1.1. Installation
This is permanently connected equipment, and it must be installed by qualified
maintenance personnel.
Condensation may occur if the UPS is moved directly from a cold to a warm
environment. The UPS must be absolutely dry before being installed. Please
allow an acclimatization time of at least two hours.
Do not install the UPS near water or in damp environment.
Do not install the UPS where it would be exposed to direct sunlight or near heat.
Do not connect appliances or items of equipment which would overload the UPS
(e.g. laser printers, etc.) to the UPS output.
Do not block ventilation openings in the UPS’s housing. Ensure allow at least
0.5m of space on front and rear of the UPS.
Place cables in such a way that no one can step on or trip over them.
Connect UPS with the earth reliably before connecting to the building wiring
terminal, and external battery source must also be earthed.
An integral single emergency switching device which prevents further supply to
the load by the UPS in any mode of operation should be provided in the building
wiring installation.
An appropriate disconnect device as short-circuit backup protection should be
provided in the building wiring installation.
The equipment is powered by two sources: the mains source, the internal
battery or the external battery source.
With the installation of the equipment, the sum of the leakage current of the UPS
and the connected load does not exceed 5% of rated value of input current.
1.2. Operation
Do not disconnect the main cable on the UPS or the building wiring terminals
during operation since this would remove the protective earth from the UPS and
all connected loads.
The UPS output terminal block may still be electrically lived even if the UPS is
1
not connected to the building wiring terminal, for there is internal current source
(batteries).
In order to fully disconnect the UPS, first turn the input breaker in the "OFF"
position, then disconnect the mains lead.
Indiscriminate operation of switches may cause output loss or damage to
equipment. Refer to instruction before conducting any control.
While the UPS work as a parallel system, the external parallel cable should be
reinforced insulation.
Ensure that no liquid or other foreign objects can enter the UPS.
2
1.4. Transport
Please transport the UPS only in the original packaging to protect against shock
and impact.
1.5. Storage
The UPS must be stockpiled in the room where is ventilated and dry.
1.6. Standards
* Safety
IEC/EN 62040-1
* EMI
*EMS
3
2. Description of Commonly Used Symbols
Some or all of the following symbols may be used in this manual. It is advisable to
familiarize yourself with them and understand their meaning:
Do not dispose
Recycle with ordinary
trash
3. Introduction
This On-Line series is an uninterruptible power supply incorporating
double-converter technology. It provides perfect protection specifically for computer
equipments, communication servers, and data centers.
The double-converter principle eliminates all mains power disturbances. A rectifier
converts the alternating current from the mains power to direct current. On the
basis of this DC voltage, the inverter generates an AC sinusoidal voltage, which
constantly supplies the loads. In the event of power failure, the maintenance-free
batteries power the inverter.
This manual covers the UPS listed as follows.
OLS6000ERT6U(M)
Standard
OLS6000ERT6U(M)
4
3.1. Feature
This series UPS is a new generation of UPS, which provides the outstanding
reliability, and most cost-performance ratio in the industrial. Following benefit the
product has:
True online double-conversion technology with high power density, frequency
independence and generator compatibility.
High input power factor ≥0.99,overall high efficiency ≥ 92%, save power
and wiring expense. Low input current distortion, avoid power pollution.
Output power factor is 0.9, perfect output sine waveform, suitable almost all
critical equipment.
Outstanding adaptability to the worst mains input condition. Extra wide input
voltage, frequency range and waveform, avoid excessive dissipating limited
battery energy.
N+X parallel redundancy to increase the reliability and flexibility. Number of
parallel operating UPS is up to 4.
ECO mode with high efficiency ≥96%, save power expense for user.
Start-able without battery.
Automatically select charging current through the external Battery Type and
external battery pack setting.
5
Fig.3-2 The rear view of OLS6000/10000ERT6U(M) Battery module
① Fuse: Replaceable fuse is accessible from the rear panel. It must be done by
qualified personnel.
② Output Connector: Use this output connector to connect the Battery module
and the Power module.
③ Battery Input Terminal Block: Use this input Terminal Block to daisy chain the
next Battery module.
Input
Phase Single
Battery
Output
Voltage* 208/220/230/240Vac
6
Synchronized 50/60×(1±10%)Hz @Line mode
Frequency
50/60×(1±0.1%)Hz @Battery mode
Line mode:
10 min 105%~125%
1 min 125%~150%
Over Load** 10 s 150%~170%
100ms >170%
Battery mode:
2 min 105%~125%
30 s 125%~150%
100ms >150%
*The load capacity would be derated to 90% automatically when the output voltage
is adjusted to 208Vac.
**The overload capacity would be derated automatically in Line mode while the
circumstance temperature is larger than 35 degree.
Note: The load capacity should be derated 1% every 100m heightened on the basis
of 1000m.
OLS10000ERT6U 438*261*680 86
7
4. Unpacking
Power Module Contains:
Power Module
Power Module
User’s Manual
Rackmount Ears
Rackmount Left Rail Rackmount Right Rail Terminal*11PCS
(Stands)*2PCS
Flat Head Screws: Pan Head Screws: Screw Hole Dust Plastic Washers
M4X8L*8PCS M5X12L*13PCS Covers*8PCS *8PCS
8
Battery Module Contains:
Battery Module
Rackmount Ears
Rackmount Left Rail Rackmount Right Rail
(Stands)*2PCS
9
*The Below table only for OLS6000ERT6UM/OLS10000ERT6UM
Manual Bypass PDU Contains:
***Manual Bypass PDU installed and used please refer to the User’s Manual of
Manual Bypass PDU.
CAUTION! Inspect the appearance of the UPS to see if there is any damage during
transportation. Do not turn on the unit and notify the carrier and dealer immediately if
there is any damage or lacking of some parts.
10
5. Hardware Installation
CAUTION! To prevent the risk of fire or electric shock, only use the supplied
hardware to attach the mounting brackets.
2) Insert dust cover into the rackmount ear screw holes that are not being used.
11
Step2.Rackmount rails installation:
1) The rails adjust to mount in 48-cm
(19-inch) panel racks from 52 to 91.5cm
(20.5 to 36 inches) deep. Select the
proper holes in the rack for positioning the
Power module in the rack. The Power
module takes up position 1 through
position 9.
2) Attach the rackmount rail to your rack with
two M5X12L screws and two plastic
washers at the front of the rack. (Located
in position 1 & position 6) Do not tighten
the screws. Adjust the rail size on the rail
assembly of your rack. Secure the rail to
the rear of the rack with two M5X12L
screws and two plastic washers. Tighten all screws at the front and rear of the
rail. Once completed, perform the same steps for assembling the other
rackmount rail.
12
Step3.Install the Power module on the rack:
1) Place the Power module on a flat stable surface with the front of the unit facing
toward you. Secure the Power module to your rack with four M5X12L screws
at the front of the rack. (Located in position 2 & position 8).
2) Once completed, perform the same steps for the Battery module.
CAUTION! The Battery module must be installed below the Power module.
13
2) Unscrew the left panel of the Power module. Separate the left panel from
Power module.
3) Rotate the LCD module to the left. Reinstall it for a tower configuration .
4) Last tighten the screws to fix the left panel and the right panel.
14
Step2.Attach the base stands:
1) Tighten the screws (M5X12*4pcs) of the base stands (rackmount ears) onto
the bottom of Power module and Battery module.
2) Insert dust cover into the rackmount ear screw holes that are not being used.
15
6. Electrical Installation
6.1. Power Wires Installation
The system must be installed and wired only by qualified electricians in
accordance with applicable safety regulations!
For safety, please cut off the mains power switch before installation!
When installing the electrical wiring, please note the nominal amperage of your
incoming feeder.
AC Contactor
L
Main
N Input
Input Main
Breaker UPS
16
2) No matter the Power module is connected to the mains power or not, the
output of the Power module may be electrically live. The parts inside the unit
may still have hazardous voltage after turning off the Power module. To make
the Power module have no output, turn off the Power module, and cut off the
mains power supply, wait the Power module shut down completely, finally cut
off the battery connection.
3) Open the terminal block cover located on the rear panel of Power module,
please refer to the appearance diagram.
17
10) It is requested to use the accessorial terminal splices which can be compacted
on the wires tightly, to ensure the connection between the wires and the
terminal block is reliable.
Important notes:
If the Power module is used in single mode, the output must be connected to sL and
sN.
If the Power module is used in parallel mode, the output must be connected to pL
and pN.
11) Install an output breaker between the output terminal of Power module and the
load, and the breaker should with leakage current protective function if
necessary.
12) Turn off all the loads first before connecting the load with the Power module,
then perform the connection and finally turn on the loads one by one.
13) After completing the installation, please check the wires to make sure all were
connected correctly and tightly.
14) Suggest charging the batteries for 8 hours before use. After Installation, turn
on the mains power switch and turn the input breaker in the "ON" position, the
Power module will charge the batteries automatically. It can also use the
Power module immediately without charging the batteries, but the backup time
may be less than the standard value.
15) If it is necessary to connect the inductance load such as a monitor or a laser
18
printer to the Power module, the start-up power should be used for calculating
the capacity of the Power module, as its start-up power consumption is too big
to make the Power module which capacity is small fail easily.
2) Connect the Battery Cable to the Power module and ensure the polarity is
right.
3) Loosen the screws to remove the Output Connector Cover of Battery module.
19
4) Connect the Battery Cable to the Battery module. Once completed, retighten
the Block Cover.
Fig.6-3 Enable the EPO status Fig.6-4 Disable the EPO status
To recover to normal status, first EPO connector should be closed (Fig.6-4), and
enter LCD menu (illustrated in the chapter of 7.3) to clear EPO status, then UPS
would stop alarm and recover to Bypass model. And UPS needs be turned on by
manual operation.
20
7. Operation
7.1. Display Panel
The UPS has a five-button, dot matrix LCD with white text and a blue background.
Besides the LCD, the UPS has four colorized LED to provide more convenient
information.
21
Press this button more than 200ms to move the focus to
UP
the up menu
Press this button for more than 200ms to move the focus
Down
to the down menu
LED definition:
Turn on ※ ※ ※ ※
Fault mode □ 〇
Warning mode □ □ □ ★
Battery mode Beep every 4 seconds, if battery low, buzzer Beep every second
22
The UPS provides useful information about UPS itself, load status, battery, events,
identification, and settings through the front panel display.
During powering on, the LCD would display the CyberPower logo for several
seconds and then enter to the default page which shows the UPS status summary.
On the UPS status screen it provides the following information:
Status summary, including mode, load, battery and utility
Alarm status, if any is present.
Fault status, if any is present.
Output parameter, including output voltage, current and frequency.
Input parameter, including input voltage and frequency.
Bypass parameter, including bypass voltage and frequency.
Power parameter, including output VA and watt.
Battery parameter, including battery capacity, voltage and remain time.
23
powered on. At this time the fan begins to rotate, LCD will show "CyberPower".
Then LCD will show the default UPS status summary screen after UPS
finishing self-test.
4) By pressing button continuously for more than 1s,the buzzer will beep for
1s, UPS starts to turn on.
5) A few seconds later, the UPS turns into Battery mode. If the mains power
comes back, the UPS will transfer to Line mode without output interruption of
the UPS.
Turning off UPS with mains:
1) To turn off the inverter of UPS by pressing button continuously for more
than 3s and the buzzer will beep for 3s. The UPS will turn into Bypass mode at
once.
2) When completing the above action, UPS output voltage is still present. In order
to cut off the UPS output, simply cut off the mains power supply. A few
seconds later, LCD display shuts down and no output voltage is available from
the UPS output terminal.
Turning off UPS without mains:
1) To power off the UPS by pressing button continuously for more than 3s,
and the buzzer will beep 3s. The UPS will cut off the output at once.
2) A few seconds later, LCD shuts down and no voltage is available from the UPS
output.
24
menu, event menu and identification menu. See Fig.7-3.
Alarm
0002:12:20:00
Cyberpower Line site
2/10
Up>200mS Down>200mS
Up>200mS Down>200mS
Alarm Alarm
0002:12:00:00 Enter>200mS 0002:12:00:00
Control Overload Overload
ESC>200mS ESC>200mS
Setting 1/10 1/10
Events ESC>200mS
ID
Fault Fault
0003:12:00:00 Enter>200mS 0003:12:00:00
Over tempearture Over tempearture
ESC>200mS
1/5 1/5
Down>200mS Up>200mS
.
. Up>200mS Down>200mS
Output parameter .
Volt: 230 V
Curr: 14.5 A
Freq: 50.0 Hz
Down>200mS Up>200mS
Input parameter
Volt: 223.5 V
Freq: 50.1 Hz
Down>200mS Up>200mS
Bypass parameter
Volt: 223.5V
Freq: 50.1Hz
Down>200mS Up>200mS
Power parameter
KW: 3.6
KVA:3.6
Down>200mS Up>200mS
Bat parameter
Bat Volt: 260V
Capacity: 95 %
Rmn time 14 Min
Up>200mS
Down>200mS
25
Buzzer mute
Yes
No
Clr EPO status
Yes
Buzzer mute No
Clr EPO status
Battery test
Battery test
Single UPS off
Yes
No
Yes
No
Please input
Password Sub setting...
****
Event
0001:12:00:00
Utility abnormal
1/10
Control Alarm
Setting 0002:12:00:00
Events Overload
ID 1/10
Fault
0003:12:00:00
Over tempearture
1/5
Yes
No
Type/model
OLS 6000ERT6U
Long model
Serial number
Type/model ************
Serial number
Rating Rating
Firmware version IP:230Vac/50Hz
OP:230Vac/50Hz
Power:6kVA/5.4kW
Firmware version
Ver:0.0.1
26
The control menu:
By pressing , enter the menu of "Control". The display would enter the next
control menu screen.
1) Buzzer mute
2) Battery test: is one command to control all UPS in a parallel system to do the
battery test at the same time.
3) Clear EPO status: once EPO status is enabled, the UPS output would be cut
off. To recover to normal status, first EPO connector should be closed, and
enter this menu to clear EPO status, then UPS would stop alarm and recover
to Bypass model. And UPS needs be turned on by manual operation.
4) Single UPS off: is one command to turn off one UPS which is operated
currently in parallel system, and other UPS continue working to supply the load
in the parallel system.
The setting menu:
Please contact your local distributor for further information before using the settings.
Some settings would change the specification, and some settings would enable or
disable some functions. The unsuitable option set by user may result in potential
failures or protecting function loss, even directly damage the load, battery or
UPS.The most of settings could only be done while UPS is in Bypass mode.
27
Short circuit clearance enabled/disabled disabled
28
8. Special Function
The series UPS has some special functions, which could satisfy some special
application of user. And the functions have own features, please contact your local
distributor for further information before using the function.
29
power strategy setting menu by following chapter of 7.3.
30
4) Connect the output wires of each UPS to an output breaker panel, and connect
each output breaker to a main output breaker and then to the loads.
5) CAUTION: Each UPS needs an independent battery pack.
6) Please refer to the wiring diagram in the following diagram.
1# Battery pack
UPS1 Output
UPS1 Input
Breaker
Breaker
2# Battery pack
UPS2 Input
UPS2 Output
Breaker
Breaker
31
TO UTILITY
Main Maintenance
Bypass Switch
TO LOAD
32
than 0.5V. If the difference is more than 0.5V, the UPS need to be regulated.
10) Press the button of one UPS, each UPS would start to turn off and
transfer to the Bypass mode, switch on the output breaker of each UPS to
parallel all the output of UPS together.
11) Press the button of one UPS, each UPS would start to turn on , after
turning on, the UPS should work parallel in the Line mod
How to join a new UPS to a parallel system:
1) First the parallel system must be installed one main maintenance bypass
switch.
2) Regulate the output voltage of the new UPS separately: check if the output
voltage difference between the new UPS and the parallel system is less than
0.5V.
3) Ensure the bypass of the parallel system is normal and the bypass setting is
"enable", Press the button of one UPS, each UPS would turn off and the
UPS system would transfer to the Bypass mode.
4) Set the main maintenance bypass switch from "UPS" to "BPS", switch off the
main output breaker and the main input breaker, the UPS would shut down.
5) Ensure the UPS shut down totally, add the new UPS and reinstall the new
UPS parallel system by following step 1) to 10) of last chapter - "How to install
a new parallel UPS system".
6) Switch on the main input breaker and the main output breaker, and set the
main maintenance bypass switch from "BPS" to "UPS", Press the button
of one UPS, each UPS would start to turn on, after turning on, the UPS should
work parallel in the Line mode.
How to remove a single UPS from a parallel system:
1) First the parallel system must be installed one main maintenance bypass
switch.
2) Ensure the bypass of the parallel system is normal and the bypass setting is
"enable", Press the button of one UPS, each UPS would turn off and the
UPS system would transfer to the Bypass mode.
3) Set the main maintenance bypass switch from "UPS" to "BPS", switch off the
main output breaker and the main input breaker, the UPS would shut down.
4) Ensure the UPS shut down totally, remove the wanted UPS and reinstall the
new UPS parallel system by following step 1) to 10) of last chapter - "How to
33
install a new parallel system".
5) Switch on the main input breaker and the main output breaker, and set the
main maintenance bypass switch from "BPS" to "UPS", Press the button
of one UPS, each UPS would start to turn on, after turning on, the UPS should
work parallel in the Line mode.
9. Trouble Shooting
If the UPS system does not operate correctly, first check the operating information
on the LCD display. Please attempt to solve the problem using the table below. If
the problem still persists, consult your dealer.
34
Battery voltage is
Check if the battery quantity is
Battery Over Voltage higher than normal
right.
value
The UPS will turn off the
Battery is over
Over Charge charger until the battery voltage
charged
is normal
The ambient
Check the environment
Amb NTC abnormal temperature is too
ventilation.
high
Ambient NTC abnormal UPS internal fault Consult dealer.
35
9.2. Trouble Shooting According To Fault Indication
Problem Displayed Possible cause Remedy
Fan blocked or
Fan fail Check the fan status
disconnected over time
Output voltage is
Back feed Consult dealer
returned to input
36
9.3. Trouble Shooting In Else Cases
Problem Possible cause Remedy
Please have the following information at hand before calling the After-Sales Service
Department:
1) Model number, serial number
2) Date on which the problem occurred
3) LCD/LED display information, Buzzer alarm status
4) Mains power condition, load type and capacity, environment temperature,
ventilation condition
5) The information (battery capacity, quantity) of Battery pack
6) Other information for complete description of the problem
37
10. Battery Maintenance
Battery replacement should be performed by qualified personnel.
This series UPS only requires minimal maintenance. The batteries used for
battery pack are value regulated sealed lead-acid maintenance free battery.
These models require minimal repairs. The only requirement is to charge the
UPS regularly in order to maximize the expected life of the battery. When
being connected to the utility power, whether the UPS is turned on or not, the
UPS keeps charging the batteries and also offers the protective function of
overcharging and over-discharging.
The UPS should be charged once every 4 to 6 months if it has not been used
for a long time.
In the regions of hot climates, the battery should be charged and discharged
every 2 months. The standard charging time should be at least 12 hours.
Under normal conditions, the battery life lasts 3 to 5 years. In case if the
battery is found not in good condition, earlier replacement should be made.
Battery replacement should be performed by qualified personnel.
Replace batteries with the same number and same type of batteries.
Do not replace the battery individually. All the batteries should be replaced at
the same time following the instructions of the battery supplier.
If the battery service life (3~5 years at 25°C ambient temperature) has been
exceeded, the batteries must be replaced.
38
11. Communication Port
11.1. USB Interface
The USB port is compliance with USB 1.1 protocol for its communication software.
39