KYN61-40.5 Metal-Claded Withdrawable Type AC Metal-Enclosed Switchgear

Download as pdf or txt
Download as pdf or txt
Download as pdf or txt
You are on page 1/ 4

www.ghorit-elec.

com

KYN61-40.5 Metal-Claded Withdrawable Type AC Metal-Enclosed Switchgear


www.ghorit-elec.com
Overview
KYN61-40.5 type metal-claded withdrawable type AC metal-enclosed switchgear (hereinafter referred to as
"switchgear") is mainly characterized by the use of ZN85-40.5 fully insulated vacuum circuit breakers and spring
operating mechanisms in the cabinet, and the cabinet body is assembled by plastic coated steel, which improves
the matching precision of the VCB and the cabinet. The VCB is easy to push and pull out and has strong
interchangeability with beautiful appearance, complete solutions, safe and reliable use.
This product is used in 35kV three-phase AC 50Hz power system. It is used for receiving and distributing electric
energy in power plants, substations and power distribution rooms of industrial and mining enterprises. It has
control, protection and monitoring functions. This product complies with standards: GB3906 "Alternating-current
metal-enclosed switchgear and controlgear for rated voltage above 3.6kV and up to and including 40.5kV", GB/T11022
"Common specifications for high-voltage switchgear and controlgear standards", DL/T404 "Alternating-current
metal-enclosed switchgear and controlgear for rated voltages above 3.6kV and up to and including 40.5kV",
IEC60298 "A.C. metal-enclosed switchgear and controlgear for rated voltages above 1 kV and up to and including
52kV".

Normal Use Conditions


● Ambient air temperature: -15℃~+40℃.
● Humidity conditions:
Daily average relative humidity: ≤95%, daily average water vapor pressure ≤2.2kPa.
The monthly average relative humidity is 90%, and the monthly average water vapor pressure is 1.8kPa.
● Altitude: ≤4000m.
● Earthquake intensity: ≤8 degrees.
● The surrounding air should not be contaminated by corrosive or combustible gas, water vapor, etc.
● Places without frequent severe vibration.

Type Description

Main Technical Parameters


Item Unit Value

Rated voltage kV 40.5

Rated current of main bus A 630, 1250, 1600


Rated current
Rated current of equipped circuit breaker A 630, 1250, 1600

1min power frequency withstand voltage:

phase-to-phase, phase-to-earth/across open contacts kV 95/110

Insulation level Lightning impulse withstand voltage (peak):

phase-to-phase, phase-to-earth,/across open contacts kV 185/215

Power frequency withstand voltage of auxiliary circuit and control circuit V/1 min 2000

Rated frequency Hz 50

Rated short circuit breaking current kA 20, 25, 31.5

Rated short time withstand current/rated short circuit duration kA/4s 20, 25, 31.5

Rated peak withstand current kA 50, 63, 80


www.ghorit-elec.com
Rated short circuit making current kA 50, 63, 80

Rated voltage of control circuit V DC110/220, AC110/220

Protection Switchgear enclosure IP4X

degree Compartment (when the doors are opened) IP2X

Technical Parameters of ZN85-40.5 Type Circuit Breaker with Spring Operating Mechanism
(Integrated)
Item Unit Value
Rated voltage kV 40.5
Rated current A 630, 1250, 1600
1min power frequency withstand voltage:
kV 95/110
phase-to-phase, phase-to-earth/across open contacts
Insulation
Lightning impulse withstand voltage (peak):
level kV 185/215
phase-to-phase, phase-to-earth,/across open contacts
Power frequency withstand voltage of auxiliary circuit and control circuit V/1 min 2000
Rated frequency Hz 50
Rated short circuit breaking current kA 20, 25, 31.5
Rated short circuit making current kA 50, 63, 80
Rated peak withstand current kA 50, 63, 80
Rated short time withstand current/rated short circuit duration kA/4s 20, 25, 31.5
Mechanical life times 1000
Closing time ms 50~100
Opening time ms 35~60
Rated operating sequence O-0.3s-CO-180s-CO

Structure
This product is divided into two parts: cabinet and VCB. The cabinet is made of bent steel plate and assembled
with bolts after spraying. According to functional characteristics, it can be divided into four parts: small bus room,
relay instrument room, VCB room, cable room and bus room, each part is separated by a grounded metal
partition. The protection degree of the switchgear enclosure is IP4X; when the VCB room door is opened, the
protection degree is IP2X.
The switchgear has main circuit schemes such as cable inlet and outlet, overhead inlet and outlet, bus connection,
disconnection, voltage transformer, and lightning arrester. The busbar adopts composite insulation, and the
inter-phase and connectors are equipped with insulating sleeves made of flame-retardant materials. The adjacent
cabinets of the main busbar are separated by busbar sleeves, which can effectively prevent the accident from
spreading and play an auxiliary support role for the main busbar. The cable room is equipped with earth switch,
overvoltage protection device, etc.
There is a metal safety shutter in front of the contact box. The upper and lower safety shutter are automatically
opened when the VCB moves from the disconnecting/test position to the working position, and automatically
closed when the VCB moves in the opposite direction, effectively disconnecting from the high voltage. The
interlocking between the main switch, VCB, earth switch and cabinet door adopts mandatory mechanical
interlocking method to meet the "five prevention" functional requirements.
The circuit breaker adopts a screw rod drive propulsion mechanism and an overrunning clutch. The screw rod nut
feed mechanism can be easily operated to move the VCB between the test position and the working position.
With the help of the self-locking property of the screw rod nut, the VCB can be reliably locked in the working
www.ghorit-elec.com
position to prevent the VCB from accident caused by fleeing due to electric power. The overrunning clutch works
when the VCB moves back to the test position and when it reaches the working position. It makes the operating
shaft and the screw shaft automatically disengage and idle, which can prevent misoperation and damage the feed
mechanism. Other VCBs use lever feed mechanism. The test work position is locked by positioning pins.
The overall dimensions of the cabinet are: W×D ×H (mm): 1400×2800×2600

Main Circuit Scheme Diagrams


Primary scheme NO. 1 2 3 4 5

Main circuit scheme diagram

Vacuum circuit breaker ZN85-40.5 1 1 1 1 1

Current transformerLZZBJ9-35 1—3 1—3 4—6

Voltage transformer JDZ9-35


Main circuit
Arrester HY5WZ2 0 or 3 optional
components
Earth switch JN24-40.5 0-1 optional

Charged display 0-1 optional

Fuse XRNP-35

Power transformer SC9-35

Application Overhead inlet (outlet)