DESCRIPTION
Medium Pressure Range Tolerable overload on one side Repeatability 0.2 3 mbar 0.5 5 mbar 1 10 mbar 5 20 mbar 10 50 mbar Resistive Load
0.025 mbar 0.05 mbar 0.05 mbar 0.05 mbar 0.15 mbar Switching Load 5 A at 250 Vac 4 A at 30 Vdc Inductive 0.8 A at 250 Vac 0.7 A at 30 Vdc Materials in contact with the medium Case: PC 10% GF Cover: PC Diaphragm: Silicone LSR tempered 200 C, free of gas emissions Temperature Medium and ambiance 30 +85 C -22.. +185F Storage 40 +85 C -40.. +185F Mechanical > 106 switching cycles Screw terminals or AMP connectors 6.3 mm or 4.8 mm according to DIN 46244 Cable gland PG11 with cable strain relief IP 00 IP 54 Pipe 6.2 mm Adapter inside thread G1/8 ETL CE conformity DVGW according to DIN 1854 EU conformity: Low voltage directive 73/23/EWG Gas appliance directive: 90/396/EWG CE 0085 A P0918
DIMENSIONS
Fig. 1
Flow area
1)
Fig. 2
Flow area
FUNCTION
The pressure switch has two separate pressure chambers, each with its own connection. The switch operates when the setpoint is either exceeded or not reached. Vacuum Monitoring Connect the pressure switch via P2. Do not connect P1. Leave P1 open. Pake sure that dirt can not get into P1. High Pressure Monitoring Connect the pressure switch via Pa. Do not Connect P2. Leave P2 open. Make sure that dirt can not get into P2. Filter Monitoring Connect P1 before the lter and P2 after it. Fan Monitoring Connect P1 after the fan (in blowing direction) and P2 before the fan.