Ring Main Unit - 8DJH ST
Ring Main Unit - 8DJH ST
Ring Main Unit - 8DJH ST
2
Technical data
Technical features
Rated values up to 12kV, 21kA, 3s
Rated frequency 50 Hz
Busbar current up to 630 A
Feeder current up to 630 A
Busbars Single busbar
Rated power frequency withstand 28kV 38kV
voltage
Rated lighting impulse withstand 75kVp 95kVp
voltage
Insulation Gas-insulated
Switchgear vessel Hermetically enclosed
Type of switchgear Factory-assembled, type-tested, metal-enclosed switchgear
according to IEC 62271-200
Panel blocks consisting of 2, 3, 4 or 5 panels
Calssification according to IEC 62271-200
Partition class PM
Loss of service continuity category LSC 2
Accessibility to compartments Busbar compartment: Non-accessible
Switching-device compartment: Non-accessible
Cable compartment: Interlock-controlled
Degree of protection For switchgear enclosure [Indoor]: IP3X
For switchgear enclosure [Outdoor]: IP54
For gas filled vessel: IP67
Internal arc classification IAC A FLR 21kA, 1.0s
Dimensions
Block width depending on number 645mm, 955mm, 1265mm, 1575mm
and type of panels
Panel height 1620 mm
Panel depth Bottom explosion: 820 mm Top explosion: 918 mm
Standards
Switchgear IEC 62271-1
IEC 62271-100
Devices Circuit breakers IEC 62271-200
Disconnector & earthing switch IEC 62271-102
Switch-disconnector IEC 62271-103
Voltage detection systems IEC 61243-5
Degree of protection IEC 60529
Insulation IEC 60071
Instrument transformers Current transformer IEC 61869-2
Voltage transformer IEC 61869-3
Installation, erection IEC 61936-1
3
Product range for panels
Cable connection [K] Ring main [R] Vacuum Circuit Breaker [L]
4
Product Range, Schemes and Dimensions
Typicals
-S- NA NA NA NA NA 620
NA ME1* NA NA NA NA 630
NA ME2* NA NA NA NA 630
5
Customer Benefits, Technical Data,
Design & Construction
Customer Benefits:
Peace of mind Design and Construction
• Gas insulated, metal enclosed, indoor/outdoor, • Ring feeders with three position switch disconnectors
Extensible/non- extensible factory assembled type (option: with auxiliary switch).
tested switchgear as per new IEC 62271-100/200. • Circuit breaker feeder with combined Vacuum
• Stringent quality standards as per ISO9001 and interrupter Dis-connector and earthing switch.
14001. • Capacitive voltage detection system for all feeders.
Saves Lives • Protective self-powered relay & current transformers
for transformer protection.
• Internal arc fault tested switchgear including cable
compartment. • Individual panel / block type construction.
• Capacitive voltage detection system for verification of • Manual operating mechanism (option: with motor).
safe isolation from supply. • Cable connection from front.
• Logical mechanical interlocks.
Increases Productivity
• Gas pressure monitoring via Manometer.
• All switching operations and cable access from the
front. Options
• Safe to touch and hermitically sealed, gas tight, • Short circuit / earth fault indicators for ring feeders.
welded stainless steel primary enclosure, independent
• Shunt release for VCB feeders.
of environmental effects (dust, moisture, vermins
etc.). • Motor-operated ring & VCB feeders.
• Extensible on either sides. • Local/remote selector switch for motorized feeders.
• Provision for two runs of cable connection max
Saves Money up to 3Cx300 sq.mm.
• Single switching element for load breaking,
disconnecting and earthing.
• Maintenance free operating mechanism accessible
outside the high voltage enclosure.
• Most compact individual panel/ block type
construction, ensuring minimum space requirement.
6
Notes
7
For more information, please contact:
Vadodara
“Vishwakarma Bhavan”
Ground Floor, Maneja Works Northern Region International Sales
Vadodara - 390 013 Gurgaon Mumbai
Tel.: +91-0265-395 7701 3rd Floor, Tower - B 2nd Floor, R&D and Technology Centre
Pune Plot No. 6-A, Sector - 18 Kalwa Works, Thane-Belapur Road
701-705, ICC Trade Tower Maruti Industrial Area, HUDA Airoli Node
B Wing, Senapati Bapat Marg Gurgaon - 122 015, Haryana (India) Navi Mumbai - 400 708
Pune - 411 016, Maharashtra (India) Tel.: +91-124-383 7377 Tel.: +91-22-3326 5005
Tel.: +91-20-3046 6039