Installation and User Manual Safepower S: 60-80kVA UPS
Installation and User Manual Safepower S: 60-80kVA UPS
Publish statement
Thank you for purchasing this series UPS.
This series UPS is an intelligent, three phase in Three phase out, high frequency online
UPS designed by our R&D team who is with years of designing experiences on UPS.
With excellent electrical performance, perfect intelligent monitoring and network
functions, smart appearance, complying with EMC and safety standards, The UPS
meets the world’s advanced level.
Read this manual carefully before installation
This manual provides technical support to the operator of the equipment.
3.Installation ............................................................................................................................................. 6
3.1 Unpack checking ........................................................................................................................... 6
4.Operation ............................................................................................................................................. 18
4.1 Operation Modes ......................................................................................................................... 18
There exists dangerous voltage and high temperature inside the UPS. During the
installation, operation and maintenance, please abide the local safety instructions and relative
laws, otherwise it will result in personnel injury or equipment damage. Safety instructions in this
manual act as a supplementary for the local safety instructions. Our company will not assume
the liability that caused by disobeying safety instructions.
2. For the sake of human being safety, please well earth the UPS before starting it.
3.Don’t open or damage battery, for the liquid spilled from the battery is strongly poisonous and
do harmful to body!
4.Please avoid short circuit between positive pole and negative of battery, otherwise, it will
7.Working environment and storage way will affect the lifetime and reliability of the UPS. Avoid
the UPS from working under following environment for long time
◆ Area where the humidity and temperature is out of the specified range(temperature 0
8.Keep ventilations in good conditions otherwise the components inside the UPS will be
2.Main Features
2.1 Summarization
This series UPS is a kind of three-in-three-out high frequency online UPS.
The UPS can solve most of the power supply problems, such as blackout, over-voltage,
under-voltage, voltage sudden drop, oscillating of decreasing extent, high voltage pulse, voltage
fluctuation, surge, inrush current, harmonic distortion (THD), noise interference, frequency
fluctuation, etc..
This UPS can be applied to different applications from computer device, automatic equipment,
communication system to industry equipment.
◆Digital Control
This series UPS is controlled by Digital Signal Processor (DSP); enhance, it increases
reliability, performance, self-protection, and self-diagnostics and so on.
◆Battery Configurable
from 32 blocks to 40 blocks, the battery voltage of this series UPS can be configured at 32 blocks,
34 blocks, 36 blocks, 38 blocks or 40 blocks according to your convenience.
With this 3-stage charging method, it extends the life of the batteries and guarantees fast charging.
◆LCD Display
With LCD plus LED displays, the user may easily get UPS status and its operational
parameters, such as input/output voltage, frequency & load%, battery % and ambient
temperature, etc...
◆EPO Function
The series UPS may be completely shut off when the EPO is pressed. REPO function
(Remote EPO) is also available in this series UPS.
2. Check the appearance to see if the UPS is damaged or not during the transportation, do not
switch on the UPS if any damage found. Please contact the dealer right away.
3. Check the accessories according to the packing list and contact the dealer in case of missing
parts.
◆The environment temperature around UPS should keep in a range of 0℃~40℃. If the
environment temperature exceeds 40℃, the rated load capacity should be reduced by 12% per
5℃. The max temperature can't be higher than 50℃.
◆If the UPS is dismantled under low temperature, it might be in a condensing condition. The
UPS can't be installed unless the internal and external of the equipment is fully dry. Otherwise,
there will be in danger of electric shock.
◆Batteries should be mounted in an environment where the temperature is within the required
specs. Temperature is a major factor in determining battery life and capacity. In a normal
installation, the battery temperature is maintained between 15°C and 25°C. Keep batteries away
from heat sources or main air ventilation area, etc.
WARNING!
Typical battery performance data are quoted for an operating
temperature between 20°C and 25°C. Operating it above this range will
reduce the battery life while operation below this range will reduce the
battery capacity.
CAUTION!
◆The UPS cooling is depending on fan, so it should be kept in good air ventilation area.
There are many ventilation holes on the front and rear, so they should not be blocked by any exotic
obstacles.
◆External Battery
The UPS and its associated batteries are protected against the effect of over-current
through a DC compatible thermo-magnetic circuit-breaker (or a set of fuses) located close to
the battery.
◆UPS Output
Any external distribution board used for load distribution shall be fitted with protective
devices that may avoid the risk of UPS overloaded.
◆Over-current
Protection device shall be installed at the distribution panel of the incoming main supply. It
may identify the power cables current capacity as well as the overload capacity of the system.
CAUTION!
Select a thermo magnetic circuit-breaker with an IEC 60947-2 trip
curve C (normal) for 125% of the current as listed below.
Cable Dimension
UPS
cabinet AC Input AC Output DC Input Grounding
(mm2) (mm2) (mm2) (mm2)
60kVA 35 35 50 35
80kVA 50 50 75 50
CAUTION!
Protective earth cable: Connect each cabinet to the main ground
system. For Grounding connection, follow the shortest route
possible.
WARNING!
Failure to follow adequate earthing procedures may result in
electromagnetic interference or in hazards involving electric shock
and fire
Bps-L2: Secondary input Phase L2 BATN: Neutral terminal of the batteries string
Bps-L3: Secondary input Phase L3 BAT-: Negative terminal of the batteries string
Warning!
In the case of “Dual input” operation, make sure the copper wire
between each input lines have been removed. The AC input and the AC
bypass supplies must be referenced to the same neutral point.
WARNING!
If the load equipment is not ready to accept power on the arrival of
the commissioning engineer then ensure that the system output cables
are safely isolated at their ends
Connect the safety earth and any necessary bonding earth cables
to the copper earth screw located on the floor of the equipment below
the power connections. All cabinets in the UPS must be grounded
properly.
CAUTION!
Note:
The BAT+ of the UPS connect poles is connected to the positive pole of battery, the
BAT-N is connected to the positive of the central battery and the negative of the
central battery, the BAT- is connected to the negative pole of battery.
CAUTION!
Ensure correct polarity battery string series connection. I.e.
inter-tier and inter block connections are from (+) to (-) terminals.
Don’t mix batteries with different capacity or different brands, or
even mix up new and old batteries, either.
WARNING!
Ensure correct polarity of string end connections to the Battery
Circuit Breaker and from the Battery Circuit Breaker to the UPS
terminals i.e. (+) to (+) / (-) to (-) but disconnect one or more
battery cell links in each tier. Do not reconnect these links and do
not close the battery circuit breaker unless authorized by the
commissioning engineer.
Make sure each UPS input breaker is in “off” position and there is no any output from each
UPS connected. Battery groups can be connected separately or in parallel, which means the
system itself provides both separate battery and common battery.
WARNING!
Make sure the N, L1, L2, L3 lines are correct, and grounding is
well connected.
◆A window of “Software Parameter Setting” comes out as below, COM choose according to the
UPS , baud rate choose 9600, protocol choose “HIP”, then save this setting.
◆On the main page of Muser4000, click the button of “Append”, then goes to a window of
“Append equipment”.
◆Click the button “Append”, then the connection between UPS & computer is accomplished.
CAUTION!
When the UPS worked on inverter. If you want to use PC to set the
output voltage and frequency. Must shut down the inverter first
modes:
◆Normal mode
The rectifier/charger derives power from the AC Mains and supplies DC power to the inverter
while floating and boosting charge the battery simultaneously. Then, the inverter converts the DC
power to AC and supplies to the load.
◆Bypass mode
If the inverter is out of order, or if overload occurs, the static transfer switch will be activated to
transfer the load from the inverter supply to bypass supply without interruption to the critical load. In
the event that the inverter output is not synchronized with the bypass AC source, the static switch will
perform a transfer of the load from the inverter to the bypass with power interruption to the critical AC
load. This is to avoid paralleling of unsynchronized AC sources. This interruption is programmable
but typically set to be less than an electrical cycle e.g. less than 15ms (50Hz) or less than 13.33ms
(60Hz).
◆ECO Mode
When the UPS is at AC Mode and the requirement to the load is not critical, the UPS can be set
at ECO mode in order to increase the efficiency of the power supplied. At ECO mode, the UPS
works at Line-interactive mode, so the UPS will transfer to bypass supply. When the AC is out of
set window, the UPS will transfer from bypass to Inverter and supplies power from the battery, and
then the LCD shows all related information on the screen.
To achieve a higher capacity and / or increase reliability, the outputs of up to four UPS can be
programmed to operate in parallel and the built-in parallel controller in each UPS ensures automatic
load sharing.
A manual bypass switch is available to ensure continuity of supply to the critical load when the
UPS is out of order or in repair and this manual bypass switch bears for equivalent rated load.
◆Set the Battery Breaker to the “ON” position according to the user’s manual.
CAUTION!
Check to see if the load is safely connected with the output of the UPS. If the
load is not ready to receive power from the UPS, make sure that it is safely
isolated from the UPS output terminals
◆ Turn ON OUTPUT breaker. (Below the UPS power units at the front door)
◆ Turn ON BYPASS breaker and MAINS breaker. (Below the UPS power units at the front
door)
If the Rectifier input is within voltage range, the rectifier will start up in 30 seconds then
the inverter will start up after then.
If the rectifier fails at startup, the bypass LED will light up. When the inverter starts up,
the UPS will transfer from bypass mode to inverter mode, then the bypass LED
extinguishes and the inverter LED lights up.
No matter whether the UPS can work normally or not, all the status will be shown on the
LCD display.
CAUTION!
The UPS is operating normally. It may take 60 seconds to boost up the
system and perform self-test completely.
◆ Switch off the MAINS to simulate utility failure, the rectifier will turn off and the battery
should feed the inverter without interruption. At this time, the LEDs of battery should be turned
on.
◆ Switch on the MAINS to simulate utility recovery, the rectifier will restart automatically
after 20 seconds and the inverter will supply to the load. It is suggested to use Dummy loads
for testing. The UPS can be loaded up to its maximum capacity during load test。
To supply the load via Mains, you may simply active the internal mechanical bypass switch.
CAUTION!
The load is not protected by the UPS when the internal mechanical bypass
system is active and the power is not conditioned.
CAUTION!
If the UPS is running normally and can be controlled through the display, carry
out steps 1 to 6; otherwise, jump to Step 5.
◆ Open the cover of maintenance switch, the UPS turns to bypass mode automatically.
At this time the bypass source will supply to the load through the MAINTENANCE breaker .
CAUTION!
Never attempt to switch the UPS back to normal operation until you have
verified that there are no internal UPS faults.
◆ Turn ON OUTPUT breaker.
The UPS powers from the static bypass instead of the maintenance bypass, then
the bypass LED will light up.
◆ Switch OFF the maintenance bypass breaker, then the output is supplied by the
CAUTION!
Follow these procedures when the input AC Utility Failure, but battery is
normal
◆ Turn on the BATTERY breaker.
The battery will feed the Auxiliary power board.
◆ Trigger the cold start(Cold start) button as the position 8 of the below drawing.
When battery normal, rectifier starts operation, 30s later, inverter starts and
operates and battery LED on.
CAUTION!
Please press the close start button after 30 seconds until closing the
battery switch.
CAUTION!
This procedure should be followed to completely shut down the UPS
and the LOAD. After all power switches, isolators and circuit breakers
are opened, there will be no output.
◆ Switch OFF the BATTERY breaker;
◆ Open the UPS door to easily access to the main power switch;
◆ To completely isolate the UPS from AC Mains, all input switches of Utility shall
be completely off, which includes the ones for rectifier and bypass.
◆ The primary input distribution panel, which is often located far away from the
WARNING!
Wait for about 5 minutes for the internal D.C. bus bar capacitors to
be completely discharged.
◆ Open Muser4000 software, after connecting with the UPS successfully, click
“System”->“User Set”
“Set” as shown in below picture. If the UPS sounds a “beep”, that means the setting is correct.
◆At the window of “Data Set”, click “Ups ID”, write a value for the parallel UPS ID at the right
side, such as “1”, then click “Set” as shown in below picture. If the UPS sounds a “beep”, that
means the setting is correct.
CAUTION!
The display provides more functions than those
described in this manual.
1) When the UPS is connecting with the Utility or Battery at cold start mode, it shows as drawing
below:
UPS ID Status
Operational Status and mode (When the UPS at single mode, it shows “NOR” or “ECO”, but If the
UPS at parallel mode, it shows “PAL” instead.)
2) Press “scroll” button, the UPS goes to next page as shown below.
IV402E Rev.001SIEL S.p.A.
Data di emissione: 2017-07-24 Pag. 25 di 52 + FR
2. Phase L1 Input Voltage/Frequency 3. Phase L2 Input Voltage/Frequency
If has battery charging, above 2-13 interface windows will also display the charging status at
the same time as below:
Charging
Status
Boost Floating
3) Pressing “scroll” button, you may circulate all messages from the first one to the last one then
returns back to the first one and vice versa.
4) All alarm codes are present when abnormal behavior(s) occur(s).
Output voltage setting (Note: Inside the broken-line is the flashing part.)
In the mode setting press “ON” or in frequency setting press “Off”, it goes to the output voltage
setting. The output voltage line flashes as in above picture. ①Use button “” to choose the different
In the output voltage setting press “ON” or in battery capacity setting press “OFF”, it goes to the
frequency setting. The frequency line flashes as in above picture. ①Use button “” to choose the
different frequency. There are 2 different frequency---50,60Hz. ②Press ”ON” to exit the frequency
setting and save the frequency setting value and goes to battery capacity setting. ③Press ”OFF” to
exit the frequency setting, and goes to output voltage setting.
CAUTION!
When powered by inverter, it is necessary to turn off the inverter
before setting voltage and frequency level.
Battery capacity setting (Note: Inside the broken-line is the flashing part.)
In the frequency setting press “ON” or in battery quantity setting press “OFF”, it goes to the
battery capacity setting. The battery capacity line flashes as in above picture. ①Use button “” to
choose the different battery capacity. Battery capacity range is 1-999Ah. (Note: long-press of “” can
adjustment battery capacity quickly.) ②Press ”ON” to exit the battery capacity setting and save the
capacity setting value and goes to battery quantity setting. ③Press ”OFF” to exit the battery capacity
setting and goes to frequency setting.
Battery quantity setting (Note: Inside the broken-line is the flashing part.)
In the battery capacity setting press “ON” or in bypass voltage upper limit setting press “OFF”, it
goes to the battery quantity setting. The battery quantity line flashes as in above picture. ①Use
button “” to choose the different battery quantity. Battery quantity range is 32,34,36,38,40. ②Press
“ON” to exit the battery quantity setting and save the battery quantity setting value and goes to
bypass voltage upper limit setting. ③Press “OFF” to exit the battery quantity setting and goes to
battery capacity setting.
Bypass voltage upper limit setting (Note: Inside the broken-line is the flashing part.)
In the battery quantity setting press “ON” or in bypass voltage lower setting press “OFF”, it goes
to the bypass upper limit setting. The bypass upper limit line flashes as in above picture. ①Use
button “” to set the different bypass voltage upper limit. The bypass voltage upper limit range is 10%,
15%, 20%, 25 %( 25% only for 220V output). ②Press “ON” to exit the bypass voltage upper limit
setting and save the bypass voltage upper limit setting value and goes to bypass voltage lower limit
setting. ③Press “OFF” to exit the bypass voltage upper limit setting and goes to battery quantity
setting.
Bypass voltage lower limit setting (Note: Inside the broken-line is the flashing part.)
In the bypass voltage upper limit setting press “ON” or in parallel ID setting press “OFF”, it goes
to the bypass lower limit setting. The bypass lower limit line flashes as in above picture. (“-” for
negative, positive does not have any symbol.) ①Use button “” to set the different bypass voltage
lower limit. The bypass voltage lower limit range is 10%, 20%, 30%, 45%. ②Press “ON” to exit the
bypass voltage lower limit setting and save the bypass voltage lower limit setting value and goes to
buzzer mute setting. ③Press “OFF” to exit the bypass voltage lower limit setting and goes to bypass
upper limit setting.
In the bypass voltage low limit setting press “ON” or in battery self-test setting press “OFF”, it
goes to buzzer setting. The scintillation of setting state shows as the figure (Note: ON shows MUTE,
OFF shows NO MUTE).①Press button “” for Mute Cycle Settings, mute choice has On and Off.
②Press button “ON” exits mute setting and save mute setting state and change to battery self-test
settings. ③Press button “OFF” exits mute setting and change to bypass voltage lower limit setting.
Periodical battery self-test setting (note: the part in dashed box flashes)
In the buzzer setting press “ON” or in parallel ID setting press “OFF”, it goes to the battery
self-test setting. In the meantime the setting state flashes as above picture shows (Note: ON 1- the
battery self-test function is enabled, UPS will do self-test 10 seconds every 30 days; ON 2- the
battery self-test function is enabled, UPS will do self-test 10 minutes every 30 days; ON 3- the battery
self-test function is enabled, UPS will do self-test till battery voltage reaches EOD point every 30 days;
OFF-battery self-test function is disabled.). ①Press “” to set periodically self-test setting. The
options are OFF, ON 1, ON 2 and ON 3. ②Press “ON” to exit Periodically Self-test setting and save
the setting value, and goes to battery temperature compensation sensor switch setting. ③Press
“OFF” to exit Periodically Self-test setting and goes to buzzer setting.
Press “ON” under the periodical battery self-test setting or press “OFF” under device address
setting, goes to the battery temperature compensation switch setting. The setting state flashes as
above picture shows (Note: OFF means turn off the sensor switch, ON means turn on the sensor
switch, send query command to sensor with address 11,12 every second. ①Press “” is to set the
battery sensor, with options OFF & ON. ②Press “ON” to exit the battery sensor setting and save
the battery sensor setting value and transfer to device address setting. ③Press “OFF” to exit the
battery sensor setting and transfer to battery periodical battery self-test setting.
Device address setting(Note: the information in the red box will be flashing)
Press “ON” under the battery temperature compensation sensor switch setting or press
“OFF” under parallel ID set- ting, goes to the device address setting. The setting state flashes as
above picture shows (Note: device address is1~15, it is the MODBUS device address at RS232 &
RS485 communication ports. ①Press “” to set the address, with options 1~15. When battery
temperature sensor is open, can choose 1~10 & 13~15; If it’s parallel mode and device address
<= parallel quantity, device address= parallel ID. ②Press “ON” to exit the device address setting
and save the device address setting value and parallel ID setting. (Note: Under single UPS mode,
until this device address setting save and exit, single UPS setting is done.) ③Press “OFF” to exit
the device address setting and transfer to battery temperature compensation sensor setting.
When in device address setting press “ON” or when under parallel quantity setting press “OFF”,
it goes to the parallel ID setting. The parallel ID flashes as in above picture. ①Use button “” to set
the different parallel ID. The parallel ID range is 1~4. ②press “ON” to exit the parallel ID setting and
save the parallel ID setting value and goes to parallel quantity setting. ③press “OFF” to exit the
parallel ID setting and goes to device address setting.
CAUTION!
Parallel cable cannot be connected when setting the parallel
parameters.
Parallel quantity setting (Note: Inside the broken-line is the flashing part.)
When under the parallel ID setting press “ON” or when under parallel redundancy quantity
setting press “OFF”, it goes to the parallel quantity setting. The parallel quantity flashes as in above
picture. ①Use button “” to set the parallel quantity. The parallel quantity range is 2~4. ②Press
“ON” to exit the parallel quantity setting and save the parallel quantity setting value and goes to
parallel redundancy quantity setting. ③Press “OFF” to exit the parallel quantity setting and goes to
parallel ID setting.
IV402E Rev.001SIEL S.p.A.
Data di emissione: 2017-07-24 Pag. 35 di 52 + FR
4.4.14 Parallel redundancy quantity setting
Parallel redundancy quantity setting (Note: Inside the broken-line is the flashing part.)
When under the parallel quantity setting press “ON”, it goes to the parallel redundancy quantity
setting. The parallel redundancy quantity flashes as in above picture. ①Use button “” to set the
parallel redundancy quantity. The parallel redundancy quantity range is 0~3. ②press “ON” to exit the
mode setting and save the mode setting value and then UPS LCD panel setting is accomplished. ③
Press “OFF” to go to parallel quantity setting.
4) Turn off the input breaker of Unit 1, and make sure the UPS is off. Turn on the input breaker of Unit
2,access the LCD setting interface, setting the parallel working mode, ID(NO.2), parallel 4 units,
redundant number .The other setting are the same as UPS 1 operation.
8) Turn on all the battery breaker and confirm the parameter (V/I) are normal.
9) Connected the Load, and check whether the output current are balance.
Switch on and off the utility breaker to test all the UPS converters system from Utility to battery
and restored function are working find
Display messages
Alarm Information
Fault code
UPS Alarm Warning Buzzer LED
(Err)
1 Rectifier Fault Beep continuously Fault LED lit
Inverter fault(Including Inverter
2 Beep continuously Fault LED lit
bridge is shorted)
3 Inverter Thyristor short Beep continuously Fault LED lit
4 Inverter Thyristor broken Beep continuously Fault LED lit
5 Bypass Thyristor short Beep continuously Fault LED lit
6 Bypass Thyristor broken Beep continuously Fault LED lit
7 Fuse broken Beep continuously Fault LED lit
8 Parallel relay fault Beep continuously Fault LED lit
9 Fan fault Beep continuously Fault LED lit
10 Reserve Beep continuously Fault LED lit
11 Auxiliary power fault Beep continuously Fault LED lit
12 Initializtion fault Beep continuously Fault LED lit
13 P-Battery Charger fault Beep continuously Fault LED lit
14 N-Battery Charger fault Beep continuously Fault LED lit
15 DC Bus over voltage Beep continuously Fault LED lit
16 DC Bus below voltage Beep continuously Fault LED lit
17 DC bus unbalance Beep continuously Fault LED lit
IV402E Rev.001SIEL S.p.A.
Data di emissione: 2017-07-24 Pag. 38 di 52 + FR
18 Soft start failed Beep continuously Fault LED lit
19 Rectifier Over Temperature Twice per second Fault LED lit
20 Inverter Over temperature Twice per second Fault LED lit
21 Input neutral loss Twice per second Fault LED lit
22 Battery reverse Twice per second Fault LED lit
23 Cable connection error Twice per second Fault LED lit
24 CAN comm. Fault Twice per second Fault LED lit
25 Parallel load sharing fault Twice per second Fault LED lit
26 Battery over voltage Once per second Fault LED blinking
27 Mains Site Wiring Fault Once per second Fault LED blinking
28 Bypass Site Wiring Fault Once per second Fault LED blinking
29 Output Short-circuit Once per second Fault LED blinking
30 Rectifier over current Once per second Fault LED blinking
31 Bypass over current Once per second BPS LED blinking
INV or BPS LED
32 Overload Once per second
blinking
33 No battery Once per second Battery LED blinking
34 Battery under voltage Once per second Battery LED blinking
35 Battery low pre-warning Once per second Battery LED blinking
36 Internal Communication Error Once per 2 seconds Fault LED blinking
37 DC component over limit. Once per 2 seconds INV LED blinking
38 Parallel Overload Once per 2 seconds INV LED blinking
39 Mains volt. Abnormal Once per 2 seconds Battery LED lit
40 Mains freq. abnormal Once per 2 seconds Battery LED lit
41 Bypass Not Available BPS LED blinking
42 Bypass unable to trace BPS LED blinking
43 Inverter on invalid
44 Reserve
45 inverter not on
46 Output switch not ON Once per 3 seconds
4.7 Options
SNMP card: internal SNMP / external SNMP optional
◆ Carefully pull out the card. Reverse the procedure for re-installation
The slot called SNMP supports the MEGAtec protocol. We advise that NetAgent II-3 port is
also a tool to remotely monitor and manage any UPS system
NetAgent II-3Ports supports the Modem Dial-in (PPP) function to enable the remote control
via the internet when the network is unavailable.
In addition to the features of a standard NetAgent Mini, NetAgent II has the option to add
NetFeeler Lite to detect temperature, humidity, smoke and security sensors. Thus, making
NetAgent II a versatile management tool. NetAgent II also supports multiple languages and is
setup for web-based auto language detection.
Relay card
The card is used for providing the interface for UPS peripheral monitoring. The contact
signals can reflect UPS running status. The card is connected to peripheral monitoring devices
via DB9 female to facilitate the effective monitoring of the real-time status of UPS and timely
feedback the status to monitor when abnormal situation occurs (such as UJPS failure, mains
interruption, UPS bypass and ect.). It is installed in the intelligent slot of the UPS.
The relay card includes 6 output ports and one input port. Please refer to the following table
for detail.
DB9 interface: Connect to upper control terminal. The definition of the pins is defined as
below:
INPUT
Nominal voltage 380/400/415Vac, (3Ph+N+PE)
Operating voltage range 208~478Vac
Operating frequency
40Hz-70Hz
range
Power factor ≥0.99
Harmonic distortion
≤3% (100%non-linear load )
(THDi)
220Vac Max.voltage: +25%(optional +10%,+15%,+20% )
230Vac Max.voltage: +20%(optional +10%,+15% )
Bypass voltage range 240Vac Max.voltage: +15%(optional +10% )
Min. voltage: -45% (optional -20%,-30%)
Frequency synchronize tracing range: ±10%
BATTERY
Charge Current(A)
(charge current can be
Max.current 30A
set according to battery
capacity installed)
SYSTEM FEATURES
Transfer time Utility to Battery : 0ms; Utility to bypass: 0ms
Overload Load≤110%: last 60min,≤125%: last 10min,≤150%: last 1min,≥150% change to bypass.
EMC IEC/EN62040-2,IEC61000-4-2,IEC61000-4-3,IEC61000-4-4,IEC61000-4-5,IEC61000-4-6,IEC61000-4-8
Buzzer long beeps, LCD The UPS output is in Make sure the load is not in short
7 short circuit
display “29”fault code circuit, and then restart the UPS.
The UPS is set to ECO Set the UPS working mode to UPS
The UPS only works on mode, or the transfer type(non-parallel) or to reset the
8
bypass mode times to bypass mode times of transferring to bypass or
are limited. re-start the UPS
Battery switch is not
properly closed:
Close the battery switch:
Battery fuse is not open:
Change the fuse:
Or Battery low:
Recharge the battery:
9 Cannot Black start Battery quantity set
Power ON the UPS with AC to set
wrong;
the battery quantity &quantity;
Power breaker in the
Switch on the power breaker.
rear panel not switch
ON.
Buzzer beeps
continuously and LCD Consult with your local agent for
10 UPS is out of order
indicates 1,3,5,9,15, etc repair
fault codes
Definition of port:
CAUTION!
USB, RS232 and RS485 interface cannot be used at the same time,
you can only use one of them at one time.
CAUTION!
USB, RS232 and RS485 interface cannot be used at the same time,
you can only use one of them at one time.
Definition of port:
Connection between the Device’s RS485 port and UPS RS485 port.
CAUTION!
USB, RS232 and RS485 interface cannot be used at the same time,
you can only use one of them at one time.
Definition of port:
Connection between the Temperature senator RJ45 port and UPS RJ45 port.
Definition of port:
Connection between the UPS1’s LBS1 port and UPS2’s LBS2 port.
◆The output power of two or more UPS in non-parallel system should be synchronized with each
other.
◆The output phase of two or more UPS in non-parallel system should be synchronized with each
other.
CAUTION!
Two or more LBS cables must be used to form a ring when two or more
LBS in non-parallel system.
Instruction:
UPS Instruction
Pin1 UPS Battery Low
Function description:
◆ Shutdown UPS.
Definition of port:
Connection diagram:
◆A remote emergency stop switch can be installed in a remote location and connection through
◆The remote switch can be connected to several UPS in a parallel architecture allowing the user to
1)Remove the screws of the right and left panel, and then open both panels
2)Remove the screws at the left side of the front panel, remove the LCD connection cable , then