Building HVAC Control Systems - Role of Controls and Optimization
Building HVAC Control Systems - Role of Controls and Optimization
WeB12.3
I. I NTRODUCTION
Energy consumed in commercial buildings is a significant
fraction of that consumed in all end-use sectors. Buildings
consume approximately 36% of total US primary energy
use by sector (transportation and industry consuming the
remaining). For commercial buildings, approximately 32% of
energy is consumed by the HVAC system, while an additional
8% is used to heat water (see Chart in Figure 1). Moreover,
the commercial building segment continues to grow.
Space Heating
15%
22%
Cooling
Ventilation
13%
6%
2%
4%
3%
8%
27%
Fig. 1.
Water heating
Lighting
Refrigeration
Cooking
Office Equipment
Other
Heating, Ventilation and Air Conditioning (HAVC) Systems and other building components are typically designed
and specified independently of each other. A path to achieving higher overall energy conversion efficiencies is to enable
and create hybrid building energy systems that integrate
emerging component and control system technologies into
the broader HVAC building system and optimize building
system energy efficiency.
This work was supported by the National Institute of Standards and
Technology Advanced Technology Program under agreement number
70NANB4H3024, and the United Technologies Corporate Research.
1121
Authorized licensed use limited to: Universiti Teknikal Malaysia Melaka-UTEM. Downloaded on June 3, 2009 at 23:38 from IEEE Xplore. Restrictions apply.
1122
Authorized licensed use limited to: Universiti Teknikal Malaysia Melaka-UTEM. Downloaded on June 3, 2009 at 23:38 from IEEE Xplore. Restrictions apply.
Cooling Towers
pensates for any excess flow that does not pass through the
secondary loop. This configuration makes the chilled water
system robust and stable. However, at reduced thermal loads,
the air handlers reduce the required secondary flow resulting
in increased bypass flow, which introduces inefficiency in the
overall system performance. Many manufacturers of chillers
now make chillers with variable flow primary pumps [25],
where the primary flow is reduced at part-load conditions
in order to reduce the bypass flow. This couples the chiller
operation with thermal loads and disturbances and requires
careful control to avoid equipment operating constraints. As
chilled water systems using variable speed drives become
more prevalent [25], [26], controls would play an increasingly critical role in robust performance and optimization.
Tower 1
Condenser
Water Supply
Secondary Pumps
Tower 2
Leaving Chilled
Water Supply
Air Handlers
Zone m
Bypass
Zone 3
Chiller 2
Zone 2
Zone 1
Chiller 1
Chiller n
Building Return
Water
Primary Pumps
Fig. 2.
From
Cooling
Tower (27qC)
To
Cooling
Tower (35qC)
Condenser (gas-to-liq)
Cold refrigerant
(low pres liquid)
Hot refrigerant
(high pres. gas)
Cold refrigerant
(low pres gas)
Compressor
Expansion
Valve
Hot refrigerant
(high pres. liquid)
Evaporator (liq-to-gas)
Chilled Water
Supply (6 qC)
Building water
Return (18qC)
Fig. 3.
Schematic of a chiller
1123
Authorized licensed use limited to: Universiti Teknikal Malaysia Melaka-UTEM. Downloaded on June 3, 2009 at 23:38 from IEEE Xplore. Restrictions apply.
4000
3500
]
W
[
r
e
w
o
Pl
at
o
T
3000
2500
2000
1500
1000
baseline at TCoW SP = 4odegC + Tw etbulb
500
Optimized
10
12
14
16
18
20
22
24
time [hours]
Time
[hours]
Fig. 4.
Total power improvement over baseline operation: Limit of
Performance
11
44
10.5
42
]
C
[
t
ni
o
p
t
e
s
r
et
a
w
r
e
s
n
e
d
n
o
C
]
C[
t
ni
o
pt
e
s
r
et
a
w
d
ell
i
h
c
40
38
36
34
32
30
Wet-bulb
10
9.5
10
15
time [hours]
20
25
3-chillers on
8.5
7.5
6.5
28
10
15
20
time [hours]
1124
Authorized licensed use limited to: Universiti Teknikal Malaysia Melaka-UTEM. Downloaded on June 3, 2009 at 23:38 from IEEE Xplore. Restrictions apply.
5000
4500
4000
3500
3000
100
2500
95
Plant
Input Dynamics
Tower
Return
Temperature
Set Point
Convex
nonlinearity
Fi (s )
316
Output Dynamics
Fo (s )
312
310
90
308
POWER
304
al
r
he
302
s
sh
314
d
oa
[%
e jI
a sin(Zt )
Fig. 6.
Controller
307
306
Ambient Temp
7.5
7
temperature above
wetbulb temperature
6.5
5.5
305
4.5
10
12
14
16
18
20
time [h]
304
Wetbulb Temp
Fig. 10.
303
4500
302
Constant Tower
Setpoint
301
10
12
14
16
18
20
4000
Fig. 7.
time [h]
Tower
Control
T
Chillers
Fan
speed
Tower
power
Cooling
Towers
Condenser
heat
3000
With extremum
seeking control
Total
Power
2500
Chiller
power
Building
Load
3500
10
12
14
16
18
20
time [h]
Fig. 11.
Total Power Consumption: comparison of extremum seeking
control set-point and a strategy that maintains condenser water at a constant
o
4 difference above ambient wet-bulb
Extremum
Seeking
Controller
VI. ACKNOWLEDGMENTS
Fig. 8.
The authors gratefully acknowledge the support of National Institute of Standards and Technologys Advanced
1125
Authorized licensed use limited to: Universiti Teknikal Malaysia Melaka-UTEM. Downloaded on June 3, 2009 at 23:38 from IEEE Xplore. Restrictions apply.
1126
Authorized licensed use limited to: Universiti Teknikal Malaysia Melaka-UTEM. Downloaded on June 3, 2009 at 23:38 from IEEE Xplore. Restrictions apply.