ITA2 User Manual
ITA2 User Manual
ITA2 User Manual
USER MANUAL
10H52261UM60 – rev. 1
ITA2
Special Declaration
Safety of Personnel
1. This product must be installed by qualified professionals, engineers appointed by the manufacturer or an
authorized agent. Failure to observe this condition may result in product malfunction, and compromise the safety of
personnel.
2. Take the time to read this product manual and the safety precautions thoroughly before installing and
commissioning this product. Failure to observe this condition may result in product malfunction, and compromise
the safety of personnel.
3. This product is not intended for use with life support systems
4. Never attempt to dispose of the internal and external batteries in fire as they may explode, leading to serious
injuries, or even death.
Product Safety
1. If the product is to be stored or unused for extended periods, place the equipment in a clean, dry environment
within the specified temperature range
2. This product should be used in an appropriate operating environment. Consult the Site Preparation section for
information about the ideal operating and maintenance environment for this product
3. This product is not designed for use in conditions and/or environments where:
The temperature and relative humidity are outside the specified limits
It is subject to vibration or shocks
It is exposed to the presence of conductive dust, corrosive gases, salts, or inflammable gases
It is exposed to heat sources or strong electro-magnetic interference
Disclaimer
Vertiv may not be held accountable or responsible for defects and malfunctions arising for the following reasons:
Application range or operating environment outside the specified limits
Unauthorized modification, incorrect installation or operation
Force majeure
Other actions not in compliance with the instructions in this manual
Safety Precautions
Always observe the following safety symbols!
Used for instructions that the user must read carefully and observe, even if failure to do so may not
result in damage.
This manual contains the information about installing and operating the Liebert ITA2 Rack mounted 20kVA UPS
(hereinafter referred to as the UPS). Please read this manual carefully before installing the UPS. To reduce the risk
of accidents, please read the safety precautions attentively before operating the UPS. The 'Caution/Note/Warning'
instructions in this user manual and on the product do not represent all the safety instructions to be observed, and
are intended as supplementary to the such instructions. Therefore, personnel assigned to install and operate the
UPS must have received thorough training and have fully understood the various operations and safety instructions
before starting work. When operating Vertiv products, personnel must observe the general safety regulations
applicable in the sector, the general safety instructions and the special safety instructions provided by Vertiv.
Warning
1. The UPS must be installed, commissioned and serviced by engineers designated by the manufacturer or its agent. Failure to
observe this could place personnel at risk, cause the UPS to malfunction and invalidate the warranty.
2. The UPS has been designed for commercial and industrial use only, and is not recommended for use in life support
applications.
3. This is a Class C2 UPS product. Nevertheless, in a residential environment it may cause radio interference, in which case,
the user is required to take additional measures to reduce such interference.
Isolate the UPS and check for hazardous voltage between all terminals, and between the terminals and earth, prior to working
on this circuit.
The UPS complies with 2014/35/EU (LVD), 2014/30/EU (EMC), 2011/65/EU (Rohs) and the following product standards for
UPS:
IEC/EN 62040-1+A1:2013, General and safety requirements for UPS
IEC/EN 62040-2:2006 Class C2 compliant
IEC/EN 62040-3: Performance requirements and test methods
When installing the UPS, always follow the instructions provided above and use the accessories supplied by the manufacturer.
According to EN 61000-3-11, the UPS system is subjected to conditional connection, and the maximum permissible system
impedance, Zmax, at the point of connection of the equipment to the supply is given by the following expressions:
Z-phase = 0.086 Ohm + j 0.054 Ohm (0.086 Ohm + 171 uH)
Z-neutral = 0.057 Ohm + j 0.036 Ohm (0.057 Ohm + 114 uH)
Hazard
High voltages are present on some parts of the UPS when it is operating, direct or indirect contact with such parts may result
in serious injury of death.
Warning
1. Disconnect mains input power and the battery and make sure that the UPS is completely shut down before moving or
rewiring it. Failure to observe the above may result in hazardous voltages being present on the UPS output terminals
2. Liquids and other foreign objects must not be introduced into the UPS.
3. In the event of a fire, use a dry, chemical fire extinguisher only. Using a foam fire extinguisher will result in electric shock.
4. The UPS output neutral line is derived directly from the input, therefore, if the neutral line is interrupted by the upstream
protection devices, the output neutral line is disconnected.
5. To prevent radio frequency interference generated by the output cables from disturbing other electrical equipment, we
recommended a maximum length of 10 m for the UPS output cables.
1. The unit must be connected to earth before it is connected to its AC mains input and battery power supplies
2. The earth leakage current ranges from 3.5mA to 100mA.
3. Transient and steady state earth leakage currents, which may occur when the equipment is started, should be taken into
consideration while selecting instantaneous RCCB (residual current circuit breaker) and RCD (residual current detector)
devices.
4. It is also necessary to take into account that the load earth leakage current of the load will be borne by the RCCB or RCD.
5. The equipment must be earthed in compliance and accordance with the local electrical code of practice.
Warning
1. When selecting the UPS system upstream distribution protection device, ensure that it complies with the local electric
regulations.
2. The specified upstream breakers are required to obtain the conditional short-circuit current rating of 10kA Icc symmetrical
rms current. The specified upstream breakers should comply with an IEC 60947 series standard.
1. The UPS does not contain any user-serviceable parts or components. Do not remove the cover. Removing the cover may
result in electric shock and will invalidate any warranty.
2. The parts of the UPS that can be accessed by the user are fully compliant with the safety requirements. Only service
personnel may be exposed to contact with the hazardous voltages present inside the UPS. However, this risk is minimized since
all parts and components where hazardous voltages may be present are protected by covers that may only be removed by
using tools. All risks may be avoided by following the general norms and operating in accordance with the procedures
described in this manual.
1. All battery service and maintenance operations shall be performed by trained technicians.
2. Batteries can cause electric shock and high short-circuit currents, therefore, ensure the following conditions are observed
before working on the battery:
Remove watches, rings and other metal objects.
Use tools with insulated handles.
Wear rubber glove and shoes.
Avoid placing tools and metal objects on the surfaces of the battery.
Disconnect the battery charger power supply before connecting or disconnecting the battery terminals.
Check whether the battery is earthed accidentally, if so, disconnect the earth connection. Contacting any part of the
battery to earth will result in electric shock. Therefore, make sure that the battery is not earthed during installation and
maintenance.
3. Battery manufacturers provide the details of the precautions to be observed when working on, or in the vicinity of,
batteries. These precautions should be followed scrupulously at all times. Attention should be paid to the recommendations
concerning local environmental conditions and the provision of protective clothing, first aid and fire-fighting facilities.
1.3.2 Components
Front panel
As shown in Figure 1-2, the UPS front panel houses the ventilation holes, operator and display panel, LED indicators and
function keys.
Rear panel
As shown in Figure 1-3, the UPS rear panel houses the parallel/LBS ports, dry contact port, I/O terminal block, battery
terminal block, Intellislot port, USB port, RS232 port, REPO port and multi function port. The SIC card in the Intellislot
port is optional and may be purchased separately, if required.
1. Intellislot port 2. Dry contact port 3. RS232 port 4. Ethernet port (blocked)
Note
Non-authorized personnel are prohibited from opening the UPS chassis cover.
Maintenance bypass
Static switch
Bypass input
Rectifier/PFC Inverter
Mains input UPS output UPS outp
Charger
Battery
1. The UPS consists of mains input (main and bypass), rectifier/PFC, battery charger, inverter, bypass, battery, DSP
controller, and output.
2. When the mains supply is within normal limits, the rectifier will be switched on, and the battery charger will recharge
the battery string. Before the UPS is switched on, the load is supplied directly from the mains input, via the bypass. When
the UPS is switched on, the electronic transfer switch connects the inverter output to the load, and the mains supplies
DC power to the inverter via the rectifier/PFC circuit. The inverter then converts the DC power into pure sine wave AC
power, which is fed to the load via the electronic transfer switch.
3. When the mains supply is outside normal limits, the rectifier/PFC circuit boosts the battery voltage and supplies it to
the inverter. The inverter then converts it into pure sine wave AC power, which is fed to the load via the electronic
transfer switch.
4. When the mains supply returns within normal limits, the UPS will automatically transfer from Battery mode to Normal
mode, so that the mains supplies DC power to the inverter via the rectifier/PFC circuit, and the electronic transfer switch
supplies AC power to the load.
1.5 UPS States and Operating Modes
For information about the LED indicators mentioned in this section, refer to 4.1.1 LED Indicators.
The UPS states and operating modes include: Normal mode, Bypass mode, Battery mode, ECO mode, Fault state and
Maintenance Bypass mode. The schematic diagrams illustrating Normal mode, Bypass mode, Battery mode and
Maintenance Bypass mode are illustrated in Figure 1-5 to Figure 1-8.
Note
Maintenance Bypass mode is valid only when the UPS power output distribution unit (POD for short) is configured.
When the mains input is within normal limits, it is processed by the rectifier and inverter in order to supply the load with
voltage and frequency-stabilized power, while the battery charger recharges the battery. This condition is known as
Normal operating mode.
In Normal mode, the run indicator (green) is on, the alarm indicator is off, and the buzzer is silenced.
Static switch
Bypass input
Rectifier/PFC Inverter
Mains input UPS output
Charger
Battery
If the overload duration is exceeded, or in the event of an inverter or rectifier failure while the UPS is in normal operating
mode, the UPS switches to Bypass mode, so that the load is supply by the bypass source, which is derived directly from
the mains input. If the rectifier is still operative, the battery charger will continue to charge the battery.
In Bypass mode, the run indicator (green) is on, alarm indicator (yellow) is on, and the buzzer beeps at one second
intervals. The 'Current' page on the LCD will indicate 'On Bypass'.
Static switch
Bypass input
Rectifier/PFC Inverter
Mains input UPS output
Charger
Battery
Note
In the event of a mains failure or if the mains voltage is outside tolerance while the UPS is in Bypass mode, the UPS will shut down
and the power supply to the load will be interrupted.
In the event of a mains failure or if the mains voltage is outside tolerance, the rectifier and internal charger will stop
running, and the battery will supply power to the load through the inverter. In Battery mode, the run indicator (green) is
on, alarm indicator (yellow) is on, and the buzzer beeps at one second intervals. The 'Current' page on the LCD will
indicate 'On Battery'.
Static switch
Bypass input
Rectifier/PFC Inverter
Mains input UPS output
Charger
Battery
Note
1. The battery has been fully charged before delivery. However, some loss of capacity is inevitable during transportation and
storage. Therefore, it is important to charge the battery for eight hours before putting the UPS into operation for the first time, to
ensure it is capable of providing adequate backup time.
2. The battery cold start function may also be used to start the UPS from the Battery (providing it is fully charged) mode in the
event of a mains failure. This means that the battery power can be used independently to improve the system availability, to a
certain extent.
1.5.4 ECO Mode (For Single UPS With External Battery Only)
In ECO mode, the load is powered by bypass when the bypass voltage is normal, and the load is powered by inverter
when the bypass voltage is abnormal. ECO mode is an energy-saving operating mode. When using the UPS to supply
equipment that is no sensitive to mains power quality, ECO mode may be used to reduce power losses.
Note
1. In ECO mode, if the bypass fails or the bypass voltage goes outside normal limits, the UPS will transfer to Normal mode (providing
the output is not overloaded). However, if the bypass fails or the bypass voltage goes outside normal limits while the output is
overloaded, the UPS will not transfer to Normal mode, but will shut down the Bypass.
2. In ECO mode, the efficiency of the UPS is increased to 99%.
In Normal mode, the UPS will transfer to Bypass mode in the event of an inverter failure or UPS over-temperature. In
Battery mode (with no bypass mains), the UPS will shut down and interrupt the output supply to the load in the event of
an inverter failure or UPS over-temperature. In the UPS Fault state, the alarm indicator (red) will remain on in the fixed
state, the buzzer will continue to beep, and the corresponding fault information will be displayed on LCD.
If it is necessary to service or repair the UPS, you can switch the load to the Maintenance Bypass using the maintenance
bypass MCB, so that the power supply to the load is not interrupted. The maintenance bypass MCB is located on the
front panel of the POD, and is rated to handle the requirements of the total load capacity. Refer to Liebert ITA2 20kVA
UPS Power Output Distribution Unit User Manual for a more detailed description of the POD.
Maintenance bypass
Static switch
Bypass input
Rectifier/PFC Inverter
Mains input UPS output
Charger
Battery
Note
In the event of UPS malfunctions or abnormal operation, contact your nearest Vertiv branch office or local service centre. NEVER
attempt to repair the UPS yourself, as this may result in injury to personnel and/or damage to equipment.
1.6 Specifications
Table 1-2 Specifications
Specifications
Item
20kVA
Rated voltage 380/400/415Vac
176Vac ~ 288Vac, at full load
Voltage range 100Vac ~ 176Vac, linear derating
Input 100Vac, at half load
Rated frequency 50Hz
Frequency range 40Hz ~ 70Hz
Power factor ≥0.99, at full load; ≥0.98, at half load
Rated power 20kW
220/230/240Vac (single phase output)
Voltage
380/400/415Vac (three phase output)
Frequency
Output synchronization Rated frequency ±3Hz. Configurable range: ±0.5Hz ~ ±5Hz
range
Frequency track
0.5Hz/s. Configurable range: 0.2/0.5/1Hz/s (single UPS), 0.2Hz/s (parallel system)
rate
Rated power factor 1
Crest factor 3:1
Voltage harmonic single UPS :2%(0-100%linear load ), 5%(0-100%non-linear load)
distortion parallel UPS : 3%(0-100%linear load ), 8%(0-100%non-linear load)
Dynamic response
Output 40ms
recovery time
Overload capacity At 25°C: 105% ~ 125%, 5min; 125% ~ 150%, 1min; 150%, 200ms
Upper limit: +10%, +15% or +20%; default: +20%
Bypass voltage
Lower limit: -10%, -20%, -30% or -40%; default: -40%
Mains efficiency up to 96%
Type Sealed, lead-acid, maintenance-free battery
Cell No. 24, 32, 40; 32 by default
Battery
Rated voltage 288Vdc ~ 480Vdc
Charge current ≤ 13A (Extended back-up model)
Mains←→Battery 0ms
Transfer Synchronous transfer: ≤0ms
time Inverter←→Bypa
Asynchronous transfer (default): ≤20ms
ss
40ms, 60ms, 80ms, 100ms and 200ms also available
Noise < 58dB
Panel display mode Colour LCD
Safety IEC/EN62040-1+A1:2013
Conduction
IEC/EN62040-2:2006
emission
EMC
Current
IEC/EN61000-3-12
harmonics
IEC/EN-61000-4-5, withstand level 4 (4kV) (live line to earth), level 3 (2kV) (between live
Surge protection lines);
ANSI C62.41, 6kV/2Ohms
Protection level IP20
Operating
0°C ~ 50°C (0.7 derating at temperatures above 50°C)
temperature
Storage
Ambient -40°C ~ +70°C (battery excluded); -25°C ~ +55°C (battery included)
temperature
conditions
Relative
5%RH ~ 95%RH, non-condensing
humidity
Altitude ≤3000m; derating at altitudes above 3000m
Dimensions W*D*H (mm) 430*500*130
Net weight (kg) 23
Weight Gross weight
41
(kg)
1. The UPS should be installed by a qualified engineer in accordance with the information provided in this section. In the event of
any problems, contact your local Vertiv service centre immediately.
2. The UPS must NOT be switched on without the approval of the commissioning engineer.
3. In the case of any equipment or items not covered by this section, refer to the specific mechanical and/or electrical installation
instructions provided with such items.
The UPS can be connected to 3-phase, 5-line (A, B, C, N, PE) TN, TT and IT AC power distribution systems (IEC60364-3).
2. Remove the cover plate from the cardboard box, and remove the UPS, as shown in Figure 2-2.
2. Check the accessories and models correspond to the shipping documents. If any problem is found, please notify the
dealer immediately.
2.2 Moving and Handling the UPS
Warning
The UPS may be moved manually, or by using a forklift truck or similar lifting equipment.
2.3 Installation Preparation
2.3.1 Location
UPS room
The UPS is designed for indoor operation, in a clean and well-ventilated environment designed to maintain the ambient
temperature within the specification limits.
The internal fans provide forced air cooling for the UPS. Cooling air enters the UPS through the ventilation holes on the
front panel, and the hot air is expelled via the ventilation holes on the rear panel. For this reason it is very important not
to obstruct the ventilation holes. Maintain at least 200mm clearances between the front, rear of the UPS and the wall or
adjacent equipment (see Figure 2-3), in order to avoid obstructing the UPS ventilation holes and preventing heat
dissipation. Otherwise, the UPS internal temperature will rise, which will shorten the UPS life.
If necessary, an indoor exhaust fan should be installed to prevent the indoor temperature from rising. An air filter should
be used when the UPS is to be operated in a dusty environment.
Reserved space
Wall
500mm
Cabinet
200mm
Note
Battery room
A small amount of hydrogen and oxygen will be generated at the end of the battery charging cycle, therefore it is
important to ensure that the battery installation environment fresh air ventilation capacity meets the EN50272-2001
requirements.
The battery ambient temperature should maintained constant, since ambient temperature is the main factor affecting
battery capacity and working life. The standard battery operating temperature is 20°C, operating it above this
temperature will shorten battery life, while operating it below this temperature will reduce battery capacity. If the average
battery operating temperature rises from 20°C to 30°C, the battery life will be reduced by 50%; if the battery operating
temperature exceeds 40°C, battery life will decrease exponentially. In general, the permitted ambient temperature of the
battery is 15°C ~ 25°C. The battery should be kept away from heat and ventilation holes.
When the UPS uses an external battery, you must install a protection device (such as fuse or circuit breaker) close to the
battery, and keep the wiring distance between the battery and the protection device to a minimum.
Storage environment
When the UPS is not to be installed immediately, it must be stored indoors in an environment where it is protected from
the excessive moisture and/or high temperatures. The battery should be stored in a cool, dry, well-ventilated environment
for storage; the most suitable storage temperature is 20°C ~ 25°C.
During the storage period, the battery must be charged at regular intervals, in accordance with the battery instructions. When
charging the battery, you can connect the UPS to the mains temporarily to charge the battery and activate it.
Warning
1. For reasons of safety, all installation tools used on live components must be insulated.
2. The tools listed in Table 2-1 are for reference only; please adapt to the actual requirements for on-site installation and
connection.
Stepladder Forklift
Overcurrent
The appropriate over-current protection device should be installed on the mains input power distribution line, and the
current capacity of the power cable and the system overload requirements should be taken into account during the
installation procedure (see Table 2-2).For information about the thermo-magnetic circuit breaker, see Table 2-4.
Split-bypass
In the case of split-bypass configurations, separate protection devices should be installed on the mains and bypass
lines at the mains input power distribution.
protection cable, the coil is energised (12 V - COM), and the relay contact is closed. The relay A contact controls the UPS
main input shunt trip coil (L - N), so that it, in turn, is energised when the contact is closed. When the shunt trip coil is
energised, it triggers the UPS mains input CB, thus interrupting the back-feed path and guaranteeing the protection. In
this way, the bypass can continue to supply power to the load even in the presence of mains back-feed.
(2) Bypass back-feed
The bypass relay and dry contact are highlighted in GREEN in the Figure. The internal UPS sensor detects back-feed at
the bypass input terminals, UPS Dry Output Contact 2 is closed. Since the dry output contact is connected to the POD
internal relay B coil terminals via the back-feed protection cable, the coil is energised (12 V - COM), and the relay contact
is closed. The relay B contact controls the UPS bypass input shunt trip coil (L - N), so that it, in turn, is energised when
the contact is closed. When the shunt trip coil is energised, it triggers the UPS bypass input CB, thus interrupting the
back-feed path and guaranteeing the protection. In this way, the mains can continue to supply power to the load even in
the presence of bypass back-feed. Figure 2 shows the wiring diagram between 1 + 1 parallel POD and two UPS. The
back-feed protection principle in this configuration is the same as that for the single POD, the only difference being the
number of CB and the back-feed protection cable, which is not shown in detail in this case.
Note that the POD internal relays A, B, and the 12V voltage generator circuit are included on the same internal control
board; the position shown in Figure is purely indicative. The attachment is the specification of the internal shunt trip and
the internal control board.
Warning
1. The same neutral line must be used for the rectifier and bypass input power.
2. In the case of IT power grid systems, the 4-pole protection device for 3-phase UPS must be installed at the UPS external I/O
power distribution point, while the 2-pole protection device for 1-phase UPS must be installed at the UPS external I/O power
distribution point.
When using the earth RCD in split-bypass or parallel systems, the RCD should be located at the upstream input power
distribution point to avoid spurious operation.
The earth leakage current fed by the RFI filter in the UPS ranges from 3.5mA to 100mA. We recommend confirming the
sensitivity of each differential device in stalled on the upstream input power distribution and downstream power
distribution (load) lines.
Vertiv battery module options are provided with built-in over-current protective devices. Otherwise, the external battery
cabinet should fitted with a DC compatible circuit breaker in order to provide over-current protection for the UPS and its
batteries.
The protection device must be installed on the UPS output power distribution line. The protective device specification is
shown in Table 2-4.
2.5 Mechanical Installation
Two installation versions are available: tower installation and rack installation. Select the suitable installation version,
depending on the actual conditions.
1. Select the support bases from the accessories, assemble a pair of support bases and a support base extension using
the fastenings, as shown in Figure 2-7, and place them on a flat installation surface.
Fastening
Support base
2. If it is also necessary to install the battery module, select the other support base extensions delivered with the battery
module, and then assemble the support base extensions and the support bases using the fastenings, as shown in Figure
2-8.
Fastening
Support base extension
Support base
Figure 2-8 Connecting the support base to the support base extension
3. Place the UPS on the support bases and support base extensions, as shown in Figure 2-9.
UPS
UPS
Support base
Figure 2-9 Complete UPS and battery module Installation
Screw (8pcs)
Bracket (2pcs)
Note
Guide
Guide rail rail
screwscrew
b) Adjust the length of the guide rail according to the dimensions of the rack.
c) Align the installation holes on the guide rail with the square holes on the rack, secure the guide rail to the rack using
the guide rail screws (eight in total), each guide rail requires four guide rail screws, as shown in Figure 2-13.
Guide rail
Note
1. The guide rail holder must be close to the front of the rack.
2. Each end of the guide rail has four installation holes (see Figure 2-9), do not use the two installation holes in the middle when
securing the guide rail. We recommend using the top and bottom installation holes (from top to bottom, installation hole 1 and
installation hole 4).
This completes the guide rail installation procedure, as shown in Figure 2-14.
3. Position the UPS on the guide rails, and push it completely into the rack. Use four M6 × 16 screws to secure the UPS in
the rack using the brackets, as shown in Figure 2-15.
Guide rail
Rack
UPS
Bracket
Screw (4pcs)
UPS
When selecting the battery cables, the maximum permissible voltage drop is 4 Vdc, according to the current value shown
in this table. Avoid coiling the cables as this would increase the electromagnetic interference (EMI).
1: The input mains current of the rectifier and the bypass.
2: Non-linear loads (switch mode power) affect the design of the output and the bypass neutral cable. The neutral cable
current may exceed the rated phase current by a factor of up to1.732.
Table 2-3 Single UPS cable CSA (unit: mm2, ambient temperature: 25°C)
Neutral
Model Input Output Bypass PE Battery Battery PE
cable
20kVA (3-in 3-out) 10 10 10 10 10 10 10
20kVA (3-in 1-out) 10 25 25 25 25 10 10
15 kVA (3-in 3-out) 10 2.5 2.5 10 10 10 10
15 kVA (3-in 1-out) 10 16 16 16 16 10 10
10 kVA (3-in 3-out) 4 1.5 1.5 4 4 4 4
10 kVA (3-in 1-out) 4 10 10 10 10 4 4
The recommended I/O MCB capacity of the UPS is listed in Table 2-4; select the MCBs according to your requirements.
Note
The UPS generates high leakage currents, therefore we do not recommended using MCB with leakage current protection.
Note
The specified upstream breakers below are required to obtain the conditional short-circuit current rating of 10kA Icc symmetrical
rms current. The specified upstream breakers should comply with an IEC 60947 series standard.
1. The 3-in 3-out bypass MCB (125A) is used to connect the bypass input in the case of split-bypass configurations. The
main MCB may only be used in the case of common input configurations.
2. The battery CB should be rated at 250Vdc or above.
The UPS power cables should be connected via the I/O terminal block located on the UPS rear panel. As shown in Figure
2-17.
Output terminals
PE PE
sC sB sA N N pC pB pA
BAT N
BAT+
BAT-
PE N N bC mC bB mB bA mA
Note:
Output terminals--Mains input terminals: sA, sB, sC; Programmable input live wire terminals:
pA, pB, pC; Output PE terminal: PE.
PE; Common N: N.
Input terminals--Mains input terminals: mA, mB, mC; Bypass input terminals: bA, bB, bC;
Common N: N; Input PE terminal: PE.
Battery terminals--BAT1+, BAT1-,
BAT+, BAT BAT2+,
N, BAT-; BAT2-;
Battery PEBattery PEPE.
terminal: terminal: PE.
The shorting copper bar of the 3-in 3-out (common input) has been linked before delivery.
Note
After connecting the power cables, replace the protective cover on the I/O terminal block in order to prevent electric shocks.
The connection procedures for the four types of self-distribution I/O cables are as follows:
3-in 3-out, common input configuration
1. Before delivery, the terminals mA and bA, mB and bB, mC and bC, respectively, on the UPS I/O terminal block are short
circuited using the three copper shorting bars 1.
2. Connect the mains input live cables (L1, L2, L3), input N line and input PE line respectively to the I/O terminal block
(mA, mB, mC, N and PE terminals) on the UPS.
3. Connect the standard output live cables (phase-A, phase-B and phase-C) to the output terminals sA, sB and sC,
respectively. Connect the programmable output live cables (phase-A, phase-B and phase-C) to the output terminals pA,
pB and pC, respectively. Connect the output N line and output PE line to the output N and PE terminals, respectively. As
shown in Figure 2-18.
4. As shown in Figure 2-18, route the positive battery cable, N battery cable, negative battery cable through the cable hole
on the junction box, then connect them to the BAT+, BAT N, and BAT- terminals, respectively, as well as the PE cable, and
tighten the retaining screws.
PE sC sB sA N N pC pB pA PE
PE
1 1 1
bC mC bB mB bA mA
N N L3 L2 L1
BAT N
BAT-
BAT+
Figure 2-18 Wiring diagram (3-in 3-out, common input configuration)
PE
N N
mB
mC
mA
BAT N
bC
bA
bB
BAT-
BAT+
4. Connect the standard output live cable (sL) to the copper shorting bar 2 (sA, sB and sC). Connect the programmable
output live cable (pL) to the copper shorting bar 2 (pA, pB and pC). Connect the output N line and output PE line to the
output N and PE terminals, respectively. As shown in Figure 2-20.
5. As shown in Figure 2-20, route the positive battery cable, N battery cable, negative battery cable through the cable
hole on the junction box, then connect them to the BAT+, BAT N, and BAT- terminals, respectively, as well as the PE
cable, and tighten the retaining screws.
PE sL N pL PE
sC sB sA N N pC pB pA
2 5 2
PE 1 4
N N bC mC bB mB bA mA
N L3 L1 L2
BAT N
BAT-
BAT+
sC sB sA N N pC pB pA
2 5 2
PE 1 3
N N bC mC bB mB bA mA
L3 bL L2 L1
BAT N
N
BAT-
BAT+
5. As shown in Figure 2-21, route the positive battery cable, N battery cable, negative battery cable through the cable hole
on the junction box, then connect them to the BAT+, BAT N, and BAT- terminals, respectively, as well as the PE cable, and
tighten the retaining screws.
Warning
The following wiring will change the power distribution mode, please adhere scrupulously to the procedures described below.
1 1 1
2. Remove the EPO jumpers from the REPO dry contact port.
3. Switch the system on. Set the system to '3phase' by selecting ENTER -> 'Settings' (default password: 111111) -> ' Output'
-> 'Output phase No.', and then switch the system off completely and switch it on again, access the above menu again to
verify that the setting is valid.
4. Switch the system off completely, replace the EPO jumpers on the REPO dry contact port, and disconnect the main
input cables.
From 3-in 3-out to 3-in 1-out
1. Remove all the three copper shorting bars 1 (3-in 3-out, common input configuration)that were installed before delivery;
then install the copper shorting bars (1, 2, 4, 5), see Figure 2-23. Connect all the cables.
2 5 2
1 4
2. Remove the EPO jumpers from the REPO dry contact port.
3. Switch the system on. Set the system to '1phase' by selecting ENTER -> 'Settings' (default password: 111111) -> ' Output'
-> 'Output phase No.', and then switch the system off completely and switch it on again, access the above menu again to
verify that the setting is valid.
4. Switch the system off completely, and restore the EPO jumpers on the REPO dry contact port.
Warning
Prior to the commissioning engineer's visit, if the load is not ready to be connected to the power supply, it is important to ensure
the terminals of the output cables are insulated safely.
After the connecting the output cables, locate the label (using the 20kVA model as an example) shown in Figure 2-24 on
the top cover of the UPS and tick the 'AC OUTPUT' and 'BYPASS INPUT' boxes corresponding to the installation
configuration, in order to simplify maintenance operations.
Notes
1. Before connecting the battery cables, confirm that the actual number of battery cells and the battery capacity are
consistent with the parameter settings on the LCD menus.
2. NEVER reverse the polarity of the battery cables.
3. Before replacing the battery module and connecting the battery cables, disconnect the DC battery MCB, switch the
UPS off completely, and insulate the terminals.
4. We recommend a maximum battery cable length of three metres. If the cables are longer than this, the UPS may not
operate correctly.
Installing the battery insulating plates
The battery terminals must be fitted with insulating plates in order to guarantee sufficient insulation distance between
the external battery cable connections and prevent faults such as arcing, and short circuits
To install the battery insulating plates, proceed as follows:
1. First crimp the user external cable to the battery terminals, Figure 2-30 shows the OT terminals.
2. Crimp the battery insulating plates, and use the screws to fasten the OT terminals and insulating plates together onto
the terminal block.
Note: The OT terminals and insulating plates installation sequence must be observed scrupulously, otherwise the
user external cable connections will be separated.
Warning
1. As shown in Figure 2-24, one DC battery MCB must be installed between the battery strings and the UPS.
2. The battery string delivers a high DC voltage, the capacity of the MCB and output cables is listed in Table 2-4.
Battery BAT+
module
Battery
module
BAT-
Terminal A
BAT+
BAT N Second group of battery module
BAT-
PE
Cables between battery module and Terminal A
ITA2 UPS (ITA-BCI0020K02L3)
Figure 2-28 Cables between UPS and battery modules (unit: mm)
The cable connections between the battery module and 20kVA UPS are shown in Figure 2-28.
BAT N
PE BAT- BAT+
ITA-BCI0020K02L3
Terminal A
Terminal B
Terminal A
ITA-BCI0
020K02L2 Terminal B
Terminal A
Terminal B ITA-BCI0020K02L2
Terminal A
Terminal B
Figure 2-29 Cable connection diagram between the battery module and UPS
1. Check and confirm that the UPS and POD power distribution mode (if configured) is correct, that the power and
signal cables are connected correctly, and there are no short circuits.
2. Check that the batteries have been installed properly, the cable have been connected correctly, and that the positive
and negative battery poles are correct.
3. Measure the mains voltage and frequency, and verify that they are correct.
4. The UPS and POD (if configured) output terminals are energised when the UPS is switched on. If the load is already
connected to the output terminals, make sure that it is safe to apply power to it.
The first time the system is started up, mains input mode only may be used, and the LCD screen will display the start-up
interface, see Figure 2-30.
1. Close the UPS external output MCB and input MCB one by one. If the single POD is selected for connection to the UPS,
close the input MCB, bypass MCB and output MCB on the POD.
Warning
After closing the UPS external output MCB or the POD output MCB, the output terminal block of the UPS, output terminal block of
the POD and power distribution end of the load will be live, pay attention to personnel safety to avoid electric shock. Verify whether
it is safe to feed power to the load.
2. The rectifier runs in normal state for about 30 seconds, after which the rectifier start-up phase is complete.
3. Finish setting up the single UPS parameters and check them.
a) Access the main menu screen, press the or key to select 'Settings', and press the key to access the
interface shown in Figure 2-31.
b) Press the or key to select and set-up corresponding parameters (taking 'Output' as an example). As shown
in Figure 2-32.
4. After setting up the corresponding parameters, press the power button for two seconds so that the dialogue box
shown in Figure 2-33 appears on the LCD screen.
Confirm
S Turn on UPS? ol
NO YES
After selecting 'YES', the run indicator (green) blinks, the inverter starts, and the run indicator switches on.
5. Measure the inverter output voltage and verify whether it is within normal limits.
6. If the battery is not connected, the alarm indicator will be coloured yellow. If the battery is connected, the alarm
indicator will be extinguished.
1. Close the battery MCB, and press the power button on the UPS front panel for two seconds, the LCD displays the
start-up screen. The alarm indicator will be coloured yellow and the buzzer will beep continuously after the rectifier
completes the start-up phase.
2. Press the power button for two seconds so that the dialogue box shown in Figure 2-34 appears on the LCD screen.
After selecting 'YES', the inverter starts, and the run indicator (green) is illuminated.
40 User Manual 10H52261UM60 - Rev. 1 - 10/2017
ITA2
POD (1Piece)
UPS (2PCS)
The UPS power cables are connected to the I/O terminal block on the rear panel of the UPS, the layout of the I/O terminal
block is shown in 2.6.1 Connecting I/O Cables.
Power distribution mode
There are two UPS parallel power distribution modes: using the 1 + 1 parallel POD (optional) provided by Vertiv, and
self-distribution.
The parallel system power distribution mode is the same as that of the single unit, refer to 2.6.1 Connecting I/O Cables.
1. Using parallel POD power distribution
We recommend using 1 + 1 parallel POD power distribution mode if you require a 1 + 1 parallel system, for the information
on installing and commissioning different models, refer to the Liebert ITA2 20kVA UPS Power Output Distribution Unit
User Manual.
2. Self-distribution for the parallel system
When the parallel system consists of more than two UPS units, select self-distribution mode.
See Figure 3-2 for a block diagram of a three UPS parallel system. Refer to Power distribution mode in
2.6.1 Connecting I/O Cables for the cable connection to each UPS. Refer to 2.6 Connecting Power Cables for the input
and output MCB, the battery MCB and the cables when using the self-distribution mode.
UPS1
UPS3
Warning
Configure each UPS with an external input MCB and an external output MCB when installing the power distribution for the parallel
system, as shown in Figure 3-2.
Note
After connecting the power cables, replace the protective cover on the I/O terminal block in order to prevent electric shocks.
The parallel system provides a parallel cable option. The parallel cables form a ring connection via the parallel ports on
the rear panel of the UPS. See Figure 3-3 for a cable connection diagram of a 3 + 1 parallel system.
UPS1
UPS2
UPS3
UPS4
Note
1. The Vertiv parallel cables must be used for the parallel system.
2. If a parallel communication fault occurs during parallel commissioning or operation, switch the system off and check whether the
parallel cables are connected correctly.
3. Do not attempt to disconnect the parallel cables while the parallel system is operating as this could damage the system.
In the parallel system, the UPS units use common or separate battery strings.
Note
Each UPS should be equipped with an independent battery MCB. Refer to Table 2-4 when selecting the battery MCB.
Note
Make sure that the LCD settings are correct when using separate battery strings for a parallel system, refer to
3.5.2 Parallel System Parameters Settings for details.
Battery BAT+
module
Battery
module
BAT-
Parallel
cable
Battery BAT+
module
Battery
module
BAT-
Note
1. If the battery strings (four standard battery modules, option) are connected in common mode in a parallel system, the backup time
of the battery module ranges from two minutes to three minutes at full load.
2. To ensure sufficient battery backup time, we recommend use an external battery cabinet having a large capacity.
Wiring
Switch the parallel system off completely, disconnect all the individual UPS unit battery MCB devices, and then use the
battery cables (refer to 2.6 Connecting Power Cables for the respective cables and the MCB devices) to connect the '+',
'N', '-' and 'PE' terminals of the battery strings to the respective 'BAT+', 'BAT-', 'BAT N' and 'PE' terminals on the
corresponding I/O terminal block of the UPS units in the parallel system, via each battery MCB, as shown in Figure 3-5.
UPS1 UPS2
UPS2
BAT N
BAT N
BAT+
BAT+
BAT-
BAT-
PE
UPS
UPS11MCB
MCB UPS2
UPS2 MCB
MCB
+ - PE + - PE
Figure 3-5 Connection diagram for common battery string in 1 + 1 parallel systems
Refer to Figure 3-6 when configuring the positive battery and negative battery strings.
First
1st cell
block 2nd block
Second cell 3rd block
Third cell Sixteen
16th cell
block
Battery module
module
+ + + + Bat +
BAT+
……
Battery
cabinet
- - - -
Battery cabinet
Bat -
BAT-
Battery
PE
PE
Figure 3-6 Internal connection diagram for positive battery and negative battery strings
1. Check and confirm that the UPS and 1 + 1 POD (if configured) power distribution mode is correct, that the power and
signal cables are connected correctly, and there are no short circuits.
2. Check that the batteries have been installed and connected correctly, that there are no short circuits and that the
battery positive and negative poles are correct. It is especially important to check the above items when the parallel
system UPS units share a common battery string.
3. Check the complete working status of the parallel system, ensure that the phase sequence of the main, bypass and
output of each UPS is correct and consistent, that the parallel cable is connected securely, and that the user load is not
connected during switch-on
4. Measure the mains voltage and frequency, and verify that they are correct.
5. The UPS and 1 + 1 parallel POD (if configured) output terminals are energised when the UPS is switched on. If the load
is already connected to the output terminals, make sure that it is safe to apply power to it.
Warning
The UPS and POD (if configured) output terminals are energised when the UPS is switched on. When bypass of the individual UPS
units in the parallel system is not consistent,a system fault may occur, check and confirm the bypass before switching on.
It is necessary to set-up the parallel parameters for all the UPS units in the parallel system. As shown in Figure 3-7.
Redundant YES
System parallel num 1
The user can change these settings according to actual needs, refer to Appendix 1 LCD Parameters Setting for details.
After modifying parameters, press “Sync parallel parameters” to confirm the settings.
1. Set-up the parallel parameters for each UPS in the parallel system, then commission the inverter.
The specific commissioning procedures are as follows:
a) Make sure that the output MCB devices on each UPS unit in the parallel system are open, and then close the external
input MCB on each UPS, at this point, all the UPS are switched on. If 1 + 1 parallel POD is configured, close the
corresponding input MCB and bypass MCB. At the same time, close the corresponding output MCB on the other UPS
under test, and make sure that the corresponding output MCB on the other UPS is open.
Warning
After closing the UPS external output MCB or the POD output MCB, the UPS output terminal block, POD output terminal block and
load will all be live, pay attention to personnel safety to avoid electric shocks. Verify whether it is safe to supply power to the load.
b) The LCD displays the self check screen, and the alarm indicator (red) and run indicator (green) are on simultaneously
for about five seconds.
c) The rectifier runs in normal state for about 30 seconds, after which the rectifier start-up phase is complete.
d) Refer to 3.5.2 Parallel System Parameters Setting for the parallel parameters setting for each UPS. Check whether
the 'Parallel comm. Fail’ alarm is active, if yes, clear the fault as indicated in Table 4-5. Carry out the following procedures
if the UPS is running normally.
e) Press the power button on one the UPS units for 2 seconds, if 1 + 1 parallel POD is configured, press the power button
on the UPS under test in the parallel system, then press Enter key to start the UPS. The run indicator (green) will blink,
after 20 seconds, the inverter will start, and the run indicator will switch on, if 1 + 1 parallel POD is configured, the other
UPS will display no redundancy in parallel, ignore the prompt for the moment.
f) If the battery is not connected, the alarm indicator on in fixed mode, and the buzzer will beep once a second. If the
battery is connected, the alarm indicator will be extinguished.
g) If the UPS is working normally, press the power button for two seconds to switch the inverter off.
h) Repeat the preceding steps a) ~ step g) to switch on and commission the other UPS inverters.
Note
Carry out the parallel commissioning procedures once each UPS is running normally.
2. After confirming that the inverter of each UPS functions normally, commission the parallel system; the specific
procedures are as follows:
a) Close the external output MCB and input MCB on each UPS, so that all the UPS units are switched on at the same time.
Once the rectifier start phase is complete, press the power button on one UPS for two seconds, the run indicator (green)
will switch on. Measure the inverter output voltage and verify whether it is within normal limits. If 1 + 1 parallel POD is
configured, close the corresponding input MCB and bypass MCB and output MCB on the POD.
b) Start the second UPS inverter, check whether the LCD for alarms, and confirm that the UPS parallel works normally.
c) Repeat the inverter start-up procedures for the third or fourth UPS in order to connect the UPS into the parallel
system.
Warning
1. During the parallel start-up phase, confirm that the external output MCB on each UPS has been closed, and that the outputs of all
the UPS inverters are connected in parallel.
2. During the parallel start-up phase, confirm that the system is working normally, then supply power to the load in order to avoid
load power failure.
3. If it is necessary to add a UPS to the parallel system, carry out the commissioning procedures described below:
a) Check and confirm the power distribution mode, and that all the power and signal cables are connected correctly to
the additional UPS, and that there are no short circuits. Check that the batteries have been installed and connected
correctly, that there are no short circuits and that the battery positive and negative poles are correct.
b) Repeat Part 1, steps a) to h) to complete commissioning the additional UPS. Switch off the UPS completely.
C) Ensure that the power and signal cables are connected securely.
d) Close the external input switch on the additional UPS, after starting up the UPS; access the interface shown in Figure
3-7 on any of the UPS units in the parallel system. Set the system parallel No. from 'N' to 'N+1', then click 'Sync parallel
parameters'.
e) Close the external output switches on the additional UPS, start the inverter in normal mode, after the rectifier start-up
phase is complete. Next, check that there are no alarms indicated on the LCD, and that the UPS parallel system is
working normally.
Note
1. In the case of 1+1 parallel systems, when one UPS is faulty and needs to be replaced on line, the procedure described above may be
used. The only difference in this case is that there is no need to change the parallel No., simply click 'Sync parallel parameters' for the
replacement UPS.
2. Clicking 'Sync parallel parameters' synchronises the items in the parallel settings interface, so that the parameters are applied to
the parallel system. The user should set-up up the other parameters manually, as required.
3. When parallel system output is active, the 'Sync parallel parameters' function can only be executed via a UPS with the output
switched on, otherwise this function is invalid.
4. When adding a single unit to a parallel system, first ensure that the parallel cables are connected correctly, then switch the
additional unit on.
The dual bus system consists of two independent UPS systems; each UPS system consists of one or two
parallel-connected single UPS units, or multiple parallel-connected single UPS units.
The dual bus system provides high reliability, which makes it suitable for use with loads having multiple input terminals.
In the case of single input UPS loads, it is possible to add and optional static trigger switch (STS) in order to start the
standard Load Bus Synchronization (LBS) system.
Place the UPS units side by side, and connect them as follows:
The dual bus system uses the LBS system to synchronise the outputs of two independent (or parallel) UPS systems. One
is the master system, while the other is the slave system. The dual bus system operating mode includes the master
system and/or slave system running in Normal mode or Bypass mode. Figure 3-8 illustrates the circuit diagram of the LBS
consisting of two UPS units.
Bypass input
Bypass
Mains input
UPS1
Mains
To load
LBS cable STS
Bypass input
Bypass
Mains input
UPS2
Mains
Note
Refer to 3.5 Commissioning Parallel System for the parallel system settings.
See 2.4 External Protective Devices for details of installation and type selection.
In the case of dual bus systems, refer to 2.6 Connecting Power Cables and 3.4 Connecting Power Cables when
selecting the power cables for single UPS and the parallel system, respectively. The bypass input power and main input
power must use the input terminal of the same neutral line. If the input terminal has leakage current, the leakage current
protective device should be installed upstream of the input terminal.
Note
1. The appearance of the LBS port is the same as the parallel port (see Figure 1-3).
2. In the case of dual bus systems consisting of parallel UPS units, we recommend preparing two LBS cables for connecting any two
parallel/LBS ports of the two parallel system, in order to guarantee a secure connection.
UPS1
UPS2
The LBS is the load synchronisation system, and is used to synchronise the output voltage phases of the two sections of
the UPS system. The two sections of the UPS system may consist of two single UPS units, or two UPS parallel systems.
'Master' and 'Slave' may be set-up manually via the LCD screen.
The UPS selected as the LBS master can send synchronization signals to LBS slave based on its inverter voltage phase.
After the slave receives the synchronization signal sent by the master, it will adjust its inverter voltage phase so that it is
synchronised with the master.
Thanks to this system, it is possible to synchronise the two sections of the UPS system, guaranteeing reliable transfer
between the respective output voltages and the STS, and hence a reliable, uninterrupted power supply to the load.
Note: The device includes a gravity sensor function, so that the LCD display direction will adapt to the device
layout mode.
The LED indicators consist of the run indicator and alarm indicator. Table 4-1 provides a description of these indicators.
UPS operation is accompanied with the following two different kinds of audible alarms, as described in Table 4-2.
Table 4-2 Description of audible alarms
Sound Meaning
This sound is generated in the event of a UPS fault condition, such as a fuse or hardware
Continuous beep
failure
This sound is generated in the event of a critical UPS alarm condition, such as an Inverter
One beep every 0.5 seconds
overload
This sound is generated in the event of a critical UPS alarm condition, such as low battery
One beep every second
voltage
One beep every 3.3 seconds This sound is generated in the event of a general UPS alarm condition
The operator and display panel includes five function keys, the respective functions are described in Table 4-3.
Table 4-3 Description of control buttons
Function key Silkscreen Description
The LCD includes a user-friendly interface and a 320 × 240 dot matrix image display. Thanks to the user-friendly,
menu-oriented LCD it is possible to browse easily through the UPS input, output, load and battery parameters, obtain
information about the current UPS status and alarm messages, as well as performing functional setting and control
operations. The LCD also stores historical alarm records that can be retrieved for reference and diagnosis.
When the UPS is the initial start-up phase, the interface shown in Figure 4-3 will appear to guide the user through the
basic UPS parameter setting procedure.
Welcome page
Click Next to start the guide procedure.
Language, date and time page
On this page, you can set-up the language, date and time as required.
If there is an external battery module, the 'Local battery total Ah' will not appear, see Figure 4-6.
Output page
As shown in Figure 4-8, you can set-up the output voltage, output frequency, and output phase.
In the case of 20kVA models, the 'Output phase No.' may be set to 'single' or '3 phases'. See the right hand diagram in
Figure 4-7.
Note
In the case of the output page, the REPO terminal (forcible output shut-down) must be unplugged when carrying out the settings,
otherwise the interface shown in Figure 4-8 will appear.
End page
In the case of 20 kVA models, the interface shown in Figure 4-10 will appear. This means that the function keys and LCD
are invalid; the user cannot continue with the operation. Please switch the UPS off based on the prompt shown in Figure
4-9, confirm that the actual wiring method applied to the output terminal is consistent with the method selected during
the set-up procedure, and then switch the UPS on again.
After start-up the user will be able top operate the UPS normally.
When the UPS is started up it performs a system self-test, during which the Start Screen is displayed for approximately
10 seconds, as shown in Figure 4-11.
Once the UPS self-test is complete, the flow screen shown in Figure 4-12 will appear.
The flow screen provides a total status overview of the UPS, including the input, bypass, rectifier, battery, inverter and
output, etc. Operating modes are displayed in colour, while invalid are displayed in grey.
228.0V 228.1V
49.9Hz 49.8Hz
229.2V 0%
49.8Hz No battery
Press the key on the flow page to access the primary screen.
The main menu screen consists of six icons: Status, Settings, Control, Log, About, Maintain. As shown in Figure 4-13.
Press the key on the main menu screen to return to the flow screen. Press the or key to move the cursor
and select the required sub-menu, then press the key to confirm it.
The sub-menu screen contains the UPS parameters and item settings.
After accessing the sub-menu screen, if there is a tab control, just move the cursor to the tab. At this point, you can press
the or key to switch the tab. Press the key to move the cursor to a specific item.
After accessing the sub-menu screen, if there is no tab control, the cursor will stop on a certain Item.
Settings page
The Settings page can be used to access the Output, Battery, Parallel, Monitor, System, and Outlet settings. For details
about the setting up the parameters, refer to Appendix 1 LCD Parameter Settings.
See below:
Control page
The Control page may be used to access the Turn ON/OFF/to BYPASS, Manual battery test, etc. functions. See below:
Log page
The Log page can be used to access a list of current and historical UPS events. See below:
Current History
About page
The About page contains information about the Product, Network, and Efficiency. See below:
Maintain page
Note
The Maintain page is password protected and reserved for use by Vertiv service engineers only.
During the UPS operation, if there is no alarms for two minutes, the display will revert to the default as shown in Figure
4-14. While the Default screen is displayed, if there are no alarm or fault conditions active, the Flow screen will be
displayed if the user presses any key.
If the alarm is generated as the result of a software value set-up by an authorised Vertiv engineer, and you wish to modify
the setting, please get in touch with your local Vertiv customer service centre.
During operation, the buzzer alarm may be activated, if so, can press the key for three seconds to silence the
audible alarm.
Warning: hazardous mains and/or battery voltage exists behind the protective covers
1. No user serviceable parts are located behind the protective covers that can only be removed by using tools.
2. Only qualified service personnel are authorized to remove such covers.
3. If it is necessary to carry out maintenance operations on the rack, it is important to bear in mind that the neutral line remains live.
Warning
This procedure results in mains voltage being applied to the UPS output terminals. Confirm that it is safe to apply power to the
load, if there is a load to be connected to the UPS output terminals. If the load is not ready to accept power, isolate it from the UPS
output terminals.
The single UPS start-up modes include normal start-up mode and battery start-up mode; refer to 2.7.3 Normal Start-Up
Mode and 2.7.4 Battery Start-Up Mode for details.
5.2 Procedures for Transferring between Operating Modes
Note
The Inverter operating modes include Normal mode (inverter supplied by mains) and Battery module (inverter supplied by battery).
In the event of a mains failure, the UPS will transfer to Battery mode. If you wish to transfer the UPS from Battery mode
to Normal mode, wait few seconds for the mains input to recover. After about ten seconds, the rectifier will restart
automatically, and the inverter will restore the power.
In standby mode, press and hold the power button. If the rectifier and inverter are normal, the interface shown in Figure
5-1 will appear, select 'YES' to switch the UPS on.
In Inverter mode, press and hold the power button. If the bypass is normal, the interface shown in Figure 5-2 will appear.
Select 'To Bypass' and click OK to transfer the UPS to Bypass mode; select 'Turn off UPS' and click OK to turn switch the
UPS off.
In Inverter mode, press and hold the power button. If the bypass is abnormal, then the interface shown in Figure 5-3 will
appear, select 'YES' to shut down the UPS output.
Note
In Bypass mode, the load is supplied with power derived directly from the mains input, rather than the conditioned power from the
inverter output.
For detailed information about Normal mode, Bypass mode, and Battery and Maintenance Bypass mode, please refer to
1.5 UPS State And Operating Mode.
Select 'Turn on UPS' and click OK to transfer to Inverter mode, see Figure 5-5.
Select 'Turn off UPS' and click OK to shut down the UPS output.
If ECO mode is enabled, the interface shown in Figure 5-6 will appear. Select 'YES' to shut down the UPS output.
When the UPS is running in Normal mode, you can use this procedure to transfer the load from inverter output to
maintenance bypass.
70 User Manual 10H52261UM60 - Rev. 1 - 10/2017
ITA2
Caution
1. Before performing this procedure, you should check the LED information first, and make sure the bypass is normal and
synchronized with the inverter. Failure to do so may result in a brief interruption in the power supply to the load.
2. You should select the single POD, or prepare the maintenance bypass MCB, in order to execute this function.
1. Access the LCD settings page and change Dry contact 3 to 'Maintain mode'. See Figure 5-7.
2. Remove the maintenance bypass switch baffle retaining screws, rotate the baffle upwards until it is locked in position,
and then fasten the retaining screws.
At this point, the system Interlock function has been activated and the UPS will transfer to internal bypass mode; you
should confirm that the UPS has been transferred to internal bypass mode.
3. After confirming, close the maintenance bypass switch.
Following UPS maintenance operations, this procedure may be used to transfer the load from the maintenance bypass to
the inverter.
Warning
If the maintenance bypass switch has been configured by the user, following UPS maintenance operations the user must transfer
the UPS to bypass mode manually, and then close the output switch. Failure to observe this may cause damage to the equipment.
1. Confirm that the maintenance bypass switch baffle has been rotated upwards and secured in position.
2. Close the mains input MCB and bypass input MCB on the front panel of the POD. At this point, the UPS will switch on
again and operate in bypass mode.
3. Confirm that the UPS is operating in Bypass mode, then close the output MCB on the front panel of the POD.
4. Open the maintenance bypass MCB on the front panel of the POD. Return the maintenance bypass switch baffle to its
original position, then fasten the retaining screws.
5. Press the power button on the operator and display panel of the UP so that the UPS transfers to Inverter mode.
5.3 Complete UPS Shut-down
In the case of UPS systems with POD, if you need to shut down the UPS completely, transfer the UPS from Inverter mode
to Maintenance Bypass mode, as described in para. 5.2.4 Transferring From Inverter Mode To Maintenance Bypass
Mode, so as to avoid affecting the power supply to the load during the UPS shut-down procedure. Then, if it is not
necessary to maintain the power supply to the load, open the maintenance bypass MCB directly, as shown in Figure 5-8.
CB1 SW CB2
In the case of UPS systems where the power distribution system has been set-up by the user, if it is necessary to isolate
the UPS from AC power, open the external input MCB. (If the main and bypass inputs are connected to separate mains
supplies, open both input MCB devices).
Warning
5.4 REPO
The REPO port, located at rear of the UPS, is designed to switch off the UPS in the event of an emergency (such as fire,
flood). The system will switch off the rectifier and inverter, and interrupt the power supply to the load immediately
(inverter and bypass output included), while the battery will stop charging or discharging. In the event of an emergency,
simply unplug the terminal connected to the REPO port.
If the mains input is present, the UPS control circuit will remain active; however, the output is interrupted. In order
disconnect all mains power from the UPS, the open the external main input MCB.
5.5 Auto Restart
In the event of a mains power failure, the UPS draws power from the battery in order to supply the load until the batteries
are discharged, at which point the UPS will shut down.
The UPS will restart automatically and resume supplying power to the load:
Once the mains power supply is restored.
If the UPS Auto Restart function is enabled.
After the Auto Restart delay has expired (default: 10s). During the Auto Restart delay, the UPS will charge the
battery in order to provide a safety margin for equipment shut-down if input power fails again.
If the Auto Restart function is disabled, you can restart the UPS manually by pressing the power button.
5.6 Mains/Bypass Backfeed Protection Enabled
For information about the mains/bypass backfeed protection function, please refer to 2.4.1 Rectifier And Bypass Input.
5.7 Language Selection
The LCD menus are available in two languages: Chinese, English.
Language selection procedure:
1. Access the main menu screen and press the or key to switch the cursor to select 'Settings', then press the
key to confirm. See Figure 5-9.
2. Press the key to move the cursor to 'Monitor', see Figure 5-10.
Monitor System Outlet
Language English
Date 2016-10-01
Time 00:00:00
Auto-
Display orientation
rota...
Audible alarm Enable
Modbus address 1
4. Press the or key to select the your required language, then press the key to confirm. At this point the
LCD information will be displayed in your selected language. See Figure 5-12.
Language English
Date 2016-10-01
Time 00:00:00
Auto-
Display orientation
rota...
Audible alarm Enable
Modbus address 1
5. Press the key several times to return to the main menu screen.
5.8 Changing the Current Date And Time
Procedures for changing the system date and time:
1. Access the main menu screen and press the or key to switch the cursor to select 'Settings', then press the
key to confirm. See Figure 5-13.
2. Press the key to move the cursor to 'Monitor', see Figure 5-14.
Monitor System Outlet
Language English
Date 2016-10-01
Time 00:00:00
Auto-
Display orientation
rota...
Audible alarm Enable
Modbus address 1
3. Press the key, followed by the or key to highlight the date and time, see Figure 5-15.
Language English
Date 2016-10-01
Time 00:00:00
Auto-
Display orientation
rota...
Audible alarm Enable
Modbus address 1
4. Press the key, move the cursor and press the or key to change the date and time as required. See
Figure 5-16.
Language English
Date 2016-10-01
Time 00:00:00
Auto-
Display orientation
rota...
Audible alarm Enable
Modbus address 1
5. Press the key to confirm, and then press the key several times to return to the main menu screen.
2. Press the key, the interface shown in Figure 5-18 will appear.
1. Press the key to move the cursor to the 'Monitor’ page, see Figure 5-19.
2. Press the key, then press the key to select 'Change settings password', see Figure 5-20.
3. Press the key, the interface shown in Figure 5-21 will appear.
4. Enter the current password and press the key to confirm; at this point requests the user to enter a new password.
See Figure 5-22.
5. After entering the new password, press the key to confirm; at this point the system requests the user to confirm
the new password by entering it again, see Figure 5-23.
6. After the confirming the new password, press the key; at this point a system prompt appears indicating that the
password has been changed successfully, see Figure 5-24.
7. Press the key several times to return to the main menu screen.
Note
In order to access the UPS parameters it is necessary to enter the correct password (default:111111)
Chapter 6 Communication
The following section provides a brief overview of the UPS communication functions.
The communication ports include: intelligent card port, dry contact port, built-in port, RS 232 port, control port and USB
port.
Note
We recommend limiting signal cable lengths to no more than 3 metres, and keeping them away from power cables.
The UPS includes an intelligent card port (see Figure 6-1), which may be used to install communication device options,
such SIC and RDU-SIC cards. The intelligent card port and USB port can be used at the same time.
Relay card
Provides dry contact alarm information, including: On Battery, On Bypass, Low Battery, Summary Alarm, UPS Fault and
On UPS signals for communication to a remote monitoring system or for use with Liebert MultiLink® software. This card
also can accept the input signals used to shut down the UPS, irrespective of the current operating mode.
Refer to the corresponding user manual for the installation and operation information.
Unity card
• IS-UNITY-LIFE: This card is installed as standard on every Liebert ITA2 unit. It is used for communication between the
Liebert ITA2 UPS and Vertiv Trellis® NMS and LIFE Services.
• IS-UNITY-S: This optional card can be used instead of the standard card if communication to a third party platform is
required. Third-party platforms include SNMP or RS 485 (Modbus/Bacnet) protocols. This card may also be used for
communication between the Liebert ITA2 and Vertiv Trellis NMS and LIFE Services. All communication protocols are
active
simultaneously.
• IS-UNITY-DP: This optional card can be used instead of the standard card if communication to two third party platforms
is required. Third-party platforms include SNMP and RS 485 (Modbus/Bacnet) protocols. This card may also be used for
communication between the Liebert ITA2 UPS and Vertiv Trellis NMS and LIFE Services. All communication protocols are
active
simultaneously.
Refer to the corresponding user manual for the installation and operation information.
6.2 Connection Cables for Dry Contact Ports
The UPS provides five dry contact ports. The silkprints of the five dry contact ports are 1 ~ 12. The pin layout of each dry
contact port is shown in Figure 6-2, and the port description is shown in Table 6-1.
User Manual 10H52261UM60 - Rev. 1 - 10/2017 79
ITA2
GND
GND
GND
GND
GND
1 2 3 4 5 6 7 8 9 10 11 12
Figure 6-2 Pin layout of dry contact ports
Note
Activating the UPS EPO will deactivate the rectifier, inverter and static bypass, but does not disconnect the UPS from the mains
input. If you wish to disconnect the UPS completely, it is also necessary to open the input MCB installed upstream of the UPS when
activating the EPO.
In the event of an emergency, close the REPO switch (supplied and installed by the user) in order to shut down the
rectifier and inverter, and switch the UPS off. Under normal conditions, the REPO switch cannot be used to isolate the
UPS from the mains input power. If an electronically controlled circuit breaker function is installed at the UPS input, the
REPO switch can be used to trip this breaker, thus cutting off the UPS mains input power. The position of the REPO
switch is shown in Figure 1-3, and the REPO cable connection is shown in Figure 6-3.
Note
1. We recommend using 0.82mm2 ~ 0.33mm2 copper core cable ( 18AWG ~ 33AWG signal cable).
2. If the REPO has been configured to trip an electronically controlled circuit breaker switch, after the REPO has been activated it will
be necessary to re-arm the switch before restarting the UPS.
Chapter 7 Maintenance
This section focuses on UPS maintenance, including fan maintenance, battery maintenance, UPS cleaning, UPS state
checks, and UPS function checks.
Note
Never attempt to carry out maintenance on the UPS while it is on line. Ensure that the UPS has been switched off completely when
performing any internal maintenance operations on it.
In order to avoid injury or damaging the device, wait until the fan is completely stationary before inserting fingers or any tools into
it.
The UPS fans are expected to run for 20,000 hours ~ 40,000 hours in continuous operation. The higher the ambient
temperature, the shorter the fan life.
During the UPS operation, it is important to check the condition of the fans at least once a year by confirming that they
blow air out of the ventilation holes on the rear panel.
7.2 Battery Maintenance
Note
The internal UPS battery module houses a sealed, lead-acid, maintenance-free battery. The battery life depends on the
ambient temperature, and charge and discharge times. High ambient temperatures and heavy discharge cycles will
shorten the battery life.
To preserve the battery life, it is necessary to:
Maintain the ambient temperature between 15°C and 25°C
Prevent small current discharge. DO NOT operate the UPS in battery mode for periods in excess of 24 hours.
Charge the battery for at least 12 hours if it hasn't been charged for three months while the ambient temperature
remains within the specified limits, or two months in the event of high ambient temperatures
Note
1. Check the battery connection screws are regular intervals, and re-tighten them if necessary.
2. Make sure that all the safety devices present, in good condition and that they function correctly, and make sure that the battery
management parameter settings are correct.
3. Measure and log the ambient temperature in the battery room.
4. Check whether the battery ports are damaged or hot, and check the condition of the chassis and the covers.
If any of the batteries are found to be leaking, place them in a suitable container and dispose of them in accordance with
local regulations.
Lead-acid batteries are classified as hazardous waste material. The control of waste battery pollution is a nationally
important issue. Batteries must be stored, transported, used and disposed of in accordance with national and local legal
requirements and all other criteria applicable to the treatment of hazardous waste material and waste battery pollution
prevention.
According to the applicable regulations, waste lead-aid batteries must be recycled, while all other disposal methods are
prohibited. Uncontrolled or random disposal of waste lead-acid batteries, or other improper disposal methods can result
in serious environmental pollution, which will be investigated by the relevant authorities.
82 User Manual 10H52261UM60 - Rev. 1 - 10/2017
ITA2
As the provider of lead-acid batteries, Vertiv has developed a dedicated service network and waste battery recycling
system to assist users to dispose of waste batteries legally. Contact Vertiv or your nearest service centre for detailed
information about the waste battery the recycling system.
Vertiv may not be held liable for the environmental impact resulting from the failure to comply with the guidelines set out
in this section, or to use the waste battery recycling system offered by Vertiv.
7.3 Cleaning the UPS
Clean the UPS periodically, especially the ventilation holes, to ensure free airflow inside the UPS. If necessary, clean the
UPS with a vacuum cleaner. Confirm that the ventilation holes are unobstructed.
7.4 Checking the state of the UPS
We recommend checking the operational state of the UPS at least twice a year.
Check the following items:
1. Check for any UPS fault conditions: Is the alarm indicator on? Are there any UPS alarms active?
2. Check if the UPS is operating in Bypass mode. Under normal conditions, the UPS operates in Normal mode; if you find
that it is operating in Bypass mode, determine the reason (operator intervention, overload, internal fault, etc.)
3. Check if the battery is discharging: When the AC mains supply is within normal limits, the battery should not be
discharging; if you find that it is operating in Bypass mode, determine the reason (mains failure, battery test, operator
intervention, etc.)
7.5 Checking the UPS Functions
Note
Checking the UPS functions may interrupt the power supply to the load!
Chapter 8 Options
This section introduces the options that are available for the UPS.
8.1 List of Options
See Table 8-1 for the list of the available options.
Table 8-1 List of Options
Option name Model Note
Battery module ITA-BCI0020k02 (3U) Battery module with built-in 16-block 12V (9Ah) batteries
ITA-20K00POD10 Single POD (20 kVA with maintenance bypass)
POD
ITA-20K00POD11 1 + 1 POD (20 kVA with maintenance bypass)
ITA-20k00AL3A02C00L1 UPS parallel communication cables (1m)
Communication cables
ITA-20k00AL3A02CL3 UPS parallel communication cables (3m)
Guide rail GXT4-RMKIT1832 Guide rail for rack installation
Dual bus assembly ITA-20k00AL3A02C00L2 20kVA UPS LBS cables
Relay Card The Relay card is used with the UPS series Intellislot
Communication options
Unity Card The Unity card is used with the UPS series Intellislot
Temperature/humidity IRM-S01T Intelligent temperature sensor
sensor IRM-S02TH Intelligent temperature/humidity sensor
Note
1. The battery loop and AC input are not insulated, therefore hazardous voltages may exist between the battery port and earth. In
order to avoid electric shocks, never touch them without using the appropriate protection equipment.
2. The battery cables must be configured according to the specific installation requirements. The UPS requires ITA-BCI0020k02L3
battery modules.
There is no operator and display panel on the front of the battery module. The plastic panel can be removed and adjusted
according to specific requirements, as shown in Figure 8-2.
Plastic panel
The battery module is complete with ventilation holes, battery ports and a battery output switch on the rear panel, as
shown in Figure 8-3.
Ventilation hole Battery port A Battery output switch
The backup time of the ITA-BCI0020k02 battery module is shown in Table 8-3.
Table 8-3 Backup time list (Unit: min)
Module Backup time
Model
number 20kVA 18kVA 16kVA 14kVA 12kVA 10kVA 8kVA 6kVA 4kVA 2kVA
4 5.5 6.5 7.5 9.5 11.5 15.0 21.0 31.0 51.5 111.0
6 10.0 11.5 14.0 17.0 21.0 27.0 36.5 51.5 81.5 181.5
20kVA 8 15.0 17.5 21.0 25.5 31.0 39.5 52.0 72.0 112.0 252.5
10 21.0 24.5 28.5 34.0 41.5 52.0 67.0 92.5 148.0 324.0
12 27.0 31.5 36.5 43.0 52.0 64.0 82.0 112.5 184.0 395.0
To guarantee the backup time, we recommend configuring at least four groups of battery modules for the 20kVA model.
Note
1. Backup time may vary depending on battery manufacturer, model and usage. The data in the above table are provided for
reference only.
2. The backup times listed in Table 8-3 are provided on the assumption that the battery is in good condition. If the battery
performance is reduced, the actual achievable time may not correspond to the values indicated in Table 8-3.
8.3 POD
The POD (UPS option) is designed to provide safe and reliable power distribution. For a description of the POD options,
see Table 8-4.
Table 8-4 POD
Type Name Description
Single POD with maintenance
ITA-20K00POD10 (W × D × H): 435mm × 500mm × 130mm
bypass
1 + 1 POD with maintenance
ITA-20K00POD11 (W × D × H): 430mm × 500mm × 261mm
bypass
For information on installing and commissioning the POD, refer to Liebert ITA2 20kVA UPS Power Output Distribution
Unit User Manual.
Remove the plastic panel to access the POD front panel; remove the rear baffle plate to access the POD rear panel. The
front panel and rear panel of the single POD are shown in Figure 8-4. The front panel and rear panel of the 1 + 1 parallel
POD are shown in Figure 8-5.
Figure 8-4 Front panel and rear panel of the single POD (20kVA)
IS-UNITY-LIFE
1. UPS system, alarm and fault information for displays
Unity card 、IS-UNITY、
2. can be used to download UPS alarm and event information.
IS-UNITY-DP
Intelligent
Complete with LCD screen, can be connected to the SIC card
Temperature IRM-S01T
or the multifunction port
sensor
Temperature Complete with LCD screen, can be connected to the SIC card
RDU-A-S02TH
humidity sensor or the multifunction port
Note
When connecting the temperature sensor to the SIC card for the battery temperature compensation function, connect to the COM1
88 User Manual 10H52261UM60 - Rev. 1 - 10/2017
ITA2
port of the SIC card, and set the DIP switch on the temperature sensor to '1'. Refer to RDU-SIC Card User Manual for instructions on
how to install the SIC card and set it up.
Appendix 2 Glossary
AC Alternating current
CB Circuit breaker
CSA Cross sectional area
DC Direct current
DIP Dual in-line package
DSP Digital signal processor
EMC Electromagnetic compatibility
EMI Electromagnetic interference
EOD End-of-discharge
EPO Emergency power off
I/O Input/output
LBS Load bus synchronizer
LCD Liquid crystal display
LED Light-emitting diode
MCB Miniature circuit breaker
NMS Network management system
PE Protective earth
RCCB Residual current circuit breaker
RCD Residual current detector
REPO Remote emergency power off
RFI Radio frequency interference
SCR Silicon-controlled rectifier
SNMP Simple network monitoring protocol
STS Static transfer switch
UPS Uninterruptible power system
Hazardous substances
Parts Lead Mercury Cadmium Chrome6+ PBB PBDE
(Pb) (Hg) (Cd) (Cr (VI)) (PBB) (PBDE)
Cables × ○ ○ ○ ○ ○
This table has been prepared in accordance with the Standard SJ/T 11364.
○: Indicates that the content of hazardous substances in the average quality of all the materials used to manufacture the parts is
within the limits specified in GB/T 26572
×: Indicates that the content of hazardous substances in the average quality of at least one of the materials used to manufacture the
parts is outside the limits specified in GB/T 26572
Limit of applicability Liebert ITA2 Rack mounted 20kVA UPS