ITCC in Riyadh Residential Complex J10-13300 08329-1 Vertical Coiling Fire Rated Shutters
ITCC in Riyadh Residential Complex J10-13300 08329-1 Vertical Coiling Fire Rated Shutters
ITCC in Riyadh Residential Complex J10-13300 08329-1 Vertical Coiling Fire Rated Shutters
2 Vertical Coiling Fire & Smoke Rated Shutters as shown on Drawings and as specified herein.
REFERENCES A. ASTM - American Society for Testing and Materials: ASTM A 366 ASTM A 525 ASTM A 526 ASTM A 569 ASTM E 90 B. Steel sheets, Carbon, cold-Rolled Commercial Quality General Requirement for Steel (Galvanized) by the Hot Dip Process Sheet, Zinc-Coated
Steel Sheet, Zinc-Coated (Galvanized) by the Hot Dip Process, Commercial Quality Steel Carbon (0.15 Maximum Percent) Hot-Rolled sheet and Strip, Commercial Quality Laboratory Measurement of Airborne Sound Transmission Loss of Building Partitions
NFPA - National Fire Protection Association: NFPA 80 NFPA 101 Fire Doors and Windows Code for Safety to Life from Fire in Buildings and Structures
1.3
SUBMITTALS A. B. Product Data: Submit manufacturer's specifications for fabrication and installation, including data substantiation that products comply with requirements. Shop Drawing: Furnish shop drawings for Engineer's approval. Include elevations, sections, and details indicating dimensions, materials, finishes, conditions for anchorage and support of each shutter. Product Literature: Submit manufacturer's technical literature describing the product to be used under this section. 1. Maintenance and Operating Manuals: Furnish complete manuals describing the materials, devices and procedures to be followed in operating and maintaining all shutters under this section. Include manufacturer's brochures and parts lists describing the actual materials
C.
1.4
A. B. C. D. 1.5
Deliver, store and handle hollow metal work in a manner to prevent damage and deterioration. Provide packaging such as cardboard or other containers, separators, banding, spreaders and paper wrappings to protect hollow metal items. Store doors and frames upright, in a protected dry covered area, at least 100 mm or more above ground or floor and at least 6 mm between individual pieces. Doors and frames are to have a metal tag with the door number thereon.
WARRANTY A. Submit a written 1 year guarantee, starting from substantial handover of the project, for all items specified under this Section, signed by manufacturer and the contractor, against all the defects, including bowing, and twisting.
1.6
QUALITY ASSURANCE A. Fire & Smoke Rated Assemblies: Provide all doors with fire and smoke resistance rating required to comply with governing regulations which are inspected, tested, listed and labeled by UL or WH and complying with NFPA 80 for class of opening. Provide units tested and approved under UL 10B and UBC 7-2-1997 Part II. Provide testing agency label permanently fastened to each fire shutter assembly. Regulatory Requirements: Comply with applicable requirements of the laws, codes, ordinances and regulations of federal, state and municipal authorities having jurisdiction. Testing: Provide documentation from a certified testing agency that the fire shutter operator and self-closing governor mechanism has been tested for a minimum of 50,000 cycles and 500 trip tests. Manufacturer Requirements: Shutter manufacturer shall have been in the business of and have experience in manufacturing the type of product covered under this specification section as well as giving credible service for a minimum of five (5) years. Provide list of at least ten (10) completed projects which include the products covered under this section.
B.
C.
D.
PART 2 - PRODUCTS 2.1 VERTICAL COILING FIRE & SMOKE RATED SHUTTERS A. General: Vertical coiling fire and smoke rated shutters shall be the as manufactured by McKeon Door Company; type as selected by Engineer. Provide Vertical coiling fire and smoke rated shutters for locations as shown on drawings, size as required.
B.
General: Each unit shall consist of an interlocking slat curtain designed to travel in a Vertical plane, smoothly and without binding. Curtain shall be driven to the
08329-2 Vertical Coiling Fire Rated Shutters
open and close position by a positive action sprocket drive, engaging the slat interlocks, without the use of cables or counterbalance weights. 1. Curtain: Shall be fabricated of cold rolled galvanized steel, interlocking slats of McKeon F3 design, with an approximate cross section not less than 3" wide by 7/8" deep. Each end of each slat shall be equipped with rollwindlocks. Roll-windlocks shall be secured to slats with monobolts. Rollwindlocks shall be shouldered where bearing on slats to provide automatic alignment and shall be so contoured to insure minimum frictional losses.
C. D.
Leading Edge: Curtain shall be furnished of a structural steel member of tubular design to provide stiffness, limit deflection and provide for a tight fitting closure. Tracks: Shall be of not less than 1/8 thick steel and shall be provided with an integral locking bar. The faying surface shall not be less than 38% of the flat plate area of the continuous roll-windlocks when the shutter is in the closed position. Locking bar shall lock the curtain in place. Perimeter Smoke Seals: Provide UL classified brush smoke seals at tracks and at coiling curtain entry to coil box area. Counterbalance Assemblies: The fire shutter shall be counterbalanced by means of adjustable steel helical torsion springs attached to shaft enclosed in pipe with required mounting blocks or rings for attachment of curtain. Torsion springs shall be anchored to the same shaft and held in position by the same adjusting wheel accessible from outside the barrel assemblies. Coil Box: Shall be provided to entirely enclose coiled curtain and counterbalance assemblies. Coil box cover shall be of a rectangular design fabricated of 22 gauge galvanized sheet steel. Electric Motor Operator: Each shutter shall be provided with a compact power unit designed and built by the shutter manufacturer. Operator shall be equipped with an adjustable screw-type limit switch to break the circuit at termination of travel. High efficiency planetary gearing running in an oil bath, shall be furnished together with a centrifugal governor, spring-set solenoid-operated brake and a fail-safe magnetic release device, completely housed to protect against damage, dust, and moisture. Operator is to be NEMA type 1 enclosure. An efficient overload protection device, which will break the power circuit and protect against damage to the motor windings shall be integral with the unit. 1. Motor: Shall be totally enclosed, intermediate duty, thermally protected, ball bearing type with a class A or better insulation. Horsepower of motor is to be hp minimum or of manufacturer's recommended size which ever is greater. Starter: Shall be size "0" magnetic reversing starter, across the line type with mechanical and electrical interlocks, with 24 volt control circuit. Reducer: Planetary gear type, 90% efficiency minimum, 77:1 reduction. Brake: Double shoe type, continuous duty, solenoid activated, integral within the operators housing. Control Station: Provide flush mount key switch control station marked
08329-3 Vertical Coiling Fire Rated Shutters
E. F.
G.
H.
2. 3. 4. 5.
ITCC in Riyadh Residential Complex J10-13300
open, close and stop. I. Self-Closing Mechanism: The fire shutter shall be designed with a centrifugal governor as an integral part of the operator's construction. The automatic release mechanism shall be triggered by smoke detector or fire alarm. When triggered the shutter is released and begins to close due to the captured torsion spring force. The speed of the shutter shall be governed by a centrifugal governor, designed to match the normal operating speed of the shutter, at a rate of not greater than 6" per second or less than 3" per second. The fire shutter shall selfclose under its own power. Battery back-up systems to achieve self-closing are not acceptable. Magnetic Release with 10 Second Time Delay: A fail-safe magnetic release device shall be built into the operator as an integral part of the release mechanism. When power is interrupted to the release mechanism by the smoke detector or fire alarm, the shutter shall begin to self-close. In the event of power failure the time delay shall prevent the fire shutter from closing for a period of 10 seconds. Once the 10 seconds have lapsed, the fire shutter shall self-close without the aid of electricity or battery back-up systems. Once power has been restored the automatic reset time delay as well as the fire shutter shall reset themselves, and the shutter shall automatically power it-self back to the fully open position. Safety Edge: Each fire shutter shall be designed with a radio activated obstruction sensing safety edge. In the event that the safety edge meets an obstruction during the closing operation, the shutter shall stop, reverse and return to the open position. Easy Trip Test Feature: Each fire shutter shall be designed so that it may be triptested simply by cutting power to the operator. By turning the power switch off, the shutter shall self-close without the aid or electricity or battery back-up systems. Once the fire shutter has satisfactorily closed, it shall be reset and power it-self back to the fully open position simply by turning the power back on. No ladders or tools shall be needed to reset the shutter or the time delay unit. Painting: After completion of fabrication, clean all metal surfaces to remove dirt and chemically treat to provide for paint adhesion. Slats are to receive a prime coat of .2 mils of Urethane primer and .6 mils of Polyester paint.
J.
K.
L.
M.
08329-4
PART 3 - EXECUTION 3.1 EXAMINATION A. Examine surfaces and field conditions to which this work is to be performed and notify architect if conditions of surfaces exist which are detrimental to proper installation and timely completion of work. Do not proceed with the work until unsatisfactory conditions have been corrected in a manner acceptable to the Engineer. Verify all dimensions taken at job site affecting the work. Notify the architect in any instance where dimensions vary. Coordinate and schedule work under this section with work of other sections so as not to delay job progress.
B. C. D. 3.2
INSTALLATION A. B. C. Perform installation using only factory approved and certified representatives of the shutter manufacturer. Remove, repair or replace materials which have been damaged in any way. Clean surfaces of grime and dirt using acceptable and recommended means and methods. END OF SECTION
08329-5