RT Svx21f en (3 10 Ton Iom)
RT Svx21f en (3 10 Ton Iom)
RT Svx21f en (3 10 Ton Iom)
Operation and
Maintenance
Packaged Gas/Electric
3 - 10 Ton
Model Numbers:
YSC036A - YSC120A YHC036E - YHC060E
YHC033A - YHC120A YSC072 - YSC120E
YSC036E - YSC060E
WARNING
R410a Refrigerant under
Higher Pressure than R-22!
R-410A refrigerant systems operate
at higher pressures than standard R-
22 systems. Do not use R-22 service
equipment or components on R-
410A refrigerant equipment. Using
service equipment not rated for R-
410A could result in the equipment
exploding under higher pressure
which could result in death or
serious injury.
WARNING
Equipment Damage From
Ultraviolet (UV) Lights!
The manufacturer does not
recommend field installation of
ultraviolet lights in its equipment for
the intended purpose of improving
indoor air quality. High intensity C-
band ultraviolet light is known to
severely damage polymer (plastic)
materials and poses a personal
safety risk to anyone exposed to the
light without proper personal
protective equipment. Polymer
materials commonly found in HVAC
equipment that may be susceptible
include insulation on electrical
wiring, fan belts, thermal insulation,
various fasteners and bushings.
Degradation of these materials could
result in serious damage to the
equipment.
The manufacturer accepts no
responsibility for the performance or
operation of our equipment in which
ultraviolet devices were installed
outside of the manufacturer’s factory
or its approved suppliers.
NOTICE
Roof Damage!
System contains oil and refrigerant
under high pressure. Roofs should be
protected from exposure to oils and
refrigerant in the system. If rooftop is
not protected damage to the roof
could occur.
RT-SVX21F-EN 3
Contents
Hazard Identification . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Unit Inspection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Storage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Overview of Manual . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Model Number Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
General Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Unit Clearances . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Unit Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Pre-Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Installation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Foundation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Roof Curb . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
General Unit Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Horizontal Discharge Conversion . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
TCO-1 Instructions: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Horizontal Discharge Conversion . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Return Air Smoke Detector . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Through the Base Gas Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
Requirements for Gas Heat . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
Filter Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
Field Installed Power Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
Main Unit Power . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
Main Unit Power . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
Controls using DC Analog Input/Outputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
Smoke Detector
Customer Low Voltage Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
Space Temperature Averaging . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
Voltage Imbalance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
Electrical Phasing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
Pre-Start. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
Test Modes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
Verifying Proper Air Flow . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
ReliaTel™ Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
Electro Mechanical Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
Verifying Proper Air Flow . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
Start-Up . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
Verifying Proper Air Flow . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
Return Air Smoke Detector . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
Economizer Start-Up . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
Compressor Start-Up . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
Final System Setup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
Fan Belt Adjustment - Belt Drive Units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
Monthly Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
Filters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
4 RT-SVX21F-EN
Contents
Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
Annual Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
Final Process . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
ReliaTel™ Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45
System Status Checkout Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45
Trouble Shooting. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45
Resetting Cooling and Ignition Lockouts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46
Zone Temperature Sensor (ZTS) Service Indicator . . . . . . . . . . . . . . . . . . . . . . . . . . 46
Clogged Filter Switch . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47
Fan Failure Switch . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47
Zone Temperature Sensor (ZTS) Test . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47
Unit Economizer Control (ECA) Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . 48
Resetting Cooling and Ignition Lockouts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
Unit Economizer Control (ECA) Test Procedures . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
Wiring Diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50
Combination Gas Electric Air Conditioner . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52
Limited Warranty . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52
Combination Gas Electric Air Conditioner . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53
RT-SVX21F-EN 5
Model Number Description
Y H C 033 A 3 R B A ** C 0 0 0 A 1 0 0 0 1 A 1
1 2 3 456 7 8 9 10 11 12,13 14 15 16 17 18 19 20 21 22 23 24 25
6 RT-SVX21F-EN
Model Number Description
2. Available for R-410A units only. 21. Novar Sensor utilized with digit
21 = (4) Novar 3051 Controls
3. Standard on all 15 SEER and 4-5 without Zone Sensor.
Tons Heat Pump R-22 units.
4. Not available with
electromechanical controls.
5. Manual outside air damper will
ship factory supplied within the
unit, but must be field installed.
6. High pressure control is standard
on all units.
7. Multispeed direct drive standard
on single-phase and 15 SEER
products. Belt drive standard on
three-phase 13 SEER and 6-10
RT-SVX21F-EN ton R410a products. 7
General Information
8 RT-SVX21F-EN
General Information
nominally, the RTRM will shut off all (if installed), and a manual reset will Power Exhaust Control
mechanical operations, lock the be required to restart the (Optional)
system out, send a diagnostic to ICS, compressor.
and the SERVICE output will flash.
ReliaTel Control
The system will remain locked out Low Pressure Control
until a reset is initiated either The power exhaust fan is started
manually or through ICS. ReliaTel Control whenever the position of the
economizer dampers meets or
Clogged Filter Switch (Optional) When the LPC is opened for 1 exceed the power exhaust setpoint
continuous second, the compressor when the indoor fan is on.
The unit mounted clogged filter for that circuit is turned off
switch monitors the pressure immediately. The compressor will With the optional ventilation override
differential across the return air not be allowed to restart for a accessory, the power exhaust fan is
filters. It is mounted in the filter minimum of 3 minutes. independent of the indoor fan.
section and is connected to the The setpoint panel is located in the
RTOM. A diagnostic SERVICE signal If four consecutive open conditions
occur during an active call for return air section and is factory set at
is sent to the remote panel if the 25%.
pressure differential across the filters cooling, the compressor will be
is at least 0.5" w.c. The contacts will locked out, a diagnostic
communicated to ICS™, if applicable, Electromechanical Control
automatically open when the
pressure differential across the filters and a manual reset required to The power exhaust fan is started
decreases to approximately 0.4" w.c. restart the compressor. On dual whenever the indoor fan is on and
The clogged filter output is energized compressor units only the affected the adjustable damper limit switch
when the supply fan is operating and compressor circuit is locked out. DLS is closed.
the clogged filter switch has been
closed for at least 2 minutes. The Electromechanical Control Lead/Lag Control
system will continue to operate When the LPC is opened, the (Dual Circuit Only)
regardless of the status of the filter compressor for that circuit is turned
switch. off immediately. The compressor will ReliaTel Control Only
Note: On units equipped with restart when the LPC closes.
factory installed MERV 13 Lead/Lag is a selectable input located
on the RTRM. The RTRM is
filters, a clogged filter switch High Pressure Control configured from the factory with the
with different pressure (Optional — except on
settings will be installed. Lead/Lag control disabled. To
This switch will close when
R-410A units) activate the Lead/Lag function,
the differential pressure is simply cut the wire connected to J3-8
approximately 0.8' w.c. and ReliaTel Control at the RTRM. When it is activated,
open when the differential each time the designated lead
The high pressure controls are wired compressor is shut off due to the
falls to 0.7" w.c. in series between the compressor load being satisfied, the lead
outputs on the RTRM and the compressor or refrigeration circuit
Compressor Disable (CPR1/2) compressor contactor coils. If the switches. When the RTRM is
This input incorporates the low high pressure control switch opens, powered up, i.e. after a power failure,
pressure control (LPC) of each the RTRM senses a lack of current the control will default to the number
refrigeration circuit and can be while calling for cooling and locks the one circuit compressor.
activated by opening a field supplied compressor out.
contact installed on the LTB. If four consecutive open conditions Zone Sensor Module (ZSM)
If this circuit is open before the occur during an active call for (BAYSENS106*)
compressor is started, the cooling, the compressor will be
locked out, a diagnostic This electronic sensor features three
compressor will not be allowed to
communicated to ICS™, if applicable, system switch settings (Heat, Cool,
operate. Anytime this circuit is
and a manual reset required to and Off) and two fan settings (On
opened for 1 continuous second
during compressor operation, the restart the compressor. On dual and Auto). It is a manual changeover
compressor for that circuit is compressor units only the affected control with single setpoint. (Cooling
immediately turned “Off”. The compressor circuit is locked out. Setpoint Only)
compressor will not be allowed to
restart for a minimum of 3 minutes Electromechanical Control
should the contacts close. When the HPC is opened, the
If four consecutive open conditions compressor for that circuit is turned
occur during the first three minutes off immediately. The compressor will
of operation, the compressor for that restart when the HPC closes.
circuit will be locked out, a diagnostic
communicated to the remote panel
RT-SVX21F-EN 9
General Information
Zone Sensor Module (ZSM) The Zone Sensor allows selection of Remote Zone Sensor
(BAYSENS108*) 2, 3 or 4 system modes (Heat, Cool, (BAYSENS016*)
Auto, and Off), two fan modes (On
This electronic sensor features four and Auto). It has dual temperature This bullet type temperature sensor
system switch settings (Heat, Cool, selection with programmable start can be used for; outside air (ambient)
Auto, and Off) and two fan settings time capability. sensing, return air temperature
(On and Auto). It is a manual or auto sensing, supply air temperature
changeover control with dual The occupied cooling set point sensing, remote temperature sensing
setpoint capability. It can be used ranges between 45 and 98 degrees (uncovered. Wiring procedures vary
with a remote zone temperature Fahrenheit. The heating set point according to the particular
sensor BAYSENS077*. ranges between 43 and 96 degrees application and equipment involved.
Fahrenheit. Refer to the unit’s wiring diagrams
Zone Sensor (BAYSENS110*) A liquid crystal display (LCD) displays for proper connections.
zone temperature, temperature set
This electronic sensor features four points, day of the week, time, and Remote Zone Sensor
system switch settings (Heat, Cool, operational mode symbols.
Auto, and Off) and two fan settings (BAYSENS077*)
(On and Auto) with four system The Option Menu is used to enable or This electronic sensor can be used
status LED’s. It is a manual or auto disable applicable functions, i.e.; with BAYSENS006B, 008B, 010B,
changeover control with dual Morning Warm-up, Economizer 019B Remote Panels. When this
setpoint capability. It can be used minimum position override during sensor is wired to a BAYSENS019B
with a remote zone temperature unoccupied status, Fahrenheit or Remote Panel, wiring must be 18
sensor BAYSENS077*. Centigrade, Supply air tempering, AWG Shielded Twisted Pair (Belden
Remote zone temperature sensor, 12/ 8760 or equivalent). Refer to The
Wall Mounted Relative 24 hour time display, Smart fan, and specific Remote Panel for wiring
Computed recovery. details.
Humidity Sensor
(BAYSENS036*) During an occupied period, an
auxiliary relay rated for 1.25 amps @ Electro Mechanical Control
Field installed, wall mounted 30 volts AC with one set of single
humidity sensor is used to control pole double throw contacts is The unit must have a Thermostat to
activation of the hot gas reheat activated. operate.
dehumidification option. Humidity • BAYSTAT036A
set points can be selected for relative Status Inputs (4 Wires
humidity levels between 40% and – Single Stage - 1 Heat/1 Cool
60% by adjusting the DEHUMID
Optional)
• BAYSTAT037A
setting on the ReliaTel Options The ZSM can be wired to receive four
Module. See Figure 29 on page 28. – Multi Stage - 2 Heat/2 Cool -
(4) operating status signals from the
Can be Used for Economizer
RTRM (HEAT, COOL, SYSTEM “ON”,
Operation
Duct Mounted Relative SER-VICE).
Humidity Sensor • BAYSENS025A
Four (4) wires from the RTRM should
(BAYSENS037*) be connected to the appropriate – Remote sensor for
terminals (7, 8, 9 & 10) on the ZSM. BAYSTAT036A and
Field installed, duct mounted BAYSTAT037A
humidity sensor is used to control
activation of the hot gas reheat Remote Zone Sensor
dehumidification option. Humidity (BAYSENS073*) High Temperature Sensor
set points can be selected for relative (BAYFRST001A)
This electronic sensor features
humidity levels between 40% and remote zone sensing and timed This sensor connects to the RTRM
60% by adjusting the DEHUMID override with override cancellation. It Emergency Stop Input on the LTB
setting on the ReliaTel Options is used with a Trane Integrated and provides high limit “shutdown”
Module. See Figure 29 on page 28. Comfort™ building management of the unit. The sensor is used to
system. detect high temperatures due to fire
Programmable Zone Sensor - in the air conditioning or ventilation
(BAYSENS119*) Remote Zone Sensor ducts. The sensor is designed to
mount directly to the sheet metal
This 7 day programmable sensor (BAYSENS074*) duct. Each kit contains two sensors.
features 2, 3 or 4 periods for This electronic sensor features single The return air duct sensor
Occupied or Unoccupied setpoint capability and timed (X1310004001) is set to open at 135 F.
programming per day. If the power is override with override cancellation. It The supply air duct sensor
interrupted, the program is retained is used with a Trane Integrated (X1310004002) is set to open at 240 F.
in permanent memory. If power is off ComfortTM building management The control can be reset after the
for an extended period of time, only system. temperature has been lowered
the clock and day may have to be approximately 25 F below the cutout
reset. setpoint.
10 RT-SVX21F-EN
General Information
Evaporator Frost Control from performing it's design unit operation.The power supply
(ReliaTel™ Option) function. circuit is not balanced with the
proper phase sequence of L1, L2, L3
This input incorporates the Frostat™ Note: Airflow through the unit is
for the 3 conductors of a 3 phase
control (FOS) mounted in the indoor affected by the amount of dirt
circuit. The line to line voltage is not
coil circuit and can be activated by and debris accumulated on
between 180 volts and 633 volts
closing a field supplied contact the indoor coil and filters. To
installed in parallel with the FOS. insure that airflow through
the unit is adequate for
If this circuit is open before the proper sampling by the
compressor is started, the return air smoke detector,
compressor will not be allowed to complete adherence to the
operate. Anytime this circuit is maintenance procedures,
opened for 1 continuous second including recommended
during compressor operation, the intervals between filter
compressor for that circuit is changes, and coil cleaning is
immediately turned “Off”. The required.
compressor will not be allowed to
restart for a minimum of 3 minutes Note: Periodic checks and
should the FOS close. maintenance procedures
must be performed on the
smoke detector to insure that
(Electro Mechanical Option) it will function properly. For
This input incorporates the Frostat™ detailed instructions
control (FOS) mounted in the indoor concerning these checks and
coil circuit and can be activated by procedures, refer to the
opening a field supplied contact appropriate section(s) of the
installed in series with the FOS. smoke detector Installation
and Maintenance Instructions
If this circuit is open before the provided with the literature
compressor is started, the package for this unit.
compressor will not be allowed to
operate. Anytime this circuit is In order for the supply air smoke
opened during compressor detector or return air smoke detector
operation, the compressor for that to properly sense smoke in the
circuit is immediately turned “Off”. supply air stream or return air
The compressor will restart when the stream, the air velocity entering the
FOS closes. smoke detector unit must be
between 500 and 4000 feet per
Smoke Detector Sensor minute. Equipment covered in this
manual will develop an airflow
(Optional) velocity that falls within these limits
This sensor is only applicable on over the entire airflow range
units equipped with a RTOM. It specified in the evaporator fan
provides high limit “shutdown” of performance tables.
the unit and requires a manual reset. There are certain models, however, if
The sensor is used to detect smoke operated at low airflow, will not
due to fire in the air conditioning or develop an airflow velocity that falls
ventilation ducts. within the required 500 to 4000 feet
Note: The supply and return air per minute range. For these models,
smoke detectors are the design airflow shall be greater
designed to shut off the unit if than or equal to 1000 feet per minute
smoke is sensed in the supply MINIMUM.
air stream or return air
stream. This function is Phase Monitor
performed by sampling the
airflow entering the unit at This sensor monitors voltage
the return air opening. Follow between the 3 conductors of the 3
the instructions provided phase power supply. Two LED lights
below to assure that the are provided. The green light
airflow through the unit is indicates that a balanced 3 phase
sufficient for adequate supply circuit is properly connected.
sampling. Failure to follow The red light indicates that unit
these instructions will operation has been prevented. There
prevent the smoke detectors are two conditions that will prevent
RT-SVX21F-EN 11
Unit Dimensions
Figure 1. Typical Installation Clearances for Single & Multiple Unit Applications
12 RT-SVX21F-EN
Unit Dimensions
Figure 2. Unit Dimensional Data YHC033A, Y(H/S)C036A, YHC043A, Y(H/S)C048A — Low and Medium Heat
YSC060A — Low and Medium Heat
1775
Figure 3. YHC033A, Y(H/S)C036A, YHC043A,Y(H/S)C048A — High Heat YSC060A — High Heat YHC060A, YHC063A
— Low, Medium, and High Heat YSC036E, YSC048E, YSC060E, YHC036E
1775
RT-SVX21F-EN 13
Unit Dimensions
Figure 4. Unit Dimensional Data Y(H/S)C072A, YSC090A, YSC092A, YHC048E, YHC060E, YSC072E
14 RT-SVX21F-EN
Pre-Installation
WARNING
Fiberglass Wool!
Product contains fiberglass wool.
Disturbing the insulation in this
product during installation,
maintenance or repair will expose
you to airborne particles of glass
wool fibers and ceramic fibers
known to the state of California to
cause cancer through inhalation.
Glass wool fibers may also cause
respiratory, skin or eye irritation.
Precautionary Measures
• Avoid breathing fiberglass dust.
• Use a NIOSH approved dust/
mist respirator.
• Avoid contact with the skin or
eyes. Wear long-sleeved, loose-
fitting clothing, gloves, and eye
protection.
• Wash clothes separately from
other clothing: rinse washer
thoroughly.
• Operations such as sawing,
blowing, tear-out, and spraying
may generate fiber
concentrations requiring
additional respiratory
protection. Use the appropriate
NIOSH approved respiration in
these situations.
RT-SVX21F-EN 15
Installation
16 RT-SVX21F-EN
Installation
Table 1. Typical unit weights and point Table 2. Typical accessory weights
loading data (continued)
Weight - Net lbs
Center of YHC033 YH/ YH/
Net Corner Wt. (lbs) Gravity (In.)
Weight Option/Accessory , 043, YSC036- YSC072-
Unit Model (lbs) A B C D Length Width Description 063 060 120
YHC048A(3,4,W)*(L,M,X,Y) 511 157 126 108 121 32 20 Power Exhaust N/A N/A 80
YHC048A(3,4,W)*(H,Z) 539 166 133 114 126 32 20 Belt Drive Motor Standard 31 Standard
(3 phase only)
YHC048E1, E3, E4 790 173 145 266 141 40 25
Hinged Access 10 10 12
YHC060A1*(L,M) 562 176 137 116 133 31 20
Hail Guard 12 12 20
YHC060A1*(H,Z) 574 179 140 119 136 32 20
Through the Base: 8 8 13
YHC060A(3,4,W)*(L,M,X,Y) 550 175 133 110 131 31 19 Electrical
YHC063A(3,4,W)*(L,M,X,Y) 612 180 151 144 137 31 19 Through the Base: 5 5 5
Gas
YHC060A(3,4,W)*(H,Z) 561 178 137 113 134 31 19
Unit Disconnect 5 5 5
YHC063A(3,4,W)*(H,Z) 561 178 137 113 134 31 19
Switch
YHC060E1, E3, E4 748 222 92 345 89 41 24
Unit Circuit Breaker 5 5 5
YHC072A(3,4,W)*(L,X) 756 245 193 137 181 39 22
Conv. Outlet: 2 2 2
YHC072A(3,4,W)*(M,Y) 768 248 197 140 183 39 22 Unpowered
RT-SVX21F-EN 17
Installation
Foundation
Figure 9. 3-5 ton R-22, 3-5 ton Standard Efficiency R-410A, 3 ton
Horizontal Units High Efficiency R-410A Down flow Unit Supply & Return
Air Opening
If the unit is installed at ground level,
elevate it above the snow line.
Provide concrete footings at each
support location with a “full
perimeter” support structure or a
slab foundation for support. Refer to
Table 1, “Typical unit weights and
point loading data,” on page 16 for
the unit’s operating and point loading
weights when constructing a footing
foundation.
If anchoring is required, anchor the
unit to the slab using hold down
bolts or isolators. Isolators should be
installed to minimize the
transmission of vibrations into the
building.
For rooftop applications, ensure the
roof is strong enough to support the
combined unit and support structural
weight. Refer to Table 1, p. 16 for the
unit operating weights. If anchoring
is required, anchor the unit to the
roof with hold-down bolts or
isolators.
Check with a roofing contractor for
proper waterproofing procedures.
Figure 8. 3-5 ton R22, 3-5 ton Standard Efficiency R410a, 3 ton
High Efficiency R410a Horizontal Unit Supply & Return
Air Opening
18 RT-SVX21F-EN
Installation
Figure 10. 4-5 ton High Efficiency R410a, 6-10 ton R22 and R410a Roof Curb
Horizontal Unit Supply & Return Air Opening
Down flow
The roof curbs for these units
consists of a “full perimeter”
enclosure to support the unit.
Before installing any roof curb,
verify;
Return • it is the correct curb for the unit,
Supply • it includes the necessary gaskets
and hardware,
• the purposed installation
location provides the required
clearance for proper operation,
• the curb is level and square. The
top surface of the curb must be
true to assure an adequate curb-
to-unit seal.
WARNING
Combustible Materials!
Maintain proper clearance between
Figure 11. 4-5 ton High Efficiency R410a, 6-10 ton R22 and R410a the unit heat exchanger, vent
Down flow Unit Supply & Return Air Openings surfaces and combustible materials.
Refer to unit nameplate and
installation instructions for proper
clearances. Improper clearances
could result in a fire hazard. Failure to
maintain proper clearances could
result in death or serious injury or
property damage.
Verify that appropriate materials
were used in the construction of roof
and ductwork. Combustible materials
should not be used in the
construction of ductwork or roof curb
that is in close proximity to heater
elements or any hot surface. Any
combustible material on the inside of
the unit base should be removed and
replaced with appropriate material.
Step-by-step curb assembly and
installation instructions ship with
each accessory roof curb kit. Follow
the instructions carefully to assure
Ductwork proper fit-up when the unit is set into
place.
Figure 8, p. 18 illustrates the supply When attaching the ductwork to the
and return air openings as viewed Note: To assure proper condensate
unit, provide a water tight flexible
from the rear of the unit. flow during operation, the
connector at the unit to prevent
unit (and curb) must be level.
Elbows with turning vanes or operating sounds from transmitting
splitters are recommended to through the ductwork. If the unit is elevated, a field
minimize air noise due to turbulence constructed catwalk around the unit
All outdoor ductwork between the
and to reduce static pressure. is strongly recommended to provide
unit and the structure should be
easy access for unit maintenance and
weather proofed after installation is
service.
completed.
Recommendations for installing the
Supply Air and Return Air ductwork
RT-SVX21F-EN 19
Installation
joining the roof curb are included in not use cables, chains, or slings • Verify that the installation
the curb instruction booklet. Curb except as shown. location of the unit will provide
ductwork must be fabricated and the required clearance for proper
4. Install a lifting bar, as shown in
installed by the installing contractor operation.
Figure 7, p. 17, to protect the unit
before the unit is set into place.
and to facilitate a uniform lift. • Assemble and install the roof
Note: For sound consideration, cut The minimum distance between curb (if applicable). Refer to the
only the holes in the roof the lifting hook and the top of the latest edition of the curb
deck for the ductwork unit should be 7 feet. installers guide that ships with
penetrations. Do not cut out each curb kit.
5. Test-lift the unit to ensure it is
the entire roof deck within the
properly rigged and balanced, • Fabricate and install ductwork;
curb perimeter.
make any necessary rigging secure ductwork to curb.
adjustments.
If a Curb Accessory Kit is not • Install pitch pocket for power
used: 6. Lift the unit enough to allow the supply through building roof. (If
removal of two Fork Lift brackets applicable)
• The ductwork can be attached and hardware. Remove the two
directly to the factory-provided • Rigging the unit.
Fork Lift brackets, two metal
flanges around the unit’s supply runners and three wooden • Set the unit onto the curb; check
and return air openings. Be sure boards as shown in the following for levelness.
to use flexible duct connections Figure.
at the unit. • Ensure unit-to-curb seal is tight
and without buckles or cracks.
• For “built-up” curbs supplied by
others, gaskets must be installed Figure 12. Fork pocket • Install and connect a condensate
around the curb perimeter flange drain line to the evaporator drain
and the supply and return air connection.
opening flanges.
Factory Installed Economizer
Rigging • Ensure the economizer has been
A Rigging illustration and Center-of- pulled out into the operating
Gravity dimensional data table is position. Refer to the economizer
shown in Figure 7, p. 17. Refer to the installers guide for proper
typical unit operating weights table position and setup.
before proceeding. • Install all access panels.
7. Down flow units; align the base
1. Remove all drill screws fastening rail of the unit with the curb rail
wood protection to metal while lowering the unit onto the Temperature Limit Switch
baserail. Remove all screws curb. Make sure that the gasket Usage for Gas Heat Units
securing wooden protection to on the curb is not damaged
wooden top crate. Units are factory shipped in the down
while positioning the unit.
flow discharge configuration but can
2. Remove Wooden Top Crate. be field converted to a horizontal
General Unit
WARNING
discharge configuration. Some, but
Requirements not all units require a different TCO1
Heavy Objects! limit switch, which is attached to the
Do not use cables (chains or slings) The checklist listed below is a combustion blower motor if
except as shown. Each of the cables summary of the steps required to horizontal discharge configuration is
(chains or slings) used to lift the unit successfully install a commercial used.
must be capable of supporting the unit. This checklist is intended to
Note: The following units require a
entire weight of the unit. Lifting acquaint the installing personnel
limit switch change out for
cables (chains or slings) may not be with what is required in the
horizontal discharge. The
of the same length. Adjust as installation process. It does not
additional limit switch is
necessary for even unit lift. Other replace the detailed instructions
shipped attached to the
lifting arrangements may cause called out in the applicable sections
combustion blower housing.
equipment or property-only damage. of this manual.
Proceed to the Horizontal
Failure to properly lift unit could • Check the unit for shipping Discharge Conversion, Step 5
result in death or serious injury. See damage and material shortage; on page 24 for the following
details below. file a freight claim and notify models "ONLY".
3. Rig the unit as shown in Figure 7, appropriate sales representative. Y*C072A**(H,Z),
p. 17. Attach adequate strength YSC090A**(H,Z),
• Verify correct model, options and
lifting slings to all four lifting YSC092A**(H,Z),
voltage from unit nameplate.
brackets in the unit base rail. Do YHC092A**(M,Y),
YHC092A**(H,Z),
Y*C102A**(H,Z),
20 RT-SVX21F-EN
Installation
If any of the aforementioned units are Y*C060A**(H,Z) 170F / 200F YHC060E**(M,Y)-BD 170F
installed in the down flow discharge Y*C072A**(L,X) 170F YHC060E**(H,Z)-DD 190F/220F
configuration, remove the additional
Y*C072A**(M,Y) 155F YHC060E**(H,Z)-BD 220F/230F
TCO1 limit switch from the
combustion blower motor and Y*C072A**(H,Z) 145F/155F
discard. YSC072E**(M,Y) 155F Horizontal Discharge
BD= Belt drive ID motor YSC072E**(L,X) 170F Conversion
DD= Direct drive ID motor YSC072E**(H,Z) 145F/155F
YSC090A**(L,X) 155F 3 Through 5 Ton Units
YSC090A**(M,Y) 170F Supplies Needed by Installer for
Table 3. TC01 tripping values
YSC090A**(H,Z) 180F/220F Conversion: 3 oz. tube of High
TCO1 Tripping Temperature RTV sealant. (500°F /
Values Down YHC092A**(L,X) 225F
260°C: Similar to Dow Corning 736)
Unit Model flow/ Horizontal
YHC092A**(M,Y) 180F/220F
YHC033A**(L,X) 170F Note: Failure to use recommended
YHC092A**(H,Z) 200F /260F sealant could result in unit
YHC033A**(M,Y) 220F
YSC092A**(L,X) 155F performance loss.
YHC033A**(H,Z) 210F
YSC092A**(M,Y) 170F If a unit is to be converted to a
YSC036E**(L,X)-DD 180F Horizontal discharge, the following
YSC092A**(H,Z) 180F/220F
YSC036E**(L,X)-BD 170F conversion must be performed:
YSC092E**(L,X) 225F
Y*C036A**(L,X) 170F 1. Remove RETURN and SUPPLY
YSC092E**(M,Y) 180F / 220F
YSC036E**(M,Y)-DD 170F/190F duct covers.
YSC092E**(H,Z) 220F /260F
YSC036E**(M,Y)-BD 180F/190F 2. Locate supply cover. Apply ¼ in.
Y*C102A**(L,X) 225F
Y*C036A**(M,Y) 220F (6mm.) continuous bead of 500°F
Y*C102A**(M,Y) 230F
RTV sealant to the flange as
YSC036E**(H,Z)-DD 170F/190F
Y*C102A**(H,Z) 200F / 260F shown.
YSC036E**(H,Z)-BD 155F/190F
Y*C102E**(L,X) 225F
Y*C036A**(H,Z) 210F
YSC102E**(M,Y) 230F
YHC043A**(L,X) 170F
YSC102E**(H,Z) 200F / 260F
YHC043A**(M,Y) 170F
Y*C120A**(L,X) 230F
YHC043A**(H,Z) 180F /220F
Y*C120A**(M,Y) 190F / 260F
YSC048E**(L,X)-DD 180F
Y*C120A**(H,Z) 230F / 210F
YSC048E**(L,X)-BD 170F
YSC120E**(L,X) 230F
Y*C048A**(L,X) 170F
RT-SVX21F-EN 21
Installation
2. Place SUPPLY DUCT COVER over required for the unit 3. Replace and discard the existing
down-flow return opening. undergoing installation. TCO1 originally installed at the
(insulation side down) factory for down flow operation
6. After completing installation of
with the TCO1 shipped attached
3. Using self-drilling screws, (or the duct covers for horizontal
to the combustion blower for
screws removed from duct discharge, proceed to TCO-1
horizontal operation.
cover), screw through dimples to instructions.
attach DUCT COVER to base. 4. Replace heat section access
panel.
Figure 19. Duct cover
Figure 17.
Figure 20.
Supply Duct Cover
Insulation side
down
Screw into 4
Return duct
dimples on top Insulation side up
cover
edge
RT-SVX21F-EN 23
Installation
24 RT-SVX21F-EN
Installation
4. Using pipe sealant, attach the 6 piping in excess of 0.50 psig or 6. 6. Replace evaporator access
1/2" nipple and gas shutoff 14 " W.C. to prevent component panel and supply air access
assembly to the 90° elbow on the failure. panels.
gas supply line.
• Drip leg Installed in the gas
5. Using pipe sealant, attach the 5" piping near the unit. To convert drain condensate
pipe nipple and union to the through the base of unit:
• Minimum gas supply pressure
street el attached to the gas
should be 4.5" W.C. 1. Remove evaporator access
valve.
• Maximum gas supply pressure panel and supply air access
6. Connect 5" pipe nipple and union panels.
must not exceed 14.0" W.C.
to 6 1/2" nipple and gas shutoff
assembly. • Manifold pressure for single 2. Remove the support panel that
stage heaters should be set to the condensate drain pan exits
3.3" W.C. through.
Figure 24. Typical through the base
• Manifold pressure for two stage 3. Slide the condensate drain pan
gas installation out of the unit.
heaters should be set to 3.5"
W.C. on HIGH FIRE and 1.8" W.C. 4. Place on a level surface in the
on LOW FIRE. position it was removed from the
• Flue Exhaust clear of any unit.
obstruction. 5. Remove the plug knockout in the
bottom of the drainpan to
Condensate Drain convert it to through the base
Configuration drainage.
An evaporator condensate drain 6. Plug the original condensate
connection is provided on each unit. drain opening with a field
Refer to Figure 8, p. 18 and Figure 10, supplied 3/4" NPT plug.
p. 19 for the appropriate drain 7. Slide the condensate drain pan
location. back into the unit, align the drain
The condensate drain pan is factory support with the grommeted
installed to drain condensate to the opening in the rear support
Requirements for Gas back side of the unit. See Figure 8, panel and push until the support
p. 18 and Figure 10, p. 19. It can be is seated in the grommet.
Heat converted to drain condensate out 8. Replace the front support panel
Note: The unit gas train and the front side of the unit or through by aligning the panel with tabs in
Optional Through The Base the base. the raceway. Align the plugged
Gas Shut-Off Valve are rated To convert drain condensate out the condensate drain pan coupling
at 1/2 PSIG maximum. A front of unit: in the grommeted hole as the
pressure reducing regulator panel is put in place.
is recommended to prevent 1. Remove evaporator access
this maximum from being panel and supply air access 9. Replace evaporator access panel
exceeded. These components panels. and supply air access panels.
must be isolated during field 2. Remove the support panel that A condensate trap must be installed
gas piping test that exceed the condensate drain pan exits at the unit due to the drain
1/2 PSIG. It is recommended connection being on the “negative
through.
that the field piping be pressure” side of the fan. Install the
capped prior to the unit gas 3. Slide the condensate drain pan P-Trap using the guidelines in
train or Optional Through out of the unit and rotate 180°. Figure 25, p. 26.
The Base Gas Shut-Off Valve 4. Slide the condensate drain pan
if present. A condensate drain line must be
back into the unit, align the drain connected to the P-Trap. Pitch the
with the grommeted opening in drain lines at least 1/2 inch for every
the rear support panel and push 10 feet of horizontal run to assure
• Gas supply line properly sized until the coupling is seated in the
and connected to the unit gas proper condensate flow. Do not allow
grommet. the horizontal run to sag causing a
train.
5. Replace the front support panel possible double-trap condition which
• All gas piping joints properly could result in condensate backup
by aligning the panel with tabs in
sealed. the raceway. Align the due to “air lock”.
• Gas piping leak checked with a condensate drain pan support in
soap solution. If piping the grommeted hole as the panel
connections to the unit are is put in place.
complete, do not pressurize
RT-SVX21F-EN 25
Installation
Note: All field wiring must conform 4. Route low voltage wiring per Note: Ensure that the wiring
to NEC guidelines as well as illustrations on page 24. between controls and the
state and local codes. unit’s termination point does
not exceed two and a half
Table 4. Electromechanical Thermostat (2.5) ohms/conductor for the
Control Power Transformer 24V AC Conductors with length of the run.
The 24 volt control power ReliaTel
transformers are to be used only with • Do not run the electrical wires
Distance from Unit Recommended transporting DC signals in or
the accessories called out in this to Control Wire Size
manual. Transformers rated greater around conduit housing high
000 - 460 feet 18 gauge voltage wires.
than 50 VA are equipped with
internal circuit breakers. If a circuit 000 - 140 m .75 mm2
• Route low voltage wiring per
breaker trips, turn “Off” all power to 461 - 732 feet 16 gauge illustrations on page 24.
the unit before attempting to reset it. 141 - 223 m 1.3 mm2
Failure to disconnect power before 0 - 9.1 m .33 m2 241 -385 feet 18 gauge
servicing can cause severe personal 31 - 50 feet 20 gauge 73.5 - 117.3 m .75 mm2
injury or death.
9.5 - 15.2 m .50m2 386 - 610 feet 16 gauge
The transformer is located in the 117.7 - 185.9 m 1.3 mm2
51 - 75 feet 18 gauge
control panel. The circuit breaker is
15.5 - 22.9 m .75 m2 611 - 970 feet 14 gauge
located on the left side of the
transformer and can be reset by 76 - 125 feet 16 gauge 186.2 - 295.7 m 2.0 mm2
pressing in on the black reset button. 23.1 - 38.1 m 1.3 m2
126 - 200 feet 14 gauge
Controls using 24 VAC
38.4 - 60.9 m 2.0 m2
Before installing any connecting
wiring, refer to “Unit Dimensions,”
p. 12 for the electrical access Controls using DC Analog
locations provided on the unit and Input/Outputs
Table 4 or Table 5 for AC conductor
sizing guidelines, and;
(Standard Low Voltage Multi
1. Use copper conductors unless conductor Wire)
otherwise specified.
Before installing any connecting
2. Ensure that the AC control wiring wiring between the unit and
between the controls and the components utilizing a DC analog
unit’s termination point does not input\output signal, refer to “Unit
exceed three (3) ohms/conductor Dimensions,” p. 12 for the electrical
for the length of the run. access locations provided on the
Note: Resistance in excess of 3 unit.
ohms per conductor may • Table 6 lists the conductor sizing
cause component failure due guidelines that must be followed
to insufficient AC voltage when interconnecting the DC
supply. binary output devices and the
Note: Be sure to check all loads and system components utilizing a
conductors for grounds, DC analog input\output signal to
shorts, and mis-wiring. the unit.
3. Do not run the AC low voltage Note: Resistance in excess of 2.5
wiring in the same conduit with ohms per conductor can
the high voltage power wiring. cause deviations in the
accuracy of the controls.
RT-SVX21F-EN 27
Installation
Figure 27. ReliaTel conventional thermostat Figure 29. ReliaTel options module
field wiring diagrams
RTRM
28 RT-SVX21F-EN
Installation
RT-SVX21F-EN 29
Installation
Smoke Detector If you have supply and return smoke If you have more than 5 HVAC units,
detectors in all HVAC units, you can you can connect all the supplies
Customer Low Voltage connect a maximum of 5 HVAC units together on one power supply (up to
Wiring (10 detectors) up to one power 10 HVAC units), and all the returns
supply. See the following field wiring together (up to 10 HVAC units) on
When interlocking System Sensor example. another power supply. See the
smoke detectors together, all of the following field wiring example.
detectors must be powered from the Figure 34. Up to 5 HVAC units
same power supply. If the smoke Figure 35. Up to 5 HVAC units
detectors are powered up by
different power supplies, harmonics
are set up and will fry the boards in
some, if not all, of the detectors.
If multiple smoke detectors are
required, all detectors must be
disconnected from the HVAC unit
power supply and connected
together from another single source
supply.
Note: Do not interconnect any
smoke detectors together
that have separate power
supplies. Do not exceed ten
smoke detectors on one
power supply.
Note: Multiple System Sensor
smoke detectors are
connected together using
terminals 1 and 12 on each
detector.
30 RT-SVX21F-EN
Installation
Space Temperature Example #1 illustrates two series Example #3 illustrates the circuit
circuits with two sensors in each required for this sensor. Figure 7,
Averaging circuit wired in parallel. The square p. 33 lists the temperature versus
of any number of remote sensors is resistance coefficient for all sensors.
(ReliaTel™ only) required.
Space temperature averaging is Example #2 illustrates three sensors
accomplished by wiring a number of squared in a series/parallel circuit.
remote sensors in a series/parallel Using BAYSENS077*, two sensors
circuit. are required to accomplish space
temperature averaging.
Using the BAYSENS016* or
BAYSENS077*, at least four sensors
are required to accomplish space
temperature averaging.
RT-SVX21F-EN 31
Installation
Figure 37. Typical field wiring diagrams for optional controls (ReliaTel only)
BAYSENS077*
BAYSENS077*
ASYSTAT111*
ASYSTAT111*
BAYSENS106* BAYSENS108*
Zone Sensor BAYSENS110*
Zone Sensor Zone Sensor
BAYSENS119*
ASYSTAT777*
BAYSENS074* Zone Sensor
BAYSENS073*
Zone Sensor Zone Sensor
BAYSENS077*/ASYSTAT111*
32 RT-SVX21F-EN
Installation
RT-SVX21F-EN 33
Pre-Start
Use the checklist provided below in panels in preparation for starting equal as much as a 20% current
conjunction with the “General Unit the unit. imbalance with a resulting increase
Requirements” checklist to ensure in motor winding temperatures that
that the unit is properly installed and will decrease motor life. If the
ready for operation.
Voltage Imbalance voltage imbalance is over 2%, notify
Three phase electrical power to the the proper agencies to correct the
WARNING unit must meet stringent
requirements for the unit to operate
voltage problem before operating
this equipment.
Hazardous Voltage w/
Capacitors! properly.
Disconnect all electric power, Measure each leg (phase-to-phase) Electrical Phasing
including remote disconnects and of the power supply. Each reading
discharge all motor start/run must fall within the utilization range (Three Phase Motors)
capacitors before servicing. Follow stamped on the unit nameplate. If
proper lockout/tagout procedures to any of the readings do not fall within The compressor motor(s) and the
ensure the power cannot be the proper tolerances, notify the supply fan motor are internally
inadvertently energized. Verify with power company to correct this connected for the proper rotation
an appropriate voltmeter that all situation before operating the unit. when the incoming power supply is
capacitors have discharged. Failure phased as A, B, C.
Excessive three phase voltage
to disconnect power and discharge imbalance between phases will Proper electrical supply phasing can
capacitors before servicing could cause motors to overheat and be quickly determined and corrected
result in death or serious eventually fail. The maximum before starting the unit by using an
injury.Check all electrical allowable voltage imbalance is 2%. instrument such as an Associated
connections for tightness and “point Measure and record the voltage Research Model 45 Phase Sequence
of termination” accuracy. between phases 1, 2, and 3 and Indicator and following the steps
Verify that the condenser airflow will calculate the amount of imbalance below:
be unobstructed. as follows: • Turn the field supplied
34 RT-SVX21F-EN
Pre-Start
RT-SVX21F-EN 35
Pre-Start
Minimum
Fan On Position Off Off Off Off 2.2K
1 Setpoint 0%
Minimum On Selectable Off Off Off Off
Ventilation
2 Economizer On Open Off Off Off Off 3.3K
Test Open
3 Cool On Minimum (Note 1) Off Off Off 4.7K
Stage 1 Position On
4 Cool On Minimum (Note 1) (Note 1) Off Off 6.8K
(Note 3) Stage 2 Position On On
5 Reheat On Minimum On On Off Off 33K
(Note 3)
6 Heat On Minimum Off Off On Off 10K
(Note 3) Stage 1
7 Heat On Minimum Off Off On On 15K
(Note 3) Stage 2
Notes:
1 - The condenser fans will operate any time a compres-
though the resistance is left on
the test terminals.
Electromechanical
sor is "On.
providing the outdoor air temperatures are within the
3. Auto Test Mode - This method is
Controls Test
operating values.
2 - The exhaust fan will turn on anytime the economizer not recommended for start-up Procedure
damper position is equal to or greater than the ex- due to the short timing between
haust fan setpoint. See unit schematic for correct wire
3 - Steps for optional accessories and non-applicable
individual component steps. This
modes in unit will be skipped. method initiates the different numbers.
components of the unit, one at a
Test Modes time, when a jumper is installed Fan Test and Minimum
across the test terminals. The Ventilation
There are three methods in which the unit will start the first test step
“Test” mode can be cycled at LTB- and change to the next step Connect red thermostat wire (R) to
Test 1 and LTB-Test 2. every 30 seconds. black thermostat wire (G).
1. Step Test Mode - This method At the end of the test mode,
control of the unit will Economizer Cooling
initiates the different
components of the unit, one at a automatically revert to the Connect a jumper wire across OTS
time, by temporarily shorting applied “System” control on Economizer Control (ECA).
across the two test terminals for method.
Connect red thermostat (R) wire to
two to three seconds. For unit test steps, test modes, and yellow thermostat wire (Y1).
For the initial start-up of the unit, step resistance values to cycle the
this method allows the various components, refer to Cool 1
technician to cycle a component Table 10.
“On” and have up to one hour to Connect red thermostat wire (R) to
Electro Mechanical Controls
complete the check. yellow thermostat wire (Y1).
Upon power initialization, the Gas
2. Resistance Test Mode - This Ignition Module (IGN) performs self-
method can be used for start-up Cool 2
diagnostic checks to insure that all
providing a decade box for internal controls are functional. It Connect red thermostat wire (R) to
variable resistance outputs is also checks the configuration yellow thermostat wire (Y2).
available. This method initiates parameters against the components
the different components of the connected to the system. The System Heat 1
unit, one at a time, when a LED located on the IGN module is
specific resistance value is turned “On” within one second of Connect red thermostat wire (R) to
placed across the two test power-up if internal operation is brown thermostat wire (W1).
terminals. The unit will remain in okay.
the specific test mode for Heat 2
approximately one hour even
Connect red thermostat wire (R) to
brown thermostat wire (W2).
36 RT-SVX21F-EN
Start-Up
Verifying Proper Air Flow With the fan operating properly, The actual external static pressure is
determine the total system external approximately 0.45" w.c., airflow
static pressure (inches w.c.) by; equals 2100 CFM.
(Units with Two Speed Direct
Drive Indoor Fan) 1. Measuring the supply and return If the static pressure reading was
duct static pressure, higher, motor current would have to
Much of the systems performance be lower proportionately to get an
and reliability is closely associated 2. Using the accessory pressure
accurate CFM measurement in direct
with, and dependent upon having drop table in the Service Facts,
drive applications.
the proper airflow supplied both to calculate the total static pressure
the space that is being conditioned drop for all of the accessories 5. If the required CFM is too low,
and across the evaporator coil. installed on the unit; i.e., curb, (external static pressure is high
economizer, etc. causing motor HP output to be
The indoor fan motor is factory below table value),
wired to operate on low speed in the Note: Static pressure is based on
desired CFM and may not be a. Relieve supply and/or return
cooling and heating mode. It can be duct static.
rewired for high speed operation actual static pressure.
should the application require it. 3. Add the total accessory static b. Change indoor fan speed to
Refer to the wiring diagram that pressure drop (step 2) to the "High" and repeat steps 1
shipped in the unit. duct external static pressure through 4.
The indoor fan motors are (step 1). The sum of these two 6. If the required CFM is too high,
specifically designed to operate values represents the total (external static pressure is low
within the BHP parameters listed in system external static pressure. causing motor HP output to be
the fan performance tables of the 4. Measure the amperage at the above table value), increase
unit Service Facts. By understanding supply fan contactor and supply and/or return duct static.
that these motors will safely work compare it with the full load 7. To stop the SERVICE TEST, turn
within these conditions, before an amp (FLA) rating stamped on the main power disconnect
oversized motor is required, will the motor nameplate. switch to the "Off" position or
allow the air distribution system to a. Calculate the theoretical BHP proceed to the next component
be set up properly and diagnostics start-up procedure.
enhanced should a problem occur. Actual Motor Amps X Motor HP
When verifying direct drive fan Motor Nameplate Amps Verifying Proper Air Flow
performance, the tables must be b. Using the fan performance
used somewhat differently than tables in the unit Service
those of belt driven fans. Fan
(Units with Belt Drive Indoor
Facts, plot the total external
performance diagnostics can be static pressure (step 3) and
Fan)
easily recognized when these tables the BHP (step 4a) to obtain Much of the systems performance
are used correctly. the operating CFM. and reliability is closely associated
Before starting the SERVICE TEST, c. When plotted, if the two with, and dependent upon having
set the minimum position setpoint values can not be the proper airflow supplied both to
for the economizer to 0 percent interpolated the space that is being conditioned
using the setpoint potentiometer correspondingly, the static and across the evaporator coil.
located on the Economizer Control pressure will most likely be The indoor fan speed is changed by
(ECA), if applicable. the least accurate opening or closing the adjustable
measurement. Because of motor sheave.
the direct drive motor
ReliaTel™ Control operation, the RPM Before starting the SERVICE TEST,
Using the Service Test Guide in performance is relatively set the minimum position setpoint
Table 10, momentarily jump across constant making the for the economizer to 0 percent
the Test 1 & Test 2 terminals on LTB1 operating current a very using the setpoint potentiometer
one time to start the Minimum reliable diagnostic tool. located on the Economizer Control
Ventilation Test. (ECA), if applicable.
• Example: W_D060 single phase,
low speed.
Electro Mechanical ReliaTel Control
Actual Motor Amp (5.25) =.99%
Control Using the Service Test Guide in
Motor Nameplate Amps (5.3) Table 10, momentarily jump across
Using the Service Test Guide 0.99 X Motor HP (0.6) =.59 BHP the Test 1 & Test 2 terminals on LTB1
perform the proper test mode one time to start the Minimum
connections. Ventilation Test.
RT-SVX21F-EN 37
Start-Up
Electro Mechanical Control Verifying Proper Air Flow With the fan operating properly,
determine the total system external
Using the Service Test Guide perform static pressure (inches w.c.) by the
the proper test mode connections. (Units with 5-Tap Direct Drive following method:
Once the supply fan has started, Indoor Fan)
1. Measure the supply and return
check for proper rotation. The Much of the systems performance duct static pressure and sum the
direction of rotation is indicated by and reliability is closely associated resulting absolute values,
an arrow on the fan housing. with, and dependent upon having the
proper airflow supplied both to the 2. Use the accessory pressure drop
With the fan operating properly, table in the Service Facts, to
determine the total system airflow space that is being conditioned and
across the evaporator coil. calculate the total static pressure
(CFM) by; drop for all of the accessories
1. Measuring the actual RPM, The indoor fan motor is factory wired installed on the unit; i.e., curb,
to operate on speed tap 1 in the economizer, etc.
2. Measure the amperage at the cooling and heating mode for
supply fan contactor and electric/electric units. For Gas/Electric Note: Accessory static pressure
compare it with the full load amp units, the motor is factory wired to drop is based on desired CFM
(FLA) rating stamped on the operate on speed tap 1 during and may not be actual static
motor nameplate. cooling. For 3 & 4 ton Gas/Electric pressure drop.
a. Calculate the theoretical BHP units operating in heat mode, the 3. Add the total accessory static
minimum setting is Tap 4. pressure drop (step 2) to the duct
Actual Motor Amps X Motor HP
For these units, a separate tap external static pressure (step 1).
Motor Nameplate Amps terminal is provided to change The sum of these two values
b. Using the fan performance speeds automatically between represents the total system
tables in the unit Service heating and cooling. The motor can external static pressure.
Facts, plot the actual RPM be rewired for different speed Using the Fan Performance Tables in
(step 1) and the BHP (step 2a) settings should the application the Service Facts, look up the
to obtain the operating CFM. require it. Refer to the wiring diagram selected speed tap setting and match
3. If the required CFM is too low, that shipped in the unit and the unit the measured ESP to determine the
(external static pressure is high fan performance tables in the Service approximate CFM.
causing motor HP output to be Facts.
If the required CFM is too low,
below table value), The indoor fan motors are (external static pressure is high) do
a. Relieve supply and/or return specifically designed to operate one or both of the following and
duct static. within the BHP parameters listed in repeat procedure:
the fan performance tables of the a. Relieve supply and/or return
b. Change indoor fan speed and
unit Service Facts. duct static.
repeat steps 1 and 2.
When verifying direct drive fan b. Change indoor fan speed tap
• To Increase Fan RPM; Loosen the
performance, the tables must be to a higher value
pulley adjustment set screw and
used somewhat differently than
turn sheave clockwise. If the required CFM is too high,
those of belt driven fans. Fan
• To Decrease Fan RPM; Loosen performance diagnostics can be (external static pressure is low), do
the pulley adjustment set screw easily recognized when these tables one or both of the following and
and turn sheave are used correctly. repeat procedure:
counterclockwise. a. Increase supply and/or return
Before starting the SERVICE TEST, set
duct static.
• If the required CFM is too high, the minimum position setpoint for
(external static pressure is low the economizer to 0 percent using the b. Change indoor fan speed tap
causing motor HP output to be setpoint potentiometer located on to a lower value.
above table value), change the Economizer Control (ECA), if Note: Minimum setting for units
indoor fan speed and repeat applicable. with Gas or Electric Heat is
steps 1 and 2. 320 CFM per Ton. For 3 & 4
• To stop the SERVICE TEST, turn ReliaTel Control Ton Gas Heat units operating
the main power disconnect in heating mode the heat
Using the Service Test Guide in
switch to the "Off" position or speed set cannot be lower
Table 10, momentarily jump across
proceed to the next component than Speed Set 4.
the Test 1 & Test 2 terminals on LTB1
start-up procedure. one time to start the Minimum 4. To stop the SERVICE TEST, turn
Ventilation Test. the main power disconnect
switch to the "Off" position or
Electro Mechanical Control proceed to the next component
start-up procedure.
Using the Service Test Guide perform
the proper test mode connections.
38 RT-SVX21F-EN
Start-Up
RT-SVX21F-EN 39
Start-Up
Monitor the suction pressure for 15 • Close the main disconnect switch
minutes. The suction pressure or circuit protector switch that
should remain within 5 psi of normal provides the supply power to the
cooling operation. If the unit has a 2 unit’s terminal block or the unit
speed Outdoor fan and if the Outdoor mounted disconnect switch.
air temperature is below 70° F, verify
that the OD fan is in low speed. WARNING
Live Electrical Components!
Gas Heat Units During installation, testing, servicing
Open the main disconnect switch to and troubleshooting of this product,
shut the unit off and to reset the it may be necessary to work with live
RTRM. electrical components. Have a
qualified licensed electrician or other
Follow the Test Guide in Table 10 to individual who has been properly
start the unit in the heating mode. trained in handling live electrical
ReliaTel Control Momentarily jump components perform these tasks.
across the Test 1 & Test 2 terminals Failure to follow all electrical safety
on LTB1 one additional time if precautions when exposed to live
continuing from previous component electrical components could result in
start-up or until the desired start-up death or serious injury.
component Test is started.
Make sure all personnel are standing
Electro Mechanical Control clear of the unit before proceeding.
The system components will start
Using the Service Test Guide perform when the power is applied.
the proper test mode connections
When starting the unit for the first
time or servicing the heaters, it is a
good practice to start the heater with
the main gas supply turned “Off”.
Once the ignition system and
components have been checked,
open the main power disconnect
switch to reset the unit.
40 RT-SVX21F-EN
Maintenance
RT-SVX21F-EN 41
Maintenance
detector, complete adherence to the • Generally inspect the unit for and condenser coils using the
maintenance procedures, including unusual conditions (e.g., loose instructions outlined below. Be sure
recommended intervals between access panels, leaking piping to follow these instructions as closely
filter changes, and coil cleaning is connections, etc.) as possible to avoid damaging the
required. coils.
• Make sure that all retaining
Periodic checks and maintenance screws are reinstalled in the unit Note: For units equipped with hail
procedures must be performed on access panels once these checks guards follow removal
the smoke detector to insure that it are complete. procedure listed below.
will function properly. For detailed
• With the unit running, check and
instructions concerning these checks Hail Guard Removal
record the: ambient temperature;
and procedures, refer to the
compressor suction and • Unlatch hail guard.
appropriate section(s) of the smoke
discharge pressures (each
detector Installation and • Pull the top of the hail guard
circuit); superheat (each circuit);
Maintenance Instructions provided outward until the fastener studs
with the literature package for this • Record this data on an are free of the retaining nuts.
unit. “operator’s maintenance log”
like the one shown in Table 12 on • Lift the hail guard from the lower
Cooling Season page 44. If the operating retaining bracket and set aside.
pressures indicate a refrigerant To clean refrigerant coils, use a soft
• Check the unit’s drain pans and shortage, measure the system brush and a sprayer (either a garden
condensate piping to ensure that superheat. For guidelines, refer pump-up type or a high-pressure
there are no blockages. to the “Compressor Start-Up” sprayer). A high-quality detergent is
• Inspect the evaporator and section. also required; suggested brands
condenser coils for dirt, bent Note: Do Not release refrigerant to include “SPREX A.C.”, “OAKITE 161”,
fins, etc. If the coils appear dirty, the atmosphere! If adding or “OAKITE 166” and “COILOX”. If the
clean them according to the removing refrigerant is detergent selected is strongly
instructions described in “Coil required, the service alkaline (ph value exceeds 8.5), add
Cleaning” later in this section. technician must comply with an inhibitor.
WARNING
• Manually rotate the condenser all federal, state and local
fan(s) to ensure free movement laws.
and check motor bearings for Hazardous Chemicals!
wear. Verify that all of the fan Heating Season Coil cleaning agents can be either
mounting hardware is tight. acidic or highly alkaline. Handle
• Inspect the unit’s air filters. If
• Inspect the F/A-R/A damper necessary, clean or replace them. chemical carefully. Proper handling
hinges and pins to ensure that all should include goggles or face
• Check supply fan motor shield, chemical resistant gloves,
moving parts are securely
bearings; repair or replace the boots, apron or suit as required. For
mounted. Keep the blades clean
motor as necessary. personal safety refer to the cleaning
as necessary.
• Inspect both the main unit agent manufacturer’s Materials
• Verify that all damper linkages Safety Data Sheet and follow all
control panel and heat section
move freely; lubricate with white recommended safe handling
control box for loose electrical
grease, if necessary. practices. Failure to follow all safety
components and terminal
• Check supply fan motor connections, as well as damaged instructions could result in death or
bearings; repair or replace the wire insulation. Make any serious injury.
motor as necessary. necessary repairs. 1. Remove enough panels from the
• Check the fan shaft bearings for • Clean burner area, verify gas unit to gain access to the coil.
wear. Replace the bearings as heat system operates properly. 2. Protect all electrical devices such
necessary. as motors and controllers from
• Check the supply fan belt. If the Coil Cleaning any over spray.
belt is frayed or worn, replace it. Regular coil maintenance, including 3. Straighten any bent coil fins with
Refer to the “Fan Belt annual cleaning, enhances the unit’s a fin comb.
Adjustment” section for belt operating efficiency by minimizing:
replacement and adjustments. 4. Mix the detergent with water
compressor head pressure and according to the manufacturer’s
• Verify that all wire terminal amperage draw; evaporator water instructions. If desired, heat the
connections are tight. carryover; fan brake horsepower, due solution BUT DO NOT EXCEED
to increase static pressure losses; 150 F maximum to improve its
• Remove any corrosion present airflow reduction.
on the exterior surfaces of the cleansing capability.
unit and repaint these areas. At least once each year, or more
often if the unit is located in a “dirty”
environment, clean the evaporator
42 RT-SVX21F-EN
Maintenance
WARNING Note: Secure hail guard latches. Note: Clean the reheat coil on the
same interval and method as
Hazardous Pressures!
the evaporator coil.
Coils contain refrigerant under Figure 41.
pressure. When cleaning coils, Replace the reheat coil to its proper
maintain coil cleaning solution location once cleaning is complete.
temperature under 150°F to avoid Align the screw heads in the top of
excessive pressure in the coil. Failure the reheat coil with the slots in the
to follow these safety precautions evaporator top block off. Press the
could result in coil bursting, which coil assembly into place and verify
could result in death or serious that the reheat coil is flush against
injury. the evaporator top block off. Set the
HAIL GUARD locking bracket on the top of the
Do not heat the detergent-and-water
reheat coil flush with the evaporator
solution above 150º F. Hot liquids
coil top block off.
sprayed on the exterior of the coil
will raise the coil’s internal pressure Apply pressure to the center of the
and may cause it to burst. Failure to bracket and slide the bracket towards
follow proper procedures can result the rear of the unit. Tighten the
in personal illness or injury or severe screw to secure the bracket and the
equipment damage. coil in place.
5. Pour the cleaning solution into
the sprayer. If a high-pressure
sprayer is used:
a. do not allow sprayer pressure
Figure 42.
to exceed 600 psi.
b. the minimum nozzle spray
angle is 15 degrees.
c. maintain a minimum
clearance of 6" between the
sprayer nozzle and the coil.
d. spray the solution
perpendicular (at 90 degrees)
to the coil face.
6. Spray the leaving-airflow side of
the coil first; then spray the
opposite side of the coil. Allow
the cleaning solution to stand on
the coil for five minutes. 10. Restore the unit to it’s
7. Rinse both sides of the coil with operational status and check
cool, clean water. system operation.
RT-SVX21F-EN 43
Maintenance
44 RT-SVX21F-EN
Trouble Shooting
RT-SVX21F-EN 45
Trouble Shooting
46 RT-SVX21F-EN
Trouble Shooting
RT-SVX21F-EN 47
Trouble Shooting
48 RT-SVX21F-EN
Trouble Shooting
Heating Failure Unit Economizer Control 2. Testing the Outdoor Air Switch. If
the temperature is above 60
Verify Heat Failure by Ignition (ECA) Test Procedures degrees, it will need to be chilled.
Module (IGN) LED indicator: Measure the resistance of the
OFF: No Power or Failure Electro Mechanical Control sensor on the ECA SO and +.
ON: Normal This series of tests will allow you to The resistance should be
diagnose, and determine where, and approximately 390 Ohms.
Slow Flash: Normal, Heat Call if a problem exists in the system Replace the Switch if it is open.
Fast Flash:Error Code: economizer operation. Test 1
determines if the problem is in the Replace the ECA if it is out of
1 Flash:No Communication Unit, or if it is in the ECA. Test 2 tests range.
2 Flashes:System Lockout sensor inputs. Test 3 tests the 3. Testing the R1 Resistance.
resistors and sensors. Conduct the
3 Flashes:Pressure Switch Fail Measure the resistance of the
tests in numerical order until
sensor on the ECA SR and +.
4 FlashesTC01 or TC02 Open problem is found.
The resistance should be
5 Flashes:Flame w/o Gas Valve approximately 420 Ohms.
Test 1
6 Flashes:Flame Rollout Open Replace the ECA if it is out of
Verifying that the economizer
range.
actuator (ECA) is functional:
Cooling Failure 4. Testing the R2 Resistance.
1. Using the “Test Mode” described
1. Cooling and heating set point in the “System Start-Up” Measure the resistance of the
(slide pot) on the thermostat has section, put the unit into the sensor on the ECA P and P1.
failed. economizer mode and verify that The resistance should be
2. CC1 or CC2 24 VAC control circuit the economizer actuator (ECA) approximately 130 Ohms.
has opened, check CC1 & CC2 drives fully open (approximately
coils, and any of the controls 90 seconds). Replace the ECA if it is out of
below that apply to the unit range.
2. If the ECA is not driving the
(HPC1, HPC2, LPC1, LPC2, dampers, verify that 24 VAC is
Frostat™). between the ECA terminals TR
and TR1 is present. If 24 volts is
Resetting Cooling and not present, a wiring or terminal
problem exists from the control
Ignition Lockouts transformer. Make any necessary
Cooling Failures and Ignition repairs, see wiring diagrams to
Lockouts are reset in an identical troubleshoot.
manner. Method 1 explains resetting 3. If 24 VAC is present, adjust the
the system from the space; Method 2 minimum position
explains resetting the system at the potentiometer fully clockwise. If
unit. the actuator does not drive, the
economizer actuator is bad.
Method 1 Replace the ECA.
To reset the system from the space,
turn the “Mode” selection switch at Test 2
the thermostat to the “Off” position. Testing the ECA resistors and
After approximately 30 seconds, turn sensors
the “Mode” selection switch to the
desired mode, i.e. Heat, Cool or Auto. 1. Testing the Mixed Air Sensor
(MAS). Disconnect the wires
Method 2 connected to T and T1 on the
ECA, and;
To reset the system at the unit, cycle a. Measure the resistance of the
the unit power by turning the sensor between the wires
disconnect switch “Off” and then 180B and 181B.
“On”.
b. Measure the temperature at
the MAS location. Using the
Temperature versus
Resistance chart, verify the
accuracy of the MAS.
Replace the sensor if it is out of
range.
RT-SVX21F-EN 49
Wiring Diagrams
Note: For easier access, published unit wiring diagrams (individual, separate diagrams for unitary product lines) will
become available via e-Library instead of through wiring manuals after 2007. For diagrams prior to 2008 please
refer to wiring diagram books Y_C-SVE001C-EN or Y_C-SVE002C-EN for cooling only units.
Drawing
Number Description
Connection Diagrams
4366-1000 230v/60hz/3ph — 2 - 5 Ton Single Stage Gas Heat / Direct Drive Motor
4366-1002 230v/60hz/1ph — 2 - 5 Ton Single Stage Gas Heat / Direct Drive Motor
4366-1004 460-575v/60hz/3ph — 3 Ton Single Stage Gas Heat / Direct Drive Motor
4366-1005 460-575v/60hz/3ph — 2 - 7.5 Ton Single Stage Gas Heat / Belt Drive Motor
4366-1011 460-575v/60hz/3ph — 4 - 5 Ton Single Stage Gas Heat / Oversize Drive Motor
4366-1016 230v/60hz/3ph — 2 - 7.5 Ton Single Stage Gas Heat / Belt Drive Motor
4366-1017 230v/60hz/3ph — 2 - 5 Ton Single Stage Gas Heat / Oversize Drive Motor
4366-1018 230v/60hz/1ph — 2 - 5 Ton Single Stage Gas Heat / Oversize Drive Motor
4366-1032 460-575v/60hz/3ph — 4 - 5 Ton Single Stage Gas Heat / Direct Drive Motor
4366-1033 230v/60hz/3ph — 7.5 - 10 Ton Gas Heat / Dual Compressor
4366-1034 460-575v/60hz/3ph — 7.5 - 10 Ton Gas Heat / Dual Compressor
4366-1500 230v/60hz/1ph — Single Stage Gas Heat / Direct Drive
4366-1501 230v/60hz/1ph — 3 - 5 Ton Single Stage Gas Heat / Direct Drive
4366-1502 230v/60hz/3ph — Single Stage Gas Heat / Direct Drive
4366-1503 230v/60hz/3ph — 3 - 5 Ton Single Stage Gas Heat / Direct Drive
4366-1504 230v/60hz/3ph — 3 - 5 Ton Single Stage Gas Heat / Oversize Motor
4366-1513 2 - 3 Ton Single Stage Gas Heat / Direct Drive
4366-1514 460-575v/60hz/3ph — 3 Ton Gas Heat / Direct Drive
4366-1515 460-575v/60hz/3ph — 4 - 5 Ton Gas Heat / Oversize Motor
4366-1516 460-575v/60hz/3ph — 3 - 5 Ton Gas Heat / Belt Drive
4366-1517 460-575v/60hz/3ph — 4 - 5 Ton Single Stage Gas Heat / Direct Drive
4366-1518 460-575v/60hz/3ph — 4 - 5 Ton Gas Heat / Direct Drive
4366-1519 230v/60hz/1ph — Single Stage Gas Heat / Oversize Motor
4366-1520 230v/60hz/1ph — 3 - 5 Ton Single Stage Gas Heat / Oversize Motor
4366-1521 230v/60hz/3ph — Single Stage Gas Heat / Belt Drive
4366-1522 230v/60hz/3ph — 3 - 5 Ton Single Stage Gas Heat / Belt Drive
4366-1523 460-575v/60hz/3ph — Single Stage Gas Heat / Belt Drive
4366-1525 230v/60hz/3ph — Single Stage Gas Heat / Oversize Motor
4366-1526 460-575v/60hz/3ph — 4 - 5 Ton Single Stage Gas Heat / Oversize Motor
4366-1529 230v/60hz/3ph — 7. 5 - 10 Ton Gas Heat / Dual Compressor
4366-1530 230v/60hz/3ph — 7.5 - 10 Ton Gas Heat / Dual Compressor
4366-1531 460-575v/60hz/3ph — 7.5 - 10 Ton Gas Heat / Dual Compressor
4366-1532 460-575v/60hz/3ph — 7.5 - 10 Ton Gas Heat / Dual Compressor
4366-1537 230v/60hz/3ph — 6 - 7. 5 Ton Gas Heat / Single Compressor
4366-1538 460-575v/60hz/3ph — 6 - 7.5 Ton Gas Heat / Single Compressor
4366-1539 230v/60hz/3ph — 6 - 7.5 Ton Gas Heat / Single Compressor
4366-1540 460-575v/60hz/3ph — 6 - 7.5 Ton Gas Heat / Single Compressor
4366-4562 230v/60Hz/1Ph — 3 - 5 Ton R410A / Direct Drive Indoor Motor
4366-4564 230v/60Hz/1Ph — 3 - 4 Ton R410A / Direct Drive Indoor Motor
4366-4576 230v/60Hz/1Ph — 3 - 5 Ton R410A
4366-4705 230v/60Hz/1Ph — 5 Ton R410A / Direct Drive Indoor Motor
50 RT-SVX21F-EN
Wiring Diagrams
Drawing
Number Description
4366-5163 230v/60Hz/3Ph — 3 - 5 Ton R410A / Hi Eff
4366-5164 460v/60Hz/3Ph — 3 - 5 Ton R410A / Hi Eff
4366-5183 230v/60Hz/3Ph — 3 - 4 Ton R410A / Hi Eff / Direct Drive Indoor Motor
4366-5184 230v/60Hz/3Ph— 5 Ton R410A / Hi Eff / Direct Drive Indoor Motor
4366-5185 230v/60Hz/3Ph — 3 - 4 Ton Hi Eff / R410A / Direct Drive Indoor Motor
4366-5186 230v/60Hz/3Ph — 5 Ton R410A / Hi Eff / Direct Drive Indoor Motor
4366-5200 460v/60Hz/3Ph — 3 - 4 Ton R410A / Hi Eff / Direct Drive Indoor Motor
4366-5201 460v/60Hz/3Ph — 5 Ton R410A / Hi Eff / Direct Drive Indoor Motor
4366-5202 460v/60Hz/3Ph — 3 - 4 Ton R410A / Direct Drive Indoor Motor
4366-5203 460v/60Hz/3Ph — 5 Ton R410A / Direct Drive Indoor Motor
Control Diagrams
4366-1001 Single Stage Gas Heat / Direct Drive
4366-1027 2 - 5 Ton Single Stage Gas Heat / Belt Drive or Oversize Motor
4366-1045 6 - 7.5 Ton Gas Heat / Single Compressor
4366-1039 7.5 - 10 Ton Gas Heat / Dual Compressor
4366-4702 5 Ton 230v/1Ph / R410A Std Eff — 5 Ton R410A Hi Eff / Direct Drive Indoor Motor
4366-4570 3 - 4 Ton 230v/1Ph / R410A Std Eff — 3 - 4 Ton R410A Hi Eff / Direct Drive Indoor Motor
4366-1031E Through the Base Utility Schematic
4366-1006 2 - 5 Ton Single Stage Gas Heat / Direct Drive
4366-1015 2 - 5 Ton Single Stage Gas Heat / Belt Drive or Oversize Motor
4366-1042 7.5 -10 Ton Gas Heat
4366-1039 7.5 - 10 Ton Gas Heat / Dual Compressor
4366-1047 Novar Schematic 3051
4366-4703 5 Ton 230v/1Ph / R410A Std Eff — 5 Ton R410A Hi Eff / Direct Drive Indoor Motor
4366-4571 3 - 4 Ton 230v/1Ph / R410A Std Eff — 3 - 4 Ton R410A Hi Eff /Direct Drive Indoor Motor
4366-1048 CO2 Sensor / Ventilation Override Schematic
RT-SVX21F-EN 51
Limited Warranty
Combination Gas Electric This limited warranty does not cover Some states do not allow limitations
failure of your combination gas on how long an implied limited
Air Conditioner electric air conditioner if it is warranty lasts or do not allow the
damaged while in your possession, exclusion or limitation of incidental
YCC, YCD, YCH, YCP, YSC and failure attributable or caused by or consequential damages, so the
YHC (Parts Only) unreasonable use of the above limitation or exclusion may
combination gas electric air not apply to you. This limited
conditioner and/or failure to properly warranty gives you specific legal
Models Less Than 20 Tons for maintain the combination gas rights, and you may also have other
Residential Use* electric air conditioner as set forth in rights which vary from state to state.
This limited warranty is extended by the Use and Care manual.
Parts will be provided by our factory
Trane to the original purchaser and This limited warranty applies to organization through an authorized
to any succeeding owner of the real product installed on or after 10/1/ service organization in your area
property to which the Combination 2001 where product is manufactured listed in the yellow pages. If you
Gas Electric Air Conditioner is after 1/1/2000. This limited warranty wish further help or information
originally affixed, and applies to is not retroactive to any installations concerning this limited warranty,
products purchased and retained for prior to 10/1/2001 or on product contact:
use within the U.S.A. and Canada. produced prior to 2000.
Trane
If any part of your Combination Gas THE LIMITED WARRANTY AND
Electric Air Conditioner fails because 2701 Wilma Rudolph Blvd.
LIABILITY SET FORTH HEREIN ARE
of a manufacturing defect within five IN LIEU OF ALL OTHER Clarksville, TN 37040-1008
years from the date of the original WARRANTIES AND LIABILITIES,
purchase, Warrantor will furnish Attention: Manager, Product Service
WHETHER IN CONTRACT OR IN
without charge the required NEGLIGENCE, EXPRESS OR GW-618-4001
replacement part. Any local IMPLIED, IN LAW OR IN FACT,
transportation, related service labor, * This limited warranty is for
INCLUDING IMPLIED WARRANTIES
diagnosis calls, air filters, refrigerant residential usage of this equipment
OF MERCHANTABILITY AND
and related items are not included. and not applicable when this
FITNESS FOR PARTICULAR USE,
equipment is used for a commercial
If the sealed motor-compressor fails AND IN NO EVENT SHALL
application. A commercial use is any
because of a manufacturing defect WARRANTOR BE LIABLE FOR ANY
application where the end purchaser
within five years from the date of INCIDENTAL OR CONSEQUENTIAL
uses the product for other than
original purchase, Warrantor will DAMAGES.
personal, family or household
furnish without charge the required purposes.
replacement compressor. Any local
transportation, related service labor,
diagnosis calls, refrigerant and
related items are not included.
In addition, if the steel heat
exchanger fails because of a
manufacturing defect within the
sixth through tenth year from the
date of original purchase, Warrantor
will furnish without charge a
replacement heat exchanger. Any
local transportation, related service
labor and diagnosis calls are not
included.
52 RT-SVX21F-EN
Limited Warranty
RT-SVX21F-EN 53
Literature Order Number RT-SVX21F-EN
Date February 2009
Supersedes RT-SVX21F-EN (December 2008)
The manufacturer has a policy of continuous product and product data improvement and reserves
the right to change design and specifications without notice.