 10 16 16 20 25 31.5 40 50 50 63 80 80 100(1) 125(1) 125(1) 20 6.3 6.3 10 10 16 16 25 25 31.5 40 40 50 50 63 80 100(1) 125(1) 24 22 6.3 6.3 10 10 10 16 20 25 25 31.5 40 40 50 50 80 80 100(1) (2) Fusarc CF for dry type transformers 30 10 10 16 20 25 31.5 31.5 50 50 63 63 36 31.5 10 10 16 20 25 25 31.5 50 50 63 63 33 6.3 10 16 20 25 25 31.5 40 50 50 63 34.5 6.3 10 16 20 25 25 31.5 40 50 50 63 Fusarc CF oil immersed type transformers (2) 30 10 10 16 20 25 31.5 31.5 40 40 50 63 36 31.5 10 10 16 20 25 31.5 31.5 40 40 50 63 33 10 10 16 20 25 25 31.5 31.5 40 40 50 34.5 10 10 16 20 25 25 31.5 31.5 40 40 50 The color code is linked to the rated voltage of the fuse Rating in A - no overload at 5C < t < 40C.
(1) SIBA fuses (2) This selection table has been prepared according to the technical characteristics of France Transfo. The characteristics of transformers and fuses may change according to manufactures and standards. AMTED398078EN
77
Protection of transformers
Fuses dimensions
Solefuse (UTE standards)
DE53563
55
(mm) 55 55 55 55
Weight (kg) 2 2 2 2
450 35 35
23
24
45
Ur (kV) 7.2 12
L (mm) 292 292 292 292 292 292 292 292 292 292 292 292 442 442 442 442 442 442 442 442 442 442 537 537 537 537 537 537 537
(mm) 86 50.5 50.5 50.5 50.5 57 57 57 78.5 78.5 78.5 78.5 50.5 50.5 50.5 50.5 57 57 57 78.5 78.5 86 50.5 50.5 57 78.5 78.5 86 86
Weight (kg) 3.3 1.2 1.2 1.2 1.2 1.5 1.5 1.5 2.8 2.8 2.8 2.8 1.6 1.6 1.6 1.6 2.2 2.2 2.2 4.1 4.1 5.3 1.8 1.8 2.6 4.7 4.7 6.4 6.4
L 33 33
23
SIBA
DE57467
45
Ur (kV) 7.2 12
(mm) 85 85 67 85 85 85 85 85
L 33 33
23 17.5 24
78
AMTED398078EN
Interlocks
Switch units
b the switch can be closed only if the earthing switch is open and the access panel is in position. b the earthing switch can be closed only if the switch is open. b the access panel for connections can be opened only if the earthing switch is closed. b the switch is locked in the open position when the access panel is removed. The earthing switch may be operated for tests.
Functional interlocks
These comply with IEC recommendation 62271-200 and EDF specication HN 64-S-41 (for 24 kV). In addition to the functional interlocks, each disconnector and switch include: b built-in padlocking capacities (padlocks not supplied) b four knock-outs that may be used for keylocks (supplied on request) for mechanism locking functions.
Circuit-breaker units
b the disconnector(s) can be closed only if the circuit breaker is open and the front panel is locked (interlock type 50). b the earth switch(es) can be closed only if the disconnector(s) is/are open. b the access panel for connections can be opened only if: v the circuit breaker is locked open, v the disconnector(s) is/are open, v the earth switch(es) is/are closed.
Note: it is possible to lock the disconnector(s) in the open position for no-load operations with the circuit breaker.
Unit interlock
Units
IM, IMB, IMC PM, QM, QMB, QMC, DM1-A, DM1-D, DM1-W, DM1-Z, DM1-S, DMV-A, DMV-D, DMV-S, DMVL-A, DMVL-D CRM, CVM NSM GAM SM DM2, DM2-W b b
Interlock
A1 C1 C4 A3 b b b A4 b A5 50 b 52 P1 b P2 P3 P5
b b b b
b b b b b
DE53565
A1 type
O
Key-type interlocks
Outgoing units
Aim: b to prevent the closing of the earthing switch on a transformer protection unit unless the LV circuit breaker is locked in open or disconnected position.
DE53566
C1 type
b to prevent the access to the transformer if the earthing switch for transformer protection has not rst been closed.
S
DE53567
C4 type
O
S O
b to prevent the closing of the earthing switch on a transformer protection unit unless the LV circuit breaker is locked in open or disconnected position. b to prevent the access to the transformer if the earthing switch for transformer protection has not rst been closed.
MT20240EN
AMTED398078EN
79
Interlocks
DE53568
A3 type
O
Ring units
Aim: b to prevent the closing of the earthing switch of a load-side cubicle unless the line-side switch is locked open.
O
DE53569
A4 type
O O
DE53570
A5 type
O
b to prevent the closing of the earthing switch of the casing unit unless the downstream and the upstream switches are locked in the open position.
S O S
DE53571
50 type
O O
Prevents b on-load switching of the disconnectors. Allows b off-load operation of the circuit breaker with the disconnectors open (double isolation). b off-load operation of the circuit breaker with the disconnector open (single isolation).
DE59203
Type 52
O O
Prevents b on-load switching of the disconnectors. Allows b off-load operation of the contactor with the disconnectors open (double isolation). b off-load operation of the contactor with the disconnector open (single isolation).
MT20240EN
80
AMTED398078EN
Interlocks
DE53572
P1 type
O X
b to prevent the closing of an earthing switch if the switch of the other unit has not been locked in the open position.
DE53573
P2 type
X O O
b to prevent on-load operation of the disconnector unless the switch is locked open b to prevent the closing of the earthing switches unless the disconnector and the switch are locked open.
DE53574
P3 type
AX O
b to prevent on-load operation of the disconnector unless the switch is locked open b to prevent the closing of the earthing switches with the unit energised, unless the disconnector and the switch are locked open b to allow off-load operation of the switch.
DE53575
P5 type
P
b to prevent the closing of the earthing switch of the incoming unit unless the disconnector and the switch is locked open.
MT20240EN
AMTED398078EN
81
82
AMTED398078EN
Connections
Contents
84 84 85 85 86 87 88 89 89 90 90
AMTED398078EN
83
Connections
PE50775
PE57840
Round connector
PE50776
Square connector
1 or 2 per phase y 400 mm2 400 < 1 y 630 mm2 per phase
Round connector
50 to 630 mm2
1 per phase
Note: b The cable end terminals, covered by a eld distributor, can be square, b PM/QM type cubicle, round end connections 30 mm max.
84
AMTED398078EN
Connections
DE58676
DE58677
630 A
IM, NSM-cables, NSM-busbars SM IMC PM, QM QMC CRM, CVM DM1-A DMVL-A DMV-S DM1-W GAM2 GAM DMV-A DM1-S 945 945 400 400 400 430 430 430 320 370 760 470 320 543
1250 A
945
320
DE58678
CRM, CVM
GAM, GAM2
DE58679 DE53581
H
H
200
200 420
275
DMV-A (1250 A)
333
330
789
145 145
445
371,5
510,5
X 313
AMTED398078EN
85
Connections
DE53585
b Through trenches: the trench depth P is given in the following table for usual dry single-core cables type (for tri-core cables consult us). b With stands: to reduce depth P or avoid trenches, by placing the units on 400 mm concrete footings. b With oor void: the trench depth is given in the following table for usual types of cables. 630 A
Cable section (mm2) All cubicles expect ... 12.5 kA/1s S < 120 330 16 kA/1s 550 550 Other cubicles DMVA 12-16 kA/1s 550 800 CVM 12.5 kA/1s 330 16 kA/1s 550 DM1A, DM1S, DM1W, DMVLA 12.5 kA/1s 16 kA/1s 550 SM, GAM 12-16 kA/1s DM1A, DMV-A, DM1-W 12-16 kA/1s
1250 A
Depth P (mm)
330 120 < S < 240 330 Opposite to Under the 550 circuit breaker: circuit breaker: 330 450
187.5
S > 400
1000
1400
630 A units
DM1-A, DM1-W For single-core cables
100
DE57179
100
100
600 740 50
600 740 50
840 740 50
600 740 50
86
AMTED398078EN
Connections
100
100
P1 P2 P2
P3
P1
600
25
25
25
IM
IM QMC
IM
IM IM
DM1
DM1
IM
Note 1: for connection with conduits, the bevel (C) must correspond to the following trench dimensions: P1 = 75 mm or P2/P3 = 150 mm. Note 2: please refer to chapter Layout examples for a site application.
PE50797
On each 630 A unit of the range, except those including a low-voltage control cabinet and EMB compartment, the connection is made with dry-type and single-core cables.
Remarks: b Not available for internal arc IEC 62271-200 in busbar compartment. b Not available in 1250 A.
AMTED398078EN
87
Connections
5 50 minimu m
70
50 60 50
740
110 min
Installation with cable trench for 12.5 kA 1 s downwards exhaust for 16 kA 1 s and 20 kA 1 s upwards exhaust
b Position of xing holes b depends on the width of the unit:
Cubicle width (mm) 125 375 500 625 750 b (mm) 95 345 470 595 720 2150 minimu m
DE57196
4 x M8
330 minimu m
100 50 740 60 0
88
AMTED398078EN
DE57188
Connections
Units 630 A IM, IMC, QM, CM, CM2, PM, DM1-A, DM1-W, GAM, GAM2, SM, TM, NSM Depth P (mm) P1 P2
350 380 410 425 455 470 500 530 550 580 610 625 655 670 700 730
Note: the unit and the cables requiring the greatest depth must be taken into account when determining the depth P for single-trench installations. In double-trench installations must be taken into account to each type of unit and cable orientations.
Trench diagrams
Cable entry or exit through right or left side
DE59723 DE59724
100
100
100
P2
200 1000
P1 P2
P2
200 1000
300
1000
300
QM IM IM
100
100
QM 100 IM IM
100 100
200
100
100
100
AMTED398078EN
89
Connections
Side view
IM, SM units
DE59727 DE57183
QM, PM units
DE57184
GAM2 unit
Front view
IM, SM
DE57185
QMC
GAM
GAM2
QM, PM
DM1-A, DM1-W
375
375
510
90
AMTED398078EN
Installation
Contents
Dimensions and weights for 24 kV Units dimensions for 24 kV Civil engineering for 24 kV Layout examples for 24 kV Dimensions and weights for 36 kV Civil engineering for 36 kV Layout examples for 36 kV
92 93 95 96 97 98 99
AMTED398078EN
91
Installation
DE57186
90 Exhaust channelling
(1) Add to height 450 mm for low-voltage enclosures for control/monitoring and protection functions. To ensure uniform presentation, all units (except GIM and GEM) may be equipped with low-voltage enclosures. (2) Depending on the busbar conguration in the VM6 unit, two types of extension units may be used: b to extend a VM6 DM12 or DM23 unit, use an extension unit with a depth of 1060 mm b for all other VM6 units, a depth of 930 mm is required. (3) For the 1250 A unit.
92
AMTED398078EN
Installation
IM, IMB, PM, QM, QMB, SM, IMC, QMC, CM, CM2
DE58661 DE58662
GBM, GAM2
450
1600
1600
90
840
30 70
90
840
30 70
90
840
30 70
GAM
DE58664 DE58665
GIM
DE58666
GEM
1600
1600
1600
90
840
30 70
930
930 1060
GBC-A, GBC-B
DE58667 DE58668
1600
1600
90
840
100
90
840
30 70
AMTED398078EN
93
Installation
450
503
450
1600
1600
1600
90
840
200 100
90
840
90
DMV-A 630 A
DE58672 DE58673
DMV-A 1250 A
1680
1680
DMV-D
DE58674 DE58675
DMV-S
1680
1600
100
90 85 840 100
94
AMTED398078EN
Installation
Fixing of units
With each other The units are simply bolted together to form the MV switchboard (bolts supplied). Busbar connections are made using a torque wrench set to 28 mN. On the ground b For switchboards comprising up to three units, the four corners of the switchboard must be secured to the ground with using: v M8 bolts (not supplied) screwed into nuts set into the ground using a sealing pistol v screw rods grouted into the ground. b For switchboards comprising more than three units, each unit may be xed to the ground b In circuit-breaker or contactor units, xing devices are installed on the opposite side of the switchgear.
AMTED398078EN
95
Installation
930
25 (minimum)
300 (minimum)
300 (minimum)
930
300 (minimum)
Evacuation duct
569
400
400
1600
96
AMTED398078EN
Installation
(1) The depth measures are given for the oor surface. (2) The depth in these units are 1615 mm with the enlarged low voltage compartment. (3) The depth in these units are 1500 mm with the standard low voltage compartment.
Dimensions
IM, SM, IMC, QM, PM, IMB, GBM, GAM, GAM2, GBC-A,GBC-B QMB, QMC units
DE59662 DE59663
100
215
215
2250
2250
2250
1400
32
1400
32
1400
32 230
AMTED398078EN
97
Installation
150
DE5961
A B 50
Fixing of units
With each other The units are simply bolted together to form the MV switchboard (bolts supplied). Busbar connections are made using a torque wrench set to 28 mN. On the ground b for switchboards comprising up to three units, the four corners of the switchboard must be secured to the ground using: v bolts (not supplied) screwed into nuts set into the ground using a sealing pistol v screw rods grouted into the ground b for switchboards comprising more than three units, the number and position of xing points depends on local criteria (earthquake withstand capacities, etc.) b position of xing holes depends on the width of units.
Unit type IM, IMC, IMB, QM, PM, SM, CM, CM2, TM GBC-A, GBC-B, GBM, GAM2, IMB, GAM, QMB DM1-A, DM1-D, DM1-W, QMC DM2, NSM, DM2-W GIM A (mm) 750 1000 1500 250 B (mm) 650 900 1400 150
14.2 x 25
98
AMTED398078EN
Installation
Side view
100
2550 min.
(1)
min.
100
100
100
Minimum required dimensions (mm) (1) In case of upper incoming option: it must be 2730 mm (no internal arc withstand if selected) (2) In case of upper incoming option: it must be 2830 mm (no internal arc withstand if selected)
Top view
DE59667
100
AMTED398078EN
99
100
AMTED398078EN
Contents
Appendices
Trip curves for VIP 300 LL or LH relays Trip curves for VIP 35 relays Fusarc CF fuses Solefuse fuses
102 103 104 105
Order form
SM6 - Switching
Switching Automatic Transfer System 106 106 107 108 108 110 111 112 113 114 115 116
SM6 - Protection
Circuit breaker Fuse switch Vacuum contactor (Direct Motor Starter) for 24 kV
SM6 - Metering SM6 - Other functions SF1 - Lateral disconnectable or withdrawable SFset - Lateral disconnectable for SM6 24 kV Evolis - Frontal xed version for SM6 24 kV (up to 17.5 kV) Evolis - Lateral disconnectable version for SM6 24 kV (up to 24 kV)
117
AMTED398078EN
101
Appendices
DE53614
t>
t>
t >>
t >>
Is 1.2 Is
10 Is
I >>
Is 1.2 Is 10 Is
I >>
VI curve
t (s) 100
100
10
10
1 0.6 0.4 0.3 0.2 0.15 0.1 0.07 0.05 I/Is 1 1.2 10 100
0.1
0.1
0.6 0.4 0.3 0.2 0.15 0.1 0.07 0.05 I/Is 1 1.2 10 100
0.01
0.01
EI curve
t (s)
DE53616
RI curve
t (s) 10
1000
100
1 10 0.6 0.4 0.3 1 0.1 0.6 0.4 0.3 0.2 0.15 0.1 0.07 0.05 1 1.2 10 0.2 0.15 0.1 0.07 0.05
0.1
0.01
I/Is 100
0.01 1 10
I/Is 100
102
AMTED398078EN
Appendices
s 100
The trip curve shows the time before the relay acts, to which must be added 70 ms to obtain the breaking time.
10
0.1
AMTED398078EN
103
Appendices
Fusarc CF fuses
Fuse and limitation curves
DE53618
100 A
250 A
Current (A)
8 6 4
Ia
2
8 1.
Ik
Is
Ik
2
250 A 200 A 160 A 125 A 100 A 80 A 63 A 50 A 40 A 31.5 A 25 A 20 A 16 A 10 A 6.3 A
10 8 6 4
1 8 6 4
4A
0.1
0.1
10
100
104
AMTED398078EN
Appendices
Solefuse fuses
Fuse and limitation curves
DE53620
100 A 125 A
Current (A)
8 6 4
Ia
2
8 1.
Ik
Is
Ik
2
125 A 100 A 80 A 63 A 43 A 31.5 A 25 A 20 A 16 A 10 A 6.3 A
10 8 6 4
1 8 6 4
0.1 0.1
10
100
AMTED398078EN
105
Order form
SM6
Switching
Only one of the boxes (ticked X or lled by the needed value) have to be considered between each horizontal line. Green box X corresponds to none priced functions.
Basic cubicle
Rated voltage Ur Service voltage Short-circuit current Isc Rated current Ir Internal arc withstand Type of cubicle 24 kV SM 375 IM 375 IM 500 IM 750 IMC 750 Middle IMC 500 12.5 kA 1s for 24 kV
Options
Common options
Replacement of CIT by Electrical driving motorization and/or coil voltage (not applicable on SM cubicle) 24 Vdc 32 Vdc 48 Vdc 60 Vdc Signalling contact Interlocking 2 O & 2 C on SW CI1 110 Vdc 120-125 Vdc 137 Vdc 220 Vdc CI2 120/127 Vac (50 Hz) 220/230 Vac (50 Hz) 120/127 Vac (60 Hz) 220/230 Vac (60 Hz)
1 C on SW and 1 O & 1 C on ES (not applicable on SM cubicle) 2 O & 3 C on SW and 1 O & 1 C on ES Flat key type P1 SM6-SM6 On earthing switch Cubicle no. P3 SM6-SM6 Flair 23DV zero sequence Flair 22D Flair 23DV
Tubular key type For all cubicle (except SM) A4 Localisation of 2nd lock for A3 Localisation of 2nd lock for A4 SM cubicle only A3 SM6-SM6 On switch
P2 SM6-SM6 Replacement of 630 A upper busbar by 1250 A (not possible for IMB) Digital ammeter or fault current indicator AMP 21D Flair 21D
24 kV options
Remote control signalling 2 lights 2 lights and 2 PB 2 lights and 2 PB + 1 switch 220 V
Voltage of the lights (must be the same than electrical driving mechanism) 24 V 48 V 110/125 V Roof conguration (A, B or C only one choice possible) A - Cable connection by the top (cable maxi 240 mm2 with VPIS) Single core B - Low voltage control cabinet (h = 450 mm) C - Wiring duct Cable connection by the bottom (not applicable on IMB, cable maxi 240 mm2) Three core 50 W heating element Surge arresters for IM 500 7.2 kV 10 kV Operation counter CTs for IMC (quantity) Visibility of main contacts Pressure indicator device Analogic manometer without visibility of main contacts Pressure switch Analogic manometer with visibility of main contacts Busbar eld distributors for severe conditions (only for 630 A) Internal arc version (not possible with top incomer option) 16 kA 1 s Gaz exhaust direction Downwards (only for 16 kA 1s) 20 kA 1 s Upwards 12 kV 1 17.5 kV 2 24 kV 3 Single core 2 x single core 2 x single core With unpunched door
36 kV options
Electrical driving mechanism (with O/C coils and AC contacts) O/C coils without electrical driving mechanism Cable connection by the top (single core cable maxi 240 mm2 with VPIS) Cable connection by the bottom (2 x single core, cable maxi 240 mm2, not applicable on IMC) Surge arresters (not applicable on IMB, IMC cubicles) 36 kV
106
AMTED398078EN
Order form
SM6
Switching
Automatic Transfer System
Only one of the boxes (ticked X or lled by the needed value) have to be considered between each horizontal line. Green box X corresponds to none priced functions.
Basic cubicle
Rated voltage Ur Service voltage Short-circuit current Isc Rated current Ir Internal arc withstand Type of cubicle/upper busbar for 24 kV Ir = 630 A, Ir busbar = 400 A Ir = 630 A, Ir busbar = 630 A Ir = 630 A, Ir busbar = 1250 A Type of cubicle for 36 kV Position in the switchboard First on left Incoming bottom busbar for NSM busbar NSM busbar Middle NSM busbar NSM busbar 12.5 kA 1s for 24 kV
Quantity (kV) (kV) (kA) (A) 16 kA 1s for 36 kV NSM cable NSM cable NSM cable NSM cable Last on right Right
Left Cable connection by the bottom (cable maxi 240 mm2) for NSM cable Three core on both Stand by source Utility with paralleling Control unit HMI language French English Spanish Portuguese Single core on both
2 x single core on both Generator without paralleling Utility without paralleling Chinese
Options
Common options
Signalling contact Operation counter Interlocking SM6-SM6 1 x P1 2 x P1 1 x A3 2 x A3 Right cubicle Left cubicle Control and monitoring Protocol type Modem type DNP3 FFSK PSTN IEC 101/204 RS485 GSM Modbus (by default) RS232 (by default) FSK Right cubicle On switch On switch On switch Tubular key type Right cubicle Flat key type Left cubicle Right and left cubicle Left cubicle On earthing switch On earthing switch On earthing switch 1 C on SW and 1 O & 1C on ES
24 kV options
2 heating elements Busbar eld distributors for severe conditions (only for 630 A) Internal arc version (not possible with top incomer option) 16 kA 1 s Gaz exhaust direction Downwards (only for 16 kA 1s) 20 kA 1 s Upwards
AMTED398078EN
107
Order form
SM6
Protection
Circuit breaker
Only one of the boxes (ticked X or lled by the needed value) have to be considered between each horizontal line. Green box X corresponds to none priced functions.
Basic cubicle
Common 24/36 kV
Rated voltage Ur Service voltage Short-circuit current Isc Rated current Ir Internal arc withstand 24 kV For SF1 circuit breaker DM1-A 750 DM1-S 750 For SFset circuit breaker For Evolis frontal 630 A CB For Evolis lateral 630 A CB 36 kV For SF1 circuit breaker DM1-A 1000 DM1-W 1000 DMV-A 12.5 kA 1s for 24 kV DM1-D left 750 DM1-Z 750 DM2 left 750 DM1-D left 750 DMV-S DMVL-A DM1-D left 1000 DM2 left 1500
Quantity
(kV) (kV) (kA) (A) 16 kA 1s for 36 kV DM1-D right 750 DM1-W 750 DM2 right 750 DM1-D right 750 DMV-D right DMVL-D DM1-D right 1000 DM2 right 1500 DM2-W right 1500
First on left
Middle
Last on right See specic order form See specic order form
Basic 24 kV
Busbar (Ir u Ir cubicle) For DM1-A, DM1-S, DM1-W, DMVL-A, DMVL-D ,DM1-D, DM2 400 A For DM1-A, DM1-D, DM1-W, DM1-Z For DMV-A, DMV-D For DMV-S Protection For DM1-S, DMV-S For DM1-S For DMV-A, DMV-D For DM2, DM1-Z, DM1-W Control for DMV-A and DMV-D Local (shunt trip coil compulsory) Remote (opening coil and closing coil compulsory) Local and remote (opening coil and closing compulsory) Voltage of the auxiliaries Voltage of signalling 48/60 Vdc 48/60 Vdc 110/125 or 220/250 Vdc 110/130 or 220/240 Vac (50 Hz) 110/125 Vdc 220/250 Vdc 220/240 Vac (50 Hz) 110/130 Vac (50 Hz) Cable connection by the bottom For DM1-A, DM1-W, DMVL-A 3 x single core cable maxi 240 mm2 Current sensors MV type CT 6 x single core cable maxi 240 mm2 LPCT ring type for DM1-A 630 A LPCT MV type for DM1-D,DM1-W 630 A Statimax 5 A, 2 s VIP35 with CRc Sepam series 10 with CRa VIP300LL with CRa VIP300LL with CRb Sepam series 10 with CRb Sepam series 20/40 Statimax 1 A, 2 s 630 A 630 A 630 A 1250 A 1250 A 1250 A
Basic 36 kV
Voltage of the auxiliaries Voltage of signalling 48/60 Vdc 48/60 Vdc 110/130 Vac (50 Hz) 110/125 or 220/250 Vdc 110/130 or 220/240 Vac (50 Hz) 110/125 Vdc 220/250 Vdc 220/240 Vac (50 Hz) See following page
Options
108
AMTED398078EN
Order form
SM6
Protection
Circuit breaker
Only one of the boxes (ticked X or lled by the needed value) have to be considered between each horizontal line. Green box X corresponds to none priced functions.
Options
Common options
Interlocking Tubular key type Not applicable on DM2 Signalling contact A1 C1 Flat key type C4
2 O & 2 C on SW (not applicable with VTs) 2 O & 3 C on SW and 1 O & 1 C on ES (not applicable with VTs) 1 O & 2 C on SW (available only on cubicle with VTs) See specic order form
24 kV options
Roof conguration (not applicable on DMV-A, DMV-S, DMV-D) (A, B or C only one choice possible) A - Cable connection by the top (cable maxi 240 mm2 with VPIS) Single core DM2 B - Low voltage control cabinet DM2 C - Wiring duct Surge arrester 50 W heating element Replacement of 630 A upper busbars 400-630 A by 1250 A Busbar eld distributors for severe conditions (only for 630 A) Internal arc version (not possible with top incomer option) 16 kA 1 s Gaz exhaust direction Downwards (only for 16 kA 1s) 20 kA 1 s Upwards DM2 Other cubicles 1 cabinet 1 set 1 set 2 cabinets 2 sets 1 set 2 x single core 2 sets
36 kV options
Cable connection by the top (single core cable maxi 240 mm2 with VPIS) Cable connection by the bottom (for DM1-A and DM1-W only) 3 x 2 x single core cable maxi 240 mm2 Surge arrester Sepam relay protection 36 kV See specic order form
AMTED398078EN
109
Order form
SM6
Protection
Fuse switch
Only one of the boxes (ticked X or lled by the needed value) have to be considered between each horizontal line. Green box X corresponds to none priced functions.
Basic cubicle
Rated voltage Ur Service voltage Short-circuit current Isc Rated current Ir Internal arc withstand Type of cubicle 24 kV QM 375 QM 500 36 kV QM 750 Position in the switchboard Quantity of CTs Direction of lower busbars for QMB Left QMB 750 QMC 1000 QMB 375 QMC 625 12.5 kA 1s for 24 kV
Middle First on left Current transformers for QMC 24 kV (to see price structure) 1 2
Options
Common options
Fuses (see fuse price structure) Replacement of mechanism Electrical driving motorization 24 Vdc 32 Vdc 48 Vdc 60 Vdc Shunt trip Opening (on CI1) 24 Vdc 32 Vdc 48 Vdc 60 Vdc Auxiliary contact signalling 2 O & 2 C on SW Interlocking A1 C1 C4 110 Vdc 120-125 Vdc 137 Vdc 220 Vdc Service voltage y 12 kV CIT by CI1 (only for PM) 120/127 Vac (50 Hz) 220/230 Vac (50 Hz) 120/127 Vac (60 Hz) 220/230 Vac (60 Hz)
Closing and opening (on CI2) 110 Vdc 120-125 Vdc 137 Vdc 220 Vdc 120/127 Vac (50 Hz) 220/230 Vac (50 Hz) 120/127 Vac (60 Hz) 220/230 Vac (60 Hz) 380 Vac (50/60 Hz) 1 C on SW and 1 O & 1 C on ES 2 O & 3 C on SW and 1 O & 1 C on ES Flat key type
Replacement of 630 A upper busbar by 1250 A (not possible for QMB) Blown fuse signalling contact (for QM, QMB, QMC)
24 kV options
Replacement of mechanism Remote control signalling (for QM only) 2 lights 2 lights and 2 PB 2 lights and 2 PB + 1 switch Voltage of the lights (must be the same than electrical driving mechanism) 24 V 48 V 110/125 V 220 V Blown fuse signalling contact (mechanical indication PM, electrical for the other cubicles) Roof conguration (A, B or C only one choice possible) A - Cable connection by the top (cable maxi 240 mm2 with VPIS) Single core B - Low voltage control cabinet (h = 450 mm) C - Wiring duct 50 W heating element Operation counter Digital ammeter (not applicable for QMB) Visibility of main contacts Pressure indicator device Analogic manometer without visibility of main contacts Pressure switch Analogic manometer with visibility of main contacts Busbar eld distributors for severe conditions (only for 630 A) Internal arc version (not possible with top incomer option) 16 kA 1 s Gaz exhaust direction Downwards (only for 16 kA 1s) 20 kA 1 s Upwards AMP21D 2 x single core With unpunched door CI1 by CI2 (only for QM)
36 kV options
Replacement of mechanism CIT by CI2 (only for PM) Cable connection by the top (single core cable maxi 240 mm2 with VPIS)
110
AMTED398078EN
Order form
SM6
Protection
Vacuum contactor (Direct Motor Starter) for 24 kV
Only one of the boxes (ticked X or lled by the needed value) have to be considered between each horizontal line. Green box X corresponds to none priced functions.
Basic cubicle
Rated voltage Ur Service voltage Short-circuit current Isc (6.3 kA without fuse) Rated current Ir (max. 400 A without fuse) Internal arc withstand Position in the switchboard Busbar Ir Phase current sensors Key interlockings for 52 type First on left 400 A 1 CT Middle 630 A 2 CT
Quantity (kV) (kV) (kA) (A) 12.5 kA 1s Last on right 1250 A 3 CT 3 LPCT ring type Tubular key type Flat key type
7.2
Options
MV fuses 25 A 31.5 A 40 A 50 A 200 A 63 A 250 A 80 A 100 A 125 A 160 A Busbar eld distributors for severe conditions (only for 630 A) Key interlockings for C1 type Voltage transformer (quantity) Tubular key type
1 Internal arc version (not possible with top incomer option) Gaz exhaust direction
Contactor
Vacuum contactor Open release Closing coil Magnetic hold 48 Vdc 110 Vac/dc 220 Vac/dc Mechanical latching 125 Vdc 120 Vac/dc 240 Vac/dc 250 Vdc 125 Vac/dc 250 Vac/dc
AMTED398078EN
111
Order form
SM6
Metering
Only one of the boxes (ticked X or lled by the needed value) have to be considered between each horizontal line. Green box X corresponds to none priced functions.
Basic cubicle
Common 24/36 kV
Rated voltage Ur Service voltage Short-circuit current Isc Rated current Ir Internal arc withstand Type of cubicle/upper busbar for 24 kV Ir = 630 A, Ir busbar = 400 A Ir = 630 A, Ir busbar = 630 A Ir = 630 A, Ir busbar = 1250 A Ir = 1250 A, Ir busbar = 1250 A Type of cubicle for 36 kV CM 750 CM2 750 TM 750 Position in the switchboard First on left Direction of lower busbars for GBC-A Signalling contact (for CM, CM2 and TM only) Fuses (for CM, CM2 and TM only) Middle Left CM CM CM CM2 CM2 CM2 TM TM TM 12.5 kA 1s for 24 kV
Quantity
(kV) (kV) (kA) (A) 16 kA 1s for 36 kV GBC-A GBC-A GBC-A GBC-A GBC-B GBC-B GBC-B GBC-B GBC-A 750 GBC-B 750 Last on right Right 1 O and 1 C on SW See fuse price structure
Basic 24 kV
VTs for GBC (to see price structure) CTs for GBC (to see price structure) Ratio choice for GBC Protections 1 secondary 2 secondaries 1 high secondary 1 low secondary Phase/phase Quantity 1 Phase/earth 2 3
Basic 36 kV
Voltage transformers See specic order form
Options
24 kV options
Roof conguration (A, B or C only one choice possible) A - Cable connection by the top (cable maxi 240 mm2 with VPIS) Single core B - Low voltage control cabinet (h = 450 mm) C - Wiring duct 50 W heating element for CM, CM2, TM Busbar eld distributors for severe conditions (only for 630 A and CM, CM2 and TM cubicles) Blown fuse auxiliary contact (for CM, CM2 and TM only) Internal arc version (not possible with top incomer option) 16 kA 1 s Gaz exhaust direction Downwards (only for 16 kA 1s) 1 O and 1 C 20 kA 1 s Upwards See specic order form 2 x single core With unpunched door
36 kV options
Current transformers and voltage transformers for GBC Cable connection by the top (single core cable maxi 240 mm2 with VPIS) Replacement of 630 A busbar by 1250 A (for CM, CM2 and TM only)
112
AMTED398078EN
Order form
SM6
Other functions
Only one of the boxes (ticked X or lled by the needed value) have to be considered between each horizontal line. Green box X corresponds to none priced functions.
Basic cubicle
Rated voltage Ur Service voltage Short-circuit current Isc Rated current Ir Internal arc withstand Type of cubicle/upper busbar for 24 kV Ir = 630 A, Ir busbar = 400 A Ir = 630 A, Ir busbar = 630 A Ir = 1250 A, Ir busbar = 1250 A Type of cubicle for 36 kV Position in the switchboard GAM 500 GAM 500 GAM 500 GAM 750 GAM2 750 Middle GAM2 375 GAM2 375 12.5 kA 1s for 24 kV
Quantity (kV) (kV) (kA) (A) 16 kA 1s for 36 kV GBM 375 GBM 375 GBM 375 GBM 750 Last on right Right
Options
24 kV options
Roof conguration (A, B or C only one choice possible) A - Cable connection by the top (cable maxi 240 mm2 with VPIS) Single core B - Low voltage control cabinet (h = 450 mm) C - Wiring duct Wiring duct for GBM ES auxiliary contact (only on GAM 500) Surge arresters for GAM 500, 630 A 7.2 kV 10 kV 12 kV 17.5 kV Flat key type P5 SM6-SM6 Cubicle no. 24 kV Interlocking on GAM 500 1 O and 1 C 2 x single core With unpunched door
Localisation of 2nd lock for P5 Heating element (on GAM 500 630 A and on GAM2) Digital ammeter or Fault current indicator AMP 21D (except GBM) Flair 21D Flair 22D
Internal arc version (not possible with top incomer option) 16 kA 1 s Gaz exhaust direction Downwards (only for 16 kA 1s)
36 kV options
Cable connection by the top (single core cable maxi 240 mm2 with VPIS) Replacement of 630 A busbar by 1250 A (for GAM2 only) Surge arresters for GAM2
AMTED398078EN
113
Order form
SF1
Lateral disconnectable or withdrawable
by Only one of the boxes (ticked X or lled the needed value) have to be considered between each horizontal line. Green box X corresponds to none priced functions.
48 Vdc 125 Vdc Undervoltage release YM 24 Vdc 30 Vdc 48 Vdc Mitop 60 Vdc 110 Vdc 125 Vdc
48 Vdc 125 Vdc Undervoltage release YM 24 Vdc 30 Vdc 48 Vdc Mitop 60 Vdc 110 Vdc 125 Vdc
Remote control
Electrical motor M Shunt closing release YF 24 Vdc 30 Vdc 48 Vdc Leaets language 60 Vdc 110 Vdc 125 Vdc 220 Vdc 48 Vac (50 Hz) 110 Vac (50 Hz) French 220 Vac (50 Hz) 120 Vac (60 Hz) 240 Vac (60 Hz) English 2432 Vdc 4860 Vdc/ac 110127 Vdc/ac 220250 Vdc/ac
Different releases combinations Shunt opening releases YO1/YO2 Undervoltage release YM Mitop
1 1 1
1 1
1 1 1 1 AMTED398078EN
114
Order form
SFset
Lateral disconnectable for SM6 24 kV
Basic circuit breaker
Rated voltage Ur Service voltage Impulse voltage Up Short-circuit current Isc Rated current Ir Frequency Mechanism position Colour for push buttons and indicators Push buttons open/close: Red/black Indicator open/close: Black/white Operating mechanism charged/discharged: White/yellow 60 Hz A1
by Only one of the boxes (ticked X or lled the needed value) have to be considered between each horizontal line. Green box X corresponds to none priced functions.
Is = 10 to 50 A Is = 63 to 312 A Is = 10 to 50 A Is = 63 to 312 A
VIP 300LL
48 Vdc 125 Vdc Undervoltage release YM 24 Vdc 30 Vdc 48 Vdc 60 Vdc 110 Vdc 125 Vdc
Remote control
Electrical motor M Shunt closing release YF 24 Vdc 30 Vdc 48 Vdc Test box (VAP 6) Leaets language French English 60 Vdc 110 Vdc 125 Vdc 220 Vdc 48 Vac (50 Hz) 110 Vac (50 Hz) 220 Vac (50 Hz) 120 Vac (60 Hz) 240 Vac (60 Hz) 2432 Vdc 4860 Vdc/ac 110127 Vdc/ac 220250 Vdc/ac
Different releases combinations Mitop Shunt opening release YO2 Undervoltage release YM AMTED398078EN
1 1
1 1
115
Order form
Evolis
Frontal fixed version for SM6 24 kV (up to 17.5 kV)
Basic xed circuit breaker
Rated voltage Ur (kV) Service voltage Short-circuit current Isc Rated normal current Ir (A) Phase distance 630 12 (kV) 25 kA 1250 185 mm
Only one of the boxes (ticked X or lled by the needed value) have to be considered between each horizontal line. Green box X corresponds to none priced functions.
Quantity 17.5
If locks 1 lock 2 identical locks Disabling of O/C circuit breaker push buttons
1 1
1 1 AMTED398078EN
116
Order form
Evolis
Lateral disconnectable version for SM6 24 kV (up to 24 kV)
Basic circuit breaker
Rated voltage Ur Service voltage Impulse voltage Up Rated normal current Ir Phase distance Mechanism position Colour for push buttons and indicators Push buttons open/close: Red/black Indicator open/close: Black/white Operating mechanism charged/discharged: White/yellow (kV) (kVbil) 630 A maximum 250 mm B1
Only one of the boxes (ticked X or lled by the needed value) have to be considered between each horizontal line. Green box X corresponds to none priced functions.
Quantity 24 (kV)
Different releases combinations Shunt opening releases YO1 Shunt opening releases YO2 Undervoltage release YM Mitop AMTED398078EN
1 1
1 1
1 1
1 1 1
117
Notes
118
AMTED398078EN
10-31-1247