Location via proxy:   [ UP ]  
[Report a bug]   [Manage cookies]                
0% found this document useful (0 votes)
496 views

Installation and User Manual Safepower S: 60-80kVA UPS

Uploaded by

Waheed Mido
Copyright
© © All Rights Reserved
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
496 views

Installation and User Manual Safepower S: 60-80kVA UPS

Uploaded by

Waheed Mido
Copyright
© © All Rights Reserved
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 53

60-80kVA UPS

INSTALLATION AND USER MANUAL


SAFEPOWER S

KEEP FOR FUTURE REFERENCE


for the entire life of the appliance

IV402E Rev.001 SIEL S.p.A.


Data di emissione: 2017-07-24 Pag. 0 di 52 + FR
All rights reserved.
The information in this document is subject to change without notice.

Publish statement
Thank you for purchasing this series UPS.
This series UPS is an intelligent, three phase in Three phase out, high frequency online
UPS designed by our R&D team who is with years of designing experiences on UPS.
With excellent electrical performance, perfect intelligent monitoring and network
functions, smart appearance, complying with EMC and safety standards, The UPS
meets the world’s advanced level.
Read this manual carefully before installation
This manual provides technical support to the operator of the equipment.

IV402E Rev.001SIEL S.p.A.


Data di emissione: 2017-07-24 Pag. 1 di 52 + FR
Contents
1.Safety...................................................................................................................................................... 3
1.1 Safety notes ................................................................................................................................... 3

1.2 Symbols used in this guide.......................................................................................................... 4

2.Main Features ........................................................................................................................................ 4


2.1 Summarization ............................................................................................................................... 4

2.2 Functions and Features ................................................................................................................ 4

3.Installation ............................................................................................................................................. 6
3.1 Unpack checking ........................................................................................................................... 6

3.2 Cabinet Outlook ............................................................................................................................ 6

3.3 LCD control panel ......................................................................................................................... 8

3.4 Installation notes ........................................................................................................................... 8

3.5 External Protective Devices .......................................................................................................... 9

3.6 Power Cables ................................................................................................................................. 9

3.7 Power cable connect ................................................................................................................... 11

3.8 Battery connection ...................................................................................................................... 14

3.9 UPS parallel Installation .............................................................................................................. 15

3.10 Computer access ...................................................................................................................... 16

4.Operation ............................................................................................................................................. 18
4.1 Operation Modes ......................................................................................................................... 18

4.2 Turn on/off UPS ........................................................................................................................... 19

4.3 The LCD Display .......................................................................................................................... 24

4.4 Parameters setting ...................................................................................................................... 29

4.5 Parallel system commissioning ................................................................................................ 36

4.6 Display Messages/Troubleshooting .......................................................................................... 38

4.7 Options ......................................................................................................................................... 39

Appendix 1 Specifications ....................................................................................................................... 41


Appendix 2 Problems and Solution ........................................................................................................ 42
Appendix 3 USB communication port definition ................................................................................... 43
Appendix 4 RS232 communication port definition ............................................................................... 44
Appendix 5 RS485 communication port definition ............................................................................... 45
Appendix 6 BAT_T communication port definition ............................................................................... 47
Appendix 7 LBS communication port definition ................................................................................... 48
Appendix 8 Dry contact port communication port definition............................................................... 49
Appendix 9 REPO instruction.................................................................................................................. 50
Appendix 10 Dust-proof net replacement .............................................................................................. 51
IV402E Rev.001SIEL S.p.A.
Data di emissione: 2017-07-24 Pag. 2 di 52 + FR
1.Safety
Important safety instructions - Save these instructions

There exists dangerous voltage and high temperature inside the UPS. During the
installation, operation and maintenance, please abide the local safety instructions and relative
laws, otherwise it will result in personnel injury or equipment damage. Safety instructions in this
manual act as a supplementary for the local safety instructions. Our company will not assume
the liability that caused by disobeying safety instructions.

1.1 Safety notes


1. Even no connection with utility power, 220/230/240VAC voltage may still exist at UPS
terminal!

2. For the sake of human being safety, please well earth the UPS before starting it.

3.Don’t open or damage battery, for the liquid spilled from the battery is strongly poisonous and

do harmful to body!

4.Please avoid short circuit between positive pole and negative of battery, otherwise, it will

cause spark or fire!

5.Don’t disassemble the UPS cover, or there may be an electric shock!

6.Check if there exists high voltage before touching the battery

7.Working environment and storage way will affect the lifetime and reliability of the UPS. Avoid

the UPS from working under following environment for long time

◆ Area where the humidity and temperature is out of the specified range(temperature 0

to 40℃, relative humidity 5%-95%)

◆ Direct sunlight or location nearby heat

◆ Vibration Area with possibility to get the UPS crashed.

◆ Area with erosive gas, flammable gas, excessive dust, etc

8.Keep ventilations in good conditions otherwise the components inside the UPS will be

over-heated which may affect the life of the UPS.

IV402E Rev.001SIEL S.p.A.


Data di emissione: 2017-07-24 Pag. 3 di 52 + FR
1.2 Symbols used in this guide
WARNING!
Risk of electric shock
CAUTION!
Read this information to avoid equipment damage

2.Main Features
2.1 Summarization
This series UPS is a kind of three-in-three-out high frequency online UPS.

The UPS can solve most of the power supply problems, such as blackout, over-voltage,
under-voltage, voltage sudden drop, oscillating of decreasing extent, high voltage pulse, voltage
fluctuation, surge, inrush current, harmonic distortion (THD), noise interference, frequency
fluctuation, etc..

This UPS can be applied to different applications from computer device, automatic equipment,
communication system to industry equipment.

2.2 Functions and Features


◆3Phase In/3Phase Out UPS
It is 3Phase In/3Phase Out high-density UPS system, of which input current is kept in balance.
No unbalance problem might occur.

◆Digital Control
This series UPS is controlled by Digital Signal Processor (DSP); enhance, it increases
reliability, performance, self-protection, and self-diagnostics and so on.

◆Battery Configurable
from 32 blocks to 40 blocks, the battery voltage of this series UPS can be configured at 32 blocks,
34 blocks, 36 blocks, 38 blocks or 40 blocks according to your convenience.

◆Charging Current is configurable


Via setting tool, the user may set the capacity of the batteries as well as reasonable charging
current as well as maximum charging current. Constant voltage mode, constant current mode or
floating mode can be switched automatically and smoothly.

◆Intelligent Charging Method


The series UPS adopts advanced three-stage charging method—

1st stage: high current constant current charging

to guarantee to charge back to 90%;

2nd-stage: Constant Voltage


IV402E Rev.001SIEL S.p.A.
Data di emissione: 2017-07-24 Pag. 4 di 52 + FR
In order to vitalize battery and make sure batteries are fully charged

3rd stage: floating mode.

With this 3-stage charging method, it extends the life of the batteries and guarantees fast charging.

◆LCD Display
With LCD plus LED displays, the user may easily get UPS status and its operational
parameters, such as input/output voltage, frequency & load%, battery % and ambient
temperature, etc...

◆Intelligent Monitoring Function


Via optional SNMP Card, you may remotely control and monitor the UPS.

◆EPO Function
The series UPS may be completely shut off when the EPO is pressed. REPO function
(Remote EPO) is also available in this series UPS.

IV402E Rev.001SIEL S.p.A.


Data di emissione: 2017-07-24 Pag. 5 di 52 + FR
3.Installation
3.1 Unpack checking
1. Don’t lean the UPS when moving it out from the packaging

2. Check the appearance to see if the UPS is damaged or not during the transportation, do not
switch on the UPS if any damage found. Please contact the dealer right away.

3. Check the accessories according to the packing list and contact the dealer in case of missing
parts.

3.2 Cabinet Outlook

Front View Side View

IV402E Rev.001SIEL S.p.A.


Data di emissione: 2017-07-24 Pag. 6 di 52 + FR
60-80kVA Rear View (terminal block without cover)

(1) LCD panel (2) Parallel port 1

(3) Parallel port 2 (4) REPO port

(5) RS485 port (6) LBS port

(7) RS232 port (8) Cold start button

(9) EPO switch (10) Bypass Switch

(11) I/P Switch (12) Ground


(13) Intelligent Slot 1 (SNMP card/ Relay
(14) Dry contact port
card)
(15) USB port (16) Intelligent Slot 2 (SNMP card/ Relay card)

(17) O/P Switch (18) Maintenance switch & its cover

IV402E Rev.001SIEL S.p.A.


Data di emissione: 2017-07-24 Pag. 7 di 52 + FR
3.3 LCD control panel

LCD control panel introduction


(1) LED(from top to bottom: “alarm”, “bypass”, “battery”, “inverter”) (2)LCD display(3)
scroll button (4)Off button (5)On button(battery cold start switch)

3.4 Installation notes


Note: Consider for the convenience of operation and maintenance, the space in
front and back of the cabinet should be left at least 100cm and 80cm respectively when
installing the cabinet.
◆Please place the UPS in a clean, stable environment, avoid the vibration, dust, humidity,
flammable gas and liquid, corrosive. To avoid from high room temperature, a system of room
extractor fans is recommended to be installed. Optional air filters are available if the UPS operates
in a dusty environment.

◆The environment temperature around UPS should keep in a range of 0℃~40℃. If the
environment temperature exceeds 40℃, the rated load capacity should be reduced by 12% per
5℃. The max temperature can't be higher than 50℃.

◆If the UPS is dismantled under low temperature, it might be in a condensing condition. The
UPS can't be installed unless the internal and external of the equipment is fully dry. Otherwise,
there will be in danger of electric shock.

◆Batteries should be mounted in an environment where the temperature is within the required
specs. Temperature is a major factor in determining battery life and capacity. In a normal
installation, the battery temperature is maintained between 15°C and 25°C. Keep batteries away
from heat sources or main air ventilation area, etc.

WARNING!
Typical battery performance data are quoted for an operating
temperature between 20°C and 25°C. Operating it above this range will
reduce the battery life while operation below this range will reduce the
battery capacity.

◆Should the equipment not be installed immediately it must be stored in a room so as to


protect it against excessive humidity and or heat sources.

CAUTION!

An unused battery must be recharged every 6months Temporarily


connecting the UPS to a suitable AC supply mains and activating it for
the time required for recharging the batteries.

IV402E Rev.001SIEL S.p.A.


Data di emissione: 2017-07-24 Pag. 8 di 52 + FR
◆The highest altitude that UPS may work normally with full load is 1500 meters. The load
capacity should be reduced when this UPS is installed in place whose altitude is higher than 1500
meters, shown as the following table:
(Load coefficient equals max load in high altitude place divided by nominal power of the UPS)
Altitude(
1500 2000 2500 3000 3500 4000 4500 5000
m)
Load
100% 95% 90% 85% 80% 75% 70% 65%
coefficient

◆The UPS cooling is depending on fan, so it should be kept in good air ventilation area.
There are many ventilation holes on the front and rear, so they should not be blocked by any exotic
obstacles.

3.5 External Protective Devices


For safety reasons, it is necessary to install, external circuit breaker at the input A.C. supply and
the battery. This chapter provides guidelines for qualified installers that must have the knowledge of
local wiring practices for the equipment to be installed.

◆External Battery
The UPS and its associated batteries are protected against the effect of over-current
through a DC compatible thermo-magnetic circuit-breaker (or a set of fuses) located close to
the battery.

◆UPS Output
Any external distribution board used for load distribution shall be fitted with protective
devices that may avoid the risk of UPS overloaded.

◆Over-current
Protection device shall be installed at the distribution panel of the incoming main supply. It
may identify the power cables current capacity as well as the overload capacity of the system.
CAUTION!
Select a thermo magnetic circuit-breaker with an IEC 60947-2 trip
curve C (normal) for 125% of the current as listed below.

3.6 Power Cables


◆The cable design shall comply with the voltages and currents provided in this section, Kindly
follow local wiring practices and take into consideration the environmental conditions (temperature
and physical support media) .
WARNING!
Upon starting. Please ensure that you are aware of the location and
operation of the external isolators which are connected to the UPS
input/bypass supply of the mains distribution panel. Check to see if
these supplies are electrically isolated. And post and necessary
warning signs to prevent any inadvertent operation.

IV402E Rev.001SIEL S.p.A.


Data di emissione: 2017-07-24 Pag. 9 di 52 + FR
◆For future expansion purpose, it is economical to install power cable according to the full rating

capacity initially. The diameter of cable is shown bellow:

Cable Dimension
UPS
cabinet AC Input AC Output DC Input Grounding
(mm2) (mm2) (mm2) (mm2)
60kVA 35 35 50 35
80kVA 50 50 75 50
CAUTION!
Protective earth cable: Connect each cabinet to the main ground
system. For Grounding connection, follow the shortest route
possible.
WARNING!
Failure to follow adequate earthing procedures may result in
electromagnetic interference or in hazards involving electric shock
and fire

IV402E Rev.001SIEL S.p.A.


Data di emissione: 2017-07-24 Pag. 10 di 52 + FR
3.7 Power cable connect
Once the equipment has been finally positioned and secured, connect the power cables as
described in the following procedure.
Verify the UPS is totally isolated from its external power source and also all power isolators of the
UPS are open. Check to see if they are electrically isolated, and post any necessary warning signs to
prevent their inadvertent operation.
Open the UPS rear panel; Remove the cover of terminals for wiring easily.

3.7.1 Common input connection

M/1R Primary input Line IN/OUT Input / Output

Output-L1: Output Phase L1


Input-L1: Primary input Phase L1 Output-L2: Output Phase L2

Input -L2: Primary input Phase L2 Output-L3: Output Phase L3

Input -L3: Primary input Phase L3 Output-N: Output Neutral


Input-N: Input Neutral for primary and
GND: Grounding
secondary input
BAT+: Positive terminal of the batteries string

BATN: Neutral terminal of the batteries string

BAT-: Negative terminal of the batteries string

IV402E Rev.001SIEL S.p.A.


Data di emissione: 2017-07-24 Pag. 11 di 52 + FR
3.7.2 Dual input connection

M/1R Primary input Line IN/OUT Input / Output


B/2R Secondary/Bypass input line
Output-L1: Output Phase L1
(optional)
Mains-L1: Primary input Phase L1 Output-L2: Output Phase L2

Mains-L2: Primary input Phase L2 Output-L3: Output Phase L3

Mains-L3: Primary input Phase L3 Output-N: Output Neutral


Input-N: Input Neutral for primary and
GND: Grounding
secondary input
Bps-L1: Secondary input Phase L1 BAT+: Positive terminal of the batteries string

Bps-L2: Secondary input Phase L2 BATN: Neutral terminal of the batteries string

Bps-L3: Secondary input Phase L3 BAT-: Negative terminal of the batteries string

Warning!

In the case of “Dual input” operation, make sure the copper wire
between each input lines have been removed. The AC input and the AC
bypass supplies must be referenced to the same neutral point.

IV402E Rev.001SIEL S.p.A.


Data di emissione: 2017-07-24 Pag. 12 di 52 + FR
Choose appropriate power cable.(Refer to the table above)and pay attention to the
diameter of the connection terminal of the cable that should be greater than or equal to that
of the connection poles;

WARNING!
If the load equipment is not ready to accept power on the arrival of
the commissioning engineer then ensure that the system output cables
are safely isolated at their ends
Connect the safety earth and any necessary bonding earth cables
to the copper earth screw located on the floor of the equipment below
the power connections. All cabinets in the UPS must be grounded
properly.

CAUTION!

The earthing and neutral bonding arrangement must be in accordance


with local and national codes of practice.

IV402E Rev.001SIEL S.p.A.


Data di emissione: 2017-07-24 Pag. 13 di 52 + FR
3.8 Battery connection
The UPS adopts positive and negative double battery framework, totally 16pcs (optional 18/20)
in series. A neutral cable is retrieved from the joint between the negative pole of the 16th
(17th/18th/19th/20 th) and the positive pole of the 17th (18th/19th/20th/21th) of the batteries. Then the
neutral cable, the battery Positive and the battery negative are connected with the UPS respectively.
The battery sets between the Battery positive pole and the neutral are called positive batteries and
that between neutral and negative pole are called negative ones. The user can choose the capacity
and the numbers of the batteries according to their desire.
External battery connections for long-run units.

Note:
The BAT+ of the UPS connect poles is connected to the positive pole of battery, the
BAT-N is connected to the positive of the central battery and the negative of the
central battery, the BAT- is connected to the negative pole of battery.

Factory setting of the long-run unit is battery quantity---32pcs, battery


capacity---12V65AH (charger current 9.75A). When connecting 32/34/36/38/40 batteries,
please re-set desired battery quantity and its capacity after UPS starts at AC mode.
Charger current could be adjusted automatically according to battery capacity selected.
All related settings can be done through LCD panel or monitoring software

CAUTION!
Ensure correct polarity battery string series connection. I.e.
inter-tier and inter block connections are from (+) to (-) terminals.
Don’t mix batteries with different capacity or different brands, or
even mix up new and old batteries, either.

WARNING!
Ensure correct polarity of string end connections to the Battery
Circuit Breaker and from the Battery Circuit Breaker to the UPS
terminals i.e. (+) to (+) / (-) to (-) but disconnect one or more
battery cell links in each tier. Do not reconnect these links and do
not close the battery circuit breaker unless authorized by the
commissioning engineer.

IV402E Rev.001SIEL S.p.A.


Data di emissione: 2017-07-24 Pag. 14 di 52 + FR
3.9 UPS parallel Installation
The following sections introduce the installation procedures specified to the parallel system.

3.9.1 Cabinet installation


Connect all the UPS needed to be put into parallel system as below picture.

Make sure each UPS input breaker is in “off” position and there is no any output from each
UPS connected. Battery groups can be connected separately or in parallel, which means the
system itself provides both separate battery and common battery.
WARNING!
Make sure the N, L1, L2, L3 lines are correct, and grounding is
well connected.

3.9.2 Parallel cable installation


Shielded and double insulated control cables available must be interconnected in a ring
configuration between UPS units as shown below. The ring configuration ensures high
reliability of the control.

3.9.3 Requirement for the parallel system


A group of paralleled UPS behaves as one large UPS system but with the advantage of
presenting higher reliability. In order to assure that all UPS are equally utilized and comply with
relevant wiring rules, please follow the requirements below:
1) All UPS must be of the same rating and be connected to the same bypass source.
2) The outputs of all the UPS must be connected to a common output bus.
3) The length and specification of power cables including the bypass input cables and the UPS
output cables should be the same. This facilitates load sharing when operating in bypass
mode.

IV402E Rev.001SIEL S.p.A.


Data di emissione: 2017-07-24 Pag. 15 di 52 + FR
3.10 Computer access
◆One end of a USB cable connect to the computer, the other end connect to the USB port on the
UPS.

◆Open the software Muser4000, click “system” button.

◆A window of “Software Parameter Setting” comes out as below, COM choose according to the
UPS , baud rate choose 9600, protocol choose “HIP”, then save this setting.

◆On the main page of Muser4000, click the button of “Append”, then goes to a window of
“Append equipment”.

IV402E Rev.001SIEL S.p.A.


Data di emissione: 2017-07-24 Pag. 16 di 52 + FR
◆Put the UPS name into “Equipment Name”, and UPS’ ID address into “Equipment address”.

◆Click the button “Append”, then the connection between UPS & computer is accomplished.

CAUTION!

When the UPS worked on inverter. If you want to use PC to set the
output voltage and frequency. Must shut down the inverter first

IV402E Rev.001SIEL S.p.A.


Data di emissione: 2017-07-24 Pag. 17 di 52 + FR
4.Operation
4.1 Operation Modes
The UPS is a double-conversion on-line UPS that may operate in the following alternative

modes:

◆Normal mode
The rectifier/charger derives power from the AC Mains and supplies DC power to the inverter
while floating and boosting charge the battery simultaneously. Then, the inverter converts the DC
power to AC and supplies to the load.

◆Battery mode (Stored Energy Mode)


If the AC mains input power fails, the inverter, which obtains power from the battery, supplies the
critical AC load. There is no power interruption to the critical load. The UPS will automatically return to
Normal Mode when AC recovers.

◆Bypass mode
If the inverter is out of order, or if overload occurs, the static transfer switch will be activated to
transfer the load from the inverter supply to bypass supply without interruption to the critical load. In
the event that the inverter output is not synchronized with the bypass AC source, the static switch will
perform a transfer of the load from the inverter to the bypass with power interruption to the critical AC
load. This is to avoid paralleling of unsynchronized AC sources. This interruption is programmable
but typically set to be less than an electrical cycle e.g. less than 15ms (50Hz) or less than 13.33ms
(60Hz).

◆ECO Mode
When the UPS is at AC Mode and the requirement to the load is not critical, the UPS can be set
at ECO mode in order to increase the efficiency of the power supplied. At ECO mode, the UPS
works at Line-interactive mode, so the UPS will transfer to bypass supply. When the AC is out of
set window, the UPS will transfer from bypass to Inverter and supplies power from the battery, and
then the LCD shows all related information on the screen.

◆Parallel redundancy mode (system expansion)

To achieve a higher capacity and / or increase reliability, the outputs of up to four UPS can be
programmed to operate in parallel and the built-in parallel controller in each UPS ensures automatic
load sharing.

◆Maintenance mode (Manual Bypass)

A manual bypass switch is available to ensure continuity of supply to the critical load when the
UPS is out of order or in repair and this manual bypass switch bears for equivalent rated load.

IV402E Rev.001SIEL S.p.A.


Data di emissione: 2017-07-24 Pag. 18 di 52 + FR
4.2 Turn on/off UPS
4.2.1 Restart procedure
CAUTION!
MAKE SURE GROUNDING IS PROPERLY DONE!

◆Set the Battery Breaker to the “ON” position according to the user’s manual.

CAUTION!
Check to see if the load is safely connected with the output of the UPS. If the
load is not ready to receive power from the UPS, make sure that it is safely
isolated from the UPS output terminals

◆ Turn ON OUTPUT breaker. (Below the UPS power units at the front door)

◆ Turn ON BYPASS breaker and MAINS breaker. (Below the UPS power units at the front
door)

If the Rectifier input is within voltage range, the rectifier will start up in 30 seconds then
the inverter will start up after then.

If the rectifier fails at startup, the bypass LED will light up. When the inverter starts up,
the UPS will transfer from bypass mode to inverter mode, then the bypass LED
extinguishes and the inverter LED lights up.

No matter whether the UPS can work normally or not, all the status will be shown on the
LCD display.

4.2.2 Test procedure

CAUTION!
The UPS is operating normally. It may take 60 seconds to boost up the
system and perform self-test completely.

◆ Switch off the MAINS to simulate utility failure, the rectifier will turn off and the battery

should feed the inverter without interruption. At this time, the LEDs of battery should be turned
on.

◆ Switch on the MAINS to simulate utility recovery, the rectifier will restart automatically

after 20 seconds and the inverter will supply to the load. It is suggested to use Dummy loads

for testing. The UPS can be loaded up to its maximum capacity during load test。

IV402E Rev.001SIEL S.p.A.


Data di emissione: 2017-07-24 Pag. 19 di 52 + FR
4.2.3 MAINTENANCE BYPASS

To supply the load via Mains, you may simply active the internal mechanical bypass switch.

CAUTION!
The load is not protected by the UPS when the internal mechanical bypass
system is active and the power is not conditioned.

Switch to mechanical bypass

CAUTION!

If the UPS is running normally and can be controlled through the display, carry
out steps 1 to 6; otherwise, jump to Step 5.
◆ Open the cover of maintenance switch, the UPS turns to bypass mode automatically.

◆ Turn on MAINTANCE breaker;

◆ Switch OFF BATTERY breaker;

◆ Switch OFF MAINS breaker;

◆ Switch OFF BYPASS breaker;

◆ Switch OFF OUTPUT breaker;

At this time the bypass source will supply to the load through the MAINTENANCE breaker .

Switch to normal operation (from mechanical bypass)

CAUTION!
Never attempt to switch the UPS back to normal operation until you have
verified that there are no internal UPS faults.
◆ Turn ON OUTPUT breaker.

◆ Turn ON BYPASS breaker.

◆ Turn ON MAINS breaker.

The UPS powers from the static bypass instead of the maintenance bypass, then
the bypass LED will light up.

◆ Switch OFF the maintenance bypass breaker, then the output is supplied by the

static bypass of the UPS.

◆ Put on the maintenance switch cover.


IV402E Rev.001SIEL S.p.A.
Data di emissione: 2017-07-24 Pag. 20 di 52 + FR
The rectifier will operate normally after 30 seconds. If the inverter works normally,
the system will be transferred from bypass mode to normal mode.

4.2.4 Cold start procedure

CAUTION!
Follow these procedures when the input AC Utility Failure, but battery is
normal
◆ Turn on the BATTERY breaker.
The battery will feed the Auxiliary power board.

◆ Turn on the OUTPUT breaker.

◆ Trigger the cold start(Cold start) button as the position 8 of the below drawing.

When battery normal, rectifier starts operation, 30s later, inverter starts and
operates and battery LED on.

CAUTION!
Please press the close start button after 30 seconds until closing the
battery switch.

4.2.5 Shut down procedure

CAUTION!
This procedure should be followed to completely shut down the UPS
and the LOAD. After all power switches, isolators and circuit breakers
are opened, there will be no output.
◆ Switch OFF the BATTERY breaker;

◆ Open the UPS door to easily access to the main power switch;

◆ Switch OFF the MAINS breaker.

◆ Switch OFF the BYPASS breaker.

◆ Open the OUTPUT breaker. The UPS shuts down;

◆ To completely isolate the UPS from AC Mains, all input switches of Utility shall

be completely off, which includes the ones for rectifier and bypass.

◆ The primary input distribution panel, which is often located far away from the

IV402E Rev.001SIEL S.p.A.


Data di emissione: 2017-07-24 Pag. 21 di 52 + FR
UPS area, so a label should be posted to advise service personnel that the

UPS circuit is under maintenance。

WARNING!

Wait for about 5 minutes for the internal D.C. bus bar capacitors to
be completely discharged.

4.2.6 Parallel setting


◆Connect the UPS with computer. Power on the UPS.

◆ Open Muser4000 software, after connecting with the UPS successfully, click

“System”->“User Set”

◆Click “Set” at “User Set” window;

IV402E Rev.001SIEL S.p.A.


Data di emissione: 2017-07-24 Pag. 22 di 52 + FR
◆At the window of “Data Set”, click “Work Mode”,, choose “Parallel” for the value, then click

“Set” as shown in below picture. If the UPS sounds a “beep”, that means the setting is correct.

◆At the window of “Data Set”, click “Ups ID”, write a value for the parallel UPS ID at the right

side, such as “1”, then click “Set” as shown in below picture. If the UPS sounds a “beep”, that
means the setting is correct.

IV402E Rev.001SIEL S.p.A.


Data di emissione: 2017-07-24 Pag. 23 di 52 + FR
CAUTION!
After changing the parallel system ID, the connection between
Muser4000 and equipment might be interrupted. If it occurs, please
re-connect in accordance with the instruction described before.
CAUTION!
Parallel cable cannot be connected when setting the parallel parameters.
◆After setting the UPS needed to be paralleled, power off all the UPS. Connect all the UPS

according to “parallel cable installation”, and then power on the UPS.

4.3 The LCD Display

Overview of the operating panel of the UPS


(1)LED indicator (2)LCD display (3)Scroll button: enter to next item (4)Off button (5)On button

IV402E Rev.001SIEL S.p.A.


Data di emissione: 2017-07-24 Pag. 24 di 52 + FR
Introduction

CAUTION!
The display provides more functions than those
described in this manual.

There are 17 interfaces available in the LCD display:

Item Interface Description Content Displayed


01 CODE Operational status and mode
02 Input L1 Voltage & Frequency
03 Input L2 Voltage & Frequency
04 Input L3 Voltage & Frequency
05 Bat. + Voltage & Current
06 Bat. - Voltage & Current
07 Backup time Capacity & Time
08 Output L1 Voltage & Frequency
09 Output L2 Voltage & Frequency
10 Output L3 Voltage & Frequency
11 Load L1 Load
12 Load L2 Load
13 Load L3 Load
14 Total Load Load
1: Environment temperature (ENV)
2: Internal PFC temperature (PFC)
3: Internal inverter temperature (INV)
15 Temperature
4: Internal bypass temperature (BPS)
5: Battery temperature(need to connect batter
sensor)
Version of rectifier software, version of inverter
16 Software version & model
software, model
17 CODE Alarm Code(Warming Message)

1) When the UPS is connecting with the Utility or Battery at cold start mode, it shows as drawing
below:

UPS ID Status

Operational Status and mode (When the UPS at single mode, it shows “NOR” or “ECO”, but If the
UPS at parallel mode, it shows “PAL” instead.)

2) Press “scroll” button, the UPS goes to next page as shown below.
IV402E Rev.001SIEL S.p.A.
Data di emissione: 2017-07-24 Pag. 25 di 52 + FR
2. Phase L1 Input Voltage/Frequency 3. Phase L2 Input Voltage/Frequency

4. Phase L3 Input Voltage/Frequency 5. Bat + (Positive)

6. Bat – (Negative) 7. Backup time

IV402E Rev.001SIEL S.p.A.


Data di emissione: 2017-07-24 Pag. 26 di 52 + FR
8. Phase L1 Output Voltage/Frequency 9. Phase L2 Output Voltage/Frequency

10. Phase L3 Output Voltage/Frequency 11. Phase L1 Load Capacity

12. Phase L2 Load Capacity 13. Phase L3 Load Capacity

IV402E Rev.001SIEL S.p.A.


Data di emissione: 2017-07-24 Pag. 27 di 52 + FR
14. Total Load Capacity 15. Temperature (environment/PFC/INV/BPS/battery)

16. Software version & model 17.Alarm Code

If has battery charging, above 2-13 interface windows will also display the charging status at
the same time as below:

Charging
Status
Boost Floating
3) Pressing “scroll” button, you may circulate all messages from the first one to the last one then
returns back to the first one and vice versa.
4) All alarm codes are present when abnormal behavior(s) occur(s).

IV402E Rev.001SIEL S.p.A.


Data di emissione: 2017-07-24 Pag. 28 di 52 + FR
4.4 Parameters setting
The setting function is controlled by 3 buttons (, OFF, ON) : ---goes into the setting page and
value adjustment; OFF---for exit setting; ---for choosing different pages.
After the UPS turn ON, press buttons “” & “OFF” for 2 seconds and then goes into the setting
interface page.

4.4.1 Mode setting

Mode setting (Note: Inside the broken-line is the flashing part.)


After entering the setting menu, its mode setting defaulted, and the mode setting line flashing as
in above picture. ①Use button “” to choose different mode. There are 3 different modes for setting:
ECO, PAL, NOR. ②Press “ON” to exit the mode setting and save the mode setting value, and goes
to output voltage setting. ③Press “OFF” to exit the mode setting, and goes to parallel redundancy
quantity setting.

4.4.2 Output voltage setting

Output voltage setting (Note: Inside the broken-line is the flashing part.)
In the mode setting press “ON” or in frequency setting press “Off”, it goes to the output voltage
setting. The output voltage line flashes as in above picture. ①Use button “” to choose the different

IV402E Rev.001SIEL S.p.A.


Data di emissione: 2017-07-24 Pag. 29 di 52 + FR
output voltage. There are 3 different voltages---220, 230, 240. ②Press “ON” to exit the output
voltage setting and save the output voltage setting value, and goes to frequency setting. ③Press
“OFF” to exit the output voltage setting, and goes to mode setting.
CAUTION!

When powered by inverter, it is necessary to turn off the inverter


before setting voltage and frequency level.

4.4.3 Frequency setting

Frequency setting (Note: Inside the broken-line is the flashing part.)

In the output voltage setting press “ON” or in battery capacity setting press “OFF”, it goes to the
frequency setting. The frequency line flashes as in above picture. ①Use button “” to choose the
different frequency. There are 2 different frequency---50,60Hz. ②Press ”ON” to exit the frequency
setting and save the frequency setting value and goes to battery capacity setting. ③Press ”OFF” to
exit the frequency setting, and goes to output voltage setting.

CAUTION!
When powered by inverter, it is necessary to turn off the inverter
before setting voltage and frequency level.

IV402E Rev.001SIEL S.p.A.


Data di emissione: 2017-07-24 Pag. 30 di 52 + FR
4.4.4 Battery capacity setting

Battery capacity setting (Note: Inside the broken-line is the flashing part.)

In the frequency setting press “ON” or in battery quantity setting press “OFF”, it goes to the
battery capacity setting. The battery capacity line flashes as in above picture. ①Use button “” to
choose the different battery capacity. Battery capacity range is 1-999Ah. (Note: long-press of “” can
adjustment battery capacity quickly.) ②Press ”ON” to exit the battery capacity setting and save the
capacity setting value and goes to battery quantity setting. ③Press ”OFF” to exit the battery capacity
setting and goes to frequency setting.

4.4.5 Battery quantity setting

Battery quantity setting (Note: Inside the broken-line is the flashing part.)

In the battery capacity setting press “ON” or in bypass voltage upper limit setting press “OFF”, it
goes to the battery quantity setting. The battery quantity line flashes as in above picture. ①Use
button “” to choose the different battery quantity. Battery quantity range is 32,34,36,38,40. ②Press
“ON” to exit the battery quantity setting and save the battery quantity setting value and goes to
bypass voltage upper limit setting. ③Press “OFF” to exit the battery quantity setting and goes to
battery capacity setting.

IV402E Rev.001SIEL S.p.A.


Data di emissione: 2017-07-24 Pag. 31 di 52 + FR
4.4.6 Bypass voltage upper limit setting

Bypass voltage upper limit setting (Note: Inside the broken-line is the flashing part.)

In the battery quantity setting press “ON” or in bypass voltage lower setting press “OFF”, it goes
to the bypass upper limit setting. The bypass upper limit line flashes as in above picture. ①Use
button “” to set the different bypass voltage upper limit. The bypass voltage upper limit range is 10%,
15%, 20%, 25 %( 25% only for 220V output). ②Press “ON” to exit the bypass voltage upper limit
setting and save the bypass voltage upper limit setting value and goes to bypass voltage lower limit
setting. ③Press “OFF” to exit the bypass voltage upper limit setting and goes to battery quantity
setting.

4.4.7 Bypass voltage lower limit setting

Bypass voltage lower limit setting (Note: Inside the broken-line is the flashing part.)

In the bypass voltage upper limit setting press “ON” or in parallel ID setting press “OFF”, it goes
to the bypass lower limit setting. The bypass lower limit line flashes as in above picture. (“-” for
negative, positive does not have any symbol.) ①Use button “” to set the different bypass voltage
lower limit. The bypass voltage lower limit range is 10%, 20%, 30%, 45%. ②Press “ON” to exit the
bypass voltage lower limit setting and save the bypass voltage lower limit setting value and goes to
buzzer mute setting. ③Press “OFF” to exit the bypass voltage lower limit setting and goes to bypass
upper limit setting.

IV402E Rev.001SIEL S.p.A.


Data di emissione: 2017-07-24 Pag. 32 di 52 + FR
4.4.8 Buzzer Mute Setting

Buzzer Settings (note: red dashed box is the scintillation part

In the bypass voltage low limit setting press “ON” or in battery self-test setting press “OFF”, it
goes to buzzer setting. The scintillation of setting state shows as the figure (Note: ON shows MUTE,
OFF shows NO MUTE).①Press button “” for Mute Cycle Settings, mute choice has On and Off.
②Press button “ON” exits mute setting and save mute setting state and change to battery self-test
settings. ③Press button “OFF” exits mute setting and change to bypass voltage lower limit setting.

4.4.9 Periodical battery self-test Setting

Periodical battery self-test setting (note: the part in dashed box flashes)

In the buzzer setting press “ON” or in parallel ID setting press “OFF”, it goes to the battery
self-test setting. In the meantime the setting state flashes as above picture shows (Note: ON 1- the
battery self-test function is enabled, UPS will do self-test 10 seconds every 30 days; ON 2- the
battery self-test function is enabled, UPS will do self-test 10 minutes every 30 days; ON 3- the battery
self-test function is enabled, UPS will do self-test till battery voltage reaches EOD point every 30 days;
OFF-battery self-test function is disabled.). ①Press “” to set periodically self-test setting. The
options are OFF, ON 1, ON 2 and ON 3. ②Press “ON” to exit Periodically Self-test setting and save
the setting value, and goes to battery temperature compensation sensor switch setting. ③Press
“OFF” to exit Periodically Self-test setting and goes to buzzer setting.

IV402E Rev.001SIEL S.p.A.


Data di emissione: 2017-07-24 Pag. 33 di 52 + FR
4.4.10 Battery temperature compensation sensor switch setting

Battery temperature compensation sensor switch setting


(Note: the information in the red box will be flashing)

Press “ON” under the periodical battery self-test setting or press “OFF” under device address
setting, goes to the battery temperature compensation switch setting. The setting state flashes as
above picture shows (Note: OFF means turn off the sensor switch, ON means turn on the sensor
switch, send query command to sensor with address 11,12 every second. ①Press “” is to set the
battery sensor, with options OFF & ON. ②Press “ON” to exit the battery sensor setting and save
the battery sensor setting value and transfer to device address setting. ③Press “OFF” to exit the
battery sensor setting and transfer to battery periodical battery self-test setting.

4.4.11 Device address setting

Device address setting(Note: the information in the red box will be flashing)
Press “ON” under the battery temperature compensation sensor switch setting or press
“OFF” under parallel ID set- ting, goes to the device address setting. The setting state flashes as
above picture shows (Note: device address is1~15, it is the MODBUS device address at RS232 &
RS485 communication ports. ①Press “” to set the address, with options 1~15. When battery
temperature sensor is open, can choose 1~10 & 13~15; If it’s parallel mode and device address
<= parallel quantity, device address= parallel ID. ②Press “ON” to exit the device address setting
and save the device address setting value and parallel ID setting. (Note: Under single UPS mode,
until this device address setting save and exit, single UPS setting is done.) ③Press “OFF” to exit
the device address setting and transfer to battery temperature compensation sensor setting.

IV402E Rev.001SIEL S.p.A.


Data di emissione: 2017-07-24 Pag. 34 di 52 + FR
4.4.12 Parallel ID setting

Parallel ID setting (Note: Inside the broken-line is the flashing part.)

When in device address setting press “ON” or when under parallel quantity setting press “OFF”,
it goes to the parallel ID setting. The parallel ID flashes as in above picture. ①Use button “” to set
the different parallel ID. The parallel ID range is 1~4. ②press “ON” to exit the parallel ID setting and
save the parallel ID setting value and goes to parallel quantity setting. ③press “OFF” to exit the
parallel ID setting and goes to device address setting.

CAUTION!
Parallel cable cannot be connected when setting the parallel
parameters.

4.4.13 Parallel quantity setting

Parallel quantity setting (Note: Inside the broken-line is the flashing part.)

When under the parallel ID setting press “ON” or when under parallel redundancy quantity
setting press “OFF”, it goes to the parallel quantity setting. The parallel quantity flashes as in above
picture. ①Use button “” to set the parallel quantity. The parallel quantity range is 2~4. ②Press
“ON” to exit the parallel quantity setting and save the parallel quantity setting value and goes to
parallel redundancy quantity setting. ③Press “OFF” to exit the parallel quantity setting and goes to
parallel ID setting.
IV402E Rev.001SIEL S.p.A.
Data di emissione: 2017-07-24 Pag. 35 di 52 + FR
4.4.14 Parallel redundancy quantity setting

Parallel redundancy quantity setting (Note: Inside the broken-line is the flashing part.)
When under the parallel quantity setting press “ON”, it goes to the parallel redundancy quantity
setting. The parallel redundancy quantity flashes as in above picture. ①Use button “” to set the
parallel redundancy quantity. The parallel redundancy quantity range is 0~3. ②press “ON” to exit the
mode setting and save the mode setting value and then UPS LCD panel setting is accomplished. ③
Press “OFF” to go to parallel quantity setting.

4.5 Parallel system commissioning


Parallel system should be commissioning when the stand-alone are all intact.
Take 4 units in parallel for example.
1) Confirm the input/output wires connection and input phase sequence are correct; switch off the
battery breaker, and measure the +/- bat voltage of all battery group are normal.

2) Connect the parallel cable, it should be formed loop connection。


3) Switch on the input breaker of unit 1,and access LCD setting interface to setting the working
mode、ID、parallel number、redundant number. The setting interface is showed as below, require
setting the in series number、capacity of battery. The output voltage level and Bypass protection
range are default setting.

4) Turn off the input breaker of Unit 1, and make sure the UPS is off. Turn on the input breaker of Unit
2,access the LCD setting interface, setting the parallel working mode, ID(NO.2), parallel 4 units,
redundant number .The other setting are the same as UPS 1 operation.

IV402E Rev.001SIEL S.p.A.


Data di emissione: 2017-07-24 Pag. 36 di 52 + FR
5) For Unit 3 and Unit 4 UPS, the operation setting are all the same as Unit 1 and 2.
6) Turn on Bypass/input/output breaker of all the paralleled UPS, then confirm all the setting are
correct. Each UPS has their owed different ID.
7) There are only one master in parallel system .The one has a dot behind parallel mode is the
master. You can turn on all the UPS after confirm all the setting are correct.

8) Turn on all the battery breaker and confirm the parameter (V/I) are normal.
9) Connected the Load, and check whether the output current are balance.
Switch on and off the utility breaker to test all the UPS converters system from Utility to battery
and restored function are working find

IV402E Rev.001SIEL S.p.A.


Data di emissione: 2017-07-24 Pag. 37 di 52 + FR
4.6 Display Messages/Troubleshooting
This section lists the event and alarm messages that the UPS might display. The messages are
listed in alphabetical order. This section is listed with each alarm message to help you troubleshoot
problems.

Display messages

Operational Status and Mode(s)

Code Information LED


(ST) stand for Fault Bypass Battery Inverter
1 Initialized EXTINGUISH EXTINGUISH EXTINGUISH EXTINGUISH
2 Standby Mode EXTINGUISH EXTINGUISH X EXTINGUISH
3 No Output EXTINGUISH EXTINGUISH X EXTINGUISH
4 Bypass Mode EXTINGUISH LIGHT X EXTINGUISH
5 Utility Mode EXTINGUISH EXTINGUISH X LIGHT
6 Battery Mode EXTINGUISH EXTINGUISH LIGHT EXTINGUISH
Battery
7 EXTINGUISH EXTINGUISH LIGHT EXTINGUISH
Self-diagnostics
Inverter is
8
starting up
EXTINGUISH X X EXTINGUISH
9 ECO Mode EXTINGUISH X X X
10 EPO Mode LIGHT EXTINGUISH X EXTINGUISH
Maintenance
11 EXTINGUISH EXTINGUISH EXTINGUISH EXTINGUISH
Bypass Mode
12 Fault Mode LIGHT X X X

CAUTION:"X" means it is determined by other conditions

Alarm Information
Fault code
UPS Alarm Warning Buzzer LED
(Err)
1 Rectifier Fault Beep continuously Fault LED lit
Inverter fault(Including Inverter
2 Beep continuously Fault LED lit
bridge is shorted)
3 Inverter Thyristor short Beep continuously Fault LED lit
4 Inverter Thyristor broken Beep continuously Fault LED lit
5 Bypass Thyristor short Beep continuously Fault LED lit
6 Bypass Thyristor broken Beep continuously Fault LED lit
7 Fuse broken Beep continuously Fault LED lit
8 Parallel relay fault Beep continuously Fault LED lit
9 Fan fault Beep continuously Fault LED lit
10 Reserve Beep continuously Fault LED lit
11 Auxiliary power fault Beep continuously Fault LED lit
12 Initializtion fault Beep continuously Fault LED lit
13 P-Battery Charger fault Beep continuously Fault LED lit
14 N-Battery Charger fault Beep continuously Fault LED lit
15 DC Bus over voltage Beep continuously Fault LED lit
16 DC Bus below voltage Beep continuously Fault LED lit
17 DC bus unbalance Beep continuously Fault LED lit
IV402E Rev.001SIEL S.p.A.
Data di emissione: 2017-07-24 Pag. 38 di 52 + FR
18 Soft start failed Beep continuously Fault LED lit
19 Rectifier Over Temperature Twice per second Fault LED lit
20 Inverter Over temperature Twice per second Fault LED lit
21 Input neutral loss Twice per second Fault LED lit
22 Battery reverse Twice per second Fault LED lit
23 Cable connection error Twice per second Fault LED lit
24 CAN comm. Fault Twice per second Fault LED lit
25 Parallel load sharing fault Twice per second Fault LED lit
26 Battery over voltage Once per second Fault LED blinking
27 Mains Site Wiring Fault Once per second Fault LED blinking
28 Bypass Site Wiring Fault Once per second Fault LED blinking
29 Output Short-circuit Once per second Fault LED blinking
30 Rectifier over current Once per second Fault LED blinking
31 Bypass over current Once per second BPS LED blinking
INV or BPS LED
32 Overload Once per second
blinking
33 No battery Once per second Battery LED blinking
34 Battery under voltage Once per second Battery LED blinking
35 Battery low pre-warning Once per second Battery LED blinking
36 Internal Communication Error Once per 2 seconds Fault LED blinking
37 DC component over limit. Once per 2 seconds INV LED blinking
38 Parallel Overload Once per 2 seconds INV LED blinking
39 Mains volt. Abnormal Once per 2 seconds Battery LED lit
40 Mains freq. abnormal Once per 2 seconds Battery LED lit
41 Bypass Not Available BPS LED blinking
42 Bypass unable to trace BPS LED blinking
43 Inverter on invalid
44 Reserve
45 inverter not on
46 Output switch not ON Once per 3 seconds

4.7 Options
SNMP card: internal SNMP / external SNMP optional

◆ Loosen the 2 torque screws (on each side of the card).

◆ Carefully pull out the card. Reverse the procedure for re-installation

The slot called SNMP supports the MEGAtec protocol. We advise that NetAgent II-3 port is
also a tool to remotely monitor and manage any UPS system

NetAgent II-3Ports supports the Modem Dial-in (PPP) function to enable the remote control
via the internet when the network is unavailable.

In addition to the features of a standard NetAgent Mini, NetAgent II has the option to add
NetFeeler Lite to detect temperature, humidity, smoke and security sensors. Thus, making
NetAgent II a versatile management tool. NetAgent II also supports multiple languages and is
setup for web-based auto language detection.

IV402E Rev.001SIEL S.p.A.


Data di emissione: 2017-07-24 Pag. 39 di 52 + FR
Typical topology of the UPS Network Management

Relay card

The card is used for providing the interface for UPS peripheral monitoring. The contact
signals can reflect UPS running status. The card is connected to peripheral monitoring devices
via DB9 female to facilitate the effective monitoring of the real-time status of UPS and timely
feedback the status to monitor when abnormal situation occurs (such as UJPS failure, mains
interruption, UPS bypass and ect.). It is installed in the intelligent slot of the UPS.

The relay card includes 6 output ports and one input port. Please refer to the following table
for detail.

DB9 interface: Connect to upper control terminal. The definition of the pins is defined as
below:

IV402E Rev.001SIEL S.p.A.


Data di emissione: 2017-07-24 Pag. 40 di 52 + FR
Appendix 1 Specifications
MODEL 60KVA 80KVA

Capacity (VA/Watts) 60K / 54K 80K / 72K

INPUT
Nominal voltage 380/400/415Vac, (3Ph+N+PE)
Operating voltage range 208~478Vac
Operating frequency
40Hz-70Hz
range
Power factor ≥0.99
Harmonic distortion
≤3% (100%non-linear load )
(THDi)
220Vac Max.voltage: +25%(optional +10%,+15%,+20% )
230Vac Max.voltage: +20%(optional +10%,+15% )
Bypass voltage range 240Vac Max.voltage: +15%(optional +10% )
Min. voltage: -45% (optional -20%,-30%)
Frequency synchronize tracing range: ±10%

Generator input Support


OUTPUT
Output voltage 380/400/415Vac (3Ph+N+PE)
Voltage regulation ±1%
Power factor 0.9
1.Line Mode: synchronize with input; when input frequency >±10% (±1%/±2%/±4%/±5%
Output frequency optional), output (50/60±0.1)Hz.
2.Battery Mode:(50/60±0.1)Hz
Crest factor 3:1

Harmonic distortion ≤2% with linear load


(THD) ≤5% with non linear load
Efficiency 94.5%

BATTERY

Battery voltage Optional Voltage:±192V/±204V/±216V/±228V/±240Vdc(32/34/36/38/40pcs optional)

Charge Current(A)
(charge current can be
Max.current 30A
set according to battery
capacity installed)
SYSTEM FEATURES
Transfer time Utility to Battery : 0ms; Utility to bypass: 0ms

Overload Load≤110%: last 60min,≤125%: last 10min,≤150%: last 1min,≥150% change to bypass.

Alarm overload, utility abnormal, UPS fault, battery low, etc.


Protection short circuit, overload, over temperature, battery low, fan fault alarm.
USB,RS232, RS485, Parallel port, REPO port, LBS port, Coupler dry contact, Intelligent slot, SNMP
Communication
card (optional), Relay card (optional)
ENVIRONMENTAL
Operating temperature 0℃~40℃
IV402E Rev.001SIEL S.p.A.
Data di emissione: 2017-07-24 Pag. 41 di 52 + FR
Storage temperature -25℃~55℃(no battery)
Humidity range 0~95% (non condensing)
Altitude < 1500m.When>1500m,lower the rated power for use
Noise level <63dB
PHYSICAL
Dimension D×W×H
828x360x868
(mm)
Net weight (kg) 118 122
STANDARDS
Safety IEC/EN62040-1,IEC/EN60950-1

EMC IEC/EN62040-2,IEC61000-4-2,IEC61000-4-3,IEC61000-4-4,IEC61000-4-5,IEC61000-4-6,IEC61000-4-8

Appendix 2 Problems and Solution


In case the UPS cannot work normally, it might be wrong in installation, wiring or operation.
Please check these aspects first. If all these aspects are checked without any problem, please
consult with local agent right away and provide below information.
(1) Product model name and serial number.
(2) Try to describe the fault with more details, such as LCD display info, LED lights status,
etc.
Read the user manual carefully, it can help a lot for using this UPS in the right way. Some FAQ
(frequently asked questions) may help you to troubleshoot your problem easily.

No. Problem Possible reason Solution


Input power supply is not
Measure if the UPS input
Utility is connected but connected;
voltage/frequency is within the
the UPS cannot be Input voltage low;
1 window.
powered ON. The input switch of the
Check if UPS input is switched on
UPS is not switched on.
The input breakers of the
Utility normal but Utility
UPS are not switched Switch on the input breaker;
LED does not light on,
2 on; Make sure the input cable is well
and the UPS operates at
input cable is not well connected.
battery mode
connected
The UPS does not Output cable does not
Make sure the output cable is well
indicate any failure, but well connected;
connected;
3 output do not have Output breaker do not
Switch on the output breaker.
voltage switch on
If the UPS operates at battery mode,
Utility voltage exceeds please pay attention to the
4 Utility LED is flashing
UPS input range. remaining backup time needed for
your system.
Battery LED is flashing Battery breaker does not Switch on the battery breaker. If
but switch on, or batteries batteries are damaged, need to
5
no charge voltage and are damaged, or battery replace whole group batteries,
current is reversely connected. Connect the battery cables correctly;

IV402E Rev.001SIEL S.p.A.


Data di emissione: 2017-07-24 Pag. 42 di 52 + FR
Battery number and Go to LCD setting of the battery
capacity are not set number and capacity, set the correct
correctly. data.
Buzzer beeps every 0.5
seconds and LCD Overload Remove some load
6 display “output overload”

Buzzer long beeps, LCD The UPS output is in Make sure the load is not in short
7 short circuit
display “29”fault code circuit, and then restart the UPS.

The UPS is set to ECO Set the UPS working mode to UPS
The UPS only works on mode, or the transfer type(non-parallel) or to reset the
8
bypass mode times to bypass mode times of transferring to bypass or
are limited. re-start the UPS
Battery switch is not
properly closed:
Close the battery switch:
Battery fuse is not open:
Change the fuse:
Or Battery low:
Recharge the battery:
9 Cannot Black start Battery quantity set
Power ON the UPS with AC to set
wrong;
the battery quantity &quantity;
Power breaker in the
Switch on the power breaker.
rear panel not switch
ON.
Buzzer beeps
continuously and LCD Consult with your local agent for
10 UPS is out of order
indicates 1,3,5,9,15, etc repair
fault codes

Appendix 3 USB communication port definition

Definition of port:

Connection between PC USB port and UPS USB port.

PC USB port UPS USB port Description

Pin 1 Pin 1 PC : +5V

Pin 2 Pin 2 PC : DPLUS signal

Pin 3 Pin 3 PC :DMINUS signal

Pin 4 Pin 4 Signal ground

Available function of USB

IV402E Rev.001SIEL S.p.A.


Data di emissione: 2017-07-24 Pag. 43 di 52 + FR
◆ Monitor UPS power status.

◆ Monitor UPS alarm info.

◆ Monitor UPS running parameters.

◆ Timing off/on setting.

Communication data format

Baud rate ---------- 9600bps

Byte length ---------- 8bit

End bit ---------- 1bit

Parity check ---------none

CAUTION!

USB, RS232 and RS485 interface cannot be used at the same time,
you can only use one of them at one time.

Appendix 4 RS232 communication port definition

Definition of Male port:

Connection between PC RS232 port and UPS RS232 port

PC RS232 port UPS RS232 port

Pin 2 Pin 2 UPS send,PC receive

Pin 3 Pin 3 PC send,UPS receive

Pin 5 Pin 5 ground

IV402E Rev.001SIEL S.p.A.


Data di emissione: 2017-07-24 Pag. 44 di 52 + FR
Available function of RS232

◆Monitor UPS power status.

◆Monitor UPS alarm info.

◆Monitor UPS running parameters.

◆Timing off/on setting.

RS-232 communication data format

Baud rate ---------- 9600bps

Byte length ---------- 8bit

End bit ---------- 1bit

Parity check ---------none

CAUTION!

USB, RS232 and RS485 interface cannot be used at the same time,
you can only use one of them at one time.

Appendix 5 RS485 communication port definition

Definition of port:

Connection between the Device’s RS485 port and UPS RS485 port.

device(RJ45) UPS(RJ45) Description

Pin 1/5 Pin 1/5 485+ “A”

Pin 2/4 Pin 2/4 485 - “B”

Pin7 Pin7 +12Vdc

Pin8 Pin8 GND

Available function of RS485

◆ Monitor UPS power status.

◆ Monitor UPS alarm info.

IV402E Rev.001SIEL S.p.A.


Data di emissione: 2017-07-24 Pag. 45 di 52 + FR
◆ Monitor UPS running parameters.

◆ Timing off/on setting.

◆Battery environment temperature monitoring.

◆Charging voltage modulation depending on batteries temperature

Communication data format

Baud rate ---------- 9600bps

Byte length ---------- 8bit

End bit ---------- 1bit

Parity check ---------none

CAUTION!

USB, RS232 and RS485 interface cannot be used at the same time,
you can only use one of them at one time.

RS485 port pin7 is 12Vdc!

IV402E Rev.001SIEL S.p.A.


Data di emissione: 2017-07-24 Pag. 46 di 52 + FR
Appendix 6 BAT_T communication port definition

Definition of port:

Connection between the Temperature senator RJ45 port and UPS RJ45 port.

Temperature senator(RJ45) UPS BAT_T(RJ45) Description

Pin 1/5 Pin 1/5 TX

Pin 2/4 Pin 2/4 RX

Pin 7 Pin 7 12V

Pin 8 Pin 8 GND

Available function of BAT_T

◆Battery environment temperature monitoring.

◆Charging voltage modulation depending on batteries’ temperature

IV402E Rev.001SIEL S.p.A.


Data di emissione: 2017-07-24 Pag. 47 di 52 + FR
Appendix 7 LBS communication port definition

Definition of port:

Connection between the UPS1’s LBS1 port and UPS2’s LBS2 port.

UPS1 LBS1(RJ45) UPS2 LBS2(RJ45) Description

Pin 1/5 Pin 1/5 LBS_BPSIDE_BC

Pin 2/4 Pin 2/4 LBS_TRACE_BC

Pin 8 Pin 8 GND

Available function of LBS

◆The output power of two or more UPS in non-parallel system should be synchronized with each

other.

◆The output phase of two or more UPS in non-parallel system should be synchronized with each

other.

CAUTION!

Two or more LBS cables must be used to form a ring when two or more
LBS in non-parallel system.

IV402E Rev.001SIEL S.p.A.


Data di emissione: 2017-07-24 Pag. 48 di 52 + FR
Appendix 8 Dry contact port communication port definition
Definition of Male port:

Instruction:

UPS Instruction
Pin1 UPS Battery Low

Pin2 AC Power Failure

Pin3 Turn off UPS

Pin4 Common GND

Function description:

◆ Monitor UPS status;

◆ Monitor UPS battery status;

◆ Shutdown UPS.

IV402E Rev.001SIEL S.p.A.


Data di emissione: 2017-07-24 Pag. 49 di 52 + FR
Appendix 9 REPO instruction

Definition of port:
Connection diagram:

Connection between the button and UPS REPO port.

Button UPS REPO Description

Pin 1 Pin 1 EPO

Pin 2 Pin 2 GND

◆A remote emergency stop switch can be installed in a remote location and connection through

simple wires to the REPO connector.

◆The remote switch can be connected to several UPS in a parallel architecture allowing the user to

stops all units at once.

IV402E Rev.001SIEL S.p.A.


Data di emissione: 2017-07-24 Pag. 50 di 52 + FR
Appendix 10 Dust-proof net replacement

1)Remove the screws of the right and left panel, and then open both panels

2)Remove the screws at the left side of the front panel, remove the LCD connection cable , then

remove the front panel.

IV402E Rev.001SIEL S.p.A.


Data di emissione: 2017-07-24 Pag. 51 di 52 + FR
3)Remove the dust proof net according to the following direction.

IV402E Rev.001SIEL S.p.A.


Data di emissione: 2017-07-24 Pag. 52 di 52 + FR

You might also like