Cat
Cat
May 2000
RT-PRC002-EN
Introduction
SM
RP-PRC002-EN
Contents
Introduction
Application Considerations
9
10
11
Selection Procedure
Model Number Description
General Data
12
Performance Data
Controls
20
20
35
54
56
Electric Power
57
78
Mechanical Specifications
98
Cooling Performance
Fan Performance
Heat Performance
RP-PRC002-EN
Features and
Benefits
Compressors
Voyager contains the best
compressor technology available, in
order to achieve the highest
performance possible. Our
compressor line includesTrane built
Climatuff, Model H and 3-D
Scrolls, along with Copeland
Compressors.
Our Compressor designs are tested
inTranes SEET (System Extreme
EnvironmentalTest) facility inTyler,
Texas where five years of operation
are simulated in a sixteen week test.
Quick-Sess (3-7 tons) and QuickAccess (8-25 tons) panels reduce the
number of possiblewater entry points.
RT-PRC002-EN
Features and
Benefits
Ease Of Installation
Micro
Conversionless Units
The dedicated design units are either
downflow or horizontal and require no
panel removal and alteration time to
convert in the field a major cost
savings during installation.
Horizontal units come complete with
duct flanges so the contractor doesnt
have to field fabricate them.These duct
flanges are a time and cost saver.
Improved Airflow
U-shaped airflow allows for improved
static capabilities.
Single Side Access
Access to all of Voyagers components is
accomplished through the Quick-Sess
and Quick-Access panels. No more than
three screws must be removed to
access components.
RT-PRC002-EN
Features and
Benefits
Serviceability
Todays owners are more conscious of
the cost of service and maintenance.
Voyager was designed with input from
service contractors.Their information
helped us design a unit that would get
the serviceman off the job quicker and
save the owner money. Here is why
Voyager can save money in service.
Single-Side Service
Single-side service is standard on all
Voyager units.
Quick-Sess 3-7 ton and Quick-Access
Panels 8-25 Ton Units
Remove three or fewer screws for access
to the standardized internal components
and wiring.
Micro
The
Standardized
Components
Colored and
Numbered Wiring
Easy Access Low Voltage
Terminal Board
6
RT-PRC002-EN
Features and
Benefits
Voyager Helps Win Jobs And Engineer
Specifications
The Voyager units are built utilizing
important input from our consulting
engineers. Engineers want a unit that
performs to their rigorous standards in a
variety of applications. They want a unit
that lives up to their customers
expectations after giving their stamp of
approval. Here is how Voyager performs
to that standard.
Micro
Capacity Modulation
Flexible Applications
Trane
Communication
Interface
RT-PRC002-EN
Features and
Benefits
VariTrac
TIME
CLOCK
INPUT/
STATUS
PANEL
EDIT
TERMINAL
VariTrac
Training
Voyager 3 - 25 tons . . .
Product
Application
Service
Special Applications
Specifications
Computer Programs and much more
RT-PRC002-EN
Application
Considerations
NOTE:THE EFFECTIVENESS OF
BAROMETRIC RELIEF DAMPER
DURING ECONOMIZING OPERATION
IS SYSTEM RELATED.
PRESSURE DROP OFTHE RETURN AIR
SYSTEM SHOULD BE CONSIDEREDTO
CONTROL BUILDING PRESSURIZATION.
RT-PRC002-EN
Selection
Procedure
Cooling Capacity
Step 1
Calculate the buildings total and sensible
cooling loads at design conditions. Use
theTrane calculation methods or any
other standard accepted method.
Factors used in unit selection:
A
Total Cooling Load: 85 MBh
B
Sensible Cooling Load: 60 MBh
C
Airflow: 3000 cfm
D
Electrical Characteristics: 460/60/3
E
Summer Design Conditions: Entering
Evaporator Coil: 80 DB, 67 WB Outdoor
Ambient: 95
F
External Static Pressure: 0.52 in. wg
G
Rooftop - downflow configuration
H
Accessories
Roof curb
Economizer
Electric Heat
I
Heating
Capacity 70 MBh
460 volt/3 phase Electric Heat 3000
cfm
Step 2
As a starting point, a rough
determination must be made of the size
of the unit.The final selection will be
made after examining the performance
at the given conditions. Divide the total
cooling load by nominal BTUH per ton
(12 MBh per ton); then round up to the
nearest unit size.
85 MBh / 12 MBh = 7.08Tons or 7Tons
Step 3
Table PD-7 shows that aTCD090C4 has a
gross cooling capacity of 90 MBh and
65.0 MBh sensible capacity at 3000 cfm
and 95 DB outdoor ambient with 80 DB,
67 WB air entering the evaporator.
10
0.10 wg
Economizer
0.03 wg
0.70 wg
RT-PRC002-EN
Model
Number
Description
10
11
12
RT-PRC002-EN
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
No Factory-installed Options
Factory-installed Economizer
Oversized Motor
Downflow Economizer and Oversized
Motor
F = Trane Communications Interface (TCI)
G = Downflow Economizer and TCI
11
General
Data
(3, 4 , 5Ton)
Standard Efficiency
37,400
10.00
1,200/1,200
36,000
4.016
49,900
10.007
1,600/1,600
48,000
5.34
48,900
10.007
1,600/1,600
47,000
5.26
64,000
9.85
2,000/2,000
61,500
6.95
62,500
10.00
2,000/2,000
60,000
6.71
1/Climatuff
8.2
Hi-Performance
.375
5.87
2/16
Hi-Performance
.375
3.67
2/15
Short Orifice
1/ PVC
Propeller
1/24
Direct/1
3,150
1/.25
850
FC Centrifugal
1
9x9
Direct/2
1
.33/.40
1/Climatuff
8.6
Hi-Performance
.375
7.43
2/16
Hi-Performance
.375
4.83
2/15
Short Orifice
1/ PVC
Propeller
1/24
Direct/1
3,940
1/.33
850
FC Centrifugal
1
12 x 9
Direct/2
1
.50/.75
1/Climatuff
8.6
Hi-Performance
.375
5.83
2/16
Hi-Performance
.375
4.83
2/15
Short Orifice
1/ PVC
Propeller
1/24
Direct/1
3,630
1/.33
1,075
FC Centrifugal
1
12 x 9
Direct/2
1
.50/.75
1/Climatuff
8.6
Hi-Performance
.375
11.32
2/16
Hi-Performance
.375
6.33
2/15
Short Orifice
1/ PVC
Propeller
1/24
Direct/1
4,900
1/.50
975
FC Centrifugal
1
12 x 9
Direct/2
1
.60/.75
1/Climatuff
8.6
Hi-Performance
.375
9.76
2/16
Hi-Performance
.375
6.33
2/15
Short Orifice
1/ PVC
Propeller
1/24
Direct/1
4,270
1/.40
1,075
FC Centrifugal
1
12 x 9
Direct/2
1
.60/.75
1075/1400
850/1040
850/1040
850/1040
850/1040
48/48
Throwaway/Yes
(2) 20 x 25 x 1
5.6
48/48
Throwaway/Yes
(2) 20 x 25 x 15
6.6
48/48
Throwaway/Yes
(2) 20 x 25 x 15
5.6
48/48
Throwaway/Yes
(2) 20 x 25 x 1
8.4
48/48
Throwaway/Yes
(2) 20 x 25 x 1
7.9
NOTES:
1. Cooling Performance is rated at 95 F ambient, 80 F entering dry bulb, 67 F entering wet bulb. Gross capacity does not include the effect of fan motor heat. ARI capacity is
net and includes the effect of fan motor heat. Units are suitable for operation to 20% of nominal cfm. Certified in accordance with the Unitary Air-Conditioner Equipment
certification program, which is based on ARI Standard 210/240.
2. SEER is rated at ARI conditions and in accordance with DOE test procedures.
3. Sound Rating shown is tested in accordance with ARI Standard 270 or 370.
4. Refrigerant charge is an approximate value. For a more precise value, see unit nameplate and service instructions.
5. TCH048 models require (2) 16 x 25 x 1 filters
6. TCD036C3, C4 system power KW 3.99.
6. Hoizontal models have 8.95 SEER.
12
RT-PRC002-EN
General
Data
(6, 7 Ton)
Standard Efficiency
75,000
9.00
2,500/2,188
72,000
8.00
92,000
9.00
3,000/2,625
88,000
9.78
90,000
9.00
3,000/2,625
86,000
9.40
9.56
1/Climatuff
8.8
Hi-Performance
.375
11.32
2/16
Hi-Performance
.375
7.00
2/15
Short Orifice
1/ PVC
Propeller
1/24
Direct/1
4,870
1/.50
1,075
FC Centrifugal
1
12 x 9
Belt/1
1
1.0/2.0
1,725/1,725
56/56
Throwaway/Yes
(3) 16 x 25 x 1
9.1
1/Trane H
8.8
Hi-Performance
.375
12.09
2/16
Hi-Performance
.375
7.88
3/15
Short Orifice
1/ PVC
Propeller
1/24
Direct/1
5,450
1/.50
1,075
FC Centrifugal
1
12 x 9
Belt/1
1
1.0/2.0
1,725/1,725
56/56
Throwaway/Yes
(3) 16 x 25 x 1
10.6
2/Climatuff
8.8
Hi-Performance
.375
14.00
2/16
Hi-Performance
.375
7.88
2/15
Short Orifice
1/ PVC
Propeller
1/24
Direct/1
5,620
1/.50
1,075
FC Centrifugal
1
12 x 9
Belt/1
1
1.0/2.0
1,725/1,725
56/56
Throwaway/Yes
(3) 16 x 25 x 1
6.3/Circuit
NOTES:
1. Cooling Performance is rated at 95 F ambient, 80 F entering dry bulb, 67 F entering wet bulb. Gross capacity does not include the effect of fan motor heat. ARI capacity is
net and includes the effect of fan motor heat. Units are suitable for operation to 20% of nominal cfm. Certified in accordance with the Unitary Large Equipment
certification program, which is based on ARI Standard 340/360-93.
2. EER is rated at ARI conditions and in accordance with DOE test procedures.
3. Integrated Part Load Value is based in accordance with ARI Standard 210/240 or 360. Units are rated at 80 F ambient, 80 F entering dry bulb, and 67 F entering wet bulb at
ARI
rated cfm.
4. Sound Rating shownis tested in accordance with ARI Standard 270 or 370.
5. Refrigerant charge is an approximate value. For a more precise value, see unit nameplate and service instructions.
RT-PRC002-EN
13
General
Data
(8, 10Ton)
Standard Efficiency
107,000
9.2
3,400/3,000
102,000
9.4
11.09
125,000
9.26
4,000/3,500
118,000
9.16
12.836
2/Climatuff
9.2
Hi-Performance
.375
16.03
2/16
Hi-Performance
.375
10.50
2/15
Short Orifice
1/0.75 PVC
Propeller
1/26
Direct/1
7,000
1/1.0
1,125
FC Centrifugal
1
15 x 11
Belt/1
1
2.0/3.0
1,740/1,740
145T/145T
Throwaway/Yes
2/Climatuff
9.2
Hi-Performance
.375
18.67
2/16
Hi-Performance
.375
10.50
3/15
Short Orifice
1/0.75 PVC
Propeller
1/26
Direct/1
7,700
1/1.0
1,125
FC Centrifugal
1
15 x 11
Belt/1
1
3.0/5.0
1,740/3,450
145T/145T
Throwaway/Yes
(2) 20 x 20 x 2, (2) 16 x 20 x 2
(2) 20 x 25 x 2, (2) 16 x 25 x 2
7.1/Circuit
(2) 20 x 20 x 2, (2) 16 x 20 x 2
(2) 20 x 25 x 2, (2) 16 x 25 x 2
8.5/Circuit
NOTES:
1. Cooling Performance is rated at 95 F ambient, 80 F entering dry bulb, 67 F entering wet bulb. Gross capacity does not include the effect of fan motor heat. ARI capacity is
net and includes the effect of fan motor heat. Units are suitable for operation to 20% of nominal cfm. Certified in accordance with the Unitary Large Equipment
certification program, which is based on ARI Standard 340/360-93.
2. EER is rated at ARI conditions and in accordance with ARI Standard 210/240 or 360.
3. Integrated Part Load Value is based in accordance with ARI Standard 210/240 or 360. Units are rated at 80 F ambient, 80 F entering dry bulb, and 67 F entering wet bulb at
ARI rated cfm.
4. Sound Rating shown is tested in accordance with ARI Standard 270 or 370.
5. Refrigerant charge is an approximate value. For a more precise value, see unit nameplate and service instructions.
6. Horizontal models EER 9.4, IPLV 9.3, system power KW 12.55.
14
RT-PRC002-EN
General
Data
(12, 15 Ton)
Standard Efficiency
150,000
9.2
5,000/4,400
142,000
8.9
15.44
180,000
9.06
6,000/5,300
170,000
8.9
18.906
2/Climatuff Scroll
9.2
Hi-Performance
.375
23.93
2/16
Hi-Performance
.375
12.637
3/15
Short Orifice
1/1.00 NPT
Propeller
1/26
Direct/1
7,800
1/1.00
1,125
FC Centrifugal
1
15 x 15
Belt/1
1
3.0/5.0
1,740/3,450
145T/145T
Throwaway/Yes
(3) 20 x 20 x 2, (3) 16 x 20 x 2
(4) 20 x 25 x 2
(2) 20 x 20 x 2, (4) 20 x 25 x 2
(2) 20 x 20 x 2, (4) 20 x 25 x 2
8.4/9.1/Circuit
8.6/Circuit
13.4/7.7/Circuit
13.4/7.7/Circuit
NOTES:
1. Cooling Performance is rated at 95 F ambient, 80 F entering dry bulb, 67 F entering wet bulb. Gross capacity does not include the effect of fan motor heat. ARI capacity is
net and includes the effect of fan motor heat. Units are suitable for operation to 20% of nominal cfm. Certified in accordance with the Unitary Large Equipment
certification program, which is based on ARI Standard 340/360-93.
2. EER is rated at ARI conditions and in accordance with ARI Standard 210/240 or 360.
3. Integrated Part Load Value is based in accordance with ARI Standard 210/240 or 360. Units are rated at 80 F ambient, 80 F entering dry bulb, and 67 F entering wet bulb at
ARI rated cfm.
4. Sound Rating shown is tested in accordance with ARI Standard 270 or 370.
5. Refrigerant charge is an approximate value. For a more precise value, see unit nameplate and service instructions.
6. Horizontal models EER 9.1, system power KW 18.68.
7. Face area for Indoor Coil on horizontal models is 12.36.
RT-PRC002-EN
15
General
Data
20 Ton
Downflow and Horizontal Units
TCR240B3, B4, BW
25 Ton
Downflow and Horizontal Units
TCR300B3, B4, BW
246,000
9.2
8,000/7,000
232,000
9.3
25.22
290,000
9.7
10,000/8,750
272,000
9.8
28.05
2/Trane 3-DScroll
9.4
Hi-Performance
.375
32.57
2/16
Hi-Performance
.375
26.00
2/15
Short Orifice
1/1.00 NPT
Propeller
2/26
Direct/1
14,800
2/1.0
1,125
FC Centrifugal
1
18 x 18
Belt / 1
1
5.0/7.5
3,450/3,470
145T/184T
Throwaway/Yes
(4) 20 x 20 x 2, (4) 20 x 25 x 2
(8) 20 x 25 x 2
13.8/Circuit
(4) 20 x 20 x 2, (4) 20 x 25 x 2
(8) 20 x 25 x 2
17.0/Circuit
NOTES:
1. Cooling Performance is rated at 95 F ambient, 80 F entering dry bulb, 67 F entering wet bulb. Gross capacity does not include the effect of fan motor heat. ARI capacity is
net and includes the effect of fan motor heat. Units are suitable for operation to 20% of nominal cfm. 17 and 20 ton model ratings shown are certified in accordance
with the Unitary Large Equipment certification program, which is based on ARI Standard 340/360-93. 25 ton model ratings shown are tested in accordance with ARI
Standard 340/360-93.
2. EER is rated at ARI conditions and in accordance with ARI Standard 210/240 or 360.
3. Integrated Part Load Value is based in accordance with ARI Standard 210/240 or 360. Units are rated at 80 F ambient, 80 F entering dry bulb, and 67 F entering wet bulb at
ARI rated cfm.
4. Sound Rating shown is tested in accordance with ARI Standard 270 or 370.
5. Refrigerant charge is an approximate value. For a more precise value, see unit nameplate and service instructions.
6. Refrigerant charge for horizontal models is 14.4/8.7 per circuit.
16
RT-PRC002-EN
General
Data
(3, 4, 5, 6, 7Ton)
High Efficiency
4 Ton
5 Ton
Downflow and Horizontal Units
TCR049C3,C4
TCR061C3,C4
6 Ton
7 Ton
Downflow and Horizontal Units
TCR074C3,C4
TCR086C3,C4
42,400
12.00/
1,200/1,200
41,000
3.78
51,400
12.00/
1,600/1,600
49,500
4.61
60,500
12.00/
2,000/2,000
58,000
5.38
72,000
/10.00
2,500/2,188
68,000
6.80
82,000
/9.50
2,500/2,188
78,000
8.21
1/Climatuff
8.2
Hi-Performance
0.375
11.32
2/16
Hi-Performance
0.375
6.33
2/15
Short Orifice
1 / PVC
Propeller
1/24
Direct/1
4,100
1/.25
850
FC Centrifugal
1
9x9
Direct/2
1
.33/.40
1/Climatuff
8.2
Hi-Performance
0 .375
11.32
2/16
Hi-Performance
0.375
6.33
3/15
Short Orifice
1/ PVC
Propeller
1/24
Direct/1
4,100
1/.25
850
FC Centrifugal
1
12 x 9
Direct/2
1
.50/.75
1/Climatuff
8.2
Hi-Performance
0 .375
12.09
2/16
Hi-Performance
0.375
7.00
3/15
Short Orifice
1/ PVC
Propeller
1/24
Direct/1
4,150
1/.25
850
FC Centrifugal
1
12x 9
Direct/2
1
.60/.75
1/Climatuff
8.2
Hi-Performance
0.375
11.32
2/16
Hi-Performance
0.375
7.88
3/15
Short Orifice
1/ PVC
Propeller
1/24
Direct/1
4,100
1/.25
850
FC Centrifugal
1
12 x 9
BELT/1
1
1.0/2.0
1/Climatuff
8.8
Hi-Performance
0.375
14.00
2/16
Hi-Performance
0.375
7.88
3/15
Short Orifice
1/ PVC
Propeller
1/24
Direct/1
5,620
1/.50
1,075
FC Centrifugal
1
12 x 9
BELT/1
1
1.0/2.0
1075/1400
850/1040
850/1040
1725/1725
1725/1725
48/48
Throwaway/Yes
(2) 20 x 25 x 1
8.3
48/48
Throwaway/Yes
(2) 20 x 25 x 1
8.9
48/48
Throwaway/Yes
(3) 16 X 25 X 1
10.2
56/56
Throwaway/Yes
(3)16 X 25 X 1
10.0
56/56
Throwaway/Yes
(3) 16 X 25 X 1
11.6
NOTES:
1. Cooling Performance is rated at 95 F ambient, 80 F entering dry bulb, 67 F entering wet bulb. Gross capacity does not include the effect of fan motor heat. ARI capacity is
net and includes the effect of fan motor heat. Units are suitable for operation to 20% of nominal cfm. 3 - 5 ton models are certified in accordance with the Unitary AirConditioner Equipment certification program, which is based on ARI Standard 210/240. 6 and 7 ton models are certified in accordance with the Unitary Large Equipment
certification program, which is based on ARI Standard 340/360-93.
2. EER and SEER are rated at ARI conditions and in accordance with DOE test procedures.
3. Sound Rating shown is tested in accordance with ARI Standard 270 or 370.
4. Refrigerant charge is an approximate value. For a more precise value, see unit nameplate and service instructions.
RT-PRC002-EN
17
General
Data
10 Ton
12Ton
Downflow and Horizontal Models
TCR121C3,C4,CW
TCR151C3,C4,CW
86,000
10.00
3,000/2,625
81,000
10.10
8.1
106,000
11.00
3,400/3,000
101,000
11.9
9.18
127,000
11.5
4,000/3,500
120,000
12.4
10.43
154,000
11.3
5,000/4,400
147,000
11.5
13.01
2/Climatuff
8.8
Hi-Performance
0.375
14.00
2/16
Hi-Performance
0.375
7.88
3/15
Short Orifice
1 / PVC
Propeller
1/24
Direct/1
5,620
1/.50
1075
FC Centrifugal
1
12 x 9
BELT/1
1
1.0/2.0
2/Copeland Scroll
9.0
Hi-Performance
0 .375
23.93
2/16
Hi-Performance
0.375
12.636
3/15
Short Orifice
1/1.0 NPT
Propeller
1/26
Direct/1
7,100
1/1.00
1125
FC Centrifugal
1
15 x 11
BELT/1
1
2.0/3.0
2/Climatuff
9.2
Hi-Performance
0 .375
28.21
2/16
Hi-Performance
0.375
17.50
3/15
Short Orifice
1/1.0 NPT
Propeller
2/26
Direct/1
10,800
2/.50
1100
FC Centrifugal
1
15 x 15
BELT/1
1
2.0/3.0
2/Copeland Scroll
9.2
Hi-Performance
0.375
27.12
3/16
Hi-Performance
0.375
17.50
3/15
Short Orifice
1/1.0 NPT
Propeller
2/26
Direct/1
10,400
2/.50
1100
FC Centrifugal
1
15 x 15
BELT/1
1
3.0/5.0
1725/1725
1740/1740
1740/1740
1740/3450
56/56
Throwaway/Yes
(3)16 X 25 X 1
145T/145T
Throwaway/Yes
(3)20 X 20 X 2/
(3)16 X 20 X 27
9.1/9.58
145T/145T
Throwaway/Yes
(2)20 X 20 X 2/
(4)20 X 25 X 2
11.0/11.0
145T/145T
Throwaway/Yes
(2)20 X 20 X 2/
(4)20 X 25 X 2
15.0/13.8
6.4/6.4
NOTES:
1. Cooling Performance is rated at 95 F ambient, 80 F entering dry bulb, 67 F entering wet bulb. Gross capacity does not include the effect of fan motor heat. ARI capacity is
net and includes the effect of fan motor heat. Units are suitable for operation to 20% of nominal cfm. Certified in accordance with the Unitary Large Equipment
certification program, which is based on ARI Standard 340/360-93.
2. EER is rated at ARI conditions and in accordance with DOE test procedures.
3. Integrated Part Load Value is based in accordance with ARI Standard 210/240 or 360. Units are rated at 80F ambient, 80F entering dry bulb, and 67F entering wet bulb
at ARI rated cfm.
4. Sound Rating shown is tested in accordance with ARI Standard 270 or 370.
5. Refrigerant charge is an approximate value. For a more precise value, see unit nameplate and service instructions.
6. Face area for Indoor Coil on horizontal models is 12.36.
7. Horizontal models have 4 - 20 x 25 x 2 filters.
8. The refrigerant charge for 8 ton horizontal models is 7.8/8.1 per circuit.
18
RT-PRC002-EN
General
Data
17 Ton
20 Ton
Downflow and Horizontal Models
TCR211C3,C4,CW
TCR241C3,C4,CW
TCR181C3,C4,CW
Cooling Performance1
Gross Cooling Capacity
189,000
220,000
268,000
EER 2
11.5
11.0
10.6
Nominal CFM / ARI Rated CFM
6,000/5,300
7,000/6,200
8,000/7,000
ARI Net Cooling Capacity
180,000
208,000
250,000
Integrated Part Load Value 3
13.3
12.0
11.2
System Power KW
15.65
18.91
23.58
Compressor
No./Type
2/Trane 3-DScroll/Climatuff Scroll 2/Trane3-D Scroll/Copeland Scroll 2/Trane 3-D Scroll
Sound Rating (BELS)4
9.2
9.4
9.4
Outdoor Coil Type
Hi-Performance
Hi-Performance
Hi-Performance
Tube Size (in.) O.D.
0.375
0 .375
0.375
Face Area (sq ft)
35.30
35.30
35.30
Rows/FPI
3/16
3/16
3/16
Indoor Coil Type
Hi-Performance
Hi-Performance
Hi-Performance
Tube Size (in.)
0.375
0.375
0.375
Face Area (sq ft)
26.00
26.000
26.00
Rows/FPI
3/15
4/15
4/15
Refrigerant Control
Short Orifice
Short Orifice
Short Orifice
Drain Connection No./Size (in.)
1/1.0 NPT
1 /1.0 NPT
1/1.0 NPT
Outdoor Fan Type
Propeller
Propeller
Propeller
No. Used/Diameter (in.)
2/26
2/26
2/26
Drive Type/No. Speeds
Direct/1
Direct/1
Direct/1
CFM
11,000
12,800
13,700
No. Motors/HP
2/.50
2/1.00
2/1.00
Motor RPM
1100
1125
1125
Indoor Fan Type
FC Centrifugal
FC Centrifugal
FC Centrifugal
No. Used
1
1
1
Diameter x Width (in.)
18 x 18
18 x 18
18 x 18
Drive Type/No. Speeds
BELT/1
BELT/1
BELT/1
No. Motors
1
1
1
Motor HP (Standard/Oversized)
3.0/5.0
5.0/7.5
5.0/7.5
Motor RPM
(Standard/Oversized)
1740/3450
3450/3470
3450/3470
Motor Frame Size
(Standard/Oversized)
145T/145T
145T/184T
145T/184T
Filters Type/Furnished?
Throwaway/Yes
Throwaway/Yes
Throwaway/Yes
(No.) Size Recommended (in.)
(4/4)20 X 20 X 2/20 X 25 X 26 (4/4)20 X 20 X 2/20 X 25 X 26 (4/4)20 X 20 X 2/20 X 25 X 26
Refrigerant Charge (Lbs of R-22) 5 / Circuit
25/13
25.7/12.5
21.8/21.8
25 Ton
TCR301C3,C4,CW
300,000
10.4
10,000/8,750
278,000
11.0
26.73
2/Trane 3-D Scroll
9.4
Hi-Performance
0.375
35.30
3/16
Hi-Performance
0.375
26.00
4/15
Short Orifice
1/1.0 NPT
Propeller
2/26
Direct/1
13,700
2/1.00
1125
FC Centrifugal
1
18 x 18
BELT/1
1
7.5/NA
3470/NA
184T/NA
Throwaway/Yes
(4/4)20X20X2/20X25X26
24.5/24.5
NOTES:
1. Cooling Performance is rated at 95 F ambient, 80 F entering dry bulb, 67 F entering wet bulb. Gross capacity does not include the effect of fan motor heat. ARI capacity is
net and includes the effect of fan motor heat. Units are suitable for operation to 20% of nominal cfm. 15, 17 and 20 ton models are certified in accordance with the
Unitary Large Equipment certification program, which is based on ARI Standard 340/360-93. 25 ton model ratings shown are tested in accordance with ARI Standard 340/
360-93.
2. EER is rated at ARI conditions and in accordance with DOE test procedures.
3. Integrated Part Load Value is based in accordance with ARI Standard 210/240 or 360. Units are rated at 80F ambient, 80F entering dry bulb, and 67F entering wet bulb
at ARI
rated cfm.
4. Sound Rating shown is tested in accordance with ARI Standard 270 or 370.
5. Refrigerant charge is an approximate value. For a more precise value, see unit nameplate and service instructions.
6. Horizontal models have 8 - 20 x 25 x 2 filters.
RT-PRC002-EN
19
Performance
Data
(3, 4Ton)
Standard Efficiency
Table PD-1 Gross Cooling Capacities (MBH) 3 Ton Single/Three Phase TCD036C1, C3, C4
85
CFM
Airflow
1080
1200
1320
1440
Enter.
Dry
Bulb
61
(F) MBH SHC
75 34.5 26.9
80 34.9 32.0
85 35.9 35.9
90 38.2 38.2
75 35.5 28.5
80 36.0 34.0
85
37.5 37.5
90 39.4 39.4
75 36.3 30.0
80
37.0 36.0
85 38.6 38.6
90 40.4 40.4
75
37.0 31.4
80
37.4 37.4
85 39.5 39.5
90 41.2 41.2
67
MBH SHC
38.8 22.1
39.0 26.1
39.3 30.9
39.6 35.7
39.5 22.1
39.7 27.3
40.0 32.4
40.4 37.5
39.9 22.9
40.2 28.2
40.5 33.7
41.1 39.1
40.3 23.6
40.6 29.1
41.0 34.9
41.6 40.5
73
MBH SHC
41.3 14.6
41.6 19.8
41.9 24.2
42.3 28.5
41.5 14.8
41.9 20.5
42.3 26.0
42.8 29.4
41.8 15.0
42.2 21.2
42.6 27.1
43.2 30.1
41.9 15.2
42.4 21.8
42.9 25.8
43.5 30.8
61
MBH SHC
31.7 25.3
32.2 30.4
33.6 33.6
36.1 36.1
32.6 26.8
33.2 32.4
35.2 35.2
37.5 37.5
33.3 28.2
33.8 33.8
36.5 36.5
38.6 38.6
34.0 29.7
35.0 35.0
37.5 37.5
39.4 39.4
105
67
MBH SHC
33.5 19.4
33.7 23.3
33.9 28.3
34.6 33.4
34.5 19.3
34.6 24.7
34.9 30.2
35.3 35.3
35.1 20.1
35.2 26.0
35.6 32.0
36.4 36.4
35.6 20.9
35.7 27.2
36.2 33.5
37.3 37.3
115
73
MBH SHC
37.6 12.4
37.8 17.4
37.9 22.3
38.2 27.1
38.0 12.6
38.2 18.1
38.5 23.3
38.8 28.4
38.3 12.9
38.6 18.8
38.9 24.1
39.2 29.5
38.5 13.1
38.8 19.5
39.2 24.9
39.6 30.5
61
MBH SHC
25.5 21.8
26.2 26.2
28.5 28.5
31.0 31.0
26.2 23.3
27.4 27.4
29.9 29.9
32.5 32.5
26.9 24.8
28.4 28.4
31.1 31.1
33.8 33.8
27.4 26.1
29.4 29.4
32.1 32.1
34.8 34.8
67
MBH SHC
30.1 16.6
30.2 21.5
30.5 26.5
31.1 31.1
30.9 17.5
31.0 22.9
31.4 28.5
32.6 32.6
31.5 18.4
31.6 24.3
32.2 30.3
33.9 33.9
32.0 19.2
32.2 25.5
33.0 32.1
34.9 34.9
73
MBH SHC
34.9 11.1
35.0 16.0
35.2 21.0
35.4 25.9
35.4 11.3
35.5 16.8
35.7 22.1
35.9 27.4
35.8 11.5
35.9 17.4
36.2 23.1
36.5 28.7
36.0 11.7
36.3 18.1
36.5 24.0
36.9 30.0
NOTES:
1. All capacities shown are gross and have not considered indoor fan heat. To obtain net cooling subtract indoor fan heat.
2. MBH = Total Gross Capacity
3. SHC = Sensible Heat Capacity
Table PD-2 Gross Cooling Capacities (MBH) 4 Ton Single Phase TCR048C1
85
CFM
Airflow
1440
1600
1760
1920
Enter.
Dry
Bulb
61
(F) MBH SHC
75 45.9 35.7
80 46.2 42.1
85
47.4 47.4
90 50.3 50.3
75
47.1 37.6
80
47.6 44.7
85 49.4 49.4
90 51.9 51.9
75 48.2 39.5
80 48.8 47.2
85 50.8 50.8
90 53.2 53.2
75 49.0 41.2
80 49.8 49.5
85 51.9 51.9
90 54.2 54.2
67
MBH SHC
51.4 29.9
51.7 34.5
51.9 40.7
52.2 46.9
52.2 29.3
52.5 35.9
52.8 42.5
53.2 49.1
52.8 30.3
53.1 37.1
53.5 44.1
54.0 51.1
53.2 31.2
53.6 38.2
54.1 45.6
54.7 52.8
73
MBH SHC
54.5 19.6
54.9 26.4
55.3 31.9
55.8 37.5
54.9 19.8
55.4 27.2
55.8 34.3
56.5 38.6
55.2 20.1
55.7 28.0
56.2 35.7
57.0 39.5
55.5 20.4
56.0 28.8
56.6 34.0
57.3 40.3
61
MBH SHC
42.5 33.7
42.9 40.2
44.7 44.7
47.8 47.8
43.6 35.7
44.2 42.8
46.6 46.6
49.6 49.6
44.6 37.5
45.4 45.3
48.3 48.3
51.0 51.0
45.4 39.3
46.4 46.4
49.6 49.6
52.1 52.1
105
67
MBH SHC
45.2 26.7
45.4 31.3
45.6 37.7
46.2 44.2
46.4 26.1
46.5 33.0
46.7 40.0
47.5 47.2
47.2 27.1
47.3 34.7
47.6 42.2
48.4 48.4
47.8 28.1
47.9 36.1
48.3 44.2
49.5 49.5
115
73
MBH SHC
50.2 17.1
50.4 23.6
50.6 29.8
51.0 35.9
50.7 17.4
51.0 24.5
51.3 31.0
51.7 37.5
51.1 17.7
51.5 25.3
51.8 32.0
52.3 38.9
51.4 17.9
51.8 26.1
52.3 32.9
52.8 40.2
61
MBH SHC
35.0 29.6
35.6 35.6
38.7 38.7
41.8 41.8
36.0 31.5
37.2 37.2
40.4 40.4
43.6 43.6
36.8 33.3
38.6 38.6
41.9 41.9
45.3 45.3
37.5 35.1
39.8 39.8
43.3 43.3
46.5 46.5
67
MBH SHC
41.1 24.8
41.3 29.2
41.5 35.6
41.9 41.9
42.2 24.0
42.3 31.0
42.6 38.0
43.7 43.7
43.0 25.1
43.1 32.6
43.5 40.3
45.4 45.4
43.7 26.1
43.8 34.2
44.4 42.5
46.5 46.5
73
MBH SHC
47.0 15.6
47.2 21.9
47.3 28.3
47.5 34.6
47.6 15.8
47.8 22.8
48.0 29.7
48.3 36.4
48.1 16.1
48.3 23.7
48.6 30.9
48.9 38.0
48.4 16.3
48.7 24.4
49.1 31.9
49.4 39.5
NOTES:
1. All capacities shown are gross and have not considered indoor fan heat. To obtain net cooling subtract indoor fan heat.
2. MBH = Total Gross Capacity
3. SHC = Sensible Heat Capacity
20
RT-PRC002-EN
Performance
Data
(4, 5Ton)
Standard Efficiency
Table PD-3 Gross Cooling Capacities (MBH) 4 Ton Three Phase TCR048C3, C4, CW
85
CFM
Airflow
1440
1600
1760
1920
Enter.
Dry
Bulb
61
(F) MBH SHC
75 45.0 35.2
80 45.3 41.7
85 46.7 46.7
90 49.6 49.6
75 46.2 37.2
80 46.7 44.3
85 48.7 48.7
90 51.2 51.2
75
47.2 39.1
80
47.9 46.8
85 50.1 50.1
90 52.5 52.5
75 48.1 40.8
80 48.6 48.6
85 51.2 51.2
90 53.5 53.5
67
MBH SHC
50.6 29.5
50.8 34.2
51.1 40.4
51.4 46.6
51.4 29.0
51.7 35.7
51.9 42.3
52.4 49.0
52.0 29.9
52.3 36.9
52.7 44.0
53.3 51.0
52.5 30.9
52.9 38.0
53.3 45.5
54.0 52.8
73
MBH SHC
54.0 19.4
54.4 26.1
54.7 31.8
55.2 37.4
54.5 19.6
54.9 27.0
55.3 34.0
55.9 38.5
54.8 19.9
55.3 27.8
55.8 35.5
56.4 39.6
55.1 20.2
55.6 28.6
56.2 34.0
56.9 40.5
61
MBH SHC
41.6 33.3
42.1 39.8
44.0 44.0
47.1 47.1
42.7 35.3
43.4 42.5
45.9 45.9
48.9 48.9
43.7 37.1
44.3 44.3
47.6 47.6
50.2 50.2
44.5 38.9
45.7 45.7
48.8 48.8
51.3 51.3
105
67
MBH SHC
44.3 26.3
44.5 30.9
44.6 37.3
45.3 43.9
45.3 25.6
45.5 32.6
45.7 39.6
46.2 46.2
46.1 26.7
46.2 34.3
46.5 41.8
47.5 47.5
46.6 27.7
46.8 35.7
47.2 43.8
48.7 48.7
115
73
MBH SHC
49.1 16.7
49.3 23.2
49.6 29.4
49.9 35.5
49.7 17.0
49.9 24.1
50.2 30.6
50.6 37.1
50.1 17.3
50.4 24.9
50.8 31.6
51.2 38.5
50.4 17.5
50.8 25.7
51.2 32.6
51.7 39.8
61
MBH SHC
34.2 29.3
35.0 35.0
38.0 38.0
41.1 41.1
35.1 31.2
36.5 36.5
39.7 39.7
43.0 43.0
35.9 33.0
37.9 37.9
41.2 41.2
44.4 44.4
36.6 34.8
39.1 39.1
42.5 42.5
45.5 45.5
67
MBH SHC
40.2 24.4
40.4 28.9
40.6 35.3
41.2 41.2
41.2 23.6
41.3 30.6
41.7 37.7
43.1 43.1
42.0 24.7
42.1 32.3
42.6 40.0
44.5 44.5
42.7 25.8
42.8 33.9
43.5 42.1
45.6 45.6
73
MBH SHC
45.8 15.2
46.0 21.5
46.2 27.9
46.4 34.1
46.4 15.4
46.6 22.4
46.8 29.2
47.1 35.5
46.9 15.7
47.1 23.3
47.4 30.4
47.7 37.5
47.2 15.9
47.5 24.0
47.9 31.5
48.2 39.0
NOTES:
1. All capacities shown are gross and have not considered indoor fan heat. To obtain net cooling subtract indoor fan heat.
2. MBH = Total Gross Capacity
3. SHC = Sensible Heat Capacity
Table PD-4 Gross Cooling Capacities (MBH) 5 Ton Single Phase TCR060C1
85
CFM
Airflow
1800
2000
2200
2400
Enter.
Dry
Bulb
61
(F) MBH SHC
75 58.9 45.9
80 59.4 54.1
85 60.7 60.7
90 64.2 64.2
75 60.5 48.3
80 61.2 57.4
85 63.2 63.2
90 66.2 66.2
75 61.8 50.7
80 62.6 60.5
85 64.9 64.9
90
67.8 67.8
75 62.8 52.9
80 63.7 63.2
85 66.3 66.3
90 69.0 69.0
67
MBH SHC
65.7 36.5
65.9 44.4
66.2 52.1
66.7 59.9
66.7 37.6
66.9 46.1
67.3 54.4
67.9 62.8
67.4 38.8
67.7 47.6
68.2 56.5
68.9 65.3
67.9 39.7
68.4 49.0
68.9 58.4
69.8 67.5
73
MBH SHC
69.6 25.3
70.1 33.8
70.5 41.0
71.1 48.0
70.2 25.5
70.7 34.9
71.2 42.1
71.9 49.5
70.6 25.9
71.2 35.9
71.8 45.6
72.5 50.7
70.9 26.2
71.6 36.9
72.2 47.3
73.0 51.8
61
MBH SHC
54.8 43.6
55.5 51.9
57.5 57.5
61.4 61.4
56.3 46.1
57.2 55.2
60.0 60.0
63.7 63.7
57.5 48.4
58.7 58.4
62.1 62.1
65.4 65.4
58.6 50.7
59.7 59.7
63.6 63.6
66.8 66.8
105
67
MBH SHC
58.4 34.7
58.6 40.6
58.9 48.7
59.7 57.0
59.9 34.0
60.0 42.8
60.3 51.7
61.4 60.8
60.9 35.3
61.0 44.9
61.5 54.5
62.4 62.4
61.6 36.6
61.8 46.8
62.4 57.0
63.8 63.8
115
73
MBH SHC
64.9 22.6
65.1 30.8
65.3 38.9
65.6 46.6
65.6 23.0
65.9 31.9
66.1 40.4
66.6 48.7
66.1 23.3
66.5 33.0
66.8 41.8
67.3 50.6
66.6 23.6
67.0 34.0
67.4 43.0
68.0 52.3
61
MBH SHC
45.8 38.8
46.4 46.4
50.2 50.2
54.1 54.1
47.0 41.2
48.4 48.4
52.4 52.4
56.5 56.5
48.1 43.5
50.1 50.1
54.3 54.3
58.7 58.7
49.0 45.8
51.7 51.7
56.1 56.1
60.3 60.3
67
MBH SHC
53.2 32.4
53.5 38.1
53.9 46.3
55.0 54.7
54.6 31.5
54.8 40.3
55.3 49.3
56.6 56.6
55.7 32.9
55.8 42.5
56.6 52.2
58.8 58.8
56.6 34.2
56.8 `44.5
57.8 55.0
60.4 60.3
73
MBH SHC
61.0 20.8
61.2 28.9
61.4 37.0
61.5 45.0
61.8 21.1
62.0 30.0
62.2 38.8
62.5 47.4
62.5 21.5
62.7 31.1
62.9 40.4
63.3 49.5
63.0 21.8
63.3 32.2
63.6 41.9
64.0 51.6
NOTES:
1. All capacities shown are gross and have not considered indoor fan heat. To obtain net cooling subtract indoor fan heat.
2. MBH = Total Gross Capacity
3. SHC = Sensible Heat Capacity
21
Performance
Data
(5, 6Ton)
Standard Efficiency
Table PD-5 Gross Cooling Capacities (MBH) 5 Ton Three Phase TCR060C3, C4, CW
85
CFM
Airflow
1800
2000
2200
2400
Enter.
Dry
Bulb
61
(F) MBH SHC
75
57.5 44.8
80 58.0 52.8
85 59.3 59.3
90 62.7 62.7
75 59.0 47.2
80 59.7 56.0
85 61.7 61.7
90 64.7 64.7
75 60.3 49.5
80 61.2 59.1
85 63.4 63.4
90 66.2 66.2
75 61.3 51.6
80 62.2 61.8
85 64.7 64.7
90
67.4 67.4
67
MBH SHC
64.1 37.4
64.4 43.3
64.6 50.9
65.1 58.5
65.1 36.7
65.3 45.0
65.7 53.2
66.3 61.3
65.8 37.9
66.2 46.5
66.6 55.2
67.3 63.8
66.4 39.1
66.8 47.9
67.3 57.0
68.2 66.0
73
MBH SHC
68.0 24.7
68.5 33.0
68.8 40.1
69.4 46.9
68.5 24.9
69.1 34.1
69.6 42.8
70.2 48.3
68.9 25.3
69.5 35.1
70.1 44.5
70.8 49.5
69.2 25.6
69.9 36.0
70.5 46.2
71.3 50.6
61
MBH SHC
53.5 42.6
54.2 50.7
56.1 56.1
60.0 60.0
54.9 45.0
55.8 53.9
58.5 58.5
62.2 62.2
56.2 47.3
57.3 57.0
60.6 60.6
63.8 63.8
57.2 49.5
58.3 58.3
62.1 62.1
65.2 65.2
105
67
MBH SHC
57.0 33.9
57.3 39.6
57.5 47.5
58.3 55.7
58.5 33.2
58.6 41.8
58.9 50.5
59.9 59.4
59.4 34.5
59.6 43.8
60.0 53.2
60.9 60.9
60.2 35.7
60.3 45.7
60.9 55.7
62.3 62.3
115
73
MBH SHC
63.4 22.0
63.5 30.0
63.8 38.0
64.1 45.5
64.1 22.4
64.3 31.1
64.7 39.8
65.0 47.5
64.6 22.7
64.9 32.2
65.3 41.6
65.8 49.4
65.0 23.0
65.4 33.2
65.9 43.3
66.4 51.1
61
MBH SHC
44.7 37.9
45.3 45.3
49.0 49.0
52.8 52.8
45.9 40.2
47.2 47.2
51.1 51.1
55.1 55.1
46.9 42.5
48.9 48.9
53.0 53.0
57.2 57.2
47.9 44.7
50.4 50.4
54.7 54.7
58.9 58.9
67
MBH SHC
52.1 29.3
52.2 37.2
52.6 45.2
53.7 53.4
53.3 30.8
53.5 39.4
54.0 48.1
55.2 55.2
54.3 32.1
54.5 41.5
55.3 51.0
57.3 57.3
55.3 33.4
55.4 43.4
56.4 53.7
58.9 58.9
73
MBH SHC
59.6 20.3
59.8 28.2
59.9 36.1
60.1 43.9
60.4 20.6
60.6 29.3
60.8 38.0
61.0 46.3
61.0 21.0
61.2 30.4
61.5 39.8
61.8 48.4
61.5 21.3
61.8 31.4
62.1 40.9
62.5 50.4
NOTES:
1. All capacities shown are gross and have not considered indoor fan heat. To obtain net cooling subtract indoor fan heat.
2. MBH = Total Gross Capacity
3. SHC = Sensible Heat Capacity
Table PD-6 Gross Cooling Capacities (MBH) 6 Ton Three Phase TCR075C3, C4, CW
85
CFM
Airflow
2250
2500
2750
3000
Enter.
Dry
Bulb
61
(F) MBH SHC
75 70.2 55.7
80 70.8 66.1
85 73.1 73.1
90 76.7 76.7
75 71.8 58.8
80 72.6 70.1
85 75.4 75.4
90 78.8 78.8
75 73.1 61.5
80 74.1 73.7
85
77.1 77.1
90 80.3 80.3
75 74.0 64.1
80 75.0 75.0
85 78.6 78.6
90 81.6 81.6
67
MBH SHC
77.3 45.8
77.7 53.1
78.1 62.8
78.7 72.4
78.3 44.9
78.7 55.1
79.2 65.5
80.0 75.7
79.0 46.5
79.5 56.9
80.1 67.9
81.1 78.6
79.6 47.9
80.2 58.4
80.9 70.0
82.0 81.2
73
MBH SHC
81.3 29.6
81.9 40.2
82.6 48.5
83.4 57.0
81.8 29.8
82.5 41.5
83.2 52.7
84.2 58.6
82.2 30.3
83.0 42.8
83.8 50.6
84.8 60.1
82.5 30.7
83.3 44.0
84.3 51.5
85.3 61.3
61
MBH SHC
65.2 53.0
66.1 63.4
69.2 69.2
73.4 73.4
66.8 56.0
68.0 67.5
71.8 71.8
75.6 75.6
68.1 58.9
69.4 69.4
73.8 73.8
77.3 77.3
69.3 61.7
71.3 71.3
75.3 75.3
78.7 78.7
105
67
MBH SHC
68.9 41.6
69.1 49.0
69.4 59.2
70.5 69.6
70.2 40.6
70.4 51.6
70.8 62.8
71.9 71.9
71.1 42.1
71.3 54.1
71.9 66.0
73.7 73.7
71.8 43.6
72.1 56.3
72.9 68.9
75.2 75.2
115
73
MBH SHC
75.2 26.0
75.6 36.3
75.9 46.0
76.5 55.5
75.9 26.5
76.3 37.7
76.8 47.7
77.4 57.9
76.4 26.9
76.9 39.0
77.6 49.3
78.2 60.1
76.8 27.2
77.4 40.3
78.1 50.6
78.8 62.0
61
MBH SHC
54.5 47.3
55.9 55.9
60.4 60.4
65.0 65.0
55.9 50.3
58.2 58.2
62.9 62.9
67.5 67.5
57.0 53.1
60.1 60.1
65.0 65.0
69.4 69.4
58.1 55.8
61.9 61.9
66.8 66.8
70.9 70.9
67
MBH SHC
63.0 38.9
63.3 46.2
63.8 56.5
65.1 65.1
64.5 37.8
64.7 48.9
65.3 60.2
67.6 67.6
65.6 39.5
65.8 51.5
66.6 63.7
69.5 69.5
66.4 41.0
66.6 53.9
67.7 67.1
71.0 71.0
73
MBH SHC
70.8 24.0
71.0 34.1
71.3 44.1
71.6 53.9
71.5 24.3
71.8 35.5
72.2 46.1
72.6 56.7
72.1 24.7
72.5 36.8
72.9 47.9
73.4 59.2
72.6 25.1
72.9 37.7
73.5 49.5
74.1 61.5
NOTES:
1. All capacities shown are gross and have not considered indoor fan heat. To obtain net cooling subtract indoor fan heat.
2. MBH = Total Gross Capacity
3. SHC = Sensible Heat Capacity
22
RT-PRC002-EN
Performance
Data
(7Ton)
Standard Efficiency
Table PD-7 Gross Cooling Capacities (MBH) 7 Ton Three Phase TCR090C3, C4, CW
85
CFM
Airflow
2700
3000
3300
3600
Enter.
Dry
Bulb
61
(F) MBH SHC
75 86.3 68.4
80
87.1 81.1
85 89.8 89.8
90 94.3 94.3
75 88.4 72.2
80 89.5 86.1
85 92.7 92.7
90
97.0 97.0
75 90.0 75.6
80 91.3 90.4
85 95.0 95.0
90 99.0 99.0
75 91.3 78.7
80 92.4 92.4
85 96.9 96.9
90 101.0 101.0
67
MBH SHC
95.3 55.9
95.7 65.3
96.3 77.0
97.1 88.8
96.6 55.4
97.1 67.7
97.7 80.3
98.7 92.8
97.5 57.3
98.1 69.8
98.9 83.1
100.0 96.2
98.2 59.2
99.0 71.7
99.9 85.7
101.0 99.3
73
MBH SHC
100.0 36.3
101.0 49.6
102.0 59.5
103.0 69.9
101.0 36.9
102.0 51.3
103.0 65.1
104.0 71.8
102.0 37.5
103.0 53.0
104.0 67.9
105.0 73.5
102.0 38.0
103.0 54.5
104.0 70.6
106.0 75.0
61
MBH SHC
79.3 64.6
80.4 77.4
84.4 84.4
89.8 89.8
81.3 68.4
82.9 82.6
87.9 87.9
92.7 92.7
83.1 72.1
84.8 84.8
90.4 90.4
95.0 95.0
84.7 75.6
87.4 87.4
92.4 92.4
96.8 96.8
105
67
MBH SHC
83.7 50.1
84.0 59.7
84.4 72.3
85.8 85.1
85.5 49.5
85.7 63.1
86.2 76.8
87.7 87.7
86.7 51.4
86.9 66.1
87.7 80.8
90.2 90.2
87.6 53.3
87.9 69.0
89.0 84.6
92.1 92.1
115
73
MBH SHC
92.2 31.7
92.7 44.5
93.0 56.5
93.7 68.2
93.1 32.4
93.7 46.2
94.2 58.7
94.9 71.2
93.8 33.0
94.3 47.5
95.2 60.6
96.0 73.9
94.4 33.4
95.0 48.5
95.9 62.3
96.8 76.4
61
MBH SHC
64.7 57.0
66.8 66.8
72.5 72.5
78.3 78.3
66.3 60.7
69.7 69.7
75.7 75.7
81.8 81.8
67.9 64.3
72.2 72.2
78.4 78.4
84.3 84.3
69.3 67.8
74.4 74.4
80.9 80.9
86.4 86.4
67
MBH SHC
75.6 46.5
75.9 55.9
76.6 68.6
78.6 78.6
77.4 45.7
77.6 59.3
78.6 73.2
82.0 82.0
78.8 47.8
79.1 62.6
80.4 77.8
84.5 84.5
80.1 49.8
80.4 65.7
81.2 81.2
86.5 86.5
73
MBH SHC
86.3 29.1
86.6 41.5
86.9 54.1
87.2 66.1
87.4 29.5
87.7 43.3
88.0 56.6
88.5 69.7
88.2 30.1
88.6 45.0
89.0 58.9
89.6 72.9
88.8 30.6
89.2 46.3
89.9 61.1
90.6 75.9
NOTES:
1. All capacities shown are gross and have not considered indoor fan heat. To obtain net cooling subtract indoor fan heat.
2. MBH = Total Gross Capacity
3. SHC = Sensible Heat Capacity
Table PD-8 Gross Cooling Capacities (MBH) 7 Ton Three Phase - Dual Compressor TCR090D3, D4, DW
85
CFM
Airflow
2700
3000
3300
3600
Enter.
Dry
Bulb
61
(F) MBH SHC
75 83.7 66.2
80 84.5 78.3
85
87.0 87.0
90 91.4 91.4
75 85.8 69.8
80 86.9 83.0
85 89.8 89.8
90 93.9 93.9
75
87.4 73.0
80 88.3 86.6
85 92.0 92.0
90 95.8 95.8
75 88.7 76.0
80 90.0 89.3
85 93.8 93.8
90
97.3 97.3
67
MBH SHC
92.5 54.6
92.9 63.2
93.4 74.4
94.2 85.7
93.7 53.7
94.2 65.5
94.8 77.5
95.8 89.4
94.5 55.4
95.2 67.5
95.9 80.3
97.1 92.7
95.2 57.1
96.0 69.3
96.8 82.7
98.1 95.6
73
MBH SHC
97.1 35.5
97.9 48.0
98.6 57.7
99.6 67.6
97.7 35.8
98.5 49.5
99.4 62.7
101.0 69.4
98.1 36.3
99.0 51.0
100.0 62.3
101.0 70.9
98.4 36.7
99.4 52.5
100.0 64.0
102.0 72.3
61
MBH SHC
77.8 62.9
78.9 75.2
82.3 82.3
87.6 87.6
79.8 66.5
80.8 79.3
85.7 85.7
90.3 90.3
81.5 69.9
83.3 82.8
88.2 88.2
92.4 92.4
83.0 73.2
85.2 85.2
90.1 90.1
94.1 94.1
105
67
MBH SHC
82.8 49.8
83.1 58.5
83.4 70.4
84.2 82.2
84.4 48.7
84.6 61.6
85.1 74.6
86.6 85.9
85.6 50.5
85.8 64.4
86.5 78.3
88.3 88.3
86.5 52.3
86.8 67.0
87.7 81.7
90.1 90.1
115
73
MBH SHC
90.5 31.7
90.9 43.7
91.3 55.0
91.9 66.1
91.3 32.1
91.8 45.3
92.4 57.0
93.1 68.8
91.8 32.6
92.5 46.8
93.2 58.7
94.0 71.2
92.3 33.1
93.1 48.3
93.9 60.2
94.8 73.4
61
MBH SHC
64.9 56.2
66.4 66.4
71.9 71.9
77.4 77.4
66.6 59.7
69.1 69.1
74.9 74.9
80.7 80.7
68.0 63.0
71.6 71.6
77.6 77.6
83.3 83.3
69.4 66.3
73.8 73.8
80.0 80.0
85.2 85.2
67
MBH SHC
75.7 46.6
76.0 55.2
76.5 67.2
78.4 77.9
77.5 45.4
77.7 58.4
78.5 71.5
80.9 80.9
78.9 47.4
79.1 61.4
80.2 75.8
83.3 83.3
80.1 49.3
80.3 64.3
81.2 79.2
85.2 85.2
73
MBH SHC
85.4 29.3
85.7 41.2
85.9 52.9
86.4 64.3
86.3 29.7
86.7 42.8
87.1 55.2
87.6 67.5
87.0 30.2
87.5 44.3
88.0 57.3
88.6 70.4
87.6 30.6
88.1 45.6
88.7 59.1
89.5 73.0
NOTES:
1. All capacities shown are gross and have not considered indoor fan heat. To obtain net cooling subtract indoor fan heat.
2. MBH = Total Gross Capacity
3. SHC = Sensible Heat Capacity
23
Performance
Data
(8, 10Ton)
Standard Efficiency
Table PD-9 Gross Cooling Capacities (MBH) 8 Three Phase TCR102C3, C4, CW
Ambient Temperature
85
CFM
Air Flow
3060
3400
3740
4080
Enter
Dry
Bulb
61
67
73
(F) MBH SHC MBH SHC MBH SHC
75 98.2 78.0 110.0 61.6 115.0 42.2
80 99.0 92.2 110.0 74.7 116.0 57.0
85 102.0 102.0 111.0 87.6 116.0 67.6
90 108.0 108.0 112.0 101.0 118.0 78.7
75 101.0 82.3 111.0 63.6 116.0 42.5
80 102.0 97.9 112.0 77.2 117.0 58.1
85 106.0 106.0 113.0 91.0 117.0 69.3
90 111.0 111.0 114.0 105.0 118.0 80.4
75 103.0 86.4 112.0 65.0 116.0 43.0
80 103.0 103.0 113.0 79.4 117.0 59.0
85 109.0 109.0 114.0 93.9 118.0 70.8
90 113.0 113.0 115.0 108.0 119.0 81.9
75 105.0 90.0 113.0 66.2 116.0 43.5
80 106.0 106.0 114.0 81.2 118.0 59.6
85 111.0 111.0 115.0 96.4 119.0 71.9
90 115.0 115.0 116.0 111.0 120.0 83.3
95
105
115
61
MBH SHC
73.5 65.2
76.2 76.2
82.9 82.9
89.9 89.9
75.5 69.4
79.5 79.5
86.8 86.8
94.2 94.2
77.4 73.4
82.6 82.6
90.2 90.2
98.1 98.1
77.6 77.6
85.3 85.3
93.3 93.3
101.0 101.0
67
MBH SHC
87.2 54.4
87.4 64.1
88.0 78.0
90.6 89.9
89.6 53.1
89.7 68.0
90.6 83.2
94.2 94.2
91.6 55.5
91.7 71.6
93.0 88.2
98.0 98.0
93.2 57.8
93.5 75.2
93.3 93.3
101.0 101.0
73
MBH SHC
102.0 35.5
103.0 49.1
103.0 62.7
103.0 75.8
104.0 36.1
104.0 51.0
104.0 65.5
105.0 79.6
104.0 36.6
105.0 52.8
105.0 67.9
106.0 82.8
105.0 37.2
106.0 54.5
106.0 70.0
107.0 85.8
NOTES:
1. All capacities shown are gross and have not considered indoor fan heat. To obtain net cooling subtract indoor fan heat.
2. MBH = Total Gross Cooling Capacity
3. SHC = Sensible Heat Capacity
Table PD-10 Gross Cooling Capacities (MBH) 10 Ton Three Phase TCR120C3, C4, CW
85
CFM
Airflow
3600
4000
4400
4800
Ambient Temperature
95
105
115
Enter
Dry
Entering Wet Bulb
Bulb
61
67
73
61
67
73
61
67
73
61
67
73
(F) MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC
75 115.0 96.2 129.0 74.8 136.0 49.8 106.0 91.1 123.0 70.8 132.0 47.2 95.4 85.9 113.0 66.2 126.0 44.2 85.5 80.9 101.0 63.2 118.0 40.7
80 116.0 116.0 130.0 91.3 137.0 67.8 108.0 107.0 123.0 88.8 133.0 65.8 99.7 99.7 113.0 84.3 127.0 62.4 91.5 91.5 101.0 79.0 119.0 58.8
85 124.0 124.0 130.0 108.0 138.0 81.4 117.0 117.0 124.0 107.0 134.0 81.0 109.0 109.0 114.0 103.0 127.0 79.4 100.0 100.0 103.0 97.4 119.0 76.5
90 130.0 130.0 132.0 125.0 139.0 96.3 124.0 124.0 124.0 124.0 135.0 96.8 117.0 117.0 117.0 117.0 128.0 96.1 109.0 109.0 109.0 109.0 119.0 94.0
75 118.0 102.0 131.0 76.6 137.0 50.5 109.0 96.9 125.0 73.9 133.0 48.0 98.1 91.6 115.0 69.6 127.0 45.0 86.9 86.9 104.0 64.4 120.0 41.7
80 121.0 120.0 132.0 94.8 138.0 69.2 113.0 113.0 125.0 93.3 134.0 67.9 104.0 104.0 116.0 89.4 128.0 64.8 95.6 95.6 104.0 84.2 120.0 61.4
85 128.0 128.0 133.0 113.0 139.0 83.4 122.0 122.0 126.0 113.0 135.0 83.3 114.0 114.0 117.0 110.0 129.0 82.6 105.0 105.0 105.0 105.0 121.0 80.5
90 133.0 133.0 134.0 131.0 141.0 98.9 128.0 128.0 128.0 128.0 136.0 100.0 122.0 122.0 122.0 122.0 130.0 101.0 114.0 114.0 114.0 114.0 121.0 99.3
75 121.0 107.0 132.0 78.6 137.0 51.2 111.0 103.0 126.0 76.8 134.0 48.8 101.0 97.2 117.0 72.8 128.0 45.9 90.0 90.0 106.0 67.7 121.0 42.5
80 124.0 124.0 133.0 97.8 139.0 70.0 117.0 117.0 127.0 97.4 135.0 69.9 108.0 108.0 118.0 94.3 129.0 66.5 99.2 99.2 106.0 89.2 122.0 63.9
85 131.0 131.0 134.0 117.0 140.0 85.1 125.0 125.0 128.0 118.0 136.0 85.6 118.0 118.0 120.0 116.0 130.0 85.4 109.0 109.0 109.0 108.0 122.0 84.0
90 136.0 136.0 136.0 136.0 142.0 101.0 131.0 131.0 131.0 131.0 137.0 103.0 125.0 125.0 125.0 125.0 131.0 104.0 118.0 118.0 118.0 118.0 123.0 104.0
75 123.0 112.0 133.0 80.3 138.0 51.9 114.0 108.0 127.0 79.1 134.0 49.6 102.0 102.0 119.0 75.9 129.0 46.7 92.8 92.8 107.0 70.8 122.0 43.3
80 127.0 127.0 134.0 101.0 139.0 70.7 121.0 121.0 128.0 101.0 136.0 71.2 112.0 112.0 120.0 98.9 130.0 68.0 102.0 102.0 108.0 94.1 122.0 65.9
85 133.0 133.0 135.0 121.0 140.0 86.3 128.0 128.0 130.0 122.0 137.0 87.5 121.0 121.0 121.0 121.0 131.0 87.9 112.0 112.0 112.0 112.0 123.0 87.3
90 137.0 137.0 137.0 137.0 142.0 103.0 133.0 133.0 133.0 133.0 138.0 106.0 128.0 128.0 128.0 128.0 132.0 108.0 120.0 120.0 120.0 120.0 124.0 109.0
NOTES:
1. All capacities shown are gross and have not considered indoor fan heat. To obtain net cooling subtract indoor fan heat.
2. MBH = Total Gross Cooling Capacity
3. SHC = Sensible Heat Capacity
24
RT-PRC002-EN
Performance
Data
(12, 15Ton)
Standard Efficiency
Table PD-11 Gross Cooling Capacities (MBH) 12 Ton Three Phase TCR150C3, C4, CW
Ambient Temperature
85
CFM
Airflow
4500
5000
5500
6000
Enter
Dry
Bulb
61
(F) MBH SHC
75
139 116
80
141 138
85
148 148
90
156 156
75
142 122
80
144 144
85
153 153
90
159 159
75
145 128
80
149 149
85
156 156
90
162 162
75
147 134
80
152 152
85
159 159
90
164 164
67
MBH SHC
155 89.6
156 110
156 131
158 151
157 92.5
157 114
158 136
160 157
158 94.4
159 118
160 141
162 162
159 96.3
160 121
162 145
164 164
95
73
MBH SHC
161 59.5
162 82.4
163 99.9
165 118
162 60
163 85.7
165 104
167 118
163 60.9
165 83.3
167 102
168 120
164 61.8
165 84.3
167 104
169 122
105
MBH
118
122
132
142
121
127
138
147
124
132
142
150
127
136
146
153
61
SHC
105
122
132
142
112
127
138
147
118
132
142
150
124
136
146
153
MBH
138
138
139
142
141
141
142
147
143
143
145
150
144
145
147
153
67
SHC
80.9
103
124
142
84.6
108
132
147
88.1
113
139
150
91.5
118
145
153
115
MBH
152
152
153
154
153
154
155
156
154
155
156
157
155
156
157
159
73
SHC
53.8
75.4
95.5
115
54.7
78.3
98.9
120
55.6
79.9
102
124
56.4
81.4
105
128
MBH
108
114
124
134
111
119
129
139
113
123
134
143
115
127
137
145
61
SHC
99.8
114
124
134
106
119
129
139
113
123
134
143
115
127
137
145
MBH
127
127
129
134
130
130
132
139
132
132
134
143
134
134
137
145
67
SHC
76.1
97.6
119
134
79.9
103
127
139
83.4
109
134
143
86.8
114
137
145
MBH
144
144
145
145
145
146
146
147
146
147
148
149
147
148
149
150
73
SHC
50.2
71.7
92.5
113
51.1
74.6
96.4
118
51.9
77
99.9
123
52.8
78.9
103
127
NOTES:
1. All capacities shown are gross and have not considered indoor fan heat. To obtain net cooling subtract indoor fan heat.
2. MBH = Total Gross Cooling Capacity
3. SHC = Sensible Heat Capacity
Table PD-12 Gross Cooling Capacities (MBH) 15 Ton Three Phase TCR180B3, B4, BW
Ambient Temperature
85
CFM
Airflow
5400
6000
6600
7200
Enter.
Dry
Bulb
(F)
75
80
85
90
75
80
85
90
75
80
85
90
75
80
85
90
61
MBH
164
160
171
181
169
166
177
186
172
175
182
190
175
178
186
193
SHC
131
160
171
181
138
166
177
186
144
167
182
190
150
173
186
193
67
MBH
184
185
185
186
187
187
188
186
188
190
191
190
190
191
193
195
SHC
103
126
148
170
107
131
154
186
110
135
159
190
112
138
164
185
95
73
MBH
195
196
197
199
196
197
199
201
198
199
201
203
199
200
202
204
SHC
71.5
95.9
116
135
72.4
98.3
118
139
73.5
99.8
121
142
74.5
102
124
145
61
MBH
154
155
163
174
158
161
170
180
161
165
175
184
164
170
179
188
SHC
125
146
163
174
132
154
170
180
139
161
175
184
145
168
179
188
67
MBH
177
177
177
174
179
180
180
179
182
182
183
186
183
184
185
189
SHC
99.7
122
145
174
103
128
152
179
107
132
158
178
110
136
163
183
105
Entering Wet Bulb
73
61
MBH
190
191
191
193
191
193
194
195
193
193
195
197
194
195
197
199
SHC
68.9
92.5
114
134
69.7
95.5
117
138
70.7
97.3
119
142
71.7
98.8
122
145
MBH
143
146
154
166
146
151
161
172
150
155
167
176
153
159
171
180
SHC
120
139
154
166
126
147
161
172
133
155
167
176
139
159
171
180
115
67
MBH
167
167
167
169
170
170
171
174
172
173
174
178
174
175
171
181
SHC
94.4
117
140
159
98.3
123
148
167
102
128
155
174
105
133
171
180
73
MBH
183
183
184
185
184
185
186
188
186
186
188
190
187
188
190
191
SHC
65.4
88.6
111
131
66.2
91.6
114
136
67.3
94.2
117
141
68.3
96
120
145
61
MBH
131
135
145
157
135
140
152
163
133
145
157
168
137
149
162
172
SHC
114
133
145
157
120
140
152
163
133
145
157
168
137
149
162
172
67
MBH
155
155
155
159
158
158
159
164
161
161
157
168
163
163
162
172
SHC
88.9
112
135
153
92.9
118
143
162
96.6
123
157
168
100
129
162
172
73
MBH
174
174
174
175
176
176
177
178
177
178
179
180
178
179
180
181
SHC
61.4
84.3
107
128
62.3
87.3
111
134
63.3
90.2
114
139
64.2
92.5
118
145
NOTES:
1. All capacities shown are gross and have not considered indoor fan heat. To obtain net cooling subtract indoor fan heat.
2. MBH = Total Gross Capacity
3. SHC = Sensible Heat Capacity
25
Performance
Data
(17, 20Ton)
Standard Efficiency
Table PD-13 Gross Cooling Capacities (MBH) 17 Ton Three Phase TCR210C3, C4, CW
Ambient Temperature
95
85
CFM
Airflow
6300
7000
7700
8400
Enter
Dry
Bulb
(F)
75
80
85
90
75
80
85
90
75
80
85
90
75
80
85
90
61
MBH
189
190
196
207
195
196
203
214
199
200
209
219
202
203
214
223
SHC
149
175
196
207
157
185
203
214
164
195
209
219
170
203
214
223
67
MBH
213
213
214
215
216
217
218
219
219
220
221
223
220
222
223
225
SHC
118
144
168
193
122
149
175
201
126
153
181
209
129
157
186
215
73
MBH
227
228
229
231
229
230
232
234
230
231
234
236
231
232
234
238
SHC
82.8
110
133
155
83.6
113
136
159
84.8
117
138
162
86.1
118
143
166
61
MBH
177
177
186
199
181
183
194
206
185
187
201
212
189
193
206
216
SHC
142
168
186
199
150
178
194
206
157
187
201
212
164
193
206
216
SHC
113
139
164
190
117
145
172
199
121
151
179
208
125
155
186
216
MBH
221
222
222
224
223
224
225
227
225
225
228
230
226
227
229
232
SHC
79.3
106
130
153
80.2
109
134
158
81.6
112
137
162
82.9
114
140
166
105
61
MBH
163
165
176
189
168
169
183
197
171
176
190
203
175
181
196
208
SHC
135
161
176
189
142
169
183
197
149
176
190
203
156
181
196
208
115
67
MBH
192
192
192
194
196
197
197
197
200
200
201
203
202
203
204
208
SHC
107
133
159
185
112
140
167
197
116
146
175
203
120
151
183
208
73
MBH
213
213
214
215
215
216
217
218
217
218
219
221
218
219
221
223
SHC
75.1
101
126
150
76.3
105
131
156
77.7
108
135
161
78.7
110
138
166
61
MBH
149
152
165
178
153
158
172
186
157
164
179
193
160
170
185
198
SHC
128
152
165
178
135
158
172
186
142
164
179
193
149
170
185
198
67
MBH
178
178
178
178
182
183
183
186
186
186
187
192
189
189
190
198
73
SHC
100
126
152
178
105
133
161
186
109
139
169
192
113
145
178
198
MBH
202
203
203
204
205
206
206
207
207
208
209
210
209
210
211
213
SHC
70.5
96.1
122
146
71.6
99.6
127
153
72.7
103
131
159
73.8
106
135
164
NOTES:
1. All capacities shown are gross and have not considered indoor fan heat. To obtain net cooling subtract indoor fan heat.
2. MBH = Total Gross Cooling Capacity
3. SHC = Sensible Heat Capacity
Table PD-14 Gross Cooling Capacities (MBH) 20 Ton Three Phase TCR240B3, B4, BW
85
CFM
Airflow
7200
8000
8800
9600
Enter.
Dry
Bulb
61
(F) MBH SHC
75
228 183
80
230 216
85
237 237
90
248 248
75
233 192
80
236 228
85
244 244
90
254 254
75
237 200
80
240 238
85
249 249
90
258 258
75
240 208
80
243 243
85
253 253
90
261 261
67
MBH SHC
249 141
250 171
252 201
254 231
251 145
253 177
255 209
258 240
254 148
256 181
258 215
261 248
255 151
258 185
260 220
263 254
73
MBH SHC
260 95.9
263 130
267 149
270 175
262 96.7
265 132
268 159
271 187
264 98.1
267 134
270 162
273 190
265 99.4
268 135
271 164
274 194
61
MBH SHC
209 173
212 207
224 224
240 240
215 183
217 217
234 234
248 248
220 192
225 225
241 241
254 254
224 202
232 232
247 247
259 259
95
67
MBH SHC
241 135
242 168
242 201
245 233
246 141
246 177
247 211
250 246
249 146
249 184
251 221
254 254
251 151
252 190
254 229
259 259
115
73
MBH SHC
253 87.6
253 120
254 153
254 185
256 89.3
257 125
257 160
258 194
258 90.8
259 130
260 166
262 202
260 92.1
262 134
263 172
264 210
61
MBH SHC
170 152
177 177
192 192
208 208
175 162
184 184
200 200
217 217
179 171
191 191
208 208
225 225
183 180
197 197
214 214
233 233
67
MBH SHC
200 115
200 148
202 181
208 208
204 121
205 157
207 194
217 217
208 127
209 166
212 205
225 225
212 132
212 174
217 217
232 232
73
MBH SHC
235 79.6
235 112
235 145
235 177
239 81.4
240 117
240 153
241 188
243 83.3
244 122
244 160
245 198
246 84.9
247 126
247 167
248 208
NOTES:
1. All capacities shown are gross and have not considered indoor fan heat. To obtain net cooling subtract indoor fan heat.
2. MBH = Total Gross Capacity
3. SHC = Sensible Heat Capacity
26
RT-PRC002-EN
Performance
Data
(25 Ton)
Standard Efficiency
Table PD-15 Gross Cooling Capacities (MBH) 25 Ton Three Phase TCR300B3, B4, BW
85
CFM
Airflow
9000
10000
10500
11000
Enter.
Dry
Bulb
61
(F) MBH SHC
75
266 224
80
270 268
85
286 286
90
301 301
75
272 237
80
277 277
85
294 294
90
308 308
75
275 243
80
282 282
85
298 298
90
312 312
75
278 248
80
286 286
85
301 301
90
314 314
67
MBH SHC
299 174
300 215
301 255
304 295
303 180
304 223
306 266
310 309
305 183
306 227
308 272
311 311
306 185
308 231
310 277
314 314
73
MBH SHC
319 118
321 161
323 196
326 232
322 120
324 171
327 208
329 239
323 122
325 174
328 216
330 256
324 123
325 160
327 224
330 266
61
MBH SHC
247 215
252 252
272 272
289 289
253 227
262 262
282 282
297 297
256 233
267 267
286 286
301 301
258 239
271 271
289 289
304 304
95
67
MBH SHC
285 167
285 209
286 250
289 289
290 174
290 219
291 263
297 297
291 177
292 223
294 270
301 301
293 181
294 228
296 276
304 304
115
73
MBH SHC
297 108
297 149
298 189
300 229
300 109
301 155
302 197
304 239
301 111
302 157
304 200
306 244
302 113
304 160
305 204
307 249
61
MBH SHC
209 196
221 221
240 240
259 259
214 208
229 229
249 249
268 268
216 214
233 233
253 253
273 273
217 217
237 237
257 257
276 276
67
MBH SHC
244 163
244 190
246 233
259 259
249 156
249 201
253 248
268 268
251 178
251 206
256 255
272 272
253 184
253 212
257 257
276 276
73
MBH SHC
280 99.9
280 142
281 183
282 224
284 102
284 147
285 192
286 235
285 103
286 150
286 196
288 241
286 104
287 153
288 200
289 246
NOTES:
1. All capacities shown are gross and have not considered indoor fan heat. To obtain net cooling subtract indoor fan heat.
2. MBH = Total Gross Capacity
3. SHC = Sensible Heat Capacity
4. Table is for 460 volt capacity. For capacity at 230 volt, multiply table capacity by 101%.
RT-PRC002-EN
27
Performance
Data
(3, 4Ton)
High Efficiency
Table PD-16 Gross Cooling Capacities (MBH) 3 Ton Three Phase TCD037C3, C4
95
67
MBH SHC
41.5 22.3
41.6 27.6
41.7 32.8
41.9 38.0
42.3 23.3
42.4 29.0
42.6 34.7
43.0 40.3
43.0 24.2
43.1 30.3
43.3 36.3
43.8 42.4
43.5 25.1
43.7 31.5
44.0 37.9
44.6 44.2
85
CFM
Airflow
1080
1200
1320
1440
Enter.
Dry
Bulb
61
(F) MBH SHC
75 39.0 29.9
80 39.2 35.3
85 40.0 40.0
90 42.5 42.5
75 40.2 31.6
80 40.4 37.5
85 41.8 41.8
90 44.0 44.0
75 41.1 33.3
80 41.5 39.7
85 43.1 43.1
90 45.2 45.2
75
41.9 34.8
80 42.4 41.7
85 44.2 44.2
90 46.1 46.1
67
MBH SHC
43.8 23.8
44.0 29.0
44.2 34.0
44.4 39.1
44.5 24.6
44.7 30.2
45.0 35.6
45.3 41.1
45.0 25.5
45.3 31.1
45.6 37.0
46.0 42.7
45.2 25.9
45.7 32.0
46.1 38.1
46.6 44.1
73
MBH SHC
45.9 16.4
46.3 22.0
46.6 26.5
47.1 30.9
46.3 16.6
46.6 22.9
47.0 27.1
47.6 31.7
46.5 16.9
47.0 23.9
47.5 27.7
48.0 32.4
46.8 17.1
47.3 24.1
48.0 28.3
48.4 33.0
61
MBH SHC
36.0 28.1
36.2 33.5
37.5 37.5
40.2 40.2
37.0 29.9
37.4 35.8
39.3 39.3
42.0 42.0
37.9 31.5
38.5 38.0
40.9 40.9
43.3 43.3
38.7 33.1
39.4 39.4
42.1 42.1
44.3 44.3
115
73
MBH SHC
42.8 14.3
43.0 19.6
43.2 24.8
43.3 29.7
43.4 14.6
43.6 20.4
43.8 25.9
44.1 31.2
43.8 14.9
44.1 21.2
44.4 26.8
44.8 32.5
44.2 15.2
44.5 21.8
44.9 27.6
45.3 33.6
61
67
MBH SHC MBH SHC
29.3 24.4 34.7 19.8
29.9 29.9 34.8 2 4.1
32.3 32.3 35.0 29.3
34.9 34.9 35.5 34.7
30.2 26.1 35.7 19.9
31.1 31.1 35.8 25.6
33.9 33.9 36.0 31.4
36.7 36.7 36.6 36.6
31.0 27.7 36.5 20.9
32.4 32.4 36.6 27.1
35.3 35.3 36.9 33.3
38.2 38.2 38.1 38.1
31.7 29.3 37.2 21.8
33.6 33.6 37.3 28.5
36.6 36.6 37.7 35.3
39.3 39.3 39.3 39.3
73
MBH SHC
39.9 12.9
40.0 18.1
40.2 23.3
40.3 28.4
40.6 13.2
40.7 18.9
40.9 24.5
41.1 30.0
41.0 13.5
41.3 19.7
41.5 25.6
41.7 31.4
41.4 13.7
41.7 20.4
42.0 26.6
42.3 32.8
NOTES:
1. All capacities shown are gross and have not considered indoor fan heat. To obtain net cooling subtract indoor fan heat.
2. MBH = Total Gross Capacity
3. SHC = Sensible Heat Capacity
Table PD-17 Gross Cooling Capacities (MBH) 4 Ton Three Phase TCR049C3, C4
Ambient Temperature
85
CFM
Airflow
1440
1600
1760
1920
Enter.
Dry
Bulb
(F)
75
80
85
90
75
80
85
90
75
80
85
90
75
80
85
90
61
MBH
47.6
48.1
50.4
52.9
48.8
49.5
52.0
54.3
49.8
50.7
53.3
55.3
50.6
51.9
54.2
56.0
SHC
38.7
46.1
50.4
52.9
40.9
49.2
52.0
54.3
43.1
50.7
53.3
55.3
45.1
51.9
54.2
56.0
95
67
MBH
53.0
53.2
53.5
53.9
53.5
53.9
54.2
54.8
53.9
54.4
54.8
55.5
54.4
54.9
55.4
56.0
SHC
30.0
36.8
43.7
50.5
30.8
38.2
45.6
52.8
31.6
39.3
47.1
54.6
32.3
40.4
48.5
56.0
73
MBH
55.7
56.2
57.0
57.3
56.1
56.7
57.4
57.7
56.5
57.1
57.8
58.2
56.8
57.5
58.2
58.6
SHC
20.2
27.5
33.7
39.2
20.5
28.0
34.3
40.1
20.9
28.5
34.9
41.0
21.2
28.8
35.5
41.9
61
MBH
43.9
44.6
47.5
50.6
45.0
46.0
49.5
52.3
46.0
47.7
51.0
53.6
46.9
49.2
52.2
54.7
SHC
36.6
44.1
47.5
50.6
38.9
46.0
49.5
52.3
41.1
47.7
51.0
53.6
43.2
49.2
52.2
54.7
67
MBH
50.4
50.5
50.7
51.2
51.2
51.4
51.6
52.2
51.9
52.1
52.5
53.6
52.5
52.8
53.2
54.7
SHC
28.4
35.6
42.7
49.9
29.6
37.4
45.1
52.2
30.8
39.1
47.4
53.6
31.9
40.6
49.4
54.7
105
Entering Wet Bulb
73
61
MBH
54.3
54.7
55.0
55.5
54.5
54.9
55.5
56.1
54.9
55.4
55.9
56.5
55.3
55.7
56.3
56.9
SHC
19.1
26.5
32.8
39.3
19.4
27.0
33.7
40.6
19.7
28.9
34.5
41.6
20.1
29.2
35.3
42.7
MBH
40.0
41.0
44.3
47.6
41.0
42.7
46.2
49.5
42.0
44.3
47.9
50.9
42.8
45.7
49.3
52.1
SHC
34.5
41.0
44.3
47.6
36.8
42.7
46.2
49.5
38.9
44.3
47.9
50.9
41.0
45.7
49.3
52.1
115
67
MBH
46.6
46.7
46.9
47.6
47.7
47.8
48.1
49.5
48.5
48.6
49.0
50.9
49.1
49.2
49.8
52.1
SHC
27.6
33.7
40.9
47.6
27.9
35.7
43.6
49.5
29.1
37.6
46.2
50.9
30.2
39.4
48.5
52.1
73
MBH
51.9
52.2
52.3
52.6
52.6
52.8
53.1
53.4
53.1
53.3
53.7
54.1
53.5
53.8
54.3
54.7
SHC
17.8
25.0
31.9
38.6
18.1
26.0
33.3
40.5
18.5
26.8
34.5
42.3
18.9
27.5
35.6
43.8
61
MBH
35.9
37.6
40.9
44.2
36.8
39.2
42.7
46.2
37.7
40.7
44.3
47.7
38.3
42.0
45.8
48.9
SHC
32.3
37.6
40.9
44.2
34.5
39.2
42.7
46.2
36.7
40.7
44.3
47.7
38.3
42.0
45.8
48.9
67
MBH
42.2
42.3
42.6
44.2
43.2
43.3
43.8
46.2
44.0
44.1
44.8
47.7
44.7
44.9
45.8
48.9
73
SHC
25.6
31.5
38.8
44.2
25.7
33.6
41.5
46.2
27.0
35.5
44.2
47.7
28.2
37.4
45.8
48.9
MBH
48.5
48.6
48.7
48.9
49.1
49.3
49.5
49.7
49.7
49.9
50.1
50.4
50.1
50.3
50.7
51.0
SHC
16.1
23.3
30.4
37.3
16.5
24.3
32.0
39.5
16.8
25.4
33.4
41.5
17.2
26.2
34.7
43.3
NOTES:
1. All capacities shown are gross and have not considered indoor fan heat. To obtain net cooling subtract indoor fan heat.
2. MBH = Total Gross Capacity
3. SHC = Sensible Heat Capacity
28
RT-PRC002-EN
Performance
Data
(5, 6Ton)
High Efficiency
Table PD-18 Gross Cooling Capacities (MBH) 5 Ton Three Phase TCR061C3, C4
Ambient Temperature
85
CFM
Airflow
1800
2000
2200
2400
105
115
Enter.
Dry
Entering Wet Bulb
Bulb
61
67
73
61
67
73
61
67
73
61
67
73
(F) MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC
75
80
85
90
75
80
85
90
75
80
85
90
75
80
85
90
56.5
57.0
59.8
62.8
57.8
58.7
61.6
64.5
58.9
60.0
63.1
65.8
59.8
61.3
64.3
66.8
46.0
55.0
59.8
62.8
48.7
58.6
61.6
64.5
51.2
60.0
63.1
65.8
53.5
61.3
64.3
66.8
62.7
63.0
63.3
63.8
63.5
63.9
64.3
65.0
64.2
64.6
65.1
66.0
64.7
65.2
65.8
66.8
35.6
43.9
52.2
60.5
36.8
45.7
54.6
63.5
37.8
47.3
56.8
66.0
38.7
48.7
58.8
66.8
95
66.3
66.8
67.4
68.0
66.8
67.3
68.0
68.8
67.2
67.8
68.7
69.3
67.5
68.2
69.3
69.8
23.9
33.4
39.8
47.1
24.3
34.9
40.8
48.5
24.7
36.0
41.8
49.7
25.0
36.3
42.8
50.8
52.0
52.8
56.3
59.8
53.3
54.5
58.5
61.7
54.3
56.4
60.1
63.2
55.3
58.0
61.4
64.3
43.6
52.6
56.3
59.8
46.2
54.5
58.5
61.7
48.7
56.4
60.1
63.2
51.2
58.0
61.4
64.3
59.3
59.5
59.7
60.4
60.3
60.5
60.8
61.7
61.0
61.3
61.7
63.2
61.6
61.9
62.5
64.3
33.5
42.2
50.8
59.4
35.0
44.3
53.6
61.7
36.3
46.3
56.3
63.2
37.5
48.1
58.6
64.3
64.0
64.4
64.8
65.3
64.5
64.9
65.5
66.1
65.0
65.4
66.1
66.8
65.3
66.1
66.6
67.3
22.4
31.2
39.0
46.8
22.8
32.0
40.2
48.6
23.2
32.7
41.3
50.2
23.6
33.3
42.3
51.6
47.3
48.5
52.4
56.3
48.5
50.5
54.6
58.3
49.5
52.3
56.5
59.9
50.5
53.9
58.0
61.2
41.0
48.5
52.4
56.3
43.6
50.5
54.6
58.3
46.1
52.3
56.5
59.9
48.6
53.9
58.0
61.2
54.6
54.8
55.1
56.2
55.9
56.0
56.5
58.4
56.9
57.0
57.7
60.1
57.7
57.8
58.6
61.5
33.0
39.8
48.5
56.2
32.7
42.2
51.7
58.4
34.2
44.5
54.9
60.1
35.6
46.6
57.8
61.5
61.3
61.5
61.7
62.0
62.0
62.3
62.5
62.9
62.5
62.9
63.3
63.7
63.0
63.3
63.8
64.3
20.8
29.4
37.9
46.2
21.2
30.6
39.7
48.6
21.6
31.8
41.2
50.8
21.9
32.6
42.6
52.7
42.4
44.5
48.3
52.2
43.5
46.3
50.3
54.5
44.5
47.9
52.2
56.1
45.2
49.4
53.8
57.5
38.4
44.5
48.3
52.2
41.0
46.3
50.3
54.5
43.5
47.9
52.2
56.1
45.2
49.4
53.8
57.
49.4
49.7
50.1
52.1
50.6
50.7
51.4
54.3
51.5
51.6
52.6
56.2
52.2
52.5
53.7
5 57.6
30.6
37.3
46.0
52.1
30.2
39.6
49.2
54.3
31.6
41.9
52.4
56.2
33.0
44.1
53.7
57.6
56.8
56.9
57.1
57.3
57.5
57.7
57.9
58.2
58.0
58.3
58.6
59.0
58.5
58.8
59.2
59.6
18.7
27.3
35.8
44.2
19.1
28.5
37.7
46.8
19.5
29.7
39.4
49.2
19.8
30.7
41.0
51.3
NOTES:
1. All capacities shown are gross and have not considered indoor fan heat. To obtain net cooling subtract indoor fan heat.
2. MBH = Total Gross Capacity
3. SHC = Sensible Heat Capacity
Table PD-19 Gross Cooling Capacities (MBH) 6 Ton Three Phase TCR074C3, C4
Ambient Temperature
85
CFM
Airflow
2250
2500
2750
3000
Enter.
Dry
Bulb
(F)
75
80
85
90
75
80
85
90
75
80
85
90
75
80
85
90
61
MBH
68.1
69.1
72.2
75.5
69.5
70.6
74.1
77.3
70.5
72.3
75.7
78.6
71.4
73.6
76.9
79.7
SHC
57.0
68.4
72.2
75.5
60.2
70.6
74.1
77.3
63.1
72.3
75.7
78.6
65.7
73.6
76.9
79.7
67
MBH
74.7
75.0
75.5
76.3
75.5
76.0
76.5
77.6
76.2
76.8
77.4
78.6
76.8
77.4
78.2
79.6
SHC
43.2
53.4
63.7
73.9
44.5
55.5
66.5
77.3
45.7
57.3
69.0
78.6
46.7
59.0
71.3
79.6
95
73
MBH
78.7
79.4
80.7
80.8
79.3
80.2
81.1
81.6
79.7
80.8
81.6
82.2
80.1
81.0
82.1
82.8
SHC
28.8
43.0
48.8
56.9
29.1
43.9
49.7
58.6
29.7
44.8
50.6
60.0
30.1
45.8
51.5
61.4
61
MBH
62.9
64.0
68.6
72.2
64.3
66.4
70.6
74.1
65.5
68.4
72.3
75.5
66.7
69.9
73.6
76.7
SHC
54.2
64.0
68.6
72.2
57.4
66.4
70.6
74.1
60.5
68.4
72.3
75.5
63.5
69.9
73.6
76.7
67
MBH
70.8
71.0
71.3
72.2
71.7
72.0
72.5
74.0
72.4
72.8
73.5
75.5
73.1
73.5
74.4
76.7
SHC
41.1
51.8
62.5
72.2
42.8
54.3
65.8
74.0
44.3
56.6
68.8
75.5
45.6
58.6
71.6
76.7
105
Entering Wet Bulb
73
61
MBH
75.7
76.1
76.8
77.4
76.3
76.8
77.6
78.3
76.8
77.5
78.2
79.0
77.2
78.3
78.8
79.6
SHC
27.0
37.7
47.1
56.7
27.4
38.6
48.6
58.8
28.0
39.4
49.8
60.6
28.4
40.3
51.0
62.3
MBH
57.3
59.4
64.0
68.2
58.7
61.7
66.3
70.2
59.8
63.6
68.1
71.7
60.9
65.4
69.5
73.0
SHC
51.2
59.4
64.0
68.2
54.4
61.7
66.3
70.2
57.5
63.6
68.1
71.7
60.5
65.4
69.5
73.0
115
67
MBH
65.8
66.0
66.4
68.2
66.8
67.0
67.6
70.2
67.7
67.9
68.7
71.7
68.3
68.6
69.5
73.0
SHC
38.5
49.5
60.4
68.2
40.3
52.3
64.2
70.2
42.0
54.8
67.6
71.7
43.6
57.3
69.5
73.0
73
MBH
71.9
72.3
72.7
73.1
72.5
72.9
73.5
74.1
73.1
73.5
74.2
74.8
73.5
74.0
74.8
75.4
SHC
25.0
35.8
45.9
56.0
25.4
37.0
47.7
58.5
25.8
38.0
49.3
60.8
26.3
38.8
50.8
62.9
61
MBH
51.5
54.5
59.1
63.6
52.7
56.6
61.3
65.7
53.6
58.4
63.3
67.3
55.0
60.0
64.8
68.6
SHC
48.2
54.5
59.1
63.6
51.3
56.6
61.3
65.7
53.6
58.4
63.3
67.3
55.0
60.0
64.8
68.6
67
MBH
59.3
59.5
60.2
63.5
60.5
60.7
61.7
65.8
61.4
61.7
63.1
67.5
62.2
62.6
64.9
68.9
SHC
38.3
46.4
57.5
63.5
37.4
49.3
61.5
65.8
39.2
52.1
63.1
67.5
40.9
54.8
64.9
68.9
73
MBH
67.4
67.6
67.8
68.1
68.2
68.5
68.7
69.1
68.9
69.2
69.5
69.9
69.4
69.7
70.1
70.7
SHC
22.6
33.5
44.3
54.9
23.1
35.0
46.6
58.0
23.6
36.5
48.7
61.0
24.1
37.7
50.7
63.7
NOTES:
1. All capacities shown are gross and have not considered indoor fan heat. To obtain net cooling subtract indoor fan heat.
2. MBH = Total Gross Capacity
3. SHC = Sensible Heat Capacity
RT-PRC002-EN
29
Performance
Data
(7, 7Ton)
High Efficiency
Table PD-20 Gross Cooling Capacities (MBH) 7 Ton Three Phase TCR086C3, C4
Ambient Temperature
85
CFM
Airflow
2250
2500
2750
3000
Enter.
Dry
Bulb
61
(F) MBH SHC
75 76.9 60.9
80
77.4 72.1
85 79.7 79.7
90 83.4 83.4
75 78.6 64.1
80 79.3 76.3
85 82.1 82.1
90 85.6 85.6
75 79.8 67.1
80 80.8 80.0
85 84.0 84.0
90
87.4 87.4
75 80.8 69.7
80 81.8 81.8
85 85.6 85.6
90 88.7 88.7
67
MBH SHC
84.3 47.2
84.6 57.6
85.0 67.9
85.6 78.2
85.4 48.9
85.8 59.8
86.3 70.8
87.1 81.7
85.9 49.9
86.7 61.5
87.4 73.3
88.3 84.8
86.4 50.8
87.3 62.9
88.1 75.3
89.2 87.2
95
73
MBH SHC
87.7 32.1
88.5 43.4
89.2 54.3
89.9 60.6
88.3 32.4
89.3 44.2
90.0 61.4
90.8 62.1
88.8 32.9
89.8 44.8
90.9 54.3
91.5 63.5
89.2 33.4
90.3 45.3
91.3 61.4
92.1 64.6
61
MBH SHC
71.6 58.0
72.3 69.2
75.6 75.6
80.0 80.0
73.3 61.3
74.4 73.6
78.5 78.5
82.4 82.4
74.8 64.4
76.0 76.0
80.5 80.5
84.3 84.3
76.1 67.4
78.1 78.1
82.3 82.3
85.9 85.9
67
MBH SHC
80.5 45.0
80.7 55.8
81.0 66.4
81.6 77.1
81.7 46.8
82.0 58.4
82.4 69.8
83.3 81.2
82.7 48.5
83.1 60.6
83.5 72.9
84.3 84.3
83.4 49.8
83.9 62.7
84.5 75.7
85.9 85.9
105
Entering Wet Bulb
73
61
MBH SHC MBH SHC
86.2 30.6 65.9 54.9
86.8 41.8 66.9 66.2
87.2 51.5 71.0 71.0
87.9 61.1 75.9 75.9
86.6 31.0 67.5 58.2
87.1 42.8 68.8 68.8
88.1 52.9 73.9 73.9
88.9 63.2 78.4 78.4
86.8 31.4 68.9 61.3
87.7 45.6 71.2 71.2
88.6 54.0 76.3 76.3
89.6 64.8 80.5 80.5
87.1 31.8 70.2 64.3
88.0 45.9 73.3 73.3
89.0 54.0 78.2 78.2
90.0 66.1 82.2 82.2
67
MBH SHC
75.7 42.4
75.8 53.3
76.0 64.1
76.9 75.2
77.0 44.3
77.2 56.1
77.5 67.9
78.4 78.4
78.0 46.0
78.2 58.7
78.7 71.3
80.4 80.4
78.9 47.6
79.1 61.1
79.8 74.6
82.2 82.2
115
73
MBH SHC
82.6 28.7
82.9 39.6
83.2 50.0
83.7 60.0
83.4 29.2
83.9 41.1
84.3 51.9
84.9 62.6
84.1 29.7
84.5 42.3
85.2 53.5
85.8 65.0
84.7 30.2
85.2 43.2
85.9 55.0
86.6 67.1
61
MBH SHC
60.0 51.7
61.3 61.3
66.1 66.1
71.0 71.0
61.4 55.0
63.8 63.8
68.8 68.8
73.8 73.8
62.8 58.1
66.0 66.0
71.2 71.2
75.9 75.9
64.0 61.1
67.9 67.9
73.3 73.3
77.7 77.7
67
MBH SHC
69.3 42.0
69.6 50.3
69.9 61.1
71.0 71.0
70.9 41.3
71.1 53.2
71.6 65.1
73.8 73.8
72.2 43.2
72.3 56.0
73.1 68.9
75.9 75.9
73.1 44.9
73.3 58.6
74.3 72.6
77.6 77.6
73
MBH SHC
77.8 26.4
78.0 37.2
78.3 47.9
78.5 58.2
78.7 26.9
79.0 38.7
79.3 50.1
79.7 61.2
79.4 27.3
79.8 40.1
80.2 52.0
80.7 64.0
80.1 27.8
80.4 41.3
81.0 53.9
81.5 66.5
NOTES:
1. All capacities shown are gross and have not considered indoor fan heat. To obtain net cooling subtract indoor fan heat.
2. MBH = Total Gross Capacity
3. SHC = Sensible Heat Capacity
Table PD-21 Gross Cooling Capacities (MBH) 7 Ton Three Phase TCR091D3, D4
Ambient Temperature
85
CFM
Airflow
2700
3000
3300
3600
Enter.
Dry
Bulb
(F)
75
80
85
90
75
80
85
90
75
80
85
90
75
80
85
90
61
MBH
80.5
81.5
85.2
89.3
82.3
83.1
87.7
91.6
83.8
85.3
89.6
93.4
84.9
87.1
91.2
94.7
SHC
66.3
79.1
85.2
89.3
69.9
83.1
87.7
91.6
73.3
85.3
89.6
93.4
76.4
87.1
91.2
94.7
67
MBH
89.2
89.5
89.9
90.8
90.2
90.7
91.3
92.4
91.1
91.8
92.4
93.8
91.8
92.6
93.4
94.7
95
73
SHC MBH
50.9 93.5
62.8 95.0
74.6 95.1
86.3 96.1
52.7 94.1
65.2 95.3
77.8 95.8
90.2 96.8
54.1 94.5
67.3 95.7
80.7 96.6
93.5 97.5
55.3 94.9
69.2 96.1
83.2 97.3
94.7 98.0
SHC
34.3
45.5
56.4
66.6
34.6
46.5
57.6
68.2
35.2
47.6
58.8
69.6
35.7
48.7
60.0
71.0
61
MBH
74.3
75.0
80.6
85.3
76.1
77.9
83.4
87.8
77.6
80.5
85.5
89.7
79.1
82.6
87.3
91.2
SHC
62.9
75.0
80.6
85.3
66.6
77.9
83.4
87.8
70.1
80.5
85.5
89.7
73.4
82.6
87.3
91.2
67
MBH
84.5
84.7
85.0
86.2
85.7
86.0
86.5
87.8
86.7
87.1
87.8
89.7
87.5
88.0
88.9
91.2
105
Entering Wet Bulb
73
61
SHC MBH
48.4 90.8
60.7 91.4
72.9 92.0
85.1 92.7
50.4 91.6
63.6 92.1
76.7 92.9
87.8 93.8
52.3 92.1
66.2 92.7
80.1 93.7
89.7 94.6
53.8 92.4
68.5 93.5
83.2 94.3
91.2 95.3
SHC
32.5
45.0
55.7
66.6
33.0
46.0
57.4
69.0
33.5
46.9
58.9
71.1
34.0
47.5
60.0
72.9
MBH
67.8
69.8
75.3
80.6
69.5
72.5
78.3
83.2
71.0
74.9
80.6
85.2
72.3
77.1
82.5
86.9
SHC
59.5
69.8
75.3
80.6
63.1
72.5
78.3
83.2
66.6
74.9
80.6
85.2
70.0
77.1
82.5
86.9
115
67
MBH
78.5
78.7
79.1
80.6
79.9
80.1
80.7
83.1
81.0
81.2
82.1
85.2
81.9
82.2
83.3
86.8
SHC
45.5
57.9
70.3
80.6
47.5
61.0
74.6
83.1
49.5
64.0
78.4
85.2
51.3
66.7
82.0
86.8
73
MBH
86.3
86.8
87.1
87.7
87.2
87.7
88.2
88.8
87.8
88.3
89.1
89.8
88.4
89.0
89.8
90.6
61
SHC MBH
30.2 61.1
42.5 64.2
54.1 69.7
65.5 75.2
30.7 62.7
44.2 66.7
56.1 72.5
68.4 77.9
31.2 64.1
45.2 69.0
58.0 74.9
70.9 80.0
31.7 64.9
46.2 71.0
59.6 76.9
73.3 81.8
SHC
56.0
64.2
69.7
75.2
59.6
66.7
72.5
77.9
63.1
69.0
74.9
80.0
64.9
71.0
76.9
81.8
67
MBH
71.1
71.4
72.1
75.2
72.7
72.9
74.0
77.9
73.9
74.2
74.9
80.0
75.0
75.3
76.9
81.7
73
SHC MBH
45.7 80.8
54.4 81.0
66.9 81.3
75.2 81.6
44.2 81.7
57.7 82.0
71.4 82.4
77.9 82.8
46.2 82.4
60.8 82.8
74.9 83.3
80.0 83.9
48.1 83.0
63.7 83.4
76.9 84.0
81.7 84.7
SHC
27.5
39.8
51.9
63.7
28.0
41.5
54.3
67.0
28.6
43.1
56.4
70.0
29.0
44.2
58.4
72.8
NOTES:
1. All capacities shown are gross and have not considered indoor fan heat. To obtain net cooling subtract indoor fan heat.
2. MBH = Total Gross Capacity
3. SHC = Sensible Heat Capacity
30
RT-PRC002-EN
Performance
Data
(8Ton)
High Efficiency
Table PD-22 Gross Cooling Capacities (MBH) 8 Ton Three Phase TCD103C3, C4, CW
Ambient Temperature
85
CFM
Air Flow
3060
3400
3740
4080
Enter
Dry
Bulb
(F)
75
80
85
90
75
80
85
90
75
80
85
90
75
80
85
90
95
61
67
73
SHC
42.0
57.6
70.5
83.7
42.8
58.5
72.1
85.9
43.5
63.0
73.3
87.8
44.1
65.3
74.5
89.5
61
105
Entering Wet Bulb
67
73
SHC
40.0
56.3
69.4
83.3
40.7
57.6
71.4
86.1
41.4
58.6
73.1
88.6
42.2
59.5
74.7
90.8
115
61
67
73
SHC
37.6
53.9
68.5
83.2
38.4
55.8
71.2
86.9
39.2
57.4
73.4
90.1
39.9
58.8
75.4
92.9
61
67
73
SHC
35.0
51.2
66.8
82.0
35.9
53.6
70.1
86.5
36.6
55.4
73.0
90.5
37.4
57.0
75.6
94.1
NOTES:
1. All capacities shown are gross and have not considered indoor fan heat. To obtain net cooling subtract indoor fan heat.
2. MBH = Total Gross Cooling Capacity
3. SHC = Sensible Heat Capacity
Table PD-23 Gross Cooling Capacities (MBH) 8 Ton Three Phase TCH103C3, C4, CW
Ambient Temperature
85
CFM
Airflow
3060
3400
3740
4080
Enter.
Dry
Bulb
(F)
75
80
85
90
75
80
85
90
75
80
85
90
75
80
85
90
61
67
95
73
SHC
41.4
56.1
68.3
80.6
42.0
56.7
69.3
82.1
42.6
62.3
70.1
83.3
43.2
64.5
70.9
84.4
61
67
105
Entering Wet Bulb
73
61
SHC
39.5
55.5
67.8
81.6
40.3
56.5
69.8
84.0
40.9
57.3
71.1
86.0
41.5
57.8
72.1
87.3
67
115
73
SHC
37.3
53.6
68.0
82.6
38.0
55.0
70.3
85.8
38.7
56.4
72.2
88.6
39.4
57.8
73.9
90.9
61
67
73
SHC
34.5
50.7
66.1
81.3
35.3
53.1
69.2
85.6
36.1
54.7
72.0
89.4
36.9
56.2
74.5
92.8
NOTES:
1. All capacities shown are gross and have not considered indoor fan heat. To obtain net cooling subtract indoor fan heat.
2. MBH = Total Gross Capacity
3. SHC = Sensible Heat Capacity
RT-PRC002-EN
31
Performance
Data
(10, 12Ton)
High Efficiency
Table PD-24 Gross Cooling Capacities (MBH) 10 Ton Three Phase TCR121C3, C4, CW
Ambient Temperature
85
CFM
Airflow
3600
4000
4400
4800
95
105
115
Enter
Dry
Entering Wet Bulb
Bulb
61
67
73
61
67
73
61
67
73
61
67
73
(F) MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC
75 117.0 99.3 131.0 76.4 137.0 50.5 106.0 93.7 124.0 72.8 134.0 48.0 95.1 88.5 112.0 68.1 129.0 45.0 81.1 81.1 100.0 62.7 120.0 41.5
80 119.0 119.0 131.0 93.6 139.0 68.7 110.0 110.0 125.0 91.9 136.0 67.2 101.0 101.0 113.0 86.6 130.0 64.3 92.6 92.6 101.0 81.2 120.0 60.7
85 127.0 127.0 132.0 111.0 140.0 83.6 120.0 120.0 125.0 111.0 137.0 84.3 110.0 110.0 114.0 106.0 130.0 82.5 101.0 101.0 102.0 101.0 120.0 79.5
90 133.0 133.0 134.0 129.0 142.0 98.8 128.0 128.0 128.0 128.0 138.0 101.0 120.0 120.0 120.0 120.0 131.0 100.0 110.0 110.0 110.0 110.0 121.0 98.4
75 120.0 106.0 132.0 78.6 138.0 51.3 109.0 100.0 127.0 76.2 136.0 48.9 97.8 94.8 116.0 71.5 130.0 45.9 90.6 90.6 102.0 65.8 123.0 42.7
80 124.0 124.0 133.0 97.2 140.0 69.7 115.0 115.0 127.0 96.9 137.0 69.2 106.0 106.0 116.0 92.6 131.0 67.2 96.7 96.7 103.0 87.0 123.0 63.8
85 130.0 130.0 134.0 116.0 141.0 85.4 125.0 125.0 128.0 117.0 138.0 86.9 116.0 116.0 118.0 114.0 132.0 86.2 106.0 106.0 106.0 106.0 123.0 84.6
90 136.0 136.0 136.0 134.0 143.0 101.0 132.0 132.0 132.0 132.0 140.0 105.0 125.0 125.0 125.0 125.0 133.0 105.0 116.0 116.0 116.0 116.0 124.0 105.0
75 123.0 112.0 134.0 80.8 139.0 52.2 112.0 107.0 128.0 79.5 136.0 49.8 99.9 99.9 118.0 75.3 132.0 46.9 91.1 91.1 104.0 69.4 124.0 43.7
80 127.0 127.0 135.0 100.0 141.0 75.6 120.0 120.0 129.0 102.0 138.0 70.6 110.0 110.0 119.0 98.4 133.0 69.5 100.0 100.0 105.0 92.6 125.0 66.7
85 133.0 133.0 136.0 120.0 142.0 87.0 128.0 128.0 130.0 123.0 139.0 89.2 121.0 121.0 121.0 121.0 133.0 89.3 110.0 110.0 110.0 110.0 125.0 89.0
90 138.0 138.0 138.0 138.0 144.0 104.0 134.0 134.0 134.0 134.0 141.0 108.0 129.0 129.0 129.0 129.0 134.0 110.0 121.0 121.0 121.0 121.0 126.0 111.0
75 125.0 118.0 135.0 82.6 140.0 53.1 115.0 113.0 130.0 82.1 137.0 50.7 103.0 103.0 120.0 78.9 132.0 47.8 94.0 94.0 106.0 72.9 125.0 44.5
80 130.0 130.0 136.0 103.0 141.0 78.3 124.0 124.0 130.0 106.0 139.0 71.7 114.0 114.0 121.0 104.0 134.0 71.4 104.0 104.0 108.0 98.2 126.0 69.3
85 135.0 135.0 137.0 124.0 143.0 88.4 131.0 131.0 132.0 129.0 140.0 91.2 125.0 125.0 125.0 125.0 134.0 92.2 115.0 115.0 115.0 115.0 126.0 92.9
90 139.0 139.0 139.0 139.0 145.0 106.0 137.0 137.0 137.0 137.0 142.0 111.0 132.0 132.0 132.0 132.0 136.0 114.0 125.0 125.0 125.0 125.0 128.0 116.0
NOTES:
1. All capacities shown are gross and have not considered indoor fan heat. To obtain net cooling subtract indoor fan heat.
2. MBH = Total Gross Cooling Capacity
3. SHC = Sensible Heat Capacity
Table PD-25 Gross Cooling Capacities (MBH) 12 Ton Three Phase TCR151C3, C4, CW
85
CFM
Airflow
4500
5000
5500
6000
Enter
Dry
Bulb
(F)
75
80
85
90
75
80
85
90
75
80
85
90
75
80
85
90
61
Ambient Temperature
105
95
67
73
61
67
67
115
73
61
67
73
MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC
137.0 116.0 157.0 90.2 166.0 60.8 127.0 110.0 151.0 87.1 163.0 58.5 116.0 105.0 140.0 82.3 158.0 55.8 106.0 99.7 128.0 80.6 152.0 52.8
140.0 139.0 158.0 111.0 167.0 82.9 130.0 130.0 151.0 109.0 164.0 80.8 122.0 122.0 141.0 104.0 159.0 77.8 114.0 114.0 128.0 98.5 152.0 74.6
149.0 149.0 158.0 132.0 169.0 100.0 142.0 142.0 151.0 131.0 165.0 99.4 133.0 133.0 141.0 126.0 159.0 98.2 125.0 125.0 130.0 121.0 152.0 96.0
158.0 158.0 160.0 153.0 170.0 118.0 152.0 152.0 154.0 152.0 166.0 118.0 145.0 145.0 145.0 145.0 160.0 118.0 137.0 137.0 137.0 137.0 153.0 117.0
141.0 123.0 159.0 93.4 167.0 61.6 131.0 117.0 154.0 90.9 164.0 59.4 120.0 112.0 144.0 86.6 159.0 56.8 109.0 107.0 132.0 81.0 153.0 53.7
145.0 145.0 160.0 116.0 168.0 84.1 136.0 136.0 154.0 114.0 165.0 82.4 128.0 128.0 144.0 110.0 161.0 80.9 119.0 119.0 132.0 105.0 154.0 77.5
155.0 155.0 161.0 138.0 170.0 103.0 148.0 148.0 155.0 138.0 166.0 102.0 140.0 140.0 145.0 135.0 161.0 102.0 131.0 131.0 134.0 129.0 154.0 100.0
162.0 162.0 163.0 160.0 172.0 121.0 157.0 157.0 157.0 157.0 168.0 122.0 151.0 151.0 151.0 151.0 163.0 123.0 143.0 143.0 143.0 143.0 155.0 122.0
145.0 129.0 161.0 95.8 168.0 62.6 134.0 124.0 156.0 94.4 165.0 60.4 123.0 119.0 147.0 90.4 161.0 57.8 112.0 112.0 135.0 85.1 154.0 54.6
150.0 150.0 162.0 119.0 169.0 85.2 142.0 142.0 156.0 119.0 167.0 84.0 133.0 133.0 147.0 116.0 162.0 82.4 124.0 124.0 135.0 111.0 155.0 80.1
158.0 158.0 163.0 143.0 172.0 104.0 153.0 153.0 157.0 144.0 168.0 104.0 146.0 146.0 149.0 143.0 163.0 105.0 137.0 137.0 137.0 137.0 156.0 104.0
165.0 165.0 165.0 165.0 173.0 123.0 161.0 161.0 161.0 161.0 170.0 126.0 156.0 156.0 156.0 156.0 164.0 127.0 149.0 149.0 149.0 149.0 157.0 127.0
148.0 136.0 162.0 97.9 168.0 63.5 137.0 131.0 157.0 97.1 166.0 61.4 126.0 125.0 150.0 94.3 162.0 58.9 116.0 116.0 138.0 89.0 155.0 55.6
154.0 154.0 163.0 123.0 170.0 86.2 147.0 147.0 158.0 124.0 168.0 85.8 138.0 138.0 150.0 122.0 162.0 83.3 128.0 128.0 138.0 117.0 156.0 82.2
161.0 161.0 165.0 147.0 172.0 106.0 157.0 157.0 160.0 150.0 169.0 106.0 151.0 151.0 152.0 150.0 164.0 107.0 142.0 142.0 142.0 142.0 158.0 107.0
167.0 167.0 167.0 167.0 174.0 126.0 164.0 164.0 164.0 164.0 171.0 128.0 159.0 159.0 159.0 159.0 166.0 131.0 153.0 153.0 153.0 153.0 159.0 132.0
NOTES:
1. All capacities shown are gross and have not considered indoor fan heat. To obtain net cooling subtract indoor fan heat.
2. MBH = Total Gross Cooling Capacity
3. SHC = Sensible Heat Capacity
32
RT-PRC002-EN
(15, 17Ton)
High Efficiency
Table PD-26 Gross Cooling Capacities (MBH) 15 Ton Three Phase TCR181C3, C4, CW
Ambient Temperature
85
CFM
Airflow
5400
6000
6600
7200
Enter.
Dry
Bulb
61
(F) MBH SHC
75
172 144
80
175 169
85
185 185
90
195 195
75
177 153
80
181 180
85
192 192
90
201 201
75
181 162
80
186 186
85
197 197
90
204 204
75
184 170
80
191 191
85
200 200
90
207 207
67
MBH SHC
194 112
195 138
196 164
195 195
197 116
198 144
199 172
200 200
198 123
200 151
202 179
205 202
200 127
202 153
204 185
208 207
95
73
MBH SHC
205 75.2
207 103
209 126
211 149
207 76
209 105
211 129
214 153
208 76.6
210 107
213 131
215 157
209 79.1
211 108
214 134
217 160
61
MBH SHC
159 138
164 162
176 176
188 188
164 147
170 170
183 183
194 194
168 155
177 177
189 189
199 199
168 168
182 182
194 194
203 203
67
MBH SHC
185 107
186 134
186 161
190 184
189 112
189 142
190 171
195 194
191 117
192 148
194 180
199 199
193 121
194 154
194 194
203 203
105
Entering Wet Bulb
73
61
MBH SHC MBH SHC
200 71.9 147 131
202 99.7 153 153
203 124 165 165
204 148 178 178
202 73.2 151 140
204 103 159 159
206 129 173 173
208 155 185 185
204 74.4 152 152
206 105 166 166
208 132 179 179
209 159 191 191
206 76.4 156 156
207 107 171 171
209 136 185 185
211 163 195 195
67
MBH SHC
172 101
173 128
174 156
179 179
176 106
177 136
173 173
185 185
180 111
180 144
183 173
191 191
182 116
183 151
187 181
195 195
115
73
MBH SHC
193 68
194 95.4
195 122
196 147
195 69.3
196 99.4
197 127
199 154
197 70.6
198 102
199 132
201 160
198 71.9
199 105
201 135
203 166
61
MBH SHC
130 130
142 142
155 155
168 168
138 131
148 148
162 162
175 175
142 139
154 154
168 168
181 181
145 145
159 159
174 174
186 186
67
MBH SHC
158 97
158 122
155 155
167 167
162 99.8
162 130
162 162
175 175
165 105
166 137
170 166
181 181
168 110
169 145
174 174
186 186
73
MBH SHC
183 63.4
183 90.5
184 117
184 144
185 64.8
186 94.6
186 124
187 152
187 66.2
188 98.6
189 129
190 160
189 67.4
190 102
191 134
192 167
NOTES:
1 All capacities shown are gross and have not considered indoor fan heat. To obtain net cooling subtract indoor fan heat.
2. MBH = Total Gross Capacity
3. SHC = Sensible Heat Capacity
Table PD-27 Gross Cooling Capacities (MBH)17 Ton Three Phase TCR211C3, C4, CW
Ambient Temperature
85
CFM
Airflow
6300
7000
7700
8400
Enter
Dry
Bulb
(F)
75
80
85
90
75
80
85
90
75
80
85
90
75
80
85
90
61
67
95
73
61
67
105
Entering Wet Bulb
73
61
67
115
73
61
67
73
MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC
200.0 169.0 224.0 130.0 233.0 86.2 184.0 162.0 215.0 125.0 231.0 83.3 169.0 154.0 199.0 118.0 226.0 79.3 147.0 147.0 180.0 113.0 214.0 74.2
202.0 202.0 225.0 161.0 236.0 118.0 190.0 190.0 216.0 158.0 234.0 117.0 177.0 177.0 200.0 151.0 227.0 112.0 164.0 164.0 181.0 142.0 214.0 107.0
216.0 216.0 227.0 191.0 239.0 143.0 206.0 206.0 217.0 190.0 236.0 146.0 193.0 193.0 202.0 184.0 228.0 144.0 180.0 180.0 185.0 176.0 215.0 139.0
227.0 227.0 230.0 221.0 242.0 169.0 220.0 220.0 220.0 220.0 239.0 175.0 209.0 209.0 209.0 209.0 229.0 174.0 196.0 196.0 195.0 195.0 217.0 171.0
205.0 180.0 226.0 134.0 234.0 87.6 190.0 172.0 219.0 131.0 233.0 84.8 174.0 164.0 204.0 124.0 228.0 80.8 155.0 155.0 184.0 116.0 218.0 76.0
210.0 210.0 228.0 167.0 237.0 119.0 198.0 198.0 220.0 167.0 236.0 120.0 185.0 185.0 205.0 160.0 229.0 117.0 171.0 171.0 186.0 152.0 218.0 112.0
223.0 223.0 230.0 199.0 241.0 145.0 215.0 215.0 222.0 202.0 238.0 150.0 202.0 202.0 209.0 197.0 231.0 150.0 188.0 188.0 191.0 189.0 219.0 147.0
232.0 232.0 233.0 230.0 244.0 173.0 227.0 227.0 227.0 227.0 241.0 180.0 218.0 218.0 218.0 218.0 232.0 182.0 205.0 205.0 204.0 204.0 221.0 181.0
210.0 190.0 228.0 138.0 235.0 88.9 195.0 183.0 222.0 137.0 234.0 86.0 179.0 175.0 208.0 130.0 229.0 82.4 161.0 161.0 188.0 122.0 220.0 77.7
217.0 217.0 231.0 173.0 239.0 120.0 206.0 206.0 223.0 174.0 237.0 121.0 192.0 192.0 209.0 169.0 231.0 121.0 178.0 178.0 190.0 161.0 221.0 116.0
228.0 228.0 232.0 206.0 242.0 148.0 221.0 221.0 226.0 211.0 240.0 153.0 210.0 210.0 214.0 209.0 234.0 156.0 196.0 196.0 195.0 195.0 222.0 154.0
235.0 235.0 235.0 235.0 245.0 176.0 232.0 232.0 232.0 232.0 243.0 185.0 224.0 224.0 224.0 224.0 235.0 189.0 213.0 213.0 212.0 212.0 224.0 191.0
214.0 200.0 230.0 141.0 236.0 90.3 200.0 193.0 224.0 141.0 235.0 87.4 181.0 181.0 211.0 136.0 230.0 83.8 166.0 166.0 191.0 128.0 222.0 79.2
222.0 222.0 232.0 177.0 239.0 133.0 213.0 213.0 226.0 181.0 238.0 123.0 199.0 199.0 213.0 178.0 233.0 124.0 184.0 184.0 194.0 170.0 223.0 121.0
231.0 231.0 234.0 211.0 243.0 149.0 226.0 226.0 229.0 220.0 241.0 155.0 216.0 216.0 216.0 216.0 235.0 161.0 203.0 203.0 202.0 202.0 224.0 162.0
238.0 238.0 238.0 238.0 246.0 178.0 235.0 235.0 235.0 235.0 244.0 189.0 229.0 229.0 229.0 229.0 237.0 195.0 219.0 219.0 219.0 219.0 227.0 199.0
NOTES:
1. All capacities shown are gross and have not considered indoor fan heat. To obtain net cooling subtract indoor fan heat.
2. MBH = Total Gross Cooling Capacity
3. SHC = Sensible Heat Capacity
33
Performance
Data
(20, 25 Ton)
High Efficiency
Table PD-28 Gross Cooling Capacities (MBH) 20 Ton Three Phase TCR241C3, C4, CW
95
67
MBH SHC
263 152
264 190
265 228
268 265
267 159
268 199
270 240
274 274
270 164
271 208
274 250
280 280
273 169
274 215
277 260
284 284
85
CFM
Airflow
7200
8000
8800
9600
Enter.
Dry
Bulb
61
(F) MBH SHC
75
246 205
80
250 245
85
263 263
90
274 274
75
253 218
80
257 257
85
270 270
90
280 280
75
258 230
80
264 264
85
276 276
90
285 285
75
262 240
80
270 270
85
280 280
90
288 288
67
MBH SHC
273 158
274 192
275 227
278 262
275 163
277 199
279 236
282 273
278 167
280 204
282 244
286 281
280 169
282 209
284 250
288 288
73
MBH SHC
284 105
287 142
290 171
293 201
285 107
289 144
292 174
295 205
287 109
290 155
293 177
297 209
288 110
291 161
295 179
298 212
61
MBH SHC
228 196
232 232
251 251
266 266
234 209
243 243
261 261
274 274
240 221
252 252
268 268
280 280
246 233
260 260
274 274
284 284
115
73
MBH SHC
273 96.5
274 135
275 170
277 205
275 98.3
277 140
278 177
280 214
277 100
279 144
281 182
283 221
278 102
281 147
282 186
285 228
61
MBH SHC
191 176
201 201
219 219
239 239
194 189
210 210
230 230
250 250
199 199
218 218
240 240
258 258
205 205
226 226
248 248
264 264
67
MBH SHC
222 136
223 172
225 211
237 237
228 142
228 184
232 226
248 248
232 149
233 195
238 238
258 258
236 156
237 205
246 246
265 265
73
MBH SHC
261 91.5
261 130
262 168
262 205
266 93.6
266 136
266 177
267 218
269 95.5
269 141
269 185
271 229
271 97.1
271 146
272 193
275 240
NOTES:
1. All capacities shown are gross and have not considered indoor fan heat. To obtain net cooling subtract indoor fan heat.
2. MBH = Total Gross Capacity
3. SHC = Sensible Heat Capacity
Table PD-29 Gross Cooling Capacities (MBH)25 Ton Three PhaseTCR301C3, C4, CW
85
CFM
Airflow
9000
10000
10500
11000
Enter.
Dry
Bulb
(F)
75
80
85
90
75
80
85
90
75
80
85
90
75
80
85
90
61
MBH
277
284
300
312
284
294
307
318
286
297
310
320
289
300
312
322
SHC
243
284
300
312
258
294
307
318
265
297
310
320
272
300
312
322
95
67
MBH
306
307
309
313
310
310
313
318
311
312
315
320
312
313
316
321
SHC
187
225
269
312
188
233
280
318
190
237
285
320
192
240
289
321
73
MBH
316
321
325
329
319
323
327
331
320
324
328
332
321
324
329
332
SHC
117
169
198
236
121
175
202
241
122
178
204
244
123
181
205
246
61
MBH
258
269
289
305
264
280
298
312
267
285
302
314
270
289
305
317
SHC
234
269
289
305
249
280
298
312
256
285
302
314
264
289
305
317
67
MBH
295
295
298
305
299
300
303
312
300
302
305
314
302
304
307
317
SHC
178
225
271
305
185
236
286
312
189
241
293
314
192
246
299
317
SHC
115
161
202
240
117
170
207
248
118
174
210
251
119
177
212
255
MBH
238
252
273
293
244
263
284
301
247
267
289
305
249
272
293
308
SHC
224
252
273
293
239
263
284
301
246
267
289
305
249
272
293
308
115
67
MBH
276
277
280
293
282
283
287
301
284
285
289
305
286
287
293
308
SHC
169
217
266
293
178
230
284
301
182
237
289
305
186
243
293
308
73
MBH
305
307
308
310
308
309
312
314
309
310
313
316
309
311
314
317
SHC
110
158
201
245
112
163
208
255
113
165
212
260
114
170
215
265
61
MBH
218
235
256
277
224
245
267
287
228
249
272
292
231
253
276
295
SHC
214
235
256
277
224
245
267
287
228
249
272
292
231
253
276
295
67
MBH
253
254
259
277
259
260
267
287
261
262
272
292
263
265
276
295
73
SHC
163
207
256
277
168
221
267
287
172
227
272
292
176
234
276
295
MBH
292
293
293
295
295
296
297
299
296
298
299
301
297
299
300
303
SHC
104
151
198
244
106
158
208
257
107
162
213
264
108
165
217
270
NOTES:
1. All capacities shown are gross and have not considered indoor fan heat. To obtain net cooling subtract indoor fan heat.
2. MBH = Total Gross Capacity
3. SHC = Sensible Heat Capacity
34
RT-PRC002-EN
Performance
Data
(3, 4, 5Ton)
Standard Efficiency
Tons
Unit
Model No.
TCD036C1
TCD048C1
TCH048C1
TCD060C1
TCH060C1
High Speed
Low Speed
CFM
ESP
BHP
ESP
BHP
ESP
BHP
1000
1100
1200
1300
1400
1500
1300
1400
1500
1600
1700
1800
1900
2000
1300
1400
1500
1600
1700
1800
1900
2000
1700
1800
1900
2000
2100
2200
2300
2400
1700
1800
1900
2000
2100
2200
2300
2400
.72
.63
.56
.49
.38
.27
.85
.83
.80
.75
.71
.65
.60
.55
.82
.78
.73
.69
.64
.60
.53
.47
.80
.75
.70
.65
.60
.53
.47
.40
.75
.71
.66
.60
.56
.48
.40
.33
.30
.32
.34
.36
.38
.40
.49
.50
.52
.54
.56
.58
.60
.62
.46
.48
.49
.50
.52
.54
.56
.58
.59
.61
.63
.66
.69
.71
.73
.76
.59
.62
.64
.66
.68
.70
.73
.76
.60
.52
.40
.25
.77
.70
.63
.55
.42
.70
.65
.60
.52
.44
.32
.16
.72
.66
.60
.52
.45
.35
.23
.68
.60
.57
.48
.40
.29
.17
.28
.30
.33
.38
.37
.39
.42
.44
.49
.34
.36
.39
.41
.43
.47
.52
.48
.50
.52
.55
.59
.62
.67
.48
.50
.52
.56
.59
.63
.67
1.48
1.34
1.16
.97
.75
.50
1.62
1.53
1.46
1.39
1.31
1.23
1.16
1.08
1.59
1.52
1.45
1.38
1.31
1.23
1.16
1.08
1.40
1.32
1.25
1.19
1.12
1.03
.92
.78
1.36
1.28
1.21
1.14
1.07
.98
.85
.71
.61
.63
.66
.69
.73
.77
.74
.77
.80
.83
.86
.90
.93
.97
.77
.79
.81
.83
.86
.90
.93
.96
.86
.90
.93
.96
1.01
1.05
1.09
1.13
.86
.90
.93
.97
1.01
1.05
1.09
1.13
RT-PRC002-EN
35
Performance
Data
(6-7 Ton)
Standard Efficiency
Tons
Unit
Model No.
TCD075C
TCH075C
739
787
839
895
953
.55
.72
.92
1.15
1.44
782
829
877
928
983
TCD090C
TCH090C
2400
2700
3000
3300
3600
721
802
884
966
1048
.62
.86
1.17
1.54
1.98
760
836
915
994
1075
.66
.92
1.23
1.60
2.06
801
872
946
1022
1101
952
1011
1073
1139
1208
.89
1.17
1.52
1.93
2.42
988
1043
1104
1167
1234
.92
1.22
1.57
1.99
2.49
1025
1075
1134
1195
1260
.96
1.27
1.63
2.05
2.55
1058
1108
1163
1223
2.11
TCD090D
TCH090D
2700
3000
3300
3600
775
853
932
1011
0.82
1.11
1.46
1.88
813
888
963
1040
0.88
1.18
1.53
1.96
848
920
994
1069
0.93
1.24
1.60
2.04
884
952
1023
1096
0.99
1.30
1.67
2.11
919
984
1052
1122
1.04
1.36
1.74
2.18
953
1016
1081
1148
1.09
1.42
1.80
2.26
987
1047
1110
1176
1.14
1.47
1.87
2.33
1020
1077
1138
1203
1.19
1.53
1.93
2.40
1052
1108
1166
1229
1.23
1.58
1.99
2.47
1084
1137
1194
1254
2.54
Tranes factory supplied motors, in commercial equipment, are definite purpose motors,
specifically designed and tested to operate reliably and continuously at all cataloged
conditions. Using the full horsepower range of our fan motors as shown in our tabular
data will not result in nuisance tripping or premature motor failure. Our products
warranty will not be affected.
36
RT-PRC002-EN
Performance
Data
(8Ton)
Standard Efficiency
CFM
2720
3060
3400
3740
4080
963 2.75
889
925
964
1007
1.68
1.99
2.35
2.78
914
949
987
1028
1.79
2.11
2.48
2.91
986 2.88 1009 3.02 1030 3.15 1051 3.29 1072 3.43
3 HP Oversized Motor & Drive
2720
3060
3400
3740
4080
CFM
1.20
1.30
RPM BHP RPM BHP
2720
3060
3400
3740
4080
RT-PRC002-EN
2.00
RPM BHP
1059
1082
1108
1135
2.37
2.70
3.05
3.45
37
(10 Ton)
Performance
Data
Standard
Efficiency
1.20
1.30
RPM BHP RPM BHP
948
996
1048
1104
1166
2.03
2.49
3.04
3.71
4.53
972
1019
1069
1123
1183
2.13
2.62
3.17
3.83
4.65
3200
3600
4000
4400
4800
CFM
3200
3600
4000
4400
4800
640
704
768
833
1.04
1.39
1.82
2.34
676
736
798
860
1.15
1.52
1.96
2.48
651
708
767
827
887
782
827
876
927
982
1.35
1.70
2.12
2.62
3.21
812
856
902
952
1004
1.47
1.82
2.25
2.76
3.36
842
883
928
976
1027
1.58
1.94
2.38
2.90
3.50
949
987
1027
1070
1115
2.04
2.45
2.93
3.48
4.11
3200
3600
4000
4400
4800
38
RT-PRC002-EN
Performance
Data
Table PD-36 Evaporator Fan Performance
CFM
4000
4500
5000
5500
6000
12 1/2 Ton
(12 Ton)
Standard
Efficiency
TCD150C
4000
4500
5000
5500
6000
12 1/2 Ton
969
1005
1046
1089
3.04
3.62
4.32
5.13
(2)
1.30
RPM BHP
TCH150C
1.10
1.20
1.30
RPM BHP RPM BHP RPM BHP
872
903
939
978
1020
2.78
3.30
3.92
4.66
5.51
901
930
964
1002
2.99
3.52
4.15
4.90
929
957
989
1025
3.21
3.75
4.39
5.14
6000
RT-PRC002-EN
39
Performance
Data
CFM
4800
5400
6000
6600
7200
15 Ton
Standard Efficiency
TCR180B
1.20
1.30
RPM BHP RPM BHP
844
878
916
956
999
2.43 871
3.00 901
3.61 938
4.34 977
5.25 1018
2.57
3.15
3.79
4.51
5.41
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
3 HP Standard Motor & High Static Drive Accessory
4800 898 2.70 923 2.83 946 2.96 970 3.09 994 3.23 1018 3.39 1041 3.54
5400 923 3.29 945 3.43 969 3.58 993 3.73 1016 3.88 1038 4.03 1060 4.17
6000 959 3.97 980 4.15 1000 4.31 1019 4.46 1040 4.62 1061 4.78 1082 4.95
6600 997 4.70 1018 4.90 1037 5.10 1056 5.30 1075 5.49 1093 5.67
7200 1038 5.58 1057 5.77
1.00
1.10
1.20
1.30
RPM BHP RPM BHP RPM BHP RPM BHP
5 HP Standard Motor & Drive
879 3.21 903 3.37 927 3.53 949 3.70
937 4.14 957 4.30 976 4.46 997 4.63
999 5.26 1018 5.44 1036 5.61 1053 5.79
1061 6.59 1079 6.78 1097 6.98 1114 7.18
1128 8.19 1143 8.37 1159 8.57
2.00
RPM BHP
1101
1136
1181
1228
4.97
5.98
7.17
8.58
40
RT-PRC002-EN
Performance
Data
(20Ton)
Standard Efficiency
6400
7200
8000
8800
9600
NOTES:
Fan motor heat (MBH) = 3.15 x Fan BHP
Data includes pressure drop due to wet coils and filters
1. Field Supplied Fan Sheave BK190 Required. Field Supplied Belt may be
necessary.
2. 7.5 HP Standard Motor with Field Supplied Motor Sheave IVP50 Required.
Field Supplied Belt may be necessary.
Table PD-40 Continued
CFM
6400
7200
8000
8800
9600
41
Performance
Data
(25Ton)
Standard Efficiency
7000
7500
8000
8500
9000
9500
10000
10500
11000
For Standard Evaporator Fan Speed (RPM), reference Table PD-53. Tranes factory supplied motors, in commercial equipment, are
definite purpose motors, specifically designed and tested to operate
For Standard Motor & High Static Drive Accessory Fan Speed
reliably and continuously at all cataloged conditions. Using the full
(RPM), reference Table PD-54.
horsepower range of our fan motors as shown in our tabular data
For Standard Motor & Low Static Drive Accessory Fan Speed
will not result in nuisance tripping or premature motor failure. Our
(RPM), reference Table PD-56.
products warranty will not
NOTES:
be affected.
Fan motor heat (MBH) = 3.15 x Fan BHP
Data includes pressure drop due to wet coils and
Table PD-41 Continued
filters
CFM
7000
7500
8000
8500
9000
9500
10000
10500
11000
42
RT-PRC002-EN
Performance
Data
(3, 4, 5Ton)
High Efficiency
Tons
Unit
Model No.
High Speed
Low Speed
CFM
ESP
BHP
ESP
BHP
ESP
BHP
900
1000
1100
1200
1300
1400
1500
0.83
0.78
0.72
0.65
0.59
0.50
0.40
0.28
0.30
0.32
0.34
0.36
0.38
0.40
0.74
0.67
0.61
0.50
0.36
0.26
0.28
0.30
0.33
0.38
1.57
1.43
1.26
1.08
0.88
0.63
0.61
0.63
0.66
0.69
0.73
0.77
TCD049C*
1200
1300
1400
1500
1600
1700
1800
1900
2000
0.91
0.88
0.85
0.83
0.78
0.74
0.69
0.64
0.60
0.48
0.49
0.50
0.52
0.54
0.56
0.58
0.60
0.62
0.83
0.77
0.72
0.65
0.58
0.45
0.35
0.37
0.39
0.42
0.44
0.49
1.63
1.55
1.48
1.41
1.34
1.27
1.20
1.12
0.74
0.77
0.80
0.83
0.86
0.90
0.93
0.97
TCH049C*
1200
1300
1400
1500
1600
1700
1800
1900
2000
0.88
0.84
0.80
0.76
0.72
0.68
0.64
0.57
0.51
0.45
0.46
0.48
0.49
0.50
0.52
0.54
0.56
0.58
0.77
0.72
0.68
0.64
0.55
0.47
0.36
0.20
0.32
0.34
0.36
0.39
0.41
0.43
0.47
0.52
1.68
1.61
1.55
1.47
1.42
1.34
1.27
1.20
1.13
0.75
0.77
0.79
0.81
0.83
0.86
0.90
0.93
0.96
TCD061C*
1600
1700
1800
1900
2000
2100
2200
2300
2400
0.77
0.72
0.67
0.61
0.55
0.48
0.40
0.31
0.23
0.58
0.59
0.61
0.63
0.66
0.69
0.71
0.73
0.76
0.70
0.64
0.56
0.48
0.39
0.29
0.16
0.46
0.48
0.50
0.52
0.55
0.59
0.62
0.67
1.42
1.35
1.29
1.23
1.18
1.09
1.01
0.88
0.78
0.82
0.86
0.90
0.93
0.96
1.01
1.05
1.09
1.13
1600
1700
1800
1900
2000
2100
2200
2300
2400
0.79
0.75
0.71
0.66
0.61
0.55
0.48
0.40
0.31
0.58
0.59
0.62
0.64
0.66
0.68
0.70
0.73
0.76
0.73
0.68
0.63
0.58
0.50
0.42
0.31
0.19
0.46
0.48
0.50
0.52
0.56
0.59
0.63
0.67
1.46
1.42
1.37
1.31
1.25
1.18
1.10
1.00
0.90
0.83
0.86
0.90
0.93
0.97
1.01
1.05
1.09
1.13
TCD037C*
TCH061C*
RT-PRC002-EN
43
Performance
Data
Table PD-43 Evaporator Fan Performance
(6 - 7Ton)
High Efficiency
TCD086
TCH086
2400
2700
TCD091D
3000
TCH091D
3000
3600
721
802
884
966
1048
0.62
0.86
1.17
1.54
1.98
760
836
915
994
1075
0.85
1.13
1.47
1.87
2.34
952
1011
1073
1139
1208
0.58
0.76
0.98
1.23
1.52
924
964
1005
1053
1104
0.60
0.79
1.02
1.28
1.57
965
1000
1041
1084
1134
0.89
1.17
1.52
1.93
2.42
988
1043
1104
1167
1234
0.92
1.22
1.57
1.99
2.49
1025 0.96
1075 1.27
1134 1.63
1195 2.05
1260
0.99
1.31
1.68
2.11
1142
1186
1236
1289
2.26
44
RT-PRC002-EN
Performance
Data
CFM
.10
RPM BHP
2720
3060
3400
3740
4080
494
540
587
634
0.61
0.81
1.06
1.35
(8Ton)
High Efficiency
8 Ton TCR103C
CFM
2720
3060
3400
3740
4080
2.00
RPM BHP
1028 2.31
1042 2.53
1063 2.82
45
Performance
Data
CFM
3200
3600
4000
4400
4800
(10Ton)
High Efficiency
10 Ton TCD121C
1.00
1.10
1.20
1.30
RPM BHP RPM BHP RPM BHP RPM BHP
2 HP Standard Motor & High
Static Drive Accessory
766 1.38 795 1.48 823 1.61 851 1.73
787 1.65 816 1.77 844 1.89 871 2.00
809 1.94 838 2.08 865 2.21 892 2.35
831 2.26 859 2.41 887 2.56 913 2.71
853 2.60 881 2.78 909 2.95 935 3.11
3 HP Oversize Motor & Drive
CFM
3200
3600
4000
4400
4800
CFM
3200
3600
4000
4400
4800
10 Ton TCH121C
406
442
479
515
0.58
0.76
0.98
1.25
0.82
1.00
1.22
1.48
1.79
558
578
602
628
656
0.93
1.12
1.35
1.61
1.93
591
609
631
655
682
623
640
659
682
707
1.18
1.38
1.62
1.90
2.22
653
669
687
708
731
1.31
1.52
1.76
2.05
2.38
763
775
791
807
825
1.85
2.09
2.38
2.70
3.05
CFM
3200
3600
4000
4400
4800
46
1.06
1.25
1.48
1.75
2.07
Performance
Data
Table PD-47 Evaporator Fan Performance
CFM
4000
4500
5000
5500
6000
(12 Ton)
High
Efficiency
12 Ton TCD151C
CFM
4000
4500
5000
5500
6000
918
944
971
999
1027
.10
.20
RPM BHP RPM BHP
4000
4500
5000
5500
6000
521 1.17
534 1.40 566 1.54
581 1.83 611 1.99
628 2.34 657 2.51
2.48
2.97
3.50
4.09
4.72
1013
1039
1065
1092
1120
3.01
3.57
4.19
4.86
5.59
1035
1061
1087
1114
3.17
3.72
4.36
5.05
1057
1082
1108
1135
3.33
3.85
4.52
5.24
12 Ton TCH151C
1.30
RPM BHP
791
811
835
862
893
2.38
2.78
3.24
3.80
4.43
4000
4500
5000
5500
6000
RT-PRC002-EN
47
Performance
Data
Table PD-49 Evaporator Fan Performance
CFM
4800
5400
6000
6600
7200
(15, 17 Ton)
High
Efficiency
15 Ton TCR181C
445
479
519
560
1.04
1.38
1.79
2.28
598
621
648
679
712
1.60
1.95
2.36
2.87
3.46
629
648
673
702
734
1.77
2.12
2.55
3.05
3.65
658
676
699
725
755
760
778
798
816
839
2.68
3.07
3.56
4.09
4.74
4800
5400
6000
6600
7200
.10
.20
RPM BHP RPM BHP
5600
6300
7000
7700
8400
532 1.76
546 2.11 578 2.31
594 2.75 625 2.98
642 3.52 671 3.78
17 Ton TCR211C
Indicates
bothboth
downflow
andand
horizontal
units
. .
Indicates
downflow
horizontal
units
48
5600
6300
7000
7700
8400
RT-PRC002-EN
Performance
Data
6400
7200
8000
8800
9600
(20Ton)
High Efficiency
20 Ton TCR241C
Table 45-2
Evaporator Fan
Table 45-1
1.10
1.20
1.30
RPM BHP RPM BHP RPM BHP
5 HP Standard Motor & High
Static Drive Accessory
765 3.49 788 3.70 810 3.91
799 4.31 820 4.53 841 4.76
837 5.26 857 5.51 876 5.76
879 6.43 897 6.67 915 6.93
925 7.83 941 8.07 958 8.32
8000 896 6.01 915 6.26 934 6.52 953 6.77 971 7.03 989 7.29
8800 933 7.19 951 7.46 969 7.74 986 8.01
49
Performance
Data
CFM
7000
7500
8000
8500
9000
9500
10000
10500
11000
(25Ton)
High Efficiency
25 Ton TCR301C
608 2.54 633 2.73 656 2.89 678 3.06 700 3.25 723 3.44 745 3.65 768 3.87
611 2.78 640 3.02 665 3.24 687 3.43 708 3.61 729 3.79 749 3.98 770 4.19 792 4.41
616 3.07 645 3.31 672 3.56 696 3.80 719 4.02 739 4.22 759 4.41 778 4.60 797 4.81 817 5.03
650 3.66 678 3.90 704 4.16 728 4.43 750 4.68 771 4.90 790 5.10 808 5.31 826 5.52 844 5.74
685 4.31 712 4.56 737 4.83 760 5.12 782 5.39 802 5.65 821 5.88 839 6.09 856 6.30 873 6.53
721 5.04 746 5.30 770 5.58 792 5.88 814 6.18 834 6.46 853 6.72 870 6.96 887 7.18 903 7.41
756 5.85 780 6.12 803 6.41 825 6.72 846 7.04 866 7.35 884 7.64 902 7.90 918 8.14 934 8.38
791 6.74 814 7.03 836 7.33 858 7.64 878 7.98 898 8.31 916 8.62
827 7.71 849 8.02 870 8.33 891 8.63
7.5 HP Standard Motor & Drive
10500
11000
1.50
RPM BHP
875
894
915
937
961
985
4.99
5.59
6.26
6.99
7.79
8.67
50
RT-PRC002-EN
Performance
Data
(6-25Ton)
Unit
Model No.
6 Turns
Open
5 Turns
Open
4 Turns
Open
3 Turns
Open
2 Turns
Open
1 Turn
Open
6, 6
7, 7
Closed
TCR074,075
TCR086,090,091
N/A
N/A
735
722
805
791
875
860
945
929
1015
998
1085
1066
TCD102
TCH102
TCR103
N/A
N/A
N/A
725
604
649
773
652
701
822
701
753
870
749
805
919
798
857
967
846
909
TCR120
TCR121
TCR150
TCR151
807
N/A
706
640
857
519
756
680
908
571
807
720
958
623
857
760
1009
675
908
800
1059
779
958
840
N/A
N/A
N/A
N/A
15
TCR180
TCR181
679
560
721
600
764
640
806
680
849
720
891
760
N/A
N/A
17
TCR210
TCR211
869
615
923
659
978
703
1032
747
1087
791
1141
835
N/A
N/A
20
TCR240,TCR241
615
659
703
747
791
835
N/A
25
TCR300,TCR301
705
742
779
817
854
891
N/A
10
12
Table PD-54 Standard Motor & High Static Drive Accessory Fan Speed (RPM)
Tons
8
10
Unit
Model No.
TCR102
TCR103
TCR120
TCR121
6 Turns
Open
5 Turns
Open
4 Turns
Open
3 Turns
Open
2 Turns
Open
1 Turn
Open
Closed
N/A
N/A
958
N/A
870
779
1008
779
918
831
1059
831
967
883
1109
883
1015
935
1160
935
1064
987
1210
987
1112
1039
N/A
1039
12
TCR151
807
857
908
958
1009
1059
N/A
15
TCR180
TCR181
TCR211
TCR240/TCR241
806
640
835
835
849
680
879
879
891
720
923
923
934
760
967
967
976
800
1011
1011
1019
840
1055
1055
N/A
N/A
N/A
N/A
TCR300/TCR301
816
853
890
928
Table PD-55 Oversize Motor & Sheave/Fan Speed (RPM)
965
1002
N/A
17
20
25
Tons
Unit
Model No.
6 Turns
Open
5 Turns
Open
4 Turns
Open
3 Turns
Open
2 Turns
Open
1 Turn
Open
6, 6,7
7
Closed
TCR074,075,086
TCR090,TCR091
N/A
N/A
923
923
992
992
1060
1060
1129
1129
1197
1197
1265
1265
TCR102
TCR103
958
807
1008
857
1059
908
1109
958
1160
1009
1210
1059
N/A
N/A
10
TCR120
TCR121
1032
807
1086
857
1141
908
1195
958
1250
1009
1304
1059
N/A
N/A
12
TCR150
TCR151
869
869
923
923
978
978
1032
1032
1087
1087
1141
1141
N/A
N/A
15
TCR180
TCR181
806
705
856
755
907
806
957
856
1008
907
1058
957
N/A
N/A
17
TCR210
TCR211
949
816
1008
853
1068
890
1127
928
1187
965
1246
1002
N/A
N/A
928
965
1002
N/A
TCR240,TCR241
816
853
890
Table PD-56 Standard Motor & Low Static Fan Drive
20
NOTE:
1. Factory set at 3 turns open.
Tons
Unit
Model No.
17
25
TCR210
TCR300/TCR301
6 Turns
Open
5 Turns
Open
4 Turns
Open
3 Turns
Open
2 Turns
Open
1 Turn
Open
Closed
705
594
755
631
806
668
856
705
907
742
957
779
N/A
N/A
51
Performance
Data
(3-17Ton)
Table PD-57 Static Pressure Drops Through Accessories (Inches Water Column)
Unit
Model No.
Economizer with
OA/RA Dampers2
Electric Heater
Accessory (KW)3
CFM
Standard
Filters1
100% OA
100% RA
5-12
14-23
TCR036C
TCR037C
960
1200
1440
.03
.04
.04
.05
.06
.07
.01
.01
.01
.01
.01
.02
.01
.02
.03
TCR048C
TCR049C
1280
1600
1920
.04
.06
.09
.06
.02
.10
.01
.08
.03
.01
.02
.03
.02
.04
.06
TCR060C
1600
2000
2400
.04
.06
.08
.08
.10
.12
.02
.03
.06
.02
.03
.05
.04
.07
0.11
TCR061C
1600
2000
2400
.02
.04
.06
.08
.10
.12
.01
.01
.02
.01
.01
.01
.01
.01
.02
6, 6, 7
TCR075C
TCR074C
TCR086C
2000
2500
3000
.04
.07
0.10
.10
.13
.15
.01
.02
.03
.01
.02
.03
.02
.04
.05
TCR090C, D
TCR091D
2400
3000
3600
.06
.10
.15
.12
.15
.20
.02
.03
.03
.02
.03
.04
.03
.05
.07
TCD/TCH102C
2720
3400
4080
.08/.05
.13/.08
.18/.12
.13
.16
.19
.07/.03
.11/.04
.16/.07
.06/.05
.08
.11
.07
.11/.12
.15/.16
TCD/TCH103C
2720
3400
4080
.04/.04
.06/.07
.08/.09
.13
.16
.19
.04
.06
.08
.02
.03
.04
.03
.04
.06
TCD/TCH120C
3200
4000
4800
.11/.07
.17/.11
.25/.16
.15
.19
.22
.10/.04
.15/.06
.22/.10
.07/.08
.11
.14/.18
0.10
.15/.16
.19/.23
TCR121C
3200
4000
4800
.03
.05
.07
.13
.19
.25
.01
.02
.03
.03
.04
.06
.03
.05
.07
.04
.06
.09
TCD/TCH150C
4000
5000
6000
.08/.09
.12/.14
.17/.20
.19
.23
.28
.07
.12
.17
.07/.05
.10/.08
.14/.11
.09/.07
.13/.11
.18/.15
0.11/.08
0.16/0.13
.22/.19
TCR151C
4000
5000
6000
.05
.07
.10
.19
.26
.33
.02
.03
.04
.03
.04
.06
.03
.05
.07
.04
.06
.09
TCR180B
4800
6000
7200
.07
.10
.15
.25
.33
.40
.03
.04
.05
.04
.06
.09
.04
.07
.10
.05
.08
.12
TCD/TCH181C
4800
6000
7200
.04/.03
.06/.05
.09/.07
.14
.20
.27
.03
.04
.05
04
06
09
.04
.07
.10
.05
.08
.12
TCR210C
5600
7000
8400
.09
.14
.20
.30
.39
.47
.04
.05
.06
.06
.10
.15
.07
.11
.17
TCD/TCH211C
5600
7000
8400
.06/.05
.09/.07
.12/.10
.18
.26
.35
.04
.04
.06
.05
.08
.12
.06
.09
.13
.07
.11
.16
Tons
10
12
15
17
36
54
72
.03
.05
.07
NOTES:
1. Tested with: 1" filters 3-7 tons, 2" filters 8-25 tons
2. OA = Outside Air and RA = Return Air.
3. Nominal KW ratings at 240, 480, 600 volts.
52
RT-PRC002-EN
Performance
Data
(20, 25Ton)
Table PD-57 Static Pressure Drops Through Accessories (Inches Water Column) Continued
Tons
Unit
Model No.
Economizer with
OA/RA Dampers2
Electric Heater
Accessory (KW)3
CFM
Standard
Filters1
100% OA
100% RA
TCD240B
TCD241C
6400
8000
9600
.07
.11
.16
.22
.32
.44
.04
.05
.07
.06
.10
.14
.08
.12
.17
.09
.14
.20
TCH240B
TCH241C
6400
8000
9600
.06
.09
.13
.22
.32
.44
.04
.05
.07
.06
.10
.14
.08
.12
.17
.09
.14
.20
TCD300B
TCD301C
7000
9000
11000
.09
.14
.21
.26
.40
.57
.04
.07
.10
.08
.13
.18
.10
.15
.22
.11
.18
.26
TCH300B
TCH301C
7000
9000
11000
.07
.11
.17
.26
.40
.60
.04
.07
.10
.08
.13
.18
.10
.15
.22
.11
.18
.26
20
25
5-12
14-23
36
54
72
NOTES:
1. Tested with: 1" filters 3-7 tons, 2" filters 8-25 tons
2. OA = Outside Air and RA = Return Air.
3. Nominal KW ratings at 240, 480, 600 volts.
53
Performance
Data
(3-25Ton)
Unit
Model No.
KW
Input1
MBH
Output1
No. of
Stages
TCD036C1
5.00
10.00
13.80
17.07
34.14
47.10
TCD036C3, C4
TCD037C3, C4
6.00
12.00
17.40
5.00
10.00
13.80
17.60
6.00
12.00
17.40
23.00
TCR048, 060C1
4, 5
Stage1
Stage 2
KW
Input1
MBH
Output1
KW
Input1
MBH
Output1
1
2
2
5.00
5.00
8.80
17.07
17.07
30.03
5.00
5.00
17.07
17.07
20.48
40.96
59.39
1
2
2
6.00
6.00
8.70
20.48
20.48
29.69
6.00
8.70
20.48
29.69
17.07
34.14
47.10
60.07
20.48
40.96
59.39
78.50
1
2
2
2
1
2
2
2
5.00
5.00
8.80
8.80
6.00
6.00
8.70
14.30
17.07
17.07
30.03
30.03
20.48
20.48
29.69
48.81
5.00
5.00
8.80
17.07
17.07
30.03
6.00
8.70
8.70
20.48
29.69
29.69
5,6, 6, 7, 7
TCR061C3,C4
TCR074, 75C3, C4, CW
TCR090C3, D3, C4, D4, CW, DW
TCR086C,TCR091D
9.003
17.303, 4
18.00
27.004
36.003, 4
30.72
59.04
61.43
92.15
122.87
1
1
1
2
2
9.00
17.30
18.00
18.00
18.00
30.7
59.0
61.4
61.4
61.4
9.00
18.00
18.00
36.00
54.005
61.47
122.94
184.41
1
2
2
18.00
18.00
36.00
61.47
61.47
122.94
18.00
18.00
8-15
17, 20, 25
36.00
54.00
72.006
122.94
184.41
245.88
2
2
2
18.00
36.00
36.00
61.47
122.94
122.94
18.00
18.00
36.00
61.47
61.47
122.94
NOTES:
1. Does not include indoor fan power or heat.
2. Heaters are rated at 240v, 480v. and 600v. For other than rated voltage, CAP =
3. Not available for TCR075, 090CW.
4. Not available for TCR061C3,C4.
5. Not available on TCR102, 120C.
6. Not available on TCR210C.
Voltage
Rated Voltage
30.7
61.4
61.47
61.47
x rated cap.
Distribution
Voltage
Capacity
Multiplier
240
208
230
240
0.75
0.92
1.00
480
440
460
480
0.84
0.94
1.00
600
540
575
600
0.81
0.92
1.00
54
RT-PRC002-EN
Performance
Data
(3-25Ton)
Stages
TCD036C1
1
1
2
2
2
2
2
2
13.2
26.4
36.4
4 Ton
1600 CFM
Three Phase
TCD036C3, C4
TCD037C3, C4
Single Phase
15.8
31.6
45.9
5 Ton
2000 CFM
Single Phase
TCR048C1
Three Phase
TCR048C3,C4
TCR049C3,C4
9.9
19.8
27.3
34.8
11.9
23.7
34.4
45.5
7.9
15.8
21.8
27.8
Three Phase
TCR060C3, C4
TCR061C3, C4
TCR060C1
9.5
19.0
27.5
36.4
For minimum design airflow, see airflow performance table for each unit.
To calculate temp rise at different air flow, use following formula:
Temp. Rise across Elect. Htr =
KW x 3413
1.08 x CFM
NOTE:
1. TCR061C3,C4, 23 KW not available.
KW
9.00
17.30
18.00
27.00
36.00
54.001
72.002
Stages
1
1
1
2
2
2
2
7 Ton
3000 CFM
8 Ton
3400 CFM
9.5
18.2
19.0
28.5
37.9
17.8
35.6
53.4
10 Ton
4000 CFM
12 Ton
5000 CFM
15 Ton
6000 CFM
17 Ton
7000 CFM
20 Ton
8000 CFM
25 Ton
9000 CFM
Three Phase
TCR120
TCR121
Three Phase
TCR150
TCR151
Three Phase
TCR180
TCR181
Three Phase
TCR210
TCR211
Three Phase
TCR240
TCR241
Three Phase
TCR300
TCR301
14.2
28.5
42.7
11.4
9.5
22.8
34.1
19.0
28.5
16.3
24.4
32.5
14.2
21.3
28.5
12.6
19.0
25.3
For minimum design airflow, see airflow performance table for each unit.
To calculate temp rise at different air flow, use following formula:
KW x 3413
Temp. Rise across Elect. Htr =
1.08 x CFM
NOTES:
1. Not available on TCR102, 120 models.
2. Not available on TCR210 model.
55
Controls
Manual/Automatic Changeover
Auto, Heat, Cool or Off System Switch.
Fan Auto or Off
Switch.Two
temperature
setpoint
levers. Optional
Status Indication
LED lights,
System On,
Heat, Cool, or
Service.
Economizer
Controls The
standard
equipment
offering is a fixed
dry bulb
changeover
control. In addition, there are two
optional controls, Enthalpy and
Differential Enthalpy Control.
Enthalpy Control Replaces the dry
bulb control with a wet bulb changeover
controller which has a fully adjustable
set point. Enthalpy control offers a
higher level of comfort control, along
with energy savings potential, than the
standard dry bulb control. This is due to
the additional wet bulb sensing
capability.
56
RT-PRC002-EN
Electrical
Data
Unit
Model No.
Unit
Operating
Voltage Range
TCD036C1
TCD036C3
TCD036C4
187-253
187-253
414-506
27.1
18.6
9.4
40
25
15
28.3
19.8
9.7
45
30
15
TCR048C1
TCR048C3
TCR048C4
TCR048CW
187-253
187-253
414-506
517-633
36.3
24.8
11.9
9.5
60
35
15
15
38.7
27.2
13.0
10.3
60
40
20
15
TCR060C1
TCR060C3
TCR060C4
TCR060CW
187-253
187-253
414-506
517-633
46.5
31.3
16.3
11.9
60
45
25
15
47.8
32.6
16.9
12.0
60
50
25
15
TCR075C3
TCR075C4
TCR075CW
187-253
414-506
517-633
36.6
17.7
14.2
50
25
20
39.5
18.9
14.7
60
25
20
TCR090C3 / D3
TCR090C4 / D4
TCR090CW / DW
187-253
414-506
517-633
43.1/41.7
20.9/20.8
16.7/16.0
60/50
30/25
25/20
46.0/44.6
22.1/22.0
17.2/16.5
60/50
30/25
25/20
TCR102C3
TCR102C4
TCR102CW
187-253
414-506
517-633
49
29
19
60
35
20
53
31
20
60
40
25
10
TCR120C3
TCR120C4
TCR120CW
187-253
414-506
517-633
55
31
22
60
40
25
59
34
24
70
40
30
12
TCR150C3
TCR150C4
TCR150CW
187-253
414-506
518-633
71
32
25
80
40
30
77
35
27
90
45
35
15
TCR180B3
TCR180B4
TCR180BW
187-253
414-506
517-633
85
38
31
100
50
40
91
41
34
100
50
45
17
TCR210C3
TCR210C4
TCR210CW
187-253
414-506
517-633
101
45
37
125
60
45
109
49
40
125
60
50
20
TCR240B3
TCR240B4
TCR240BW
187-253
414-506
517-633
123
53
42
150
60
50
130
57
45
150
70
50
25
TCR300B3
TCR300B4
TCR300BW
187-253
414-506
517-633
132
57
45
150
70
50
N/A
N/A
N/A
N/A
N/A
N/A
Tons
NOTE:
1. HACR breaker per NEC.
2. Values do not include power exhaust accessory.
57
Electrical
Data
Unit
Model No.
Unit
Operating
Voltage Range
TCD037C3
TCD037C4
187-253
414-506
19.6
9.9
30
15
20.8
10.2
30
15
TCR049C3
TCR049C4
187-253
414-506
24.7
11.8
35
15
27.1
12.9
40
15
TCR061C3
TCR061C4
187-253
414-506
30.6
15.9
45
25
31.9
16.5
50
25
TCR074C3
TCR074C4
187-253
414-506
35.2
16.6
50
25
38.1
17.8
50
25
TCR086C3
TCR086C4
187-253
414-506
38.1
18.1
60
25
41.0
19.3
60
25
TCR091D3
TCR091D4
187-253
414-506
41.7
21.6
50
25
44.6
22.8
50
25
TCR103C3
TCR103C4
TCR103CW
187-253
414-506
517-633
45
24
19
50
30
20
48
25
20
60
30
25
TCR121C3
TCR121C4
TCR121CW
187-253
414-506
517-633
49
30
22
60
35
25
52
31
23
60
40
25
TCR151C3
TCR151C4
TCR151CW
187-253
414-506
517-633
61
31
25
80
40
30
67
34
27
80
40
30
TCR181C3
TCR181C4
TCR181CW
187-253
414-506
517-633
81
38
30
100
50
40
87
40
33
100
50
45
TCR211C3
TCR211C4
TCR211CW
187-253
414-506
517-633
94
46
36
110
60
45
102
49
39
125
60
50
TCR241C3
TCR241C4
TCR241CW
TCR301C3
TCR301C4
TCR301CW
187-253
414-506
517-633
187-253
414-506
517-633
123
53
42
130
56
45
150
60
50
150
70
50
130
56
45
N/A
N/A
N/A
150
70
50
N/A
N/A
N/A
Tons
10
12
15
17
20
25
NOTE:
1. HACR breaker per NEC.
2. Values do not include power exhaust accessory.
58
RT-PRC002-EN
Electrical
Data
Tons
6, 6, 7, 7
Accessory
Model Number
Accessory
Operating
Voltage
Phase
HP
RPM
FLA
LRA
BAYPWRX013
208-230
.75
1100
6.6
13.5
BAYPWRX015
460
.75
1100
3.1
6.4
BAYPWRX014
575
.75
1100
2.4
5.2
BAYPWRX016
208-230
3/4
1040
6.6
13.5
460
3/4
1040
3.2
8.4
102, 122
Amps
BAYPWRX018
575
3/4
1040
2.1
5.2
BAYPWRX019
208-230
3/4
1040
6.6
13.5
15, 17
BAYPWRX020
460
3/4
1040
3.2
8.4
20, 25
BAYPWRX021
575
3/4
1040
2.1
5.2
NOTES:
1. 10 and 12 Ton Standard Unit.
2. 10 and 12 Ton High Efficiency Unit.
Table ED-4 Unit Wiring With Electric Heat (Single Point Connection) Standard Efficiency
Standard Indoor Motor
Tons
To Use
With
Heater
Model No.
Heater
KW Rating1
Control
Stages
MCA
TCD036C1
BAYHTRP105A
BAYHTRP110A
BAYHTRP114A
3.7/5.0
7.5/10.0
10.3/13.8
1
2
2
27.1/29.3
48.3/55.3
65.5/75.1
40/40
50/60
70/80
28.3/30.8
49.9/56.8
67.0/76.6
45/45
50/60
70/80
TCR048C1
BAYHTRP105A
BAYHTRP110A
BAYHTRP114A
BAYHTRP118A
3.7/5.0
7.5/10.0
10.3/13.8
13.2/17.6
1
2
2
2
36.3/36.3
50.4/57.3
67.5/77.1
84.7/96.9
60/60
60/60
70/80
90/100
38.7/38.7
53.4/60.3
70.5/80.1
87.7/99.9
60/60
60/70
80/90
90/100
TCR060C1
BAYHTRP105A
BAYHTRP110A
BAYHTRP114A
BAYHTRP118A
3.7/5.0
7.5/10.0
10.3/13.8
13.2/17.6
1
2
2
2
46.5/46.5
51.8/58.7
68.9/78.5
86.1/98.3
60/60
60/60
70/80
90/100
47.8/47.8
53.4/60.3
70.5/80.1
87.7/99.9
60/60
60/70
80/90
90/100
TCD036C3
BAYHTRP306A
BAYHTRP312A
BAYHTRP318A
4.5/6.0
9.0/12.0
13.0/17.4
1
2
2
18.9/21.3
34.5/39.3
48.6/55.6
25/25
35/40
50/60
20.4/22.8
36.0/40.8
50.1/57.1
30/30
40/45
60/60
TCR048C3
BAYHTRP306A
BAYHTRP312A
BAYHTRP318A
BAYHTRP323A
4.5/6.0
9.0/12.0
13.0/17.4
17.2/23.0
1
2
2
2
24.8/24.8
36.5/41.3
50.6/57.6
65.2/74.4
35/35
40/45
60/60
70/80
27.2/27.2
39.5/44.3
53.6/60.6
68.2/77.4
40/40
40/45
60/70
70/80
BAYHTRP306A
BAYHTRP312A
BAYHTRP318A
BAYHTRP323A
4.5/6.0
9.0/12.0
13.0/17.4
17.2/22.0
1
2
2
2
31.3/31.3
37.9/42.7
52.0/59.0
66.6/75.8
45/45
45/45
60/60
70/80
32.6/32.6
39.5/44.3
53.6/60.6
68.2/77.4
50/50
50/50
60/70
70/80
AYRHTRA309BA
AYRHTRA318BA
AYRHTRA327BA
AYRHTRA336BA
6.75/9.0
12.9/17.3
20.2/27.0
27.0/36.0
1
1
2
2
36.6/36.6
52.5/59.4
77.7/88.6
101.2/115.6
50/50
60/60
80/90
110/125
39.5/39.5
56.1/63.0
81.4/92.2
104.8/119.3
60/60
60/70
90/100
110/125
TCR060C3
TCR075C3
NOTES:
1. Heater kw ratings are at 208/240 for 208/230V unit
2. HACR type circuit breaker per NEC.
59
Electrical
Data
Table ED-4 Unit Wiring With Electric Heat (Single Point Connection) Standard Efficiency Continued
Standard Indoor Motor
Tons
To Use
With
Heater
Model No.
Heater
KW Rating1
Control
Stages
MCA
AYRHTRA309BA
AYRHTRA318BA
AYRHTRA327BA
AYRHTRA336BA
6.75/9.0
12.9/17.3
20.2/27.0
27.0/36.0
1
1
2
2
43.1/43.1
52.5/59.4
77.7/88.6
101.2/115.6
60/60
60/60
80/90
110/125
46.0/46.0
56.1/63.0
81.4/92.2
104.8/119.3
60/60
60/70
90/100
110/125
TCR090D3
AYRHTRA309BA
AYRHTRA318BA
AYRHTRA327BA
AYRHTRA336BA
6.75/9.0
12.9/17.3
20.2/27.0
27.0/36.0
1
1
2
2
41.7/41.7
52.5/59.4
77.7/88.6
101.2/115.6
50/50
60/60
80/90
110/125
44.6/44.6
56.1/63.0
81.4/92.2
104.8/119.3
50/50
60/70
90/100
110/125
TCR102C3
AYRHTRJ318A
AYRHTRJ336A
13.5/18.0
27.0/36.0
1
2
57/64
104/118
60/70
110/125
61/68
108/122
70/70
110/125
10
TCR120C3
AYRHTRJ318A
AYRHTRJ336A3
13.5/18.0
27.0/36.0
1
2
59/66
106/121
60/70
110/125
64/71
N/A
70/80
N/A
12
TCR150C3
AYRHTRF318A
AYRHTRF336A
AYRHTRF354A
13.5/18.0
27.0/36.0
40.5/54.0
1
2
2
71/71
108/122
154/176
80/80
110/125
175/200
77/77
115/130
162/184
90/90
125/150
175/200
15
TCR180B3
AYRHTRF318A
AYRHTRF336A
AYRHTRF354A
13.5/18.0
27.0/36.0
40.5/54.0
1
2
2
85/85
108/122
154/176
100/100
110/125
175/200
91/91
115/130
162/184
100/100
125/150
175/200
17
TCR210C3
AYRHTRH336A
AYRHTRH354A
27.0/36.0
40.5/54.0
2
2
115/130
162/184
125/150
175/200
125/139
171/193
125/150
175/200
20
TCR240B3
AYRHTRH336A
AYRHTRH354A
AYRHTRH372A
27.0/36.0
40.5/54.0
54.0/72.0
2
2
2
123/130
162/184
209/238
150/150
175/200
225/250
130/139
171/193
218/247
150/150
175/200
225/250
25
TCR300B3
AYRHTRH336A
AYRHTRH354A
AYRHTRH372A
27.0/36.0
40.5/54.0
54.0/72.0
2
2
2
130/139
171/193
218/247
150/150
175/200
225/250
TCD036C4
BAYHTRP406A
BAYHTRP412A
BAYHTRP418A
6.0
12.0
17.4
1
2
2
11.0
20.0
28.2
15
25
30
11.4
20.4
28.5
15
25
30
TCR048C4
BAYHTRP406A
BAYHTRP412A
BAYHTRP418A
BAYHTRP423A
6.0
12.0
17.4
23.0
1
2
2
2
11.9
20.5
28.7
37.1
15
25
30
40
13.0
21.9
30.0
38.5
20
25
35
40
TCR060C4
BAYHTRP406A
BAYHTRP412A
BAYHTRP418A
BAYHTRP423A
6.0
12.0
17.4
23.0
1
2
2
2
16.3
21.2
29.3
37.7
25
25
30
40
16.9
21.9
30.0
38.5
25
25
35
40
TCR075C4
AYRHTRA409BA
AYRHTRA418BA
AYRHTRA427BA
AYRHTRA436BA
9.0
18.0
27.0
36.0
1
1
2
2
17.7
31.1
44.6
58.1
25
35
45
60
19.0
32.6
46.1
59.6
25
35
50
60
NOTES:
1. Heater kw ratings are at 208/240 for 208/230V unit
2. HACR type circuit breaker per NEC.
3. Do not use in conjunction with oversized motor.
60
RT-PRC002-EN
Electrical
Data
Table ED-4 Unit Wiring With Electric Heat (Single Point Connection) Standard Efficiency Continued
Standard Indoor Motor
Tons
To Use
With
Heater
Model No.
Heater
KW Rating1
Control
Stages
MCA
MCA
AYRHTRA409BA
AYRHTRA418BA
AYRHTRA427BA
AYRHTRA436BA
9.0
18.0
27.0
36.0
1
1
2
2
20.9
31.1
44.6
58.1
30
35
45
60
22.1
32.6
46.1
59.6
30
35
50
60
TCR090D4
AYRHTRA409BA
AYRHTRA418BA
AYRHTRA427BA
AYRHTRA436BA
9.0
18.0
27.0
36.0
1
1
2
2
20.8
31.1
44.6
58.1
25
35
45
60
22.0
32.6
46.1
59.6
25
35
50
60
TCR102C4
AYRHTRJ418A
AYRHTRJ436A
18.0
36.0
1
2
32
59
35
60
34
61
40
70
10
TCR120C4
AYRHTRJ418A
AYRHTRJ436A
18.0
36.0
1
2
34
61
40
70
37
64
40
70
12
TCR150C4
AYRHTRE418A3
AYRHTRE436A
AYRHTRE454A
18.0
36.0
54.0
1
2
2
34
61
88
40
70
90
37
64
91
45
70
100
15
TCR180B4
AYRHTRE418A3
AYRHTRE436A
AYRHTRE454A
18.0
36.0
54.0
1
2
2
38
61
88
50
70
90
41
64
91
50
70
100
17
TCR210C4
AYRHTRG436A
AYRHTRG454A
36.0
54.0
2
2
64
91
70
100
68
95
70
100
20
TCR240B4
AYRHTRG436A
AYRHTRG454A
AYRHTRH472A
36.0
54.0
72.0
2
2
2
64
91
118
70
100
125
68
95
123
70
100
125
25
TCR300B4
AYRHTRG436A
AYRHTRG454A
AYRHTRH472A
36.0
54.0
72.0
2
2
2
68
95
123
70
100
125
TCR048CW
BAYHTRPW06A
BAYHTRPW12A
BAYHTRPW18A
BAYHTRPW23A
6.0
12.0
17.4
23.0
1
2
2
2
9.5
16.6
23.1
29.8
15
20
25
35
10.3
17.6
24.1
30.8
15
20
25
35
TCR060CW
BAYHTRPW06A
BAYHTRPW12A
BAYHTRPW18A
BAYHTRPW23A
6.0
12.0
17.4
23.0
1
2
2
2
11.9
17.4
23.9
30.7
15
20
25
35
12.0
17.6
24.1
30.8
15
20
25
35
TCR075CW
AYRHTRAW18BA
AYRHTRAW27BA
18.0
27.0
1
2
24.9
35.7
25
40
25.5
36.4
30
40
TCR090CW,DW
AYRHTRAW18BA
AYRHTRAW27BA
18.0
27.0
1
2
24.9
35.7
25
40
25.5
36.4
30
40
TCR102CW
AYRHTRJW18A
AYRHTRJW36A
18.0
36.0
1
2
26
48
30
50
27
49
30
50
NOTES:
1. Heater kw ratings are at 480V for 460 unit and 600V for 575V unit.
2. HACR type circuit breaker per NEC.
3. Heater model number for horizontal is AYHHTRC418A.
61
Electrical
Data
Table ED-4 Unit Wiring With Electric Heat (Single Point Connection) Standard Efficiency Continued
Standard Indoor Motor
Tons
To Use
With
Heater
Model No.
Heater
KW Rating1
Control
Stages
MCA
MCA
TCR120CW
AYRHTRJW18A
AYRHTRJW36A
18.0
36.0
1
2
27
49
30
50
30
51
30
60
12
TCR150CW
AYRHTRDW18A4
AYRHTRGW36A4
AYRHTREW54A
18.0
36.0
54.0
1
2
2
27
49
70
30
50
70
30
51
73
35
60
80
15
TCR180BW
AYRHTRDW18A4
AYRHTRGW36A4
AYRHTREW54A
18.0
36.0
54.0
1
2
2
31
49
70
40
50
70
34
51
73
45
60
80
17
TCR210CW
AYRHTRGW36A3
AYRHTRGW54A
36.0
54.0
2
2
51
73
60
80
55
77
60
80
20
TCR240BW
AYRHTRGW36A3
AYRHTRGW54A
AYRHTRHW72A
36.0
54.0
72.0
2
2
2
51
73
95
60
80
100
55
77
98
60
80
100
25
TCR300BW
AYRHTRGW36A3
AYRHTRGW54A
AYRHTRHW72A
36.0
54.0
72.0
2
2
2
55
77
98
60
80
100
NOTES:
1. Heater kw ratings are at 600V for 575V unit
2. HACR type circuit breaker per NEC.
3. The heater model number for horizontal is AYHHTRCW36A.
4. The heater model number for horizontal is AYHHTRCW18A, AYHHTRCW36A.
62
RT-PRC002-EN
Electrical
Data
Table ED-5 Unit Wiring With Electric Heat (Single Point Connection) High Efficiency
Standard Indoor Motor
Tons
To Use
With
Heater
Model No.
Heater
KW Rating1
Control
Stages
MCA
TCD037C3
BAYHTRP306A
BAYHTRP312A
BAYHTRP318A
4.5/6.0
9.0/12.0
13.0/17.4
1
2
2
19.6/21.3
34.5/39.3
48.5/55.6
30/30
35/40
50/60
20.8/22.8
36.0/40.8
50.1/57.1
30/30
40/45
60/60
TCR049C3
BAYHTRP306A
BAYHTRP312A
BAYHTRP318A
BAYHTRP323A
4.5/6.0
9.0/12.0
13.0/17.4
17.2/23.0
1
2
2
2
24.7/24.7
36.5/41.3
50.6/57.6
65.2/74.4
35/35
40/45
60/60
70/80
27.1/27.1
39.5/44.3
53.6/60.6
68.2/77.4
40/40
40/45
60/70
70/80
TCR061C3
AYRHTRA309B
AYRHTRA318B
6.7/9.0
12.9/17.3
1
1
30.6/33.7
51.7/58.6
45/45
60/60
31.9/35.3
53.3/60.3
50/50
60/70
TCR074C3
AYRHTRA309B
AYRHTRA318B
AYRHTRA327B
AYRHTRA336B
6.7/9.0
12.9/17.3
20.2/27.0
27.0/36.0
1
1
2
2
35.2/35.2
52.5/59.4
77.7/88.6
101.2/115.6
50/50
60/60
80/90
110/125
38.1/38.1
56.1/63.0
81.4/92.2
104.8/119.3
50/50
60/70
90/100
110/125
TCR086C3
AYRHTRA309B
AYRHTRA318B
AYRHTRA327B
AYRHTRA336B
6.7/9.0
12.9/17.3
20.2/27.0
27.0/36.0
1
1
2
2
38.1/38.1
52.5/59.4
77.7/88.6
101.2/115.6
60/60
60/60
80/90
110/125
41.0/41.0
56.1/63.0
81.4/92.2
104.8/119.3
60/60
60/70
90/100
110/125
TCR091D3
AYRHTRA309B
AYRHTRA318B
AYRHTRA327B
AYRHTRA336B
6.7/9.0
12.9/17.3
20.2/27.0
27.0/36.0
1
1
2
2
41.7/41.7
52.5/59.4
77.7/88.6
101.2/115.6
50/50
60/60
80/90
110/125
44.6/44.6
56.1/63.0
81.4/92.2
104.8/119.3
50/50
60/70
90/100
110/125
TCR103C3
AYRHTRD318A
AYRHTRD336A
AYRHTRD354A
13.5/18.0
27.0/36.0
40.5/54.0
1
2
2
57/64
104/118
151/172
60/70
110/125
175/175
61/68
108/122
154/176
70/70
110/125
175/200
10
TCR121C3
AYRHTRD318A
AYRHTRD336A
AYRHTRD354A
13.5/18.0
27.0/36.0
40.5/54.0
1
2
2
57/64
104/118
151/172
60/70
110/125
175/175
61/68
108/122
154/176
70/70
110/125
175/200
12
TCR151C3
AYRHTRF318A
AYRHTRF336A
AYRHTRF354A
13.5/18.0
27.0/36.0
40.5/54.0
1
2
2
72/72
108/122
154/176
80/80
110/125
175/200
78/78
115/130
162/184
90/90
125/150
175/200
15
TCR181C3
AYRHTRF318A
AYRHTRF336A
AYRHTRF354A
13.5/18.0
27.0/36.0
40.5/54.0
1
2
2
81/81
108/122
154/176
100/100
110/125
175/200
87/87
115/130
162/184
100/100
125/150
175/200
17
TCR211C3
AYRHTRH336A
AYRHTRH354A
AYRHTRH372A
27.0/36.0
40.5/54.0
54.0/72.0
2
2
2
115/130
162/184
209/238
125/150
175/200
225/250
125/139
171/193
218/247
125/150
175/200
225/250
20
TCR241C3
25
TCR301C3
AYRHTRH336A
AYRHTRH354A
AYRHTRH372A
AYRHTRH336A
AYRHTRH354A
AYRHTRH372A
27.0/36.0
40.5/54.0
54.0/72.0
27.0/36.0
40.5/54.0
54.0/72.0
2
2
2
2
2
2
123/130
162/184
209/238
132/139
171/193
218/247
150/150
175/200
225/250
150/150
175/200
225/250
130/139
171/193
218/247
150/150
175/200
225/250
NOTES:
1. Heater kw ratings are at 208/240 for 208/230V unit
2. HACR type circuit breaker per NEC.
63
Electrical
Data
Table ED-5 Unit Wiring With Electric Heat (Single Point Connection) High Efficiency Continued
Standard Indoor Motor
Tons
To Use
With
Heater
Model No.
Heater
KW Rating1
Control
Stages
MCA
MCA
TCD037C4
BAYHTRP406A
BAYHTRP412A
BAYHTRP418A
6.0
12.0
17.4
1
2
2
11.0
20.0
28.2
15
25
30
11.4
20.4
28.5
15
25
30
TCR049C4
BAYHTRP406A
BAYHTRP412A
BAYHTRP418A
BAYHTRP423A
6.0
12.0
17.5
23.0
1
2
2
2
11.8
20.5
28.7
37.1
15
25
30
40
12.9
21.9
30.0
38.5
20
25
35
40
TCR061C4
AYRHTRA409B
AYRHTRA418B
9.0
18.0
1
1
16.7
30.2
25
35
17.4
30.9
25
35
TCR074C4
AYRHTRA409B
AYRHTRA418B
AYRHTRA427B
AYRHTRA436B
9.0
18.0
27.0
36.0
1
1
2
2
17.5
31.1
44.6
58.1
25
35
45
60
19.0
32.6
46.1
59.6
25
35
50
60
TCR086C4
AYRHTRA409B
AYRHTRA418B
AYRHTRA427B
AYRHTRA436B
9.0
18.0
27.0
36.0
1
1
2
2
18.1
31.1
44.6
58.1
25
35
45
60
19.3
32.6
46.1
59.6
25
35
50
60
TCR091D4
AYRHTRA409B
AYRHTRA418B
AYRHTRA427B
AYRHTRA436B
9.0
18.0
27.0
36.0
1
1
2
2
21.6
31.1
44.6
58.1
25
35
45
60
22.8
32.6
46.1
59.6
25
35
50
60
TCR103C4
AYRHTRC418A
AYRHTRD436A4
AYRHTRD454A4
18.0
36.0
54.0
1
2
2
32
59
86
35
60
90
34
61
88
35
70
90
10
TCR121C4
AYRHTRC418A
AYRHTRD436A4
AYRHTRD454A4
18.0
36.0
54.0
1
2
2
32
59
86
35
60
90
34
61
88
40
70
90
12
TCR151C4
AYRHTRF418A3
AYRHTRF436A
AYRHTRF454A
18.0
36.0
54.0
1
2
2
34
61
88
40
70
90
37
64
91
45
70
100
15
TCR181C4
AYRHTRE418A3
AYRHTRE436A
AYRHTRE454A
18.0
36.0
54.0
1
2
2
38
61
88
50
70
90
40
64
91
50
70
100
17
TCR211C4
AYRHTRG436A
AYRHTRG454A
AYRHTRH472A
36.0
54.0
72.0
2
2
2
64
91
118
70
100
125
68
95
122
70
100
125
20
TCR241C4
TCR301C4
36.0
54.0
72.0
36.0
54.0
72.0
2
2
2
2
2
2
64
91
118
68
95
122
70
100
125
70
100
125
68
95
122
70
100
125
25
AYRHTRG436A
AYRHTRG454A
AYRHTRH472A
AYRHTRG436A
AYRHTRG454A
AYRHTRH472A
NOTES:
1. HACR type circuit breaker per NEC.
2. Values do not include power exhaust accessory.
3. Horizontal model heater number is AYHHTRC418A.
4. Horizontal model heater numbers are AYHHTRE436A and AYHHTRE454A.
64
RT-PRC002-EN
Electrical
Data
Table ED-5 Unit Wiring With Electric Heat (Single Point Connection) High Efficiency Continued
Standard Indoor Motor
Tons
To Use
With
Heater
Model No.
Heater
KW Rating1
Control
Stages
MCA
MCA
TCR103CW
TCR103CW
TCD103CW
TCH103CW
AYRHTRCW18A
AYRHTRDW36A
AYDHTRCW54A
AYHHTREW54A
18.0
36.0
54.0
54.0
1
2
2
2
32
48
69
69
35
50
70
70
34
49
70
70
35
50
70
70
10
TCR121CW
TCR121CW
TCD121CW
TCH121CW
AYRHTRCW18A
AYRHTRCW36A
AYDHTRCW54A
AYHHTREW54A
18.0
36.0
54.0
54.0
1
2
2
2
26
48
69
69
30
50
70
70
27
49
70
70
30
50
70
70
12
TCD151CW
TCH151CW
TCD151CW
TCH151CW
TCR151CW
AYDHTRDW18A
AYHHTRCW18A
AYDHTRGW36A
AYHHTRCW36A
AYRHTREW54A
18.0
18.0
36.0
36.0
54.0
1
1
2
2
2
27
27
49
49
70
30
30
50
50
70
30
30
51
51
73
35
35
60
60
80
15
TCD181CW
TCH181CW
TCD181CW
TCH181CW
TCR181CW
AYDHTRDW18A
AYHHTRCW18A
AYDHTRGW36A
AYHHTRCW36A
AYRHTREW54A
18.0
18.0
36.0
36.0
54.0
1
1
2
2
2
30
30
49
49
70
40
40
50
50
70
33
33
51
51
73
45
45
60
60
80
TCD211CW
TCH211CW
TCR211CW
TCR211CW
AYDHTRGW36A
AYHHTRCW36A
AYRHTRGW54A
AYRHTRHW72A
36.0
36.0
54.0
72.0
2
2
2
2
51
51
73
95
60
60
80
100
55
55
77
98
60
60
80
100
TCD241CW
TCH241CW
TCR241CW
TCR241CW
AYDHTRGW36A
AYHHTRCW36A
AYRHTRGW54A
AYRHTRHW72A
36.0
36.0
54.0
72.0
2
2
2
2
51
51
73
95
60
60
80
100
55
55
77
98
60
60
80
100
TCD301CW
TCH301CW
TCR301CW
TCR301CW
AYDHTRGW36A
AYHHTRCW36A
AYRHTRGW54A
AYRHTRHW72A
36.0
36.0
54.0
72.0
2
2
2
2
55
55
77
98
60
60
80
100
17
20
25
NOTE:
1. HACR type circuit breaker per NEC.
2. Values do not include power exhaust accessory.
65
Electrical
Data
Tons
Unit
Model No.
Amps
No.
Volts
Phase
HP
FLA
LRA
No.
Volts
Phase
HP
FLA
LRA
TCD036C1
TCD036C3, TCD037C3
TCD036C4, TCD037C4
1
1
1
208-230
208-230
460
1
1
1
.33
.33
.33
2.4
2.4
1.1/1.6
7.2
7.2
2.2
1
1
1
208-230
208-230
460
1
1
1
.40
.40
.40
3.8
3.8
1.9
6.9
6.9
3.1
TCR048C1
TCR048C3, TCR049C3
TCR048C4, TCR049C4
TCR048CW
1
1
1
1
208-230
208-230
460
575
1
1
1
1
.50
.50
.50
.50
4.2
4.2
2.0
1.9
9.2
9.2
4.3
3.4
1
1
1
1
208-230
208-230
460
575
1
1
1
1
.75
.75
.75
.75
6.6
6.6
3.1
2.4
13.5
13.5
6.4
5.2
TCR060C1
TCR060C3, TCR061C3
TCR060C4, TCR061C4
TCR060CW
1
1
1
1
208-230
208-230
460
575
1
1
1
1
.60
.60
.60
.60
5.3
5.3
2.5
2.4
11.1
11.1
5.6
4.7
1
1
1
1
208-230
208-230
460
575
1
1
1
1
.75
.75
.75
.75
6.6
6.6
3.1
2.5
13.5
13.5
6.4
5.2
TCR075C3, TCR074C3
6, 6 TCR075C4, TCR074C4
TCR075CW
1
1
1
208-230
460
575
3
3
3
1.00
1.00
1.00
5.9
3.2
2.6
32.2
16.1
13.2
1
1
1
208-230
460
575
3
3
3
2.00
2.00
2.00
8.8
4.4
3.1
53.0
26.5
18.4
208-230
1.00
5.9
32.2
208-230
2.00
8.8
53.0
1
1
460
575
3
3
1.00
1.00
3.2
2.6
16.1
13.2
1
1
460
575
3
3
2.00
2.00
4.4
3.1
26.5
18.4
TCR102C3, TCR103C3
TCR102C4, TCR103C4
TCR102CW, TCR103CW
1
1
1
208-230
460
575
3
3
3
2.00
2.00
2.00
7.5
3.4
3.0
47.2
23.6
22.8
1
1
1
208-230
460
575
3
3
3
3.00
3.00
3.00
10.6
4.8
3.9
81.0
40.5
31.0
TCR120C3
TCR120C4
TCR120CW
TCR121C3
TCR121C4
TCR121CW
1
1
1
1
1
1
208-230
460
575
208-230
460
575
3
3
3
3
3
3
3.00
3.00
3.00
2.00
2.00
2.00
9.4
4.8
3.9
7.5
3.4
3.0
81.0
40.5
31.0
47.2
23.6
22.8
1
1
1
1
1
1
208-230
460
575
208-230
460
575
3
3
3
3
3
3
5.00
5.00
5.00
3.00
3.00
3.00
13.4
7.6
6.1
10.6
4.8
3.9
109.8
54.9
41.6
81.0
40.5
31.0
12
TCR150C3, TCR151C3
TCR150C4, TCR151C4
TCR150CW, TCR151CW
1
1
1
208-230
460
575
3
3
3
3.00
3.00
3.00
10.6
4.8
3.9
81.0
40.5
31.0
1
1
1
208-230
460
575
3
3
3
5.00
5.00
5.00
16.7
7.6
6.1
109.8
54.9
41.6
15
TCR180B3, TCR181C3
TCR180B4, TCR181C4
TCR180BW, TCR181CW
1
1
1
208-230
460
575
3
3
3
3.00
3.00
3.00
10.6
4.8
3.9
81.0
40.5
31.0
1
1
1
208-230
460
575
3
3
3
5.00
5.00
5.00
16.7
7.6
6.1
109.8
54.9
41.6
17
TCR210C3, TCR211C3
TCR210C4, TCR211C4
TCR210CW, TCR211CW
1
1
1
208-230
460
575
3
3
3
5.00
5.00
5.00
16.7
7.6
6.1
109.8
54.9
41.6
1
1
1
208-230
460
575
3
3
3
7.50
7.50
7.50
17.6
8.6
7.0
120.4
74.0
60.0
20
TCR240B3, TCR241C3
TCR240B4, TCR241C4
TCR240BW, TCR241CW
1
1
1
208-230
460
575
3
3
3
5.00
5.00
5.00
16.7
7.6
6.1
109.8
54.9
41.6
1
1
1
208-230
460
575
3
3
3
7.50
7.50
7.50
17.6
8.6
7.0
120.4
74.0
60.0
25
TCR300B3, TCR301C3
TCR300B4, TCR301C4
TCR 300BW, TCR301CW
1
1
1
208-230
460
575
3
3
3
7.50
7.50
7.50
17.6
8.6
7.0
120.4
74.0
60.0
TCR090C3,D3,
TCR086C3,091D3
7, 7 TCR090C4,D4,
TCR086C4,091D4
TCR090CW,DW
8
10
66
RT-PRC002-EN
Electrical
Data
Standard
Efficiency
Table ED-7 Electrical Characteristics Compressor Motor And Condenser Motor 60 Cycle Standard Efficiency
Compressor Motors
Unit
Model No.
No.
Volts
TCD036C1
TCD036C3
TCD036C4
1
1
1
208-230
208-230
460
TCR048C1
TCR048C3
TCR048C4
TCR048CW
1
1
1
1
TCR060C1
TCR060C3
TCR060C4
TCR060CW
Amps
Phase
HP
RPM
RLA
LRA
No.
Phase
HP
FLA
LRA
1
3
3
3.00
3.00
3.00
3450
3450
3450
18.0
11.2
5.5
92
101
51
1
1
1
1
1
1
.25
.25
.25
2.0
2.0
.9
5.3
5.3
2.1
208-230
208-230
460
575
1
3
3
3
4.00
4.00
4.00
4.00
3450
3450
3450
3450
24.0
14.8
7.1
5.5
119
101
51
41
1
1
1
1
1
1
1
1
.33
.33
.33
.33
2.1
2.1
1.0
.9
4.8
4.8
2.6
2.1
1
1
1
1
208-230
208-230
460
575
1
3
3
3
5.00
5.00
5.00
5.00
3450
3450
3450
3450
28.8
18.6
10.0
6.7
142
118
71
43
1
1
1
1
1
1
1
1
.50
.40
.40
.40
5.2
2.7
1.3
1.1
6.5
7.8
3.2
2.4
TCR075C3
TCR075C4
TCR075CW
1
1
1
208-230
460
575
3
3
3
6.25
6.25
6.25
3450
3450
3450
21.8
9.7
7.8
124
64
51
1
1
1
1
1
1
.50
.50
.50
3.4
2.4
1.8
10.8
5.4
4.1
TCR090C3
TCR090C4
TCR090CW
1
1
1
208-230
460
575
3
3
3
7.50
7.50
7.50
3450
3450
3450
27.0
12.2
9.8
164
79
63
1
1
1
1
1
1
.50
.50
.50
3.4
2.4
1.8
10.8
5.4
4.1
TCR090D3
TCR090D4
TCR090DW
TCR102C3
TCR102C4
TCR102CW
2
2
2
2
2
2
208-230
460
575
208-230
460
575
3
3
3
3
3
3
4.00/3.50
4.00/3.50
4.00/3.50
4.30/4.30
4.30/4.30
4.30/4.30
3450
3450
3450
3450
3450
3450
14.4
7.1
5.4
16.0
10.0
5.9
101
51
41
118
71
43
1
1
1
1
1
1
1
1
1
1
1
1
.50
.50
.50
1.00
1.00
1.00
3.4
2.4
1.8
5.5
2.9
2.0
10.8
5.4
4.1
18.3
9.3
5.7
TCR120C3
TCR120C4
TCR120CW
2
2
2
208-230
460
575
3
3
3
118
71
43
1
1
1
1
1
1
1.00
1.00
1.00
5.5
2.9
2.0
18.3
9.3
5.7
TCR150C3
TCR150C4
TCR150CW
2
2
2
208-230
460
575
3
3
3
156
70
54
1
1
1
1
1
1
1.00
1.00
1.00
5.5
2.9
2.0
18.3
9.3
5.7
15
TCR180B3
TCR180B4
TCR180BW
2
2
2
208-230
460
575
3
3
3
253/128
118/63
97/49
2
2
2
1
1
1
.50
.50
.50
3.2
1.6
1.3
8.8
3.8
3.2
17
TCR210C3
TCR210C4
TCR210CW
2
2
2
208-230
460
575
3
3
3
253/164
118/100
97/72
2
2
2
1
1
1
1.00
1.00
1.00
5.5
2.9
2.0
18.3
9.3
5.7
20
TCR240B3
TCR240B4
TCR240BW
2
2
2
208-230
460
575
3
3
3
9.30
9.30
9.30
3450
3450
3450
42.1
17.4
13.9
247
95
76
2
2
2
1
1
1
1.00
1.00
1.00
5.5
2.9
2.0
18.3
9.3
5.7
25
TCR300B3
TCR300B4
TCR300BW
2
2
2
208-230
460
575
3
3
3
10.00
10.00
10.00
3450
3450
3450
42.8
17.7
14.2
247
95
76
2
2
2
1
1
1
1.00
1.00
1.00
5.5
2.9
2.0
18.3
9.3
5.7
Tons
3
10
12
6.00
6.00
6.00
3450
3450
3450
24.3
10.6
8.4
NOTES:
1. Amp draw for each motor; multiply value by numbers of motors to determine total amps.
2. HP for each compressor.
67
Electrical
Data
High
Efficiency
Table ED-8 Electrical Characteristics Compressor Motor And Condenser Motor 60 Cycle High Efficiency
Compressor Motors
Unit
Model No.
No.
Volts
TCD037C3
TCD037C4
1
1
208-230
460
TCR049C3
TCR049C4
TCR061C3
TCR061C4
1
1
1
1
TCR074C3
TCR074C4
TCR086C3
TCR086C4
TCR091D3
TCR091D4
TCR103C3
TCR103C4
TCR103CW
Amps
Phase
HP
RPM
RLA
LRA
No.
Phase
FLA
LRA
3
3
3.00
3.00
3450
3450
12.0
5.9
101
51
1
1
1
1
.25
.25
2.0
.9
5.3
2.1
208-230
460
208-230
460
3
3
3
3
3.50
3.50
4.30
4.30
3450
3450
3450
3450
14.8
7.1
18.6
10.0
101
51
118
71
1
1
1
1
1
1
1
1
.25
.25
.25
.25
2.0
.9
2.0
.9
5.3
2.1
5.3
2.1
1
1
1
1
2
2
2
2
2
208-230
460
208-230
460
208-230
460
208-230
460
575
3
3
3
3
3
3
3
3
3
5.00
5.00
6.25
6.25
3.00
3.00
3.80
3.80
3.80
3450
3450
3450
3450
3450
3450
3450
3450
3450
21.0
10.0
23.0
10.0
14.4
7.1
14.0
7.5
5.9
118
71
124
64
101
51
91
46
37
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
.25
.25
.50
.50
.50
.50
1.00
1.00
1.00
2.0
.9
3.4
2.4
3.4
2.4
5.5
2.9
2.0
5.3
2.1
10.8
5.4
10.8
5.4
18.3
9.3
5.7
TCR121C3
TCR121C4
TCR121CW
2
2
2
208-230
460
575
3
3
3
4.30
4.30
4.30
3450
3450
3450
15.4
10.0
6.9
118
71
43
2
2
2
1
1
1
.50
.50
.50
3.2
1.6
1.3
8.8
3.8
3.2
TCR151C3
TCR151C4
TCR151CW
TCR181C3
TCR181C4
TCR181CW
2
2
2
2
2
2
208-230
460
575
208-230
460
575
3
3
3
3
3
3
5.70
5.70
5.70
9.30/4.50
9.30/4.50
9.30/4.50
3450
19.4
156
3450
10.0
70
3450
7.8
54
3450 37.0/16.9 253/124
3450 17.4/7.4 118/60
3450 13.9/6.1 97/49
2
2
2
2
2
2
1
1
1
1
1
1
.50
.50
.50
.50
.50
.50
3.2
1.6
1.3
3.2
1.6
1.3
8.8
3.8
3.2
8.8
3.8
3.2
17
TCR211C3
TCR211C4
TCR211CW
2
2
2
208-230
460
575
3
3
3
9.30/5.70
9.30/5.70
9.30/5.70
2
2
2
1
1
1
1.00
1.00
1.00
5.5
2.9
2.0
18.3
9.3
5.7
20
TCR241C3
TCR241C4
TCR241CW
2
2
2
208-230
460
575
3
3
3
9.30
9.30
9.30
3450
3450
3450
42.1
17.4
13.9
253
118
97
2
2
2
1
1
1
1.00
1.00
1.00
5.5
2.9
2.0
18.3
9.3
5.7
25
TCR301C3
TCR301C4
TCR301CW
2
2
2
208-230
460
575
3
3
3
10.00
10.00
10.00
3450
3450
3450
42.1
17.4
13.9
253
118
97
2
2
2
1
1
1
1.00
1.00
1.00
5.5
2.9
2.0
18.3
9.3
5.7
Tons
3
4
5
6
7
7
8
10
12
15
HP
NOTES:
1. Amp draw for each motor; multiply value by numbers of motors to determine total amps.
2. HP for each compressor.
68
RT-PRC002-EN
Jobsite
Connections
DISCONNECT
SWITCH
(BY OTHERS)
ZONE SENSORS
ROOFTOP
UNIT
RT-PRC002-EN
69
Typical
Wiring
70
(3-7Ton)
RT-PRC002-EN
Typical
Wiring
(3-7Ton)
RT-PRC002-EN
71
Typical
Wiring
72
(3-7Ton)
RT-PRC002-EN
Typical
Wiring
(3-7Ton)
RT-PRC002-EN
73
Typical
Wiring
74
(8-25 Ton)
RT-PRC002-EN
Typical
Wiring
(8-25 Ton)
RT-PRC002-EN
75
Typical
Wiring
76
(8-25 Ton)
RT-PRC002-EN
Typical
Wiring
(8-25 Ton)
RT-PRC002-EN
77
Dimensional
Data
78
RT-PRC002-EN
Dimensional
Data
RT-PRC002-EN
79
&
80
RT-PRC002-EN
81
82
RT-PRC002-EN
RT-PRC002-EN
83
Dimensional
Data
NOTE:
Duct flanges mount 7-7/16" down
inside the curb on the 1" curb
flanges. See recommended duct
dimensions on the next page.
84
RT-PRC002-EN
Dimensional
Data
1"
16 3/16"
51 7/8"
22 5/16"
44 1/2"
1 1\2"
PERIMETER
CURB FLANGE
14 1/16"
7 7/16"
1"
UR
T
RE
LY
P
UP
S
NOTE:
Duct flanges mount 7-7/16" down
inside the curb on the 1" curb
flanges.
RT-PRC002-EN
85
NOTE:
Duct flanges mount 7-7/16" down
inside the curb on the 1" curb
flanges. See recommended duct
dimensions on the next page.
86
RT-PRC002-EN
17 7/8"
59 7/16"
26 5/16"
52 1/2"
1 1\2"
PERIMETER
CURB FLANGE
14 1/16"
7 7/16"
1"
UR
T
RE
LY
PP
SU
NOTE:
Duct flanges mount 7-7/16" down
inside the curb on the 1" curb
flanges.
RT-PRC002-EN
87
NOTE:
Duct flanges mount 7-7/16" down
inside the curb on the 1" curb
flanges. See recommended duct
dimensions on the next page.
88
RT-PRC002-EN
Dimensional
Data
All dimensions are in inches.
1"
19 5/16"
73 7/16"
66 1/2"
1"
1 1\2"
PERIMETER
CURB FLANGE
14 1/16"
7 7/16"
26 5/16"
RN
TU
E
R
LY
PP
U
S
NOTE:
Duct flanges mount 7-7/16" down
inside the curb on the 1" curb
flanges.
RT-PRC002-EN
89
Dimensional
Data
(3-7Ton)
Accessories
Note:
When applying economizer to horizontal units,
connecting ductwork must be run full size to allow
proper operation of Economizer Damper.
90
RT-PRC002-EN
Dimensional
Data
(8-25 Ton)
Accessories
Note:
When applying economizer to horizontal units,
connecting ductwork must be run full size to
allow proper operation of Economizer Damper.
Table DD-1
Unit
Model #
TCR102-120, 150
14 /4
TCR121, 151-180, 210 171/2
TCR181, 211-301
191/2
1
B1
C2
33
53
64
33
36
39
NOTES:
1. Horizontal dimension only. Downflow economizer is
width of end panel.
2. Power exhaust is applied on downflow economizer
only.
RT-PRC002-EN
91
Dimensional
Data
Factory Installed
Options (FIOPS)
Table DD-2
Unit
Model #
TCD036-060
TCD061-090
TCD090-091
TCD102, 120
311/4
511/8
25
331/4
531/8
25
32
531/8
287/8
Table DD-3
Unit
Model #
3/
8
TCD103, 150
33
TCD121, 151, 180, 210 423/8
TCD181, 211-301
291/2
92
39 /8
483/8
56
31
31
381/2
RT-PRC002-EN
Dimensional
Data
Factory Installed
Options (FIOPS)
Disconnect Switch
or Circuit Breaker
RT-PRC002-EN
93
(3-25Ton)
Dimensional
Data
Tons
Downflow Only
A
3, 4, 5
6, 7
8, 10
12
15, 17
20, 25
Condensate
Drain Size
3/
13
153/16
153/16
227/16
267/16
267/16
16
3/
22
22
22
14
22
28
16
1/
2
1/
2
1/
2
1/
2
3/
4
C
1/
11
12
12
17
18
19
4
15/
16
15/
16
11/
16
11/
16
15/
16
7/
3/
2
31/4
43/16
41/4
41/4
41/4
8
3
33/8
33/8
41/4
41/4
41/4
8
7/
39
427/8
427/8
5413/16
627/16
765/16
8
1/
32
351/4
351/4
473/16
5411/16
6811/16
4
3/
PVC
PVC
4 PVC
1 NPT
1 NPT
1 NPT
3/
4
4
3/
Horizontal
19
22
23
5/
24
25
26
5/
3/
8
8
4
20
2 3/16
3/
28 16
16
6
5 3/8
Tons
3, 4
5,6,7,7
8
10, 12
15-25
94
Condensate
Drain Size
Downflow Only
133/16
153/16
227/16
267/16
267/16
223/16
221/2
141/2
221/2
283/4
111/4
1215/16
1711/16
1811/16
1915/16
27/8
31/4
41/4
41/4
41/4
33/8
33/8
41/4
41/4
41/4
397/8
427/8
5413/16
627/16
765/16
321/4
351/4
473/16
5411/16
6811/16
Downflow
E
3/
PVC
3/
4 PVC
1 NPT
1 NPT
1 NPT
4
19
22
Horizontal
24
25
26
5/
5/
3/
8
8
4
20 3/8
2 3/16
16
6
5 3/8
RT-PRC002-EN
(3-25Ton)
Weights
Power
Exhaust4
High6
Static
Drive
Oversized
Motor
Adder
Roof
Curb4
Low6
Static
Drive
Model No.
Net
Manual
TCR036,048,060C
TCR037,049
40
32
TCR075,090C,090D
TCR061,074,086C,091D,
TCR102C, 120C
40
32
35
65
82
TCD103C
TCD150C
40
32
35
75
165
TCD180B
TCD121,151C, TCD210C
65
32
60
95
205
TCD240B
TCD181,211,241C
80
32
75
95
235
TCD300B.301C
80
32
75
95
TCH103, 150C
35
32
35
TCH180B, 210C
TCH121,151C
50
32
60
TCH240B
TCH181,211,241C
65
32
75
TCH300B,301C
65
32
75
N/A
N/A
80
235
N/A
N/A
All Zone
Sensors
6-23 KW
240/480V2
27-36 KW
240/480V2 3
54 KW
240/480V2
72 KW
240/480V2
20/20
26/26
26/265
TCD103, 150C
28/21
31/27
38/32
TCD180B, 210C
TCD121,151,181C
28/217
31/27
38/32
TCD240B
TCD211,241C
TCD300B,301C
28/21
31/27
38/32
TCH180B, 210C
TCH121,151,181C
28/217
31/27
38/32
TCH240B
TCH211, 241C
33/27
40/32
43/34
TCH300B, 301C
33/27
40/32
43/34
33/27
40/32
43/34
33/27
40/32
43/34
NOTES:
1. Net weight should be added to unit weight when ordering factory installed accessories.
2. For 600V heaters net weights are same as 480V heaters.
3. To estimate shipping weight add 5 lbs to net weight.
4. Downflow only.
5. 27 - 36 KW Heaters not available for TCR061C.
6. Not available on all models (See Fan Performance tables for specific models).
7. 9 - 23 KW Heaters not available for TCR210C.
8. TC102-300 factory installed options for economizers, multiply net capacity x .99, EER x .97. For oversized motors, multiply net capacity x .98, EER x .93.
This is provided in compliance with ARI certification program.
95
Weights
Table W-3 Maximum Unit And Corner Weights (Lbs) And Center Of Gravity Dimensions (In.)
Corner Weights (Lbs)1
Tons
Unit
Model No.
Net
Length
Width
3
4
5
6, 6
TCD036C/TCD037C
TCR048C/TCR049C
TCR060C/TCR061C
TCR075C/TCR074C
702/731
731/765
751/821
819/852
541/571
559/592
579/633
630/663
184/192
190/196
194/284
196/207
137/139
138/147
143/156
162/173
99/107
106/114
109/121
123/130
120/133
123/135
134/152
150/153
36/36
36/37
36/38
39/40
19/20
19/20
20/21
21/21
TCR090C/TCR086C
Single Compressor
878/861
689/673
229/213
177/173
130/130
153/156
39/39
20/21
TCR090D/TCR091D
Dual Compressor
940/953
751/765
264/265
182/188
130/135
175/176
36/37
20/20
TCR102C/TCR103C
TCR120C/TCR121C
TCR150C/TCR151C
TCR180B/TCR181C
TCR210C/TCR211C
TCR240B/TCR241C
TCR300B/ TCR301C
1064/1393
1086/1753
1460/1776
1739/2309
1820/2380
2309/2470
2365/2475
857/1094
879/1385
1161/1408
1371/1850
1452/1921
1850/2011
1906/2016
298/353
302/468
389/474
482/635
500/643
654/692
661/695
217/291
225/357
307/349
350/464
378/495
487/523
507/524
144/203
150/242
205/248
227/317
247/341
303/343
320/343
197/246
202/317
260/337
312/434
327/442
406/453
454/454
37/43
38/46
42/45
45/52
46/53
52/53
53/53
20/26
20/29
26/30
28/35
28/35
33/34
33/34
7, 7
8
10
12
15
17
20
25
Shipping
NOTES:
1. Corner weights are given for information only. 8-25 ton models must be supported continuously by a curb or equivalent frame support.
2. Weights are approximate. Horizontal and downflow unit and corner weights may vary slightly.
96
RT-PRC002-EN
Weights
Model
Number
FIYHEMT001,002
FIYHEMT003-005
FIYHEMT006-008
FIYHNGE001,002
FIYHNGE003-009
FIYCOPO101-206
FIYTBUE101-111
FIYTBUE201-216
FIYUCB4015-4150
FIYUCB3175-3250
FIYUDC4150,6100
FIYUDC3250
Weight
15
49
36
10
27
38
16
23
5
10
5
10
NOTES:
1. Weights for FIOP accessories not listed are >5 lbs.
2. Net weight should be added to unit weight when ordering factory installed accessories.
3. See Table W-1 for standard factory installed economizer, electric heater and oversized motor.
RT-PRC002-EN
97
Mechanical
Specifications
General
The units shall be dedicated downflow
or horizontal airflow.The operating
range shall be between 115 F and 0 F in
cooling as standard from the factory for
all units. Cooling performance shall be
rated in accordance with ARI testing
procedures. All units shall be factory
assembled, internally wired, fully
charged with R-22 and 100% run tested
to check cooling operation, fan and
blower rotation and control sequence
before leaving the factory. Wiring
internal to the unit shall be colored and
numbered for simplified identification.
Units shall be UL listed and labeled,
classified in accordance to UL 1995/
CAN/CSA No. 236-M90 for Central
Cooling Air Conditioners. Canadian
units shall be CSA Certified.
Casing
Unit casing shall be constructed of zinc
coated, heavy gauge, galvanized steel.
All components shall be mounted in a
weather resistant steel cabinet with a
painted exterior. Cabinet construction
shall allow for all maintenance on one
side of the unit. Service panels shall
have lifting handles and shall be
removed and reinstalled by removing
not more than three screws while
providing a water and air tight seal. All
exposed vertical panels and top covers
in the indoor air section shall be
insulated with fire-resistant,
permanent, ordorless glass fiber
material. The base of the downflow
unit is insulated with a foil-faced,
closed-cell material. The downflow
units base pan shall have no
penetrations within the perimeter of
the curb other than the raised 11/8" high
supply/return openings to provide an
added water integrity precaution
should the condensate drain back up.
Each unit has a sloped condensate
drain pan. The base of the unit shall
have provisions for forklift and crane
lifting.
98
Filters
One inch, throwaway filters shall be
standard on all 3-7 ton units. Filter rack
can be converted to two inch capability.
Two inch filters shall be factory supplied
on all units above 7 tons.
Compressors
All 3-10 ton standard, 3-7 and 10 ton
high efficiency units shall have directdrive hermetic, reciprocating type
compressors. The reciprocating type
compressors have a centrifugal oil pump
providing positive lubrication to moving
parts. Motor shall be suction gas-cooled
and shall have a voltage utilization range
of plus or minus 10 percent of unit
nameplate voltage. Crankcase heater,
internal temperature and currentsensitive motor overloads shall be
included for maximum protection. Shall
have internal spring isolation and sound
muffling to minimize vibration
transmission and noise. Low pressure
switches shall be standard.
8 ton high efficiency and 12 to 25 ton
standard and high efficiency units shall
have direct-drive, hermetic, scroll type
compressors with centrifugal type oil
pumps. Motor shall be suction gascooled and shall have a voltage
utilization range of plus or minus 10
percent of unit nameplate voltage.
Internal overloads shall be provided with
the scroll compressors. The scrolls used
on the 12, 15 and 17 ton high
efficiency and 15, 17, and 25 ton
standard efficiency units have crankcase
heaters.
Refrigerant Circuits
Each refrigerant circuit shall have
independent fixed orifice expansion
devices, service pressure ports and
refrigerant line filter driers factoryinstalled as standard. An area shall be
provided for replacement suction line
driers.
RT-PRC002-EN
Mechanical
Specifications
Controls
Unit shall be completely factory wired
with necessary controls and contactor
pressure lugs or terminal block for
power wiring. Units shall provide an
external location for mounting fused
disconnect device. Micro-processor
controls shall be provided for all 24 volt
control functions. The resident control
algorithms shall make all heating,
cooling and/or ventilating decisions in
response to electronic signals from
sensors measuring indoor and outdoor
temperatures.The control algorithm
maintains accurate temperature control,
minimizes drift from set point and
provides better building comfort. A
centralized Micro-processor shall provide
anti-short cycle timing and time delay
between compressors to provide a
higher level of machine protection.
Accessories
Electric Heaters Electric heat
modules shall be available for
installation within basic unit. Electric
heater elements shall be constructed of
heavy-duty nickel chromium elements
internally delta connected for 240 volt,
wye connected for 480 and 600 volt.
Staging shall be achieved through the
unitary control processor (UCP). Each
heater package shall have automatically
reset high limit control operating
through heating element contactors. All
heaters shall be individually fused from
factory, where required, and meet all
NEC and CEC requirements when
properly installed. Power assemblies
shall provide single-point connection.
Electric heat modules shall be UL listed
or CSA certified.
Roof Curb - Downflow The roof
curb shall be designed to mate with the
downflow unit and provide support and
a water tight installation when installed
properly. The roof curb design shall
allow field-fabricated rectangular supply/
return ductwork to be connected directly
to the curb. Curb design shall comply
with NRCA requirements. Curb shall
ship knocked down for field assembly
and include wood nailer strips.
RT-PRC002-EN
Control Options
Trane Communication Interface
(TCI) Shall be provided to interface
with theTrane Integrated ComfortTM
System.
Zone Sensors Shall be provided to
interface with the Micro equipped
Voyagers and shall be available in either
manual, automatic programmable with
night setback, with system malfunction
lights or remote sensor options.
Conventional Thermostat Interface
(CTI) This field installed circuit board
shall provide interface with electromechanical thermostats or automation
systems.
Differential Pressure Switches
This field installed option allows
individual fan failure and dirty filter
indication.The fan failure switch will
disable all unit functions and flash the
Service LED on the zone sensor.The dirty
filter switch will light the Service LED on
the zone sensor and will allow continued
unit operation.
Input/Output Expansion Accessory
This kit allows Integrated Comfort
Systems to read Supply AirTemperature,
Return AirTemperature, Return Air
Humidity, and direct indication of fan
failure without the use of an economizer
or motorized outside air accessory.
Electronic Time Clock This field
installed accessory allows up to 4 units
night set-back and unoccupied functions
when using a standard (Dual Setpoint)
zone sensor module.
99
Mechanical
Specifications
Powered or Unpowered
Convenience Outlet This option is a
GFCI, 120v/15amp, 2 plug, convenience
outlet, either powered or unpowered.
When the convenience outlet is
powered, a service receptacle disconnect
will be available. The convenience outlet
is powered from the line side of the
disconnect or circuit breaker, and
therefore will not be affected by the
position of the disconnect or circuit
breaker. This option can only be ordered
when theThrough the Base Electrical
with either the Disconnect Switch, or
Circuit Breaker, option is ordered.This
option is available on all 3-25 ton
downflow models.
Clogged Filter/Fan Failure Switch
A dedicated differential pressure switch
is available to achieve active fan failure
indication and/or clogged filter
indication. These indications will be
registered with either a zone sensor with
status indication lights or an Integrated
Comfort System.
Reference or Comparative Enthalpy
Reference or Comparative Enthalpy
option shall be available when a factory
installed Downflow Economizer is
ordered.This option is available on all 325 ton downflow models.
Input/Output Expansion Module
This factory installed option will allow an
Integrated Comfort System to read
Supply AirTemperature, Return Air
Temperature, Return Air Humidity, and
direct indication of fan failure without the
use of an economizer or motorized
outside air accessory.
High Pressure Cutout This option is
offered for units that do not have High
Pressure cutout as standard. The units
WITH High Pressure Cutout as standard
are: TC*090C,TC*180-301B,C
Hinged Access Doors Sheet metal
hinges are available factory installed on
the Filter/Evaporator Access Door and
the Compressor/Control Access Door.
This option is available on all 3-25 ton
downflow models.
100
RT-PRC002-EN
RT-PRC002-EN
RT-PRC002-EN
File Number
Supersedes
Stocking Location
Since The Trane Company has a policy of continuous product and product data improvement, it reserves the