BAC Product & Application Handbook Vol 1 - 2005
BAC Product & Application Handbook Vol 1 - 2005
BAC Product & Application Handbook Vol 1 - 2005
VOLUME I - 2005
Welcome...
.to the first edition of the BAC Product & Application
Handbook. We are excited about providing you with a vehicle that
combines industry critical knowledge with product application
details. This handbook reflects our commitment to facilitate your
application of our products, services, and technical resources to
meet project needs in a timely, efficient manner.
BAC has a rich history in the design and development of the
worlds largest array of evaporative cooling and ice thermal
storage products. I hope you find this publication to be a valuable
resource, and a service to the industry we live.
Sincerely,
Steve Duerwachter
President, Baltimore Aircoil Company
Contents
Baltimore Aircoil Company . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .B1
Introduction to Evaporative Cooling Products . . . . . . . . . . . . .C1
Open Cooling Towers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .D1
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .D1
Series 3000 Open Cooling Towers . . . . . . . . . . . . . . . . . . . .D8
Series 1500 Open Cooling Towers . . . . . . . . . . . . . . . . . . .D34
FXT Open Cooling Towers . . . . . . . . . . . . . . . . . . . . . . . . . .D52
Series V Open Cooling Towers . . . . . . . . . . . . . . . . . . . . . .D64
Engineering Considerations . . . . . . . . . . . . . . . . . . . . . . . .D85
Closed Circuit Cooling Towers . . . . . . . . . . . . . . . . . . . . . . . . . . . .E1
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .E1
Advantages of Closed Circuit Cooling Towers . . . . . . . . . .E7
FXV Closed Circuit Cooling Towers . . . . . . . . . . . . . . . . . .E10
Series V Closed Circuit Cooling Towers . . . . . . . . . . . . . . .E32
HXV Closed Circuit Hybrid Cooling Towers . . . . . . . . . . .E56
Engineering Considerations . . . . . . . . . . . . . . . . . . . . . . . .E76
Evaporative Condensers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .F1
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .F1
Series V Evaporative Condensers . . . . . . . . . . . . . . . . . . . . .F7
CXV Evaporative Condensers . . . . . . . . . . . . . . . . . . . . . . .F35
Engineering Considerations . . . . . . . . . . . . . . . . . . . . . . . .F58
ICE CHILLER
Product Information
Equipment Specifications
Technical Articles
F/85
F/78
F
Series 3000 Cooling Towers deliver independently verified, fully rated thermal performance over a wide
range of flow and temperature requirements. Standard design features satisfy todays environmental
concerns, minimize installation costs, maximize year-round operating reliability, and simplify maintenance
requirements.
Series 3000 Cooling Towers
Low energy consumption
Low installed cost
Easy maintenance
Reliable year-round operation
Long service life
ASHRAE Standard 90.1 compliant
Five-year warranty on mechanical equipment
Series 3000 Open Cooling Towers
O
p
e
n
C
o
o
l
i
n
g
T
o
w
e
r
s
D10
...because temperature matters
S
e
r
i
e
s
3
0
0
0
D11
Baltimore Aircoil Company
Low Energy Consumption
Evaporative cooling equipment minimizes the energy consumption of the entire system because it
provides lower operating temperatures. The owner saves money while conserving
natural resources and reducing environmental impact.
The Series 3000 provides the heat rejection required at the lowest possible energy input via:
High efficiency, low horsepower axial fans
High efficiency BACross
Chamber
further reduces installation costs by eliminating overhead piping and piping support requirements
(see page D17 for details).
Easy Maintenance
Easy Cleaning The wet deck surface is elevated
above the sloped cold water basin floor to facilitate
flushing of dirt and debris from this critical area.
Hinged Access Doors Provide easy access to the
unit interior to adjust the make-up float valve,
clean the cold water basin and strainer, and service
the fan drive system.
Easy Maintenance -The optional EASY CONNECT
Chamber simplifies maintenance by allowing all routine maintenance of the water distribution system
to be performed from the unit interior. This option includes an integral strainer that collects dirt and
debris before reaching the hot water basins, keeping nozzles clean (see page D17 for details).
Benefits
O
p
e
n
C
o
o
l
i
n
g
T
o
w
e
r
s
D12
...because temperature matters
Reliable Year-Round Operation
Drive System Backed by a
five-year fan drive and motor warranty, the
BALTIDRIVE
Power Train
Premium quality, solid backed, multi-groove belt
Corrosion resistant cast aluminum sheaves
Heavy-duty bearings (280,000 hour average life)
Cooling tower duty fan motor
Five-year motor and
drive warranty
Low HP Axial Fan
Quiet operation
Corrosion resistant aluminum
Water Distribution System
Steel covers in easy to remove sections
Low pump head gravity distribution basins
Large orifice, non-clog nozzles
BACross
Construction:
Steel panels and structural elements are constructed of Type 304 stainless steel. Seams between
panels inside the cold water basin are welded. The basin is leak tested at the factory and welded
seams are provided with a Five-Year leak-proof warranty. Casing panels and air inlet louvers are
constructed of corrosion and UV resistant fiberglass reinforced polyester (FRP). Each cooling tower
provided with the JE PREMIER SERIES
Power
Train*. This BAC engineered drive system consists of a specially designed powerband and two cast
aluminum sheaves located on minimum shaft centerline distances to maximize belt life. A cooling
tower duty fan motor, custom engineered for BAC to provide maximum performance for cooling tower
service, is provided and backed by BACs comprehensive Five-Year motor and fan drive warranty.
(*) Note: Model 31301A is provided with a gear fan drive system.
Custom Features and Options
O
p
e
n
C
o
o
l
i
n
g
T
o
w
e
r
s
D16
...because temperature matters
ENERGY-MISER
Fan System
The ENERGY-MISER
Fan System
Gear Drive System, Close-Coupled Motor
Gear Drive System,
Externally Mounted Motor
S
e
r
i
e
s
3
0
0
0
D17
Baltimore Aircoil Company
Low Sound Operation
The low sound levels generated by Series 3000 Cooling Towers make
them suitable for installation in most environments. For very sound
sensitive installations, the Series 3000 is available with a low sound fan
option that significantly reduces the sound levels generated from the
tower with minimal impact on thermal performance. The cooling tower
thermal performance with the low sound fan has been certified in
accordance with CTI Standard STD-201.
For extremely sound sensitive installations, factory designed, tested and
rated sound attenuation is available for both the air inlet and discharge of Series 3000 Cooling Towers.
Basinless Unit Construction
The basinless unit construction option enables Series
3000 Cooling Towers to be directly applied to new or
existing concrete cold water basins. This custom
feature, available exclusively on BAC Series 3000 Cooling
Towers, reduces maintenance costs by eliminating the
integral basin from traditional units. It simplifies piping and
pumping requirements of multi-cell installations and
provides a cost-effective solution for many field-erected
cooling tower replacement projects.
EASY CONNECT
Chamber
This exclusive BAC option reduces routine maintenance and simplifies
water inlet piping on the Series 3000. The BALANCE CLEAN
Chamber
features an integral strainer which prevents large debris from reaching the
hot water distribution basins. The BALANCE CLEAN
Chamber auto-
matically balances flow within each cell, eliminating the need for flow
balancing valves. The unique design of the water distribution system
enables all routine maintenance to be performed from the unit interior,
thereby eliminating the need to use the cooling tower fan deck as a
working surface to perform routine maintenance of the water distribution
system. A single water inlet connection, located on the side or bottom of
each unit, eliminates the need for overhead piping and piping supports.
Custom Features and Options
Unit with intake and discharge
sound attenuation
Basinless Series 3000 Cooling Tower
on a concrete basin
Integral strainer, BALANCE
CLEAN
Chamber option
Optional EASY CONNECT
Chamber
O
p
e
n
C
o
o
l
i
n
g
T
o
w
e
r
s
D18
...because temperature matters
Ladder, Safety Cage, Gate and Handrails
In the event the owner requires easy access to the cooling
tower fan deck, the Series 3000 can be furnished with ladders
extending from the top of the unit to the base, as well as safety
cages, safety gates, and handrail packages. All components are
designed to meet OSHA requirements. All access to the top of
the equipment must be made in accordance with applicable
governmental occupational safety standards.
External Service Platforms
For external service, louver face platforms, access door
platforms and fan deck extensions can be added to the cooling
tower when the unit is purchased or as an aftermarket item.
Safety cages and safety gates are also available. All
components are designed to meet OSHA requirements.
Internal Walkway and
Service Platform
A galvanized steel internal walkway is
available to provide a permanent working
surface for easy access to the strainer,
outlet, and make-up water assembly. For
access to the motor and drive assemblies
on two-piece units, an internal ladder and
upper service platform with handrails is
available. Safety gates are available for
all handrail openings. All components are
designed to meet OSHA requirements.
Vibration Cutout Switch
A factory mounted vibration cutout switch is available to effectively protect against equipment failure due
to excessive vibration of the mechanical equipment system. BAC can provide either a mechanical or
solid-state electronic vibration cutout switch in a NEMA 4 enclosure to ensure reliable protection.
Additional contacts can be provided to either switch type to activate an alarm.
Accessories
Internal ladder and
service platform
Internal walkway
External platform at louver face
S
e
r
i
e
s
3
0
0
0
D19
Baltimore Aircoil Company
Basin Heaters
Cooling towers exposed to below freezing ambient temperatures require protection to prevent freezing
of the water in the cold water basin when the unit is idle. Factory-installed heaters, which maintain
+40F (4.4C) water temperature, are a simple and inexpensive way of providing such protection.
Heater Sizing Data
Electric Water Level Control Package
The electric water level control replaces the standard
mechanical makeup valve when a more precise
water level control is required. This package consists
of a conductance-actuated level control mounted in
the basin and a solenoid activated valve in the
make-up water line. The valve is slow closing to
minimize water hammer.
Extended Lubrication Lines
Extended lubrication lines with grease fittings are available for lubrication of the fan shaft bearings.
Fittings are located inside the plenum area next to the access door.
High Temperature Wet Deck
If operation above 130F (54.4C) is anticipated, an optional high temperature wet deck material is
available which increases the maximum allowable entering water temperature to 135F (57.2C).
Accessories
Electric Water Level Control Package
No. of Heaters kW per Heater No. of Heaters kW per Heater
3240A thru 3379A 2 6 2 9
3412A thru 3527A 2 8 2 12
3473A thru 3672A 2 10 2 14
3728A thru 31056A 2 12 2 15
3583A thru 3725A 2 14 2 18
31132A thru 31301A 2 14 2 20
0F (-17.8C) Ambient Heaters
MODEL NUMBERS
-20F (-28.9C) Ambient Heaters
O
p
e
n
C
o
o
l
i
n
g
T
o
w
e
r
s
D20
...because temperature matters
Factory Mutual Approval
All multi-cell Series 3000 Cooling Towers are available with Factory Mutual (FM)
Approved construction as an option.
Air Inlet Screens
Wire mesh screens can be factory-installed over the
inlet louvers to prevent debris from entering the tower.
Basin Sweeper Piping
Basin sweeper piping provides an effective method of
preventing sediment from collecting in the cold water
basin of the tower. A complete piping system, including
nozzles, is provided in the tower basin for connection to
side stream filtration equipment (by others).
Side Outlet Depressed Sump
A side outlet depressed sump box is available for field installation below the base of the tower to
facilitate jobsite piping. The outlet connection is designed to mate with an ASME Class 150 flat face
flange. See the Connection Guide (page J2) for more information on standard and optional unit
connection types.
Velocity Recovery Stacks
Velocity recovery stacks are available on
the Series 3000 for incremental thermal
performance increases. This accessory can
be used to gain extra capacity in tight
layouts, while maintaining the same
footprint and unit horsepower, as well as
maintaining CTI certification. Field assembly
is required.
Basin Sweeper Piping
Velocity Recovery Stacks
S
e
r
i
e
s
3
0
0
0
D21
Baltimore Aircoil Company
Do not use for construction. Refer to factory certified dimensions. This brochure includes data current
at time of publication, which should be reconfirmed at the time of purchase. Up-to-date engineering data,
free product selection software, and more can be found at www.BaltimoreAircoil.com.
Notes:
1. Operating weight is for tower with the water level in the
cold water basin at overflow. If a lower operating weight is
needed to meet design requirements, your local BAC
Sales Representative can provide additional assistance.
2. 31301A is supplied with a gear fan drive system as
standard.
3. Models shipped with an optional gear drive or low sound
fan may have heights up to 10.5" greater than shown.
4. Refer to page D24 for dimensional reference drawings.
5. Nominal tons of cooling respresents 3 gpm of water from a
95F entering water temperature to an 85F leaving water
temperature at a 78F entering wet-bulb temperature.
Engineering Data
Single Cell Unit
3240A 240 10 62,790 14,770 6,790 6,790
3272A 272 15 71,340 14,900 6,920 6,920 8'-5 3/4" 18'-0 1/2" 9'-3 5/8" 8'-7 3/4"
3299A 299 20 78,110 14,960 6,980 6,980
3333A 333 20 85,720 15,750 7,260 7,260
3358A 358 25 91,960 15,780 7,290 7,290 8'-5 3/4" 18'-0 1/2" 10'-7 5/8" 9'-11 3/4"
3379A 379 30 97,400 15,830 7,340 7,340
3412A 412 25 103,700 18,580 8,420 8,420
3436A 436 30 109,830 18,630 8,470 8,470
3455A 455 25 112,250 19,480 8,740 8,740
3482A 482 30 118,880 19,530 8,790 8,790 9'-9 1/4" 20'-0 1/2" 12'-1 1/8" 11'-3 3/4"
3527A 527 40 130,160 19,690 8,950 8,950
3473A 473 25 118,870 23,090 10,190 10,190
3501A 501 30 125,900 23,140 10,240 10,240
3552A 552 30 136,170 25,690 10,800 10,800
3604A 604 40 149,090 25,850 10,960 10,960
3648A 648 50 159,950 25,860 10,970 10,970
3672A 672 60 166,020 27,060 12,180 12,180
3728A 728 40 178,860 32,060 13,770 8,720
3781A 781 50 191,890 32,070 13,780 8,730 11'-9 3/4" 21'-6 1/2" 16'-4 7/8" 15'-5 1/2"
3828A 828 60 203,230 32,290 13,990 8,940
3872A 872 50 206,630 35,030 14,500 8,800
3923A 923 60 218,840 35,250 14,710 9,010 11'-9 3/4" 21'-6 1/2" 19'-0 7/8" 18'-1 1/2"
3970A 970 75 230,080 36,530 16,000 10,300
3985A 985 60 229,950 40,240 15,560 9,460
31056A 1056 75 246,700 40,330 15,650 9,550
3583A 583 25 143,950 30,300 12,070 12,070
3618A 618 30 152,460 30,350 12,120 12,120
3676A 676 40 166,920 30,510 12,280 12,280
3725A 725 50 179,080 30,520 12,290 12,290
31132A 1132 75 267,880 41,290 16,610 10,230 13'-11 1/8" 24'-0 1/2" 19'-2 7/8" 18'-1 1/2"
31213A 1213 75 282,010 44,300 17,550 10,720
31301A
2
1301 100 302,580 46,590 19,840 13,010
DIMENSIONS
4
L W H
3
A OPERATING
1
SHIPPING
HEAVIEST
SECTION
WEIGHTS (lbs)
MODEL
NUMBER
NOMINAL
TONNAGE
5
MOTOR
HP
FAN
(CFM)
11'-9 3/4" 21'-6 1/2" 12'-2 1/8" 11'-3 3/4"
9'-11 3/4" 10'-9 1/8" 20'-0 1/2" 9'-9 1/4"
11'-9 3/4" 21'-6 1/2" 10'-10 1/8" 9'-11 3/4"
13'-11 1/8" 24'-0 1/2" 21'-10 7/8" 20'-9 1/2"
13'-11 1/8" 24'-0 1/2' 12'-3 1/8" 11'-3 3/4"
11'-9 3/4" 21'-6 1/2" 21'-8 7/8" 20'-9 1/2"
O
p
e
n
C
o
o
l
i
n
g
T
o
w
e
r
s
D22
...because temperature matters
Notes:
1. Operating weight is for tower with the water level in the
cold water basin at overflow. If a lower operating weight is
needed to meet design requirements, your local BAC
Sales Representative can provide additional assistance.
2. 31301A-2 is supplied with a gear fan drive system
as standard.
3. Models shipped with an optional gear drive or low sound
fan may have heights up to 10.5" greater than shown.
4. Refer to page D24 for dimensional reference drawings.
5. Nominal tons of cooling respresents 3 gpm of water from a
95F entering water temperature to an 85F leaving water
temperature at a 78F entering wet-bulb temperature.
Double Cell Unit
See page D85
for Engineering
Considerations.
3240A-2 480 (2) 10 125,580 29,540 13,580 6,790
3272A-2 544 (2) 15 142,680 29,800 13,840 6,920 17'-2" 18'-0 1/2" 9'-3 5/8" 8'-7 3/4"
3299A-2 598 (2) 20 156,220 29,920 13,960 6,980
3333A-2 666 (2) 20 171,440 31,500 14,520 7,260
3358A-2 716 (2) 25 183,920 31,560 14,580 7,290 17'-2" 18'-0 1/2" 10'-7 5/8" 9'-11 3/4"
3379A-2 758 (2) 30 194,800 31,660 14,680 7,340
3412A-2 824 (2) 25 207,400 37,160 16,840 8,420
3436A-2 872 (2) 30 219,660 37,260 16,940 8,470
3455A-2 910 (2) 25 224,500 38,960 17,480 8,740
3482A-2 964 (2) 30 237,760 39,060 17,580 8,790 19'-9" 20'-0 1/2" 12'-1 1/8" 11'-3 3/4"
3527A-2 1,054 (2) 40 260,320 39,380 17,900 8,950
3473A-2 946 (2) 25 237,740 46,180 20,380 10,190
3501A-2 1,002 (2) 30 251,800 46,280 20,480 10,240
3552A-2 1,104 (2) 30 272,340 51,380 21,600 10,800
3604A-2 1,208 (2) 40 298,180 51,700 21,920 10,960
3648A-2 1,296 (2) 50 319,900 51,720 21,940 10,970
3672A-2 1,344 (2) 60 332,040 54,120 24,360 12,180
3728A-2 1,456 (2) 40 357,720 64,120 27,540 8,720
3781A-2 1,562 (2) 50 383,780 64,140 27,560 8,730 23'-10" 21'-6 1/2" 16'-4 7/8" 15'-5 1/2"
3828A-2 1,656 (2) 60 406,460 64,580 27,980 8,940
3872A-2 1,744 (2) 50 413,260 70,060 29,000 8,800
3923A-2 1,846 (2) 60 437,680 70,500 29,420 9,010 23'-10" 21'-6 1/2" 19'-0 7/8" 18'-1 1/2"
3970A-2 1,940 (2) 75 460,160 73,060 32,000 10,300
3985A-2 1,970 (2) 60 459,900 80,480 31,120 9,460
31056A-2 2,112 (2) 75 493,400 80,660 31,300 9,550
3583A-2 1,166 (2) 25 287,900 60,600 24,140 12,070
3618A-2 1,236 (2) 30 304,920 60,700 24,240 12,120
3676A-2 1,352 (2) 40 333,840 61,020 24,560 12,280
3725A-2 1,450 (2) 50 358,160 61,040 24,580 12,290
31132A-2 2,264 (2) 75 535,760 82,580 33,220 10,230 28'-0 3/4" 24'-0 1/2" 19'-2 7/8" 18'-1 1/2"
31213A-2 2,426 (2) 75 564,020 88,600 35,100 10,720
31301A-2
2
2,602 (2) 100 605,160 93,180 39,680 13,010
DIMENSIONS
4
L W H
3
A OPERATING
1
SHIPPING
HEAVIEST
SECTION
WEIGHTS (lbs)
MODEL
NUMBER
NOMINAL
TONNAGE
5
MOTOR
HP
FAN
(CFM)
23'-10" 21'-6 1/2" 12'-2 1/8" 11'-3 3/4"
9'-11 3/4" 10'-9 1/8" 20'-0 1/2" 19'-9"
23'-10" 21'-6 1/2" 10'-10 1/8" 9'-11 3/4"
28'-0 3/4" 24'-0 1/2" 21'-10 7/8" 20'-9 1/2"
28'-0 3/4" 24'-0 1/2' 12'-3 1/8" 11'-3 3/4"
23'-10" 21'-6 1/2" 21'-8 7/8" 20'-9 1/2"
S
e
r
i
e
s
3
0
0
0
D23
Baltimore Aircoil Company
Do not use for construction. Refer to factory certified dimensions. This brochure includes data current
at time of publication, which should be reconfirmed at the time of purchase. Up-to-date engineering data,
free product selection software, and more can be found at www.BaltimoreAircoil.com.
Engineering Data
Notes:
1. The actual size of the inlet and outlet connection may vary with the design flow rate.
2. Unless otherwise indicated, all connections 3 and smaller are MPT, and connections 4 and larger are beveled for
welding and grooved to suit a mechanical coupling.
3. On double cell units, connections are the same size but are located on both ends of the unit.
B C D E F G J
3240A
3272A 8 1/16" 5'-8 1/4" 10'-4 1/2" 7'-1 1/4" 1/4" 4'-2 7/8" 8'-8 1/4" 1-0" (2) 6" 8" 8"
3299A
3333A
3358A 8 1/16" 6'-1 1/4" 10'-4 1/2" 7'-1 1/4" 1/4" 4'-2 7/8" 8'-8 1/4" 1-0" (2) 6" 8" 8"
3379A
3412A
3436A
3455A
3482A 9 1/8" 6'-6 3/4" 11'-4 1/2" 8'-1 1/4" 1-1/4" 4'-10 5/8" 9'-11 3/4" 1-1/2" (2)6" 10" 10"
3527A
3473A
3501A
3552A
3604A
3648A
3672A
3728A
3781A 9 1/8" 10'-4 1/2" 12'-1 1/2" 8'-10 1/4" 5'-10 7/8" 12'-0 1/4" 1-1/2" (2) 8" 12" 12"
3828A
3872A
3923A 9 1/8" 13-0 1/2" 12'-1 1/2" 8'-10 1/4" 5'-10 7/8" 12'-0 1/4" 1-1/2" (2) 8" 12" 12"
3970A
3985A
31056A
3583A
3618A
3676A
3725A
31132A 9 5/8" 13'-0 1/2" 13'-4 1/2" 10'-1 1/4" 5/8" 6'-11 5/16" 14'-1 5/8" 2" (2) 10" 14" 14"
31213A
31301A
5'-10 7/8" 1-1/2" 1-1/4"
6'-11 9/16" 14'-1 5/8"
5'-10 7/8" 12'-0 1/4"
1-1/4" 5'-10 7/8"
5/8"
12'-0 1/4"
9 1/8"
CONNECTION SIZES
1,3
2" (2) 10" 14" 14"
1-1/2" (2) 8" 12" 12" 9 1/8" 15'-8 1/2" 12'-1 1/2" 8'-10 1/4"
9 5/8" 15'-8 1/2" 13'-4 1/2" 10'-1 1/4"
6'-6 3/4" 12'-1 1/2" 8'-10 1/4"
8"
(2) 8" 10" 10"
1-1/2" (2) 6" 8"
9 1/8" 6'-6 3/4" 12'-1 1/2" 8'-10 1/4"
10" 9 1/8" 6'-6 3/4" 13'-4 1/2" 10'-1 1/4" 5/8" 6'-11 5/16" 14'-1 5/8" 1-1/2" (2) 8" 10"
1-1/2" (2) 8" 10"
8 1/16" 6'-1 1/4" 11'-4 1/2" 8'-1 1/4"
SINGLE
INLET OUTLET
1-1/4"
1-1/4"
1-1/4"
1-1/4" 4'-10 5/8" 9'-11 3/4"
10"
12'-0 1/4"
MODEL
NUMBER
DIMENSIONS
MAKE-UP
WATER
TOP
INLET
O
p
e
n
C
o
o
l
i
n
g
T
o
w
e
r
s
D24
...because temperature matters
Note:
3728A thru 31056A and 31132A thru 31301A ship in two sections per cell.
The top section is the heaviest and tallest.
Top section heights are:
3728A thru 3970A: 10' 3-18"
31132A: 10' 11-18"
3985A thru 31056A: 11' 7-18"
31213A: 12' 3-18"
31301A: 12' 6-12"
Double Cell Unit Single Cell Unit
See page D85
for Engineering
Considerations.
S
e
r
i
e
s
3
0
0
0
D25
Baltimore Aircoil Company
Concrete Basin Engineering Data
for Optional Basinless Units
Do not use for construction. Refer to factory certified dimensions. This brochure includes data current
at time of publication, which should be reconfirmed at the time of purchase. Up-to-date engineering data,
free product selection software, and more can be found at www.BaltimoreAircoil.com.
Note:
1. Purchaser to design, construct and furnish basin
(including anchor bolts) in accordance with requirements
given. Purchaser must also supply sump, overflow, drain,
cleanout and water make-up to suit requirements.
2. All anchor bolts shall be 3/4 diameter, 1-1/2 projection (+/- 1/4),
fully threaded. Bolt to have one nut and washer. Anchor bolt and
column bearing point locations and elevations must be
maintained +/- 1/8.
3. Pier dimensions shown are minimum bearing surfaces required
for the tower structure and do not include corner chamfers on the
concrete piers.
4. Wet deck to be located below the operating water level.
(see section A-A, next page)
5. Maximum operating weight does not include concrete basin or
water retained in the basin.
Single Cell Unit
MODEL
NUMBER
OPERATING
LOAD
VERTICAL
MAXIMUM
OPERATING
WEIGHT (lbs)
A B C D
3240A 2,420 9,690
3272A 2,460 9,820
3299A 2,470 9,880
3333A 2,670 10,670
3358A 2,680 10,700
3379A 2,690 10,750
3412A 3,130 12,510
3436A 3,140 12,560
3455A 3,350 13,410
3482A 3,370 13,460
3527A 3,410 13,620
3473A 3,770 15,070
3501A 3,780 15,120
3552A 4,100 16,140
3604A 4,140 16,570
3648A 4,150 16,580
3672A 4,450 17,780
3728A 5,640 22,570
3781A 5,650 22,580
3828A 5,700 22,800
3872A 6,390 25,540
3923A 6,440 25,760
3970A 6,760 27,040
3985A 7,690 30,750
31056A 7,710 30,840
3583A 3,100 18,630
3618A 3,110 18,680
3676A 3,140 18,840
3725A 3,140 18,850
31132A 4,940 29,620 14'-7 1/8" 24'-4 1/2" 7'-8 1/4" 9'-0"
31213A 5,440 32,630
31301A 5,820 34,920
9'-1 3/4" 18'-4 1/2" 9'-2 1/4" N/A
9'-2 1/4" N/A
10'-5 1/4" 20'-4 1/2" 10'-2 1/4" N/A
9'-1 3/4" 18'-4 1/2"
10'-5 1/4" 20'-4 1/2" 10'-2 1/4" N/A
12'-5 3/4" 21'-10 1/2" 10'-11 1/4" N/A
12'-5 3/4" 21'-10 1/2" 10'-11 1/4" N/A
12'-5 3/4" 21'-10 1/2" 10'-11 1/4" N/A
12'-5 3/4" 21'-10 1/2" 10'-11 1/4" N/A
12'-5 3/4" 21'-10 1/2" 10'-11 1/4" N/A
14'-7 1/8" 24'-4 1/2" 7'-8 1/4" 9'-0"
14'-7 1/8" 24'-4 1/2" 7'-8 1/4" 9'-0"
O
p
e
n
C
o
o
l
i
n
g
T
o
w
e
r
s
D26
Models 3240A thru Models 31056A
Models 3583A thru Models 31301A
All Models
AIR IN AIR IN
6" MIN.
7
5
/
8
"
1
0
5
/
8
"
M
I
N
.
3" MIN.
(TYP)
3
"
M
I
N
.
(
T
Y
P
)
PLAN VIEW OF BASIN
7
5
/
8
"
1
0
5
/
8
"
M
I
N
.
1'-5 7/8" MIN.
1'-2 7/8"
1'-5 7/8" MIN.
1'-2 7/8"
C
(6) 3/4" DIA.
ANCHOR BOLTS
B
A
A A
PLAN VIEW OF BASIN
8
1
/
4
"
1
1
1
/
4
"
M
I
N
.
1'-5 7/8" MIN.
1'-2 7/8"
1'-5 7/8" MIN.
1'-2 7/8"
C
B
A
6"
MIN.
C
6"
MIN.
8
1
/
4
"
1
1
1
/
4
"
M
I
N
.
3" MIN.
(TYP)
3
"
M
I
N
.
(
T
Y
P
)
D
A A
AIR IN AIR IN
(8) 3/4" DIA.
ANCHOR BOLTS
1
'-
6
"
SECTION A-A
1
'-
3
"
TOP OF PIERS
AND BASE OF
COOLING TOWER
OPERATING
WATER LEVEL
BASIN
DEPTH
SEE DETAIL A
DETAIL A
1
"
CONCRETE BASIN WALL SLOPE
BASIN
DEPTH
TOP OF PIERS AND
BASE OF COOLING
TOWER
OPERATING
WATER LEVEL
SEE DETAIL A
1
'-
6
"
SECTION A-A
1
'-
3
"
See page D85
for Engineering
Considerations.
...because temperature matters
S
e
r
i
e
s
3
0
0
0
D27
Baltimore Aircoil Company
Concrete Basin Engineering
Data for Basinless Units
Do not use for construction. Refer to factory certified dimensions. This brochure includes data current
at time of publication, which should be reconfirmed at the time of purchase. Up-to-date engineering data,
free product selection software, and more can be found at www.BaltimoreAircoil.com.
Double Cell Unit
MODEL
NUMBER
OPERATING
LOAD
VERTICAL
MAXIMUM
OPERATING
WEIGHT (lbs)
A B C D E
3240A-2 2,420 19,380
3272A-2 2,460 19,640
3299A-2 2,470 19,760
3333A-2 2,670 21,340
3358A-2 2,680 21,400
3379A-2 2,690 21,500
3412A-2 3,130 25,020
3436A-2 3,140 25,120
3455A-2 3,350 26,820
3482A-2 3,370 26,920
3527A-2 3,410 27,240
3473A-2 3,770 30,140
3501A-2 3,780 30,240
3552A-2 4,100 32,820
3604A-2 4,140 33,140
3648A-2 4,150 33,160
3672A-2 4,450 35,560
3728A-2 5,640 45,140
3781A-2 5,650 45,160
3828A-2 5,700 45,600
3872A-2 6,390 51,080
3923A-2 6,440 51,520
3970A-2 6,760 54,080
3985A-2 7,690 61,500
31056A-2 7,710 61,680
3583A-2 3,100 37,260
3618A-2 3,110 37,360
3676A-2 3,140 37,680
3725A-2 3,140 37,700
31132A-2 4,940 59,240 28'-8 3/4" 24'-4 1/2" 7'-8 1/4" 9'-0" 13'-2 5/8"
31213A-2 5,440 65,260
31301A-2 5,820 69,840
N/A
28'-8 3/4" 24'-4 1/2" 7'-8 1/4" 9'-0"
7'-10 1/2"
17'-10" 18'-4 1/2" 9'-2 1/4" N/A 7'-10 1/2"
17'-10" 18'-4 1/2" 9'-2 1/4" N/A
9'-2"
20'-5" 20'-4 1/2" 10'-2 1/4" N/A 9'-2"
20'-5" 20'-4 1/2" 10'-2 1/4" N/A
11'-2 1/2"
24'-6" 21'-10 1/2" 10'-11 1/4" N/A 11'-2 1/2"
24'-6" 21'-10 1/2" 10'-11 1/4" N/A
11'-2 1/2"
24'-6" 21'-10 1/2" 10'-11 1/4" N/A 11'-2 1/2"
24'-6" 21'-10 1/2" 10'-11 1/4" N/A
13'-2 5/8"
11'-2 1/2"
28'-8 3/4" 24'-4 1/2" 7'-8 1/4" 9'-0" 13'-2 5/8"
24'-6" 21'-10 1/2" 10'-11 1/4"
Note:
1. Purchaser to design, construct and furnish basin
(including anchor bolts) in accordance with requirements
given. Purchaser must also supply sump, overflow, drain,
cleanout and water make-up to suit requirements.
2. All anchor bolts shall be 3/4 diameter, 1 1-1/2 projection
(+/- 1/4), fully threaded. Bolt to have one nut and washer.
Anchor bolt and column bearing point locations and elevations
must be maintained +/- 1/8.
3. Pier dimensions shown are minimum bearing surfaces required
for the tower structure and do not include corner chamfers on the
concrete piers.
4. Base of the cooling tower to be located below the water.
5. Maximum operating weight does not include concrete basin or
water retained in the basin.
O
p
e
n
C
o
o
l
i
n
g
T
o
w
e
r
s
D28
...because temperature matters
Models 3240A-2 thru Models 31056A-2
Models 3583A-2 thru Models 31301A-2
All Models
6" MIN.
7
5
/
8
"
1
0
5
/
8
"
M
I
N
.
3" MIN.
(TYP)
3
"
M
I
N
.
(
T
Y
P
)
PLAN VIEW OF BASIN
7
5
/
8
"
1
0
5
/
8
"
M
I
N
.
1'-5 7/8" MIN.
1'-2 7/8"
1'-5 7/8" MIN.
1'-2 7/8"
C
(12) 3/4" DIA.
ANCHOR BOLTS
B
A
A A
9
3
/
4
"
E
E
AIR IN AIR IN
AIR IN AIR IN
6"
MIN.
8
1
/
4
"
1
1
1
/
4
"
M
I
N
.
3" MIN.
(TYP)
3
"
M
I
N
.
(
T
Y
P
)
PLAN VIEW OF BASIN
8
1
/
4
"
1
1
1
/
4
"
M
I
N
.
1'-5 7/8" MIN.
1'-2 7/8"
1'-5 7/8" MIN.
1'-2 7/8"
C
B
A
6"
MIN.
C D
A A
AIR IN
(16) 3/4" DIA.
ANCHOR BOLTS
AIR IN
E
1
1
"
E
AIR IN AIR IN
1
'-
6
"
SECTION A-A
1
'-
3
"
TOP OF PIERS
AND BASE OF
COOLING TOWER
OPERATING
WATER LEVEL
BASIN
DEPTH
SEE DETAIL A
DETAIL A
1
"
CONCRETE BASIN WALL SLOPE
BASIN
DEPTH
TOP OF PIERS AND
BASE OF COOLING
TOWER
OPERATING
WATER LEVEL
SEE DETAIL A
1
'-
6
"
SECTION A-A
1
'-
3
"
See page D85
for Engineering
Considerations.
S
e
r
i
e
s
3
0
0
0
D29
Baltimore Aircoil Company
The recommended support arrangement for the Series 3000 Cooling Tower consists of parallel I-beams
positioned as shown in the drawings. Besides providing adequate support, the steel also serves to
raise the unit above any solid foundation to assure access to the bottom of the tower. The Series 3000
may also be supported on columns at the anchor bolt locations shown in Plan A or Plan C. A minimum
bearing surface of twelve (12) square inches must be provided under each of the concentrated load
points (See Note 7, next page). To support a Series 3000 Cooling Tower on columns, or in an alternate
steel support arrangement, consult your BAC Representative.
See notes, next page.
Structural Support
L1 L2 W A B C D E
3240A 6,790 14,770 3,693
3272A 6,920 14,900 3,725 8'-5 3/4" 17'-2" 18'-0 1/2" 9'-4" 16'-4 1/2" 1 1/8" 8'-3 1/2" 4 3/4"
3299A 6,980 14,960 3,740
3333A 7,260 15,750 3,938
3358A 7,290 15,780 3,945 8'-5 3/4" 17'-2" 18'-0 1/2" 9'-4" 16'-4 1/2" 1 1/8" 8'-3 1/2" 4 3/4"
3379A 7,340 15,830 3,958
3412A 8,420 18,580 4,645
3436A 8,470 18,630 4,658
3455A 8,740 19,480 4,870
3482A 8,790 19,530 4,883 9'-9 1/4" 19'-9" 20'-0 1/2" 11'-4" 18'-4 1/2" 1 1/8" 9'-7" 4 3/4"
3527A 8,950 19,690 4,923
3473A 10,190 23,090 5,773
3501A 10,240 23,140 5,785
3552A 10,800 25,690 6,423
3604A 10,960 25,850 6,463 11'-9 3/4" 23'-10" 21'-6 1/2" 12'-10" 19'-10 1/2" 1 1/8" 11'-7 1/2" 4 3/4"
3648A 10,970 25,860 6,465
3672A 12,180 27,060 6,765
3728A 13,770 32,060 8,015
3781A 13,780 32,070 8,018 11'-9 3/4" 23'-10" 21'-6 1/2" 12'-10" 19'-10 1/2" 1 1/8" 11'-7 1/2" 4 3/4"
3828A 13,990 32,290 8,073
3872A 14,500 35,030 8,758
3923A 14,710 35,250 8,813 11'-9 3/4" 23'-10" 21'-6 1/2" 12'-10" 19'-10 1/2" 1 1/8" 11'-7 1/2" 4 3/4"
3970A 16,000 36,530 9,133
3985A 15,560 40,240 10,060
31056A 15,650 40,330 10,083
3583A 12,070 30,300 7,575
3618A 12,120 30,350 7,588
3676A 12,280 30,510 7,628 13'-11 1/8" 28'-0 3/4" 24'-0 1/2" 15'-4" 22'-4 1/2" 1 7/16" 13'-8 1/4" 5 3/8"
3725A 12,290 30,520 7,630
31132A 16,610 41,290 10,323 13'-11 1/8" 28'-0 3/4" 24'-0 1/2" 15'-4" 22'-4 1/2" 1 7/16" 13'-8 1/4" 5 3/8"
31213A 17,550 44,300 11,075
31301A 19,840 46,590 11,648
22'-4 1/2" 1 7/16" 13'-8 1/4" 5 3/8" 13'-11 1/8" 28'-0 3/4" 24'-0 1/2" 15'-4"
19'-10 1/2" 1 1/8" 11'-7 1/2" 4 3/4" 11'-9 3/4" 23'-10" 21'-6 1/2" 12'-10"
19'-10 1/2" 1 1/8" 11'-7 1/2" 4 3/4" 11'-9 3/4" 23'-10" 21'-6 1/2" 12'-10"
4 3/4" 11'-4"
WT. AT BOLT
HOLE
LOCATIONS
18'-4 1/2" 1 1/8" 9'-7"
WEIGHTS (LBS.)
9'-9 1/4" 19'-9" 20'-0 1/2"
SHIPPING
1
OPERATING
1,2
MODEL
NUMBER
DIMENSIONS
O
p
e
n
C
o
o
l
i
n
g
T
o
w
e
r
s
D30
...because temperature matters
Notes:
1. Weights are for a single cell. To obtain weights
for multi-cell units, multiply by the number
of cells.
2. Operating weight and weight loading are for a
single cell tower with water at overflow level in
the cold water basin.
3. Support beams and anchor bolts to be selected
and installed by parties other than BAC.
4. All support steel must be level at the top.
5. Beams must be selected in accordance with
accepted structural practice. Maximum
deflection of beam under unit to be 1/360 of
span, not to exceed 1/2 inch.
6. All single and double cell units can be furnished
with optional vibration isolation rail packages,
when required, to be installed between the tower
and supporting steel. The BAC standard
vibration isolation rail package is designed for
support Plan A for single cell units and support
Plan C for double cell units. Plan B rails are
available upon request. When determining the
length of the supporting steel, allow for the
length of the vibration rails, as they are
sometimes longer than the cooling tower
dimensions shown.
7. If point vibration isolation is used with multi-cell
towers, the isolators must be located under the
support steel, not between the support steel and
the cooling towers.
Double Cell Unit
Plan A Plan B
Plan C
Single Cell Unit
3/4" DIA. MOUNTING HOLES
(4 REQUIRED MODELS 324OA THRU 3725A)
(16 REQUIRED MODELS 3728A THRU 31301A)
INLET
L2
ADDITIONAL
ANCHOR BOLT
MODELS 3728A
THRU 31301A
3
C
D
B0LTS
UNIT OVERALL
W
AIR
INLET
AIR
INLET
AIR
UNIT OUTLINE
INLET
AIR
C
D
BOLTS
C
L
C
L
B0LTS
C
L
A
E
ADDITIONAL
ANCHOR BOLT
MODELS 3728A
THRU 31301A
3/4" DIA. MOUNTING HOLES
(4 REQUIRED MODELS 324OA THRU 3725A)
(8 REQUIRED MODELS 3728A THRU 31301A)
UNIT OUTLINE
C
AIR
INLET
BOLTS
UNIT OVERALL
W
BOLTS
AIR
INLET
C
3
A
D
C
L
C
L
L1
3/4" DIA. MOUNTING HOLES
(4 REQUIRED MODELS 324OA THRU 3725A)
(8 REQUIRED MODELS 3728A THRU 31301A)
INLET
AIR
INLET
5'2 5/8"
AIR
C
C
C
L
C
L
B
W
D
BOLTS
REQUIRED ON MODELS
3728A THRU 31301A
BOLTS
UNIT OUTLINE
UNIT OVERALL
WEIGHT GIVEN ON
PAGE D29 IS AT
MIDPOINT BETWEEN
TWO LOCATIONS
S
e
r
i
e
s
3
0
0
0
D31
Baltimore Aircoil Company
1.0 Cooling Tower
1.1 General: Furnish and install _____ factory-assembled,
induced draft, crossflow cooling tower(s) with vertical air
discharge, conforming in all aspects to the specifications,
schedules and as shown on the plans. Overall dimensions shall
not exceed approximately _____ ft (mm) long X ______ ft (mm)
wide X _____ ft (mm) high. The total connected fan horsepower
shall not exceed _____ HP (kW). The cooling tower(s) shall be
Baltimore Aircoil Model ______.
1.2 Thermal Capacity: The cooling tower(s) shall be warranted
by the manufacturer to cool _____ US gpm (lps) of water from
______ F(C) to _____ F(C) at _____ F(C) entering
wet-bulb temperature. Additionally, the thermal performance shall
be certified by the Cooling Technology Institute in accordance
with CTI Certification Standard STD-201. Lacking such
certification, a field acceptance test shall be conducted within the
warranty period in accordance with CTI Acceptance Test Code
ATC-105, by the Cooling Technology Institute or other qualified
independent third party testing agency. Manufacturers
performance guarantees or performance bonds without CTI
Certification or independent field thermal performance test shall
not be accepted. The cooling tower(s) shall comply with the
energy efficiency requirements of ASHRAE Standard 90.1.
1.3 Corrosion Resistant Construction (standard): Unless
otherwise noted in this specification, all steel panels and
structural members shall be constructed of heavy-gauge G-235
(Z700 metric) hot-dip galvanized steel with all edges given a
protective coating of zinc-rich compound.
(Alternate) 1.3 Corrosion Resistant Construction: Unless
otherwise noted in this specification, all steel panels and
structural members shall be protected with the BALTIBOND
F/85
F/78
F
Series 1500 Cooling Towers minimize the operating, installation, and maintenance costs associated with
both new and replacement cooling tower projects. The Series 1500 delivers independently verified, fully
rated thermal performance over a wide range of flow and temperature requirements. Standard design
features minimize the costs associated with enclosures, support requirements, electrical service, piping,
and rigging.
Series 1500 Cooling Towers
Ideal replacement unit
Single side air inlet
Low energy consumption
Low installed cost
Easy maintenance
Reliable year-round operation
Long service life
ASHRAE Standard 90.1 compliant
Five-year warranty on mechanical equipment
Series 1500 Open Cooling Towers
O
p
e
n
C
o
o
l
i
n
g
T
o
w
e
r
s
D36
...because temperature matters
S
e
r
i
e
s
1
5
0
0
D37
Baltimore Aircoil Company
Ideal Replacement Unit
Support Steel Units are designed to mount
directly on existing support steel of many cooling
towers (both crossflow and counterflow).
Electrical Service Fan motor configurations
can be supplied to match existing wiring.
Enclosures Units fit in most existing
enclosures with little or no modifications due to
the single air inlet design.
Low Energy Consumption
Evaporative cooling equipment minimizes the energy consumption of the entire system because it
provides lower operating temperatures. The owner saves money while conserving natural resources
and reducing environmental impact.
The Series 1500 provides the heat rejection required at the lowest possible energy input via:
High efficiency, low horsepower axial fans
High efficiency BACross
Power Train
Premium quality, solid-backed, multi-groove belt
Corrosion resistant cast aluminum sheaves
Heavy-duty bearings (280,000 hour average life)
Cooling tower duty fan motor
Five-year motor and
drive warranty
Low HP Axial Fan
Quiet operation
Corrosion resistant aluminum
Water Distribution System
Steel covers in easy to remove sections
Low pump head gravity distribution basin
Large orifice, non-clog nozzles
Integral strainer
BACross
Fan System
The ENERGY-MISER
Fan System
S
e
r
i
e
s
1
5
0
0
D43
Baltimore Aircoil Company
Service Platforms
For access to the motor and drive assemblies on Models
15296 through 15425, an internal ladder with or without
upper service platform with handrails is available. For
external service, louver face platforms and access door
platforms are options that can be added to the cooling tower
either when the unit is purchased or as an aftermarket item.
Safety gates are available for all handrail openings supplied
by BAC. All components are designed to meet OSHA
requirements.
Vibration Cutout Switch
A factory mounted vibration cutout switch is available to effectively protect against equipment failure
due to excessive vibration of the mechanical equipment system. BAC can provide either a mechanical
or solid-state electronic vibration cutout switch in a NEMA 4 enclosure to ensure reliable protection.
Additional contacts can be provided to either switch type to activate an alarm.
Basin Heaters
Cooling towers exposed to below freezing ambient temperatures require protection to prevent freezing
of the water in the cold water basin when the unit is idle. Factory-installed heaters, which maintain
+40F (4.4C) water temperature, are a simple and inexpensive way of providing such protection.
Heater Sizing Data
Accessories
External platform at louver face
Internal ladder and service platform Standard internal walkway
MODEL
NUMBER
0F (-17.8C) Ambient -20F (-28.9C) Ambient
15146 to 15282 8 kW 12 kW
15296 to 15425 12 kW 16 kW
O
p
e
n
C
o
o
l
i
n
g
T
o
w
e
r
s
D44
...because temperature matters
Electric Water Level Control Package
The electric water level control replaces the standard
mechanical make-up valve when a more precise
water level control is required. This package consists
of a conductance-actuated level control mounted in
the basin and a solenoid activated valve in the
make-up water line. The valve is slow closing to
minimize water hammer.
Extended Lubrication Lines
Extended lubrication lines are available for lubrication
of the fan shaft bearings. Fittings are located inside
the plenum area next to the access door.
High Temperature Wet Deck
If operation above 120F (48.9C) is anticipated, an
optional high temperature wet deck material is
available which increases the maximum allowable
entering water temperature to 135F (57.2C).
Air Inlet Screens
Wire mesh screens are available factory-installed
over the air inlet louvers to prevent debris from
entering the tower.
Basin Sweeper Piping
Basin sweeper piping is an effective method of
eliminating sediment that may collect in the cold
water basin of the tower. A complete piping system,
including nozzles, is provided for connection in the
tower basin to side stream filtration equipment
(by others).
Side Outlet Depressed Sump Box
A side outlet depressed sump box is available for
field installation below the base of the tower to
facilitate jobsite piping. The outlet connection is
designed to mate with an ASME Class 150 flat face
flange. See the Connection Guide (page J2) for more
information on standard and optional unit connection types.
Electric Water Level Control Package
Grease fittings at the access door (inset) & bearings
with the extended lubrication line option
Basin sweeper piping
S
e
r
i
e
s
1
5
0
0
D45
Baltimore Aircoil Company
Do not use for construction. Refer to factory certified dimensions. This brochure includes data current
at time of publication, which should be reconfirmed at the time of purchase. Up-to-date engineering data,
free product selection software, and more can be found at www.BaltimoreAircoil.com.
Notes:
1. Operating weight is for tower with water level in the cold water
basin at overflow. If a lower operating weight is needed to
meet design requirements, your local BAC sales
representative can provide additional assistance.
2. The actual size of the inlet and outlet connection may vary
with the design flow rate. Consult unit print for dimensions.
3. Unless otherwise indicated, all connections 3" and smaller are
MPT. Connections 4" and larger are beveled for welding and
mechanically grooved.
4. The heaviest section for all models except 15214 through
15282 is the upper section. Models 15146 to 15219 ship
in one piece.
5. Models 15296 through 15425 2 1/8
6. Models 15296 through 15425 8
7. Models 15146 through 15219 and 15296 through
15425 2 3/4
8. Models 15296 through 15425 1 1/2
9. Nominal tons of cooling respresents 3 gpm of water from a
95F entering water temperature to an 85F leaving water
temperature at a 78F entering wet-bulb temperature.
Engineering Data
Single Cell Unit
8" WATER OUTLET
2
5
8
6 MAKE UP
WATER INLET AIR OUT
AIR IN
AIR IN
ACCESS DOOR
OVERFLOW
DRAIN
7
6
L H A C
15146 146 7.5 N/A 40,320 7,920 3,940 3,940
15160 160 10 N/A 44,190 7,940 3,960 3,960
15176 176 15 N/A 48,160 7,990 4,010 4,010
15162 162 7.5 N/A 43,080 8,610 4,200 4,200
15177 177 10 N/A 47,070 8,630 4,220 4,220
15201 201 15 N/A 53,450 8,690 4,280 4,280
15219 219 20 N/A 58,240 8,710 4,300 4,300
15200 200 10 N/A 52,320 11,430 5,350 2,770
15227 227 15 N/A 59,380 11,490 5,410 2,780
15250 250 20 N/A 65,400 11,510 5,430 2,800
15214 214 10 N/A 56,610 12,450 5,640 2,920
15245 245 15 N/A 64,810 12,510 5,700 2,920
15270 270 20 N/A 71,420 12,530 5,720 2,920
15282 282 25 N/A 74,600 12,610 5,800 2,920
15296 296 15 (2) 7.5 77,440 15,540 6,750 3,540
15325 325 20 (2) 10 85,030 15,590 6,800 3,590
15350 350 25 (2) 15 91,560 15,640 6,850 3,640
15368 368 30 (2) 15 96,280 15,660 6,870 3,660
15310 310 15 (2) 7.5 82,000 17,050 7,070 3,540
15340 340 20 (2) 10 89,940 17,100 7,120 3,590
15365 365 25 (2) 15 96,550 17,150 7,170 3,640
15385 385 30 (2) 15 101,840 17,180 7,200 3,670
15425 425 40 (2) 20 112,430 17,450 7,470 3,940
SHIPPING
HEAVIEST
SECTION
DIMENSIONS WEIGHTS (lbs)
MODEL
NUMBER
NOMINAL
TONNAGE
9
MOTOR HP
AIRFLOW
(CFM)
15'-1"
11'-1"
9'-9"
8'-6" 14'-3" 7'-5" 13'-9"
OPERATING
1
IND. FAN
MOTOR
OPTION
8'-6" 15'-7" 8'-9"
8'-6" 11'-7" N/A
N/A 10'-3" 8'-6"
INLET
CONN.
2
6"
12'-1" 15'-7" 8'-9" 15'-1"
12'-1" 14'-3" 7'-5" 13'-9"
8"
6"
8"
6"
6"
O
p
e
n
C
o
o
l
i
n
g
T
o
w
e
r
s
D46
...because temperature matters
Notes:
1. Operating weight is for tower with water level in the cold water
basin at overflow. If a lower operating weight is needed to
meet design requirements, your local BAC sales
representative can provide additional assistance.
2. The actual size of the inlet and outlet connection may vary
with the design flow rate. Consult unit print for dimensions.
3. Unless otherwise indicated, all connections 3" and smaller are
MPT. Connections 4" and larger are beveled for welding and
mechanically grooved.
4. The heaviest section for all models except 15214 through
15282 is the upper section. Models 15146 to 15219 ship
in one piece.
5. Models 15296 through 15425 2 1/8
6. Models 15296 through 15425 8
7. Models 15146 through 15219 and 15296 through
15425 2 3/4
8. Models 15296 through 15425 1 1/2
9. Nominal tons of cooling respresents 3 gpm of water from a
95F entering water temperature to an 85F leaving water
temperature at a 78F entering wet-bulb temperature.
Multi-Cell Units
8" WATER OUTLET
5
8
WATER INLET
MAKE UP
AIR IN
AIR IN
AIR OUT
ACCESS DOORS
(BOTH ENDS)
OVERFLOW
DRAIN
CONNECTIONS SAME BOTH ENDS
6
7
5
See page D85
for Engineering
Considerations.
L H A C D
15146-2 292 (2) 7.5 N/A 80,640 15,840 7,880 3,940
15160-2 320 (2) 10 N/A 88,380 15,880 7,920 3,960
15176-2 352 (2) 15 N/A 96,320 15,980 8,020 4,010
15162-2 324 (2) 7.5 N/A 86,160 17,220 8,400 4,200
15177-2 354 (2) 10 N/A 94,140 17,260 8,440 4,220
15201-2 402 (2) 15 N/A 106,900 17,380 8,560 4,280
15219-2 438 (2) 20 N/A 116,480 17,420 8,600 4,300
15200-2 400 (2) 10 N/A 104,640 22,860 10,700 2,770
15227-2 454 (2) 15 N/A 118,760 22,980 10,820 2,780
15250-2 500 (2) 20 N/A 130,800 23,020 10,860 2,800
15214-2 428 (2) 10 N/A 113,220 24,900 11,280 2,920
15245-2 490 (2) 15 N/A 129,620 25,020 11,400 2,920
15270-2 540 (2) 20 N/A 142,840 25,060 11,440 2,920
15282-2 564 (2) 25 N/A 149,200 25,220 11,600 2,920
15296-2 592 (2) 15 (4) 7.5 154,880 31,080 13,500 3,540
15325-2 650 (2) 20 (4) 10 170,060 31,180 13,600 3,590
15350-2 700 (2) 25 (4) 15 183,120 31,280 13,700 3,640
15368-2 736 (2) 30 (4) 15 192,560 31,320 13,740 3,660
15310-2 620 (2) 15 (4) 7.5 164,000 34,100 14,140 3,540
15340-2 680 (2) 20 (4) 10 179,880 34,200 14,240 3,590
15365-2 730 (2) 25 (4) 15 193,100 34,300 14,340 3,640
15385-2 770 (2) 30 (4) 15 203,680 34,360 14,400 3,670
15425-2 850 (2) 40 (4) 20 224,860 34,900 14,940 3,940
13'-9" 6'-5/8" (2) 8"
24'-5" 15'-7" 8'-9" 15'-1" 6'-5/8" (2) 8"
13'-9" 4'-3" (2) 6"
17'-2" 15'-7" 8'-9" 15'-1" 4'-3" (2) 6"
9'-9" 4'-3" (2) 6"
17'-2" 11'-7" N/A 11'-1" 4'-3" (2) 6"
24'-5" 14'-3" 7'-5"
17'-2" 14'-3" 7'-5"
17'-2" 10'-3" N/A
INLET
CONN.
2
MODEL
NUMBER
NOMINAL
TONNAGE
9
MOTOR HP
AIRFLOW
(CFM)
IND. FAN
MOTOR
OPTION SHIPPING
HEAVIEST
SECTION
DIMENSIONS WEIGHTS (lbs)
OPERATING
1
S
e
r
i
e
s
1
5
0
0
D47
Baltimore Aircoil Company
The recommended support arrangement for the Series 1500 Cooling Tower consists of parallel I-beams
positioned as shown in the following drawing. Besides providing adequate support, the steel also serves to
raise the unit above any solid foundation to ensure access to the bottom of the tower. The Series 1500 may
also be supported on columns at the anchor bolt locations shown in Plan A or Plan C. A minimum 12x12
bearing surface must be provided under each of the concentrated load points (See Note 5). To support a
Series 1500 Cooling Tower on columns or in an alternate steel support arrangement, consult your local
BAC Representative.
Structural Support
Notes:
1. Support beams and anchor bolts are to be selected and installed
by others.
2. All supporting steel must be level at the top.
3. Beams must be selected in accordance with accepted structural
practice. Maximum deflection of beam under unit to be 1/360 of
span, not to exceed 1/2 inch.
4. All units can be furnished with an optional vibration isolation
package, if required, to be installed between the tower and
supporting steel. The BAC vibration isolation package is designed
for units on support plan A/C. When determining the length of
steel beams, allow for the length of vibration isolation rails, as they
may be longer than the tower length shown above.
5. If point vibration isolation is used with multi-cell towers, the
isolators must be located under the supporting steel, not between
the support steel and the cooling towers.
6. If existing vibration isolator rails are being reused on a
replacement project, springs/elastomers must be resized to match
the new cooling tower weight distribution. Consult your local BAC
Representative for details.
7. When using Alternative Plan A support arrangements with optional
bottom water outlet, size and location restrictions will apply to
water outlet piping. Consider the Cantilevered Plan support
arrangement or consult your local BAC Representative for details.
Plan A/C: Single-Cell and Multi-Cell Units
Plan A/C
Plan B
Plan B: Single-Cell Units Only
MODEL NUMBER A L1 L
15146 to 15282 6 9-3/4 8 5-3/4 -
15296 to 15425 10 5-1/4 12 1-1/4 -
15146-2 to 15282-2 6 9-3/4 8 5-3/4 17 2
15296-2 to 15425-2 10 5-1/4 12 1-1/4 24 5
MODEL NUMBER A L
15146 to 15282 8 3-1/2 8 5-3/4
15296 to 15425 11 11 12 1-1/4
O
p
e
n
C
o
o
l
i
n
g
T
o
w
e
r
s
D48
...because temperature matters
See Notes on previous page.
For replacement installations, the Series 1500 Cooling Tower has been designed to match the supporting
steel of most existing counterflow and crossflow cooling towers without modifications. Shown below are the
most common steel support arrangements which can be accommodated by the Series 1500. If individual
point support is required, or if steel arrangement is not as shown below, consult your local BAC
Representative for assistance.
Structural Support Alternatives
Alternative Plan A: Typical Dimensions for Single-Cell, Two-Cell Units
Cantilevered Plan A: Typical Dimensions for Single-Cell, Two-Cell Units
Alternative Plan A
Cantilevered Plan A
MODEL NUMBER UNIT REPLACED A B C L1
15146 to 15282 VLT/VST 8 9-1/8 1 6-7/16 8 3-1/2 8 5-3/4
VLT/VST/VXT 8 11-1/4 1 5-3/8 11 11 12 1-1/4
VXT/VXMT 9 7-1/2 1 1-1/4 11 11 12 1-1/4
CFT 8 0 1 11 8 3-1/2 8 5-3/4
Series 3000 8 3-1/4 1 9-3/8 8 3-1/2 8 5-3/4
CFT 8 0 1 11 11 11 12 1-1/4
Series 3000 9 6 1 2 11 11 12 1-1/4
15296 to 15425
15146 to 15282
15296 to 15425
MODEL NUMBER UNIT REPLACED A B C1 C2 L1
15146 to 15282 VLT/VST 8 9-1/8 2 11-3/4 8 3-1/2 6 9-3/4 8 5-3/4
VLT/VST/VXT 8 11-1/4 2 9-5/8 11 11 10 5-1/4 12 1-1/4
VXT/VXMT 9 7-1/2 2 1-3/8 11 11 10 5-1/4 12 1-1/4
CFT 8 0 3 8-7/8 8 3-1/2 6 9-3/4 8 5-3/4
Series 3000 8 3-1/4 3 5-5/8 8 3-1/2 6 9-3/4 8 5-3/4
CFT 8 0 3 8-7/8 11 11 10 5-1/4 12 1-1/4
Series 3000 9 6 2 2-7/8 11 11 10 5-1/4 12 1-1/4
15146 to 15282
15296 to 15425
15296 to 15425
S
e
r
i
e
s
1
5
0
0
D49
Baltimore Aircoil Company
1.0 Cooling Tower
1.1 General: Furnish and install _____ factory-assembled,
induced draft, crossflow cooling tower(s) with vertical air
discharge conforming in all aspects to the specifications,
schedules and as shown on the plans. Overall dimensions shall
not exceed approximately _____ft (mm) long x _____ ft (mm)
wide x _____ ft (mm) high. The total connected fan horsepower
shall not exceed _____ HP(kW). The cooling tower(s) shall be
Baltimore Aircoil Model
__________ .
1.2 Thermal Capacity: The cooling tower(s) shall be warranted
by the manufacturer to cool _____ US gpm (lps) of water from
___ F(C) to ___ F(C) at ___ F(C) entering wet-bulb
temperature. Additionally, the thermal performance shall be
certified by the Cooling Technology Institute in accordance with
CTI Certification Standard STD-201. Lacking such certification, a
field acceptance test shall be conducted within the warranty
period in accordance with CTI Acceptance Test Code ATC-105,
by the Cooling Technology Institute or other qualified
independent third party testing agency. A manufacturers
performance guarantee or performance bond without CTI
Certification or independent field thermal performance test shall
not be accepted. The cooling tower shall comply with the energy
efficiency requirements of ASHRAE Standard 90.1.
1.3 Corrosion Resistant Construction (standard): Unless
otherwise noted in this specification, all steel panels and
structural members shall be constructed of heavy-gauge G-235
(Z700 metric) galvanized steel with all edges given a protective
coating of zinc-rich compound.
(Alternate 1.3) Corrosion Resistant Construction: Unless
otherwise noted in this specification, all steel panels and
structural members must be protected with the BALTIBOND
F/85
F/78
F
FXT Cooling Towers deliver independently verified, fully rated thermal performance over a wide range of flow
and temperature requirements. Standard design features satisfy todays environmental concerns, minimize
installation costs, maximize operating reliability, and simplify maintenance requirements.
FXT Cooling Towers
Low energy consumption
Low installed cost
Easy maintenance
Long service life
ASHRAE Standard 90.1 compliant
Five-year warranty on mechanical equipment
FXT
Cooling Towers
O
p
e
n
C
o
o
l
i
n
g
T
o
w
e
r
s
D54
...because temperature matters
F
X
T
D55
Baltimore Aircoil Company
Low Energy Consumption
Evaporative cooling equipment minimizes the energy consumption of the entire system because it
provides lower operating temperatures. The owner saves money while conserving natural resources
and reducing environmental impact.
The FXT provides the heat rejection required at the lowest possible energy input via:
High efficiency, low horsepower axial fans
High efficiency BACross
OUTLET
FXT-6 6 1/3 2,400 2' 1/8" 6' 9-3/8" 4' 7-7/8" 22 5/8" 7" 1' 8-1/2" 980 370 3" 3"
FXT-7.5 7.5 1/2 3,000 2' 1/8" 6' 9-3/8" 4' 7-7/8" 22 5/8" 7" 1' 8-1/2" 980 370 3" 3"
FXT-11 11 1/2 4,400 3' 1/8" 6' 9-7/8" 4' 7-7/8" 22 5/8" 7" 1' 8-1/2" 1,420 470 3" 3"
FXT-16 16 1/2 5,700 3' 1/8" 6' 10-7/8" 5' 11-7/8" 19 3/4" 7 1/2" 1' 8-1/2" 1,330 570 4" 4"
FXT-20 20 1 7,100 3' 1/8" 6' 10-7/8" 5' 11-7/8" 19 3/4" 7 1/2" 1' 8-1/2" 1,350 590 4" 4"
FXT-26 26 1 9,200 4' 6-1/8" 7' 7-7/8" 5' 11-7/8" 19 3/4" 6 7/8" 1' 8" 2,080 940 4" 4"
FXT-30 30 1 1/2 10,600 4' 6-1/8" 7' 7-7/8" 5' 11-7/8" 19 3/4" 6 7/8" 1' 8" 2,090 950 4" 4"
FXT-33 33 2 11,700 4' 6-1/8" 7' 7-7/8" 5' 11-7/8" 19 3/4" 7 7/8" 1' 8" 2,090 950 4" 4"
FXT-38 38 1 1/2 12,100 4' 6-1/8" 7' 7-7/8" 7' 3-1/4" 16 7/8" 7 7/8" 1' 10-1/2" 2,420 1,000 6" 6"
FXT-42 42 2 13,400 4' 6-1/8" 7' 7-7/8" 7' 3-1/4" 16 7/8" 7 7/8" 1' 10-1/2" 2,420 1,000 6" 6"
FXT-47 47 3 15,000 4' 6-1/8" 7' 7-7/8" 7' 3-1/4" 16 7/8" 7 7/8" 1' 10-1/2" 2,440 1,020 6" 6"
FXT-58 58 3 18,500 6' 1/8" 7' 7-7/8" 7' 3-1/4" 16 7/8" 7 7/8" 1' 10-1/2" 3,140 1,220 6" 6"
FXT-68 68 5 21,700 6' 1/8" 7' 7-7/8" 7' 3-1/4" 16 7/8" 7 7/8" 1' 10-1/2" 3,150 1,230 6" 6"
WEIGHTS (LBS) CONNECTION SIZES
MODEL
NUMBER
MOTOR
HP
AIRFLOW
(CFM)
DIMENSIONS
NOMINAL
TONNAGE
3
O
p
e
n
C
o
o
l
i
n
g
T
o
w
e
r
s
D62
...because temperature matters
Models FXT-74 to 268
7' - 3 3/8"
Notes:
1. Unless otherwise indicated, all connections 6 and smaller are MPT and connections 8 and larger are beveled for welding.
2. Operating weight is for tower with water level in the cold water basin at overflow.
3. Nominal tons of cooling respresents 3 gpm of water from a 95F entering water temperature to an 85F leaving water
temperature at a 78F entering wet-bulb temperature.
Inlet piping must rest on the flow
divider located 7/8 below the top of the
water distribution box. The inlet piping
to the distribution box must be the
correct size, as indicated below.
See page D85
for Engineering
Considerations.
L H A B C
OPERATING
2
SHIPPING INLET
OUTLET
FXT-74 74 3 21,800 6' 1/8" 8' 4" 4' 1-3/8" 8 1/2" 2' 1-1/8" 4,230 1,720 8" 8"
FXT-87 87 5 25,600 6' 1/8" 8' 4" 4' 1-3/8" 8 1/2" 2' 1-1/8" 4,240 1,730 8" 8"
FXT-99 99 7 1/2 29,100 6' 1/8" 8' 4" 4' 1-3/8" 8 1/2" 2' 1-1/8" 4,280 1,770 8" 8"
FXT-115 115 5 33,900 9' 1-1/8" 8' 4" 4' 1-3/8" 8 1/2" 2' 1-1/8" 6,080 2,220 8" 8"
FXT-130 130 7 1/2 38,300 9' 1-1/8" 8' 4" 4' 1-3/8" 8 1/2" 2' 1-1/8" 6,120 2,260 8" 8"
FXT-142 142 10 41,800 9' 1-1/8" 8' 4" 4' 1-3/8" 8 1/2" 2' 1-1/8" 6,160 2,300 8" 8"
FXT-160 160 7 1/2 47,100 12' 1/8" 8' 4" 4' 1-3/8" 8 1/2" 2' 1-1/8" 8,030 2,880 8" 8"
FXT-175 175 10 51,500 12' 1/8" 8' 4" 4' 1-3/8" 8 1/2" 2' 1-1/8" 8,070 2,920 8" 8"
FXT-200 200 15 58,900 12' 1/8" 8' 4" 4' 1-3/8" 8 1/2" 2' 1-1/8" 8,120 2,970 8" 8"
FXT-216 216 10 56,400 12' 1/8" 11' 3' 7-3/4" 8 1/2" 2' 3-1/8" 9,420 3,560 8" 8"
FXT-250 250 15 65,300 12' 1/8" 11' 3' 7-3/4" 8 1/2" 2' 3-1/8" 9,470 3,610 8" 8"
FXT-268 268 20 70,000 12' 1/8" 11' 3' 7-3/4" 8 1/2" 2' 3-1/8" 9,490 3,630 8" 8"
WEIGHTS (LBS) CONNECTION SIZES
MODEL
NUMBER
MOTOR
HP
AIRFLOW
(CFM)
DIMENSIONS
NOMINAL
TONNAGE
3
F
X
T
D63
Baltimore Aircoil Company
1.0 Cooling Tower
1.1 General: Furnish and install ___ factory-assembled,
forced-draft, crossflow cooling tower(s). The tower(s) shall have
air entry on one side only. The tower(s) shall have the fan and
all moving parts located in the dry entering airstream to provide
greater reliability and long life. Overall dimensions shall not
exceed approximately ____ft (mm) long x ____ft (mm) wide, with
an overall height not exceeding ____ft (mm). The total
connected fan horsepower shall not exceed ___ HP (kW). The
cooling tower shall be Baltimore Aircoil Model FXT _____.
1.2 Thermal Capacity: The cooling tower(s) shall be warranted
by the manufacturer to cool _____ US gpm (lps) of water from
___F (C) to ___F (C) at ___F (C) entering wet-bulb
temperature. Additionally, the performance shall be certified by
the Cooling Technology Institute in accordance with CTI
Certification Standard STD-201. Lacking such certification, a field
acceptance test shall be conducted within the warranty period in
accordance with CTI Acceptance Test Code ATC-105, by the
Cooling Technology Institute or other CTI-accredited independent
testing agency. The cooling tower(s) shall comply with the
energy efficiency requirements of ASHRAE Standard 90.1-2001.
1.3 Corrosion Resistant Construction (standard): Unless
otherwise noted in this specification, all steel panels and
structural members shall be constructed of heavy-gauge, G-235
(Z700 metric) hot-dip galvanized steel with all cut edges given a
protective coating of zinc-rich compound.
(Alternate) 1.3 BALTIBOND
F/85
F/78
F
Series V Cooling Towers deliver independently verified, fully rated thermal performance over a wide range of
flow and temperature requirements. The Series V can be installed indoors and is available in a low profile
version to accommodate limited ceiling or enclosure heights. It is also suitable for high temperature applica-
tions with entering water temperatures of up to 170F. The Series V minimizes sound levels and installation
costs, provides year-round operating reliability, and simplifies maintenance requirements.
Series V Cooling Towers
Suitable for indoor and outdoor installations
Low profile models available
Suitable for high temperature applications
Low sound
Single side air inlet
Low energy consumption
Low installed cost
Easy maintenance
Reliable year-round operation
Long service life
ASHRAE Standard 90.1 compliant
Five-year warranty on mechanical equipment
Series V Cooling Towers
O
p
e
n
C
o
o
l
i
n
g
T
o
w
e
r
s
D66
...because temperature matters
S
e
r
i
e
s
V
D67
Baltimore Aircoil Company
Installation and Application Flexibility
Indoor Installations Centrifugal fans can overcome the static pressure imposed by external
ductwork, allowing the Series V to be installed indoors.
Low Profile Models - Motors and drives of low
profile units are adjacent to the casing section to
yield models suitable for use in height sensitive
installations. Low profile models are available in
capacities from 16 to 272 nominal tons, which
correspond to heights of 5 1-1/4 and
8 1-13/16, respectively.
High Temperature Applications A range of wet
deck and construction options are available to
accommodate entering water temperatures of up
to 170F.
Low Sound
Centrifugal Fan - Centrifugal fans have inherently low sound characteristics.
Single Air Inlet - Particularly sound-sensitive areas can be accommodated by facing the quiet
blank-off panel to the sound-sensitive direction.
Low Energy Consumption
Evaporative Cooling Equipment - Minimizes the energy consumption of the entire system
because it provides lower operating temperatures. The owner saves money while conserving natural
resources and reducing environmental impact.
Low Installed Cost
Support All models mount directly on two parallel I-beams and ship complete with motors
and drives factory-installed and aligned.
Modular Design Large models ship in multiple sections to minimize the size and weight of the
heaviest lift, allowing for the use of smaller, less costly cranes.
Benefits
Low profile unit shown in contrast
to a standard unit
O
p
e
n
C
o
o
l
i
n
g
T
o
w
e
r
s
D68
...because temperature matters
Easy Maintenance
Internal Access - The interior of the unit is easily
accessible for adjusting the float valve, cleaning the
strainer or flushing the basin.
Reliable Year-Round Operation
V-Belt Drive The fans, motor, and drive system are located outside of the moist
discharge airstream, protecting them from moisture, condensation and icing.
Backed by a five-year fan drive and motor warranty, these units are suitable for
year-round operation.
Long Service Life
Materials of Construction Various materials are available to meet the corrosion resistance,
unit operating life, and budgetary requirements of any project (see page D71 for construction options).
The water level control is easily
reached from the access door
External V-Belt Drive System (shown here with panel removed)
S
e
r
i
e
s
V
D69
Baltimore Aircoil Company
Upper Section:
VT0 & VT1 Models
Lower Section:
VT0 & VT1 Models
Construction Details
VT0 and VT1 Models
1
2
3
4
5
6
7
O
p
e
n
C
o
o
l
i
n
g
T
o
w
e
r
s
D70
...because temperature matters
Heavy-Duty Construction
G-235 (Z700 metric) hot-dip galvanized steel
panels
Fan Drive System
V-belt drive
Heavy-duty bearings (280,000 hour
average life)
Cooling tower duty fan motor
Five-year motor and drive
warranty
Low Sound Centrifugal Fan(s)
Quiet operation
Water Distribution System
Schedule 40 PVC spray header and branches
Large orifice, non-clog nozzles
Grommetted for easy maintenance
BACount
Corrosion Protection
System).
Optional Water-Contact Stainless Steel Construction:
A cost effective alternative to all stainless steel construction, only components in the cooling tower
that are exposed to the recirculating water are provided in Type 304 stainless steel. The remaining
components are constructed of the base material of construction (galvanized steel or the
BALTIBOND
Fan System
The ENERGY-MISER
Fan System
Unit with intake and discharge sound attenuation
S
e
r
i
e
s
V
D73
Baltimore Aircoil Company
Accessories
External Access Options
(VT0 and VT1 Models Only)
VT0 and VT1 models can be furnished with platforms,
ladders extending from the top of the unit to the base, as
well as safety cages, safety gates and handrail packages
to meet OSHA requirements. All access to the top of the
equipment must be made in accordance with applicable
governmental occupational safety standards.
NOTE: When these access options are employed, the
tower must be equipped with steel drift eliminators.
Vibration Cutout Switch
A factory mounted vibration cutout switch is available to effectively protect against equipment failure
due to excessive vibration of the mechanical equipment system. BAC can provide either a mechanical
or solid-state electronic vibration cutout switch in a NEMA 4 enclosure to ensure reliable protection.
Additional contacts can be provided to either switch type to activate an alarm.
Basin Heaters
Cooling towers exposed to below freezing ambient temperatures require protection to prevent freezing
of the water in the cold water basin when the unit is idle. Factory installed heaters, which maintain
+40F (4.4C) water temperature, are a simple and inexpensive way of providing such protection.
Optional External Platform
No. of HEATERS kW per HEATER No. of HEATERS kW per HEATER
VTL-016 thru 039 1 2 1 2
VTL-045 thru 079 1 3 1 4
VTL-082 thru 095 1 4 1 5
VTL-103 thru 137 1 5 1 7
VTL-152 thru 227 1 7 1 9
VTL-245 thru 272 1 9 1 12
VT0-12 thru 57 1 2 1 2
VT0-65 thru 88 1 2 1 3
VT0-102 thru 176 1 3 1 5
VT1-N209 thru N255 1 5 1 7.5
VT1-N301 thru N395 1 7 1 10
VT1-N418 thru N510 2 5 2 7.5
VT1-275 thru 415 1 8 1 10
VT1-416 thru 600 1 12 2 7.5
VT1-550 thru 830 2 8 2 10
VT1-825 thru 1335 3 8 3 10
MODEL NUMBER
0F (-17.8C) AMBIENT HEATERS -20F (-29.8C) AMBIENT HEATERS
O
p
e
n
C
o
o
l
i
n
g
T
o
w
e
r
s
D74
...because temperature matters
Electric Water Level Control Package
The electric water level control replaces the standard mechanical
makeup valve when a more precise water level control is
required. This package consists of a conductance-actuated level
control mounted in the basin and a solenoid activated valve in
the make-up water line. The valve is slow closing to minimize
water hammer.
Extended Lubrication Lines
Extended lubrication lines with grease fittings located outside the
fan section are available for lubrication of the fan shaft bearings.
High Temperature Wet Deck
If operation above 130F (54.4C) is anticipated, optional high temperature wet deck materials are
available to increase the maximum allowable entering water temperature to 170F (76.7C).
Bottom Screens (VT0 and VT1 Models Only)
Wire mesh screens are available factory-installed over the bottom openings to prevent unauthorized
access.
Basin Sweeper Piping
Basin sweeper piping is an effective method of eliminating sediment that may collect in the cold water
basin of the tower. A piping system is provided for connection to side stream filtration equipment
(by others) with a supply pressure of 10-20 psig.
Capacity Control Dampers
Modulating capacity control dampers are available to provide better leaving water temperature control
than can be obtained from fan cycling alone. A standard electrical control package for dampers is
available.
Solid Bottom Panels
Factory-installed bottom panels are required when intake air is ducted to the unit.
Discharge Hoods
Discharge hoods reduce the risk of recirculation in tight enclosures by increasing discharge air velocity,
and can be used to elevate the tower discharge above adjacent walls to comply with layout guidelines.
Electric Water Level Control Package
S
e
r
i
e
s
V
D75
Baltimore Aircoil Company
Do not use for construction. Refer to factory certified dimensions. This brochure includes data current
at time of publication, which should be reconfirmed at the time of purchase. Up-to-date engineering data,
free product selection software, and more can be found at www.BaltimoreAircoil.com.
VTL Engineering Data
INLET
1" MAKE-UP
ACCESS
SUCTION OVERFLOW
2" DRAIN
H
A
40
20
211-5/16
2-1/4
4-9/16
2 3-3/4
411-7/8
7 0-3/4
2-1/4
2-5/8
11-5/8
18
7-5/8
41-1/4
7-3/4
1" MAKE-UP
ACCESS
OVERFLOW
2" DRAIN
H
511-5/8
3
3 26-5/8
38-5/8
51-3/4
510-5/8
1011-3/4
2-5/8
11-5/8
18
1" MAKE-UP
ACCESS
OVERFLOW
2" DRAIN
H
811-7/16
4-1/8
56-7/16
68-7/16
73-5/8
510-5/8
1411-9/16
2-5/8
11-5/8
18
41/8
1" MAKE-UP
ACCESS
OVERFLOW
2" DRAIN
H
1111-5/8
4-1/8
86-5/8
98-5/8
103-11/16
510-5/8
1711-3/4
2-5/8
11-5/8
18
41/8
VTL Models
Models
VTL-016-E to 137-M
Models VTL-082-K to 095-K
Models VTL-103-K to 137-M
Models
VTL-016-E to 039-H
Models
VTL-045-H to 079-K
OPERATING
1
SHIPPING
A H
INLET OUTLET OVERFLOW
VTL-016-E 16 1.5 7,680 1,620 1,100 4' 0-3/4" 5' 1-1/4" 3" 3" 2"
VTL-021-F 21 2 8,150 1,660 1,140 4' 0-3/4" 5' 1-1/4" 3" 3" 2"
VTL-027-F 27 2 7,370 1,740 1,220 5' 7" 6' 6-1/4" 3" 3" 2"
VTL-030-G 30 3 8,270 1,770 1,250 5' 7" 6' 6-1/4" 3" 3" 2"
VTL-034-H 34 5 9,420 1,810 1,290 5' 7" 6' 6-1/4" 3" 3" 2"
VTL-039-H 39 5 8,680 1,910 1,390 7' 1-5/16" 8' 1-13/16" 3" 3" 2"
VTL-045-H 45 5 16,910 2,710 1,650 4' 0-3/4" 5' 1-1/4" 4" 4" 2"
VTL-051-G 51 3 13,350 2,810 1,750 5' 7" 6' 6-1/4" 4" 4" 2"
VTL-059-H 59 5 15,490 2,830 1,770 5' 7" 6' 6-1/4" 4" 4" 2"
VTL-066-J 66 7.5 17,210 2,900 1,840 5' 7" 6' 6-1/4" 4" 4" 2"
VTL-072-K 72 10 18,690 2,930 1,870 5' 7" 6' 6-1/4" 4" 4" 2"
VTL-079-K 79 10 17,500 3,100 2,040 7' 1-5/16" 8' 1-13/16" 4" 4" 2"
VTL-082-K 82 10 22,400 3,810 2,260 5' 7" 6' 6-1/4" 6" 6" 2"
VTL-092-L 92 15 24,980 3,940 2,390 5' 7" 6' 6-1/4" 6" 6" 2"
VTL-095-K 95 10 21,150 4,070 2,510 7' 1-5/16" 8' 1-11/16" 6" 6" 3"
VTL-103-K 103 10 24,990 4,740 2,680 5' 7" 6' 6-1/4" 6" 6" 3"
VTL-116-L 116 15 28,200 4,800 2,740 5' 7" 6' 6-1/4" 6" 6" 3"
VTL-126-M 126 20 30,700 4,810 2,750 5' 7" 6' 6-1/4" 6" 6" 3"
VTL-137-M 137 20 29,560 5,120 3,060 7' 1-5/16" 8' 1-13/16" 6" 6" 3"
WEIGHTS (LBS) DIMENSIONS CONNECTIONS
MODEL
NUMBER
MOTOR
HP
3
AIRFLOW
(CFM)
NOMINAL
TONNAGE
4
O
p
e
n
C
o
o
l
i
n
g
T
o
w
e
r
s
D76
...because temperature matters
Notes:
1. Operating weight is for tower with water level in the cold water basin at overflow.
2. Unless otherwise indicated, all connections 6" and smaller are MPT. Connections 8" and larger are beveled for welding.
3. Fan horsepower is at 0 external static pressure.
4. Nominal tons of cooling respresents 3 gpm of water from a 95F entering water temperature to an 85F leaving water
temperature at a 78F entering wet-bulb temperature.
2" MAKE-UP
ACCESS
OVERFLOW
2" DRAIN
H
1111-5/8
5
86-5/8
98-5/8
103-11/16
510-7/8
1711-3/4
2-5/8
11-5/8
18
5
2" MAKE-UP
ACCESS
OVERFLOW
2" DRAIN
H
811-7/16
5
56-7/16
68-7/16
73-5/8
510-5/8
1411-9/16
2-5/8
11-5/8
18
5
INLET
A
79-1/4
310-5/8
6-1/8
710-1/2
311-1/4
Models
VTL-152-M to 272-P
Models VTL-152-M to 227-O
Models VTL-245-P to 272-P
See page D85
for Engineering
Considerations.
OPERATING
1
SHIPPING
A H
INLET OUTLET OVERFLOW
VTL-152-M 152 20 45,870 6,580 3,440 4' 0-3/4" 5' 1-1/4" 8" 8" 3"
VTL-171-L 171 15 39,940 6,820 3,680 5' 7" 6' 6-1/4" 8" 8" 3"
VTL-185-M 185 20 43,150 6,960 3,820 5' 7" 6' 6-1/4" 8" 8" 3"
VTL-198-N 198 25 46,090 7,000 3,860 5' 7" 6' 6-1/4" 8" 8" 3"
VTL-209-O 209 30 48,630 7,040 3,900 5' 7" 6' 6-1/4" 8" 8" 3"
VTL-227-O 227 30 46,550 7,470 4,300 7' 1-5/16" 8' 1-13/16" 8" 8" 3"
VTL-245-P 245 40 58,820 8,970 4,790 5' 7" 6' 6-1/4" 8" 8" 3"
VTL-272-P 272 40 56,760 9,490 5,310 7' 1-5/16" 8' 1-13/16" 8" 8" 3"
WEIGHTS (LBS) DIMENSIONS CONNECTIONS
MODEL
NUMBER
MOTOR
HP
3
AIRFLOW
(CFM)
NOMINAL
TONNAGE
4
S
e
r
i
e
s
V
D77
Baltimore Aircoil Company
Do not use for construction. Refer to factory certified dimensions. This brochure includes data current
at time of publication, which should be reconfirmed at the time of purchase. Up-to-date engineering data,
free product selection software, and more can be found at www.BaltimoreAircoil.com.
VT0 Engineering Data
1" MAKE-UP
OVERFLOW
WATER OUT
WATER IN
2" DRAIN
H
B
A
38-1/8
33
36-1/4
26-1/8
30
311-1/2
8-3/8
4-1/8
17-1/4
21-1/8
2-1/4
ACCESS
1" MAKE-UP
OVERFLOW
WATER OUT
WATER IN
2" DRAIN
H
B
A
54-1/2
41-1/2
49-7/8 3-1/4
3-1
30-1/2
48-5/8
15-3/4
5-5/8
18-1/4
2-1/2
36 4-1/2
4 2-1/4 3-1/4
M
60 4-1/2
4 2-1/4 60
M
811-3/4 4-1/2
4 2-1/4 811-3/4
M
1111-1/2 5-1/2
1111-3/4
511-7/8
M
120 4-1/2
4 2-1/4 1111-3/4
M
Models
VTO-12 to 116
Models
VTO-12 to 28
Models
VTO-32 to 57
Models
VTO-65 to 88
Models VTO-132 to 176 Models VTO-102 to 116
Models
VTO-132 to 176
Notes:
1. Operating weight is for tower with water level in the cold water
basin at overflow.
2. Unless otherwise indicated, all connections 3" and smaller are
MPT. Connections 4" and larger are beveled for welding and
grooved for mechanical coupling.
3. Fan horsepower is at 0 external static pressure.
4. Nominal tons of cooling respresents 3 gpm of water from a 95F
entering water temperature to an 85F leaving water
temperature at a 78F entering wet-bulb temperature.
VT0 Models
OPERATING
1
SHIPPING
HEAVIEST
SECTION H A B INLET OUTLET OVERFLOW
VTO-12-E 12 1 1/2 4,970 960 790 790 7' 6-1/8" 6' 7-7/8" 12 7/8" 3" 3" 2"
VTO-14-F 14 2 5,460 970 800 800 7' 6-1/8" 6' 7-7/8" 12 7/8" 3" 3" 2"
VTO-19-G 19 3 6,190 990 820 820 7' 6-1/8" 6' 7-7/8" 12 7/8" 3" 3" 2"
VTO-24-G 24 3 5,945 1,050 950 630 9' 0-1/8" 8' 1-7/8" 12 7/8" 3" 3" 2"
VTO-28-H 28 5 6,960 1,170 970 650 9' 0-1/8" 8' 1-7/8" 12 7/8" 3" 3" 2"
VTO-32-H 32 5 11,820 1,590 1,230 1,230 7' 6-1/8" 6' 7-7/8" 12 7/8" 3" 3" 2"
VTO-41-J 41 7 1/2 13,435 1,650 1,290 1,290 7' 6-1/8" 6' 7-7/8" 12 7/8" 3" 3" 2"
VTO-52-J 52 7 1/2 12,960 1,780 1,540 870 9' 0-1/8" 8' 1-7/8" 12 7/8" 3" 3" 2"
VTO-57-K 57 10 14,180 1,790 1,550 880 9' 0-1/8" 8' 1-7/8" 12 7/8" 3" 3" 2"
VTO-65-J 65 7 1/2 16,860 2,580 2,000 1,070 9' 0-1/8" 8' 1-7/8" 12 7/8" 4" 4" 2"
VTO-75-K 75 10 18,435 2,590 2,010 1,080 9' 0-1/8" 8' 1-7/8" 12 7/8" 4" 4" 2"
VTO-78-K 78 10 17,990 2,710 2,130 1,080 10' 6-1/8" 9' 7-1/8" 12 7/8" 4" 4" 2"
VTO-88-L 88 15 20,420 2,770 2,190 1,140 10' 6-1/8" 9' 7-1/8" 12 7/8" 4" 4" 2"
VTO-102-L 102 15 25,060 3,310 2,500 1,330 9' 0-1/8" 8' 1-7/8" 12 7/8" 4" 4" 2"
VTO-107-L 107 15 24,460 3,680 2,870 1,540 10' 6-1/8" 9' 7-7/8" 12 7/8" 4" 4" 2"
VTO-116-M 116 20 26,760 3,740 2,930 1,600 10' 6-1/8" 9' 7-7/8" 12 7/8" 4" 4" 2"
VTO-132-L 132 15 30,600 5,190 3,820 2,000 11' 9-1/8" 10' 9-7/8" 23 1/4" 6" 6" 3"
VTO-145-M 145 20 33,670 5,200 3,830 2,010 11' 9-1/8" 10' 9-7/8" 23 1/4" 6" 6" 3"
VTO-155-N 155 25 36,240 5,250 3,880 2,060 11' 9-1/8" 10' 9-7/8" 23 1/4" 6" 6" 3"
VTO-166-N 166 25 35,265 5,650 4,280 2,220 13' 3-1/8" 12' 3-7/8" 23 1/4" 6" 6" 3"
VTO-176-O 176 30 37,330 5,680 4,310 2,250 13' 3-1/8" 12' 3-7/8" 23 1/4" 6" 6" 3"
DIMENSIONS CONNECTIONS WEIGHTS (LBS)
MODEL
NUMBER
MOTOR
HP
3
AIRFLOW
(CFM)
NOMINAL
TONNAGE
4
O
p
e
n
C
o
o
l
i
n
g
T
o
w
e
r
s
D78
...because temperature matters
Do not use for construction. Refer to factory certified dimensions. This brochure includes data current
at time of publication, which should be reconfirmed at the time of purchase. Up-to-date engineering data,
free product selection software, and more can be found at www.BaltimoreAircoil.com.
VT1 Engineering Data
ACCESS
2" MAKE-UP
3" OVERFLOW
WATER OUT
2" DRAIN
H
B
A
68-3/4
42
79-1/4 7/8
33-1/2
375-8
710-3/8
6-5/8
8-3/4
4-3/4
238-1/2 4
511-7/8
INLET
M
240-1/2
511-7/8
INLET
M
117-3/4 4
1111-3/4
511-7/8
INLET
M
178-1/8 4
180-1/8
90-1/16
INLET
M
Models
VT1-N209 to N540
Models VT1-N301 to N395 Models VT1-N418 to N510
Models VT1-N209 to N255
Notes:
1. Operating weight is for tower with water level in the cold water
basin at overflow.
2. Unless otherwise indicated, all connections 6" and smaller are
MPT. Connections 8" and larger are beveled for welding.
3. Fan horsepower is at 0 external static pressure.
4. Nominal tons of cooling respresents 3 gpm of water from a 95F
entering water temperature to an 85F leaving water
temperature at a 78F entering wet-bulb temperature.
Models VT1-N209-P to VT1-N510-P
OPERATING
1
SHIPPING
HEAVIEST
SECTION H A B INLET OUTLET
VT1-N209-P 209 40 66,300 9,180 5,350 3,300 11' 3-3/8" 10' 7-5/8" 12" 8" 8"
VT1-N220-O 220 30 53,100 9,490 5,660 3,110 13' 2-1/8" 12' 4-5/8" 12" 8" 8"
VT1-N240-P 240 40 57,950 9,680 5,850 3,300 13' 2-1/8" 12' 4-5/8" 12" 8" 8"
VT1-N255-P 255 40 55,900 10,380 6,550 3,300 14' 6-7/8" 13' 9-3/8" 12" 8" 8"
VT1-N301-Q 301 50 86,150 13,380 7,530 4,590 11' 3-3/8" 10' 7-5/8" 12" 8" 8"
VT1-N325-P 325 40 77,450 14,110 8,260 4,550 13' 2-1/8" 12' 4-5/8" 12" 8" 8"
VT1-N346-Q 346 50 83,050 14,150 8,300 4,590 13' 2-1/8" 12' 4-5/8" 12" 8" 8"
VT1-N370-Q 370 50 80,150 15,130 9,280 4,690 14' 6-7/8" 13' 9-3/8" 12" 8" 8"
VT1-N395-R 395 60 84,750 15,250 9,400 4,710 14' 6-7/8" 13' 9-3/8" 12" 8" 8"
VT1-N418-P 418 (2) 40 120,600 18,490 10,680 6,580 11' 3-3/8" 10' 7-5/8" 11" (2) 8" 10"
VT1-N440-O 440 (2) 30 106,200 19,110 11,300 6,200 13' 2-1/8" 12' 4-5/8" 11" (2) 8" 10"
VT1-N480-P 480 (2) 40 115,900 19,490 11,680 6,580 13' 2-1/8" 12' 4-5/8" 11" (2) 8" 10"
VT1-N510-P 510 (2) 40 111,800 20,890 13,080 6,580 14' 6-7/8" 13' 9-3/8" 11" (2) 8" 10"
DIMENSIONS CONNECTIONS
MODEL
NUMBER
MOTOR
HP
3
AIRFLOW
(CFM)
WEIGHTS (LBS)
NOMINAL
TONNAGE
4
S
e
r
i
e
s
V
D79
Baltimore Aircoil Company
Do not use for construction. Refer to factory certified dimensions. This brochure includes data current
at time of publication, which should be reconfirmed at the time of purchase. Up-to-date engineering data,
free product selection software, and more can be found at www.BaltimoreAircoil.com.
VT1 Engineering Data
ACCESS
MAKE-UP
3" OVERFLOW
WATER OUT
2" DRAIN
H
B
A
84
3 4-7/16
11 8-3/4 7/8
2 9-1/16
5 5-1/4
11 10
6-5/8
27-1/8
4-3/4
3-3/8
M
180-1/8
178-1/8 4
90-1/16
INLET
M
M
1111-3/4
117-3/4 4
511-7/8
INLET
Models
VT1-275 to 600
Models VT1-416 to 600
Models VT1-275 to 415
Models VT1-550-P to VT1-1335-S
OPERATING
1
SHIPPING
HEAVIEST
SECTION
H A B
INLET OUTLET MAKE-UP
VT1-275-P 275 40 82,530 15,190 8,040 5,140 12' 10-5/8" 12' 2-7/8" 14 1/2" 8" 8" 2"
VT1-307-O 307 30 74,350 15,780 8,630 4,950 14' 9-3/8" 13' 11-7/8" 14 1/2" 8" 8" 2"
VT1-340-P 340 40 81,550 15,970 8,820 5,140 14' 9-3/8" 13' 11-7/8" 14 1/2" 8" 8" 2"
VT1-375-P 375 40 79,300 16,940 9,790 5,140 16' 2-1/8" 15' 4-5/8" 14 1/2" 8" 8" 2"
VT1-400-Q 400 50 85,150 16,980 9,830 5,180 16' 2-1/8" 15' 4-5/8" 14 1/2" 8" 8" 2"
VT1-415-R 415 60 90,250 17,100 9,950 5,300 16' 2-1/8" 15' 4-5/8" 14 1/2" 8" 8" 2"
VT1-416-O4 416 (2) 30 125,046 22,430 11,530 7,280 12' 10-5/8" 12' 1-7/8" 13 1/2" 10" 10" 2"
VT1-478-N4 478 (2) 25 116,150 23,600 12,700 7,240 14' 9-3/8" 13' 10-7/8" 13 1/2" 10" 10" 2"
VT1-507-O4 507 (2) 30 123,150 23,640 12,740 7,280 14' 9-3/8" 13' 10-7/8" 13 1/2" 10" 10" 2"
VT1-560-O4 560 (2) 30 119,750 25,080 14,180 7,280 16' 2-1/8" 15' 3-5/8" 13 1/2" 10" 10" 2"
VT1-600-P4 600 (2) 40 131,250 25,460 14,560 7,660 16' 2-1/8" 15' 3-5/8" 13 1/2" 10" 10" 2"
DIMENSIONS CONNECTIONS
MODEL
NUMBER
MOTOR
HP
3
AIRFLOW
(CFM)
WEIGHTS (LBS)
NOMINAL
TONNAGE
5
O
p
e
n
C
o
o
l
i
n
g
T
o
w
e
r
s
D80
...because temperature matters
ACCESS
MAKE-UP
3" OVERFLOW
WATER OUT
2" DRAIN
H
B
A
84
3 4-7/16
11 8-3/4 7/8
2 9-1/16
5 5-1/4
11 10
6-5/8
27-1/8
4-3/4
3-3/8
M
180-5/8
INLET
M
4
511-7/8
INLET
361-1/4
359-1/4 4
511-7/8
INLET
M
M
4
5 11-7/8
INLET
M
24 0-1/2
23 8-1/2
5 11-7/8
INLET
Models
VT1-550 to 1355
Models VT1-825 to 1335
Models VT1-550 to 830
Notes:
1. Operating weight is for tower with water level in the cold water
basin at overflow.
2. Unless otherwise indicated, all connections 6" and smaller are
MPT. Connections 8" and larger are beveled for welding.
3. Fan horsepower is at 0 external static pressure.
4. Fans on models VT1-416 through 600 must be cycled
simultaneously for capacity control. For additional steps of control
beyond on/off operation, a variable frequency drive, the ENERGY-
MISER
Corrosion
Protection System Units; 150F (65.6C) for
Galvanized & Stainless Steel Units
170F (76.7C)
O
p
e
n
C
o
o
l
i
n
g
T
o
w
e
r
s
D88
...because temperature matters
Sound Levels
Sound rating data is available for all BAC Cooling Towers. When calculating the sound levels generated by a
unit, the designer must take into account the effects of the geometry of the tower as well as the distance and
direction from the unit to noise-sensitive areas. Low sound fans and intake and discharge sound attenuation
can be supplied on certain models to provide reduced sound characteristics (see the Custom Features and
Options section of the appropriate product line for details). The ENERGY-MISER
F/85
F/78
F
FXV Closed Circuit Cooling Towers deliver independently verified, fully rated thermal performance over a wide
range of flow and temperature requirements. Standard design features satisfy todays environmental concerns,
minimize installation costs, maximize year-round operating reliability, and simplify maintenance requirements.
FXV Closed Circuit Cooling Towers
Low energy consumption
Low installed cost
Easy maintenance
Application flexibility
Reliable year-round operation
Long service life
ASME B31.5 compliant heat transfer coils
Five-year warranty on mechanical equipment
FXV
Closed Circuit Cooling Towers
C
l
o
s
e
d
C
i
r
c
u
i
t
C
o
o
l
i
n
g
T
o
w
e
r
s
E12
...because temperature matters
F
X
V
E13
Baltimore Aircoil Company
Benefits
Low Energy Consumption
Evaporative cooled equipment minimizes the energy consumption of the entire system because it
provides lower operating temperatures. The owner saves money while conserving natural resources
and reducing environmental impact.
The FXV provides heat rejection at the lowest possible energy input and maintenance
requirements via:
High efficiency, low horsepower axial fans
Closed loop cooling, which minimizes process fouling
Patented combined flow technology*, which reduces evaporation directly off the coil,
minimizing the potential for scaling and fouling
Parallel flow of air and spray water, which eliminates scale-promoting dry spots
Variable Frequency Drives
ENERGY-MISER
Power Train
Premium quality, solid-backed,
multi-groove belt
Corrosion resistant cast aluminum sheaves
Heavy-duty bearings
(280,000 hour average life)
Cooling tower duty fan motor
Five-year motor and
drive warranty
Low HP Axial Fan(s)
Quiet operation
Corrosion resistant aluminum
Water Distribution System
Visible and accessible during operation
Overlapping spray patterns ensure proper
water coverage
Large orifice, non-clog nozzles
Coil Section (Not Shown)
Continuous serpentine, steel tubing
Hot-dip galvanized after fabrication (HDGAF)
Pneumatically tested at 375 psig
Sloped tubes for free drainage of fluid
ASME B31.5 compliant
When required, orders shipping into
Canada are supplied with a CRN
BACross
Power Train
Premium quality, solid backed, multi-groove belt
Corrosion resistant cast aluminum sheaves
Heavy-duty bearings (280,000 hour average life)
Cooling tower duty fan motor
Five-year motor and drive warranty
Low HP Axial Fan
Quiet operation
Corrosion resistant aluminum
Water Distribution System
Visible and accessible during operation
Overlapping spray patterns ensure proper
water coverage
Large orifice, non-clog nozzles
Coil Sections
Continuous serpentine, steel tubing
Hot-dip galvanized after fabrication (HDGAF)
Pneumatically tested at 375 psig
Sloped tubes for free drainage of fluid
ASME B31.5 compliant
When required, orders shipping into Canada
are supplied with a CRN
BACross
Power Train.
This BAC engineered drive system consists of a specially designed powerband and two cast aluminum
sheaves located on minimum shaft centerline distances to maximize belt life. A cooling tower duty fan
motor, custom engineered for BAC to provide maximum performance for cooling tower service, is
provided and backed by BACs comprehensive five year motor and fan drive warranty.
ENERGY-MISER
Fan System
The ENERGY-MISER
Fan System
F
X
V
E21
Baltimore Aircoil Company
Independent Fan Operation
Models FXV-43X, 44X, Q44X, 64X, and Q64X are provided with one fan motor driving two fans as
standard. Models FXV-66X and Q66X are provided with two fan motors driving three fans as standard.
The Independent Fan option consists of one fan motor and drive assembly for each fan to allow
independent operation, adding an additional step of fan cycling and capacity control.
Gear Drive System,
Close-Coupled Motor
Models FXV-288 and 364 are available
with a close-coupled gear drive system.
Both the gear drive and couplings are
selected with a 2.0 service factor. Gear
construction includes a nickel-alloy steel
shaft, casehardened gears, self
lubrication, and a single piece, gray iron
housing. This drive system ships
completely installed and aligned.
Gear Drive System,
Externally Mounted Motor
Models FXV-288 and 364 are available
with a gear drive system with external
TEFC motor. A non-corrosive carbon-fiber
composite drive shaft with stainless steel
hubs is selected with a 2.0 service factor.
The motor and drive shaft ship separately
for easy field installation.
Custom Features and Options
Gear Drive System, Close-Coupled Motor
Gear Drive System, Externally Mounted Motor
C
l
o
s
e
d
C
i
r
c
u
i
t
C
o
o
l
i
n
g
T
o
w
e
r
s
E22
...because temperature matters
Basinless Unit Construction
(FXV-288 and 364 Models Only)
The basinless unit construction option enables units to be directly
applied to new or existing concrete cold water basins. This custom
feature, reduces maintenance costs by eliminating the integral
basin from traditional units. It simplifies piping and pumping
requirements of multi-cell installations and provides a
cost-effective solution for many field-erected replacement projects.
Low Sound Operation
The low sound levels generated by FXV
Closed Circuit Cooling Towers make them
suitable for installation in most
environments. For very sound sensitive
installations, a low sound fan option is
available to significantly reduce the sound
levels generated from the tower with
minimal impact on thermal performance.
The FXV thermal performance with the
low sound fan has been certified in
accordance with CTI Standard STD-201.
For extremely sound sensitive installations,
factory designed, tested and rated sound
attenuation is available for both the air
intake and discharge.
Installation on a concrete basin
Unit with intake and discharge sound attenuation
F
X
V
E23
Baltimore Aircoil Company
Accessories
External Service Platforms
For external service, louver face and access door
platforms can be added to the unit when purchased
or as an aftermarket item. Safety cages and safety
gates are also available. All components are
designed to meet OSHA requirements.
Ladder, Safety Cage, Gate and Handrails (FXV-288 and 364 Models Only)
In the event the end-user elects to provide access to the fan deck, models FXV-288 and 364 can be
furnished with ladders extending from the top of the unit to the base, as well as safety cages, safety
gates, fan deck extensions and handrail packages. All components are designed to meet OSHA
requirements. All access to the top of the equipment must be made in accordance with applicable
governmental occupational safety standards.
Note: Partial or full grating above the coil air intake is recommended with this option.
Internal Ladder
For access to the motor and drive assemblies on single air inlet models, an internal ladder is available.
Internal Service Platforms
For access to the motor and drive assemblies on
single air inlet models FXV-L641 through FXV-Q661
and all dual air inlet models, an internal ladder and
upper service platform with handrails is available.
Safety gates are available for all handrail openings.
All components are designed to meet OSHA
requirements.
Vibration Cutout Switch
A factory mounted vibration cutout switch is available to effectively protect against equipment failure
due to excessive vibration of the mechanical equipment system. BAC can provide either a mechanical
or solid-state electronic vibration cutout switch in a NEMA 4 enclosure to ensure reliable protection.
Additional contacts can be provided to either switch type to activate an alarm.
External platform at louver face
Internal ladder and service platform
C
l
o
s
e
d
C
i
r
c
u
i
t
C
o
o
l
i
n
g
T
o
w
e
r
s
E24
...because temperature matters
Positive Closure Damper (PCD) Hoods
The FXVs innovative design results in a low heat loss when the unit is idle. When additional heat loss
protection is desired, coil air intake hoods with factory mounted PCDs and damper actuators can be
provided. The addition of factory mounted insulation to the hood and casing further reduces the heat
loss by minimizing losses due to conduction. See page E29 for Heat Loss Data on all FXV models.
Basin Heaters
Closed circuit cooling towers exposed to below
freezing ambient temperatures require protection
to prevent freezing of the water in the cold water
basin when the unit is idle. Factory-installed
heaters, which maintain +40F (4.4C) water
temperature, are a simple and inexpensive way
of providing such protection.
Heater Sizing Data
Electric Water Level Control Package
The electric water level control replaces the standard mechanical
makeup valve when a more precise water level control is required.
This package consists of a conductance-actuated level control
mounted in the basin and a solenoid activated valve in the
make-up water line. The valve is slow closing to minimize
water hammer.
Electric Water Level
Control Package
Basin Heater
No. of HEATERS kW per HEATER No. of HEATERS kW per HEATER
FXV-42X 1 4 1 6
FXV-43X 1 6 1 8
FXV-44X 1 8 1 12
FXV-64X 1 12 1 16
FXV-66X 1 16 1 21
FXV-288 2 12 2 15
FXV-364 2 14 2 20
MODEL NUMBERS
0F (-17.8C) AMBIENT HEATERS -20F (-28.9C) AMBIENT HEATERS
F
X
V
E25
Baltimore Aircoil Company
Accessories
Extended Lubrication Lines
Extended lubrication lines are available for
lubrication of the fan shaft bearings. Grease fittings
are located inside the plenum area next to the
access door.
High Temperature Wet Deck
Optional high temperature wet deck material is available for high entering fluid temperatures.
Air Inlet Screens
Wire mesh screens can be factory-installed over the inlet
louvers and the spray distribution system to prevent debris
from entering the tower.
Basin Sweeper Piping
Basin sweeper piping provides an effective method of
preventing debris from collecting in the cold water basin of the
tower. A complete piping system, including nozzles, is provided
in the tower basin for connection to side stream filtration
equipment (by others).
Grease fittings at the access door & bearings with the extended lubrication line option
Basin Sweeper Piping
C
l
o
s
e
d
C
i
r
c
u
i
t
C
o
o
l
i
n
g
T
o
w
e
r
s
E26
...because temperature matters
Notes:
1. Support steel and anchor bolts to be designed and furnished
by others.
2. All support steel must be level at the top.
3. Beams must be selected in accordance with accepted structural
practice. Maximum deflection of beam under unit to be 1/360
of span, not to exceed 1/2 inch.
4. If vibration isolation rails are to be used between the unit and
supporting steel, be certain to allow for the length of the vibration
rails when determining the length of the supporting steel, as
vibration rail length and mounting hole locations may differ from
those of the unit.
5. If point vibration isolation is used with multi-cell units, the isolators
must be located under the support steel, not between the support
steel and the towers.
Single Air Inlet
Dual Air Inlet
The recommended support arrangement for FXV Closed Circuit Cooling Towers consists of parallel
I-beams positioned as shown in the drawings. Besides providing adequate support, the steel also
serves to raise the unit above any solid foundation to assure access to the bottom of the tower.
Alternate steel support designs include a cantilevered plan as indicated by the optional minimum D
dimension in the table below. When unit is supported with a cantilever plan, the side opposite the air
inlet shall be cantilevered. To support an FXV on columns or in an alternate arrangement not shown
here, consult your local BAC Representative.
Structural Support
MODEL
NUMBER D
OPTIONAL
MINIMUM D
MAX.
DEFLECTION
FXV-42x 8'-3" 5'-9" 3/16"
FXV-43x 8'-3" 5'-9" 5/16"
FXV-44x 8'-3" 5'-9" 3/8"
FXV-64x 11'-7 3/4" 8'-0" 3/8"
FXV-66x 11'-7 3/4" 8'-0" 1/2"
MODEL
NUMBER D
MAX.
DEFLECTION
FXV-288-xxx 23'-9 1/8" 1/2"
FXV-364-xxx 26'- 5/8" 1/2"
F
X
V
E27
Baltimore Aircoil Company
Do not use for construction. Refer to factory certified dimensions. This brochure includes data current
at time of publication, which should be reconfirmed at the time of purchase. Up-to-date engineering data,
free product selection software, and more can be found at www.BaltimoreAircoil.com.
Engineering Data
3" OVERFLOW
2" DRAIN
Single Air Inlet Models
Notes:
1. Operating weight is for the tower with the water level in the cold
water basin at the overflow.
2. The actual size of the inlet and outlet connection may vary with
the design flow rate. Consult unit print for dimensions.
3. Inlet and outlet connections are beveled for welding.
4. Standard make-up, drain and overflow connections are MPT.
5. Nominal tons of cooling represents 3 gpm of water from 95F to
85F at a 78F entering wet-bulb temperature.
FAN PUMP OPERATING
1
SHIPPING
HEAVIEST
SECTION L W H A P
MAKE-UP
WATER
COIL
FXV-421 33 7,730 5,050 2,900 46
FXV-422 46 8,190 5,370 3,220 60
FXV-423 52 8,680 5,710 3,560 74
FXV-424 59 9,160 6,050 3,900 88
FXV-431 57 11,230 7,160 4,240 69
FXV-432 73 11,930 7,650 4,730 90
FXV-433 81 12,630 8,140 5,220 112
FXV-434 95 13,380 8,680 5,760 133
FXV-441 92 14,220 8,760 5,120 91
FXV-442 111 15,150 9,410 5,770 120
FXV-443 122 16,080 10,060 6,420 149
FXV-444 140 17,070 10,770 7,130 178
FXV-Q440 88 15,150 9,410 5,770 124
FXV-Q441 125 17,070 10,770 7,130 182
FXV-641 144 18,560 10,890 6,730 146
FXV-642 175 20,050 11,930 7,770 192
FXV-643 193 21,550 12,980 8,820 238
FXV-644 215 23,050 14,040 9,880 284
FXV-Q640 134 20,050 11,930 7,770 194
FXV-Q641 186 23,050 14,040 9,880 286
FXV-661 231 27,070 15,510 9,690 218
FXV-662 267 29,290 17,070 11,250 288
FXV-663 295 31,570 18,670 12,850 358
FXV-664 331 33,810 20,280 14,460 429
FXV-Q660 215 29,290 17,070 11,250 299
FXV-Q661 299 33,810 20,280 14,460 439
900
8'-8 3/4"
5 to 15
3 to 10 1.5
2
13'-2 3/4"
6'-3/4" 6'-1 1/4" 8'-5 1/4"
7.5 15 to 45
10 to 30
7.5 to 20 3
5
1'-8 1/4"
1'-8 1/4"
18'-1 1/4" 11'-10" 16'-4 1/4" 9'-2 1/4" 2'-3/8"
12'-1 1/4" 11'-10" 15'-10 3/4"
6'-3/4"
MODEL
NUMBER
MOTOR HP
12'-1 1/4" 8'-5 1/4"
NOMINAL
TONS
5
13'-2 3/4"
9'-1 1/4" 8'-5 1/4" 13'-2 3/4"
WEIGHTS (LBS) DIMENSIONS
1'-3 3/4"
1'-4 1/4" 6'-3/4"
1/2" 4"
CONNECTION
SIZES
1/2" 4"
1"
1"
1"
1"
1/2"
1/2"
4"
6"
SPRAY
PUMP
(GPM)
INTERNAL
COIL
VOLUME
(GAL)
4"
8"
4"
6"
190
290
500
715
C
l
o
s
e
d
C
i
r
c
u
i
t
C
o
o
l
i
n
g
T
o
w
e
r
s
E28
...because temperature matters
6" FLUID OUT
6" FLUID IN
Dual Air Inlet Models
Notes:
1. Operating weight is for the tower with the water level in the cold
water basin at the overflow.
2. The actual size of the inlet and outlet connection may vary with
the design flow rate. Consult unit print for dimensions.
3. Inlet and outlet connections are beveled for welding.
4. Standard make-up, drain and overflow connections are located
on the bottom of the unit. Make-up connection is 1-1/2 MPT
standpipe, drain is 2 FPT and overflow is 3 FPT.
5. Models shipped with an optional gear drive or low sound fan
may have heights up to 10.5" greater than shown.
6. Nominal tons of cooling represents 3 gpm of water from 95F to
85F at a 78F entering wet-bulb temperature.
See page E76
for Engineering
Considerations.
FAN PUMP OPERATING
1
SHIPPING
HEAVIEST
SECTION L W H
5
FXV-288-31x 468 46,470 28,150 8,050 600
FXV-288-41x 502 50,160 30,910 9,430 712
FXV-288-1Qx 439 50,160 30,910 9,430 706
FXV-364-31x 579 54,440 32,170 9,390 696
FXV-364-41x 624 58,800 35,450 11,030 828
FXV-364-1Qx 550 58,800 35,450 11,030 862
1,720
1,720 15
TOTAL MOTOR HP
13'-11 1/8"
DIMENSIONS
26'-3 1/2"
18'-7 7/8"
18'-9 7/8" 25 to 75
11'-11" 24'-1/2" 20 to 60 15
SPRAY
PUMP
(GPM)
INTERNAL
COIL
VOLUME
(GAL)
MODEL
NUMBER
WEIGHTS (LBS)
NOMINAL TONS
6
F
X
V
E29
Baltimore Aircoil Company
Engineering Data:
Cold Weather Operation
Notes:
1 Heat loss based on 50F entering coil water and 10F ambient
with 45 mph wind (fans and pump off).
2. One inch thick PVC nitrile rubber blend thermal insulation on both
the PCD hood and the casing panels surrounding the coil.
Notes:
1. Hood shipping weight
includes shipping skid
weight.
FXV Heat Loss Data (Btu/hr)
Dimensional Data of Positive Closure Damper Hood
MODEL
NUMBER
STANDARD
UNIT
UNIT w/
PCD HOOD
UNIT w/ PCD
HOOD &
INSULATION
FXV-421 68,400 43,500 30,100
FXV-422 87,100 47,100 32,300
FXV-423 105,200 50,500 34,700
FXV-424 122,400 54,000 37,000
FXV-431 102,800 60,800 43,200
FXV-432 131,200 65,600 46,500
FXV-433 158,000 70,600 49,600
FXV-434 183,000 74,900 52,800
FXV-441 135,700 76,700 55,200
FXV-442 172,900 82,100 59,100
FXV-443 208,000 87,600 62,900
FXV-444 241,000 92,900 66,500
FXV-Q440 172,900 82,100 59,100
FXV-Q441 241,000 92,900 66,500
FXV-641 203,400 103,800 75,300
FXV-642 259,800 109,700 79,300
FXV-643 313,100 115,600 83,200
FXV-644 362,900 121,300 86,900
FXV-Q640 259,800 109,700 79,300
FXV-Q641 362,900 121,300 86,900
FXV-661 304,500 158,200 118,000
FXV-662 387,500 165,500 123,000
FXV-663 404,700 172,400 127,600
FXV-664 536,900 179,100 132,200
FXV-Q660 387,500 165,500 123,000
FXV-Q661 536,900 179,100 132,200
FXV-288-31x 760,200 280,700 202,000
FXV-288-41x 881,100 294,500 211,000
FXV-288-1Qx 881,100 294,500 211,000
FXV-364-31x 894,000 330,100 237,600
FXV-364-41x 1,036,200 346,400 248,100
FXV-364-1Qx 1,036,200 346,400 248,100
MODEL
NUMBER
HOOD SHIP.
WEIGHT (lbs.)
Operating
Weight Add
(lbs.) LENGTH (L)
WIDTH
(W)
HOOD
HEIGTH
(X)
UNIT
HEIGTH
(H)
FXV-42x 390 320 5-11 7/8 3'-5 1/4" 2-5 1/8 15-1 3/4
FXV-43x 540 430 8-11 7/8 3'-5 1/4" 2-5 1/8 15-1 3/4
FXV-44x 720 570 11-11 7/8" 3'-5 1/4" 2-5 1/8 15-1 3/4
FXV-64x 1160 920 11-11 7/8" 5'-3 1/2" 2-5 1/8 179 3/4
FXV-66x 1650 1300 17 11 7/8 5'-3 1/2" 2-5 1/8 179 3/4
FXV-288-xxx 1300 1040 13-11 1/8" 6-3 3/8" 2-5 1/8 20'-2 5/8"
FXV-364-xxx 1500 1200 11'-11" 6-3 3/8" 2-5 1/8 20'-2 5/8"
C
l
o
s
e
d
C
i
r
c
u
i
t
C
o
o
l
i
n
g
T
o
w
e
r
s
E30
...because temperature matters
1.0 Closed Circuit Cooling Tower
1.1 General: Furnish and install, as shown on the plans, ___
factory-assembled closed circuit cooling tower(s) of induced draft
design with vertical air discharge. Overall dimensions shall not
exceed approximately ___ ft (m) x ___ ft (m), with an overall
height not exceeding approximately ___ ft (m). Operating weight
shall not exceed _____ lbs (kg). The closed circuit cooling tower
shall be Baltimore Aircoil Model FXV-___.
1.2 Thermal Capacity (water as heat transfer fluid): The closed
circuit cooling tower shall be warranted by the manufacturer to
have capacity to cool _______ US gpm (lps) of water from
______F (C) to _____F (C) at _____F (C) entering
wet-bulb temperature. Coil pressure drop shall not exceed
________ psi (kPa). The performance shall be certified by the
Cooling Technology Institute in accordance with CTI Certification
Standard STD-201 or, lacking such certification, a field
acceptance test shall be conducted within the warranty period in
accordance with CTI Acceptance Test Code ATC-105, by the
Cooling Technology Institute, or other qualified independent third
party testing agency. Manufacturers' performance guarantees or
performance bonds without CTI Certification of water ratings
shall not be accepted.
(Alternate) 1.2 Thermal Capacity (aqueous glycol solution as
heat transfer fluid): The closed circuit cooling tower(s) shall be
warranted by the manufacturer to cool ________US gpm (lps) of
_____% by volume ethylene/propylene glycol solution from
______F (C) to _____F (C) at _____F (C) entering
wet-bulb temperature. Coil pressure drop shall not exceed
________ psi (kPa). Basis for thermal performance rating shall
be the Cooling Technology Institute (CTI) certified rating for
water cooling appropriately adjusted for the thermal properties of
the aqueous glycol solution used. Additionally, the thermal
performance of the Product Line with water as the heat transfer
fluid shall be certified by the CTI in accordance with CTI
Certification Standard STD-201. Manufacturers' performance
guarantees or performance bonds without CTI Certification of
water ratings shall not be accepted.
1.3 Quality Assurance: The cooling tower manufacturer shall
have a Management System certified by an accredited registrar
as complying with the requirements of ISO-9001:2000 to ensure
consistent quality of products and services.
2.0 Construction Details
2.1 G-235 (Z700 metric) Hot-Dip Galvanized Steel Structure: All
steel panels and structural elements shall be constructed from
heavy-gauge, G-235 (Z700 metric) hot-dip galvanized steel, with
cut edges given a protective coat of zinc-rich compound.
(Alternate) 2.1 Optional BALTIBOND
Corrosion Protection
System: All steel panels, support structure, hot and cold water
basins, fan deck and fan cylinder shall be protected with the
BALTIBOND
F/78
F
Series V Closed Circuit Cooling Towers deliver independently verified, fully rated thermal performance over a
wide range of flow and temperature requirements. The Series V can be installed indoors and is available in a
low profile version to accommodate limited ceiling or enclosure heights. The Series V design minimizes sound
levels and installation costs, provides year-round operating reliability, and simplifies maintenance
requirements.
Series V Closed Circuit Cooling Towers
Suitable for indoor or outdoor installations
Low profile models available
Low sound
Single side air inlet
Low energy consumption
Low installed cost
Easy maintenance
Reliable year-round operation
Long service life
ASME B31.5 compliant heat transfer coil
Five-year warranty on mechanical equipment
Series V
Closed Circuit Cooling Towers
C
l
o
s
e
d
C
i
r
c
u
i
t
C
o
o
l
i
n
g
T
o
w
e
r
s
E34
...because temperature matters
S
e
r
i
e
s
V
E35
Baltimore Aircoil Company
Benefits
Installation and Application Flexibility
Indoor Installations Centrifugal fans can
overcome the static pressure imposed by
external ductwork, allowing the Series V to
be installed indoors.
Low Profile Models The fan section of low
profile units are adjacent to the casing section to
yield models suitable for use in height sensitive
installations. Low profile models are available in
capacities from 12 to 361 nominal tons, which
correspond to heights of 5 5 and 8 4-3/4,
respectively.
Low Sound
Centrifugal Fan Centrifugal fans have inherently low sound characteristics.
Single Air Inlet - Particularly sound-sensitive areas can be accommodated by facing the quiet
blank-off panel to the sound-sensitive direction.
Low Energy Consumption
Evaporative cooling equipment minimizes the energy consumption of the entire system because it
provides lower operating temperatures. The owner saves money while conserving natural resources
and reducing environmental impact.
Low Installed Cost
Support All models mount directly on two parallel I-beams and ship complete with motors and
drives factory-installed and aligned (see sketches on next page).
Modular Design Large models ship in multiple sections to minimize the size and weight of the
heaviest lift, allowing for the use of smaller, less costly cranes.
Low Profile Series V
Closed Circuit Cooling Tower
C
l
o
s
e
d
C
i
r
c
u
i
t
C
o
o
l
i
n
g
T
o
w
e
r
s
E36
...because temperature matters
Easy Maintenance
Internal Access The interior of the unit is easily
accessible for adjusting the float valve,
cleaning the strainer or flushing the basin.
Reliable Year-Round Operation
V-Belt Drive The fans, motor, and drive system are
located outside of the moist discharge airstream, protecting
them from moisture, condensation and icing. Backed by a
five-year fan drive and motor warranty, these units are
suitable for year-round operation.
Long Service Life
Materials of Construction Various materials are available to meet
the corrosion resistance, unit operating life, and budgetary
requirements of any project (see page E39 for construction options).
V-Belt Drive System
The water level control (optional
electric control shown here) is easily
reached from the access door
VF1 Models
VFL Models
Steel Supports
Steel Supports
S
e
r
i
e
s
V
E37
Baltimore Aircoil Company
Heavy-Duty Construction
G-235 (Z700 metric) hot-dip galvanized
steel panels
Water Distribution System
Schedule 40 PVC spray branches
Large orifice, non-clog nozzles
Grommetted for easy maintenance
Coil
Continuous serpentine, steel tubing
Hot-dip galvanized after fabrication (HDGAF)
Pneumatically tested at 375 psig
Sloped tubes for free drainage of fluid
ASME B31.5 compliant
When required, orders shipping into
Canada are supplied with a CRN
Drift Eliminators
Polyvinyl chloride (PVC)
Impervious to rot, decay and biological attack
Flame spread rating of 5 per ASTM E84-77a
Assembled in easy to handle sections
Construction Details
1
2
2
1
3
3
4
4
Coil section typical for
all models
C
l
o
s
e
d
C
i
r
c
u
i
t
C
o
o
l
i
n
g
T
o
w
e
r
s
E38
...because temperature matters
Fan Drive System
V-belt drive
Heavy-duty bearings
(280,000 hour average life)
Cooling tower duty fan motor
Five-year motor and drive warranty
Low Sound Centrifugal Fan(s)
Quiet operation
Recirculating Spray Pump
Close coupled, bronze fitted centrifugal pump
Totally enclosed fan cooled (TEFC) motor
Bleed line with metering valve installed from
pump discharge to overflow
Access Door
Circular access door
Strainer (Not Shown)
Anti-vortexing design to prevent air entrainment
5
5
4
2
3
1
8
7
5
6
6
7
8
9
8
7
VF1 Models
VFL Models
S
e
r
i
e
s
V
E39
Baltimore Aircoil Company
Construction Options
Standard Construction:
Steel panels and structural elements are constructed of heavy-gauge G-235 hot-dip galvanized steel.
Optional BALTIBOND
Corrosion Protection
System).
Optional Water-Contact Stainless Steel Construction:
A cost effective alternative to all stainless steel construction, all components that are exposed to the
recirculating water are provided in Type 304 stainless steel. The remaining components are
constructed of the base material of construction (galvanized steel or the BALTIBOND
Corrosion
Protection System).
See page J4 for more details on the materials described above.
Coil Configurations
Standard Serpentine Coil:
The standard cooling coil is constructed of continuous lengths of all prime surface steel, hot-dip
galvanized (outside surface) after fabrication (HDGAF). The coil is designed for low pressure drop
with sloping tubes for free drainage of fluid. Each coil is pneumatically tested at 375 psig (2586 kPa)
and is ASME B31.5 compliant.
Optional Extended Surface Coil:
Coils are available with half or all the rows finned at 5 fins per inch for seasonal wet/dry operation.
The coil is hot-dip galvanized (outside surface) after fabrication (HDGAF). The coil is designed for
low pressure drop with sloping tubes for free drainage of fluid. Each coil is pneumatically tested at
375 psig (2586 kPa) and is ASME B31.5 compliant.
Custom Features and Options
C
l
o
s
e
d
C
i
r
c
u
i
t
C
o
o
l
i
n
g
T
o
w
e
r
s
E40
...because temperature matters
Optional Stainless Steel Coil:
Coils are available in Type 304 stainless steel for specialized applications. The coil is designed for low
pressure drop with sloping tubes for free drainage of fluid. Each coil is pneumatically tested at
375 psig (2586 kPa) and is ASME B31.5 compliant.
Optional Cleanable Header Coil:
The cleanable header tube bundle provides removable cover plates on the inlet and outlet header
boxes to permit access to each serpentine tube circuit for solvent or air-pressure cleaning. Tubes are
all prime surface steel tubing formed into a serpentine shape and welded into an assembly. Coil
material options include carbon steel coils (hot-dip galvanized outside surface) or stainless steel coils.
Each coil is pneumatically tested at 125 psig (860 kPa).
Optional Straight-Through Mechanically-Cleanable Coil:
A header box with a removable cover plate at each end of the coil allows access to every tube end for
mechanical cleaning or plugging. It is available in carbon steel (hot-dip galvanized inside and out) or
stainless steel. Each coil is pneumatically tested at 125 psig (860 kPa).
Optional ASME U Stamp Coil:
This coil is manufactured and tested in accordance with the ASME Boiler and Pressure Vessel Code,
Section VIII, Division 1, and bears the ASME U stamp. ASME coils are hot-dip galvanized
(outside surface) after fabrication (HDGAF). The coil is designed for low pressure drop with sloping
tubes for free drainage of fluid. Each coil is pneumatically tested at 375 psig (2586 kPa).
When required, orders shipping into Canada are supplied with a CRN. Other coil configurations are
available for specific applications. Contact your local BAC Representative for details.
Cleanable Header Coil Straight-through Mechanically-Cleanable Coil
S
e
r
i
e
s
V
E41
Baltimore Aircoil Company
Fan Drive System
The fan drive system provides the cooling air
necessary to reject unwanted heat from the system
to the atmosphere. Dynamically balanced, forwardly
curved, centrifugal fans driven by matched V-belts
with taper lock sheaves designed for not less than
150% of the motor nameplate horsepower are
standard. Cooling tower duty fan motors, custom
engineered for BAC to provide maximum
performance for cooling tower service, are provided
and backed by BACs comprehensive five-year
motor and fan drive warranty.
ENERGY-MISER
Fan System
The ENERGY-MISER
Fan System
C
l
o
s
e
d
C
i
r
c
u
i
t
C
o
o
l
i
n
g
T
o
w
e
r
s
E42
...because temperature matters
Accessories
External Access Options (VF1 Models Only)
In the event the end-user elects to provide access to
the top of the unit, VF1 models can be furnished
with ladders extending from the base of the unit to
the top, as well as safety cages, safety gates and
handrail packages. All components are designed to
meet OSHA requirements. All access to the top of
the equipment must be made in accordance with
applicable governmental occupational safety
standards.
NOTE: When these access options are employed,
the tower must be equipped with steel drift
eliminators.
Vibration Cutout Switch
A factory mounted vibration cutout switch is
available to effectively protect against equipment
failure due to excessive vibration of the mechanical
equipment system. BAC can provide either a
mechanical or solid-state electronic vibration cutout
switch in a NEMA 4 enclosure to ensure reliable
protection. Additional contacts can be provided to
activate an alarm.
Electric Water Level Control Package
The electric water level control replaces the
standard mechanical makeup valve when a more
precise water level control is required. This package
consists of a conductance-actuated level control
mounted in the basin and a solenoid activated valve
in the make-up water line. The valve is slow closing
to minimize water hammer.
Electric Water Level Control Package
Vibration Cutout Switch
Unit Shown with External Access Platform
S
e
r
i
e
s
V
E43
Baltimore Aircoil Company
Basin Heaters
Closed circuit cooling towers
exposed to below freezing ambient
temperatures require protection to
prevent freezing of the water in the
cold water basin when the unit is
idle. Factory installed heaters, which
maintain +40F (4.4C) water
temperature, are a simple and
inexpensive way of providing such
protection.
Heater Sizing Data
Basin Heater
No. of HEATERS kW per HEATER No. of HEATERS kW per HEATER
VFL-012-X 1 2 1 2
VFL-024-X 1 3 1 4
VFL-036-X 1 4 1 5
VFL-048-X 1 5 1 7
VFL-072-X 1 7 1 9
VFL-096-X 1 9 1 12
VF1-009-X 1 2 1 2
VF1-018-X 1 2 1 2
VF1-027-X 1 2 1 3
VF1-036-X 1 3 1 5
VF1-048-X 1 3 1 5
VF1-072-X 1 5 1 7. 5
VF1-096-X 1 5 1 7. 5
VF1-144N-X 1 7 1 10
VF1-144-X 1 8 1 10
VF1-192-X 2 5 2 7. 5
VF1-216-X 1 12 1 16
VF1-288N-X 2 7 2 10
VF1-288-X 2 8 2 10
VF1-432-X 2 12 2 16
MODEL NUMBERS
0F (-17.8C) AMBIENT HEATERS -20F (-28.9C) AMBIENT HEATERS
C
l
o
s
e
d
C
i
r
c
u
i
t
C
o
o
l
i
n
g
T
o
w
e
r
s
E44
...because temperature matters
Extended Lubrication Lines
Extended lubrication lines with grease fittings located outside the fan section are available for lubrication
of the fan shaft bearings.
Bottom Screens (VF1 Models Only)
Wire mesh screens are available factory-installed over the bottom openings to prevent unauthorized
access.
Basin Sweeper Piping
Basin sweeper piping is an effective method of eliminating sediment that may collect in the cold water
basin of the tower. A piping system is provided for connection to side stream filtration equipment
(by others) with a supply pressure of 10-20 psig.
Solid Bottom Panels
Factory-installed bottom panels are required when
intake air is ducted to the unit.
Capacity Control Dampers
Modulating capacity control dampers are available to
provide better leaving water temperature control
than can be obtained from fan cycling alone. A
standard electrical control package for dampers is
available.
Discharge Hoods
BAC offers a full line of standard discharge hoods
with and without positive closure dampers that are
built, tested, and rated specifically for all Series V
Closed Circuit Cooling Towers. The tapered hoods
are designed to increase the discharge air
velocity to avoid recirculation in extremely tight
enclosures. Straight or tapered hoods can be used
to elevate the unit discharge above adjacent walls.
A larger fan motor may be necessary when this
option is provided. See page E51 for details of
hoods furnished with positive closure dampers.
Solid Bottom Panels
Tapered Discharge Hood w/ Positive Closure Dampers
S
e
r
i
e
s
V
E45
Baltimore Aircoil Company
Do not use for construction. Refer to factory certified dimensions. This brochure includes data current
at time of publication, which should be reconfirmed at the time of purchase. Up-to-date engineering data,
free product selection software, and more can be found at www.BaltimoreAircoil.com.
VFL Engineering Data
4' 1-1/4"
1"
2" DRAIN
End Elevation View
Models VFL-012 to 048
Models VFL-072 to 096
Side Elevation View
7' 10-1/2"
2" MAKE-UP
2"
End Elevation View Side Elevation View
C
l
o
s
e
d
C
i
r
c
u
i
t
C
o
o
l
i
n
g
T
o
w
e
r
s
E46
...because temperature matters
Notes:
1. Nominal tonnage is CTI Certified performance at a 95F entering
water temperature, an 85F leaving water temperature, and a
78F entering wet-bulb temperature. Consult BAC selection
software for all other conditions.
2 Operating weight is for the unit with water level in the cold water
basin at the overflow.
3. Standard coil connections are beveled for welding.
4. If discharge hoods with positive closure dampers are furnished,
see page E51 for added weight and height. Fan motor
horsepower may increase; consult selection software for
verification.
5. Fan horsepower is at 0 external static pressure.
6. The number and location of coil connections will vary with
design flow and coil arrangement.
7. Units ship in one piece.
See page E76
for Engineering
Considerations.
VFL-012-02G 4.5 3 9,220 2,560 1,880 5'- 5" 1'-2 1/4" 45 18
VFL-012-12G 7.4 3 9,010 2,810 2,090 6'-3 3/4" 1'-10 3/4" 45 25
VFL-012-22G 9.4 3 8,870 3,140 2,330 6'-10" 2'-7 1/4" 45 32
VFL-012-32G 12 3 8,760 3,425 2,555 7'-6 1/2" 3'-3 3/4" 45 39
VFL-012-32H 14 5 10,380 3,425 2,555 7'- 6 1/2" 3'-3 3/4" 45 39
VFL-024-12H 17 5 15,430 4,610 3,120 6'-3 3/4" 1'-9 3/4" 94 47
VFL-024-22H 21 5 15,180 5,130 3,510 6'-7 1/4" 2'-6 1/4" 94 61
VFL-024-32H 26 5 14,990 5,750 3,960 7'-3 3/4 3'-2 3/4" 94 75
VFL-024-32J 30 7 1/2 17,160 5,750 4,000 7'-6 1/2" 3'-2 3/4" 94 75
VFL-036-22K 35 10 23,580 7,070 4,690 6'-10 1/4 2'-9 1/4" 142 90
VFL-036-32K 43 10 23,290 7,950 5,330 7'-8 3/4" 3'-6 1/2" 142 111
VFL-036-31M 49 20 29,340 7,970 5,350 7'-11 1/2" 3'-6 1/2" 142 111
VFL-048-22L 43 15 29,150 8,905 5,615 6'-10 1/4 3'-6 1/2" 192 119
VFL-048-31L 46 15 28,790 9,920 6,480 7'-8 3/4" 3'-6 1/2" 192 148
VFL-048-31M 52 20 31,680 9,920 6,480 7'-8 3/4" 3'-6 1/2" 192 148
VFL-048-41M 55 20 31,360 10,950 7,230 8'-4 3/4" 4'-3 3/4" 192 177
VFL-072-22N 69 25 45,390 13,555 8,755 7'-1" 2'-9 1/4" 284 180
VFL-072-22O 75 30 48,240 13,555 8,755 7'-1" 2'-9 1/4" 284 180
VFL-072-31O 81 30 47,640 15,190 9,920 7'-11 1/2" 3'-6 1/2" 284 223
VFL-072-41O 86 30 47,150 16,590 10,950 8'-7 1/2" 4'-3 3/4" 284 265
VFL-072-41P 97 40 51,900 16,590 10,950 8'-7 1/2" 4'-3 3/4" 284 265
VFL-096-41O 94 30 54,110 20,680 12,960 8'-4 3/4" 4'-3 3/4" 384 347
VFL-096-41P 108 40 59,560 20,680 12,960 8'-4 3/4" 4'-3 3/4" 384 347
SPRAY
PUMP
(GPM)
INTERNAL COIL
VOLUME (GAL)
SHIPPING
DIMENSIONS CONNECTIONS
COIL OVERFLOW
3"
3"
3"
MODEL
NUMBER
NOMINAL
TONS
1
FAN PUMP
AIRFLOW
(CFM)
WEIGHTS (LBS)
OPERATING
2
4"
4"
4"
7'-0 3/4"
10'-11 3/4"
17'-11 3/4"
1 1/2
2
1 1/2
14'-11 9/16"
17'-11 3/4"
MOTOR HP
1/3
1/2
1
2"
2"
2"
L H F
14'-11 9/16"
3"
4"
4"
S
e
r
i
e
s
V
E47
Baltimore Aircoil Company
Do not use for construction. Refer to factory certified dimensions. This brochure includes data current
at time of publication, which should be reconfirmed at the time of purchase. Up-to-date engineering data,
free product selection software, and more can be found at www.BaltimoreAircoil.com.
VF1 Engineering Data
3' 11-1/2"
1"
2"
2"
End Elevation View
Models VF1-009 to 036
Side Elevation View
1"
3"
2"
4' 8-5/8"
End Elevation View
Models VF1-048
Side Elevation View
2"
7' 10-3/8"
3"
End Elevation View
Models VF1-072
Side Elevation View
C
l
o
s
e
d
C
i
r
c
u
i
t
C
o
o
l
i
n
g
T
o
w
e
r
s
E48
...because temperature matters
See page E76
for Engineering
Considerations.
Notes:
1. Nominal tonnage is CTI Certified performance at a 95F entering
water temperature, an 85F leaving water temperature, and a 78F
entering wet-bulb temperature. Consult BAC selection software for
all other conditions.
2. Operating weight is for the unit with water level in the cold water
basin at the overflow.
3. Standard coil connections are beveled for welding.
4. If discharge hoods with positive closure dampers are furnished,
see page E51 for added weight and height. Fan motor horsepower
may increase; consult selection software for verification.
5. Fan horsepower is at 0 external static pressure.
6. The number and location of coil connections will vary with design
flow and coil arrangement.
7. Units marked with an asterisk ship in one piece. The coil section is
the heaviest section.
VF1-009-12G 5.5 3 5,690 1,875 1,625 1,625*
7'-3 3/4"
1'-10 3/4 " 20
VF1-009-22G 6.8 3 5,590 2,075 1,785 1,000
8'-0 1/4"
2'-7 3/4" 26
VF1-009-32G 8.3 3 5,520 2,295 1,965 1,180
8'-8 3/4"
3'-3 3/4" 31
VF1-009-42G 9.2 3 5,470 2,495 2,125 1,340
9'-4 3/4"
3'-11 3/4" 36
VF1-018-02H 9.5 5 11,180 2,635 2,175 2,175*
6'-7 1/4"
1'-1 1/4" 27
VF1-018-12H 14 5 10,930 2,955 2,415 2,415 *
7'-3 3/4"
1'-9 3/4" 38
VF1-018-22J 20 7.5 12,310 3,260 2,640 1,720
8'-0 1/4"
2'-6 1/4" 49
VF1-018-32J 22 7.5 12,150 3,660 2,940 2,010
8'-8 3/4"
3'-2 3/4" 60
VF1-018-42J 24 7.5 12,030 4,010 3,190 2,260
9'-5 1/4"
3'-11 1/4" 71
VF1-027-22H 24 5 14,060 4,940 3,830 2,410
7'-6"
2'-0" 72
VF1-027-22J 28 7 1/2 16,090 4,860 3,750 2,470
8'-3 1/4"
2'-9 1/4" 72
VF1-027-32K 35 10 17,490 5,440 4,108 2,850
9'-0 1/2"
3'-6 1/2" 89
VF1-027-42K 37 10 17,310 5,970 4,570 3,240
9'-9 3/4"
4'-3 3/4" 106
VF1-036-21L 41 15 24,870 6,280 4,760 3,200
8'-3 1/4"
2'-9 1/4" 95
VF1-036-31L 44 15 24,560 7,020 5,310 3,720
9'-0 1/2"
3'-6 1/2" 118
VF1-036-41L 47 15 24,310 7,710 5,810 4,220
9'-9 3/4"
4'-3 3/4" 140
VF1-036-51L 49 15 24,100 8,390 6,310 4,720
10'-7"
5'-1" 163
VF1-048-21M 55 20 35,790 10,230 7,870 4,920
9'-11 5/8"
2'-9 1/4" 137
VF1-048-31N 65 25 38,070 11,390 8,460 5,930
10'-8 7/8"
3'-6 1/2"
5'-4 1/2"
170
VF1-048-41N 70 25 37,690 12,690 9,320 6,600
11'-6 1/8'
4'-3 3/4" 203
VF1-072-21O 75 30 52,650 15,670 10,720 6,580
11'-3 7/8"
2'-9 1/4" 190
VF1-072-31O 81 30 51,990 17,380 12,050 7,950
12'-1 1/8"
3'-6 1/2" 235
VF1-072-41O 86 30 51,460 18,000 12,480 8,410 12'-10 3/8" 4'-3 3/4" 281
COIL
CONNECTION
SIZE
115
150
220
305
1/3
1/2
WEIGHTS (LBS)
35
75
3'-0"
6'-0"
3'-8 1/8"
3'-8 1/8"
INTERNAL
COIL
VOLUME
(GAL) OPERATING
2
MODEL
NUMBER NOMINAL TONS
1
SPRAY
PUMP
(GPM) F A
MOTOR HP
FAN PUMP
3/4
1
1 1/2
2
8'-11 3/4"
12'-0"
11'-11 1/2"
11'-7 3/4"
3'-8 1/8"
3'-8 1/8"
6'-8 3/4'
3"
4"
4"
4"
4"
4"
SHIPPING
HEAVIEST
SECTION
7
AIRFLOW
(CFM)
DIMENSIONS
L H
S
e
r
i
e
s
V
E49
Baltimore Aircoil Company
Do not use for construction. Refer to factory certified dimensions. This brochure includes data current
at time of publication, which should be reconfirmed at the time of purchase. Up-to-date engineering data,
free product selection software, and more can be found at www.BaltimoreAircoil.com.
VF1 Engineering Data
2" MAKE-UP
3" OVERFLOW
7' 10-3/8"
ACCESS
End Elevation View
Models VF1-096N to 288N Models VF1-096 to 144N
Side Elevation View
OVERFLOW
DRAIN 2"
11' 10"
3"
MAKE-UP
End Elevation View
Models VF1-144 to 432 Models VF1-216
Side Elevation View
C
l
o
s
e
d
C
i
r
c
u
i
t
C
o
o
l
i
n
g
T
o
w
e
r
s
E50
...because temperature matters
See page E76
for Engineering
Considerations.
Notes:
1. Nominal tonnage is CTI Certified performance at a 95F entering
water temperature, an 85F leaving water temperature, and a 78F
entering wet-bulb temperature. Consult BAC selection software for
all other conditions.
2. Operating weight is for the unit with water level in the cold water
basin at the overflow.
3. Standard coil connections are beveled for welding.
4. If discharge hoods with positive closure dampers are furnished,
see page E51 for added weight and height. Fan motor horsepower
may increase; consult selection software for verification.
5. Fan horsepower is at 0 external static pressure.
6. The number and location of coil connections will vary with design
flow and coil arrangement.
7. Unless marked with a double asterisk (**), the coil section is the
heaviest section.
VF1-096-31O 81 30 53,540 19,385 12,795 8,460 13'-6 3/8" 3'-6 1/2" 296
VF1-096-41P 99 40 58,320 21,345 14,215 9,880 14'-3 5/8" 4'-3 3/4" 8'- 1 5/8" 353
VF1-096-51Q 114 50 62,290 22,255 14,855 10,520 15'-0 7/8" 5'-1" 411
VF1-144N-21Q 127 50 72,700 25,610 16,430 10,390 12'-9 1/8 " 2'-9 1/4" 356
VF1-144N-31R 148 60 76,290 28,480 18,490 12,570 13'-6 3/8" 3'-6 1/2" 443
VF1-144N-41R 157 60 75,510 31,560 20,750 14,750 14'-3 5/8" 4'-3 3/4" 529
VF1-192-31O 163 (2) 30 108,150 38,900 25,570 8,460 13'-6 3/8" 3'-6 1/2" 592
VF1-192-41P 198 (2) 40 115,640 42,780 28,360 9,880 14'-3 5/8" 4'-3 3/4" 706
VF1-192-51Q 228 (2) 50 123,490 44,600 29,780 10,520 15'-0 7/8" 5'-0" 822
VF1-288N-21Q 253 (2) 50 145,510 51,260 32,750 11,970** 12'-9 1/8" 2'-9 1/4" 712
VF1-288N-31R 295 (2) 60 152,700 57,080 36,250 12,570 13'-6 3/8" 3'-6 1/2' 886
VF1-288N-41R 313 (2) 60 151,140 62,280 40,520 14,750 14'-3 5/8" 4'-3 3/4" 1,058
VF1-144-21Q 129 50 87,600 27,090 16,530 10,300 12'-11 1/2" 2'-9 1/4" 365
VF1-144-31Q 140 50 86,500 29,980 18,610 12,370 13'-8 3/4" 3'-6 1/2" 453
VF1-144-41R 164 60 90,990 32,840 20,640 14,440 14'-6" 4'-3 3/4" 541
VF1-216-21O 188 (2) 30 125,030 40,190 24,200 15,170 12'-11 1/2" 2'-9 1/4" 545
VF1-216-31P 231 (2) 40 135,890 44,370 27,140 18,290 13'-8 3/4" 3'-6 1/2" 677
VF1-216-41P 245 (2) 40 134,510 48,570 30,090 21,410 14'-6" 4'-3 3/4" 809
VF1-288-21Q 259 (2) 50 175,190 54,300 32,930 11,430** 12'-11 1/2" 2'-9 1/4" 730
VF1-288-31Q 281 (2) 50 173,010 60,820 37,020 12,370 13'-8 3/4" 3'-6 1/2" 906
VF1-288-41R 325 (2) 60 181,970 65,720 41,050 14,440 14'-6" 4'-3 3/4" 1,082
VF1-432-21O 376 (4) 30 250,060 78,200 45,960 15,620** 12'-11 1/2" 2'-9 1/4" 1,090
VF1-432-31P 462 (4) 40 271,790 87,120 52,400 18,290 13'-8 3/4" 3'-6 1/2" 1,354
VF1-432-41P 490 (4) 40 289,790 96,420 59,200 21,410 14'-6" 4'-3 3/4" 1,618
23'-8 1/2"
35'-9 1/4"
(2) 3
INTERNAL
COIL
VOLUME
(GAL) A COIL MAKE-UP
4"
DIMENSIONS CONNECTION SIZES
SPRAY
PUMP
(GPM) OPERATING
2
MODEL
NUMBER
NOMINAL
TONS
1
MOTOR HP
AIRFLOW
(CFM) FAN PUMP
WEIGHTS (LBS)
SHIPPING
HEAVIEST
SECTION
7
L H F
400
5 17'-8 1/3" 8'- 1 5/8" 4" 2" 610
3 11'-7 3/4"
8'- 1 5/8" 4" 2"
2"
8'-4" 4"
800
(2) 5 35'-9 1/4" 8'- 1 5/8" 4" 2" 1,220
23'-8 1/2"
2" 620
7.5 17'-8 1/8" 8'-4" 4" 2" 900
5 11'-7 3/4"
(2) 5 8'-4" 1,240
(2) 7.5 8'-4" 1,800
2" 4"
4" 3"
S
e
r
i
e
s
V
E51
Baltimore Aircoil Company
Discharge Hoods with Positive Closure Dampers
Both tapered and straight discharge hoods with factory mounted positive closure dampers and damper
actuators are available for all Series V Closed Circuit Cooling Towers. Hoods are designed to minimize
heat loss from convective air flow through an idle unit. The addition of factory installed insulation to the
hood and casing further reduces the heat loss by minimizing losses due to conduction. Heat loss data is
presented on page E52 for units without hood, with hood, and with insulated casing and hood. Damper
actuators and linkage are factory mounted on the hood.
All wiring and actuator controls must be furnished by others. 115 volt single phase power supply is
required. Damper actuators should be interlocked with the temperature control system so that the
dampers are open when the pumps are running and closed when the pumps are off.
The additional external static pressure of the tapered discharge hood with dampers may require the use
of a larger fan motor; consult selection software for verification. Consult your local BAC Representative
for unit drawing with a hood and positive closure dampers.
Engineering Data
Notes (applicable to specific models only):
1. On these models, the discharge hood surrounds the drift
eliminators and is recessed into the drift eliminator frame;
therefore, the overall height of the unit with hood equals H (of unit)
plus H (of hood) minus 4.
2. On these units, the hood sits directly on top of the casing.
3. Includes drift eliminators and skid.
4. Includes skid only. Drift eliminators are included in unit weight.
VFL-012 1 2'-11 1/8" 2'-3 1/2" 2'-6 1/2"
2
220
4
2'-11 1/8" 3'-3/8" 2'-9 1/4"
2
260
4
VFL-024 1 3'-10 1/4" 2'-3 1/2" 2'-6 1/2"
2
330
4
5'-3" 3'-3/8" 2'-9 1/4"
2
410
4
VFL-036 1 6'-11" 2'-3 1/2" 2'-6 1/2"
2
470
4
8'-2 1/2" 3'-3/8" 2'-9 1/4"
2
540
4
VFL-048 1 9'-10" 2'-3 1/2" 2'-6 1/2"
2
590
4
11'-2" 3'-3/8" 2'-9 1/4"
2
760
4
VFL-072 1 6'-11" 4'-1/2" 4'-0"
2
910
4
8'-2 1/2" 6'-3 3/4" 2'-9 1/4"
2
960
4
VFL-096 1 8'-2 1/2" 4'-1/2" 4'-0"
2
1,100
4
11'-2" 6'-3 3/4" 2'-9 1/4"
2
1,200
4
VF1-009 1 2'-11 1/8" 1'-4 1/4" 2'-10 3/8"
1
280
3
2'-11 1/8" 3'-3/8" 2'-9 1/8"
1
300
3
VF1-018 1 3'-10 1/4" 1'-4 1/4" 2'-10 3/8"
1
470
3
5'-1/4" 3'-3/8" 2'-9 1/8"
1
490
3
VF1-027 1 6'-11" 1'-4 1/4" 2'-10 3/8"
1
640
3
8'-2 1/2" 3'-3/8" 2'-9 1/8"
1
680
3
VF1-036 1 9'-10" 1'-4 1/4" 2'-10 3/8"
1
760
3
11'-2" 3'-3/8" 2'-9 1/8"
1
840
3
VF1-048 1 8'-2 1/2" 2'-3 1/2" 4'-5 1/2"
1
1,240
3
11'-2" 4'-1/2" 3'-6 1/8"
1
1,220
3
VF1-072 1 8'-2 1/2" 3'-3/8" 4'-5 1/2"
1
1,540
3
10'-5 1/8" 5'-10" 3'-6 1/8"
1
1,620
3
VF1-096 1 8'-2 1/2" 4'-1/2" 4'-1 1/2"
2
1,200
4
11'-2" 6'-3 3/4" 3'-6 1/8"
2
1,320
4
VF1-144N 1 14'-1 1/2" 3'-7 1/2" 4'-1 1/2"
2
1,750
4
16'-8" 6'-3 3/4" 3'-6 1/8"
2
1,820
4
VF1-144 1 8'-2 1/2" 6'-3 3/4" 4'-1 1/2"
2
1,550
4
11'-2" 10'-3 7/8" 3'-6 1/8"
2
1,750
4
VF1-192 2 8'-2 1/2" 4'-1/2" 4'-1 1/2"
2
2,400
4
11'-2" 6'-3 3/4" 3'-6 1/8"
2
2,640
4
VF1-216 1 14'-1 1/2" 5'-11" 4'-1 1/2"
2
2,150
4
16'-8" 10'-3 7/8" 3'-6 1/8"
2
2,400
4
VF1-288N 2 14'-1 1/2" 3'-7 1/2" 4'-1 1/2"
2
3,500
4
16'-8" 6'-3 3/4" 3'-6 1/8"
2
3,640
4
VF1-288 2 8'-2 1/2" 6'-3 3/4" 4'-1 1/2"
2
3,100
4
11'-2" 10'-3 7/8" 3'-6 1/8"
2
3,500
4
VF1-432 2 14'-1 1/2" 5'-11" 4'-1 1/2"
2
4,300
4
16'-8" 10'-3 7/8" 3'-6 1/8"
2
4,800
4
TAPERED Straight
MODEL
NUMBER
NUMBER OF
HOODS
REQUIRED
TOTAL
SHIPPING
WEIGHT (lbs)
TOTAL
SHIPPING
WEIGHT (lbs) L W H L W H
C
l
o
s
e
d
C
i
r
c
u
i
t
C
o
o
l
i
n
g
T
o
w
e
r
s
E52
...because temperature matters
Heat Loss Data
VFL Heat Loss Data (Btu/hr)
1
VF1 Heat Loss Data (Btu/hr)
1
See page E76
for Engineering
Considerations.
Notes:
1. Heat loss is based on 50F coil water and 10F ambient with a 45 mph wind. Fan(s) and pump(s) are off.
2. One inch thick PVC nitrite rubber blend thermal insulation with protective paint.
VFL-012-02G 19,200 16,500 11,000
VFL-012-12G 25,000 17,800 11,900
VFL-012-22G 29,900 19,200 12,800
VFL-012-32G/H 33,800 20,500 13,700
VFL-024-12H 48,200 28,500 19,000
VFL-024-22H 57,700 30,400 20,300
VFL-024-32H/J 65,400 32,300 21,500
VFL-036-22K 87,000 47,100 30,700
VFL-036-32K/M 98,400 49,800 32,500
VFL-048-22L 126,400 66,000 42,600
VFL-048-31L/M 138,800 69,300 44,800
VFL-048-41M 151,200 72,600 47,000
VFL-072-22N/O 210,900 84,400 56200
VFL-072-31O 234,100 87,900 58,600
VFL-072-41O/P 252,900 91,400 60,900
VFL-096-41O/P 311,700 103,600 69,000
MODEL NUMBER
(VFL Models Only)
HEAT LOSS
(Btu/hr)
UNIT w/HOOD
& POSITIVE
CLOSURE
DAMPERS
UNIT w/HOOD,
POSITIVE
CLOSURE
DAMPERS &
INSULATION
2
VF1-009-12G
24,300 17,100 10,300
VF1-009-22G
29,400 18,800 12,000
VF1-009-32G
32,900 20,500 12,000
VF1-009-42G
34,800 22,200 13,700
VF1-018-02H
34,700 25,600 15,400
VF1-018-12H
46,200 27,300 15,400
VF1-018-22J
56,000 29,100 17,100
VF1-018-32J
64,300 30,800 17,100
VF1-018-42J
70,950 32,550 18,800
VF1-027-22H/J
86,100 46,100 27,300
VF1-027-32K
97,700 49,500 29,100
VF1-027-42K
106,300 52,900 29,100
VF1-036-21L
112,600 63,200 39,300
VF1-036-31L
128,900 66,600 39,300
VF1-036-41L
145,200 70,000 43,600
VF1-036-51L
161,500 73,400 43,600
VF1-048-21M
154,900 80,200 52,900
VF1-048-31N
177,200 83,700 52,900
VF1-048-41N
197,000 85,600 54,600
VF1-072-21O 212,400 83,700 51,200
VF1-072-31O 241,100 87,100 51,200
VF1-072-41O 269,800 90,500 56,800
VF1-096-31O 286,700 97,600 60,000
VF1-096-41P 312,100 102,600 60,900
VF1-096-51Q 329,800 107,900 61,700
VF1-144N-21Q 381,400 128,300 81,300
VF1-144N-31R 429,900 134,700 82,800
VF1-144N-41R 464,800 141,400 84,400
VF1-144-21Q 385,000 139,900 88,600
VF1-144-31Q 435,500 146,900 90,200
VF1-144-41R 474,600 154,200 91,900
VF1-192-31O 576,300 228,400 153,600
VF1-192-41P 627,300 240,100 156,700
VF1-192-51Q 662,800 252,500 160,100
VF1-216-21O 579,900 194,000 122,900
VF1-216-31P 653,500 203,700 125,100
VF1-216-41P 707,300 213,800 127,300
VF1-288N-21Q 762,800 256,600 162,600
VF1-288N-31R 859,800 269,400 165,600
VF1-288N-41R 929,600 282,800 168,800
VF1-288-21Q 750,800 260,300 171,900
VF1-288-31Q 849,300 273,300 175,000
VF1-288-41R 925,600 286,800 178,300
VF1-432-21O 1,142,500 390,000 259,400
VF1-432-31P 1,287,400 409,500 264,000
VF1-432-41P 1393500 429,800 268,500
MODEL NUMBER
(VF1 Models Only)
HEAT LOSS
(Btu/hr)
UNIT w/HOOD
& POSITIVE
CLOSURE
DAMPERS
UNIT w/HOOD,
POSITIVE
CLOSURE
DAMPERS &
INSULATION
2
S
e
r
i
e
s
V
E53
Baltimore Aircoil Company
Structural Support
The recommended support arrangement for the Series V Closed Circuit Cooling Tower consists of parallel
I-beams running the full length of the unit, spaced as shown in the following drawing. Besides providing
adequate support, the steel also serves to raise the unit above any solid foundation to ensure access to the
bottom of the tower. To support a Series V Closed Circuit Cooling Tower in an alternate steel support
arrangement, consult your BAC Representative.
Notes:
1. Support beams and anchor bolts are to be selected and
installed by others.
2. All supporting steel must be level at the top.
3. Beams must be selected in accordance with accepted structural
practice. The maximum allowable deflection of beams under the
unit shall be as specified in the table above.
4. All units can be furnished with an optional vibration isolation
package, if required, to be installed between the tower and
supporting steel. When determining the length of steel beams,
allow for the length of vibration isolation rails, as they may be
longer than the tower length shown above.
5. If point vibration isolation is used, the isolators must be located
under the supporting steel, not between the support steel and the
cooling tower.
MODEL NUMBER A B
MAXIMUM
DEFLECTION
3
VFL-012 3 11 4 6 1/4
VFL-024 3 11 7 11-1/2 3/8
VFL-036 3 11 10 11-1/4 1/2
VFL-048 3 11 13 11-1/2 1/2
VFL-072 7 8-1/4 10 11-1/4 1/2
VFL-096 7 8-1/4 13 11-1/2 1/2
VF1-009 45-3/8 29-1/2 3/32
VF1-018 45-3/8 65-1/2 3/16
VF1-027 45-3/8 101-1/4 5/16
VF1-036 45-3/8 137-1/2 3/8
VF1-048 54-1/4 137-1/2 3/8
VF1-072, 096 91-5/8 127-1/2 3/8
VF1-144N 91-5/8 199-3/4 1/2
VF1-192 91-5/8 272-1/4 1/2
VF1-288N 91-5/8 416-3/4 1/2
VF1-144 139-1/4 127-1/2 3/8
VF1-216 139-1/4 199-3/4 1/2
VF1-288 139-1/4 272-1/4 1/2
VF1-432 139-1/4 416-3/4 1/2
All VFL Models
VF1-009 thru -048, -072, -096, & -144
VF1-288N & -432
VF1-144N, -192, -216 & -288
C
l
o
s
e
d
C
i
r
c
u
i
t
C
o
o
l
i
n
g
T
o
w
e
r
s
E54
...because temperature matters
1.0 Closed Circuit Cooling Tower
1.1 General: Furnish and install ____factory assembled, forced
draft, centrifugal fan, closed circuit cooling tower(s) with vertical
air discharge, conforming in all aspects to the specifications and
schedules as shown on the plans. Overall dimensions shall not
exceed approximately ____ft (m) long x ____ft (m) wide x ____ft
(m) high. The total connected fan horsepower shall not exceed
____HP (kW). The total connected pump horsepower shall not
exceed ____HP (kW). The closed circuit cooling tower(s) shall be
Baltimore Aircoil Company Model(s) ________________.
1.2 Thermal Capacity (water as heat transfer fluid): The
closed-circuit cooling tower(s) shall be warranted by the
manufacturer to cool ______US gpm (lps) of _______ water from
____F (C) to ____F (C) at ____F (C) entering wet-bulb
temperature. The thermal performance shall be certified by the
Cooling Technology Institute in accordance with CTI Certification
Standard STD-201. A manufacturers performance guarantee or
performance bond without CTI Certification will not be accepted.
(Alternate) 1.2 Thermal Capacity (aqueous glycol solution as
heat transfer fluid): The closed circuit cooling tower(s) shall be
warranted by the manufacturer to cool ________US gpm (lps) of
_____% by volume ethylene/propylene glycol solution from
______F (C) to _____F (C) at _____F (C) entering wet-bulb
temperature. Coil pressure drop shall not exceed ________ psi
(kPa). Basis for thermal performance rating shall be the Cooling
Technology Institute (CTI) certified rating for water cooling
appropriately adjusted for the thermal properties of the aqueous
glycol solution used. Additionally, the thermal performance of the
product line with water as the heat transfer fluid shall be certified
by the CTI in accordance with CTI Certification Standard
STD-201. Manufacturers' performance guarantees or
performance bonds without CTI Certification of water ratings
shall not be accepted.
1.3 Corrosion Resistant Construction: Unless otherwise noted in
this specification, all steel panels and structural members shall be
constructed of heavy-gauge G-235 (Z700 metric) hot-dip
galvanized steel, with all sheared edges given a protective
coating of zinc-rich compound.
(Alternate) 1.3 Corrosion Resistant Construction: Unless
otherwise noted in this specification, all steel panels and
structural members shall be protected with the BALTIBOND
F/85
F/78
F
HXV Closed Circuit Hybrid Cooling Towers deliver fully rated thermal performance over a wide range of flow
and temperature requirements. Distinct advantages of the HXV include plume abatement, significant water
savings over traditional water-cooled equipment, and its suitability for high temperature cooling (>180F).
Standard design features satisfy todays environmental concerns, minimize installation costs, maximize
year-round operating reliability, and simplify maintenance requirements.
HXV Closed Circuit Cooling Towers
Plume abatement
Maximum water savings
High temperature cooling (>180F)
Low energy consumption
Low installed cost
Easy maintenance
Reliable year-round operation
Long service life
ASME B31.5 compliant prime surface coil
Five-year warranty on mechanical equipment
HXV Closed Circuit Hybrid
Cooling Towers
C
l
o
s
e
d
C
i
r
c
u
i
t
C
o
o
l
i
n
g
T
o
w
e
r
s
E58
...because temperature matters
H
X
V
E59
Baltimore Aircoil Company
Benefits
Plume Abatement
The HXV offers a combination of sensible, adiabatic, and evaporative heat transfer to significantly
reduce any plume that may occur with conventional evaporative cooling equipment. During the
coldest times of the year, when the potential for visible discharge is greatest, the HXV operates
100% dry, completely eliminating plume.
Maximum Water Savings
Water savings are achieved throughout the year with each of three different operating modes of the
HXV. In some areas, the water cost savings alone can pay for the equipment in as little as two years!
At peak conditions in the dry/wet operating mode, a significant amount of heat is removed
by sensible heat transfer, providing reduced water consumption versus conventional
evaporative cooling
When the heat load and/or ambient temperatures drop, water consumption is further
reduced in the adiabatic operating mode
Water consumption is totally eliminated in the dry operating mode
See page E71 for details on operating modes.
High Temperature Cooling
The finned dry coil tempers the incoming fluid, allowing higher inlet water temperatures than
traditional closed circuit cooling towers.
Low Energy Consumption
The HXV provides heat rejection at the lowest possible energy input and maintenance
requirements via:
High efficiency, low horsepower axial fans
Closed loop cooling, which minimizes process fouling
Patented combined flow technology, which reduces evaporation directly off the coil,
minimizing the potential for scaling and fouling
Parallel flow of air and spray water, which eliminates scale-promoting dry spots
Variable Frequency Drives
ENERGY-MISER
Power Train
(Not Shown)
Premium quality, solid-backed,
multi-groove belt
Corrosion resistant cast aluminum sheaves
Heavy-duty bearings (280,000
hour average life)
Cooling tower duty fan motor
Five-year motor and drive warranty
Low HP Axial Fan(s)
(Not Shown)
Quiet operation
Corrosion resistant aluminum
Water Distribution System
Overlapping spray patterns ensure proper
water coverage
Large orifice, non-clog nozzles
Prime Surface Coil (Not Shown)
Continuous serpentine, steel tubing
Hot-dip galvanized after fabrication (HDGAF)
Pneumatically tested at 375 psig
Sloped tubes for free drainage of fluid
ASME B31.5 compliant
When required, orders shipping into Canada
are supplied with a CRN
Dry Finned Coil
Copper tubing with high density aluminum fins
Pneumatically tested at 320 psig
Sloped tubes for free drainage of fluid
BACross
Fan System
The ENERGY-MISER
Fan System consists of two standard single-speed fan motor and drive
assemblies. One drive assembly is sized for full speed and load, and the other is sized approximately
2/3 speed and consumes only 1/3 the design horsepower. This configuration allows the system to be
operated like a two-speed motor, but with the reserve capacity of a standby motor in the event of fail-
ure. As a minimum, approximately 70% capacity will be available from the low horsepower motor, even
on a design wet-bulb day. Controls and wiring are the same as those required for a two-speed, two-
winding motor. Significant energy savings are achieved when operating at low speed during periods of
reduced load and/or low wet-bulb temperatures.
Independent Fan Operation
Models HXV-64X and Q64X are provided with one fan motor driving two fans as standard. Models
HXV-66X and Q66X are provided with two fan motors driving three fans as standard. The Independent
Fan option consists of one fan motor and drive assembly for each fan to allow independent operation,
providing an additional step of fan cycling and capacity control.
Low Sound Operation
The low sound levels generated by HXV Closed Circuit Hybrid Cooling Towers make them suitable for
installation in most environments. For extremely sound sensitive installations, factory designed, tested
and rated sound attenuation is available for both the air intake and discharge.
C
l
o
s
e
d
C
i
r
c
u
i
t
C
o
o
l
i
n
g
T
o
w
e
r
s
E66
...because temperature matters
Accessories
External Service Platforms
For external service, louver face and access door platforms can be added to the unit when purchased or
as an aftermarket item. Safety cages and safety gates are also available. All components are designed
to meet OSHA requirements.
Internal Ladder
For access to the motor and drive assemblies, an internal ladder is available.
Internal Service Platforms
For access to the motor and drive assemblies, an internal ladder and upper service platform with
handrails is available. Safety gates are available for all handrail openings. All components are designed
to meet OSHA requirements.
Vibration Cutout Switch
A factory mounted vibration cutout switch is available to
effectively protect against equipment failure due to
excessive vibration of the mechanical equipment
system. BAC can provide either a mechanical or
solid-state electronic vibration cutout switch in a NEMA
4 enclosure to ensure reliable protection. Additional
contacts can be provided to activate an alarm.
Basin Heaters
Although most HXV units will operate dry in the winter, basin heaters are available for freeze protection
when required. Basin heaters prevent freezing of the water in the cold water basin when the unit is idle.
Factory-installed heaters, which maintain +40F (4.4C) water temperature, are a simple and
inexpensive way of providing such protection.
Heater Sizing Data
No. of HEATERS kW per HEATER No. of HEATERS kW per HEATER
HXV-64X, Q64X 1 12 1 16
HXV-66X, Q66X 1 16 1 21
MODEL NUMBERS
0F (-17.8C) AMBIENT HEATERS -20F (-28.9C) AMBIENT HEATERS
Vibration Cutout Switch
H
X
V
E67
Baltimore Aircoil Company
Electric Water Level Control Package
The electric water level control replaces the standard mechanical
makeup valve when a more precise water level control is
required. This package consists of a conductance-actuated level
control mounted in the basin and a solenoid activated valve in
the make-up water line. The valve is slow closing to minimize
water hammer.
Flow Control Package
A flow control package is available to provide maximum plume control and water savings. This package
consists of a temperature sensor, a 3-way flow control valve arrangement with actuator, and all
connecting piping. 3-way flow control valve arrangement shown below for single prime surface and
double prime surface coil connections.
Electric Water Level
Control Package
Single Prime
Surface Coil
Connections
Double Prime
Surface Coil
Connections
FLUID IN
FLUID OUT
FLUID IN
FLUID OUT
Accessories
C
l
o
s
e
d
C
i
r
c
u
i
t
C
o
o
l
i
n
g
T
o
w
e
r
s
E68
...because temperature matters
Extended Lubrication Lines
Extended lubrication lines are available for
lubrication of the fan shaft bearings. Grease fittings
are located inside the plenum area next to the
access door.
High Temperature Wet Deck
Optional high temperature wet deck material is available for high entering fluid temperatures.
Air Inlet Screens
Wire mesh screens can be factory-installed over the inlet
louvers to prevent debris from entering the tower.
Basin Sweeper Piping
Basin sweeper piping provides an effective method of prevent-
ing debris from collecting in the cold water basin of the tower. A
complete piping system, including nozzles, is provided in the
tower basin for connection to side stream filtration equipment
(by others).
Grease fittings at the access door & bearings with the extended lubrication line option
Basin Sweeper Piping
H
X
V
E69
Baltimore Aircoil Company
Do not use for construction. Refer to factory certified dimensions. This brochure includes data current
at time of publication, which should be reconfirmed at the time of purchase. Up-to-date engineering data,
free product selection software, and more can be found at www.BaltimoreAircoil.com.
Engineering Data
1" MAKE UP
(4) 4" BFW FLUID OUT
(4) 4" BFW FLUID IN
ACCESS DOOR
(THIS END ONLY)
ACCESS DOORS
THIS SIDE ONLY
3" OVERFLOW
2" DRAIN
3'-2 3/8"
HXV Q64x
2'-8 3/8"
A
2
2
'-
3
1
/
8
"
11'-10"
ACCESS DOOR
(THIS END ONLY)
8
'-
8
3
/
4
"
(4) 4" BFW FLUID IN
(4) 4" BFW FLUID OUT
6" BFW FLUID OUT
6" BFW FLUID IN
F
AIR
INLET
HXV 64x
(2) 4" BFW FLUID IN
(2) 4" BFW FLUID OUT
INLET
AIR
2
'-
7
1
/
2
"
1'-8 1/4" 6"
12'-1 1/4"
2'-2 1/4"
3
"
1
1
1
/
2
"
2'-7 1/8"
F
2
2
'-
3
1
/
8
"
A
2'-2 3/8"
8
'-
8
3
/
4
"
11'-10"
3'-2 3/8"
2'-8 3/8"
A
2
2
'-
8
5
/
8
"
11'-10"
ACCESS DOOR
(THIS END ONLY)
9
'-
2
1
/
4
"
(4) 4" BFWFLUID IN
8" BFWFLUID OUT
8" BFWFLUID IN
F
(4) 4" BFWFLUID OUT
AIR
INLET
HXV 66x HXV Q66x
(2) 4" BFWFLUID IN
(2) 4" BFWFLUID OUT
INLET
AIR
3
'-
1
"
2'-0 3/8" 6"
18'-1 1/4"
2'-2 1/4"
8
1
/
2
"
1
'-
5
"
2'-7 1/8"
1" MAKE UP
(4) 4" BFWFLUID OUT
(4) 4" BFWFLUID IN
ACCESS DOOR
(THIS END ONLY)
ACCESS DOORS
THIS SIDE ONLY
3" OVERFLOW
2" DRAIN
F
2
2
'-
8
5
/
8
"
A
2'-2 3/8"
9
'-
2
1
/
4
"
11'-10"
HXV-64X/Q64X
HXV-66X/Q66X
Notes:
1. Operating weight is for the tower with the water level in the cold
water basin at the overflow.
2. The actual size of the inlet and outlet connection may vary with
the design flow rate. Consult the unit print for dimensions.
3. Pipe sizes are nominal diameters. Standard connections are
beveled-for-welding (BFW).
4. Dimensional drawings show standard (right hand) arrangements
with the standard finned coil arrangement.
5. Nominal tons of cooling represents 3 gpm of water from 95F to
85F at a 78F entering wet-bulb temperature.
FAN PUMP OPERATING
1
SHIPPING
HEAVIEST
SECTION A F
HXV-641-OM 160
30 5
24,800 15,800 6,800
14' 2" 2' 0"
HXV-642-OM 180
30 5
26,300 16,900 7,800
14' 2" 2' 9-1/4"
HXV-Q640-OM 164
30 5
26,300 16,900 7,800
14' 1" 2' 7-3/8"
HXV-Q641 191
30 5
29,300 18,900 9,900
14' 1" 4' 1-7/8"
HXV-661-OM 252
30 & 15 7.5
35,700 22,400 9,700
14' 7-1/2" 2' 0"
HXV-662-OM 283
30 & 15 7.5
38,000 23,900 11,300
14' 7-1/2" 2' 9-1/4"
HXV-Q660-OM 268
30 & 15 7.5
38,000 23,900 11,300
14' 5-1/2" 2' 5-3/8"
HXV-Q661 305 30 & 15 7.5 42,400 27,100 14,500 14' 5-1/2" 3' 11-7/8"
MODEL
NUMBER
MOTOR HP WEIGHTS (lbs) DIMENSIONS
NOMINAL
TONS
5
C
l
o
s
e
d
C
i
r
c
u
i
t
C
o
o
l
i
n
g
T
o
w
e
r
s
E70
...because temperature matters
Modes of Operation
Notes:
1. During dry mode, two-speed, variable frequency drive (VFD), or ENERGY-MISER
Corrosion Protection
System: All steel panels, support structure, hot and cold water
basins, fan deck and fan cylinder shall be protected with the
BALTIBOND
Fan System, two-speed motors, or variable frequency drives can also be used to reduce sound during
periods of non-peak thermal loads. For more information on sound and how it relates to evaporative cooling
equipment, see page J20. For detailed low sound selections, please consult your local BAC Representative.
E
n
g
i
n
e
e
r
i
n
g
C
o
n
s
i
d
e
r
a
t
i
o
n
s
E79
Baltimore Aircoil Company
Protection Against Basin Water Freezing
When a unit is shut down in freezing weather, the basin water must be protected by draining to an indoor
auxiliary remote sump tank (see page H5 for remote sump engineering data; page J16 for sizing guidelines)
or by providing supplementary heat to the cold water basin. Supplementary heat can be provided by electric
immersion heaters or in some cases, hot water or steam coils, or steam injectors. All exposed water piping,
make-up lines, and spray pumps (if applicable) that do not drain at shutdown should be traced with electric
heater tape and insulated.
When dry operation is planned for low ambient conditions, centrifugal fan units should be supplied with
oversized fan motors to prevent motor overload when the spray water is not operating. Dry operation with
standard fan motors is acceptable for axial fan units. For remote sump applications, the spray water pump
must be selected for the required flow at a total head which includes the vertical lift, pipe friction (in supply
and suction lines) plus the required pressure at the inlet header of the water distribution system (2.0 psi for
FXV models; 1.0 psi for Series V models). A valve should always be installed in the discharge line from the
pump to permit adjusting flow to the unit requirement. Inlet water pressure should be measured by a
pressure gauge installed in the water supply riser at the spray water inlet, and adjusted to the specified inlet
pressure. See page J16 for more information.
Indoor Installations (Applicable to Series V Models Only)
Many indoor installations require the use of inlet and/or discharge ductwork. Units installed with inlet
ductwork must be ordered with solid-bottom panels. Generally, intake ducts are used only on smaller
units while the equipment room is used as a plenum for larger units. Discharge ductwork will normally be
required to carry the saturated discharge air from the building.
Both intake and discharge ductwork must have access doors to allow servicing of the fan assembly, drift
eliminators, and water distribution system. All ductwork should be symmetrical and designed to provide even
air distribution across the face of air intakes and discharge openings.
WARNING:
The discharge opening must be positioned to prevent the introduction of discharge air into the fresh air
intakes serving the unit or the ventilation systems of adjacent buildings.
Note: Axial fan units are not suitable for indoor installations.
Safety
Adequate precautions, appropriate for the installation and location of these products, should be taken to
safeguard the public from possible injury and the equipment and the premises from damage. Operation,
maintenance and repair of this equipment should be undertaken only by personnel qualified to do so. Proper
care, procedures and tools must be used in handling, lifting, installing, operating, maintaining, and repairing
this equipment to prevent personal injury and/or property damage.
C
l
o
s
e
d
C
i
r
c
u
i
t
C
o
o
l
i
n
g
T
o
w
e
r
s
E80
...because temperature matters
Fluid Compatibility
The fluid to be cooled must be compatible with the coil material (standard serpentine and cleanable header
coils are carbon steel, hot-dip galvanized on the outside only). Fluids not compatible with coil materials
can lead to corrosion and tube failure. Certain fluids may require occasional pressure cleaning or
mechanical cleaning of the inside of coil tubes. In such cases the coil must be designed to provide this
capability (Optional Coil Configurations: for FXV see page E19, for Series V see page E39, and for HXV see
page E63).
Open/Closed System
The standard galvanized steel serpentine and cleanable header serpentine coils are carbon steel,
hot-dip galvanized on the outside only, and are intended for application on closed, pressurized
systems which are not open to the atmosphere. Stainless steel coils or cleanable coil units (with tubes
hot-dip galvanized inside and out) are available to cool corrosive fluids or water and ethylene/propylene
glycol solutions in systems open to the atmosphere (Optional Coil Configurations: for FXV see page E19, for
Series V see page E39, and for HXV see page E63).
Protection Against Coil Freezing
At below freezing ambient conditions, the closed circuit cooling tower can experience heat loss even without
the recirculating spray water pump and fans in operation. Without a heat load on the circulating fluid, coil
freezing can occur even at full flow. Protective means are readily available to avoid potential freeze
problems. Where the system will permit, the best protection against coil freeze-up is the use of an
industrially inhibited anti-freeze solution. When this is not possible, the system must be designed to meet
both of the following conditions:
1. Maintain minimum recommended flow through the coil at all times, as per the table below:
See product sections for
applicable heat loss data:
FXV - page E29
Series V - page E52
HXV - page E72
MODEL MINIMUM FLOW (GPM)
FXV-42X, 43X, 44X 75
FXV-Q44X 150
FXV-64X, 66X 110
FXV-Q64X, Q66X 220
FXV-288-X1X 275
FXV-288-XQX 550
FXV-364-X1X 275
FXV-364-XQX 550
HXV-6XX 110
HXV-Q6XX 220
VFL-012 thru 048 65
VFL-072 thru 096 125
VF1-009 thru 036 50
VF1-048 75
VF1-072 100
VF1-096 thru 144N 125
VF1-192 thru 288N 250
VF1-144 thru 216 200
VF1-288 thru 432 400
E
n
g
i
n
e
e
r
i
n
g
C
o
n
s
i
d
e
r
a
t
i
o
n
s
E81
Baltimore Aircoil Company
2. Maintain a heat load on the circulating fluid so that the temperature of the fluid leaving the coil will not be
below 45F (7.2C).
If the process load is extremely light, or if the process is periodically shut off entirely, then an auxiliary heat
load must be applied to the circulating fluid when below freezing ambient temperatures exist to prevent
damage to the coil. Refer to the Heat Loss Data table (for FXV see page E29, for Series V see page E52,
and for HXV see page E72) for the auxiliary heat load requirement. The amount of auxiliary heat necessary
to prevent coil freezing can be further reduced by the use of a positive closure damper hood and insulation.
Draining the coil is not recommended as a normal method of freeze protection. However, draining is
acceptable as an emergency method of freeze protection. Frequent draining can promote corrosion inside
the coil tubes. If the coil is not protected by an industrially inhibited anti-freeze solution, an automatic drain
valve and air vent is recommended to drain the coil if flow stops or fluid temperature drops below 45F
(7.2C) when the ambient temperature is below freezing. Note that cold water basin heaters will not provide
freeze protection for the coil.
Code Requirement
Standard coils are ASME B31.5 compliant and are provided with a Canadian Registration Number (CRN)
when required. State or local codes, or certain applications may require the use of pressure vessels
designed, fabricated, tested and U stamped in accordance with the ASME Boiler and Pressure Vessel
Code, Section VIII, Division I. In such cases, the optional ASME U Stamp coil must be provided.
Warranties
Please refer to the Limitation of Warranties applicable to and in effect at the time of the sale/purchase of
these products.
E
v
a
p
o
r
a
t
i
v
e
C
o
n
d
e
n
s
e
r
s
F1
...because temperature matters
Evaporative Condensers
Evaporative condensers provide heat rejection for many types of systems, and the specific application
will largely determine which BAC Evaporative Condenser is best suited for a project. The table on page
F4 is intended as a general guide.
The information contained within this section is geared towards the use of evaporative condensers in
the HVAC and light industrial markets only. Evaporative condensers are used in these markets to
provide lower condensing temperatures and compressor horsepower savings of up to 15 percent when
compared with traditional systems. For technical support with a refrigeration application, contact your
local BAC Refrigeration Sales Representative.
Principle of Operation
The vapor to be condensed is circulated through a condensing coil, which is continually wetted on the
outside by a recirculating water system. Air is pulled over the coil, causing a small portion of the
recirculating water to evaporate. The evaporation removes heat from the vapor in the coil, causing it to
condense.
Configuration
BAC manufactures two types of evaporative condensers: combined flow and counterflow.
Combined Flow
Combined flow is the use of both a condensing coil and wet deck surface for heat transfer in an
evaporative condenser. The addition of wet deck surface to the traditional evaporative condenser design
reduces evaporation in the coil section, reducing the potential for scaling and fouling. BACs combined
flow evaporative condensers utilize parallel flow of air and spray water over the coil, and crossflow
air/water flow through the wet deck surface.
O
v
e
r
v
i
e
w
F2
Baltimore Aircoil Company
In parallel flow, air and water flow over the coil in the same direction. In the wet deck section of BACs
combined flow evaporative condensers, air and water interact in a crossflow configuration: water flows
vertically down the wet deck as air flows horizontally across it.
Counterflow
In a counterflow evaporative condenser design, the flow of the air is in the opposite direction of the spray
water. In BACs counterflow evaporative condensers, air travels vertically up through the unit while the spray
water travels vertically down over the coil.
Combined Flow: Crossflow
configuration over the wet deck
Water Down
Air Across
Combined Flow: Parallel flow of
air and water over the coil
Counterflow Configuration
Water Down
Air Up
E
v
a
p
o
r
a
t
i
v
e
C
o
n
d
e
n
s
e
r
s
F3
...because temperature matters
Fan System
The flow of air through most factory assembled evaporative
condensers is provided by one or more mechanically driven fans.
The fan(s) may be axial or centrifugal, each type having its own
distinct advantages.
Axial fan units require approximately half the fan motor
horsepower of comparably sized centrifugal fan units, offering
significant life-cycle cost savings.
Centrifugal fan units are capable of overcoming reasonable
amounts of external static pressure ( 0.5), making them
suitable for both indoor and outdoor installations. Centrifugal fans
are also inherently quieter than axial fans, although the difference
is minimal and can often be overcome through the application of
optional low sound fans and/or sound attenuation on axial fan
units.
Induced Draft
The rotating air handling components of induced draft equipment are mounted in the top deck of the
unit, minimizing the impact of fan noise on near-by neighbors and providing maximum protection from
fan icing with units operating in sub-freezing conditions. The use of corrosion resistant materials ensures
long life and minimizes maintenance requirements for the air handling components.
Forced Draft
Rotating air handling components are located on the air inlet face at the base of forced draft units,
facilitating easy access for routine maintenance and service. Additionally, location of these
components in the dry entering air stream extends component life by isolating them from the corrosive
saturated discharge air.
Capacity Range
In the following table, product capacities are called out in nominal ammonia (R-717) or R-22 tons. All
capacities shown are for a single cell; multiple cell units can be applied to achieve larger capacities.
BACs product selection software is available at www.BaltimoreAircoil.com.
Typical Applications
A list of typical applications is provided on page F4 for your reference.
Axial Fan
Centrifugal Fan
O
v
e
r
v
i
e
w
F4
Baltimore Aircoil Company
Evaporative Condenser
Product Lines
Principle of
Operation
Configuration Combined Flow Combined Flow
Fan System Axial Fan, Induced Draft Axial Fan, Induced Draft
Small to large HVAC & industrial
applications
Very large industrial refrigeration and process projects
Typical
Applications
Capacity Range 64 to 962 Nominal Ammonia Tons 645 to 1888 Nominal Ammonia Tons
CXV - T CXV
E
v
a
p
o
r
a
t
i
v
e
C
o
n
d
e
n
s
e
r
s
F5
...because temperature matters
VC1 VC2 VCL
Counterflow Counterflow Counterflow
Centrifugal Fan, Forced Draft Axial Fan, Forced Draft Centrifugal Fan, Forced Draft
Small to medium HVAC systems and
sound-sensitive industrial projects
Medium to large HVAC systems,
industrial projects, and unrestricted
installations
HVAC systems, supermarkets, ice
rinks, and sound-sensitive industrial
projects
Installations with limited plan area Installations with limited plan area
Installations with extremely low height
requirements
Indoor installations Indoor installations
Skid packages
138 to 1914 Nominal R-22 Tons 16 to 299 Nominal R-22 Tons 10 to 1608 Nominal R-22 Tons
Series V
DRIFT
ELIMINATORS
SPRAY PUMP
Water Distribution System
AIR
INLET
LIQUID
OUT
WARM AIR
OUT
Condensing Coil
VAPOR
IN
Baltimore Aircoil Company
Reduces Fouling Tendancy
Advanced coil technology, applied on FXV Closed Circuit
Cooling Towers and CXV Evaporative Condensers, is used to
reduce the tendency to accumulate fouling and scale on the
coils exterior surface. Four facets of the unique product design
contribute to the reduced tendency for fouling:
The Air and Water Flow in a Parallel Path:
Better water coverage over the coil is maintained because the
air and spray water flow in a smooth, parallel, downward path
over the coil. With this parallel flow, the spray water is not
stripped from the underside of the tubes by the upward air flow,
as on other, conventional designs. This eliminates
scale-producing dry spots on the coil.
Increased Water Flow Over the Coil:
The spray water flow rate over the coil plan area is more than
twice that of conventional units. This heavy coverage provides
continuous flooding of the primary heat transfer surface for
decreased fouling potential. Improved spray water coverage is
provided at no increase in pumping horsepower due to the
unique heat transfer system of the design.
Evaporative Cooling Occurs Primarily in the
Wet Deck:
FXV & CXV models incorporate combined flow technology,
using both primary and secondary heat transfer surfaces. The
primary heat transfer surface is the serpentine coil, which is the
most important and expensive component in the unit. In BACs
combined flow design, more than 80% of the latent heat transfer
occurs in the secondary surface, PVC cooling tower wet deck, effectively moving the evaporation process
away from coil. The coil is protected from detrimental fouling and scale since it relies primarily on sensible
conduction/convection heat transfer and, therefore, is less susceptible to scale formation than are other
designs that rely primarily on latent (evaporative) heat transfer.
Colder Spray Water:
Spray water at a colder temperature has a lower propensity to form scale because scale-forming
compounds remain in solution, rather than deposit as solids on the coil exterior surface. Spray water flowing
over the coil is commonly 6F to 8F colder than on other designs due to the addition of the secondary heat
transfer surface. Colder spray water alone typically reduces the scaling potential* by 25% compared to other
designs. This is over and above the fouling reductions achieved by the first three factors described above.
*Using Langelier Index
P
r
o
d
u
c
t
R
e
p
o
r
t
Advanced Coil Technology
F6
PROCESS FLUID OR
REFRIGERANT
Advanced Coil Technology
PROCESS FLUID OR
REFRIGERANT
Conventional Designs
E
v
a
p
o
r
a
t
i
v
e
C
o
n
d
e
n
s
e
r
s
Series V
Evaporative Condensers
F7
Product Detail
Product Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .F8
Benefits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .F10
Construction Details . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .F12
Custom Features & Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . .F14
Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .F17
Engineering Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .F20
Structural Support . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .F30
Engineering Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .F32
Engineering Considerations . . . . . . . . . . . . . . . . . . . . . . . . . . . .F58
S
e
r
i
e
s
V
F8
Baltimore Aircoil Company
Single Model Capacity:
10 1,914 Nominal R-22 Tons
(7 1,357 Nominal R-717 Tons)
Series V Evaporative Condensers deliver fully rated thermal performance over a wide range of heat rejection
and temperature requirements for various refrigerants. VC1 and VCL models can be installed indoors and
minimize sound levels, and low profile models (VCL) are available to accommodate limited ceiling or
enclosure heights. VC1-C models are designed to fit in standard dry van containers to minimize ocean freight
costs. The Series V minimizes installation costs, provides year-round operating reliability, and simplifies
maintenance requirements.
Series V Evaporative Condensers
Suitable for indoor and outdoor installations
(VC1 and VCL models)
Suitable for locations with limited ceiling or
enclosure heights (VCL models)
Low sound (VC1 and VCL models)
Low ocean freight costs (VC1-C models)
Lower HP models (VC2 models)
Single side air inlet
Low energy consumption
Low installed cost
Easy maintenance
Reliable year-round operation
Long service life
ASME B31.5 compliant coil
Five-year warranty on mechanical equipment
Series V
Evaporative Condensers
E
v
a
p
o
r
a
t
i
v
e
C
o
n
d
e
n
s
e
r
s
F9
...because temperature matters
S
e
r
i
e
s
V
F10
Baltimore Aircoil Company
Benefits
Installation and Application Flexibility
Indoor Installations Centrifugal fan units
(VC1 and VCL models) can overcome the static
pressure imposed by external ductwork, allowing
these units to be installed indoors.
Low Profile Models The fan section of low
profile units (VCL models) is adjacent to the
casing section to yield models suitable for use in
height sensitive installations. Low profile models
are available in capacities from 16 to 299
nominal R-22 tons (11 to 212 nominal R-717
tons), which correspond to heights of 5 2-1/4
and 8 4-3/4, respectively.
Low Sound
Single Air Inlet Particularly sound-sensitive areas can be accommodated by facing the quiet
blank-off panel to the sound-sensitive direction.
Centrifugal Fans Centrifugal fans units (VC1 and VCL models) have inherently low sound
characteristics.
Low Ocean Freight Cost
Size VC1-C models are designed to fit in
standard dry van containers to minimize ocean
freight costs.
Low Energy Consumption
Evaporative cooling equipment minimizes the
energy consumption of the entire system
because it provides lower operating temperatures.
The owner saves money while conserving natural
resources and reducing environmental impact.
Evaporative condensers provide lower condensing
temperatures and can offer significant horsepower savings over conventional air-cooled and
water-cooled condensing systems.
Low Profile Series V
Evaporative Condenser
VC1-C Model in Dry Van Container
E
v
a
p
o
r
a
t
i
v
e
C
o
n
d
e
n
s
e
r
s
F11
...because temperature matters
Low Installed Cost
Support All models mount directly on two parallel I-beams and ship complete with motors and
drives factory-installed and aligned.
Modular Design Large models ship in multiple
sections to minimize the size and weight of the
heaviest lift, allowing for the use of smaller, less
costly cranes.
Easy Maintenance
Internal Access The interior of the unit is easily
accessible for adjusting the float valve, cleaning the
strainer or flushing the basin.
Reliable Year-Round Operation
Drive System The fans, motor, and drive system are
located outside of the moist discharge airstream,
protecting them from moisture condensation and icing.
Backed by a five-year fan drive and motor warranty,
these units are suitable for year-round operation.
Long Service Life
Materials of Construction Various materials are available to
meet the corrosion resistance, unit operating life, and budgetary
requirements of any project (see page F14 for construction options).
The water level control is easily
reached from the access door
Drive System
S
e
r
i
e
s
V
F12
Baltimore Aircoil Company
Construction Details
Lower Section:
VC1 Models
Lower Section:
VC2 Models
VC2-N Models
Upper Section:
VC1 & VC2 Models
1
1
1
1
2
3
4
5
6
7
7
8
8
10
10
11
11
VCL Models
1
2
3
4
5
6
7
8
8
7
E
v
a
p
o
r
a
t
i
v
e
C
o
n
d
e
n
s
e
r
s
F13
...because temperature matters
Heavy Duty Construction
G-235 (Z700 metric) hot-dip galvanized
steel panels
Water Distribution System
Schedule 40 PVC spray branches
Large orifice, non-clog nozzles
Grommetted for easy maintenance
Coil
Continuous serpentine, steel tubing
Hot-dip galvanized after fabrication (HDGAF)
Pneumatically tested at 375 psig
Sloped tubes for free drainage of fluid
ASME B31.5 compliant
Orders shipping into Canada are supplied
with a CRN
Drift Eliminators
Polyvinyl chloride (PVC)
Impervious to rot, decay and biological attack
Flame spread rating of 5 per ASTM E84-77a
Assembled in easy to handle sections
Fan Drive System
(VC1/VCL Models)
V-belt drive
Heavy-duty bearings
(280,000 hour average life)
Cooling tower duty fan motor
Five-year motor and drive warranty
Low Sound Centrifugal Fan(s)
(VC1/VCL Models)
Quiet operation
Recirculating Spray Pump
Close coupled, bronze fitted centrifugal pump
Totally enclosed fan cooled (TEFC) motor
Bleed line with metering valve installed from
pump discharge to overflow
Access Door
Circular access door
Strainer (Not Shown)
Anti-vortexing design to prevent air
entrainment
Fan Drive System
(VC2 Models Only)
V-belt drive
Heavy-duty bearings
(280,000 hour average life)
Extended lubrication lines
Cooling tower duty fan motor
Five-year motor and drive warranty
Low HP Axial Fan(s)
(VC2 Models)
Corrosion resistant aluminum
1
2
3
4
5
6
7
8
9
10
11
S
e
r
i
e
s
V
F14
Baltimore Aircoil Company
Construction Options
Standard Construction:
Steel panels and structural elements are constructed of heavy-gauge G-235 hot-dip galvanized steel.
Optional BALTIBOND
Corrosion
Protection System).
Optional Water-Contact Stainless Steel Construction:
A cost effective alternative to all stainless steel construction, all components that are exposed to the
recirculating water are provided in Type 304 stainless steel. The remaining components are
constructed of the base material of construction (galvanized steel or the BALTIBOND
Corrosion
Protection System).
See page J4 for more details on the materials described above.
Coil Configurations
Standard Serpentine Coil:
The standard condensing coil is constructed of continuous lengths of all prime surface steel, hot-dip
galvanized after fabrication (HDGAF).
Optional Extended Surface Coil:
Coils are available with selected rows finned at 5 fins per inch for wet/dry applications. The coil is
hot-dip galvanized after fabrication (HDGAF).
Optional Stainless Steel Coil:
Coils are available in Type 304 stainless steel for specialized applications.
Custom Features and Options
E
v
a
p
o
r
a
t
i
v
e
C
o
n
d
e
n
s
e
r
s
F15
...because temperature matters
Optional ASME U Stamp Coil:
This coil meets the requirements of the ASME Boiler and Pressure Vessel Code, Section VIII,
Division 1, and bears the ASME U stamp. ASME coils are hot-dip galvanized after fabrication
(HDGAF).
Multiple Refrigerant Circuit Coils:
In general, multiple circuit coils are required primarily on halocarbon refrigerant systems where it is
common practice to maintain individual compressor systems. Also, a circuit can be isolated to provide
cooling of a water or glycol loop for compressor jacket cooling. A wide range of multiple circuit
arrangements are available.
All coils are designed for low pressure drop with sloping tubes for free drainage of fluid. Each coil is
pneumatically tested at 375 psig (2586 kPa) and is ASME B31.5 compliant. Orders shipping into
Canada are supplied with a CRN.
Other coil configurations are available for specific applications. Contact your local BAC Representative
for details.
Fan Drive System
The fan drive system provides the cooling air necessary to
reject unwanted heat from the system to the atmosphere.
Dynamically balanced, forwardly curved, centrifugal fans
driven by matched V-belts with taper lock sheaves designed
for not less than 150% of the motor nameplate horsepower
are standard on VC1 and VCL models. Two stage, axial flow
fans are mounted in series in a close-fitting cylinder with a
smooth contoured inlet ring and intermediate guide vanes
to maximize fan efficiency on VC2 models.
Cooling tower duty fan motors, custom engineered for BAC
to provide maximum performance for evaporative cooling
service, are provided and backed by BACs comprehensive
five-year motor and fan drive warranty.
Standard Drive System,
VC1 and VCL models
Standard Drive System, VC2 models
S
e
r
i
e
s
V
F16
Baltimore Aircoil Company
ENERGY-MISER
Fan System
The ENERGY-MISER
Fan System
E
v
a
p
o
r
a
t
i
v
e
C
o
n
d
e
n
s
e
r
s
F17
...because temperature matters
Accessories
Ladder, Safety Cage, Gate and Handrails (VC1 and VC2 Models Only)
In the event the end-user elects to provide access to the top of the unit, VC1 and VC2 models can be
furnished with ladders extending from the base of the unit to the top, as well as safety cages, safety
gates and handrail packages. All components are designed to meet OSHA requirements. All access to
the top of the equipment must be made in accordance with applicable governmental occupational
safety standards.
NOTE: When these access options are employed, the condenser must be equipped with steel drift eliminators
External Platform
(Models VC1-386 thru -1608 and VC2-319 thru -1914 Only)
Models VC1-386 thru -1608 and VC2-319 thru -1914 can be provided with an external platform for
easy access to the drift eliminators and spray system of the unit. Safety gates are available for handrail
openings. All components are designed to meet OSHA requirements.
Vibration Cutout Switch
A factory mounted vibration cutout switch is available to effectively protect against equipment failure
due to excessive vibration of the mechanical equipment system. BAC can provide either a mechanical
or solid-state electronic vibration cutout switch in a NEMA 4 enclosure to ensure reliable protection.
Additional contacts can be provided to activate an alarm.
Electric Water Level Control Package
The electric water level control replaces the
standard mechanical make-up valve when a more
precise water level control is required. This
package consists of a conductance-actuated level
control mounted in the basin and a solenoid
activated valve in the make-up water line. The
valve is slow closing to minimize water hammer.
Extended Lubrication Lines
Extended lubrication lines with grease fittings located outside the fan section are available for
lubrication of the fan shaft bearings (this option is standard on VC2 models).
Electric Water Level Control Package
S
e
r
i
e
s
V
F18
Baltimore Aircoil Company
Accessories
Basin Heaters
Units exposed to below freezing ambient temperatures require protection to prevent freezing of the
water in the cold water basin when the unit is idle. Factory installed heaters, which maintain +40F
(4.4C) water temperature, are a simple and inexpensive way of providing such protection.
Heater Sizing Data
No. of HEATERS kW per HEATER No. of HEATERS kW per HEATER
VC1-10 thru 25 1 2 1 2
VC1-30 thru 65 1 2 1 2
VC1-72 thru 90 1 2 1 3
VC1-100 thru 135 1 3 1 5
VC1-150 thru 205 1 3 1 5
VC1-N208 thru N230 1 5 1 7. 5
VC1-N243 thru N315 1 5 1 7. 5
VC1-C216 thru C320 1 5 1 7. 5
VC1-N338 thru N470 1 7 1 10
VC1-C334 thru C469 1 5 1 7. 5
VC1-386 thru 516 1 8 1 10
VC1-540 thru 804 1 12 1 16
VC1-772 thru 1032 2 8 2 10
VC1-1158 thru 1608 2 12 2 16
VC2-N138 thru N191 1 5 1 9
VC2-N206 thru N235 1 7 1 10
VC2-N261 thru N301 1 8 1 10
VC2-N356 thru N446 1 12 1 16
VC2-342 thru 626 1 10 1 16
VC2-526 thru 957 1 16 1 20
VC2-N870 thru N1204 2 10 2 16
VC2-684 thru 1252 2 10 2 16
VC2-1052 thru 1914 2 16 2 20
VCL-016 thru 035 1 2 1 2
VCL-038 thru 079 1 3 1 4
VCL-087 thru 120 1 4 1 5
VCL-134 thru 155 1 5 1 7
VCL-167 thru 234 1 7 1 9
VCL-257 thru 299 1 9 1 12
MODEL NUMBERS
0F (-17.8C) AMBIENT HEATERS -20F (-28.9C) AMBIENT HEATERS
E
v
a
p
o
r
a
t
i
v
e
C
o
n
d
e
n
s
e
r
s
F19
...because temperature matters
Bottom Screens
Wire mesh screens are available factory-installed over the bottom
openings to prevent unauthorized access.
Basin Sweeper Piping
Basin sweeper piping is an effective method of eliminating sediment that may collect in the cold water
basin of the tower. A piping system is provided for connection to side stream filtration equipment
(by others) with a supply pressure of 10-20 psig.
Capacity Control Dampers (VC1 and VCL Models Only)
Modulating capacity control dampers are available to
provide better leaving water temperature control
than can be obtained from fan cycling alone. A
standard electrical control package for dampers is
available.
Solid Bottom Panels
Factory-installed bottom panels are required when
intake air is ducted to the unit.
Copper Sweat Fittings
Optional copper sweat fittings are available to
simplify field piping.
Subcooling Coils
Subcooling coils are available for those halocarbon refrigerant installations where subcooled refrigerant
is specified, or where the pressure drop or a vertical rise in the liquid line is great enough to cause
excessive flashing. Standard subcooling coil sections provide approximately 10F of subcooling at
standard conditions. Subcooling sections are approximately 7 high and are mounted between the coil
and pan/fan sections. Coils are hot-dip galvanized after fabrication and pneumatically tested at 375 psig.
Copper Sweat Fittings
Solid BottomPanels
For information on other
options and accessories,
please contact your
local BAC Representative.
S
e
r
i
e
s
V
F20
Baltimore Aircoil Company
Do not use for construction. Refer to factory certified dimensions. This brochure includes data current
at time of publication, which should be reconfirmed at the time of purchase. Up-to-date engineering data,
free product selection software, and more can be found at www.BaltimoreAircoil.com.
VC1 Engineering Data
Notes:
1. Model number denotes nominal tons using R-22 at a 105F
condensing temperature, a 40F suction temperature, and
a 78F wet-bulb temperature.
2. R-717 tons are at a 96.3F condensing temperature, a 20F
suction temperature, and a 78F wet-bulb temperature.
3. Fan horsepower is at 0 external static pressure.
4. Operating weight shown is based on total unit weight, weight of
refrigerant operating charge, and cold water basin filled to the
overflow level.
5. Unless otherwise noted by asterisk, the coil section is the
heaviest section.
6. Standard refrigerant connection sizes are 3-inch BFW inlet and
outlet for VC1-10 through -25, and 4 BFW inlet and outlet for
all other models.
7. Refrigerant charge listed is R-717 operating charge. To
determine operating charge for R-22, multiply charge by
1.93. For R-134a, multiply by 1.98.
See page J16
for information on sizing
a remote sump tank.
FAN
3
PUMP OPERATING
4
SHIPPING
HEAVIEST
SECTION
5
H F
VC1-10 7 1/2 1/3 2,900 1,400 1,270 *1,270 79 1/4" 14 1/4" 19 2
VC1-15 11 1 1/3 3,800 1,600 1,460 *1,460 87 3/4" 22 3/4" 25 2.7
VC1-20 14 1 1/2 1/3 4,400 1,770 1,620 1,000 96 1/4" 31 1/2" 32 3.5
VC1-25 18 3 1/3 5,300 1,820 1,670 1,050 96 1/4" 31 1/4" 34 3.5
VC1-30 21 3 1/2 8,200 2,300 2,010 *2,010 79 1/4" 13 1/4" 35 3.5
VC1-38 27 3 1/2 8,900 2,560 2,240 *2,240 87 3/4" 21 3/4" 45 5.0
VC1-46 33 3 1/2 8,500 2,880 2,540 1,650 96 1/4" 30 1/4" 61 6.5
VC1-52 37 5 1/2 10,200 2,930 2,590 1,700 96 1/4" 30 1/4" 65 6.5
VC1-58 41 5 1/2 9,800 3,230 2,860 1,940 104 3/4" 38 3/4" 76 8.0
VC1-65 46 7 1/2 1/2 11,600 3,300 2,930 2,010 104 3/4" 38 3/4" 80 8.0
VC1-72 51 5 3/4 12,300 4,210 3,510 2,400 99 1/4" 33 1/4" 90 9.6
VC1-80 57 7 1/2 3/4 14,500 4,280 3,580 2,470 99 1/4" 33 1/4" 100 9.6
VC1-90 64 7 1/2 3/4 14,000 4,750 4,000 2,850 108 1/2" 42 1/2" 110 12
VC1-100 71 7 1/2 1 19,600 5,420 4,450 3,060 99 1/4" 33 1/4" 120 13
VC1-110 78 10 1 22,000 5,500 4,530 3,140 99. 1/4" 33 1/4" 130 13
VC1-125 89 10 1 21,000 6,080 5,060 3,640 108 1/2" 42 1/2" 145 16
VC1-135 96 15 1 23,000 6,160 5,180 3,640 108 1/2" 42 1/2" 145 16
VC1-150 106 10 1 1/2 28,200 8,730 7,480 4,920 119 5/8" 33 1/4" 170 18
VC1-165 117 10 1 1/2 27,200 9,680 8,060 5,830 128 7/8" 42 1/2" 210 23
VC1-185 131 15 1 1/2 33,300 9,770 8,170 5,930 128 7/8" 42 1/2" 210 23
VC1-205 145 20 1 1/2 35,800 10,420 8,820 6,580 138 1/8" 51 3/4" 245 27
R-717
OPERATING
CHARGE
7
(LBS)
INTERNAL
COIL
VOLUME
(FT
3
)
MODEL
NUMBER
1
R-717
TONS
2
WEIGHT (LBS)
AIRFLOW
(CFM)
DIMENSIONS MOTOR HP
E
v
a
p
o
r
a
t
i
v
e
C
o
n
d
e
n
s
e
r
s
F21
...because temperature matters
2
2
Notes:
1. Model number denotes nominal tons using R-22 at a 105F
condensing temperature, a 40F suction temperature, and a
78F wet-bulb temperature.
2. R-717 tons are at a 96.3F condensing temperature, a 20F
suction temperature, and a 78F wet-bulb temperature.
3. Fan horsepower is at 0 external static pressure.
4. Operating weight shown is based on total unit weight, weight
of refrigerant operating charge, and cold water basin filled to
the overflow level.
5. The coil section is the heaviest section.
6. Standard refrigerant connection size is 4 BFW
(inlet and outlet).
7. Refrigerant charge listed is R-717 operating charge. To
determine operating charge for R-22, multiply charge by
1.93. For R-134a, multiply by 1.98.
See page F58
for Engineering
Considerations.
FAN
3
PUMP OPERATING
4
SHIPPING
HEAVIEST
SECTION
5
H F
VC1-N208 148 15 2 39,650 13,710 10,170 6,580 135 7/8" 33 1/4" 230 25
VC1-N230 163 15 2 38,550 15,000 11,410 8,220 145 1/4" 42 1/2" 245 31
VC1-N243 172 20 3 46,150 15,140 10,720 7,050 153 1/4" 33 1/4" 290 32
VC1-N257 182 25 3 49,700 15,190 10,770 7,050 153 1/4" 33 1/4" 290 32
VC1-N275 195 20 3 44,800 16,700 12,130 8,460 162 3/8" 42 1/2" 360 40
VC1-N301 213 25 3 47,150 18,210 13,580 9,860 171 5/8" 51 3/4" 430 47
VC1-N315 223 30 3 50,100 18,230 13,600 9,860 171 5/8" 51 3/4" 430 47
VC1-N338 240 20 5 60,450 22,360 15,630 10,390 153 1/4" 33 1/4" 435 48
VC1-N357 253 25 5 65,100 22,410 15,680 10,390 153 1/4" 33 1/4" 435 48
VC1-N373 265 30 5 69,200 22,430 15,700 10,390 153 1/4" 33. 1/4" 435 48
VC1-N417 296 30 5 67,200 24,820 17,880 12,570 162 3/8" 42 1/2" 540 59
VC1-N470 333 40 5 72,250 27,410 20,250 14,750 171 5/8" 51 3/4" 645 71
DIMENSIONS MOTOR HP R-717
OPERATING
CHARGE
(LBS)
INTERNAL
COIL
VOLUME
(FT
3
)
MODEL
NUMBER
1
R-717
TONS
2
WEIGHT (LBS)
AIRFLOW
(CFM)
S
e
r
i
e
s
V
F22
Baltimore Aircoil Company
Do not use for construction. Refer to factory certified dimensions. This brochure includes data current
at time of publication, which should be reconfirmed at the time of purchase. Up-to-date engineering data,
free product selection software, and more can be found at www.BaltimoreAircoil.com.
VC1 Engineering Data
Notes:
1. Model number denotes nominal tons using R-22 at a 105F
condensing temperature, a 40F suction temperature, and a
78F wet-bulb temperature.
2. R-717 tons are at a 96.3F condensing temperature, a 20F
suction temperature, and a 78F wet-bulb temperature.
3. Fan horsepower is at 0 external static pressure.
4. Operating weight shown is based on total unit weight, weight of
refrigerant operating charge, and cold water basin filled to the
overflow level.
5. Unless otherwise noted by asterisk, the coil section is the
heaviest section.
6. Standard refrigerant connection size is 4 BFW (inlet and outlet).
7. Refrigerant charge listed is R-717 operating charge. To
determine operating charge for R-22, multiply charge by
1.93. For R-134a, multiply by 1.98.
FAN
3
PUMP OPERATING
4
SHIPPING
HEAVIEST
SECTION
5
H F
VC1-386 274 30 5 74,250 23,860 15,810 10,300 155 1/" 33 1/4" 445 49
VC1-436 309 30 5 72,050 26,140 17,880 12,370 164 3/4" 42 1/2" 550 60
VC1-467 331 40 5 79,300 26,330 18,070 12,370 164 3/4" 42 1/2" 550 60
VC1-454 322 30 5 70,400 28,430 19,950 14,440 174" 51 3/4" 655 72
VC1-487 345 40 5 77,500 28,620 20,140 14,440 174" 51 3/4" 655 72
VC1-516 366 50 5 83,450 28,660 20,180 14,440 174" 51 3/4" 655 72
VC1-540 383 (2) 15 5 97,250 35,090 22,850 15,170 155 1/2" 33 1/4" 665 72
VC1-579 411 (2) 20 5 107,050 35,110 22,870 15,170 155 1/2" 33 1/4" 665 72
VC1-612 434 (2) 25 5 115,300 35,210 22,970 15,170 155 1/2" 33 1/4" 665 72
VC1-646 458 (2) 20 5 103,900 38,560 25,990 18,290 164 3/4" 42 1/2" 825 90
VC1-683 484 (2) 25 5 111,950 38,660 26,090 18,290 164 3/4" 42 1/2" 825 90
VC1-715 507 (2) 30 5 118,950 38,700 26,130 18,290 164 3/4" 42 1/2" 825 90
VC1-748 530 (2) 30 5 116,200 42,140 29,240 21,400 174" 51 3/4" 990 108
VC1-804 570 (2) 40 5 127,900 42,520 29,620 21,400 174" 51 3/4" 990 108
VC1-772 548 (2) 30 (2) 5 148,500 47,930 31,560 *10,960 155 1/2" 33 1/4" 890 98
VC1-872 618 (2) 30 (2) 5 144,100 52,490 35,700 12,370 164 3/4" 42 1/2" 1,100 121
VC1-934 662 (2) 40 (2) 5 158,600 52,870 36,080 12,370 164 3/4" 42 1/2" 1,100 121
VC1-908 644 (2) 30 (2) 5 140,800 57,070 39,840 14,440 174" 51 3/4" 1,310 144
VC1-974 691 (2) 40 (2) 5 155,000 57,450 40,220 14,440 174" 51 3/4" 1,310 144
VC1-1032 732 (2) 50 (2) 5 166,900 57,530 40,300 14,440 174" 51 3/4" 1,310 144
VC1-1158 821 (4) 20 (2) 5 214,100 70,450 45,710 *15,340 155 1/2" 33 1/4" 1,330 146
VC1-1224 868 (4) 25 (2) 5 230,600 70,650 45,910 *15,540 155 1/2" 33 1/4" 1,330 146
VC1-1366 969 (4) 25 (2) 5 223,900 77,520 52,120 18,290 164 3/4" 42 1/2" 1,650 181
VC1-1430 1014 (4) 30 (2) 5 237,900 77,600 52,200 18,290 164 3/4" 42 1/2" 1,650 181
VC1-1496 1061 (4) 30 (2) 5 232,400 84,480 58,420 21,400 174" 51 3/4" 1,980 216
VC1-1608 1140 (4) 40 (2) 5 255,800 85,240 59,180 21,400 174" 51 3/4" 1,980 216
DIMENSIONS MOTOR HP R-717
OPERATING
CHARGE
(LBS)
INTERNAL
COIL
VOLUME
(FT
3
)
MODEL
NUMBER
1
R-717
TONS
2
WEIGHT (LBS)
AIRFLOW
(CFM)
E
v
a
p
o
r
a
t
i
v
e
C
o
n
d
e
n
s
e
r
s
F23
...because temperature matters
Designed to minimize ocean freight costs, VC1-C models fit in standard dry van containers.
2 Side Drain
Notes:
1. Model number denotes nominal tons using R-22 at a 105F
condensing temperature, a 40F suction temperature, and a 78F
wet-bulb temperature.
2. R-717 tons are at a 96.3F condensing temperature, a 20F
suction temperature, and a 78F wet-bulb temperature.
3. Fan horsepower is at 0 external static pressure.
4. Operating weight shown is based on total unit weight, weight of
refrigerant operating charge, and cold water basin filled to the
overflow level.
5. The coil section is the heaviest section.
6. Standard refrigerant connection size is 4 BFW (inlet and outlet).
7. Refrigerant charge listed is R-717 operating charge. To determine
operating charge for R-22, multiply charge by 1.93. For R-134a,
multiply by 1.98.
FAN
3
PUMP OPERATING
4
SHIPPING
HEAVIEST
SECTION
5
H F
VC1-C216 153 15 3 40,060 14,880 10,270 6,680 142 1/4" 33 1/4" 265 29
VC1-C231 164 20 3 44,090 14,890 10,280 6,680 142 1/4" 33 1/4" 265 29
VC1-C242 172 15 3 38,870 16,300 11,560 7,970 151 1/2" 42 1/2" 330 36
VC1-C260 184 20 3 42,790 16,310 11,570 7,970 151 1/2" 42 1/2" 330 36
VC1-C274 194 25 3 46,090 16,360 11,620 7,970 151 1/2" 42 1/2" 330 36
VC1-C286 203 30 3 48,980 16,380 11,640 7,970 151 1/2" 42 1/2" 330 36
VC1-C299 212 30 3 47,830 17,720 12,920 9,250 160 3/4" 51 3/4" 390 43
VC1-C320 227 40 3 52,650 17,910 13,110 9,250 160 3/4" 51 3/4" 390 43
VC1-C339 241 25 5 62,180 22,040 15,050 9,830 142 1/4" 33 1/4" 395 43
VC1-C354 251 30 5 66,080 22,060 15,070 9,830 142 1/4" 33 1/4" 395 43
VC1-C380 269 40 5 72,730 22,250 15,260 9,830 142 1/4" 33 1/4" 395 43
VC1-C396 281 30 5 64,180 24,240 17,050 11,810 151 1/2" 42 1/2" 490 54
VC1-C424 301 40 5 70,640 24,430 17,240 11,810 151 1/2" 42 1/2" 490 54
VC1-C445 316 40 5 69,020 26,630 19,240 13,810 160 3/4" 51 3/4" 590 64
VC1-C469 333 50 5 74,340 26,670 19,280 13,810 160 3/4" 51 3/4" 590 64
DIMENSIONS MOTOR HP R-717
OPERATING
CHARGE
(LBS)
INTERNAL
COIL
VOLUME
(FT
3
)
MODEL
NUMBER
1
R-717
TONS
2
WEIGHT (LBS)
AIRFLOW
(CFM)
See page F58
for Engineering
Considerations.
S
e
r
i
e
s
V
F24
Baltimore Aircoil Company
Do not use for construction. Refer to factory certified dimensions. This brochure includes data current
at time of publication, which should be reconfirmed at the time of purchase. Up-to-date engineering data,
free product selection software, and more can be found at www.BaltimoreAircoil.com.
VC2 Engineering Data
Notes:
1. Model number denotes nominal tons using R-22 at a 105F
condensing temperature, a 40F suction temperature, and a 78F
wet-bulb temperature.
2. R-717 tons are at a 96.3F condensing temperature, a 20F
suction temperature, and a 78F wet-bulb temperature.
3. Operating weight shown is based on total unit weight, weight of
refrigerant operating charge, and cold water basin filled to the
overflow level.
4. The coil section is the heaviest section.
5. Standard refrigerant connection size is 4 BFW (inlet and outlet).
6. Refrigerant charge listed is R-717 operating charge. To determine
operating charge for R-22, multiply charge by 1.93. For R-134a,
multiply by 1.98.
FAN
3
PUMP OPERATING
4
SHIPPING
HEAVIEST
SECTION
5
H F
VC2-N138 98 5 1 1/2 25,900 8,920 7,130 4,920 131 1/8" 33 1/4" 170 18
VC2-N150 106 7 1/2 1 1/2 28,300 9,010 7,220 5,830 131 1/8" 33 1/4" 190 18
VC2-N170 121 7 1/2 1 1/2 28,000 9,930 8,120 5,930 140 3/8" 42 1/2" 210 23
VC2-N191 135 10 1 1/2 30,100 10,580 8,770 6,580 149 5/8" 51 3/4" 245 27
VC2-N206 146 10 2 39,650 14,950 9,960 6,580 143 1/4" 33 1/4" 230 25
VC2-N215 152 7 1/2 2 35,050 16,180 11,190 7,810 152 3/4" 42 1/2" 290 31
VC2-N235 167 10 2 38,750 16,200 11,210 7,810 152 3/4" 42 1/2" 290 31
VC2-N261 185 10 3 43,400 15,380 11,860 8,460 152 3/4" 42 1/2" 360 40
VC2-N301 213 15 3 48,550 16,970 13,310 9,860 162" 51 3/4" 430 47
VC2-N356 252 15 5 67,650 20,260 15,170 10,390 155 1/2" 33 1/4" 435 48
VC2-N396 281 15 5 65,700 22,650 17,350 12,570 164 3/4" 42 1/2" 540 59
VC2-N416 295 15 5 64,200 25,050 19,530 14,750 174" 51 3/4" 645 71
VC2-N446 316 20 5 70,650 25,060 19,540 14,750 174" 51 3/4" 645 71
DIMENSIONS MOTOR HP
R-717
OPERATING
CHARGE (LBS)
INTERNAL
COIL
VOLUME
(FT
3
)
MODEL
NUMBER
1
R-717
TONS
2
WEIGHT (LBS)
AIRFLOW
(CFM)
E
v
a
p
o
r
a
t
i
v
e
C
o
n
d
e
n
s
e
r
s
F25
...because temperature matters
See page F58
for Engineering
Considerations.
-626 -957
Notes:
1. Model number denotes nominal tons using R-22 at a 105F
condensing temperature, a 40F suction temperature, and a 78F
wet-bulb temperature.
2. R-717 tons are at a 96.3F condensing temperature, a 20F
suction temperature, and a 78F wet-bulb temperature.
3. Operating weight shown is based on total unit weight, weight of
refrigerant operating charge, and cold water basin filled to the
overflow level.
4. Unless otherwise noted, the coil section is the heaviest section.
5. Standard refrigerant connection size is 4 BFW (inlet and outlet).
6. Refrigerant charge listed is R-717 operating charge. To determine
operating charge for R-22, multiply charge by 1.93. For R-134a,
multiply by 1.98.
FAN
3
PUMP OPERATING
4
SHIPPING
HEAVIEST
SECTION
5
H F
VC2-319 226 7.5 5 54,300 24,590 15,240 10,300 163 1/2" 33 1/4" 445 49
VC2-342 243 10 5 59,750 24,640 15,290 10,300 163 1/2" 33 1/4" 445 49
VC2-377 267 15 5 68,400 24,690 15,340 10,300 163 1/2" 33 1/4" 445 49
VC2-420 298 15 5 68,400 26,970 17,410 12,370 172 3/4" 42 1/2" 550 60
VC2-451 320 20 5 73,100 26,980 17,420 12,370 172 3/4" 42 1/2" 550 60
VC2-471 334 20 5 71,400 29,010 19,450 14,400 182" 51 3/4" 675 72
VC2-491 348 25 5 76,950 29,030 19,470 14,400 182" 51 3/4" 675 72
VC2-513 364 30 5 81,750 29,050 19,490 14,400 182" 51 3/4" 675 72
VC2-541 384 30 5 81,500 30,510 20,870 15,780 182" 51 3/4" 750 80
VC2-580 411 40 5 89,700 30,700 21,060 15,780 182" 51 3/4" 750 80
VC2-585 415 30 5 77,040 33,445 22,740 18,205 194 1/4" 61" 875 93
VC2-626 444 40 5 85,200 33,500 22,795 18,205 194 1/4" 61" 875 93
VC2-526 373 10 & 5 5 89,700 36,430 22,220 15,170 163 1/2" 33 1/4" 665 73
VC2-581 412 15 & 7.5 5 102,650 36,540 22,330 15,170 163 1/2" 33 1/4" 665 73
VC2-623 442 20 & 10 5 113,000 36,560 22,350 15,170 163 1/2" 33 1/4" 665 73
VC2-642 455 15 & 7.5 5 99,600 39,990 25,450 18,290 172 3/4" 42 1/2" 825 90
VC2-688 488 20 & 10 5 109,650 40,010 25,470 18,290 172 3/4" 42 1/2" 825 90
VC2-711 504 20 & 10 5 107,150 43,450 28,580 21,400 182" 51 3/4" 990 108
VC2-752 533 25 & 15 5 115,400 43,550 28,680 21,400 182" 51 3/4" 990 108
VC2-785 557 30 & 15 5 122,650 43,570 28,700 21,400 182" 51 3/4" 990 108
VC2-827 587 30 & 15 5 122,200 45,760 30,780 23,480 182" 51 3/4" 1,100 120
VC2-887 629 40 & 20 5 134,500 45,960 30,980 23,480 182" 51 3/4" 1,100 120
VC2-895 635 30 & 15 7.5 115,000 49,895 33,655 27,160 194 1/4" 61" 1,290 140
VC2-957 679 40 & 20 7.5 126,080 50,005 33,765 27,160 194 1/4" 61" 1,290 140
INTERNAL
COIL
VOLUME
(FT
3
)
MODEL
NUMBER
1
R-717
TONS
2
MOTOR HP WEIGHT (LBS)
AIRFLOW
(CFM)
R-717
OPERATING
CHARGE (LBS)
DIMENSIONS
S
e
r
i
e
s
V
F26
Baltimore Aircoil Company
Do not use for construction. Refer to factory certified dimensions. This brochure includes data current
at time of publication, which should be reconfirmed at the time of purchase. Up-to-date engineering data,
free product selection software, and more can be found at www.BaltimoreAircoil.com.
VC2 Engineering Data
11'-10"
2" DRAIN
ACCESS
3" OVERFLOW 2" MAKE-UP
3'-0 1/4" 5'-8 1/4"
11'-8 3/4"
BFW REFRIG OUT
BFW REFRIG IN
7
3
/
4
"
H
9
'-
0
"
F
3'-0 1/4"
VC2-N1204
VC2-N870
23'-8 1/2" 2'-0"
M M
2'-3"
Notes:
1. Model number denotes nominal tons using R-22 at a 105F
condensing temperature, a 40F suction temperature, and a 78F
wet-bulb temperature.
2. R-717 tons are at a 96.3F condensing temperature, a 20F
suction temperature, and a 78F wet-bulb temperature.
3. Operating weight shown is based on total unit weight, weight of
refrigerant operating charge, and cold water basin filled to the
overflow level.
4. The coil section is the heaviest section.
5. Standard refrigerant connection size is 4 BFW (inlet and outlet).
6. Refrigerant charge listed is R-717 operating charge. To determine
operating charge for R-22, multiply charge by 1.93. For R-134a,
multiply by 1.98.
Designed to minimize refrigerant piping, these models have coil connections on just one end.
FAN
3
PUMP OPERATING
4
SHIPPING
HEAVIEST
SECTION
5
H F
VC2-N870 617 (2) 15 (2) 5 132,800 53,195 32,325 23,855 175 3/4" 42 1/2" 1,100 112
VC2-N932 661 (2) 20 (2) 5 146,200 53,285 32,415 23,855 175 3/4" 42 1/2" 1,100 112
VC2-N1000 709 (2) 25 (2) 5 163,100 53,595 32,725 23,855 175 3/4" 42 1/2" 1,100 112
VC2-N1071 760 (2) 30 (2) 5 163,500 58,445 38,595 27,795 185" 51 3/4" 1,350 136
VC2-N1124 797 (2) 30 (2) 5 160,230 61,480 39,610 30,510 185" 51 3/4" 1,510 150
VC2-N1204 854 (2) 40 (2) 5 176,340 61,610 39,740 30,510 185" 51 3/4" 1,510 150
INTERNAL
COIL
VOLUME
(FT
3
)
AIRFLOW
(CFM)
MODEL
NUMBER
1
R-717
TONS
2
R-717
OPERATING
CHARGE
(LBS)
MOTOR HP WEIGHT (LBS) DIMENSIONS
E
v
a
p
o
r
a
t
i
v
e
C
o
n
d
e
n
s
e
r
s
F27
...because temperature matters
See page F58
for Engineering
Considerations.
11'-10"
2" DRAIN
ACCESS
3" OVERFLOW
2" MAKE-UP
3'-0 1/4" 5'-8 1/4"
11'-8 3/4"
BFW REFRIG OUT
BFW REFRIG IN
4
3
/
4
"
H
9
'-
0
"
F
3'-0 1/4"
VC2-1252
VC2-684
23'-8 1/2" 2'-0"
M M
2'-3"
VC2-1914
VC2-1052
35'-9 1/4" 2'-0"
M M M M
2'-3"
Notes:
1. Model number denotes nominal tons using R-22 at a 105F
condensing temperature, a 40F suction temperature, and a 78F
wet-bulb temperature.
2. R-717 tons are at a 96.3F condensing temperature, a 20F
suction temperature, and a 78F wet-bulb temperature.
3. Operating weight shown is based on total unit weight, weight of
refrigerant operating charge, and cold water basin filled to the
overflow level.
4. The coil section is the heaviest section.
5. Standard refrigerant connection size is 4 BFW (inlet and outlet).
6. Refrigerant charge listed is R-717 operating charge. To determine
operating charge for R-22, multiply charge by 1.93. For R-134a,
multiply by 1.98.
FAN
3
PUMP OPERATING
4
SHIPPING
HEAVIEST
SECTION
5
H F
VC2-684 485 (2) 10 (2) 5 119,500 49,580 30,570 10,300 163 1/2" 33 1/4" 890 98
VC2-754 535 (2) 15 (2) 5 136,800 49,680 30,670 10,300 163 1/2" 33 1/4" 890 98
VC2-840 596 (2) 15 (2) 5 132,800 54,240 34,810 12,370 172 3/4" 42 1/2" 1,100 121
VC2-902 640 (2) 20 (2) 5 146,200 54,260 34,830 12,370 172 3/4" 42 1/2" 1,100 121
VC2-942 668 (2) 20 (2) 5 142,800 58,020 38,900 14,400 182" 51 3/4" 1,350 144
VC2-982 696 (2) 25 (2) 5 153,900 58,060 38,940 14,400 182" 51 3/4" 1,350 144
VC2-1026 728 (2) 30 (2) 5 163,500 58,100 38,980 14,400 182" 51 3/4" 1,350 144
VC2-1082 767 (2) 30 (2) 5 160,230 61,020 41,740 15,780 182" 51 3/4" 1,510 160
VC2-1160 823 (2) 40 (2) 5 176,340 61,400 42,120 15,780 182" 51 3/4" 1,510 160
VC2-1170 830 (2) 30 (2) 5 154,080 67,645 45,905 15,780 194 1/4" 61" 1,715 186
VC2-1252 888 (2) 40 (2) 5 170,400 67,755 46,015 15,780 194 1/4" 61" 1,715 186
VC2-1052 746 (2) 10 & (2) 5 (2) 5 179,400 73,170 44,420 15,170 163 1/2" 33 1/4" 1,330 146
VC2-1162 824 (2) 15 & (2) 7 1/2 (2) 5 205,300 73,390 44,640 15,170 163 1/2" 33 1/4" 1,330 146
VC2-1246 884 (2) 20 & (2) 10 (2) 5 226,000 73,430 44,680 15,170 163 1/2" 33 1/4" 1,330 146
VC2-1284 911 (2) 15 & (2) 7 1/2 (2) 5 199,200 80,290 50,880 18,290 172 3/4" 42 1/2" 1,650 181
VC2-1376 976 (2) 20 & (2) 10 (2) 5 219,300 80,330 50,920 18,290 172 3/4" 42 1/2" 1,650 181
VC2-1422 1,009 (2) 20 & (2) 10 (2) 5 214,300 87,210 57,140 21,400 182" 51 3/4" 1,980 216
VC2-1504 1,067 (2) 25 & (2) 15 (2) 5 230,800 87,410 57,340 21,400 182" 51 3/4" 1,980 216
VC2-1570 1,113 (2) 30 & (2) 15 (2) 5 245,300 87,450 57,380 21,400 182" 51 3/4" 1,980 216
VC2-1654 1,173 (2) 30 & (2) 15 (2) 5 240,400 91,840 61,540 23,480 182" 51 3/4" 2,210 241
VC2-1774 1,258 (2) 40 & (2) 20 (2) 5 264,600 92,240 61,940 23,480 182" 51 3/4" 2,210 241
VC2-1790 1,269 (2) 30 & (2) 15 (2) 7.5 230,000 99,790 67,000 27,160 194 1/4" 61" 2,580 280
VC2-1914 1,357 (2) 40 & (2) 20 (2) 7.5 252,160 100,010 67,220 27,160 194 1/4" 61" 2,580 280
INTERNAL
COIL
VOLUME
(FT
3
)
AIRFLOW
(CFM)
MODEL
NUMBER
1
R-717
TONS
2
R-717
OPERATING
CHARGE
(LBS)
MOTOR HP WEIGHT (LBS) DIMENSIONS
S
e
r
i
e
s
V
F28
Baltimore Aircoil Company
Do not use for construction. Refer to factory certified dimensions. This brochure includes data current
at time of publication, which should be reconfirmed at the time of purchase. Up-to-date engineering data,
free product selection software, and more can be found at www.BaltimoreAircoil.com.
VCL Engineering Data
E
v
a
p
o
r
a
t
i
v
e
C
o
n
d
e
n
s
e
r
s
F29
...because temperature matters
Notes:
1. Model number denotes nominal tons using R-22 at a 105F
condensing temperature, a 40F suction temperature, and a 78F
wet-bulb temperature.
2. R-717 tons are at a 96.3F condensing temperature, a 20F
suction temperature, and a 78F wet-bulb temperature.
3. Fan horsepower is at 0 external static pressure.
4. Operating weight shown is based on total unit weight, weight of
refrigerant operating charge, and cold water basin filled to the
overflow level.
5. All models ship in one piece.
6. Standard refrigerant connection sizes are 3-inch BFW inlet and
outlet for VCL-016 through -035, and 4 BFW inlet and outlet for
all other models.
7. Refrigerant charge listed is R-717 operating charge. To determine
operating charge for R-22, multiply charge by 1.93. For R-134a,
multiply by 1.98.
FAN
3
PUMP OPERATING
4
SHIPPING H F
VCL-016 11 1 1/3 7,040 2,210 1,660 62 1/4" 14 1/4" 23 2.5
VCL-019 13 2 1/3 8,310 2,240 1,690 65" 14 1/4" 23 2.5
VCL-024 17 2 1/3 8,010 2,470 1,900 75 3/4" 22 3/4" 34 3.3
VCL-029 21 2 1/3 7,660 2,700 2,120 82" 31 1/4" 44 4.3
VCL-035 25 3 1/3 8,140 2,960 2,360 90 1/2" 39 3/4" 52 5.2
VCL-038 27 3 1/2 12,800 3,530 2,400 62 1/4" 13 1/4" 44 4.4
VCL-044 31 2 1/2 12,620 3,940 2,760 73" 21 3/4" 62 6.3
VCL-048 34 3 1/2 14,250 3,970 2,790 73" 42 1/2" 62 6.3
VCL-054 38 5 1/2 16,150 3,990 2,810 75 3/4" 21 3/4" 62 6.3
VCL-058 41 3 1/2 13,570 4,370 3,180 79 1/4" 30 1/4" 83 8.2
VCL-065 46 5 1/2 15,600 4,390 3,200 79 1/4" 30 1/4" 83 8.2
VCL-073 52 5 1/2 15,150 4,820 3,610 87 3/4" 38 3/4" 101 10
VCL-079 56 7 1/2 1/2 16,690 4,890 3,680 90 1/2" 38 3/4" 101 10
VCL-087 62 5 1 19,280 6,130 4,380 82 1/4" 33 1/4" 122 12
VCL-096 68 7 1/2 1 21,570 6,160 4,410 82 1/4" 33 1/4" 122 12
VCL-102 72 10 1 23,730 6,190 4,440 82 1/4" 33 1/4" 122 12
VCL-108 77 7 1/2 1 21,200 6,770 4,990 92 9/16" 42 1/2" 159 15
VCL-115 82 10 1 22,970 6,800 5,020 92 9/16" 42 1/2" 159 15
VCL-120 85 10 1 22,210 7,440 5,620 100 3/4" 51 3/4" 182 18
VCL-134 95 10 1 1/2 25,130 8,590 6,160 92 9/16" 42 1/2" 203 20
VCL-148 105 15 1 1/2 28,400 8,650 6,220 92 9/16" 42 1/2" 203 20
VCL-155 110 15 1 1/2 28,000 9,450 6,950 100 3/4" 51 3/4" 242 24
VCL-167 118 10 1 1/2 36,870 11,570 8,030 82 1/4" 33 1/4" 244 24
VCL-185 131 15 1 1/2 41,560 11,630 8,090 82 1/4" 33 1/4" 244 24
VCL-209 148 15 1 1/2 40,780 12,870 9,270 92 9/16" 42 1/2" 317 30
VCL-223 158 20 1 1/2 44,290 12,880 9,280 92 9/16" 42 1/2" 317 30
VCL-234 166 20 1 1/2 43,480 14,140 10,460 100 3/4" 51 3/4" 364 35
VCL-257 182 20 2 47,860 16,000 11,080 92 9/16" 42 1/2" 406 40
VCL-271 192 20 2 47,370 17,540 12,480 100 3/4" 51 3/4" 484 47
VCL-286 203 25 2 50,670 17,580 12,520 100 3/4" 51 3/4" 484 47
VCL-299 212 30 2 53,520 17,620 12,560 100 3/4" 51 3/4" 484 47
DIMENSIONS
R-717
OPERATING
CHARGE
7
(LBS)
INTERNAL
COIL VOLUME
(FT
3
)
MODEL
NUMBER
1
R-717
TONS
2
WEIGHT (LBS)
AIRFLOW
(CFM)
MOTOR HP
See page F58
for Engineering
Considerations.
S
e
r
i
e
s
V
F30
Baltimore Aircoil Company
Structural Support
The recommended support arrangement for the Series V Evaporative Condenser consists of parallel
I-beams running the full length of the unit, spaced as shown in the following drawings. Besides
providing adequate support, the steel also serves to raise the unit above any solid foundation to ensure
access to the bottom of the unit. To support a Series V Evaporative Condenser in an alternate steel
support arrangement, consult your BAC Representative.
Steel Supports
Steel Supports
VC1 Models
(Also representative of VC2 models)
VCL Models
E
v
a
p
o
r
a
t
i
v
e
C
o
n
d
e
n
s
e
r
s
F31
...because temperature matters
Notes:
1. Support beams and anchor bolts are to be selected and
installed by others.
2. All supporting steel must be level at the top.
3. Beams must be selected in accordance with accepted structural
practice. The maximum allowable deflection of the beams under
the unit shall be as specified in the table above.
4. All units can be furnished with an optional vibration isolation
package, if required, to be installed between the unit and
supporting steel. When determining the length of steel beams,
allow for the length of vibration isolation rails, as they may be
longer than the unit length shown above.
5. If point vibration isolation is used, the isolators must be located
under the supporting steel, not between the support steel and
the unit.
All VCL Models VC1-10 thru -516, -N208 thru -N315,
& -C216 thru -C320
VC2-319 thru -626 & -N138 thru -N301
VC1-540 thru -1032, -N338 thru -N470,
& -C339 thru -C469
VC2-526 thru -1252 & -N356 thru -N1204
VC1-1158 thru -1608 & VC2-1052 thru -1914
MODEL NUMBER A B
MAXIMUM
DELFECTION
3
VC1-10 thru 25 3 9-3/8 2 5-1/2 3/32
VC1-30 thru 65 3 9-3/8 5 5-1/2 3/16
VC1-72 thru 90 3 9-3/8 8 5-1/4 5/16
VC1-100 thru 135 3 9-3/8 11 5-1/2 3/8
VC1-150 thru 205 4 6-1/4 11 5-1/2 3/8
VC1-N208 thru N315 7 7-5/8 10 7-1/2 3/8
VC1-N338 thru N470 7 7-5/8 16 7-3/4 1/2
VC1-386 thru 516 11 7-1/4 10 7-1/2 3/8
VC1-540 thru 804 11 7-1/4 16 7-3/4 1/2
VC1-772 thru 1032 11 7-1/4 22 8-1/4 1/2
VC1-1158 thru 1608 11 7-1/4 34 8-3/4 1/2
VC1-C216 thru C320 7 1-5/8 10 7-1/2 3/8
VC1-C339 thru C469 7 1-5/8 16 7-3/4 1/2
VC2-N138 thru N191 4 9-1/2 11 5 3/8
VC2-N206 thru N235 6 4-1/4 10 7-1/2 3/8
VC2-N261 thru N301 7 8 10 7-1/2 3/8
VC2-N356 thru N446 7 8 16 7-3/4 1/2
VC2-319 thru 626 11 7-1/4 10 7-1/2 3/8
VC2-526 thru 957 11 7-1/4 16 7-3/4 1/2
VC2-N870 thru N1204 11 7-1/4 22 8-1/4 1/2
VC2-684 thru 1252 11 7-1/4 22 8-1/4 1/2
VC2-1052 thru 1914 11 7-1/4 34 8-3/4 1/2
VCL-016 thru -035 3 11 4 6 1/4
VCL-038 thru -079 3 11 7 11-1/2 3/8
VCL-087 thru -120 3 11 10 11-1/4 1/2
VCL-134 thru -155 3 11 13 11-1/2 1/2
VCL-167 thru -234 7 8-1/4 10 11-1/4 1/2
VCL-257 thru -299 7 8-1/4 13 11-1/2 1/2
S
e
r
i
e
s
V
F32
Baltimore Aircoil Company
Part 1: General
A. General: Furnish and install, _____ factory assembled
evaporative condenser(s) of counterflow blow-through design,
with single side entry, conforming in all aspects to the
specifications and schedule as shown on the plans.
B. Capacity: The evaporative condenser(s) shall be warranted
by the manufacturer to have condensing capacity of _____
BTUH heat rejection, operating with ____ refrigerant and ___F
condensing temperature and ___F entering wet-bulb
temperature.
C. Warranty: The manufacturers standard equipment warranty
shall be for a period of one year from the date of startup or
eighteen months from the date of shipment, whichever ends first.
The manufacturer shall, in addition, provide a 5-year mechanical
drive warranty covering the fans, fan shafts, bearings, sheaves,
supports, and fan motors.
D. Factory Testing: Equipment manufacturer shall be capable of
testing the operation of the condenser in the manufacturers own
test facility. Test facilities shall be capable of simulating design
conditions, including but not limited to design wet-bulb, airflow,
refrigerant mass flow rate, refrigerant condensing temperature,
and total heat rejection.
E. Quality Assurance: The manufacture shall have
Management System certified by an accredited registrar as
complying with the requirements of ISO-9001 to ensure
consistent quality of products and services. Manufacturers that
are not ISO-9001 certified shall provide an additional one-year
warranty to the customer at no additional cost.
Part 2: Products
2.01 Evaporative Condenser Materials and Components
A. General: All steel panels and structural elements shall be
constructed from heavy-gauge, G-235 (Z700 metric) hot-dip
galvanized steel, with cut edges given a protective coating of
zinc-rich compound.
2.02 Coil Casing Assembly
A. The evaporative condenser shall include a coil casing section
consisting of a refrigerant condensing coil, a spray water
distribution system, and drift eliminators as indicated by the
manufacturer.
1.The refrigerant condensing coil shall be fabricated of all
prime surface steel at the manufacturers own facility, and
hot-dip galvanized after fabrication.
a. The refrigerant condensing coil shall be tested at
375 psig (2687 kPa) air pressure under water.
b. The refrigerant condensing coil shall be designed for
low pressure drop with sloping tubes for free drainage
of liquid refrigerant.
c. The refrigerant condensing coil shall be ASME
B31.5 compliant and coils shipping into Canada shall
be supplied with a CRN.
2. Water shall be distributed evenly over the coil at a
minimum flow rate of 4.5 gpm/ft2 (3.1 lps/m2) to ensure
complete wetting of the coil at all times by large-diameter,
non-clog, 360plastic distribution nozzles spaced across
the coil face area in Schedule 40 PVC spray branches.
Nozzles shall utilize a two-stage diffusion pattern to
provide overlapping, umbrella spray patterns that create
multiple intersection points with adjacent nozzles.
a. Directional nozzles shall not be acceptable.
b. Spray branches and nozzles shall be held in place
by snap-in rubber grommets, allowing quick removal
of individual nozzles or complete branches for
cleaning or flushing.
c. Nozzles shall have a minimum of 0.25" (6.35 mm)
protrusion inside the spray branches to ensure
unimpeded water flow between regular cleanings of
the water distribution system.
3. Removable PVC drift eliminators shall be positioned to
prevent moisture from leaving the evaporative condenser
and incorporate a minimum of three (3) changes in air
direction.
2.03 Pan Assembly
A. The evaporative condenser shall include a pan assembly
consisting of cold water basin with pump assembly and fan
assemblies with single side air inlet and integral air plenum.
1. The cold water basin shall include: a drain/clean-out
connection; a steel strainer; a brass make-up valve; overflow
connection; and a water recirculation pump assembly.
a. Drain/cleanout connection shall be located in the
cold water basin to allow removal of recirculating
water.
b. Lift-out steel strainer shall be supplied with
perforated openings sized smaller than the water
distribution nozzle orifices and an integral anti-vortexing
hood to prevent air entrainment.
c. Brass make-up valve shall be supplied with a
large-diameter plastic float arranged for easy
adjustment.
d. Overflow connection shall be provided in the cold
water basin to protect against recirculating water
spillage.
e. Water recirculation pump shall be a close-coupled,
bronze-fitted centrifugal pump equipped with a
mechanical seal, mounted on the basin and piped from
the suction strainer to the water distribution system.
i. The pump shall be installed so that it may drain
freely when the basin is drained.
ii. The pump assembly shall include an integral
metering valve and bleed line to control the bleed
rate from the pump discharge to the overflow
connection.
iii. The pump motor shall be totally enclosed fan
cooled (TEFC) type suitable for _____ V, ____
phase______ Hz electrical service.
Engineering Specifications
See our website at www.BaltimoreAircoil.com for an electronic copy of product engineering specifications.
E
v
a
p
o
r
a
t
i
v
e
C
o
n
d
e
n
s
e
r
s
F33
...because temperature matters
f. On installations requiring a remote sump, the
evaporative condenser shall be modified to
accommodate the use of an independent sump and
pump for recirculating water (by others)
i. The recirculating water pump, steel strainer,
make-up valve, and integral bleed line assemblies
shall be omitted from the evaporative condenser
scope of supply.
ii. The evaporative condenser shall be supplied with
a cold water basin outlet sized and located as
indicated on the drawings for gravity drain to the
remote sump.
iii. The water distribution system shall have an
operating pressure of 2 psig (115 kPa) at the
evaporative condenser spray water inlet connection.
VC2 Models
2. Air shall enter the evaporative condenser through the axial fan
assemblies and integral air plenum.
a. Fans and motors shall be located in the dry entering
airstream to provide greater reliability and ease of
maintenance.
b. Fan motors and drives shall be located at the front base
of the unit to facilitate access without requiring access to
the inside of the unit.
c. Fan cylinders shall have curved inlets for efficient
air entry.
d. Each fan assembly shall contain two axial-flow fans
mounted in series on a common shaft with discharge
guide vanes between the fans for increased fan
efficiency.
e. Fans shall be heavy-duty, axial flow type with aluminum
alloy blades driven by a one-piece, multi-groove
neoprene/polyester belt designed for a minimum of 150%
of the motor nameplate horsepower.
i. Fan shafts shall be mounted in heavy-duty,
self-aligning, grease-packed relubricatable ball
bearings with eccentric locking collars, designed for a
minimum L10 life of 40,000 hours.
ii. Bearing lubrication lines shall be extended to the
exterior of the unit.
iii. Fan and motor sheaves shall be fabricated from
corrosion-resistant materials.
f. Fan motor(s) shall be totally enclosed fan cooled (TEFC)
type with a 1.15 service factor, suitable for _____ V, ____
phase, ______ Hz electrical service and shall be
mounted on an easily adjusted, heavy-duty motor base.
Special moisture protection shall be provided on the
windings, shafts and bearings.
g. Integral air plenum shall contain additional guide vanes
to ensure uniform airflow into the coil casing section.
VC1 Models
2. Air shall enter the evaporative condenser through the
centrifugal fan assemblies and integral air plenum.
a. Fans and motors shall be located in the dry entering
airstream to provide greater reliability and ease of
maintenance.
b. Fan housings shall have curved inlet rings for efficient air
entry and rectangular discharge cowls that extend into
the pan to increase fan efficiency and prevent water from
entering the fans.
c. Fan housings on units more than 8' wide shall be split to
facilitate the removal of the fan shaft.
d. Fan(s) shall be heavy-duty, centrifugal flow type mounted
on a steel shaft with heavy-duty, self-aligning,
relubricatable bearings with cast iron housings, designed
for a minimum L10 life of 40,000 hours.
e. Fan motor(s) shall be totally enclosed fan cooled (TEFC)
type with a 1.15 service factor, suitable for _____ V, ____
phase, ______ Hz electrical service and shall be
mounted on an easily adjusted, heavy-duty motor base.
Special moisture protection shall be furnished on the
windings, shafts, and bearings.
VCL Models
2. Air shall enter the evaporative condenser through the
centrifugal fan assemblies and integral air plenum.
a. Centrifugal fan assemblies shall be located adjacent to
the casing and the cold water basin to minimize overall
unit height.
b. Fan housings shall have curved inlet rings for efficient air
entry and rectangular discharge cowls which extend into
the pan to increase fan efficiency and prevent water from
entering the fans.
c. Fan housings shall be split to facilitate the removal of
the fan shaft.
d. Fan(s) shall be heavy-duty, centrifugal flow type mounted
on a steel shaft with heavy-duty, self-aligning,
relubricatable bearings with cast iron housings, designed
for a minimum L10 life of 40,000 hours.
e. Fan motor(s) shall be totally enclosed fan cooled (TEFC)
type with a 1.15 service factor, suitable for _____ V, ____
phase, ______ Hz electrical service and shall be
mounted on an easily adjusted, heavy-duty motor base.
Special moisture protection shall be provided on the
windings, shafts and bearings.
2.04 Optional Equipment Specifications
A. Evaporative condenser shall be provided with basin heaters to
prevent freezing of the water in the cold water basin when the
evaporative condenser is idle.
1. The basin heaters shall be selected to maintain +40F
(4.4C) basin water temperature at a 0F (-17.8C)
ambient temperature and 10 mph (16.1 km/hr) wind
speed.
2. Basin heaters shall be electric immersion type controlled
by a remote thermostat with the sensing bulb located in
the basin water.
3. Basin heaters shall be provided with a factory-installed
low water level cutout switch to prevent heater operation
unless the heater elements are fully submerged.
B. Evaporative condenser shall be supplied with dedicated
motors and drives so that each fan can be cycled independently,
and an internal baffle shall be supplied to deter air bypass within
the unit.
C. Evaporative condenser shall be provided with a factory
assembled, field-installed external platform with an access ladder
and handrails complying with OSHA standards and regulations to
provide access to the top of the evaporative condenser.
1. External platform shall have a 24" (610 mm) wide
non-skid walking surface and 42" (1220 mm) high
safety railings.
2. Optional ladder/safety cage shall be available to
meet OSHA requirements as necessary.
D. Evaporative condenser shall be supplied with the ENERGY-
MISER
Power Train
utilizes special corrosion-resistant materials of
construction and state-of-the-art technology to ensure
ease of maintenance and reliable year-round performance.
Separate Air Inlet Louvers Reduce the potential for
scale build-up and damaging ice formations at the air/water
interface by providing a line of sight from the outside of the
unit into the fill.
Long Service Life
Materials of Construction Various materials are available
to meet the corrosion resistance, unit operating life, and
budgetary requirements of any project (see page F44 for
construction options).
Oversized, hinged access door
Drift eliminators can be removed
for additional access to the
condensing coil
Spray distribution system
C
X
V
F40
Baltimore Aircoil Company
Construction Details
CXV Models
1
2
3
4
7
8
9
10
E
v
a
p
o
r
a
t
i
v
e
C
o
n
d
e
n
s
e
r
s
F41
...because temperature matters
Heavy-Duty Construction
G-235 (Z700 metric) hot-dip
galvanized steel panels
BALTIDRIVE
Power Train
Premium quality, solid-backed,
multi-groove belt
Corrosion resistant cast
aluminum sheaves
Heavy-duty bearings
(280,000 hour average life)
Cooling tower duty fan motor
Five-year motor and drive warranty
Low HP Axial Fan(s)
Quiet operation
Corrosion resistant aluminum
Water Distribution System
Visible and accessible during operation
Overlapping spray patterns ensure proper
water coverage
Large orifice, non-clog nozzles
Coil Section (Not Shown)
Continuous serpentine, steel tubing
Hot-dip galvanized after fabrication (HDGAF)
Pneumatically tested at 375 psig
Sloped tubes for free drainage of fluid
ASME B31.5 compliant
Orders shipping into Canada are supplied
with a CRN
BACross
Power Train
Premium quality, solid backed,
multi-groove belt
Corrosion resistant cast
aluminum sheaves
Heavy-duty bearings
(280,000 hour average life)
Cooling tower duty fan motor
Five-year motor and drive warranty
Low HP Axial Fan
Quiet operation
Corrosion resistant aluminum
Water Distribution System
Visible and accessible during operation
Overlapping spray patterns ensure proper
water coverage
Large orifice, non-clog nozzles
Coil Sections
Continuous serpentine, steel tubing
Hot-dip galvanized after fabrication (HDGAF)
Pneumatically tested at 375 psig
Sloped tubes for free drainage of fluid
ASME B31.5 compliant
Orders shipping into Canada are supplied
with a CRN
BACross
Wet Deck Surface with
Integral Drift Eliminators
Polyvinyl chloride (PVC)
Impervious to rot, decay and biological attack
Flame spread rating of 5 per ASTM E84-77a
FRP Air Inlet Louvers
Corrosion resistant
UV resistant finish
Maintenance free
Cold Water Basin
Sloped cold water basin for easy cleaning
Suction strainer with anti-vortex hood
Adjustable water make-up assembly
Integral Recirculating Spray
Water Pumps (Not Shown)
Close coupled, bronze fitted centrifugal pumps
Totally enclosed fan cooled (TEFC) motors
Bleed line with metering valve installed
from pump discharge to overflow
Hinged Access Doors
(Not Shown)
Inward swinging door on each end wall
1
2
3
4
5
6
7
8
9
10
11
C
X
V
F44
Baltimore Aircoil Company
Construction Options
Standard Construction:
All Models: All steel panels and structural elements are constructed of heavy-gauge G-235 hot-dip
galvanized steel. Inlet louvers are constructed of UV-resistant, fiberglass reinforced polyester (FRP).
CXV-T Models: Casing panels are constructed of UV-resistant, fiberglass reinforced polyester (FRP).
Optional BALTIBOND
Power Train.
This BAC engineered drive system consists of a specially designed powerband and two cast aluminum
sheaves located on minimum shaft centerline distances to maximize belt life. A cooling tower duty fan
motor, custom engineered for BAC to provide maximum performance for evaporative cooling service, is
provided and backed by BACs comprehensive five-year motor and fan drive warranty.
ENERGY-MISER
Fan System
The ENERGY-MISER
Fan System
Unit with intake and
discharge sound attenuation
C
X
V
F46
Baltimore Aircoil Company
Gear Drive System, Externally
Mounted Motor (CXV-T Models Only)
CXV-T Models are available with a gear drive
system with external TEFC motor. A non-corrosive
carbon-fiber composite drive shaft with stainless
steel hubs is selected with a 2.0 service factor. The
motor and drive shaft ship separately for easy field
installation.
Gear Drive System, Close-Coupled
Motor (CXV-T Models Only)
CXV-T Models are available with a close-coupled
gear drive system. Both the gear drive and
couplings are selected with a 2.0 service factor.
Gear construction includes a nickel-alloy steel shaft,
casehardened gears, self lubrication, and a single
piece, gray iron housing. This drive system ships
completely installed and aligned.
Basinless Unit Construction
(CXV-T Models Only)
The basinless unit construction option enables units to be directly
applied to new or existing concrete cold water basins. This
custom feature, available exclusively on BAC CXV-T evaporative
condensers, reduces maintenance costs by eliminating the
integral basin from traditional units. It simplifies piping and
pumping requirements of multi-cell installations and provides a
cost-effective solution for many field-erected replacement
projects.
Custom Features and Options
Gear Drive System,
Externally Mounted Motor
CXV-T installation on a
concrete basin
Gear Drive System,
Close-Coupled Motor
E
v
a
p
o
r
a
t
i
v
e
C
o
n
d
e
n
s
e
r
s
F47
...because temperature matters
Accessories
External Service Platforms
For external service, louver face and access door
platforms can be added to the unit when purchased
or as an aftermarket item. Safety gates are available
for all handrail openings. All components are
designed to meet OSHA requirements.
Ladder, Safety Cage, Safety Gate and Handrails (CXV-T Models Only)
In the event the end-user elects to provide access to the fan deck, CXV-T models can be furnished
with ladders extending from the top of the unit to the base, as well as safety cages, safety gates, fan
deck extensions and handrail packages. All components are designed to meet OSHA requirements. All
access to the top of the equipment must be made in accordance with applicable governmental
occupational safety standards.
NOTE: Partial or full grating above the coil air intake is recommended with this option
Internal Ladder
For access to the motor and drive assemblies on models CXV-64 thru -962 and CXV-N465 thru -N687,
an internal ladder is available.
Internal Service Platforms
For access to the motor and drive assemblies on
models CXV-196 thru -962, CXV-N465 thru -N687,
and all CXV-T models, an upper service platform
with ladder and handrails is available. Safety gates
are available for handrail openings. All components
are designed to meet OSHA requirements.
Internal ladder and service platform
External platform at louver face
with ladder and safety cage
C
X
V
F48
Baltimore Aircoil Company
Accessories
Vibration Cutout Switch
A factory mounted vibration cutout switch is available to effectively protect against equipment failure
due to excessive vibration of the mechanical equipment system. BAC can provide either a mechanical
or solid-state electronic vibration cutout switch in a NEMA 4 enclosure to ensure reliable protection.
Additional contacts can be provided to activate an alarm.
Basin Heaters
Evaporative condensers exposed to below freezing ambient temperatures require protection to prevent
freezing of the water in the cold water basin when the unit is idle. Factory-installed heaters, which
maintain +40F (4.4C) water temperature, are a simple and inexpensive way of providing such
protection.
Electric Water Level Control Package
The electric water level control replaces the
standard mechanical makeup valve when a more
precise water level control is required. This
package consists of a conductance-actuated level
control mounted in the basin and a solenoid
activated valve in the make-up water line. The
valve is slow closing to minimize water hammer.
Electric Water Level Control Package
No. of HEATERS kW per HEATER No. of HEATERS kW per HEATER
CXV-64 thru -95 1 4 1 6
CXV-103 thru -153 1 6 1 8
CXV-160 thru -206 1 8 1 12
CXV-196 thru -305 1 12 1 16
CXV-310 thru -481 1 16 1 21
CXV-N465 thru -N687 2 10 2 15
CXV-420 thru -610 2 12 2 16
CXV-620 thru -962 2 16 2 21
CXV-T645 thru -T792 2 12 2 15
CXV-T791 thru -T944 2 14 2 20
CXV-T1290 thru -T1584 4 12 4 15
CXV-T1654 thru -T1888 4 14 4 20
MODEL NUMBERS
0F (-17.8C) AMBIENT HEATERS -20F (-28.9C) AMBIENT HEATERS
E
v
a
p
o
r
a
t
i
v
e
C
o
n
d
e
n
s
e
r
s
F49
...because temperature matters
Extended Lubrication Lines
Extended lubrication lines are available for lubrication of the fan shaft bearings. Grease fittings are
located inside the plenum area next to the access door.
Air Inlet Screens
Wire mesh screens can be factory-installed over the inlet louvers and the spray distribution system to
prevent debris from entering the unit.
Basin Sweeper Piping
Basin sweeper piping provides an effective method of preventing
debris from collecting in the cold water basin of the unit. A
complete piping system, including nozzles, is provided in the
cold water basin for connection to side stream filtration
equipment (by others).
Copper Sweat Fittings
Optional copper sweat fittings are available to simplify
field piping.
Grease fittings at the access door & bearings with the extended lubrication line option
Basin Sweeper Piping
Copper Sweat Fittings
C
X
V
F50
Baltimore Aircoil Company
Do not use for construction. Refer to factory certified dimensions. This brochure includes data current
at time of publication, which should be reconfirmed at the time of purchase. Up-to-date engineering data,
free product selection software, and more can be found at www.BaltimoreAircoil.com.
Engineering Data
12'1-1/4"
SIDE ELEVATION
1/2" MAKE UP
MODELS
160206
1'8-1/4"
1/2" MAKE UP
MODELS MODELS
103153 6495
9'1-1/4"
SIDE ELEVATION
1'4-1/4"
1/2" MAKE UP
SIDE ELEVATION END ELEVATION
6'1-1/4" 1'3-3/4"
ACCESS DOOR
BOTH ENDS
3" OVERFLOW
2" DRAIN
8' 5-1/4"
6
"
0
-
3
/
4
"
1
3
'
2
-
3
/
4
"
REFRIG IN
REFRIG OUT
Notes:
1. Model number denotes nominal ammonia capacity in
evaporator tons at a 96.3F condensing temperature, a 20F
suction temperature, and a 78F wet-bulb temperature.
2. R-22 tons are at a 105F condensing temperature, a 40F
suction temperature, and a 78F wet-bulb temperature.
3. Operating weight is for the unit with the water level in the
cold water basin at the overflow.
4. For R-22 and R-134a, the coil connection quantity will double
(except for the CXV-64 thru -153).
5. The R-22 operating charge is 1.93 times the ammonia charge;
R-134a is 1.98 times.
6. Inlet and outlet connections are beveled for welding.
7. Standard make-up, drain and overflow connections are MPT.
See page J16
for information on sizing
a remote sump tank.
FAN PUMP OPERATING
3
SHIPPING
HEAVIEST
SECTION
CXV-64 81 5 1.5 28,950 7,410 5,020 2,870 51 6.2
CXV-77 97 5 1.5 28,550 7,780 5,340 3,190 67 8.0
CXV-86 109 5 1.5 27,850 8,170 5,680 3,530 84 10
CXV-95 120 7.5 1.5 31,050 8,570 6,030 3,880 101 12
CXV-103 130 10 2 48,650 10,800 7,160 4,240 76 9.2
CXV-119 151 7.5 2 43,650 11,350 7,640 4,720 101 12
CXV-125 158 10 2 48,000 11,360 7,650 4,730 101 12
CXV-134 170 7.5 2 42,550 11,910 8,130 5,210 126 15
CXV-143 181 10 2 45,650 12,480 8,630 5,710 151 18
CXV-153 194 15 2 52,150 12,530 8,680 5,760 151 18
CXV-160 203 10 3 58,750 14,330 9,360 5,720 135 16
CXV-171 216 15 3 67,150 14,380 9,410 5,770 135 16
CXV-179 227 10 3 57,250 15,060 10,010 6,370 168 20
CXV-192 243 15 3 65,450 15,130 10,060 6,420 168 20
CXV-184 233 10 3 55,850 15,830 10,670 7,030 201 24
CXV-206 261 20 3 70,200 15,930 10,770 7,130 201 24
INTERNAL
COIL
VOLUME
(FT
3
)
R-717
OPERATING
CHARGE
5
(LBS)
WEIGHTS (LBS)
MODEL
NUMBER
1
AIRFLOW
(CFM)
MOTOR HP
NOMINAL
R-22
TONS
2
E
v
a
p
o
r
a
t
i
v
e
C
o
n
d
e
n
s
e
r
s
F51
...because temperature matters
REFRIG OUT
REFRIG IN
ACCESS DOOR
BOTH ENDS
H
A
3" OVERFLOW
2" DRAIN
11'10"
END ELEVATION SIDE ELEVATION SIDE ELEVATION
1'8-1/4" 12'1-1/4"
1" MAKE UP
MODELS
196305
MODELS
310481
2'0-3/8" 18'1-1/4"
1" MAKE UP
Notes:
1. Model number denotes nominal ammonia capacity in
evaporator tons at a 96.3F condensing temperature, a 20F
suction temperature, and a 78F wet-bulb temperature.
2. R-22 tons are at a 105F condensing temperature, a 40F
suction temperature, and a 78F wet-bulb temperature.
3. Operating weight is for the unit with the water level in the cold
water basin at the overflow.
4. For R-22 and R-134a, the coil connection quantity will double.
5. The R-22 operating charge is 1.93 times the ammonia charge;
R-134a is 1.98 times.
6. Inlet and outlet connections are beveled for welding.
7. Standard make-up, drain and overflow connections are MPT.
See page F58
for Engineering
Considerations.
FAN PUMP OPERATING
3
SHIPPING
HEAVIEST
SECTION
A H
CXV-196 248 10 5 68,160 17,480 10,740 6,580 164 20 8'-8 3/4" 15'-10 3/4"
CXV-210 266 15 5 77,900 17,530 10,790 6,630 164 20 8'-8 3/4" 15'-10 3/4"
CXV-220 278 20 5 85,650 17,580 10,840 6,680 164 20 8'-8 3/4" 15'-10 3/4"
CXV-235 297 10 5 67,200 18,670 11,780 7,620 217 26 8'-8 3/4" 15'-10 3/4"
CXV-253 320 15 5 76,800 18,720 11,830 7,670 217 26 8'-8 3/4" 15'-10 3/4"
CXV-264 334 10 5 64,930 19,870 12,830 8,670 270 32 8'-8 3/4" 15'-10 3/4"
CXV-283 358 15 5 74,200 19,920 12,880 8,720 270 32 8'-8 3/4" 15'-10 3/4"
CXV-290 367 15 5 72,700 21,110 13,920 9,760 321 38 8'-8 3/4" 15'-10 3/4"
CXV-305 386 20 5 79,950 21,160 13,970 9,810 321 38 8'-8 3/4" 15'-10 3/4"
CXV-310 392 15/7.5 7.5 117,900 25,500 15,320 9,500 243 29 9'-2 1/4" 16'-4 1/4"
CXV-324 410 10/5 7.5 129,650 25,590 15,410 9,590 243 29 9'-2 1/4" 16'-4 1/4"
CXV-337 427 25/15 7.5 139,550 25,690 15,510 9,690 243 29 9'-2 1/4" 16'-4 1/4"
CXV-349 442 10/5 7.5 101,760 27,210 16,810 10,990 321 39 9'-2 1/4" 16'-4 1/4"
CXV-373 472 15/7.5 7.5 116,300 27,290 16,890 11,070 321 39 9'-2 1/4" 16'-4 1/4"
CXV-388 491 10/5 7.5 98,310 29,030 18,400 12,580 401 48 9'-2 1/4" 16'-4 1/4"
CXV-398 504 10/5 7.5 96,290 30,830 19,990 14,170 475 57 9'-2 1/4" 16'-4 1/4"
CXV-416 527 15/7.5 7.5 112,350 29,110 18,480 12,660 401 48 9'-2 1/4" 16'-4 1/4"
CXV-427 541 15/7.5 7.5 110,050 30,910 20,070 14,250 475 57 9'-2 1/4" 16'-4 1/4"
CXV-449 568 20/10 7.5 121,050 30,990 20,150 14,330 475 57 9'-2 1/4" 16'-4 1/4"
CXV-466 590 25/15 7.5 130,300 31,100 20,260 14,440 475 57 9'-2 1/4" 16'-4 1/4"
CXV-481 609 30/15 7.5 138,350 31,120 20,280 14,460 475 57 9'-2 1/4" 16'-4 1/4"
INTERNAL
COIL
VOLUME
(FT
3
)
DIMENSIONS
AIRFLOW
(CFM)
R-717
OPERATING
CHARGE
5
(LBS)
MOTOR HP WEIGHTS (LBS)
MODEL
NUMBER
1
NOMINAL R-
22 TONS
2
C
X
V
F52
Baltimore Aircoil Company
Do not use for construction. Refer to factory certified dimensions. This brochure includes data current
at time of publication, which should be reconfirmed at the time of purchase. Up-to-date engineering data,
free product selection software, and more can be found at www.BaltimoreAircoil.com.
Engineering Data
ACCESS DOOR
BOTH ENDS
REFRIG OUT
REFRIG IN
H
A
3" OVERFLOW
2" DRAIN
11'10"
END ELEVATION SIDE ELEVATION
1'8-1/4"
24 -5"
2-1/2"
1" MAKE UP
MODELS
420610
1'8-1/4"
SIDE ELEVATION
2'0-3/8"
36'5"
2-1/2"
1" MAKE UP 1" MAKE UP
MODELS
620962
2'0-3/8"
Notes:
1. Model number denotes nominal ammonia capacity in
evaporator tons at a 96.3F condensing temperature, a 20F
suction temperature, and a 78F wet-bulb temperature.
2. R-22 tons are at a 105F condensing temperature, a 40F suction
temperature, and a 78F wet-bulb temperature.
3. Operating weight is for the unit with the water level in the cold
water basin at the overflow.
4. For R-22 and R-134a, the coil connection quantity will double.
5. The R-22 operating charge is 1.93 times the ammonia charge; R-
134a is 1.98 times.
6. Inlet and outlet connections are beveled for welding.
7. Standard make-up, drain and overflow connections are MPT.
FAN PUMP OPERATING
3
SHIPPING
HEAVIEST
SECTION A H
CXV-420 532 (2) 15 (2) 5 155,800 35,060 21,580 6,630 328 39 8'-8 3/4" 15'-10 3/4"
CXV-470 595 (2) 10 (2) 5 134,400 37,340 23,560 7,620 434 51 8'-8 3/4" 15'-10 3/4"
CXV-506 641 (2) 15 (2) 5 153,600 37,440 23,660 7,670 434 51 8'-8 3/4" 15'-10 3/4"
CXV-528 668 (2) 10 (2) 5 129,860 39,740 25,660 8,670 540 64 8'-8 3/4" 15'-10 3/4"
CXV-566 716 (2) 15 (2) 5 148,400 39,840 25,760 8,720 540 64 8'-8 3/4" 15'-10 3/4"
CXV-580 734 (2) 15 (2) 5 145,400 42,220 27,840 9,760 642 76 8'-8 3/4" 15'-10 3/4"
CXV-610 772 (2) 20 (2) 5 159,900 42,320 27,940 9,810 642 76 8'-8 3/4" 15'-10 3/4"
CXV-620 785 (2)15/(2)7.5 (2) 7.5 235,800 51,000 30,640 9,500 486 58 9'-2 1/4" 16'-4 1/4"
CXV-648 820 (2)20/(2)10 (2) 7.5 259,300 51,180 30,820 9,590 486 58 9'-2 1/4" 16'-4 1/4"
CXV-674 853 (2)25/(2)15 (2) 7.5 279,100 51,380 31,020 9,690 486 58 9'-2 1/4" 16'-4 1/4"
CXV-698 884 (2)10/(2)5 (2) 7.5 203,520 54,400 33,600 11,000 642 77 9'-2 1/4" 16'-4 1/4"
CXV-746 944 (2)15/(2)7.5 (2) 7.5 232,600 54,580 33,780 11,070 642 77 9'-2 1/4" 16'-4 1/4"
CXV-776 982 (2)10/(2)5 (2) 7.5 196,620 58,040 36,780 12,590 802 96 9'-2 1/4" 16'-4 1/4"
CXV-796 1,008 (2)10/(2)5 (2) 7.5 192,580 61,660 39,980 14,180 950 115 9'-2 1/4" 16'-4 1/4"
CXV-832 1,053 (2)15/(2)7.5 (2) 7.5 224,700 58,220 36,960 12,660 802 96 9'-2 1/4" 16'-4 1/4"
CXV-854 1,081 (2)15/(2)7.5 (2) 7.5 220,100 61,820 40,140 14,250 950 115 9'-2 1/4" 16'-4 1/4"
CXV-898 1,137 (2)20/(2)10 (2) 7.5 242,100 61,980 40,300 14,330 950 115 9'-2 1/4" 16'-4 1/4"
CXV-932 1,180 (2)25/(2)15 (2) 7.5 260,600 62,200 40,520 14,440 950 115 9'-2 1/4" 16'-4 1/4"
CXV-962 1,218 (2)30/(2)15 (2) 7.5 276,700 62,240 40,560 14,460 950 115 9'-2 1/4" 16'-4 1/4"
MOTOR HP
MODEL
NUMBER
1
NOMINAL
R-22
TONS
2
INTERNAL
COIL
VOLUME
(FT
3
)
DIMENSIONS
R-717
OPERATING
CHARGE
5
(LBS)
AIRFLOW
(CFM)
WEIGHTS (LBS)
E
v
a
p
o
r
a
t
i
v
e
C
o
n
d
e
n
s
e
r
s
F53
...because temperature matters
See page F58 for
engineering
considerations
REFRIG IN
REFRIG OUT
ACCESS DOOR
BOTH ENDS
3" OVERFLOW
2" DRAIN
11'10"
END ELEVATION
9
'
2
-
1
/
4
"
1
6
'
4
-
1
/
4
"
1'8-1/4" 23'6"
SIDE ELEVATION
1" MAKE UP
MODELS
N465N687
1'8-1/4"
Notes:
1. Model number denotes nominal ammonia capacity in
evaporator tons at a 96.3F condensing temperature, a 20F
suction temperature, and a 78F wet-bulb temperature.
2. R-22 tons are at a 105F condensing temperature, a 40F suction
temperature, and a 78F wet-bulb temperature.
3. Operating weight is for the unit with the water level in the cold
water basin at the overflow.
4. For R-22 and R-134a, the coil connection quantity will double.
For ammonia applications above 676 tons, the coil connection
quantity will double.
5. The R-22 operating charge is 1.93 times the ammonia charge;
R-134a is 1.98 times.
6. Inlet and outlet connections are beveled for welding.
7. Standard make-up, drain and overflow connections are MPT.
8. The vertical liquid leg height for models CXV-N465 thru
CXV-N687 should be at least 12 feet for multiple condenser
installations on ammonia applications. Minimum liquid leg height
is subject to overall system piping requirements.
FAN PUMP OPERATING
3
SHIPPING
HEAVIEST
SECTION
CXV-N465 589 (2) 15 (2) 5 174,270 34,400 20,890 12,750 323 39
CXV-N491 622 (2) 10 (2) 5 149,230 36,590 22,780 14,640 427 51
CXV-N530 671 (2) 15 (2) 5 170,810 36,730 22,920 14,780 427 51
CXV-N559 708 (2) 20 (2) 5 188,430 36,770 22,960 14,820 427 51
CXV-N574 727 (2) 15 (2) 5 169,210 39,110 25,000 16,860 532 63
CXV-N605 766 (2) 20 (2) 5 186,220 39,150 25,040 16,900 532 63
CXV-N636 805 (2) 20 (2) 5 183,020 41,510 27,120 18,980 631 76
CXV-N664 841 (2) 25 (2) 5 197,790 41,610 27,220 19,080 631 76
CXV-N687 870 (2) 30 (2) 5 210,170 41,890 27,500 19,360 631 76
NOMINAL
R-22
TONS
2
MODEL
NUMBER
1
INTERNAL
COIL
VOLUME
(FT
3
)
R-717
OPERATING
CHARGE
5
(LBS)
AIRFLOW
(CFM)
MOTOR HP WEIGHTS (LBS)
Designed to minimize refrigerant piping, these models have coil connections on just one end.
C
X
V
F54
Baltimore Aircoil Company
Do not use for construction. Refer to factory certified dimensions. This brochure includes data current
at time of publication, which should be reconfirmed at the time of purchase. Up-to-date engineering data,
free product selection software, and more can be found at www.BaltimoreAircoil.com.
Engineering Data - CXV-T Models
END ELEVATION
SPRAY PUMPS
ACCESS DOORS
BOTH ENDS
REFRIG. IN
REFRIG. OUT
REFRIG. IN
REFRIG. OUT
H
1
0
'
-
4
3
/
4
"
W
CXV
T1290 to T1888
2-1/2"
L
SIDE ELEVATION SIDE ELEVATION
CXV
T645 to T944
L
Notes:
1. Model number denotes nominal ammonia capacity in
evaporator tons at a 96.3F condensing temperature, a 20F
suction temperature, and a 78F wet-bulb temperature.
2. R-22 tons are at a 105F condensing temperature, a 40F suction
temperature, and a 78F wet-bulb temperature.
3. Operating weight is for the unit with the water level in the cold
water basin at the overflow.
4. Coil connections also available on the end. For other refrigerants,
contact your local BAC Representative for the coil connection
quantity.
5. The R-22 operating charge is 1.93 times the ammonia charge;
R-134a is 1.98 times.
6. Inlet and outlet connections are beveled for welding.
7. Standard make-up, drain and overflow connections are located on
the bottom of the unit. Make-up connection is 1-1/2 MPT
standpipe, drain is 2 FPT and overflow is 3 FPT.
8. Models shipped with an optional gear drive or low sound fan may
have heights up to 10.5" greater than shown.
FAN PUMP OPERATING
3
SHIPPING
HEAVIEST
SECTION W L H
8
CXV-T645 816 30 (2) 7.5 177,100 42,640 27,710 8,050 656 76 24'-1/2" 11'-11" 18'-7 7/8"
CXV-T686 868 40 (2) 7.5 195,420 42,780 27,850 8,050 656 76 24'-1/2" 11'-11" 18'-7 7/8"
CXV-T717 908 50 (2) 7.5 210,980 42,840 27,910 8,050 656 76 24'-1/2" 11'-11" 18'-7 7/8"
CXV-T729 923 40 (2) 7.5 193,150 45,810 30,610 9,430 780 91 24'-1/2" 11'-11" 18'-7 7/8"
CXV-T763 966 50 (2) 7.5 208,490 45,870 30,670 9,430 780 91 24'-1/2" 11'-11" 18'-7 7/8"
CXV-T792 1,003 60 (2) 7.5 221,910 46,030 30,830 9,430 780 91 24'-1/2" 11'-11" 18'-7 7/8"
CXV-T791 1,001 40 (2) 7.5 225,480 50,070 31,770 9,390 753 89 26'-3 1/2" 13'-11 1/8" 18'-9 7/8"
CXV-T827 1,047 50 (2) 7.5 245,080 50,130 31,830 9,390 753 89 26'-3 1/2" 13'-11 1/8" 18'-9 7/8"
CXV-T857 1,085 60 (2) 7.5 260,910 50,290 31,990 9,390 753 89 26'-3 1/2" 13'-11 1/8" 19'-5 7/8"
CXV-T876 1,109 50 (2) 7.5 240,050 53,740 35,110 11,030 903 107 26'-3 1/2" 13'-11 1/8" 18'-9 7/8"
CXV-T906 1,147 60 (2) 7.5 255,630 53,900 35,270 11,030 903 107 26'-3 1/2" 13'-11 1/8" 19'-5 7/8"
CXV-T944 1,195 75 (2) 7.5 278,020 53,950 35,320 11,030 903 107 26'-3 1/2" 13'-11 1/8" 19'-5 7/8"
CXV-T1290 1,633 (2) 30 (4) 7.5 354,200 85,280 55,420 8,050 1,312 153 24'-1/2" 24'-1/2" 18'-7 7/8"
CXV-T1372 1,737 (2) 40 (4) 7.5 390,840 85,560 55,700 8,050 1,312 153 24'-1/2" 24'-1/2" 18'-7 7/8"
CXV-T1434 1,815 (2) 50 (4) 7.5 421,960 85,680 55,820 8,050 1,312 153 24'-1/2" 24'-1/2" 18'-7 7/8"
CXV-T1458 1,846 (2) 40 (4) 7.5 386,300 91,620 61,220 9,430 1,560 183 24'-1/2" 24'-1/2" 18'-7 7/8"
CXV-T1526 1,932 (2) 50 (4) 7.5 416,980 91,740 61,340 9,430 1,560 183 24'-1/2" 24'-1/2" 18'-7 7/8"
CXV-T1584 2,005 (2) 60 (4) 7.5 443,820 92,060 61,660 9,430 1,560 183 24'-1/2" 24'-1/2" 18'-7 7/8"
CXV-T1582 2,003 (2) 40 (4) 7.5 450,960 100,140 63,540 9,390 1,506 179 26'-3 1/2" 28'-3/4" 18'-9 7/8"
CXV-T1654 2,094 (2) 50 (4) 7.5 490,160 100,260 63,660 9,390 1,506 179 26'-3 1/2" 28'-3/4" 18'-9 7/8"
CXV-T1714 2,170 (2) 60 (4) 7.5 521,820 100,580 63,980 9,390 1,506 179 26'-3 1/2" 28'-3/4" 18'-9 7/8"
CXV-T1752 2,218 (2) 50 (4) 7.5 480,100 107,480 70,220 11,030 1,806 214 26'-3 1/2" 28'-3/4" 18'-9 7/8"
CXV-T1812 2,294 (2) 60 (4) 7.5 511,260 107,800 70,540 11,030 1,806 214 26'-3 1/2" 28'-3/4" 18'-9 7/8"
CXV-T1888 2,390 (2) 75 (4) 7.5 556,040 107,900 70,640 11,030 1,806 214 26'-3 1/2" 28'-3/4" 18'-9 7/8"
INTERNAL
COIL
VOLUME
(FT
3
)
DIMENSIONS R-717
OPERATING
CHARGE
4
(LBS)
AIRFLOW
(CFM)
MOTOR HP WEIGHTS (LBS)
MODEL
NUMBER
1
NOMINAL
R-22
TONS
2
E
v
a
p
o
r
a
t
i
v
e
C
o
n
d
e
n
s
e
r
s
F55
...because temperature matters
The recommended support arrangement for CXV Evaporative Condensers consists of parallel I-beams
positioned as shown in the drawings. Besides providing adequate support, the steel also serves to raise
the unit above any solid foundation to assure access to the bottom of the unit. Alternate steel support
designs include a cantilevered plan as indicated by the optional minimum D dimension in the table below.
When unit is supported with a cantilever plan, the side opposite the air inlet shall be cantilevered. To
support a CXV on columns or in an alternate arrangement not shown here, consult your local BAC
Representative.
Structural Support
AIR
IN
1 1/8" D
STEEL SUPPORT
A
A/2
1 7/16"
AIR
IN
AIR
IN
Notes:
1. Support steel and anchor bolts to be designed and furnished
by others.
2. All support steel must be level at the top.
3. Beams must be selected in accordance with accepted structural
practice. Maximum deflection of beam under unit to be 1/360 of
span, not to exceed 1/2 inch.
4. If vibration isolation rails are to be used between unit and
supporting steel, be certain to allow for the length of the vibration
rails when determining the length of the supporting steel, as
vibration rail length and mounting hole locations may differ from
those of the unit.
5. If point vibration isolation is used with multi-cell units, the isolators
must be located under the support steel, not between the support
steel and the units.
MODEL NUMBER D
OPTIONAL
MINIMUM D
MAXIMUM
DELFECTION
CXV-64 to 95 8'-3" 6'-0" 3/16"
CXV-103 to 153 8'-3" 6'-0" 5/16"
CXV-160 to 206 8'-3" 6'-0" 3/8"
CXV-196 to 305 11'-7 3/4" 9'-6" 3/8"
CXV-310 to 481 11'-7 3/4" 9'-6" 1/2"
CXV-N465 to N687 11'-7 3/4" 9'-6" 1/2"
CXV-420 to 610 11'-7 3/4" 9'-6" 3/8"
CXV-620 to 962 11'-7 3/4" 9'-6" 1/2"
MODEL NUMBER A
MAXIMUM
DEFLECTION
CXV-T645 to T792 23'-9 5/8" 1/2"
CXV-T791 to T944 26'- 5/8" 1/2"
CXV-T1290 to T1584 23'-9 5/8" 1/2"
CXV-T1654 to T1888 26'- 5/8" 1/2"
C
X
V
F56
Baltimore Aircoil Company
Part 1: General
A. General: Furnish and install ________ factory assembled
evaporative condenser(s) of induced draft design with vertical
discharge, conforming in all aspects to the specifications and
schedules as shown on the plans.
B. Capacity: The evaporative condenser(s) shall be warranted
by the manufacturer to have condensing capacity of _____
BTUH heat rejection, operating with _____ refrigerant at ___F
condensing temperature and ___F entering wet-bulb
temperature.
C. Warranty: The manufacturer shall provide a five-year
mechanical drive warranty covering the fans, fan shafts, bear-
ings, sheaves, supports, and fan motors. The manufacturers
standard equipment warranty for the balance of the components
shall be for a period of one year from the date of startup or
eighteen months from the date of shipment, whichever ends first.
D. Factory Testing: The manufacturer shall be capable of
testing the operation of the condenser in the manufacturers own
test facility. Test facilities shall be capable of simulating design
conditions, including but not limited to design wet-bulb, airflow,
refrigerant mass flow rate, refrigerant condensing temperature,
and total heat rejection.
E. Quality Assurance: The manufacturer shall have a
Management System certified by an accredited registrar as
complying with the requirements of ISO-9001:2000 to ensure
consistent quality of products and services. Manufacturers that
are not ISO-9001:2000 certified shall provide an additional one
year warranty to the customer at no additional cost.
Part 2: Products
2.01 Evaporative Condenser Materials and Components
A. General: A. General: All steel panels and structural elements
shall be constructed from heavy-gauge, G-235 (Z700 metric)
hot-dip galvanized steel, with cut edges given a protective
coating of zinc-rich compound.
Or, for CXV-T Models
A. General: All steel panels and structural elements shall be
constructed from heavy-gauge, G-235 (Z700 metric), hot-dip
galvanized steel, with cut edges given a protective coating of
zinc-rich compound. Casing panels shall be constructed of
corrosion resistant, fiberglass, reinforced polyester (FRP).
2.02 Coil Casing Assembly
A. The evaporative condenser shall include a coil casing section
consisting of refrigerant condensing coil, spray water distribution
system, drift eliminators, and air plenum with fan assemblies as
indicated by the manufacturer.
1.The refrigerant condensing coil shall be fabricated of
continuous lengths of all prime surface steel at the
manufacturers own facility, and hot-dip galvanized
after fabrication.
a. The refrigerant condensing coil shall be pneumatically
tested at 375 psig (2687 kPa).
b. The refrigerant condensing coil shall be designed for
low pressure drop with sloping tubes for free drainage
of liquid refrigerant.
c. The refrigerant condensing coil shall be ASME B31.5
compliant and coils shipping into Canada shall be
supplied with a CRN.
2. Water shall be distributed evenly over the coil at a
minimum flow rate of 10 gpm/ft
2
(6.8 lps/m
2
) to ensure
complete wetting of the coil at all times. Large-diameter,
non-clog, 360plastic distribution nozzles shall be
spaced across the coil face area in Schedule 40 PVC
spray branches. Nozzles shall utilize a two-stage
diffusion pattern to provide overlapping, umbrella spray
patterns that create multiple intersection points with
adjacent nozzles.
a. Nozzles and spray branches shall be observable and
accessible for cleaning from the outside of the
evaporative condenser during condenser operation
without the removal of other components.
b. Spray branches and nozzles shall be held in place by
snap-in rubber grommets, allowing quick removal of
individual nozzles or complete branches for cleaning
or flushing.
3. Removable PVC drift eliminators shall be positioned to
prevent moisture from entering the air plenum and
incorporate a minimum of three (3) changes in air
direction.
4. Fan(s) shall be heavy-duty, axial type with aluminum
alloy blades driven by a one-piece, multi-groove
neoprene/polyester belt designed for a minimum of 150%
of the motor nameplate horsepower.
a. Fan(s) and shafts shall be supported by heavy-duty,
self aligning, grease-packed ball bearings with
moisture-proof seals and integral sealer rings,
designed for a minimum L10 life of 40,000 hours
(280,000 hours average life).
b. Fan and motor sheaves shall be fabricated from
corrosion resistant materials.
c. Fan motor(s) shall be totally enclosed air over (TEAO)
type with a 1.15 service factor, suitable for ____ volt,
____ phase, ___ Hz electrical service and shall be
mounted on an easily adjusted, heavy-duty motor
base.
d. The motor shall be furnished with double-sealed,
permanently lubricated bearings and special moisture
protection on windings, shafts and bearings.
e. Air plenum shall provide a minimum of 48 (1220 mm)
clearance under the motor base to provide comfortable
working space for service personnel.
Engineering Specifications
See our website at www.BaltimoreAircoil.com for an electronic copy of product engineering specifications.
E
v
a
p
o
r
a
t
i
v
e
C
o
n
d
e
n
s
e
r
s
F57
...because temperature matters
2.03 Pan Assembly
A. The evaporative condenser shall include a pan assembly
consisting of cold water basin with pump assembly, heat
transfer section for spray water cooling with integral drift
eliminators, and wide spaced air inlet louvers.
1. The cold water basin shall be constructed of heavy-gauge
steel panels and structural members. Basin shall include a
depressed section with drain/cleanout connection. The
basin area under the wet deck surface shall be sloped
toward the depressed section to facilitate cleaning.
- OR -
1. The cold water basin shall be constructed of heavy-gauge
Type 304 stainless steel panels and structural members,
with all welded seams. The welded stainless steel basin
shall be leak tested at the factory. Basin shall include a
depressed section with drain/cleanout connection. The
basin area under the wet deck surface shall be sloped
toward the depressed section to facilitate cleaning.
2. The cold water basin shall include: a drain/clean-out
connection; a steel strainer; a brass make-up valve; over
flow connection; and a water recirculation pump assembly.
a. Cold water basin shall be designed so that the strainer,
makeup valve and float, and pump assembly are easily
accessible without removing any of the unit panels or
other components.
b.Lift-out steel strainer shall be supplied with perforated
openings sized smaller than the water distribution nozzle
orifices and an integral anti-vortexing hood to prevent air
entrainment.
c. Water recirculation pump shall be a close-coupled,
bronze-fitted centrifugal pump equipped with a
mechanical seal, mounted on the basin and piped from
the suction strainer to the water distribution system.
i. The pump shall be installed with adequate drains so
that it may drain freely when the basin is drained.
ii. The pump assembly shall include an integral metering
valve and bleed line to control the bleed rate from the
pump discharge to the overflow connection.
iii.The pump motor shall be totally enclosed fan cooled
(TEFC) type suitable for _____ volt, ____ phase,
______ Hz electrical service.
d.On installations requiring a remote sump, the evaporative
condenser shall be modified to accommodate the use of
an independent sump and pump for recirculating water
(by others).
i. The recirculating water pump, steel strainer, make-up
valve, and integral bleed line assemblies shall be
omitted from the evaporative condenser scope of
supply.
ii. The evaporative condenser shall be supplied with a
cold water basin outlet sized and located as indicated
on the drawings for gravity drain to the remote sump.
iii.The water distribution system shall have a design
operating pressure of 1 psig (108.25 kPa) at the
evaporative condenser spray water inlet connection.
3. The heat transfer section shall consist of wet deck surface
with integral drift eliminators for cooling the spray water
leaving the coil to optimize the thermal performance of the
evaporative condenser.
a. The wet deck surface and integral drift eliminators shall
be formed from polyvinyl chloride (PVC).
b.The wet deck surface and integral drift eliminators shall
be impervious to rot, decay, fungus, and biological attack.
4. The air inlet louvers shall be manufactured of wave-formed,
fiberglass-reinforced polyester (FRP) widely spaced to
minimize air resistance and prevent water splash-out.
2.04 Optional Equipment Specifications
A. Evaporative condenser shall be provided with basin heaters to
prevent freezing of the recirculating water when the evaporative
condenser is idle.
1. The basin heaters shall be selected to maintain +40F
(4.4C) basin water temperature at a 0F (-17.8C) ambient
temperature and 10 mph (16.1 km/hr) wind speed.
2. Basin heaters shall be electric immersion type controlled by
a remote thermostat with the sensing bulb located in the
basin water.
3. Basin heaters shall be provided with a low water level
cutout switch to prevent heater operation unless the heater
elements are adequately submerged.
B. Evaporative condenser shall be provided with extended
lubri cation lines with standard grease fittings for lubricating the
fan shaft bearings from the outside base of the condenser.
C. Evaporative condenser shall be supplied with dedicated
motors and drives so that each fan can be cycled
independently.
D. Evaporative condenser shall be provided with a factory
assembled, field-installed external platform with an access
ladder and handrails complying with OSHA standards and
regulations to provide access to the top of the evaporative
condenser.
1. External platform shall have a 24 (610 mm) wide non-skid
walking surface and 42 (1220 mm) high safety railings.
2. Optional ladder safety cage shall be available to meet
OSHA requirements as necessary.
Or, for CXV-T Models
D. Evaporative condenser shall be provided with factory
assembled, field installed perimeter safety railings and walking
surface above coil air intake to provide access to the top of
the evaporative condenser.
E. Evaporative condenser shall be provided with a moveable
ladder with fixed ladder supports to provide access to the fan
drive system and coil assembly.
F. Evaporative condenser shall be provided with an internal
walkway at the access door to facilitate servicing the unit.
G. Evaporative condenser shall be provided with a factory
assembled internal working platform with ladder to provide a
permanent working surface for maintenance personnel
(CXV-193 and larger only).
H. Evaporative condenser shall be provided with the ENERGY-
MISER
Fan System, two-speed motors, or variable frequency drives can also be used to reduce sound during
periods of non-peak thermal loads. For more information on sound and how it relates to evaporative cooling
equipment, see page J20. For detailed low sound selections, please consult your local BAC Representative.
E
v
a
p
o
r
a
t
i
v
e
C
o
n
d
e
n
s
e
r
s
F61
...because temperature matters
Protection Against Basin Water Freezing
When a unit is shut down in freezing weather, the basin water must be protected by draining to an indoor
auxiliary remote sump tank (see page H5 for remote sump engineering data; page J16 for sizing guidelines)
or by providing supplementary heat to the cold water basin. Supplementary heat can be provided by electric
immersion heaters or in some cases, hot water or steam coils, or steam injectors. All exposed water piping,
make-up lines, and spray pumps (if applicable) that do not drain at shutdown should be traced with electric
heater tape and insulated.
When dry operation is planned for low ambient conditions, centrifugal fan units should be supplied with
oversized fan motors to prevent motor overload when the spray water is not operating. Dry operation with
standard fan motors is acceptable for axial fan units. For remote sump applications, the spray water pump
must be selected for the required flow at a total head which includes the vertical lift, pipe friction (in supply
and suction lines) plus the required pressure at the inlet header of the water distribution system (2.0 psi for
CXV models; 1.0 psi for Series V models). A valve should always be installed in the discharge line from the
pump to permit adjusting flow to the unit requirement. Inlet water pressure should be measured by a pressure
gauge installed in the water supply riser at the spray water inlet, and adjusted to the specified inlet pressure.
See page J17 for more information.
Indoor Installations (Applicable to Series V Models Only)
Many indoor installations require the use of inlet and/or discharge ductwork. Units installed with inlet
ductwork must be ordered with solid-bottom panels. Generally, intake ducts are used only on smaller
units while the equipment room is used as a plenum for larger units. Discharge ductwork will normally be
required to carry the saturated discharge air from the building.
Both intake and discharge ductwork must have access doors to allow servicing of the fan assembly, drift
eliminators, and water distribution system. All ductwork should be symmetrical and designed to provide even
air distribution across the face of air intakes and discharge openings.
WARNING:
The discharge opening must be positioned to prevent the introduction of discharge air into the fresh air
intakes serving the unit or the ventilation systems of adjacent buildings.
Note: Axial fan units are not suitable for indoor installations.
Safety
Adequate precautions, appropriate for the installation and location of these products, should be taken to
safeguard the public from possible injury and the equipment and the premises from damage. Operation,
maintenance and repair of this equipment should be undertaken only by personnel qualified to do so. Proper
care, procedures and tools must be used in handling, lifting, installing, operating, maintaining, and repairing
this equipment to prevent personal injury and/or property damage.
E
n
g
i
n
e
e
r
i
n
g
C
o
n
s
i
d
e
r
a
t
i
o
n
s
F62
Baltimore Aircoil Company
Code Requirement
Standard coils are ASME B31.5 compliant and are provided with a Canadian Registration Number (CRN)
when required. State or local codes, or certain applications may require the use of pressure vessels
designed, fabricated, tested and U stamped in accordance with the ASME Boiler and Pressure Vessel
Code, Section VIII, Division I. In such cases, the optional ASME U Stamp coil must be provided.
Purging
Air and other non-condensable gases collect in refrigeration systems from several sources: poor evacuation
prior to charging or after repairs; a leak into the system if pressures are below atmospheric; and chemical
breakdown of oil and/or refrigerant. If permitted to accumulate, non-condensables in the system cause high
condensing pressures and, therefore, increased power input to the compressors. Purging can be
accomplished during shut down, from the high point of the system, or during operation, from the top of the
condensing coil outlet and high pressure receiver.
Refer to the BAC Evaporative Condenser Engineering Manual for more detailed recommendations on piping
and purging.
Refrigerant Liquid Subcooling
The pressure at the expansion device feeding the evaporator(s) can be substantially lower than the receiver
pressure due to liquid line pressure losses. If the liquid line is long or the evaporator is above the receiver,
which further reduces the pressure at the expansion device, significant flashing can occur in the liquid line.
To avoid liquid line flashing where the above conditions exist, it is necessary to subcool the liquid refrigerant
after it leaves the receiver. The minimum amount of subcooling required is the temperature difference
between the condensing temperature and the saturation temperature corresponding to the pressure at the
expansion device. To determine the degree of subcooling required, it is necessary to calculate the liquid line
pressure drop including valves, ells, tees, strainers, etc., and add to it the pressure drop equivalent to the
static head loss between the receiver and the expansion device at the evaporator, if the evaporator is locat-
ed above the receiver.
Some compressor manufacturers publish their compressor ratings based on a fixed amount of subcooling at
the expansion device. Subcooled liquid at the expansion device of the evaporator does increase system
capacity since it increases the refrigeration effect per pound of refrigerant circulated. But the increase is
relatively small and seldom justifies the cost of the subcooling device and piping for this reason alone.
However, where compressor ratings based on subcooled liquid are used, the specified amount of subcooling
must be added to that required for liquid line pressure drop and static head loss.
E
v
a
p
o
r
a
t
i
v
e
C
o
n
d
e
n
s
e
r
s
F63
...because temperature matters
One method commonly used for supplying subcooled
liquid for halocarbon systems is to provide a
subcooling coil section in the evaporative condenser,
located below the condensing coil (see Figure 1).
Note: This option is available on Series V
Evaporative Condensers Only. Depending upon the
design wet-bulb temperature, condensing temperature,
and subcooling coil surface, these sections will
normally furnish 10F to 15F (5.6C to 8.3C) of liquid
cooling. However, to be effective, the subcooling coil
must be piped between the receiver and evaporator as
shown in Figure 1.
Note: Increasing the evaporative condenser size over the capacity required for the system will not
produce liquid subcooling. The increased condenser capacity will result only in lower operating
condensing temperatures. The same result will occur if the condensing coil is piped directly to the
subcooling coil.
Low temperature, multistage ammonia (R-717) refrigeration systems often use liquid subcooling between
stages for more economical operation. However, subcooling coils in an evaporative condenser are seldom,
if ever, used with an ammonia refrigeration system for several reasons:
1. Design condensing temperatures are generally lower with ammonia, thus limiting the amount of
subcooling that can be obtained.
2. The density of ammonia liquid is approximately 37 pounds per cubic foot, less than half that of the
normally used halocarbons, and static head losses are proportionately less.
3. The expansion devices and system designs normally used for ammonia systems are less sensitive to
small amounts of flash gas.
4. The high latent heat of ammonia (approximately 480 Btu/lb versus 70 Btu/lb for R-22) results in
comparatively small amounts of flash gas with a liquid line properly sized for low pressure drop.
Warranties
Please refer to the Limitation of Warranties applicable to and in effect at the time of the sale/purchase of
these products.
Figure 1
L
a
y
o
u
t
G
u
i
d
e
l
i
n
e
s
F64
Baltimore Aircoil Company
Layout Guidelines Available on the Web!
www.BaltimoreAircoil.com
Open cooling towers, closed circuit cooling towers, and evaporative condensers all depend upon an
adequate supply of fresh, ambient air to provide design capacity. The layout guidelines available at
www.BaltimoreAircoil.com provide minimum spacing requirements for each BAC evaporative cooling
product. Additional guidance is available through your local BAC Representative.
Layout guidelines include easy to read tables, formulas, and examples for the most common layout
configurations. If you have questions or encounter a layout not covered in these guidelines, please contact
your local BAC Representative for assistance.
T
h
e
r
m
a
l
S
t
o
r
a
g
e
P
r
o
d
u
c
t
s
ICE CHILLER
Thermal Storage Products
G1
Product Detail
Product Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .G2
Benefits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .G4
Proven Technology . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .G8
Construction Details . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .G12
Engineering Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .G14
Modular Coils . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .G15
Engineering Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . .G20
Engineering Considerations . . . . . . . . . . . . . . . . . . . . . . . . . . . .G21
I
C
E
C
H
I
L
L
E
R
G2
Baltimore Aircoil Company
Cooling with ice thermal storage can be the most cost-effective, reliable system approach to cooling offices,
schools, hospitals, malls and other buildings, and provides a steady source of low temperature fluids for
process cooling applications. These systems are environmentally friendly because they help lower energy
consumption and reduce greenhouse gas emissions. With thousands of successful installations worldwide,
BAC is the global leader in the application of ice thermal storage.
Ice Thermal Storage
Lowest first cost
Reduced energy cost
Variable capacity
Improved system reliability
Reduced maintenance
Environmentally friendly
Proven technology
ICE CHILLER
Thermal Storage Products
T
h
e
r
m
a
l
S
t
o
r
a
g
e
P
r
o
d
u
c
t
s
G3
...because temperature matters
I
C
E
C
H
I
L
L
E
R
G4
Baltimore Aircoil Company
Benefits
Lowest First Cost
Systems with ice thermal storage can be installed at the same or lower first cost than traditional sys-
tems when designed with the colder supply water available from ice. The savings that result from the
use of smaller chillers and cooling towers, reduced pump and pipe sizes and less connected
horsepower, offset the cost of the ice thermal storage equipment. Additional savings can be found
when using lower temperature air distribution, which allows reduced ductwork and fan sizes.
Smaller Chillers and Heat Rejection Equipment: By designing
the system around 24-hour per day chiller operation, the size of
the chillers and cooling towers or air-cooled condensers required
for an ice system is significantly reduced, when compared to
conventional chillers and heat rejection equipment sized for the
instantaneous peak load. A typical thermal storage design
includes chillers that provide 50 to 60% of the peak cooling load.
The balance of the cooling requirement is provided from the ice
storage system.
Reduced Pump and Pipe Sizes: Pump and pipe sizes are also
reduced in a properly designed ice storage system. Substantial
savings in the chilled water distribution loop are realized when the
system design incorporates reduced flow rates that result from
using a larger temperature range in the water loop. Use of a larger
temperature range, for example 18F (10C) instead of the more
traditional 10F (5.5C) temperature range results in a reduction of
pipe size. Condenser water pipe sizes are reduced due to lower
flow requirements for the smaller chiller. Pump savings due to
reduced chilled water and condenser water flow rates are also
realized.
Reduced Cooling Coil and Supply Air Fan Sizes: Cooling coils
sized using lower supply water temperatures and traditional supply
air temperatures are generally smaller due to fewer rows.
The reduction in rows leads to lower supply fan HP (kW).
Reduced Air Handling Equipment: When the air distribution is designed with lower supply air
temperatures, the size of the ductwork, fans and fan motors are reduced.
T
h
e
r
m
a
l
S
t
o
r
a
g
e
P
r
o
d
u
c
t
s
G5
...because temperature matters
Reduced Electrical Distribution: Smaller chillers, heat rejection equipment and pumps
require less horsepower than a traditional system, which results in smaller transformers,
switchgear, wire sizes and starter panels.
Reduced Generator Size: If a facility has a generator for daily or back-up power, the size of the
generator will be significantly reduced when the peak electrical load of the facility is reduced using
ice storage.
Reduced Energy Cost
An ice thermal storage system reduces peak demand, shifts energy usage to non-peak hours, saves
energy, and reduces energy costs.
Reduces Peak Demand and Shifts Energy Usage: With less connected horsepower, ice storage
can lower peak electrical demand for the HVAC or process cooling system by 50% or more. Since
most electrical rates include demand charges during peak demand times and/or higher day versus
night kWh charges, savings on electrical bills can be substantial. Peak electrical demand rates of
$15 to $18 per kW are not uncommon. In areas with real time pricing, where the electric rate
varies hour by hour based on the market price of electricity, day to night kWh costs can vary by
500 to 1000%. The use of electricity at night versus peak daytime hours can lead to large savings
on energy bills.
Saves Energy: In addition, total annual kilowatt-hours used are less when the system is designed
taking advantage of the low supply water temperature available from the ice storage system.
Lower kWh consumption is possible for five reasons:
1. Although making ice requires more energy than producing chilled water, the efficiency
penalty is not as large since the ice is made at night when condensing temperatures are
lower, increasing the efficiency of the chiller.
2. Ice systems typically operate the chiller at full load. Chillers are inefficient when run with
low loads during the spring and fall. A typical chiller will operate at less than 30% capacity
for half the year.
3. Reduced pumping horsepower.
4. Reduced fan horsepower due to lower air pressure drop across the cooling coil. A higher
chilled water temperature differential across the cooling coil usually results in fewer rows
and therefore a lower pressure drop.
5. The ability to recover waste heat from the chiller for heating water both night and day.
I
C
E
C
H
I
L
L
E
R
G6
Baltimore Aircoil Company
Benefits
Additional kWh savings are possible if the air distribution is
designed to take advantage of the low temperatures
available from the ice storage system. As the electric
industry continues to deregulate, and time-of-use rates, real
time pricing schedules and negotiated power prices become
standard, ice storage can provide even greater future
savings in operating costs.
Variable Capacity
The ice thermal storage system will maintain a constant supply
temperature regardless of the variations in instantaneous
cooling demand. The flow and entering water temperature set
the instantaneous capacity.
Improved System Reliability
Ice storage systems provide the reliability necessary to ensure
air-conditioning is available. With traditional systems, installing multiple chillers provides redundancy. In
the event of a mechanical failure of one chiller, the second chiller provides limited cooling capacity. The
maximum available cooling for the traditional system would only be 50% on a design day.
Most ice storage systems utilize two chillers in addition to the
ice storage equipment. Two chillers are designed to provide
approximately 60% of the required cooling on a design day
while the ice storage provides the remaining 40% of the
cooling capacity. In the event only one chiller is available to
provide cooling during the day, up to 70% of the cooling
capacity is available. The one operable chiller provides 30%
of the cooling requirement while the ice provides up to 40%.
Based on typical HVAC load profiles and ASHRAE weather
data, 70% of the cooling capacity would meet the total daily
cooling requirements 85% of the time.
T
h
e
r
m
a
l
S
t
o
r
a
g
e
P
r
o
d
u
c
t
s
G7
...because temperature matters
Reduced Maintenance
The ice thermal storage coils have no moving parts so very little maintenance is required. Because the
chillers, pumps and heat rejection equipment are smaller, ice storage systems will have less
maintenance than a traditional system. The ice thermal storage system also allows a chiller to undergo
routine maintenance during the day when the ice storage can handle the system load.
Environmentally Friendly
Reducing energy consumption and using electricity at night will reduce global warming. Electricity
generated at night generally has a lower heat rate (lower fuel use per power output), and therefore
lower carbon dioxide and greenhouse gas emissions resulting in less global warming. The California
Energy Commission concluded that the use of electricity at night created a 31% reduction in air
emissions over the use of electricity during the day.
With smaller chillers, an ice thermal storage system reduces the amount of refrigerant in a system. Most
refrigerants in use today are slated to be banned in the future under the Montreal Protocol because they
contribute to global warming. Using smaller amounts of refrigerant helps to save the ozone and reduce
global warming.
I
C
E
C
H
I
L
L
E
R
G8
Baltimore Aircoil Company
Proven Technology
BAC has successfully applied ice thermal storage technology to thousands of installations worldwide.
BAC has the application and system experience to assist you in the design, installation and operation
of your ice storage system. BAC has supplied ICE CHILLER
Thermal
Storage Coils are available for installation in field-erected tanks.
The BAC product offering provides system design flexibility. Ice can be built using various refrigerants
or glycols on steel coils and is used to provide either chilled water or glycol to the cooling system. This
flexibility, combined with a broad range of application experiences, allows BAC to provide a
cost-effective product to meet your specific requirements.
Merchandise Mart
In 1986 the Merchandise Mart in Chicago, Illinois installed
26,400 ton-hours (93.2 MWh) of ICE CHILLER
Thermal
Storage Coils in a retrofit of the buildings air-conditioning
system. The Merchandise Mart was built in 1930. The
increased air-conditioning load on the building from
computers, other electrical equipment and increased
people density made the old system too small. Ice thermal
storage with the low temperature water available allowed
the retrofit of the air-conditioning system to go ahead
without replacing piping and ductwork. Increasing the temperature ranges on the piping and air
distribution system allowed the Merchandise Mart to install an ice thermal storage system at a lower
first cost than a conventional system.
T
h
e
r
m
a
l
S
t
o
r
a
g
e
P
r
o
d
u
c
t
s
G9
...because temperature matters
Friendship Annex 3 Office Building
The HVAC renovation of Friendship Annex (FANX) 2 and 3 in Baltimore, MD received the 1994
Outstanding Engineering Achievement of the Year Award from the Engineering Society of Baltimore.
Ice with low temperature air distribution cools these buildings renovated in 1994. To meet federal
guidelines, a comprehensive study of five alternate systems was made using life cycle costing. The
analysis showed ice storage with low temperature chilled water and low temperature air to be the most
economical system. A total of 15,230 ton hours (53.8 MWh) of ICE CHILLER
G10
Baltimore Aircoil Company
Proven Technology
Low Temperature Air
Omni Interlocken Resort
Hotel
The Omni Interlocken Resort Hotel just
outside of Denver, CO was designed
with a low temperature air and water
system using ICE CHILLER
Thermal
Storage Units. The challenge was to
design a high-quality HVAC system
sensitive to building aesthetics, which
would provide good guest comfort, low
operating/maintenance costs and could
be constructed within a tight
construction budget. The first
conceptual design was a four-pipe
fan-coil system for the hotel rooms with air-cooled chillers and rooftop air-handler units for the public
spaces. The final design was a low temperature air system with Modular ICE CHILLER
Thermal
Storage Units. This low temperature air system was $500,000 less than the original conceptual
design. In addition the hotels energy bills are $100,000 less than with a conventional system.
Villa Julie College
Modular ICE CHILLER
Thermal Storage
Unit to provide back-up cooling to one of their computer
centers in Silver Spring, MD. If the chiller that provides
cooling goes down for any reason, power outage or alarm,
the system immediately switches over to the ice thermal
storage system for cooling. The pump on the ice thermal
storage system is on the continuous power back up with the
computers. There is enough ice to provide cooling for 30 minutes. This gives Verizon enough time to
clear the alarm or get the back-up generator running and the chiller back on line.
I
C
E
C
H
I
L
L
E
R
G12
Baltimore Aircoil Company
Construction Details
1
2
3
4
5
6
7
8
9
11
T
h
e
r
m
a
l
S
t
o
r
a
g
e
P
r
o
d
u
c
t
s
G13
...because temperature matters
Covers
Watertight
G-235 (Z700 Metric) Hot-dip
galvanized steel panels
Insulated with 2 expanded
polystyrene insulation
Coil Support Beams
Prevent contact between coil and
primary liner
Glycol Connections
Victaulic connections
Galvanized Steel Coil
Hot-dip galvanized after fabrication
(HDGAF)
Continuous serpentine, steel tubing
Pneumatically tested at 190 psig
Rated for 150 psig operating pressure
Primary Liner
Single piece
48-hour integrity test before shipment
Extruded Polystyrene
Insulation
1.5 thick, installed between primary and
secondary liners
Contributes to total insulating value of R-18
Secondary Liner/Vapor
Barrier
Prevents moisture from penetrating through
the insulation
Wall Panel
Heavy-gauge galvanized steel with double
brake flanges
3 of expanded polystyrene insulation
Contributes to total insulating value of R-18
Sight Tube
Visual indicator of the amount of ice
remaining in unit
Operating Control
(Not Shown)
High-level float switch and low water cutout
mounted on the outside of the tank
Can be provided for one tank (standard) or
all tanks (optional)
Ice Inventory Sensor
(Optional)
Differential pressure transmitter provides an
electrical 4-20 mA output signal which is
proportional to the amount of ice in
inventory
1
2
3
4
5
6
7
8
9
10
11
I
C
E
C
H
I
L
L
E
R
G14
Baltimore Aircoil Company
Do not use for construction. Refer to factory certified dimensions. This brochure includes data current
at time of publication, which should be reconfirmed at the time of purchase. Up-to-date engineering data
and more can be found at www.BaltimoreAircoil.com.
Engineering Data
Contact your local BAC Sales
Representative for selection
assistance.
PERCENT ICE BUILD
OVER FLOW
100 %
75 %
50 %
25 %
0 %
Notes:
1. Unit should be continuously supported on a flat level surface.
2. All connections are grooved for mechanical coupling.
MODEL
NUMBER OPERATING SHIPPING TANK WATER COIL GLYCOL L W
TSU-237M 39,100 9,750 2,990 260 10' 7-5/8" 7' 10-3/8" 2"
TSU-476M 73,900 16,750 5,840 495 19' 10-1/4" 7' 10-3/8" 3"
TSU-594M 93,100 20,200 7,460 610 19' 10-1/4" 9' 9-1/4" 3"
TSU-761M 113,800 24,000 9,150 790 19' 10-1/4" 11' 9-3/4" 3"
CONNECTION
SIZE
WEIGHTS (lbs) DIMENSIONS VOLUMES (lbs)
T
h
e
r
m
a
l
S
t
o
r
a
g
e
P
r
o
d
u
c
t
s
G15
...because temperature matters
Custom Coils
BAC will manufacture custom ICE CHILLER
Thermal Storage Coils are constructed of continuous 1.05" O.D. all prime surface
serpentine steel tubing, with no intermediate butt welds. The coils are assembled in a structural steel
frame designed to support the weight of the coil stack with a full ice build. After fabrication the coils are
tested for leaks using 375 psig air pressure under water, then hot-dip galvanized for corrosion
protection.
For glycol applications the coils are configured to provide countercurrent glycol flow in adjacent circuits
for maximum storage capacity.
Individual coils are factory-assembled into modules of two (2) coils. Glycol manifolds are coated with
zinc-rich, cold galvanizing finish at the factory. Necessary support steel and lifting lugs are provided on
the modules to allow for lifting into and final positioning within the storage tank.
Note: Engineering data continued on next page.
Installation of coil module at Oriole Park at Camden Yards, Baltimore, MD
I
C
E
C
H
I
L
L
E
R
G16
Baltimore Aircoil Company
The modular ICE CHILLER
Thermal Storage Unit can operate in any of five distinct operating modes.
These modes of operation provide the flexibility required by building operators to meet their daily HVAC
cooling requirements.
Ice Build
In this operating mode, ice is built by circulating a 25% solution (by weight) of inhibited ethylene/
propylene glycol through the coils contained in the ICE CHILLER
G18
Baltimore Aircoil Company
Engineering Data:
System Schematics
Two basic flow schematics are applied to select
ICE CHILLER
G20
Baltimore Aircoil Company
The ICE CHILLER
SR-1 and
UCARTHERM
Thermal
Storage Units.
For large tonhour applications, BAC will provide ICE CHILLER
Thermal Storage Coil layout guidelines. For large projects that require ICE CHILLER
Coils,
contact your local BAC Representative for selection and dimensional information.
Figure 1
Figure 3 Figure 2
E
n
g
i
n
e
e
r
i
n
g
C
o
n
s
i
d
e
r
a
t
i
o
n
s
G22
Baltimore Aircoil Company
Unit Piping
Piping to the ICE CHILLER
Thermal Storage Unit should follow established piping guidelines. The coil
connections on the unit are galvanized steel and are grooved for mechanical coupling.
For single tank applications, each pair of manifolded
coil connections should include a shut off valve so
the unit can be isolated from the system. Figure 4
illustrates the valve arrangement for a single unit. It is
recommended that the piping include a bypass circuit
to allow operation of the system without the ICE
CHILLER
Thermal
Storage Units are installed, the system should be
divided into groups of units. Then, balancing of each
unit can be eliminated and a common balancing
valve for each group of units installed. Shut off valves
for isolating individual units should be installed but
not used for balancing glycol flow to the unit.
Figure 4
Figure 5
T
h
e
r
m
a
l
S
t
o
r
a
g
e
P
r
o
d
u
c
t
s
G23
...because temperature matters
Controls
To ensure efficient operation of the ICE CHILLER
Thermal Storage Units are fully charged. When the units are fully
charged, the chiller should be turned off and not allowed to re-start until cooling is required. The ice build
cycle is terminated by the Operating Control Assembly. This assembly includes a low water cutout and a
shut-off switch. The low water cutout prevents the ice build mode from starting if there is insufficient water in
the tank. The shutoff switch will terminate the build cycle when the units are fully charged and will prevent
the next ice build mode from starting until 15% of the ice has melted.
Note: Multiple Operating Control Assemblies must be wired in series so that a full build signal from
any one tank will terminate the ice build cyle.
An inventory control that provides a 4 - 20 mA signal is available. This control should be used for
determining the amount of ice in inventory but not to terminate the ice build cycle. Complete operating
control details are provided in the Installation, Operation and Maintenance Manual.
Glycol
ICE CHILLER
Thermal Storage Units typically use a 25% (by weight) solution of industrially inhibited
ethylene/propylene glycol for both corrosion protection and freeze protection. Industrial grade inhibited glycol
is specifically designed to prevent corrosion in HVAC and heat transfer equipment. Inhibitors are used to
prevent the ethylene glycol from becoming acidic and to protect the metal components in the thermal
storage system. The systems lowest operating temperature should be 5F to 7F (2.8C to 3.9C) above the
glycol freeze point. The freeze point for a system with 25% by weight ethylene glycol is 13F (10.6C); the
freeze point for a system with 25% by weight propylene glycol is 15F (9.4C).
Acceptable industrial grade inhibited glycol solutions are DOWTHERM
SR1, DOWFROST
HD and
UCARTHERM
SR-1, DOWFROST
and UCARTHERM
Thermal
Storage Unit, the water treatment should not alter the freeze point of water.
Winterization
CAUTION:
Precautions must be taken to protect the unit and associated piping from freezing conditions. Heat
tracing and insulation should be installed on all piping connected to the unit. The sight tube,
operating controls and optional inventory sensor must be protected if the units are installed
outdoors and exposed to sub-freezing ambient conditions.
For this purpose, BAC can provide an optional heated enclosure, complete with a 100 W heater.
Otherwise, the sight tube, operating controls and optional inventory sensor must be heat traced and
insulated. It is not necessary to drain the unit during cold weather.
PROPERTY OF WATER RANGE
pH 7.0 to 9.0
1
Hardness as CaCO3 30 to 500 ppm
Alkalinity as CaCO3 500 ppm maximum
Total Dissolved Solids 625 ppm maximum
Maximum Conductivity 1000 micromhos/cm @ 32F
Chlorides 125 ppm maximum as Cl
Sulfates 125 ppm maximum
T
h
e
r
m
a
l
S
t
o
r
a
g
e
P
r
o
d
u
c
t
s
G25
...because temperature matters
Pressure Drop
The ICE CHILLER
Thermal Storage Unit is designed for low pressure drop. Figure 6 shows the pressure
drop associated with each unit for a 25% solution of industrially inhibited ethylene glycol. Data for flow rates
not shown should not be extrapolated from the performance curve. Pressure drops for flow rates not
presented in this table and for alternative fluids, are available by contacting the local BAC Representative.
Warranties
Please refer to the Limitation of Warranties applicable to and in effect at the time of the sale/purchase of
these products.
Figure 6
R
e
m
o
t
e
S
u
m
p
T
a
n
k
s
RS
Remote Sump Tanks
H1
Product Detail
Product Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .H2
Benefits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .H3
Custom Features and Options . . . . . . . . . . . . . . . . . . . . . . . . . . .H4
Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .H4
Engineering Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .H5
Structural Support . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .H6
Engineering Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .H7
R
e
m
o
t
e
S
u
m
p
T
a
n
k
s
H2
...because temperature matters
RS Remote Sump Tanks
Single Tank Capacity:
94 1,390 US Gallons (Maximum Storage Volume)
Remote sump tanks can be added to cooling tower, closed circuit cooling tower, or evaporative condenser
systems. Remote sumps are often installed indoors in a heated space to prevent freezing of the recirculating
water during cold weather operation. Because the recirculating water is quickly drained from the unit when the
pump is shut off, the indoor remote sump tank eliminates the need for other methods of freeze protection such
as cold water basin heaters, hot water coils, or steam coils. Remote sump tanks are also used to simplify water
treatment for multiple cell installations by providing a single location for monitoring water quality. Remote sump
tanks also facilitate dry operation of closed circuit cooling towers and evaporative condensers by eliminating
the need to drain the cold water basin when switching from wet to dry operation. BACs RS Remote Sump
Tanks are available in a variety of sizes in galvanized steel or the BALTIBOND
Corrosion Protection
System (see next page for construction options).
The water level control is easily reached from outside the unit.
R
e
m
o
t
e
S
u
m
p
T
a
n
k
s
H4
...because temperature matters
Construction Options
Standard Construction:
Steel panels and structural elements are constructed of heavy-gauge G-235 hot-dip galvanized steel.
Optional BALTIBOND
Corrosion Protection System. The system shall consist of G-235 (Z700 metric)
hot-dip galvanized steel prepared in a four-step (clean, pre-treat, rinse, dry) process with an electrostatically sprayed, thermosetting
hybrid polymer fuse-bonded to the substrate during a thermally activated curing stage and monitored by a 23-step quality assurance
program. Panel design shall be flanged and gasketed.
2.0 Construction Details
2.1 Strainer: A large area, lift-out, hot-dip galvanized steel strainer with perforated openings and an integral anti-vortexing hood to
prevent air treatment shall be provided.
2.2 Make-up Assembly: A brass make-up valve with a large diameter, unsinkable plastic float arranged for easy adjustment shall
be provided.
Engineering Specifications
T
e
c
h
n
i
c
a
l
R
e
s
o
u
r
c
e
s
Technical Resources
J1
Connection Guide . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .J2
Materials of Construction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .J4
Selection Software . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .J6
CTI Certification . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .J8
The Value of Standards and Independent Certification Programs . .J10
Selection of a Remote Sump Tank for an Open Cooling Tower . . . . .J12
Selection of a Remote Sump Tank for a Closed Circuit
Cooling Tower or Evaporative Condenser . . . . . . . . . . . . . . . . . . . . . . .J16
Fundamentals of Sound . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .J20
Piping Considerations - Maximum Fluid Velocity . . . . . . . . . . . . . . . .J55
Cooling Tower Pumping & Piping . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .J56
Friction Loss Table . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .J101
Wet-Bulb Temperature Selection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .J102
Conversion Factors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .J113
Formulas & Tables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .J114
Psychrometric Chart . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .J115
Temperature Conversion Chart . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .J118
Spare Parts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .J119
Water Quality Guidelines . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .J120
Maintenance Check List . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .J122
Glossary . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .J125
Resources Index
C
o
n
n
e
c
t
i
o
n
G
u
i
d
e
J2
Baltimore Aircoil Company
Connection Guide
A summary of connection types used by BAC follows. The specific connection type for a particular BAC
model can be found on the unit print drawing (available on BACs website) or from your local BAC
Representative.
Beveled for Welding (BFW):
This connection type is a pipe stub with a
beveled edge. The bevel allows for
easier welding in the field and a full
penetration weld. Weld materials fill the
trimmed area between two beveled edges
as shown here.
Grooved to Suit a Mechanical Coupling:
This connection type is a pipe stub with a groove to accept
a mechanical pipe coupler.
BFW/Grooved:
Many of BACs connections are both beveled for weld and
grooved to suit a mechanical coupling. Either method of
fastening to field-fabricated piping can be used when this
connection type is provided.
ASME Class 150 Flat Face Flange:
This connection type is a standard bolt and hole
pattern at the point of connection to mate to an
ASME Class 150 Flat Face Flange. When BAC
provides this connection type to a hot water basin,
mounting bolts are permanently fastened to the
connection plate. When BAC provides this connec-
tion type from a cold water basin, a back-up ring
and neoprene washers are provided. All other
components (piping, nuts, bolts, flatwashers, etc.)
are provided by others unless otherwise specified.
Weld Details
BFW/Grooved Connection
Beveled edge of
field-installed piping
Beveled edge of
BAC connection
Beveled edge
Grooved for
mechanical coupling
Weld Material
An ASME Class 150 Flat Face Flange pattern is
shown on this cold water basin panel
T
e
c
h
n
i
c
a
l
R
e
s
o
u
r
c
e
s
J3
...because temperature matters
An ASME Class 150 Flat Face Flange pattern with mounting bolts is
shown on this hot water basin panel
Male Pipe Thread (MPT):
This connection type is a threaded pipe
stub connection designed to mate with
a Female Pipe Thread (FPT) fitting.
Side Outlet Depressed Sump Box:
This option is offered to facilitate
horizontal piping below the cold water
basin of a unit, and is a compact
alternative to using an elbow in the
piping arrangement, saving installation
time and cost.
MPT Connection
Side Outlet Depressed Sump Box
M
a
t
e
r
i
a
l
s
o
f
C
o
n
s
t
r
u
c
t
i
o
n
J4
Baltimore Aircoil Company
Materials of Construction
Operating environment, desired life expectancy, and budget all influence the materials of construction
selected for an evaporative cooling unit. BAC products are available in a variety of materials and BAC
designs focus on long life and easy maintenance. As a result, owners can maximize their operational goals.
This section describes the materials of construction available for BAC products. To determine the best
material options for your specific project, consult your local BAC Representative.
Galvanized Steel
G-235 hot-dip galvanized steel is the heaviest commercially available galvanized steel, universally
recognized for its strength and corrosion resistance. To assure long-life, G-235 hot-dip galvanized steel is
used as the base material for all steel products and parts, and all exposed cut edges are protected with a
zinc-rich coating after fabrication. With good maintenance and proper water treatment, G-235 galvanized
steel products will provide excellent service life under the operating conditions normally encountered in
comfort cooling and industrial applications.
BALTIBOND
Corrosion Protection System can extend the service life of equipment and alleviates
concerns with white rust, virtually eliminating the need for periodic passivation of galvanized steel
components.
Fused Bonded Thermosetting Polymer
Zinc
Steel
Zinc
Fused Bonded Thermosetting Polymer
T
e
c
h
n
i
c
a
l
R
e
s
o
u
r
c
e
s
J5
...because temperature matters
Stainless Steel
Type 304 stainless steel is the industrys traditional alternative to galvanized steel when elevated levels of
corrosion resistance are required. It is the most widely used and accepted type of stainless steel available on
the market today. Type 304 stainless steel materials can be provided in lieu of standard materials for unit
structure, as well as many auxiliary components.
Component Construction
In addition to the various materials available for the structure of its units, BAC carefully selects the materials
used for all components of its products. Additional materials such as corrosion resistant fiberglass reinforced
polyester (FRP), polyvinyl chloride (PVC), aluminum and copper are used for components when necessary to
provide the corrosion resistance required of a unit providing evaporative cooling service.
Which material option is right for my project?
Included within the product section of each open cooling tower, closed circuit cooling tower and evaporative
condenser in this catalog is a discussion on construction options. These sections define the availability of
certain materials and combinations of materials for each product. Refer to these sections for specific product
information. Your local BAC Sales Representative can guide you on the proper unit construction for your
specific project.
HXV shown with optional BALTIBOND
Corrosion
Protection System
S
e
l
e
c
t
i
o
n
S
o
f
t
w
a
r
e
J6
Baltimore Aircoil Company
Selection Software
Easy-To-Use Selection Software
BAC offers free, easy-to-use selection software to assist you in the selection and evaluation of evaporative
cooling products. In addition to catalog models, CTI certified alternate-horsepower selections are also
available from the selection software. The program provides equipment specifications, engineering data,
performance curves, layout recommendations, sound data and other information to aid in selecting the best
BAC product for your application.
Cooling Tower Selections
All cooling tower models in the selection program are
included in the CTI thermal performance certification
program. The selection program also provides the ability
to make selections outside the scope of CTI thermal
performance certification program criteria. BAC warrants
the thermal performance of all cooling tower selections
made by the selection program, whether or not under the
scope of the certification program.
Product selections often contain reserve capacity at the
design conditions. The selection program can optimize the performance of a unit at specified conditions.
Select a unit for design conditions, and then you can maximize flow rate, hot and cold water temperatures,
wet bulb temperature or approach.
Closed Circuit Cooling Tower Selections
The closed circuit cooling tower selection program provides equipment selections for applications utilizing
water, aqueous ethylene glycol or aqueous propylene glycol as the process fluid. As with open circuit cooling
towers, all models are CTI Certified.
Evaporative Condenser Selections
The evaporative condenser selection program provides equipment selections for applications utilizing R-717
(ammonia), R-22, and R-134a.
Accessories
The selection program evaluates the use of accessories that may impact capacity (i.e., low-sound fans,
sound attenuation, etc.)
T
e
c
h
n
i
c
a
l
R
e
s
o
u
r
c
e
s
J7
...because temperature matters
Alternative Motors
Standard selections utilize a standard horsepower motor to meet the full load performance required for the
project. Alternative selections based on a reduced speed provided by the ENERGY-MISER
Fan System, a
2-speed motor or a variable frequency drive are also available.
Performance Curves
The selection program generates performance curves
based on flow rates ranging from 80% to 120% of the
design flow rate. Performance curves are a graphical
representation of the leaving water temperature versus the
entering wet-bulb temperature, and are typically evaluated
at a number of ranges.
Sound Data
The selection program provides sound ratings for standard selections at 5 and 50-foot distances for your
reference. For extremely sound sensitive installations, sound ratings are also available for units with
low sound fans and sound attenuation.
Website
The BAC selection software is available from our website,
www.BaltimoreAircoil.com. Direct links to the website
within the program provide users of the selection program
with additional information pertaining to Unit Engineering
Data, Certified Unit Drawings, Layout Guidelines and
Specifications. Consult your local BAC Representative for
additional application assistance.
Performance curves from the Cooling
Tower Selection Program
C
T
I
C
e
r
t
i
f
i
c
a
t
i
o
n
J8
Baltimore Aircoil Company
Cooling Technology Institute
(CTI) Certification
Independent Assurance of Thermal
Performance In Advance
For over two decades, cooling tower owners, operators, design
engineers and installing contractors have relied upon CTI certification of
cooling tower thermal performance in accordance with CTI Standard
STD-201. CTI Certification provides independent assurance, prior to
shipment and installation, that a specific cooling tower will perform in
accordance with the manufacturers published thermal performance data.
Having CTI certification in advance eliminates the need for costly onsite
field tests and ensures system performance will meet design objectives.
BAC Commitment to CTI Certification
BAC is committed to providing independent thermal performance verification for all its products. Starting with
the FXT Cooling Tower line in 1981, every factory assembled BAC cooling tower line since (including the
Series 3000 in 1984, the Series V in 1986, the Low Profile Series V in 1988, and the Series 1500 in 1994)
has achieved CTI certification.
CTI Certification For Closed Circuit Cooling Towers
More recently, CTI Standard STD-201 was expanded to include closed circuit cooling towers. Once again
BAC has led the industry, certifying the thermal performance of the FXV Closed Circuit Cooling Tower line in
1998 and the Series V Closed Circuit Cooling Tower line in 2000. Dual air inlet FXV models were added in
2003, with the largest capacity of any factory-assembled closed circuit cooling tower cell in the industry. BAC
Closed Circuit Cooling Towers can be specified with the same assurance of thermal performance as our
open circuit cooling towers.
Why is CTI Certification Important to You?
Equipment Owners and Operators
Independent certification of cooling tower thermal performance assures owners and operators that they will
receive full value from their investment. It eliminates the potential for years of excessive operating costs due
to deficient equipment and provides this benefit at no cost to the project. In fact, performance certification
can actually reduce first cost by eliminating the need for safety factors when sizing the equipment and the
cost of a field acceptance test to verify performance.
T
e
c
h
n
i
c
a
l
R
e
s
o
u
r
c
e
s
J9
...because temperature matters
Design Engineers
By specifying CTI certification of thermal performance, a design engineer can protect the owner and ensure
that his or her client receives the performance paid for. CTI performance certification provides a responsible
basis for design and complements codes and standards used to control other systems and products. Many
industry organizations are working to include certification in their standards. For instance, California Title 24
will require CTI certification of all cooling towers starting in 2005. CTI certification complies with these codes,
prevents involvement in contractual misunderstandings, and eliminates disputes over deficient performance
after installation.
Installing Contractors
Independent certification of cooling tower thermal performance assures the installing contractor that all
certified cooling tower proposals are based on the same level of thermal performance. This not only
eliminates the potential for costly callbacks due to deficient thermal performance but also maintains a
responsible basis of design for design/build, design/assist, or value-engineered projects.
The Cost of Cooling Tower Deficiency
While sometimes hard to detect, a deficient cooling tower forces other system components to work harder to
make up for its shortcomings. In an air conditioning application, this burden is imposed upon the chiller. If the
cooling tower cannot reject the required load at the lowest possible temperatures, the chiller is forced to
operate against a condensing pressure higher than necessary, thereby consuming considerably more energy.
This may not affect building comfort levels except at peak conditions, but it will increase operating costs
year-round. A tower that is 20% underrated will cost the owner three to four times the original price of the
tower in added energy costs! Why take a chance insist on CTI certified performance!
Specify CTI Certification for ALL of
Your Cooling Tower Needs
The equipment sections of this catalog include
suggested specifications for each product. When
adding verbiage to an existing specification,
suggested wording is as follows:
The thermal performance shall be certified by the
Cooling Technology Institute in accordance with CTI
Standard STD-201 or, lacking such certification, a
field acceptance test shall be conducted within the
warranty period in accordance with CTI Acceptance
Test Code ATC-105, by the Cooling Technology
Institute, or other qualified independent third-party
testing agency, licensed by CTI. Tests performed by
the manufacturers personnel will not be acceptable.
Performance testing in BACs R&D facility
T
h
e
V
a
l
u
e
o
f
S
t
a
n
d
a
r
d
s
J10
Baltimore Aircoil Company
The Value of Standards and
Independent Certification Programs
Baltimore Aircoil Company strongly believes in the value of standards and independent certification
programs. Through this philosophy, customers can be assured of a consistent level of performance and
quality when using BAC products and services. These standards and certification programs cover many
diverse areas, ranging from how product improvements are implemented in BACs factories to how BAC
products are rated for thermal performance.
This fundamental belief is demonstrated first and foremost by ISO 9001:2000 Certification of BACs design,
engineering, and manufacturing of evaporative cooling products. Compliance with ISO 9001:2000
standards offers BAC customers better, more consistent quality, reliable
performance, and confidence that the product can be delivered on time
and per the specifications. Consistent quality also reduces the potential
for installation and operational problems. Any problems reported from
the field receive swift corrective and preventative actions to prevent
reoccurrence. This level of performance is assured through frequent
internal training and audits, backed by rigorous external audits by an
independent, ISO-accredited Registrar. ISO 9001:2000 also requires demonstrating continuous
improvement of products, processes, and systems over time, benefiting both BAC and its many customers.
BAC is also fervently committed to providing independent thermal
performance verification for all its products. BAC leads the industry with
nine product lines, including both open and closed circuit cooling towers,
currently registered with the Cooling Technology Institute (CTI), more than
any other manufacturer. Independent certification by the CTI assures
owners, operators, consulting engineers, and installing contractors that
BAC units will perform in accordance with published thermal performance
ratings.
Owners and operators can realize the full value of their investment in their cooling system, and avoid the
operating cost penalties associated with a deficient tower. System design engineers can reduce or eliminate
safety factors and avoid the need to specify costly field performance tests, while minimizing their liability.
Contractors can compare equipment based on features and benefits, rather than questioning whether all the
proposals are based on the same true level of thermal performance. CTI certification also reduces the
potential for costly callbacks due to deficient performance. Leveling the playing field also advances the
state of the industry: manufacturers must devote their energies towards product improvement to gain true
competitive advantage. Users of evaporative cooling equipment benefit from this true competition with
innovative new products, features, and service options.
T
e
c
h
n
i
c
a
l
R
e
s
o
u
r
c
e
s
J11
...because temperature matters
The design of BAC products is also influenced by many other standards. Examples include the following:
All access platforms, ladder systems, and handrail packages are designed and manufactured to meet
or exceed OSHA standards.
Evaporative cooling equipment with Factory Mutual (FM) Approval is available where required to help
reduce insurance premiums and potentially eliminate the need for fire suppression sprinkler systems.
The standard heat transfer coils used in BAC evaporative condensers and closed circuit cooling towers
comply with the ASME B31.5 Refrigeration Piping and Heat Transfer Component Standard. This
standard assures the user of the pressure integrity, material composition, engineering design, and
fabrication techniques used for the heat exchange coils. When required by local codes or the specific
needs of a project, BAC can also produce coils with the ASME U stamp per Section VIII, Division 1 of
the ASME Boiler & Pressure Vessel Code.
Compliance with these codes and standards help to assure BAC customers that the unit they purchase is
suitable for the duty required.
Besides supporting these standards, BAC actively works with industry organizations, such as ASHRAE,
ASME, ARI, CTI, and FM to improve their standards, or develop standards where none currently exist. For
instance, BAC led the industry by working with CTI to update the certification standard in the early 1980s,
and led the way by certifying the first factory assembled cooling tower product line under this updated
standard. BAC is also currently working with both CTI and ARI on developing standards for evaporative
condenser thermal performance, as well as keeping current standards up-to-date. Additionally, BAC actively
participated on the ASME B31.5 Piping Committee to integrate heat transfer components, such as
evaporative condensers and closed circuit cooling towers, within the standard.
BAC strongly encourages our customers, suppliers, and
competitors to join us in developing and supporting these
standards and certification programs for the benefit of the
industry and society as a whole. BAC welcomes feedback on
this subject, which can be sent to info@baltimoreaircoil.com.
R
e
m
o
t
e
S
u
m
p
T
a
n
k
-
S
e
l
e
c
t
i
o
n
J12
Baltimore Aircoil Company
Selection of a Remote Sump Tank for an
Open Cooling Tower
Note: This section provides a simplified method for the selection of a remote sump tank for an open cooling
tower only. For information on sizing a remote sump tank for a closed circuit cooling tower or evaporative
condenser, see page J16.
Remote sump tanks are used on evaporative cooling systems to provide a means of cold water basin freeze
protection during cold weather operation. The remote sump tank is usually located in a heated, indoor
space, and may preclude the need to winterize the evaporative cooling equipment. A remote sump tank
must provide sufficient storage volume to accommodate all the water that will drain back to it during cooling
system shutdown, including:
The total volume of water contained within the cooling tower during operation (cooling tower volume).
The volume of water contained in all system piping located above the operating water level of the
remote sump tank (system piping volume).
The volume of water contained within any heat exchanger, or other equipment located above the
operating water level of the remote sump tank that will drain to the tank when the cooling system is
shut down (system components volume).
The maximum volume of water contained within the cooling tower is the volume of water to the overflow
level. Besides the water in the cold water basin during operation, this volume will take into consideration
water in the distribution system, water in suspension in the wet deck, plus an allowance for the external
pulldown from piping and other equipment. This simplified method is a conservative approach as it will not
consider any volume reductions based on flow rates. For specific information for your application, contact
your local BAC Representative.
Cold water basin volumes at the overflow level are given in Tables 1 through 4. Table 5 provides pipe
capacities (gallons per linear foot) for common Schedule 40 nominal pipe sizes, useful when determining
system piping volume.
Safety Factor
When selecting a remote sump tank, select a model with a net available volume that is 5% greater than the
total volume required. The net available volume is the volume between the operating level and the overflow
level in the remote sump tank. See page H5 for engineering data (including net available volume) on BACs
RS Remote Sump Tanks. The minimum operating level must be maintained in the remote sump tank to
prevent vortexing of air through the tank's suction connection.
T
e
c
h
n
i
c
a
l
R
e
s
o
u
r
c
e
s
J13
...because temperature matters
Table 1. Series 3000 - Cold Water Basin Volume at Overflow
Table 2. Series 1500 - Cold Water Basin Volume at Overflow
Model Number Overflow Volume (gallons)
3240A thru 3290A 958
3333A thru 3379A 1,019
3412A thru 3436A 1,219
3455A thru 3527A 1,289
3473A thru 3501A 1,549
3552A thru 3672A 1,787
3728A thru 3828A 2,196
3872A thru 3970A 2,465
3985A thru 31056A 2,674
3583A thru 3725A 2,237
31132A 2,963
31213A thru 31301A 3,211
Model
Number
Flow Range
(gpm)
Overflow Volume
(gallons)
up to 440 425
441-600 450
601-745 475
up to 480 425
481-650 450
651-815 475
up to 530 425
531-710 450
711-895 475
up to 490 450
491-650 485
651-805 530
up to 535 470
536-710 497
711-880 530
up to 605 480
606-800 500
801-1000 530
up to 660 485
661-870 510
871-1085 530
up to 600 540
601-780 630
781-960 725
up to 685 560
686-885 645
886-1085 725
up to 750 580
751-970 655
971-1190 725
up to 645 575
646-840 700
841-1035 815
up to 735 605
736-960 710
961-1180 815
15227
15250
15214
15245
15177
15201
15219
15200
15146
15160
15176
15162
Model
Number
Flow Range
(gpm)
Overflow Volume
(gallons)
up to 810 625
811-1050 720
1051-1295 815
up to 850 640
851-1100 725
1101-1350 815
up to 890 755
891-1160 890
1161-1425 1,050
up to 975 755
976-1270 905
1271-1560 1,050
up to 1050 790
1051-1360 925
1361-1675 1,050
up to 1105 805
1106-1435 930
1436-1760 1,050
up to 960 790
931-1215 990
1216-1500 1,200
up to 1020 820
1021-1335 1,010
1336-1645 1,200
up to 1095 840
1096-1430 1,020
1431-1760 1,200
up to 1155 855
1156-1505 1,025
1506-1855 1,200
up to 1275 890
1276-1660 1,045
1661-2045 1,200
15270
15282
15296
15325
15365
15385
15425
15350
15368
15310
15340
R
e
m
o
t
e
S
u
m
p
T
a
n
k
-
S
e
l
e
c
t
i
o
n
J14
Baltimore Aircoil Company
Table 3. FXT - Cold Water Basin Volume at Overflow
Model Number Overflow Volume (gallons)
FXT-6 thru FXT-7.5 63
FXT-11 98
FXT-16 thru FXT-20 73
FXT-26 thru FXT-33 113
FXT-38 thru FXT-47 146
FXT-58 thru FXT-68 197
FXT-74 thru FXT-99 273
FXT-115 thru FXT-142 420
FXT-160 thru FXT-200 558
FXT-216 thru FXT-268 666
Model Number Overflow Volume (gallons)
VTL-016-E thru VTL-039-H 72
VTL-045-H thru VTL- 079-K 146
VTL-082-K thru VTL-095-K 215
VTL-103-K thru VTL-137-M 287
VTL-152-M thru VTL- 227-O 432
VTL-245-P thru VTL- 272-P 574
VT0-12-E thru VT0-28-H 26
VT0-32-H thru VT0-57-K 55
VT0-65-J thru VT0-88-L 85
VT0-102-L thru VT0-116-M 114
VT0-132-L thru VT0-176-O 153
VT1-N209-P thru VT1-N270-Q 488
VT1-N301-Q thru VT1-N395-R 742
VT1-N418-P thru VT1-N540-Q 994
VT1-275-P thru VT1-415-R 900
VT1-416-O thru VT1-600-P 1,367
VT1-550-P thru VT1-830-R 1,832
VT1-825-P thru VT1-1335-S 2,764
Table 4. Series V - Cold Water Basin Volume at Overflow
T
e
c
h
n
i
c
a
l
R
e
s
o
u
r
c
e
s
J15
...because temperature matters
Example
A VTL-059-H will be installed on a cooling tower/heat exchanger system that will also utilize an RS Remote
Sump Tank. The tower side volume contained in the heat exchanger is 25 gallons. The system has been
designed with 35 feet of 4 inch pipe that will be above the operating level of the remote sump tank. What is
the correct RS Remote Sump Tank selection?
Solution:
From Table 4, the cold water basin volume at overflow for the VTL-059-H is 146 gallons.
From Table 5, the 4 pipe will contain 0.662 gallons of water per linear foot. The total volume contained in the
4 pipe is 23 gallons.
The tower side volume of the heat exchanger is 25 gallons.
The total volume required is:
Cooling Tower Volume at Overflow (146 gallons)
+ System Piping Volume (23 gallons)
+ System Components Volume (25 gallons)
= Total Volume 194 gallons
194 gallons x 1.05 (safety factor) = 204 gallons required.
From the engineering data on page H5, the correct RS Remote Sump Tank selection is an RS-335, which
has a net available volume of 257 gallons.
Nominal Pipe Size Gallons Per Linear Foot
2 0.174
3 0.384
4 0.662
6 1.503
8 2.603
10 4.101
12 5.822
14 7.04
16 9.193
18 11.636
20 14.461
24 20.916
Table 5. Schedule 40 Pipe Capacities*
* Not applicable for other types of piping.
R
e
m
o
t
e
S
u
m
p
T
a
n
k
-
S
e
l
e
c
t
i
o
n
J16
Baltimore Aircoil Company
Selection and Application of a Remote
Sump Tank for a Closed Circuit Cooling
Tower or Evaporative Condenser
Note: This section provides instruction in the selection of a remote sump tank for a closed circuit cooling
tower or evaporative condenser only. For information on sizing a remote sump tank for an open cooling
tower, see page J12.
Remote sump tanks are used on evaporative cooling systems to provide a means of cold water basin freeze
protection during cold weather operation. When the recirculating pump of a closed circuit cooling tower or
evaporative condenser is not operating, all of the recirculating water drains by gravity to the remote sump.
The remote sump tank is usually located in a heated, indoor space, and may preclude the need to winterize
the cold water basin.
The remote sump must be sized to accommodate the suction head for the pump plus a surge volume to
hold all the water that will drain back to the tank when the pump is shut down. This surge volume (also
called drain down volume) includes water in the evaporative cooling equipment and water held in the piping
between the unit and the remote sump. The volume of water in the evaporative equipment includes the
water in suspension (water within the spray distribution system and falling through the heat transfer section)
and water in the cold water basin during normal operation. Tables 1 through 4 provide the volume of water
in suspension plus the water in the cold water basin, labeled as "spray water volume." Table 5 can be used
to calculate the volume of water in the piping between the unit and the remote sump (includes riser and
drain piping) for applications where piping is Schedule 40.
To select a remote sump tank for a particular application, determine the total volume (spray water volume
plus piping volume) and select a remote sump tank with a net available volume that is 5% greater than
required. See page H5 for RS Remote Sump Tank Engineering Data.
T
e
c
h
n
i
c
a
l
R
e
s
o
u
r
c
e
s
J17
...because temperature matters
Application Notes
The standard close-coupled centrifugal pump normally furnished with BAC units is designed and selected
specifically for the pump head and flow rate required when the pump is mounted on the unit. This pump
cannot be used for remote sump applications and is therefore omitted. The following factors should be
considered when selecting remote pumps:
Total static head from the remote sump tank operating level to the inlet of the evaporative equipment.
Pipe and valve friction losses.
For FXV & HXV Closed Circuit Cooling Towers and CXV Evaporative Condensers, 1.0 psig water
pressure is required at the inlet of the water distribution system. For Series V Closed Circuit Cooling
Towers and Evaporative Condensers, 2.0 psig water pressure is required at the inlet of the water
distribution system.
Required flow rate as shown in Tables 1 through 4.
A valve should always be installed in the pump discharge line so that the water flow can be adjusted
to the proper flow rate and pressure. Inlet water pressure should be measured with a pressure gauge
installed in the water supply riser near the equipment inlet. The valve should be adjusted to permit the
specified inlet pressure, which results in the design water flow rate.
Accurate inlet water pressure and flow rate are important for proper evaporative equipment operation.
Higher pressure (in excess of 10 psig) can cause leaks in the spray distribution system. Lower pressure or
low flow may cause improper wetting of the coils, which will negatively affect thermal performance, promote
scaling, and may also cause excessive drift.
On remote sump applications, the standard float valve(s) and strainer(s) are omitted from the cold water
basin and a properly sized outlet connection is added. Tables 1 through 4 include the proper outlet size for
each model. The remote sump outlet connection is located on the bottom of most units. On smaller Series V
units, the connection is located on the end of the unit. To clarify the location of the remote sump outlet
connection, refer to the appropriate unit print, available from your local BAC Representative or at
www.BaltimoreAircoil.com.
Another effect of using a remote sump is that the operating weight of the evaporative unit is reduced (design
changes, the omission of the integral spray pump, and/or changes in cold water basin volume can contribute
to this deduct). Please refer to the tables below for the operating weight deduct associated with a remote
sump application.
R
e
m
o
t
e
S
u
m
p
T
a
n
k
-
S
e
l
e
c
t
i
o
n
J18
Baltimore Aircoil Company
Table 1. FXV/CXV Remote Sump Data
Table 2. Low Profile Series V (VFL/VCL) Remote Sump Data
Table 3. Series V Centrifugal Fan (VF1/VC1) Remote Sump Data
Closed Circuit Cooling
Tower Model
Evaporative Condenser
Model
Spray Water
Volume
1,2
(Gallons)
Required
Flow Rate
(GPM)
Outlet
Size
3
(in)
Weight
Deduct
(lbs)
FXV-42X CXV-64 thru 95 270 190 6 290
FXV-43X CXV-103 thru 153 290 290 6 330
FXV-44X CXV-160 thru 206 550 500 8 560
FXV-64X CXV-196 thru 305 600 715 10 560
FXV-66X CXV-310 thru 481 750 900 10 560
N/A CXV-420 thru 610 1,200 1,430 (2) 10 1,120
N/A CXV-620 thru 962 1,500 1,800 (2) 10 1,120
FXV-288-X CXV-T645 thru T792 1,625 1,720 12 1,400
FXV-364-X CXV-T791 thru T944 2,000 1,720 12 1,400
N/A CXV-T1290 thru T1584 3,250 3,440 (2) 12 2,800
N/A CXV-T1582 thru T1888 4,000 3,440 (2) 12 2,800
Closed Circuit Cooling
Tower Model
Evaporative
Condenser Model
Spray Water
Volume
1,2
(Gallons)
Required Flow
Rate (GPM)
Outlet Size
3
(in)
Weight
Deduct
(lbs)
VFL-012-X VCL-016 thru 035 40 45 3 350
VFL-024-X VCL-038 thru 079 95 94 4 550
VFL-036-X VCL-087 thru 120 200 142 4 290
VFL-048-X VCL-134 thru 155 250 192 6 600
VFL-072-X VCL-167 thru 234 385 284 6 720
VFL-096-X VCL-257 thru 299 405 384 8 1,740
Closed Circuit Cooling
Tower Model
Evaporative
Condenser Model
Spray Water
Volume
1,2
(Gallons)
Required Flow
Rate (GPM)
Outlet Size
3
(in)
Weight
Deduct
(lbs)
VF1-009-X VC1-10 thru 25 25* 35 2 1/2 180
VF1-018-X VC1-30 thru 65 50* 75 3 310
VF1-027-X VC1-72 thru 90 75* 115 4 440
VF1-036-X VC1-100 thru 135 105* 150 4 590
VF1-048-X VC1-150 thru 205 140* 220 6 850
VF1-072-X VC1-N208 thru N230 360* 305 6 2,250
VF1-096-X VC1-N243 thru N315 360* 385 6 2,100
VF1-144N-X VC1-N338 thru N470 520* 580 6 3,250
VF1-192-X N/A 720* 770 (2) 6 4,200
VF1-288N-X N/A 1,040* 1,160 (2) 6 6,500
VF1-144-X VC1-386 thru 516 600 585 8 4,510
VF1-216-X VC1-540 thru 804 710 835 10 6,560
VF1-288-X VC1-772 thru 1032 1,360 1,170 10 8,170
VF1-432-X VC1-1158 thru 1608 2,090 1,670 12 13,270
N/A VC1-C216 thru C321 360* 385 6 2,100
N/A VC1-C339 thru C469 520* 580 6 3,250
T
e
c
h
n
i
c
a
l
R
e
s
o
u
r
c
e
s
J19
...because temperature matters
Example
An FXV-421 will be installed on a system that will also utilize an RS Remote Sump Tank. The system has
been designed with 40 feet of 6-inch pipe that will be above the operating level of the remote sump tank.
What is the correct RS Remote Sump Tank selection?
Solution:
From Table 1, the spray water volume for an FXV-421 is 270 gallons.
From Table 5, the 6-inch pipe will contain 1.503 gallons of water per linear foot. The total volume contained
in the 6-inch pipe is 40 feet x 1.503 gallons/foot = 60 gallons.
The total volume required is:
Spray Water Volume (270 gallons)
+ System Piping Volume (60 gallons)
= Total Volume 330 gallons
330 gallons x 1.05 (safety factor) = 347 gallons required.
From the engineering data on page H5, the correct RS Remote Sump Tank selection is an RS-457, which
has a net available volume of 351 gallons.
Notes Tables 1 - 4:
1. The spray water volume is
based on the maximum
operating water level in the cold
water basin with no net drop leg
included in the piping system
below the unit outlet.
2. All remote sump unit volumes
are based on bottom outlets
sized as noted, except those
models with an asterisk, which
are based on an end outlet
sized as noted.
3. Drain connection size is for
remote sump applications only.
Evaporative
Condenser Model
Spray Water
Volume
1,2
(Gallons)
Required Flow
Rate (GPM)
Outlet Size
3
(in)
Weight
Deduct
(lbs)
VC2-N138 thru N191 270* 220 6 1,310
VC2-N206 thru N235 430* 305 6 2,260
VC2-N261 thru N301 480* 385 8 1,960
VC2-N356 thru N446 820* 580 10 3,010
VC2-319 thru 626 480 585 8 5,040
VC2-526 thru 957 670 835 10 7,380
VC2-N870 thru N1204 1,440 1,170 10 10,260
VC2-684 thru 1252 1,440 1,170 10 10,260
VC2-1052 thru 1914 2,220 1,670 12 14,930
Table 4. Series V Axial Fan (VC2) Remote Sump Data
Table 5. Schedule 40 Pipe Capacities*
* Not applicable for types of piping.
Nominal Pipe Size Gallons Per Linear Foot
2 0.174
3 0.384
4 0.662
6 1.503
8 2.603
10 4.101
12 5.822
14 7.040
16 9.193
18 11.636
20 14.461
24 20.916
F
u
n
d
a
m
e
n
t
a
l
s
o
f
S
o
u
n
d
J20
Baltimore Aircoil Company
Sound is an important consideration in the selection of mechanical equipment. The purpose of this article is
to present a procedure for evaluating the sound levels created by evaporative cooling equipment to
determine if these levels will be acceptable to the neighbors* who live or work near the installation. In
addition, sound levels must comply with local code requirements. While most often these levels are found to
be acceptable, certain situations may call for sound levels lower than those produced by the equipment. It is
then the task of the manufacturer, engineer, and owner to determine the best way to decrease the sound
levels for the particular installation. This article presents a means for assessing the impact of the
evaporative cooling equipments sound on a neighbor and possible means to reduce that impact should it be
a potential problem.
The procedure consists of three steps, followed by a fourth step if necessary:
1. Establish the noise criterion for the equipment: i.e., determine the sound levels that will be considered
acceptable by the neighbors who will be exposed to them. Also consult local codes for appropriate
sound levels. For a general idea of how sound levels produced by a cooling tower compare to sound
from other common sound sources, see the graph below.
2. Estimate the sound levels that will be produced by the equipment, taking into account the effects of
equipment geometry, the installation, and the distance from the equipment to the neighbor.*
3. Compare the noise criterion with the expected sound levels to determine if the sound levels from the
equipment will be acceptable.
4. In the event that the equipment sound levels are excessive for the particular site conditions, a method
should be determined to modify the neighbors perception of the sound. There are three ways to
change the effects that any undesirable sound has on the receiver of that sound:
Modify the source of the sound
Control the path of the sound
Adjust the receivers expectation or satisfaction, keeping in mind that sound can be very
subjective and is highly dependent on perception
*In this article, the term neighbor is used to denote the person or group of persons to be protected against excessive
sound levels created by the evaporative cooling equipment. It is intended that this include not only the occupants of
other buildings, but also the occupants of the building served by the equipment.
Fundamentals of Sound
T
e
c
h
n
i
c
a
l
R
e
s
o
u
r
c
e
s
J21
...because temperature matters
Some ways that sound from BAC equipment can be adjusted for a more favorable impact on the receiver
include:
Modify equipment location or position
If possible, simply do not run the equipment at the critical time (at night for residential areas and during
the day for office parks)
Install a second motor, two-speed motor, or VFD so that the unit can run at lower speeds when the full
capacity is not required
Use a low sound fan
Oversize the equipment and run the fan at lower speed and power level
Construct sound barriers (sound walls, etc.) or use existing barriers (trees, other buildings, etc.) when
planning the location of the equipment
Install sound attenuation (available on the air intake and air discharge of the equipment)
The article also includes several appendices to lend assistance in understanding and performing some
aspects of a sound analysis. Contact your local BAC Representative with questions on sound analysis or
sound issues specific to your installation.
Receiver
Path
Terminology and Units of Measurement
The following terms and units of measure are used in this article, in accordance with accepted
U.S. Standards:
Decibel (dB) the unit of measurement used in sound control (dimensionless, used to express
logarithmically the ratio of a sound level to a reference level).
dB(A) the A-weighted sound pressure level.
Evaporative cooling equipment used in this article to represent all BAC product lines in the sound
analysis (includes open cooling towers, closed circuit cooling towers, and evaporative condensers).
Frequency the number of repetitions per unit time (the unit for frequency is the Hertz (1 cycle/s)).
Hertz abbreviated Hz, is the unit of frequency, defined as cycles per second.
Noise unwanted sound.
Source
F
u
n
d
a
m
e
n
t
a
l
s
o
f
S
o
u
n
d
J22
Baltimore Aircoil Company
At the beginning of any sound analysis, it is necessary to establish the sound level at a particular site that
would be considered acceptable by those who might be affected. This acceptable sound level is called the
noise criterion for that situation, and it is important to realize that it may vary widely for different situations.
The procedure for developing the noise criterion involves consideration of the following:
1. The type of activity of those people in the vicinity of the evaporative cooling equipment who will be
affected
2. The amount of attenuation from acoustic barriers or walls that lie between the equipment and the
people who may hear it
3. The outdoor background noise that might help mask the sound from the equipment
From these factors, we can arrive at the final noise criterion for the particular installation.
Establishing the Noise Criterion
Noise Criteria the maximum allowable sound pressure level(s) (Lp) at a specific location. Criteria may be
expressed as a single overall value or in individual octave bands. The NC values and curves are further
explained throughout this article.
Octave Band a range of sound frequencies with an upper limit twice its lower limit. The bands are
identified by their center frequencies (identifying frequencies), which is the square root of the product of the
upper and lower cutoff frequencies of a pass band. These center frequencies and band widths are shown
on page J23. In some sound data tables, these eight octave bands are also called by their Band
Numbers; hence, the Band Numbers are also listed as such in this article, in addition to the BAC Sound
Rating Program and BAC Selection Software.
Sound the sensation of hearing; rapid, small fluctuations to which our ears are more or less sensitive;
small perturbation of the ambient state of a medium (ambient air in most cases) that propagate at a speed
characteristic of the medium.
Sound Pressure Level (Lp) in dB a ratio of a sound pressure to a reference pressure and is defined as:
Lp = 20LogP/0.002(dB), reference 0.0002 microbar.
The reference pressure used in this article is the long-used and accepted value of 0.0002 microbar. Another
way to describe the same value, which may be used in other publications, is the value of 20 x 10
-6
Pascals
(N/m
2
).
Sound Power Level (Lw) in dB the measure of the total acoustic power radiated by a given source and
is defined by:
Lw = 10Log (W/10
-12
)dB, reference 10
-12
.
The standard reference power used in the BAC literature is 10
-12
watt. To eliminate any possible confusion,
the reference power should always be quoted, as in a sound power level of 94 dB reference 10
-12
watt.
Unit a single cell of evaporate cooling equipment.
T
e
c
h
n
i
c
a
l
R
e
s
o
u
r
c
e
s
J23
...because temperature matters
The noise that humans hear covers a frequency range of about 20 Hz to about 20,000 Hz. Of course, there
are exceptions to this, but this range has come to be accepted for most practical purposes. Furthermore, for
most engineering applications, most of this audio range is subdivided into eight frequency bands called
octave bands which cover the range of frequency somewhat as the octaves on a piano cover the range of
pitch. The eight octave bands used in this article have the following identifying center frequencies and
ranges:
When sound levels are plotted on a graph, they are most often divided into these eight octave bands. In this
way it is possible to observe the variation of a sound level with change in frequency. This variation is
important in any situation since humans display a different sensitivity and a different response to low
frequency sounds as compared with high frequency sounds. In addition, engineering solutions for low
frequency sound issues differ markedly from those for high frequency sound issues.
Band
Number
Identifying
Frequency (Hz)
Aprox. Frequency
Range (Hz)
1 63 44-88
2 125 88-176
3 250 176-353
4 500 353-707
5 1000 707-1414
6 2000 1414-2828
7 4000 2828-5656
8 8000 5656-11312
Indoor Neighbor Activity
From earlier studies of real-life situations where people have judged sounds all the way from comfortable to
acceptable to disturbing and even to unacceptable for various indoor working or living activities, a series
of Noise Criterion Curves (NC curves) has been developed. Figure 1 is a graph of these NC curves.
Each curve represents an acceptable balance of low frequency to high frequency sound levels for particular
situations, and is keyed into the listening conditions associated with the sound. The lower NC curves
describe sound levels that are quiet enough for resting or sleeping or for excellent listening conditions, while
the upper NC curves describe rather noisy work areas when even conversation becomes difficult and
restricted. These curves may be used to set desired sound level goals for almost all typical indoor functional
areas where some acoustic need must be served.
Note that the curves of Figure 1 have as their x-axis the eight octave frequency bands; and as their y-axis,
sound pressure levels given in decibels (dB) relative to the standard reference pressure of 0.0002 microbar.
For convenience, Table 1 lists the sound pressure levels at each octave band center frequency, for each
Noise Criterion.
F
u
n
d
a
m
e
n
t
a
l
s
o
f
S
o
u
n
d
J24
Baltimore Aircoil Company
Table 1 - Octave Band Sound Pressure Levels (dB re 0.0002 microbar) of Indoor Noise Criterion
(NC) Curves of Figure 1
Figure 1 - Noise criterion NC Curves. The octave band sound pressure levels associated with the
noise criterion conditions of Table 2
63 125 250 500 1000 2000 4000 8000
NC-15 47 36 29 22 17 14 12 11
NC-20 51 40 33 26 22 19 17 16
NC-25 54 44 37 31 27 24 22 21
NC-30 57 48 41 35 31 29 28 27
NC-35 60 52 45 40 36 34 33 32
NC-40 64 56 50 45 41 39 38 37
NC-45 67 60 54 49 46 44 43 42
NC-50 71 64 58 54 51 49 48 47
NC-55 74 67 62 58 56 54 53 52
NC-60 77 71 67 63 61 59 58 57
NC-65 80 75 71 68 66 64 63 62
Noise
Criterion
Octave Band Center Frequency in Hz
T
e
c
h
n
i
c
a
l
R
e
s
o
u
r
c
e
s
J25
...because temperature matters
Table 2 is used with the NC curves and lists some typical activities that require indoor background sound
levels in range of NC-15 to NC-55. Certain unusual acoustical requirements may not easily fall into one of
the Table 2 groups. It may be necessary to apply specific criteria for those special situations or to assign a
criterion based in similarity to one of the criterion given in the table.
It is emphasized that the NC curves are based on, and should be used only for, indoor activity.
The first step in the development of the evaporative cooling equipments noise criterion is to select from Table
2 the particular activity that best describes what the indoor neighbors in the vicinity of the equipment will be
doing when the equipment is operating. Where two or more neighbor conditions may be applicable, the one
having the lowest NC value should be selected. The corresponding NC values of Figure 1 or Table 1 give the
eight octave band sound pressure levels, in decibels, for that selection. The goal is to keep the sound heard
by the neighbor, inside his home or building, at or below these sound pressure levels.
Table 2 - Suggested Schedule of Noise Criteria for Indoor Neighbor Activities
* The ASHRAE Guide usually lists a 10 dB range of NC values for each situation leaving it to the option of
the user to select the specific NC value for his own need. In the interest of more assuredly achieving
satisfactory neighbor conditions, Table 2 listings are the more conservative lower 5 dB range of the ASHRAE
value.
ACTIVITY
Sleeping, Resting, Relaxing
Homes, apartments, hotels, hospitals, etc.
Suburban and rural NC-20 to NC-25
Urban NC-25 to NC30
Excellent Listening Conditions Required
Concert halls, recording studios, etc. NC-15 to NC-20
Very Good Listening Conditions Required
Auditoriums, theaters NC-20 to NC-25
Large meeting and conference rooms NC-25 to NC-30
Good Listening Conditions Required
Private offices, school classrooms, libraries, small confrence rooms, radio and
television listening in the home, etc.
NC-30 to NC-35
Fair Listening Conditions Desired
Large offices, restaurants, retail shops, and stores, etc. NC-35 to NC-40
Moderately Fair Listening Conditions Acceptable
Business machine areas, lobbies, cafeterias, laboratory work areas, drafting
rooms, satisfactory telephone use, etc.
NC-40 to NC-45
Acceptable Working Conditions with Minimum Speech Interference
Light to heavy machinery spaces, industrial areas, commercial areas such as
garages, kitchens, laundries, etc.
NC-45 to NC-55
SUGGESTED RANGE OF
NOISE CRITERIA
F
u
n
d
a
m
e
n
t
a
l
s
o
f
S
o
u
n
d
J26
Baltimore Aircoil Company
Sound Reduction Provided by Building Construction
Neighbors who are either indoors in their own building or outdoors on their property may hear sound from
outdoor equipment. If they are outdoors, they may judge the sound against the more-or-less steady
background sounds in the area. If they are indoors, they may tend to judge the sound by whether it is
audible or identifiable or intrusive into the surroundings.
When outdoor sound passes into a building, it suffers some reduction, even if the building has open
windows. The actual amount of sound reduction depends on building construction, orientation, wall area,
window area, open window area, interior acoustic absorption, and possibly some other factors. The
approximate sound reduction values provided by several typical building constructions are given in Table 3.
For convenience in identification, the listed wall constructions are labeled with letters A through G and are
described in the notes under Table 3. Note that A represents no wall, hence no sound reduction, and the
use of A indicates that the selected NC curve would actually apply in this special case to an outdoor activity,
such as for a screened-in porch, an outdoor restaurant, or an outdoor terrace.
By selecting the wall construction in Table 3 which most nearly represents that of the building containing the
neighbor activity, and adding the amounts of sound reduction from Table 3 to the indoor NC curves,
band-by-band, the outdoor sound pressure levels that would yield the desired indoor NC values when the
equipment sound passes through the wall and comes inside, are obtained. This second step, then, provides
a tentative outdoor noise criterion based on hearing the sound indoors in the neighbors building.
Table 3 - Approximate Sound Reduction (in dB) Provided by Typical Exterior Wall Construction
A: No wall; outside conditions
B: Any typical wall construction, with open windows covering about 5% of exterior wall area
C: Any typical wall construction, with small open-air vents of about 1% of exterior wall area, all windows closed
D: Any typical wall construction, with closed but operable windows covering about 10%-20% of exterior wall area
E: Sealed glass wall construction, 1/4 inch thickness over approximately 50% of exterior wall area
F: Approximately 20 lb/sq foot solid wall construction with no windows and no cracks or openings
G: Approximately 50 lb/sq foot solid wall construction with no windows and no cracks or openings
Octave
Frequency
Band
(Hz) A B C D E F G
63 0 10 13 19 14 24 32
125 0 10 14 20 20 25 34
250 0 10 15 22 26 27 36
500 0 10 16 24 28 30 38
1000 0 10 17 26 29 33 42
2000 0 10 18 28 30 38 48
4000 0 10 19 30 31 43 53
8000 0 10 20 30 33 48 58
Wall Type (See Notes Below)
T
e
c
h
n
i
c
a
l
R
e
s
o
u
r
c
e
s
J27
...because temperature matters
Outdoor Background Sound
In a relative noisy outdoor area, it is possible that the outdoor background sound is even higher than the
tentative outdoor noise criterion. In this case, the steady background sound in the area may mask the
sound from the evaporative cooling equipment and take over as the controlling outdoor noise criterion.
Determining whether or not this situation does exist is the third step in developing the noise criterion.
The best way to judge this is to take a few sound pressure level measurements to get the average minimum
background level during the quietest intervals in which the equipment is expected to operate, or during the
intervals when noise complaints are most likely to be caused; for example, at night in residential areas where
cooling equipment is operating at night, or during the day in office areas exposed to daytime cooling
equipment sound.
In the event that background sound measurements cannot be made, Tables 4 and 5, and Figure 2 may be
used to estimate the approximate outdoor background noise. In Table 4, the condition should be determined
that most nearly describes the community area or the traffic activity in the vicinity of the evaporative cooling
equipment during the quietest time that the equipment will operate. For the condition selected, there is a
curve in Figure 2 that gives an estimate of the average minimum outdoor background sound pressure levels.
The sound pressure levels of the Figure 2 curves are also listed in Table 5.
It is cautioned that these estimates should be used only as approximations of background sounds, and that
local conditions can give rise to a wide range of actual sound levels.
Table 4 - Estimate of Outdoor Background Sounds Based on General Type of Community Area and
Nearby Automotive Traffic Activity
(Determine the appropriate conditions that seem to best describe the area in question during the time interval that is most critical, i.e.,
day or night. Then refer to corresponding Curve No. in Figure 2 or Table 5 for average minimum background sound levels to be used in
sound analysis. Use lowest Curve No. where several conditions are found to be reasonably appropriate.)
1
2
3
2
3
4
5
3
4
5
6
4
6
5
7
4
5
5
6
2
3
3
4
23. 2000 to 4000 ft from intermittent light traffic
24. 2000 to 4000 ft from continuous light traffic
25. 2000 to 4000 ft from continuous medium-density traffic
19. 1000 to 2000 ft from intermittent light traffic
20. 1000 to 2000 ft from continuous light traffic
21. 1000 to 2000 ft from continuous medium-density traffic
22. 1000 to 2000 ft from continuous heavy-density traffic
15. 300 to 1000 ft from intermittent light traffic
16. 300 to 1000 ft from continuous light traffic
17. 300 to 1000 ft from continuous medium-density traffic
18. 300 to 1000 ft from continuous heavy-density traffic
11. Within 300 ft of intermittent light traffic
12. Within 300 ft of continuous light traffic
13. Within 300 ft of continuous medium-density traffic
14. Within 300 ft of continuous heavy-density traffic
7. Nighttime, business or commercial area
8. Daytime, business or commercial area
9. Nighttime, industrial or manufacturing area
10. Daytime, industrial or manufacturing area
3. Nighttime, suburban; no nearby traffic of concern
4. Daytime, suburban; no nearby traffic of concern
5. Nighttime, urban; no nearby traffic of concern
6. Daytime, urban; no nearby traffic of concern
CONDITION CURVE No. in FIGURE 2 or TABLE 5
1. Nighttime, rural; no nearby traffic of concern
2. Daytime, rural; no nearby traffic of concern
1
2
F
u
n
d
a
m
e
n
t
a
l
s
o
f
S
o
u
n
d
J28
Baltimore Aircoil Company
Figure 2 -Approximate average minimum outdoor background sound pressure levels associated with the
conditions of Table 4
Table 5 - Octave Band Sound Pressure Levels (in dB) of Outdoor Background Noise Curves of Figure 2
Final Noise Criterion
The measured or estimated average minimum background sound levels should now be compared,
band-by-band, with the tentative outdoor noise criterion determined previously. The larger of these values,
in each frequency band, now becomes the octave band sound pressure levels that comprise the final
outdoor noise criterion for the equipment installation.
Any new intruding sound is generally judged in comparison with the background sound that was already
there. If the new sound stands out loudly above the existing sound, the neighbors will notice it, be disturbed
by it, and object to it. On the other hand, if the new sound can hardly be heard in the presence of the old
sound, it will pass relatively unnoticed. Therefore, if the sound coming from the equipment is below or just
equal to the final noise criterion, it will not be noticed and our objectives will have been satisfied.
If there are two or more different criterion for a particular installation, the analysis should be carried out for
each situation and the lowest final criterion should be used.
63 125 250 500 1000 2000 4000 8000
1 40 37 32 27 22 18 14 12
2 45 42 37 32 27 23 19 17
3 50 47 42 37 32 28 24 22
4 55 52 47 42 37 33 29 27
5 60 57 52 47 42 38 34 32
6 65 62 57 52 47 43 39 37
7 70 67 62 57 52 48 44 42
CURVE No. In
FIGURE 2
OCTAVE BAND CENTER FREQUENCY In Hz
T
e
c
h
n
i
c
a
l
R
e
s
o
u
r
c
e
s
J29
...because temperature matters
Municipal Codes and Ordinances
Where local sound codes or ordinances exist, it is necessary to check the expected sound levels of the unit
to be installed, including any sound control treatments, to determine if they comply with the code
requirements. Depending on the form and language of the code, it may be necessary to introduce the code
sound levels into the noise criterion analysis.
Example
To summarize this procedure, consider a cooling tower installation located near the edge of a college
campus, approximately 300 feet (91.44 m) from a classroom building. The college is located within a large
city, and two main streets pass by one corner of the campus about 1500 feet (457.20 m) from the classroom
building. The cooling tower will be used both day and night during warm weather. The classroom must rely
on open windows for air circulation. Determine the noise criterion for the cooling tower.
The steps for this example are given in the sample Sound Evaluation Work Sheet, included as
Appendix D in this article.
Step 1 Determine the neighbor activity condition from Table 2. For good listening conditions inside a typical
classroom, select NC-30 as the noise criterion.
Step 2 In the indicated spaces under Item 2 of the Sound Evaluation Work Sheet, enter the sound pressure
levels for the octave frequency bands of the NC-30 curve as taken from Figure 1 or Table 1.
Step 3 Determine the wall condition of Table 3 that best describes the exterior wall of the classroom. Wall B
can be selected for normally open windows during the summer time. Insert the Wall B values in the Item 3
spaces.
Step 4 Add the values of Steps 2 and 3 together and insert the sums in the Item 4 spaces. This is the
tentative outdoor noise criterion.
Step 5 In the Item 5 spaces, enter either the measured average minimum background sound pressure levels
or the estimated background levels obtained from the use of Figure 2 and Tables 4 and 5. In this example,
we estimate that the traffic activity is best represented by 1000-2000 feet (304.8-609.6 m) from continuous
heavy-density traffic. This leads to Curve 5 of Figure 2 and Table 5, whose values are then inserted in the
Item 5 spaces.
Step 6 In the Item 6 spaces insert the higher value, in each frequency band, of either the Item 4 or Item 5
values. This is the final noise criterion.
F
u
n
d
a
m
e
n
t
a
l
s
o
f
S
o
u
n
d
J30
Baltimore Aircoil Company
In this example, note that the Item 4 values are equal to or higher than the Item 5 values in all bands. Thus,
the final noise criterion is based essentially on the classroom noise criterion and the wall condition.
However, the outdoor background noise estimate equals the tentative outdoor noise criterion in the 250
and 500 Hz bands. If they had been higher, in this example, those higher values would have been used in
setting the final noise criterion in those bands.
We will attempt to keep all octave band sound pressure levels of the selected cooling tower equal to, or
below, the values of Step 6. Should a sound code exist, this would be an appropriate point in the analysis to
check agreement between the code and the Step 6 final outdoor noise criterion. If the criterion developed
here is lower than the sound code levels at the specified distance, the sound analysis will yield results that
will comply with the code.
The remaining steps of this sound evaluation example are explained in later sections of this article as we
progress with the entire sound evaluation procedure.
Sound Levels for Evaporative Cooling
Equipment
Now that we have established an acceptable noise criterion, the next step is to study the source of the
sound and develop equipment sound levels at the neighbor location, in the same sound pressure level terms
used to express the noise criterion. It will be the aim of this section to discuss the actual sound pressure
levels of BAC evaporative cooling equipment, and to show how these levels can be corrected for various
distances and certain geometric arrangements.
The orientation of the equipment and distance from the equipment to the most critical neighbor will be our
primary concern. Where possible, the distance from the equipment to the neighbor should be kept as large
as possible, and the equipment should be oriented so that its lowest sound levels are radiated toward the
neighbor.
Evaporative cooling equipment sound ratings can be stated in terms of both sound pressure levels and
sound power levels, and both may be necessary to permit thorough sound analysis in a given situation.
However, in any sound evaluation, octave band sound pressure levels for the proposed equipment are
essential, and it is important to have a fairly accurate indication of the directivity characteristics of the
equipments sound.
For general use, sound pressure levels measured in the four different horizontal directions (one from each
side) of the unit, plus the vertical direction above, will yield the desired directivity data. The primary
requirements for obtaining the outdoor equipments sound levels are:
T
e
c
h
n
i
c
a
l
R
e
s
o
u
r
c
e
s
J31
...because temperature matters
1. Accurate calibrated sound measurement equipment should be used.
2. Octave band sound pressure levels are mandatory.
3. The sound level data should indicate the true directivity effects of the units sound (there should be no
nearby buildings or obstructions to distort the true radiation pattern of the unit test).
4. The measurement distance should be specified.
Some equipment is rated in terms of the total sound power radiated, expressed as sound power level. Sound
power level is a valid index for comparing the sum of sounds radiated by evaporative cooling equipment, but
has the serious disadvantage of not revealing the directivity effects of the radiated sounds. Where only
sound power level data are given, the resulting conversion to sound pressure level at a particular location will
give less accurate results than if directional sound pressure level data are used. Sound generated by
evaporative cooling equipment is directional, and sound pressure level ratings are necessary in order to
determine the actual sound in any direction around the installation.
Single Number Rating System
Many attempts have been made to express the frequency content and pressure level (intensity) of sounds
using a single number system. The most common method used is the A-B-C weighting network of sound
level meters.
Sound meters with A-B-C weighting networks attempt to simulate the ears response to sound at different
pressure intensities. At a relatively low sound pressure level, the human ear is considerably more sensitive
to high frequency than to low frequency sounds. This difference, however, becomes less noticeable at higher
sound levels where the ear approaches more nearly equal sensitivity for low frequency and high frequency
sounds.
The A-scale weighting network is designed to simulate the ears response for low pressure sounds (below
about 55 dB). The B-scale weighting is designated to simulate the ears response for medium pressure
sounds (about 55 dB to 85 dB). The C-scale weighting tends to provide nearly equal response in all
frequencies and is used to approximate the ears response at higher sound pressure levels (above about
85 dB).
A-B-C scale ratings have been used in some sound ordinances and equipment sound ratings because of
their simplicity of statement. They may have value in some sound comparison situations, but such data are
of little value in making an engineering evaluation of a sound issue caused by evaporative cooling equipment,
because no indication of the frequency content of the sound is apparent. For example, two different types of
cooling towers could have the same A scale rating, but one could have most of its energy in the low
frequency bands while the other could have its energy concentrated in the high frequency bands. A single
number rating will give no indication of this and its use could lead to less than optimal and sometimes costly
decisions.
F
u
n
d
a
m
e
n
t
a
l
s
o
f
S
o
u
n
d
J32
Baltimore Aircoil Company
Comparison of Evaporative Cooling Equipment employing a Centrifugal
Fan versus an Axial Fan
Based on extensive studies of field data from several cooling tower installations, it has been found that
overall sound pressure levels of centrifugal fan cooling towers are about 5 to 7 dB lower than those of axial
fan cooling towers for the same cooling capacity even though the axial towers use about half the
horsepower. As a comparison, this means that an axial fan cooling tower would have to be twice as far
away from the neighbors as a centrifugal fan tower in order to be just as quiet (6 dB reduction for each
doubling of distance, see Table 6). The frequency distribution and the radiation patterns also differ for these
two types of units. For any specific comparison of cooling towers, the manufacturers actual measured data
should be used.
BAC Sound Ratings
BAC has measured the sound levels radiated by its products at 5-foot (1.52 m) and 50-foot (15.24 m)
distances for the five principle directions, (four horizontal and one vertical). The sample sound rating data
sheet shown on page J33 indicates the five principle directions and the type of sound data available for a
BAC cooling tower. As the data sheet suggests, the data given in the five blocks pertain to the sound pres-
sure levels measured at 5-foot and 50-foot distances from the five principle directions of the cooling tower.
Where it might be desired to estimate the sound pressure levels at some intermediate direction, such as
halfway between the right end and the air inlet, levels can be averaged or interpolated from the data actually
presented.
In addition to the five sets of sound pressure levels at each of the two distances, the data sheets contain the
calculated sound power level values for the reference power level 10
-12
watt. Current sound data for all BAC
equipment is available from BAC Representatives and from the BAC Selection Program, available at
www.BaltimoreAircoil.com.
Since sound power levels are being mentioned here, it is appropriate at this point to note that Appendices A,
B, and C are given at the end of this article to supply basic information related to sound power levels and to
other calculations that may be required from time to time in a sound evaluation. Appendix A describes a
simplified method for calculating the sound power level of a unit where the five sets of sound pressure level
readings are known. Appendix B gives a procedure for calculating the average sound pressure level at a
given distance if the sound power level is known. Appendix C gives a simple procedure for adding decibel
values. This is required, for example, in converting sound pressure levels into sound power levels, or in
calculating an overall sound pressure level from the eight individual octave band levels, or in adding two or
more sound sources.
T
e
c
h
n
i
c
a
l
R
e
s
o
u
r
c
e
s
J33
...because temperature matters
Baltimore Aircoil Company
Sound Rating Program, 11/21/2003 Release, 06/20/2002 Data
Series 3000
Top Lp
Sound Pressure (dB)
Distance
0clave
8ard 5 ft 50 ft
1
2
3
4
5
6
7
8
60
78
85
79
81
82
79
75
51
57
63
65
68
68
65
66
Model : 3299A
No. of Fans: (1) 7.5 ft. Diameter Fan Per Cell
Fan Type: Standard
Motor HP: 20 HP per fan
Octave band and A-weighted sound pressure levels (Lp) are expressed in decibels (dB)
reference 0.0002 microbar. Sound power levels (Lw) are expressed in decibels (dB)
reference one picowatt. Octave band 1 has a center frequency of 63 Hertz.
A-Wld 87 74
Air Inlet Lp
Sound Pressure (dB)
End Lp
Sound Pressure (dB)
Distance Distance
0clave
8ard 5 ft 50 ft
0clave
8ard 5 ft 50 ft
1
2
3
4
5
6
7
8
61
70
73
76
79
78
71
66
46
53
61
61
64
64
57
54
1
2
3
4
5
6
7
8
68
68
73
73
75
72
65
59
56
60
63
59
65
61
54
53
A-Wld 83 69 A-Wld 78 68
End Lp
Sound Pressure (dB)
Air Inlet Lp
Sound Pressure (dB)
Distance Distance
0clave
8ard 5 ft 50 ft
0clave
8ard 5 ft 50 ft
1
2
3
4
5
6
7
8
68
68
73
73
75
72
65
59
56
60
63
59
65
61
54
53
1
2
3
4
5
6
7
8
61
70
73
76
79
78
71
66
46
53
61
61
64
64
57
54
A-Wld 78 68 A-Wld 83 69
Sound Power (dB)
0clave
8ard
Cerler Frequercy
(lerlz) Lw
1
2
3
4
5
6
7
8
63
125
250
500
1000
2000
4000
8000
85
90
94
94
97
96
92
92
F
u
n
d
a
m
e
n
t
a
l
s
o
f
S
o
u
n
d
J34
Baltimore Aircoil Company
Effect of Distance Beyond 50 feet (15.24 m)
In any actual situation, it is usually necessary to determine the sound pressure levels of the equipment at
some distance other than the 5-foot (1.52 m) and 50-foot (15.24 m) distances given in the BAC rating
sheets. In this section, distance corrections are given for estimating sound pressure levels at distances
beyond 50 feet.
For distances that are large compared to the dimensions of the unit, the inverse square law holds for
sound reduction with distance: i.e., for each doubling of distance from the unit, the sound pressure level
decreases 6 dB. Thus, for distances beyond 50 feet the inverse square law applies and the distance
correction is quite straightforward. Table 6 presents the reduction of sound pressure level for distances from
50 feet out to 2500 feet (762 m). The values given in Table 6 are to be subtracted from the sound pressure
levels at the given distance of 50 feet in order to arrive at the sound pressure levels at the distance of
interest.
For relatively short distances (less than 100 feet (30.5 m)), the same correction value applies to all eight
frequency bands. For the larger distances (greater than 100 feet), high frequency sound energy is absorbed
in the air and the correction terms have larger values in the high frequency bands. For distances greater
than about 500 feet, wind and temperature of the air may further influence sound propagation; but because
these are variables, they are not considered in this article and the correction figures of Table 6 represent
more or less average sound propagation conditions.
If the critical distance falls between the specific distances given in the left-hand column of Table 6,
interpolate the sound reduction value to the nearest 1 dB. Do not attempt to use fractions of decibels.
Table 6 - Reduction of Sound Pressure Level (in dB) for Distances beyond 50 feet
63 125 250 500 1000 2000 4000 8000
50 0 0 0 0 0 0 0 0
63 2 2 2 2 2 2 2 2
80 4 4 4 4 4 4 4 4
100 6 6 6 6 6 6 7 7
125 8 8 8 8 8 8 9 10
160 10 10 10 10 10 10 11 12
200 12 12 12 12 12 13 14 15
250 14 14 14 14 14 15 16 18
320 16 16 16 16 16 17 18 21
400 18 18 18 18 19 19 21 24
500 20 20 20 20 21 22 24 27
630 22 22 22 22 23 24 27 31
800 24 24 24 25 25 26 30 35
1000 26 26 26 27 27 29 34 40
1250 28 28 28 29 30 32 38 46
1600 30 30 30 31 32 35 43 53
2000 32 32 32 33 35 38 47 61
2500 34 34 34 36 38 42 53 70
Distance
(ft)
Octave Band Center Frequency in Hz
T
e
c
h
n
i
c
a
l
R
e
s
o
u
r
c
e
s
J35
...because temperature matters
Effect of Distance Between 5 feet (1.52 m) and 50 feet (15.24 m)
In this section, distance corrections are given for estimating sound pressure levels in the close-in range of 5
feet (1.52 m) to 50 feet (15.24 m). When the distance from a sound source is small or comparable to the
dimensions of the source, the inverse square law does not necessarily hold true for variations of sound level
with distance. So, for the relatively short distances of 5 feet to 50 feet, it might be necessary to accept some
sound pressure level variations, which do not follow the straightforward trends that hold for distances beyond
50 feet. Table 7 permits us to estimate the sound pressure levels at these close-in distances, provided the
5-foot and 50-foot sound pressure levels are known.
To illustrate the use of Table 7, suppose the sound pressure level of a unit in a particular frequency band is
68 dB at 5 feet and 54 dB at 50 feet distance. The difference between these two values is 14 dB. In Table 7,
we find the column of values under the heading If the difference between the 5-foot and 50-foot levels is 13
15 dB. The numbers in this column are the values (in decibels) to be added to the 50-foot sound pressure
level of 54 dB to obtain the sound pressure level at some desired shorter distance. If, for instance, we wish
to know the sound pressure level of this unit at 15 feet, we find that we must add 8 dB to the 50-foot level of
54 dB to get 62 dB as the sound pressure level at the desired distance of 15 feet.
Now, for these close distances, the difference values between the 5-foot and 50-foot sound pressure levels
may not be constant for all frequency bands so it is necessary to follow this procedure for each octave band.
For example, in one frequency band the difference may be 12 dB but in another band it may be 15 or 16 dB.
Close-in interpolation of sound pressure levels is inherently somewhat unreliable; so do not be surprised if
some oddities or discrepancies in the data begin to appear at very close distances. The method used here at
least gives some fairly usable data to work with.
Table 7 - Interpolation Terms for Obtaining Sound Pressure Levels (in dB) Between 5 feet and 50 feet
* This column of values is based on the "Inverse Square Law" variation with distance from 50 feet all the way in to 5 feet.
All other columns represent variations with distances that do not follow the "Inverse Square Law."
4-6 dB 7-9 dB 10-12 dB 13-15 dB 16-18 dB 19-21 dB* 22-24 dB
50 0 0 0 0 0 0 0
45 0 0 1 1 1 1 1
40 1 1 1 2 2 2 2
35 1 1 2 3 3 3 3
30 2 2 3 4 4 4 5
25 2 3 4 5 5 6 7
20 2 4 5 6 7 8 9
15 3 5 6 8 9 10 12
10 4 6 8 10 12 14 16
5 5 8 11 14 17 20 23
Distance at
which SPL is
desired(ft)
If the difference between the 5 ft and 50 ft levels is:
Add the following value to the 50-ft. sound level to obtain sound level at desired distance:
F
u
n
d
a
m
e
n
t
a
l
s
o
f
S
o
u
n
d
J36
Baltimore Aircoil Company
Reflecting Walls and Enclosures
Discussion so far has been concerned with what might be considered simple installations from an acoustic
point of view, where only distance to the neighbor and relative orientation of the unit have been required
points of consideration.
Frequently, the geometry of an installation involves some nearby reflecting walls or buildings, which adds to
the acoustic complexity of the site. Let us consider this for three typical situations:
Cases in which reflecting walls modify the radiation pattern of the sound from the unit to the neighbor
Cases in which close-in walls confine the unit and cause a build-up of close-in sound levels
Cases in which the unit is located in a well and all the sound radiates from the top of the wall
1. Effect of Reflecting Walls
Several factors that influence the amount of reflected sound are the following:
1) The sound radiation pattern (directivity) of the equipment
2) The radiating area of the equipment
3) The orientation of the equipment
4) The distance of the unit to the neighbors
5) The distance of the equipment to the reflecting wall
6) The area of the reflecting wall
7) Various angles of incidence and reflection between the equipment, the wall, and the neighbors
Because so many variables are involved, we will not attempt to develop a rigorous procedure for estimating
the influence of a reflecting wall. Rather, we caution that if a large reflecting surface is located near the
equipment, it should be considered as a potential reflector of sound. If the equipment is oriented such that
its loudest side is already facing toward the neighbor, the influence of the reflecting wall can be ignored!
However, if this is not the case, these conditions must be met for the reflected sound to be of concern:
1) The area of the reflecting wall is at least three times the area of the side of the equipment that faces
that wall
2) The distance from the unit to the reflecting wall is less than half the distance from the equipment to
the neighbor
3) If a simple optical ray diagram is drawn from the center of each unit to all parts of the reflecting wall
and the reflecting rays are then drawn away from the wall, the neighbor is located within the angular
range of the reflected rays (see sketch below)
If each of these three conditions is met, then the sound pressure levels at the neighbor may be higher than
if the wall were not there.
T
e
c
h
n
i
c
a
l
R
e
s
o
u
r
c
e
s
J37
...because temperature matters
Neighbor Area Influenced by the Reflecting Wall
In Figures 3 and 4, a few representative reflecting walls are shown for various orientations, and approximate
sound pressure level adjustments are suggested for A, B, C, and D directions away from the equipment.
These adjustments should be made using the 50-foot (15.24 m) levels. Figure 3 applies to units having one
air intake, while Figure 4 applies to units having two air intakes.
As an example, for Case 1, if the neighbor is located off the A side of the unit, apply the A adjustment to the
A side 50-foot sound pressure level rating of the unit and then correct as necessary to the neighbors
distance. If the situation is that of Case 9 and the neighbor is located in the direction D, then the D
adjustment would be utilized to arrive at a 50-foot sound pressure level for the unit.
Figure 3: For Single Air Inlet Units
A
B
C
D
CASE 1
A
B
C
D
CASE 2
A. Use average of A and C levels
B. Use average of B and C levels
C. Not applicable
D. Use average of D and C levels
A. Not applicable
B. Use greater of B level or average of B and A levels
C. No change to C levels
D. Use greater of D level or average of D and A levels
C
C
F
u
n
d
a
m
e
n
t
a
l
s
o
f
S
o
u
n
d
J38
Baltimore Aircoil Company
A
B
C
D
CASE 3
A. Use greater of A level or average of A
and B levels
B. Not applicable
C. No change to C levels
D. Add 2 dB to D levels
A. Use average of A and C levels
B. Not applicable
C. Not applicable
D. Use average of D and C levels
A. Not applicable
B. Not applicable
C. No change to C levels
D. Use average of A, C, D levels
For sound levels out the open end of a 3-sided
enclosure, add 3 dB to the sound pressure levels of
the air intake side of the unit.
CASE 4
A
B
C
D
CASE 5
A
B
C
D
A
B
C
D
CASE 6
T
e
c
h
n
i
c
a
l
R
e
s
o
u
r
c
e
s
J39
...because temperature matters
A
B
C
D
CASE 7
A. Add 2 dB to A levels
B. Use average of B and C levels
C. Not applicable
D. Use average of C and D levels
A
B
C
D
CASE 8
A
B
C
D CASE 9
A. No change to A levels
B. Not applicable
C. No change to C levels
D. Add 3 dB to D levels
A. Not applicable
B. Not applicable
C. Add 2 dB to C levels
D. Add 3 dB to D levels
A
B
C
D
CASE 10
Figure 4: For dual air inlet units
These figures and their associated adjustment values are to be used to correct base 50 ft sound pressure
level ratings in the neighbor direction for the effect of the reflecting surface conditions shown. Instructions on
when and how to do so are presented on page J36.
For sound levels out the open end of a
3-sided enclosure, add 3 dB to the sound
pressure levels of the air intake side(s)
of the unit.
F
u
n
d
a
m
e
n
t
a
l
s
o
f
S
o
u
n
d
J40
Baltimore Aircoil Company
2. Build-Up of Close-In Sound Levels
Evaporative cooling equipment is sometimes located very close to a building wall, inside a court formed by
two or three surrounding walls, or even in a specially provided room or space in the mechanical equipment
area inside a building. In these installations, the principal concern may be the sound in the immediate
vicinity (within 5-10 feet) of the unit(s), rather than the sound levels radiated and reflected away to some
neighbor location.
For these situations, we may use Table 7 to determine approximately the sound pressure levels for the
close-in distances of interest, and then add an increment to account for the build-up of sound levels. Here
also, the geometry of the layout controls the problem and it is not possible to give a general solution that will
cover the multitude of possible layouts. As an approximate acknowledgement of this situation, we suggest
that the close-in sound pressure levels be increased by 5 dB, recognizing that the range of increase could
be as little as 2 or 3 dB (in a fairly open courtyard) and as much as 10 to 15 dB (in a fairly confined
mechanical room enclosure). This adjustment should be applied to all eight-octave band readings.
3. Sound Radiation from a Four-Sided Enclosure or Well
Evaporative cooling equipment is sometimes located inside a four-sided enclosure or well, where all the
sound radiates more-or-less vertically out the top of the well and then spills over the sidewalls of the well.
A simple generalized solution to this problem is not possible, but a reasonable approximation can be made.
While the sidewalls serve as barrier walls against normal sound radiation in horizontal directions, the
four-sided enclosure tends to average-out any free-field directional characteristics of the unit and causes
an average sound pressure level to be radiated from the top of the well in all directions in which sound is
free to radiate per the geometry of the situation. Appendix B provides a procedure for calculating sound
pressure levels for a given sound power level, at various distances and with several radiation patterns.
In the typical case illustrated, where the sound from the well radiates over a hemisphere, the sound
pressure levels of the unit at a 50-foot distance would be determined by subtracting 32 dB from the sound
power levels of the unit.
It should be recognized that this method of sound evaluation is an approximation. Actual sound levels may
be somewhat lower in the higher frequency bands, and could be slightly lower in the lower frequency range
depending upon the neighbor location relative to the equipment. If the sidewall of the well clearly serves as
a barrier wall for the radiated sound, barrier wall attenuation values can be applied to the problem in the
same manner as the sound evaluation procedure of this article subsequently permits for the non-well type
installation.
T
e
c
h
n
i
c
a
l
R
e
s
o
u
r
c
e
s
J41
...because temperature matters
Example Continued
Let us now summarize Step 2 in the sound evaluation process, looking at the source of sound and correcting
it for distance and path. This will yield equipment sound pressure levels for the same point, which the final
noise criterion was calculated in the earlier example.
We are now interested in Items 7-11 in the sample Sound Evaluation Work Sheet (see Appendix D) which
pertain to the cooling tower sound pressure levels as extrapolated to the 300-foot distance. We continue the
step-by-step procedure on the Sound Evaluation Work Sheet where we left off earlier.
Step 7 Decide on the preferred orientation of the cooling tower at the site. From the BAC Sound Rating
Data Sheet (page J33 shows a sample), determine the sound pressure levels at the 50-foot distance for the
side of the cooling tower facing the college classroom. Assume one of the end sides here (the blank-off
sides), since they are the quietest. Insert these sound pressure level values in the Item 7 spaces of the
Sound Evaluation Work Sheet.
Step 8 Insert the distance 300 feet in the appropriate space under Item 8 and refer to Table 6 for the
distance correction values corresponding to 300 feet. Insert these values in eight spaces of Item 8.
Step 9 The sound pressure levels at 300 feet will be lower than at 50 feet, hence subtract the Item 8 values
from the Item 7 values and insert the remainder in the Item 9 spaces. These then are the sound pressure
levels that will exist just outside the college classroom, 300 feet from the cooling tower.
Step 10 Had there been a sound increase due to the presence of a reflecting wall that met one of the
conditions illustrated by Figures 3 or 4, corrections would be inserted now in the Item 10 spaces. Had this
been a close-in problem involving a build-up of sound levels due to some nearby enclosing walls around the
tower, +5 dB would have been inserted in the Item 10 spaces. Since neither of these conditions applied in
this example, we insert 0 in each of the Item 10 spaces.
Step 11 Item 11 is the sum of Items 9 and 10. This is the sound pressure level of the cooling tower at the
300-foot distance.
F
u
n
d
a
m
e
n
t
a
l
s
o
f
S
o
u
n
d
J42
Baltimore Aircoil Company
Example Continued
From the material given in the two preceding sections, it is now possible to determine if a particular cooling
tower will be satisfactory (from a sound point-of-view) in a given location for a given set of circumstances.
The analysis now consists of comparing the estimated cooling tower sound levels with the noise criterion
developed for the neighbor situation. The comparison may be made by plotting the sound levels and the
noise criterion on a graph, as show in Figure 5, or merely by comparing the two groups of values on a
band-by-band basis. We are now interested in Items 12-13.
Step 12 Merely as a means of simplifying the next step, copy in the Item 12 spaces the values taken from
Item 6, which was the Final Noise Criterion.
Step 13 By subtracting the Final Noise Criterion (Item 12) from the Resultant Cooling Tower Sound Pressure
Levels (Item 11), we determine if there is any excess of cooling tower sound above the criterion. Any
positive-valued remainder represents sound excess above the criterion. Any negative-valued remainder
means that the cooling tower level is below the criterion and no sound reduction is required in the frequency
bank; hence, 0 is inserted in that space.
If the cooling tower levels in all eight octave bands are below the criterion values, there should be no sound
problem. If two or three of the cooling tower levels exceed the criterion values by only 1 or 2 or 3 dB, there
will probably be no sound problem. If several octave band sound levels exceed the criterion by 5 to 10 dB,
or more, a sound problem should be anticipated the higher the sound excess the more assured is the
problem if suitable measures are not taken.
Figure 5 - Comparison of Final Noise Criterion and Equipment Sound Levels
10
20
30
40
50
60
70
63 125 250 500 1000 2000 4000 8000
Octave Band Center Frequency - Hz
S
o
u
n
d
P
r
e
s
s
u
r
e
L
e
v
e
l
d
B
R
E
0
.
0
0
0
2
m
i
c
r
o
b
a
r
Final noise criterion (see line 6 & 12 of wksheet) Noise from unit at neighbor location (line 11)
Comparison of Noise Criteria and Evaporative
Cooling Equipment Sound Levels
T
e
c
h
n
i
c
a
l
R
e
s
o
u
r
c
e
s
J43
...because temperature matters
Judgment Factor
At this point, some remarks should be made on the overall reliability of this approach, and an opportunity
should be provided for inserting a judgment factor. In as much as the original criterion selection was based
mostly on lower range NC values for the various environments considered, the derivation presented here
may be somewhat conservative. Because of this, decisions based on this approach will usually lead to
acceptance of the sound from the equipment. As explained throughout the procedure, several
approximations are made (such as for the sound reduction of various general types of walls, and the sound
estimates of community or traffic background sounds, and others). These approximations may lead to some
variability from one installation to the next, although it is believed that a small amount of variability can be
accommodated by the procedure without changing the results unreasonably.
Experience shows that where the criterion is based on sleeping at night, the criterion should not be
exceeded, and therefore, the conclusions reached by this procedure should be followed. However, where the
criterion is based on somewhat less critical daytime activities, and the background sound frequently ranges
considerably above the average minimum conditions used here, then the risk is not too great if the criterion is
exceeded by about 5 dB. In such cases the criterion should not be exceeded by more than 5 dB for fear of
serious objections. If it is decided to permit the sound to exceed the criterion by as much as 10 dB or more,
sound reduction steps should be considered for future addition to the installation, even though they may not
be included in the initial installation.
In view of the above, if the equipments owner, architect or engineer chooses to follow a conservative
approach or even to allow for some excess sound on a particular project (that is, permit the equipments
sound to exceed the background sounds slightly and thus be identifiable and possibly disturbing to the
neighbors), this opportunity is afforded in Items 14 and 15 of the Sound Evaluation Work Sheet.
Step 14 Insert the cooling tower owners Judgment Factor. For a conservative approach insert 0 dB in the
Item 14 spaces of the Work Sheet. To purposely allow the cooling tower sound to exceed the acceptable
levels slightly, insert 5 dB in the Item 14 spaces.
Step 15 The Final Sound Reduction Requirement for the cooling tower is the difference, in each band,
obtained by subtracting Item 14 from Item 13. These are the attenuation values in each octave band
necessary to reduce the cooling tower sound to an acceptable level. A brief discussion of sound control for
evaporative cooling equipment is given in the next section.
Step 16 Sound reduction can be accomplished in several ways, and quantitative values for possible sound
reduction steps are discussed in the next section. Step 16 of the Sound Evaluation Work Sheet should
include the attenuation obtained from the use of two-speed fan motors, ENERGY-MISER
Fan System or a
two-speed motor is a practical option of sound control if reduced equipment loads can be made to coincide
with periods when low sound pressure levels are required. This is a normal nighttime situation for many air
conditioning installations.
An 1800-900 rpm fan motor operating at 900 rpm would provide about 60% of full-load capacity on a BAC
unit and would give approximately the following octave band dB noise reductions:
Evaporative Cooling Equipment
Sound Control
FREQUENCY BAND Hz
63 125 250 500 1000 2000 4000 8000
4 6 8 10 8 8 6 4
T
e
c
h
n
i
c
a
l
R
e
s
o
u
r
c
e
s
J45
...because temperature matters
In as much as these are average dB reductions that can be anticipated for half-speed operation, these
figures can apply to both sound power and sound pressure levels. Also, these approximations are sufficiently
accurate to be used for both centrifugal and axial fan towers.
In addition to running the equipment at a lower speed during noise-critical hours, it is beneficial to investigate
whether or not the equipment could be turned off completely during these hours. This would completely
negate any sound created by the unit; however, the system and its loads must be researched to understand if
this option is feasible.
In some cases what people find objectionable is not the steady sound of the equipment, it is the abrupt
stopping and starting of the fan system. Properly setting the tower control sequence to avoid excessive
cycling of fan motors is important in this regard, as well as to protect the motor from overheating. VFDs
solve this issue by allowing for a soft start of the fans, followed by a gentle ramping up and down of the fan
speed in line with the load requirement. Simply stated, VFD's allow the fan motor to run at the speed
required to meet leaving water temperature requirements rather than running at full speed all the time.
Decreasing the motor speed, and therefore the fan rpm, can decrease sound levels significantly. VFD's also
minimize harsh sounding on-off cycles by providing a gradual start.
Figure 6 - BAC axial fan cooling tower utilizing the ENERGY-MISER
Fan System
Figure 7 - If applicable, turn towers off at night to eliminate sound
F
u
n
d
a
m
e
n
t
a
l
s
o
f
S
o
u
n
d
J46
Baltimore Aircoil Company
Figure 8 - VFD with Integrated Bypass
Oversizing the Equipment
If space and budget allow, it may be beneficial to oversize the equipment and run the larger capacity
equipment at a lower fan speed rated for the specific job. As discussed in the previous section, reducing the
motor speed reduces the fan speed and because fan speed is directly proportional to sound, reduces sound.
Low Sound Fans
Another option for reducing the sound that
the equipment produces is to select a low
sound fan. Low sound fans provide
greater solidity than regular fans and so
are able to move the same amount of air,
while operating at a slower speed.
Barrier Walls
Barrier walls can be used to provide sound
attenuation. In some cases barrier walls may exist due to the architectural treatment of the site, while at
other times they are constructed specifically to provide needed sound reduction.
Taking the first case, a wall used to shield a unit from view can also act to reduce the sound radiated by the
tower, particularly high frequency sound (broadly considered here as the upper four octave frequency
bands). However, such barrier walls must cover by line-of-sight the entire sound source as observed from
the neighbors position. Louvered, latticed or slotted openings will render negligible the attenuation abilities
of a barrier wall. A solid wall of height equal to a unit and located close to it will provide the following
approximate attenuation:
Figure 9 - Axial Fans
T
e
c
h
n
i
c
a
l
R
e
s
o
u
r
c
e
s
J47
...because temperature matters
When greater attenuation is required, a larger specially constructed barrier wall may be designed and
installed. Care must be taken, though, in locating the wall because of the many geometric and material
considerations involved.
As an example, a barrier wall that (1) extends at least 3 to 5 feet (.9 to 1.5m) beyond the line-of-sight in both
the horizontal and vertical directions, (2) that is located within 5 to 8 feet (1.5 to 2.4m) of the cooling tower
and (3) that is made of a solid impervious material having a surface weight of at least 2 lb per sq foot will
have approximately the following attenuation:
A still larger and heavier barrier wall will provide still greater attenuation. To be most effective, however, a
barrier wall must be located as close as possible to the sound source and there must be no reflecting
surfaces in the area that can reflect sound around the barrier.
Design details of barrier walls and other acoustic treatment such as customengineered plenum chambers
and acoustic mufflers are best left to acoustical engineers or consultants and acoustical treatment
manufacturers.
Figure 10 - Architectural walls being constructed around FXV Closed Circuit Cooling Towers
FREQUENCY BAND Hz
63 125 250 500 1000 2000 4000 8000
4 5 5 5 5 6 7 8
FREQUENCY BAND Hz
63 125 250 500 1000 2000 4000 8000
5 5 6 8 10 12 14 16
F
u
n
d
a
m
e
n
t
a
l
s
o
f
S
o
u
n
d
J48
Baltimore Aircoil Company
Sound Attenuation
A significant feature of both axial and centrifugal fan equipment is that its noise, if it is a problem at all, can
be treated with relatively simple package attenuation. Figure 11 is a photograph of a BAC Series 3000
Cooling Tower (axial fan), with sound attenuation on both the intake and discharge of the unit. The fan
intake attenuator is an array of parallel baffles and the discharge treatment is a lined plenum chamber.
Lined plenum chambers, to be effective, (1) must be fairly large, (2) should contain a thick absorbent lining,
and (3) should be arranged such that the sound path through the plenum includes does not allow line-of-
sight. Depending on the degree to which the plenum chamber conforms to these three requirements, its
sound reduction may range in the order of 5 to 10 dB for low frequency noise up to 10 to 20 dB for high
frequency noise.
Some BAC attenuation packages provide a sound reduction in the horizontal direction of about 12 to 17 dB
in the high frequency bands. The attenuation is less in the low frequency bands. Such accessory-type
attenuation can provide an economical solution to most sound problems. Exact values of the attenuation of
these factory-available units can be obtained from BAC Representatives.
Figure 11 - Intake and discharge sound attenuation on a BAC
Series 3000 Cooling Tower
Effects of Sound Reduction Options on
Equipment Performance
The cost of sound attenuation, including the effect on performance, must be evaluated versus simpler
methods such as oversizing the unit(s) to meet the sound criteria for a project. Note that with either low
sound fans or add-on attenuation, lower sound levels often come at the expense of lower airflow. The
system designer must ensure that the manufacturers ratings are adjusted to account for any decrease in
thermal performance from this reduction in airflow.
Another caution is for the use of sound barrier walls. It is necessary for barrier walls to be far enough away
from the tower so as to prevent recirculation of the moist discharge air. If this practice is not followed, the
warm air can be introduced to the air intake, increasing the wet bulb temperature of the unit, and in turn
decreasing the cooling capacity of the tower.
T
e
c
h
n
i
c
a
l
R
e
s
o
u
r
c
e
s
J49
...because temperature matters
Summary
Appendix A
This article provides a simple and direct evaluation method for determining whether or not a given
evaporative cooling equipment installation is producing, or will produce, excess sound. It also offers some
general information on methods that can be used to reduce the sound.
BAC can provide reliable sound level data on its open cooling towers, closed-circuit cooling towers, and
evaporative condensers through their representatives. Consult your local BAC Representative for specific
project applications.
Acknowledgement:
BAC extends its sincere appreciation to Mark E. Schaeffer, P.E. (President of Schaffer
Acoustics Inc. of Pacific Palisades, CA) for his contributions to this article.
The Calculation of Sound Power Level (Lw) From Measured Sound
Pressure Levels (Lp)
Sound power is a measure of the total acoustic power radiated by a sound source. Sound power level is
the sound power, expressed in decibels, relative to the reference power quantity 10
-12
watt.
Sound power is not directly measured as such. Instead, it is a calculated quantity and is obtained from the
measurement of sound pressure levels at a suitable number of measurement positions. Even in indoor
testing with reverberant or semi-reverberant rooms and a standard reference sound source, sound power
level is calculated from sound pressure level measurements. In this discussion, no technical detail is given for
the derivation of sound power level; instead, a very simple procedure is provided for establishing the
approximate sound power level of evaporative cooling equipment for the case in which the sound pressure
level is measured at four horizontal positions (each position at a specific distance from each of the four sides)
plus one vertical position above the unit. The measurement positions may be at any distance between 2 and
4 times the units largest dimension, which is usually its length.
The measured sound pressure levels must be obtained with accurate, calibrated equipment, and the sound
data must be in the conventional eight octave bands of frequency. The measurements should be made
under essentially free-field conditions: i.e., outside in an area free of any nearby reflecting surfaces. The unit
is assumed to be located on the ground or on a platform reasonably close to ground level.
The approximate sound power level in each of the eight octave bands is the sum, by decibel addition, of the
individual five sound pressure level readings in each octave band plus a correction term (K) which is a
function of the number of measurements positions, the measurement distance and the reference power. In
equation form, this can be expressed as
Lw= Lp + K
F
u
n
d
a
m
e
n
t
a
l
s
o
f
S
o
u
n
d
J50
Baltimore Aircoil Company
The decibel summation of a number of sound pressure levels is determined from the material given in
Appendix C and the correction terms are given below in Table A for the appropriate conditions. The use of
the five measurement positions and the decibel addition of the five readings automatically introduce the
directivity characteristics of the unit into the calculated sound power level. No further provision for directivity
is required in this simplified method.
To illustrate this procedure, suppose we wish to estimate the sound power level (Lw) in one octave band for
the case of the five-position measurements 50 feet (15.24 m) from a cooling tower. Assume the five sound
pressure levels measured in the particular frequency band are 56, 53, 59, 53 and 47 dB (re 0.0002
microbar).
By the decibel addition method shown in Appendix C we find that the decibel sum of these five sound
pressure levels is 62 dB. From Table A we then find that for the 50-foot measurement distance, the
correction term is 25 dB re 10
-12
watt. For this example,
Lw = Lp + K
= 62 + 25
= 87 dB
The same procedure could be followed for all octave bands to get the complete Lw of the cooling tower.
The procedure given here is for the specific five measurement positions noted and may not be applicable
generally to other situations. The procedure is not accurate to less than 1 dB, so fractional values of
decibels should not be used or relied upon.
Table A
Correction term K to be used in converting Sound Pressure Levels (Lp) into Sound Power Level (Lw) for
special five-position procedure given
Measurement Distance
(to Acoustic Center) (ft)
Correction Term K for
Lw re 10
-12
Watt (dB)
25 19
30 20
35 21
40 23
45 24
50 25
60 26
70 27
80 29
90 30
100 31
T
e
c
h
n
i
c
a
l
R
e
s
o
u
r
c
e
s
J51
...because temperature matters
The Calculation of Average Sound Pressure Level (Lp) For A Given Sound
Power Level (Lw)
For comparative purposes it may occasionally be necessary to estimate the approximate average sound
pressure level radiated by a unit for which only the sound power level is given. There are also some
applications that are best appraised by converting sound power back to average sound pressure levels. The
procedure outlined in this Appendix will provide this estimate.
It is important to realize that the resulting value is an average sound pressure level that theoretically would be
radiated the same in all directions from the unit. In practice, the unit probably would not radiate the same
levels in all directions; but, when only the sound power level is given it is not possible to know the directivity
characteristics of the unit.
The average sound pressure level at a desired distance is obtained by subtracting from the sound power
level in any given octave frequency band the appropriate correction term (C) from Table B. In equation form,
this relationship is expressed as
Lp
Avg.
= Lw C
As an illustration, suppose we wish to know the average sound pressure at a 50-foot (15.24 m) distance for a
cooling tower that is stated to have a sound power level 87 dB re 10
-12
watt. (Note that this is the
counterpart of the example given in Appendix A.) From Table B, for a 50-foot distance, we see that the
correction term is 32 dB.
Lp
Avg.
= Lw C
= 87 32
= 55 dB
By comparing this value with the five levels fed into the illustration in Appendix A, we see that although this is
an average value, it actually does not equal any of the levels from the five measured directions. Note again
that the average value does not pretend to show the directivity characteristics of the sound source.
If two competitive cooling towers are being compared for a particular site condition, a comparison of the
sound power level or the average sound pressure level may be a general clue to the relative sound from the
two units, but a more careful comparison should take into account the actual sound levels to be radiated in
the particular critical direction(s).
Appendix B
F
u
n
d
a
m
e
n
t
a
l
s
o
f
S
o
u
n
d
J52
Baltimore Aircoil Company
Table B
Correction terms C to be used in converting Sound Power Level into average Sound Pressure Level
for special five-position procedure given.
Note: The correction term C is based on the sound radiating uniformly over a hemisphere. This would apply
for a typical ground level installation or for a unit located on a large roof. If there are conditions such that
the sound will radiate over a large angle, say a 3/4 sphere, add 3 dB to the above C. Subtract 3 dB from
the above C for a 1/4 sphere radiation.
For distance beyond 100 feet (30.48 m) calculate the average Lp for 50 feet (15.24 m) using the method
here; then extrapolate to the desired distance using the Lp reduction values of Table 6 on page J34.
Measurement Distance
(to Acoustic Center) (ft)
Correction Term K for
Lw re 10
-12
Watt (dB)
25 26
30 27
35 28
40 30
45 31
50 32
60 33
70 34
80 36
90 37
100 38
T
e
c
h
n
i
c
a
l
R
e
s
o
u
r
c
e
s
J53
...because temperature matters
Addition of Decibels
Since decibels are logarithmic values it is not proper to add them by normal algebraic addition. For example,
63 dB plus 63 dB does not equal 126 dB but only 66 dB.
A very simple, but adequate schedule for adding decibels is as follows:
When several decibel values are to be added, perform the above operation on any two numbers at a time,
the order does not matter. Continue the process until only a single value remains.
As an illustration let us add the five sound levels used in the example of Appendix B.
Or, suppose we arrange the same numbers in a different order, as in:
Sometimes, using different orders of adding may yield sums that might differ by 1 dB, but this is not too
significant a difference in acoustics. In general, the above simplified summation procedure will yield accurate
sums to the nearest 1 dB. This degree of accuracy is considered acceptable in the material given in this
article.
Appendix C
1 dB
When two decibel
values differ by:
9 dB or more 0 dB
Add the following amount
to the higher value
0 or 1 dB
2 or 3 dB
4 to 8 dB
3 dB
2 dB
= 58
= 60
= 60
= 62
= 54
= 61
= 57
= 62
56
53
56
59
59
53
47
47
53
53
dB
dB
F
u
n
d
a
m
e
n
t
a
l
s
o
f
S
o
u
n
d
J54
Baltimore Aircoil Company
BAC Sound Evaluation Worksheet
Job Name______________________________ Date_____________________________________
Address _______________________________ Engineer ________________________________
Architect ______________________________ BAC Unit_________________________________
Appendix D
63 125 250 500 1000 2000 4000 8000
C
o
m
p
a
r
i
s
o
n
,
C
r
i
t
e
r
i
a
v
s
L
e
v
e
l
s
3. Tabulate sound reduction provided by wall
construction. (Obtain Values from Table 3)
N
o
i
s
e
C
r
i
t
e
r
i
o
n
6. Set final outdoor background Noise Criterion. (high
value, by octave band, of Items 4 and 5)
7. Enter unit sound pressure level rating at 50 ft.
8. Insert distance correction to adjust unit ratings to
distance of ____ ft in direction toward critical neighbor.
(For distances greater than 50 ft use Table 6; for
distances less than 50 ft use Table 7)
S
o
u
n
d
L
e
v
e
l
s
1. Determine appropriate "NC" Criterion for neighbor
activity from ASHRAE Handbook or Table 2 of this article.
4. Establish tentative outdoor Noise Criterion for the unit.
(Item 2 plus Item 3)
5. List average minimum outdoor background sound
levels. (measured, or estimated from Figure 2 and Tables
4, 5)
2. Insert sound pressure levels (Lp) for selected "NC"
Criterion. (Obtain values from Figure 1 or Table 1)
Center Frequency-Hz
NC=
9. Establish outdoor unit Lp at neighbor location. (Item 7
minus Item 8 for distances greater than 50 ft. Item 7 plus
Item 8 for distances less than 50 ft.)
10. Apply reflection adjustment to meet condition existing
at unit site. Refer to Figures 3 and 4 for effect of reflecting
walls; or add 5 dB for close-in build up of noise; 0 dB if no
reflection effects.
16. Indicate estimated or rated attenuation of all sound
reduction treatment if used. (Should at least equal Item
15)
14. Apply judgment factor. (For conservative approach,
use "0" in all bands. To permit unit noise to exceed
background levels slightly, insert "5")
11. Tabulate resultant unit Lp at critical neighbor location.
(Item 9 plus Item 10)
12. Copy Item 6 levels from above. This is the outdoor
noise criterion for the critical neighbor.
13. Ascertain tentative sound reduction required for unit.
(Item 11 minus Item 12. Insert "0" for negative values).
15. Tabulate final sound reduction requirement for the
job. (Item 13 minus Item 14)
Items Steps
P
i
p
i
n
g
C
o
n
s
i
d
e
r
a
t
i
o
n
s
J55
...because temperature matters
Piping Considerations
Maximum Fluid Velocity
BAC designs its standard evaporative cooling products to limit fluid velocities to approximately 10 feet per
second (fps) through all piping connection points. This generally accepted piping practice is recommended
for a variety of reasons:
Friction Loss: Higher fluid velocities increase friction losses (commonly referred to as pressure drop),
resulting in increased pump energy costs.
Noise and Vibration: Systems designed to current codes minimize excessive noise or vibration
when the fluid velocity is held to 10 fps.
Erosion / Corrosion: Fluids have a greater propensity to damage the inside walls of pipe at high
velocities. The effect of velocity is increased with chemically aggressive fluids or fluids with a high amount of
solids entrained in the fluid stream.
Hydraulic Shock: Also known as water hammer, hydraulic shock can cause excessive damage
when a line is shut down suddenly. Maintaining a low fluid velocity will substantially reduce the impact of
hydraulic shock.
BAC Standard Connection Sizes
GPM = (U.S.) Gallons Per Minute
BACs Closed Circuit Cooling Tower selection software is programmed to automatically select the appropriate
quantity and size of entering and leaving process fluid connections, to maintain the limits listed above. Only
by specific customer request and acceptance will BAC provide evaporative cooling products designed for
higher velocities. Fewer connection points and smaller pipe sizes associated with high fluid velocities may
reduce installation costs, but the customer must also consider the increased operating costs and equipment
maintenance concerns. Successful operation of BACs equipment in the system is based on established
industry principles.
Connection
Diameter
Maximum Flow
Max. Fluid
Velocity
Connection
Diameter
Maximum
Flow
Max. Fluid
Velocity
3 225 GPM 10.2 fps 10 2,300 GPM 9.4 fps
4 400 GPM 10.2 fps 12 3,200 GPM 9.1 fps
6 900 GPM 10.2 fps 14 3,700 GPM 7.8 fps
8 1,600 GPM 10.2 fps 16 4,650 GPM 6.7 fps
C
o
o
l
i
n
g
T
o
w
e
r
P
u
m
p
i
n
g
&
P
i
p
i
n
g
J56
Baltimore Aircoil Company
This section courtesy of ITT Industries, Inc.