Flatpack2 24/2000WOR

The combination of cost-effective design, power density and reliability makes the Flatpack2 a product family that truly stands outs and provides unparalleled network availability. The versatility of the Flatpack2 rectifier means that it can be used in a wide variety of 48VDC and 24VDC applications across the globe.

FLATPACK2 24/2000WOR
(RECTIFIER MODULE)
Doc 241115.250.DS3 rev6

APPLICATIONS
Wireless, fiber and fixed line communication Todays communications demand state of the art, cost effective and compact DC power systems. Flatpack2 delivers an industry leading power density and superb reliability at lowest lifetime cost Broadband and network access Increasing network speed demands flexible and expandable DC power solutions. The Flatpack2 rectifiers are your key building blocks for future needs. Small and large Due to the high power density, cost competitive design and a highly flexible system communication interface, Flatpack2 rectifiers are used in system solutions from 5kW to 96kW.

PRODUCT DESCRIPTION
The Flatpack2 WOR is a battery charger and rectifier for stand-alone use or for working in parallel as part of a DC power system controlled and monitored by the Smartpack. Its output voltage window is optimized for use with any type of batteries. Flatpack2 is optimized for a wide range of system sizes. Digital communication over CAN bus with Smartpack simplifies system design and enhances flexibility. Realization of Flatpack2 systems is possible by fitting 4 rectifiers across a 23 or 19 shelf.

KEY FEATURES
HIGHEST EFFICIENCY IN MINIMUM SPACE
Resonant topology makes the module efficiency industry leading and contributes to the rectifiers ultra compact dimensions.

DIGITAL CONTROLLERS
The number of component has been reduced by 40% - for highly reliable, long life, trouble free DC power systems.

HEAT MANAGEMENT

Front-to-back air flow with chassisintegrated heat sinks and no limitations in the scalability of the desired system solution. Time - to- install and cost-reducing solution.

UNIQUE CONNECTION

GLOBAL APPROVALS
Flatpack2 WOR is CE and UL marked.

Eltek - Grterudveien 8, PB 2340 Strms, 3003 Drammen, Norway

Phone: +47 32 20 32 00

Eltek 2013 www.eltek.com

FLATPACK2 24/2000WOR
(RECTIFIER MODULE)
INPUT DATA
Voltage Frequency Maximum Current Power Factor Input Protection 85-300 VAC (Nominal 185 275 VAC) 44 to 66Hz 12.5 Arms maximum at nominal input and full load > 0.99 at 50% load or more o o o Varistors for transient protection Mains fuse in both lines Disconnect above 300 VAC

OUTPUT DATA
Voltage Output Power Maximum Current Current Sharing Static voltage regulation Dynamic voltage regulation Hold up time Ripple and Noise Output Protection o Adjustable range: 21.5-36.0 VDC o Default voltage: 26.7 VDC 2000 W at nominal input 70.0 Amps at 29 VDC and nominal input 5% of maximum current from 10% to 100% load 0.5% from 10% to 100% load 5.0% for 10-90% or 90-10% load variation, regulation time < 50ms > 20ms; output voltage > 21.5 VDC at 1500W load < 100 mV peak to peak, 30 MHz bandwidth < 0.96 mV rms psophometric o Overvoltage shutdown o Fuse on output

o o

Short circuit proof High temperature protection

OTHER SPECIFICATIONS
Efficiency Isolation Alarms Typical 91% 3.0 kVAC input and output 1.5 kVAC input earth o Low mains shutdown o High temperature shutdown o Rectifier Failure o Overvoltage shutdown on output o Low temperature shutdown o Rectifier in power derate mode o Remote battery current limit activated Green LED: ON, no faults Red LED: rectifier failure Yellow LED : rectifier warning -40 to +75C (-40 to +167F) -40 to +85C (-40 to +185F) 2 fans (front to back airflow) Temperature and load regulated > 200, 000 hours Telcordia SR-332 Issue I, method III (a) (Tambient : 25C) < 65dBA at nominal input and 70% load (Tambient < 30C) Operating: Storage: 5% to 95% RH noncondensing 0% to 99% RH non-condensing 109 x 41.5 x 327mm (wxhxd) (4.25 x 1.69 x 13) 1.9 kg (3.97 lbs) 0.5 kVDC output earth o Fan failure, one or two fans. o Low voltage alarm at 21.0V o CAN bus failure o o Input voltage out of range, flashing at overvoltage Loss of CAN communication with control unit, stand alone mode

Warnings

Visual indication

Operating temp. Storage temp. Cooling Fan Speed MTBF Acoustic Noise Humidity Dimensions Weight

APPLICABLE STANDARDS
Electrical safety EMC IEC 60950-1 UL 60950-1 ETSI EN 300 386 V.1.3.2 (telecommunication network) EN 61000-6-4 (emission, industry) EN 61000-6-3 (emission, light industry) EN 61000-3-2 ETSI EN 300 019-2 ETSI EN 300 132-2 CSA 22.2

EN 61000-6-2 (immunity, industry) EN 61000-6-1 (immunity, light industry) Telcordia NEBS GR1089 CORE Telcordia NEBS GR63 CORE Zone 4 RoHS compliant

Mains Harmonics Environment

ORDERING INFORMATION
Part No. 241115.250
Doc 241115.250.DS3 rev6

Description Flatpack2 24/2000 WOR


Specifications are subject to change without notice

Eltek - Grterudveien 8, PB 2340 Strms, 3003 Drammen, Norway

Phone: +47 32 20 32 00

Eltek 2013 www.eltek.com