Nulec - Autorecloser
Nulec - Autorecloser
Nulec - Autorecloser
Loop Automation
Reclosers & Sectionalizers
NU-LEC LLC
Nu-Lec Industries
Corporate Office and
Factory. Brisbane
Electronic Products
NU-LECs
Distribution Automation Optimized Family of
Products
NU-LEC
N SERIES RECLOSER
8
CIRCUIT BREAKER
plus
ELECTRONIC CONTROL
equals
AUTO-CIRCUIT RECLOSER
9
N Series
Recloser
N Series Recloser
Large Open/Close
Indicator
Four models:
N12-15 rated 15.5kV 630A 110kV 12.5kA
N36-27 rated 27kV 630A 150kV 12.5kA
N36-12.5 rated 38kV 630A 170kV 12.5kA
N36-16 rated 38kV 800A 170kV 16kA
PTCC control and communications cubicle with integral RTU
Type Tested to comply with ANSI C37.60,IEC56 & IEC255
11
13
Insulated
throughout
Control Cubicle
Operator Hatch
PTCC
Control
Cubicle
Comms. Tray with RS232 cable
and DC power supply
14
HV LINE 3 PHASES
CIRCUIT BREAKER
AUXILIARY
SWITCHES
MODEM
MEMORY
MOTOR
POWER
SUPPLY
TRIP/
CLOSE
MOTOR
UNINTERRUPTIBLE
POWER SUPPLY
CONTROL
CABLE
SPI
OPERATOR
SUB SYSTEM
PANEL
CONTROL CUBICLE
SERIAL
INTERFACE
PRESSURE
SENSOR
RS232
MICRO
PROCESSOR
CVT
ANALOGUE TO
DIGITAL
CONVERTER
DIGITAL INTERFACE
VACUUM
INTERRUPTER
CAPM
ANALOGUE
FRONT END
CT
WSOS
OPERATOR
PC
RS232
V23 FSK
TRIP
CAPACITOR
CLOSE
CAPACITOR
REMOTE
I/O
MODEM
RADIO
BATTERY
15
---------Auto ON/OFF
Local/Remote
---------S
Prot Group
Reset Flags
16
Measurement
17
Protection
18
NU-LEC
RL SERIES
LOAD-BREAK SWITCH
AND
SECTIONALIZER
19
RL Series
Natural matte finish,
grade 316 stainless steel
Lifting Handles
Add SCADA and fully Automate
with PTCC Control Cubicle
20
RL Series
15-27 kV
15-27 kV
Continuous current
630 A
12.5 kA/16kA
31.5 kA/40kA
Mechanical Operations
3000
600
21
Installation
Lightning arrestors
Grounding points
All grounding should be
of correct size, using
crimped connections and
be kept as short as
practicable to prevent
high impedances during
impulse.
SCADA comms.
(optional)
Control cable
PTCC Control
cubicle (optional)
22
Protection
Auto Change to protection group A and B depending on direction of power flow.
User configurable.
Protection settings easily loaded from the control panel or WSOS software.
Special Features
Loop Automation: Has the ability to isolate a faulted section of feeder within
one minute with out the need for peer-to-peer communications.
Auto-Changeover: Has the ability to quickly change over from a main feed
to an alternate feed at a critical load; requires peer-to-peer communications.
23
24
Adjustable height
galvanized steel Substation
Mounting Frame
25
UtiliNet
Radio
26
Auto-Changeover
&
Feeder Automation
Reclosers & Sectionalizers