Circuit Braker
Circuit Braker
contents
general overview feature - company profile MCCB - NF series circuit breaker, double repulsion breaking method - double number of copper contacts, materials of the NF series - method of installation, MCCB cross sectional area, positive indication & operation - suitability for isolation, compliance with standards - selection | quick & easy selection table - power distribution | technical details - ambient temperature - characteristic curves | NF series - physical dimensions & mounting holes | NF series - accessories | phase insulation barriers, electrical accessories & shunt trip - accessories | under voltage device - accessories | signal switches, rotary handle - accessories | rotary handle - mounting position | internal accessory - internal resistance & power loss - short circuit table | DC voltage - selection table | motor circuit protection - motor selection - installation safety distance requirement - terminal-tightening torque - terminal-cable & copper busbar connection data ELCBs - EG series | with overload & short circuit protection - EG series | operating characteristics & dimensions MCBs - BHQ series | fixed type - BHP series | plug-in type - BHQ & BHP | operating characteristics & dimensions RCBOs - EQ series | fixed type - EP series | plug-in type - EQ & EP series | dimensions & operating characteristics ordering codes ... 2
... 6
... 7 ... 8 ... 9 ... 10 ... 11 ... 12 ... 16 ... 17 ... 22 ... ... ... ... ... ... ... ... ... ... ... ... 30 31 32 33 35 36 39 40 41 43 44 45
... 46 ... 48
NF series
The NF series MCCBs are available from 50AF to 1200AF. Pole sizes from 1 to 4 are available for the various models. All NF series MCCBs are suitable for isolation. 10kA (2P & 3P)
50AF
NF-50MA
250AF
NF-250GP NF-250MA NF-250HA NF-250L
10kA 25kA 50kA 65kA
2
100AF
NF-100GP NF-100HA
10kA 25kA 50kA 65kA
NF-100MA NF-100L
1200AF
NF-1200HA
50kA (3P & 4P)
400AF
NF-400GP NF-400HA
25kA (3P & 4P) 50kA (3P & 4P) 65kA (3P)
NF-400L
general overview
Accessories
shunt trip
signaling switches
rotary handle
ELCB: EG series
100AF
EG-100MA EG-100HA
4
250AF
EG-250MA EG-250HA
25kA (3P & 4P) 50kA (3P & 4P)
100AF
BHQ-2
6kA (2P)
100AF
BHQ-3
6kA (3P)
100AF
BHP-1
6kA (1P)
100AF
BHP-2
6kA (2P)
100AF
BHP-3
6kA (3P)
50AF
EQ-2
10kA (2P)
50AF
EQ-3
10kA (3P)
50AF
EP-1
10kA (1P)
50AF
EP-2
10kA (2P)
50AF
EP-3
10kA (3P)
5
feature
company profile
Since our inception in 1974, our company specializes in manufacturing low voltage circuit breakers and have a reputation of producing products of consistent quality and high reliability.
Our manufacturing facilities are certified to the international quality standards of ISO 9001, while our products are certified by ASTA Certification Services UK. With such high standards, our range of circuit breakers are able to meet your highest demands for quality, safety and reliability.
MCCB
Fm
opening
Fm
7
fixed contact
MCCB
method of installation
The NF series circuit breakers can be installed in vertical or horizontal position without any impact on its performance or de-rating of characteristics.
horizontal vertical
MCCB
isolation
10
technical details
model Code Ampere Frame (AF) NF-50
50AF
electrical characteristics
NF-100
100AF
NF-250
250AF
Rated Current: In (A) at Ambient Temp 50C Number of Poles Available Rated Insulation Voltage: U i(V) Rated Impulse withstand Voltage: U imp (kV) Rated Ultimate Short Circuit Breaking Capacity: I cu (kA) 690V 500V 440V IEC 60947-2 415V 400V 380V 230V DC 250V
10 15 20 30 40 50 2 3 600 8 MA 5 7.5 10 10 10 15 25 5 50
125 150 160 175 200 225 250 3 4 690 8 GP 5 7.5 10 10 10 15 25 5 50 8 MA 10 15 25 25 25 30 50 10 50 8 HA 10 40 50 50 50 60 85 20 50 8 L 35 50 65 65 65 100 125 40 50
Rated Service Short Circuit Breaking Capacity: I cs = % I cu Rated Short Circuit Breaking Capacity: (kA) 600V JIS C 8201-2 (sym) 440V 380V 220V DC
12
7.5 10 15 25 5 A 2 20000
7.5 10 15 25 5 A 2
10 22 30 50 10 A 2
30 50 50 85 20 A 2
50 65 100 125 40 A 2
7.5 10 15 25 5 A 2
10 22 30 50 10 A 2
30 50 50 85 20 A 2
50 65 100 125 40 A 2
250V
Suitable for Isolation Utilization Category Pollution Degree No. of Electrical Operations
Notes: - denotes available.
15000
15000
technical details
model Code Ampere Frame (AF) NF-400
400AF
electrical characteristics
NF-600 & NF-800
800AF
NF-1200
1200AF
Rated Current: In (A) at Ambient Temp 50C Number of Poles Available Rated Insulation Voltage: U i(V) Rated Impulse withstand Voltage: U imp (kV) Rated Ultimate Short Circuit Breaking Capacity: I cu (kA) 690V 500V 440V IEC 60947-2 415V 400V 380V 230V DC 250V
8 GP 10 22 25 25 25 30 50 20 50
Rated Service Short Circuit Breaking Capacity: I cs = % I cu Rated Short Circuit Breaking Capacity: (kA) 600V JIS C 8201-2 (sym) 440V 380V 220V DC 250V
18 25 30 50 20 A 3
30 50 50 85 40 A 3 11000
50 65 100 125 40 A 3
18 25 30 50 20 A 3
30 50 50 85 40 A 3 11000
50 65 100 125 40 A 3
30 50 50 85 40 A 3 8000 13
Suitable for Isolation Utilization Category Pollution Degree No. of Electrical Operations
Notes: - denotes available.
technical details
thermomagnetic trip release
model Code Ampere Frame (AF) Rated Ultimate Short Circuit Breaking Capacity: I cu (kA) Fixed thermal, Fixed Magnetic 10 x Ith Fixed thermal, Adjustable Magnetic NF-50
50AF MA GP
NF-100
100AF MA HA L GP
NF-250
250AF MA HA L
mechanical characteristics
Number of Poles (P)
a aa ca c
3 75 130 68 90 110 25
1 42
2 60
3 90 155
4 120 155
1 48 165 68 92 126 35
a b c ca bb aa
50 130 68 90 110
155 155 68 90
ON
OFF
bb b
(mm)
Type of Terminals
1.5(1.6)
1.9
accessories
Shunt Trip Device Under Voltage Trip Device Auxiliary Switch Alarm Switch
14
Notes: All L-type breakers are only available in the 3-pole version; ( ) denotes for L-type. - denotes available; however, all accessories are not available for 1-pole models.
technical details
thermomagnetic trip release
model Code Ampere Frame (AF) Rated Ultimate Short Circuit Breaking Capacity: I imp (kA) Fixed thermal, Fixed Magnetic 10 x Ith Fixed thermal, Adjustable Magnetic
GP
NF-400
400AF HA L
NF-1200
1200AF HA
mechanical characteristics
Number of Poles (P)
a aa ca c
a b c ca bb aa
ON OFF
bb b
(mm)
Type of Terminals
accessories
Shunt Trip Device Under Voltage Trip Device Auxiliary Switch Alarm Switch Auxiliary + Alarm Switch Rotary Handle
15
Notes: All L-type breakers are only available in the 3-pole version; ( ) denotes for L-type. - denotes available.
The NF series circuit breakers are able to operate in temperatures between 25 to 70C. The nominal current of circuit breakers are rated 100% at 50C. Please refer to the table below for temperature derating. 1-Pole, 2-Pole, 3-Pole and 4-Pole In (A) 25C
10 15 20 30 40 50 60 75 80 100 125 150 160 175 200 225 250 300 350 400 500 600 700 800 16 1000 1200 11.2 16.8 22.4 33.6 42.2 52.8 63.3 79.1 84.4 105.5 138.1 165.8 176.8 193.4 221.0 248.6 282.5 339.0 395.5 452.0 557.5 669.0 763.0 872.0 1110.0 1308.0
30C
10.9 16.4 21.8 32.7 41.8 52.3 62.7 78.4 83.6 104.5 136.3 163.5 174.4 190.8 218.0 245.3 275.0 330.0 385.0 440.0 547.5 657.0 749.0 856.0 1090.0 1272.0
35C
10.8 16.2 21.6 32.4 41.4 51.8 62.1 77.6 82.8 103.5 134.4 161.3 172.0 188.1 215.0 241.9 270.0 324.0 378.0 432.0 537.5 645.0 735.0 840.0 1070.0 1260.0
40C
10.5 15.8 21.0 31.5 41.0 51.3 61.5 76.9 82.0 102.5 131.3 157.5 168.0 183.8 210.0 236.3 262.5 315.0 367.5 420.0 522.5 627.0 728.0 832.0 1045.0 1248.0
45C
10.3 15.5 20.6 30.9 40.4 50.5 60.6 75.8 80.8 101.0 128.8 154.5 164.8 180.3 206.0 231.8 257.5 309.0 360.5 412.0 512.5 615.0 714.0 816.0 1025.0 1224.0
50C
10.0 15.0 20.0 30.0 40.0 50.0 60.0 75.0 80.0 100.0 125.0 150.0 160.0 175.0 200.0 225.0 250.0 300.0 350.0 400.0 500.0 600.0 700.0 800.0 1000.0 1200.0
55C
9.8 14.7 19.6 29.4 38.4 48.0 57.6 72.0 76.8 96.0 122.5 147.0 156.8 171.5 196.0 220.5 243.8 292.5 341.3 390.0 485.0 582.0 686.0 784.0 970.0 1176.0
60C
9.6 14.4 19.2 28.8 37.2 46.5 55.8 69.8 74.4 93.0 118.8 142.5 152.0 166.3 190.0 213.8 236.3 283.5 330.8 378.0 475.0 570.0 672.0 768.0 945.0 1140.0
65C
9.4 14.1 18.8 28.2 36.6 45.8 54.9 68.6 73.2 91.5 116.3 139.5 148.8 162.8 186.0 209.3 231.3 277.5 323.8 370.0 465.0 558.0 658.0 752.0 920.0 1128.0
70C
9.2 13.8 18.4 27.6 36.0 45.0 54.0 67.5 72.0 90.0 111.3 133.5 142.4 155.8 178.0 200.3 222.5 267.0 311.5 356.0 450.0 540.0 644.0 736.0 900.0 1104.0
MCCB characteristics
NF-50MA
4hr 2hr 1hr 30min 20min 14min 10min 6min 4min 2min 1min
characteristic curves
temperature characteristic
tripping curve
Operating Characteristics
Operating time
Max
30sec 20sec 10sec 5sec 2sec 1sec 0.5sec 0.2sec 0.1sec 0.05sec 0.02sec 0.01sec
1 1.3 2 3 4 5 6 7 10 15 20 30 40
50
Rated ambient
60
NF-100GP, MA & HA
tripping curve
4hr 2hr 1hr 30min 20min 14min 10min 6min 4min 2min 1min
characteristic curves
temperature characteristic
Operating Characteristics
Max
110
Operating time
30sec 20sec 10sec 5sec 2sec 1sec 0.5sec 0.2sec 0.1sec 0.05sec 0.02sec 0.01sec
1 1.3 2
Min
100 40A~100A 90
20
30
40
50
Rated ambient
60
17
Instantaneous trip
15 20 30 40
MCCB characteristics
NF-250GP, MA & HA
tripping curve
4hr 2hr 1hr 30min 20min 14min 10min 6min 4min 2min 1min
characteristic curves
temperature characteristic
130
Operating Characteristics
120
Max
110
Operating time
30sec 20sec 10sec 5sec Min 2sec 1sec 0.5sec 0.2sec 0.1sec 0.05sec 0.02sec 0.01sec
1 1.3 2
100
90
20
30
40
50
Rated ambient
60
70
Instantaneous trip
15 20 30 40
NF-400GP & HA
tripping curve
4hr 2hr 1hr 30min 20min 14min 10min 6min 4min 2min 1min
characteristic curves
temperature characteristic
Operating Characteristics
130
Max
110
Operating time
30sec 20sec 10sec 5sec 2sec 1sec 0.5sec 0.2sec 0.1sec 0.05sec 0.02sec Max. Total interrupting time Min
100
90
20
30
40
50
Rated ambient
60
70
18
0.01sec
Instantaneous trip
15 20 30 40
NF-600/800GP & HA
tripping curve
4hr 2hr 1hr 30min 20min 14min 10min 6min 4min 2min 1min
characteristic curves
temperature characteristic
Operating Characteristics
110
Operating time
30sec 20sec 10sec 5sec 2sec 1sec 0.5sec 800AF 0.2sec 0.1sec 0.05sec 0.02sec 0.01sec
1
100 800AF 90
Min
600AF
20
30
40
Rated ambient
50 60
70
Instantaneous trip
10 15 20 30 40
NF-1200HA
tripping curve
240 120 60 In
1000A 1200A
characteristic curves
temperature characteristic
130
High
6000A10% 7200A10%
Itr Low
3000A25% 3600A25%
Minute
Max: value
120
110
Operating time
100 1200AF 90
Adjustable Instantaneous tripping setting range Max total fault clearing time
Second
20
30
40
Rated ambient
50 60
20
1000AF
70
19
15 20 30 40 50 80 100
MCCB characteristics
NF-100L
characteristic curves
tripping curve
4hr 2hr 1hr 30min 20min 14min 10min 6min 4min 2min 1min
Operating Characteristics
Operating time
30sec 20sec 10sec 5sec 2sec 1sec 0.5sec 0.2sec 0.1sec 0.05sec 0.02sec 0.01sec
1 1.3 2
Min
Instantaneous trip
20 30 40
NF-250L
characteristic curves
tripping curve
4hr 2hr 1hr 30min 20min 14min 10min 6min 4min 2min 1min
Operating Characteristics
Max
Operating time
30sec 20sec 10sec 5sec 2sec 1sec 0.5sec 0.2sec 0.1sec 0.05sec 0.02sec
Min
20
0.01sec
1 1.3 2
Instantaneous trip
15 20 30 40
NF-400L
characteristic curves
tripping curve
4hr 2hr 1hr 30min 20min 14min 10min 6min 4min 2min 1min
Operating Characteristics
250A 175025% 400010% 300A 210025% 480010% 350A 245025% 560010% 400A 280025% 640010%
Operating time
30sec 20sec 10sec 5sec 2sec 1sec 0.5sec 0.2sec 0.1sec 0.05sec 0.02sec 0.01sec
1 1.3 2
Min
Instantaneous trip
20 30 40
NF-600L, 800L
4hr 2hr 1hr 30min 20min 14min 10min 6min 4min 2min 1min
characteristic curves
tripping curve
Operating Characteristics
Max
Control setting Lo 2 3 Hi Lo 2 3 Hi
Operating time
30sec 20sec 10sec 5sec 2sec 1sec 0.5sec 0.2sec 0.1sec 0.05sec 0.02sec 0.01sec
1
600
800
Inst trip current(%) 600AF 800AF 500100 800 1100 1400280 350100 550 750 950280
Instantaneous trip
10 15 20 30 40
21
NF-50MA
C L
front connection
Insulation barrier (removable)
Mounting hole
C L
Screw
110
C L
22 Trip button
130
50
24
84
50
8.5
25 50
50 75 4 61 68 72 90
27
2-pole
Breaker
3-pole
C L
Breaker
C L
C L
C L
110
C L
C L
R1
25 50 M4 Screw or 5mm 70
22.5
2-pole
3-pole
22
52
4.5
NF-100GP, MA & HA
C L
Mounting hole Insulation barrier (removable)
front connection
C L
Screw 50 24
C L
134
155
50
134
155
C L
22 Trip button 30 60 60 90
102
50
8.5
27
C L
Breaker
C L
C L
Breaker
C L
C L
R1
C L
132
C L
4.5 28 52
30
M4 Screw or 5mm
30
57 86
2-pole
3-pole
4-pole
23
NF-250GP, MA & HA
Mounting hole Insulation barrier (removable)
front connection
C L
100 Screw 24
C L
144
165
120
50
Trip button
22
100
70 105
30 105 140
45 61
Neutral pole 4
68 72 92
4-pole 3-pole
Breaker
C L
Breaker
C L
C L
126
C L
35
M4 Screw or 5mm
32.5 35 100
24
3-pole 4-pole
52
R1
4.5
8.5
NF-400GP & HA
110
|
C L
front connection
94.5 44 8 16 Conductor 43
C L
28
C L
C L
N
102
39
47 7 44
Trip button
51 112 140
14 M12 bolt
4-pole
C L
Breaker
C L
3-pole
Breaker
C L
194
C L
C L
C L
R6
44
M6 screw or 7mm 44
118
92
25
3-pole 4-pole
NF-600/800GP & HA
Mounting hole
front connection
94.5 600A frame 44 800A frame 46 600A frame 8 800A frame 12
C L
110
C L
87
Conductor
32
15
C L
N
32 Trip button 32
275
102
14
600A frame 8 800A frame 12 600A frame 14 800A frame 46 97 103 107 155
15
Neutral pole
87
14 M12bolt
4-pole 3-pole
C L
Breaker
C L
R6
C L
C L
243
C L
C L
70
M6 Screw or 7mm
70 172
51
26
3-pole 4-pole
92
Breaker
NF-1200HA
Mounting hole 110
front connection
94.5 Conductor 46
C L
C L
87
17
32
15
C L
N
32 Trip button
400
102
40
87
14
17 46
20
14 40
70 210
Neutral pole 5
14 M12bolt
4-pole 3-pole
C L
Breaker
C L
R6
C L
C L
Breaker
370
C L
C L
70
M6 Screw or 7mm
70 172
51
92
27
3-pole 4-pole
NF-100L
Mounting hole
front connection
3-pole
C L
50
C L
Breaker
C L
132
134
155
102
50
R1
8.5
22 Trip button
4.5
3-pole
NF-250L
Mounting hole
front connection
3-pole
C L
100
C L
Breaker
C L
126
144
165
102
50
8.5
22 Trip button
4.5
3-pole
28
52
R1
52
NF-400L
Insulation barrier (removable) 110
front connection
94.5 44 8 Conductor
C L
16
28
3-pole
C L
43 39
Breaker
C L
C L
47 7
Trip button
39
M6 Screw or 7mm 44 14 M12 bolt 51 112 140 5 97 103 107 155 44 118
3-pole
NF-600/800L
Mounting hole
front connection
600A frame 44 800A frame 46 600A frame 8 800A frame 12
C L
94.5 Conductor
194
C L
C L
257
102
3-pole
110
C L
87
Breaker
C L
R6
275
15 102
92
C L
C L
8
243
C L
14
Trip button 32 87
600A frame 8 800A frame 12 600A frame 14 97 5 103 107 155 800A frame 46 70
14 40 140 210
15
M6 Screw or 7mm
172
3-pole
92
29
MCCB accessories
62 95 95 95 95
a top b
NF-1200
30
50 / 60 Hz Coil Voltage
AC 110 - 240 AC 100 - 450 AC 200 - 240 AC 380 - 450 AC 380 - 550 DC 100 - 125 120 50 < 15 < 15 120
NF-100
120
NF-250
120
NF-400
20 (100V) 50 (200V) 120 (330V) 170 (450V)
NF-600
200
NF-800
200
NF-1200
200
200 200
120 10 < 15 8 to 15
10 8 to 15
70 8 to 15
Model
NF-250 & below NF-400 NF-800 NF-1200 100-110 100-110 100-110 100-120
AC Coil Voltage
200-220 200-220 200-220 200-240 380-415 400-440 400-440 380-450 440-480
Consump (VA)
5 5 5 5
MCCB accessories
signaling switches
The Signaling switches allow the breaker status information to be obtained remotely. The signaling switch consists of several dry contacts with both normally open (N.O.) and normally closed (N.C.) positions. Auxiliary Switch - Provides breaker ON and OFF status information. Alarm Switch - Provides breaker TRIP status information. Auxiliary + Alarm Switch - Provides breaker ON, OFF and TRIP status information.
Please refer to the above circuit diagram for the switch terminal codes in order to obtain different contact positions, such as N.O. and N.C. to suit the application.
ALa ALc ALb
Auxiliary Switch
Alarm Switch
rotary handle
mechanism
The breaker mounted rotary handle mechanism allows the user to easily switch the breaker ON by a rotating action. The rotary handle mechanism is equipped with a safety device that prevents the panel door from being open when the breaker is in ON position. A bypass screw is provided for manual intervention when breaker is in ON position. Pad locking facility is available on the rotary handle. The handle can be pad locked when the breaker is in OFF position.
32
rotary handle
104
external dimensions
104 45
Figure (a)
20 50
Figure (b)
rotary handle
Center of breaker
drilling plan
breaker (x) (Y)
Center of breaker
C L
F
0 9
C L
F 112 78
18
(Y) 78 112 B
Figure (c) Figure (d) Figure (e)
(X) D
Type
Breaker Type
Dimensions (mm) A
95 105
B
25
C
111
Mounting Screws
(X) breakers mounting screws (2pcs)
AC-NF-RHN0
NF-50MA NF-100GP MA HA
AC-NF-RHN1
3P 4P
30 a c e 117 107
132 (116)
M4 x 0.7 screw or 5
(Y) operating handle mounting screws (2pcs)
AC-NF-RHN2
3P 4P
35 119 44 b d e 183 70
126 (145)
AC-NF-RHN4
3P 4P
243
Note All rotary handles are supplied with M4 x 0.7 screws and self-tapping 5mm screws.
MCCB accessories
rotary handle
appearance
A direct rotating operating handle has a standard safety device which prevents the breaker from closing as long as the cover is open. It indicates the tripping of the breaker even in ON-lock position, but only in cases when a single padlock (35mm) is used. The degree of protection, in accordance with IEC529, is IP3X (or IP5X with provision of dustproof packing).
The use of the rotary handle mechanism increases the IP rating of the breaker
Left hinge X1
(5H + 100) or more (8H + 100) or more
Right hinge H
Less than 10 10 or more 0 or more
Right hinge X2
170 or more (5H + 120) or more (4H + 70) or more
0 or more
Left hinge
Breaker
X1 X2
Right hinge
The figure above shows the relationship between the hinge and breaker viewed from the load side of the breaker.
34
MCCB
mounting position
Accessories NF-50 MA Shunt Trip Coil (STC) Under Voltage Trip (UVT)
internal accessory
R1 & 2
R1 & 2
R1 & 2
R1 & 2
R1 & 2
R1 & 2
R1 & 2
R1 & 2
R1 & 2
R1 & 2
R1 & 2
R1 & 2
L1 & L2
L1 & L2
L1 & L2
L1, L2
L1, L2, L3
L1, L2, L3
L1 & L2
L1 & L2
L1 & L2
L1, L2
L1, L2, L3
L1, L2, L3
L1 & L2
L1 & L2
L1 & L2
L1, L2
L1, L2, L3
L1, L2, L3
Notes 1) It is NOT possible to install both UVT and STC in the same MCCB. 2) For NF600 onwards, it is possible to install up to a maximum of 4 Auxiliary. Switches or 2 Alarm switches. 3) UVT requires a voltage module that is installed on the right side lead wire terminal.
right side
4 3 2 1
Accessory compartment slot markings
R
left side
1 2 3 4
35
MCCB
NF-50MA
Resistance
NF-100GP
Resistance
NF-100MA
Resistance
NF-250GP
Resistance
NF-250MA
Resistance
Loss
Loss
Loss
Loss
Loss
Loss
Resistance
Loss
Resistance
Loss
1.6 2.0
60000 58000
6.0 1.3
7200 6700 6000 3100 1990 1480 1200 1100 980 770
0.7 1.5 2.4 2.8 3.1 3.7 4.3 6.2 6.5 7.7 450 400 380 350 310 260 7.0 9.0 9.7 10.7 12.4 13.2 575 525 425 395 365 335 9.0 11.8 10.9 12.1 14.6 16.9 196 162 148 120 12.3 14.6 18.1 19.2 100 90 25.0 32.4 70 60 34.3 38.4
2.5 45000 1.8 3.2 32000 2.9 3.4 19000 3.0 3.7 1650 1175 1120 1010 820 4.1 4.2 6.3 7.1 8.2
MCCB
NF 100HA
Resistance u Loss W
NF 250HA
Resistance u Loss W
NF 400HA
Resistance u Loss W
NF 600HA
Resistance u Loss W
NF 800HA
Resistance u Loss W
NF 1200HA
Resistance u Loss W
31500 33500 17000 8500 6000 3300 2000 1500 1200 950
3.2 7.5 6.8 7.7 9.6 8.2 7.2 8.4 8.8 9.5 775 725 680 595 575 535 12.1 16.3 17.4 18.1 23.0 27.0 251 188 188 138 15.7 16.9 23.0 22.1 220 210 51.0 75.6 120 105 58.8 37 67.2 55 45 55.0 64.8
MCCB
NF 100L
Resistance u Loss W
NF 250L
Resistance u Loss W
NF 400L
Resistance u Loss W
NF 600L
Resistance u Loss W
NF 800L
Resistance u Loss W
31500 33500 17500 9000 7000 4500 2200 1800 1500 1350
3.2 7.5 7.0 8.1 11.2 11.3 7.9 10.1 11.2 13.5 775 725 680 595 575 535 12.1 16.3 17.4 18.1 23.0 27.0 290 195 185 175 18.1 17.5 22.7 28.0 220 210 51.0 75.6 120 105 58.8 67.2
DC voltage
Model
NF-50MA
Pole
2 3 1 2 3 1 2 3 4 1 2 3 4 3 1 2 3 1 2 3 4 1 2 3 4 3 3 4 3 4 3 3 4 3 4 3 3 4
48V Icu/Ics 125V Icu/Ics 250V Icu/Ics 400V Icu/Ics 550V Icu/Ics 600V Icu/Ics
40 / 20 40 / 20 41 / 20 42 / 20 40 / 20 50 50 50 50 100 100 100 100 / / / / / / / / 25 25 25 25 50 50 50 50 15 / 8 15 / 8 15 / 8 15 / 8 15 / 8 30 30 30 30 80 80 80 80 / / / / / / / / 15 15 15 15 40 40 40 40 7.5 / 4 7.5 / 4 7.5 / 5 7.5 / 6 7.5 / 7 15 15 15 15 40 40 40 40 / / / / / / / / 8 8 8 8 20 20 20 20
6/3
NF-100GP
6/3
NF-100MA
10 / 5 10 / 5
8/4
8/4
NF-100HA
25 / 13 25 / 13 35 / 18
18 / 9
18 / 9
NF-100L
100 / 50 15 / 8 15 / 8 15 / 8 30 30 30 30 80 80 80 80 / / / / / / / / 15 15 15 15 40 40 40 40
NF-250GP
6/3
NF-250MA
10 / 5 10 / 5
8/4
8/4
NF-250HA
25 / 13 25 / 13 35 / 18 13 / 8 13 / 8 25 / 13 25 / 13 35 / 18 13 / 8 13 / 8 25 / 13 25 / 13 35 / 18 25 / 13 25 / 13
18 / 9
18 / 9
NF-250L NF-400GP
50 / 25 20 / 10 20 / 10 40 / 20 40 / 20 50 / 25 20 / 10 20 / 10 40 / 20 40 / 20 50 / 25 40 / 20 40 / 20
10 / 5
10 / 5
18 / 9
18 / 9
10 / 5
10 / 5 39
18 / 9
18 / 9
18 / 9
18 / 9
MCCB In [A] 10
10 10 10 NF-50MA 10 10 10 15 15
0.37 0.55 0.75 1.1 1.5 2.2 3 4 5.5 7.5 11 15 18.5 22 30 37 45 55 75 90 110 132 160 200 40 250 290 315 355
NF-100MA 20 30 40 NF-100GP 40 50 60 75 100 125 150 NF-250GP 200 225 250 300 NF-400GP 350 400 600 700 NF-600GP NF-250MA
NF-100HA
NF-100L
NF-250HA
NF-250L
NF-400HA
NF-400L
NF-600HA
Short Circuit protection of electric motors The NF series circuit breakers are suitable to combine with motor starters. As defined in IEC 60947-4 standards, the starter switching device, usually a magnetic contactor, must be coordinated with the equipment capable of providing short circuit protection for circuit wiring/cables. The common starting methods for asynchronous squirrel-cage induction motors which the NF series can be used in combination are the direct-online-starters and star-delta-starters. The following selection tables, illustrating the above, shows the suitable breaker ratings that can accommodate motor starting currents. When more than one motor is connected to a branch circuit, the sum of the motor rated current equals to the rated current of the breaker.
motor selection
Motor Ratings kW HP 0.18 1/4
1.1 10 2 0.65 10 2 0.58 10 2
|
0.55 3/4
2.4 10 2 1.4 10 2 1.3 10 2
direct-online-starter
0.75 1
3.3 10 2 1.9 10 2 1.8 10 2
0.37 1/2
2.1 10 2 1.2 10 2 1.1 10 2
1.1 1.5
4.4 10 2 2.5 10 2 2.4 10 2
1.5 2
5.9 15 2 3.4 10 2 3.2 10 2
2.2 3
8.4 20 2 4.8 10 2 4.5 10 2
3 4
11 30 2 6.4 15 2 5.9 15 2
3.7 5
13.6 30 5.5 7.9 15 2 7.3 15 2
4 5.5
15.5 30 5.5 9 20 5.5 7.7 15 2
5.5 7.5
20 50 5.5 11.5 30 5.5 10.5 20 5.5
Motor Full-Load Current (A) Rated Current (A) 3 220V Wire Size (mm2) Motor Full-Load Current (A) Rated Current (A) 3 380V Wire Size (mm2) Motor Full-Load Current (A) Rated Current (A) 3 415V Wire Size (mm2)
Motor Ratings
kW HP
7.5 10
26.5 60 14 15 30 5.5 14 30 5.5
11 15
38 75 22 22 50 8 20.5 50 8
15 20
50 100 38 29 60 14 27 60 14
18.5 25
61 100 38 36 75 22 33 75 22
22 30
71 125 60 41 100 38 38 75 22
30 40
97 150 60 56 100 38 52 100 38
37 50
120 175 80 70 150 60 65 125 60
45 60
145 200 100 84 125 60 77 125 60
55 75
180 225 125 104 150 80 95 150 80
75 100
240 400 200 143 200 100 130 175 100
90 125
290 500 200 170 225 125 154 200 100 41
Motor Full-Load Current (A) Rated Current (A) 3 220V Wire Size (mm2) Motor Full-Load Current (A) Rated Current (A) 3 380V Wire Size (mm2) Motor Full-Load Current (A) Rated Current (A) 3 415V Wire Size (mm2)
Please note that the breaker selection shown in the tables are subjected to the following: only 1 motor to be installed in the circuit and the starting current is less than 6 times of motor full load current.
MCCB
motor selection
Motor Ratings kW HP 110 150
349 600 200 202 400 150 185 300 150
direct-online-starter
160 220
500 800 325 290 500 200 260 500 200 360 600 200 330 600 200 450 800 325 415 700 325 570 1000 325 520 800 325
132 180
411 700 325 238 400 200 218 400 200
200 270
625
250 340
780
315 420
980
Motor Full-Load Current (A) Rated Current (A) 3 220V Wire Size (mm2) Motor Full-Load Current (A) Rated Current (A) 3 380V Wire Size (mm2) Motor Full-Load Current (A) Rated Current (A) 3 415V Wire Size (mm2)
motor selection
Motor Ratings kW HP 5.5 7.5
20 50 8 11.5 30 3.5 10.5 30 3.5
|
11 15
38 75 22 22 50 8
star-delta-starter
15 20
50 100 22 29 60 14 27 60 14
7.5 10
28.5 50 8 15 30 5.5 14 30 5.5
18.5 25
61 125 38 35 75 22 33 75 22
22 30
71 150 38 41 100 38 41 100 22
30 40
97 200 60 56 100 38 52 100 38
37 50
120 225 60 70 150 50 65 150 50
45 60
145 300 80 84 175 50 77 175 50
55 75
180 400 80 104 225 60 95 200 60
75 100
240 400 100 143 225 80 130 225 80
Motor Full-Load Current (A) Rated Current (A) 3 220V Wire Size (mm2) Motor Full-Load Current (A) Rated Current (A) 3 380V Wire Size (mm2) 42 Motor Full-Load Current (A) Rated Current (A) 3 415V Wire Size (mm2)
20.5 50 8
Please note that the breaker selection shown in the tables are subjected to the following: only 1 motor to be installed in the circuit and the starting current is less than 6 times of motor full load current.
motor selection
Motor Ratings kW HP 90 125
290 500 150 170 300 100 154 300 80 Motor Full-Load Current (A) Rated Current (A) 3 220V Wire Size (mm2) Motor Full-Load Current (A) Rated Current (A) 3 380V Wire Size (mm2) Motor Full-Load Current (A) Rated Current (A) 3 415V Wire Size (mm2)
|
110 150
349 600 150 202 400 125 185 300 100
star-delta-starter
132 180
411 800 200 238 400 125 218 400 125
160 220
500 1000 250 290 600 150 260 400 150
Please note that the breaker selection shown in the tables are subjected to the following: only 1 motor to be installed in the circuit and the starting current is less than 6 times of motor full load current.
installation
Model Operating Voltage
U<440V U<600V U<440V U<600V U<440V U<600V U<440V U<600V NF 50 NF 100-250 NF 400-600 NF 800-1200 25 50 75 80
R metal plate of switchboard cable panel door It is compulsory to fit a piece of insulating sheet on the base plate if if R < 8mm
B1
43
MCCB
terminal-tightening torque
To ensure the correct operation of the MCCB, it is essential to make a proper cable or busbar termination to the MCCB. It is recommended that the supplied screws be used to connect the cables or busbars to the breaker terminals and tightened to the torque, as shown in the table below.
tightening range* Nm I
1.8 ~ 2.0 2.5 ~ 3.5 2.5 ~ 3.5 N/A N/A N/A N/A
Bolt/Screw Size
M5 screw M8 screw M8 screw M12 bolt x 2 M12 bolt x 2 N/A N/A
Screw Type
Pan head Screw Screw Bolts Bolts N/A N/A
Max
22 50 150 2 x 100 2 x 200 N/A N/A
II
N/A N/A N/A 10 ~ 14 10 ~ 14 N/A N/A
Bolt/Screw Size
M5 screw M8 screw M8 screw M12 bolt x 2 M12 bolt x 2 M12 bolt x 2 M12 bolt x 2
Max w =
12.5 16.5 23 25 40 44 44
II
N/A N/A N/A 10 ~ 14 10 ~ 14 10 ~ 14 10 ~ 14
5 5 7 8 8 10 17
w t
ELCB
EG series
Ampere Frame (AF) Model Code
100
EG-100HA
Supply System Number of Pole (P) Rated Operational Voltage: Ue Vac Rated Current: In (A) at Ambient Temp 50C Rated Residual Operating Current In (mA) Max Operating Time at 5 In (Sec) Residual Operating Current Indication System Characteristics for DC Components Rated Breaking capacity AC 440V CNS 5422
(Asym/sym) kA
1 2W 1 3W 3 3W 3
3 4W 4
1 2W 1 3W 3 3W 3
3 4W 4
Instantaneous Type
AC 380V AC 230V
a aa
ca c
a b c ca bb
ON
46
OFF
bb b
(mm)
Weight
aa kg
ELCB
EG series
Ampere Frame (AF) Model Code
250
EG-250HA
Supply System Number of Pole (P) Rated Operational Voltage: Ue Vac Rated Current: In (A) at Ambient Temp 50C Rated Residual Operating Current In (mA) Max Operating Time at 5 In (Sec) Residual Operating Current Indication System Characteristics for DC Components Rated Breaking capacity AC 440V CNS 5422
(Asym/sym) kA
1 2W 1 3W 3 3W 3
3 4W 4
1 2W 1 3W 3 3W 3
3 4W 4
230-380-415 (Multi-voltage type) 125 150 160 175 200 225 250 30-100-300 (selectable) 125 150 160 175 200 225 250 30-100-300 (selectable)
Instantaneous Type
AC 380V AC 230V
a aa
ca c
a b c ca bb
ON OFF
bb b
(mm)
Weight
aa kg
ELCB characteristics
EG series
4hr 2hr 1hr 30min 20min 14min 10min 6min 4min 2min 1min
10A 15A 20A 30A 40A 50A 60A 75A 80A 100A
Max
Operating time
30sec 20sec 10sec 5sec 2sec 1sec 0.5sec 0.2sec 0.1sec 0.05sec 0.02sec 0.01sec
1 1.3 2
Min
Instantaneous trip
20 30 40
EG series |
130
10A~30A 120
110
100 40A~100A 90
30
40
50
Rated ambient
60
48
ELCB characteristics
EG series
4hr 2hr 1hr 30min 20min 14min 10min 6min 4min 2min 1min
Max
Operating time
30sec 20sec 10sec 5sec Min 2sec 1sec 0.5sec 0.2sec 0.1sec 0.05sec 0.02sec 0.01sec
1 1.3 2
Instantaneous trip
20 30 40
EG series |
130
120
110
100
90
Rated ambient
60
20
30
40
50
70
49
ELCB dimensions
EG series
Mounting hole
C L
Screw
C L
134
155
50
24
120
50
8.5
22 Trip button
60 90
27
C L
Breaker
C L
C L
132
C L
R1
28 30 M4 Screw or 5mm 30 86
50
3-pole 4-pole
52
4.5
ELCB dimensions
EG series
Mounting hole
C L
100 Screw 24
C L
144
165
102
50
8.5
22 Trip button
70 105
45 73 80 84 104
C L
Breaker
C L
C L
C L
126
3-pole
4-pole
52
R1
4.5
51
MCB
100
BHQ-2
100
BHQ-3
Number of Pole (P) Rated Voltage: Ue Vac Rated Current: In (A) at Ambient Temperature: 50 C Breaking capacity (kA) AC 220V CNS 2931
(Asym/sym) kA
1 220 / 415
2 220 / 415
3 220 / 415
10 6/3
b c
b bb
ca bb aa
Weight
kg
52
100
BHP-2
100
BHP-3
Number of Pole (P) Rated Voltage: Ue Vac Rated Current: In (A) at Ambient Temperature: 50 C Breaking capacity (kA) AC 220V CNS 2931
(Asym/sym) kA
1 220 / 415
2 220 / 415
3 220 / 415
10 6/3
AC 220/415V DC 125V a
a aa
ca c
b c ca bb aa
Weight
kg
53
MCB characteristics
operating characteristics
10A 15A 20A 30A 40A 50A 60A 75A 80A 100A
Operating time
Min (10~50A)
Min (60~100A)
15
20
30
40
temperature characteristics
130 125
10A
15 20
25 30 35 40
45 50 55
Rated ambient
60
54
MCB dimensions
front connection
32
73
95
57
100 74
C L
25
50
25
50
75
22
47
47
5.5
13.5
1-pole
2-pole
3-pole
front connection
Plug-in terminal (Line side)
57.5
71.5
113
87
55
25 25 50 25 75 25 60.5 65.5 77.5 Mig Slot
1-pole
2-pole
3-pole
RCBO
50
EQ-3
Supply System
1 2W
1 2W
1 2W 1 3W 3 3W 3 220 / 240 10 15 20 30 40 50
Number of Pole (P) Rated Operational Voltage: Ue Vac Rated Current: In (A) at Ambient Temp 50C Rated Residual Operating Current In (mA) Max Operating Time at 5 In (Sec) Characteristics for DC Components Rated Breaking capacity (kA) AC 220/380V CNS 5422
(Asym/sym) kA
1 220 / 240 10 15 20 30 40 50
2 220 / 240 10 15 20 30 40 50
30
30
30
Instantaneous Type
0.04 Type: AC
0.04 Type: AC
0.04 Type: AC
10
10
10
AC 220/240V a
10 / 5
10 / 5
10 / 5
25 96 58 77 100 0.2
50 96 58 77 100 25 0.3
75 96 58 77 100 50 0.5
ca c
b c
b bb
56
ca bb aa
Weight
kg
EP-2
Supply System
1 2W
1 2W
1 2W 1 3W 3 3W 3 220 / 240 10 15 20 30 40 50
Number of Pole (P) Rated Operational Voltage: Ue Vac Rated Current: In (A) at Ambient Temp 50C Rated Residual Operating Current In (mA) Max Operating Time at 5 In (Sec) Characteristics for DC Components Rated Breaking capacity (kA) AC 220/380V CNS 5422
(Asym/sym) kA
1 220 / 240 10 15 20 30 40 50
2 220 / 240 10 15 20 30 40 50
30
30
30
Instantaneous Type
0.04 Type: AC
0.04 Type: AC
0.04 Type: AC
10
10
10
AC 220/240V a
10 / 5
10 / 5
10 / 5
25 83 62 81 0.2
50 83 62 81 0.3
75 83 62 81 0.5 57
ca c
b c
ca bb aa
Weight
kg
RCBO characteristics
EQ & EP series
4hr 2hr 1hr 30min 20min 14min 10min 6min 4min 2min 1min 30sec 20sec 10sec 5sec Min 2sec 1sec 0.5sec 0.2sec 0.1sec 0.05sec 0.02sec 0.01sec
1 1.3 2 3
operating characteristics
Operating time
Max
5 6 7
10
15
20
30
40
EQ & EP series |
150 145 140 135
15 20
25 30 35 40
45 50 55
Rated ambient
60
58
RCBO dimensions
front connection
front connection
59
STC
accessory
3
accessory frame size
100AF
10kA 25kA 50kA 65kA
250AF
10kA 25kA 50kA 65kA
400AF
25kA
600AF
25kA
800AF
25kA
1200AF
50kA 65kA
50kA 65kA
50kA 65kA
50kA
accessories
Item Shunt trip coil (240Vac) UVT (415Vac) Auxiliary switch Alarm switch Auxiliary + alarm switch Rotary handle Code
STC UVT AUS ALS AAS RHN
poles
No of Poles Description 1 2 3 4
1 phase 2 phase 3 phase 3 phase + neutral
Example: NF
60
400
HA
300A
3P
STC
400A frame size breaker with Rated Nominal current of 300A, 3-poles and complete with 400A frame size Shunt trip coil.
what is quality ?
We define quality as products having the highest level of reliability, performance and design. Our aim for quality is to meet the requirements of other global markets and to exceed the current international standards. With our in-house design and development team, our range of products are currently manufactured in accordance and compliance to various international standards.