Location via proxy:   [ UP ]  
[Report a bug]   [Manage cookies]                

Rev. A English 11 / 2012: Procedure

Download as pdf or txt
Download as pdf or txt
You are on page 1of 54

-PUBLIC-

N-2760 REV. A ENGLISH 11 / 2012

Uninterruptible Power System


for Industrial Use

Procedure

This Standard replaces and cancels its previous revision.


The CONTEC - Authoring Subcommittee provides guidance on the
interpretation of this Standard when questions arise regarding its contents. The
Department of PETROBRAS that uses this Standard is responsible for adopting
and applying the sections, subsections and enumerates thereof.

Technical Requirement: A provision established as the most adequate and


CONTEC which shall be used strictly in accordance with this Standard. If a decision is
taken not to follow the requirement (“non-conformity” to this Standard) it shall be
Comissão de Normalização based on well-founded economic and management reasons, and be approved
Técnica and registered by the Department of PETROBRAS that uses this Standard. It is
characterized by imperative nature.
Recommended Practice: A provision that may be adopted under the conditions
of this Standard, but which admits (and draws attention to) the possibility of
there being a more adequate alternative (not written in this Standard) to the
particular application. The alternative adopted shall be approved and registered
by the Department of PETROBRAS that uses this Standard. It is characterized
by verbs of a nonmandatory nature. It is indicated by the expression:
[Recommended Practice].
Copies of the registered “non-conformities” to this Standard that may contribute
to the improvement thereof shall be submitted to the CONTEC - Authoring
SC - 06 Subcommittee.

Electricity Proposed revisions to this Standard shall be submitted to the CONTEC -


Authoring Subcommittee, indicating the alphanumeric identification and revision
of the Standard, the section, subsection and enumerate to be revised, the
proposed text, and technical/economic justification for revision. The proposals
are evaluated during the work for alteration of this Standard.

“This Standard is exclusive property of Petróleo Brasileiro S. A. -


PETROBRAS, internal application and PETROBRAS Subsidiaries and
shall be used by its suppliers of goods and services under contracts or
similar under the conditions established in Bidding, Contract, Agreement
or similar.
The use of this Standard by other companies / organizations / government
agencies and individuals is the sole responsibility of the users..”

Introduction
PETROBRAS Technical Standards are prepared by Working Groups - WG
(consisting specialized of Technical Collaborators from Company and its Subsidiaries), are
commented by Company Units and its Subsidiaries, are approved by the Authoring Subcommittees -
SCs (consisting of technicians from the same specialty, representing the various Company Units and
its Subsidiaries), and ratified by the Executive Nucleus (consisting of representatives of the Company
Units and its Subsidiaries). A PETROBRAS Technical Standard is subject to revision at any time by its
Authoring Subcommittee and shall be reviewed every 5 years to be revalidated, revised or cancelled.
PETROBRAS Technical Standards are prepared in accordance with PETROBRAS Technical
Standard N-1. For complete information about PETROBRAS Technical Standards see PETROBRAS
Technical Standards Catalog.

PROPERTY OF PETROBRAS 48 pages, 1 form, Index of Revisions and WG


-PUBLIC-

N-2760 REV. A ENGLISH 11 / 2012

Foreword

This Standard is the English version (issued in 09/2013) of PETROBRAS N-2760 REV. A 11/2012. In case of
doubt, the Portuguese version, which is the valid document for all intents and purposes, shall be used.

1 Scope

1.1 This Standard sets forth the minimum requirements which shall be complied supply of
Uninterruptible Power Systems (UPS) for PETROBRAS facilities, according to national, international
and foreign standards.

1.2 This Standard applies to UPS for industrial use with power exceeding 3 kVA.

1.3 This Standard applies to procedures started as of its date of issuance.

1.4 This Standard contains only Technical Requirements.

2 Normative References

The following referenced documents are indispensable for the application of this document. For dated
references, only the edition cited applies. For undated references, the latest edition of the referenced
document applies.

PETROBRAS N-329 - Bateria de Acumuladores (Storage Battery);

PETROBRAS N-332 - Retificadores para Uso Industrial (Rectifiers for Industrial Use);

PETROBRAS N-1219 - Colors (Cores);

ABNT NBR 5410 - Instalações Elétricas de Baixa Tensão (Low Voltage Electrical
Installations).

ABNT NBR IEC 60439-1 - Conjuntos de Manobra e Controle de Baixa Tensão - Parte 2:
Requisitos Particulares para Linhas Elétricas Pré-Fabricadas (Sistemas de Barramentos
Blindados) (Low-voltage Switchgear and Controlgear Assemblies - Part 2: Particular
requirements for Pre-Fabricated Electrical Lines [Shielded Busbar Systems]);

ABNT NBR IEC 60529 - Graus de Proteção para Invólucros de Equipamentos Elétricos
(código IP) (Degrees of Protection Provided by Enclosures (IP Code));

ISO 7779 - Acoustics - Measurement of Airborne Noise Emitted by Information Technology


and Telecommunications Equipment;

ASTM G21 - Standard Practice for Determining Resistance of Synthetic Polymeric Materials
to Fungi;

IEC 60068-2-6 - Environmental Testing - Part 2-6: Tests - Test FC: Vibration (Sinusoidal);

IEC 60068-2-27 - Environmental Testing - Part 2-27: Tests - Test Ea and Guidance: Shoc;

IEC 60146-2 - Semiconductor Converters - Part 2: Self-Commutated Semiconductor


Converters Including Direct d.c. Converters;

IEC 61000-2-2 - Electromagnetic Compatibility (EMC) Part 2-2: Environment - Compatibility


Levels for Low-Frequency Conducted Disturbances and Signaling in Public Low-Voltage
Power Supply Systems;

2
-PUBLIC-

N-2760 REV. A ENGLISH 11 / 2012

IEC 61086-1 - Coatings for Loaded Printed wire Boards (Conformal Coatings) - Part 1:
Definitions, Classification and General Requirements;

IEC 61378-1 - Convertor Transformers - Part 1: Transformers for Industrial Applications;

IEC 62040-2 - Uninterruptible Power Systems (UPS) - Part 2: Electromagnetic Compatibility


(EMC) Requirements;

IEC 62040-3 - Uninterruptible Power Systems (UPS) - Part 3: Method of Specifying the
Performance and Test Requirements;

IEC CISPR 16-1-1 - Specification for Radio Disturbance and Immunity Measuring Apparatus
and Methods - Part 1-1: Radio Disturbance and Immunity Measuring Apparatus - Measuring
Apparatus;

IEC CISPR 16-1-2 - Specification for Radio Disturbance and Immunity Measuring Apparatus
and Methods - Part 1-2: Radio Disturbance and Immunity Measuring Apparatus - Ancillary
Equipment - Conducted Disturbances;

IEC CISPR 16-1-3 - Specification for Radio Disturbance and Immunity Measuring Apparatus
and Methods - Part 1-3: Radio Disturbance and Immunity Measuring Apparatus - Ancillary
Equipment - Disturbance Power;

IEC CISPR 16-1-4 - Specification for Radio Disturbance and Immunity Measuring Apparatus
and Methods - Part 1-4: Radio Disturbance and Immunity Measuring Apparatus - Antennas
and Test Sites For Radiated Disturbance Measurements;

IEC CISPR 16-1-5 - Specification for Radio Disturbance and Immunity Measuring Apparatus
and Methods - Part 1-5: Radio Disturbance and Immunity Measuring Apparatus -
Specifications and Validation Procedures for Calts and Refts from 30 Mhz to 1 000 Mhz;

IEEE STD 485 - Recommended Practice for Sizing Lead-Acid Batteries for Stationary
Applications;

IEEE STD 1115a - Recommended Practice for Sizing Nickel-Cadmium Batteries for
Stationary Applications.

NOTE For documents referred in this Standard and for which only the Portuguese version is
available, the PETROBRAS department that uses this Standard should be consulted for any
information required for the specific application.

3 Terms and Definitions

For the purposes of this document, the following terms and definitions apply.

3.1
AC (Alternating Current) Safe Busbar
busbar fed by UPS output with controlled voltage and frequency which remains energized even with
deterioration of the main AC source

3.2
electrostatic shielding
used to reduce interference between primary and secondary windings (capacitive coupling), thereby
providing proper galvanic insulation. It is especially indicated where there is necessity for low leakage
currents between windings, such as in those situations where electric noise is present on the mains or
equipment. This shielding is comprised of a conductive layer between primary and secondary
windings, which shall be connected to the grounding of the circuit and/or mains

3
-PUBLIC-

N-2760 REV. A ENGLISH 11 / 2012

3.3
overload capacity
output current capacity of the UPS exceeding to the permanent direct current at a given time, with the
output voltage within the nominal range, in normal or stored energy mode

3.4
100 % unbalanced load
load in which 2 phases shall operate with linear load and rated current between phases or phase-
neutral (if any), and third phase with no load

3.5
linear load
load with sinusoidal waveform and peak factor equal to square root of 2, or load which current is
defined by ratio: I = V/Z, where I is the current in load, V is the feeding voltage, and Z is the load
impedance (constant as a function of time and voltage)

3.6
non-linear load
load with sinusoidal waveform and peak factor different from square root of 2, or load in which Z
impedance is not a constant as a function of time or voltage

3.7
transfer switch
mechanical switch used to connect / isolate the UPS from the load, or energize / de-energize the
alternative source circuit

3.8
static switch
electronic device consisting of one or more switches used to transfer the power from the inverter to the
alternative source

3.9
alternative source
the second power source which feeds the UPS via an alternative circuit or by-pass

3.10
Main Source
Source of energy that is normally available on a continuous basis and is usually supplied by an electric
utility company, but is sometimes generated by the facility itself

3.11
IMO
it is abbreviature of International Maritime Organization, which is the United Nations specialized
agency responsible for improving maritime safety and preventing pollution from ships

3.12
Man Machine Interface (MMI)
equipment responsible for receiving and treatment data from the UPS

3.13
DC (Direct Current) Link
Direct Current bus between the rectifier and the inverter input

4
-PUBLIC-

N-2760 REV. A ENGLISH 11 / 2012

3.14
Operation Mode of Stored Energy or Battery In Operation
Operation mode of UPS when fed under the conditions below:

— primary source disconnected or out of tolerance limits;


— DC energy storage system is discharging
— load is within its given range;
— output voltage is within its withstand range.

3.15
Operation Mode by Alternative Circuit
Operation status of UPS when it only supplies the load through alternative circuit

3.16
Normal Operating Mode
Stable operating mode which the UPS reaches when fed under the conditions below

— main power supply connected and within tolerance limits;


— storage battery is charged or recharging within the power recovery time;
— the operation is continuous or may be continuous;
— the phase synchronism is active, if any;
— the load is within the established range;
— the output voltage is within the established range;
— the alternative circuit, when used, is available and within the specified tolerance.

3.17
Modu Code
English acronym for “code for the construction and equipment of mobile offshore drilling units”. It
refers to a set of requirements intended to ensure minimum operational safety standards compatible
with the characteristics of drilling platforms

3.18
alternative circuit
circuit through which the alternative source power feeds the static switch or safe busbar of UPS
through transfer switch

3.19
TAC
Field Acceptance Test

3.20
TAF
Factory Acceptance Test

3.21
tropicalization
an industrial treatment process against degradation of electronic and mechanical components, such
as: fungus growth or oxidation due to high air relative humidity levels, which is aimed at ensuring
proper functional performance of the components when subject to the peculiar environmental
characteristics of regions having a tropical climate

5
-PUBLIC-

N-2760 REV. A ENGLISH 11 / 2012

3.22
UPS
It is abbreviature of Uninterruptible Power System. This system is constituted of a combination of
converters, switches and devices of energy storage (accumulators battery, for example), with the
purpose to keep the continuity of feeding for the load in the case of imperfection of the main supply

3.23
THD
It is abbreviature of Total Harmonic Distortion

3.24
rms
It is abbreviature of Root Meter Square

3.25
RFI
It is abbreviature of Radio Frequency Interference

4 Specific Conditions

4.1 Whenever there are discrepancies between the Data Sheet of Annex B and this Standard, the
information contained in the Standard shall prevail.

4.2 The UPS shall be designed to be a stationary, fixed, and integrated equipment to be installed in
an area that may only be accessed by qualified personnel.

4.3 The UPS shall be designed to be permanently connected.

4.4 The normal operation of the UPS shall be characterized by feeding load by inverter, synchronized
with mains and with batteries on float charge. In the occurrence of abnormal conditions in the mains,
the batteries shall assume the load. The load shall only be transferred to the by-pass via static switch
if the batteries are discharged or an inverter failure occurs.

5 General Conditions

5.1 The UPS design shall have been sold for similar applications and with at least 3 years of
successful operation. This history shall be witnessed by users. Prototypes or non-proven equipment
will not be accepted.

5.2 The specific characteristics of the UPS are those indicated on the Data Sheet of Annex B, which,
together with this Standard, is an integral part of the Material Requisition (RM).

5.3 The supplier shall fill all blank items on the Data Sheet of Annex B (technical data, list of
standards used in the design, manufacturing, and testing as well as the list of tests) and return it to
PETROBRAS duly authenticated.

5.4 The specific characteristics of each UPS are indicated on its respective Data Sheets, which are
numbered according to each design. The blank form of these Data Sheets is standardized by Annex B
of this Standard.

6
-PUBLIC-

N-2760 REV. A ENGLISH 11 / 2012

5.5 The UPS shall be designed, manufactured and tested in accordance with the provisions of this
Standard and the recommendations of the publications mentioned in Section 2 of this Standard.

5.6 Any discrepancy or alternative presented by the bidder in relation to the conditions originally
specified by PETROBRAS shall be clearly indicated in its bid in an item entitled “deviations from and
alternatives to specifications”.

5.7 When “deviations or alternatives” occur, the bid shall include matching references to the numbers
of the corresponding paragraphs of this Standard, Data Sheet or RM.

5.8 If “deviations or alternatives” are not mentioned, the manufacturer’s supply will be considered to
be fully in accordance with the specifications.

5.9 Any conflicts that may occur between the requirements of this Standard and those set forth in the
specifications, codes or reference standards, purchase orders or other design documents shall be
reported to PETROBRAS. In such cases, no action shall be taken before one seeming for writing from
PETROBRAS is emitted.

5.10 When the UPS is installed on offshore production units, it shall follow the recommendations of
the classification societies. In the case of a floating type offshore unit, the inclination requirements
specified in IMO and in the Modu Code shall also be observed.

5.11 The UPS shall be designed to provide a minimum mean time between failures (MTBF) of at least
180 000 hours and a maximum mean time to repair (MTTR), considering personnel qualified for repair
beside the equipment with spares, at most 4 hours.

5.12 The manufacturer shall be responsible for supplying the UPS set with all components as
specified in this Standard.

5.13 The UPS shall operate within, or in more severe, grid conditions established below, in normal
operating mode, as per standard IEC 62040-3:

a) input voltage variation: ± 10 % of rated voltage;


b) input frequency variation: ± 5 % of rated frequency;
c) ratio between negative and positive input sequence: ≤ 5 %;
d) total voltage harmonic distortion rate: THD ≤ 8 %;
e) individual harmonics, as defined in standard IEC 62040-3.

5.14 The UPS system specification shall be done alongside standard PETROBRAS N-329, Storage
Battery, since the storage battery sizing and recharge time are essential for sizing of UPS rectifier.

6 Environmental Conditions

6.1 The equipment shall operate in a sheltered location and in a non-hazardous area.

6.2 Printed circuits in electronic modules of equipment shall be treated for protection against
aggressive and salted environments (tropicalization) and corrosive gases (for example, gases
containing sulfur or chlorine). Treatments shall consist of application of Class 2 reinforced protective,

7
-PUBLIC-

N-2760 REV. A ENGLISH 11 / 2012

in accordance with IEC 61086-1, and fungiproof, in accordance to ASTM G21. The manufacturer shall
inform in its proposal the processes used for this protection, subjected to PETROBRAS’ approval.

6.3 The ambient temperature range is 0 ºC to 40 ºC. In this temperature range, the UPS shall operate
with rated power. Above this range, the UPS shall remain operating, allowing a reduction in the output
power

6.4 The relative air humidity is 95 %, with no condensation, at 25 ºC.

6.5 The maximum altitude is 1 000 m, unless otherwise indicated on the Data Sheet of Annex B.

7 Constructive Characteristics

7.1 General Characteristics

7.1.1 The UPS specified by this Standard shall be VFI-S type, as per IEC 62040-3.

7.1.2 The UPS and its parts and components shall be manufactured in accordance with the
recommendations of the standards mentioned in Chapter 2.

7.1.3 In an IT insulated system (see grounding system, according to ABNT NBR 5410), if the load
distribution center is defined in the scope of supply, as per Chapter 11, it shall contain an insulation
monitoring system capable of identifying the branch of the load with low isolation with more than two
simultaneous faults.

7.1.4 The by-pass system shall be mounted in a separate compartment adjacent to the UPS cabinet.

7.1.5 The components and systems of the UPS shall be designed for continuous operation under
rated output power conditions, considering allowable overload cycles of the UPS as well, without
reduction of system capability.

7.1.6 The design of power and control circuits shall be developed so as to prevent a failure in a
particular component or printed circuit board from propagating in cascading fashion or causing another
failure in the other components or printed circuit boards.

7.1.7 The UPS shall be immune to the accumulation of electrostatic charges, voltage transients,
voltage sags and electric noises caused by short circuit in the electrical system, switching of capacitor
banks, startup of electric motors, and by lightning discharges, in accordance with the essential
electromagnetic compatibility and immunity requirements specified in IEC 62040-2.

7.1.8 Insulators of bars, supports and joining parts shall be made of non-hygroscopic and
nonflammable material.

7.1.9 Where indicated on the Data Sheet, the UPS shall be provided with heating resistors fed at 120
Vac, one for each vertical section or compartment. These resistors are fed by a source external to the
UPS. They shall be protected by a thermomagnetic circuit breaker and automatically controlled by
means of a thermostat with a maximum scale range of 60 °C.

8
-PUBLIC-

N-2760 REV. A ENGLISH 11 / 2012

7.1.10 The internal circuits of the UPS, excluding the circuits of heating resistors, shall be fed by
redundant sources with feed from both, the safe DC busbar of the UPS and of the by-pass circuit.

7.1.11 Autotransformers shall not be used for adapting the UPS input or output voltage or by-pass
voltage.

7.1.12 The efficiency of the rectifier/inverter assembly of the UPS, including isolation transformers,
under any operating conditions, shall not be lower than the values specified in EC 62040-3.

7.1.13 The UPS shall include self-monitoring of hardware and software, continuously monitored, and
any irregularity immediately detected shall cause a local signal and set off a remote alarm as specified
in items 12.7 and 12.13.

7.1.14 The audible noise shall be ≤ 75 dBA, in accordance with IEC 62040-3.

7.1.15 In normal operating mode, the UPS shall remain in operation without the battery bank.

7.1.16 The parameterization of internal adjustments of the UPS shall allow modifications to be made
by the user, with specific instructions being included in the installation, operation or maintenance
manual.

7.1.17 The circuit fed by the alternative source shall contain a transformer as specified in Section 16.

7.2 Power Semiconductors

Provision shall be made for a redundant forced ventilation system to keep power semiconductors
within their allowable operating temperature limits. The fans of the system of forced ventilation shall be
monitored on its functioning. The fan shall be able to be replaced with no need to de-energize the
UPS, no loss of UPS functionalities and no risk for the equipment, facilities or people. In the
eventuality of non-availability of one of them alarms shall be acted in accordance with 12.7.

7.3 Enclosure

7.3.1 The degree of protection of the UPS shall be that indicated on the Data Sheet in accordance
with ABNT NBR IEC 60529.

7.3.2 The UPS shall be resistant to corrosion caused by the characteristic atmosphere of the
installation site, as indicated on the Data Sheet of Annex B.

7.3.3 The treatment and paint system of metallic plates of the UPS shall present a high performance
level for the environmental conditions indicated in this Standard and on the Data Sheet. The
manufacturer shall present, together with its proposal, the treatment and paint system to be adopted.

7.3.4 The final finish color should be as specified on the Data Sheet. When the color is not specified,
the light gray color corresponding to code 0065 of PETROBRAS N-1219 shall be used.

9
-PUBLIC-

N-2760 REV. A ENGLISH 11 / 2012

7.3.5 The UPS shall be mounted on a self-supporting panel. (see Chapter 9 of this Standard).

7.3.6 The metal parts comprising the UPS that are not expected to be of the current-carrying type
shall present electrical continuity and be connected to the ground busbar of the UPS. The doors shall
have electrical continuity with the metallic structure of the UPS through flexible copper braid.

7.3.7 The ground busbar shall be located on the bottom inside part of the UPS, covering its entire
extension and shall have a compression connector suitable for connecting a bare copper stranded
ground wire with the nominal cross-section indicated on the Data Sheet of Annex B.

7.4 Identification

7.4.1 Internal components and terminal blocks shall be identified. The wiring shall be identified
according to the respective wiring diagrams.

7.4.2 The UPS identification plate shall be attached to the outside of the UPS and shall be made of
series AISI 300 stainless steel. This plate shall contain at least the following data:

a) manufacturer’s name or brand name;


b) supply voltage, number of phases, and rated frequency;
c) rated power supply current;
d) rated power in kVA and rated power factor;
e) rated output voltage;
f) rated output current;
g) momentary current (overload) sustained for 60 seconds;
h) serial number;
i) model.

7.4.3 The panel shall be provided with a supplementary identification plate made of series AISI 300
stainless steel containing at least the following data:

a) Petróleo Brasileiro S.A. - PETROBRAS;


b) name of PETROBRAS department;
c) project name;
d) UPS-CA identification;
e) RM number;
f) Purchase and Service Order number (PCS);
g) the contract number, in case the acquisition is made under a Turn Key, Lump Sum, and
other similar types of contracts.

7.5 Printed Circuit Boards

7.5.1 The components of the printed circuit boards shall have industrial quality level.

Boards, circuits and their components shall be protected so as to prevent fungus growth or the
occurrence of damages due to local humidity, salinity, chlorine and sulfur.

7.6 Wiring and Connections

7.6.1 The insulation of internal power and control cables shall have a flame-retardant chemical
composition.

10
-PUBLIC-

N-2760 REV. A ENGLISH 11 / 2012

7.6.2 All points of wiring for external connection (input and output circuits) shall be functionally
identified within the UPS, on each terminal block or power connection, including power, grounding,
control and alarm cables.

7.6.3 Insulation and leakage distances shall be sized in accordance with ABNT NBR IEC 60439-1,
considering rated voltage V, overvoltage category III, pollution degree 3, material group 3A and non-
homogeneous field.

7.7 Local Digital Control Panel

7.7.1 The UPS shall have a local digital control panel on its front part to allow man/machine interface.
This panel shall contain at least the following devices for operation and monitoring:

a) “on” key;
b) “off” key;
c) parameter selection key;
d) parameter and adjustment programming keys;
e) key to increment functions or control values;
f) key to decrement functions or control values;
g) led indicating equipment is energized;
h) digital alphanumeric display to indicate the variables described according to Chapter 12;
i) UPS synoptic to indicate the status of system operation according to Chapter 12.

7.7.2 During the normal operation period, the display shall allow at least indication of the current,
voltage, and frequency values. The values shall be input, output and internal actual values, as defined
in block diagram of the UPS and in 12.6.

7.7.3 The data of the local control digital panel shall be stored in non-volatile memory so as to allow
recovery of parameterization, alarms, and register of events even after the UPS has fully de
energized.

7.8 UPS Communication

7.8.1 Physical Layer

Interfaces shall be made available for connection between the UPS and MMI, according to Data Sheet
of Annex B.

7.8.2 Link Layer

The UPS shall communicate with the MMI using MODBUS protocol, unless otherwise specified on the
Data Sheet.

7.9 Configuration

7.9.1 The UPSs shall allow configuration and access to all parameters via man-machine interface,
comprised of the elements specified in 7.7 and 12.9.

11
-PUBLIC-

N-2760 REV. A ENGLISH 11 / 2012

7.9.2 Any needed software for the configuration shall be provided to PETROBRAS with the UPS, at
no expense. The configuration software shall be compatible with the Windows®1) operating system.

7.9.3 The configuration of the UPS via the serial port shall be implemented with the UPS in operation,
without interrupting the AC safe busbar feed.

7.9.4 Configuration adjustments shall be implemented in the UPS in non-volatile memory.

7.9.5 Accesses for changing the configuration and for cleaning recorded data using any means shall
be protected by a configurable password available to PETROBRAS. Provision shall be made for a
password not to be required for reading UPS data.

7.11 Redundant Parallel Architecture

7.11.1 If requested in Data Sheet of Annex B, the UPS to be supplied shall have redundant parallel
architecture and present the performance requirements shown below:

7.11.1.1 The load shall be automatically and equally distributed among the UPS units.

7.11.1.2 If any failure occurs in one of the redundant UPS units, the load shall be automatically
distributed among the other ones.

7.11.1.3 There shall be no single point of failure of the synchronism system affecting the other UPSs.
It is not allowed a central module of load division control and synchronism external to redundant
UPSs.

7.11.1.4 The technology shall be capable of operating with at least 5 UPS units in parallel with active
load division. To add an UPS in parallel, it is not allowed to add hardware in the other UPSs, unless
the interconnection by means of communication between the UPSs.

7.11.1.5 The redundant system with more than one UPS in parallel shall perform an active sharing of
load and supply current equal to voltage.

7.11.1.6 The configuration of static switch shall comply with options defined in IEC 62040-3 and
established as per Data Sheet between UPS with common or shared static switch.

NOTE The parallel connection of transformers from varied by-passes is a problem due to small
impedance differences in each secondary winding. It is recommended to contact the manufacturer
is the shared static switch topology is required. In the configuration of shared static switch,
composed transfer switches shall not be used, since they add an unnecessary complexity.

7.11.1.7 The total number of redundant parallel UPSs and the load division is equal to "N + R" and
shall be defined as per Data Sheet, where N is the number of individual UPS units required to
withstand the load and R is the number of redundant UPS units.

1)
Windows® é o nome comercial de um produto da Microsoft Corporation. Esta informação é dada para facilitar
aos usuários desta Norma e não constitui um endosso por parte da PETROBRAS ao produto citado. Podem ser
utilizados produtos equivalentes, desde que conduzam aos mesmos resultados.

12
-PUBLIC-

N-2760 REV. A ENGLISH 11 / 2012

Manual
transfer
By-pass switch

By-pass
auto
Static test
switch

Rectifier Inverter 1
Main
source 1

Accumulator
battery 1

Rectifier 2 Inverter 2
Main
source 2

Accumulator
battery 2

Figure 1 - Typical Configuration of Redundant Parallel UPS N = 1 and R = 1

NOTE 1 A typical configuration, in which 2 units in redundant parallel configuration shall withstand 100% of load
each, is N = 1 and R = 1.
NOTE 2 Another example of configuration, in which many redundant units add the required to withstand the
load, for instance, 4 UPS in parallel and one redundant unit, is N = 4 and R = 1. In this case, there are
5 UPS in parallel relying on the redundant unit. In this configuration, each of the 5 units is sized to
withstand 25 % of the load.
NOTE 3 Figure 1 represents a typical configuration of scope of supply of redundant parallel UPS N = 1 and R =
1, and does not establish a supply standard. The application in a design shall be thoroughly studied so
as to adapt the configuration of the equipment being purchased to local standards and installation site
needs.

8 Input Supply Characteristics

8.1 The UPS shall meet the grid requirements, as per 5.13, unless otherwise indicated in the Data
Sheet of Annex B.

8.2 Unless otherwise indicated in Data Sheet of Annex B, the input supply shall be four-wire three-
phase.

8.3 The negative-to-positive sequence ratio shall not exceed 5 %.

8.4 The short-circuit level in the UPS feed panel shall be as indicated on the Data Sheet of Annex B.

13
-PUBLIC-

N-2760 REV. A ENGLISH 11 / 2012

9 Characteristics of Fed Load

9.1 The fed load by the UPS has non-linear characteristics with a minimum peak factor of 3, typically
comprised of switch mode power supplies, with power factor usually between 0,6 and 1.

9.2 The UPS shall be sized to continuously supply the load of 100 % of the nominal apparent power.

10 Output Characteristics

10.1 The output voltage shall be as specified on the Data Sheet of Annex B.

10.2 The frequency shall be 60 Hz ± 3 Hz synchronized with the alternative source or ± 0,05 Hz by an
internal crystal oscillator.

10.3 The inverter shall limit the total harmonic distortion of output voltage for less than 3 % of the total
RMS with 100 % of linear load, or less than 5 % RMS with 100 % of non-linear load. The individual
harmonic distortion shall not exceed 3 %. In the by-pass mode, the harmonic distortion shall be equal
to or less than the input supply voltage distortion.

10.4 The UPS shall have output voltage characteristics under conditions involving change in mode of
operation (normal/stored energy/by-pass) and under conditions involving application of load increase
or decrease, and shall comply with 10.4.1 and 10.4.2.

10.4.1 Static voltage regulation shall be better than ± 1 % of the efficient nominal voltage under any
normal operating conditions.

10.4.2 Unless otherwise specified in the Data Sheet, the output voltage dynamic performance curves
of the UPS shall remain, according to IEC 62040-3, within the limits CCC equal to 111 for change of
operation mode, degree of linear load and degree of non-linear load.

10.5 The UPS shall withstand temporary overloads of 150 % of the rated current for a period of 1
minute, and of 125 % of the rated current for a period of 10 minutes. This overload condition shall be
tested considering the UPS supplying rated power and with the internal temperature stabilized in both
the normal and stored energy modes of operation.

10.6 The UPS, when three-phase type is specified, shall provide a phase angle between voltages of
120º ± 1º for balanced loads and 120º ± 3º for 100 % unbalanced loads, in the normal and stored
energy mode of operation.

10.7 The UPS, when three-phase type is specified, shall withstand 100 % of load unbalancing in
continuous duty, keeping an unbalance of the output voltage at ± 5 %, at the most in the normal and
stored energy operation mode.

11 Load Distribution Panel

If established in Data Sheet of Annex B, the UPS manufacturer shall be responsible for supplying the
load distribution panel. The description, drawing and requirements are defined in a separated
specification to be supplied by PETROBRAS.

14
-PUBLIC-

N-2760 REV. A ENGLISH 11 / 2012

12 Protection, Metering, Control and Signaling

12.1 The protection in the UPS inputs shall operate for short circuit, overvoltage and overcurrent
conditions.

12.2 The UPS shall inhibit the rectifier by high DC voltage or by short circuit at the rectifier output.

12.3 The UPS shall disconnect the battery bank when operated by final battery discharge voltage
adjustment. If the batteries reach the discharge limit recommended by the manufacturer, the static
switch shall transfer to the alternative source provided the synchronism conditions are fulfilled.
Otherwise the power delivered to the load shall be interrupted.

12.4 The UPS shall inhibit the inverter by continuous voltage outside limits, by overload and by
inverter failure. The inverter shall limit the current to the overload values and if the specified time is
exceeded, it shall transfer to the alternative source, when synchronized, and within the specified
voltage limits.

12.5 The UPS shall inhibit transfer by loss of synchronism with the alternative source, with the
frequency being transferred to reference of internal oscillator.

12.6 The UPS shall contain an alphanumeric digital display to indicate voltage, frequency, current,
historical register of faults, display of local alarms, adjustment parameter values:

a) main source input - voltage;


b) alternative source input - voltage, frequency;
c) direct current branch - rectifier output voltage and current, battery current, battery open
circuit voltage;
d) inverter output - voltage, current and frequency.

12.7 The diagnosed failures shall be available in accessible memory through digital communication
described in item 7.8, and shall be contained in the summary of alarms:

a) main source undervoltage;


b) main source overvoltage;
c) abnormal rectifier;
d) DC undervoltage;
e) DC overvoltage;
f) rectifier overload;
g) alternative source undervoltage;
h) alternative source overvoltage;
i) synchronism under abnormal conditions;
j) out of synchronism;
k) abnormal / blocked static switch;
l) abnormal inverter;
m) inverter overload;
n) inverter output undervoltage;
o) inverter output overvoltage;
p) self-monitoring failure detection;
q) battery disconnected;
r) battery discharging;
s) static switch transferred to alternative source;
t) manual transfer to alternative source;
u) earth leakage in DC link (optional Data Sheet);
v) earth leakage in safe busbar of consumers (optional Data Sheet);

15
-PUBLIC-

N-2760 REV. A ENGLISH 11 / 2012

w) UPS ventilation failure;


x) inhibition reload for gas detection in the batteries room (optional Data Sheet)

12.8 The UPS shall store in non-volatile memory historical register of the last 50 events at least. The
man-machine interface shall allow the reading of failures and events described in Chapter 12.

12.9 The UPS shall have a synoptic panel to show system operations, indicating at least the
following:

a) presence of voltage in main source and within normal parameters;


b) rectifier in operation;
c) direct current busbar energized and within normal parameters;
d) battery on float charge;
e) battery discharging;
f) inverter in operation;
g) presence of voltage in alternative source and within normal parameters;
h) normal static switch;
i) load fed by inverter;
j) load fed by main source;
k) load fed by alternative source.

12.10 The UPS shall have a circuit breaker for the main source input and one for the alternative
source input.

12.11 The UPS shall have manual static switch control on the front part of the UPS cabinet to allow
selection of the alternative source or inverter output. If the UPS is synchronized with the alternative
source, it shall promote transfer without interrupting the power delivered to the loads.

12.12 The UPS shall have a transfer switch with single command “make before break” type or
composite with simple switches to allow removal of the UPS for maintenance, as defined in Data
Sheet of Annex B. If the UPS is synchronized with the alternative source, the operation of this switch
shall not cause interruption of power delivered to the loads. When indicated in Data Sheet of Annex B,
the single command switch shall have an intermediate test position between normal and alternative
positions, so as to feed the safe AC busbar and static switch input by alternative source. When a
composite transfer switch is defined in Data Sheet of Annex B, it shall be made of simple switches, as
per Figure.

16
-PUBLIC-

N-2760 REV. A ENGLISH 11 / 2012

Alternative
source
Composite
transfer
By-pass switch
UPS
Cabinet Composi
transfer
switch

Alternative
source
Composi
transfer
switch

Figure 2 - Composite Transfer Switch

12.13 The UPS shall have at least remote alarms of battery feeding the load, load fed by the
alternative source and summary of failures. These alarms shall be made available through voltage-
free SPDT dry contacts with capacity of 0,5 A, 250 Vac / 125 Vdc, with inductive load (L/R = 0,04 s).

12.14 If the UPS manufacturer is responsible for supplying the load distribution panel, as established
in Chapter 11, it shall also be responsible for coordinating the protection of the entire system.

13 Static Switch

13.1 The static switch of the UPS shall implement the immediate transfer of load from the inverter to
the alternative source without interruption in case of overload, voltage outside limits, protection of
battery or by manual operation command. The synchronism transfer shall take place in a time of 4 ms
or shorter by inverter failure or overload. Out of synchronism, the transfer time shall be at least 1 cycle
(16,66 ms).

13.2 The static switch of the UPS shall implement transfer up to 4 ms from the alternative source to
the inverter, for recovery to within normal conditions or by manual operation, without interruption in
power delivered to the loads, in those situations in which the voltage of the alternative source and of
the UPS are normal and synchronized.

13.3 The static switch shall be sized to continuously withstand an overload current of 125 % of the
rated current of the UPS. It shall also withstand an overload of 200 % of the rated current of the UPS
for 30 s and withstand for 100 ms a current value of 1 000% of rated current.

14 Rectifier

The technical requirements for performance are established according to PETROBRAS N-332.

17
-PUBLIC-

N-2760 REV. A ENGLISH 11 / 2012

15 Inverter

15.1 The inverter bridge or the inverter stage shall be switched at high frequency by pulse width
modulation using appropriate semiconductors.

15.2 The inverter output voltage shall allow adjustment of ±5 % of the rated voltage.

16 Transformers

16.1 Transformers used in input and by-pass shall have independent windings, between the primary
and secondary, and tertiary where applicable.

16.2 Transformers shall be of the dry type and terminals of the bolt and eye type.

16.3 Sizing of the transformer due to the harmonic content generated by the UPS shall be in
accordance with IEC 61378-1.

16.4 The transformer of alternative source shall have taps in accordance with the Data Sheet, and
have grounded electrostatic shielding and dumping system in order to minimize vibration transmission
for the UPS. If the UPS output is three-phase, the transformer beside the static switch shall have its
primary in delta.

17 Technical Documentation

17.1 With Proposal

17.1.1 Detailed calculation notes shall be provided, according to IEEE STD 485 and STD 1115a,
showing the reasons of the selected battery according to the discharge profile shown on the Data
Sheet of Annex B by PETROBRAS.

17.1.2 It shall be informed the maximum heat dissipation to the environment of the group of
equipment and components in the various possibilities of operation (normal mode, full load, with
battery being recharged; or stored energy mode, or alternative source supply mode).

17.1.3 The battery recharging cycles shall be informed in the form of waves at 25 ºC.

17.1.4 The characteristic of voltage versus current of the battery current limiting circuit shall be
informed;

17.1.5 Catalogs of parts and components of the UPS, containing the characteristics and technical
specifications.

17.1.6 Block diagram, identifying the basic systems of the UPS and their interconnections.

18
-PUBLIC-

N-2760 REV. A ENGLISH 11 / 2012

17.1.7 Dimensional drawings of the front and side views and cross-sectional area of the UPS, with
approximate dimensions.

17.1.8 List of technical standards applicable to design, fabrication and testing, referring to the country
of origin of the technology followed by the manufacturer, complementing the list of technical standard
of Chapter 2 of this Standard.

17.1.9 Data Sheet fully completed and authenticated by the manufacturer, including the spaces
referring to the standards applicable to design, fabrication and testing of the UPS.

17.1.10 Quality control plan to be followed, containing at least the tests required by this Standard,
complemented by those proposed by the manufacturer.

NOTE This test plan shall be detailed, containing all phases and procedures to be followed and
implemented during the construction of the UPS, and indicating the reference standards
used and their respective items.

17.1.11 List of spare parts as required in the RM, with description of part numbers and respective unit
prices.

17.1.12 Complete and detailed plate treatment and painting system, including chemical and physical
performance rates.

17.1.13 Estimated weight of the UPS.

17.1.14 List of deviations or alternatives to specifications.

17.1.15 If requested in the Data Sheet of Annex B, the UPS manufacturer shall present a list of
similar equipment supplied with at least 3 years of operation. Prototypes and untested equipment are
not accepted.

17.1.16 The UPS manufacturer shall present a copy of demanded Type Tests in Data Sheet or as
established in item 18.

17.2 After AFM

Technical documentation which shall be submitted for approval or information, containing at least the
information in the following items:

a) dimensional drawings of views and cross-sections, including the free space for entrance
and exit of power and grounding cables, heat dissipation value and weight of UPS;
b) drawings showing location, dimensions and types of UPS attachment device;
c) functional, control and wiring (interconnection) diagrams, indicating all terminal strips,
including those needed for interconnection to other equipment or systems outside the
manufacturer’s scope of supply, clearly showing the identified terminals;
d) drawings of input and output terminal strips of power and command circuits;
e) list of all UPS components, including, as a minimum, description, quantity and complete
coding of the manufacturer;
f) one-line power diagram;
g) power interface drawings;

19
-PUBLIC-

N-2760 REV. A ENGLISH 11 / 2012

h) technical specifications of UPS as well as all components and accessories requested in


accordance with:
— all approved requirements of the original proposal;
— all revisions made at the time of technical clarifications and/or technical report;
i) list of spare parts with description of respective part-numbers of the component
manufacturer.

17.3 After Final Approval of Drawings

17.3.1 After final approval of all documents mentioned in the preceding item, the manufacturer shall
submit the documentation specified below in optical medium and with a paper copy, also subject to
comments. Manuals shall be drawn up in Portuguese or English and organized in accordance with the
following criterion:

a) diagrams and physical arrangements of electronic cards;


b) detailed description of operation of electronic cards, including waveforms and
adjustments;
c) specification of adjustments required for the UPS;
d) assembly and installation manual, containing at least the following information:
— procedures for storage of UPS and any spare components;
— procedures and details for assembly and mechanical installation of UPS and
accessories;
— procedures and details of electrical power and grounding connections;

17.3.2 An operations manual in Portuguese in optical medium and with a paper copy, containing at
least the following information, shall be provided:

a) description of UPS;
b) theoretical fundamentals;
c) commissioning instructions;
d) procedures for implementation of adjustment and parameterization functions;
e) list of error messages, occurrence conditions and the respective corrective actions;
f) operational procedures in failure and trip events;

17.3.3 A preventive and corrective maintenance manual in Portuguese, in optical medium and with a
paper copy, containing at least the following information, shall be submitted:

a) description of circuit operation, with their respective waveforms;


b) procedures for execution of internal adjustments;
c) detailed procedures for adjustments and tests, as well as list of materials and resources
needed for execution thereof;
d) maintenance procedures to be followed for each failure symptom presented;
e) fault finding methods, using the information obtained from the self-diagnostic system and
testing and measurement instruments;
f) diagrams and identification of internal components, terminal blocks, and printed circuit
boards;
g) list of components, containing their commercial identifications, brands and models;
h) connection and wiring diagrams;
i) layout drawings of the UPS;
j) technical catalogs with characteristic data of the accessories specified, “as supplied”;
k) copy of “as manufactured” drawings;
l) Data Sheet duly filled out “as purchased” and/or “as built”;
m) copy of all reports on tests performed on the UPS.
n) technical specifications of UPS, as well as all components and accessories used, in
accordance with:
— all approved requirements of the original proposal;
— all revisions made at the time of technical clarifications and/or technical report.

20
-PUBLIC-

N-2760 REV. A ENGLISH 11 / 2012

17.4 Requirements for Presentation of Documents

Documents, drawings and manuals shall be prepared, as a minimum, in 210 mm x 297 mm paper
size, in a legible manner, each one containing at least the following information:

a) identification of PETROBRAS department or Unit;


b) PETROBRAS equipment identification number;
c) RM number;
d) Purchase Order - PCS number.

NOTE For each drawing or document, on the right side of each page, near and above the
manufacturer’s stamp, a 15 cm x 4 cm rectangle shall be left in blank to be subsequently
completed by PETROBRAS.

18 Tests

The tests applicable to the UPS-CA are listed in Table 1, and the test descriptions shall be checked in
Annex A, Test Definition. TAF and TAC tests to be presented are marked as per Data Sheet of Annex
B or as below.

Table 1 - List of Tests

Test TYPE TAF TAC


Preliminary tests
Control and monitoring signals X X
Check of interconnection cables X X
Test of UPS auxiliary devices X X
Light load test X X
UPS input feed tests
AC input voltage tolerance in permanent condition X X
Input voltage frequency variation X X
Inrush current X
UPS output characteristics - static condition
Output - normal mode - no load X X
Output - normal mode - rated load X X
Output - stored energy mode - no load X X
Output - stored energy mode - rated load X X
Unbalanced output voltage test X X
Output voltage dc component and zero sequence X X
Output - normal operation mode - overload X X
Output - stored energy operation mode - overload X X
Reference non-linear load charge output distortion – normal mode
X X
and stored energy mode
Short-circuit
Short-circuit - no transfer to static switch and no short-circuit
X X
elimination
Short-circuit - with transfer to static switch and with short-circuit
X X
elimination
UPS output dynamic tests
Linear loads X X
Non-linear loads X X
Stored energy and restored energy tests X
Restored energy time at 90% of capacity X
Input efficiency and power factor X X
Emission, radio frequency interference supportability and conducted noise tests
Emission X
Immunity (electromagnetic susceptibility) X

21
-PUBLIC-

N-2760 REV. A ENGLISH 11 / 2012

Table 1 - List of Tests (Continued)

Test Type TAF TAC


Synchronization tests
Synchronization time X X
Phase angle X X
Variation in alternative source frequency X X
Failure simulation in UPS in parallel redundancy
Failure in one of redundant parallel system units X X
Shutdown of one of redundant parallel system units X X
Transfer test
Operation in synchronism with alternative source – manual operation X X X
for transfer
Operation in synchronism with alternative source – automatic X X X
operation for transfer
Operation out of synchronism with alternative source – manual
X X X
operation for transfer
Operation out of synchronism with alternative source – automatic
X X X
operation for transfer
Division of current in parallel or redundant parallel X X
Test of ripple (residual wave) current in battery X
Harmonic components test X X
Temperature rise test X X
Static switch test
Overload tests X
Overvoltage tests X
Non-electrical tests
Environmental tests
Vibration and shock test
Shock test X
Free drop test X
Connector vibration and shock test X
Audible noise X

22
-PUBLIC-

N-2760 REV. A ENGLISH 11 / 2012

Annex A - Definition of Tests

A.1 General Conditions

A.1.1 The tests defined in this Annex shall be performed in each unit of the UPS assembly. More than
one UPS assembly shall only be used in tests of division of current in parallel or redundant parallel
and failure of one of the redundant parallel system units.

A.1.2 The linear load to be used in all tests described shall be resistive, with tolerance of 5% and
power factor ≥ 98 %. The load shall have dynamic response under 20 ms ± 5 %, after the temperature
stabilizes.

A.1.3 Measurement equipment and instruments used in test shall:

a) have calibration certificates;


b) have sufficient pass band to accurately measure real efficient values (True RMS) of wave
forms which may be other than fundamental sinusoid, in order words, with significant
harmonic content.

A.1.4 The recording instrument (Ex.: Oscilloscope with memory or oscillograph) shall have at least
4 galvanically insulated channels, CAT III (600 Vac), with x10, x100 voltage probes, current probes for
10 /100 /1 000 A, precision 0,2% and accuracy 3,5 digits.

A.2 Tests

A.2.1 Preliminary Tests

The tests described in this subsection shall be performed so as to check the correct assembly of the
equipment before the main tests.

A.2.1.1 Control and Monitoring Signals (IEC 62040-3)

The operation of indications and signals shall be checked in all performed tests. Gauge tests shall be
performed in all measurement equipment items of UPS, including components for remote measuring
through industrial networks. The manufacturer shall supply means to perform these measurements.

A.2.1.2 Check of Interconnection Cables (IEC 62040-3)

The test shall be performed after connecting the functional units which comprise the full UPS. This test
shall be performed in factory and at the installation site if there is any disassembling of equipment for
transport. The document used to check the connections shall be attached to the test documentation.

A.2.1.3 Test of UPS Auxiliary Devices (IEC 62040-3)

Functionalities of the UPS auxiliary devices, such as lighting, cooling, pumps, vents, alarms, and
optional devices, shall be checked in the light load test or during other tests.

23
-PUBLIC-

N-2760 REV. A ENGLISH 11 / 2012

A.2.1.4 Light Load Test (IEC 62040-3)

A.2.1.4.1 Test Condition

This test shall be performed to check if the UPS is correctly connected and if all functions are
operating. The tests below shall be performed with or without AC.

A.2.1.4.2 Measurements and Checks

— output voltage and frequency;


— operation of everything with controls, alarms, event logs, measurements and other
means required for proper operation of the UPS.

A.2.1.4.3 Acceptance Criterion

The UPS functionalities shall be in accordance with the manufacturer’s manual.

A.2.2 UPS Input Feed Tests (IEC 62040-3)

The UPS shall be in normal operating mode with rated output active power load. The input feed shall
come from a variable voltage/frequency generator, which output impedance able to keep the voltage
wave form within the limits of IEC 61000-2-2. In tests in which the frequency variation is not required,
the UPS may be fed by electrical power grid.

A.2.2.1 AC Input Voltage Tolerance in Permanent Condition (IEC 62040-3)

A.2.2.1.1 Test Condition

With the UPS in normal operation mode and rated input frequency, the input voltage shall be adjusted
to the minimum and maximum values of tolerance range specified by IEC 62040-3 and this Standard
(± 10 % of rated voltage), until the UPS stabilizes.

A.2.2.1.2 Measurements and Checks

A.2.2.1.2.1 The output voltage shall be measured and its tolerance registered in maximum and
minimum input voltages.

A.2.2.1.2.2 When the UPS design prevents the normal operation mode over ±10 % of rated feed
voltage, changing the operation to stored energy, the recorded value shall be the voltage before
the change.

A.2.2.1.3 Acceptance Criterion

The equipment shall operate normally and without damaging itself.

24
-PUBLIC-

N-2760 REV. A ENGLISH 11 / 2012

A.2.2.2 Input Voltage Frequency Variation (IEC 62040-3)

A.2.2.2.1 Test Condition

A.2.2.2.1.1 Adjust the generator frequency that is feeding the UPS in 60 Hz, keep the recording
instrument in the UPS output so as to record the synchronism input and output values with the
network (generator).

A.2.2.2.1.2 Vary it slowly (1 Hz/s) until less than 57 Hz and notice that, when it reaches 57 Hz, the
synchronism with grid shall be disconnected, and the UPS shall operate by its local oscillator, keeping
the output in 60 Hz ± 0.05 Hz.

A.2.2.2.1.3 Return it slowly (1 Hz/s) until 57 Hz, notice the synchronism of inverter with grid
(Generator), record with oscillograph, keep increasing the frequency slowly (1 Hz/s) until reaching
more than 63 Hz, and notice that, when reaching 63 Hz the synchronism with grid shall be
disconnected, and the UPS shall operate by its local oscillator, keeping the output in 60 Hz ± 0,05 Hz.

A.2.2.2.1.4 The test in A.2.2.1 shall be repeated with the input voltage frequency adjusted to specified
limits (± 5 % of rated frequency) alongside the input voltage variations.

NOTE It is considered that a decrease in frequency does not coincide with an increase in line
voltage, and vice-versa.

A.2.2.2.2 Measurements and checks:

When the output voltage frequency of UPS is synchronized with the input voltage frequency, the
synchronism range shall be checked. The free running frequency shall be recorded for non-
synchronous conditions. It shall be checked the moment in which there is loss of synchronism with the
grid, when the inverter starts working through the local oscillator of inverter.

NOTE The output frequency tolerance range shall be checked in temperature rise test, for specified
input voltage variation range and specified load variation range. When the frequency is
determined only by the internal oscillator, this range may be checked for the control
equipment (oscillator) along the temperature range.

A.2.2.2.3 Acceptance Criterion

Within the defined synchronism range, the UPS shall not transfer to by-pass. When the total input
frequency range exceeds the defined synchronism range, the UPS output shall revert to free running
internal oscillator operation.

A.2.2.3 Inrush Current (IEC 62040-3)

A.2.2.3.1 Test Condition

A.2.2.3.1.1 The Inrush current test shall be performed under two input voltage fault conditions:

— after a lack of input voltage for more than 5 minutes;


— after a lack of input voltage of 1s;

25
-PUBLIC-

N-2760 REV. A ENGLISH 11 / 2012

A.2.2.3.1.2 The test shall be performed with no battery and no load.

A.2.2.3.1.3 The UPS-CC shall be energized 10 times asynchronously and randomly for each
condition of lack of voltage, so as to determine the worst case condition of inrush current:

— in units coupled to a transformer, when energized in zero voltage point;


— for resistive or capacitive loads, in peak of voltage wave form of input feed, or near it;

A.2.2.3.1.4 For this test, initial current surges due to energizing of RFI capacitors in input filters with
duration under 1ms shall be ignored;

A.2.2.3.1.5 High frequency current transformers shall be used for oscillographic record;

A.2.2.3.1.6 For this test, it shall be considered the manufacturer’s standard complete UPS, excluding
voltage adapting transformers requested for specific use.

A.2.2.3.2 Measurements and Checks

A.2.2.3.2.1 Oscillographic record of UPS Inrush current.

A.2.2.3.2.2 Oscillographic record of voltage at the moment of closing the switch energizing the UPS,
used as a trigger reference.

A.2.2.3.3 Acceptance Criterion

Maximum RMS Inrush current shall not exceed 15 x Irated, and the duration shall not be longer than
two cycles.

A.2.3 UPS Output Characteristics - Static Condition (IEC 62040-3)

A.2.3.1 Output - Normal Mode - No Load (IEC 62040-3)

A.2.3.1.1 Test Condition

UPS operating in normal operation mode, with no load and with rated input voltage and frequency.

A.2.3.1.2 Measurements and Checks

Measure the output voltage and voltage of fundamental and harmonic components.

A.2.3.1.3 Acceptance Criterion

A.2.3.1.3.1 Output voltage: <= 10 % (synchronized with the grid) and ± 1 % (not synchronized with
the grid) of rated voltage.

A.2.3.1.3.2 Output voltage frequency ± 5 % (synchronized with the grid) and ± 0,05 Hz (not
synchronized with the grid) of rated frequency.

26
-PUBLIC-

N-2760 REV. A ENGLISH 11 / 2012

A.2.3.1.3.3 Output voltage harmonics: THD ≤ 3 %;

A.2.3.2 Output - Normal Mode - Rated Load (IEC 62040-3)

A.2.3.2.1 Test Condition

UPS operating in normal operation mode, with 100 % of active rated load and with rated input voltage
and frequency.

A.2.3.2.2 Measurements and Checks

Measure the output voltage and voltage of fundamental and harmonic components.

A.2.3.2.3 Acceptance Criterion

A.2.3.2.3.1 Output voltage: ± 10 % (synchronized with the grid) and ± 1 % (not synchronized with
the grid) of rated voltage.

A.2.3.2.3.2 Output voltage frequency ± 5 % (synchronized with the grid) and ± 0.05 Hz (not
synchronized with the grid) of rated frequency.

A.2.3.2.3.3 Output voltage harmonics: THD ≤ 3 %

A.2.3.3 Output - Stored Energy Mode - No Load (IEC 62040-3)

A.2.3.3.1 Test Condition

UPS operating through batteries, with no load.

A.2.3.3.2 Measurements and Checks

Measure voltage, frequency and their fundamental and harmonic components.

A.2.3.3.3 Acceptance Criterion

A.2.3.3.3.1 Output voltage: ± 1 % of rated voltage.

A.2.3.3.3.2 Output frequency ± 0.05 Hz of rated frequency (by internal oscillator).

A.2.3.3.3.3 Output voltage harmonics: THD ≤ 3 %

27
-PUBLIC-

N-2760 REV. A ENGLISH 11 / 2012

A.2.3.4 Output - Stored Energy Mode - Rated Load (IEC 62040-3)

A.2.3.4.1 Test Condition

Apply a resistive load equal to 100 % of active rated power of UPS in output.

A.2.3.4.2 Measurements and Checks

A.2.3.4.2.1 In continuous duty, in starting condition of battery discharge, measure the voltage,
frequency and fundamental and harmonic components in output.

A.2.3.4.2.2 Record the output voltage with no load and full load, check calibration.

A.2.3.4.2.3 Notice the parameters above until the UPS shuts down due to battery undervoltage.

A.2.3.4.2.4 Record the total time, voltage calibration and worst fundamental and harmonic levels,
which shall not exceed the values stated by the manufacturer.

NOTE For UPS with batteries with storage time under 10 minutes, it is allowed to connect an
additional battery to keep the test stable and allow the measurement. This test requires
instrumentation with sufficient time scan to observe the voltage decrease over battery time.

A.2.3.4.3 Acceptance Criterion

A.2.3.4.3.1 Charged battery:

— output voltage with no load within the tolerance;


— output voltage with load within the tolerance;
— calibration (± 1 %);
— output voltage harmonics: THD ≤ 3 %.

A.2.3.4.3.2 Final charge battery:

— output voltage with load within the tolerance;


— calibration (± 1 %);
— output voltage harmonics: THD ≤ 3 %.

A.2.3.5 Unbalanced Output Voltage Test (IEC 62040-3)

A.2.3.5.1 Test Condition

A.2.3.5.1 The output voltage unbalance in three-phase output UPS shall be checked under conditions
of load with balanced rated active power, and also under conditions of 100% unbalanced load.

A.2.3.5.2 The test shall be performed:

— in normal operation mode;


— in stored energy mode, fully charged and final discharge. Battery voltage simulations
are allowed for this test.

28
-PUBLIC-

N-2760 REV. A ENGLISH 11 / 2012

A.2.3.5.2 Measurements and Checks

Output voltages between phases and phase-neutral (if any) shall be observed and recorded. The
voltage unbalance shall be given in a voltage unbalance index or voltage unbalance factor, as per
IEC 60146-2. Phase angle deviations shall be determined by calculation from the values of voltages
between phases and phase-neutral.

A.2.3.5.3 Acceptance Criterion

The result shall be within the specified voltage and angle tolerance specifications, without losing
synchronism with the by-pass grid and without switching to the static switch. The UPS shall withstand
100 % of load unbalancing in continuous duty, keeping an unbalance of the output voltage at ± 5 %.
The UPS shall provide phase angle between voltages of 120º ± 1º for balanced loads, and 120º ± 3º
for 100 % unbalanced loads.

A.2.3.6 Output Voltage DC Component and Zero Sequence (IEC 62040-3)

A.2.3.6.1 Test Condition

UPS operating in normal operation mode, with no load and with rated input voltage and frequency. If
the UPS output is three-phase, the zero sequence component of this voltage shall be measured.

A.2.3.6.2 Measurements and Checks

Output voltages between phases and phase-neutral (if any) shall have an oscillographic record.

A.2.3.6.3 Acceptance Criterion

The DC component of output voltage shall be under 0,1% of the AC rms value. If there is a neutral,
there shall be no zero sequence component in output voltage.

A.2.3.7 Output - Normal Operation Mode - Overload (IEC 62040-3)

A.2.3.7.1 Test Condition

The UPS shall provide rated active power and with stabilized internal temperature in normal
operation mode. The static switch shall be blocked for transfer. The test shall be considered for
each inverter. Apply overload of 150 % of the rated current for a period of 1 minute, and of 125 %
of the rated current for a period of 10 minutes.

A.2.3.7.2 Measurements and Checks

— output voltage;
— frequency;
— output current;
— local and remote alarms of “inverter overload”;
— event log of UPS..

29
-PUBLIC-

N-2760 REV. A ENGLISH 11 / 2012

A.2.3.7.3 Acceptance Criterion

Local and remote alarm, indicating “inverter overload”, but the output voltage and frequency shall
remain within the nominal range (keep the voltage static calibration and frequency calibration of ±0,05
Hz) for the minimum time indicated above. The UPS shall not have any damage, nor equipment
shutdown due to overheating. The event shall be memorized, allowing only the manual reset of the
alarm.

A.2.3.8 Output - Stored Energy Operation Mode - Overload (IEC 62040-3)

A.2.3.8.1 Test Condition

The UPS shall provide rated active power and with stabilized internal temperature in stored energy
operation mode. The static switch shall be blocked for transfer. The test shall be considered for
each inverter. Apply overload of 150 % of the rated current for a period of 1 minute, and of 125 %
of the rated current for a period of 10 minutes.

A.2.3.8.2 Measurements and Checks

— output voltage;
— frequency;
— output current;
— local and remote alarms of “inverter overload”;
— event log of UPS..

A.2.3.8.3 Acceptance Criterion

Local and remote alarm, indicating “inverter overload”, but the output voltage and frequency shall
remain within the nominal range (keep the voltage static calibration and frequency calibration of ±0,05
Hz) for the minimum time indicated above. The UPS shall not have any damage, nor equipment
shutdown due to overheating. The event shall be memorized, allowing only the manual reset of the
alarm.

A.2.3.9 Reference Non-Linear Load Charge Output Distortion – Normal Mode and Stored
Energy Mode (IEC 62040-3)

A.2.3.9.1 Test Condition

With the UPS operating in normal mode (existing AC input), apply to UPS output a set of reference
non-linear load charge so as to obtain apparent output power for the UPS under test. After performing
the measurements, repeat the test, stopping the input feed from rectifier so as to force a transition to
stored energy operation mode.

A.2.3.9.2 Measurements and Checks

A.2.3.9.2.1 Oscillographic record of output voltage of UPS in continuous duty conditions.

A.2.3.9.2.2 Record the waveform of output voltage and its harmonic content.

30
-PUBLIC-

N-2760 REV. A ENGLISH 11 / 2012

A.2.3.9.3 Acceptance Criterion

The waveforms of output voltage wave, its fundamental and harmonic content for both test conditions
shall not exceed the established values (THD ≤ 5 %). In addition, the DC voltage of the reference non-
linear load capacitors shall be measured to ensure that its value remains within the limits calculated by
the formula of standard IEC 62040-3 for the Uc parameter.

A.2.4 Short-Circuit

A.2.4.1 Short-circuit - No Transfer to Static Switch and No Short-Circuit Elimination (IEC


62040-3)

A.2.4.1.1 Test Condition

A.2.4.1.1.1 UPS providing rated active power and with stabilized internal temperature in normal
operation mode, with no availability for Static Switch to transfer the load to other power source.

A.2.4.1.1.2 The test shall be considered for each inverter.

A.2.4.1.1.3 Apply full short-circuit to AC output of UPS indefinitely. For UPS with three-phase
output, it shall be applied phase-phase or phase-neutral short circuit, if neutral is available.

A.2.4.1.1.4 The test shall be fully repeated, simulating stored energy with fully charged battery,
and shall present the same results.

A.2.4.1.2 Measurements and Checks

A.2.4.1.2.1 Oscillographic record of UPS output voltage and current.

A.2.4.1.2.2 Record on event log of UPS.

A.2.4.1.3 Acceptance Criterion

— local and remote alarm, indicating “short-circuit in inverter”;


— UPS shall not be damaged;
— interruption of AC output of UPS;
— UPS shall protect itself, not causing fuse blowing or opening of circuit breakers;
— the event shall be memorized, not disappearing after normalization.

A.2.4.2 Short-Circuit - With Transfer to Static Switch and with Short-Circuit Elimination (IEC
62040-3)

A.2.4.2.1 Test Condition

A.2.4.2.1.1 UPS providing rated active power and with stabilized internal temperature in normal
operation mode, with availability for Static Switch to transfer the load to other power source.

31
-PUBLIC-

N-2760 REV. A ENGLISH 11 / 2012

A.2.4.2.1.2 The test shall be considered for each inverter.

A.2.4.2.1.3 Apply full short-circuit to AC output of UPS for a time determined by fuse or circuit
breaker. The fuse or circuit breaker sizing shall be as such that their opening time in short-circuit
current of inverter exceeds the transfer time to the by-pass.

A.2.4.2.1.4 Apply according to Figure A.1. For UPS with three-phase output, a phase-phase short-
circuit shall be applied. For UPS with three-phase-ground output, it shall be applied phase-ground
short-circuit.

A.2.4.2.1.5 The test shall be fully repeated in the stored energy with fully charged battery, and
shall present the same results.

UPS

Figure A.1 - Test Circuit

A.2.4.2.2 Measurements and Checks

— oscillographic record of UPS output voltage and current;


— record the operation of protective devices, short-circuit current peak and short-circuit
current in permanent duty, with its duration;
— the event shall be memorized, allowing only the manual reset of the alarm;
— local and remote alarm of “short-circuit in inverter”;
— interruption of AC output of UPS;
— event log of UPS;
— the UPS shall transfer to By-Pass.

A.2.4.2.3 Acceptance Criterion

— local and remote alarm, indicating “short-circuit in inverter”;


— UPS shall not be damaged;
— after eliminating the circuit, the UPS shall return to normal mode (return to normal
operation mode of inverter with rated voltage and frequency) in a maximum of 200 ms;
— the event shall be memorized, not disappearing after normalization.

A.2.5 UPS Output Dynamic Tests

A.2.5.1 Linear Loads

A.2.5.1.1 Change of Operation Mode - Normal to Stored Energy - Linear Load (IEC 62040-3)

A.2.5.1.1.1 Test Condition

32
-PUBLIC-

N-2760 REV. A ENGLISH 11 / 2012

— the tests described in this sub-item shall be performed with assistance of a variable
voltage generator connected to three-phase input of UPS rectifier;
— the tests described in this sub-item shall be performed at 0 %, 50 % and 100 % of rated
active power of UPS, in minimum and maximum input voltage conditions of rectifier and
alternative source. These tests shall be performed in the conditions described in
A.2.5.1.1.1.1 to A.2.5.1.1.1.3.

A.2.5.1.1.1.1 Input Voltage Variation of Rectifier

The UPS rectifier shall operate normally, keeping the DC busbar within normal operation conditions,
when the rectifier input voltage varies within the voltage range of at least ± 10 % of specified nominal
value. Out of the range (minimum of ± 10 % or higher, specified by the manufacturer), the rectifier
shall remain inhibited, being the DC busbar (batteries) responsible for supplying energy to inverter and
to output, respectively.

A.2.5.1.1.1.2 Failure of Alternative Input AC Source

The load shall be originally fed by the inverter branch. The static switch shall operate normally within
the admissible range of variation of alternative source. The variation range value is ±5 % of voltage.
Two observations shall be performed. The first is a variation within the admissible range, in which the
static switch shall operate normally without indicating failure and without any transfer. The second is a
variation of alternative voltage out of the specified range. In this case, the failure alarm shall occur, the
inverter shall lose its synchronism, and no transfer shall take place in static switch.

A.2.5.1.1.1.3 Simultaneous Failure of Rectifier and Alternative Input AC Sources

In failure of AC branches of rectifier and alternative input, the inverter output shall feed the output with
no voltage or frequency variation. The respective failure alarms shall be activated and the battery (or
DC source) energy shall supply the load at this time. The inverter shall return to rated frequency at a
maximum rate of 1 Hz/s.

A.2.5.1.1.2 Measurements and Checks:

— oscillographic record of UPS output voltage;


— oscillographic record of UPS output current.

A.2.5.1.1.3 Acceptance Criterion

The output voltage and frequency shall remain within the specified limits. The UPS shall not be
damaged.

A.2.5.1.2 Change of Operation Mode - Stored Energy to Normal - Linear Load (IEC 62040-3)

A.2.5.1.2.1 Test Condition

The test consists of checking the return of rectifier AC feed with UPS in operation. The UPS shall
be operating through the inverter branch. The test shall be performed by switching on the rectifier
input feed and observing the output voltage and frequency.

A.2.5.1.2.2 Measurements and Checks

Oscillographic record of UPS output voltage.

33
-PUBLIC-

N-2760 REV. A ENGLISH 11 / 2012

A.2.5.1.2.3 Acceptance Criterion

The output voltage and frequency shall remain within the specified limits.

A.2.5.1.3 Change of Operation Mode - Normal to By-Pass - Linear Load (IEC 62040-3)

A.2.5.1.3.1 Test Condition

With the UPS operating in normal mode, apply an overload on it, as per tests A.2.3.7 and A.2.3.8,
without the by-pass inhibition of the mentioned tests, and check the transfer of operation mode
through inverter to by-pass operation. The testes shall be repeated within the voltage and frequency
variation ranges informed by the manufacturer for automatic change of operation mode.

A.2.5.1.3.2 Measurements and Checks

Oscillographic record of input and output voltages, currents and frequency of UPS at the moment of
overload application until voltage and current stabilization through the by-pass.

A.2.5.1.3.3 Acceptance Criterion

Local and remote alarm, indicating “overload in inverter”; output voltage and frequency shall remain
within the nominal range (± 5 % of Voltage and ± 0.05 Hz frequency). The UPS shall not be damaged
or overheated. The event shall be memorized, allowing only the manual reset of the alarm. The
maximum acceptable interruption of output voltage in the change of operation mode shall be 4 ms. In
the entire tolerance range indicated by the manufacturer for input voltage and frequency variation,
there shall be change of operation mode.

A.2.5.1.4 Degrees of Load - Linear Load (IEC 62040-3)

A.2.5.1.4.1 Test Condition

With the UPS operating under conditions of A.2.3.1 (Output - normal mode – no load), apply a degree
of resistive load equal to 100 % of output active power.

A.2.5.1.4.2 Measurements and Checks

A.2.5.1.4.2.1 Oscillographic record of UPS output voltage.

A.2.5.1.4.2.2 Reduce load to 0 %. Repeat previous measurements at the moment of


disconnection, and compute the value which shall remain within the established limits.

A.2.5.1.4.2.3 Repeat the test 10 times and consider the worst case result.

A.2.5.1.4.3 Acceptance Criterion

According to Static and Dynamic Regulation established.

34
-PUBLIC-

N-2760 REV. A ENGLISH 11 / 2012

A.2.5.1.3 Change of Operation Mode - Normal to By-Pass and Return to Normal - Linear Load.
(IEC 62040-3)

A.2.5.1.5.1 Test Condition

With the UPS operating normally (with AC grid, operation through inverter, and rated active load with
100 % capacity), perform load transfer command to by-pass. Then, interrupt the feed to by-pass.

A.2.5.1.5.2 Measurements and Checks

Record the waveform, on the load, during return transfer from it to inverter output.

A.2.5.1.5.3 Acceptance Criterion

Transfer time shorter than 4 ms.

NOTE To perform this test, the UPS shall have this facility.

A.2.5.2 Non-Linear Loads

A.2.5.2.1 Change of Operation Mode – Normal to Stored Energy - Reference Non-Linear


Load (IEC 62040-3)

A.2.5.2.1.1 Test Condition

The tests described in this sub-item shall be performed with assistance of a variable voltage generator
connected to three-phase input of UPS rectifier. The tests described in this sub-item shall be
performed at 0 %, 50 % and 100 % of rated active power of UPS, in minimum and maximum input
voltage conditions of rectifier and alternative source. These tests shall be performed in the conditions
described in A.2.5.2.1.1.1 to A.2.5.1.1.3.

A.2.5.2.1.1.1 Input Voltage Variation of Rectifier

The UPS rectifier shall operate normally, keeping the DC busbar within normal operation
conditions, when the rectifier input voltage varies within the voltage range of at least ± 10 % of
specified nominal value. Out of the range (minimum of ± 10 % or higher, specified by the
manufacturer), the rectifier shall remain inhibited, being the DC busbar (batteries) responsible for
supplying energy to inverter and to output, respectively.

A.2.5.2.1.1.2 Failure of Alternative Input AC Source

a) The load shall be originally fed by the inverter branch. The static switch shall operate
normally within the admissible range of variation of alternative source. The variation
range value is ± 5 % of voltage;
b) Two observations shall be performed. The first is a variation within the admissible range,
in which the static switch shall operate normally without indicating failure and without any
transfer. The second is a variation of alternative voltage out of the specified range. In this
case, the failure alarm shall occur, the inverter shall lose its synchronism, and no transfer
shall take place in static switch.

35
-PUBLIC-

N-2760 REV. A ENGLISH 11 / 2012

A.2.5.2.1.1.3 Simultaneous Failure of Rectifier and Alternative Input AC Sources

a) in failure of AC branches of rectifier and alternative input, the inverter output shall feed
the output with no voltage or frequency variation. The respective failure alarms shall be
activated and the battery (or DC source) energy shall supply the load at this time;
b) the inverter shall return to rated frequency at a maximum rate of 1 Hz/s.

A.2.5.2.1.2 Measurements and Checks

a) oscillographic record of UPS input and output voltage;


b) oscillographic record of UPS output current.

A.2.5.2.1.3 Acceptance Criterion

The output voltage and frequency shall remain within the specified limits. The UPS shall not be
damaged.

A.2.5.2.2 Change of Operation Mode - Stored Energy to Normal - Reference Non-Linear


Load (IEC 62040-3)

Repeat the change of operation mode test of A.2.5.1.2 using 100 % of reference non-linear load, and
the same measurements, checks and acceptance criteria.

A.2.5.2.3 Degrees of Load - Normal Mode - Reference Non-Linear Load (IEC 62040-3)

A.2.5.2.3.1 Test Condition

A.2.5.2.3.1.2 With the UPS in normal operation mode, apply a reference non-linear load as per
item A.2.3.9, adjusted to obtain 33 % of rated output apparent power as base load.

A.2.5.2.3.1.3 In permanent duty conditions, apply, at the moment of waveform peak of output
voltage, an additional reference non-linear load adjusted to 33 % of rated output apparent power.

A.2.5.2.3.1.4 When applying the additional load, record the transitional deviations of output voltage
waveform.

A.2.5.2.3.1.5 When applying the additional load, record the transitional deviations of output voltage
waveform. With 66 % of initial load, apply, apply, at the moment of waveform peak of output
voltage, a degree of the remaining 33% of reference non-linear load, and repeat the measurements
of output voltage waveform.

A.2.5.2.3.1.6 In permanent duty conditions, switch off 33 % of reference non-linear load at the
moment of waveform peak of output voltage. At the moment of disconnection, repeat the
measurements of output voltage waveform.

A.2.5.2.3.1.7 Repeat the switch off of the next degree of 33% of reference non-linear load to return
the base load, and record the transitional deviations of output voltage waveform.

36
-PUBLIC-

N-2760 REV. A ENGLISH 11 / 2012

A.2.5.2.3.2 Measurements and Checks

Oscillographic record of transient performance during change of operation mode.

A.2.5.2.3.3 Acceptance Criterion

According to Static and Dynamic Regulation established.

A.2.5.2.4 Degrees of Load - Stored Energy Mode - Reference Non-Linear Load (IEC 62040-3)

A.2.5.2.4.1 Test Condition

Repeat the tests as per A.2.5.2.2 in stored energy mode, simulating the minimum and maximum
battery voltage.

A.2.5.2.4.2 Measurements and Checks

Oscillographic record of transient performance during change of operation mode.

A.2.5.2.4.3 Acceptance Criterion

The UPS may not transfer to by-pass and the static and dynamic calibration shall remain within the
limits established in this specification.

A.2.6 Stored Energy and Restored Energy Tests (IEC 62040-3)

A.2.6.1 Restored Energy Time at 90 % of Capacity (IEC 62040-3)

A.2.6.1.1 Test Condition

At the end of the stored energy time test (IEC 62040-3), apply again the input feed in UPS and
operate in normal mode, input rated voltage, and active and apparent output rated powers.

A.2.6.1.2 Measurements and Checks

After the end of recharge time defined by the manufacturer (10 hours, 0.1C10), measure the input and
output voltages, currents and active powers.

A.2.6.1.3 Acceptance Criterion

When the input current reaches the internal balance, it indicates the end of energy restoring time. It
shall be checked if the current provided by rectifier supplies 100 % of inverter load, as well as keeps
the batteries charged until reaching 90 %.

37
-PUBLIC-

N-2760 REV. A ENGLISH 11 / 2012

A.2.7 Input Efficiency and Power Factor (IEC 62040-3)

A.2.7.1 Test Condition

A.2.7.1.1 Stable input conditions shall be reached. The following charge conditions shall be imposed
to UPS:

— apply charge of 100% rated active power;


— apply charge of 100% of reference non-linear load.

A.2.7.1.2 For this test, it shall be considered the manufacturer’s standard complete UPS, excluding
voltage adapting transformers requested for specific use.

A.2.7.2 Measurements and Checks

Record the following input and output parameters for each load condition established in test condition:

— current;
— voltage;
— active power.

A.2.7.3 Acceptance Criterion

The efficiency shall be better than the established in Table A.1:

Table A.1 - Efficiency for UPS VFI-S of 3 kVA or More

Minimum acceptable
Voltage of direct current branch
efficiency
< 120 Vdc 80 %
120 Vdc to 220 Vdc 86 %
220 Vdc to 360 Vdc 88 %
> 360 Vdc 91 %

A.2.8 Emission, Radio Frequency Interference Supportability and Conducted Noise Tests
(IEC 62040-3 e 62040-2)

A.2.8.1 Definitions

A.2.8.1.1 Ambient

A.2.8.1.1.1 First Ambient: Ambient with residences, commercial installations and small industries
directly connected to public low-voltage grid without intermediate transformer.

A.2.8.1.1.2 Second Ambient: Ambient with all commercial and industrial installations not
connected to public low-voltage grid used for residential purposes.

38
-PUBLIC-

N-2760 REV. A ENGLISH 11 / 2012

A.2.8.1.2 Category

Category C3: This category includes UPS with output current over 16 A, intended to the second
ambient. These UPS are adequate for use in industrial and commercial installations with minimum
distance of 30 m from buildings classified as first ambient. Category C3 UPS shall comply with the
emission and immunity limits, as mentioned in IEC 62040-2.

A.2.8.1.3 Test Condition

According to definitions of IEC 62040-2, the UPS listed in this document are Category C3 and belong
to the Second Ambient.

A.2.8.2 Emission IEC 62040-3

A.2.8.2.1 Test Condition

A.2.8.2.1.1 Tests shall be performed with the UPS in the following conditions:

— rated input voltage;


— in normal operating mode and stored energy mode;
— load resulting in the highest levels of emission.

A.2.8.2.1.2 The installation site conditions shall not cause deviations due to pre-existing emissions in
site and to emissions caused by equipment fed by the UPS. Measurements shall be taken in operating
mode that produces the highest emission in frequency range.

A.2.8.2.2 Acceptance Criterion

Ensure that disturbances generated by UPS in normal operation do not reach level which may prevent
other equipment items from operating as intended.

A.2.8.2.2.1 Interference in feeding terminals:

— shall not exceed the limits established in IEC 62040-2;


— the UPS shall reach both the Average and Quasi-peak limits, using a detector receptor of
Average and Quasi-peak;
— the detector receptors of Average and Quasi-peak shall comply with the series IEC
CISPR 16 (16-1-1, 16-1-2, 16-1-3, 16-1-4 and 16-1-5);
— if the average limit is found when using a detector receptor of quasi-peak, the test unit
shall be deemed to comply with both limits, and the measurement with the detector
receptor of average is not necessary;
— if the measurement reading of receptor shows fluctuations near to the limit, the reading
shall be observed for at least 15 s at each measurement frequency; the higher reading
shall be recorded, except for one brief high and isolated reading, which shall be ignored.

A.2.8.2.2.2 Interference in a.c. output:

— it shall not exceed the limits established in IEC 62040-2, for UPS over 100 A. For smaller
UPS, it is allowed an increase of + 14 dB in values indicated in IEC 62040-2;
— these limits are only applied to UPS in which the output cable length may exceed 10 m.

39
-PUBLIC-

N-2760 REV. A ENGLISH 11 / 2012

A.2.8.2.2.3 Electromagnetic Emission:

— shall not exceed the limits established in IEC 62040-2;


— measurement methods shall be those established in IEC 62040-2.

A.2.8.3 Immunity (Electromagnetic Susceptibility)

A.2.8.3.1 Test Condition

Tests shall be performed with the UPS in the following conditions:

— rated input voltage;


— operations in normal mode;
— linear load in rated output power.

A.2.8.3.2 Acceptance Criterion

The UPS comply with criteria established in IEC 62040-2.

A.2.9 Synchronization Tests

A.2.9.1 Synchronization Time (IEC 62040-3)

A.2.9.1.1 Test Condition

Synchronization time is the time the inverter takes to synchronize with the alternative source. The test
shall be performed with inverter on, alternative source off, and with frequency and voltage within the
acceptable limits (voltage ± 10 % and frequency ± 5 %). Start timing from the moment the alternative
source is switched on until it synchronizes. Perform the reverse operation, that is, with alternative
source on and inverter off, and start timing the synchronism from the switching on command to
inverter.

NOTE Ten tests shall be performed and the longest time shall be considered.

A.2.9.1.2 Measurements and Checks

Output voltage and frequency of inverter and by-pass.

A.2.9.1.3 Acceptance Criterion

Maximum value = 30 s.

A.2.9.2 Phase Angle (IEC 62040-3)

A.2.9.2.1 Test Condition

Phase angle is the phase difference in degrees between the inverter output and the alternative input.
The test shall be performed with load in output from zero until the rated active power. The UPS shall
be operating through the inverter, synchronized with the alternative source.

40
-PUBLIC-

N-2760 REV. A ENGLISH 11 / 2012

A.2.9.2.2 Measurements and Checks

Oscillographic record of alternative input and UPS output voltages.

A.2.9.2.3 Acceptance Criterion

Maximum value = 8° (considering output voltage maximum tolerance of ± 1 %)

A.2.9.3 Variation in Alternative Source Frequency (IEC 62040-3)

A.2.9.3.1 Test Conditions

A.2.9.3.1.1 The inverter shall be able to keep itself synchronized within a variation rate of alternative
source. The variation limits of alternative source so that the inverter is kept synchronized shall be
comprised within the admissible frequency range of Brazilian electric system (frequency statism).

A.2.9.3.1.2 The value used is ± 5%, therefore, the limits or working range shall be comprised in ±
3 Hz. The variation rate so that the inverter is kept in synchronism shall be defined by the
manufacturer. Estimated value 1 Hz/s.

A.2.9.3.2 Measurements and Checks

A.2.9.3.2.1 Oscillographic record of alternative input and UPS output voltages.

A.2.9.3.2.2 Output voltage frequency.

A.2.9.3.3 Acceptance Criterion

The UPS shall remain synchronized with the by-pass during test.

NOTE The tests above shall be performed with assistance of a variable frequency generator
connected to the alternative voltage input of UPS.

A.2.10 Failure Simulation in UPS in Parallel Redundancy (IEC 62040-3)

A.2.10.1 Failure in One of Redundant Parallel System Units

A.2.10.1.1 Test Condition

A.2.10.1.1.1 This test aims at observing the transients (voltage and frequency) in output waveform at
the moment one of the redundant parallel system units fails. Low and high impedance defects shall be
simulated, as per IEC 62040-3. Perform this test with rated apparent load of UPS.

A.2.10.1.1.2 The test shall be performed with rated active load applied to the UPSs.

A.2.10.1.1.3 Power System Test: Remove the control signal from one semiconductors of the inverter
bridge.

41
-PUBLIC-

N-2760 REV. A ENGLISH 11 / 2012

A.2.10.1.1.4. Control System Test: Actuate the temperature sensor of the inverter bridge.

A.2.10.1.2 Measurements and Checks

— oscillographic record of UPS output voltage and frequency;


— check of UPS alarms.

A.2.10.1.3 Acceptance Criterion

A.2.10.1.3.1 The voltage or frequency variation shall be within the defined static and dynamic
calibration range.

A.2.10.1.3.2 The unit(s) without inserted defect shall take the load, while the unit with inserted
defect shall be inhibited, informing the inserted defect by the alarms.

A.2.10.1.3.3 The alarm shall characterize the inserted defect correctly.

A.2.10.1.3.4 There shall be no actuation of static switch.

A.2.10.2 Shutdown of One of Redundant Parallel System Units

A.6.1.1 Test Condition

This test is similar to the previous case (A.2.10.1), however, the simulation shall be performed by
shutting down the redundant parallel system units. The test shall be performed with rated active load
applied to the UPSs.

A.2.10.2.2 Measurements and Checks

A.2.10.2.2.1 Oscillographic record of UPS output voltage and frequency.

A.2.10.2.2.2 Check of UPS alarms.

A.2.10.2.3 Acceptance Criterion

A.2.10.2.3.1 The voltage or frequency variation shall be within the defined static and dynamic
calibration range.

A.2.10.2.3.2 The remaining unit(s) shall take the load, while the unit that was shut down shall
inform the inserted defect by the alarms.

A.2.10.2.3.3 The alarm shall characterize the inserted defect correctly.

A.2.10.2.3.4 There shall be no actuation of static switch.

42
-PUBLIC-

N-2760 REV. A ENGLISH 11 / 2012

A.2.11 Transfer Test (IEC 62040-3)

A.2.11.1 Operation in Synchronism with Alternative Source - Manual Operation to Transfer

A.2.11.1.1 Test Condition

With the output fed by inverter branch, perform the transfer to by-pass through the manual command
switch. The static switch shall switch to by-pass. This test shall be performed in 10 points, considering
the two most critical points. Perform this test for 0 %, 50 % and 100 % of rated linear load of UPS.

A.2.11.1.2 Measurements and Checks

Oscillographic record of UPS output voltage and frequency.

A.2.11.1.3 Acceptance Criteria

A.2.11.1.3.1 No frequency variation shall be observed in output waveform within the established
limits.

A.2.11.1.3.2 Tolerance: variations under 1 regarding the fundamental sinusoidal signal and
observed (transient) variations under 10 % of the real value at the moment of switching.

A.2.11.1.3.3 No test of this item shall have interruption of output voltage above 4 ms.

A.2.11.2 Operation in Synchronism with Alternative Source - Automatic Operation to Transfer

A.2.11.2.1 Test Condition

With the output fed by inverter branch, perform the transfer to by-pass through total shut down of
inverter. A way to perform this test is by shutting down the battery circuit breakers, and then turning off
the rectifier. This test shall be performed in 10 points, considering the two most critical points. Perform
this test for 0 %, 50 % and 100 % of rated linear load of UPS.

A.2.11.2.2 Measurements and Checks

Oscillographic record of UPS output voltage and frequency.

A.2.11.2.3 Acceptance Criteria

There shall be no interruption of output voltage above 4 ms.

A.2.11.3 Operation out of Synchronism with Alternative Source - Manual Operation to Transfer

A.2.11.3.1 Test Condition

A.2.11.3.1.1 With the UPS feeding the loads by the inverter branch, try to perform the manual transfer
of static switch to by-pass.

43
-PUBLIC-

N-2760 REV. A ENGLISH 11 / 2012

A.2.11.3.1.2 In laboratory, this test shall be performed by varying the by-pass frequency out of
operational range of UPS.

A.2.11.3.1.3 The test shall be performed with rated active load applied to the UPS.

A.2.11.3.2 Measurements and Checks

Oscillographic record of UPS output voltage and frequency.

A.2.11.3.3 Acceptance Criteria

The UPS shall not allow this transfer.

A.2.11.4 Operation Out of Synchronism with Alternative Source – Automatic Operation to


Transfer

A.2.11.4.1 Test Condition

A.2.11.4.1.1 Loads shall be operating by the inverter branch and without synchronism between
inverter and by-pass. The test shall be performed by causing a failure in inverter branch (the battery
shall be turned off, followed by the rectifier).

A.2.11.4.1.2 The test shall be performed with reference rated active load.

A.2.11.4.2 Measurements and Checks

Oscillographic record of UPS output voltage and frequency.

A.2.11.4.3 Acceptance Criteria

The transfer shall take place in a specific time of 1 cycle (16,66 ms). This time is required so that
the DC component of consumer circuits decreases to a low value in module and, even in the worst
situation (180 º) of phase difference between inverter and alternative source, the switching shall not
generate degrees of current high enough to turn off protections of critical feeding switchboards.

NOTE UPS feeding motor loads, the dead time for switching the static switch out of synchronism
shall be specified as a function of X/R variable of the system.

A.2.12 Division of Current in Parallel or Redundant Parallel (IEC 62040-3)

A.2.12.1 Test Condition

A.2.12.1.1 It shall preferably use load division by current.

A.2.12.1.2 Perform the test in each phase and in all balanced phases, with 100 % of rated active load,
and repeat with non-linear loads.

44
-PUBLIC-

N-2760 REV. A ENGLISH 11 / 2012

A.2.12.1.3 The Test comprises 3 steps:

a) 1st step: with all modules in parallel, observe if the current is unbalanced;
b) 2nd step: turn off 1 or more modules (preferably the master, as the case may be) and
observe if the current is divided among the others;
c) 3rd step: return the module to operation, and observe if the division returned to the
previous condition.

NOTE Request the maximum values of unbalance in worst conditions with linear and non-linear
load.

A.2.12.2 Measurements and Checks

With a oscillograph, record the currents and voltages in all modules each time a module is turned off
and on.

A.2.12.3 Acceptance Criteria

The unbalance of current between modules shall be lower than 5 %.

A.2.13 Test of Ripple (residual wave) Current in Battery (IEC 62040-3)

A.2.13.1 Test Condition

The test shall be performed with rated active load applied to the UPS, with stabilized internal
temperature and disconnected battery. In three-phase UPS, the phases shall operate with 100 %
unbalanced loads.

A.2.13.2 Measurements and Checks:

Voltage, current and ripple in direct current bar.

A.2.13.3 Acceptance Criterion

A.2.13.3.1 The output voltage ripple of the rectified shall not exceed effective 1 % with
disconnected battery.

A.2.13.3.2 The current ripple shall not exceed 5 % with connected battery of same internal
impedance value of the original equipment for the specified capacity.

A.2.14 Harmonic Components Test (IEC 62040-3)

A.2.14.1 Test Conditions

A.2.14.1.1 The test shall be performed with linear rated load applied to the UPS.

A.2.14.1.2 The AC input power supply shall be within the specified limits.

45
-PUBLIC-

N-2760 REV. A ENGLISH 11 / 2012

A.2.14.2 Measurements and Checks

A.2.14.2.1 Input Voltage and Current

A.2.14.2.2 Individual Harmonics and Input Current THD.

A.2.14.3 Acceptance Criterion

As per criteria established in IEC 62040-3.

A.2.15 Temperature Rise Test

A.2.15.1 Test Condition

The temperature rise test of the UPS shall be performed in the most critical condition to the
equipment. The UPS-CC to be tested shall have its temperature stabilized. AC input for the rectifier
shall be in the minimum value within the admissible range of normal operation of the rectifier. The
DC busbar voltage shall be in the minimum operating limit of inverter (final discharge voltage of
each rectifier element times the number of elements). The test shall be performed with linear rated
load applied to the UPS.

A.2.15.2 Measurements and Checks

The output voltage shall remain within the admissible range of normal operation, as specified.
Temperature conditions of UPS cabinets shall be monitored. All critical components of UPS (inverter
bridge, transformers, power supply electrolytic capacitors, rectifier bridge, etc.) shall be monitored.

A.2.15.3 Acceptance Criterion

The internal temperature rise of electronic components, added to the ambient temperature of
40 °C, shall not exceed 80 % of its industrial line tolerance range used by the manufacturer.

A.2.16 Static Switch Test

A.2.16.1 Overload Tests (IEC 62040-3)

A.2.16.1.1 Test Condition

— apply 125 % rated current overload;


— apply 200 % rated current overload for 30 s;
— apply 1 000 % rated current overload for a period of 100 ms.

A.2.16.1.2 Measurements and Checks

Oscillographic record of output voltage and current.

A.2.16.1.1.3 Acceptance Criterion

The static switch shall not have any damage, nor equipment shutdown due to overheating.

46
-PUBLIC-

N-2760 REV. A ENGLISH 11 / 2012

A.2.16.2 Overvoltage Tests (IEC 62040-3)

Perform test as established in IEC 62040-3.

A.2.17 Environmental Tests (IEC 62040-3)

Storage and operating tests under adverse weather conditions (cold, moist heat, dry heat, etc.) shall
be performed as per IEC 62040-3.

A.2.18 Vibration and Shock Test (IEC 62040-3)

A.2.18.1 Shock Test (IEC 62040-3)

A.2.18.1.1 Test Condition

Before the test, the electrical characteristics of UPS shall be checked. During the test performance,
the UPS shall not be operating. The UPS shall be subjected to two shock pulses of half sine of 15 g,
with nominal duration of 11 ms, in the three plans. The test method indicated in IEC 60068-2-27 shall
be followed. No measurement shall be done during test.

A.2.18.1.2 Measurements and Checks

Perform new electrical measurements as per IEC 62040-3. Check for physical damage and distortion
of component parts.

A.2.18.1.3 Acceptance Criterion

Measurements shall be the same checked before testing.

A.2.18.2 Free Drop Test (IEC 62040-3)

This test shall be performed as described in IEC 62040-3.

A.2.18.3 Vibration and Shock Test of Connectors (IEC 60068-2-6 and 60068-2-27)

A.2.18.3.1 Test Condition

All connectors used in all equipment items comprising the power supply critical systems shall
comply with the tests, in accordance with IEC 60068-2-6 for sinusoidal vibration test, and with IEC
60068-2-27 for shock test. The equipment manufacturer shall supply the test report of used
connectors. When the report is issued by a third-party laboratory, this shall be registered in the
official bodies of the country of origin. If the report is issued by the manufacturer itself,
PETROBRAS shall perform an initial inspection to authorize the supplying of the given connectors.
Parameters for the tests above are described on Tables A.2 and A.3.

47
-PUBLIC-

N-2760 REV. A ENGLISH 11 / 2012

Table A.2 - Sinusoidal Vibration Test - IEC 60068-2-6

Frequency Range 5 Hz to 150 Hz


Cross-Over Frequency 25 Hz
Displacement amplitude below
2 mm
cross-over frequency
Acceleration amplitude above
5g
cross-over frequency
Axes X, Y, Z
Length of the test 2 hours in each axis

Table A.3 - Shock Test - IEC 60068-2-27

Pulse form Half-wave


Peak acceleration 5g
Corresponding length of
50 ms
rated pulse
Number of shocks in each of
3
the six directions
X, Y, Z (positive and
Axis
negative)

A.2.18.3.2 Measurements and Checks

A.2.18.3.2.1 Measure contact resistance before and after testing.

A.2.18.3.2.2 Monitor the opening of contacts during the test.

A.2.18.3.3 Acceptance Criterion

After performing the tests, the contact resistance shall be under 150 % of the resistance measured
before testing. There shall be no opening of contacts above 1 μs.

A.2.19 Audible Noise (IEC 62040-3 and ISO 7779)

A.2.19.1 Test Condition

A.2.19.1.1 Measurements shall be performed in normal and stored energy operation modes, and
values shall be determined in acoustic decibels (dBA) 1 meter far from the equipment. The
measurement shall be done with normal input voltage and rated linear load in permanent condition.

A.2.19.1.2 In equipment items with automatic fans, the fans shall be turned on. Sound alarms shall
not be considered in measurement. The measurement method specified in ISO 7779 shall be
used, considering the equipment use position.

A.2.19.2 Acceptance Criterion

UPS acoustic noise level under 75 dBA.

48
No.
DATA SHEET
CLIENT: SHEET
of
JOB:

AREA:

TITLE:
UNINTERRUPTIBLE POWER SYSTEM FOR
INDUSTRIAL USE

INDEX OF REVISIONS

REV. DESCRIPTION AND/OR REVISED SHEETS

REV. 0 REV. A REV. B REV. C REV. D REV. E REV. F REV. G REV. H


DATE
DESIGN
EXECUTION
CHECK
APPROVAL
INFORMATION IN THIS DOCUMENT IS PROPERTY OF PETROBRAS, BEING PROHIBITED OUTSIDE OF THEIR PURPOSE.
FORM OWNED TO PETROBRAS N-2760 REV. A ANNEX B - SHEET 01/05.
No. REV.
DATA SHEET
SHEET
of
TITLE:
UNINTERRUPTIBLE POWER SYSTEM FOR
INDUSTRIAL USE
1 TAG 7.2 RATED CURRENT (DC)
2 SETUP 7.3 FLUCTUATION VOLTAGE V
2.1 SIMPLE ⃞ 7.4 RECHARGE VOLTAGE V
2.2 REDUNDANT ⃞ N= +R= RIPPLE
7.5
2.3 COMMON BY-PASS DISCONNECTED BATTERY %
3 ENVIRONMENTAL CHARACTERISTICS 7.6 NUMBER OF PULSES
3.1 INSTALLATION 7.7 DE-PHASING TRANSFORMER YES
AMBIENT TEMPERATURE RANGE 7.0 TOTAL HARMONIC DISTORTION OF CURRENT (THDi) %
3.2
0 °C - 40 °C □ °C - - °C 7.9 RECTIFIER INPUT INRUSH CURRENT
3.3 ALTITUDE: > 1000 m 8 INVERTER CHARACTERISTICS
3.4 PROXIMITY TO SEA YES 8.1 No. OF PHASES
3.5 AREA CLASSIFICATION NO 8.2 INPUT RATED VOLTAGE (DC) V
3.6 ZONE GROUP TEMP. CLASS 8.3 RATED CURRENT (AC) V
4 MAIN SOURCE 8.4 OUTPUT FREQUENCY Hz
4.1 VOLTAGE 480 V 8.5 OUTPUT RATED VOLTAGE (AC) V
4.2 TOLERANCE + % - % 8.6 OUTPUT VOLTAGE ADJUSTMENT
4.3 No. OF PHASES 8.7 VOLTAGE STATIC REGULATION TENSÃO (0 % - 100 % LOAD) %
4.4 No. OF WIRES VOLTAGE DYNAMIC REGULATION
8.8
4.5 SYMMETRIC SHORT-CIRCUIT CURRENT kA WITH 100 % LOAD %
4.6 FREQUENCY Hz DYNAMIC RECOVERY TIME
8.9
4.7 TOLERANCE +/- % WITH 100 % LOAD ms
4.8 GROUNDING SYSTEM SUBSTANTIALLY GROUNDED FREQUENCY REGULATION
5 ALTERNATIVE SOURCE 8.10 SYNCHRONIZED WITH ALTERNATIVE SOURCE Hz
5.1 VOLTAGE V INTERNAL OSCILLATOR Hz
5.2 TOLERANCE + % - % 8.11 TOTAL HARMONIC DISTORTION OF VOLTAGE (THD v ) %
5.3 No. OF PHASES 0.12 UNDER ADMISSIBLE RECHARGE %
5.4 No. OF WIRES 9 CHARACTERISTICS OF ALTERNATIVE SOURCE TRANSFORMER

5.5 SYMMETRIC SHORT-CIRCUIT CURRENT kA 9.1 POWER kVA


5.6 FREQUENCY Hz 9.2 VOLTAGE V
5.7 TOLERANCE +/- Hz 9.3 No. OF PHASES
5.8 GROUNDING SYSTEM SUBSTANTIALLY GROUNDED 9.4 FREQUENCY Hz
6 LOAD CHARACTERISTICS 9.5 EFFICIENCY
6.1 TYPE 9.6 IMPEDANCE
6.2 VOLTAGE V 9.7 INSULATION CLASS
6.3 TOLERANCE + % - % 9.8 TERMINALS
6.4 No. OF PHASES 9.9 TAPS
6.5 FREQUENCY Hz 10 STATIC SWITCH
6.6 RATED POWER kVA 10.1 RATED VOLTAGE V
6.7 POWER FACTOR 10.2 FREQUENCY Hz
6.8 PEAK FACTOR 10.3 RATED POWER kVA
6.9 AUTONOMY h OVERLOAD CAPACITY
CONTINUOUS UNTIL
7 RECTIFIER/CHARGER CHARACTERISTICS
30 s %
10.4
UNTIL
7.1 RATED VOLTAGE (DC)
100 ms %
MAXIMUM TIME FOR SWITCHING TO BY-PASS ms

INFORMATION IN THIS DOCUMENT IS PROPERTY OF PETROBRAS, BEING PROHIBITED OUTSIDE OF THEIR PURPOSE.
FORM OWNED TO PETROBRAS N-2760 REV. A ANNEX B - SHEET 02/05.
No. REV.
DATA SHEET
SHEET
of
TITLE:
UNINTERRUPTIBLE POWER SYSTEM FOR
INDUSTRIAL USE
LIFECYCLE (NUMBERS OF TRIPS) 13.12 DIGITAL INPUT FOR BATTERY RECHARGE INHIBITION YES
V 14 LOCAL SIGNALING AND ALARM
10.5
A 14.1 UPS ON YES
FULLY DISCHARGED kVA 14 2 BATTERY DISCHARGING YES
11 ASSEMBLY CHARACTERISTICS 14.3 BATTERY ON FLOAT CHARGE YES
11.1 MAXIMUM OUTPUT POWER kVA 14 4 LOAD FED BY ALTERNATIVE SOURCE YES
EFFICIENCY ACCORDING TO DEFINED POWER FACTOR 14.5 ABNORMAL VOLTAGE IN MAIN SOURCE YES
100% LOAD % 14.6 ABNORMAL VOLTAGE IN AC SAFE BUSBAR YES
11.2
75 % LOAD % 14.7 ABNORMAL VOLTAGE IN BATTERY YES
50 % LOAD % 14.8 SYNCHRONISM UNDER ABNORMAL CONDITION YES
11.3 NOISE LEVEL d BA 15 COMMUNICATION
MTBF h MTTR
11.4 15.1 PHYSICAL LEVEL
h
THERMAL DISSIPATION 15.2 LINK
11.5 50 % OF LOAD kW 16 ACCESSORIES
100 % OF LOAD kW 16.1 TERMINAL FOR AC INLET CABLE mm2
12 CONSTRUCTIVE CHARACTERISTICS TERMINAL FOR CABLE IN OUTPUT
12.1 DEGREE OF PROTECTION IP 2 1 16.2 BATTERY (DC) mm2
12.2 DEGREE OF PROTECTION Ex- CONSUMER (AC) mm2
12.3 UPPER CABLE INLET/OUTLET TERMINAL FOR HOUSING GROUND
12.4 PAINTING 16.3 NOMINAL SECTION mm2
12.5 EXTERNAL FINISHING COLOR INTERNAL
12.6 REMOVABLE PLATES IN BACK PART YES HEATING RESISTOR YES
12.7 WEIGHT kg 16.4 POWER W
SIZE VOLTAGE V
HEIGHT m 16.5 SUPPORT FOR FLOOR ATTACHMENT YES
12.8
WIDTH m 16.6 ANCHOR BOLT YES
DEPTH m 16.7 LIFTING LOOP YES
12.9 REPLACEMENT OF FANS NO INTERRUPTION 16.8 MONITOR OF EARTH LEAKAGE IN DC LINK NO
13 DEVICES 17 LOAD DISTRIBUTION PANEL NO
TRANSFER SWITCH FOR MAINTENANCE YES 17.1 MONITOR OF EARTH LEAKAGE IN SAFE BUSBAR NO
13.1
MAKE BEFORE BREAK TYPE WITH TEST POSITION 18 LIST OF SUPPLY OF SIMILAR EQUIPMENT NO
INSULATING TRANSFORMER IN MAIN SOURCE INLET APPLICABLE STANDARDIZATION PETROBRAS
YES ENTITIES STANDARD NUMBER
13.2
TYPE: DESIGN/FABRIC. TESTS
19
INSULATION CLASS: PETROBRAS N-2760 PETROBRAS
13.3 VOLTMETER AT CONSUMER BAR NO
13.4 AMMETER AT OUTPUT FOR CONSUMERS NO
13.5 VOLTMETER AT MAIN SOURCE INPUTS NO LIST OF TESTS OF STANDARD PETROBRAS N-2760 YES
20 NOTE: CHECK NO TO ESTABLISH TESTS
13.6 AMMETER AT MAIN SOURCE INPUTS NO AS PER ITEM 22 OF DATA SHEET
13.7 AMMETER AT RECTIFIER OUTPUT NO
13.8 VOLTMETER AT DC LINK NO
13.9 AMMETER AT INPUT FOR BATTERY NO
13.1
VOLTMETER AT ALTERNATIVE SOURCE INPUT NO
0
13.1
AMMETER AT ALTERNATIVE SOURCE INPUT NO
1

INFORMATION IN THIS DOCUMENT IS PROPERTY OF PETROBRAS, BEING PROHIBITED OUTSIDE OF THEIR PURPOSE.
FORM OWNED TO PETROBRAS N-2760 REV. A ANNEX B - SHEET 03/05.
No. REV.
DATA SHEET
SHEET
of
TITLE:
UNINTERRUPTIBLE POWER SYSTEM FOR
INDUSTRIAL USE
General Notes
1-
2-
3-
4-
5-
6-
7-
21 8-
9-
10-
11-
12-
13-
14-
15-
List of minimum tests to be performed / evidenced
Test description TYPE TAF TAC
Preliminary tests
Control and monitoring signals
Check of interconnection cables
Test of UPS auxiliary devices
Light load test
UPS input feed tests
AC input voltage tolerance in permanent condition
Input voltage frequency variation
Inrush current
UPS output characteristics - static condition
Output - normal mode - no load
Output - normal mode - rated load
Output - stored energy mode - no load
Output - stored energy mode - rated load
Unbalanced output voltage test
Output voltage dc component and zero sequence
Output - normal operation mode - overload
22
Output - stored energy operation mode - overload
Reference non-linear load charge output distortion – normal mode and stored energy mode
Short-circuit
Short-circuit - no transfer to static switch and no short-circuit elimination
Short-circuit - with transfer to static switch and with short-circuit elimination
UPS output dynamic tests
Linear loads
Non-linear loads
Stored energy and restored energy tests
Restored energy time at 90% of capacity
Input efficiency and power factor
Emission, radio frequency interference supportability and conducted noise tests
Emission
Immunity (electromagnetic susceptibility)
Synchronization tests
Synchronization time
Phase angle
Variation in alternative source frequency
INFORMATION IN THIS DOCUMENT IS PROPERTY OF PETROBRAS, BEING PROHIBITED OUTSIDE OF THEIR PURPOSE.
FORM OWNED TO PETROBRAS N-2760 REV. A ANNEX B - SHEET 04/05.
No. REV.
DATA SHEET
SHEET
of
TITLE:
UNINTERRUPTIBLE POWER SYSTEM FOR
INDUSTRIAL USE
General Notes
List of minimum tests to be performed / evidenced
Test description TYPE TAF TAC
Failure simulation in UPS in parallel redundancy
Failure in one of redundant parallel system units
Shutdown of one of redundant parallel system units
Transfer test
Operation in synchronism with alternative source - manual operation to transfer
Operation in synchronism with alternative source - automatic operation to transfer
Operation out of synchronism with alternative source - manual operation to transfer
Operation out of synchronism with alternative source - automatic operation to transfer
Other tests
Division of current in parallel or redundant parallel
Test of ripple (residual wave) current in battery
22.
Harmonic components test
Temperature rise test
By-pass switch test
Overload tests
Overvoltage tests
Non-electrical tests
Environmental tests
Vibration and shock test
Shock test
Free drop test
Connector vibration and shock test
Audible noise

INFORMATION IN THIS DOCUMENT IS PROPERTY OF PETROBRAS, BEING PROHIBITED OUTSIDE OF THEIR PURPOSE.
FORM OWNED TO PETROBRAS N-2760 REV. A ANNEX B - SHEET 05/05.
-PUBLIC-

N-2760 REV. A ENGLISH 11 / 2012

INDEX OF REVISIONS

REV. A
Affected Parts Description of Alteration

All Revised

IR 1/1

You might also like