Catalogo Sm6 2012

Download as pdf or txt
Download as pdf or txt
You are on page 1of 124

Medium Voltage Distribution Catalogue | 2012

SM6
Modular units
Air insulated switchgear up to 36 kV

Make the most of your energy

Medium Voltage Distribution SM6 Air insulated switchgear 1 to 36 kV

Your requirements

Continuity of Service & Complete Safety

Safety
Operating safety through protection against electrical, mechanical and thermal effects of a fault (insulation of each compartment) All operations carried out from the front, door closed Voltage Presence Indicator System located on the front panel Position indicator linked to the devices physical position Protection in the event of internal arcing Interlocking devices Anti-reflex handles

Reliability
Type-tested solution which complies with the IEC62271-200 standard Design by the most accurate three-dimensional computer techniques Manufacturing & Testing according to ISO 9001:2000 quality standard

Simplicity
Easy installation - All cubicles with the same engineering dimensions On-site information retrieval Possibility of remote management Maintenance with power on (LSC2A), very simple Compartmentalization of MV parts (insulated partitions)

Reliability + Simplicity = Cost optimization!

Medium Voltage Distribution SM6 Air insulated switchgear 1 to 36 kV

Our solutions

Schneider Electric has developed protection, monitoring and control solutions specifically dedicated to Medium Voltage networks for over 40 years. SM6 switchgear has been specifically designed on the basis of that extensive experience. It also incorporates some very new solutions, giving the best in terms of continuity of service and operators safety.

PE57150

High-performance breaking devices


kA 2 5 25 SF1 or/and Evolis* 1 6 16 SF1 or/and Evolis* 630 630 63 (*) Not available at 36 kV. 125 12 1250 A

A comprehensive solution
SM6 switchgear is fully compatible with PowerMeter metering units. Sepam multi-function protection relays - Protection - Measurements and diagnosis. VIP protection self powered relay for protection. SM6 swithchboards can thus be easily integrated into any monitoring and control system. - Local & remote indication and operation.

PM103193

SM6, a truly professional solution! More than 1,100,000 cubicles installed world-wide.

Enclosures able to withstand internal arcing


Internal Arc Classification: A-FL and A-FLR. 3-sides internal arc protection IAC: A-FL, 12,5 kA 1 s and 16 kA 1 s for 24 kV and 16 kA 1 s for 36 kV. 4-sides internal arc protection IAC: A-FLR, 16 kA 1 s and 20 kA 1 s for 24 kV. Choice of exhaust: - downwards exhaust - upwards exhaust for 24 kV.

SM6

General contents

Presentation

General characteristics

11

Characteristics of the functional units

47

Connections

83

Installation

91

Appendices Order form

101

AMTED398078EN

AMTED398078EN

Presentation

Contents

The experience of a world leader The ranges advantages Protecting the environment A full range of services The references of a leader Quality assurance

4 5 6 7 8 9

AMTED398078EN

Presentation

The experience of a world leader

The Schneider Electric experiences extends over forty years in factorybuilt cubicles and over thirty years in SF6 breaking technology for Medium Voltage switchgear. This experience means that today Schneider Electric can propose a complementary range: vacuum type circuit breaker cubicles up to 24 kV and standard or enhanced internal arc withstand cubicles to reinforce the safety of people according to the IEC standard. This gives you the advantage of unique experience, that of a world leader, with over 2,500 000 SF6 Medium Voltage units installed throughout the world. Putting this experience at your service and remaining attentive to your requirements is the spirit of active partnership that we want to develop in offering you the SM6. The modular SM6 is a range of harmonised cubicles equipped with SF6 or vacuum breaking technology switchgear with 30 years life span. These cubicles allow you to produce all your Medium Voltage substation requirements up to 36 kV by superposing their various functions.The result of in-depth analysis of your requirements, both now and in the future, SM6 cubicles mean that you can take advantage of all the features of both a modern and proven technology.

PM103194

1975: innovation Sulphur hexauoride (SF6) is rst used in an MV switch for an MV/LV transformer substation, with the VM6. 1989: experience Over 300,000 VM6 cubicles equipped networks throughout the world. 1991: innovation and experience Cumulated with the second generation of SM6 modular SF6 cubicles. 2012: a leading position With over 1,100,000 SM6 cubicles installed around the world, Schneider Electric consolidates its position as uncontested leader in the Medium Voltage eld.

AMTED398078EN

Presentation

The ranges advantages

Upgradability
SM6, a comprehensive range
b b b b b A comprehensive offer covering your present and future requirements A design adapted to the extension of your installations A catalogue of functions for all your applications A product designed to be in compliance with standards constraints Options to anticipate the control and monitoring of your installations.

Compactness
SM6, an optimised range
b Compact units, with low increment cubicles b Rationalised space requirement for switchboard installation b Reduction of civil works costs b Easy integration in factory-built outdoor substations for which the SM6 is particularly well designed.

Maintenance
SM6, a range with reduced maintenance
b The active parts (breaking and earthing) are integrated in an SF6-lled, sealed for life unit b The control mechanisms, are intented to function with reduced maintenance under normal operating conditions b Enhanced electrical endurance when breaking.

Ease of installation
SM6, a simple range to incorporate
b b b b Reduced dimensions and weights Only one civil works layout A solution adapted to cable connection Simplied switchboard busbar design.

Ease and safe to operate


SM6, a proven range
b b b b b b b A three position switch to block incorrect switching The earthing disconnector has full closing capacity Positive breaking of position indicators Internal arc withstand in the cable and switchgear compartments Clear and animated display diagrams Switching lever with an anti-reex function Compartmented cubicles.

SM6: a range designed with control and monitoring in mind


SM6 switchgear is perfectly adapted to control and monitoring applications. Motorised, either when installed or at a later date on-site without any interruption in service, SM6 combines with the Easergy T200 remote control interface. You therefore benet from a ready-to connect unit that is easy to incorporate providing guaranteed switchgear operation.

SM6: a range with adapted protection devices


With the SM6, Schneider Electric proposes solutions for network management; the Sepam and VIP or relay ranges protect installations, providing continuity of electrical supply and reducing downtime.

AMTED398078EN

Presentation

Protecting the environment

Product environmental prole & recycling service


Schneider Electrics recycling service for SF6 products is part of a rigorous management process.
61051N

Schneider Electric is committed to a long term environmental approach. As part of this, the SM6 has been designed to be environmentally friendly, notably in terms of the products recycleability. The materials used, both conductors and insulators, are identied in product environmental prole analysis and easily separable. It was performed in conformity with ISO 14040 Environmental management: life cycle assessment - principle and framework. At the end of its life, SM6 can be processed, recycled and its materials recovered in conformity with the draft European regulations on the end-of-life of electronic and electrical products, and in particular withoutany gas being released to the atmosphere nor any polluting uids being discharged. SM6 is compliant with the RoHS directive. RoHS restricts the use of six hazardous materials in the manufacture of various types of electronic and electrical equipment.

61016N

24 kV Switch unit Ferrous metal 84% Circuit breaker unit 65%

36 kV Switch unit 74%

Non-ferrous metal

4%

10.6%

8%

Thermohardening Thermoplastics Fluid

9.5% 2.35% 0.15%

22% 2.3% 0.1%

15% 2% 1%

The environmental management system adopted by Schneider Electric production sites that produce the SM6 have been assessed and judged to be in conformity with requirements in the ISO 14001 standard.

MT55145

01 ISO 140

AMTED398078EN

Presentation

A full range of services

Schneider Electric is capable of offering a full range of services either associated or not with the supply of the SM6 unit. To improve the quality of your electrical power: b Network study, harmonics study, etc. b Reactive energy compensation b Consumption monitoring b Optimisation of your electrical power supply contracts. To accompany the purchase and installation of your SM6 equipment: b Adaptation of our equipment to provide a better response to your requirements b On site assembly, testing and commissioning of your equipment b Customised nancing solutions b Warranty extension b Operator training. To accompany your installation throughout its life and upgrading your equipment: b Upgrading your existing equipment: functional adaptation, control motorisation, renovation of protections units, etc. b On site work b Supply of replacement parts b Maintenance contracts b End of life recycling. Fore more information on all the services proposed by Schneider Electric, please contact your Schneider Electric Sales Ofce.
PE57151

61052N

AMTED398078EN

Presentation

The references of a leader


SM6, a world-wide product

PE57234

Asia/Middle East
b Canal Electrical Distribution Company, Egypt b General Motors Holden, Australia b Pasteur Institute, Cambodia b Tian he City, China b Sanya Airport, China b Bank of China, Beijing, Jv Yanta, China b Plaza Hotel, Jakarta, Indonesia b Bali Airport, Indonesia b Wakasa Control Center, Japan b Otaru Shopping center, Japan b New City of Muang, Thong Than, Kanjanapas, Thailand b Danang and Quinhon Airport, Vanad, Vietnam b British Embassy, Oman b KBF Palace Riyadh, Saudi Arabia b Raka Stadium, Saudi Arabia b Bilkent University, Turkey b TADCO, BABOIL development, United Arab Emirates b Melbourne Tunnel City Link, Australia b Campus KSU Qassim Riyad, Saudi Arabia

Africa
b b b b b b b b b b ONAFEX, Hilton Hotel, Algeria Yaounde University, Cameroon Karoua Airport, Cameroon Libreville Airport, Gabon Ivarto Hospital, CORIF, Madagascar Central Bank of Abuja, ADEFEMI, Nigeria OCI Dakar, Oger international, CGE, Senegal Bamburi cement Ltd, Kenya Ivory Electricity Company, Ivory Coast Exxon, New Headquarters, Angola

South America/Pacic
b b b b b b b b b b b Lamentin Airport, CCIM, Martinique Space Centre, Kourou, Guyana Mexico City Underground System, Mexico Santiago Underground System, Chile Cohiba Hotel, Havana, Cuba Iberostar Hotel, Bavaro, Dominican Republic Aluminio Argentino Saic SA, Argentina Michelin Campo Grande, Rio de Janeiro, Brazil TIM Data Center, So Paulo, Brazil Light Rio de Janeiro, Brazil Hospital Oswaldo Cruz, So Paulo, Brazil

Europe
b b b b b b b b b b b b b b b b b b Stade de France, Paris, France EDF, France Eurotunnel, France Nestl company headquarters, France TLM Terminal , Folkestone, Great Britain Zaventem Airport, Belgium Krediebank Computer Centre, Belgium Bucarest Pumping station, Romania Prague Airport, Czech Republic Philipp Morris St Petersburg, Russia Kremlin Moscow, Russia Madrid airport, Spain Dacia Renault, Romania Lafarge cement Cirkovic, Czech Republic Caterpillar St Petersburg, Russia Ikea Kazan, Russia Barajas airport, Spain Coca-cola Zurich, Switzerland

AMTED398078EN

Presentation

Quality assurance
Quality certified to ISO 9001

A major advantage
Schneider Electric has integrated a functional organisation into each of its units. The main mission of this organisation is to check the quality and the compliance with standards. This procedure is: b Uniform throughout all departments b Recognised by many customers and approved organisations. But it is above all its strict application that has enabled recognition to be obtained by an independent organisation: The French Quality Assurance Association (FQAA).

The quality system for the design and manufacture of SM6 units has been certied in conformity with the requirements of the ISO 9001: 2000 quality assurance model.
MT55054 MT55055

ISO

900 1

ISO

9002

61002N

Meticulous and systematic controls


During manufacture, each SM6 is subject to systematic routine testing which aims to check the quality and conformity: b Sealing testing b Filling pressure testing b Opening and closing rate testing b Switching torque measurement b Dielectric testing b Conformity with drawings and plans. The results obtained are written and reported on the test certicate for each device by the quality control department.

61003N

Mean Operating Time To Failure (MTTF)


As result of Schneider Electric quality assurance system, SM6 has negligible Mean Down Time (MDT) in comparison to the Mean Up Time (MUT), thus Mean Operating Time Between Failures (MTBF) is as similar as to the MTTF. b MTTF (cumulative) = 3890 years for 24 kV * b MTTF (cumulative) = 6259 years for 36 kV *.
(*) Year 2010.

AMTED398078EN

10

AMTED398078EN

General characteristics

Contents

Field of application Units for switching function Units for protection function Units for metering function Units for other functions Operating conditions Standards Main characteristics Factory-built cubicles description Compartments description Safety of people
By switchgear By operating mechanism safety By internal arc protection

12 14 15 18 19 20 21 22 24 26 28 28 30 31 32 32 33 34 37 38 39 39 42 42 43 44 45 46

MV electrical network management


Easergy T200 S for 24 kV Easergy T200 I Automation systems

Fault indicators Ammeter Protection and control monitoring


Sepam selection guide for all applications VIP 35 protection relay VIP 300 LL protection relay Sepam series 10 with CRa/CRb sensors Protection and sensor selection table LPCT protection chain

PS100 high-availability power supply

AMTED398078EN

11

General characteristics

Field of application

The SM6 is made up of modular units containing xed, disconnectable or withdrawable metal-enclosed switchgear, using sulphur hexauoride (SF6) or vacuum: b Switch-disconnector b SF1, SFset or Evolis circuit breaker b Rollarc 400 or 400 D contactor, or vacuum contactor b Disconnector. SM6 units are used for the MV section in MV/LV transformer substations in public distribution systems and MV consumer or distribution substations up to 36 kV.

MV/LV transformer substations


UTE standard (EDF)
HV/MV substation MV consumer substation (MV metering) IM
MT55148 DE59670EN

IM

CM

DM2

QM

PM

IM

Incoming line of the main distribution switchboard

Combined public distribution/ Consumer substation PM IM IM GIM QM


MT55147

MV consumer substation (LV metering) IM IM QM DM1-S

Substation GAM2 QM

Outgoing line toward other ring substations

Other standards
MV consumer substations (MV metering) IM
MT55146

IM

DM1-D

GBC-A

QM

DM1-S

Outgoing line toward other ring substations Incoming line of the main distribution switchboard

12

AMTED398078EN

General characteristics

Field of application

Industrial distribution substations


HV/MV substation
DE59200EN

Distribution switchboard DM1-A


61004N

GBC-B

QM QM IM

IM

IMB GBM QM DM1-S

GBC-B

DM1-A

Incoming line

ATS

Incoming line

MV/LV transformer substations

Unit denitions
Below is the list of SM6 units used in MV/LV transformer substations and industrial distribution substations: b IM, IMC, IMB switch b PM fused switch b QM, QMC, QMB fuse-switch combination b CRM, CVM contactor and contactor with fuses b DM1-A, DM1-D, DM1-S single-isolation disconnectable SF6 type circuit breaker b DMV-A, DMV-D, DMV-S single-isolation vacuum type circuit breaker frontal b DMVL-A, DMVL-D single-isolation disconnectable vacuum type circuit breaker lateral b DM1-W, DM1-Z withdrawable single-isolation SF6 type circuit breaker b DM2 double-isolation disconnectable SF6 type circuit breaker b DM2-W withdrawable double-isolation SF6 type circuit breaker only for 36 kV b CM, CM2 voltage transformers b GBC-A, GBC-B current and/or voltage measurements b NSM-cables for main incoming and standby b NSM-busbars for main incoming and cables for standby b GIM intermediate bus unit b GEM extension unit b GBM connection unit b GAM2, GAM incoming cable connection unit b SM disconnector b TM MV/LV transformer unit for auxiliaries b Other units, consult us b Special function EMB busbar earthing only for 24 kV.

QM NSM-busbarsGBM SM TM

NSM-cablesQM CRM CRM DM1-W

Standby generator source

Standby source

Distribution switchboard QM QM GBC-B IM IMB GBM IM GBC-B DM1-S DM1-S

ATS

Incoming line ATS: Automatic Transfer System

Incoming line

AMTED398078EN

13

General characteristics

Units for switching function

Switching
DE59671 DE59672 DE59673

page

48

IM Switch unit 24 kV: 375 or 500 mm 36 kV: 750 mm

IMC Switch unit 24 kV: 500 mm 36 kV: 750 mm

IMB Switch unit with earthing disconnector right or left outgoing line 24 kV: 375 mm 36 kV: 750 mm

Automatic transfer system


DE59692 DE59693

49

NSM-cables Cables power supply for main incoming line and standby line 24 kV: 750 mm
DE59696 DE59697

NSM-busbars Busbars power supply for main incoming line on right or left and cables for standby line 24 kV: 750 mm

50

NSM-cables Cables power supply for main incoming line and standby line 36 kV: 1500 mm

NSM-busbars Busbars power supply for main incoming line on right or left and cables for standby line 36 kV: 1500 mm

14

AMTED398078EN

General characteristics

Units for protection function

Fuse-switch
DE59674 DE59675 DE59676

page

51

QM Fuse-switch combination unit 24 kV: 375 or 500 mm 36 kV: 750 mm


DE59677

QMC Fuse-switch combination unit 24 kV: 625 mm 36 kV: 1000 mm

QMB Fuse-switch combination unit right or left outgoing line 24 kV: 375 mm 36 kV: 750 mm

52

PM Fuse-switch unit 24 kV: 375 mm 36 kV: 750 mm

SF6 circuit-breaker
DE59678 DE59679

53

DM1-A Single-isolation, disconnectable circuit breaker unit 24 kV: 750 mm 36 kV: 1000 mm

DM1-D Single-isolation, disconnectable circuit breaker unit right or left outgoing line 24 kV: 750 mm 36 kV: 1000 mm

AMTED398078EN

15

General characteristics

Units for protection function

SF6 circuit-breaker
DE59681 DE53487 DE53490

page

54 55

DM1-W Withdrawable single-isolation circuit breaker unit 24 kV: 750 mm 36 kV: 1000 mm
DE59680

DM1-S Single-isolation, disconnectable circuit breaker unit with autonomous protection 24 kV: 750 mm
DE59691

DM1-Z Withdrawable single-isolation circuit breaker unit right outgoing line 24 kV: 750 mm

54 55

DM2 Double-isolation, disconnectable circuit breaker unit right or left outgoing line 24 kV: 750 mm 36 kV: 1500 mm

DM2-W Withdrawable double-isolation circuit breaker unit right outgoing line 36 kV: 1500 mm

Vacuum circuit-breaker
DE53491 DE53492 DE53493

56

DMV-A Single-isolation circuit breaker unit 24 kV: 625 mm

DMV-D Single-isolation circuit breaker unit right outgoing line 24 kV: 625 mm

DMV-S Single-isolation circuit breaker unit with autonomous protection 24 kV: 625 mm

16

AMTED398078EN

General characteristics

Units for protection function

Vacuum circuit-breaker
DE53485 DE59694

page

57

DMVL-A Single-isolation, disconnectable circuit breaker unit 24 kV: 750 mm

DMVL-D Single-isolation, disconnectable circuit breaker unit right outgoing line 24 kV: 750 mm

Vacuum contactor (Direct Motor Starter)


DE59231 DE59232

58

CVM Fuse-contactor unit 24 kV: 750 mm

CVM Contactor unit 24 kV: 750 mm

SF6 contactor (Direct Motor Starter)


DE59201 DE59202

59

CRM Fuse-contactor unit 24 kV: 750 mm

CRM Contactor unit 24 kV: 750 mm 17

AMTED398078EN

General characteristics

Units for metering function

DE59863

60

CM Voltage transformers for mains with earthed neutral system 24 kV: 375 mm 36 kV: 750 mm
DE53496 DE53497

DE59684

page

CM2 Voltage transformers for mains with insulated neutral system 24 kV: 500 mm 36 kV: 750 mm

61

GBC-A Current and/or voltage measurement unit right or left outgoing line 24 and 36 kV: 750 mm

GBC-B Current and/or voltage measurement unit 24 and 36 kV: 750 mm

18

AMTED398078EN

General characteristics

Units for other functions

DE59686

DE53498

62

GBM Connection unit right or left outgoing line 24 kV: 375 mm 36 kV: 750 mm
DE59687 DE59688

GEM Extension unit VM6/SM6 24 kV: 125 mm

DE59685

page

GIM Intermediate bus unit 24 kV: 125 mm 36 kV: 250 mm

63

GAM2 Incoming cable-connection unit 24 kV: 375 mm 36 kV: 750 mm

GAM Incoming cable-connection unit with earthing 24 kV: 500 mm 36 kV: 750 mm
DE53504

DE59689

64

SM Disconnector unit 24 kV: 375 mm or 500 (1) mm 36 kV: 750 mm


(1) only for 1250 A units.

DE59690

TM MV/LV transformer unit for auxiliaries 24 kV: 375 mm 36 kV: 750 mm

EMB Busbar earthing compartment 24 kV: 375 mm

AMTED398078EN

19

General characteristics

Operating conditions

In addition to its technical characteristics, SM6 meets requirements concerning safety of life and property as well as ease of installation, operation and protecting the environment.
PE57152

SM6 units are designed for indoor installations. Their compact dimensions are: b 375 to 1500 mm width b 1600 to 2250 mm height b 840 to 1400 mm depth this makes for easy installation in small rooms or prefabricated substations. Cables are connected via the front. All control functions are centralised on a front plate, thus simplifying operation. The units may be equipped with a number of accessories (relays, toroids, instrument transformers, surge arrester, control and monitoring, etc.).

Normal operating conditions


b Ambient air temperature: 1) less than or equal to 40C 2) less than or equal to 35C on average over 24 hours 3) greater or equal to 5C. b Altitude 1) less than or equal to 1000 m 2) above 1000 m, a derating coefcient is applied (please consult us). b Solar radiation 1) no solar radiation inuence is permitted. b Ambient air pollution 1) no signicant pollution by dust, smoke, corrosive and/or ammable gases, vapours or salt. b Humidity 1) average relative humidity over a 24 hour period, less than or equal to 95% 2) average relative humidity over a 1 month period, less than or equal to 90% 3) average vapor pressure over a 24 hour period, less than or equal to 2.2 kPa 4) average vapor pressure over a 1 month period, less than or equal to 1.8 kPa. For these conditions, condensation may occasionally occur. Condensation can be expected where sudden temperature changes occur in periods of high humidity. To withstand the effects of high humidity and condensation, such as breakdown of insulation, please pay attention on Civil Engineering recommendations for design of the building or housing, by suitable ventilation and installation. Severe operating conditions (please consult us).

20

AMTED398078EN

General characteristics

Standards

SM6 units meet all the following standards and specications: b IEC standards b UTE standards for 24 kV b EDF specications for 24 kV.

b IEC standards 62271-200 High-voltage switchgear and controlgear - Part 200: A.C. metalenclosed switchgear and controlgear for rated voltage above 1 kV and up to and including 52 kV. High-voltage switchgear and controlgear - Part 1: Common specications. High voltage switches - Part 1: switches for rated voltages above 1 kV and less or equal to 52 kV. High-voltage switchgear and controlgear - Part 105: High voltage alternating current switch-fuse combinations. Electrical relays. High-voltage switchgear and controlgear - Part 100: High-voltage alternating current circuit breakers. High-voltage switchgear and controlgear - Part 102: High-voltage alternating current disconnectors and earthing switches. Instrument transformers - Part 1: Current transformers. Instrument transformers - Part 2: Voltage transformers. Instrument transformers - Part 8: Low Power Current Transducers. High-voltage prefabricated switchgear and controlgear assemblies Voltage presence indicating systems. High-voltage prefabricated switchgear and controlgear assemblies Voltage presence indicating systems. Consumer substation installed inside a building and fed by a second category voltage public distribution system. High voltage electrical installations requirements. High voltage switches for rated voltage above 1 kV and less than 52 kV.

62271-1 62271-103 62271-105 60255 62271-100 62271-102 60044-1 60044-2 60044-8 61958 62271-206

b UTE standards for 24 kV NFC 13.100 NFC 13.200 NFC 64.130

NFC 64.160. Alternating current disconnectors and earthing switches EDF specications for 24 kV HN 64-S-41 HN 64-S-43 A.C. metal-enclosed swichgear and controlgear for rated voltages above 1 kV and up to and including 24 kV. Electrical independent-operating mechanism for switch 24 kV - 400 A.

AMTED398078EN

21

General characteristics

Main characteristics

PE57150

The hereunder values are for working temperatures from -5C up to +40C and for a setting up at an altitude below 1000 m.

Electrical characteristics
Rated voltage Ur Ud Ud Up Up kV 50/60 Hz, 1 min (kV rms) 50/60 Hz, 1 min (kV rms) 1.2/50 s (kV peak) 1.2/50 s (kV peak) A A Ir Ik/tk (2) A kA /1 s 25 20 (3) 16 12.5 Making capacity (50 Hz) Ima kA 62.5 50 40 31.25 7.2 20 23 60 70 16 31.5 400 - 630 -1250 630 - 1250 630 - 1250 630 - 1250 400 - 630 - 1250 630 630 630 400 - 630 630 - 800 (4) 25 25 10 25 6.3 25 25 20 DM1-S DM1-Z DM2 DM2-W Vacuum circuit breaker range DMV-A, DMV-D, DMV-S DMVL-A DMVL-D NA: Non Available (1) 60 kV peak for the CRM unit (2) 3 phases (3) In 20 kA / 3 s, consult us (4) In 800 A, consult us. kA kA kA 25 20 25 630-1250 630 630 NA NA NA kA kA kA 25 25 20 25 25 630-1250 630-1250 630 1250 630 630 NA 1250 1250 NA NA NA NA NA NA 1250 20 630 630 20 20 NA 630-1250 50 630-1250 1250 12 28 32 75 (1) 85 17.5 38 45 95 110 24 50 60 125 145 36 70 80 170 195

Insulation level
Insulation Isolation Insulation Isolation

Breaking capacity
Transformer off load Cables off load Rated current Short-time withstand current

Maximum breaking capacity (Isc)


Units IM, IMC, IMB, NSM-cables, NSM-busbars QM, QMC, QMB PM CRM CRM with fuses CVM CVM with fuses SF6 circuit breaker range DM1-A, DM1-D, DM1-W kA A kA kA kA kA kA kA

22

AMTED398078EN

General characteristics

Main characteristics

PE57150

Endurance
Units
Units IM, IMC, IMB, PM, QM (5), QMC (5), QMB (5), NSM-cables, NSM-busbars CRM Disconnector Rollarc 400 Mechanical endurance IEC 62271-103 1 000 operations class M1 IEC 62271-102 1 000 operations IEC 60470 300 000 operations 100 000 operations IEC 62271-102 1 000 operations IEC 60470 250 000 breaks at Ir IEC 60470 100 000 breaks at 320 A 300 000 breaks at 250 A 100 000 breaks at 200 A Electrical endurance IEC 62271-103 100 breaks at Ir, p.f. = 0.7, class E3

Rollarc 400D CVM Disconnector

Vacuum contactor IEC 60470 2 500 000 operations 250 000 with mechanical latching SF6 circuit breaker range DM1-A, DM1-D, DM1-W, DM1-Z, DM1-S, DM2 DM2-W Disconnector SF circuit breaker IEC 62271-102 1 000 operations IEC 62271-100 10 000 operations class M2

IEC 62271-100 30 breaks at 12.5 kA for 24 kV 25 breaks at 25 kA for 24 kV 40 breaks at 16 kA for 36 kV 15 breaks at 25 kA for 36 kV 10 000 breaks at Ir, p.f. = 0.7, class E2 IEC 62271-103 100 breaks at Ir, p.f. = 0.7, class E3 IEC 62271-100 10 000 breaks at Ir, p.f. = 0.7, class E2

Vacuum circuit breaker range DMV-A, DMV-D, DMV-S Switch IEC 62271-103 1 000 operations class M1 IEC 62271-100 10 000 operations class M2 IEC 62271-102 1 000 operations IEC 62271-100 10 000 operations class M2 IEC 62271-100 10 000 breaks at Ir, p.f. = 0.7, class E2

Evolis circuit breaker DMVL-A DMVL-D Disconnector Evolis circuit breaker

(5) As per recommendation IEC 62271-105, three breakings at p.f. = 0.2 800 A under 36 kV; 1400 A under 24 kV; 1730 A under 12 kV; 2600 A under 5.5 kV.

Internal arc withstand (in accordance with IEC 62271-200): b SM6 24 kV: v 12.5 kA 1 s, IAC: A-FL v 16 kA 1 s, IAC: A-FLR & IAC: A-FL v 20 kA 1 s, IAC: A-FLR & IAC: A-FL b SM6 36 kV: v 16 kA 1 s, IAC: A-FL. Protection index: b Classes: PI (insulating partition) b Loss of service continuity classes: LSC2A b Units in switchboard: IP3X b Between compartments: IP2X for 24 kV, IP2XC for 36 kV b Cubicle: IK08 for 24 kV, IK07 for 36 kV. Electro-magnetic compatibility: b Relays: 4 kV withstand capacity, as per recommendation IEC 60801.4 b Compartments: v electrical eld: - 40 dB attenuation at 100 MHz - 20 dB attenuation at 200 MHz v magnetic eld: 20 dB attenuation below 30 MHz. Temperatures: The cubicles must be stored and installed in a dry area free from dust and with limited temperature variations. b For stocking: from 40C to +70C b For working: from 5C to +40C b Other temperatures, consult us.

AMTED398078EN

23

General characteristics

Factory-built cubicles description


Cubicles are made up of 3 (*) compartments and 2 cabinets that are separated by metal or insulating partitions.

DE58646

Switch and fuse protection cubicles


2 1 5 4 1 switchgear: switch-disconnector and earthing switch in an enclosure lled with SF6 and satisfying sealed pressure system requirements. 2 busbars: all in the same horizontal plane, thus enabling later switchboard extensions and connection to existing equipment. 3 connection: accessible through front, connection to the lower switch-disconnector and earthing switch terminals (IM cubicles) or the lower fuse-holders (PM and QM cubicles). This compartment is also equipped with an earthing switch downstream from the MV fuses for the protection units. 4 operating mechanism: contains the elements used to operate the switchdisconnector and earthing switch and actuate the corresponding indications (positive break). 5 low voltage: installation of a terminal block (if motor option installed), LV fuses and compact relay devices. If more space is required, an additional enclosure may be added on top of the cubicle.
Options: please, refer to the chapter Characteristics of the functional units.
(*) 2 compartments for 36 kV

DE58647

SF6 circuit breaker cubicles


1 switchgear: disconnector(s) and earthing switch(es), in enclosures lled with SF6 and satisfying sealed pressure system requirements. 2 1 5 4 2 busbars: all in the same horizontal plane, thus enabling later switchboard extensions and connection to existing equipment. 3 connection and switchgear: accessible through front, connection to the downstream terminals of the circuit breaker. Two circuit breaker offers are possible: b SF1: combined with an electronic relay and standard sensors (with or without an auxiliary power supply b SFset: autonomous set equipped with an electronic protection system and special sensors (requiring no auxiliary power supply). 4 operating mechanism: contains the elements used to operate the disconnector(s), the circuit breaker and the earthing switch and actuate the corresponding indications. 4 5 low voltage: installation of compact relay devices (Statimax) and test terminal boxes. If more space is required, an additional enclosure may be added on top of the cubicle.
Options: please, refer to the chapter Characteristics of the functional units.

24

AMTED398078EN

General characteristics

Factory-built cubicles description


Frontal vacuum type circuit breaker cubicles

DE58648

2 1

5 4

1 switchgear: load break switch and earthing switch(es), in enclosure lled with SF6 and satisfying and one vacuum circuit breaker, sealed pressure system requirements. 2 busbars: all in the same horizontal plane, thus enabling later switchboard
extensions and connection to existing equipment.

3 connection and switchgear: accessible through front, connection to the downstream terminals of the circuit breaker. b Evolis: device associated with an electronic relay and standard sensors (with or without auxiliary source). 4 operating mechanism: contains the elements used to operate the disconnector(s), the circuit breaker and the earthing switch and actuate the corresponding indications. 5 low voltage: installation of compact relay devices (VIP) and test terminal boxes.
If more space is required, an additional enclosure may be added on top of the cubicle. Options: please, refer to the chapter Characteristics of the functional units.

DE58649

Lateral vacuum type circuit breaker cubicles


2 1 5 4 1 switchgear: disconnector(s) and earthing switch(es), in enclosure lled with SF6 and satisfying and one vacuum circuit breaker, sealed pressure system requirements. 2 busbars: all in the same horizontal plane, thus enabling later switchboard
extensions and connection to existing equipment.

3 connection and switchgear: accessible through front, connection to the downstream terminals of the circuit breaker. b Evolis: device associated with an electronic relay and standard sensors (with or without auxiliary source). 4 operating mechanism: contains the elements used to operate the disconnector(s), the circuit breaker and the earthing switch and actuate the corresponding indications. 5 low voltage: installation of compact relay devices (VIP) and test terminal boxes.
If more space is required, an additional enclosure may be added on top of the cubicle. Options: please, refer to the chapter Characteristics of the functional units.

Contactor cubicles
DE58650

1 switchgear: disconnector and earthing switch and contactor in enclosures lled with SF6 and satisfying sealed pressure system requirements. 2 1 2 busbars: all in the same horizontal plane, thus enabling later switchboard 5 4
extensions and connection to existing equipment.

3 connection and switchgear: accessible through front. This compartment is also equipped with an earthing switch downstream. The contactor may be equipped with fuses. 4 types may be used: b R400 with magnetic holding b R400D with mechanical latching b Vacuum with magnetic holding b Vacuum with mechanical latching. 4 operating mechanism: contains the elements used to operate the disconnector(s), the contactor and the earthing switch and actuate the corresponding indications.

5 low voltage: installation of compact relay devices and test terminal boxes.
With basic equipment, an additional enclosure is added on top of the cubicle. Options: please, refer to the chapter Characteristics of the functional units.

AMTED398078EN

25

General characteristics

Compartments description

DE53507

61007N

Busbar compartment
The three insulated busbars are parallel-mounted. Connection is made to the upper pads of the enclosure using a eld distributor with integrated captive screws. Ratings 400 (for 24 kV only) - 630 - 1250 A.

DE53508

61006N

Switch compartment
This compartment is separated from the busbar compartment and the connection compartment by the enclosure surrounding the switch, the disconnector and the earthing switch.

DE57172

Connection and switch compartment


The network cables are connected: b To the terminals of the switch b To the lower fuse holders b Or to the connection pads of the circuit breaker. Cables may have either: b Cold tted cable end for dry-type With basic equipment, the maximum allowable cross-section for cable is: b 630 mm2 or 2 x 400 mm2 for 1250 A incoming or outgoing units b 240 mm2 or 2 x 240 mm2 for incoming or outgoing units 400 - 630 A b 95 mm2 for transformer protection cubicles incorporating fuses.
SF6 and vacuum lateral type circuit breaker

See in fonctional units characteristics chapter for each unit allowable section. The earthing switch must be closed before the cubicle may be accessed. The reduced depth of the cubicle makes for easy connection of all phases. A stud incorporated in the eld distributor makes it possible to position and secure the cable-end lug with a single hand.

DE53510

Frontal vacuum type circuit breaker

26

AMTED398078EN

General characteristics

Compartments description

DE57173

PE57230

Operating-mechanism cover
These covers contain the various operating functions for the: b switch and earthing switch b disconnector(s) b circuit breaker b contactor and the voltage presence indicator. The operating-mechanism cover may be accessed with the cables and busbars energised and without isolating the substation. It also enables easy installation of padlocks, locks and standard LV accessories (auxiliary contacts, trip units, motors, etc.).

A - LV cover B - LV wiring duct h = 1600 mm h = 1690 mm


PE57153

C - LV control cabinet h = 2050 mm

Low-voltage monitoring control cabinet for 24 kV


It enables the cubicle to be equipped with low voltage switchgear providing protection, control, status indication and data transmission. According to the volume, it is available in 3 versions: cover, wiring duct and cabinet. A - LV cover: enables a very simple low voltage section to be installed such as indication buttons, push buttons or protection relays. The total height of the cubicle is then 1600 mm. B - LV wiring duct and cabinet: enables a large majority of low voltage congurations to be installed. It also takes the Sepam series 20 or series 40. The total cubicle height is then 1690 mm. C - LV control cabinet: this is only used for larger low voltage accessories or those with a depth greater than 100 mm or complex equipment, such as Sepam series 60 or series 80, converters, control and monitoring units, regulating transformers or dual secondary transformers. The total height of the cubicle then becomes 2050 mm. In all cases, these volumes are accessible, with cables and busbars energised, without de-energising the substation.
450 mm
DE57195 DE59695

C B A

A - LV cover h = 2250 mm
PE58270

Low-voltage monitoring control cabinet for 36 kV


A - LV cover: enables a very simple low voltage section to be installed such as indication buttons, push buttons or protection relays. The total height of the cubicle is then 2250 mm. B - LV control cabinet: this is only used for larger low voltage accessories or those with a depth greater than 100 mm or complex equipment, such as Sepam series 60 or series 80, converters, control and monitoring units, regulating transformers or dual secondary transformers. In all cases, these volumes are accessible, with cables and busbars energised, without de-energising the substation. AB

1500 mm 1615 mm

AMTED398078EN

27

General characteristics

Safety of people
By switchgear

61010N

Switch or disconnector and earthing switch


b Gas tightness The three rotating contacts are placed in an enclosure lled with gas to a relative pressure of 0.4 bar (400 hPa) for 24 kV and 1 bar (1000 hPa) for 36 kV. It satises sealed pressure system requirements and seal tightness is always factory checked, and leakage rate is less than 0.1% for 30 years life span. b Operating safety v the switch may be in one of three positions: closed, open, or earthed, representing a natural interlocking system that prevents incorrect operation. Moving-contact rotation is driven by a fast-acting mechanism that is independent of the action of the operator. v the device combines the breaking and disconnection functions. v the earthing switch placed in the SF6 has a short-circuit making capacity, in compliance with standards. v any accidental over-pressures are eliminated by the opening of the safety membrane, in which case the gas is directed toward the back of the unit, away from the operator.
MT20184

Switch-disconnector for 24 kV
PE57226

Switch-disconnector for 36 kV

Closed position

Open position

Earth position

b Insensitivity to the environment v parts are designed in order to obtain optimum electrical eld distribution. v the metallic structure of cubicles is designed to withstand and aggressive environment and to make it impossible to access any energised part when in operation.

61011N

Rollarc 400 and 400D contactor


b Gas tightness The three phases are placed in an enclosure lled with SF6 gas to a relative pressure of 2.5 bars (2500 hPa). It satises sealed pressure system requirements and seal tightness is always checked in the factory. b Operating safety Accidental over-pressures are eliminated by the opening of the safety membrane.
DE53513

Rollarc contactor

Contacts closed

Main contacts separated

Arcing period

Contacts open

28

AMTED398078EN

General characteristics

Safety of people
By switchgear

61012N

SF6 circuit breaker: SF1


b Gas tightness The SF1 circuit breaker is made up of three separate poles mounted on a structure supporting the operating mechanism. Each pole-unit houses all the active elements in an insulating enclosure lled with gas to a relative pressure of 0.5 bar (500 hPa) for 24 kV and 2 bar (2000 hPa) for 36 kV. It satises sealed pressure system requirements and seal tightness is always checked in the factory. b Operating safety Accidental over-pressures are eliminated by the opening of the safety membrane.
DE53514

SF1 circuit breaker

61058N

Contacts closed

Precompression

Arcing period

Contacts open

Evolis circuit breaker

Vacuum type circuit breaker: Evolis


b Vacuum tightness The Evolis circuit breaker comprises three separate pole units xed on a structure supporting the control mechanism. Each pole encloses all of the active parts in an insulating enclosure, under vacuum, and its vacuum tightness is systematically checked in the factory. b Operating safety The magnetic eld is applied along the contact axis of the vacuum type circuit breaker. This process diffuses the arc in a regular manner with high currents. It ensures optimum distribution of the energy along the compact surface so as to avoid local hot spots. The advantages of this technique: v a simplied vacuum type circuit breaker which is consequently very reliable, v low dissipation of arcing energy in the circuit breaker, v highly efcient contacts which do not distort during repeated breaking, v signicant reduction in control energy.

PE50798

Evolis lateral version

Vacuum type contactor


b Vacuum tightness Vacuum contactor comprises three separate poles xed on a structure supporting the control mechanism. Each pole encloses all of the active parts in an insulating enclosure under vacuum and its vacuum tightness is checked in the factory.
PE57841

Vacuum type contactor

AMTED398078EN

29

General characteristics

Safety of people
By operating mechanism safety

PE57230

Reliable operating mechanism


b Switchgear status indicator: Fitted directly to the drive shaft, these give a denite indication of the contacts position. (appendix A of standard IEC 62271-102). b Operating lever: This is designed with an anti-reex device that stops any attempt to re-open the device immediately after closing the switch or the earthing disconnector. b Locking device: Between one and three padlocks enable the following to be locked: v access to the switching shaft of the switch or the circuit breaker, v access to the switching shaft of the earthing disconnector, v operating of the opening release push-button.

Simple and effortless switching


Mechanical and electrical controls are side by side on the front fascia, on a panel including the schematic diagram indicating the devices status (closed, open, earthed): b Closed: the drive shaft is operated via a quick acting mechanism, independent of the operator. No energy is stored in the switch, apart from when switching operations are taking place. For combined switch fuses, the opening mechanism is armed at the same time as the contacts are closed. b Opening: the switch is opened using the same quick acting mechanism, operated in the opposite direction. For circuit breakers and the combined switch fuses, opening is controlled by: v a push-button, v a fault. b Earthing: a specic control shaft enables the opening or closing of the earthing contacts. Access to this shaft is blocked by a cover that can be slid back if the switch is open but which remains locked in place if it is closed.

PE57231

Visibility of main contacts

Visibility of main contacts (option)


The position of main contacts is clearly visible from the front of the cubicle through the window.

PE57166

Gas pressure indicator (option)


Despite SM6 switch is sealed pressure system and has open and close capacity on rated current at 0 bar relative pressure SF6, to insure you about the internal pressure, we propose on request before sale or on site by after-sales either a pressure switch or an analog manometer on the switch. These devices are both tted without any alteration on the switch, they are temperature compensated and compatible with visibility of main contacts if requested.

PE56366

Voltage Presence Indicating System


VPIS complies with IEC 61958 and 62271-206 standard allowing to indicate the voltage presence on each phase with LEDs. Designed for harsh environments so that to guarantee high reliability in MV/LV susbstations worldwide. Exits in Voltage Output version to provide voltage presence information to VD23 voltage presence relay.

30

AMTED398078EN

General characteristics

Safety of people
By internal arc protection

Standard IEC 62271-200 appendix A indicates a method for testing switchgear in metal enclosures under internal arc conditions. The aim of this test is to show that an operator situated in front of a switchboard would be protected against the effects of an internal fault.

To enhance the safety of people, it is desirable to provide as high a degree of protection as possible by evacuating the effects of internal arc using: b Evacuation systems which direct gases towards the top or the bottom of the switchboard enabling over pressure to be limited in the case of an internal fault in the compartments b Channelling and evacuating hot gases towards an external area, which is not hazardous for the operator b Materials which are non-inammable in the cubicles b Reinforced panels.

Consequently:
The SM6 is designed to offer a good level of safety b Control of the architecture: v compartment type enclosure.
DE59732

b Technological control: v electrotechnical: modelling of electrical elds, v mechanical: parts produced using CAD systems. b Use of reliable components: v choice of materials, v earthing switch with closing capacity. b v v v
Example of installation of an SM6 switchboard installed against the wall downwards exhaust 12.5 kA 1 s and 16 kA 1 s, IAC: A-FL: 3-sides internal arc protection

Devices for total operating safety: voltage presence indicator on the front face, natural reliable interlocking, locking using keys or padlocks.

Internal arc withstand (in conformity with IEC 62271-200)


b v v v
DE59734

3 versions are available for SM6 24 kV: 12.5 kA 1 s, IAC: A-FL 16 kA 1 s, IAC: A-FLR & IAC: A-FL 20 kA 1 s, IAC: A-FLR & IAC: A-FL

b 1 version is available for SM6 36 kV: v 16 kA 1 s, IAC: A-FL.

SM6 internal arc (in conformity with IEC 62271-200 appendix A)


In all internal arc versions, the SM6 has successfully passed all of the type testing relative to standard IEC 62271-200 (5 acceptance criteria). The materials used meet the constraints for which the SM6 is designed. The thermal and mechanical forces that an internal arc can produce are perfectly absorbed by the enclosure. An operator situated in front of the SM6 switchboard during an internal fault will not be exposed to the effects of arcing.

Example of installation of an SM6 24 kV switchboard installed in the middle of a room downwards exhaust 16 kA 1 s, IAC: A-FLR: 4-sides internal arc protection

SM6 proposes several options to install a standard internal arc withstand switchboard
b 3-sides internal arc protection IAC: A-FL, 12,5 kA 1 s and 16 kA 1 s for 24 kV and 16 kA 1 s for 36 kV. SM6 switchboard positioned against the wall, access to the rear of the cubicles is impossible, internal arc protection on three sides is sufcient. b 4-sides internal arc protection IAC: A-FLR, 16 kA 1 s and 20 kA 1 s for 24 kV. For SM6 switchboards installed in the middle of a room, 4-sides internal arc protection is necessary in order to protect an operator moving around the switchboard. b Choice of exhaust: (Installation requirements manual to be considered) v downwards exhaust Civil engineering with an adequate volume is necessary. v upwards exhaust for 24 kV A ceiling height greater or equal than 2 150 mm is necessary, duct at the right or left side of the cubicle (not supplied).
DE57174

Example of installation of an SM6 24 kV switchboard installed in the middle of a room upwards exhaust 16 kA 1 s and 20 kA 1 s, IAC: A-FLR: 4-sides internal arc protection

AMTED398078EN

31

General characteristics

MV electrical network management


Easergy T200 S for 24 kV
Easergy T200 S for NSM cubicle
Easergy T200 S is a simplied MV substation control unit for secondary distribution networks enabling remote control of one or two MV substation switches. T200 S, a version of the T200 unit, is integrated in the SM6 cubicle LV control cabinet. It is limited to control 2 switches. It is intended for remote control applications for source transfer switching and back up generator set switching in NSM cubicle. Easergy T200 S a multifunctional plug and play interface which integrates all functions required for remote monitoring and control of MV substations: b Acquisition of various data types: switch position, fault detectors, current values, etc. b Transmission of opening and closing orders to the switches b Exchange with the control center. Particularly used during network incidents, Easergy T200 S has proven its reliability and availability to be able to operate the switchgear at all times. It is easy to implement and operate.

PE15074

Easergy T200 S for 24 kV: remote control interface in LV control cabinet

Functional unit dedicated to Medium Voltage applications


Easergy T200 S is installed in the low voltage control cabinet of NSM cubicles for remote control of one or two switches. Easergy notably enables source transfer switching between two switches. It has a simple panel for local operation to manage electrical controls (local/remote switch) and to display switchgear status information. It integrates a fault current detector (overcurrent and zero sequence current) with detection thresholds congurable channel by channel (threshold and fault duration).
PE56421 PE56423

Plug and play and secure


Integrated in the low voltage control cabinet of an MV-equipped cubicle, it is ready to connect to the data transmission system. Easergy T200 S has been subject to severe tests on its resistance to MV electrical constraints. A back-up power supply guarantees several hours continuity of service for the electronic devices, motorization and MV switchgear. Current transformers are of split core type for easier installation.

Control command
PE15078

Back up power supply

Compatible with all SCADA remote control systems


Easergy T200 S supplies the following standard protocols: b Modbus serial and IP b DPN3 serial and IP b IEC 870-5-101 / 104. Data transmission system standards are: RS232, RS485, PSTN, FSK, FFSK, GSM/GPRS. Other systems are available on request, the radio frequency emitter/receiver is not supplied.

Split core CTs

32

AMTED398078EN

General characteristics

MV electrical network management


Easergy T200 I
Easergy T200 I: an interface designed for control and monitoring of MV networks
Easergy T200 I is a plug and play or multifunction interface that integrates all the functional units necessary for remote supervision and control of the SM6: b Acquisition of the different types of information: switch position, fault detectors, current values... b Transmission of switch open/close orders b Exchanges with the control center. Required particularly during outages in the network, Easergy T200 I is of proven reliability and availability, being able to ensure switchgear operation at any moment. It is simple to set up and to operate.

PE56311

Functional unit designed for the Medium Voltage network


b Easergy T200 I is designed to be connected directly to the MV switchgear, without requiring a special converter. b It has a simple front plate for local operation, which allows management of electrical rating mechanisms (local/remote switch) and display of information concerning switchgear status. b It has an integrated MV network fault current detection system (overcurrent and zero sequence) with detection set points that can be congured channel by channel (current value and fault current duration).

PE56421

PE56422

Medium Voltage switchgear operating guarantee


b Easergy T200 I has undergone severe MV electrical stress withstand tests. b It is a backed up power supply which guarantees continuity of service for several hours in case of loss of the auxiliary source, and supplies power to the Easergy T200 I and the MV switchgear motor mechanisms. b Ready to plug v Easergy T200 I is delivered with a kit that makes it easy to connect the motor mechanisms and collect measurements. v the connectors are polarized to avoid any errors during installation or maintenance interventions. v current measurement acquisition sensors are of the split type, to facilitate their installation. v works with 24 Vdc and 48 Vdc motor units.

Local information and control


PE56423 PE56824

Monitoring and control

Compatible with all SCADA remote control systems


Easergy T200 I supplies the following standard protocols: b Modbus serial and IP b DPN3 serial and IP b IEC 870-5-101 / 104. Data transmission system standards are: RS232, RS485, PSTN, FSK, FFSK, GSM/GPRS. Other systems are available on request, the radio frequency emitter/receiver is not supplied.

Back up power supply

Polarized connectors

PE57787

Voltage detection relay


VD23 provides accurate information of presence or absence of voltage. Associated with VPIS-Voltage Output, VD23 is typically used in critical power and safety applications.
VD23

Various combinations of voltage detection are possible: b 3 Ph-N and residual voltage: V1 + V2 + V3 + V0 b 3 Ph-N or Ph-Ph voltage: V1 + V2 + V3 or U12 + U13 + U23 b 1 Ph-N or Ph-Ph or residual voltage: V1, V2, V3, U12, U13, U23, V0. VD23 can display the MV network voltage (in % of service voltage), activate the relay output R1 to monitor a loss of voltage on 1 phase at least and active the relay output R2 to monitor a presence of voltage on 1 phase at least. b Auxilary power supply: from 24 to 48 Vdc b Assembly: compact DIN format, mounted in the same place as fault passage indicator (format DIN, integrated in switchgear), terminal connexion tted with VPIS-Voltage Output b Compatible with all neutral earthing systems.

AMTED398078EN

33

General characteristics

MV electrical network management


Automation systems

DE40552EN

Current Execution time

Easergy T200 automation systems are factory predened. No on-site programming is required. b The automation systems can be switched on and off from the local operator panel and disabled using the congurator.
Voltage drop

b Switches can be controlled manually in the following circumstances: v automation system switched off v switch in local mode.

Sectionaliser (SEC)
Time b Congurable parameters: v Number of faults: from 1 to 4 v Execution time: from 20 s to 4 mins congurable in 5 s steps v Automation system valid/invalid.
DE59320EN

The sectionaliser automation system opens the switch after a predened number of faults (1 to 4) during the voltage dip in the reclosing cycle of the top circuit breaker. b The automation system counts the number of times a fault current followed by a voltage loss is detected. It sends an open order if: v the switch is closed v the fault has disappeared v the MV supply is absent. b The automation system is reset at the end of the execution time delay.

Vn SW2 voltage O Vn O C O C O TR SW2 T1 TR SW1 TR

SW1 voltage

ATS automatic transfer system (source changeover)


The automatic transfer system performs automatic control and management of sources in the MV secondary distribution network. Network ATS version: control of two MV network channels. The network ATS automatic transfer system requires use of the VD23 relay for detection of voltage presence/absence. Generator ATS version: control of one network channel and one generating set channel (not available on T200 E). Note: ATS automatic transfer system is available only on channels 1 and 2 of each CONTROL module. Generator ATS automatic transfer system is available only on the rst CONTROL module (channels 1 to 4).
TR
DE56654

Two possible versions for ATS:

T1 TR

SW1

SW2

Network ATS - Semi-Auto Mode (without paralleling upon automatic return) TR: switch response time Vn O C O C O T1 TR SW1 T2 SW1 voltage

Operating modes
The operating mode is selected from the T200 Web server.
TR

TR

SW2

Mode SW1VSW2 or SW2VSW1 (or SWVSWG if Generator ATS): Automatic transfer system executes only one changeover from the priority channel to the backup channel. Automatic transfer system then remains on that channel. Semi-Auto mode SW1XVSW2 (or SWXVSWG if Generator ATS): In the event of a voltage loss on the active channel, automatic transfer system switches to the other channel after a time delay T1. Automatic transfer system executes no return, except in case of voltage loss on the new active channel. Auto SW1 or Auto SW2 mode (or Auto SW if Generator ATS): After a changeover, return to the priority channel occurs if the MV voltage on that channel is restored. The channel that has priority can be dened according to the state of a dedicated digital input.
Tg2

Network ATS - Auto Mode SW1 (with paralleling upon automatic return) TR: switch response time
DE59321EN

Vn 0 1 0 Vg 0 C O C O C O

SW1 voltage

T1

GE Command Tg1

6s

GE voltage

Changeover sequences:
Network ATS: in the event of voltage loss on the normal channel, changeover involves opening the normal channel after time delay T1 and then closing the backup channel. Note: in Auto mode, the sequence of return to the normal channel depends on conguration of the Paralleling upon auto return option (see below). Generator ATS: in the event of voltage loss on the network channel, changeover involves sending the order for opening the network channel and at the same time the Generator start-up order, after time delay T1. The remainder of the changeover sequence depends on the management of Generator channel closing (congurable option): b Case of Generator channel closing after start-up order: After the Generator start-up order, the closing order is given to the Generator channel, without waiting until the Generator is actually started. b Case of Generator closing after Generator power on: The Generator channel closing order is sent only when Generator voltage is detected.

TR

TR

SW

TR TR

T2 TR T2 TR

SWG

SWG

Generator ATS - Auto SW mode (Without paralleling upon Auto return) TR: Switch response time Tg1: Generator starting time (maximum 60 s) Tg2: Generator stopping time Case : Generator channel closing after Generator power on (congurable option) Case : Generator channel closing after Generator start-up command (congurable option)

34

AMTED398078EN

General characteristics

MV electrical network management


Automation systems

Congurable parameters: b Automatic transfer system ON/OFF b Operating mode: Semi-Auto, Auto SW1, Auto SW2, SW1 > SW2, SW2 > SW1 b T1: 0 ms to 2 min. in increments of 100 ms b T2: 0 s to 30 min. in increments of 5 s b Disabling/enabling transfer upon fault detection: b Choice of voltage presence detection: DI4 or VD23 b Channel connected to generator: SW1 or SW2 b Type of automatic transfer system: Network ATS or Generator ATS b Manual control enabled/disabled if ATS in operation b Paralleling enabled/disabled in auto and/or manual mode b Choice of type of changeover to Generator: immediately or after detection of Generator power on

Paralleling upon Auto return


A software-congurable option allows the automatic transfer system to disable or enable paralleling of the channels upon automatic return to the main channel (in Auto mode). Enabling of paralleling must be conrmed by the activation of a dedicated digital input. Paralleling disabled: Auto return to the priority channel involves opening the backup channel and, when it is open, closing the priority channel. Paralleling enabled: Auto return to the priority channel involves rst closing the priority channel and, when it is closed, opening the backup channel.

Changeover conditions
Changeover takes place if the following conditions are met: b Automatic transfer system in operation b SW1 open and SW2 closed or SW1 closed and SW2 open b Absence of fault current on the two channels (only if locking by fault detection option activated) b Transfer locking absent b Earthing switch absent on the two channels b MV voltage absent on the active channel b MV voltage present on the other channel. Return to the main channel for the Auto modes occurs if: b The priority channel is open b The MV voltage on the priority channel is present during time delay T2.

DE59175

DI 1 DI 2 Priority channel Genset voltage presence Parallel connection input Genset forcing The DIs can be assigned for ATS automation (congurable options) DI 3 DI 4 DI 5 DI 6

1 2 3 4 5 6 7 8 9 10 11 12

Generating set connections


Relays are installed in factory in the T200 enclosure to provide interfacing with the generating set (Generator ATS version only). Connection should be performed as follows (see diagram opposite): b Voltage: contact closed if Generator started, to be wired on the two available terminals (do not wire if detection of power on is performed by a relay VD23) b Start-up: Generator start-up order, to be wired on terminals C and B b Stop: Generator stoppage order, to be wired on terminals D and B.

Digital Input connection (J2 or J10 terminal block)

DE56806

Detection of voltage presence


Voltage presence on a channel managing the Generator can be executed by two processes: b Either by a dedicated Voltage digital input b Or by voltage relay VD23 (via cubicle cable).
Terminal block T200
C D C D

Override setting on generator (Generator ATS only)


For routine test or reduced pricing requirements, it is possible to perform override setting of operation on the generator manually, remotely (from the supervisor) or locally (activation by a dedicated digital input). When the override setting is terminated, the automatic transfer system places itself back in the initial mode, i.e. in the mode that was active before the override setting (ON or OFF). During override setting, the automatic transfer system is set to ON for channels 1 and 2.

Source transfer locking


Voltage Stop Start-up Genset

A dedicated digital input allows changeover to be locked if a problem occurs on one of the devices related to the changeover. This input is generally connected to the downstream circuit breaker. Local and remote controls are no longer possible in this case.

Specic Generator-related management


Generator Stop Start started generator generator contact order order Interface with the generating set

DE59173

b Upon transfer to the Generator, if the latter doesnt start, the automatic transfer system waits for a period of 60 s at most before stopping changeover, then: v in SW > SWG mode: the automatic transfer system is locked and must be reset (on the Control panel) to restart the device. v in SW <> SWG mode or in Auto mode: the automatic transfer system remains operational. If voltage returns to the network channel, the automatic transfer system requests return to the network channel.
1 2 3 4 +5 6

Source transfer locking DO 1 Stop/start generator order

b When the automatic transfer system is congured with auto return on the network channel, Generator stoppage is requested 6 s after the changeover sequence is completed.

Lock connection (J1 terminal block on the 4-ways interface or J9 on the 2-ways interface)

AMTED398078EN

35

General characteristics

MV electrical network management


Automation systems
Bus tie coupling (BTA) with T200 I

DE56655

SW1

SW3

SW2

The BTA (Bus Tie Automatism) is an automation system for switching sources between two incoming lines (SW1 and SW2) and a busbar coupling switch (SW3). It must be used in conjunction with VD23 type voltage presence detectors and the fault current detection function on the busbar incoming lines.

Operating mode
Normal position

SW1

SW3

SW2

Two operating modes can be congured: b Standard mode: If the voltage is lost on one busbar, the automation system opens the incoming line (SW1 or SW2) and closes the coupling switch SW3. Coupling is conditional upon the absence of a fault current on the main source. b Interlock on loss of voltage after switching mode: After execution of the automation system in standard mode, the voltage presence is checked for a congurable period. If the voltage is lost during this period, the coupling switch SW3 is opened and the automation system interlocked.

Coupling sequence
b Coupling takes place if the following conditions are met: v the automation system is switched on v the switches on incoming channels SW1 and SW2 are closed v the earthing switches SW1, SW2 and SW3 are open v there is no voltage on an incoming line SW1 or SW2 v there is no fault current detection on SW1 and SW2 v there is no transfer interlock v voltage is present on the other incoming line. b The coupling sequence in standard mode is as follows: v opening of the de-energised incoming line switch after a delay T1 v closing of the coupling switch SW3. b The coupling sequence in Interlock on loss of voltage after coupling mode i s completed as follows: v monitoring of the voltage stability for a delay T3 v opening of the coupling switch SW3 if this condition is not met v locking of BTA automation system. b The system returns to standard mode after coupling if: v the return to SW1 or SW2 option is activated v voltage on the channel has been normal for a delay T2 v the automation system is activated v the automation system is not locked v there is no coupling interlock.

Active coupling

DE59322EN

V2 V1 O C O C O

SW2 voltage

SW1 voltage

T1

SW1 T3 SW3 T2

Congurable parameters: b Operating mode: Standard/locking upon voltage loss b Automatic return: SW1/SW2 b Automation system: on/off b Delay before switching T1: 100 ms to 60 s in 100 ms steps b Delay before return T2: 5 s to 300 s in 1 s steps b Interlock delay on voltage loss T3: 100 ms to 3 s in 100 ms steps b Motorisation type: command time b Manual control: enabled/disabled in local and remote modes if automation system in operation b Paralleling: enabled/disabled in auto and (or) manual modes b Transfer locking upon fault detection.

Coupling interlock
A dedicated digital input allows changeover to be locked if a problem occurs on one of the devices related to the changeover. This input is generally connected to the downstream circuit breaker. Local and remote controls are no longer possible in this case. Locking the automation system The BTA automation system is locked if one of the following conditions is met during the coupling process: b Failure of a command to open or close a switch b Indication that an earthing switch has closed b Appearance of a fault current b Switch power supply fault b Appearance of the coupling interlock b Manual or remote ON/OFF command from the automation system.

Paralleling upon Auto return


A software-congurable option allows the automation system to disable or enable paralleling of the channels upon automatic return to the main channel (in Auto mode). Enabling of paralleling must be conrmed by the activation of a dedicated digital input. If paralleling is disabled: Auto return to the normal channel involves opening the coupling channel (SW3) and, when it is open, closing the normal channel. If paralleling is enabled: Auto return to the normal channel involves rst closing the normal channel and, when it is closed, opening the coupling channel (SW3).

36

AMTED398078EN

General characteristics

Fault indicators

Easergy Flair is a comprehensive range of underground network fault current indicators

Easergy MV underground network fault current passage indicators are a range of products adapted to all neutral earthing systems: insulated, impedant and direct earthing. b Easergy Flair 21D-22D-23DV, are self-powered with a liquid crystal display, with DIN dimensions for MV cubicle installation. b Easergy Flair 279 and 219, have a wall-mounted case for the MV cubicles substation or LV compartment and an external power supply which can be backed up (Li battery or LV supply + Li battery in LV compartment). b Easergy Flair 200C is a communicating Fault passage Indicator with advanced measurement functions and Modbus master port for data concentration.

PE57784

PE57922 PE57921

Easergy Flair Application Installation Power supply Fault detection Indication

21D - 22D - 23DV

279 - 219

200C + compensated

Underground MV networks, isolated, impedant and solidly earthed Flush mounted Self-powered or dual power Led and LCD display + optional external light indicator Current, frequency Dry output contact Dry output contact Wall-mounted 230 Vac and / or Li battery External light indicator Wall-mounted 230 Vac and rechargeable battery External light indicator (option) Current, voltage, power Modbus, DNP3, IEC101&104, GMS, GPRS and others

Phase-phase and phase-earth for all 3 ranges

Measurement Communication

PE57232

Easergy Flair 21D - 22D - 23DV


SM6 can integrate Flair 21D, Flair 22D and Flair 23DV on every incoming cubicles. b High performance indicators v indication of phase-phase and phase-earth faults, v faulty phase indication, v compatible with HV/MV substation protection devices. b Clear and comprehensive display v displaying the faulty phase for earth fault, v displaying settings, v displaying the load current including peak demand and frequency meter. b Maintenance free.
Display of settings Automatic fault detection calibration mode Short-circuit fault thresholds Earth fault thresholds Fault acknowledge time Type of CT (CT1 or CT2) Time delay for resetting upon current return (or voltage return on Flair 22D and Flair 23DV) Time delay for fault resetting Time delay for fault conrmation Inrush time delay Phase at fault and measurements Phase at fault Load current MV network frequency Current maximeter Residual current Flair 21D b b b b b Flair 22D b b b b b b b b b L1-L2-L3 b 50/60 Hz b b L1-L2-L3 b 50/60 Hz b b Flair 23DV b b b b b b b b b L1-L2-L3 b 50/60 Hz b b

AMTED398078EN

37

General characteristics

Ammeter

b At the leading edge of technology, Amp 21D is suitable for Medium Voltage network load management. b Self-powered, it ensures a permanent display of currents. b Compact and in DIN format, it ts naturally into MV cubicles. b Cost efcient, it uses the CT optimised for Fault Passage Indicator. b Performant, it displays phase current and maximum of current.

Functions
b Display of 3 phase current: I1 , I2 , I3. Range: 3 A to 630 A b Display of 3 phase current maximeter: I1 , I2 , I3. Range: 3 to 630 A.

Display principle
b v b v v v Load curents are permanently displayed continuous scrolling of L1, then L2, then L3. Maximeter access to maximeter display by pressing a dedicated push button continuous scrolling of M1, then M2, then M3 reset of all maximeter by pressing a combination of two push buttons.

Connections, assembly
Small size enclosure b DIN format: 93 x 45 mm b Secured, extraction-proff mounting b Terminal connections.

PE57786

Current sensors b Split core CT for mounting on MV cables.

Technical data
Application Frequency Load current Measurement Range Amp 21D Reset of maximeter Power supply Self power Battery Auxiliary supply Display L1 L2 L3 Sensors Phase CTs Miscellaneous Test
PE57233

Minimum current Phase current Accuracy (I < 630 A) Manual from device From the current sensors

50 Hz and 60 Hz 3A 3 to 630 A (resolution 1 A) (2% + 2 digit) Yes I load 3 A No No 4 digits LCD Yes (resolution 1 A) Yes 3 split core CT Yes

DE58404

Display Current per phase Maximeter per phase

The SM6 can integrate ammeter Amp 21D on all incoming cubicles and the fuse-switch cubicles

38

AMTED398078EN

General characteristics

Protection and control monitoring


Sepam selection guide for all applications

The Sepam range of protection and metering is designed for the operation of machines and electrical distribution networks of industrial installations and utility substations for all levels of voltage. It consists of complete, simple and reliable solutions, suited to following ve families: Sepam series 10, 20, 40, 60 and 80. A range adapted at your application
b Protection of substation (incoming, outgoing line and busbars). b Protection of transformers. b Protection of motors, and generators.

Series 10

Series 20

Protections
Current Voltage Frequency Specics b b b b b
Phase and earth fault overcurrent Breaker failure

Simplicity
Easy to install b Light, compact base unit. b Optional modules tted on a DIN rail, connected using prefabricated cords. b User friendly and powerful PC parameter and protection setting software to utilize all of Sepams possibilities. User-friendly b Intuitive User Machine Interface, with direct data access. b Local operating data in the users language.

b b
Disconnection by rate of change of frequency

Applications
Substation Busbar Transformer Motor Generator Capacitor 10A, 10B 10A, 10B S20 T20 M20 S24 B21 T24 B22

Accurate measurement and detailed diagnosis


b Measuring all necessary electrical values. b Monitoring switchgear status: sensors and trip circuit, mechanical switchgear status. b Disturbance recording. b Sepam self-diagnosis and watchdog.

Characteristics
Logic inputs Logic outputs Temperature sensors Channel
Current Voltage LPCT (1) 4 7 0 to 10 4 to 8 0 to 8 3 I + Io 3 I + Io 3V + Vo 0 to 10 4 to 8 0 to 8

Flexibility and evolutivity


b Enhanced by optional modules to evolve in step with your installation. b Possible to add optional modules at any time. b Simple to connect and commission via a parameter setting procedure.

b
1 1 to 2 1 to 2

Communication ports IEC61850 Protocol Control


Matrix (2) Logic equation editor Logipam (3)

b b

b b

Other
Backup battery Front memory cartridge with settings (1) LPCT: low-power current transformer complying with standard IEC 60044-8. (2) Control matrix for simple assignment of information from the protection, control and monitoring functions. (3) Logipam ladder language (PC programming environment) to make full use of Sepam series 80 functions. (4) Standard lithium battery 1/2 AA format, 3.6 V, front face exchangeable. Lithium battery (4)

AMTED398078EN

39

General characteristics

Protection and control monitoring


Sepam selection guide for all applications

Series 40

Series 60

Protections
Current Voltage Frequency Specics b b b b b b
Directional earth fault

b b b
Directional earth fault and phase overcurrent

b b b

b b b
Directional earth fault

b b b
Directional earth fault and phase overcurrent

Applications
Substation Busbar Transformer Motor Generator Capacitor S40 T40 M41 G40 G60 C60
0 to 28 4 to 16 0 to 16 3 I + Io 3V, 2U + Vo or Vnt

S41, S43

S42 T42

S60 T60 M61

S62 T62 G62

Characteristics
Logic inputs Logic outputs Temperature sensors Channel
Current Voltage LPCT (1) 0 to 10 4 to 8 0 to 16 3 I + Io 3V, 2U + Vo

b
1 to 2

b
1 to 2

Communication ports IEC61850 Protocol Control


Matrix (2) Logic equation editor Logipam (3)

b b b

b b b

Other
Backup battery Front memory cartridge with settings 48 hours Lithium battery (4)

(1) LPCT: low-power current transformer complying with standard IEC 60044-8. (2) Control matrix for simple assignment of information from the protection, control and monitoring functions. (3) Logipam ladder language (PC programming environment) to make full use of Sepam series 80 functions. (4) Standard lithium battery 1/2 AA format, 3.6 V, front face exchangeable.

40

AMTED398078EN

General characteristics

Protection and control monitoring


Sepam selection guide for all applications

Series 80

Protections
Current Voltage Frequency Specics b b b b b b
Directional earth fault

b b b
Directional earth fault and phase overcurrent

b b b
Disconnection by rate of change of frequency

b b b

b b b

b b b
Voltage and frequency protection for 2 sets of busbars

b b b
Capacitor-bank unbalance

Transformer Machine & transformer- differential machine unit differential

Applications
Substation Busbar Transformer Motor Generator Capacitor S80 B80 S81 T81 M81 S82 T82 G82 S84 B83 T87 M88 G88 M87 G87 C86
0 to 42 5 to 23 0 to 16 3 I + 2 x Io 3V + Vo 0 to 42 5 to 23 0 to 16 2 x 3 I + 2 x Io 3V + Vo 0 to 42 5 to 23 0 to 16 3 I + Io 2 x 3V + 2 x Vo 0 to 42 5 to 23 0 to 16 2 x 3 I + 2 x Io 3V + Vo

Characteristics
Logic inputs Logic outputs Temperature sensors Channel
Current Voltage LPCT (1)

b
2 to 4

b
2 to 4

b
2 to 4

b
2 to 4

Communication ports IEC61850 Protocol Control


Matrix (2) Logic equation editor Logipam (3)

b b b b
Lithium battery (4)

b b b b
Lithium battery (4)

b b b b
Lithium battery (4)

b b b b
Lithium battery (4)

Other
Backup battery Front memory cartridge with settings

(1) LPCT: low-power current transformer complying with standard IEC 60044-8. (2) Control matrix for simple assignment of information from the protection, control and monitoring functions. (3) Logipam ladder language (PC programming environment) to make full use of Sepam series 80 functions. (4) Standard lithium battery 1/2 AA format, 3.6 V, front face exchangeable.

AMTED398078EN

41

General characteristics

Protection and control monitoring


VIP 35 protection relay VIP 300 LL protection relay
VIP 35 relay for transformer protection

PE57159

Integrated in the DM1-S and DMV-S cubicles for SM6 24 kV The VIP 35 is an independent relay without an auxiliary power supply, powered by the current sensors, and actuating a Mitop release unit. VIP 35 provides protection against phase-to-phase faults and against earthing faults. Phase protection b phase protection is achieved by a denite time threshold which functions from 1.2 times the operating current (Is). Earthing protection b earthing fault protection functions with the residual current measurement taken from the sum of the secondary currents in the sensors. This is taken via a CRc, 8 A to 80 A gauge. b earthing protection is inverse denite time: its threshold and time delay can be set. Setting the VIP 35 relays Is: the phase operating current is adjusted directly in accordance with the transformer rating and the operating voltage. Io: the earth current threshold is adjusted according to the network characteristics. Setting values of the Is phase operating current for VIP 35
Operating Transformer rating (kVA) voltage (kV) 50 75 100 125 160 3 3.3 4.2 5.5 6 6.6 10 11 13.8 15 20 22 10 10 8 8* 8* 8* 8* 8* 8* 8* 8* 8* 15 15 12 8 8* 8* 8* 8* 8* 8* 8* 8* 20 18 15 12 10 10 8* 8* 8* 8* 8* 8* 25 22 18 15 12 12 8 8* 8* 8* 8* 8* 36 28 22 18 18 15 10 10 8 8* 8* 8* 200 45 36 28 22 20 18 12 12 10 8 8* 8* 250 55 45 36 28 25 22 15 15 12 10 8 8 315 68 56 45 36 36 28 20 18 15 15 10 10 400 80 70 55 45 45 36 25 22 18 18 12 12 500 115 90 70 55 55 45 30 28 22 20 15 15 630 140 115 90 68 68 56 37 36 28 25 20 18 800 170 140 115 90 80 70 55 45 36 36 25 22 1000 1250 1600 2000 2500 3150 4000 5000 6300 200 200 140 115 115 90 68 55 45 45 30 28 200 140 140 115 80 68 55 55 37 36 170 170 140 115 90 68 68 55 45 200 200 140 115 90 80 68 55 170 140 115 115 80 68 200 170 140 140 115 90 170 170 140 115 200 170 140 200 170

VIP 35

* Short-circuit protection, no over-load protection

PE57160

VIP 300 LL protection relay


Integrated in the DM1-S and DMV-S cubicles for SM6 24 kV VIP 300 provides protection against phase-to-phase and phase-to-earth faults. A choice of trip curves and the large number of possible settings mean that it can be used in a large variety of selectivity layouts. VIP 300 is an independent relay powered by the current sensors; it does not require an auxiliary power supply. It actuates a release unit. Phase protection b phase protection is via two independently adjustable thresholds: v the lower threshold can be chosen to be inverse denite time or denite time. The denite time curves are in conformity with IEC standard 60255-3. They are either of inverse, very inverse or extremely inverse type. v the upper threshold is inverse denite time. Earthing protection b protection against phase-to-earth faults uses the residual current measurement, taken from the sum of the secondary currents in the sensors. This is taken via a CRa X1 gauge: 10 to 50 A and X4: 40 to 200 A or via a CRb X1 gauge: 63 to 312 A and X4: 250 A to 1250 A. b as for phase protection, phase-to-earth protection had two thresholds that can be independently set. Signalling b two indicators show the origin of the trip operation (phase or earth). They remain in position after the relay power supply has been cut. two led indicators (phase and earth) show that the lower threshold has been exceeded and that its time delay is currently in progress.

VIP 300 LL

42

AMTED398078EN

General characteristics

Protection and control monitoring


Sepam series 10 with CRa/CRb sensors

Sepam series 10 with CRa/CRb sensors for transformer protection


Integrated in the DM1-S cubicle for SM6 24 kV with CRa and CRb sensors and DM1-A cubicle for SM6 36 kV with normal CTs Sepam series 10 monitors phase and/or earth-fault currents. Two models meet a wide range of different needs: b 10B: Sepam series 10B protects against overloads, phase-to-phase faults and earth faults. b 10A: Sepam series 10A provides the same functions as model B, but with a communication port, more inputs and outputs, and additional protection and monitoring functions. Setting of Sepam series 10 for DM1-S 24 kV Is: the phase operating current is adjusted directly in accordance with the transformer rating and the operating voltage. Io: the earth current threshold is adjusted according to the network characteristics. Setting values of the Is phase operating current
Transformer rating (kVA) Operating voltage (kV) 50 75 100 125 3 3.3 4.2 5.5 6 6.6 10 11 13.8 15 20 22 Sensors types legend CRa 200/1 CRb 1250/1 19 24 22 160 31 28 22 200 38 35 27 21 19 250 48 44 34 26 24 22 315 61 55 43 33 30 28 400 77 70 55 42 38 35 23 21 500 96 87 69 52 48 44 29 26 21 19 630 121 110 87 66 61 55 36 33 26 24 800 154 140 110 84 77 70 46 42 33 31 23 21 1000 192 175 137 105 96 87 58 52 42 38 29 26 1250 241 219 172 131 120 109 72 66 52 48 36 33 1600 308 280 220 168 154 140 92 84 67 62 46 42 2000 385 350 275 210 192 175 115 105 84 77 58 52 2500 481 437 344 262 241 219 144 131 105 96 72 66 3000 577 525 412 315 289 262 173 157 126 115 87 79 481 367 337 306 202 184 146 135 101 92 3500

Sepam series 10

AMTED398078EN

43

General characteristics

Protection and control monitoring


Protection and sensor selection table

General common selection of protection units


Protection type Code Protection units
series 20 b b series 40 b b b b b b b b b b b b series 60 b b b b b b b b b b b b series 80 b b b b b b b b b b b b VIP 35 b (2) b (3) 300 b (1) b (1) Sepam series 10 50 - 51 b 50N - 51N b 67N 27 59 49 b 59N 46 51LR 66 37 b

Three-phase overcurrent Zero-sequence overcurrent Directional zero-sequence current Undervoltage Overvoltage Thermal image Zero-sequence overvoltage Negative sequence overcurrent Long start-up and rotor blocking Maximum number of start-ups Single-phase undercurrent Communication

b b b b b b

(1) DT, EI, SI, VI and RI trip curves. (2) Inverse curve suited to transformer protection. (3) DT trip curve.

Current sensor for VIP 35 and VIP 300LL and Sepam series 10 for 24 kV
Type Dimensions (mm) External Internal Thickness (without fastening) 143.5 81 37.5 Weight (kg) Ratio of Class of precision transformation VIP 35 VIP 300LL Sepam 10

CRa

2.18

1/200

CRb CRc

143.5 143.5

81 81

37.5 37.5

1.26 2

1/1250 S1-S2: 1/200 S1-S3: 1/500

2% from 10 A to 100 A On load 5.7 (cal. x 1) 1% from 100 A to 1600 A 1% from 10 A to 10 kA On load 0.67 (cal. x 4) 1% from 10 A to 11 kA On load 5.7 (cal. x 1) 1 % from 10 A to 25 kA On load 0.67 (cal. x 4) S1-S2: On load 0.6 5% from 10 A to 80 A 2.5 % from 80 A to 600 A S1-S3: 2% from 20 A to 2200 A

b b b

b b

DE58402

CRa, CRb, CRc current sensor

44

AMTED398078EN

General characteristics

Protection and control monitoring


LPCT protection chain

Standard applications
PE88012

TLP130, TLP160, TLP190, CLP2 sensors for Sepam series 20, 40, 60, 80 protection units
LPCT sensors are voltage-output current sensors (Low Power Current Transformer) compliant with the IEC 60044-8 standard. These sensors are designed to measure rated current between 5 A and 630 A, with a ratio of 100 A / 22.5 mV. Sepam series 20, 40, 60 and 80 protection units are at the heart of the LPCT protection chain. Sepam series 20, 40, 60 and 80 performs the following functions: b acquisition of phase currents measured by the LPCT sensors b utilization of measurements by the protection functions b tripping of the breaking device in case of fault detection.

Sepam series 20

Advantages
Demanding applications
PE88011

Sepam series 40
DE58405EN

b Consistent protection chain with the same sensor measures phase currents from 5 A to 630 A b Simple to install and implement: v installation of LPCT sensors - TLP130, TLP160 and TLP190 are installed around MV cable - CLP2 is installed on the MV circuit v LPCT connected directly to Sepam series 20, 40, 60 and 80 v accessories available to test the LPCT protection chain by secondary current injection. b LPCTs range of use LPCT measuring and protection function guaranteeing the accuracy up to the short-time current. Following the range of use of LPCT: v from 5 A up to 1250 A respecting the error limits imposed by the accuracy class 0,5 v from 1250 A up to 50 kA respecting the error limits imposed by the accuracy class 5P.
5.00 4.75 4.50 4.25 4.00 3.75 3.50 3.25 3.00 2.75 2.50 2.25 2.00 1.75 1.50 1.25 1.00 0.75 0.50 0.25

Ratio error

Custom applications
PE88010

Protective class 5P Measuring class 0.5

Sepam series 60 and 80

A
5 20 100 1000 1250 2000 3000 31500 40000 50000

MT11325

b Optimized integration of functions: v measurement of phase rated currents as of 25 A that is set by micro-switch v monitoring of LPCT sensor by Sepam series 20, 40, 60 and 80 (detection of phase loss).

Connections
1 LPCT sensor, equipped with a shielded cable tted with an RJ45 connector to be connected directly to the card 3 2 Sepam series 20, 40, 60 and 80 protection unit 3 Card interface that adapts the voltage delivered by the LPCT sensors, with microswitch setting of rated current. v CCA671 card for series 60 and 80 v CCA670 card for series 20 and 40.

Testing and injection


4 CCA613 remote test plug, ush-mounted in front panel of cubicle, equipped with a 3-m cord to be connected to the CCA670 connector test socket (9-pin Sub D) 5 ACE917 injection interface, used to test the LPCT protection chain with a standard injection box 6 Standard 1A injection box.

AMTED398078EN

45

General characteristics

PS100 high-availability power supply


PS100 backup power supply for MV substations
Applications
The power supply unit supplies backup operating power for: b MV switchgear motor mechanisms and circuit breaker coils b Transmission equipment (e.g. radio) b Control units such as RTU or Automatic Transfer System b Protection relays, Fault Passage Indicators and others electronic devices.

Backup solution for MV switchgear power needs in the event of micro outages and power interruptions. b Easy maintenance with only one battery b Remote battery monitoring b High level of insulation to protect the electronic devices in harsh MV environments b End-of-life alarm possible via Modbus communication b Compliant with standards IEC 60 255-5 (10 kV level).

High availabilty power supply


A battery ensures uninterrupted operation of the whole substation in the event of loss of the main supply. The backup power supply unit: b Includes a regulated and temperature-compensated charger b Stops the battery before deep discharge b Carries out a battery check every 12 hours b Measures battery ageing b Forwards monitoring information via a Modbus communication port and output relays.

PM100592

PS100 benets
Only one battery
Traditional backup power supplies require a set of 2 or 4 batteries to produce 24 V or 48 V, with complicated replacement and adjustment of the battery pack. The PS100 needs only one battery, simplifying replacement.
PS100

The battery is a standard sealed lead-acid 12 V battery with a 10-year service. It can be purchased easily, anywhere in the world.

Improved availability of MV/LV substations


The PS100 is designed to ride through power network interruptions of up to 48 hours. It is associated with a battery selected to meet the required backup time. The PS100 protects and optimises the battery with state-of-the-art monitoring. A Modbus communication port forwards monitoring data to allow optimised maintenance operations. Perfect integration with the Easergy range to control and monitor your distribution network.

Additional energy backup


The PS100 stops supplying power and reserves an additional energy backup to restart the installation after an extended power interruption. The additional energy backup can be enabled with a local pushbutton to provide energy for restarting the protection relays and operating the MV switchgear.

Withstands severe substation environments


The PS100 includes 10 kV insulation, electronic protection against overvoltage and overloads, and automatic restart after a fault.

Main features
b DIN rail mounting for easy integration in any LV cabinet or MV/LV substation b 2 power supply outputs: v 12 Vdc - 18 W continuous - 100 W 20 s (for modem, radio, RTU, etc.) v 48 Vdc or 24 Vdc - 300 W /1 minute (for switchgear operating mechanism motors) and 90 W / continuous for protection relays, electronic devices, etc. b RJ45 Modbus communication port b 2 output relays (AC supply ON, Battery ON) b Diagnosis with LEDs b 1 sealed lead-acid 12 V battery with a 10-year service life (from 7 Ah to 40 Ah) b Power supply paralleling available with a 2nd PS100 b - 40C to +70C operating temperature.

Range
b b b b PS100-48V PS100-24V Bat24AH Bat38AH 48 Vdc power supply and battery charger 24 Vdc power supply and battery charger 24 Ah long life battery 38 Ah long life battery.

46

AMTED398078EN

Characteristics of the functional units

Contents

Functional units selection


Switching Protection Metering Other functions

48 48 51 60 62 65 68 70 72 73 75 76 77 79

Operating mechanisms Auxiliaries Current transformers for 24 kV Current transformers for 36 kV Voltage transformers for 24 kV Voltage transformers for 36 kV Motors protection units Protection of transformers Interlocks

AMTED398078EN

47

Characteristics of the functional units

Functional units selection


Switching

IM Switch unit
DE59700 DE53518

IMC Switch unit


DE53519

IMB Switch unit with earthing switch Right or left outgoing

Electrical characteristics
DE59710

kA 25

Ik/1s

DE59711

kA 62.5

Ima

20 Ir = 630 A 16

50 Ir = 630 A 40

12.5 7.2

Ir = 400 - 630 A 12 17.5 24 36

Ur kV

31.25 7.2

Ir = 400 - 630 A 12 17.5 24 36

Ur kV

Basic equipment:
b b b b b switch and earthing switch three-phase busbars CIT operating mechanism voltage presence indicator 150 W heating element for 36 kV b three-phase bottom busbars for outgoing lines (right or left) b one to three CTs for 24 kV b three CTs for 36 kV

b connection pads for dry-type cables

Versions:
b CI2 operating mechanism b CI1 operating mechanism b in 800 A version for 24 kV, consult us b CI1 operating mechanism for 36 kV b CI1 operating mechanism

Optional accessories:
b b b b b b motor for operating mechanism auxiliary contacts key-type interlocks release units (coil) operation counter 1250 A three-phase upper busbars b b b b b b 630 A three-phase upper busbars for severe operating conditions for 24 kV visibility of main contacts pressure indicator device enlarged low-voltage control cabinet for 24 kV 50 W heating element for 24 kV cable connection by the top (no internal arc withstand if selected)

b fault indicators b Connection pads for two dry-type single-core cables for 36 kV b digital ammeter b surge arresters (for 36 kV and for 24 kV in 500 mm width cubicle) b 630 A busbars earthing switch cabinet for 24 kV (not available for internal arc IEC62271-200)

48

AMTED398078EN

Characteristics of the functional units

Functional units selection


Switching
Automatic Transfer System for 24 kV

NSM-cables Cables power supply for main incoming line (N) and standby line (S)
DE53559 DE58401

NSM-busbars Cables power supply for main incoming line on left (N) and busbars for standby line (S) on right
DE53561

NSM-busbars Busbars power supply for main incoming line on left (N) and cables for standby line (S) on right

Electrical characteristics
DE59212 DE59218

kA 25

Ik/1s

kA 62.5

Ima

20 Ir = 630 A 16

50 Ir = 630 A 40

12.5 7.2

Ir = 400 - 630 A 12 17.5 24

Ur kV

31.25 7.2

Ir = 400 - 630 A 12 17.5 24

Ur kV

Basic equipment:
b b b b b b b b switches and earthing switches three-phase busbars connection pads for dry-type cables voltage presence indicator mechanical interlocking motorised operating mechanism CI2 with open/close coils additional enclosure automatic-control equipment (T200 S)

Optional accessories:
b b b b b b b b auxiliary contacts key-type interlocks 50 W heating element control and monitoring visibility of main contacts pressure indicator device 1250 A three-phase upper busbars 630 A three-phase upper busbars for severe operating conditions

AMTED398078EN

49

Characteristics of the functional units

Functional units selection


Switching
Automatic Transfer System for 36 kV

NSM-cables Cables power supply for main incoming line (N) and standby line (S)
DE59706 DE59707

NSM-busbars Cables power supply for main incoming line on left (N) and busbars for standby line (S) on right
DE59708

NSM-busbars Busbars power supply for main incoming line on left (N) and cables for standby line (S) on right

Electrical characteristics
DE59720

kA 25

20

16

Ir = 630 A

12.5 36 kV

Basic equipment:
b b b b b b b b switches and earthing switches three-phase busbars 630 A connection pads for dry-type cables voltage presence indicator motorised operating mechanism CI2 with shunt trips additional enclosure automatic-control equipment 150 W heating element

Optional accessories:
b auxiliary contacts b key-type interlocks b control and monitoring

50

AMTED398078EN

Characteristics of the functional units

Functional units selection


Protection
Fuse-switch

QM Fuse-switch combination unit


DE59701 DE53523

QMC Fuse-switch combination unit


DE53524

QMB Fuse-switch combination unit Outgoing line right or left

Electrical characteristics
DE59712 DE59713

kA 25

Ik/1s

kA 25

Isc

20 Ir = 200 A 16 Ir = 63 A

20 Ir = 200 A 16 Ir = 63 A

12.5 7.2 12 17.5 24 36

Ur kV

12.5 7.2 12 17.5 24 36

Ur kV

Basic equipment:
b b b b b b b switch and earthing switch three-phase busbars CI1 operating mechanism voltage presence indicator equipment for three DIN striker fuses mechanical indication system for blown fuses 150 W heating element for 36 kV b three-phase bottom busbars for outgoing lines (right or left) b one to three CTs for 24 kV b three CTs for 36 kV

b connection pads for dry-type cables b downstream earthing switch 2 kA rms making capacity

Version:
b equipment for three UTE striker fuses for 24 kV b CI2 operating mechanism b CI2 operating mechanism for 36 kV

Optional accessories:
b b b b b b b b b b b b b b motor for operating mechanism auxiliary contacts key-type interlocks auxiliary contact for blown fuses DIN striker fuses release units (coil) digital ammeter 1250 A three-phase upper busbars cable connection by the top (no internal arc withstand if selected) visibility of main contacts pressure indicator device 630 A three-phase upper busbars for severe operating conditions for 24 kV enlarged low-voltage control cabinet for 24 kV 50 W heating element for 24 kV

AMTED398078EN

51

Characteristics of the functional units

Functional units selection


Protection
Fuse-switch

PM Fused-switch unit
DE53526

Electrical characteristics
DE59714

kA 25

Ik/1s & Isc

20 Ir = 200 A 16 Ir = 63 A

12.5 7.2 12 17.5 24 36

Ur kV

Basic equipment:
b b b b b b b b switch and earthing switch three-phase busbars CIT operating mechanism voltage presence indicator connection pads for dry-type cables downstream earthing switch 2 kA rms making capacity equipment for three UTE (for 24 kV) or DIN striker fuses 150 W heating element for 36 kV

Version:
b CI1 operating mechanism b CI2 operating mechanism for 36 kV

Optional accessories:
b b b b b b b b b b b b b b motor for operating mechanism auxiliary contacts digital ammeter key-type interlocks mechanical indication system for blown fuses 1250 A three-phase upper busbars cable connection by the top (no internal arc withstand if selected) UTE (for 24 kV) or DIN striker fuses visibility of main contacts pressure indicator device 630 A three-phase upper busbars for severe operating conditions for 24 kV enlarged low-voltage control cabinet for 24 kV 50 W heating element for 24 kV Release units for 36 kV

52

AMTED398078EN

Characteristics of the functional units

Functional units selection


Protection
SF6 type circuit breaker

DM1-A Single-isolation disconnectable CB unit


DE53531 DE53532

DM1-D Single-isolation disconnectable CB unit Outgoing line on right


DE53533

DM1-D Single-isolation disconnectable CB unit Outgoing line on left

Electrical characteristics
DE59715

kA 25

Ik/1s & Isc Ir = 1250 A

20 Ir = 630 - 1250 A 16

12.5

Ir = 400 - 630 - 1250 A 7.2 12 17.5 24 36

Ur kV

Basic equipment:
b b b b b b b b b b SF1 disconnectable circuit breaker disconnector and earthing switch three-phase busbars circuit breaker operating mechanism RI disconnector operating mechanism CS voltage presence indicator three CTs auxiliary contacts on circuit breaker mechanical interlocking between circuit breaker and disconnector 150 W heating element for 36 kV b three-phase bottom busbars

b connection pads for dry-type cables b downstream earthing switch 2 kA rms making capacity at 630 A and 25 kA rms making capacity at 1250 A

Version:
b LPCT (only with Sepam series 20, 40, 60, 80) b SFset circuit breaker disconnectable (only for 400-630 A performances and 24 kV)

Optional accessories:
b cubicle: v auxiliary contacts on the disconnector v protection using Sepam programmable electronic unit v three voltage transformers v key-type interlocks v 1250 A three-phase upper busbars at Ir 630 A v cable connection by the top (no internal arc withstand if selected) v surge arresters v 630 A busbars earthing switch cabinet for 24 kV (not available for internal arc IEC62271-200) v v v v 630 A three-phase upper busbars for severe operating conditions for 24 kV enlarged low-voltage control cabinet for 24 kV 50 W heating element for 24 kV connection pads for two dry-type single-core cables for 36 kV

AMTED398078EN

53

Characteristics of the functional units

Functional units selection


Protection
SF6 type circuit breaker

DM1-S Single-isolation disconnectable CB unit with independent protection


DE58360 DE53536

DM2 Double-isolation disconnectable CB unit Outgoing line on right


DE53537

DM2 Double-isolation disconnectable CB unit Outgoing line on left

Electrical characteristics
DE59212-Isc DE59721

kA 25

Ik/1s & Isc

kA 25

Ik/1s & Isc Ir = 1250 A

20 Ir = 630 A 16

20 Ir = 630 16

12.5 7.2

Ir = 400 - 630 A 12 17.5 24

Ur kV

12.5 7.2

Ir = 400 - 630 12 17.5 24 36

Ur kV

Basic equipment:
b b b b b b b b b b b b SF1 disconnectable circuit breaker disconnector and earthing switch three-phase busbars circuit breaker operating mechanism RI disconnector operating mechanism CS auxiliary contacts on circuit breaker mechanical interlocking between circuit breaker and disconnector VIP relay three CR sensors for VIP relay protection voltage presence indicator connection pads for dry-type cables downstream earthing switch 2 kA rms making capacity b three CTs b 150 W heating element for 36 kV

Version:
b Sepam series 10 with auxiliary supply and three CR sensors

Optional accessories:
b cubicle: v three voltage transformers v key-type interlocks v 1250 A three-phase upper busbars at Ir 630 A v 630 A three-phase upper busbars for severe operating conditions for 24 kV v enlarged low-voltage control cabinet for 24 kV b v v v circuit breaker: motor for operating mechanism release units (coil) operation counter on manual operating mechanism b v v v cubicle: protection using Sepam programmable electronic unit auxiliary contacts on disconnectors 2 voltage transformers phase-to-phase or 3 voltage transformers phase-to-earth

v cable connection by the top v 50 W heating element for 24 kV

54

AMTED398078EN

Characteristics of the functional units

Functional units selection


Protection
SF6 type circuit breaker

DM1-W Withdrawable single-isolation circuit breaker unit


DE53538 DE53539

DM1-Z Withdrawable single-isolation CB unit Outgoing line on right


DE59702

DM2-W Withdrawable double-isolation CB unit Outgoing line on right

Electrical characteristics
DE59715 DE59226

kA 25

Ik/1s & Isc Ir = 1250 A

kA 25

Ik/1s & Isc

DE59716

kA 25

Ik/1s & Isc Ir = 1250 A

20 Ir = 630 - 1250 A 16

20 Ir = 1250 A 16

20 Ir = 630 - 1250 A

16

12.5

Ir = 400 - 630 - 1250 A 7.2 12 17.5 24 36

Ur kV

12.5 7.2 12 17.5 24

Ur kV

12.5 36

Ur kV

Basic equipment:
b b b b b b b b b SF1 withdrawable circuit breaker disconnector and earthing switch three-phase busbars circuit breaker operating mechanism RI disconnector operating mechanism CS voltage presence indicator three CTs auxiliary contacts on circuit breaker 150 W heating element for 36 kV

b mechanical interlocking between circuit breaker and disconnector b earthing switch operating mechanism CC b connection pads for dry-type cables b downstream earthing switch 25 kA rms making capacity b three-phase busbars

Version:
b LPCT (only with Sepam series 20, 40 and 80)

Optional accessories:
b v v v v v v v cubicle: auxiliary contacts on the disconnector protection using Sepam programmable electronic unit key-type interlocks three voltage transformers for 24 kV connection enclosure for cabling from above for 24 kV 50 W heating element for 24 kV enlarged low-voltage control cabinet for 24 kV b circuit breaker: v motor for operating mechanism v release units (coil) v operation counter on manual operating mechanism b cubicle: v auxiliary contacts on the disconnector v key-type interlocks v protection using Sepam programmable electronic unit b circuit breaker: v motor for operating mechanism v operation counter on manual operating mechanism v opening and closing shunt trips

v 1250 A three-phase upper busbars at Ir 630 A v 630 A three-phase upper busbars for severe operating conditions for 24 kV v surge arresters (only for 630 A and 24 kV)

AMTED398078EN

55

Characteristics of the functional units

Functional units selection


Protection
Vacuum type circuit breaker

DMV-A Single-isolation circuit breaker unit


DE53541 DE53542

DMV-D Single-isolation circuit breaker unit Outgoing line on right


DE53543

DMV-S Single-isolation circuit breaker unit with independent protection

Electrical characteristics
DE59227

kA 25

Ik/1s & Isc

20 Ir = 630 - 1250 A 16 Ir = 400 - 630 1250 A 7.2 12 17.5 24

12.5

Ur kV

Basic equipment:
b b b b b b b b Evolis circuit breaker frontal switch and earthing switch for 400 - 630 A disconnector and earthing switch for 1250 A three-phase busbars circuit breaker operating mechanism P2 disconnector and switch operating mechanism CIT voltage presence indicator auxiliary contacts on circuit breaker b 3 CR sensors for VIP relay b VIP protection relay b connection pads for dry-type cables b downstream earthing switch 25 kA rms making capacity

b three CTs b Sepam series 20 programmable electronic unit b connection pads for dry-type cables b downstream earthing switch 25 kA rms making capacity

Optional accessories:
b v v v v v v v v cubicle: b circuit breaker: auxiliary contacts on the disconnector v motor for operating mechanism three voltage transformers v release units (coil) key-type interlocks v operation counter on manual operating mechanism 50 W heating element connection enclosure for cabling from above 1250 A three-phase upper busbars at Ir 630 A 630 A three-phase upper busbars for severe operating conditions enlarged low-voltage control cabinet

56

AMTED398078EN

Characteristics of the functional units

Functional units selection


Protection
Vacuum type circuit breaker

DMVL-A Single-isolation disconnectable circuit breaker unit


DE53535 DE59703

DMVL-D Single-isolation disconnectable circuit breaker unit Outgoing line on right

Electrical characteristics
DE59228

kA 25

Ik/1s & Isc

DE59717

kA 25

Ik/1s & Isc

20

20 Ir = 630 A

16

Ir = 630 A

16

12.5 7.2 12 17.5 24

Ur kV

12.5 7.2 12 17.5 24

Ur kV

Basic equipment:
b b b b b b b b b b Evolis circuit breaker lateral disconnectable disconnector and earthing switch mechanical interlocking between circuit breaker and disconnector three-phase busbars circuit breaker operating mechanism RI disconnector operating mechanism CS voltage presence indicator auxiliary contacts on circuit breaker 3 CTs connection pads for dry-type cables

b downstream earthing switch 2 kA rms making capacity

Optional accessories:
b v v v v v v v v v v cubicle: b circuit breaker: auxiliary contacts on the disconnector v motor for operating mechanism three voltage transformers v release units (coil) key-type interlocks v operation counter on manual operating mechanism 50 W heating element connection enclosure for cabling from above 1250 A three-phase upper busbars at Ir 630 A 630 A three-phase upper busbars for severe operating conditions enlarged low-voltage control cabinet Sepam relay protection surge arresters

AMTED398078EN

57

Characteristics of the functional units

Functional units selection


Protection
Contactor (Direct Motor Starter) for 24 kV

CVM Disconnectable contactor unit


DE53527 DE53528

CVM Disconnectable contactor unit with fuses

Electrical characteristics
DE59220 DE59221

kA

Ik/1s & Isc

kA 25

Isc

10 8

20 Ir = 250 A 16

6.3 Ir = 400 A Ur 7.2 12 kV 12.5 7.2 12 Ur kV

Basic equipment:
b b b b b b b b b b b b b vacuum contactor disconnector and earthing switch three-phase busbars contactor operating mechanism with magnetic holding or contactor with mechanical latching disconnector operating mechanism CS one to three current transformers auxiliary contacts on contactor connection pads for dry-type cables voltage presence indicator downstream earthing switch 2 kA rms making capacity operation counter on contactor enlarged low-voltage control cabinet mechanical interlocking between contactor and disconnector/earthing switch b equipment for three DIN striker fuses b mechanical indication system for blown fuses b auxiliary contact for blown fuses

Version:
b LPCT (only with Sepam series 20, 40, 60, 80)

Optional accessories:
b v v v v v v v cubicle: auxiliary contacts on the disconnector protection using Sepam programmable electronic unit one to three voltage transformers key-type interlocks 50 W heating element 1250 A three-phase upper busbars 630 A three-phase upper busbars for severe operating conditions

b contactor: v mechanical interlocking b DIN striker fuses

58

AMTED398078EN

Characteristics of the functional units

Functional units selection


Protection
Contactor (Direct Motor Starter) for 24 kV

CRM Contactor unit


DE53527 DE53528

CRM Contactor unit with fuses

Electrical characteristics
DE57175 DE59224

kA

Ik/1s & Isc

kA 25

Isc

10 8 Ir = 400 A

20 Ir = 250 A 16

Ur 7.2 12 kV

12.5 7.2 12

Ur kV

Basic equipment:
b b b b b b b b b b b b SF6 contactor disconnector and earthing switch three-phase busbars contactor operating mechanism with magnetic holding or contactor with mechanical latching disconnector operating mechanism CS one to three current transformers auxiliary contacts on contactor connection pads for dry-type cables voltage presence indicator downstream earthing switch 2 kA rms making capacity operation counter on contactor enlarged low-voltage control cabinet b equipment for three DIN striker fuses

Optional accessories:
b v v v v v v v cubicle: auxiliary contacts on the disconnector protection using Sepam programmable electronic unit one to three voltage transformers key-type interlocks 50 W heating element 1250 A three-phase upper busbars 630 A three-phase upper busbars for severe operating conditions

b contactor: v mechanical interlocking b DIN striker fuses

AMTED398078EN

59

Characteristics of the functional units

Functional units selection


Metering

CM Voltage transformers unit for network with earthed neutral system


DE53546 DE53547

CM2 Voltage transformers unit for network with insulated neutral system

Electrical characteristics
DE59722

kA 25

Ik/1s

20 Ir = 50 A 16

12.5 7.2 12 17.5 24 36

Ur kV

Basic equipment:
b b b b b b b disconnector and earthing switch three-phase busbars operating mechanism CS LV circuit isolation switch LV fuses three 6.3 A UTE or DIN type fuses 150 W heating element for 36 kV b two voltage transformers (phase-to-phase)

b three-voltage transformers (phase-to-earth)

Optional accessories:
b b b b b b b auxiliary contacts mechanical signalling and auxiliary contact for blown fuses 1250 A three-phase upper busbars cable connection by the top (no internal arc withstand if selected) 50 W heating element for 24 kV 630 A three-phase upper busbars for severe operating conditions for 24 kV enlarged low-voltage control cabinet for 24 kV

60

AMTED398078EN

Characteristics of the functional units

Functional units selection


Metering

GBC-A Current and/or voltage measurements unit Outgoing line on right


DE53549 DE53550

GBC-A Current and/or voltage measurements unit Outgoing line on left


DE53551

GBC-B Current and/or voltage measurements unit

Electrical characteristics
DE59709

kA 25

Ik/1s Ir = 1250 A

20 Ir = 630 - 1250 A 16

12.5

Ir = 400 - 630 - 1250 A 7.2 12 17.5 24 36

Ur kV

Basic equipment:
b b b b b one to three CTs for 24 kV three CTs for 36 kV connection bars three-phase busbars 150 W heating element for 36 kV

Optional accessories:
b b b b b 1250 A three-phase upper busbars at Ir 630 A for 24 kV enlarged low-voltage control cabinet for 24 kV three voltage transformers (phase-to-earth) or two voltage transformers (phase-to-phase) for 24 kV 50 W heating element for 24 kV cable connection by the top for 36 kV (no internal arc withstand if selected)

AMTED398078EN

61

Characteristics of the functional units

Functional units selection


Other functions

GBM Connection unit Outgoing line right or left


DE53553 DE53552

GEM Extension unit VM6/SM6


DE58361

GIM Intermediate bus unit

Electrical characteristics
DE59709 DE59212

kA 25

Ik/1s Ir = 1250 A

kA 25

Ik/1s

DE59214

kA 25

Ik/1s

20 Ir = 630 - 1250 A 16

20 Ir = 630 A 16

20 Ir = 630 A 16

12.5

Ir = 400 - 630 - 1250 A 7.2 12 17.5 24 36

Ur kV

12.5 7.2

Ir = 400 - 630 A 12 17.5 24

Ur kV

12.5 7.2

Ir = 400 - 630 A 12 17.5 24 36

Ur kV

Basic equipment:
b connection bars b three-phase busbars for outgoing lines right or left b 150 W heating element for 36 kV b metallic envelop b three-phase busbars b metallic envelop

Optional accessories:
b 1250 A three-phase upper busbars at Ir 630 A b enlarged low-voltage control cabinet for 24 kV b cable connection by the top for 36 kV (no internal arc withstand if selected)

62

AMTED398078EN

Characteristics of the functional units

Functional units selection


Other functions

GAM2 Incoming-cable-connection unit


DE53554 DE53555

GAM Incoming-cable-connection unit

Electrical characteristics
DE59719

kA 25

Ik/1s Ir = 1250 A Ir = 630 A Ir = 630 1250 A

DE59709

kA 25

Ik/1s Ir = 1250 A

20

20 Ir = 630 - 1250 A 16

16

12.5 7.2

Ir = 400 - 630 A 12 17.5 24 36

Ur kV

12.5

Ir = 400 - 630 - 1250 A 7.2 12 17.5 24 36

Ur kV

Basic equipment:
b b b b b three-phase busbars voltage presence indicator connection pads for dry-type cables connection bars 150 W heating element for 36 kV b downstream earthing switch 25 kA rms making capacity b operating mechanism CC for 24 kV b operating mechanism CS for 36 kV

Optional accessories:
b b b b b b fault indicator digital ammeter 1250 A three-phase upper busbars at Ir 630 A enlarged low-voltage control cabinet for 24 kV cable connection by the top (no internal arc withstand if selected) 50 W heating element for 24 kV b auxiliary contacts b key-type interlocks b surge arresters for 24 kV

b surge arresters for 36 kV

AMTED398078EN

63

Characteristics of the functional units

Functional units selection


Other functions

SM Disconnector unit
DE59704 DE53557

TM MV/LV transformer unit for auxiliaries


DE53558 DE59212

EMB Busbars earthing switch cabinet

Electrical characteristics
DE59709

kA 25

Ik/1s Ir = 1250 A

DE59722

kA 25

Ik/1s

kA 25

Ik/1s

20 Ir = 630 - 1250 A 16

20 Ir = 50 A 16

20 Ir = 630 A 16

12.5

Ir = 400 - 630 - 1250 A 7.2 12 17.5 24 36

Ur kV

12.5 7.2 12 17.5 24 36

Ur kV

12.5 7.2

Ir = 400 - 630 A 12 17.5 24

Ur kV

Basic equipment:
b b b b disconnector and earthing switch three-phase busbars operating mechanism CS 150 W heating element for 36 kV b two 6.3 A fuses, UTE (for 24 kV) or DIN type b LV circuit isolating switch b one voltage transformer (phase-to-phase) b earthing switch b connection bars three phase b operating mechanism CIT b installation on 630 A IM 375 mm or DM1-A units (not available for internal arc IEC 62271-200) b require a key-type interlocks adapted to the switchboard network

b connection pads for dry-type cables b voltage presence indicator

Optional accessories:
b b b b b b b auxiliary contacts key-type interlocks 1250 A three-phase upper busbars at Ir 630 A cable connection by the top (no internal arc withstand if selected) enlarged low-voltage control cabinet for 24 kV 50 W heating element for 24 kV 630 A three-phase upper busbars for severe operating conditions for 24 kV b mechanical indication system and auxiliary contacts for blown fuses b auxiliary contacts

b digital ammeter for 24 kV b surge arrester for 36 kV

64

AMTED398078EN

Characteristics of the functional units

Operating mechanisms

The control devices required for the unit operating mechanisms are centralised on the front panel. The different types of operating mechanism are presented in the table opposite. Operating speeds do not depend on the operator, except for the CS.

Units

Type of operating mechanism


Switch/disconnector CIT CI1 CI2 CS CC Circuit breaker RI P2

IM, IMB IMC PM QM QMC, QMB CM, CM2, CRM, CVM DM1-A, DM1-D, DM1-S, DM1-Z, DM2, DMVL-A, DMVL-D DM1-A (2), DM1-W, DM2-W DMV-A, DMV-D, DMV-S NSM-cables, NSM-busbars GAM 24 kV SM, TM, GAM 36 kV EMB

b b b

v v v b b

v v v (1) v v b b b b b b b b b b

b Provided as standard v Other possibility


(1) Only 36 kV (2) 1250 A version

Operating mechanism types


Unit applications Main circuit switch Manual operating mode Electrical operating mode (option) Speed of operation Network applications

CIT
Load-break switch Fused switch Closing Opening Hand lever Hand lever Motor Motor 1 to 2 s 1 to 2 s Remote control network management Closing Hand lever Opening Hand lever

CI1
Load-break switch Fuse switch combination Closing Opening Hand lever Push button Motor Coil 4 to 7 s 35 ms Remote control transformer protection Closing Hand lever Opening Hand lever

CI2
Load-break switch Fuse switch combination Mechanism Closing Opening charging Hand lever Push button Push button Motor Coil Coil 4 to 7 s 55 ms 35 ms Remote control network management, need of quick reconguration (generator source, loop) N/A Closing Opening Hand lever Hand lever Hand lever

CS
Disconnector Closing Hand lever N/A N/A N/A Opening Hand lever N/A N/A

Earthing switch Manual operating mode


61029N

Closing Hand lever

Opening Hand lever

Double-function operating mechanism CIT


b Switch function Independent-operation opening or closing by lever or motor. b Earthing-switch function Independent-operation opening or closing by lever. Operating energy is provided by a compressed spring which, when released, causes the contacts to open or close. b Auxiliary contacts v switch (2 O + 2 C) *, v switch (2 O + 3 C) and earthing switch (1 O + 1 C), v switch (1 C) and earthing switch (1 O + 1 C) if motor option. b Mechanical indications Fuses blown in unit PM. b Motor option
(*) Included with the motor option

AMTED398078EN

65

Characteristics of the functional units

Operating mechanisms

61030N

Double-function operating mechanism CI1


b Switch function v independent-operation closing by lever or motor. Operating energy is provided by a compressed spring which, when released, causes the contacts to open or close. v independent-operation opening by push-button (O) or trip units. b Earthing-switch function Independent-operation closing and opening by lever. Operating energy is provided by a compressed spring which, when released, causes the contacts to open or close. b Auxiliary contacts v switch (2 O + 2 C) *, v switch (2 O + 3 C) and earthing switch (1 O + 1 C), v switch (1 C) and earthing switch (1 O + 1 C) if motor option, v fuses blown (1 C). b Mechanical indications Fuses blown in units QM. b Opening releases v shunt trip, v undervoltage for unit QM. b Motor option
(*) Included with the motor option.

61031N

Double-function operating mechanism CI2


b Switch function v independent-operation closing in two steps: 1 - operating mechanism recharging by lever or motor, 2 - stored energy released by push-button (I) or trip unit. v independent-operation opening by push-button (O) or trip unit. b Earthing-switch function Independent-operation closing and opening by lever. Operating energy is provided by a compressed spring which, when released, causes the contacts to open or close. b Auxiliary contacts v switch (2 O + 2 C) *, v switch (2 O + 3 C) and earthing switch (1 O + 1 C), v switch (1 C) and earthing switch (1 O + 1 C) if motor option. b Opening release shunt trip b Closing release shunt trip b Motor option
(*) Included with the motor option.

61032N

Double-function operating mechanism CS


b Disconnector and earth switch functions Dependent-operation opening and closing by lever. b Auxiliary contacts v disconnector (2 O + 2 C) for units DM1-A, DM1-D, DM1-W, DM2, DMVL-A, DMVL-D, CVM and CRM without VT, v disconnector (2 O + 3 C) and earthing switch (1 O + 1 C) for units DM1-A, DM1-D, DM1-W, DM2, DMVL-A, DMVL-D, CVM and CRM without VT, v disconnector (1 O + 2 C) for units CM, CM2, TM, DM1-A, DM1-D, DM2, DMVL-A, DMVL-D, CVM and CRM with VT. b Mechanical indications Fuses blown in units CM, CM2 and TM.
61033N

Single-function operating mechanism CC


b Earthing switch function Independent-operation opening and closing by lever. Operating energy is provided by a compressed spring which, when released, provokes opening or closing of the contacts. b Auxiliary contacts Earthing switch (1 O + 1 C).

66

AMTED398078EN

Characteristics of the functional units

Operating mechanisms

Single-function operating mechanism for the SF circuit breakers 24 kV and 36 kV and Evolis 24 kV lateral
b Circuit-breaker function v independent-operation closing in two steps. First operating mechanism recharge by motor or lever, then release of the stored energy by push-button (I) or trip unit. v independent-operation opening by push-button (O) or trip units. b Auxiliary contacts v circuit breaker (4 O + 4 C), v mechanism charged (1 C). b Mechanical indications Operation counter. b Opening releases v Mitop (low energy), v shunt trip, v undervoltage. b Closing release v shunt trip b Motor option (option and installation at a later date possible). Possible combinations between opening releases SF1
Release type Mitop (low energy) Shunt trip Undervoltage Combinations 1 b 2 b b b 3 b b b b b 4 5 6

PE57163

SFset
Combinations 1 b 2 b b b 3 b 4

61035N

P2 stored energy operating mechanism for the Evolis circuit breaker 17.5 kV frontal
b Circuit-breaker function v independent-switching operating closing in two steps. First operating mechanism recharge by motor or lever, then release of the stored energy by push-button (I) or trip unit. v independent-operation opening by push-button (O) or trip units. v spring energy release. b Auxiliary contacts v circuit breaker (4 O + 4 C), v mechanism charged (1 C). b Mechanical indications Operation counter. b Opening releases v Mitop (low energy), v shunt trip, v undervoltage. b Closing release v shunt trip b Motor option (option and installation at a later date possible).

AMTED398078EN

67

Characteristics of the functional units

Auxiliaries

61036N

Motor option and releases for switch-units


The operating mechanisms CIT, CI1 and CI2 may be motorised.

Un
Power supply (V)

DC
24 200 1 to 2 (s) 4 to 7 (s) 200 35 160 250 300 300 300 48 110 125 220 (W) (VA) Operating time for CIT Charging time for CI1, CI2

AC (50 Hz)*
120 230

Motor option
200 1 to 2 (s) 4 to 7 (s)

Opening releases
Shunt trip Response time Undervoltage Pick-up Hold Response time (W) (VA) (ms) (W) (VA) (W) (VA) (ms) (W) (VA) (ms) 400 35 750

280 4 45 200 55 250 300 300 300 400 55 50 45

550 40

Closing release
Shunt trip Response time 750

* Please consult us for other frequencies.

Motor option and releases for SF6 type circuit breakers and Evolis 24 kV lateral
Operating mechanism RI may be equipped with the motor option for the recharging function.

PE57164

Un
Power supply (V) (W) (VA) (s) (W) (ms) (W) (VA) (ms) (W) (VA) (W) (VA) (ms) (W) (VA) (ms)

DC
24 300 48 110 125 220

AC (50 Hz)*
120 230

Motor option
380 15 3 30 85 45 160 280 10 55 85 180 65 65 50 55 40 550 15

Charging time

Opening releases
Mitop (low energy) Response time Shunt trip Response time Undervoltage Pick-up Hold Response time 30 180 45

Closing release
Shunt trip Response time

* Please consult us for other frequencies.

68

AMTED398078EN

Characteristics of the functional units

Auxiliaries

Motor option and releases for Evolis circuit breakers 17.5 kV frontal
Charging motor and associated mechanism (P2)
Power supply Threshold Consumption Charging time Switching rate CH contact Power supply Threshold Response time to the circuit breaker at Ur (VA or W) Motor overcurrent (Vac 50/60 Hz) (Vdc) 24/30 0.85 to 1.1 Ur 180 2 to 3 Ir during 0.1 s 6 s max. 3 cycles per minute max. 10 A 240 V Direct current 0.6 A < I < 3 A 50 ms (protection relay setting) 48/60 48/60 100/130 100/125 200/240 200/250

61035N

Opening release (MITOP low energy)

Opening release (MX)


Power supply Threshold Consumption (VA or W) (Vac 50/60 Hz) (Vdc) 24 24/30 0.7 to 1.1 Ur Pick-up: 200 (during 200 ms) Hold: 4.5 Response time to the circuit breaker at Ur 50 ms 10 48 48/60 100/130 100/130 200/250 200/250

Closing release (XF)


Power supply Threshold Consumption (VA or W) (Vac 50/60 Hz) (Vdc) 24 24/30 0.85 to 1.1 Ur Pick-up: 200 (during 200 ms) Hold: 4.5 48 48/60 100/130 100/130 200/250 200/250

PE57842

Auxiliary contacts for vacuum contactor


The auxiliary contacts are of the changeover type with a common point. The following are available: b 3 NO + 3 NC for the electrically held version (optional 3 NO & 3 NC additional auxiliary contacts), b 5 NO + 6 NC for the mechanically latched version as standard. Characteristics Operating voltage Rated current Breaking capacity Minimum Maximum Vdc Vac 48 V 480 V 10 A 60 W (L/R 150 ms) 700 VA (power factor 0.35)

Open release characteristics Power supply (Vdc) 48 Consumption (W) 470 Response time (ms) 20-40

125 680 20-41

250 640 20-40

AMTED398078EN

69

Characteristics of the functional units

Current transformers for 24 kV

Synthesis table by unit


Units QMC CRM CVM DM1-A DM1-D DM1-W DM2 DMVL-D 630 A
TC ARJP1 ARM3 ARJP2 ARJP3 CLP2 TLP130

GBC-A DMVL-A DMV-A IMC GBC-B DMV-D

DM1-A DM1-W GBC-A DMV-A DM1-D DM1-Z GBC-B DMV-D 1250 A

b b b b b b b b b b b b b b b b b

Transformer ARJP1/N2F b characteristics according to IEC standard 60044-1 b single primary winding b double secondary winding for measurement and protection. Short-time withstand current Ith (kA)
I1n (A) Ith (kA) t (s) Measurement and protection 5A 5A 10 1.2 1 15 VA - class 0.5 2.5 VA - 5P20 20 2.4 30 3.6 50 6 75 10 100 10 150 10 200 10

61040N

Transformer ARJP1/N2F b characteristics according to IEC standard 60044-1 b single primary winding b double secondary winding for measurement and protection. Short-time withstand current Ith (kA)
I1n (A) Ith (kA) t (s) Measurement and protection 5A 5A 50 6 1 15 VA - class 0.5 2.5 VA - 5P20 100 10 150 200

61040N

Note: please consult us for other characteristics.

Transformer ARM3/N2F b characteristics according to IEC standard 60044-1 b double primary winding b single secondary winding for measurement and protection. Short-time withstand current Ith (kA)
I1n (A) Ith (kA) t (s) Measurement and 5 A protection 1A 5A * For 5 A protection 10/20 5 1 20/40 12.5 0.8 50/100 12.5/21* 1 100/200 12.5/25* 200/400 12.5/25* 300/600 25

61041N

7.5 VA - class 0.5 1 VA - 10P30 5 VA - 5P10 5 VA - 5P15

b characteristics according to IEC standard 60044-1 b double primary winding b double secondary winding for measurement and protection. Short-time withstand current Ith (kA)
I1n (A) Ith (kA) t (s) Measurement and protection 5A 5A 5A 50/100 14.5 1 30 VA - class 0.5 5 VA - 5P15 7.5 VA - 5P10 7.5 VA - 5P15 15 VA - 5P10 100/200 25 200/400 25 300/600 25

70

AMTED398078EN

Characteristics of the functional units

Current transformers for 24 kV

Transformer ARJP2/N2F b characteristics according to IEC standard 60044-1 b single primary winding b double secondary winding for measurement and protection. Short-time withstand current Ith (kA)
I1n (A) Ith (kA) t (s) Measurement and protection 5A 5A 50 25 1 10 VA class 0.5 2.5 VA 5P20 15 VA class 0.5 2.5 VA 5P20 15 VA class 0.5 5 VA 5P20 15 VA class 0.5 5 VA 5P20 20 VA class 0.5 7.5 VA 5P20 100 200 400 600

61042N

Transformer ARJP3/N2F b characteristics according to IEC standard 60044-1 b single primary winding b double secondary winding for measurement and protection. Short-time withstand current Ith (kA)
I1n (A) Ith (kA) t (s) Measurement and protection Measurement and protection 1A 1A 5A 5A 1000 25 1 30 VA - class 0.5 10 VA - 5P20 30 VA - class 0.5 10 VA - 5P20 1250

PE55661

61044N

Low Power Current Transformer (LPCT) CLP2 b characteristics according to IEC standard 60044-8 b large primary current range b direct output voltage for measurement and protection b RJ45-8 pts secondary connector b insulation level 24 kV.
Minimum rated primary current Rated nominal primary current Rated extended primary current Rated nominal secondary output Accuracy class for measurement Accuracy class for protection Accuracy limit factor Rated short time thermal current Highest voltage (Um) Rated power-frequency withstand 5A 100 A 1250 A 22.5 mV 0.5 5P 400 40 kA 1 s 24 kV 50 kV

Low Power Current Transformer (LPCT) TLP130 b characteristics according to IEC standard 60044-8 b large primary current range b direct output voltage for measurement and protection b RJ45-8 pts secondary connector b insulation level 0.72 kV b internal diameter 130 mm.
Minimum rated primary current Rated nominal primary current Rated extended primary current Rated nominal secondary output Accuracy class for measurement Accuracy class for protection Accuracy limit factor Rated short time thermal current Highest voltage (Um) Rated power-frequency withstand 5A 100 A 1250 A 22.5 mV 0.5 5P 250 25 kA 1 s 0.72 kV 3 kV

PE57162

AMTED398078EN

71

Characteristics of the functional units

Current transformers for 36 kV

PE57222

For units DM1-A, DM1-D, DM1-W, DM2, DM2-W, IMC, GBC-A, GBC-B
Transformer ARM6T/N1 or N2 b characteristics according to IEC standard 60044-1 b double primary winding b double secondary winding for measurement and protection. Short-time withstand current Ith (kA)
I1n (A) Ith (kA) t (s) Current transformer ARM6T Measurement and protection 5A 5A 50-100 16 - 20 1 7.5 VA - 15 VA - class 0.5 2.5 VA - 5 VA - 5P20 75-150 100-200 150-300 200-400 300/600 1000/1250 25 1 30 VA class 0.5 10 VA 5P20

For units DM1-A, DM1-D, DM2, DM2-W


Transformer ARM9T b characteristics according to IEC standard 60044-1 b double primary winding b double secondary winding for measurement and protection. Short-time withstand current Ith (kA)
I1n (A) Ith (kA) t (s) Current transformer ARM9T Measurement and protection 5A 5A 1000/1250 40 1 30 VA - class 0.5 - Fs < 10 10 VA - 5P20
PE58391

Low Power Current Transformer (LPCT) for units DM1-A, DM1-W


Transformer TLP 130, TLP 190 b characteristics according to IEC standard 60044-8 b large primary current range b direct output voltage for measurement and protection b RJ45-8 pts secondary connector b insulation level 0.72 kV b internal diameter 130 or 190 mm b in SM6-36, TLP 130 can be used for 630 A, TLP 190 can be used up to 1250 A.
LPCT Minimum rated primary current Rated extended primary current Secondary output Accuracy class for measurement Accuracy class for protection Accuracy limit factor Rated short time thermal current Highest voltage (Um) Rated power-frequency withstand

PE57162

TLP 130
5A 1250 A 22.5 mV - 100 A 0.5 5P 250 25 kA 1 s 0.72 kV 3 kV

TLP 190
5A 2500 A 22.5 mV - 100 A 0.5 5P 400 40 kA 1 s 0.72 kV 3 kV

72

AMTED398078EN

Characteristics of the functional units

Voltage transformers for 24 kV

Synthesis table by unit


Units CM VTs VRQ2-n/S1 VRFR-n/S1 VRC2/S1 VRM3-n/S2 VCT24 VRC1/S1 b b b b b b b CVM DM1-A DM1-D DM1-W DM2 DMVL-D b b b b GBC-A GBC-B DMVL-A DMV-A DMV-D CM2 b b b b b b b TM

Transformer VRQ2-n/S1 (phase-to-earth) 50 or 60 Hz b characteristics according to IEC standard 60044-2.


61045N

Rated voltage (kV) Primary voltage (kV) Secondary voltage (V) Thermal power (VA) Accuracy class Rated output for single primary winding (VA) Rated output for double primary winding (VA)

24 10/3 100/3 250 0.5 30 30 30-50 30 15/3 15-20/3 20/3

Transformer VRFR-n/S1 (phase-to-earth) 50 or 60 Hz b characteristics according to IEC standard 60044-2.


Rated voltage (kV) Primary voltage (kV) Secondary voltage (V) Thermal power (VA) Accuracy class Rated output for single primary winding (VA) 17.5 10/3 100/3 250 0.5 30 15/3

61046N

Transformer VRC2/S1 (phase-to-phase) 50 or 60 Hz b characteristics according to IEC standard 60044-2.


Rated voltage (kV) Primary voltage (kV) Secondary voltage (V) Thermal power (VA) Accuracy class Rated output for single primary winding (VA) 24 10 100 500 0.5 50 15 20

PE55648

Transformer VRM3-n/S2 (phase-to-earth and protected by fuses 0.3 A) 50 or 60 Hz b characteristics according to IEC standard 60044-2.
Rated voltage (kV) Primary voltage (kV) Secondary voltage (V) First secondary Thermal power (VA) Accuracy class Rated output for single primary (VA) Second secondary Thermal power (VA) Accuracy class Rated output 12 10/3 200 0.5 30-50 100 3P 50 17.5 15/3 24 20/3

100/3 - 100/3

AMTED398078EN

73

Characteristics of the functional units

Voltage transformers for 24 kV

Transformer VRC1/S1 (phase-to-phase) 50 or 60 Hz b characteristics according to IEC standard 60044-2.


Rated voltage (kV) Primary voltage (kV) Secondary voltage (V) Thermal power (VA) Accuracy class Rated output for single primary winding (VA) 7.2 3.3 110 300 0.5 100 5 100 5.5 110 6 100 6.6 110

DE53562

DE52402

Transformer VCT24 (phase-to-phase) 50 or 60 Hz


Rated voltage (kV) Primary voltage (kV) Secondary voltage (V) Output (VA) 24 10 220 2500 2500 4000 Note: the above mentioned voltage transformers are grounded neutral. For other characteristics, please consult us. 2500 4000 15 20

DE58408

Surge arresters
For units IM500, DM1-A, DM1-W, GAM, DMV-A*, DMVL-A
In (A) Un (kV) 400/630 7.2 10 12 17.5 24

Note: the rated voltage of the surge arrester is according to units rated voltage. (*) limited up to 17.5 kV for DMV-A circuit breaker cubicles.

74

AMTED398078EN

Characteristics of the functional units

Voltage transformers for 36 kV

PE57223

For units CM, GBC-A, GBC-B


Transformer VRF3n/S2 (phase-to-earth) b single primary winding b single secondary
Rated voltage (kV) Primary voltage (kV) Secondary voltage (V) Thermal power (VA) Accuracy class Rated output for single primary winding (VA) Voltage transformer VRF3 36 303 1003 450 0.5 30-50 3P 30 333 1003 or 1103

For units CM2


Transformer VRC3/S1 (phase-to-phase) b single primary winding b single secondary
Rated voltage (kV) Primary voltage (kV) Secondary voltage (V) Thermal power (VA) Accuracy class Rated output for single primary winding (VA) 36 30 100 700 0.5 50-100 33 100 or 110
PE57224

Voltage transformer VRC3

For units TM
Transformer VRC3/S1 (phase-to-phase) b single primary winding b single secondary
Rated voltage (kV) Primary voltage (kV) Secondary voltage (V) Thermal power (VA) 36 30 220 1000

DE58408

Surge arresters
For units IM, DM1-A, SM, GAM2
In (A) Un (kV) 630 36

AMTED398078EN

75

Characteristics of the functional units

Motors protection units

The current rating of fuses installed in units depends on: b motor current rating In b starting current Id b frequency of starts. The fuses rating is calculated such that a current equal to twice the starting current does not blow the fuse within period equal to the starting time. The adjacent table indicated the ratings which should be used, based on the following assumptions: b direct on-line startup b Id/In y 6 b pf = 0.8 (P y 500 kW) or 0.9 (P > 500 kW) b = 0.9 (P y 500 kW) or 0.94 (P > 500 kW). The indicated values are for Fusarc fuses (to DIN standard 43-625). Example: Consider a 950 kW motor at 5 kV.
In = P pf = 130 A

Selection of fuses for CRM units


The color code is linked to the rated voltage of the fuse. Starting current (A) Id/In = 6 Starting time (s) 5 10 Maximum service voltage (kV)

20

Number of starts per hour 6 12 6 12 6


1410 1290 1140 1030 890 790 710 640 610 540 480 440 310 280 250 240 230 210 180 170 250 250 250 250 250 200 200 200 200 160 160 160 160 125 125 125 125 100 100 100 250 250 250 250 250 200 200 200 200 160 160 160 160 125 125 125 125 100 100 250 250 250 250 250 200 200 200 200 160 160 160 160 125 125 125 125 100 100 250 250 250 250 250 200 200 200 200 160 160 160 160 125 125 125 100 100 250 250 250 250 250 200 200 200 200 160 160 160 160 125 125 125 100 100

12

250 250 250 250 250 200 200 200 200 160 160 160 160 125 125 125 100

3.3

6.6

Id = 6 x In = 780 A Then select the next higher value, i.e. 790 A. For six 5-second starts per hour, select fuses rated 200 A.
Note: the same motor could not be protected for 12 starts per hour since the maximum service voltage for the required 250 A rated fuses is 3.3 kV.

11

Selection of fuses for CVM units


Service voltage (kV) Starting current (A) Rated operational current (continous duty) (A) Starting time (s)

5 3
250 250 200 160 160 125 125 100 100 100 80 50

10 6
250 250 200 160 160 160 125 125 100 100 100 50

30 6
250 200 200 160 160 160 125 100 100 100 80

Number of starts per hour

Id = 6 x Ie
3.3 1100 942 785 6.6 628 565 502 439 377 314 251 188 126

Ie
183 157 131 105 94 84 73 63 52 42 31 21

3
250 250 200 160 160 160 125 100 100 100 100 63

3
250 200 200 160 160 160 125 100 100 100 80

6
250 250 200 160 160 160 160 125 100 100 80

Fuse selection method: b if Id 6 x Ie, use Id to select the fuses b if Id < 6 x Ie, use Ie to select the fuses.
Note: Fuses are 292 mm long (Fusarc fuses). Fuses are only for short circuit protection. For 250 A fuses, it is necessary to delay the opening of the contactor.

76

AMTED398078EN

Characteristics of the functional units

Protection of transformers

Fuse ratings for SM6 protection units such as PM, QM, QMB and QMC depend, among other things, on the following criteria: b service voltage b transformer rating b fuse technology (manufacturer) Different types of fuses with medium loaded striker may be installed: v Solefuse fuses as per standard UTE NCF 64.210 v Fusarc CF fuses as per IEC 60.282.1 recommendation and dimensions are related to DIN 43.625 standard. For fuse-switch combination unit type QM, QMB, QMC, refer only to the selection table and reference list of fuses. For all other type of fuses, consult us. Example: for the protection of a 400 kVA transformer at 10 kV, select either Solefuse fuses rated 43 A or Fusarc CF fuses rated 50 A.

PE57161

Fuse selection table d Please consult us for overloads and operation over 40C for France Transfo oil immersed type transformers.
Type of fuse Service Transformer rating (kVA) Rated voltage 25 50 100 125 160 200 250 315 400 500 630 800 1000 1250 1600 2000 2500 voltage (kV) (kV) Solefuse (UTE NFC standards 13.100. 64.210) 5.5 6.3 16 31.5 31.5 63 63 63 63 63 7.2 10 6.3 6.3 16 16 31.5 31.5 31.5 63 63 63 63 15 6.3 6.3 16 16 16 16 16 43 43 43 43 43 63 20 6.3 6.3 6.3 6.3 16 16 16 16 43 43 43 43 43 63 24 Solefuse (general case, UTE NFC standard 13.200) 3.3 16 16 31.5 31.5 31.5 63 63 100 100 7.2 5.5 6.3 16 16 31.5 31.5 63 63 63 80 80 100 125 6.6 6.3 16 16 16 31.5 31.5 43 43 63 80 100 125 125 10 6.3 6.3 16 16 16 31.5 31.5 31.5 43 43 63 80 80 100 12 13.8 6.3 6.3 6.3 16 16 16 16 31.5 31.5 31.5 43 63 63 80 17.5 15 6.3 6.3 16 16 16 16 16 31.5 31.5 31.5 43 43 63 80 20 6.3 6.3 6.3 6.3 16 16 16 16 31.5 31.5 31.5 43 43 63 24 22 6.3 6.3 6.3 6.3 16 16 16 16 16 31.5 31.5 31.5 43 43 63 Fusarc CF and SIBA (1) (general case for QM, QMB and QMC cubicle according to IEC 62271-105) 3.3 16 25 40 50 50 80 80 100 125 125 160(1) 200(1) 7.2 5 10 16 31.5 40 40 50 63 80 80 125 125 160(1) 5.5 10 16 31.5 31.5 40 50 50 63 80 100 125 125 160(1) 160(1) 6 10 16 25 31.5 40 50 50 63 80 80 125 125 160(1) 160(1) 6.6 10 16 25 31.5 40 50 50 63 80 80 100 125 125 160(1) 10 6.3 10 16 20 25 31.5 40 50 50 63 80 80 100 100 125(1) 200(1) 12 11 6.3 10 16 20 25 25 31.5 40 50 50 63 80 100 100 125(1) 160(1) 13.8 6.3 10 16 16 20 25 31.5 31.5 40 50 50 63 80 80 100(1) 125(1) 125(1) 17.5 15 6.3 10 10 16 16 20 25 31.5 40 50 50 63 80 80 100(1) 125(1) 125(1) 20 6.3 6.3 10 10 16 16 25 25 31.5 40 40 50 50 63 80 100(1) 125(1) 24 22 6.3 6.3 10 10 10 16 20 25 25 31.5 40 40 50 50 80 80 100(1) (2) Fusarc CF for dry type transformers 30 10 10 16 20 25 31.5 31.5 50 50 63 63 36 31.5 10 10 16 20 25 25 31.5 50 50 63 63 33 6.3 10 16 20 25 25 31.5 40 50 50 63 34.5 6.3 10 16 20 25 25 31.5 40 50 50 63 Fusarc CF oil immersed type transformers (2) 30 10 10 16 20 25 31.5 31.5 40 40 50 63 36 31.5 10 10 16 20 25 31.5 31.5 40 40 50 63 33 10 10 16 20 25 25 31.5 31.5 40 40 50 34.5 10 10 16 20 25 25 31.5 31.5 40 40 50 The color code is linked to the rated voltage of the fuse Rating in A - no overload at 5C < t < 40C.

(1) SIBA fuses (2) This selection table has been prepared according to the technical characteristics of France Transfo. The characteristics of transformers and fuses may change according to manufactures and standards. AMTED398078EN

77

Characteristics of the functional units

Protection of transformers

Fuses dimensions
Solefuse (UTE standards)
DE53563

55

Ur (kV) 7.2 12 17.5

Ir (A) 6.3 to 125 100 80 6.3 to 63

L (mm) 450 450 450 450

(mm) 55 55 55 55

Weight (kg) 2 2 2 2

450 35 35

23

24

Fusarc CF (DIN standards)


DE57467

45

Ur (kV) 7.2 12

Ir (A) 125 6.3 10 16

L (mm) 292 292 292 292 292 292 292 292 292 292 292 292 442 442 442 442 442 442 442 442 442 442 537 537 537 537 537 537 537

(mm) 86 50.5 50.5 50.5 50.5 57 57 57 78.5 78.5 78.5 78.5 50.5 50.5 50.5 50.5 57 57 57 78.5 78.5 86 50.5 50.5 57 78.5 78.5 86 86

Weight (kg) 3.3 1.2 1.2 1.2 1.2 1.5 1.5 1.5 2.8 2.8 2.8 2.8 1.6 1.6 1.6 1.6 2.2 2.2 2.2 4.1 4.1 5.3 1.8 1.8 2.6 4.7 4.7 6.4 6.4

L 33 33

23

20 25 31.5 40 50 63 80 100 24 6.3 10 16 20 25 31.5 40 50 63 80 36 10 16 25 31.5 40 50 63

SIBA
DE57467

45

Ur (kV) 7.2 12

Ir (A) 160 200 125 160 200

L (mm) 292 292 292 292 292 442 442 442

(mm) 85 85 67 85 85 85 85 85

Weight (kg) 3.8 5.4 2 3.8 3.8 5.4 5.4 5.4

L 33 33

23 17.5 24

125 100 125

78

AMTED398078EN

Characteristics of the functional units

Interlocks

Switch units
b the switch can be closed only if the earthing switch is open and the access panel is in position. b the earthing switch can be closed only if the switch is open. b the access panel for connections can be opened only if the earthing switch is closed. b the switch is locked in the open position when the access panel is removed. The earthing switch may be operated for tests.

Functional interlocks
These comply with IEC recommendation 62271-200 and EDF specication HN 64-S-41 (for 24 kV). In addition to the functional interlocks, each disconnector and switch include: b built-in padlocking capacities (padlocks not supplied) b four knock-outs that may be used for keylocks (supplied on request) for mechanism locking functions.

Circuit-breaker units
b the disconnector(s) can be closed only if the circuit breaker is open and the front panel is locked (interlock type 50). b the earth switch(es) can be closed only if the disconnector(s) is/are open. b the access panel for connections can be opened only if: v the circuit breaker is locked open, v the disconnector(s) is/are open, v the earth switch(es) is/are closed.
Note: it is possible to lock the disconnector(s) in the open position for no-load operations with the circuit breaker.

Unit interlock
Units
IM, IMB, IMC PM, QM, QMB, QMC, DM1-A, DM1-D, DM1-W, DM1-Z, DM1-S, DMV-A, DMV-D, DMV-S, DMVL-A, DMVL-D CRM, CVM NSM GAM SM DM2, DM2-W b b

Interlock
A1 C1 C4 A3 b b b A4 b A5 50 b 52 P1 b P2 P3 P5

b b b b

b b b b b

DE53565

A1 type
O

Key-type interlocks
Outgoing units
Aim: b to prevent the closing of the earthing switch on a transformer protection unit unless the LV circuit breaker is locked in open or disconnected position.

DE53566

C1 type

b to prevent the access to the transformer if the earthing switch for transformer protection has not rst been closed.
S

DE53567

C4 type
O

S O

b to prevent the closing of the earthing switch on a transformer protection unit unless the LV circuit breaker is locked in open or disconnected position. b to prevent the access to the transformer if the earthing switch for transformer protection has not rst been closed.

MT20240EN

Legend for key-type interlocks:


no key free key captive key panel or door

AMTED398078EN

79

Characteristics of the functional units

Interlocks

DE53568

A3 type
O

Ring units
Aim: b to prevent the closing of the earthing switch of a load-side cubicle unless the line-side switch is locked open.
O

DE53569

A4 type
O O

b to prevent the simultaneous closing of two switches.

DE53570

A5 type
O

b to prevent the closing of the earthing switch of the casing unit unless the downstream and the upstream switches are locked in the open position.

S O S

DE53571

50 type
O O

Prevents b on-load switching of the disconnectors. Allows b off-load operation of the circuit breaker with the disconnectors open (double isolation). b off-load operation of the circuit breaker with the disconnector open (single isolation).

DE59203

Type 52
O O

Prevents b on-load switching of the disconnectors. Allows b off-load operation of the contactor with the disconnectors open (double isolation). b off-load operation of the contactor with the disconnector open (single isolation).

MT20240EN

Legend for key-type interlocks:


no key free key captive key panel or door

80

AMTED398078EN

Characteristics of the functional units

Interlocks

DE53572

P1 type
O X

b to prevent the closing of an earthing switch if the switch of the other unit has not been locked in the open position.

DE53573

P2 type
X O O

b to prevent on-load operation of the disconnector unless the switch is locked open b to prevent the closing of the earthing switches unless the disconnector and the switch are locked open.

DE53574

P3 type
AX O

b to prevent on-load operation of the disconnector unless the switch is locked open b to prevent the closing of the earthing switches with the unit energised, unless the disconnector and the switch are locked open b to allow off-load operation of the switch.

DE53575

P5 type
P

b to prevent the closing of the earthing switch of the incoming unit unless the disconnector and the switch is locked open.

MT20240EN

Legend for key-type interlocks:


no key free key captive key panel or door

AMTED398078EN

81

82

AMTED398078EN

Connections

Contents

Connections with dry-type cables for 24 kV


Selection table

84 84 85 85 86 87 88 89 89 90 90

Cable-connection from below for 24 kV


Cable positions Trenches depth Trench diagrams example for installation IAC: A-FL classied Trench diagrams and oor void drawings example

Connections with dry-type cables for 36 kV


Selection table

Cable-connection from below for 36 kV


Cable positions

AMTED398078EN

83

Connections

Connections with dry-type cables for 24 kV


Selection table
The ageing resistance of the equipment in an MV/LV substation depends on three key factors:
b the need to make connections correctly New cold tted connection technologies offer ease of installation that favours resistance over time. Their design enables operation in polluted environments under severe conditions. b the impact of the relative humidity factor The inclusion of a heating element is essential in climates with high humidity levels and with high temperature differentials. b ventilation control The dimension of the grills must be appropriate for the power dissipated in the substation. They must only traverse the transformer area. Network cables are connected: b on the switch terminals b on the lower fuse holders b on the circuit breakers connectors. The bimetallic cable end terminals are: b round connection and shank for cables y 240 mm2 b square connection round shank for cables > 240 mm2 only. Crimping of cable end terminals to cables must be carried out by stamping. The end connectors are of cold tted type Schneider Electrics experience has led it to favour this technology wherever possible for better resistance over time. The maximum admissible cable cross section: b 630 mm2 for 1250 A incomer and feeder cubicles b 240 mm2 for 400-630 A incomer and feeder cubicles b 120 mm2 for contactor cubicles b 95 mm2 for transformer protection cubicles with fuses. Access to the compartment is interlocked with the closing of the earthing disconnector. The reduced cubicle depth makes it easier to connect all phases. A 12 mm pin integrated with the eld distributor enables the cable end terminal to be positioned and attached with one hand. Use a torque wrench set to 50 mN.

PE50775

PE57840

Round connector
PE50776

Square connector

Dry-type single-core cable


Short inner end, cold tted
Performance 3 to 24 kV 400 A - 630 A 3 to 24 kV 1250 A Cable end terminal type Round connector X-section mm2 50 to 240 mm2 Supplier All cold tted cable end suppliers: Silec, 3M, Pirelli, Raychem, etc. All cold tted cable end suppliers: Silec, 3M, Pirelli, Raychem, etc. Number of cables 1 or 2 per phase Comments For larger x-sections, more cables and other types of cable end terminals, please consult us For larger x-sections, more cables and other types of cable end terminals, please consult us

Round connector Square connector

50 to 630 mm2 > 300 mm2 admissible

1 or 2 per phase y 400 mm2 400 < 1 y 630 mm2 per phase

Three core, dry cable


Short inner end, cold tted
Performance 3 to 24 kV 400 A - 630 A 3 to 24 kV 1250 A Cable end terminal type Round connector X-section mm2 50 to 240 mm2 Supplier All cold tted cable end suppliers: Silec, 3M, Pirelli, Raychem, etc. All cold tted cable end suppliers: Silec, 3M, Pirelli, Raychem, etc. Number of cables 1 per phase Comments For larger x-sections, more cables and other types of cable end terminals, please consult us For larger x-sections, more cables and other types of cable end terminals, please consult us

Round connector

50 to 630 mm2

1 per phase

Note: b The cable end terminals, covered by a eld distributor, can be square, b PM/QM type cubicle, round end connections 30 mm max.

84

AMTED398078EN

Connections

Cable-connection from below for 24 kV


Cable positions

DE58676

DE58677

630 A
IM, NSM-cables, NSM-busbars SM IMC PM, QM QMC CRM, CVM DM1-A DMVL-A DMV-S DM1-W GAM2 GAM DMV-A DM1-S 945 945 400 400 400 430 430 430 320 370 760 470 320 543

1250 A
945

320

DE58678

Cable-connection height H measured from oor (mm)

IM, NSM-cables, NSM-busbars, SM

IMC, PM, QM, QMC

CRM, CVM

320 620 313


200 200 420

200 200 420

200 200 420

GAM, GAM2
DE58679 DE53581

DMV-A, DMV-S (630 A)

H
H

200

200 420

165 165 313

275

DM1-A, DM1-S, DMVL-A DM1-W (630 A)


DE58655 DE58656

DM1-A, DM1-W (1250 A)


DE58417

DMV-A (1250 A)

200 200 420

333

330

789

145 145

445

371,5

510,5

200 200 420

X 313

X = 330 X = 268 X = 299

: 1 single-core cable : 2 single-core cables : Three core cable

AMTED398078EN

85

Connections

Cable-connection from below for 24 kV


Trenches depth
Cabling from below (all units)

DE53585

625 500 375

b Through trenches: the trench depth P is given in the following table for usual dry single-core cables type (for tri-core cables consult us). b With stands: to reduce depth P or avoid trenches, by placing the units on 400 mm concrete footings. b With oor void: the trench depth is given in the following table for usual types of cables. 630 A
Cable section (mm2) All cubicles expect ... 12.5 kA/1s S < 120 330 16 kA/1s 550 550 Other cubicles DMVA 12-16 kA/1s 550 800 CVM 12.5 kA/1s 330 16 kA/1s 550 DM1A, DM1S, DM1W, DMVLA 12.5 kA/1s 16 kA/1s 550 SM, GAM 12-16 kA/1s DM1A, DMV-A, DM1-W 12-16 kA/1s

1250 A

Depth P (mm)
330 120 < S < 240 330 Opposite to Under the 550 circuit breaker: circuit breaker: 330 450

187.5

S > 400

1000

1400

Cable trench drawings


1250 A units (represented without switchboard side panels) SM, GAM DMV-A For single and tri-core cables For single and tri-core cables
DE57176 DE57177 DE57178

630 A units
DM1-A, DM1-W For single-core cables
100
DE57179

DMV-A, DMV-S For single cables


100

100

100

100 P 480 445 P P P

600 740 50

600 740 50

840 740 50

600 740 50

86

AMTED398078EN

Connections

Cable-connection from below for 24 kV


Trench diagrams example for installation IAC: A-FL classified
Units represented without switchboard side panels

630 A units Cable entry or exit through right or left side


DE57180 DE57181

630 A units Rear entry or exit with conduits


DE57182

630 A units Front entry or exit with conduits


100

100

100

P1 P2 P2
P3

P1

600

25

25

25

IM

IM QMC

IM

IM IM

DM1

DM1

IM

Required dimensions (mm)

Note 1: for connection with conduits, the bevel (C) must correspond to the following trench dimensions: P1 = 75 mm or P2/P3 = 150 mm. Note 2: please refer to chapter Layout examples for a site application.

PE50797

Cabling from above


Height: 450 mm

On each 630 A unit of the range, except those including a low-voltage control cabinet and EMB compartment, the connection is made with dry-type and single-core cables.
Remarks: b Not available for internal arc IEC 62271-200 in busbar compartment. b Not available in 1250 A.

AMTED398078EN

87

Connections

Cable-connection from below for 24 kV


Trench diagrams and floor void drawings example

Installation with oor void for 16 kA 1 s downwards exhaust


b Position of xing holes depends on the width of the unit:
Width 375 500 625 750 Cubicles All GAM Other QMC Other All XG (mm) X (mm) 57.5 57.5 182.5 307.5 57.5 432.5 260 260 260 260 510 260 XD (mm) 57.5 182.5 57.5 57.5 57.5 57.5 XG X XD

5 50 minimu m

70

50 60 50

740

110 min

. 930 90 min . 110

Installation with cable trench for 12.5 kA 1 s downwards exhaust for 16 kA 1 s and 20 kA 1 s upwards exhaust
b Position of xing holes b depends on the width of the unit:
Cubicle width (mm) 125 375 500 625 750 b (mm) 95 345 470 595 720 2150 minimu m
DE57196

4 x M8

330 minimu m

100 50 740 60 0

88

AMTED398078EN

DE57188

Connections

Connections with dry-type cables for 36 kV


Selection table
The ageing resistance of the equipment in an MV/LV substation depends on three key factors:
b the need to make connections correctly New cold tted connection technologies offer ease of installation that favours resistance over time. Their design enables operation in polluted environments under severe conditions. b the impact of the relative humidity factor The inclusion of a heating element is essential in climates with high humidity levels and with high temperature differentials. b ventilation control The dimension of the grills must be appropriate for the power dissipated in the substation. They must only traverse the transformer area. Network cables are connected: b on the switch terminals b on the lower fuse holders b on the circuit breakers connectors. The bimetallic cable end terminals are: b round connection and shank for cables y 240 mm2. Crimping of cable lugs to cables must be carried out by stamping. The end connectors are of cold tted type Schneider Electrics experience has led it to favour this technology wherever possible for better resistance over time. The maximum admissible copper(*) cable cross section: b 2 x (1 x 240 mm2 per phase) for 1250 A incomer and feeder cubicles b 240 mm2 for 400-630 A incomer and feeder cubicles b 95 mm2 for transformer protection cubicles with fuses. Access to the compartment is interlocked with the closing of the earthing disconnector. The reduced cubicle depth makes it easier to connect all phases. A 12 mm pin integrated with the eld distributor enables the cable end terminal to be positioned and attached with one hand. Use a torque wrench set to 50 mN.
(*) Consult us for alu cable cross sections

Single-core cables CableBending section radius (mm2) (mm)

Units 630 A IM, IMC, QM, CM, CM2, PM, DM1-A, DM1-W, GAM, GAM2, SM, TM, NSM Depth P (mm) P1 P2
350 380 410 425 455 470 500 530 550 580 610 625 655 670 700 730

1 x 35 1 x 50 1 x 70 1 x 95 1 x 120 1 x 150 1 x 185 1 x 240

525 555 585 600 630 645 675 705

Note: the unit and the cables requiring the greatest depth must be taken into account when determining the depth P for single-trench installations. In double-trench installations must be taken into account to each type of unit and cable orientations.

Cabling from below


All units through trenches b the trench depth P is given in the table opposite for commonly used types of cables.

Trench diagrams
Cable entry or exit through right or left side
DE59723 DE59724

Rear entry or exit with conduits


DE59725

Front entry or exit with conduits

100

100

100

P2

200 1000

P1 P2

P2

200 1000

300

1000

300

QM IM IM

100

QM 100 200 200 IM IM

100

QM 100 IM IM

100 100

200

100

100

100

AMTED398078EN

89

Connections

Cable-connection from below for 36 kV


Cable positions

Side view
IM, SM units
DE59727 DE57183

QM, PM units
DE57184

DM1-A, DM1-W units


DE59730

GAM2 unit

1210 540 400 456 632

350 700 350

350 700 350

380 700 380

350 700 350

Front view
IM, SM
DE57185

QMC

GAM

GAM2

QM, PM

DM1-A, DM1-W

1200 620 490 620 540 455

375 750 1000

375

470 750 750

375

375 750 1000

510

90

AMTED398078EN

Installation

Contents

Dimensions and weights for 24 kV Units dimensions for 24 kV Civil engineering for 24 kV Layout examples for 24 kV Dimensions and weights for 36 kV Civil engineering for 36 kV Layout examples for 36 kV

92 93 95 96 97 98 99

AMTED398078EN

91

Installation

Dimensions and weights for 24 kV


Dimensions and weights
Unit type IM,IMB IMC H PM, QM, QMB QMC CVM, CRM DM1-A, DM1-D, DM1-W, DM2, DMVL-A, DMVL-D DM1-S DMV-A, DMV-D DMV-S CM CM2 GBC-A, GBC-B NSM-cables, NSM-busbars GIM GEM (2) GBM GAM2 GAM SM TM Height H (mm) 1600 (1) 1600 (1) 1600 (1) 1600 (1) 2050 1600 (1) 1600 (1) 1695 (1) 1600 (1) 1600 (1) 1600 (1) 1600 (1) 2050 1600 1600 1600 1600 1600 1600 (1) 1600 Width (mm) 375/500 500 375/500 625 750 750 750 625 625 375 500 750 750 125 125 375 375 500 375 750 Depth D (mm) 1030 1030 1030 1030 1030 1230 1230 1115 1115 1030 1030 1030 1030 930 930/1060 (2) 1030 1030 1030 1030 1230 Weight (kg) 130/140 210 140/160 190 400 410 350 350 270 200 220 300 270 40 40/45 130 130 170 130/160 210 430

DE57186

90 Exhaust channelling

840 Base footprint

375/500 (3) 1030

DM1-A, DM1-D, DM1-W, DM1-Z (1250 A) 1600 (1)

(1) Add to height 450 mm for low-voltage enclosures for control/monitoring and protection functions. To ensure uniform presentation, all units (except GIM and GEM) may be equipped with low-voltage enclosures. (2) Depending on the busbar conguration in the VM6 unit, two types of extension units may be used: b to extend a VM6 DM12 or DM23 unit, use an extension unit with a depth of 1060 mm b for all other VM6 units, a depth of 930 mm is required. (3) For the 1250 A unit.

92

AMTED398078EN

Installation

Units dimensions for 24 kV

IM, IMB, PM, QM, QMB, SM, IMC, QMC, CM, CM2
DE58661 DE58662

NSM-cables, NSM-busbars, CRM, CVM


450
DE58663

GBM, GAM2

450

1600

1600

90

840

30 70

90

840

30 70

90

840

30 70

GAM
DE58664 DE58665

GIM
DE58666

GEM

1600

1600

1600

90

840

30 70

930

930 1060

GBC-A, GBC-B
DE58667 DE58668

IM with EMB option


450 503

1600

1600

90

840

100

90

840

30 70

AMTED398078EN

93

Installation

Units dimensions for 24 kV

DMVL-A, DMVL-D, DM1-A, DM1-D, DM1-W, DM1-Z, DM1-S, DM2 630 A


DE58669 DE58670

DM1-A 630 A with EMB option


DE58671

DM1-A, DM1-W 1250 A

450

503

450

1600

1600

1600

90

840

200 100

90

840

200 100 832 840

330 200 100

90

DMV-A 630 A
DE58672 DE58673

DMV-A 1250 A

1680

1680

100 150 85 90 840 100 90 74 840 100 85 445

DMV-D
DE58674 DE58675

DMV-S

1680

1600

100
90 85 840 100

150 85 90 840 100

94

AMTED398078EN

Installation

Civil engineering for 24 kV


Ground preparation
To obtain the internal arc performance, ground implementation must comply with the following requirements: b Straightness: 2 mm / 3 m (Rep.1) b Flatness: 3 mm maximum (Rep.2) All the elements allowing the evacuation of the gas (duct, casing, etc.) must be able to bear a load of 250 kg/m2.
DE100520

Cubicle front face


2

Fixing of units
With each other The units are simply bolted together to form the MV switchboard (bolts supplied). Busbar connections are made using a torque wrench set to 28 mN. On the ground b For switchboards comprising up to three units, the four corners of the switchboard must be secured to the ground with using: v M8 bolts (not supplied) screwed into nuts set into the ground using a sealing pistol v screw rods grouted into the ground. b For switchboards comprising more than three units, each unit may be xed to the ground b In circuit-breaker or contactor units, xing devices are installed on the opposite side of the switchgear.

AMTED398078EN

95

Installation

Layout examples for 24 kV

Prefabricated substation (Kiosk)


PE57168 DE58657

Position of cubicles in a substation


Installation of a switchboard classied IAC: A-FL
10

930

25 (minimum)

300 (minimum)

Installation of a switchboard classied IAC: A-FLR


DE58658EN

300 (minimum)

930

25 (minimum) or 50 (evacuation by the top)

300 (minimum)

With upwards exhaust left side


(ceiling height u 2150 mm) To enable the evacuation of gases by the top, users must install a conduit xed to the coupling ange at right or left of the switchboard. The end of the duct must block water, dust, moisture, animals, etc. from entering and at the same time enable the evacuation of gases into a dedicated area through a device situated at the outer end of the duct (not supplied). Evacuation duct example The evacuation duct must be made of metal sheet of sufcient thickness to withstand pressure and hot gases.
PE57235 DE58651

Evacuation duct

569

400

400

1600

Duct (not supplied)

Coupling ange (supplied)

96

AMTED398078EN

Installation

Dimensions and weights for 36 kV


Dimensions and weights
Unit type IM, SM IMC, IMB QM, PM, QMB QMC DM1-A DM1-D DM1-W NSM GIM DM2 DM2-W CM, CM2 GBC-A, GBC-B GBM GAM2 GAM Height (mm) 2250 2250 2250 2250 2250 2250 2250 2250 2250 2250 2250 2250 2250 2250 2250 2250 Width (mm) 750 750 750 1000 1000 1000 1000 1500 250 1500 1500 750 750 750 750 750 Depth (1) (mm) 1400 (3) 1400 (2) 1400 (3) 1400 (3) 1400 (2) 1400 (2) 1400 (2) 1400 (2) 1400 1400 (2) 1400 (2) 1400 (2) 1400 (3) 1400 (3) 1400 (3) 1400 (3) Weight (kg) 310 420 330 420 600 560 660 620 90 900 920 460 420 260 250 295

(1) The depth measures are given for the oor surface. (2) The depth in these units are 1615 mm with the enlarged low voltage compartment. (3) The depth in these units are 1500 mm with the standard low voltage compartment.

Dimensions
IM, SM, IMC, QM, PM, IMB, GBM, GAM, GAM2, GBC-A,GBC-B QMB, QMC units
DE59662 DE59663

CM, CM2, NSM units

DM1-A, DM1-D, DM2, DM1-W, DM2-W units


DE59664

100

215

215

2250

2250

2250

1400

32

1400

32

1400

32 230

AMTED398078EN

97

Installation

Civil engineering for 36 kV


Ground preparation
Units may be installed on ordinary concrete grounds, with or without trenches depending on the type and cross-section of cables. Required civil works are identical for all units.

150
DE5961

A B 50

Fixing of units
With each other The units are simply bolted together to form the MV switchboard (bolts supplied). Busbar connections are made using a torque wrench set to 28 mN. On the ground b for switchboards comprising up to three units, the four corners of the switchboard must be secured to the ground using: v bolts (not supplied) screwed into nuts set into the ground using a sealing pistol v screw rods grouted into the ground b for switchboards comprising more than three units, the number and position of xing points depends on local criteria (earthquake withstand capacities, etc.) b position of xing holes depends on the width of units.
Unit type IM, IMC, IMB, QM, PM, SM, CM, CM2, TM GBC-A, GBC-B, GBM, GAM2, IMB, GAM, QMB DM1-A, DM1-D, DM1-W, QMC DM2, NSM, DM2-W GIM A (mm) 750 1000 1500 250 B (mm) 650 900 1400 150

1100 1400 150

14.2 x 25

98

AMTED398078EN

Installation

Layout examples for 36 kV

Conventional substation (Masonery)


Top view
DE59665 DE59666

Side view

100

100 5200 min. 1770 min. 2650


(2)

2550 min.

(1)

min.

100

100

100

Minimum required dimensions (mm) (1) In case of upper incoming option: it must be 2730 mm (no internal arc withstand if selected) (2) In case of upper incoming option: it must be 2830 mm (no internal arc withstand if selected)

Top view
DE59667

3430 min. 100 1715 min.

100

AMTED398078EN

99

100

AMTED398078EN

Appendices Order form

Contents

Appendices
Trip curves for VIP 300 LL or LH relays Trip curves for VIP 35 relays Fusarc CF fuses Solefuse fuses
102 103 104 105

Order form
SM6 - Switching
Switching Automatic Transfer System 106 106 107 108 108 110 111 112 113 114 115 116

SM6 - Protection
Circuit breaker Fuse switch Vacuum contactor (Direct Motor Starter) for 24 kV

SM6 - Metering SM6 - Other functions SF1 - Lateral disconnectable or withdrawable SFset - Lateral disconnectable for SM6 24 kV Evolis - Frontal xed version for SM6 24 kV (up to 17.5 kV) Evolis - Lateral disconnectable version for SM6 24 kV (up to 24 kV)

117

AMTED398078EN

101

Appendices

Trip curves for VIP 300 LL or LH relays

DE53614

t>

t>

t >>

t >>

Is 1.2 Is

10 Is

I >>

Is 1.2 Is 10 Is

I >>

With lower denite time threshold

With lower inverse denite time threshold

Denite time tripping curves


SI curve
t (s)
DE53615

VI curve
t (s) 100

100

10

10

1 0.6 0.4 0.3 0.2 0.15 0.1 0.07 0.05 I/Is 1 1.2 10 100

0.1

0.1

0.6 0.4 0.3 0.2 0.15 0.1 0.07 0.05 I/Is 1 1.2 10 100

0.01

0.01

EI curve
t (s)
DE53616

RI curve
t (s) 10

1000

100

1 10 0.6 0.4 0.3 1 0.1 0.6 0.4 0.3 0.2 0.15 0.1 0.07 0.05 1 1.2 10 0.2 0.15 0.1 0.07 0.05

0.1

0.01

I/Is 100

0.01 1 10

I/Is 100

102

AMTED398078EN

Appendices

Trip curves for VIP 35 relays

Phase protection curve


DE53617EN

s 100

The trip curve shows the time before the relay acts, to which must be added 70 ms to obtain the breaking time.

10

0.1

Total breaking time

Type 0.01 0 1.2 5 10 15 20 25 30 I/Is

AMTED398078EN

103

Appendices

Fusarc CF fuses
Fuse and limitation curves

Fuse curve 3.6 - 7.2 - 12 - 17.5 - 24 - 36 kV


Time (s)
4A 6.3 A 10 A 16 A 20 A 25 A 31.5 A 40 A 50 A 63 A 80 A 125 A 160 A 200 A
8 1000 1000 8 6 4 2 100 8 6 4 2 10 8 6 4 2 1 8 6 4 2 0.1 8 6 4 2 0.01 2 10 4 6 8 100 2 4 6 2 4 6 8 10000

DE53618

100 A

250 A

Current (A)

Limitation curve 3.6 - 7.2 - 12 - 17.5 - 24 - 36 kV


Maximum value of the limited broken current (kA peak) The diagram shows the maximum limited broken current value as a function of the rms current value which could have occured in the absence of a fuse.
100
DE53619

8 6 4

Ia
2

8 1.

Ik

Is

Ik

2
250 A 200 A 160 A 125 A 100 A 80 A 63 A 50 A 40 A 31.5 A 25 A 20 A 16 A 10 A 6.3 A

10 8 6 4

1 8 6 4

4A

0.1

0.1

10

100

Rms value of the presumed broken current (kA)

104

AMTED398078EN

Appendices

Solefuse fuses
Fuse and limitation curves

Fuse curve 7.2 - 12 - 17.5 - 24 kV


Time (s)
6.3 A 10 A 16 A 20 A 25 A 31.5 A 43 A 63 A 80 A
6 8 2 1000 8 6 4 2 100 8 6 4 2 10 8 6 4 2 1 8 6 4 2 0.1 8 6 4 2 0.01 10 2 4 100 4 6 8 1000 2 4 6 8 10000

DE53620

100 A 125 A

Current (A)

Limitation curve 7.2 - 12 - 17.5 - 24 kV


Maximum value of the limited broken current (kA peak) The diagram shows the maximum limited broken current value as a function of the rms current value which could have occured in the absence of a fuse.
100
DE53621

8 6 4

Ia
2

8 1.

Ik

Is

Ik

2
125 A 100 A 80 A 63 A 43 A 31.5 A 25 A 20 A 16 A 10 A 6.3 A

10 8 6 4

1 8 6 4

0.1 0.1

10

100

Rms value of the presumed broken current (kA)

AMTED398078EN

105

Order form

SM6
Switching

Only one of the boxes (ticked X or lled by the needed value) have to be considered between each horizontal line. Green box X corresponds to none priced functions.

Basic cubicle
Rated voltage Ur Service voltage Short-circuit current Isc Rated current Ir Internal arc withstand Type of cubicle 24 kV SM 375 IM 375 IM 500 IM 750 IMC 750 Middle IMC 500 12.5 kA 1s for 24 kV

Quantity (kV) (kV) (kA) (A) 16 kA 1s for 36 kV IMB 375

SM 500 (for 1250 A) 36 kV SM 750 Position in the switchboard

IMB 750 Last on right Right

First on left Direction of lower busbars for IMB

Left (impossible as rst cubicle of switchboard)

Options
Common options
Replacement of CIT by Electrical driving motorization and/or coil voltage (not applicable on SM cubicle) 24 Vdc 32 Vdc 48 Vdc 60 Vdc Signalling contact Interlocking 2 O & 2 C on SW CI1 110 Vdc 120-125 Vdc 137 Vdc 220 Vdc CI2 120/127 Vac (50 Hz) 220/230 Vac (50 Hz) 120/127 Vac (60 Hz) 220/230 Vac (60 Hz)

1 C on SW and 1 O & 1 C on ES (not applicable on SM cubicle) 2 O & 3 C on SW and 1 O & 1 C on ES Flat key type P1 SM6-SM6 On earthing switch Cubicle no. P3 SM6-SM6 Flair 23DV zero sequence Flair 22D Flair 23DV

Tubular key type For all cubicle (except SM) A4 Localisation of 2nd lock for A3 Localisation of 2nd lock for A4 SM cubicle only A3 SM6-SM6 On switch

P2 SM6-SM6 Replacement of 630 A upper busbar by 1250 A (not possible for IMB) Digital ammeter or fault current indicator AMP 21D Flair 21D

24 kV options
Remote control signalling 2 lights 2 lights and 2 PB 2 lights and 2 PB + 1 switch 220 V

Voltage of the lights (must be the same than electrical driving mechanism) 24 V 48 V 110/125 V Roof conguration (A, B or C only one choice possible) A - Cable connection by the top (cable maxi 240 mm2 with VPIS) Single core B - Low voltage control cabinet (h = 450 mm) C - Wiring duct Cable connection by the bottom (not applicable on IMB, cable maxi 240 mm2) Three core 50 W heating element Surge arresters for IM 500 7.2 kV 10 kV Operation counter CTs for IMC (quantity) Visibility of main contacts Pressure indicator device Analogic manometer without visibility of main contacts Pressure switch Analogic manometer with visibility of main contacts Busbar eld distributors for severe conditions (only for 630 A) Internal arc version (not possible with top incomer option) 16 kA 1 s Gaz exhaust direction Downwards (only for 16 kA 1s) 20 kA 1 s Upwards 12 kV 1 17.5 kV 2 24 kV 3 Single core 2 x single core 2 x single core With unpunched door

36 kV options
Electrical driving mechanism (with O/C coils and AC contacts) O/C coils without electrical driving mechanism Cable connection by the top (single core cable maxi 240 mm2 with VPIS) Cable connection by the bottom (2 x single core, cable maxi 240 mm2, not applicable on IMC) Surge arresters (not applicable on IMB, IMC cubicles) 36 kV

106

AMTED398078EN

Order form

SM6
Switching
Automatic Transfer System

Only one of the boxes (ticked X or lled by the needed value) have to be considered between each horizontal line. Green box X corresponds to none priced functions.

Basic cubicle
Rated voltage Ur Service voltage Short-circuit current Isc Rated current Ir Internal arc withstand Type of cubicle/upper busbar for 24 kV Ir = 630 A, Ir busbar = 400 A Ir = 630 A, Ir busbar = 630 A Ir = 630 A, Ir busbar = 1250 A Type of cubicle for 36 kV Position in the switchboard First on left Incoming bottom busbar for NSM busbar NSM busbar Middle NSM busbar NSM busbar 12.5 kA 1s for 24 kV

Quantity (kV) (kV) (kA) (A) 16 kA 1s for 36 kV NSM cable NSM cable NSM cable NSM cable Last on right Right

Left Cable connection by the bottom (cable maxi 240 mm2) for NSM cable Three core on both Stand by source Utility with paralleling Control unit HMI language French English Spanish Portuguese Single core on both

2 x single core on both Generator without paralleling Utility without paralleling Chinese

Options
Common options
Signalling contact Operation counter Interlocking SM6-SM6 1 x P1 2 x P1 1 x A3 2 x A3 Right cubicle Left cubicle Control and monitoring Protocol type Modem type DNP3 FFSK PSTN IEC 101/204 RS485 GSM Modbus (by default) RS232 (by default) FSK Right cubicle On switch On switch On switch Tubular key type Right cubicle Flat key type Left cubicle Right and left cubicle Left cubicle On earthing switch On earthing switch On earthing switch 1 C on SW and 1 O & 1C on ES

24 kV options
2 heating elements Busbar eld distributors for severe conditions (only for 630 A) Internal arc version (not possible with top incomer option) 16 kA 1 s Gaz exhaust direction Downwards (only for 16 kA 1s) 20 kA 1 s Upwards

AMTED398078EN

107

Order form

SM6
Protection
Circuit breaker

Only one of the boxes (ticked X or lled by the needed value) have to be considered between each horizontal line. Green box X corresponds to none priced functions.

Basic cubicle
Common 24/36 kV
Rated voltage Ur Service voltage Short-circuit current Isc Rated current Ir Internal arc withstand 24 kV For SF1 circuit breaker DM1-A 750 DM1-S 750 For SFset circuit breaker For Evolis frontal 630 A CB For Evolis lateral 630 A CB 36 kV For SF1 circuit breaker DM1-A 1000 DM1-W 1000 DMV-A 12.5 kA 1s for 24 kV DM1-D left 750 DM1-Z 750 DM2 left 750 DM1-D left 750 DMV-S DMVL-A DM1-D left 1000 DM2 left 1500

Quantity

(kV) (kV) (kA) (A) 16 kA 1s for 36 kV DM1-D right 750 DM1-W 750 DM2 right 750 DM1-D right 750 DMV-D right DMVL-D DM1-D right 1000 DM2 right 1500 DM2-W right 1500

Position in the switchboard Circuit breaker

First on left

Middle

Last on right See specic order form See specic order form

Current transformers (CT) and LPCTs

Basic 24 kV
Busbar (Ir u Ir cubicle) For DM1-A, DM1-S, DM1-W, DMVL-A, DMVL-D ,DM1-D, DM2 400 A For DM1-A, DM1-D, DM1-W, DM1-Z For DMV-A, DMV-D For DMV-S Protection For DM1-S, DMV-S For DM1-S For DMV-A, DMV-D For DM2, DM1-Z, DM1-W Control for DMV-A and DMV-D Local (shunt trip coil compulsory) Remote (opening coil and closing coil compulsory) Local and remote (opening coil and closing compulsory) Voltage of the auxiliaries Voltage of signalling 48/60 Vdc 48/60 Vdc 110/125 or 220/250 Vdc 110/130 or 220/240 Vac (50 Hz) 110/125 Vdc 220/250 Vdc 220/240 Vac (50 Hz) 110/130 Vac (50 Hz) Cable connection by the bottom For DM1-A, DM1-W, DMVL-A 3 x single core cable maxi 240 mm2 Current sensors MV type CT 6 x single core cable maxi 240 mm2 LPCT ring type for DM1-A 630 A LPCT MV type for DM1-D,DM1-W 630 A Statimax 5 A, 2 s VIP35 with CRc Sepam series 10 with CRa VIP300LL with CRa VIP300LL with CRb Sepam series 10 with CRb Sepam series 20/40 Statimax 1 A, 2 s 630 A 630 A 630 A 1250 A 1250 A 1250 A

Basic 36 kV
Voltage of the auxiliaries Voltage of signalling 48/60 Vdc 48/60 Vdc 110/130 Vac (50 Hz) 110/125 or 220/250 Vdc 110/130 or 220/240 Vac (50 Hz) 110/125 Vdc 220/250 Vdc 220/240 Vac (50 Hz) See following page

Options

108

AMTED398078EN

Order form

SM6
Protection
Circuit breaker

Only one of the boxes (ticked X or lled by the needed value) have to be considered between each horizontal line. Green box X corresponds to none priced functions.

Options
Common options
Interlocking Tubular key type Not applicable on DM2 Signalling contact A1 C1 Flat key type C4

2 O & 2 C on SW (not applicable with VTs) 2 O & 3 C on SW and 1 O & 1 C on ES (not applicable with VTs) 1 O & 2 C on SW (available only on cubicle with VTs) See specic order form

VTs (not applicable for DM1-S, DMV-S)

24 kV options
Roof conguration (not applicable on DMV-A, DMV-S, DMV-D) (A, B or C only one choice possible) A - Cable connection by the top (cable maxi 240 mm2 with VPIS) Single core DM2 B - Low voltage control cabinet DM2 C - Wiring duct Surge arrester 50 W heating element Replacement of 630 A upper busbars 400-630 A by 1250 A Busbar eld distributors for severe conditions (only for 630 A) Internal arc version (not possible with top incomer option) 16 kA 1 s Gaz exhaust direction Downwards (only for 16 kA 1s) 20 kA 1 s Upwards DM2 Other cubicles 1 cabinet 1 set 1 set 2 cabinets 2 sets 1 set 2 x single core 2 sets

36 kV options
Cable connection by the top (single core cable maxi 240 mm2 with VPIS) Cable connection by the bottom (for DM1-A and DM1-W only) 3 x 2 x single core cable maxi 240 mm2 Surge arrester Sepam relay protection 36 kV See specic order form

AMTED398078EN

109

Order form

SM6
Protection
Fuse switch

Only one of the boxes (ticked X or lled by the needed value) have to be considered between each horizontal line. Green box X corresponds to none priced functions.

Basic cubicle
Rated voltage Ur Service voltage Short-circuit current Isc Rated current Ir Internal arc withstand Type of cubicle 24 kV QM 375 QM 500 36 kV QM 750 Position in the switchboard Quantity of CTs Direction of lower busbars for QMB Left QMB 750 QMC 1000 QMB 375 QMC 625 12.5 kA 1s for 24 kV

Quantity (kV) (kV) (kA) (A) 16 kA 1s for 36 kV PM 375

PM 750 Last on right 3 Right

Middle First on left Current transformers for QMC 24 kV (to see price structure) 1 2

Options
Common options
Fuses (see fuse price structure) Replacement of mechanism Electrical driving motorization 24 Vdc 32 Vdc 48 Vdc 60 Vdc Shunt trip Opening (on CI1) 24 Vdc 32 Vdc 48 Vdc 60 Vdc Auxiliary contact signalling 2 O & 2 C on SW Interlocking A1 C1 C4 110 Vdc 120-125 Vdc 137 Vdc 220 Vdc Service voltage y 12 kV CIT by CI1 (only for PM) 120/127 Vac (50 Hz) 220/230 Vac (50 Hz) 120/127 Vac (60 Hz) 220/230 Vac (60 Hz)

Closing and opening (on CI2) 110 Vdc 120-125 Vdc 137 Vdc 220 Vdc 120/127 Vac (50 Hz) 220/230 Vac (50 Hz) 120/127 Vac (60 Hz) 220/230 Vac (60 Hz) 380 Vac (50/60 Hz) 1 C on SW and 1 O & 1 C on ES 2 O & 3 C on SW and 1 O & 1 C on ES Flat key type

Tubular key type

Replacement of 630 A upper busbar by 1250 A (not possible for QMB) Blown fuse signalling contact (for QM, QMB, QMC)

24 kV options
Replacement of mechanism Remote control signalling (for QM only) 2 lights 2 lights and 2 PB 2 lights and 2 PB + 1 switch Voltage of the lights (must be the same than electrical driving mechanism) 24 V 48 V 110/125 V 220 V Blown fuse signalling contact (mechanical indication PM, electrical for the other cubicles) Roof conguration (A, B or C only one choice possible) A - Cable connection by the top (cable maxi 240 mm2 with VPIS) Single core B - Low voltage control cabinet (h = 450 mm) C - Wiring duct 50 W heating element Operation counter Digital ammeter (not applicable for QMB) Visibility of main contacts Pressure indicator device Analogic manometer without visibility of main contacts Pressure switch Analogic manometer with visibility of main contacts Busbar eld distributors for severe conditions (only for 630 A) Internal arc version (not possible with top incomer option) 16 kA 1 s Gaz exhaust direction Downwards (only for 16 kA 1s) 20 kA 1 s Upwards AMP21D 2 x single core With unpunched door CI1 by CI2 (only for QM)

36 kV options
Replacement of mechanism CIT by CI2 (only for PM) Cable connection by the top (single core cable maxi 240 mm2 with VPIS)

110

AMTED398078EN

Order form

SM6
Protection
Vacuum contactor (Direct Motor Starter) for 24 kV

Only one of the boxes (ticked X or lled by the needed value) have to be considered between each horizontal line. Green box X corresponds to none priced functions.

Basic cubicle
Rated voltage Ur Service voltage Short-circuit current Isc (6.3 kA without fuse) Rated current Ir (max. 400 A without fuse) Internal arc withstand Position in the switchboard Busbar Ir Phase current sensors Key interlockings for 52 type First on left 400 A 1 CT Middle 630 A 2 CT

Quantity (kV) (kV) (kA) (A) 12.5 kA 1s Last on right 1250 A 3 CT 3 LPCT ring type Tubular key type Flat key type

7.2

Options
MV fuses 25 A 31.5 A 40 A 50 A 200 A 63 A 250 A 80 A 100 A 125 A 160 A Busbar eld distributors for severe conditions (only for 630 A) Key interlockings for C1 type Voltage transformer (quantity) Tubular key type

Flat key type 2 16 kA 1 s 3 20 kA 1 s Upwards

1 Internal arc version (not possible with top incomer option) Gaz exhaust direction

Downwards (only for 16 kA 1s)

Contactor
Vacuum contactor Open release Closing coil Magnetic hold 48 Vdc 110 Vac/dc 220 Vac/dc Mechanical latching 125 Vdc 120 Vac/dc 240 Vac/dc 250 Vdc 125 Vac/dc 250 Vac/dc

AMTED398078EN

111

Order form

SM6
Metering

Only one of the boxes (ticked X or lled by the needed value) have to be considered between each horizontal line. Green box X corresponds to none priced functions.

Basic cubicle
Common 24/36 kV
Rated voltage Ur Service voltage Short-circuit current Isc Rated current Ir Internal arc withstand Type of cubicle/upper busbar for 24 kV Ir = 630 A, Ir busbar = 400 A Ir = 630 A, Ir busbar = 630 A Ir = 630 A, Ir busbar = 1250 A Ir = 1250 A, Ir busbar = 1250 A Type of cubicle for 36 kV CM 750 CM2 750 TM 750 Position in the switchboard First on left Direction of lower busbars for GBC-A Signalling contact (for CM, CM2 and TM only) Fuses (for CM, CM2 and TM only) Middle Left CM CM CM CM2 CM2 CM2 TM TM TM 12.5 kA 1s for 24 kV

Quantity

(kV) (kV) (kA) (A) 16 kA 1s for 36 kV GBC-A GBC-A GBC-A GBC-A GBC-B GBC-B GBC-B GBC-B GBC-A 750 GBC-B 750 Last on right Right 1 O and 1 C on SW See fuse price structure

Basic 24 kV
VTs for GBC (to see price structure) CTs for GBC (to see price structure) Ratio choice for GBC Protections 1 secondary 2 secondaries 1 high secondary 1 low secondary Phase/phase Quantity 1 Phase/earth 2 3

Basic 36 kV
Voltage transformers See specic order form

Options
24 kV options
Roof conguration (A, B or C only one choice possible) A - Cable connection by the top (cable maxi 240 mm2 with VPIS) Single core B - Low voltage control cabinet (h = 450 mm) C - Wiring duct 50 W heating element for CM, CM2, TM Busbar eld distributors for severe conditions (only for 630 A and CM, CM2 and TM cubicles) Blown fuse auxiliary contact (for CM, CM2 and TM only) Internal arc version (not possible with top incomer option) 16 kA 1 s Gaz exhaust direction Downwards (only for 16 kA 1s) 1 O and 1 C 20 kA 1 s Upwards See specic order form 2 x single core With unpunched door

36 kV options
Current transformers and voltage transformers for GBC Cable connection by the top (single core cable maxi 240 mm2 with VPIS) Replacement of 630 A busbar by 1250 A (for CM, CM2 and TM only)

112

AMTED398078EN

Order form

SM6
Other functions

Only one of the boxes (ticked X or lled by the needed value) have to be considered between each horizontal line. Green box X corresponds to none priced functions.

Basic cubicle
Rated voltage Ur Service voltage Short-circuit current Isc Rated current Ir Internal arc withstand Type of cubicle/upper busbar for 24 kV Ir = 630 A, Ir busbar = 400 A Ir = 630 A, Ir busbar = 630 A Ir = 1250 A, Ir busbar = 1250 A Type of cubicle for 36 kV Position in the switchboard GAM 500 GAM 500 GAM 500 GAM 750 GAM2 750 Middle GAM2 375 GAM2 375 12.5 kA 1s for 24 kV

Quantity (kV) (kV) (kA) (A) 16 kA 1s for 36 kV GBM 375 GBM 375 GBM 375 GBM 750 Last on right Right

First on left Direction of lower busbars for GBM

Left (impossible on the rst cubicle of the switchboard)

Options
24 kV options
Roof conguration (A, B or C only one choice possible) A - Cable connection by the top (cable maxi 240 mm2 with VPIS) Single core B - Low voltage control cabinet (h = 450 mm) C - Wiring duct Wiring duct for GBM ES auxiliary contact (only on GAM 500) Surge arresters for GAM 500, 630 A 7.2 kV 10 kV 12 kV 17.5 kV Flat key type P5 SM6-SM6 Cubicle no. 24 kV Interlocking on GAM 500 1 O and 1 C 2 x single core With unpunched door

Tubular key type A3 SM6-SM6

Localisation of 2nd lock for P5 Heating element (on GAM 500 630 A and on GAM2) Digital ammeter or Fault current indicator AMP 21D (except GBM) Flair 21D Flair 22D

Flair 23DV zero sequence Flair 23DV 20 kA 1 s Upwards

Internal arc version (not possible with top incomer option) 16 kA 1 s Gaz exhaust direction Downwards (only for 16 kA 1s)

36 kV options
Cable connection by the top (single core cable maxi 240 mm2 with VPIS) Replacement of 630 A busbar by 1250 A (for GAM2 only) Surge arresters for GAM2

AMTED398078EN

113

Order form

SF1
Lateral disconnectable or withdrawable

by Only one of the boxes (ticked X or lled the needed value) have to be considered between each horizontal line. Green box X corresponds to none priced functions.

Basic circuit breaker


Rated voltage Ur Service voltage Impulse voltage Up Short-circuit current Isc Rated current Ir Frequency Mechanism position Disconnectable Withdrawable Colour for push buttons and indicators Push buttons open/close: Red/black Indicator open/close: Black/white Operating mechanism charged/discharged: White/yellow 60 Hz A1

Quantity (kV) (kV) (kVbil) (kA) (A) 50 Hz B1 B1

Circuit breaker options


1st opening release (see possible choices combination table below)
Shunt opening release YO1 24 Vdc 30 Vdc 60 Vdc 110 Vdc 220 Vdc 48 Vac (50 Hz) 110 Vac (50 Hz) 220 Vdc 48 Vac (50 Hz) 110 Vac (50 Hz) Without contact 220 Vac (50 Hz) 120 Vac (60 Hz) 240 Vac (60 Hz) 220 Vac (50 Hz) 120 Vac (60 Hz) 240 Vac (60 Hz) With contact

48 Vdc 125 Vdc Undervoltage release YM 24 Vdc 30 Vdc 48 Vdc Mitop 60 Vdc 110 Vdc 125 Vdc

2nd opening release (see possible choices combination table below)


Shunt opening release YO2 24 Vdc 30 Vdc 60 Vdc 110 Vdc 220 Vdc 48 Vac (50 Hz) 110 Vac (50 Hz) 220 Vdc 48 Vac (50 Hz) 110 Vac (50 Hz) Without contact 220 Vac (50 Hz) 120 Vac (60 Hz) 240 Vac (60 Hz) 220 Vac (50 Hz) 120 Vac (60 Hz) 240 Vac (60 Hz) With contact

48 Vdc 125 Vdc Undervoltage release YM 24 Vdc 30 Vdc 48 Vdc Mitop 60 Vdc 110 Vdc 125 Vdc

Remote control
Electrical motor M Shunt closing release YF 24 Vdc 30 Vdc 48 Vdc Leaets language 60 Vdc 110 Vdc 125 Vdc 220 Vdc 48 Vac (50 Hz) 110 Vac (50 Hz) French 220 Vac (50 Hz) 120 Vac (60 Hz) 240 Vac (60 Hz) English 2432 Vdc 4860 Vdc/ac 110127 Vdc/ac 220250 Vdc/ac

Different releases combinations Shunt opening releases YO1/YO2 Undervoltage release YM Mitop

1 1 1

1 1

1 1 1 1 AMTED398078EN

114

Order form

SFset
Lateral disconnectable for SM6 24 kV
Basic circuit breaker
Rated voltage Ur Service voltage Impulse voltage Up Short-circuit current Isc Rated current Ir Frequency Mechanism position Colour for push buttons and indicators Push buttons open/close: Red/black Indicator open/close: Black/white Operating mechanism charged/discharged: White/yellow 60 Hz A1

by Only one of the boxes (ticked X or lled the needed value) have to be considered between each horizontal line. Green box X corresponds to none priced functions.

Quantity (kV) (kV) (kVbil) (kA) 630 A maximum 50 Hz B1

Control unit and sensors


VIP 300P (not available for all
electrical characteristics)

CSa 200/1 CSb 1250/1 CSa 200/1 CSb 1250/1

Is = 10 to 50 A Is = 63 to 312 A Is = 10 to 50 A Is = 63 to 312 A

Is = 40 to 200 A Is = 250 to 1250 A Is = 40 to 200 A Is = 250 to 1250 A

VIP 300LL

Circuit breaker options


2nd opening release (see possible choices combination table below)
Shunt opening release YO2 24 Vdc 30 Vdc 60 Vdc 110 Vdc 220 Vdc 48 Vac (50 Hz) 110 Vac (50 Hz) 220 Vdc 48 Vac (50 Hz) 110 Vac (50 Hz) 220 Vac (50 Hz) 120 Vac (60 Hz) 240 Vac (60 Hz) 220 Vac (50 Hz) 120 Vac (60 Hz) 240 Vac (60 Hz)

48 Vdc 125 Vdc Undervoltage release YM 24 Vdc 30 Vdc 48 Vdc 60 Vdc 110 Vdc 125 Vdc

Remote control
Electrical motor M Shunt closing release YF 24 Vdc 30 Vdc 48 Vdc Test box (VAP 6) Leaets language French English 60 Vdc 110 Vdc 125 Vdc 220 Vdc 48 Vac (50 Hz) 110 Vac (50 Hz) 220 Vac (50 Hz) 120 Vac (60 Hz) 240 Vac (60 Hz) 2432 Vdc 4860 Vdc/ac 110127 Vdc/ac 220250 Vdc/ac

Different releases combinations Mitop Shunt opening release YO2 Undervoltage release YM AMTED398078EN

1 1

1 1

115

Order form

Evolis
Frontal fixed version for SM6 24 kV (up to 17.5 kV)
Basic xed circuit breaker
Rated voltage Ur (kV) Service voltage Short-circuit current Isc Rated normal current Ir (A) Phase distance 630 12 (kV) 25 kA 1250 185 mm

Only one of the boxes (ticked X or lled by the needed value) have to be considered between each horizontal line. Green box X corresponds to none priced functions.

Quantity 17.5

Circuit breaker options


Opening release (see possible choices in combination table below)
Shunt opening release MX 24 Vac 48 Vac Low energy release Mitop 2430 Vdc 4860 Vdc 100130 Vdc/ac 200250 Vdc/ac

1 AC fault signalling SDE and reset 200...250 Vac are included

Remote control (operation counter already included)


Electrical motor MCH 2430 Vdc 4860 Vdc/ac Shunt closing release XF 24 Vac 48 Vac Operation counter CDM Additional auxiliary contacts OF (4 AC) Ready to close contact PF (1 AC) Locking of the circuit breaker in the open position By padlock or by locks and keys Tubular key type Flat key type 2 different locks 1 2 100125 Vdc 100130 Vac 2430 Vdc 4860 Vdc 200250 Vdc 200240 Vac 100130 Vdc/ac 200250 Vdc/ac

If locks 1 lock 2 identical locks Disabling of O/C circuit breaker push buttons

Different releases combinations Shunt opening release MX Mitop

1 1

1 1 AMTED398078EN

116

Order form

Evolis
Lateral disconnectable version for SM6 24 kV (up to 24 kV)
Basic circuit breaker
Rated voltage Ur Service voltage Impulse voltage Up Rated normal current Ir Phase distance Mechanism position Colour for push buttons and indicators Push buttons open/close: Red/black Indicator open/close: Black/white Operating mechanism charged/discharged: White/yellow (kV) (kVbil) 630 A maximum 250 mm B1

Only one of the boxes (ticked X or lled by the needed value) have to be considered between each horizontal line. Green box X corresponds to none priced functions.

Quantity 24 (kV)

Circuit breaker options


1st opening release (see possible choices combination table below)
Shunt opening release YO1 24 Vdc 48 Vdc Undervoltage release YM 24 Vdc 48 Vdc 110 Vdc 125-127 Vdc 220 Vdc 110 Vac (50 Hz) 220-230 Vac (50 Hz) 120 Vac (60 Hz) 110 Vdc 125-127 Vdc 220 Vdc 110 Vac (50 Hz) 220-230 Vac (50 Hz) 120 Vac (60 Hz)

2nd opening release (see possible choices combination table below)


Shunt opening release YO2 24 Vdc 48 Vdc Undervoltage release YM 24 Vdc 48 Vdc Low energy release Mitop 110 Vdc 125-127 Vdc 220 Vdc 110 Vac (50 Hz) 220-230 Vac (50 Hz) 120 Vac (60 Hz) 110 Vdc 125-127 Vdc 220 Vdc 110 Vac (50 Hz) 220-230 Vac (50 Hz) 120 Vac (60 Hz)

Remote control (operation counter already included)


Electrical motor M Shunt closing release YF 24 Vdc 48 Vdc 110 Vdc 125-127 Vdc 220 Vdc Operation counter (already included if remote control supplied) 110 Vac (50 Hz) 220-230 Vac (50 Hz) 120 Vac (60 Hz) 2432 Vdc 4860 Vdc/ac 110127 Vdc/ac 220250 Vdc/ac

Different releases combinations Shunt opening releases YO1 Shunt opening releases YO2 Undervoltage release YM Mitop AMTED398078EN

1 1

1 1

1 1

1 1 1

117

Notes

118

AMTED398078EN

Schneider Electric Industries SAS


35, rue Joseph Monier CS 30323 F - 92506 Rueil Malmaison Cedex (France) Tl. : +33 (0)1 41 29 70 00 RCS Nanterre 954 503 439 Capital social 896 313 776 www.schneider-electric.com AMTED398078EN As standards, specications and designs change from time to time, please ask for conrmation of the information given in this publication. Design: Schneider Electric Industries SAS Photos: Schneider Electric Industries SAS Printed: Altavia Connexion - Made in France