Practical Flow Essentials
Practical Flow Essentials
Practical Flow Essentials
Essentials of
Flow Measurement
A Control Essentials Guide, by the editors of Control
About the Control Essentials Series
The mission of the Control Essentials series is to provide process industry professionals with an up-to-date, top-level understanding of a range of key process automation topics. Our intent is to present essential engineering concepts in a practical, non-commercial fashion, together with a review of the latest technology and marketplace driversall in a form factor well suited for onscreen consumption. Check in at ControlGlobal.com/Essentials for other installments in the series.
The Control Editorial Team
This Control Essentials guide made possible by Brooks Instrument. See page 8 for more information on Brooks full range of flow measurement and control solutions.
Articles
next
Specification Considerations
he basis of good f lowmeter selection is a clear understanding of the requirements of the particular application. Therefore, time should be invested in fully evaluating the nature of the process f luid and of the overall installation. The development of specifications that state the application requirements should be a systematic, step-by-step process. Process conditions and f luid characteristics are of primary importance (table), but one should also consider such intangible factors as technology familiarity of plant personnel, their experience with calibration and maintenance, and spare parts availability at the particular plant site. It is also recommended that the cost of the installation be computed only after taking these steps. One of the most common f low measurement mistakes is the reversal of this sequence: instead of selecting a sensor which will perform properly, an attempt is made to justify the use of a device because it is less expensive. Those inexpensive purchases can be the most costly installations. In applications where products are sold or purchased on the basis of a meter reading, absolute accuracy is critical. In other applications, repeatability may be more important than absolute accuracy. Therefore, it is advisable to establish separately the accuracy and repeatability requirements of each application and to state both in the specifications. If acceptable metering performance can be obtained from two different flowmeter categories and one has no moving parts, select the one without moving parts. Furthermore, if one can obtain the same performance from both a full pipe flowmeter and a point sensor, it is generally advisable to use the flowmeter. The insensitivity of thermal and Coriolis mass flowmeters to density, pressure and viscosity variations also speak to their utility and flexibility.
he calculation of fluid flow rate from the pressure loss across a pipe restriction is among the most well established approaches to industrial flow measurement. The pressure drops generated by a wide variety of geometrical restrictions have been well characterized over the decades, and flow elements come in a wide variety of configurations, each with specific application strengths and weaknesses. By far the most common example is the orifice plate (Figure 1), in which the fluid passes through a precisely machined opening concentric with the inside pipe diameter. The loss in pressure across the orifice allows the volumetric flow rate to be calculated. And, if fluid density is known (or can be calculated from pressure and temperature measurements), a mass flow rate can be inferred. Factors affecting the overall accuracy of these devices include proper installation such as with prescribed lengths of straight pipe (or flow straighteners) upstream and downstream of the device. Erosion of the orifice plate edge over time also can affect accuracy, and the various ancillary components and multiple process penetrations make installation and maintenance of differential pressure devices both expensive and time-consuming. Rotameters, or variable area meters, exploit essentially the same physics as differential pressure meters. But instead of measuring the pressure drop across a fixed obstruction, the force of the flowing fluid moves a float/weight upward in a tapered, vertical tube (Figure 2). The higher the flow rate, the higher the floats equilibrium point. Advantages of the rotameter include its relatively low cost, simplicity, low pressure drop, relatively wide range and linear output. If only local display is needed, no power is required: the position of the float can be seen through a glass or other transparent tube on which readings are etched. Alternatively, the float can be magnetically coupled to a dial indicator, or an electronic transmitter used to send flow rate information to a remote display or supervisory controller.
Figure 1. Orifice plate flowmeters infer volumetric flow rate in a pipe by measuring the difference in static pressure before and after the fluid passes through a concentric circular restriction. Figure 2. Variable area flowmeters, or rotameters, balance the weight of an in-stream float against an upward flow. Knowledge of the tube and float weight and geometry, together with the fluid characteristics, allow calculation of the flow rate.
y their very nature, differential pressure and variable area flowmeters both rely on partially obstructing the flow to be measured in order to produce a measurable effect. Magnetic meters and ultrasonic meters, on the other hand, perform their tasks non-intrusively: they calculate the fluids average velocity by the magnetic field it generates or by its effect on the relative speed of sound, respectively. The magnetic flowmeter, or magmeter, works only with conductive fluids such as aqueous solutions, which explains its widespread use in water and wastewater treatment applications. The magmeter itself consists of a non-magnetic pipe lined with an insulating material. A pair of magnetic coils is situated as shown in Figure 3, and a pair of electrodes penetrates the pipe and its lining. If a conductive fluid flows through the pipe, a voltage proportional to the average fluid velocity is generated across the electrodes. Magmeter electrodes and coils also can packaged in an insertable probe for point detection of fluid velocity. This configuration has the advantage that it can be removed without shutting down the process. Overall accuracy, however, is highly depending on how closely the point velocity measured reflects average flow velocity within the pipe. When a magmeter is provided with a level sensor embedded in the liner, it can even measure flow in partially full pipes. In this design, the magmeter electrodes are located at the bottom of the tube (at approximately 1/10 the pipe diameter) to ensure they remain covered by the fluid. The complementary level sensor allows calculation of the flow area and, in turn, the overall flow rate. Ultrasonic flowmeters measure fluid velocity by measuring the effect a moving fluid has on the speed of sound. Transit-time, or time-of-flight, meters measure the phase shift between upstream and downstream transducers (Figure 4) and are used primarily with clean liquids and gases. Doppler-effect meters, on the other hand, rely on a single transceiver and measure the frequency shift of sound waves reflected from suspended particles or bubbles within the flowing stream. More powerful signal processing algorithms, together with multi-path configurations, have been developed to better characterize the flow profile and improve overall accuracy. In fact, due to their relatively low cost and high accuracy they now represent the fastest growing industrial flowmeter market segment. Custody transfer applications in the hydrocarbon industry are among the technologys strongest growth segments.
Figure 3. The magmeter measures the average velocity of conductive liquids: fluid movement through an applied magnetic field creates a measurable voltage across a pair of electrodes.
Figure 4. Ultrasonic flowmeters measure the effect of a moving fluid on the relative speed of sound wave propagation.
Figure 5. Vortex meters use piezo electric sensors to gauge the frequency of vortices shed from turbulent flow around an in-stream shredder bar.
Figure 6. Turbine meters often employ reluctance or inductance sensors to count rotations of the rotor. Frequency is proportional to volumetric flow rate.
he final two flowmeters in our tour of the major flow measurement technologies are the mass meters, so named primarily because of their relative insensitivity to variations in temperature, pressure and other process conditions that can significantly affect the mass flow rate accuracy calculated from a volumetric device. The Coriolis meter takes advantage of the phenomena that Gustav Coriolis first observed as the tendency of bodies moving on the surface of the earth to drift sideways because of the eastward rotation of the planet -- to the right of the motion in the Northern Hemisphere and to the left of the motion in the Southern Hemisphere. The first commercial Coriolis flowmeters, which first emerged in the 1970s, work by introducing an artificial Coriolis acceleration on a flowing stream. From a practical perspective, when mass flows through a vibrating tube, Coriolis forces will tend to twist the tubing. By measuring the magnitude of displacement cause by this twisting force, the Coriolis meter can directly calculate the mass flow rate through the tube (Figure 7). Thermal mass flowmeters also measure the mass flow rate of gases and liquids directly, by introducing a known amount of heat into the flowing stream and measuring an associated temperature change, or by maintaining a probe at a constant temperature and measuring the energy required to do so (Figure 8). Thermal mass flowmeters often are used in monitoring or controlling mass-related processes such as chemical reactions that depend on the relative masses of unreacted ingredients. One of the key capabilities of thermal mass flowmeters is the accurate measurement of low gas flow rates and low gas velocities. For pilot plant or other low flow applications, thermal mass flowmeters often are packaged as integrated mass flow controllers; a thermal mass flowmeter together with controller and valve are used to maintain a constant mass flow rate.
Figure 8. While many various configurations exist, the thermal mass flowmeter fundamentally relies on the capacity of a moving fluid to transfer heat more heat as mass flow rate increases.
Figure 7. The Coriolis effect predicts that the magnitude of twist induced on vibrating tubes is proportional to the mass flow through them.
Made Possible by
This Control Essentials guide on Flow Instrumentation was made possible by Brooks Instrument, a multi-technology instrumentation company serving a range of demanding markets. Brooks has a proven history of innovation that today includes glass and metal tube variable area meters (rotameters), thermal mass flow controllers and meters from ultra-high purity to industrial grade, and Coriolis mass flow controllers. To learn more about Brooks full range of flow measurement and control solutions, visit BrooksInstrument.com