Immunity Tests

TRA- and MIG-System

Surge Testers

CWG 1.2/50 s, 8/20 s

II Ring Wave, 100 kHz III ITU K17 10/700 s IV Accessories

General Information About Disturbance Sources


CWG 1.2/50 s, 8/20 s
The following aspects of surge testing electronic systems are relevant: - Tests for failure modes that involve flashover are influenced by the surge current that would flow after flashover. - The surge let-through of a protective device depends on the applied voltage front. - The response of a crowbar-type device, subjected to an intended current test, is influenced by the voltage front applied by the generator which senses a high-impedance test piece, until operation of the crowbar. Therefore, the generator must be capable of generating a waveform 1,2/50 s or a current waveform of 8/20 s at clamping status of the protection circuit.
U [V] 100% 90% Rise time: Ts=1,2 s 30% Half value time: Tr = 50 s 20% Over swing: <5% 50%
4 s 300 s t s

ITU K44 10/700 s


The 10/700 s wave generator has been defined in CCITT K44 for outdoor telecommunication lines. The same definition of the 10/ 700 s generator has been brought over into the document IEC 61000-4-5.
Um Fronttime: Tf=10 s 30% Half value time: Tr = 700 s 20%

Um 100 % Um 90 %

50% Um

Um 10 % 6,5 s 700 s
Rise time: Ts=4 s 20% Half value time: Tr = 300 s 20%

t s

Im

Im 100 % Im 90 %

50% Im

Im 10 %

1,2 s 50 s

Ring Wave, 100 kHz


Ring waves are used to simulate lightning or switching effects in public single or three phase supplies behind a primary protection. The current and voltage waveforms are defined in IEC 61000-4-12 and ANSI C62.41 as follows:
V Rise time: Ts=0,5 s 30% Decaying: 2. Amplitude to 1. 60 to 90 %

A]

100% 90%

Rise time: Ts=8 s 20% Half value time: Tr = 20 s 20% Under swing: < 30 % 50%

10% 8 s 20 s <30%
100% 90%

Combination waves or Hybrid, are used in a wide range of test application. The most common use is to simulate lightning impulses onto the public single or three phase supply. The current and voltage waveforms are de2 fined in IEC 61000-4-5 and ANSI C62.41

10 s 20%

10%

t
,5 s

MIG0603IN SURGE Waveform - Tester Overview, General Data


Overview of tester types MIG0603IN3: CWG 1.2/50, 8/20 s 6.3 kV, 3.15 kA Ring 100 kHz 6.3 kV Single phase CDN 10/700 s, 6 kV MIG0603-3P: CWG 1.2/50, 8/20 s 6.3 kV, 3.15 kA Automatically or manually operated CDN up to 100 A per phase MIG1206-3P: CWG 1.2/50, 8/20 s 12 kV, 6 kA Automatically or manually operated CDN up to 100 A per phase Control - Trigger: auto or manual - Ramps:Voltage, Polarity, Synchronisation - Protocol: Peak values, Polarity, Number of shots, Synchronisation - Measurement: CWG, v and i Accessories - 1 power cord depending on country - cables or connectors for EUT connections - 1 auxiliary connector (safety circuit) - 1 user manual, with verification protocol and declarations LVD, EMC Test levels CWG 1.2/50, 8/20 s and ring wave as specified in ANSI/IEEE C62.41
Location Category A Outside and Service Entrance Voltages 10 kV or more 6 kV Impulse or Ring 6 kV Ring Currents 10 kA or more 3 kA Impulse 500 A Ring 200 A Ring
Category OCV Open Circuit Voltage SCI Short Circuit Current Wave Form C Combination CWG B Combination CWG Generator Source Impedance

Location Category B Major Feeders and Short Branch Circuits

Location Category C Outlets and Long Branch Circuits

>6 kV >3 kA 6 kV 3kA 6 kV 500 A 6 kV 200 A

2 2 12 30

Ring Wave A Ring Wave

Ring wave 100 kHz as specified in IEC 61000-4-12


Test level 1 2 3 4 x Common mode [kV] 0.5 1.0 2.0 4.0 special Differential mode [kV] 0.25 0.5 1.0 2.0 special

Note: x is an open class. This level can be specified in the product specification.

Test voltages in accordance with IEC 61000-4-5


POWER SUPPLY UNSYM. OPERATED CIRCUITS, LDB SYMM. OPERATED CIRCUITS/LINES DB,SDB (1)

Installation class

Coupling mode
Line to Line kV Line to ground kV

Coupling mode
Line to line kV Line to ground kV

Coupling mode
Line to line kV Line to ground kV

Coupling mode
line to line kV line to ground kV

0 1 2 3 4 5 x N.T. 0.5 1.0 2.0 *) 0.5 1.0 2.0 4.0 *) N.T. 0.5 1.0 2.0 2.0

NO TEST is advised (N.T.)


0.5 1.0 2.0 4.0 4.0 N.T. 0.5 1.0 2.0 4.0 4.0 N.T. N.T. N.T. 0.5

MIG0603IN CWG 1.2/50, 8/20 s


The MIG0603IN is suitable to surge singlephase power supply line 230 V, 16 A up to 6.3 kV and 3.15 kA.

MIG0603IN3 CWG, Ring Wave, 10/700


The MIG0603IN3 is suitable to carry out CWG, Ring and 10/700 s test on different lines. CWG and Ring specification see MIG0603IN and -IN4 as well as 10/700 s below.

MIG0603IN: CWG 1.2/50, 8/20 s

High voltage circuit - Voltage (oc): 1.2/50 s - Current (cs): 8/20 s - Repetition rate maximum: 10/min - Source Impedance: 2 Ohm 10% . - Source energy: 220 Joule at 6 kV - Vpeak range 0.25 up to 6 kV 10% - Ipeak range 0.125 up to 3 kA 10% - Measurement accuracy 3% (v,i) - CDN single-phase 260V 16 A - Coupling path L to N, 18 F - Coupling path L-PE, 9 F and 10 Ohm

MIG0603IN3

High voltage circuit - Voltage (oc): 10/700 s - Current (cs): 4/300 s, 40 Ohm - Repetition rate maximum: 4/min - Impulse capcitance: 20 F . - Source energy: 440 Joule at 6 kV - Vpeak range 0.25 up to 6 kV 10% - Ipeak range 0.125 up to 3 kA 10% - Measurement accuracy 3% - Damping resistor 25 Ohm - Serial resistor 15 Ohm

Basic data Dimensions: 450 x 500 x 190 mm Weight: approx. 28 kg Power supply: 230 V or 115 V, 400 VA 4

Basic data Dimensions: 450 x 500 x 190 mm Weight: approx. 25 kg Power supply: 230 V or 115 V, 400 VA

MIG1206, CDN-MIG-12-32 CWG 1.2/50, 8/20 s


The MIG1206 with CDN-MIG-12-32 is suitable to surge three-phase power supply line 440 V, 32 A up to 12 kV and 6 kA.

MIG1206-2P CWG 1.2/50, 8/20 s


The MIG1203-2P is suitable to surge single-phase power supply line 230 V, 16 A up to 12 kV and 6 kA.

MIG1206

Application The three-phase coupling filter CDN-MIG1232 can be used up to 12 kV and 6 kA. Power supply three-phase up to 440 V per phase and 32 A per phase High voltage circuit - Voltage (oc): 1.2/50 s - Current (cs): 8/20 s - Repetition rate maximum: 10/min - Source Impedance: 2 Ohm 10% . - Source energy: 880 Joule at 12 kV - Vpeak range 0.5 up to 12 kV 10% - Ipeak range 0.25 up to 6 kA 10% - Measurement accuracy 3% (v,i) - CDN three-phase 440V 32 A - Coupling path L to N, 18 F - Coupling path L-PE, 9 F and 10 Ohm - Two boxes solution, which allows to use the MIG1206 together with the test cabinet TC-MIG24 for component testing. - Coupling paths switching manual

MIG1206-2P: CWG 1.2/50, 8/20 s

Application - Surge protective devices (SPD) or varistor testing - Surge superimposed on power supply High voltage circuit - Voltage (oc): 1.2/50 s - Current (cs): 8/20 s - Repetition rate maximum: 10/min - Source Impedance: 2 Ohm10% . - Source energy: 220 Joule at 6 kV - Vpeak range 0.5 up to 12 kV 10% - Ipeak range 0.25 up to 6 kA 10% - Measurement accuracy 3% (v,i) - CDN single-phase 250 V 16 A - Coupling path L to N, 18 F - Coupling path L-PE, 9 F and 10 Ohm 5

MIG0603IN4 Ring Wave 100 kHz


The MIG0603IN4 is suitable to carry out Ring Wave tests on single-phase supply line 230 V, 16 A up to 6.3 kV. Source impedance: 12 and 30 Ohm.

Accessories: CDN, Special Networks


Three-phase coupling filter CDN2000-06-25 - CDN three-phase L to L 445 V, 25 A - Coupling path L to L/ N, 18 F - Coupling path L-PE, 9 F and 10 Ohm - Sincronisation onto different phases - Coupling Ring wave 10 F at 12 Ohm - Coupling Ring wave 3 F at 30 Ohm - Damped oscillatory 100 k, 1 MHz

MIG0603IN4: Ring 100 kHz, 6.3 kV

High voltage circuit - Rise time: 500 ns 30 % - Frequencies: 100 kHz 10% - Repetition rate maximum: 10/min - Decaying: 60% first to second peak - Impedance:12, 30 Ohm - Vpeak range 0.25 up to 6 kV 10% - Ipeak range 0.125 up to 3 kA 10% - Measurement accuracy 3% - CDN single-phase 260V 16 A - Coupling 12 Ohm, 10 F - Coupling 30 Ohm, 3 F

I/O and data line coupling kits CDN2000A-06-32 - Automatically coupling paths switsching for surge, ring wave and EFT - Control of the CDN2000A-06-32 with TRA2000, TRA2000INx and MIG0603INx

CDN-KIT1000T for ISDN balanced lines - Two coupling circuits - Two decoupling circuits

Basic data Dimensions: 450 x 500 x 190 mm Weight: approx. 30 kg Power supply: 230 V or 115 V, 400 VA

EMC PARTNERs Product Range

Immunity Tests
The TRA2000 performs all of the following transient tests on electronic equipment that are required for the CE-mark up to full levels: ESD, EFT, surge, dips, a.c. magnetic field, surge magnetic field and common mode tests. A large range of accessories for different applications is available: MF antennas, three phase couplers, verification sets, coupling kits, etc. The TRA2000 complies with IEC 61000-4-2, -4, -5, -8, -9, -11, -12p, -16, -29p. The Modular Impulse Generator (MIG) performs damped oscillatory tests: 100 kHz, 1 MHz, voltage and magnetic field tests. The MIG complies with IEC 61000-4-8, -9, -10, -12 as well as with IEC 60255-4, -5, -22. The HAR1000 with the Immunity software performs the following tests: harmonics, voltage variation and ripple on d.c. The HARMONICS-1000 complies with IEC 61000-4-13, -14, -17, -29p.

Component Tests
EMC PARTNER offers a wide range of modular impulse generators (MIG) for transient component testing on: varistors, arresters, surge protective devices (SPD), capacitors, circuit breakers, watt-hour meters, protection relays, insulation material, suppressor diodes, connectors, chokes, fuses, resistors, emc-gaskets, cables, etc. EMC PARTNER has the largest range of impulse generators in the range up to 100 kV and 100 kA. Below is an example for an insulation tester up to 24 kV.

Emission Measurements
One unit performs all measurements on the power supplies of electronic equipment and products for the CE-Mark. The HAR1000 includes an amplifier for a clean power source, a line impedance network, the measurement systems Harmonics and Flicker. Accessories: three phase extension, Immunity and ANASIM software. Complies with IEC 61000-3-2 and -3. 7

Lightning Tests
EMC PARTNER offers a wide range of testers in accordance with FCC 68 part D, ITU K.44, ETS 300 046, Bellcore and RTCA DO-160D, etc. for telecom, aircraft and military electronic equipment testing.

We look forward to working with you


For more detailed information please contact our representative in your area or EMC PARTNER in Switzerland. For information on further products please visit also our website. The headquarters: EMC PARTNER AG Baselstrasse 160 CH - 4242 Laufen Switzerland Phone: ++ 41 61 763 01 11 Fax: ++ 41 61 763 01 15 Email: sales@emc-partner.ch Web-Site: www.emc-partner.com We have representatives in: America: Canada, Mexico, USA, ... Asia: China, Hong Kong, Israel, Japan, Malaysia, South Korea, Taiwan, ... Australia: Australia, New Zealand Europe: Austria, Belgium, France, Germany, Great Britain, Hungary, Ireland, Italy, Netherlands, Scandinavia, Spain, ... You will find contact information for all representatives at EMC PARTNERs website www.emc-partner.com.

EMC PARTNER offers the largest range of impulse test equipment up to 100 kA and 100 kV in the areas of: Immunity Tests Lightning Tests Component Tests Emission Measurements

Your local representative:

Subject to change without notice. Printed in Switzerland in October 2002.

You might also like