PCS 9705

Download as pdf or txt
Download as pdf or txt
You are on page 1of 3

PCS-9705

Bay Control Unit (BCU)

Functions
Measurements of current, voltage, frequency, harmonic (up
to 15th), power factor, active/reactive power and energy
Remote/local control of circuit breakers, isolators and earth
switch

The PCS-9705 bay control unit is a flexible, easy-to-use


control unit used for measuring, monitoring and control
of various bays with different voltage levels. The modular
architecture, extensive functional library, programmable
logic and configurable I/O are supported to meet specific
application. It can be optimally tailored for various
applications including transmission lines, transformers, circuit
breakers, busbars and reactors. The interlocking logic can
be configured to promote safe operation by preventing nonpermissible switching operations. IEC 61850-8-1 and IEC
60870-5-103 for station bus, IEC61850-9-2 and GOOSE for
process bus are supported.

Monitoring of circuit breaker, isolators and earth switch


Operation counter of circuit breaker
SBO (Select Before Operate) for remote control
Implementation of AGC (Automatic Generator Control)
command (optional)
Programmable Interlocking logic

1 RS-485 communication rear ports for GPS clock


synchronization, supports PPS, IRIG-B, SNP and IEC1588.
1 RS-232 communication rear ports for printer
1 front plate RJ45 port for testing and setting

Synchro-check closing for circuit breakers


Interface to transducer inputs or RTD inputs for temperature
Tap position supervision of transformer
Supervision of busbar VT failure

The relay is designed based on NRs well established and


proven UAPC hardware platform of multi-processor. Multi
CPU modules are adopted in the relay. All CPUs can operate
in parallel.

Tripping circuit supervision


Bay mimic display in large scale LCD
Master tripping lockout
Voltage and current drift auto adjustment
Self diagnostic test
Total 1024 SOE, including alarm, binary input change and
human operation reports
Up to 4 Ethernet ports with IEC 61850-8-1 for station bus
2 optional fiber Ethernet ports for process bus, support
GOOSE and IEC61850-9-2
2 RS-485 communication rear ports conform to IEC 60870-5103 protocol

Model
AC inputs
Binary Inputs
Binary Outputs
Configurable Outputs
DC Inputs(4-20mA,0-5V)
DC Outputs(4-20mA)
Synchro-check
Interlocking Logic
Support to ECVT(optional)
IEC61850 Process Bus(optional)

296

read more on www.nrelect.com

PCS-9705A
5VT/4CT
Up to 140
Up to 25 pairs
Up to 50
Up to 12
Up to 4
1 breaker
Yes
Yes
Yes

Features

All AC quantity inputs can be sampled simultaneously to


ensure the accuracy of analog quantity measurement which
is up to 15th harmonic component.
The BCU provides optional RTD input module and 4-20mA
DC input module for detection of temperature. And optional
4-20mA outputs are provided for AGC implementation.
Software and hardware timing are both adopted with 1ms
timing accuracy to ensure the resolution of sequence of
events.

PCS-9705B
13VT
Up to 140
Up to 15 pairs
Up to 50
Up to 12
Up to 4
0
Yes
Yes
Yes

Read more on the web

www.nrelect.com

PCS-9705C
8VT/7CT
Up to 140
Up to 25 pairs
Up to 50
Up to 12
Up to 4
2 breakers
Yes
Yes
Yes

PCS-9705D
24VT
Up to 120
Up to 25 pairs
Up to 50
Up to 12
Up to 4
0
Yes
Yes
Yes

PCS-9705E
13VT/12CT
Up to 140
Up to 25 pairs
Up to 50
Up to 12
Up to 4
3 breakers
Yes
Yes
Yes

The control circuits adopt many block, permit and verify


facilities, including bay level transverse interlock function based
on network communication so that the security of local and
remote control can be ensured.

The network of equipments adopts 100M optic fiber or twisted


wire Ethernet.
It adopts integral front plate and plug-in module structure. High
and low voltage circuits are separated strictly which enhances
EMC immunity performance.

Large scale LCD provides graph and text man-machineinterface which makes operation and inter-rogation convenient.

Low power consumption and wide ambient temperature range.

Technical data
Power Supply
Standard

IEC 60255-11:2008

Voltage Range

88 to 300 Vdc or 88 to 264 Vac

Permissible AC ripple voltage

15% of the nominal auxiliary voltage


<20W (for conventional substation application)
<25W (for smart substation application)
<25W (for conventional substation application)
<30W (for smart substation application)

Burden

Quiescent condition
Operating condition

Analog Current
Standard
Phase rotation
Nominal frequency (fn)
Nominal range
Accuracy
Rated current (In)
Linear to
continuously
for 10s
for 1s
for half a cycle

Thermal withstand capability


Burden

IEC 60255-27:2005
ABC
50Hz, 60Hz
90% ~ 110% fn
0.2 class
1A
0.05In~2In
2In
12In
30In
75In
< 0.2VA/phase @In

5A

< 0.4VA/phase @In

Analog voltage
Standard
Phase rotation
Nominal frequency (fn)
Nominal range
Rated phase-to-phase voltage (Un)
linear to
Accuracy

IEC 60255-6, IEC60288


ABC
50Hz, 60Hz
90% ~ 110% fn
100~130V
1~130V
0.2 class
130V
200V
250V
< 0.10VA/phase @Un

continuously
10s
1s

Thermal withstand capability


Burden

Transducer Inputs
Standard
Input range
Input resistance
Accuracy

IEC 60255-1:2009
0-20mA
235
0.5 class

0~5V
4.4 k
0.5 class

0~48V
54.2 k
0.5 class

0~250V
248 k
0.5 class

Binary Inputs
Standard
Rated voltage
Rated current
Pickup voltage
Maximum permissive voltage
Withstand

IEC 60255-1:2009
24V
48V
1.2mA
2.4mA
55%~70% of rated voltage
120% rated voltage
2000Vac, 2800Vdc

110V
1.1mA

Read more on the web

www.nrelect.com

125V
1.25mA

220V
2.2mA

250V
2.5mA

read more on www.nrelect.com

297

Resolving time for logic input

<1ms

Binary Outputs
Item
Output mode
Max system voltage

Tripping contact
Potential free contact
380Vac, 250Vdc

Signal contact

Voltage across open contact

1000V RMS for 1 minute


5.0A @ 380Vac
5.0A @ 250Vdc
<8ms
<5ms
6A@3s
15A@0.5s
0.6A @ 48Vdc, L/R=40ms
0.1A @ 110Vdc, L/R=40ms
0.05A @ 220Vdc, L/R=40ms
380V AC
250V DC
1000V RMS for 1minute

1200V RMS for 1 minute


8.0A @ 380Vac
8.0A @ 250Vdc
<10ms
<8ms
10A@3s
20A@0.5s
0.6A @ 48Vdc, L/R=40ms
0.3A @ 110Vdc, L/R=40ms
0.2A @ 220Vdc, L/R=40ms
380V AC
250V DC
1200V RMS for 1 minute

Continuous carry
Pickup time
Drop-off time
Short duration current
Breaking capacity (L/R=40ms)
Maximal working voltage
Test voltage across open contact

380Vac, 250Vdc

Mechanical Specifications
Enclosure dimensions (WHD)
Trepanning dimensions (WH)
Mounting
Protection class
Standard
Front side
Other sides
Rear side, connection terminals
Pollution degree

482.6 177.0 230.2 (unit: mm)


450.0179.0, M6 screw (unit: mm)
Flush mounted
IEC 60255-1:2009
IP40, up to IP51 (Flush mounted)
IP30
IP20
2

Ambient Temperature and Humidity Range


Standard
Operating temperature
Transport and storage temperature range
Permissible humidity
Altitude

IEC 60255-1:2009
-40C to +70C Note: The operating temperature of LCD is -20C ~ +70C
-40C ~ +70C
5% ~ 95%, condensation not permissible
<3000m

Communication Port
- Ethernet Port for RTU/SCADA
Connector type
Transmission rate
Transmission standard
Transmission distance
Protocol
Safety level

RJ-45
100Mbits/s
10Base-T/100Base-TX
<100m
IEC 60870-5-103:1997, DNP 3.0 or IEC 61850
Isolation to ELV level

- Station Level Interface


Characteristic
Optical fiber type
Connector type
Wave length
Transmission distance
Minimum transmission power
Reception sensitivity
Margin

Glass optical fiber


Multi-mode
ST, SC
1310nm
<2000m
-20dBm
-30dBm
Min. +3.0dB

- Process Level Interface


Characteristic
Optical fiber type
Connector type
Wave length
Transmission distance
Minimum transmission power
Reception sensitivity
Margin

Glass optical fiber


Multi-mode
LC
1310nm
<2000m
-20dBm
-30dBm
Min. +3.0dB

- Print Port
298

read more on www.nrelect.com