Smar Tt300ce
Smar Tt300ce
Smar Tt300ce
02% Single
Basic Accuracy
Unit and Several Options for Sensors and Connections Signal Isolation
Input PID
Advanced Largest
Supported
Dual
Channel Backup
Sensor Three
Features
0.02% Accuracy; Built-in thermocouples and RTDs True non-interactive zero and span; Local zero and span adjustment; Remote configuration via Hand-Held Alphanumerical LCD indication; Small and lightweight; Explosion proof and weather proof Intrinsically safe certification; Signal simulation for loop tests;
HART - 4 to 20 mA housing approved (IP66/68 ou IP66/68W); Terminal or via PC; linearization;
Signal isolation; Configurable user unit; Configurable local adjustment; EMC (Electromagnetic Compatibility) Write protection function; Three technology options: Sensor backup*; Universal input
F O U N D AT I O N PROFIBUS PA;
TM
according to IEC 61000-6-2: 1999, IEC 61000-6-4: 1997 and IEC 61326: 2002;
Special 16-point sensor characterization; Update output current in 0.5 s with Improved
1.5 A/bit resolution; performance due to dedicated math coprocessor;
Pt1000 included in sensor list; Setpoint generator function; Supports DTM, DD and EDDL.
Self-diagnosis; Dual channel; 12 mA consumption; 19 different types of function blocks Up to 20 function blocks; Execution of up to 29 external links;
PROFIBUS PA for control strategies and advanced diagnostics;
Integrated to Smar Profibus View and Supports DTM and EDDL; Profile 3.0 improves interchangeability.
Simatic PDM;
Dimensional Drawing
PLUG
ALLOW 150 MM MINIMUM FOR LOCAL ZERO AND SPAN ADJUSTMENT WITH MAGNETIC TOOL.
CONDUIT CONNECTION
COMMUNICATIONS TERMINAL
PLUG
MOUNTING BRACKET
PIPE 2"
FOR WALL MOUNTING 2 EXPANSION ANCHOR - S8 2 HEXAGON SCREW - 3/16X70 FOR PANEL MOUNTING 2 BOLT AND NUTS - 1/4X30 NOT INCLUDED
Functional Description
TT300 Series offers: 0.02% accuracy; Built-in thermocouples and RTDs linearization; Compact and lightweight; Interchangeable protocols. The Smar TT300 Series is a transmitter mainly intended for measurement of temperature using RTDs or thermocouples. However, it can also accept other sensors with resistance or mV output such as pyrometers, load cells, resistance position indicators, etc. The TT300 Series accepts up to two sensors and may operate in one of the modes below*: Single channel with single sensor measurement; Dual channel with dual sensor measurement (except HART protocol device); Single channel with two sensors (same type) in differential measurement; Single channel with two sensors (same type) in backup measurement; Single channel with two sensors (same type) with maximum, minimum or average signal selection (only HART protocol device). The Smar TT300 Series is a powerful and extremely versatile smart temperature transmitter. The digital technology used in the TT300 Series enables a single device to accept several types of sensors, wide ranges, single or multiple-ended measurement and an easy interface between the field and the control room. It also includes several features which reduce considerably the installation, operation and maintenance costs. The transmitter accepts two channels, i.e., two measurements. It reduces the cost per channel. The TT300 Series is suitable for direct field installation, being weather proof and explosion proof, as well as intrinsically safe, for use in hazardous areas.
to configure zero and span, setpoint and other control functions using the magnetic tool (SD1). With Smar AssetView, an user-friendly Web Tool, user can access the plant assets anywhere and anytime using an Internet browser. It is designed for management and diagnostics of field devices to ensure reactive, preventive, predictive and proactive maintenance.
HART - TT301
TT301 (HART protocol) can be configured by: Smar CONF401 for Windows; Smar DDCON100 for Windows; Smar HPC301 and HPC401 for several models of Palm; Other manufacturers' configuration tools based on DD (Device Description) or DTM (Device Type Manager), such as AMSTM, FieldCare, PACTwareTM, HHT275, HHT375 and PRM Device Viewer. For management and diagnostics, AssetView ensures continuous information monitoring.
PROFIBUS PA - TT303
TT303 (PROFIBUS PA protocol) can be configured using configuring Smar Profibus View, Simatic PDM, FDT (Field Device Tool) and DTM (Device Type Manager) concept tools, such as FieldCare and PACTwareTM. It can also be integrated by any PROFIBUS System using the GSD (General Station Description) file. PROFIBUS PA also has quality and diagnostics information, improving plant management and maintenance.
Smar and SYSTEM302 are trademarks or registered trademarks of Smar Equipamentos Industriais Ltda. in Brazil and/or other countries. Other marks are the properties of their respective owners.
Wiring Connection
HART - TT301
Power Supply
and/or
TT301
For an adequate communication, a minimun load of 250 is required between the configuration tool and the power supply.
Laptop
Shield Terminator
Junction Box
Shield
Spur
Spur Terminator
Panel Ground
Analog Ground
Panel Ground
Analog Ground
PROFIBUS - TT303
Spur Spur
DP/PA Coupler
Junction Box
Shield Terminator
DP/PA Coupler
Junction Box
Shield
Spur Terminator Panel Analog Ground Ground Spur Spur Panel Analog Ground Ground Terminators Spur Spur
HART Interface
Pyrometer
Load Cell
TT302
D F 5 0
D F 6 2
FY302
PROFIBUS - TT303
LD303 LD303 Process FY303 TT303
Power Supply
D F 5 2
DF73 TT303
PA
DP
D F 5 0
D F 7 3
Profibus DP Master
FY303
Technical Characteristics
Functional Specifications
Inputs Output and Communication Protocol See table 1, 2 and 3. HART: 2-wire, 4-20 mA according to NAMUR NE43 specification, with super-imposed digital communication (HART Protocol). FOUNDATIONTM fieldbus and PROFIBUS PA: Digital only. Complies with IEC 61158-2: 2000 (H1): 31.25 kbit/s voltage mode, bus powered. HART: 12 to 45 Vdc. FOUNDATIONTM fieldbus and PROFIBUS PA: Bus powered: 9 - 32 Vdc. Quiescent current consumption: 12 mA. 4-digit numerical and 5-character alphanumerical LCD indicator (optional). HART, FOUNDATIONTM fieldbus and PROFIBUS PA: Intrinsic Safety (FM, CSA, NEMKO, EXAM, CEPEL, NEPSI), Explosion Proof (FM, CSA, NEMKO, CEPEL), Dust Ignition Proof (FM), Non-incendive (FM) FOUNDATIONTM fieldbus and PROFIBUS PA: FISCO (FM, CSA, NEMKO, EXAM, CEPEL, NEPSI) and FNICO (FM, CSA, NEMKO, EXAM, CEPEL) Authorized representative in European Community Smar Gmbh-Rheingaustrasse 9-55545 Bad Kreuzanach EMC Directive (89/336/EEC) - Electromagnetic Compatibility The EMC test was performed according to IEC standard: IEC61326:2002. For use only in industrial environment. European Directive Information ATEX Directive (94/9/EC) - Equipment and protective systems intended for use in potentially explosive atmospheres. This product was certified according European Standards at NEMKO and EXAM (former DMT). The certified body for manufacturing quality assessment is EXAM (number 0158). LVD Directive 2006/95/EC - Electrical Equipment designed for use within certain voltage limits According the LVD directive Annex II the equipment under ATEX Electrical equipment for use in an explosive atmosphere directive are excluded from scope from this directive. Zero and Span Adjustments Noninteractive, via local adjustment and digital communication. Detailed diagnostics through communication for all protocols. HART: In case of sensor or circuit failure, the self diagnostics drives the output to 3.6 or 21.0 mA, according to the user's choice and NAMUR NE43 specification. Failure Alarm (Diagnostics) FOUNDATIONTM fieldbus: For sensor circuit failures, events are generated and status is sent to link outputs. Detailed diagnostics are available in the contained parameters. PROFIBUS PA: For sensor or circuit failures, status is sent to link outputs. Detailed diagnostics are available in the contained parameters. Temperature Limits
o -40 oC to 85 C Ambiente: o -40 C to 100 oC Storage: o C Digital Display: -20 oC to 80 o o -40 C to 85 C
(-40 to 185 oF) (-40 to 212 F) (-4 to 176 F) (normal operation) (-40 to 185 oF) (without damage)
Technical Characteristics
HART: Performs within specifications in less than 5 seconds after power is applied to the transmitter. FOUNDATIONTM fieldbus and PROFIBUS PA: Performs within specifications in less than 10 seconds after power is applied to the transmitter. HART: By digital communication (HART protocol) using the configuration software CONF401, DDCON100 (for Windows) or HPC301 and HPC401 (for Palm). It can also be configured using DD and FDT/DTM tools, and can be partially configured through local adjustment , since the transmitter is supplied with display. FOUNDATIONTM fieldbus and PROFIBUS PA: Basic configuration may be done using the local adjustment magnetic tool if device is supplied with display. Complete configuration is possible using configuration tools such as Syscon (System Configuration Tool), AMSTM, FieldCare and HHT375. The TT303 can be configured via Smar Profibus View and Simatic PDM using EDDL. 0 to 100% Relative Humidity. User configurable from 0 to 32 seconds (via digital communication).
Turn-on Time
Configuration
Performance Specifications
Accuracy Digital Stability See tables 1, 2 and 3. 0.1% of reading or 0.1 C (0.18 F), whichever is greater, for 2 years for RTDs; 0.1% of reading or 0.1 C (0.18 F), whichever is greater, for 1 year for thermocouples. For a 10 C variation: mV (-6 to 22 mV), TC (NBS: B, R, S,T): 0.03% of the input milivoltage or 0.002 mV whichever is greater; mV (-10 to 100 mV), TC (NBS: E, J, K, N; DIN: L, U): 0.03% of the input milivoltage or 0.01 mV whichever is greater; Temperature Effect mV (-50 to 500 mV): 0.03% of the input milivoltage or 0.05 mV whichever is greater; Ohm (0 to 100), RTD (GE: Cu10): 0.03% of the input resistence or 0.01 whichever is greater; Ohm (0 to 400), RTD (Edison Curve #7: Ni120; IEC: Pt50, Pt100; JIS: Pt50, Pt100): 0.03% of the input resistence or 0.04 whichever is greater; Ohm (0 to 2000), RTD (IEC: Pt500), RTD (IEC: Pt1000): 0.03% of the input resistence or 0.2 whichever is greater; Power Supply Effect Electromagnetic Interference Effect Electrical Connection 0.005% of calibrated span per volt. Approved according to IEC 61326: 2002. 1/2 - 14 NPT M20 X 1.5 PG 13.5 DIN 1/2 - 14 NPT X 3/4 NPT (316 SST) - with adapter 1/2 - 14 NPT X 3/4 BSP (316 SST) - with adapter 1/2 - 14 NPT X 1/2 BSP (316 SST) - with adapter
Note: Explosion proof approvals do not apply to adapter, only to transmitter.
Technical Characteristics
Physical Specifications
Mounting Approximate Weights Can be attached directly to the sensor. With an optional bracket can be installed on a 2" pipe or fixed on a wall or panel. Without display and mounting bracket: 0.80 kg. Add for digital display: 0.13 kg. Add for mounting bracket: 0.60 kg. HART: PID Control, Alarm and Setpoint Ramp Generator. Control Functions Characteristics (Optional) FOUNDATIONTM fieldbus Function Blocks: Resource, Transducer, Display Transducer, Diagnostic Transducer, Analog Input, PID Control, Enhanced PID Control, Arithmetic, Integrator, Input Selector, Signal Characterizer, Splitter, Analog Alarm, Timer, Lead Lag, Output Selector/Dynamic Limiter, Setpoint Generator and Constant. PROFIBUS PA Function Blocks: Physical Block, Transducer, Display Transducer and Analog Input.
Note: Additional information can be found in the Function Blocks Instruction Manual.
Inputs
2, 3 or 4 wires SENSOR TYPE Cu 10 GE Ni120 Edison Curve #7 Pt50 IEC Pt100 IEC RTD Pt500 IEC Pt1000 IEC Pt50 JIS Pt100 JIS Pt100 MILT Ni120 MILT Pt100 IEC Pt100 GOST Pt50 GOST Cu100 GOST Cu50 GOST B NBS E NBS J NBS K NBS THERMOCOUPLE N NBS R NBS S NBS T NBS L DIN U DIN RANGE C -20 to 250 -50 a 270 -200 to 850 -200 to 850 -200 to 450 -200 to 300 -200 to 600 -200 to 600 -40 a 540 -40 a 205 -200 a 850 -200 a 850 -200 a 850 -50 a 200 -50 a 200 100 to 1800 -100 to 1000 -150 to 750 -200 to 1350 -100 to 1300 0 to 1750 0 to1750 -200 to 400 -200 to 900 -200 to 600 RANGE F -4 a 482 -58 a 518 -328 to 1562 -328 to 1562 -328 to 842 -328 to 572 -328 to 1112 -328 to 1112 -40 a 1000 -40 a 400 -328 a 1562 -328 a 1562 -328 a 1562 -58 a 392 -58 a 392 212 to 3272 -148 to 1832 -238 to 1382 -328 to 2462 -148 to 2372 32 to 3182 32 to 3182 -328 to 752 -328 to 1652 -328 to 1112 MINIMUM SPAN C 50 5 10 10 10 10 10 10 10 5 10 10 10 10 10 50 20 30 60 50 40 40 15 35 50 DIFFERENTIAL
C DIGITAL
ACCURACY* 1.0 0.1 0.25 0.2 0.2 0.2 0.25 0.25 + 0,2 + 0,13 0,2 0,2 0,2 0,15 0,15 0.5** 0.2 0.3 0.6 0.5 0.4 0.4 0.15 0.35 0.5
RANGE C -270 to 270 -320 a 320 -1050 to 1050 -1050 to 1050 NA NA -800 to 800 -800 to 800 -580 a 580 -245 a 245 -1050 a 1050 -1050 a 1050 -1050 a 1050 -350 a 350 -350 a 350 -1700 to 1700 -1100 to 1100 -900 to 900 -1550 to 1550 -1400 to 1400 -1750 to 1750 -1750 to 1750 -600 to 600 -1100 to 1100 -800 to 800
RANGE F -486 to 486 -576 a 576 -1890 to 1890 -1890 to 1890 NA NA -1440 to 1440 -1440 to 1440 -1040 a 1040 -440 a 440 -1890 a 1890 -1890 a 1890 -1890 a 1890 -450 a 450 -450 a 450 -3060 to 3060 -1980 to 1980 -1620 to 1620 -2790 to 2790 -2520 to 2520 -3150 to 3150 -3150 to 3150 -1080 to 1080 -1980 to 1980 -1440 to 1440
MINIMUM SPAN C 50 5 10 10 NA NA 10 10 10 5 10 10 10 10 10 60 20 30 60 50 40 40 15 35 50
C DIGITAL
ACCURACY* 2.0 0.5 1.0 1.0 NA NA 1.0 1.5 + 1,0 + 0,5 + 1,0 + 1,0 + 1,0 + 1,0 + 1,0 1.0** 1.0 0.6 1.2 1.0 2.0 2.0 0.8 0.7 2.5
Table 3 - Ohm Sensor Characteristics Table 2 - mV Sensor Characteristics * Accuracy of value read on display and accessed by communication. The 4-20 mA accuracy is the digital accuracy 0.03%. ** Not applicable for the first 20% of the range (up to 440 C).
NA: Not applicable.
Ordering Code
MODEL TT301 TT302 TT303 TEMPERATURE TRANSMITTER HART & 4 to 20 mA FOUNDATIONTM fieldbus PROFIBUS PA COD. Local Indicator 0 Without Indicator COD. Mounting Bracket A 0 1 With Digital Indicator 1 2 Carbon Steel Bracket 316 SST Bracket 7 Carbon Steel Bracket with 316 SST Fasteners
Flat, 304 SST bracket and 316 SST accessories Without Bracket COD.
Set this code as "1" for TT301 and exclude for the others COD. Electrical Connections 1/2 - 14 NPT (8) 1/2 - 14 NPT X 3/4 NPT (316 SST) - With adapter (9) 1/2 - 14 NPT X 3/4 BSP (316 SST) - With adapter (2) COD. Housing Material (13) (14) H2 H3 Aluminium for saline atmosphere (IPW/TYPEX) (15) 316 SST for saline atmospheres (IPW/TYPEX) (15) I4 EXAM (DMT): Ex-ia I5 CEPEL: Ex-d, Ex-ia I6 Without Certification J1 Blank L4 4-wire LF Differential PID Configuration - (4) With PID (Default) COD. LCD1 Indication - (4) Y3 LCD1: Temperature (Engineering Unit) YU LCD1: According to user notes (1) (7) Y6 LCD2: Temperature (Engineering Unit) YU LCD2: According to user notes (1) (7) P5 Yellow Polyester P8 Without Painting P9 Safety Blue Epoxy - Electrostatic Painting M1 Without PID H4 Copper Free Aluminium (IPW/TYPEX) (15) H0 Aluminum (IP/TYPE) H1 316 SST (IP/TYPE) COD. Identification Plate (12) I1 I2 I3 FM: XP, IS, NI, DI NEMKO: Ex-d, Ex-ia (4) CSA: XP, IS, NI, DI (5) COD. J0 Tag Plate (12) With tag, when specified (Default) COD. Sensor Connection LD Double 2-wire (3) LB Backup J2 According to user's notes IE NEPSI: Ex-ia (3) IF CEPEL: Ex-d (4) IG CEPEL (Ex-d, Ex-ia) +IPW (6) 3 1/2 - 14 NPT X 1/2 BSP (316 SST) - With adapter (2) A M20 x 1.5 (10) B PG 13.5 DIN (11) Z According to users notes
0 1 2
Y0 LCD1: Percentage (Default) Y1 LCD1: Current - I (mA) COD. Y0 Y4 LCD2 Indication - (4) LCD2: Percentage (Default) LCD2: Current - I (mA) COD. Painting
P0 Gray Munsell N 6,5 Polyester (Default) P3 Black Polyester P4 White Epoxy COD. Sensor Type
T1 RTD Cu10 - GE TB Thermocouple type E - NBS T Q 22 mV T2 RTD Ni120 - Edison Curve #7 TC Thermocouple type J - NBS TR 100 mV T3 RTD PT50 - IEC TD Thermocouple type K - NBS TS 500 mV T4 RTD PT100 - IEC TE Thermocouple type N - NBS TT Special mV (4) T5 RTD PT500 - IEC TF Thermocouple type R - NBS TV RTD Pt100 MILT T6 RTD PT50 - JIS TG Thermocouple type S - NBS TW RTD Ni120 MILT T7 RTD PT100 - JIS TH Thermocouple type T - NBS TX RTD Pt100 - IEC (4) TU RTD PT1000 - IEC (4) TK Thermocouple type L - DIN 10 RTD Pt100 - GOST (4) T8 2K OHM TP Thermocouple type U - DIN 11 RTD Pt50 - GOST (4) T9 400 OHM TN 100 OHM 12 Cu100 - GOST (4) TA Thermocouple type B - NBS TO Special OHM (4) 13 Cu50 - GOST (4) COD. BD Burn-out (4) Down Scale BU Up Scale
1 1 1
0 0 0
H1 H1 H1
I1 I1 I1
J0 J0 J0
L2 L2 L2
M0
Y0
Y0
P8 P8 P8
T1 T1 T1
BU
2 2
(1) Values limited to 4 digits; units limited to 5 characters. (2) Not certified for use in hazardous locations. (3) Only available for TT302 and TT303. (4) Only available for TT301. (5) Only available for TT301 and TT302. (6) Not available for Aluminum housing. (7) For TT301, this code will be available only if the chosen sensor is Ohm or mV special. (8) Certified for use in hazardous locations (CEPEL, CSA, FM, NEPSI, NEMKO, EXAM). (9) Certified for use in hazardous locations (CEPEL, CSA, FM). (10) Certified for use in hazardous locations (CEPEL, FM, NEPSI, NEMKO, EXAM).
(11) Certified for use in hazardous locations (CEPEL, NEPSI, NEMKO, EXAM). (12) Rectangular plate in 316 SST. (13) IPX8 tested in 10 meters of water column for 24 hours. (14) Ingress Protection: Product TT300 CEPEL IP66/68W NEMKO / EXAM IP66/68W FM Type 4X/6 (6P) CSA Type 4X NEPSI IP67
(15) IPW/TYPE testes for 200 hours according to NBR 8094 / ASTM B 117 standard.
10
All-in-one Station Maintenance Engineering Operation - MES (Manufacturing Execution System) - ERP (Enterprise Resource Planning) - CRM (Customer Relationship Management)
Communication Server
DF100 Maintenance Maintenance and Asset Management Communication Server Alarm and Event Management
Communication Server
4 - 20 mA Inputs
Eth ern et
Auto Tuning Advanced Control
Corporate Network Internet
Internet
DFI302 Redundant Controllers HI302 HART/FOUNDATION TM DFI302 PROFIBUS DP and PA Communication Server PA DP DFI302 DeviceNet Router or Firewall
SYSTEM302 Architecture
11
Fiscal Printer Printer DFI302 AS-i Database Redundant Servers DFI302 (Controller with I/O modules) Communication Server TCP and RTU 4 - 20 mA Discrete I/O Package Units Legacy Systems CLP F&G ESD 4 - 20 mA I.S. I.S. Discrete I/O
FISCO
FOUNDATION TM
H1 I.S.
Channel 1
Channel 8
Pressure Gauge Economic Capacitive Transmitter Pressure "In Line" Transmitter Level
Flanged Transmitter
Pressure Pressure WirelessHART Transmitter Transmitter Pressure with High Transmitter Performance Position
Density/Concentration
RD400
Valve Positioner
Position Transmitter
TT400
TT411
TT421
Temperature Transmitter
12
PD3
DeviceNet
TM
Didactic Plant
CONF401
DDCON 100
HI302
IF302 IF303 FP302 FP303 FI302 FI303 FRI302 FRI303
HCC301
Triple Channel Current Triple Channel FOUNDATIONTM / TM TM to FOUNDATION / FOUNDATION / PROFIBUS PA PROFIBUS PA PROFIBUS PA to Relay and Converters Current Converters Digital Input Controllers
DFI302
LC700
CD600Plus
DeviceNet
TM
Digital Controller
13
DeviceNet
TM
smar
www.smar.com
Specifications and information are subject to change without notice. Up-to-date address information is available on our website. web: www.smar.com/contactus.asp