KYN61-40.5 Metal-Claded Withdrawable Type AC Metal-Enclosed Switchgear
KYN61-40.5 Metal-Claded Withdrawable Type AC Metal-Enclosed Switchgear
KYN61-40.5 Metal-Claded Withdrawable Type AC Metal-Enclosed Switchgear
com
Type Description
Power frequency withstand voltage of auxiliary circuit and control circuit V/1 min 2000
Rated frequency Hz 50
Rated short time withstand current/rated short circuit duration kA/4s 20, 25, 31.5
Technical Parameters of ZN85-40.5 Type Circuit Breaker with Spring Operating Mechanism
(Integrated)
Item Unit Value
Rated voltage kV 40.5
Rated current A 630, 1250, 1600
1min power frequency withstand voltage:
kV 95/110
phase-to-phase, phase-to-earth/across open contacts
Insulation
Lightning impulse withstand voltage (peak):
level kV 185/215
phase-to-phase, phase-to-earth,/across open contacts
Power frequency withstand voltage of auxiliary circuit and control circuit V/1 min 2000
Rated frequency Hz 50
Rated short circuit breaking current kA 20, 25, 31.5
Rated short circuit making current kA 50, 63, 80
Rated peak withstand current kA 50, 63, 80
Rated short time withstand current/rated short circuit duration kA/4s 20, 25, 31.5
Mechanical life times 1000
Closing time ms 50~100
Opening time ms 35~60
Rated operating sequence O-0.3s-CO-180s-CO
Structure
This product is divided into two parts: cabinet and VCB. The cabinet is made of bent steel plate and assembled
with bolts after spraying. According to functional characteristics, it can be divided into four parts: small bus room,
relay instrument room, VCB room, cable room and bus room, each part is separated by a grounded metal
partition. The protection degree of the switchgear enclosure is IP4X; when the VCB room door is opened, the
protection degree is IP2X.
The switchgear has main circuit schemes such as cable inlet and outlet, overhead inlet and outlet, bus connection,
disconnection, voltage transformer, and lightning arrester. The busbar adopts composite insulation, and the
inter-phase and connectors are equipped with insulating sleeves made of flame-retardant materials. The adjacent
cabinets of the main busbar are separated by busbar sleeves, which can effectively prevent the accident from
spreading and play an auxiliary support role for the main busbar. The cable room is equipped with earth switch,
overvoltage protection device, etc.
There is a metal safety shutter in front of the contact box. The upper and lower safety shutter are automatically
opened when the VCB moves from the disconnecting/test position to the working position, and automatically
closed when the VCB moves in the opposite direction, effectively disconnecting from the high voltage. The
interlocking between the main switch, VCB, earth switch and cabinet door adopts mandatory mechanical
interlocking method to meet the "five prevention" functional requirements.
The circuit breaker adopts a screw rod drive propulsion mechanism and an overrunning clutch. The screw rod nut
feed mechanism can be easily operated to move the VCB between the test position and the working position.
With the help of the self-locking property of the screw rod nut, the VCB can be reliably locked in the working
www.ghorit-elec.com
position to prevent the VCB from accident caused by fleeing due to electric power. The overrunning clutch works
when the VCB moves back to the test position and when it reaches the working position. It makes the operating
shaft and the screw shaft automatically disengage and idle, which can prevent misoperation and damage the feed
mechanism. Other VCBs use lever feed mechanism. The test work position is locked by positioning pins.
The overall dimensions of the cabinet are: W×D ×H (mm): 1400×2800×2600
Fuse XRNP-35