Ensure that this Instruction Manual is delivered to


the end users and the maintenance manager.

1 JEP0-IL9378-C
- Safety section -
This Safety section should be read before starting any work on the relay.
Be sure to read the instruction manuals and other related documents prior to commencing any work on the relay in
order to maintain them in a safe condition.
Be sure to be familiar with the knowledge, safety information and all caution items of the product prior to use.

Caution means that failure to observe safety information, incorrect use, or


CAUTION improper use may endanger personnel and equipment and cause
personnel injury or physical damage.

Items as classified to the caution may become to occur more sever results according to the circumstance. Therefore,
all items described in the safety section are important and to be respected without fail.

CAUTION

1. Items concerning transportation


(1) Be sure the equipment to be kept in normal direction
(2) Avoid the bumps, shock, and vibration, otherwise the product performance /life might be unfavorably affected.
2. Items concerning storage
(1) Environment shall be below, otherwise the product performance/life might be unfavorably affected.
-Ambient temperature: -20℃~+60℃ (with no condensation nor freezing)
-Relative humidity: 30~80% average of a day
-Altitude: Less than 2000m
-Avoid applying unusual shock, vibration or leaning or magnetic field
-Not expose to harmful smoke, gas, salty air, water, vapor, dust, powder, explosive material or wind, rain.
3. Items concerning mounting/wiring work
(1) Mounting and wiring work should be done correctly.
Otherwise, damage, burning or erroneous operation might occur.
(2) Screw terminal should be tightened securely.
Otherwise, damage and burning might occur.

Tightened torque of screw shall be as below table


Material Size Standard torque Permissible range Application
1.10N・m 0.932~1.27N・m
Steel M3.5 Terminals of back side
(11.2kgf・cm) (9.5~12.9kgf・cm)

(3) Grounding should be as done correctly in case it is required.


Otherwise, electric shock, damage, burning or erroneous operation might occur.
(4) Wiring should be done without mistake especially observing the correct polarity.
Otherwise, damage, burning or erroneous operation might occur.
(5) Wiring should be done without mistake especially observing the phase ordering.
Otherwise, damage, or erroneous operation might occur.
(6) Auxiliary power source, measuring transformer and power source which have enough capacity for correct
operation of product should be used.
Otherwise, an erroneous operation might occur.
(7) Be sure to restore the front cover, terminal cover, protection cover, etc to the original position, which have been
removed during the mounting/ wiring work.
Otherwise, electrical shock might occur at the time of checking.
(8) Connection should be done correctly using designated and right connectors.
Otherwise, damage or burning might occur.
4. Concerning equipment operation and settings
(1) Operational condition should be as below.
Otherwise, the product performance/life might be unfavorably affected.
-Deviation of auxiliary power: within +10%~-15% of rated voltage
-Deviation of frequency: within ±5% of rated frequency
-Ambient temperature: 0℃~+40℃ (-20℃~+50℃ is permissible during couples of hour per day, with no
condensation nor freezing)
-Relative humidity: 30~80% average of a day

2 JEP0-IL9378
-Altitude: Less than 2000m
-Avoid to be exposed to unusual shock, vibration, leaning or magnetic field
-Not expose to harmful smoke, gas, salty air, water, vapor, dust, powder, explosive material, wind or rain.
(2) Qualified personnel may work on or operate this product, otherwise, the product performance/life might be
unfavorably affected and/or burning or erroneous operation might occur.
(3) Be sure to read and understand the instruction manuals and other related documents prior to commencing
operation and maintenance work on the product. Otherwise, electrical shock, injury, damage, or erroneous
operation might occur.
(4) While energizing product, be sure not to remove any unit or parts without permissible one. Otherwise, damage,
or erroneous operation might occur.
(5) While energizing product, be sure to make short circuit of current transformer secondary circuits before setting
change or drawing out the sub unit. Otherwise, secondary circuit of live current transformer might be opened
and damage or burning might occur due to the high level voltage.
(6) While energizing product, be sure to open trip lock terminal before setting change or drawing out the internal
unit of product. Otherwise, erroneous operation might occur.
(7) Be sure to use the product within rated voltage and current.
Otherwise, damage or erroneous might occur.
5. Items concerning maintenance and checking
(1) Be sure that only qualified personnel might work on or operate this product.
Otherwise, electrical shock, injury, damage, or erroneous operation might occur.
(2) Be sure to read and understand the instruction manuals and other related documents prior to commencing
operation and maintenance work on the product. Otherwise, electrical shock, injury, damage, or erroneous
operation might occur.
(3) In case of replacing the parts, be sure to use the ones of same type, rating and specifications, etc.
If impossible to use above parts, be sure to contact the sales office or distributor nearest you.
Otherwise, damage or burning might occur.
(4) Testing shall be done with the following conditions.
-Ambient temperature: 20℃±10℃
-Relative humidity: Less than 90%
-Magnetic field: Less than 80A/m
-Atmospheric pressure: 86~106×103 Pa
-Installation angle: Normal direction±2°
-Deviation of frequency: within ±1% of nominal frequency
-Wave form(in case of AC): Distortion factor less than 2%
(Distortion factor=100%×effective value of harmonics/effective value of fundamental)
-Ripple (in case of DC): Ripple factor less than 3%
(Ripple factor=100%×(max-min)/average of DC)
(5) Deviation of auxiliary power: within ±2% of nominal voltage
(6) Be sure not to inject the voltage or current beyond the overload immunity.
Otherwise, damage or burning might occur.
(7) Be careful not to touch the energized parts.
Otherwise, the electric shock might occur.
(8) While energizing product, be sure not to clean up the product . Only wiping a stain on the front cover of product
with a damp waste might be allowable. (Be sure to wring hardly the water out of the waste.)
6. Items concerning modification and/or repair work
Be sure to ask any modification and/ or repair work for product to the sales office or distributor nearest you.
Unless otherwise, any incidents occurred with modification or repair works (including software) done by any other
entity than MITSUBIHI ELECTRIC CORPORATION shall be out of scope on warranty covered by MITSUBISHI
ELECTRIC CORPORATION.
7. Items concerning disposal
Particular regulations within the country of operation shall be applied to the disposal.

3 JEP0-IL9378
- Guarantee -
1.Guarantee period
The guarantee period of this product should be one year after delivery, unless otherwise specified by both parties.
2.Scope of guarantee
When any fault or defect is detected during the period of guarantee and such fault or defect is proved to be caused
apparently at the responsibility of MITSUBISHI ELECTRIC CORPORATION, the defective unit concerned will be repaired
or replaced by a substitute with free of charge. However, the fee for our engineer dispatching to site has to be covered by
the user. Also, site retesting or trial operation caused along with replacing the defect units should be out of scope of our
responsibilities. It is to be acknowledged that the following faults and defects should be out of this guarantee.
① When the faults or defects are resulted from the use of the equipment at the range exceeding the condition/environment
requirements stated in the catalogue and manual.
② When the faults or defects are resulted from the reason concerning without our products.
③ When the faults or defects are resulted from the modification or repair carried out by any other entity than MITSUBISHI
ELECTRIC CORPORATION.
④ When the faults or defects are resulted from a phenomenon which can not be predicted with the science and technology
put into practical use at the time of purchase or contract.
⑤ In case of integrating our products into your equipment, when damages can be hedged by the proper function or
structure in the possession of your equipment which should be completed according to the concept of the de fact
standard of industry.
⑥ In case of that the faults or defects are resulted from un-proper application being out of instruction of MITSUBISHI
ELECTRIC CORPORATION.
⑦ In case that the faults or defects are resulted from force majeure such a fire or abnormal voltage and as an act of God
such as natural calamity or disaster.
3.Exclusion of loss in opportunity and secondary loss from warranty liability
Regardless of the gratis warranty term, MITSUBISHI ELECTRIC CORPORATION shall not be liable for compensation of
damages caused by any cause found not be the responsibility of MITSUBISHI ELECTRIC CORPORATION, loss in
opportunity, lost profits incurred to the user by failures of MITSUBISHI ELECTRIC CORPORATION products, special
damages and secondary damages whether foreseeable or not, compensation for accidents, and compensation for
damages to products other than MITSUBISHI ELECTRIC CORPORATION products and other tasks
4.Applications of products
①The user is requested to confirm the standards, the regulations and the restrictions which should be applied, in case of
utilizing products described in this catalogue and another one in combination.
Also, the user is requested to confirm the suitability of our products to your applied system or equipment or apparatus by
yourself. MITSUBISHI ELECTRIC CORPORATION shall not be liable for any suitability of our products to your utilization.
②This MITSUBISHI ELECTRIC CORPORATION products described in the catalogue have been designed and
manufactured for application in general industries, etc. Thus, application in which the life or an asset could be affected,
such as medical system for life-sustaining, in nuclear power plants, power plants, aerospace, and transportation
devices(automobile, train, ship, etc )shall be excluded from the application. In addition to above, application in which the
life or an asset could be affected by potentially chemical contamination or electrical interference and also in which the
circumstances and condition are not mentioned in this catalogue shall be excluded.Note even if the user wants to use for
these applications with user’s responsibility, the user to be requested to approve the specification of MITSUBISHI
ELECTRIC CORPORATION products and to contact to the technical section of MITSUBISHI ELECTRIC
CORPORATION prior to such applications. If the user applies MITSUBISHI ELECTRIC CORPORATION products to
such applications without any contact to our technical section, MITSUBISHI ELECTRIC CORPORATION shall not be
liable for any items and not be insured, independently from mentioned in this clause.
③In using MITSUBISHI ELECTRIC CORPORATION product, the working conditions shall be that the application will not
lead to a major accident even if any problem or fault occur, and that backup or duplicate system built in externally which
should be decided depend on the importance of facility, are recommended.
④The application examples given in this catalogue are reference only and you are requested to confirm function and
precaution for equipment and apparatus and then, use our products
⑤The user is requested to understand and to respect completely all warning and caution items so that unexpected
damages of the user or the third party arising out of un-correct application of our products would not be resulted.
5.Onerous repair term after discontinuation of product
①MITSUBISHI ELECTRIC CORPORATION shall accept onerous product repairs for 7(seven) years after production is
terminated. (However, please consider the replacement of products being in operation during 15 years from ex-work.)
②Product supply (including repair parts) is not available after production is discontinued.
6.Changes in product specification
The specification given in the catalogue, manuals or technical documents are subject to change without prior to notice.
7.Scope of service
The technical service fee such as engineer dispatching fee is excluded in the price of our products. Please contact to our
agents if you have such a requirement.

4 JEP0-IL9378
MVG-A2 Series Ground Over voltage Relay [Standard: JEC 2511]
Feature
1. A digital type relay corresponding EVT, which has high 4.Enriched measurement and display functions.

accuracy and stable operating characteristic. It is available to measure the input value of voltage

2. High sensitivity detection (2% detection) and wide and display the pick-up and setting values.

setting range. 5.Forced operating is available by a test button.

3. High reliability by the self-monitoring function. 6.Not need outside auxiliary power supply.

The relay monitors control circuit, electric circuit The auxiliary power supply can be supplied by VT

and program data at all time, which are indicated by the secondary.

(LED “RUN” lights up in the normal condition and goes 7.High vibration and impulse resisting performance.

out in the abnormal condition.)

Rating and Specifications


Type Name MVG-A2V-R MVG-A2V-RD
Style No. 097PGA 516PGA
Protection Ground over voltage element × 1
Element
Measure Voltage
Input
AC110/190V
voltage
Ratings Frequency 50/60HZ (Changeover)
Auxiliary
AC100/110V (90~120V)
power supply
V0 (complete earth fault) = LOCK-2-4-6-8-10-12-14-16-18-20%
Voltage
(100% = 110V/190V)
Settings Time INST.(<60ms)-0.2-0.5-1.0-1.5-2.0-2.5-3.0-4.0-5.0s
Using
Frequency:50Hz(SW1-ON)/60Hz(SW1-OFF) changeover
Condition
Self
The LED “RUN”(green) lights up in normal condition.
monitoring
Operation The display target turns from black into orange color when relay operates.
Display (Manual resetting type)

SW No. Display function


Display
0 Input zero-phase voltage (%) :1.0~25
Numerical 1 Pickup display :U.
Display 2 Zero-phase voltage settings(%) :2.0~20
3 Operating time setting(s) :Inst.0.2~5.0
4 Frequency setting(HZ) :50/60

Forced operation is available in the condition of the rated voltage being applied.
Test button
(The button should be depressed as long as the desired operation time lasts)
V0
Power AC110V/190V circuit: 0.1VA at rated voltage applied
circuit
Consumption
Control
VA (VT) Normal:4VA Operating:7VA
circuit
Case Compact cylindrical fixed type Compact cylindrical draw-out type
Mass Approx.1.0kg Approx.1.1kg

Notes) ①“LOCK” means that to let this element not to operate.


②“INST” means instantaneous.
③ It is necessary to combine EVT with this relay.

5 JEP0-IL9378
Characteristics
Item Characteristics
Ambient temperature :-20~+50℃ (in non-freezing state)
Standard
Relative humidity:30~80%
conditions of
Altitude :2000m max.
Use
Other conditions :Not to be subject to abnormal vibration, shock or corrosive gases or excessive dust or moisture.
Operating value
Within ±10% of setting value with setting of each V0 setting value and minimum operating time.
Characteristics
Reset value
90% or more of operating value with setting of each V0 setting value and maximum operating time.
Characteristics
V0 setting=10%
Input voltage
Operating time 150% of setting value
Time setting
Characteristics
Inst. 60ms or less
0.2~5s ±10% of setting value
250ms±50ms
Reset time Test condition:
Characteristics ・Input : 150% of setting value → 0V
・Setting: V0 =10%
Operating value: Within ±10% at the rated frequency.
Operating time : Within ±10% at the rated frequency.
Frequency
Test condition:
Characteristics
・Rated frequency: ±5% variation
・Setting : V0 =10%, Operating time = 0.2s.
Variation Operating value: Within ±10% at the rated voltage.
characteristic Operating time : Within ±10% at the rated voltage.
of auxiliary Test condition:
power supply ・Rated voltage : AC90V~120V
Operation value:±10% at 20℃
Temperature Operating time :±10% at 20℃
Characteristics Test condition:
・Temperature : -20~60℃

Peak-to-peak amplitudemm When the above vibration is applied with


Vibration
Frequency (acceleration m/s2) setting of maximum operating value and
times
Vibration (HZ) Forward/ minimum operating time and applied 90%
Right/left Up/down (s)
backward input voltage (against setting value), it
10 5(9.8) 2.5(4.9) 30 is not abnormal operation and wrong
16.7 0.4(1.96) 600 display.

When apply a shock to the relay at the maximum acceleration of 294m/s2 3 times with each forward and backward,
Shock right and left, and vertically, it is not abnormality.

10MΩ or more between all the electric circuit and the case (E terminal)
Insulation 10MΩ or more between independent electric circuits DC500V megger used
Resistance 10MΩ or more between contact circuit terminals(between poles)
When tested at relative humidity of 80% RH max.
2000V AC, for 1 minute between all the electric circuits and the case(E terminal)
Voltage
2000V AC, for 1 minute between independent electric circuits
withstand
1000V AC, for 1 minute between contact circuit terminals (between poles)a11-a12, a21-a22
Apply 1.2/50μs standard waveform to positive/negative electrodes for 3 times. It is not abnormality.
Lightning ・Between all the electric circuits and the case (E terminal) : 4.5KV
impulse ・Between EVT secondary and control circuits : 4.5KV
withstand ・Between control circuits : 3KV
voltage ・Between auxiliary power supply contacts : 3KV

Apply IEC voltage waveform to the relay for 2 seconds with maximum voltage setting. It is not abnormality.
・Between EVT secondary and ground(E terminal)
Noise-proof ・Between auxiliary power supply contacts and ground (E terminal)
・Between auxiliary power supply contacts

Radio No voltage input to the relay with maximum operating setting. At the same time to put a transceiver antenna (5W

6 JEP0-IL9378
disturbance output) with 150MHz or 400MHz band closing the relay panel about 0.5m.
It is not abnormal operation.

AC110V:10A(Power factor = 0.5) AC110V:5A(Power factor = 0.5)


Contact DC220V:10A AC220V:1A(Power factor = 0.5)
Closed circuit Opened circuit
capacity DC110V:15A DC110V:0.2A
(L/R=0s) (L/R=40ms)

7 JEP0-IL9378
Construction
RUN indicated LED(Green)
Selector switch for display
Continuously monitor the auxiliary power supply
selection
circuit, electric circuit, program date, etc .,
●Set the display item
and the RUN LRD lights up in normal condition.
●To change the setting with hand
MELPRO TM-A ▲MITSUBISHI or a small(-)screwdriver.
LED for numerical display No
No ITEM
項目
0 V0 MEASURE (%)
1 PICKUP
INDICATOR SELECT

The following items can be RUN


2 U > SETTING(V)
3 T SETTING(s)
1
2
3 4
4 f SETTING(Hz)
displayed by switch setting. TEST
0
IND.

(1) Voltage measurement… OFF


Test switch
3 4 5 3 4 5
Input voltage can be 1
2 6
7 1
2 6
7 ON
1
By pressing the TEST button,
0 8 0 8
displayed with range of 1.0 NO
9
NO
9
OFF
forced operating is available.
SETTING SETTING
to 25%. U > SETTING TIME(T) SETTING FREQUENCY(f)SETTING
No 整定値
No SET.VALUE
整定値 No. No 整定値
No SET.VALUE
整定値 No SET.VALUE
整定値
整定値 No. No SET.VALUE
整定値
整定値 NoSW1
SW1整定値 周波数
(2) Pickup display・・・
No. No. FREQUENCY
0 LOCK 8 16% 0 0.1s 8 4.0s ON 50Hz
1 2% 9 18% 1 0.2s 9 5.0s OFF 60Hz
Display the pickup with U. 2
3
4%
6%
A 20% 2
3
0.5s
1.0s
Frequency setting switch
(3) Setting value display… 4
5
8%
10%
4
5
1.5s
2.0s The used frequency can be set
6 12% 6 2.5s
Each setting value can be 7 14% 7 3.0s with ON/OFF switch.
displayed. OP.
ON
U > 50HZ setting →
OFF
GROUND OVER VOLTAGE RELAY
Switches for operating voltage MVG-A2V-R
ON
and operating time setting JEC-2511
60HZ setting →
STYLE: 097PGA Aux. V: AC100/110V
● Set the setting value RATING: V0 =AC110/190V SERIAL:
OFF
● To change the setting with hand f =50/60Hz YEAR:
When the switch is set, do not
or a small (-) screwdriver. LEVER OPERATION
use any tool with a sharp point.
DON’T TOUCH THE SCREW ・INDICATOR AND

(It may cause damage to the


OPERATION RESET
(FOR INTERNAL FIXATION)
・OPERATION LOCK
MITSUBISHI ELECTRIC CORPORATION MADE IN JAPAN

switch lever.)
Display reset lever on the operation flag unit
Pushing reset lever makes it possible to reset the operation
display unit. Operation flag indicator
While the lever is being pushed up, the relay function is locked. During relay operating, this

indicator changes from black to

Note )Since the display plug of the operation display unit is of orange.
a very precise structure, avoid touching it directly by hand.

Fig. 8-1 MVG-A2 series construction(panel)

Internal Connection diagram

a(190V) a(190V)
V0 Level
detection Operation status display V0 Level
a(110V) a(110V) detection Operation display

+ RUN display RUN display


f f+
X0 a11 X0
X0 Output contact X0 a11
Output contact
Output contact Output contact
a12 a12
P1 P1
Auxiliary Auxiliary
Power supply X1 Output contact X1 Power supply X1 Output contact X1
Power supply a21 power supply a21
P2 P2 Output contact
Output contact
a22 a22
Continuously monitoring
Continuously monitoring
Power circuit monitoring
Power circuit monitoring E
E

a) MVG-A2V-R b) MVG-A2V-RD

Fig. 8-2 Internal Connection diagram

8 JEP0-IL9378
Operating Description
1.Relay function 3.Numerical Display Function
①This relay has a built-in regulated voltage circuit By changing the position of the selector switch, the
which derivers control voltage from the VT secondary following values can be displayed on the numerical
voltage, therefore, particular auxiliary power supply display LED.
is not required. ①Voltage measurement…(switch position:0)…
② The input zero-phase voltage is converted into a
Based on the zero-phase voltage signal data, the
electronic circuit level signal by a built-in auxiliary
zero-phase voltage is measured and computed, and then
VT.
③The input zero-phase voltage signal is converted into to display the input voltage value. The display range

a digital signal by A/D converter, and as data input is from 1.0% to 25%. (When less than 1.0%, nothing is

microcomputer. displayed. When more than 25%, “O.F.” is displayed.)

④The microcomputer calculates and compares the level of Here, 100% is equal to the rating input voltage.

the input zero-phase voltage signal data with the ②Pickup display…(switch position:1)…

setting value data. If the zero-phase voltage signal is When the input voltage is more than the setting value,

more than the setting value, the timer starts counting. U. is displayed.

If the counter is more than the operating time setting, Using this function, easy test the operating value.

the relay and the operating flag unit start to operate. When pressing the TEST button (forced operation),

2.RUN display(Self-monitoring Function) U. is displayed.


This relay monitors control voltage, electric circuit ③Setting value display…(Switch position:2~4)…
and program data at all time. The RUN LED (green)
This function displays the relay setting condition
lights up in the normal condition, and goes out in the
including zero-phase voltage settings(V), operating
abnormal condition. Since control voltage is derived
time T Settings (s) and frequency setting value (Hz).
from VT secondary voltage input, the LED goes out when

the auxiliary power supply voltage lower than approx.

85V.

External Connection Diagram (Example)


Type EG-4 current limiting resistance value
System Voltage
V0
6.6KV 3.3KV
Rating EG-4
Style No.
190V P7971 25Ω 50Ω
110V PB991 8Ω 16Ω

Ground type potential


transformer(EVT)
CB CB AC110 CB AC110 AC110
AC110
U V W
ZCT ZCT ZCT Z1+
Z1+ P1 P2 Z1+ P1 P2 P1 P2 P1 P2
“MZT” “MZT” “MZT” E
O
Z2 MDG-A2V Z2 MDG-A2V Z2 MDG-A2V MVG-A2V
E E E E
ED ED ED ED
a 190V a 110V a 190V a 110V a 190V a 110V + EA EA a 190V a 110V
f+
f+
f f+

a b c f

EG-4

ED
Note)This figure shows the connection of V0=190V.

Fig. 8-3 External Connection Diagram

9 JEP0-IL9378
Handling Method
1.Panel assemble setting switch. It is also possible by using a small

①Do connect the relay terminal “E” to earth at Class minus (-) screwdriver. If a large minus (-) screwdriver

D please. is used, it may damage the groove of the switch knob.

②Type MVG-A2V-RD is a draw-out type that the sub-unit can ④The switch for setting is a rotary one utilizing snap

be drawn out from case. action. When the setting is changed, turn the switch

For detail, refer to section of “Drawing out and smoothly so as not to stop it in mid-position.

Housing operation of Sub-unit” please. ⑤ The position of the display selector switch is not

2.Use and Operation specified in particular, but if it is normally set to

①About the setting of frequency, it is set OFF at the time 0 Vo Measure(%) , The input voltage value can be

of shipment, so it is necessary to set the frequency measured conveniently.

switch again according to the using frequency when begin ⑥ Since the RUN indicator LED is lighting during the

to use this relay. normal operation, check it in routine checking please.

Refer to the page 13, Cover Handling. If it turns off, check the voltage value between

②Avoid changing the setting value during relay operating, terminals of P1-P2, and if it is still in OFF state even

since it is possible to occur unwanted operation. the input voltage is approx 85V or more, please contact

However, if the setting change is unavoidable, please our local agent and branch office since the relay may

push up the reset lever in order to lock relay operating. fail.

③To change the setting may be realized manually by the

Test
A relay test is carried out sufficiently by maker before should be carried out with individual control point

shipment. But at the following cases, it is recommended that after judging the performance of this relay. Please use

the test be carried out again. this data as a later standard.

a. After the products are unpacked when received


2.Withstand Voltage Test
b. When the equipment starts operation
Perform the unit test as follows.
(Power receiving starts)
a. Apply 2000V AC (commercial frequency) between all
c. When periodical checkup is carried out
electric circuit and case (E terminal)for one
(Normally once per year)
minute, and make sure that no problem.
1.Testing Voltage Applied Terminals
a a
①About the voltage input waveform, please use a sine wave <110V> <190V> P1 a11 a12
E
without distortion. f+ P2 a21 a22

②To select the switch for each setting with hand or use b. Apply 2000V AC (commercial frequency) between all

a small regular screwdriver (“-” type). electric circuit and case(E terminal)for one minute,

0 Vo Measure(%) and make sure that no problem.


③Set the selector switch position to
Voltage Applied Terminals
as appropriate according to the test item. Set other
P1 P2 a11 a12 a21 a22
switches for setting according to the test conditions
a a
<190V> <110V> f+ a11 a12 a21 a22
of the operation characteristic control points.
a a
P1 P2 <190V> <110V> f+
④If the operation characteristics are tested specially

in individual control points (for example, when tested

with the in-service setting conditions), the test

should be performed with the operation characteristic

points when the products are received, a receiving test

10 JEP0-IL9378
3.Operation Characteristics Test 4.Operation Characteristic Control Point
① Increase the control voltage gradually, the RUN Perform the test periodically according to the

indicator LED (green) will light up at approx. 85V. following test condition and criterion.

This indicates that the electronic circuit has started


Test Condition
to operate normally.
Test Item Operation Operation Criterion
②With the rated voltage and press the TEST button located Input
value time
relay panel, make sure that the forced operation is Operation Each Minimum ±10% of
available please. ―
value setting setting setting value
③With the rated voltage and press the TEST button located
0V
10% Inst. 60ms or less
relay panel, make sure that the forced operation is Operation ↓

available please. time 150% of Other ±10% of


10%
setting above setting value

11 JEP0-IL9378
Terminal Layout

14-M3.5 screw 14-M3.5 screw

12
13
a a a a
110 190 P1 a11 a12 110 190 P1 a11 a12

14
16
E f+ P2 a21 a22 E f+ P2 a21 a22

9 9 9 9 9 9 9 9 9 9 9 9

MVG-A2V-R MVG-A2V-RD

Fig. 8-4 Terminal Layout

Drawing out and Housing operation of Sub-unit


-For compact cylindrical draw-out type(RD type)

it is available to draw out the sub-unit from the rely ・ Lock the tripping circuit

case instead of removing the external wires. So that ・ Turn off the power supply into relay

easier to carry out checking and testing. ・ Disconnect CT circuit

When drawing out and housing, please pay attention to ・ Disconnect VT circuit

not to touch the electric circuit and move the sub-unit ・Opened the auxiliary power supply

by handing the lever or form. (only the RD type relay)

Otherwise, it is possible to get an electric shock or make

internal electric parts damage.


The following operation should be checked when sub-unit

be drawn out from relay case.

Subunit Connecter of unit

Connector of subunit

Cover
Draw-out handle

Screw for fixing sub-unit Lever for reset

Fig. 8-5 RD Type Structure of MELPRO-A series

12 JEP0-IL9378
Monitoring and Dimensions

155
146 15 124
32 114
78.5

Minimum arrangement
167
φ140~φ142

124
φ138
88.5

Pitch194
2-M6 screw
15 46.5 8.3 14-M3.5 screw
14

Minimum arrangement 2-φ7 hole


pitch 170

Fig. 8-6 MOC,MGR,MDG,MUV,MOV,MVG- -R (Unit:mm)


Same as the center lines of φ140~142 hole

146 36.5 124


155
32 114 14
78.5

Minimum arrangement φ140~φ142


φ138

124
88.5
167
88.5

pitch 194

2-M6 screw
8.3 14-M3.5 screw
15 46.5 Minimum arrangement 2-φ7 hole
14

pitch 182

Fig. 8-7 MOC,MGR,MDG,MUV,MOV,MVG- -RD (Unit:mm)

Hinge

● Cover Handling
Relay cover is opening-and-closing door type. Once
forces the cover overload when open it, it will be
removed from case. Please refer to the figure shown
blow to assemble the cover at horizontal direction.
(Do not assemble it at the direction of the front.)
[Cover opening-and-closing]

13 JEP0-IL9378
Improvement on the reliability of protection function
Any parts and materials applied to the protection relay have limited life time which will bring the
degradation to the relay.
The degree of degradation will be variable and depend on the purpose, period in use, applied
circumstance and unevenness on the performance of each part.
MITSUBISHI ELECTRIC CORPORATION design the relay so as to realize that the recommended replaced
duration is more them 15 years.
However, there may be some possibilities to occur some defects before reaching 15 years due to above
mentioned the degree of degradation of parts and materials being depended on the condition in use.
To prevent unwanted operation or no operation of relay due to above reasons, it is recommended to
apply the relay with self-diagnosis function and/or multiplexing relay system such as dual or duplex
scheme.

14 JEP0-IL9378