CyberPower OLS6000-10000ERT6U User Manual

Download as pdf or txt
Download as pdf or txt
You are on page 1of 42

Userˊs Manual

OLS6000ERT6U
OLS10000ERT6U
OLS6000ERT6UM
OLS10000ERT6UM

CyberPower Systems Inc.


www.cyberpower.com
K01-C000250-02
CONTENT:
1. Safety ..............................................................................................................1
1.1. Installation ..................................................................................................1
1.2. Operation ....................................................................................................1
1.3. Maintenance, Servicing and Faults .............................................................2
1.4. Transport ....................................................................................................3
1.5. Storage .......................................................................................................3
1.6. Standards ...................................................................................................3
2. Description of Commonly Used Symbols ....................................................4
3. Introduction ....................................................................................................4
3.1. Feature .......................................................................................................5
3.2. Electrical Specifications ..............................................................................6
3.3. Operating Environment ...............................................................................7
3.4. Dimensions and Weights ............................................................................7
4. Unpacking .......................................................................................................8
5. Hardware Installation ...................................................................................11
5.1. Rackmount Installation .............................................................................11
5.2. Vertical/Tower Installation .........................................................................13
6. Electrical Installation ...................................................................................16
6.1. Power Wires Installation ...........................................................................16
6.2. Operating Procedure for Connecting with the Battery module ..................19
6.3. EPO Connection .......................................................................................20
7. Operation ......................................................................................................21
7.1. Display Panel ............................................................................................21
7.2. Turning On and Turning Off UPS ..............................................................23
7.3. LCD Operation ..........................................................................................24
8. Special Function ..........................................................................................29
8.1. ECO Function ...........................................................................................29
8.2. Converter Function ...................................................................................29
8.3. Parallel Function .......................................................................................30
9. Trouble Shooting .........................................................................................34
9.1. Trouble Shooting According To Warning Indication ..................................34
9.2. Trouble Shooting According To Fault Indication .......................................36
9.3. Trouble Shooting In Else Cases ...............................................................37
10. Battery Maintenance..................................................................................38
11. Communication Port ....................................................................................39
11.1. USB Interface .........................................................................................39
11.2. RS232 Interface .....................................................................................39
11.3. Intelligent slot .........................................................................................39
1. Safety
Please read carefully the following user manual and the safety instructions
before installing the unit or using the unit!

1.1. Installation
 This is permanently connected equipment, and it must be installed by qualified
maintenance personnel.
 Condensation may occur if the UPS is moved directly from a cold to a warm
environment. The UPS must be absolutely dry before being installed. Please
allow an acclimatization time of at least two hours.
 Do not install the UPS near water or in damp environment.
 Do not install the UPS where it would be exposed to direct sunlight or near heat.
 Do not connect appliances or items of equipment which would overload the UPS
(e.g. laser printers, etc.) to the UPS output.
 Do not block ventilation openings in the UPS’s housing. Ensure allow at least
0.5m of space on front and rear of the UPS.
 Place cables in such a way that no one can step on or trip over them.
 Connect UPS with the earth reliably before connecting to the building wiring
terminal, and external battery source must also be earthed.
 An integral single emergency switching device which prevents further supply to
the load by the UPS in any mode of operation should be provided in the building
wiring installation.
 An appropriate disconnect device as short-circuit backup protection should be
provided in the building wiring installation.
 The equipment is powered by two sources: the mains source, the internal
battery or the external battery source.
 With the installation of the equipment, the sum of the leakage current of the UPS
and the connected load does not exceed 5% of rated value of input current.

1.2. Operation
 Do not disconnect the main cable on the UPS or the building wiring terminals
during operation since this would remove the protective earth from the UPS and
all connected loads.
 The UPS output terminal block may still be electrically lived even if the UPS is

1
not connected to the building wiring terminal, for there is internal current source
(batteries).
 In order to fully disconnect the UPS, first turn the input breaker in the "OFF"
position, then disconnect the mains lead.
 Indiscriminate operation of switches may cause output loss or damage to
equipment. Refer to instruction before conducting any control.
 While the UPS work as a parallel system, the external parallel cable should be
reinforced insulation.
 Ensure that no liquid or other foreign objects can enter the UPS.

1.3. Maintenance, Servicing and Faults


 Do not remove the enclosure since the UPS operates with hazardous voltages.
It is to be serviced only by qualified maintenance personnel.
 Caution! Risk of electric shock. Even after the unit is disconnected from the
mains power supply (building wiring terminal) components inside the UPS are
still connected to the battery which are potentially dangerous.
 Before carrying out any kind of service or maintenance, isolate UPS and
disconnect the batteries. Verify that no current is present and no hazardous
voltage exists in the capacitor or BUS capacitor.
 Batteries must be replaced only by qualified personnel.
 Batteries have a high short-circuit current and pose a risk of shock. Take all
precautionary measures specified below and any other necessary measures
when working with batteries:
─ remove all jewellery, wristwatches, rings and other metal objects
─ use only tools with insulated grips and handles.
 When changing batteries, replace with the same quantity and the same type of
batteries.
 Do not attempt to dispose of batteries by burning them. It could cause explosion.
 The UPS may be connected to Battery pack. Proper disposal of batteries is
required. Refer to your local codes for disposal requirements.
 Do not open or destroy batteries. Effluent electrolyte can cause injury to the skin
and eyes. It may be toxic.
 Replace the fuse only by a fuse of the same type and of the same spec in order
to avoid fire hazards.

2
1.4. Transport
Please transport the UPS only in the original packaging to protect against shock
and impact.

1.5. Storage
The UPS must be stockpiled in the room where is ventilated and dry.

1.6. Standards
* Safety

IEC/EN 62040-1

* EMI

Conducted Emission................................:IEC/EN 62040-2 Category C3

Radiated Emission...................................:IEC/EN 62040-2 Category C3

*EMS

ESD....................................................... ..:IEC/EN 61000-4-2 Level 3

RS............................................................:IEC/EN 61000-4-3 Level 3

EFT..........................................................:IEC/EN 61000-4-4 Level 4

SURGE....................................................:IEC/EN 61000-4-5 Level 4

Low Frequency Signals............................:IEC/EN 61000-2-2

Warning: This is a product for commercial and industrial application in the


second environment-installation restrictions or additional measures may be
needed to prevent disturbances.

3
2. Description of Commonly Used Symbols
Some or all of the following symbols may be used in this manual. It is advisable to
familiarize yourself with them and understand their meaning:

Symbol and Explanation

Symbol Explanation Symbol Explanation

Alert you to pay Caution of high


special attention voltage

Alternating current Direct current


source(AC) source(DC)

Turn on or turn off Protective


the UPS ground

Do not dispose
Recycle with ordinary
trash

3. Introduction
This On-Line series is an uninterruptible power supply incorporating
double-converter technology. It provides perfect protection specifically for computer
equipments, communication servers, and data centers.
The double-converter principle eliminates all mains power disturbances. A rectifier
converts the alternating current from the mains power to direct current. On the
basis of this DC voltage, the inverter generates an AC sinusoidal voltage, which
constantly supplies the loads. In the event of power failure, the maintenance-free
batteries power the inverter.
This manual covers the UPS listed as follows.

Mode NO. Type

OLS6000ERT6U(M)
Standard
OLS6000ERT6U(M)

4
3.1. Feature
This series UPS is a new generation of UPS, which provides the outstanding
reliability, and most cost-performance ratio in the industrial. Following benefit the
product has:
 True online double-conversion technology with high power density, frequency
independence and generator compatibility.
 High input power factor ≥0.99,overall high efficiency ≥ 92%, save power
and wiring expense. Low input current distortion, avoid power pollution.
 Output power factor is 0.9, perfect output sine waveform, suitable almost all
critical equipment.
 Outstanding adaptability to the worst mains input condition. Extra wide input
voltage, frequency range and waveform, avoid excessive dissipating limited
battery energy.
 N+X parallel redundancy to increase the reliability and flexibility. Number of
parallel operating UPS is up to 4.
 ECO mode with high efficiency ≥96%, save power expense for user.
 Start-able without battery.
 Automatically select charging current through the external Battery Type and
external battery pack setting.

Fig.3-1 The rear view of OLS6000/10000ERT6U(M) Power module

5
Fig.3-2 The rear view of OLS6000/10000ERT6U(M) Battery module
① Fuse: Replaceable fuse is accessible from the rear panel. It must be done by
qualified personnel.
② Output Connector: Use this output connector to connect the Battery module
and the Power module.
③ Battery Input Terminal Block: Use this input Terminal Block to daisy chain the
next Battery module.

3.2. Electrical Specifications


Model OLS6000ERT6U(M) OLS10000ERT6U(M)

Input

Phase Single

Voltage Rage 110~276Vac (Depends on load level)

Frequency Rage 50/60±10%Hz

Rated Current 36A 55A

Power Factor ≥0.99 @ full load

Battery

Rated Voltage 240Vdc

Rated Current 28A 47A

Output

Power Rating 6kVA/5.4kW 10kVA/9kW

Voltage* 208/220/230/240Vac

6
Synchronized 50/60×(1±10%)Hz @Line mode
Frequency
50/60×(1±0.1%)Hz @Battery mode

Wave Form sine

Load Type PF 0.5~1, lagging

THDV ≤ 2% @ full linear load;≤5% @ full nonlinear load

Line mode:
10 min 105%~125%
1 min 125%~150%
Over Load** 10 s 150%~170%
100ms >170%
Battery mode:
2 min 105%~125%
30 s 125%~150%
100ms >150%
*The load capacity would be derated to 90% automatically when the output voltage
is adjusted to 208Vac.
**The overload capacity would be derated automatically in Line mode while the
circumstance temperature is larger than 35 degree.

3.3. Operating Environment


Temperature Humidity Altitude Storage
temperature
0℃~40℃ <95% <1000m -15℃~50℃

Note: The load capacity should be derated 1% every 100m heightened on the basis
of 1000m.

3.4. Dimensions and Weights


Dimensions
Model Net Weight(kg)
W×H×D(mm)

OLS6000ERT6U 438*261*680 72.5

OLS10000ERT6U 438*261*680 86

OLS6000ERT6UM 438*261*821 75.1

OLS10000ERT6UM 438*261*821 88.6

7
4. Unpacking
Power Module Contains:

Power Module
Power Module
User’s Manual

RS232 Cable USB Communication Parallel Port


Parallel Cable
(optional) Cable Cover Plate

Rackmount Ears
Rackmount Left Rail Rackmount Right Rail Terminal*11PCS
(Stands)*2PCS

Flat Head Screws: Pan Head Screws: Screw Hole Dust Plastic Washers
M4X8L*8PCS M5X12L*13PCS Covers*8PCS *8PCS

*PowerPanel® Personal Edition software is available on our website. Please visit


www.cyberpower.com and go to the Software Section for free download.

8
Battery Module Contains:

Battery Module

Rackmount Ears
Rackmount Left Rail Rackmount Right Rail
(Stands)*2PCS

Flat Head Screws: Pan Head Screws: Screw Hole Dust


M4X8L*8PCS M5X12L*13PCS covers*8PCS

Plastic Washers*8PCS Battery Cable(RED)

9
*The Below table only for OLS6000ERT6UM/OLS10000ERT6UM
Manual Bypass PDU Contains:

Manual Bypass PDU User’s


Manual Bypass PDU
Manual

UPS Input Cable(BLUE) Terminal

Flat Head Screws:


UPS Output Cable(GRAY)
M4X8L*8PC

Round Head Screws:


Rackmount Ears*2PCS
M3X6L*4PC

***Manual Bypass PDU installed and used please refer to the User’s Manual of
Manual Bypass PDU.
CAUTION! Inspect the appearance of the UPS to see if there is any damage during
transportation. Do not turn on the unit and notify the carrier and dealer immediately if
there is any damage or lacking of some parts.

10
5. Hardware Installation
CAUTION! To prevent the risk of fire or electric shock, only use the supplied
hardware to attach the mounting brackets.

5.1. Rackmount Installation


UPS systems can be mounted in a rackmount or vertical tower orientation. This
versatility is especially important to growing organizations with changing needs that
value having the option to position a UPS on a floor or in a rackmount system. Please
follow the instructions below for the respective mounting methods.
Step1.Rackmount ears installation:
1) Attach the two rackmount ears to the Power module using the provided screws
M4X8L*8pcs.

2) Insert dust cover into the rackmount ear screw holes that are not being used.

11
Step2.Rackmount rails installation:
1) The rails adjust to mount in 48-cm
(19-inch) panel racks from 52 to 91.5cm
(20.5 to 36 inches) deep. Select the
proper holes in the rack for positioning the
Power module in the rack. The Power
module takes up position 1 through
position 9.
2) Attach the rackmount rail to your rack with
two M5X12L screws and two plastic
washers at the front of the rack. (Located
in position 1 & position 6) Do not tighten
the screws. Adjust the rail size on the rail
assembly of your rack. Secure the rail to
the rear of the rack with two M5X12L
screws and two plastic washers. Tighten all screws at the front and rear of the
rail. Once completed, perform the same steps for assembling the other
rackmount rail.

12
Step3.Install the Power module on the rack:
1) Place the Power module on a flat stable surface with the front of the unit facing
toward you. Secure the Power module to your rack with four M5X12L screws
at the front of the rack. (Located in position 2 & position 8).

2) Once completed, perform the same steps for the Battery module.
CAUTION! The Battery module must be installed below the Power module.

5.2. Vertical/Tower Installation


Step1.Rotate the multifunction LCD module:
1) Unscrew the right panel of the Power module. Separate the right panel from
Power module.

13
2) Unscrew the left panel of the Power module. Separate the left panel from
Power module.

3) Rotate the LCD module to the left. Reinstall it for a tower configuration .

4) Last tighten the screws to fix the left panel and the right panel.

14
Step2.Attach the base stands:
1) Tighten the screws (M5X12*4pcs) of the base stands (rackmount ears) onto
the bottom of Power module and Battery module.

2) Insert dust cover into the rackmount ear screw holes that are not being used.

15
6. Electrical Installation
6.1. Power Wires Installation
The system must be installed and wired only by qualified electricians in
accordance with applicable safety regulations!
For safety, please cut off the mains power switch before installation!
When installing the electrical wiring, please note the nominal amperage of your
incoming feeder.

Use cable cross section and protective device specification :

Model OLS6000ERT6U(M) OLS10000ERT6U(M)


Protective earthing conductor 6mm² 10mm²
Min cross section (UL101510AWG) (UL1015 8AWG)
Input L, N, G 6mm² 10mm²
Min conductor cross section (1015 10AWG) (UL1015 8AWG)

Input breaker 40A/250Vac 63A/250Vac

Output L,N, 6mm² 10mm²


Min conductor cross section (1015 10AWG) (UL1015 8AWG)
3.95~4.97Nm
Torque for fixing above terminals
(35~44 1b in)
1) It is suggested to install an external isolating device against current backfeed
between mains input and Power module. After the device is installed, it must
add a warning label with the following wording or the equivalent on the external
AC contactor: RISK OF VOLTAGE BACKFEED. Isolate the Power module
before operating on this circuit, then check for hazardous voltage between all
terminals.

AC Contactor
L
Main
N Input
Input Main
Breaker UPS

Coil Remotes Swith

Fig.6-1 Typical external isolating device installation

16
2) No matter the Power module is connected to the mains power or not, the
output of the Power module may be electrically live. The parts inside the unit
may still have hazardous voltage after turning off the Power module. To make
the Power module have no output, turn off the Power module, and cut off the
mains power supply, wait the Power module shut down completely, finally cut
off the battery connection.
3) Open the terminal block cover located on the rear panel of Power module,
please refer to the appearance diagram.

4) For OLS6000ERT6U(M), it is recommended to select the UL1015


10AWG/6mm²or other insulated wire which complies with AWG Standard for
the Power module input and output wirings.
5) For OLS10000ERT6U(M), it is recommended to select the UL1015
8AWG/10mm²or other insulated wire which complies with AWG Standard for
the Power module input and output wirings.
6) Ensure the capacity of mains power supply. Do not use the wall receptacle as
the input power source for the Power module, as its rated current is less than
the Power module’s maximum input current. Otherwise the receptacle may be
burned and destroyed.
7) The protective earth ground wire should be installed first according to the
following diagram. It is better to use green wire or green wire with yellow ribbon
wire.
8) Connect other input and output wires to the corresponding input and output
terminals according to the following diagram.
9) Operating procedure for connecting with the Battery module by following the
chapter 6.2.

17
10) It is requested to use the accessorial terminal splices which can be compacted
on the wires tightly, to ensure the connection between the wires and the
terminal block is reliable.

Parallel Mode Output L Input Ground


Parallel Mode Output N Input N
Output Ground Input L
Single Mode Output L Battery +

Single Mode Output N Battery -


Battery Ground

Fig.6-2 Input and output terminal block wiring diagram

Important notes:
If the Power module is used in single mode, the output must be connected to sL and
sN.
If the Power module is used in parallel mode, the output must be connected to pL
and pN.
11) Install an output breaker between the output terminal of Power module and the
load, and the breaker should with leakage current protective function if
necessary.
12) Turn off all the loads first before connecting the load with the Power module,
then perform the connection and finally turn on the loads one by one.
13) After completing the installation, please check the wires to make sure all were
connected correctly and tightly.
14) Suggest charging the batteries for 8 hours before use. After Installation, turn
on the mains power switch and turn the input breaker in the "ON" position, the
Power module will charge the batteries automatically. It can also use the
Power module immediately without charging the batteries, but the backup time
may be less than the standard value.
15) If it is necessary to connect the inductance load such as a monitor or a laser

18
printer to the Power module, the start-up power should be used for calculating
the capacity of the Power module, as its start-up power consumption is too big
to make the Power module which capacity is small fail easily.

6.2. Operating Procedure for Connecting with the


Battery module
1) Loosen the screws to remove the Terminal Block Cover located on the rear
panel of Power module.

2) Connect the Battery Cable to the Power module and ensure the polarity is
right.

3) Loosen the screws to remove the Output Connector Cover of Battery module.

19
4) Connect the Battery Cable to the Battery module. Once completed, retighten
the Block Cover.

6.3. EPO Connection


EPO (Emergency power off): when the emergency occurs, such as the failure of
load, the UPS can cut off the output at once by operating the EPO port manually.
The connection:
Normally the EPO connector is closed with a wire on the rear panel(Fig.6-4), which
is supplied in the accessory. Once the connector is open, the UPS would stop the
output and enter EPO status (Fig.6-3).

Fig.6-3 Enable the EPO status Fig.6-4 Disable the EPO status
To recover to normal status, first EPO connector should be closed (Fig.6-4), and
enter LCD menu (illustrated in the chapter of 7.3) to clear EPO status, then UPS
would stop alarm and recover to Bypass model. And UPS needs be turned on by
manual operation.

20
7. Operation
7.1. Display Panel
The UPS has a five-button, dot matrix LCD with white text and a blue background.
Besides the LCD, the UPS has four colorized LED to provide more convenient
information.

Fig.7-1 LCD Panel


Control button functions:

The Button Function illustration

When the unit is no power and has connected with


Power on
battery, press this button for >200ms&<1s to power on
When the unit is powered on and is in Bypass mode,
Turn on
press this button more than 1s to turn on
When the unit has been turned on, press this button
Turn off
more than 3s to turn off
Press this button more than 200ms to confirm current
Enter
selection or enter the current selection window
Press this button more than 200ms to cancel current
ESC Exit
selection and return to previous menu.

21
Press this button more than 200ms to move the focus to
UP
the up menu
Press this button for more than 200ms to move the focus
Down
to the down menu

LED definition:

Normal BATTERY BYPASS FAULT


UPS state
(Green LED) (Yellow LED) (Yellow LED) (Red LED)
Bypass mode without
★ □
output

Bypass mode with output 〇 □


Line mode 〇 □
Battery mode 〇 〇 □
ECO mode 〇 〇 □
Battery test mode ※ ※ ※ ※

Turn on ※ ※ ※ ※

Fault mode □ 〇

Warning mode □ □ □ ★

Note:〇: Lightened constantly; ※: #1-#4 Lightened circularly;


★: Flashing; □: Depended on the fault/warning status or other status
Alarm definition:

UPS condition Buzzer status

Fault active Continuous

Warning active Beep every second

Battery mode Beep every 4 seconds, if battery low, buzzer Beep every second

Bypass mode Beep every 2 minutes

Overload Beep twice every second

22
The UPS provides useful information about UPS itself, load status, battery, events,
identification, and settings through the front panel display.
During powering on, the LCD would display the CyberPower logo for several
seconds and then enter to the default page which shows the UPS status summary.
On the UPS status screen it provides the following information:
 Status summary, including mode, load, battery and utility
 Alarm status, if any is present.
 Fault status, if any is present.
 Output parameter, including output voltage, current and frequency.
 Input parameter, including input voltage and frequency.
 Bypass parameter, including bypass voltage and frequency.
 Power parameter, including output VA and watt.
 Battery parameter, including battery capacity, voltage and remain time.

7.2. Turning On and Turning Off UPS


Attention: The UPS could only be turning on while connecting with the mains at
the first time.
Attention: Please switch off the connected loads first before turning on the UPS,
and switch on the loads one by one after the UPS is turned on. Switch off all of the
connected loads before turning off the UPS.
Turning on UPS with mains:
1) Check all the connection is correct, and the DC voltage of battery pack output
is right.
1) Set input breaker in "ON" position. At this time the fan begins to rotate, LCD
will show "CyberPower". Then LCD will show the default UPS status summary
screen after UPS finishing self-test.
2) By pressing button continuously for more than 1 second,the buzzer will
beep for 1s, UPS starts to turn on.
3) A few seconds later, the UPS turns into Line mode. If the mains power is
abnormal, the UPS will transfer to Battery mode without output interruption of
the UPS.
Turning on UPS without mains:
2) Check all the connection is correct, and the DC voltage of battery pack output
is right.
3) By pressing button continuously for >200ms&<1s, the UPS would be

23
powered on. At this time the fan begins to rotate, LCD will show "CyberPower".
Then LCD will show the default UPS status summary screen after UPS
finishing self-test.
4) By pressing button continuously for more than 1s,the buzzer will beep for
1s, UPS starts to turn on.
5) A few seconds later, the UPS turns into Battery mode. If the mains power
comes back, the UPS will transfer to Line mode without output interruption of
the UPS.
Turning off UPS with mains:
1) To turn off the inverter of UPS by pressing button continuously for more
than 3s and the buzzer will beep for 3s. The UPS will turn into Bypass mode at
once.
2) When completing the above action, UPS output voltage is still present. In order
to cut off the UPS output, simply cut off the mains power supply. A few
seconds later, LCD display shuts down and no output voltage is available from
the UPS output terminal.
Turning off UPS without mains:
1) To power off the UPS by pressing button continuously for more than 3s,
and the buzzer will beep 3s. The UPS will cut off the output at once.
2) A few seconds later, LCD shuts down and no voltage is available from the UPS
output.

7.3. LCD Operation


Except the default UPS status summary screen, the user could get more useful
information about UPS current status, old events which ever occurred, UPS own
identification, and could change the settings to fit the user own requirements,
optimize the function of UPS.
The status screen:
In the UPS status screen, when pressing or >200ms the detailed
information about UPS information that include alarm, fault output, input, bypass,
load and battery parameter would be shown, See Fig.7-2.
when pressing > 200ms the main menu would be shown. In fault or alarm
screen, when pressing > 200ms, the other alarm or fault would be shown by
pressing or >200ms, and press >200ms the display would return to
status screen. The main menu includes four branches: UPS control menu, setting

24
menu, event menu and identification menu. See Fig.7-3.

Alarm
0002:12:20:00
Cyberpower Line site
2/10

Up>200mS Down>200mS
Up>200mS Down>200mS

Alarm Alarm
0002:12:00:00 Enter>200mS 0002:12:00:00
Control Overload Overload
ESC>200mS ESC>200mS
Setting 1/10 1/10
Events ESC>200mS
ID
Fault Fault
0003:12:00:00 Enter>200mS 0003:12:00:00
Over tempearture Over tempearture
ESC>200mS
1/5 1/5

Down>200mS Up>200mS Up>200mS Down>200mS

Load: 60 % Cable loss


I/P Volt: 223.5 V 0003:12:00:00
Bat Volt: 260 V Over tempearture
Status:Line 2/5

Down>200mS Up>200mS
.
. Up>200mS Down>200mS
Output parameter .
Volt: 230 V
Curr: 14.5 A
Freq: 50.0 Hz

Down>200mS Up>200mS

Input parameter
Volt: 223.5 V
Freq: 50.1 Hz

Down>200mS Up>200mS

Bypass parameter
Volt: 223.5V
Freq: 50.1Hz

Down>200mS Up>200mS

Power parameter
KW: 3.6
KVA:3.6

Down>200mS Up>200mS

Bat parameter
Bat Volt: 260V
Capacity: 95 %
Rmn time 14 Min

Up>200mS
Down>200mS

Fig.7-2 UPS status menu

25
Buzzer mute

Yes
No
Clr EPO status

Yes
Buzzer mute No
Clr EPO status
Battery test
Battery test
Single UPS off
Yes
No

Single UPS off

Yes
No

Please input
Password Sub setting...
****

Event
0001:12:00:00
Utility abnormal
1/10

Control Alarm
Setting 0002:12:00:00
Events Overload
ID 1/10

Fault
0003:12:00:00
Over tempearture
1/5

Events&alarms Clear all events


Fault
Clear all events Yes
Clear all faults No

Clear all faults

Yes
No

Type/model

OLS 6000ERT6U
Long model

Serial number

Type/model ************
Serial number
Rating Rating
Firmware version IP:230Vac/50Hz
OP:230Vac/50Hz
Power:6kVA/5.4kW

Firmware version

Ver:0.0.1

Fig.7-3 Main menu

26
The control menu:
By pressing , enter the menu of "Control". The display would enter the next
control menu screen.
1) Buzzer mute
2) Battery test: is one command to control all UPS in a parallel system to do the
battery test at the same time.
3) Clear EPO status: once EPO status is enabled, the UPS output would be cut
off. To recover to normal status, first EPO connector should be closed, and
enter this menu to clear EPO status, then UPS would stop alarm and recover
to Bypass model. And UPS needs be turned on by manual operation.
4) Single UPS off: is one command to turn off one UPS which is operated
currently in parallel system, and other UPS continue working to supply the load
in the parallel system.
The setting menu:
Please contact your local distributor for further information before using the settings.
Some settings would change the specification, and some settings would enable or
disable some functions. The unsuitable option set by user may result in potential
failures or protecting function loss, even directly damage the load, battery or
UPS.The most of settings could only be done while UPS is in Bypass mode.

Submenu item Optional Values Default Value

User password* enabled/disabled enabled

Audio alarm enabled/disabled enabled

Site wiring fault alarm enabled/disabled enabled

Ambient temperature warning enabled/disabled enabled

DC start enabled/disabled enabled

Auto Restart enabled/disabled enabled

Automatic overload restart enabled/disabled enabled

Auto Bypass enabled/disabled enabled

27
Short circuit clearance enabled/disabled disabled

Power strategy** normal/ECO/converter normal

Rated output voltage 208/220/230/240V 230V

Output frequency 50/60Hz 50Hz

Bypass voltage low range 10%,15%,20% 15%

Bypass voltage high range 10%,15% 10%

Bypass frequency range 1%~10% 10%

ECO voltage range 10%,15% 10%

ECO frequency range 1%~10% 5%

Ext. Bat Type*** Standard/Customized Standard

Ext. Bat Pack **** 1Packs~15Packs 0 Packs

Automatic battery tests period 0~45days 7days

Day: hour: minute: second


Set running time 0000:0000:00~9999:23:59:59 Running time

Restore default setting Yes/NO

*Password is AAAA when enabled.


**Read the chapter of 8.1 and 8.2, before using ECO or converter function. UPS
need shut down, if change work mode from converter to others.
***Large current Charging when Ext. Bat Type is "Customized".
****Small current Charging when Ext. Bat Pack≤1 Packs. Large current Charging
when Ext. Bat Pack >1 Packs.

28
8. Special Function
The series UPS has some special functions, which could satisfy some special
application of user. And the functions have own features, please contact your local
distributor for further information before using the function.

8.1. ECO Function


Brief introduction of ECO function:
If ECO function is set to enable, after the UPS is turned on, the power used by the
load is directly supplied from the mains power via internal filter while the utility
power is in normal range, so the economy mode could be gained in ECO mode.
Once the mains power is loss or abnormal, the UPS would transfer to Line mode or
Battery mode and the load is supplied continuously.
The great virtue is overall high efficiency≥96% of UPS, to save power for user.
But the disadvantage is:
1) The load can’t be protected as well as in Line mode, for the load is directly
supplied from the mains;
2) The transfer time of UPS output from ECO mode to Battery mode is about
10ms.
So the function is not suitable to some sensitive loads, and the region where the
mains power is unstable.
Set the function:
The function could be enabled through the LCD setting in Bypass mode. Enter the
power strategy setting menu by following chapter of 7.3.

8.2. Converter Function


Brief introduction of Converter function:
In converter mode, the UPS would free run with fixed output frequency (50Hz or
60Hz). Once the mains power is loss or abnormal, the UPS would transfer to
Battery mode and the load is supplied continuously.
The great virtue is the output frequency is fixed, which is required by some very
sensitive loads. But the disadvantage is the load capacity of UPS should be
derated to 60% in converter mode.
Set the function:
The function could be enabled through the LCD setting in Bypass mode. Enter the

29
power strategy setting menu by following chapter of 7.3.

8.3. Parallel Function


Brief introduction of the redundancy:
N+X is currently the most reliable power supply structure. N represents the
minimum UPS number that the total load needs, X represents the redundant UPS
number, i.e. the fault UPS number that the system can handle simultaneously.
When the X is larger, the reliability of the power system is higher. For occasions
where reliability is highly depended on, N+X is the optimal mode.
As long as the UPS is equipped with parallel cables, up to 4 UPS can be connected
in parallel to realize output power sharing and power redundancy.
How to install a new parallel UPS system:
1) Before installing a new parallel UPS system, user need to prepare input and
output wires, input and output breaker, main maintenance bypass switch.
2) Remove the cover plate of the parallel port on the UPS, connect each UPS
one by one with the parallel cable, and re-screw the parallel port cover which is
supplied in the accessories.

Fig.8-1 Parallel cable connect diagram


3) Strictly follow the chapter of 6.1, the wiring requirement of single UPS to
perform the wiring of each UPS.

30
4) Connect the output wires of each UPS to an output breaker panel, and connect
each output breaker to a main output breaker and then to the loads.
5) CAUTION: Each UPS needs an independent battery pack.
6) Please refer to the wiring diagram in the following diagram.

OUTPUT BATTERY INPUT


pN pL sL sN - + L N

1# Battery pack
UPS1 Output

UPS1 Input
Breaker
Breaker

OUTPUT BATTERY INPUT


pN pL sL sN - + L N

2# Battery pack
UPS2 Input
UPS2 Output

Breaker
Breaker

Main Output Ground

Main Input Ground

To Main To Main Input


Output Breaker Breaker

Fig.8-2 Input and output terminal block wiring diagram

31
TO UTILITY

Main Maintenance
Bypass Switch

Maintenance Bypass for Parallel


Main Input
Breaker

UPS2 Input Breaker

UPS3 Input Breaker


UPS1 Input Breaker

UPS1 Output Breaker

UPS2 Output Breaker

UPS3 Output Breaker


Main Output
Breaker

TO LOAD

Fig.8-3 Parallel installation diagram


7) The distance between the UPS in parallel and the breaker panel is required to
be less than 20 meters. The difference between the wires of input and output
of the UPS is required to be less than 20%.
8) Do not switch on the output breaker of each UPS, switch on the input breaker
of the each UPS, the UPS should work in bypass with output, observe their
display to check if there are any warning or fault information, measure the
output voltage of each UPS separately to check if the voltage difference
between them is less than 1V. If the difference is more than 1V, check the
wiring.
9) Press the button of one UPS, each UPS would start to turn on, all the
UPS would transfer to the Line mode together. Measure the output voltage of
each UPS separately to check if the voltage difference between them is less

32
than 0.5V. If the difference is more than 0.5V, the UPS need to be regulated.
10) Press the button of one UPS, each UPS would start to turn off and
transfer to the Bypass mode, switch on the output breaker of each UPS to
parallel all the output of UPS together.
11) Press the button of one UPS, each UPS would start to turn on , after
turning on, the UPS should work parallel in the Line mod
How to join a new UPS to a parallel system:
1) First the parallel system must be installed one main maintenance bypass
switch.
2) Regulate the output voltage of the new UPS separately: check if the output
voltage difference between the new UPS and the parallel system is less than
0.5V.
3) Ensure the bypass of the parallel system is normal and the bypass setting is
"enable", Press the button of one UPS, each UPS would turn off and the
UPS system would transfer to the Bypass mode.
4) Set the main maintenance bypass switch from "UPS" to "BPS", switch off the
main output breaker and the main input breaker, the UPS would shut down.
5) Ensure the UPS shut down totally, add the new UPS and reinstall the new
UPS parallel system by following step 1) to 10) of last chapter - "How to install
a new parallel UPS system".
6) Switch on the main input breaker and the main output breaker, and set the
main maintenance bypass switch from "BPS" to "UPS", Press the button
of one UPS, each UPS would start to turn on, after turning on, the UPS should
work parallel in the Line mode.
How to remove a single UPS from a parallel system:
1) First the parallel system must be installed one main maintenance bypass
switch.
2) Ensure the bypass of the parallel system is normal and the bypass setting is
"enable", Press the button of one UPS, each UPS would turn off and the
UPS system would transfer to the Bypass mode.
3) Set the main maintenance bypass switch from "UPS" to "BPS", switch off the
main output breaker and the main input breaker, the UPS would shut down.
4) Ensure the UPS shut down totally, remove the wanted UPS and reinstall the
new UPS parallel system by following step 1) to 10) of last chapter - "How to

33
install a new parallel system".
5) Switch on the main input breaker and the main output breaker, and set the
main maintenance bypass switch from "BPS" to "UPS", Press the button
of one UPS, each UPS would start to turn on, after turning on, the UPS should
work parallel in the Line mode.

9. Trouble Shooting
If the UPS system does not operate correctly, first check the operating information
on the LCD display. Please attempt to solve the problem using the table below. If
the problem still persists, consult your dealer.

9.1. Trouble Shooting According To Warning


Indication
Problem Displayed Possible cause Remedy
EPO connector is Check the EPO connector
EPO Active
open status
The Ground wire is
disconnected or Phase Check the Ground wire status.
Site Fail and neutral conductor at Reverse mains power wiring.
input of
UPS system are
Do the battery test to confirm.
reversed
Check the battery bank is
Battery Open Battery is disconnected connected to the UPS.
Check the battery breaker is
turn on.

When audible alarm sounding


Battery volt low Battery voltage is low every second, battery is almost
empty.

Check the loads and remove


Over load Over load some non-critical loads.
Check if some loads are failed.
Check if the fan is running
Fan Fail Fan abnormal
normally.

Charger Fail The charge fails Consult dealer.

34
Battery voltage is
Check if the battery quantity is
Battery Over Voltage higher than normal
right.
value
The UPS will turn off the
Battery is over
Over Charge charger until the battery voltage
charged
is normal
The ambient
Check the environment
Amb NTC abnormal temperature is too
ventilation.
high
Ambient NTC abnormal UPS internal fault Consult dealer.

The parallel cable is


Cable disconnect Check the parallel cable.
disconnected

The parallel cable is


Cable loss Check the parallel cable.
disconnected

The battery packs of


Check if all the battery pack is
Battery Differ some UPSs are
connected.
disconnected
The mains input of Check the building wiring and
Line Differ some UPSs is input cable.
disconnected Check if the input breaker is
closed.
The UPSs with different power
There are different Ensure the UPSs are
strategy setting (Ex. one Line
Work Mode Differ power strategy setting connected to same input
mode and one Converter mode)
in parallel system source.
are forbidden to parallel.

The UPSs with different


There are different
capacity (Ex. one OLS6000E
Rate Power Differ UPSs in parallel
and one OLS10000E) are
system
forbidden to parallel.
ECO function is
ECO function is forbidden in
ECO In Para enabled in parallel
parallel system.
system
Fuse Open Input fuse break Check the input fuse status

35
9.2. Trouble Shooting According To Fault Indication
Problem Displayed Possible cause Remedy

Remove all the loads. Turn off the


UPS. Check if UPS output and loads
Output short Output short circuit
is short circuit. Ensure short circuit is
removed before turning on again.

Check the loads and remove some


Over load Over load non-critical loads.
Check if some loads are failed.

Remove some non-critical loads.


The load is pure
Neg power fail Bypass supplies the load first, ensure
inductive and capacitive
there is no overload, then turn on UPS

Inside temperature of Check the ventilation of UPS and the


Over temperature
UPS is too high ambient temperature

Fan blocked or
Fan fail Check the fan status
disconnected over time

Output voltage is
Back feed Consult dealer
returned to input

DC short Bus short Consult dealer.

DC over Bus over voltage Consult dealer.

DC under Bus under voltage Consult dealer.

DC unbalance Bus unbalance Consult dealer.

DC soft fail Bus soft start fail Consult dealer.

Output soft fail Output soft start fail Consult dealer.

Output volt low Output volt low Consult dealer.

Output volt high Output volt high Consult dealer.

36
9.3. Trouble Shooting In Else Cases
Problem Possible cause Remedy

No indication, no warning tone Check the building wiring and


even though system is connected No input voltage input cable. Check if the input
to mains power supply breaker is closed
BYPASS LED light up even though Inverter not Press button to turn on
the power supply is available switched on UPS.
Input voltage Check input power source.
BATTERY LED lights up, and
and/or frequency Check the building wiring and
audible alarm sounding every 1
are out of input cable. Check if the input
beep in every 4 seconds
tolerance breaker is closed.

Batteries not fully Charge the batteries for at


Emergency supply period shorter
charged /batteries least 12 hours and then check
than nominal value
defect capacity.

Please have the following information at hand before calling the After-Sales Service
Department:
1) Model number, serial number
2) Date on which the problem occurred
3) LCD/LED display information, Buzzer alarm status
4) Mains power condition, load type and capacity, environment temperature,
ventilation condition
5) The information (battery capacity, quantity) of Battery pack
6) Other information for complete description of the problem

37
10. Battery Maintenance
Battery replacement should be performed by qualified personnel.

 This series UPS only requires minimal maintenance. The batteries used for
battery pack are value regulated sealed lead-acid maintenance free battery.
These models require minimal repairs. The only requirement is to charge the
UPS regularly in order to maximize the expected life of the battery. When
being connected to the utility power, whether the UPS is turned on or not, the
UPS keeps charging the batteries and also offers the protective function of
overcharging and over-discharging.
 The UPS should be charged once every 4 to 6 months if it has not been used
for a long time.
 In the regions of hot climates, the battery should be charged and discharged
every 2 months. The standard charging time should be at least 12 hours.
 Under normal conditions, the battery life lasts 3 to 5 years. In case if the
battery is found not in good condition, earlier replacement should be made.
Battery replacement should be performed by qualified personnel.
 Replace batteries with the same number and same type of batteries.
 Do not replace the battery individually. All the batteries should be replaced at
the same time following the instructions of the battery supplier.
 If the battery service life (3~5 years at 25°C ambient temperature) has been
exceeded, the batteries must be replaced.

38
11. Communication Port
11.1. USB Interface
The USB port is compliance with USB 1.1 protocol for its communication software.

11.2. RS232 Interface


The RS-232 port is available for UPS monitoring, control, and firmware updates.

11.3. Intelligent slot


This series is equipped with an intelligent slot for other optional card to achieve
remote management of the UPS through internet / intranet. Please contact your
local distributor for further information.

CyberPower Systems Inc.


www.cyberpower.com
6F, No. 32, Sec. 1, Chenggong Rd., Nangang District, Taipei 115, Taiwan
Entire contents copyright© 2013 CyberPower Systems Inc., All rights reserved. Reproduction in whole or
in part without permission is prohibited. PowerPanel® Business Edition and PowerPanel® Personal
Edition are trademarks of CyberPower Systems Inc.

39