MCCBs Simpact Series

Download as pdf or txt
Download as pdf or txt
You are on page 1of 24

Simpact TM Merlin Gerin

Moulded Case Circuit Breaker

The New Horizon

Building a New Electric World

NKS100R

Simpact TM Merlin Gerin


One step further... to simplify your life

NKF250C

onstant innovation and cutting edge technology has positioned Schneider Electric as the world leader in its field. And Simpact TM range of MCCBs are completely in

line with this exemplary performance. is now associated with

Little wonder then that Merlin Gerin

Simpact TM MCCBs after they were subjected to the most stringent quality tests and have passed the exacting demands of Schneider Electric's worldwide norms. But these aren't the only reasons that set Simpact TM apart from regular MCCBs. It comes with a host of thoughtful features: adjustable centralised thermal setting, line load reversibility, very high endurance level, to name some.
NKF400C

Add to this, it is tropicalised to withstand extreme electrical, mechanical, climatic and environmental conditions. In short, Simpact TM offers safety, reliability, flexibility and economy of operation. Its easy to install, easy to use and easy to maintain. Still wondering how Simpact TM MCCBs simplify your life?

Schneider Electric, Moving from strength to strength.

NKF800C

Schneider Electric

Simpact TM : presentation

Ratings and breaking capacities


The rating plates on the front face of the circuit breakers indicate the breaking capacity: R: 10 kA D: 25 kA C: 35 kA K: 50 kA

rated current (A)

800

NKF800K
NKF800C

630

NKF630K
NKF630C

400
NKF400C

NKF400K

250
NKF250C NKF250D

NKF250K

100
NKF10 NKF10 0D NKF10 00 NKS1 R 0C 0K

50 (kA 35

10

25

Ultimate breaking capacity Icu (kA rms) at 415 V- IEC 60947-2 (IS 13947 Part 2)

Description
NKF
Simpact TM Circuit breaker NKS NKF

100
Frame size 100:100A 200: 200A 250: 250A 400: 400A 630: 630A 800: 800A

D
Breaking Capacity R-10KA D-25 KA C-35 KA K-50 KA

40
Amp. Ratings

AC
Alternating Current

3P
No. of poles

F
Trip unit F-fixed

NKF250C Schneider Electric

Note: NKS Range is fixed type

Functions and characteristics

Power supply
Simpact TM circuit breakers can be connected with power supply from either top or bottom (reverse feeding) without any reduction in performance. This capability facilitates connection when installed in a switchboard.

Degree of protection
As per standards IEC 60529 (IP degree of protection). IK degree of protection against external mechanical impact (IEC 62262).

Bare circuit breaker with terminal shields

With toggle

IP20

IK07

With direct rotary handle

IP40

IK07

Circuit breaker installed in a switchboard

With toggle

IP20

IK07

With direct rotary handle

IP42

IK07

Schneider Electric

Functions and characteristics

Solution for all applications

NKS 100-200R
Single frame size with compact dimension available in 3 pole version Available from 10 Amp up to 200 Amp with 10kA breaking capacity Trip units fully magnetic with fixed setting

NKS100R

NKF 100.800 Amp (fixed version)


Four frame sizes for entire range available in 3/4 pole version Available from 20 Amp up to 800 Amp with 25/35/50 kA breaking capacity Trip unit fixed thermal for entire range, magnetic fixed upto 400 Amp and adjustable setting from 500 Amp onwards

NKF400C

NKF 100800 Amp (adjustable)


Four frame sizes for entire range available in 3/4 pole version Available from 20 Amp upto 800 amp with 25/35/50 kA breaking capacity Trip unit centralised overload adjustment for entire range and magnetic setting adjustable from 500 Amp onwards

NKF630C

Main applications
Suitable for protection of distribution transformer, DG set, distribution board. Suitable for applications like power distribution, furnace incomer, UPS.

MCCB will be supplied with spreaders

Schneider Electric

Functions and characteristics

Protection of low-voltage distribution networks Simpact TM circuit breakers upto 250 A


Typ e
Number of poles Electrical characteristics as per IEC 60947-2 & IS 13947 Part 2 In Rated current (A)

Rated insulation voltage (V) Impulse-withstand voltage (kV) Rated operational voltage (V) NKS100R Ultimate Breaking Capacity Icu (kA rms) Service Breaking Capacity Ics (% Icu) Utilisation Category Endurance (CO cycle) Overload Protection Overload Release Setting (A)

Ui Uimp Ue AC 50/60 Hz

I r a t 4 0 oC

Short Circuit Protection Short Circuit Release Setting (x In) Installation and Connection Fixed/front Connection Bus bar Crimped lugs NKF250C Installation Accessories Terminal Shroud Phase Barriers

Im maximum width (mm) C a p a c i t y A l / C u ( m m 2)

Internal Accessories (maximum 2 accessories per breaker) Under Voltage Release Shunt Trip Release Alarm Switch Auxiliary Switch Alarm/Auxiliary Switch External Accessories Rotary Handle Dimensions Overall dimensions W x H x D (mm)

Overall weight (kg) ** For 160A the short circuit release is set at 10 In Available * Available from 2004 in adjustable range

Note: MCCB will be supplied with spreaders

Schneider Electric

Frame 1
NKS100R NKS160R NKS200R NKF100D NKF100C

Frame 2
NKF100K NKF250D NKF250C NKF250K

3 40 C
o

3/4

10, 15, 20, 110, 125, 25, 30, 32, 140, 150, 40, 50, 60, 160 63, 75, 90, 100

175, 200

20, 25, 32, 40, 50, 63, 80,100

20*, 25, 32, 40, 50, 63, 80, 100

20*, 25, 32, 40, 50, 63, 80, 100 690 8 415 50 50%

125, 160, 200, 250

125, 160, 200, 250

125, 160, 200, 250

AC 50/60 Hz 415V

690 8 415 10 50%

25

35

25

35

50

mechanical electrical AC Fixed Adjustable x In (Bimetal) 5 0 oC / 5 5 oC o n r e q u e s t Fixed Without Spreaders With Spreaders Without Spreaders With Spreaders 3P w/o Spreaders 415 V

10000 1500

A 10000 1500

10000 1500

20000 10000

15000 6000

A 15000 6000

15000 6000

15000 6000

15000 6000

Centralised 0.8 ... 1

12 16 23 35 70

12** 23 95

10 23 150

10 16 25 35 70

10 25 95 -

10 25 95 -

10 25 25 95 185

10 25 25 95 185

10 25 25 95 185

1 2 1 2

C/O C/O C/O C/O

Breaker Mounted

3 Pole 4 Pole 3 Pole 4 Pole 1.2

90X153X83 1.6 1.6 1.4 2.2 2.9 2.2 2.9

105X165X78 140X165X78 2.4 2.4 3.1 3.1

2.4 3.1

Schneider Electric

Functions and char acter istics

Protection of low-voltage distribution networks Simpact TM circuit breakers from 400 to 800A
Ty p e
Number of poles Electrical characteristics as per IEC 60947-2 & IS 13947 part 2 Rated current (A) In Rated insulation voltage (V) Impulse-withstand voltage (kV) Rated operational voltage (V) Ultimate Breaking Capacity Icu (kA rms) Ui Uimp Ue AC 40/60 Hz

NKF400C

Service Breaking Capacity Ics (% Icu) Utilisation category Endurance (CO cycle) Overload Protection Overload Release Setting (A)

I r a t 4 0 oC

Short Circuit Protection Short Circuit Release Setting (x In) Installation and Connection Fixed/front Connection Bus bar Crimped lugs NKF630C Installation Accessories Terminal Shroud Phase Barriers Internal Accessories (maximum 2 accessories per breaker) Under Voltage Release Shunt Trip Release Alarm Switch Auxiliary Switch Alarm/Auxiliary Switch External Accessories Rotary Handle Dimensions and Weights Overall dimensions W x H x D (mm) maximum width (mm) Capacity Al/Cu (mm )
2

Im

Weight (kg) n Available Note: For technical data on single pole/DC rating MCCB please refer KS-KF series catalogue

Note: MCCB will be supplied with spreaders

Schneider Electric

Frame 3
NKF400C 3/4 40 C
o

Frame 4
NKF630C NKF630K 3/4 500, 630 690 8 415 800 NKF800C NKF800K

NKF400K

320, 400 690 8

AC 50/60 Hz 415V 35

415 50 50% A 35 50

35 50% A 8000 2500

50

mechanical electrical AC Fixed Adjustable x In (Bimetal) 5 0 oC / 5 5 oC o n r e q u e s t Fixed Adjustable in 4 steps Without Spreaders With Spreaders Without Spreaders With Spreaders 415 V

10000 4000

Centralised 0.8 ... 1

Centralised 0.8 ... 1

10

3.5 to 10 3.5 to 10

25 300

40 300x2

1 C/O 2 C/O 1 C/O 2 C/O

Breaker Mounted

3 Pole 4 Pole 3 Pole 4 Pole

140 x 257 x 103 185 x 257 x 103 5.7 7.3 5.7 7.3 9.7 12.9

210 x 274 x 103 280 x 274 x 103 9.7 12.9 10.3 13.75 10.3 13.75

Schneider Electric

Functions and characteristics

Protection of low-voltage distribution trip units for Simpact TM NKF100 to NKF800


t
1

fixed thermal magnetic trip unit

FIXED

Push to trip

Ir
: fixed threshold thermal protection against overload (1) : fixed threshold magnetic protection against short circuit upto 400 Amp and adjustable from 500 Amp (2)

Im

Protection

trip unit for Simpact TM NKF100 to 800 Amp rating (A) for circuit breaker In
0 40C

Fixed 20 25 32 40 50 63 80 100 125 160 200 250 320 400 500 630 700 800

Simpact NKF100D ...........F Simpact TM NKF100C/K ........F Simpact TM NKF250D/C/K .....F Simpact TM NKF400C/K ........F Simpact TM NKF630C/K ........F Simpact TM NKF800C/K ........F

TM

overload protection (thermal) tripping threshold (A) neutral protection (A) In 4p+3d Fixed no protection

short-circuit protection (magnetic) tripping threshold (A)


TM

Im

Fixed

Simpact NKF100D ...........F 200 250 320 400 500 630 800 1000 Simpact TM NKF100C/K ........F 200 250 320 400 500 630 800 1000 Simpact TM NKF250D/C/K .....F 1250 1600 2000 2500 TM Simpact NKF400C/K ........F 3200 4000 3.5-10 In 3.5-10 In Simpact TM NKF630C/K ........F Simpact TM NKF800C/K ........F 3.5-10 In 3.5-10 In

Note: Simpact TM NKS100...200R for technical details refer to page 6

Schneider Electric

10

Functions and characteristics

Protection of low-voltage distribution trip units for Simpact TM NKF100 to NKF400


t
1

adjustable thermal magnetic trip unit

0.8

2
In x
O/L SETTING

Push to trip

Ir
: adjustable threshold thermal protection against overload (1) : fixed threshold magnetic protection against short circuit (2)

Im

Protection

trip unit for Simpact TM NKF100 to 400 Amp rating (A) for circuit breaker In
0 40C

Adjustable

20

25

32

40

50

63

80

100

125

160

200

250

320

400

Simpact NKF100D ............ TM Simpact NKF100C/K ......... TM Simpact NKF250C/K ......... Simpact TM NKF400C/K .........
In 4p+3d adjustable 0.8...1 x In no protection

TM

overload protection (thermal) tripping threshold (A) neutral protection (A)

short-circuit protection (magnetic) tripping threshold (A) rating (A) for circuit breaker In
TM

Im 40C
0

Fixed

20

25

32 320 320

40 400 400

50 500 500

63 630 630

80 800 800

100 1000 1000

125

160

200

250

320

400

Simpact NKF100D ............ 200 250 250 Simpact TM NKF100C/K ......... Simpact TM NKF250C/K ......... Simpact TM NKF400C/K .........

1250 1650 2000 2500 3200 4000

Schneider Electric

11

Functions and characteristics

Protection of low-voltage distribution trip units for Simpact TM NKF630 to NKF800


t
1

adjustable thermal magnetic trip unit TM

Push to trip
S/C SETTING In x 3.5 S/C SETTING In x 3.5 S/C SETTING In x 3.5 0.8 1

5.5

10

5.5

10

5.5

10

In x O/L SETTING

Ir

Im

Protection

: adjustable threshold thermal protection against overload (1) : adjustable threshold magnetic protection against short circuit (2)

trip unit for Simpact TM NKF630 to 800 Amp rating (A) for circuit breaker In
0 40C

Adjustable 500 630 800

Simpact NKF630C/K ....... Simpact TM NKF800C/K .......


In 4p+3d adjustable 0.8...1 x In no protection

TM

overload protection (thermal) tripping threshold (A) neutral protection (A)

short-circuit protection (magnetic) tripping threshold (A) Im adjustable

Simpact TM NKF630C/K .......... Simpact TM NKF800C/K ..........

3.5....10 In 3.5....10 In

Schneider Electric

12

Functions and char acter istics

Auxiliaries

Indication contact
Auxiliary contact indicates the position of the circuit breaker contacts (open and closed). Alarm contact indicates that circuit breaker has tripped due to an overload, a short circuit fault or operation of the 'push to trip' button. It resets when the circuit breaker is reset.

Characteristics
Contacts

standard 5A AC12 5 5 5 5 AC15 5 5 5 5

Rated thermal current (A) Utilisation category (IEC 60947-5-1) Operational current (A) 24V 48V 125V Indication contact 250V

Remote tripping
Under voltage or shunt release are voltage releases used to trip the circuit breaker Under voltage release This release trips the circuit breaker when the control voltage drops below a tripping threshold. Tripping threshold between 0.35 and 0.7 times the rated voltage It shall permit closing of circuit breaker at supply voltages equal to or above 0.85 Un. The upper limit of supply voltage will be 1.1 Un. Circuit breaker tripping by an UV release meets the requirements of standard IEC 60947-2. Shunt trip This release is used to trip the circuit breaker from remote. The opening voltage of the release shall be 70 ~ 110 Un Under voltage trip Control signal can be impulse type but shall not exceed 5 sec (1 sec for 440 V)

Direct rotary handle


Degree of protection IP40 (IP42 with enclosure). The direct rotary handle maintains: Three position OFF, ON and Tripped Circuit breaker locking capabilities in the OFF position by one to three padlocks Door opening disabled when the circuit breaker is ON

Rotary handle

Schneider Electric

13

Functions and characteristics

Phase barriers / Spreaders


Phase barriers provide safety for maximum insulation at the power connection points. Slots provided to slide onto the circuit breaker. Spreaders are provided as standard for range above 63 Amp upto 800 Amp#

Pole distance(mm) Without spreaders With spreaders

NKF NKF NKF 100 250 400 30 35 56

NKF 630/800 70

NKS 100R 30 36.5

NKS NKF 160/200R 100C/K 30 40 35 -

36.5 47

Phase Barriers / Spreaders

#Not provided for NKF100C/K and125/160 Amp for NKF250C/K MCCB Earth fault relay on request

Schneider Electric

14

Additional characteristics

Tripping curves Simpact TM NKS/F 100 to 250 Protection of distribution systems

Fixed / full magnetic trip units


NKS 100R/160R (upto 150A)
NKS 160R (160A) / NKS 200R

Current (% rated current)

Current (% rated current)

Fixed / Adjustable thermal magnetic trip units


NKF 100D
NKF 100/250C/K

Current (% rated current)

Current (% rated current)

Schneider Electric

15

Additional characteristics

Fixed / Adjustable thermal magnetic trip units


NKF 400C/K

NKF 630/800 C/K

Current (% rated current)

Current (% rated current)

NOTE: MAGNETIC TRIP SETTINGS ARE GIVEN AS % In

Schneider Electric

16

Functions and characteristics

Temperature derating

Thermal Magnetic MCCBs (NKF Range):


The rated current is dependent on ambient temperature. The rated current at ambient temperatures from 30oC - 50oC is given below in the following table.

MCCB Rating (A) o at 40 C

30 C

35 C

Rated Current (A) o o 40 C 45 C

50 C

20 25 32 40 50 63 80 100 125 160 200 250 320 400 500 630 700 800

21.2 26.5 34.9 42.4 53.0 67.7 84.7 105.9 132.4 169.4 211.8 264.8 338.9 423.6 533.5 672.2 746.9 853.6

20.2 25.8 33.0 41.2 51.5 64.9 82.4 103.0 128.8 164.8 206.0 257.5 329.5 412.0 516.5 650.8 723.1 826.4

20 25 32 40 50 63 80 100 125 160 200 250 320 400 500 630 700 800

19.0 23.8 30.4 38.0 47.5 59.9 76.0 95.0 118.8 152.0 190.0 237.5 304.0 380.0 475.0 598.5 665.0 760.0

18.0 22.5 28.8 36.0 45.0 56.7 72.0 90.0 112.5 144.0 180.0 225.0 288.0 360.0 450.0 567.0 630.0 720.0

The magnetic trip setting given in % In ( Max setting) at 400 C are independent of ambient temperature.

Full magnetic MCCBs (NKS Range)


No derating required for higher ambient temperatures. The tripping time is dependent on the ambient temperature. At different ambient temperatures, the tripping time varies as shown in the table.

Effect on the tripping time (%)


Rating (A) 10 ~ 200 30oC 122 35oC 110 40oC 100 45oC 92 50oC 85

The magnetic trip time is independent of ambient temperature.

Schneider Electric

17

Dimensions, volumes

Simpact TM

NKS 100....200R Dimensions


35.2 t3.2 EXTENDED TERMINALS FOR RATINGS ABOVE 63A ONLY. (OPTIONAL FOR LOWER RATINGS.) 4-MOUNTING HOLES 96.0 SUITABLE FOR 36.5 36.5 M4x40 CH. HD. SCREW.

NKS 100....200R Mounting

PHASE BARRIER (0PTIONAL BELOW 60 AMP.) 4-M4 TAPPED OR %%C5.0 HOLES FOR MOUNTING CENTRE LINE OF MCCB HANDLE. 30.0 DRILLING PLAN

13.0

23.0

%%c10.2 HOLES.

60.0
90.0
60 30 70 90 13

TRIPPED ON

24.0

7.5

9.5

65.5

66.0 60.0

9.0

212.0

6.5

OFF

60.0

73.0

30.0

RESET

42.0
72.5 69.0

23.0

PUSH TO TRIP

90.0 30.0

30.0 24.0

5.0

80.0 83.0 105.0

U.V. IF FITTED

NKF 100D Dimensions


32.4 t3.2 13 23 EXTENDED TERMINALS ABOVE 63 AMP ONLY. 96 36.5 36.5 4-MOUNTING HOLES SUITABLE FOR M4x40 CH. HD. SCREW. %%c10.2 HOLES. 7.5

13.0

70.0

`A'

153.0

NKF 100D Mounting

4-M4 TAPPED OR %%C5.0 HOLES FOR MOUNTING CENTRE LINE OF MCCB HANDLE.

70.0

ON TRIPPED 30 6.5
R1

33

65.5

24

15

9.5

60

212

60

73

DRILLING PLAN

OFF 42 RESET

72.5

69

23 30

90 30

5 105

83 U.V. IF FITTED PHASE BARRIER

24

70

`A'

Schneider Electric

153

18

153

153.0

15.0

12.0

12

Dimensions volumes

Simpact TM

NKF 100C/K Dimensions 3 poles


75 24.2

4 poles
4- MOUNTING HOLES SUITABLE FOR M4x90 CH. HD. SCREW. 15

PHASE BARRIER.

4- MOUNTING HOLES SUITABLE FOR M4x90 CH. HD. SCREW.

ON TRIP

70.0

15

9.5

33

63.5

35
60

78.5

149

165

OFF RESET
PUSH TO TRIP

In=100A

71.5

165.0

30

0.8

78 83 100

35 105

35

35.0

35.0 140.0

35.0

NKF 250C/K Dimensions 3 poles


75.0
17.0

4 poles
* SPREADERS SHALL BE PROVIDED ONLY FOR 200A & 250A.

119.0
47.0 25 47.0

166
47 47 47

6.5

27.0

4- MOUNTING HOLES SUITABLE FOR M4x90 CH. HD. SCREW.

4- MOUNTING HOLES SUITABLE FOR M4x90 CH. HD. SCREW. 17

25

TRIP 8.0

34.0

ON

34.0

9.5

63.5

15

33

70 165 30

237.0

203.0

237.0

203.0

63.5 78.5

35

60

78.5

RESET

30

140

71.5

OFF

71.5

78

83
100

35

35

%%C11.0 HOLES.

PHASE BARRIER 140.0 PHASE BARRIER

NKF 100...250C/K Mounting


3 poles
4- M4 TAPPED OR %%C5.0 HOLES FOR MOUNTING.
15

4 poles
4- M4 TAPPED OR %%C5.0 HOLES FOR MOUNTING.
135 165

165

* SPREADERS (FOR 200A & 250A ONLY)

63.5 135

63.5

35

70

15

35

71.5

63.5

30.0

78.5

CENTRE LINE OF MCCB HANDLE

CENTRE LINE OF MCCB HANDLE L C OF HANDLE 140

105

Schneider Electric

19

165

12

12

Dimensions volumes

Simpact TM

NKF 400C/K Dimensions


3 poles
43.5 8

4 poles
56 56 4-MOUNTING HOLES. FOR M6 SCREWS. 16

56.0 44.0 25.0

56.0 44.0

56.0 6-MOUNTING HOLES FOR M6 SCREWS. 16.0

44 25

TRIP PED

ON

49.0

40

49

62

17

70.5 62.0

337

305

90

194

90

225

305.0

194.0

225.0 185.0 193.0

RESET

OFF

97 6 136.9 103

137

140

NKF 400C/K Mounting


3 poles
257

4 poles

194

4-MOUNTING HOLES. 7.0 OR M6 TAPPING.

6-MOUNTING HOLES 7.0 OR M6 TAPPING 194.0 257.0

44

44.0 44.0 48.0

140

185.0

Schneider Electric

40.0
11

45

40

337.0

257.0
.0 11

257

90.0

11

15

20

Dimensions, volumes

Simpact TM

NKF 630-800C/K Dimensions 3 poles


`t' 35 13.5 HOLES. %%C13 MOUNTING HOLES FOR M6 SCREW 70 40 13.5 HOLES. 70

4 poles
MOUNTING HOLES FOR M6 SCREW 70 40

60

%%C8

ON
20

TRIP

31

30

O/L SETTING KNOB


12

394

243

OFF
3.5In 3.5In 10In 5.5In 8In PUSH TO TRIP 5.5In 8In 3.5In 10In 5.5In 8In 3.5In 0.8 1 5.5In 10In PUSH TO TRIP 5.5In 8In 3.5In 10In 5.5In 8In 3.5In 0.8 1

274

43

L C

L C

394

243

30

O/L SETTING KNOB


In x O/L SETTING 10In

RESET

In x O/L SETTING 10In

8In

30

103 141 70 210 70 70 70 280 70

NKF 630-800C/K Mounting


3 poles
70

60

4 poles
70 70

121.5

MOUNTING HOLES 105 L C OF MCCB HANDLE PAD M6 TAPPED OR 7.0 HOLES.

121.5

MOUNTING HOLES
274 243

M6 TAPPED OR 7.0 HOLES. L C OF MCCB HANDLE PAD

243

L C OF MCCB HANDLE 280

Schneider Electric

60

274

60

15

21

Schneider Electric India Pvt. Ltd. (A 100% subsidiary of Schneider Electric Industries SAS)
For more information visit our website at: www.schneider-electric.co.in Corporate Office: A-29, Mohan Co-operative Industrial Estate, New Delhi-110044. Tel: 51590000. Fax: 51678010-12. Sales Offices Delhi A-29, Mohan Co-operative Industrial Estate, New Delhi-110044. Tel: 51590000 Fax: 51678010-11 Chandigarh S.C.O. 13-14-15, 4th floor, Sector 34-A, Chandigarh-160022. Tel: 0172-376782-84 Fax: 0172-783439 Jaipur Jaipur Business Centre, 309, 3rd floor, Sangam Tower, 190, Church Road, Jaipur-302001. Tel: 0141-5118249, 2366456 Fax: 0141-2378023 Lucknow 101/102, ACE House, 5, Saran Chambers-II, Park Road, Hazratganj, Lucknow-226001. Tel: 0522-2222012/3 Tel/Fax: 0522-2237708 Mumbai Floral Deck Plaza 617/618, E- Wing, MIDC Road, Near Seepz, Marol, Andheri (East), Mumbai-400093. Tel: 022-28311309/11/12 Fax: 022-28311314 Pune 331-332, Saurabh Hall, Sasoon Road, Pune-411001. Tel: 020-6136613, 4012245/46 Fax: 020-4012246 Ahmedabad 42-A, 4th floor, Space House, Opp. Shrikrishna House, Mithakhali, Six Roads, Ahmedabad-380009. Tel: 079-6426944/48 Fax: 079-6426944/48 Vadodara 165, GIDC Estate, Makarpura, Vadodara-390010, Tel: 0265-2638971/3/8 Fax: 0265-2638972 Bangalore Unit No. 1002/1001, Prestige Meridian II, 10th floor, No. 30, Mahatma Gandhi Road, Bangalore-560001. Tel: 080-5095694, 5582503 Fax: 080-5095695 Chennai G-4, Karumuthu Centre, 498, Anna Salai, Nandanam, Chennai-600035. Tel: 044-24314491/94 Fax: 044-24355702 Cochin 1st floor, Kurian Tower, Door No. 28/3825 C, Elamkulam, Sahodaran Ayyappan Road, Kadavanthra P.O., Kochi - 682020. Tel: 0484-2318189 Fax: 0484-2323001 Hyderabad 303, Meridian Plaza, Green Lands, Ameerpet, Hyderabad-500016. Tel: 040-5561664/694 Fax: 040-5561664 Coimbatore 9/36A, Chennys Business Centre,1st floor, Dr. Nanjappa Road, Coimbatore-641018. Tel: 0422-2380410, 2302912 Fax: 0422-2380901 Nagpur Fortune Business Centre, 6, Vasant Vihar, W.H.C Road, Shankar Nagar, Nagpur-440010. Tel: 0712-2558581/2550070 Fax: 0712-2542218 Kolkata Block No. 8, Azimganj House, 4th floor, 7, Camac Street, Kolkata-700017. Tel: 033-22820091-4, 22820067 Fax: 033-22820081 Resident Engineer Locations (Tel/Fax) Jamshedpur: 0657-2226560 Bhubaneshwar: 0674-2554061 Ludhiana: 0161-5010988/89 Vishakapatnam: 0891-508990 Goa: 0832-2364474 Indore: 0731-2263619 Surat: 0261-22766620 Guwahati: 0361-2456769 Udaipur: 09829042366 Kanpur: 0512-2202327 Aurangabad: 09823377388 Trivandrum: 0471-2450608 Nashik Works: 58, MIDC, Satpur, Nashik-422007. Tel: 0253-2350394/8 Fax: 0253-2350771 Chennai Works: 25A/2A, Dairy Road, SIDCO Industrial Estate (North Phase), Ambattur, Chennai-600098. Tel: 044-26520105-08 Fax: 044-26523836

SEI/COMM/CG/21(New)

28/05/2003/5000