Melpro D
Melpro D
Melpro D
MELPRO -D Series
TM
MELPRO -D Series
TM
MELPRO -D
TM
HEAD OFFICE
CAUTION
TO PREVENT IT FROM THE RISK OF DAMAGE AND MAL FUNCTION,
BE SURE TO READ OPERATING AND MAINTENANCE (SERVICING)
INSTRUCTIONS BEFORE USING.
SE-E840-C(11.03-1.0)ROS
Published Mar.2011
Safety section
This Safety section should be read before starting any work on the relay. Be sure to read the instruction
manuals and other related documents prior to commencing any work on the relay in order to maintain them
in a safe condition. Be sure to be familiar with the knowledge, safety information and all caution items of the
product prior to use.
CAUTION Caution means that failure to un-observe safety information, incorrect use, or improper use may endanger personnel and equipment and cause personnel injury or physical damage.
Items as classified to the caution may become to occur more sever results according to the circumstance. Therefore, all items described
in the safety section are important and to be respected without fail.
CAUTION
1. Items concerning transportation
(1) Be sure the equipment to be kept in normal direction
(2) Avoid the bumps, shock, and vibration, otherwise the product performance /life might be unfavorably affected.
2. Items concerning storage
(1) Environment shall be as below, otherwise the product performance/life might be unfavorably affected.
-Ambient temperature: -20+60(with no condensation nor freezing)
-Relative humidity: 3080% average of a day
-Altitude: Less than 2000m
-Avoid applying unusual shock, vibration or leaning or magnetic field
-Not expose to harmful smoke, gas, salty air, water, vapor, dust, powder, explosive material or wind, rain.
3. Items concerning mounting/wiring work
(1) Mounting and wiring work should be done correctly. Otherwise, damage, burning or erroneous operation might occur.
(2) Screw terminal should be tightened securely. Otherwise, damage and burning might occur.
(3) Grounding should be done correctly in case it is required. Otherwise, electric shock, damage, burning or erroneous operation might occur.
(4) Wiring should be done without mistake especially observing the correct polarity. Otherwise, damage, burning or erroneous operation might
occur.
(5) Wiring should be done without mistake especially observing the phase ordering. Otherwise, damage, or erroneous operation might occur.
(6) Auxiliary power source, measuring transformer and power source which have enough capacity for correct operation of product should be used.
Otherwise, an erroneous operation might occur.
(7) Be sure to restore the front cover, terminal cover, protection cover, etc to the original position, which have been removed during the mounting/
wiring work. Otherwise, electrical shock might occur at the time of checking.
(8) Connection should be done correctly using designated and right connectors. Otherwise, damage or burning might occur.
(9) Fully insert the sub unit into the case until you can hear a click while pressing the handles located on both sides of the sub unit front face.
Otherwise, incomplete inserting the sub unit might only establish a poor contact with the terminals located on the back side of unit, which might
cause erroneous operation or heating.
4. Concerning equipment operation and settings
(1) Operational condition should be as below. Otherwise, the product performance/life might be unfavorably affected.
-Deviation of auxiliary power: within +10%-15% of rated voltage
-Deviation of frequency: within 5%of rated frequency
-Ambient temperature: 0+40(-10+50 is permissible during couples of hour per day, with no condensation nor freezing)
-Relative humidity: 3080% average of a day
-Altitude: Less than 2000m
-Avoid to be exposed to unusual shock, vibration, leaning or magnetic field
-Not expose to harmful smoke, gas, salty air, water, vapor, dust, powder, explosive material, wind or rain.
(2) Qualified personnel may work on or operate this product, otherwise, the product performance/life might be unfavorably affected and/or
burning or erroneous operation might occur.
(3) Be sure to read and understand the instruction manuals and other related documents prior to commencing operation and maintenance work on
the product. Otherwise, electrical shock, injury, damage, or erroneous operation might occur.
(4) While energizing product, be sure not to remove any unit or parts without permissible one. Otherwise, damage, or erroneous operation might
occur.
(5) While energizing product, be sure to make short circuit of current transformer secondary circuits before setting change or drawing out the sub
unit. Otherwise, secondary circuit of live current transformer might be opened and damage or burning might occur due to the high level
voltage.
(6) While energizing product, be sure to open trip lock terminal before setting change or drawing out the internal unit of product. Otherwise,
erroneous operation might occur.
(7) Be sure to use the product within rated voltage and current. Otherwise, damage or erroneous operation might occur.
(8) While energizing product, be sure not to clean up the product. Only wiping a stain on the front cover of product with a damp waste might be
allowable. (Be sure to wring hardly the water out of the waste.)
5. Items concerning maintenance and checking
(1) Be sure that only qualified personnel might work on or operate this product. Otherwise, electrical shock, injury, damage, or erroneous operation
might occur.
(2) Be sure to read and understand the instruction manuals and other related documents prior to commencing operation and maintenance work on
the product. Otherwise, electrical shock, injury, damage, or erroneous operation might occur.
(3) In case of replacing the parts, be sure to use the ones of same type, rating and specifications, etc. If impossible to use above parts, be sure to
contact the sales office or distributor nearest you. Otherwise, damage or burning might occur.
(4) Testing shall be done with the following conditions.
-Ambient temperature: 2010
-Relative humidity: Less than 90%
-Magnetic field: Less than 80A/m
-Atmospheric pressure: 86106103 Pa
-Installation angle: Normal direction2
-Deviation of frequency: within 1%of nominal frequency
-Wave form (in case of AC): Distortion factor less than 2% (Distortion factor=100%effective value of harmonics/effective value of fundamental)
-Ripple (in case of DC): Ripple factor less than 3% (Ripple factor=100%(max-min)/average of DC)
-Deviation of auxiliary power: within 2% of nominal voltage
-Be sure not to inject the voltage or current beyond the overload immunity. Otherwise, damage or burning might occur.
-Be careful not to touch the energized parts. Otherwise, the electric shock might occur.
6. Items concerning modification and/or repair work
Be sure to ask any modification and/or repair work for product to the sales office or distributor nearest you.
Unless otherwise, any incidents occurred with modification or repair works (including software) done by any other entity than MITSUBIHI
ELECTRIC CORPORATION shall be out of scope on warranty covered by MITSUBISHI ELECTRIC CORPORATION.
7. Items concerning disposal
Particular regulations within the country of operation shall be applied to the disposal.
63
How to order
Please check the specifications and be ready with the following information when placing order.
Sample of ordering
In case of COC4-A01D1
Optional specification
Fundamental specification
Items to be informed
Remarks
Type name
COC4A01D1
Frequency
50Hz
Ratings
Languages
English language
Communication
function
Parts
Case
When ordering, please specify the type of case D1 or D2 and uses of case (for testing
purpose or not). Please note that CT circuits shorten mechanism is not equipped in
the dedicated case of testing purpose.
Cover
Please specify the type of relay and terminal block arrangement(from the left side of
the back A,B,C,E). Please note ordering only cover is not accepted.
Please note that other specification than described in this catalogue is not applicable for manufacturing.
Function
Hardware size
Digital computation
The digital computation is also
applied to filter and then little
deterioration of filter characteristics
makes improving of reliability.
Analog digital
conversion
High degree of reliability
X1
dual system
Self-diagnosis function
Dual system
Prevent the misoperation due
to the hardware failure.
P L C
I/F
RYMELPRO-D
RY
Other than RY
Case
Sub unit
RS-232C
Cover
MELPRO -D series
TM
Output sequence
can be set freely
with usingORlogic
X0
I
X3
X4
X5
In the event of system fault, input effective value and wave form data have been
measured and stored at the time when one of the protection elements operates to
issue an output signal. Data for up to five phenomena can be stored and displayed.
Therefore, analyze of phenomena becomes easy.
Upper Fig. : Image of waveform down loaded by the Direct PC HMI software
The dimension of the panel cutting is the same as the prior MULTICAP series. Replacing from the existing one to this new type is possible easily without using adaptor.
Also, as this relay has a high degree of compatibility with the existing relay, the design change of the existing system is minimized.Except for some types of relay
Easy maintenance
The draw-out unit mechanisms with automatic CT shorting is adopted, so that relay unit can be draw out without removing any parts
or wirings. Thereby, it is possible to improve maintenance ease.
contents
Safety section 2
How to order
Display/Setting Operation 62
61
Series
CMP2A02D2
CGP1A01D2
CGP1A03D2
49
37
46
47
66
67S
67P
95L
95H
91L df/dt
84
87G
87T
64
CGP2A02D2
59
CGP2A01D2
CPP1A11D2
CMP1A02D1
CPP1A01D2
CMP1A01D1/2
CAC1A01D2
CDG1A01D1
CFP1A02D1
CFP1A01D1
CUB1A01D1
COC4A03D1
COC4A02D1
CBV4A01D1
COC4A01D1
CBV3A01D1
COC3A03D1
COC3A01D1
27
CBV2A01D1
COC2A01D1
COC1A02D1
COC1A01D1
Type
Type of MELPRO-D series and implemented elements for each type are shown as below Table.
40
Remarks
CTphase current
CTphase current
P.47
P.35
P.24
P.20
Voltage relay
P.9
Overcurrent relay
NGR
CT
I I
CT
CB
CT
EVT
M
NGR
SC
TR
VT
I I
50/51
51G
VT
59
27
CT
CB
Id/I
87T
: Circuit Breaker
: Current Transformer
: Earthed type voltage Transformer
: Motor
: Neutral Grounded Resister
: Static Condenser
: Transformer
: Voltage Transformer
Abbreviation
SC
CB
51G
50/51
11kV/22kV
51G
50/51
51G
50/51
27
CB
CB
CT
Resistance grounded C T
neutral system
TR
CT
CT
CB
VT
33W 66kV
III
INSC
Its
50 51 51G 37 46 49 66
67G
CB
CT
ZCT
50/51
III
INSC
Its
50 51 67G 37 46 49 66
EVT
64
59
27
6.6kV/3.3kV
87T
51G
Id/I
51G
50/51
CT
27
50/51
CB
ZCT
CB
CT
CT
TR
CT
CT
CB
VT
33W 22kV/11kV
50 51 67G
37 46 49 66
50/51
51G
50/51
51G
27
59
87T
50/51
51G
50/51
51G
50/51
27
59
64
50/51
67G
27
59
64
50 51 51G
37 46 49 66
27
Device number
TM
MELPRO -D
COC4-A01D1
COC4-A01D1
COC4-A02D1
COC4-A03D1
COC2-A01D1
CMP1-A01D1/CMP1-A01D2
CMP1-A02D1/CMP2-A02D2
CBV3-A01D1
CFP1-A01D1
CBV3-A01D1
3COC3-A01D1/COC3-A03D1
COC4-A01D1
1COC1-A02D1
COC3-A01D1/COC3-A03D1
3COC3-A01D1/COC3-A03D1
1COC1-A02D1
1CBV2-A01D1
2CBV3-A01D1
CAC1-A01D2
3COC3-A01D1/COC3-A03D1
1COC1-A02D1
3COC3-A01D1/COC3-A03D1
1COC1-A02D1
1CBV3-A01D1
3CBV2-A01D1
Remark 1: It is advisable to adopt the dual system or 2 out of 3 systems in order to improve the reliability of the important facilities.
Remark 2: In case of not available an uninterruptible power source, please use AC/DC converter type B-T1 manufactured by
MITSUBISHI ELECTRIC CORPORATION or commercially available uninterruptible power source (UPS) instead of using AC
auxiliary power source such as derived from VT secondary circuit because of no guarantee against power interruption during
system faults.
High voltage
(secondary of
transformer)
Incoming of
extra high voltage
Network
Environment
Ratings
DESCRIPTION
IEC60255-6
25 to 70
IEC60255-6
Damp heat
IEC60068-2-78
IEC60255-6
Operative range of
auxiliary power supply
DC: 15 to 10
(Temporarily 20 to 30)
AC: 15 to 10
(Temporarily 15 to 15)
IEC60255-6
Frequency
50 or 60Hz
IEC60255-6
Burden
VT
CT
Thermal
withstand
VT
CT
1.15VN, 3hours
40IN, 1second
Contact
capacity
For signalling and alarm
IEC60255-6
Make
(L/R0)
IEC60255-0-20
Break
(L/R40ms)
IEC60255-0-20
Break
500VA
60W
(cos 0.4)
(L/R0.007s)
IEC60255-0-20
Max.
current
5A
IEC60255-0-20
Max.
voltage
380VAC/125VDC
IEC60255-0-20
For trip
500VAC, 1min.
Dielectric test
2000VAC, 1min.
Open contact
1000VAC, 1min.
5kV, 1.2s/50s
Common mode
Differential mode
8kV
15kV
Contact discharge
Air discharge
STANDARD
10 to 55
VT
CT
Auxiliary power supply
High-frequency
disturbance
test
CONDITION
Ambient operating
temperature
IEC60255-5
IEC60255-5
IEC60255-22-1
class 3
IEC60255-22-2
class 4
IEC60255-22-3
class 3
IEC60255-22-4
Vibration test
Refer to class 1
IEC60255-21-1
class 1
Shock response
Refer to class 2
IEC60255-21-2
class 2
Shock withstand
Refer to class 1
IEC60255-21-2
class 1
Bump
Refer to class 1
IEC60255-21-2
class 1
Enclosure protection
IP51
IEC60529
Display
Forced operation
Direct communication port
Communication
Remote communication port
Burden (at rating)
Mass
Sample of external connection diagram
Remarks
COC3A01D1
COC1A01D1
COC2A01D1
5A
5A
5A
50Hz or 60Hz
51/50 3 phases
51/50 2 phases
51/50 1 phase
LOCK112A0.1A step
LOCK0.10.8A0.05A step
0.250.550 0.5 step
Normal inverse time-delayed3 kinds, Very inverse time-delayed2 kinds,
Extremely inverse time-delayed3 kinds, Long inverse time-delayed3 kinds, Definite time-delayed1 kind
Normal inverse time-delayed 1 kind, Definite time-delayed 2 kinds
LOCK280A1A step
LOCK18A0.1A step
INST0.10.5s 0.1s step
Refer to the external connection diagram/Auto reset for all contacts Default setting at ex-works
All LED self-hold Default setting at ex-works
15101212.5152025304050607580100120125150200250300400500600750800100012001250
150020002500300040005000600075008000[A] Positive phase rating : Applicable 1 A rating product only
Phase current 2 phases Phase current 3 phases
Phase current 1 phase
Phase current 2 phases Phase current 3 phases
Phase current 1 phase
Phase current 2 phases Phase current 3 phases
Phase current 1 phase
Record and indicate the operated elements
010 (The value 0 indicates the status of input current reaching the setting value or more and
the value 110 indicate the elapse time up to operating of the time delayed element.
Normal result: On the RUN LEDgreenStatus indication item No.400=No display.
Abnormal result: Off the RUN LEDStatus indication item No.400=Display defects code
Each output contact
Standard equipmentPC software for Direct communication: option
Option For CC-LINK
Phase current circuit: Less than 0.5VA/phase
Auxiliary power supply circuit: at DC100V=Approx. 5W, at AC100V=Approx. 7VA, at DC220V=Approx. 6W,
at AC220V=Approx. 12VAIn case of installing communication card, add 2 VA.
Net weight of relay unit: Approx. 2.3kg, Including case: Approx. 3.0kg
Fig.157
Fig.135
Fig.1-8
Fig.1-9
The rated current 0.2A product can be made based on the 1A rating product.Also, the rated current 1A
product can be made based on the 5A rating product.
The setting value of time delayed element and instantaneous element of 0.2A product and 1A product are
calculated by performing a multiplication 1/5 of above mentioned value.
COC1A02D1
1A
Please refer to the instruction manual regarding the details on this specification.
COC
COC4A01D1
COC4A03D1
COC4A02D1
5A
5A
5A
1A
1A
5A
50Hz or 60Hz
51/50 3 phases, 51G/50GZero-phase
51/50 3 phases
Protective element
Operation current
LOCK112A0.1A step
LOCK0.58A0.1A step
Operation time multiplier
0.250.550 0.5 step
Phase fault
Operation time
Normal inverse time-delayed 3 kinds, Very inverse time-delayed 2 kinds,
time-delayed
characteristics
Extremely inverse time-delayed 3 kinds, Long inverse time-delayed 3 kinds, Definite time-delayed 1 kind
Reset time characteristics
Normal inverse time-delayed1 kind, Definite time-delayed 2 kinds
Phase fault Operation current
LOCK280A1A step
instantaneous Operation time
INST0.10.5s 0.1s step
Operation current
1025%5% step
Operation indicator LED hold
Refer to the external connection diagram/Auto reset for all contacts Default setting at ex-works
Output contact configuration
All LED self-hold Default setting at ex-works
CT primaryPhase current
15101212.5152025304050607580100120125150200250300400500600750800100012001250
CT primaryZero-phase current 150020002500300040005000600075008000[A] Positive phase rating : Applicable 1 A rating product only
Type name
Phase current
Rating Zero-phase current
Frequency
COC3A03D1
5A
Remarks
The rated current 1A product can be made based on the 5A rating product.
The setting value of time delayed element and instantaneous element of 1A product is calculated by
performing a multiplication 1/5 of above mentioned value.
The operation current setting range "LOCK-2130A (1A step)" for phase fault instantaneous element of
type COC4-A02D1 is also available.
Please refer to the instruction manual regarding the details on this specification.
10
COC
Characteristics
Items
Condition
Common condition1
2
I
If2
3 DC
100
If1
IDC
2 IAC
2
In case of harmonic current
superposing method
Reset value
Common condition1
Operation time
Phase fault
instantaneous
element
Earth fault time
delayed element
Reset time
Overshoot
characteristic
Earth fault
instantaneous
element
All elements
Phase fault time
delayed element
Earth fault time-delayed element
Guaranteed performance
Setting 1.02.0A for 5A rating product
Setting 0.20.4A for 1A rating product
Setting value 10%
For setting of other range
Setting value 5%
Setting value 10%
Setting 0.10.2A for 5A rating product
Setting 0.020.04A for 1A rating product
Setting value 10%
For setting of other range
Setting value 5%
Setting value 10%
IAC254330
Setting value10%
10 Setting value
Setting value 15
1525 Setting value
Setting value 10
Setting 1.02.0A for 5A rating product
Setting 0.20.4A for 1A rating product
Operation value90% or more
For setting of other range
Operation value95% or more
Operation value95% or more
Setting 0.10.2A for 5A rating product
Setting 0.020.04A for 1A rating product
Operation value90% or more
For setting of other range
Operation value95% or more
Operation value95% or more
Operation value85% or more
Refer to fig.1-1.2
Timing accuracy for I3Current setting value,
3.5% of reference at actual pick up
Setting value 25ms
In case of INST setting 40ms or less (except COC4-A03D1)
50ms or lessCOC4-A03D1
Refer to fig.1-1.2
Timing accuracy for I3Current setting valve,
3.5% of reference at actual pick up
Setting value 25ms
In case of INST setting 40ms or less (except COC4-A03D1)
50ms or lessCOC4-A03D1
Refer to table 1-1
No-operation limit time/Operation time=90% or more
1Common condition
1Rating Frequency2Ambient temperature203Auxiliary power supply: Rating voltage
11
COC
Inrush current Ip
Approx. 20A
Approx. 55A
Approx. 25A
Approx. 65A
3. Trip circuit
Only the dedicated contacts can be used for the circuit breaker trip
circuit. Please keep in mind that the contacts for signaling can not be
used for the trip circuit. (If used, the contact may burn). Also, connect
the pallet contact (52a) of the circuit breaker to the trip coil circuit in
series.
4. Self-diagnosis output circuit
The self-diagnosis output contact is so configured that the auxiliary
relay is energized
( break contactopened) when normal result of
self-diagnosis is received. This type of contact will allow the relay to
output abnormal result even after the built-in power failures.
Therefore, the break contact is still closed in the aftermath of the
power applying and will be opened after 50ms. If the auxiliary power
of the relay and the self-diagnosis output contact feed from a same
power source, the break contact will be closed temporarily after
auxiliary power supply is turned on. In this case where the
phenomenon stated in the above would conflict with your system
requirement, it is recommended that the self-diagnosis output contact
should be connected via the time-delay timer.
5. Grounding circuit
Be sure to make a wiring to the earth terminal located on the back of
the relay according to the Class D earth wiring method (Grounding
resistance should be less than 100 ohm).
6. CC-Link communication circuit
Please include the communication card into your purchasing order in
case of the application of the communication facility as the card
necessary for communication (CC-Link ) is option. In case of retrofit
existing relay with communication card, please inform the followings
of existing relay. a:Type, b:Style number, c:Manufacturing year,
d:Serial number, e:Date of stamp on the checking seal (The above
mentioned items a.d. are indicated on the bottom right of front face
of the relay and item e. is indicated on the upper of back side of the
relay.) The version number of CC-Link is 1.00.
7. Improvement of reliability of protection system
For the important facilities, multiplex system such as dual should be
provided to improve reliability.
8. Effects of external surge
Some type of surge with a certain condition may inversely affect the
relay. If so, take it into account to install surge absorbers.
9. The residual connection of 3 phases CT is needed for the earth fault
current elements of COC4-A01, A02, A03D1 types.
10. It is possible to use the COC3 and COC4 as the phase over current
protection provided with two phases. However, residual connection of
2 phases can not be applied to the earth fault over current element of
COC3 and COC4 types. The residual connection of 3 phases only can
be applied to the earth fault over current element. In case of only two
phase CTs being available for phase over current protection, ZCT or
one more CT is needed for earth fault over current element.
12
COC
I 1
10 (s)
500
I1
10 (s)
100
500
100
I1
10 (s)
10
LI02
LI01
NI01
I 1
10 (s)
I
10 (s)
EI01
0.1
10
10
LI21
NI21
1
EI11
Operation time
Current
(Multiple of input current
against setting value)
Operation time multiplier
EI12
0.1
20
10
20
60
M
I1
10 (s)
Operation time
Current
(Multiple of input current
against setting value)
Operation time multiplier
These curves show the operation
time characteristic for each type in
case of the time multiplier M=10.
Approx.M10
or less
immediately
8
tr
1I2
M
10
(s)
13
COC
Auxiliary
power supply
circuit
A01
Y
B05
Self diagnosis output
B06
B07
A03
X0
Instantaneous
I
B08
B09
A07
IA
A08
X1
For
signaling
B10
B11
X2
Time-delayed
I
B12
B13
X3
B14
B17
CT
X4
B18
B19
IOR I
For trip
X5
E A02
Communication card
(option)
B20
ED
Programmable output
Default setting at ex-works
B01 DA
B02 DB
B03 DG
B04 SLD
ED
Auxiliary
power supply
circuit
A01
Y
B05
Self diagnosis output
B06
B07
A03
X0
B08
B09
Instantaneous
I
X1
For
signaling
B10
B11
X2
B12
B13
A07
Time-delayed
I
X3
IO
B14
B17
A08
X4
B18
B19
CT
IOR I
For trip
X5
E A02
Communication card
(option)
B20
ED
B01 DA
Programmable output
Default setting at ex-works
B02 DB
B03 DG
B04 SLD
ED
14
The connection diagram shows concepts of the wiring only. Therefore, please note that there will have some difference
between the connection diagram and actual installation status of CT,VT and safety devices such as fuse, etc.
COC
Auxiliary
power supply
circuit
A01
Y
B05
Self diagnosis output
B06
B07
A03
X0
A05
X1
A06
For
signaling
B10
B11
I0
Instantaneous
I
B08
B09
X2
Time-delayed
I
B12
B13
X3
B14
B17
COC3A01D1
CT
X4
B18
B19
IOR I
For trip
X5
E A02
Communication card
(option)
B20
ED
Programmable output
Default setting at ex-works
B01 DA
B02 DB
B03 DG
B04 SLD
ED
The terminal number A-05 is changed to A-07 and A-06 is changed to A-08 in case of COC1-A01D1 type
Auxiliary
power supply
circuit
COC3A01D1
A01
Y
B05
Self diagnosis output
B06
B07
A03
X0
B08
B09
X1
Earth fault
Instantaneous
I
For
signaling
B10
B11
X2
B12
B13
Example:
400/5 or more
X3
CT
B14
B17
ED
A05
Example:
100/5
I0
Earth fault
Time-delayed
I
X4
B18
B19
A06
IOR I
For trip
X5
B20
E A02
Communication card
(option)
ED
B01 DA
Programmable output
Default setting at ex-works
B02 DB
B03 DG
B04 SLD
ED
15
COC
Auxiliary
power supply
circuit
A01
Y
B05
Self diagnosis output
B06
B07
A03
X0
Earth fault
Instantaneous
I
B08
B09
X1
For
signaling
B10
B11
X2
A05
ZCT
Example: 100/5
IO
Earth fault
Time-delayed
I
B12
B13
X3
B14
B17
A06
X4
ED
B18
B19
IOR I
For trip
X5
E A02
Communication card
(option)
B20
Programmable output
Default setting at ex-works
B01 DA
B02 DB
B03 DG
B04 SLD
ED
+
Auxiliary
power supply
circuit
A01
Y
B05
Self diagnosis output
B06
B07
A03
X0
B08
B09
A07
IA
A08
X1
IC
A12
CT
For
signaling
B10
B11
X2
B12
B13
A11
Instantaneous
I
Time-delayed
I
X3
B14
B17
X4
B18
B19
IOR I
For trip
X5
E A02
Communication card
(option)
B20
ED
B01 DA
Programmable output
Default setting at ex-works
B02 DB
B03 DG
B04 SLD
ED
16
The connection diagram shows concepts of the wiring only. Therefore, please note that there will have some difference
between the connection diagram and actual installation status of CT,VT and safety devices such as fuse, etc.
COC
+
Auxiliary
power supply
circuit
A01
Y
B05
Self diagnosis output
B06
B07
A03
X0
Instantaneous
I
B08
B09
A07
IA
A08
A09
IB
X1
For
signaling
B10
B11
X2
Time-delayed
I
B12
B13
X3
B14
B17
A10
X4
A11
A12
CT
ED
E A02
IOR I
For trip
X5
B20
Communication card
(option)
IC
B18
B19
Programmable output
Default setting at ex-works
B01 DA
B02 DB
B03 DG
B04 SLD
ED
Auxiliary
power supply
circuit
A01
Y
IA
A08
X0
B08
B09
X1
B10
B11
A09
IB
X2
IC
X3
B14
B17
A12
A05
I0
B12
B13
A10
A11
A06
X4
B18
B19
X5
Earth faultInstantaneous
I
Earth faultTime-delayed
I
Phase faultInstantaneous
I
For
signaling
Phase faultTime-delayed
I
IOR I
OR IOR I
For trip
B20
ED
Tr
E A02
Communication card
(option)
CT
A03
A07
B05
B01 DA
Programmable output
Default setting at ex-works
B02 DB
B03 DG
B04 SLD
ED
Fig.110COC4A01D1COC4A02D1COC4A03D1
The connection diagram shows concepts of the wiring only. Therefore, please note that there will have some difference
between the connection diagram and actual installation status of CT,VT and safety devices such as fuse, etc.
17
COC
Auxiliary
power supply
circuit
A01
Y
IA
A08
B08
B09
IC
Earth faultTime-delayed
I
X1
B10
B11
Phase faultInstantaneous
I
X2
B12
B13
A10
A11
CT
Earth faultInstantaneous
I
X0
A09
IB
A03
A07
B05
Phase faultTime-delayed
I
X3
B14
B17
A12
X4
ED
IOR I
B18
B19
I0
A06
ED
E A02
OR IOR I
X5
For trip
B20
Communication card
(option)
A05
ZCT
Example: 100/5
For
signaling
Programmable output
Default setting at ex-works
B01 DA
B02 DB
B03 DG
B04 SLD
ED
Fig.111COC4A01D1COC4A02D1COC4A03D1
+
Auxiliary
power supply
circuit
A01
Y
IA
A08
X0
B08
B09
X1
B10
B11
A09
IB
X2
IC
B12
B13
A10
A11
Example:
400/5 or more
A03
A07
B05
X3
B14
B17
A12
X4
B18
B19
ED
A05
Example:
100/5
I0
A06
ED
E A02
X5
Earth faultTime-delayed
I
Phase faultInstantaneous
I
For
signaling
Phase faultTime-delayed
I
IOR I
OR IOR I
For trip
B20
Communication card
(option)
CT
Earth faultInstantaneous
I
B01 DA
Programmable output
Default setting at ex-works
B02 DB
B03 DG
B04 SLD
ED
Fig.112COC4A01D1COC4A02D1COC4A03D1
18
The connection diagram shows concepts of the wiring only. Therefore, please note that there will have some difference
between the connection diagram and actual installation status of CT,VT and safety devices such as fuse, etc.
COC
+
Auxiliary
power supply
circuit
A01
Y
IA
A08
B08
B09
IC
Earth faultTime-delayed
I
X1
B10
B11
Phase faultInstantaneous
I
X2
B12
B13
A10
A11
CT
Earth faultInstantaneous
I
X0
A09
IB
A03
A07
B05
Phase faultTime-delayed
I
X3
B14
B17
A12
X4
I0
A06
ZCT
Example: 100/5
E A02
ED
OR IOR I
X5
For trip
B20
Communication card
(option)
A05
Tr
IOR I
B18
B19
ED
For
signaling
Programmable output
Default setting at ex-works
B01 DA
B02 DB
B03 DG
B04 SLD
ED
Fig.113COC4A01D1COC4A03D1
Auxiliary
power supply
circuit
A01
Y
IA
A08
X0
B08
B09
X1
B10
B11
A09
IB
X2
IC
B12
B13
A10
A11
CT
A03
A07
B05
X3
B14
B17
A12
X4
B18
B19
ED
I0
Tr
A06
CT
E A02
ED
Earth faultTime-delayed
I
Phase faultInstantaneous
I
For
signaling
Phase faultTime-delayed
I
IOR I
OR IOR I
For trip
B20
Communication card
(option)
A05
X5
Earth faultInstantaneous
I
B01 DA
Programmable output
Default setting at ex-works
B02 DB
B03 DG
B04 SLD
ED
Fig.114COC4A02D1
The connection diagram shows concepts of the wiring only. Therefore, please note that there will have some difference
between the connection diagram and actual installation status of CT,VT and safety devices such as fuse, etc.
19
CBV
CUB
CBV2A01D1
57120V
CBV3A01D1
57120V
110V/190V
CBV4A01D1
57120V
110V/190V
CUB1A01D1
57120V
50Hz or 60Hz
27 1 phase, 59 1 phase,
27 3 phases,
27 3 phases,
Protective element
64 Zero-phase
64 Zero-phase
2
59 3 phases, 47
LOCK10110V1V step
Under Operation voltage
voltage Operation time
INST0.110s 0.1s step
Operation voltage
LOCK60155V1V step
LOCK60155V1V step
Over
voltage Operation time
INST0.110s 0.1s step
LOCKUSE
Reverse Changeover Lock/Use
phase Operation time
LOCK1050V1V step
Setting Open Operation voltage
phase Operation time
Line voltage,
Line voltage3,
Real time measurement
Line voltage3
Line voltage3
Zero-phase voltage
Zero-phase voltage
Line voltage,
Line voltage3,
Max.record
Line voltage3
Line voltage3
Zero-phase voltage
Zero-phase voltage
Line voltage,
Line voltage3,
Line voltage3,
Display
Fault record (operation value)
Line voltage3
Zero-phase voltage
Zero-phase voltage
Negative sequence voltage
Fault record (operation item)
Record and indicate the operated elements.
Normal result:On the RUN LED (green) Status indication item No.400=No display.
Self-diagnosis
Abnormal result:Off the RUN LEDStatus indication item No.400=Display defects code
Each output contact
Forced operation
Standard equipmentPC software for Direct communication: Option
Direct communication port
Not applicable
Communication
Option For CC-LINK
Remote communication port
Not applicable
Voltage circuit:Less than 1 VA, Zero-phase voltage circuit:Less than 0.15 VA
Auxiliary power supply circuit:at DC100V=Approx. 5W, at AC100V=Approx. 7VA,
Burden (at rating)
at DC220V=Approx. 6W, at AC220V=Approx. 12VAIn case of installing communication card, add 2 VA.
Net weight of relay unit:Approx. 2.3kg, Including case:Approx. 3.0kg
Mass
27 3 phases,
59 3 phases
Fig.21
Fig.22
Please refer to the instruction manual regarding the details on this specification.
20
Fig.23
Fig.24
Characteristics
Condition
Items
Under voltage element
Over voltage element Common condition1
Earth fault over voltage element
Operation value Reverse phase element Impress 3 phases negative sequence voltage
Impress 3 phases negative sequence voltage
Open phase element However, in case of applying single phase power source,
impress the voltage of setting value3
Under voltage element
Over voltage element
Reset value Earth fault over voltage element Common condition1
Reverse phase element
Open phase element
Under voltage element Rated voltagesetting value70%
Over voltage element 0Vsetting value120%
Earth fault over voltage element 0Vsetting value150%
Operation time
Reverse phase element 0V3 phases negative sequence voltage
Open phase element
Reset time
Guaranteed performance
Setting value5%
CBV
CUB
200ms25ms
1Common condition
1Rating Frequency2Ambient temperature203Auxiliary power supply: Rating voltage
2Please refer to the instruction manual regarding the details on this specification.
Inrush current Ip
Approx. 20A
Approx. 55A
Approx. 25A
Approx. 65A
3. Trip circuit
Only the dedicated contacts can be used for the circuit breaker trip
circuit. Please keep in mind that the contacts for signaling can not be
used for the trip circuit. (If used, the contact may burn). Also, connect
the pallet contact (52a) of the circuit breaker to the trip coil circuit in
series.
4. Self-diagnosis output circuit
The self-diagnosis output contact is so configured that the auxiliary
relay is energized
( break contactopened ) when normal result of
self-diagnosis is received. This type of contact will allow the relay to
21
Auxiliary
power supply
circuit
A01
B05
A03
X0
Under voltage
U
B08
B09
VT
X1
A07
A08
X2
VAB
X3
B14
B17
A10
VBC
X4
A11
VCA
Over voltage
U
B12
B13
A09
ED
For
signaling
B10
B11
B18
B19
UOR U
For trip
X5
A12
Communication card
(option)
B20
E A02
B01 DA
Programmable output
Default setting at ex-works
B02 DB
B03 DG
B04 SLD
ED
+
Auxiliary
power supply
circuit
B
C
A01
Y
B05
Self diagnosis output
B06
B07
A03
X0
B08
B09
EA
X1
B10
B11
EVT
X2
B12
B13
ED
X3
A07
B14
B17
VAB
A08
Under voltage
U
For
signaling
Over voltage
U
X4
B18
B19
UOR
UOR U
For trip
X5
B20
A05
R
ED
V0
A06
E A02
Communication card
(option)
B01 DA
Programmable output
Default setting at ex-works
B02 DB
B03 DG
B04 SLD
ED
Fig.22CBV3A01D1
22
The connection diagram shows concepts of the wiring only. Therefore, please note that there will have some difference
between the connection diagram and actual installation status of CT,VT and safety devices such as fuse, etc.
+
Auxiliary
power supply
circuit
B
C
A01
Y
CBV
CUB
B05
Self diagnosis output
B06
B07
A03
X0
B08
B09
EA
X1
A07
EVT
VAB
B10
B11
B12
B13
A09
VBC
X2
A08
ED
Under voltage
U
X3
B14
B17
A10
X4
A11
VCA
A12
f
ED
V0
For trip
B20
A05
UOR
UOR U
X5
Programmable output
Default setting at ex-works
Communication card
(option)
B18
B19
A06
E A02
B01 DA
B02 DB
B03 DG
B04 SLD
ED
A resistance is necessary for the isolated neutral system.
Fig.23CBV4A01D1
Auxiliary
power supply
circuit
A01
Y
B05
Self diagnosis output
B06
B07
A03
X0
B08
B09
VT
A07
A08
X1
B10
B11
X2
B12
B13
VAB
A09
X3
B14
B17
A10
Under voltage
U
Over voltage
U
Reverse phase
RV
For
signaling
Open phase
UNSV
X4
VBC
A11
VCA
A12
B18
B19
UOR UOR
For trip
RVOR UNSV
X5
B20
Programmable output
Default setting at ex-works
E A02
ED
Fig.24CUB1A01D1
The connection diagram shows concepts of the wiring only. Therefore, please note that there will have some difference
between the connection diagram and actual installation status of CT,VT and safety devices such as fuse, etc.
23
Type name
Phase current
Zero-phase current
Rating
Zero-phase voltage
Frequency
Protective element
Combined
Zero-phase current
instrument
Zero-phase voltage
transformer
Operation current
Operation time multiplier
Timedelayed Operation time
characteristics
CFP
CDG
CFP1A01D1
5A
2A
110/190V
V0
Earth fault
directional
I0
Lead
I0
Lag
V0
Maximum
sensitive angle
Maximum
sensitive angle
Maximum
sensitive angle
Operation area
Setting
Operation area
15
Non-operation area
15
EVT primary
EVT tertiary
ZCT error correction on/off
ZCT error adjustment
Display
Forced operation
Direct communication port
Communication
Remote communication port
Mass
Sample of external connection diagram
Remarks
Refer to the external connection diagram/Auto reset for all contacts Default setting at ex-works
All LED self-hold Default setting at ex-works
15101212.515202530405060758010012012515020025030040050060075080010001200
1250150020002500300040005000600075008000[A]Applicable 1 A rating product only.
100999V1V step,
100999V1V step,10009990V10V step,
10009990V10V step,
10.0k99.9kV0.1kV step, 100k300kV1kV step
10.0k99.9kV0.1kV step,
100k300kV1kV step
1001101151201003
1001101151201003110311531203V
100311531203V
OFFON
When the actual measured transforming ratio is within range of 200/
1.54.1mA, the deviation from the ZCT nominal transforming ratio 200/1.5mA can be corrected.
Phase current2, Zero-phase current, Zero-phase voltage, Characteristic angle Zero phase current, Zero phase voltage, Phase
Phase current2, Zero-phase current, Zero-phase voltage
Zero phase current, Zero phase voltage
Phase current2, Zero-phase current, Zero-phase voltage, Characteristic angle Zero phase current, Zero phase voltage, Phase
Record and indicate the operated elements
010(The value 0 indicates the status of input current reaching the setting value or more and
the value 110 indicate the elapse time up to operating of the time delayed element.)
Normal result:On the RUN LED (green) Status indication item No.400=No display.
Abnormal result:Off the RUN LEDStatus indication item No.400=Display defects code
Each output contact
Standard equipmentPC software for Direct communication:Option
Not applicable
Option For CC-LINK
Not applicable
Phase current circuitLess than 0.5VA, Zero-phase current circuitLess than 10,
Zero-phase voltage circuitLess than 0.15VA,
Auxiliary power supply circuitat DC100V=Approx. 5W, at AC100V=Approx. 7VA, at DC220V=Approx. 6W,
at AC220V=Approx. 12VAIn case of installing communication card, add 2 VA.
Net weight of relay unit:Approx. 2.3kg, Including case:Approx. 3.0kg
Fig.31
Fig.3-2,3-3
The rated current 1 A product can be made based on the 5A rating product.
The setting value of time delayed element and instantaneous element of
1A product is calculated by performing a multiplication 1/5 of above mentioned value.
Please refer to the instruction manual regarding the details on this specification.
24
Characteristics
Items
Phase fault timedelayed element
Condition
Common condition
Operation
value
Earth fault
directional element
Zero-phase
current
(CDG1-A01D1)
Zero-phase
voltage
(CFP1-A01/A02D1)
Setting value 5%
Zero-phase
voltage
(CDG1-A01D1)
Setting value 5%
Common condition
Earth fault
directional element
Reset
value
Zero-phase
current
(CDG1-A01D1)
Zero-phase
voltage
(CFP1-A01/A02D1)
Zero-phase
voltage
(CDG1-A01D1)
Phase fault
instantaneous element
Earth fault
Operation
directional element
time
(CFP1-A01/A02D1)
Earth fault
Directional element
(CDG1-A01D1)
Phase fault time-delayed element
Phase fault instantaneous element
Earth fault
directional element
(CFP1-A01/A02D1)
Earth fault
Directional element
(CDG1-A01D1)
Refer to fig.1-1.2
Timing accuracy for I3Current setting value,
3.5% of reference at actual pick up
Setting value25ms
In case of INST setting 40ms or less
CFP
CDG
Zero-phase
current
(CFP1-A01/A02D1)
Reset
time
Guaranteed performance
Setting 1.02.0A for 5A rating productSetting value 10%
Setting 0.20.4A for 1A rating productSetting value 10%
For setting of other rangeSetting value 5%
Setting value 10%
200ms25ms
200ms25ms
17. Type CDG1 is applicable for earth fault directional relay in the resistance grounded neutral system.
Refer to the Fig 3-2 and Fig. 3-3 on the combination with the Overcurrent relay.
Common condition
1Rating Frequency2Ambient temperature203Auxiliary power supplyRating voltage
25
Characteristics
Items
Overshoot
characteristic
CFP
CDG
Phase
characteristic
Condition
Time-delayed operation value: Minimum
Operation time multiplier: 10
Operation characteristic: All characteristics
Input current:0ASetting value1000%
Setting: Zero phase current, voltage=minimum
Input: Zero phase current=Setting value1000%,
Zero phase voltage=Rating voltage30%
Operation time: Minimum
Input: Zero phase current=Setting value1000%
Zero phase voltage=30V
Guaranteed performance
Setting value5
17. Type CDG1 is applicable for earth fault directional relay in the resistance grounded neutral system.
Refer to the Fig 3-2 and Fig. 3-3 on the combination with the Overcurrent relay.
Common condition
1Rating Frequency2Ambient temperature203Auxiliary power supplyRating voltage
26
Inrush current Ip
Approx. 20A
Approx. 55A
Approx. 25A
Approx. 65A
3. Trip circuit
Only the dedicated contacts can be used for the circuit breaker trip
circuit. Please keep in mind that the contacts for signaling can not be
used for the trip circuit. (If used, the contact may burn). Also, connect
the pallet contact (52a) of the circuit breaker to the trip coil circuit in
series.
4. Self-diagnosis output circuit
The self-diagnosis output contact is so configured that the auxiliary
relay is energized
( break contactopened ) when normal result of
self-diagnosis is received. This type of contact will allow the relay to
output abnormal result even after the built-in power failures.
Therefore, the break contact is still closed in the aftermath of the
power applying and will be opened after 50ms. If the auxiliary power
of the relay and the self-diagnosis output contact feed from a same
power source, the break contact will be closed temporarily after
auxiliary power supply is turned on. In this case where the
phenomenon stated in the above would conflict with your system
requirement, it is recommended that the self-diagnosis output contact
should be connected via the time-delay timer.
5. Grounding circuit
Be sure to make a wiring to the earth terminal located on the back of
the relay according to the Class D earth wiring method (Grounding
resistance should be less than 100 ohm).
6. CC-Link communication circuit
Please include the communication card into your purchasing order in
case of the application of the communication facility as the card
5. The UV test function will be used for single phase test for under
voltage element. (UV test LED (yellow color) will turn on during
selecting UV TEST). UV TEST should be set as OFF in the
operational condition.
6. The function of the ZCT error correction installed in the relay is
applied for the purpose of correcting ZCT transformation error, so
that improving the composite characteristics is achieved. The ZCT
error correction range is 200mA/1.5mA4.1mA(0+2.6mA) for the
nominal transformation ratio 200mA/1.5mA specified with JEC-1201.
27
CFP
CDG
A
B
C
Auxiliary
power supply
circuit
CFP
CDG
EA
A09
IA A10
A11
CT
B05
Self diagnosis output
B06
B07
A03
CB
EVT
Y
X0
B08
B09
X1
B10
B11
For
Phase faultInstantaneous signaling
I
X2
B12
B13
IC A12
Phase faultTime-delayed
I
X3
a
f
R
K
ZCT
(200/1.5mA) L
ED+ A07
I0
A08
r
ED
+ A05
B14
B17
X4
For trip
X5
B20
ED V0 A06
Programmable output
Default setting at ex-works
Communication card
(option)
E A02
IOR
IOR I
B18
B19
B01 DA
B02 DB
Serial communication bus
B03 DG
B04 SLD
ED
A resistance is necessary for the isolated neutral system.
Fig.31CFP1A01D1CFP1A02D1
+ A01
A
B
C
Auxiliary
power supply
circuit
EA
A07
I0 A08
B05
Self diagnosis output
B06
B07
A03
CB
EVT
Y
X0
B08
B09
X1
B10
B11
For
signaling
For trip
X2
CT
B12
B13
COC3-A01D1
X3
B14
B17
X4
ED
+ A05
ED V0 A06
B18
B19
X5
B20
Programmable output
Default setting at ex-works
E A02
ED
Fig.32CDG1A01D1
28
The connection diagram shows concepts of the wiring only. Therefore, please note that there will have some difference
between the connection diagram and actual installation status of CT,VT and safety devices such as fuse, etc.
+ A01
A
B
C
Auxiliary
power supply
circuit
B05
Self diagnosis output
B06
B07
A03
X0
EA
CFP
CDG
B08
B09
CB
EVT
X1
B10
B11
For
signaling
For trip
X2
CT
B12
B13
COC3-A01D1
ED
X3
I0
ED
B14
B17
A07
A08
X4
+ A05
X5
ED V0 A06
B18
B19
B20
Programmable output
Default setting at ex-works
E A02
ED
Fig.33CDG1A01D1
The connection diagram shows concepts of the wiring only. Therefore, please note that there will have some difference
between the connection diagram and actual installation status of CT,VT and safety devices such as fuse, etc.
29
CAC1A01D2
5AAllowable continuous current: 8.7A
50Hz or 60Hz
87Tfor 2 windings transformer
2.212.5A0.1A step
Tr primary side CT matching tap IT1
2.212.5A0.1A step
Tr secondary side CT matching tap IT2
IT
LOCK203040%
Operation Current
203040%
Bias
Setting
1025%5% step
2nd harmonic blocking
IT512 times 1time step
Differential overcurrent multiplier
Refer to the external connection diagram/Auto reset for all contacts Default setting at ex-works
Output contact configuration
All LED self-hold Default setting at ex-works
Operation indicator LED hold
Restraining current, Differential current, Percentage of 2nd harmonic current content
Real time measurement
Restraining current, Differential current
Max.record
Restraining current, Differential current, Percentage of 2nd harmonic current content
Fault record (operation value)
Display
Record and indicate the operated elements.
Fault record (operation item)
Normal result:On the RUN LEDgreenStatus indication item No.400=No display.
Self-diagnosis
Abnormal result:Off the RUN LEDStatus indication item No.400=Display defects code
Forced operation
Each output contact
Direct communication port
Standard equipmentPC software for Direct communication:Option
Communication
Remote communication port
Option For CC-LINK
Phase current circuit:Less than 0.5VA/phase
Auxiliary power supply circuit:at DC100V=Approx. 7W, at AC100V=Approx. 25VA, at DC220V=Approx. 9W,
Burden (at rating)
at AC220V=Approx. 30VAIn case of installing communication card, add 2 VA.
Mass
Net weight of relay unit:Approx. 3.8kg, Including case:Approx. 5.0kg
Sample of external connection diagram
Fig.415
Remarks
Possible to make 1A rating
CAC
Characteristics
Operation
current
Reset
value
Operation
time
Reset
time
Items
Biased differential element
Differential overcurrent element
Biased differential element
Differential overcurrent element
Biased differential element
Differential overcurrent element
Biased differential element
Differential overcurrent element
Condition
Iop=ITOperation current%
Iop=ITDifferential overcurrent
Iop=ITOperation current%
Iop=ITDifferential overcurrent
0[A]Iop300%
0[A]Iop300%
Iop300%0[A]
Iop300%0[A]
Matching tapIT1 = IT2 = IT
At minimum matching tap setting I1
I2 = IT200%
I1I2
CT
Bias
Whichever is greater
Guaranteed performance
Within Iop5%
95% or more of operations current
50ms or less
40ms or less
within 20025ms
I2
CT
Tr
Phase characteristic
Operating zone
I2
Through fault side
Both lead and lag operation phase angle between I1 and I2 are shown below table.
Nominal bias ratio
20[%]
168.55
30[%]
162.75
40[%]
156.95
If1
2 IACIDC
IAC=Sine wave current
2
Percentage of 2nd harmonic current content
IAC=254330[%]setting:10%
IAC=137188[%]setting:15%
IAC=81119[%]setting:20%
IAC=4777[%]setting:25%
Please refer to the instruction manual regarding the details on this specification.
30
Inrush current Ip
Approx. 20A
Approx. 55A
Approx. 25A
Approx. 65A
3. Trip circuit
Only the dedicated contacts can be used for the circuit breaker trip
circuit. Please keep in mind that the contacts for signaling can not be
used for the trip circuit. (If used, the contact may burn). Also, connect
the pallet contact (52a) of the circuit breaker to the trip coil circuit in
series.
4. Self-diagnosis output circuit
The self-diagnosis output contact is so configured that the auxiliary
relay is energized
( break contact opened) when normal result of
self-diagnosis is received. This type of contact will allow the relay to
output abnormal result even after the built-in power failures.
Therefore, the break contact is still closed in the aftermath of the
power applying and will be opened after 50ms. If the auxiliary power
of the relay and the self-diagnosis output contact feed from a same
power source, the break contact will be closed temporarily after
auxiliary power supply is turned on. In this case where the
phenomenon stated in the above would conflict with your system
requirement, it is recommended that the self-diagnosis output contact
should be connected via the time-delay timer.
5. Grounding circuit
Be sure to make a wiring to the earth terminal located on the back of
the relay according to the Class D earth wiring method (Grounding
resistance should be less than 100 ohm).
6. CC-Link communication circuit
Please include the communication card into your purchasing order in
case of the application of the communication facility as the card
31
CAC
Auxiliary
power supply
circuit
k
A17
IA
IB
IC
A18
A19
A20
A21
A22
Transformer
Dd0
L
Biased differential
Differential overcurrent A phase
B08
B09
Biased differential
Differential overcurrent B phase
X1
B10
B11
For
signaling
Biased differential
Differential overcurrent C phase
X2
B12
B13
X3
B14
B17
2f blocking
A,B,C phase
X4
A12
Biased differential
Differential overcurrent
A phase OR B phase OR For trip
C phase
B18
B19
A11
IA
X0
ED
CT2
B05
B06
B07
A03
CT1
CAC
A01
X5
B20
A13
IB
A14
A15
IC
k
A16
E A02
ED
Communication card
(option)
A
IA
Programmable output
Default setting at ex-works
B01 DA
B02 DB
Serial communication bus
B03 DG
B04 SLD
ED
Fig.41CAC1A01D2TransformerDd0
B C
IB IC
+
Auxiliary
power supply
circuit
k
A17
IAIC
IBIA
ICIB
A18
A19
A20
CT1
A21
A22
Transformer
Y
Yd1
CT2
Biased differential
Differential overcurrent A phase
B08
B09
Biased differential
Differential overcurrent B phase
X1
B10
B11
Biased differential
Differential overcurrent C phase
X2
B12
B13
X3
B14
B17
B18
B19
A11
A12
X5
A14
A15
ICIB
k
A16
E A02
ED
Biased differential
Differential overcurrent For trip
A phase OR B phase OR
C phase
B20
A13
IBIA
For
signaling
2f blocking
A,B,C phase
X4
IAIC
X0
ED
r
B05
B06
B07
A03
A01
Communication card
(option)
A
IA
Programmable output
Default setting at ex-works
B01 DA
B02 DB
B03 DG
B04 SLD
ED
Fig.42CAC1A01D2Transformer YYd1
32
The connection diagram shows concepts of the wiring only. Therefore, please note that there will have some difference
between the connection diagram and actual installation status of CT,VT and safety devices such as fuse, etc.
A
IA
B C
IB IC
Auxiliary
power supply
circuit
k
K
L
A01
Y
B10
B11
For
Biased differential
signaling
Differential overcurrent C phase
X2
A21
B12
B13
A22
B14
B17
X4
Biased differential
Differential overcurrent
For trip
A phase OR B phase OR
C phase
B18
B19
A11
IAIB
X5
A12
B20
A14
A15
ICIA
k
A16
E A02
ED
Communication card
(option)
A13
IBIC
CAC
2f blocking
A,B,C phase
X3
ED
Biased differential
Differential overcurrent B phase
X1
A19
A20
CT2
Biased differential
Differential overcurrent A phase
B08
B09
A18
CT1
X0
A17
B05
B06
B07
A03
IAIB
IBIC
ICIA
Transformer
Y
Yd11
L
Programmable output
Default setting at ex-works
B01 DA
B02 DB
Serial communication bus
B03 DG
B04 SLD
ED
Fig.43CAC1A01D2Transformer YYd11
C
Auxiliary
power supply
circuit
k
K
L
A01
Y
A17
A18
A19
CT1
A20
r
A21
A22
Transformer
Y
Dy1
A03
IAIB
IBIC
ICIA
B05
Biased differential
Differential overcurrent A phase
X0
B08
B09
Biased differential
Differential overcurrent B phase
X1
B10
B11
Biased differential
Differential overcurrent C phase
X2
B12
B13
X3
B14
B17
ED
2f blocking
A,B,C phase
X4
r
CT2
A11
A12
A14
IBIC
A15
IB
IC
X5
A16
ICIA
k
E A02
ED
Biased differential
Differential overcurrent For trip
A phase OR B phase OR
C phase
B20
A13
IAIB
IA
B18
B19
Communication card
(option)
For
signaling
Programmable output
Default setting at ex-works
B01 DA
B02 DB
B03 DG
B04 SLD
ED
Fig.44CAC1A01D2TransformerYDy1
The connection diagram shows concepts of the wiring only. Therefore, please note that there will have some difference
between the connection diagram and actual installation status of CT,VT and safety devices such as fuse, etc.
33
+
Auxiliary
power supply
circuit
k
K
L
CAC
A01
Y
A17
IAIC
IBIA
ICIB
A18
A19
CT1
A20
r
A21
A22
Transformer
Y
Dy11
L
CT2
K
X0
B08
B09
Biased differential
Differential overcurrent B phase
X1
B10
B11
For
signaling
Biased differential
Differential overcurrent C phase
X2
B12
B13
X3
B14
B17
ED
2f blocking
A,B,C phase
X4
r
IAIC
A11
IBIA
A12
ICIB
A13
A14
A15
IA
B05
B06
B07
A03
IB
A16
IC
E A02
ED
B18
B19
X5
Biased differential
Differential overcurrent
For trip
A phase OR B phase OR
C phase
B20
Communication card
(option)
Programmable output
Default setting at ex-works
B01 DA
B02 DB
B03 DG
B04 SLD
ED
Fig.45CAC1A01D2TransformerYDy11
34
The connection diagram shows concepts of the wiring only. Therefore, please note that there will have some difference
between the connection diagram and actual installation status of CT,VT and safety devices such as fuse, etc.
Rating
Type name
Phase current
Zero-phase current
Zero-phase voltage
CMP1A01D2
5A
2A
100208V
DC110V (Permissible variable range 77143V) or
DC24V(Permissible variable range DC19.2V31.2V)
Input voltage 24V is applicable only for the case that auxiliary
CMP1A01D1
Frequency
Protective element
Combined
Zero-phase current
instrument
Zero-phase voltage
transformer
Motor rated currentIM
Operation current
Overcurrent
instantaneous Operation time
Operation current
Operation timeKoct
Overcurrent
time-delayed Operation time
characteristics
equation
Negative
Operation current
sequence
overcurrent Operation time
Operation current
Operation timeKTH
Koct
Toct3s
I
The selected Koct valve is equal to the operating time of time-delayed element in case of I3.
LOCKIM0.58 times
0.5 times step
0.110s
0.1s step
LOCKIM105125%
5% step
812162024324048648096112128160200240
Operation time characteristics for HOT
IP12KIP22
I12KI22
TTH8.49KTHloges
I12KI22
1
Overload
CMP
Operation time
characteristics
equation
Setting
Operation time for COLD characteristics, in the above equation, becomes equal to case conditioned as follows :IP12KIP22
0
Selected value of KTH, when input is provided so as to meet the conditions of I12KI2232 and IP12KIP220,
becomes equal to the time (sec) that will be taken until operation.
Negative-sequence heat
multiplying factorK
110
1 step
Changeover characteristic
Operation current
Operation time
Number of start-up
Limit the
number of
Start-up time
start-up times Countdown rate
Io Operation current
Earth fault Vo Operation voltage
directional Operation time
Maximum sensitive angle
Output contact configuration
Operation indicator LED hold
0
COLD
1
HOT
LOCK1.04.0A
0.1A step
1600s
1s step
LOCK15
1 step
2120s
1s step
2250s/h
0.5s/h step
110mA
ZCT secondary current
0.5mA step
LOCK560V
1V step
INST0.110s
0.1s step
Lead 0
90
5
step
Refer to the external connection diagram/Auto reset for all contacts
Default setting at ex-works
All LED self-hold
Default setting at ex-works
15101212.5152025304050607580100120125150200250300400500600750800100012001250
CT primaryPhase current
150020002500300040005000600075008000[A]Applicable only 1 A
Undercurrent
100999V
1V step
,10009990V
10V step
,
10.0k99.9kV
0.1kV step
,100k300kV
1kV step
EVT tertiary
1001101151201003110311531203V
ZCT error correction on/off
OFFON
When the actual measured transforming ratio is within range of 200/1.54.1mA,
ZCT error adjustment
the deviation from the ZCT nominal transforming ratio 200/1.5mA can be corrected.
Real time measurement
Phase current, Zero-phase current, Zero-phase voltage, Characteristic angle, Negative sequence current
Max.record
Phase current, Zero-phase current, Zero-phase voltage
Fault recordoperation value
Phase current, Zero-phase current, Zero-phase voltage, Characteristic angle, Negative sequence current
Fault recordoperation item
Record and indicate the operated elements.
Normal result:On the RUN LED
green
Status indication item No.400=No display.
Self-diagnosis
Abnormal result:Off the RUN LEDStatus indication item No.400=Display defects code
Forced operation
Each output contact
Direct communication port
Standard equipment
PC software for Direct communication:Option
Communication
Remote communication port
Option
For CC-LINK
Phase current circuitLess than 0.5VA, Zero-phase current circuitLess than 10, Zero-phase voltage circuitLess than 0.15VA
Auxiliary power supply circuitat DC100V=Approx. 4W, at AC100V=Approx. 8VA, at DC220V=Approx. 5W,
Burden (at rating)
at AC220V=Approx. 15VA
In case of installing communication card, add 2 VA.
Net weight of relay unit:Approx. 2.1kg
D1 type
, Including case:Approx. 2.8kg
D1 type
,
Mass
Net weight of relay unitApprox. 3.1kg
D2 type
, Including case:Approx. 4.3kg
D2 type
Display
EVT primary
Fig.51,2
The rated current 1A product can be made based on the 5A rating product. The setting value of current elements
on 1A product is calculated by performing a multiplication 1/5 of above mentioned value. The DI input facility is
available for CMP1-A01D2, CMP1-A02D2 and not available for type CMP1-A01D1 and CMP2-A01D1.
Please refer to the instruction manual regarding the details on this specification.
35
Rating
Type name
Phase current
Zero-phase current
CMP2A02D2
5A
5A
DC110V (Permissible variable range 77143V) or
DC24V(Permissible variable range DC19.2V31.2V)
Input voltage 24V is applicable only for the case that auxiliary
CMP1A02D1
Frequency
Protective element
Motor rated currentIM
Overcurrent Operation current
instantaneous Operation time
Operation current
Operation timeKoct
CMP
Overcurrent
time-delayed Operation time
characteristics
(1)
equation
Setting
Overcurrent
time-delayed
(2)
Negative
sequence
overcurrent
Operation current
Operation time
Operation current
Operation time
Operation current
Operation timeKTH
Koct
Toct3s
I
The selected Koct valve is equal to the operating time of time-delayed element in case of I3.
LOCKIM115450%
5% step
0.55.0s
0.5s step
LOCKIM0.58 times
0.5 times step
0.110s
0.1s step
LOCKIM105125%
5% step
812162024324048648096112128160200240
IP12KIP22
I12KI22
TTH8.49KTHloges
I12KI22
1
Overload
Operation time
characteristics
equation
Operation time for COLD characteristics, in the above equation, becomes equal to case conditioned asIP12KIP220
Selected value of KTH, when input is provided so as to meet the conditions of I12KI2232 and IP12KIP220,
becomes equal to the time (sec) that will be taken until operation.
Negative-sequence heat
multiplying factorK
110
1 step
Changeover characteristic
Operation current
Undercurrent
Operation time
Number of start-up
Limit the
number of
Start-up time
start-up times Countdown rate
Earth fault Operation current
overcurrent Operation time
Output contact configuration
Operation indicator LED hold
Display
0
COLD
1
HOT
LOCK1.04.0A
0.1A step
1600s
1s step
LOCK15
1 step
2120s
1s step
2250s/h
0.5s/h step
LOCK0.052.50A
0.05A step
INST0.110s0.1s step
Refer to the external connection diagram/Auto reset for all contacts
Default setting at ex-works
All LED self-hold
Default setting at ex-works
1#5101212.5152025304050607580100120125150200250300400500600750800100012001250
CT primaryPhase current
150020002500300040005000600075008000[A]#Applicable only 1 A product
CT primaryZero-phase current
Real time measurement
Max.record
Fault recordoperation value
Fault recordoperation item
Self-diagnosis
Forced operation
Direct communication port
Communication
Remote communication port
Burden (at rating)
Mass
Sample of external connection diagram
Remarks
Please refer to the instruction manual regarding the details on this specification.
36
Fig.54
The rated current 1A product can be made based on the 5A rating product. The setting value of current elements
on 1A product is calculated by performing a multiplication 1/5 of above mentioned value. The DI input facility is
available for CMP1-A01D2, CMP2-A02D2 and not available for type CMP1-A01D1 and CMP1-A02D1.
Characteristics
Earth fault
directional element
CMP1-A01
Condition
Items
Overload element
Positive sequence current
Overcurrent time-delayed element (1)
Overcurrent time-delayed element (2)
Common condition1
Overcurrent instantaneous element
Under current element
Negative sequence overcurrent element Negative sequence current
Setting: Zero phase voltage=minimum
Operation
Zero-phase
value
Input: Zero phase voltage=Rating voltage30%,
current
Phase=Maximum sensitive angle
Setting: Zero phase current=minimum
Zero-phase
Input: Zero phase current=Setting value1000%,
voltage
Phase=Maximum sensitive angle
Guaranteed performance
Setting value 5%
Reset
value
Earth fault
directional element
CMP1-A01
Overload element
Overcurrent time-delayed element (1)
Overcurrent time-delayed element (2) Common condition1
Overcurrent instantaneous element
Negative sequence overcurrent element
Zero-phase
current
Zero-phase
voltage
Earth fault
directional element
CMP1-A01
Overload element
Operation
time
Negative sequence
overcurrent element
Earth fault
directional element
CMP1-A01
Earth fault
overcurrent element
CMP1A02
Setting: minimum
Overcurrent
instantaneous element Input:0setting value200%
Under current element
CMP
Setting: maximum
Input:Setting value300%IM12%
Setting: minimum
Input:Negative sequence current=0Setting value200%
Setting: Zero phase current=minimum
Input: Zero phase current=0Setting value1000%
Zero phase voltage=0Rating voltage30%
Phase=Maximum sensitive angle
Setting: minimum
Input: Zero phase current=0Setting value200%
1Common condition
1Rating Frequency2Ambient temperature203Auxiliary power supply: Rating voltage
37
Items
Overload element
Condition
SettingOperation time settingKTH=8
Input: Positive sequence current=Setting value300%0A
CMP
38
Guaranteed performance
HOT characteristic300% input is applied for 5
minutes or more and then input is turned to zero.
149.2s15%
COLD characteristic: 20025ms
20025ms
1s5%
10%
0%
14.4s
Inrush current Ip
Approx. 20A
Approx. 55A
Approx. 25A
Approx. 65A
3. Trip circuit
Only the dedicated contacts can be used for the circuit breaker trip
circuit. Please keep in mind that the contacts for signaling can not be
used for the trip circuit. (If used, the contact may burn). Also, connect
the pallet contact (52a) of the circuit breaker to the trip coil circuit in
series.
4. Self-diagnosis output circuit
The self-diagnosis output contact is so configured that the auxiliary
relay is energized
( break contact opened) when normal result of
self-diagnosis is received. This type of contact will allow the relay to
output abnormal result even after the built-in power failures.
Therefore, the break contact is still closed in the aftermath of the
power applying and will be opened after 50ms. If the auxiliary power
of the relay and the self-diagnosis output contact feed from a same
power source, the break contact will be closed temporarily after
auxiliary power supply is turned on. In this case where the
phenomenon stated in the above would conflict with your system
requirement, it is recommended that the self-diagnosis output contact
should be connected via the time-delay timer.
5. Grounding circuit
Be sure to make a wiring to the earth terminal located on the back of
the relay according to the Class D earth wiring method (Grounding
resistance should be less than 100 ohm).
6. CC-Link communication circuit
39
CMP
A
B
C
Auxiliary
power supply
circuit
EA
f
R 1
B08
B09
IA A10
X1
A11
X2
K
ZCT
200/1.5mA
L
Negative sequence
For
overcurrent element
signaling
INSC
Earth fault directional element
I
B12
B13
X3
B14
B15
+ A07
X4
A08
r
ED
Overload element
B10
B11
IC A12
k ED
I0
Overcurrent
under current element
I
II
X0
A09
CT
A03
CB
EVT
CMP
B05
B16
B17
IOR IOR
X5
+ A05
ED V0 A06
IOR OR
For trip
B18
B19
INSCOR I
B20
B01 DA
Programmable output
Default setting at ex-works
Communication card
(option)
X6
M
E A02
B02 DB
B03 DG
B04 SLD
ED
1 A resistance is necessary for the isolated neutral system.
Fig.51CMP1A01D1
A
B
C
Auxiliary
power supply
circuit
EA
R 1
ED
A21
X2
ED
X3
B14
B15
X4
ED V0 A16
B16
B17
B18
B19
X6
B20
DI input1E03
+ E02
M
2
DC110V
DI input2E04
E A02
Communication card
(option)
DC110V
X5
+ E01
2
Negative sequence
For
overcurrent element signaling
INSC
Earth fault directional element
I
B12
B13
+ A17
+ A15
Overload element
B10
B11
A18
r
Overcurrent
under current element
I
II
B08
B09
X1
I0
ZCT
200/1.5mA
L
X0
IA A20
IC A22
B05
B06
B07
A19
CT
A03
CB
EVT
+ A01
IOR OR
For trip
INSCOR I
OR DI1OR DI2
Programmable output
Default setting at ex-works
B01 DA
B02 DB
B03 DG
Serial
communication bus
B04 SLD
ED
Fig.52CMP1A01D2
40
The connection diagram shows concepts of the wiring only. Therefore, please note that there will have some difference
between the connection diagram and actual installation status of CT,VT and safety devices such as fuse, etc.
A
B
C
Auxiliary
power supply
circuit
+ A01
B05
A03
B08
B09
A07
CB
IA A08
X1
A09
X2
Overload element
B10
B11
B12
B13
IB A10
X3
B14
B15
A11
CT
Overcurrent
under current element
I
II
X0
B16
B17
X5
+ A05
I0
A06
CMP
X4
IC A12
IOR
OR
For trip
B18
B19
INSCOR I
B20
B01 DA
Programmable output
Default setting at ex-works
Communication card
(option)
X6
ED
M
E A02
B02 DB
B03 DG
B04 SLD
ED
Fig.53CMP1A02D1
A
B
C
Auxiliary
power supply
circuit
+ A01
A03
X0
B08
B09
A17
IA A18
X1
A19
X2
B10
B11
B12
B13
IB A20
X3
B14
B15
A21
CT
X4
IC A22
+ A15
X5
A16
X6
I0
ED
DC110V
DI input1E03
+ E02
DI input2E04
E A02
1 In case of auxiliary power supply voltage 24V,
input voltage E-01, 03 and E-02, 04 should be DC 24V.
Overcurrent
under current element
I
II
Overload element
Negative sequence overcurrent element For
signaling
INSC
Earth fault overcurrent element
I
Limit of the number
of start-up times element
ts
B16
B17
IOR IOR
B18
B19
INSCOR I
B20
Communication card
(option)
+ E01
P
CB
B05
B01 DA
IOR
OR
For trip
OR DI1OR DI2
Programmable output
Default setting at ex-works
B02 DB
B03 DG
B04 SLD
ED
Fig.54CMP2A02D2
The connection diagram shows concepts of the wiring only. Therefore, please note that there will have some difference
between the connection diagram and actual installation status of CT,VT and safety devices such as fuse, etc.
41
Frequency
Protective element
Combined instrument transformer Zero-phase voltage
CPP1A11D2
5A
57120V
100208V
DC110VPermissible variable range 77143Vor DC24VPermissible variable range DC19.2V31.2V
Input voltage 24V is applicable only for the case that auxiliary power supply voltage is 24V.
In any other cases, only DC110V is applicable as for photo coupler input voltage.
50Hz or 60Hz
64,59,27,67S,95L,95H,67P,91L,df/dt Applicable only for A11
Commercially available EVTConformity with JEC-1201
CPP1A01D2
LOCK560V1V step
Earth fault Operation voltage
over voltage
0.050.115s 0.1s step
Operation time
LOCK110150V1V step
Operation voltage
Over
voltage Operation time
0.050.115s 0.1s step
LOCK20110V1V step
Operation voltage
Under
voltage Operation time
0.050.115s 0.1s step
LOCKRated current5A
120%1% step
L element operation value
0.050.115s 0.1s step
L element operation time
Phase fault
LOCKRated current5A
20100%1% step
directional H element operation value
0.050.115s 0.1s step
H element operation time
NO USE20100V1V step
UV element for DS operation value
Operation value
Rated frequency:50HzLOCK49.545Hz0.1Hz step,Rated frequency:60HzLOCK59.555Hz0.1Hz step
Under
frequency Operation time
0.050.115s 0.1s step
LOCKRated current5A
0.230%0.21%:0.1% step,130%:1% step
Reverse Operation value
power
Operation time
0.050.115s 0.1s step
Operation value
Rated frequency:50HzLOCK50.555Hz0.1Hz step,Rated frequency:60HzLOCK60.565Hz0.1Hz step
Over
Setting frequency Operation time
0.050.115s 0.1s step
Operation value
LOCKRated current5A
130%1% step
Under
Operation time
0.050.115s 0.1s step
power
Open circuit detecting function lock
OFFONSet ON in case of open circuit detecting function lock
Lock at uninterconnected condition
010s 0.1s step
LOCK0.0252Hz/s
Islanding Operation value
detection
0.025Hz/s step
df/dt Operation time
0.21s 0.1s step
CPP
Fig.61
The island detection facility is available for CPP1-A11D2 and not available for type CPP1-A01D2
Please refer to the instruction manual regarding the details on this specification.
42
Characteristics
Items
Earth fault over
voltage element
Over voltage element
Under voltage element
Phase fault directional element
L,H element
Operation
value
Condition
Common condition1
Reverse power
element
Islanding detection
element
CPP1-A11D2
Earth fault over
voltage element
Over voltage element
Under voltage element
Phase fault directional element
L,H element
Reverse power
element
Over frequency
element
Under frequency
element
Reverse power
element
Over frequency
element
Under power
element
Setting value 5%
[Value for full operation]
Setting value: 0.0125Hz/s
CPP
Under frequency
element
Under power
element
Operation
time
Setting value 5%
Under power
element
Reset value
Guaranteed performance
1Common condition
1Rating Frequency2Ambient temperature203Auxiliary power supply: Rating voltage
43
Items
Operation
time
Islanding detection
element
CPP1-A11D2
CPP
Reset time
Under frequency
element
Reverse power
element
Over frequency
element
Under-power
element
Condition
Operation setting value: Minimum
Input voltage: Rated voltage
Frequency:Rated frequency
Rated frequency+setting value
500%
Change abruptly at the same phase.
DI input voltage: Rated voltage0
Measuring the time between contact open statusclose status.
Operation setting value: Minimum
Input: Operation setting value150%0
Operation setting value: Minimum
Input: Operation setting value120%0
Operation setting value: 100V
Input: operation setting value70%rated voltage
Operation setting value: minimum, UV setting for DS: NO USE
Input voltage: Rated voltage
Input current: setting value200%0
Phase of current: Maximum sensitive angle
Operation setting value: Minimum
Input voltage: Rated voltage
Frequency: setting value+1Hz
Rated frequency with moving up rate df/dt=5Hz/s
Operation setting value: Minimum
Input voltage: Rated voltage
Input current: setting value200%0
Phase of current: Maximum sensitive angle
Operation setting value: Minimum
Input voltage: Rated voltage
Frequency: setting value1Hz
Rated frequency with moving down rate df/dt=5Hz/s
Operation setting value: Maximum
Input voltage: Rated voltage
Input current: 0setting value300%
Phase of current: Maximum sensitive angle
Guaranteed performance
200ms20ms
Islanding detection
Output contact
element
Common condition1
latching time
CPP1-A11D2
55
5
Phase fault
directional element
L,H element
305
5
Operation side
35
Reverse power
Phase
characteristic element
Operation side
Under power
element
Operation side
1Common condition
1Rating Frequency2Ambient temperature203Auxiliary power supply: Rating voltage
44
Inrush current Ip
Approx. 20A
Approx. 55A
Approx. 25A
Approx. 65A
3. Trip circuit
Only the dedicated contacts can be used for the circuit breaker trip
circuit. Please keep in mind that the contacts for signaling can not be
used for the trip circuit. (If used, the contact may burn). Also, connect
the pallet contact (52a) of the circuit breaker to the trip coil circuit in
series.
4. Self-diagnosis output circuit
The self-diagnosis output contact is so configured that the auxiliary
relay is energized
( break contactopened ) when normal result of
self-diagnosis is received. This type of contact will allow the relay to
output abnormal result even after the built-in power failures.
Therefore, the break contact is still closed in the aftermath of the
power applying and will be opened after 50ms. If the auxiliary power
of the relay and the self-diagnosis output contact feed from a same
power source, the break contact will be closed temporarily after
auxiliary power supply is turned on. In this case where the
for under voltage element. (UV test LED will turn on during selecting
UV TEST). UV TEST should be set as OFF in the operational
condition.
6. The DS test function (item No. 546) will be used for single phase test
for the phase fault directional element. (DS test LED will turn on
during selecting DS TEST). DS TEST should be set as OFF in the
operational condition.
7. The 67P and 91L elements detect 3 phases active power(3EIcos).
100% of 3 phases power equal to that when nominal voltage (110V)
and nominal current (5A) are impressed.
45
CPP
+ A01
Auxiliary
power supply
circuit
B05
Y
A03
B07
A18
52R
X0
IA A17
A20
B08
B09
X1
A22
B10
IB A19
CT
B11
X2
B12
IC A21
B13
X3
ED
B14
CPP
C07
X4
EA
C08
EVT
A13
VAB
VBC
Tr
C09
X5
C10
A14
A15
C11
X6
C12
ED
C13
X7
Under-power element
P
C14
a
C15
R 3
ED
+
Un-interconnected
condition
4
DC110V
+ A11
X8
A12
V0
C16
X9
X8
2
Xa
X9
+ E01
52Rb52Gb etc
E03
Xb
Xa
2
Xc
Xb
52G
B17
B18
B19
Under-power element
P
B20
1
C17
C18
For trip
UOR UOR I
OR fOR POR f
OR df/dt
C19
C20
Programmable output
Default setting at ex-works
Communication card
(option)
Consumer-owned
dispersed generator
B01 DA
B02 DB
B03 DG
A02
B04 SLD
ED
1
2
3
4
Fig.61CPP1A01D2, CPP1A11D2
46
The connection diagram shows concepts of the wiring only. Therefore, please note that there will have some difference
between the connection diagram and actual installation status of CT,VT and safety devices such as fuse, etc.
CGP1A03D2
CGP1A01D2
5A
57120V
100208V
DC110V
Permissible variable range 77143Vor DC24V
Permissible variable range DC19.2V31.2V
Input voltage 24V is applicable only for the case that auxiliary power supply voltage is 24V.
Photo coupler input voltage
In any other cases, only DC110V is applicable as for photo coupler input voltage.
50Hz or 60Hz
Frequency
Protective element
51,50,462,84,59,27,95L,95H,67P,51G
51,50,462,84,59,27,95L,95H,67P,67G,64
Combined instrument Zero phase current Commercially available ZCTConformity with JEC-1201 200/1.5mA
transformer
Zero-phase voltage Commercially available EVT
Conformity with JEC-1201
2.55A
IG Generator rating current
0.1A step
Operation current
LOCKIG100120%1% step
Operation time multiplier
0.250.5100.5 step
Rating
Overcurrent
time-delayed
Operation time
characteristics
Operation current
Overcurrent
instantaneous Operation time
Operation current
Operation time multiplier
Unbalance
current 1
Operation time
characteristics
Unbalance Operation current
current 2
Operation time
Operation
Voltage
detecting Operation time
Operation
Over
voltage
Operation time
Operation
Under
voltage
Operation time
Operation
Under
frequency Operation time
Operation
Over
Setting frequency Operation time
Operation
Reverse
power
Operation time
Operation currentI0
Earth fault OperationV0
directional Operation time
Maximum sensitive angle
Operation
Earth fault
over voltage Operation time
Operation
Earth fault
overcurrent Operation time
Output contact configuration
Operation indicator LED hold
CT primary
VT primary
VT secondary
EVT primary
EVT tertiary
ZCT error correction on/off
ZCT error adjustment
Real time measurement
Max.record
Fault record (operation value)
Display
Fault record (operation item)
Self-diagnosis
Forced operation
Direct communication port
Communication
Remote communication port
Mass
Sample of external connection diagram
0.14
M
NI
t
s tOperation time
s
Normal inverse time-delayed
I0.021
10
IMultiple of input current against setting
150
M
EI
t
s
Extremely inverse time-delayed
I21
10
value
IG100%120%
M
DT
MOperation time multiplier
times
t2
s
Definite time-delayed
10
LOCKIG100%1200%50% step
INST0.10.5s0.1s step
LOCKIG5%30%
1% step
10501 step
M
t
s
I22
tOperation time
s
I2Multiple of input negative sequence current against IG
MOperation time multiplier
times
LOCKIG5%30%
1% step
110s
0.1s step
LOCK80110V
1V step
0.510s
0.1s step
LOCK110155V
1V step
0.110s
0.1s step
LOCK20110V
1V step
0.110s
0.1s step
Rating50Hz
LOCK49.5Hz45Hz
0.1Hz step
,Rating60Hz
LOCK59.555Hz
0.1Hz
0.110s
0.1s step
Rating50Hz
LOCK50.5Hz55Hz
0.1Hz step
,Rating60Hz
LOCK60.565Hz
0.1Hz
0.110s
0.1s step
LOCKIG0.5130%
1% step
0.120s
0.1s step
10mA
ZCT secondary
0.5mA step
LOCK560V
1V step
INST0.110s
0.1s step
Lead 0
90
5 step
LOCK560V
1V step
0.120s0.1s step
LOCK0.12.0A0.1A step
INST0.10.5s0.1s step
CGP1
10.0k99.9kV
1kV step
,100k300kV
1kV step
10011011512010031103
11531203V
OFFON
When the actual measured transforming ratio is within
Please refer to the instruction manual regarding the details on this specification.
# Not applicable for CGP1-A03D2
47
Characteristics
Operation
value
CGP1
Reset value
Operation
time
Condition
Guaranteed performance
Items
Setting value 5%
Overcurrent time-delayed element
Common condition
1
Setting value 10%
Overcurrent instantaneous element
Unbalance current element 1
Negative sequence current
Unbalance current element 2
Setting value 5%
Voltage detecting element
1
Over voltage element Common condition
Under voltage element
Under frequency element Input voltage: Rated voltage
Setting value 0.05Hz
Over frequency element Input voltage: Rated voltage
0.5, 13% setting: Setting value5mA
Input voltage: Rated voltage
Reverse power
For another setting: setting value 5%
Phase of current: Maximum sensitive angle
element
Setting: Zero phase voltage: minimum
1.0 and 1.5mA setting: setting value10%
Zero phase
Input: Zero phase voltage=rated voltage30%
current
For another setting: setting value 5%
Earth fault
Phase: maximum sensitive angle
directional element
Setting: Zero phase current: minimum
CGP1A01D2
Zero phase
Input: Zero phase current=setting value1000% Setting value 5%
voltage
Phase: maximum sensitive angle
Earth fault overcurrent
Setting value 5%
Common condition
1
CGP1A03D2
Earth fault over voltage element
Setting value 5%
Common condition
1
CGP1A01D2
Overcurrent time-delayed element
Common condition
1
Overcurrent instantaneous element
Unbalance current element 1
Setting value95% or more
Negative sequence current
Unbalance current element 2
Voltage detecting element
Over voltage element Common condition
1
Setting value105% or less
Under voltage element
Difference between operation value and reset value is
Under frequency element Input voltage: Rated voltage
0.05Hz or less
Over frequency element Input voltage: Rated voltage
0.5, 13% setting: operation value80% or more
Reverse power
Input voltage: Rated voltage
For another setting: setting value95% or more
element
Phase of current: Maximum sensitive angle
Setting: Zero phase voltage: minimum
Zero phase
Input: Zero phase voltage=rated voltage30%
current
Earth fault
Phase: maximum sensitive angle
Operation value90% or more
directional element
Setting: Zero phase current: minimum
Zero phase
CGP1A01D2
Input:
Zero
phase
current=setting
value1000%
voltage
Phase: maximum sensitive angle
Earth fault overcurrent
Setting value95% or more
Common condition
1
CGP1A03D2
Earth fault over voltage element
Setting value95% or more
Common condition
1
CGP1A01D2
NI,EI Input: 300%: nominal value12% or less
Operation setting value: minimum
Input: 500%: nominal value12% or less
Operation time multiplier: 10
Input: 1000%: nominal value7% or less
Input: 0setting value300.500.1000%
0.14
M
DT Nominal value5% or less
NINormal inverse time delayed
t
s
Overcurrent
characteristics
I0.021
10
time-delayed
M
150
EIExtremely inverse
t
s
element
time-delayed characteristic
10
I21
M
DTDefinite time-delayed
t2
s
characteristic
10
t: operation time(s)
I: Multiple of input current against operation value
(Ig100120%)
M: Operation time multiplier
times
Unbalance current
element 1
t: operation time(s)
I2: Multiple of input negative sequence
M
t
s
current against Ig
I22
M: Operation time multiplier
times
Setting: minimum
Input: negative sequence current=0setting value200%
Voltage detecting element Operation setting value: minimum
Over voltage element Input: 0operation setting value120%
Operation setting value: 100V
Under voltage
element
Input: rated voltageoperation setting value70%
Unbalance current
element 2
1Common condition
1Rating Frequency2Ambient temperature203Auxiliary power supply: Rating voltage
48
Items
Under frequency
element
Over frequency
element
Operation
time
Reverse power
element
Earth fault
directional element
CGP1A01D2
Earth fault overcurrent element
CGP1A03D2
Earth fault over voltage element
CGP1A01D2
Overcurrent time-delayed element
Overcurrent instantaneous element
Unbalance current element 1
Unbalance current element 2
Voltage detecting element
Over voltage element
Under voltage
element
Under frequency
element
Reset time
Over frequency
element
Reverse power
element
Earth fault
directional element
CGP1A01D2
Earth fault overcurrent element
CGP1A03D2
Earth fault over voltage element
CGP1A01D2
Condition
Guaranteed performance
CGP1
200ms25ms
49
CGP1
50
+ A01
Auxiliary
power supply
circuit
B05
Y
A03
EA
B07
EVT
X0
B08
B09
X1
CB
B10
B11
a
X2
R 1
67G
trip
direction K
ZCT
(200/1.5mA) L
B12
+ A09
ED
B13
V0 A10
X3
+ A15
X4
B15
IA 3
X6
C11
X7
A22
VAB
C13
X8
ED
C14
A12
C15
VBC
C12
A11
VT
CGP1
C10
A21
IC 3
67P
protection
direction
C09
A18
C08
A17
CT
K
C07
X5
ED
ED
B16
A16
B14
I0
r
ZCT
X9
A13
C16
C17
Xa
C18
B17
Xb
+
DC110V
DI1
B19
Xc
E03
B20
Generator
Communication card
(option)
B18
+ E01
For trip
fOR fOR P
Programmable output
Default setting at ex-works
B01 DA
B02 DB
B03 DG
A02
B04 SLD
ED
1 A resistance is necessary for the isolated neutral system.
2 The application voltage for terminal E-01, E-03 and terminal E-02, E-04 is 24V in case that the supplied auxiliary power voltage is 24V.
3
Indicates the direction of current flowing into the generator side during generator failure occurrence.
Indicates the direction of current being output from the generator side when the system is healthy.
Fig.71CGP1A01D2
The connection diagram shows concepts of the wiring only. Therefore, please note that there will have some difference
between the connection diagram and actual installation status of CT,VT and safety devices such as fuse, etc.
51
+ A01
Auxiliary
power supply
circuit
B05
Y
A03
X0
B08
B09
X1
CB
B10
A17
IA 2
B11
A18
X2
B12
A19
ED
B13
IB 2
67P
trip
direction
X3
A20
B14
A21
CT
IC 2
B15
X4
B16
A22
C07
+ A15
CGP1
X5
I0
C08
A16
C09
X6
C10
C11
X7
A11
VT
VAB
VBC
ED
C12
C13
A12
X8
C14
A13
C15
X9
C16
C17
Xa
+ E01
+
DC110V
DI1
B17
E03
Xb
IOR IOR I
I OR INSC
OR NSC
B18
OR
B19
Xc
E04
B20
UOR UOR
For trip
fOR fOR P
Programmable output
Default setting at ex-works
Generator
Communication card
(option)
C18
+ E02
DI2
B01 DA
B02 DB
B03 DG
A02
B04 SLD
ED
1 The application voltage for terminal E-01, E-03 and terminal E-02, E-04 is 24V in case that the supplied auxiliary power voltage is 24V.
2
Indicates the direction of current flowing into the generator side during generator failure occurrence.
Indicates the direction of current being output from the generator side when the system is healthy.
Fig.72CGP1A03D2
52
The connection diagram shows concepts of the wiring only. Therefore, please note that there will have some difference
between the connection diagram and actual installation status of CT,VT and safety devices such as fuse, etc.
CGP2A01D2
Please refer to the instruction manual regarding the details on this specification.
53
CGP2
Characteristics
Items
Biased differential
characteristic
Minimum operation
Operation current
value
Loss of excitation element
ZF operation value
Loss of excitation element
ZB operation value
Loss of excitation element
ZF reset value
Loss of excitation element
Reset value ZB reset value
Biased differential
characteristic
Reset value
Biased differential
characteristic
Operation
time
Loss of excitation
element
Biased differential
characteristic
Reset time
CGP2
Loss of excitation
element
Biased differential
characteristic
Phase
characteristic
Loss of excitation element
Condition
Setting: Minimum operation value,
Bias and operation time for all elements = minimum
Input: One terminal feeding for neutral side or load side
( called "one terminal feeding" in afterward)
Setting: All settings operation time = minimum
Input: Current=rated current12 constantly 10A
Ia=5A, Ib5A, Ia-Ib=10A
Current phase: lag 270
against voltage
When measuring operation values, if voltage reaches 110V
or more with the 2rated current being constant,
measurement is realized by reducing the current with
voltage being constant at 110V.
Setting value 5%
Setting value 5%
Setting value 5%
105% or less of operation value
95% or more of operation value
200ms20ms
200ms20ms
Bias setting
10%
15%
20%
I1
11A
11.5A
12A
I2:15A10%
Setting value 5%
Please refer to the instruction manual regarding the details on this specification.
54
Guaranteed performance
Bias
I2=10A
5%
Bias10%:174.35
Bias15%:171.45
Bias20%:168.55
In the inputting theoretic operation value,
theoretic phase angle value5% and theoretic
operation value5% at the characteristic
control point.
Setting value 5%
0.8A5%
Inrush current Ip
Approx. 20A
Approx. 55A
Approx. 25A
Approx. 65A
3. Trip circuit
Only the dedicated contacts can be used for the circuit breaker trip
circuit. Please keep in mind that the contacts for signaling can not be
used for the trip circuit. (If used, the contact may burn). Also, connect
the pallet contact (52a) of the circuit breaker to the trip coil circuit in
series.
4. Self-diagnosis output circuit
The self-diagnosis output contact is so configured that the auxiliary
relay is energized
( break contact opened ) when normal result of
self-diagnosis is received. This type of contact will allow the relay to
output abnormal result even after the built-in power failures.
Therefore, the break contact is still closed in the aftermath of the
power applying and will be opened after 50ms. If the auxiliary power
of the relay and the self-diagnosis output contact feed from a same
power source, the break contact will be closed temporarily after
auxiliary power supply is turned on. In this case where the
phenomenon stated in the above would conflict with your system
requirement, it is recommended that the self-diagnosis output contact
should be connected via the time-delay timer.
5. Grounding circuit
Be sure to make a wiring to the earth terminal located on the back of
the relay according to the Class D earth wiring method (Grounding
resistance should be less than 100 ohm).
6. CC-Link communication circuit
Please include the communication card into your purchasing order in
case of the application of the communication facility as the card
3. When current input for the loss of excitation element is derived from
the generator neutral point side, the phase current measuring does
not indicate outgoing current but incoming current.
55
CGP2
Auxiliary
power supply
circuit
+ A01
A03
B05
Y
B15
A09
VT
X4
VAB
B16
A10
B07
X0
ED
A18
A17
B09
X1
IA
For
signaling
A19
B11
A20
IB
X2
A21
B13
X3
CT
Loss of excitation
B14
A22
B17
IC
X5
B18
B19
ED
CGP2
X6
Generator
B20
Biased differential or
Loss of excitation
For trip
Biased differential or
Loss of excitation
Programmable output
Default setting at ex-works
ED
CT
A15
A16
IC
A13
A14
A11
IB
A12
IA
+ E01
DI1
E03
N.G.R
Communication card
(option)
+
DC110V
B01 DA
B02 DB
B03 DG
A02
B04 SLD
ED
1 The application voltage for terminal E-01, E-03 and terminal E-02, E-04 is 24V in case that the supplied auxiliary power voltage is 24V.
Fig.81CGP2A01D2
56
The connection diagram shows concepts of the wiring only. Therefore, please note that there will have some difference
between the connection diagram and actual installation status of CT,VT and safety devices such as fuse, etc.
A B C
Auxiliary
power supply
circuit
+ A01
A03
B05
Y
B15
A09
VT
X4
VAB
B16
A10
B07
X0
ED
A18
A17
B09
X1
IA
For
signaling
A19
B11
A20
IB
X2
A21
B13
X3
Loss of excitation
B14
A22
CT
B17
X5
B18
B19
ED
X6
Generator
B20
Biased differential or
Loss of excitation
For trip
Biased differential or
Loss of excitation
CGP2
Programmable output
Default setting at ex-works
A15
A16
A13
A14
A11
A12
+ E01
DI1
E03
N.G.R
Communication card
(option)
+
DC110V
B01 DA
B02 DB
B03 DG
A02
B04 SLD
ED
1 The application voltage for terminal E-01, E-03 and terminal E-02, E-04 is 24V in case that the supplied auxiliary power voltage is 24V.
57
A B C
Auxiliary
power supply
circuit
+ A01
B05
Y
A03
X4
B16
B07
X0
A18
A17
B09
X1
IA
For
signaling
A19
B11
A20
IB
X2
A21
B13
X3
CT
A22
B17
IC
X5
CGP2
X6
Generator
For trip
B19
ED
Programmable output
Default setting at ex-works
ED
CT
A15
A16
IC
A13
A14
A11
IB
A12
IA
+ E01
DI1
E03
N.G.R
Communication card
(option)
+
DC110V
B01 DA
B02 DB
B03 DG
A02
B04 SLD
ED
1 The application voltage for terminal E-01, E-03 and terminal E-02, E-04 is 24V in case that the supplied auxiliary power voltage is 24V.
Fig.83CGP2A02D2
58
The connection diagram shows concepts of the wiring only. Therefore, please note that there will have some difference
between the connection diagram and actual installation status of CT,VT and safety devices such as fuse, etc.
184
205
(185)
46 holes
Case type
D 1
D 2
2 out of 3
relay case
194
203
150
35
M3.5 screws
4M5 screws
Dimension in mm
CPS1
59
Ry 1
Ry 2
Ry 1
Ry 2
Ry 3
Ry 2
Ry 3
Ry 1
Trip
Ry 3
Trip
60
RUN LED
Communication LED
Unit LED
Phase LED
Setting/Cancel switch
Select/Set switch
UP switch
DOWN switch
Indication/
Indication End switch
Operation Indicator
Reset switch
Operation Indicator LEDs
Setting/Cancel
No.
Symbol
SETTING/CANCEL
SELECT/SET
Select/Set
Setting End/Trip
SET.END/TRIP
UP
UP select
DOWN select
DOWN
Indication/Indication End
Reset
Item No.
Item Data
Indicator LEDs
IND./IND.END
RESET
Green
Red
RUN
Green
Communication
Green
Unit
Phase
Setting/Cancel
Setting End/Trip
Yellow
Yellow
Yellow
Yellow
Red
Operation
Direct communication port
Description
Pressing this switch will start the procedure for setting, forced operation or option.
When this switch is pressed again instead of the SET.END/TRIP switch, data that
has been programmed will be all cleared to terminate the selected procedure.The
SETTING/CANCEL indicator LED is lit during the procedure.
This switch is used to select an item number and program item data
during setting, forced operation or option procedure.
When data is programmed to be ready for replacing the currently used
setting, the SET.END/TRIP LED will blink.
When the SET.END/TRIP switch is pressed with its LED blinking during
setting, forced operation or option procedure, the current setting will be
replaced by data given by programming. The new setting will be thus enabled.
These switches are used for selecting data elements. Pressing these
switches for a while will allow fast forward.
With the cover operating button, you can use the switches without
removing the cover.
Pressing this switch will start or end the display of settings and
measurements. With the cover operating button, you can use the switches
without removing the cover.
Pressing this switch will reset output contacts after the relay operated and
extinguish the operation indicator LEDs. With the cover operating button,
you can use the switches without removing the cover.
A number allocated to the selected setting, forced operation or option item
is indicated here.
Data that corresponds to the item number selected is displayed here. For
the indication of individual letters, see the instruction manual specifically
prepared for each model.
Indicate the result of the auto self-check. The lamp will be lit for normal
conditions while off for abnormal conditions.
Indicate the operational status of the communication card.
With a communication card installed: the lamp will be lit for normal
conditions, blinking during communication and off for abnormal conditions.
With a communication card not installed: the lamp will be off.
Indicate the unit used for the item data.
Indicate the phase that corresponds to the item data.
This lamp will be lit during setting, forced operation or option procedure.
This lamp will blink when new data is programmed to be ready for
replacing the current setting.
Indicate the applicable operation elements and phases of the relay.
This port is used for connecting PC and relay with the dedicated cable
(option). The measuring values, operating conditions and setting changes
can be done by PC with the dedicated software (option).
61
DISPLAY
CANSEL
IND.
END
IND.
DOWN
UP
RESET
OPERATION INDICATOR
TRIP
SET.END
SET
SELECT
CANSEL
SETTING
ITEM DATA
IND.
END
IND.
CANSEL
SETTING
ITEM DATA
UP
RESET
OPERATION INDICATOR
TRIP
SET.END
SET
SELECT
UP
DOWN
ITEM DATA
CANSEL
SETTING
ITEM No.
ITEM
No.
Start setting
Initial status
ITEM
No.
RESET
IND.
END
IND.
DOWN
UP
RESET
TRIP
SET.END
SET
SELECT
OPERATION INDICATOR
IND.
END
IND.
DOWN
UP
SETTING
OPERATION INDICATOR
TRIP
SET.END
SET
SELECT
CANSEL
SETTING
ITEM DATA
Start display
ITEM
No.
Initial status
IND.
END
IND.
DOWN
UP
IND.
END
IND.
DOWN
UP
RESET
OPERATION INDICATOR
TRIP
SET.END
SET
SELECT
CANSEL
SETTING
ITEM DATA
IND.
END
IND.
DOWN
UP
IND.
END
IND.
CANSEL
SETTING
ITEM DATA
UP
RESET
OPERATION INDICATOR
TRIP
SET.END
SET
SELECT
UP
DOWN
ITEM DATA
CANSEL
SETTING
ITEM No.
ITEM
No.
RESET
OPERATION INDICATOR
TRIP
SET.END
SET
SELECT
CANSEL
SETTING
IND.
END
IND.
DOWN
UP
RESET
OPERATION INDICATOR
TRIP
SET.END
SET
SELECT
CANSEL
SETTING
ITEM DATA
ITEM
No.
Release
IND.
END
IND.
DOWN
UP
ITEM
No.
TRIP
SET.END
SET
SELECT
CANSEL
SETTING
UP
IND.
IND.
END
DOWN
ITEM DATA
RESET
OPERATION INDICATOR
TRIP
SET.END
SET
SELECT
CANSEL
SETTING
ITEM DATA
Release
IND.
END
IND.
DOWN
UP
RESET
OPERATION INDICATOR
TRIP
SET.END
SET
SELECT
CANSEL
SETTING
ITEM DATA
IND.
END
IND.
DOWN
UP
TRIP
SET.END
SET
SELECT
CANSEL
SETTING
ITEM
No.
DOWN
UP
Note:
Please repeat the same operation in case of two or more items setting
(The above is applicable only for the same group classified with the same number of top digit.)
ITEM
No.
RESET
OPERATION INDICATOR
TRIP
SET.END
SET
SELECT
CANSEL
SETTING
Display/Setting Operation
When the product is shipped from the factory, each setting value is "LOCK" (for element with LOCK position) or "minimum setting value" (for element without LOCK position), therefore, please
make new setting as you wish according to the above mentioned procedure for each element.
SETTING
62
Safety section
This Safety section should be read before starting any work on the relay. Be sure to read the instruction
manuals and other related documents prior to commencing any work on the relay in order to maintain them
in a safe condition. Be sure to be familiar with the knowledge, safety information and all caution items of the
product prior to use.
CAUTION Caution means that failure to un-observe safety information, incorrect use, or improper use may endanger personnel and equipment and cause personnel injury or physical damage.
Items as classified to the caution may become to occur more sever results according to the circumstance. Therefore, all items described
in the safety section are important and to be respected without fail.
CAUTION
1. Items concerning transportation
(1) Be sure the equipment to be kept in normal direction
(2) Avoid the bumps, shock, and vibration, otherwise the product performance /life might be unfavorably affected.
2. Items concerning storage
(1) Environment shall be as below, otherwise the product performance/life might be unfavorably affected.
-Ambient temperature: -20+60(with no condensation nor freezing)
-Relative humidity: 3080% average of a day
-Altitude: Less than 2000m
-Avoid applying unusual shock, vibration or leaning or magnetic field
-Not expose to harmful smoke, gas, salty air, water, vapor, dust, powder, explosive material or wind, rain.
3. Items concerning mounting/wiring work
(1) Mounting and wiring work should be done correctly. Otherwise, damage, burning or erroneous operation might occur.
(2) Screw terminal should be tightened securely. Otherwise, damage and burning might occur.
(3) Grounding should be done correctly in case it is required. Otherwise, electric shock, damage, burning or erroneous operation might occur.
(4) Wiring should be done without mistake especially observing the correct polarity. Otherwise, damage, burning or erroneous operation might
occur.
(5) Wiring should be done without mistake especially observing the phase ordering. Otherwise, damage, or erroneous operation might occur.
(6) Auxiliary power source, measuring transformer and power source which have enough capacity for correct operation of product should be used.
Otherwise, an erroneous operation might occur.
(7) Be sure to restore the front cover, terminal cover, protection cover, etc to the original position, which have been removed during the mounting/
wiring work. Otherwise, electrical shock might occur at the time of checking.
(8) Connection should be done correctly using designated and right connectors. Otherwise, damage or burning might occur.
(9) Fully insert the sub unit into the case until you can hear a click while pressing the handles located on both sides of the sub unit front face.
Otherwise, incomplete inserting the sub unit might only establish a poor contact with the terminals located on the back side of unit, which might
cause erroneous operation or heating.
4. Concerning equipment operation and settings
(1) Operational condition should be as below. Otherwise, the product performance/life might be unfavorably affected.
-Deviation of auxiliary power: within +10%-15% of rated voltage
-Deviation of frequency: within 5%of rated frequency
-Ambient temperature: 0+40(-10+50 is permissible during couples of hour per day, with no condensation nor freezing)
-Relative humidity: 3080% average of a day
-Altitude: Less than 2000m
-Avoid to be exposed to unusual shock, vibration, leaning or magnetic field
-Not expose to harmful smoke, gas, salty air, water, vapor, dust, powder, explosive material, wind or rain.
(2) Qualified personnel may work on or operate this product, otherwise, the product performance/life might be unfavorably affected and/or
burning or erroneous operation might occur.
(3) Be sure to read and understand the instruction manuals and other related documents prior to commencing operation and maintenance work on
the product. Otherwise, electrical shock, injury, damage, or erroneous operation might occur.
(4) While energizing product, be sure not to remove any unit or parts without permissible one. Otherwise, damage, or erroneous operation might
occur.
(5) While energizing product, be sure to make short circuit of current transformer secondary circuits before setting change or drawing out the sub
unit. Otherwise, secondary circuit of live current transformer might be opened and damage or burning might occur due to the high level
voltage.
(6) While energizing product, be sure to open trip lock terminal before setting change or drawing out the internal unit of product. Otherwise,
erroneous operation might occur.
(7) Be sure to use the product within rated voltage and current. Otherwise, damage or erroneous operation might occur.
(8) While energizing product, be sure not to clean up the product. Only wiping a stain on the front cover of product with a damp waste might be
allowable. (Be sure to wring hardly the water out of the waste.)
5. Items concerning maintenance and checking
(1) Be sure that only qualified personnel might work on or operate this product. Otherwise, electrical shock, injury, damage, or erroneous operation
might occur.
(2) Be sure to read and understand the instruction manuals and other related documents prior to commencing operation and maintenance work on
the product. Otherwise, electrical shock, injury, damage, or erroneous operation might occur.
(3) In case of replacing the parts, be sure to use the ones of same type, rating and specifications, etc. If impossible to use above parts, be sure to
contact the sales office or distributor nearest you. Otherwise, damage or burning might occur.
(4) Testing shall be done with the following conditions.
-Ambient temperature: 2010
-Relative humidity: Less than 90%
-Magnetic field: Less than 80A/m
-Atmospheric pressure: 86106103 Pa
-Installation angle: Normal direction2
-Deviation of frequency: within 1%of nominal frequency
-Wave form (in case of AC): Distortion factor less than 2% (Distortion factor=100%effective value of harmonics/effective value of fundamental)
-Ripple (in case of DC): Ripple factor less than 3% (Ripple factor=100%(max-min)/average of DC)
-Deviation of auxiliary power: within 2% of nominal voltage
-Be sure not to inject the voltage or current beyond the overload immunity. Otherwise, damage or burning might occur.
-Be careful not to touch the energized parts. Otherwise, the electric shock might occur.
6. Items concerning modification and/or repair work
Be sure to ask any modification and/or repair work for product to the sales office or distributor nearest you.
Unless otherwise, any incidents occurred with modification or repair works (including software) done by any other entity than MITSUBIHI
ELECTRIC CORPORATION shall be out of scope on warranty covered by MITSUBISHI ELECTRIC CORPORATION.
7. Items concerning disposal
Particular regulations within the country of operation shall be applied to the disposal.
63
MELPRO -D Series
TM
MELPRO -D Series
TM
MELPRO -D
TM
HEAD OFFICE
CAUTION
TO PREVENT IT FROM THE RISK OF DAMAGE AND MAL FUNCTION,
BE SURE TO READ OPERATING AND MAINTENANCE (SERVICING)
INSTRUCTIONS BEFORE USING.
SE-E840-C(11.03-1.0)ROS
Published Mar.2011