Smar Tt300ce

Download as pdf or txt
Download as pdf or txt
You are on page 1of 14

0.

02% Single

Basic Accuracy

Unit and Several Options for Sensors and Connections Signal Isolation

Input PID

Control Capability Diagnostics

Advanced Largest

Library of Function Block Execution Capacity FDT/DTM by DD, EDDL, and

Supported

Dual

Channel Backup

Sensor Three

Bus Technology Options

Features
0.02% Accuracy; Built-in thermocouples and RTDs True non-interactive zero and span; Local zero and span adjustment; Remote configuration via Hand-Held Alphanumerical LCD indication; Small and lightweight; Explosion proof and weather proof Intrinsically safe certification; Signal simulation for loop tests;
HART - 4 to 20 mA housing approved (IP66/68 ou IP66/68W); Terminal or via PC; linearization;

Signal isolation; Configurable user unit; Configurable local adjustment; EMC (Electromagnetic Compatibility) Write protection function; Three technology options: Sensor backup*; Universal input
F O U N D AT I O N PROFIBUS PA;
TM

according to IEC 61000-6-2: 1999, IEC 61000-6-4: 1997 and IEC 61326: 2002;

HART, fieldbus, and

accepts several thermocouples, RTDs, mV and Ohm.

Excellent long term stability due to 2-wire,


auto-zero at the input circuit; 4-20 mA output plus direct digital communication;

PID control function; Match sensor (Callendar Van Dusen Maximum,


equation); minimum and average input sensor selection, also working with two sensors simultaneously;

Special 16-point sensor characterization; Update output current in 0.5 s with Improved
1.5 A/bit resolution; performance due to dedicated math coprocessor;

Multidrop operation mode;


FOUNDATIONTM fieldbus

Pt1000 included in sensor list; Setpoint generator function; Supports DTM, DD and EDDL.

Self-diagnosis; Dual channel; 12 mA consumption; 19 different types of function blocks Up to 20 function blocks; Execution of up to 29 external links;
PROFIBUS PA for control strategies and advanced diagnostics;

Dynamic block instantiation improves Fieldbus


interchangeability; Foundation TM registered and ITK (Interoperability Test Kit) approved;

LAS (Link Active Scheduler) capability; MVC (Multivariable Container)


enabled.

Self-diagnosis; Dual channel; 12mA consumption; 2 analog input function blocks;

Integrated to Smar Profibus View and Supports DTM and EDDL; Profile 3.0 improves interchangeability.
Simatic PDM;

Dimensional Drawing

PLUG

ALLOW 150 MM MINIMUM FOR LOCAL ZERO AND SPAN ADJUSTMENT WITH MAGNETIC TOOL.

CONDUIT CONNECTION

COMMUNICATIONS TERMINAL

PLUG

WALL OR PANEL MOUNTING

MOUNTING BRACKET

PIPE 2"

FOR WALL MOUNTING 2 EXPANSION ANCHOR - S8 2 HEXAGON SCREW - 3/16X70 FOR PANEL MOUNTING 2 BOLT AND NUTS - 1/4X30 NOT INCLUDED

Functional Description
TT300 Series offers: 0.02% accuracy; Built-in thermocouples and RTDs linearization; Compact and lightweight; Interchangeable protocols. The Smar TT300 Series is a transmitter mainly intended for measurement of temperature using RTDs or thermocouples. However, it can also accept other sensors with resistance or mV output such as pyrometers, load cells, resistance position indicators, etc. The TT300 Series accepts up to two sensors and may operate in one of the modes below*: Single channel with single sensor measurement; Dual channel with dual sensor measurement (except HART protocol device); Single channel with two sensors (same type) in differential measurement; Single channel with two sensors (same type) in backup measurement; Single channel with two sensors (same type) with maximum, minimum or average signal selection (only HART protocol device). The Smar TT300 Series is a powerful and extremely versatile smart temperature transmitter. The digital technology used in the TT300 Series enables a single device to accept several types of sensors, wide ranges, single or multiple-ended measurement and an easy interface between the field and the control room. It also includes several features which reduce considerably the installation, operation and maintenance costs. The transmitter accepts two channels, i.e., two measurements. It reduces the cost per channel. The TT300 Series is suitable for direct field installation, being weather proof and explosion proof, as well as intrinsically safe, for use in hazardous areas.

* Please consult your Smar representative to check the option availability.

Programming and Diagnostics


TT300Series is available in three different technologies: HART (TT301), FOUNDATIONTM fieldbus (TT302), and PROFIBUS PA (TT303). These instruments can be configured with Smar software and other manufacturer configuration tools. Local adjustment is available in all TT300 Series. It is possible
Local Adjustment

to configure zero and span, setpoint and other control functions using the magnetic tool (SD1). With Smar AssetView, an user-friendly Web Tool, user can access the plant assets anywhere and anytime using an Internet browser. It is designed for management and diagnostics of field devices to ensure reactive, preventive, predictive and proactive maintenance.

HART - TT301
TT301 (HART protocol) can be configured by: Smar CONF401 for Windows; Smar DDCON100 for Windows; Smar HPC301 and HPC401 for several models of Palm; Other manufacturers' configuration tools based on DD (Device Description) or DTM (Device Type Manager), such as AMSTM, FieldCare, PACTwareTM, HHT275, HHT375 and PRM Device Viewer. For management and diagnostics, AssetView ensures continuous information monitoring.

DDCON100 - Configuration Software

HPC401- Configuration Software

FOUNDATION fieldbus - TT302


TT302 utilizes the FOUNDATIONTM fieldbus H1 protocol, an open technology that allows any H1 enabled configuration tool to configure this device. Syscon (System Configuration Tool) is a software tool used to configure, and operate the field devices. Syscon offers efficient and friendly interaction with the user, using Windows. Configuration tools such as AMSTM, FieldCare and HHT375 can configure TT302 devices. DD (Device Description) and CF (Capability File) files can be downloaded at either the Smar or Fieldbus FoundationTM website. TT302 supports complex strategies configuration due to the high capacity and variety of dynamic instantiable function blocks.

PROFIBUS PA - TT303
TT303 (PROFIBUS PA protocol) can be configured using configuring Smar Profibus View, Simatic PDM, FDT (Field Device Tool) and DTM (Device Type Manager) concept tools, such as FieldCare and PACTwareTM. It can also be integrated by any PROFIBUS System using the GSD (General Station Description) file. PROFIBUS PA also has quality and diagnostics information, improving plant management and maintenance.

Smar and SYSTEM302 are trademarks or registered trademarks of Smar Equipamentos Industriais Ltda. in Brazil and/or other countries. Other marks are the properties of their respective owners.

Wiring Connection
HART - TT301
Power Supply

and/or

TT301

For an adequate communication, a minimun load of 250 is required between the configuration tool and the power supply.

HHT based on Palm platform

Laptop

FOUNDATIONTM fieldbus - TT302


Spur Junction Box

Shield Terminator

Junction Box

Shield

Spur

Spur Terminator

Panel Ground

Analog Ground

Panel Ground

Analog Ground

PROFIBUS - TT303
Spur Spur

DP/PA Coupler

Junction Box

Shield Terminator

DP/PA Coupler

Junction Box

Shield

Spur Terminator Panel Analog Ground Ground Spur Spur Panel Analog Ground Ground Terminators Spur Spur

* For some DP/PA couplers, the bus terminator is built-in.

Appli cat i ons


HART - TT301

Power Supply 250 W

HART Interface

Control Room Plant Floor

DCS, computer with CONF401 or DDCON100

TT301 TT301 TT301 TT301

Pyrometer

Load Cell

FOUNDATIONTM fieldbus - TT302


LD302 FY302 TT302

LD302 Process Power Supply + Bus Impedance


D F 5 2 D F 5 3

TT302

D F 5 0

D F 6 2

HSE Link Device BT302 Bus Terminator

BT302 Bus Terminator

FY302

PROFIBUS - TT303
LD303 LD303 Process FY303 TT303

Power Supply
D F 5 2

DF73 TT303

PA

BT302 Bus Terminator

DP

BT302 Bus Terminator

D F 5 0

D F 7 3

Profibus DP Master

FY303

Technical Characteristics
Functional Specifications
Inputs Output and Communication Protocol See table 1, 2 and 3. HART: 2-wire, 4-20 mA according to NAMUR NE43 specification, with super-imposed digital communication (HART Protocol). FOUNDATIONTM fieldbus and PROFIBUS PA: Digital only. Complies with IEC 61158-2: 2000 (H1): 31.25 kbit/s voltage mode, bus powered. HART: 12 to 45 Vdc. FOUNDATIONTM fieldbus and PROFIBUS PA: Bus powered: 9 - 32 Vdc. Quiescent current consumption: 12 mA. 4-digit numerical and 5-character alphanumerical LCD indicator (optional). HART, FOUNDATIONTM fieldbus and PROFIBUS PA: Intrinsic Safety (FM, CSA, NEMKO, EXAM, CEPEL, NEPSI), Explosion Proof (FM, CSA, NEMKO, CEPEL), Dust Ignition Proof (FM), Non-incendive (FM) FOUNDATIONTM fieldbus and PROFIBUS PA: FISCO (FM, CSA, NEMKO, EXAM, CEPEL, NEPSI) and FNICO (FM, CSA, NEMKO, EXAM, CEPEL) Authorized representative in European Community Smar Gmbh-Rheingaustrasse 9-55545 Bad Kreuzanach EMC Directive (89/336/EEC) - Electromagnetic Compatibility The EMC test was performed according to IEC standard: IEC61326:2002. For use only in industrial environment. European Directive Information ATEX Directive (94/9/EC) - Equipment and protective systems intended for use in potentially explosive atmospheres. This product was certified according European Standards at NEMKO and EXAM (former DMT). The certified body for manufacturing quality assessment is EXAM (number 0158). LVD Directive 2006/95/EC - Electrical Equipment designed for use within certain voltage limits According the LVD directive Annex II the equipment under ATEX Electrical equipment for use in an explosive atmosphere directive are excluded from scope from this directive. Zero and Span Adjustments Noninteractive, via local adjustment and digital communication. Detailed diagnostics through communication for all protocols. HART: In case of sensor or circuit failure, the self diagnostics drives the output to 3.6 or 21.0 mA, according to the user's choice and NAMUR NE43 specification. Failure Alarm (Diagnostics) FOUNDATIONTM fieldbus: For sensor circuit failures, events are generated and status is sent to link outputs. Detailed diagnostics are available in the contained parameters. PROFIBUS PA: For sensor or circuit failures, status is sent to link outputs. Detailed diagnostics are available in the contained parameters. Temperature Limits
o -40 oC to 85 C Ambiente: o -40 C to 100 oC Storage: o C Digital Display: -20 oC to 80 o o -40 C to 85 C

Power Supply / Current Consumption Indicator

Hazardous Area Certifications

(-40 to 185 oF) (-40 to 212 F) (-4 to 176 F) (normal operation) (-40 to 185 oF) (without damage)

Technical Characteristics
HART: Performs within specifications in less than 5 seconds after power is applied to the transmitter. FOUNDATIONTM fieldbus and PROFIBUS PA: Performs within specifications in less than 10 seconds after power is applied to the transmitter. HART: By digital communication (HART protocol) using the configuration software CONF401, DDCON100 (for Windows) or HPC301 and HPC401 (for Palm). It can also be configured using DD and FDT/DTM tools, and can be partially configured through local adjustment , since the transmitter is supplied with display. FOUNDATIONTM fieldbus and PROFIBUS PA: Basic configuration may be done using the local adjustment magnetic tool if device is supplied with display. Complete configuration is possible using configuration tools such as Syscon (System Configuration Tool), AMSTM, FieldCare and HHT375. The TT303 can be configured via Smar Profibus View and Simatic PDM using EDDL. 0 to 100% Relative Humidity. User configurable from 0 to 32 seconds (via digital communication).

Turn-on Time

Configuration

Humidity Limits Damping Adjustment

Performance Specifications
Accuracy Digital Stability See tables 1, 2 and 3. 0.1% of reading or 0.1 C (0.18 F), whichever is greater, for 2 years for RTDs; 0.1% of reading or 0.1 C (0.18 F), whichever is greater, for 1 year for thermocouples. For a 10 C variation: mV (-6 to 22 mV), TC (NBS: B, R, S,T): 0.03% of the input milivoltage or 0.002 mV whichever is greater; mV (-10 to 100 mV), TC (NBS: E, J, K, N; DIN: L, U): 0.03% of the input milivoltage or 0.01 mV whichever is greater; Temperature Effect mV (-50 to 500 mV): 0.03% of the input milivoltage or 0.05 mV whichever is greater; Ohm (0 to 100), RTD (GE: Cu10): 0.03% of the input resistence or 0.01 whichever is greater; Ohm (0 to 400), RTD (Edison Curve #7: Ni120; IEC: Pt50, Pt100; JIS: Pt50, Pt100): 0.03% of the input resistence or 0.04 whichever is greater; Ohm (0 to 2000), RTD (IEC: Pt500), RTD (IEC: Pt1000): 0.03% of the input resistence or 0.2 whichever is greater; Power Supply Effect Electromagnetic Interference Effect Electrical Connection 0.005% of calibrated span per volt. Approved according to IEC 61326: 2002. 1/2 - 14 NPT M20 X 1.5 PG 13.5 DIN 1/2 - 14 NPT X 3/4 NPT (316 SST) - with adapter 1/2 - 14 NPT X 3/4 BSP (316 SST) - with adapter 1/2 - 14 NPT X 1/2 BSP (316 SST) - with adapter
Note: Explosion proof approvals do not apply to adapter, only to transmitter.

Technical Characteristics
Physical Specifications
Mounting Approximate Weights Can be attached directly to the sensor. With an optional bracket can be installed on a 2" pipe or fixed on a wall or panel. Without display and mounting bracket: 0.80 kg. Add for digital display: 0.13 kg. Add for mounting bracket: 0.60 kg. HART: PID Control, Alarm and Setpoint Ramp Generator. Control Functions Characteristics (Optional) FOUNDATIONTM fieldbus Function Blocks: Resource, Transducer, Display Transducer, Diagnostic Transducer, Analog Input, PID Control, Enhanced PID Control, Arithmetic, Integrator, Input Selector, Signal Characterizer, Splitter, Analog Alarm, Timer, Lead Lag, Output Selector/Dynamic Limiter, Setpoint Generator and Constant. PROFIBUS PA Function Blocks: Physical Block, Transducer, Display Transducer and Analog Input.
Note: Additional information can be found in the Function Blocks Instruction Manual.

Inputs
2, 3 or 4 wires SENSOR TYPE Cu 10 GE Ni120 Edison Curve #7 Pt50 IEC Pt100 IEC RTD Pt500 IEC Pt1000 IEC Pt50 JIS Pt100 JIS Pt100 MILT Ni120 MILT Pt100 IEC Pt100 GOST Pt50 GOST Cu100 GOST Cu50 GOST B NBS E NBS J NBS K NBS THERMOCOUPLE N NBS R NBS S NBS T NBS L DIN U DIN RANGE C -20 to 250 -50 a 270 -200 to 850 -200 to 850 -200 to 450 -200 to 300 -200 to 600 -200 to 600 -40 a 540 -40 a 205 -200 a 850 -200 a 850 -200 a 850 -50 a 200 -50 a 200 100 to 1800 -100 to 1000 -150 to 750 -200 to 1350 -100 to 1300 0 to 1750 0 to1750 -200 to 400 -200 to 900 -200 to 600 RANGE F -4 a 482 -58 a 518 -328 to 1562 -328 to 1562 -328 to 842 -328 to 572 -328 to 1112 -328 to 1112 -40 a 1000 -40 a 400 -328 a 1562 -328 a 1562 -328 a 1562 -58 a 392 -58 a 392 212 to 3272 -148 to 1832 -238 to 1382 -328 to 2462 -148 to 2372 32 to 3182 32 to 3182 -328 to 752 -328 to 1652 -328 to 1112 MINIMUM SPAN C 50 5 10 10 10 10 10 10 10 5 10 10 10 10 10 50 20 30 60 50 40 40 15 35 50 DIFFERENTIAL

C DIGITAL
ACCURACY* 1.0 0.1 0.25 0.2 0.2 0.2 0.25 0.25 + 0,2 + 0,13 0,2 0,2 0,2 0,15 0,15 0.5** 0.2 0.3 0.6 0.5 0.4 0.4 0.15 0.35 0.5

RANGE C -270 to 270 -320 a 320 -1050 to 1050 -1050 to 1050 NA NA -800 to 800 -800 to 800 -580 a 580 -245 a 245 -1050 a 1050 -1050 a 1050 -1050 a 1050 -350 a 350 -350 a 350 -1700 to 1700 -1100 to 1100 -900 to 900 -1550 to 1550 -1400 to 1400 -1750 to 1750 -1750 to 1750 -600 to 600 -1100 to 1100 -800 to 800

RANGE F -486 to 486 -576 a 576 -1890 to 1890 -1890 to 1890 NA NA -1440 to 1440 -1440 to 1440 -1040 a 1040 -440 a 440 -1890 a 1890 -1890 a 1890 -1890 a 1890 -450 a 450 -450 a 450 -3060 to 3060 -1980 to 1980 -1620 to 1620 -2790 to 2790 -2520 to 2520 -3150 to 3150 -3150 to 3150 -1080 to 1080 -1980 to 1980 -1440 to 1440

MINIMUM SPAN C 50 5 10 10 NA NA 10 10 10 5 10 10 10 10 10 60 20 30 60 50 40 40 15 35 50

C DIGITAL
ACCURACY* 2.0 0.5 1.0 1.0 NA NA 1.0 1.5 + 1,0 + 0,5 + 1,0 + 1,0 + 1,0 + 1,0 + 1,0 1.0** 1.0 0.6 1.2 1.0 2.0 2.0 0.8 0.7 2.5

Table 1 - Sensor Characteristics


SENSOR RANGE mV -6 to 22 mV -10 to 100 -50 to 500 MINIMUM SPAN mV 0.40 2.00 10.00 DIGITAL* ACCURACY % 0.02% or 2 V 0.02% or 10 V 0.02% or 50 V Ohm SENSOR RANGE Ohm 0 to 100 0 to 400 0 to 2000 MINIMUM SPAN Ohm 1 4 20 DIGITAL* ACCURACY % 0.02% or 0.01 Ohm 0.02% or 0.04 Ohm 0.02% or 0.20 Ohm

Table 3 - Ohm Sensor Characteristics Table 2 - mV Sensor Characteristics * Accuracy of value read on display and accessed by communication. The 4-20 mA accuracy is the digital accuracy 0.03%. ** Not applicable for the first 20% of the range (up to 440 C).
NA: Not applicable.

Ordering Code
MODEL TT301 TT302 TT303 TEMPERATURE TRANSMITTER HART & 4 to 20 mA FOUNDATIONTM fieldbus PROFIBUS PA COD. Local Indicator 0 Without Indicator COD. Mounting Bracket A 0 1 With Digital Indicator 1 2 Carbon Steel Bracket 316 SST Bracket 7 Carbon Steel Bracket with 316 SST Fasteners

Flat, 304 SST bracket and 316 SST accessories Without Bracket COD.

Set this code as "1" for TT301 and exclude for the others COD. Electrical Connections 1/2 - 14 NPT (8) 1/2 - 14 NPT X 3/4 NPT (316 SST) - With adapter (9) 1/2 - 14 NPT X 3/4 BSP (316 SST) - With adapter (2) COD. Housing Material (13) (14) H2 H3 Aluminium for saline atmosphere (IPW/TYPEX) (15) 316 SST for saline atmospheres (IPW/TYPEX) (15) I4 EXAM (DMT): Ex-ia I5 CEPEL: Ex-d, Ex-ia I6 Without Certification J1 Blank L4 4-wire LF Differential PID Configuration - (4) With PID (Default) COD. LCD1 Indication - (4) Y3 LCD1: Temperature (Engineering Unit) YU LCD1: According to user notes (1) (7) Y6 LCD2: Temperature (Engineering Unit) YU LCD2: According to user notes (1) (7) P5 Yellow Polyester P8 Without Painting P9 Safety Blue Epoxy - Electrostatic Painting M1 Without PID H4 Copper Free Aluminium (IPW/TYPEX) (15) H0 Aluminum (IP/TYPE) H1 316 SST (IP/TYPE) COD. Identification Plate (12) I1 I2 I3 FM: XP, IS, NI, DI NEMKO: Ex-d, Ex-ia (4) CSA: XP, IS, NI, DI (5) COD. J0 Tag Plate (12) With tag, when specified (Default) COD. Sensor Connection LD Double 2-wire (3) LB Backup J2 According to user's notes IE NEPSI: Ex-ia (3) IF CEPEL: Ex-d (4) IG CEPEL (Ex-d, Ex-ia) +IPW (6) 3 1/2 - 14 NPT X 1/2 BSP (316 SST) - With adapter (2) A M20 x 1.5 (10) B PG 13.5 DIN (11) Z According to users notes

0 1 2

L2 2-wire L3 3-wire COD. M0

Y0 LCD1: Percentage (Default) Y1 LCD1: Current - I (mA) COD. Y0 Y4 LCD2 Indication - (4) LCD2: Percentage (Default) LCD2: Current - I (mA) COD. Painting

P0 Gray Munsell N 6,5 Polyester (Default) P3 Black Polyester P4 White Epoxy COD. Sensor Type

T1 RTD Cu10 - GE TB Thermocouple type E - NBS T Q 22 mV T2 RTD Ni120 - Edison Curve #7 TC Thermocouple type J - NBS TR 100 mV T3 RTD PT50 - IEC TD Thermocouple type K - NBS TS 500 mV T4 RTD PT100 - IEC TE Thermocouple type N - NBS TT Special mV (4) T5 RTD PT500 - IEC TF Thermocouple type R - NBS TV RTD Pt100 MILT T6 RTD PT50 - JIS TG Thermocouple type S - NBS TW RTD Ni120 MILT T7 RTD PT100 - JIS TH Thermocouple type T - NBS TX RTD Pt100 - IEC (4) TU RTD PT1000 - IEC (4) TK Thermocouple type L - DIN 10 RTD Pt100 - GOST (4) T8 2K OHM TP Thermocouple type U - DIN 11 RTD Pt50 - GOST (4) T9 400 OHM TN 100 OHM 12 Cu100 - GOST (4) TA Thermocouple type B - NBS TO Special OHM (4) 13 Cu50 - GOST (4) COD. BD Burn-out (4) Down Scale BU Up Scale

TT301 TT302 TT303


Note:

1 1 1

0 0 0

H1 H1 H1

I1 I1 I1

J0 J0 J0

L2 L2 L2

M0

Y0

Y0

P8 P8 P8

T1 T1 T1

BU

2 2

(1) Values limited to 4 digits; units limited to 5 characters. (2) Not certified for use in hazardous locations. (3) Only available for TT302 and TT303. (4) Only available for TT301. (5) Only available for TT301 and TT302. (6) Not available for Aluminum housing. (7) For TT301, this code will be available only if the chosen sensor is Ohm or mV special. (8) Certified for use in hazardous locations (CEPEL, CSA, FM, NEPSI, NEMKO, EXAM). (9) Certified for use in hazardous locations (CEPEL, CSA, FM). (10) Certified for use in hazardous locations (CEPEL, FM, NEPSI, NEMKO, EXAM).

(11) Certified for use in hazardous locations (CEPEL, NEPSI, NEMKO, EXAM). (12) Rectangular plate in 316 SST. (13) IPX8 tested in 10 meters of water column for 24 hours. (14) Ingress Protection: Product TT300 CEPEL IP66/68W NEMKO / EXAM IP66/68W FM Type 4X/6 (6P) CSA Type 4X NEPSI IP67

(15) IPW/TYPE testes for 200 hours according to NBR 8094 / ASTM B 117 standard.

10

All-in-one Station Maintenance Engineering Operation - MES (Manufacturing Execution System) - ERP (Enterprise Resource Planning) - CRM (Customer Relationship Management)

Communication Server

DF100 Maintenance Maintenance and Asset Management Communication Server Alarm and Event Management

Fiber Optic Ring

Communication Server

DFI302 Redundant Controllers

4 - 20 20 mA m tpu tp uts s Outputs

4 - 20 mA Inputs

Eth ern et
Auto Tuning Advanced Control
Corporate Network Internet

Internet

DFI302 Redundant Controllers HI302 HART/FOUNDATION TM DFI302 PROFIBUS DP and PA Communication Server PA DP DFI302 DeviceNet Router or Firewall

SYSTEM302 Architecture

11
Fiscal Printer Printer DFI302 AS-i Database Redundant Servers DFI302 (Controller with I/O modules) Communication Server TCP and RTU 4 - 20 mA Discrete I/O Package Units Legacy Systems CLP F&G ESD 4 - 20 mA I.S. I.S. Discrete I/O

DC302 (Remote I/O)

FISCO

Intrinsic Safety Barrier FOUNDATION TM

rete isc tD rete Ou isc D In

FOUNDATION TM

H1 I.S.

Channel 1

Channel 8

Main Smar Products


Pressure
4-20 mA LD290 LD291 LD292 LD293 LD1.0

Pressure and Level


4-20 mA LD290 4-20 mA LD290 LD291 LD292 LD292 LD293 LD293 LD291

Pressure, Level and Flow


LD400 LD301 LD302 LD303 LD400

Pressure Gauge Economic Capacitive Transmitter Pressure "In Line" Transmitter Level

Flanged Transmitter

Pressure Transmitter with Extended Probe

Pressure Pressure WirelessHART Transmitter Transmitter Pressure with High Transmitter Performance Position

Density/Concentration

RD400

DT301 DT302 DT303

FY301 FY302 FY303 FY400

Guided Wave Level Transmitter

Intelligent Density / Concentration Transmitter Position


ACP400 FY400 FY301 FY302 FY303 ACP301 ACP302 ACP303

Valve Positioner

Valve Positioner with Auto Tuning

ACP400 ACP301 ACP302 ACP303

4-20 mA TP290 TP301 TP302 TP303

Valve Positioner with Remote Sensor

Pneumatic Linear Cylindric Actuador Temperature


TT383 TT400 HART SIS

Pneumatic Rotary Cylindric Actuador

Position Transmitter

TT400

TT411

TT421

TT301 TT302 TT303

Temperature Transmitter

Eight Input Temperature Transmitter

Smart Temperature Transmitter

WirelessHART Temperature Transmitter

Panel Mounting Temperature Transmitter

Head Mouting Temperature Transmitter

12

Main Smar Products


Junction Box JM1
4-20 mA

Didactic Products JM400


4-20 mA

PD3

DeviceNet

TM

3 Ways Junction Box

4 Ways Junction Box Configurators

Didactic Plant

Didactical Kits Interfaces HI311/HI321 PBI-PLUS

CONF401

DDCON 100

HART Configurator Interface

HART Configurator Interface

HART Configurator Converters

HART-USB Advanced PROFIBUS PA Interface for PC Interface

HI302
IF302 IF303 FP302 FP303 FI302 FI303 FRI302 FRI303

HCC301

FOUNDATIONTM / PROFIBUS PA to Pneumatic Signal Converter

Triple Channel Current Triple Channel FOUNDATIONTM / TM TM to FOUNDATION / FOUNDATION / PROFIBUS PA PROFIBUS PA PROFIBUS PA to Relay and Converters Current Converters Digital Input Controllers

HART / Fieldbus Interface

HART / Current Converter

DFI302

LC700

CD600Plus

DeviceNet

TM

Interface Universal Fieldbus

Programmable Logical Controller

Digital Controller

13

Main Smar Products


Controllers - Remote Input and Output DF100 DC303 DC302

HSE Controller and WirelessHART Gateway

FOUNDATIONTM fieldbus / PROFIBUS PA Remote Input and Output SYSTEM302

ProcessView Supervision / Operation System

SimulationView Control Strategy Simulator

AssetView STANDALONE Asset Management System

Syscon Control Strategy and Industrial Network Configurator

Process Equipment Database Plant Information Management

LogicView for FFB IEC61131 Programming Tool

DeviceNet

TM

smar
www.smar.com
Specifications and information are subject to change without notice. Up-to-date address information is available on our website. web: www.smar.com/contactus.asp

Copyright 2006 - Smar International - all rights reserved. - October/2012