Location via proxy:   [ UP ]  
[Report a bug]   [Manage cookies]                

Process Control For Process I/O: Modbus Communications Manual

Download as pdf or txt
Download as pdf or txt
You are on page 1of 31

MTL8000

Process Control for Process I / O


Modbus Communications Manual
Application Note
CONTENTS
i
Contents AN80021 April 1999
MODBUS COMMUNICATIONS .......................................................................................................... 1
INTRODUCTION....................................................................................................................................... 1
Related publications.......................................................................................................................... 1
WHAT IS MODBUS?................................................................................................................................ 2
MODBUS TRANSACTIONS ....................................................................................................................... 2
THE QUERY-RESPONSE CYCLE............................................................................................................... 3
The query.......................................................................................................................................... 4
The response.................................................................................................................................... 4
THE TRANSMISSION MODE...................................................................................................................... 4
MODBUS MESSAGE FRAMING.................................................................................................................. 5
THE MESSAGE FIELDS............................................................................................................................ 5
The address field.............................................................................................................................. 5
The function field .............................................................................................................................. 5
The data field.................................................................................................................................... 6
The error check field......................................................................................................................... 6
DATA ENCODING AND SCALING.............................................................................................................. 6
MODBUS CONCEPTS AND NOMENCLATURE.............................................................................................. 7
The register concept ......................................................................................................................... 7
Register and flag organisation and addressing................................................................................. 7
DATA & CONTROL FUNCTIONS....................................................................................................... 9
READ COIL STATUS (FUNCTION 01)........................................................................................................ 9
READ INPUT STATUS (FUNCTION 02)..................................................................................................... 10
READ HOLDING REGISTERS (FUNCTION 03) ......................................................................................... 11
READ INPUT REGISTERS (FUNCTION 04)............................................................................................... 12
FORCE SINGLE COIL (FUNCTION 05) .................................................................................................... 13
PRESET SINGLE REGISTER (FUNCTION 06)........................................................................................... 13
DIAGNOSTICS (FUNCTION 08) ............................................................................................................... 14
Return Query Data (sub-function 00 00)........................................................................................ 14
Restart Comm Option (sub-function 00 01)................................................................................... 15
Return Diagnostic Register (sub-function 00 02)............................................................................ 15
Change Input Delimiter Character (sub-function 00 03) ................................................................ 16
Force Slave to Listen only Mode (sub-function 00 04) ................................................................... 16
FETCH COMMUNICATIONS EVENT COUNTER (FUNCTION 11) ................................................................. 16
FETCH COMMUNICATIONS EVENT LOG (FUNCTION 12).......................................................................... 17
What Event Bytes Contain.............................................................................................................. 18
FORCE MULTIPLE COILS (FUNCTION 15)............................................................................................... 19
PRESET MULTIPLE REGISTERS (FUNCTION 16) ..................................................................................... 20
REPORT SLAVE ID (FUNCTION 17)........................................................................................................ 20
EXCEPTION RESPONSES ............................................................................................................... 22
CONSTRUCTION OF EXCEPTION RESPONSES......................................................................................... 22
EXCEPTION RESPONSE TYPES .............................................................................................................. 22
Illegal Function (exception code 01)................................................................................................ 23
Illegal Data Address (exception code 02)........................................................................................ 23
Illegal Data Value (exception code 03) ............................................................................................ 23
Failure in subsystem (exception code 04)....................................................................................... 23
Acknowledge (exception code 05) .................................................................................................. 24
Slave Device Busy (exception code 06) .......................................................................................... 24
Negative Acknowledge (exception code 07).................................................................................... 24
CONTENTS
ii
THE MODBUS PHYSICAL LAYER................................................................................................... 25
The RS485 serial interface standard .............................................................................................. 25
2- and 4-wire interconnection.......................................................................................................... 25
Point-to-point and multi-drop connection......................................................................................... 26
Data converters............................................................................................................................... 26
APPENDIX - CALCULATION OF THE CRC IN RTU MODE............................................................ 27
MODBUS COMMUNICATIONS
1
Modbus Communications
Introduction
This manual provides a background to the Modbus protocol and, broadly, how it is
implemented for the MTL8000 Series
1
of bus interface equipment for process I/O. It is only
one of a range of protocols available to interface control systems to the above equipment but
it has substantial history in the industry and is a protocol that control engineers have become
familiar with and is one into which they can comfortably delve. This manual is designed to
assist engineers in their understanding of the protocol and possible development of custom
interfaces for controlling the MTL8000 equipment.
The manual is organised as follows:
A discussion of how Modbus originated and its basic structure
A review of the main Modbus Control Functions and the data involved
A look at Exception Responses - when instructions from the master can not be executed
Implementing the physical layer of Modbus
Related publications
Information specific to the Modbus interfaces in the MTL8000 Series is available in the
following MTL publications:
INM8505 Instruction Manual, MTL8505 - Modbus BIM
INM8800BUS BUS8800-MB Interface Manual
The MTL8000 Series Bus Interface Module (BIM) has a dedicated software package to enable
the user to configure it and to define parameters such as network address, etc. This software
is explained in the following MTL publication:
INM8450 Instruction Manual, BIM Configuration Software

1
Throughout this manual, references to MTL8000 Series automatically includes the MTL8800L Series
equipment.
MODBUS COMMUNICATIONS
2
What is Modbus?
Modbus is a communication protocol developed by AEG-Modicon, and was devised initially
for use with their own Programmable Logic Controllers. It has, subsequently, become widely
accepted as a communications standard, and many products have now been developed which
use this protocol.
The protocol specification is maintained by its originators, AEG-Modicon, independently of
any professional body or industry association. Consequently, there is no formal process by
which a product may be certified to be 'Modbus compatible'. The onus is on the manufacturer
of the product to confirm that their products are, and continue to remain, compatible with
other Modbus devices.
The protocol defines a message structure and format, and determines how a slave will
recognise messages sent to it by its master, and how it should decode the information
contained in the message. Standardisation of these elements has meant that Modbus devices
from a number of different manufacturers can be interconnected, without the need for
specialised software drivers for each component.
Note: Modicon have also developed a new protocol called Modbus Plus. This has remained
proprietary and is not widely used; consequently, Modbus Plus is not supported by the
MTL8000 bus interfaces.
JBUS is a very similar protocol to Modbus and, insofar as the commands provided for the
Modbus slave coincide with those of JBUS, the JBUS protocol will be supported. However,
where there are minor differences in interpretation of the diagnostics sub-functions the
Modbus version will take precedence.
Modbus Transactions
Modbus controllers communicate using a master-slave technique, in which only one device
(the master) can initiate a communication sequence.
Note: Throughout this manual the term slave can normally be interpreted as referring to an
MTL8000 bus interface, unless otherwise indicated. The reason for this is so that topics can
be expressed in general Modbus terms which will then be of more general use to a reader.
Figure 1 - Master - slave communication
The sequence begins with the master issuing a request or command on to the bus (a 'query'),
which is received by the slaves.
The slaves respond by:
taking appropriate action,
supplying requested data to the master or
informing the master that the required action could not be carried out.
The master can address individual slaves or can transmit a message to be received by all slaves
- through a 'broadcast' message (Figure 1).
When a slave receives a message addressed specifically to that slave, it will return a message
to the master called a 'response'.
The response confirms:
that the message was received, understood and acted upon, or
it informs the master that the action required could not be carried out.
MODBUS COMMUNICATIONS
3
If the 'query' requests data from the slave, this will be returned as part of the response.
Messages 'broadcast' to all slaves do not require responses.
Figure 2 - Broadcast communication
Modbus slaves will only transmit on to the network when required to do so by the master.
Slaves never transmit unsolicited messages.
If the slave cannot carry out the requested action, then it will respond with an error message.
This error message, known as an exception response, indicates to the master:
the address of the responding slave,
the action it was requested to carry out and
an indication of why the action could not be completed.
If the slave identifies an error during receipt of the message, the message will be ignored. This
ensures that a slave does not take action that was really intended for another slave, and does
not carry out actions other than those it is commanded to. Should, for some reason, the
message be ignored, the master will know that it's query has not been received correctly, as it
has not received a response, and will resend it.
Modbus does not define how numerical data shall be encoded within the message. This is
decided by the equipment manufacturer and a wide range of options are available.
Modbus ports frequently employ RS232C compatible serial interfaces, though RS422 and
RS485 interfaces are also used. The type of interface used defines the connector pin-outs, the
cabling and the signal levels; these are not defined in Modbus. Similarly, transmission rates and
parity checking are not defined in Modbus and will depend on the serial interface used and
the options made available by the manufacturer of each Modbus component.
Modbus will support up to 247 slaves from addresses 1 to 247 (JBUS 1 to 255) - address 0 is
reserved for broadcast messages. In practice, the number of slaves that can be used is
determined by the physical communications link that is chosen. For example, RS485 is limited
to a total of 31 slaves.
The query-response cycle
The query-response cycle forms the basis of all communication on a Modbus network. In all
situations it is the master that initiates the query and the slave that responds.
Figure 3 - The query / response cycle
MODBUS COMMUNICATIONS
4
The query
The query is made up of four parts: the device address; the function code; eight bit data
bytes; and an error check.
The device address - uniquely identifies a particular slave or indicates that the message is a
'broadcast' addressed to all slaves.
The function code - tells the slave what type of action to perform.
The data - bytes contain any data that the slave will require to carry out the requested
function (this may be a register address within the slave, a value to be used by the slave, etc.).
The error check - field allows the slave to confirm the integrity of the message received
from the master. If an error is detected, the slave ignores the query and waits for the next
query to be addressed to that slave.
The response
A slave will normally be required to provide a response (when a query has been addressed to
that slave specifically, and not broadcast to all slaves), which will have the same overall
structure format as was used for the query: a device address; a function code; eight bit data
bytes; and an error check.
The device address - in the response is that of the addressed slave. This indicates to the
master which slave is replying to it's query, and allows it to confirm that the correct slave is
responding.
The function code - in the response is normally an exact copy of the function code in the
query, and will only vary if the slave is unable to carry out the requested function. In such
circumstances the function code returned is a modified form of the original code - this then
indicates which function the slave was unable to perform.
The data - contain any data requested in the query.
The error check - allows the master to confirm the integrity of the message received from
the slave - if the error check is not correct, the response is ignored.
The transmission mode
There are, in fact, two modes available for transmitting serial data over a Modbus network
RTU and ASCII. The two transmission modes differ in a number of ways: the way that the bit
contents of the messages are defined, the way that information is packed in to the message
fields, the way it will be decoded and the speed of operation at a given baud rate. They
cannot be used together, and the mode used must be adopted by all the Modbus components
throughout the network.
The RTU (Remote Terminal Unit) mode is faster and more robust than ASCII and it is for
these reasons that it has been adopted for the MTL8000 Series bus interfaces. None of the
MTL8000 Series bus interfaces accommodate the Modbus ASCII mode and so no further
space will be devoted to discussing it.
The RTU mode has the following characteristics:
8-bit data is encoded in the message as one 8-bit byte .
The transmitted messages are not printable.
The start and end of each message is signalled by 'gaps' in transmission.
Transmission of data within the message must be continuous.
The error checking employed is a Cyclical Redundancy Check (CRC).
The format for each byte in the RTU mode is:
Coding system: 8-bit binary, comprising two 4-bit hexadecimal characters
Bits per byte: 1 start bit, 8 data bits, least significant bit sent first,
1 bit for even/odd parity; no bit for no parity and 1 or 2 stop bits
Error check field: Cyclical Redundancy Check (CRC)
MODBUS COMMUNICATIONS
5
The table below shows the encoding of a message:
Message RTU
start of frame - > 3 chars
slave address 01 0000 0001
function 04 0000 0100
data 04 01 0000 0100
0000 0001
error check - 1111 0001
1100 1001
end of frame - -
The message above requests that the slave with address '01' reads a holding register (function
'04') - and returns the values to the master. For simplicity, start, stop and parity bits have been
omitted.)
Modbus message framing
Modbus messages must be structured (or 'framed') so that the different Modbus components
can detect the start, content structure and end point of a message. It also allows any errors to
be detected.
An RTU message begins with a gap in transmission of at least 3.5 character periods (T).
Network components monitor the bus continuously and when a 'silent' period of more than
3.5 character periods is detected, the first character following the transmission gap is
translated to determine if it corresponds to the device's own address.
START ADDRESS FUNCTION DATA CRC CHECK END
T1-T2-T3-T4 8 BITS 8 BITS n X 8 BITS 16 BITS T1-T2-T3-T4
The end of the transmitted message is marked by a further interval of at least 3.5 character
periods duration. A new message can only begin after this interval.
The entire message field must be transmitted as a continuous stream. If an interval of more
than 1.5 character periods is detected during transmission of the message, then the message is
assumed to be incomplete and the device returns to waiting for the next device address. The
action taken on receipt of an incomplete message is as for receipt of an incorrect message,
and it is ignored.
If a new message begins within 3.5 characters periods of the end of the previous frame, the
device again ignores the message.
The message fields
The address field
Slave addresses may be in the range 1 to 247 with Modbus (1 to 255 with JBUS). A slave is
addressed by the master placing the relevant address in the address field of the query
message. When the slave sends its response, it places its own address in the message field to
indicate to the master that the correct slave is replying.
Address '0' is used for 'broadcast' messages. All suitable slaves read them, but do not provide
responses to such query messages.
The function field
Function codes may be in the range 1 - 255, though not all functions will be supported by all
devices. When a message is sent from a master to a slave, the function code defines the action
that is required from the addressed slave. Examples of action requested by the various
function codes include: read input status; read register content; change a status within the
slave; etc..
When the slave sends its response to the master, it will repeat the function code received, to
indicate that the slave has understood the query and acted accordingly. If the query
instruction could not be carried out by the slave, an 'exception response' is generated and the
function code and data fields are used to inform the master of the reason for the exception.
MODBUS COMMUNICATIONS
6
The exception response is generated by returning the original function code from the master,
but with its most significant bit set to '1'. Further information regarding the exception
response is passed to the master via the data field of the response message. This tells the
master what kind of error occurred and allows it to take the most appropriate action - either
to repeat the original message, to try and diagnose what has happened to the slave, to set
alarms or to take whatever action is most appropriate.
The data field
Firstly, the responses to a number of queries require the slave to inform the master of the
number of data bytes that are being returned in the response, and this requires a special
implementation within the data field.
A typical example of this would be when the master has requested the slave to communicate
the status of a range of registers. The slave responds by repeating the function code and it's
own address, followed by the data field. The first byte of the data field identifies the number
of bytes that are being returned that contain the register status information.
The main data field then transmits a number of two hexadecimal values, each in the range 00
to FF represented by a single character.
Significantly, the encoding of numerical data is not defined by Modbus, and consequently a
number of data formats can be employed. The choice from those available is left to the user.
The data field provides the slave with any additional information needed to perform the
function requested in the query. This would typically be a register address, a register range or
a value. For some functions, the data field is not required and is not included in the query.
If no errors have occurred, the data field of the response is used by the slave to pass data
back to the master. If an error does occur, the data field is used to pass more information to
the master relating to the nature of the fault detected.
The error check field
The error checking technique employed on the Modbus network depends on the
transmission mode selected. The error check value (in RTU mode) is the result of a Cyclical
Redundancy Check (CRC) calculation performed on the message contents. A fuller
explanation of this error checking technique is given at the end of this manual in the
Appendix.
On receipt of the message, the receiving device also calculates an error check value and then
compares it with the error check value in the received message. If these two values do not
match exactly, then the receiving device knows that it has not received the message correctly,
and disregards it.
Parity checking can be optionally selected.
Data Encoding and Scaling
As has been mentioned, the encoding of numerical data is not defined by the Modbus
protocol, and manufacturers supplying products for general use must allow the user to select
the data encoding technique. The numerical data formats used include:
signed (2s complement) 16-bit integer,
unsigned 16-bit integer
16 bits that represent 16 individual logic states
Another area associated with the encoding of data is the way in which the data is scaled
details of such scaling are available from the relevant bus interface documents.
MODBUS COMMUNICATIONS
7
Modbus concepts and nomenclature
Modbus was originally written as a communication protocol for use with Modicon's own PLCs,
and the nomenclature and concepts within Modbus reflect this early intention.
The register concept
The Modbus protocol operates on the basis that slaves hold their data in a series of defined
status flags and registers, which have defined addresses. A number of flags and registers are
set aside for various purposes: single and multi bit output and single and multi bit input/output.
Register and flag organisation and addressing
The registers and flags within Modbus devices are normally grouped as below:
Figure 4 - Addressing Modbus registers
It is not absolutely necessary for manufacturers of Modbus devices to follow the register
numbering adopted by Modicon's PLCs, but it is conventional to do so wherever possible.
Note: Commands issued by the master, relating to individual coils or registers, always use an
address not the number of the coil or register, and all data addresses in Modbus messages are
referenced to zero. Consequently, the first occurrence of a data item (e.g. coil 1) is addressed
as item number zero. Other examples of the addressing pattern are given below.
The coil known as coil 1 in the slave is addressed as coil 0000 in the data address field of a
Modbus message.
Coil 127 decimal is addressed as coil 007E hex (126 decimal)
Holding register 40001 is addressed as register 0000 in the data address field of the
message. The function code that precedes the data in the message already specifies the
operation as relating to a holding register; therefore, the 4xxxx reference is implicit and
does not need the additional digit.
Holding register 40108 is addressed as register 006B hex (107 decimal).
COIL STATUS flags (read/write)
The single bit 'COIL STATUS' flags are conventionally numbered 0xxxx, and store digital
output informationwhere an output is defined as being from the slave to the field. The
Modbus master can both read from, and write to, these flags.
Note: The term 'coil' comes from the original PLC application, in which the outputs from the PLC
were set by controlling the coils of the output relays.
MODBUS COMMUNICATIONS
8
INPUT STATUS flags (read only)
The single bit 'INPUT STATUS' flags are conventionally numbered 1xxxx. They store the
status of digital inputs to the Modbus slave and can only be read by the master. There is no
facility, nor any need, for the master to write to these locations.
INPUT REGISTERS (read only)
The 16-bit 'INPUT REGISTERS' are conventionally numbered 3xxxx. They store data which
has been collected from the field by the Modbus slave . These registers can only be read by
the Modbus master.
HOLDING REGISTERS (read/write)
The 16-bit 'HOLDING REGISTERS' are conventionally numbered 4xxxx. They hold general
purpose data within the slave. . The master can both read from, and write to, these flags. A
typical application for these registers would be to hold configuration data.
DATA & CONTROL FUNCTIONS
9
Data & Control Functions
The following table lists a range of Modbus functions some or all of which are supported by
the MTL8000 bus interfaces.
FUNCTION No.
READ COIL STATUS 01
READ INPUT STATUS 02
READ HOLDING REGISTERS 03
READ INPUT REGISTERS 04
FORCE SINGLE COIL 05
PRESET SINGLE REGISTER 06
DIAGNOSTICS 08
FETCH COMM EVENT COUNTER 11
FETCH COMM EVENT LOG 12
FORCE MULTIPLE COILS 15
PRESET MULTIPLE REGISTERS 16
REPORT SLAVE ID 17
Note: This section contains a number of detailed tables that demonstrate the construction of
messages passed along the Modbus network. However, most Modbus masters have a user-
interface that shelters the user from many of these details, and will only require set-up of
the slave address, the function code, the initial coil or register location and the number of coils
or registers to be read. High-level users will not need not concern themselves with the
details presented here.
Some of the values are shown as hexadecimal (hex) some as binary. The hex values are given
to describe the code or value that must be sent in the query and the response. The binary
code for transmission in RTU mode is given directly, and it will be seen that this is a simple
encoding of the equivalent hex value.
In the body of the text, decimal values are used, so as to be consistent with the numbering of
the function codes in Revision 'G' of the Modbus specification. Where the encoding of these
decimal values in to hex makes them appear differently in the table, the hex value is given in
parenthesis - e.g. function code 10 ('OA' in hex). For simplicity, start, stop and parity bits are
ignored throughout.
Read Coil Status (function 01)
This function requests that the slave reads the status of a specified range of it's single bit
input/output flags and returns these to the master. The range of flags to be read is given in the
query, by the master indicating the address of the first flag to be read and then total number
of subsequent flags - including the first.
The example in the following table shows the query required to read the status of coils 00001
to 00009 of slave number 20 (14 in hex.). The start address and number of coils to be read
are always transmitted as two bytes - most significant bits (MSB) first, followed by the least
significant bits (LSB):
FIELD NAME HEX. VALUE RTU
slave address 14 0001 0100
function 01 0000 0001
starting address MSB 00 0000 0000
starting address LSB 00 0000 0000
no. of locations MSB 00 0000 0000
no. of locations LSB 09 0000 1001
error check - CRC
DATA & CONTROL FUNCTIONS
10
Note: Recall that, as the address is always 1 less than the least significant 4 digits of the coil
number, the coil '10001' is addressed as '00 00' (hex).
The normal response to a READ COIL STATUS query contains the slave address, the
repeated function code, the number of data bytes that are being transmitted in the response,
the data bytes themselves and the error check.
The data bytes encode the status of the flags so that the status of the first flag to be read
forms the LSB of the first data byte. Subsequent flag states form the next most significant bits
of the first byte - thus if the master had requested the status of 8 flags, the data would be
transmitted in a single data byte, with the LSB being the status of the first flag and the MSB
being the status of the eighth. This is continued so that the status of the ninth flag requested
forms the LSB of the second data byte.
If the master requests the status of a number of flags so that it is not possible to return
'complete' 8-bit data bytes (e.g. if the master requests the status of 9 flags, as above, which
would require one complete 8-bit byte and a single bit), then the last data byte to be
transmitted is 'packed' with '0's in it's MSBs.
The convention followed for the status is: 1 = ON; 0 = OFF.
A response to the query above would have the following format:
FIELD NAME HEX. VALUE RTU
slave address 14 0001 0100
function 01 0000 0001
number of data bytes returned 02 0000 0010
first data byte XX XXXX XXXX
second data byte 0X 0000 000X
error check - CRC
Note: The seven most significant bits of the second data byte in RTU mode are zero, as the
query only requested the status of 9 inputs. The seven zeros were packed in to the response
to allow the slave to return complete 8-bit data bytes.
Read Input Status (function 02)
This function requests that the slave reads the status of a specified range of it's single bit
output flags and returns these to the master. The range of inputs to be read is given in the
query, by the master indicating the address of the first input to be read and then total number
of subsequent flags - including the first.
The example below shows the query required to read the status of flags 10001 to 10030 of
slave number 17 (11 in hex.). The start address and number of flags to be read are always
transmitted as two bytes - most significant bits (MSB) first, followed by the least significant bits
(LSB):
FIELD NAME HEX. VALUE RTU
slave address 11 0001 0001
function 02 0000 0010
starting address MSB 00 0000 0000
starting address LSB 00 0000 0000
no. of locations MSB 00 0000 0000
no. of locations LSB 1E 0001 1110
error check - CRC
Note: Recall that, as the address is always 1 less than the least significant 4 digits of the input
number, the input '10001' is addressed as '00 00' (hex).
The normal response to a READ INPUT STATUS comprises the slave address, the repeated
function code, the number of data bytes that are being transmitted in the response, the data
bytes themselves and the error check.
DATA & CONTROL FUNCTIONS
11
The data bytes encode the status of the inputs so that the status of the first input to be read
forms the LSB of the first data byte. Subsequent input states form the next most significant
bits of the first byte - thus if the master had requested the status of 8 inputs, the data would
be transmitted in a single data byte, with the LSB being the status of the first input and the
MSB being the status of the eighth. This is continued so that the status of the ninth input
requested forms the LSB of the second data byte.
If the master requests the status of a number of inputs so that it is not possible to return
'complete' 8-bit data bytes (e.g. if the master requests the status of 30 inputs as in the above
request, which would require three complete 8-bit bytes and 6 single bits), then the last data
byte to be transmitted is 'packed' with '0's in it's MSBs.
The convention followed for the status is: 1 = ON; 0 = OFF.
A response to the query above would have the following format:
FIELD NAME HEX. VALUE RTU
slave address 11 0001 0001
function 02 0000 0010
number of data bytes returned 4 0000 0100
first data byte xx xxxx xxxx
second data byte xx xxxx xxxx
third data byte xx xxxx xxxx
fourth data byte xx 00xx xxxx
error check - CRC
Note: The two most significant bits of the fourth data byte in RTU mode are zero, as the
query only requested the status of 30 inputs. The two zeros were packed in to the response
to allow the slave to return complete 8-bit data bytes.
Read Holding Registers (function 03)
This function requests that the slave reads the binary contents of a specified range of its 16-bit
holding registers and returns the values to the master. The range of registers to be read is
given in the query, by the master indicating the address of the first register and the total
number of subsequent registers to be read - which includes the first register.
The example below shows the query that requests the values held in holding registers 40108
to 40110 in slave 17 (108 and 17 are 6C and 11 in hex).
FIELD NAME HEX. VALUE RTU
slave address 11 0001 0001
function 03 0000 0011
starting address MSB 00 0000 0000
starting address LSB 6B 0101 1011
no. of registers MSB 00 0000 0000
no. of registers LSB 03 0000 0011
error check - CRC
Note: Recall that, as the address is always 1 less than the least significant 4 digits of the
register number, register '40108' is addressed as 0107 (hex. value '6B').
The normal response returns the slave address, the repeated function code, the number of
data bytes that are being transmitted in the response, the data bytes themselves and the error
check.
The data bytes encode the contents of the holding registers as two bytes per register, with
the binary contents right justified within each byte. For each register, the first byte contains
the high order bits and the second byte the low order bits.
DATA & CONTROL FUNCTIONS
12
A response to the query above would have the following format:
FIELD NAME HEX. VALUE RTU
slave address 11 0001 0001
function 03 0000 0011
number of data bytes returned 06 0000 0110
first data byte (MSB 40108) xx xxxx xxxx
second data byte (LSB 40108) xx xxxx xxxx
third data byte (MSB 40109) xx xxxx xxxx
fourth data byte (LSB 40109) xx xxxx xxxx
fifth data byte (MSB 40110) xx xxxx xxxx
sixth data byte (LSB 40110) xx xxxx xxxx
error check - CRC
Read Input Registers (function 04)
This function requests that the slave reads the binary contents of a specified range of its 16-bit
input registers and returns the values to the master. The range of inputs to be read is given in
the query, by the master indicating the address of the first register and the total number of
registers to be read - including the first register.
The example below shows the query required to read the values held in input register 30009
from slave 31 (1F in hex).
FIELD NAME HEX. VALUE RTU
slave address 1F 0001 1111
function 04 0000 0100
starting address MSB 00 0000 0000
starting address LSB 08 0000 1000
no. of points MSB 00 0000 0000
no. of points LSB 01 0000 0001
error check - CRC
Note: Recall that, as the address is always 1 less than the least significant 4 hex. values of the
register number, register '30009' is addressed by the hex. value '00 08'.
The normal response to a READ INPUT REGISTERS query comprises the slave address, the
repeated function code, the number of data bytes that are being transmitted in the response,
the data bytes themselves and the error check.
The data bytes encode the contents of the input registers as two bytes per register. For each
register, the first byte contains the high order bits and the second byte the low order bits.
A response to the query above would have the following format:
FIELD NAME HEX. VALUE RTU
slave address 1F 0001 1111
function 04 0000 0100
number of data bytes returned 02 0000 0010
first data byte (MSB) xx xxxx xxxx
second data byte (LSB) xx xxxx xxxx
error check - CRC
DATA & CONTROL FUNCTIONS
13
Force Single Coil (function 05)
The FORCE SINGLE COIL function requests that the slave sets a specified input/output flag
to a particular status. The address of the flag to be set is given in the query. The status to
which the flag must be set is provided by two data bytes. If the flag is to be set to '1', then the
data bytes sent are FF 00. If the flag is to be set to '0' the data bytes are 00 00.
The example below shows the query required to force the status of a flag with address 10065
of slave 18 to '1'. (65 and 18 are '41' and '12' in hex.)
FIELD NAME HEX. VALUE RTU
slave address 12 0001 0010
function 05 0000 0101
flag address MSB 00 0000 0000
flag address LSB 40 0100 0000
force data MSB FF 1111 1111
force data LSB 00 0000 0000
error check - CRC
The normal response to a FORCE SINGLE COIL query comprises the slave address, an echo
of the function code, echoes of the flag address and status request, and an error check.
A response to the query above would have the following format:
FIELD NAME HEX. VALUE RTU
slave address 12 0001 0010
function 05 0000 0101
flag address MSB 00 0000 0000
flag address LSB 40 0100 0000
force data MSB FF 1111 1111
force data LSB 00 0000 0000
error check - CRC
Preset Single Register (function 06)
The Preset Single Register function requests the slave writes specified data in a particular
register. The address of the register to be written to is given in the query. The data to be
written is provided by two data bytes.
The example below shows the query required to pre-set or write a register so that it holds
the value FF FF. The register location is 40003 of slave 1.
FIELD NAME HEX. VALUE RTU
slave address 01 0000 0001
function 06 0000 0110
register address MSB 00 0000 0000
register address LSB 02 0000 0010
pre-set data MSB FF 1111 1111
pre-set data LSB FF 1111 1111
error check - CRC
The normal response to a Preset Single Register query comprises the slave address, and echo
of the function code, echoes of the register address and the pre-set data, and an error check.
DATA & CONTROL FUNCTIONS
14
A response to the query above would have the following format:
FIELD NAME HEX. VALUE RTU
slave address 01 0000 0001
function 06 0000 0110
register address MSB 00 0000 0000
register address LSB 02 0000 0010
pre-set data MSB FF 1111 1111
pre-set data LSB FF 1111 1111
error check - CRC
Diagnostics (function 08)
The diagnostics function has a number of tests to check the communications link between the
master and the slave. The type of test is identified by a sub-function code in the first two
bytes of the data field.
Some of the tests specified by the subfunctions require the slave to return data in the
response to the query, others only require the slave to acknowledge receipt of the response
in the normal way. Responses to diagnostic functions will return the subfunction code as well
as the 08 function code.
There are a number of sub-function codes and the user is referred to the instruction manual
appropriate to the MTL8000/8800L equipment of interest for information on the particular
codes in use. The following lists and then describes some of the most used sub-functions.
SUB-FUNCTION No.
RETURN QUERY DATA 00
RESTART COMM OPTION 01
RETURN DIAGNOSTIC REGISTER 02
CHANGE ASCII I/P DELIMITER 03
FORCE LISTEN ONLY MODE 04
Return Query Data (sub-function 00 00)
The diagnostic subfunction Return Query Data requests the addressed slave to return (loop-
back) to the master an exact copy of the data contained in the query. This is a useful method
for confirming correct communication.
An example of a query and response with this subfunction is given below. The master
requests slave number 4 to return the hexadecimal data 'AA BB'.
The query:
FIELD NAME HEX. VALUE RTU
slave address 04 0000 0100
function 08 0000 1000
subfunction MSB 00 0000 0000
subfunction LSB 00 0000 0000
data MSB AA 1010 1010
data LSB BB 1011 1011
error check - CRC
The response echoes the original message:
FIELD NAME HEX. VALUE RTU
slave address 04 0000 0100
function 08 0000 1000
subfunction MSB 00 0000 0000
subfunction LSB 00 0000 0000
data MSB AA 1010 1010
data LSB BB 1011 1011
error check - CRC
DATA & CONTROL FUNCTIONS
15
Restart Comm Option (sub-function 00 01)
This code causes the slave to be reset and all counters to be cleared. If Continue on Error
(FF 00) is specified, the COMM EVENT LOG will be cleared. A normal response is sent
before the restart is executed. If the slave is in Listen Only Mode when the Restart command
is received, no response will be initiated.
Restart is the only command that will bring the slave out of Listen Only Mode. If this
command is received, a restart is attempted, executing the power-up confidence tests.
Successful completion of these tests will put the unit back in on-line mode.
An example of a query and response with this subfunction is given below. The master is
attempting to restart slave number 8 and is also specifying the Continue on Error command
(FF 00).
The query:
FIELD NAME HEX. VALUE RTU
slave address 08 0000 1000
function 08 0000 1000
subfunction MSB 00 0000 0000
subfunction LSB 01 0000 0000
data MSB FF 1111 1111
data LSB 00 0000 0000
error check - CRC
The normal response to a Restart Comm Option, unless in Listen Only mode, comprises the
slave address, and echo of the function code, echoes of the register address and the pre-set
data, and an error check.
Return Diagnostic Register (sub-function 00 02)
The diagnostic subfunction Return Diagnostic Register requests that the slave reads the
contents of its diagnostic register and returns the binary data values to the master.
The query sends two zero data bytes, following the data bytes containing the subfunction
code. The response returns two 8-bit data bytes containing the register data.
The contents of the diagnostic register may be defined by the manufacturer, according to the
needs of each Modbus slave.
The following example shows the query and response generated when the master requests
diagnostic subfunction 00 02 from the slave with address 12 ('0C' in hex.).
The query:
FIELD NAME HEX. VALUE RTU
slave address 0C 0000 1100
function 08 0000 1000
subfunction MSB 00 0000 0000
subfunction LSB 02 0000 0010
data MSB 00 0000 0000
data LSB 00 0000 0000
error check - CRC
The response:
FIELD NAME HEX. VALUE RTU
slave address 0C 0000 1100
function 08 0000 1000
subfunction MSB 00 0000 0000
subfunction LSB 02 0000 0010
data MSB XX XXXX
XXXX
data LSB XX XXXX
XXXX
error check - CRC
DATA & CONTROL FUNCTIONS
16
Change Input Delimiter Character (sub-function 00 03)
The character passed by the master in the data field provides a means to define, or re-define,
the line feed (LF) character used to delimit an ASCII message.
An example of a query using this subfunction is given below. The master is telling slave
number 4 to use the character 0A as an ASCII message delimiter.
The query:
FIELD NAME HEX. VALUE RTU
slave address 04 0000 0100
function 08 0000 1000
subfunction MSB 00 0000 0000
subfunction LSB 03 0000 0000
data MSB 0A 0000 1010
data LSB 00 0000 0000
error check - CRC
A normal response, that echoes the query, is issued by the slave.
Force Slave to Listen only Mode (sub-function 00 04)
This function forces the slave into listen only mode (LOM). When in this mode the slave
monitors transmitted data but no response will be issued. The only query that will be
recognised is the Restart command (see Diagnostics sub-function 00 01).
When in LOM all active controls are immediately turned off and the Ready watchdog timer is
allowed to expire, locking these controls off. This isolates a failed unit from other stations on
the line, allowing the others to continue full communication without interference.
The following example shows the query when the master uses diagnostic subfunction 00 04 to
force slave 12 ('0C' in hex.) into Listen only Mode.
The query:
FIELD NAME HEX. VALUE RTU
slave address 0C 0000 1100
function 08 0000 1000
subfunction MSB 00 0000 0000
subfunction LSB 04 0000 0100
data MSB 00 0000 0000
data LSB 00 0000 0000
error check - CRC
As stated earlier, no response is generated by the slave for this query.
Fetch Communications Event Counter (function 11)
This function requests that the slave returns a status word and an event count from the its
communications event counter. By fetching the current count before and after a series of
messages, a master can determine whether the messages were handled normally by the slave.
Broadcast is not supported by this function.
The controllers event counter is incremented once for each successful message completion.
It is not incremented for exception responses, poll commands or fetch event counter
commands.
The event counter can be reset by means of the Diagnostics function (code 08), with
subfunction 00 01 or 00 10 (decimal). See the Diagnostics section for more details.
The example below shows the query required to fetch the communications event counter in
slave 17 (11 hex).
FIELD NAME HEX. VALUE RTU
slave address 11 0001 0001
function 0B 0000 1011
error check - CRC
DATA & CONTROL FUNCTIONS
17
The normal response contains the slave address, an echo of the function code, a twobyte
status word, a twobyte event count and an error check. The status word will contain all ones
(FF FF hex) if a previously-issued program command is still being processed by the slave (a
busy condition exists). Otherwise, the status word will be all zeros.
A response to the query above might look like the following, where the status word - FF FF
hex - indicates that the slave is busy with another function. The event count shows that 264
(01 08 hex) events have been counted by the controller.
FIELD NAME HEX. VALUE RTU
slave address 11 0001 0001
function 06 0000 1011
status MSB FF 1111 1111
status LSB FF 1111 1111
event count data MSB 01 0000 0001
event count data LSB 08 0000 1000
error check - CRC
Fetch Communications Event Log (function 12)
This function requests that the slave return a status word, an event count, a message count
and a field of event bytes. Broadcast is not supported by this function.
The status word and event count are identical to that returned by the Fetch Communications
Event Counter (function 11).
The message counter contains the quantity of messages processed by the slave since its last
restart, clear counters operation or power-up. The count is identical to that returned by
diagnostic sub-function Return Bus Message Count (code 00 11).
The event bytes field contains 0 - 64 bytes, with each byte corresponding to the status of one
Modbus send or receive operation for the slave. The events are pushed into the data field as
they occur. At any time, byte 0 is the most recent event. When full, a new byte causes the
oldest byte to be flushed from the field.
The example below shows the query required to fetch the communications event counter in
slave 17 (11 hex).
FIELD NAME HEX. VALUE RTU
slave address 11 0001 0001
function 0B 0000 1011
error check - CRC
A response to this query might be:
FIELD NAME HEX. VALUE RTU
slave address 11 0001 0001
function 0C 0000 1100
number of data bytes returned 46 0100 0110
status MSB 00 0000 0000
status LSB 00 0000 0000
event count data MSB 01 0000 0001
event count data LSB 08 0000 1000
message count data MSB 01 0000 0001
message count data LSB 21 0010 0001
DATA & CONTROL FUNCTIONS
18
event 0 20 0010 0000
event 1 00 0000 0000
error check - CRC
In this example, the status word is 00 00 hex, indicating that the slave is not processing a
program function, The event counter shows that 264 (01 08 hex) events have been counted,
and the message count shows that 289 (01 21 hex) messages have been processed.
The most recent event is shown in the event 0 byte. Its contents (20 hex) show that it has
recently entered the Listen Only Mode. The previous event - event 1 - shows that the slave
received a Communications Restart (00 hex).
What Event Bytes Contain
The Modbus specification states that an event byte returned by the Fetch Communications
Event Log function can be one of the following four types:
Slave Modbus Receive Event
Slave Modbus Send Event
Slave Entered Listen Only Mode
Slave Initiated Communication Restart
The type is defined by bit 7 (the highest bit) in each byte. It may be further defined by bit 6,
as explained below.
Slave Modbus Receive Event
If a slave receives a query message, before processes the message it will store an event byte
to record its arrival. This event is defined by bit 7 being set to a logic 1. The other bits will
be set to a 1 if the corresponding condition is TRUE.
BIT MEANING
0 Not used
1 Communications Error
2 Not used
3 Not used
4 Character Overrun
5 Currently in Listen Only Mode
6 Broadcast Received
7 1 (by definition)
Slave Modbus Send Event
This type of event byte is stored by the slave when it finishes processing a query message. It is
stored whether the slave returns a normal response, an exception response or no response.
This event is defined by bit 7 being set to a logic 0, with bit 6 set to a 1. The other bits will
be set to a 1 if the corresponding condition is TRUE.
BIT MEANING
0 Read Exception Sent ( Exception Codes 1-3)
1 Slave Abort Exception Sent ( Exception Code 4)
2 Slave Busy Exception Sent ( Exception Codes 5-6)
3 Slave Program NAK Exception Sent ( Exception Code 7)
4 Write Timeout Error Occurred
5 Currently in Listen Only Mode
6 1 (by definition)
7 0 (by definition)
Slave Entered Listen Only Mode
This type of event byte is stored by the slave when it enters the Listen Only Mode. The event
is marked by the byte contents being set to 04 (hex).
BIT 7 6 5 4 3 2 1 0
CONTENTS 0 0 1 0 0 0 0 0
DATA & CONTROL FUNCTIONS
19
Slave Initiated Communication Restart
This type of event byte is stored by the slave when its communications port is restarted. The
slave can be restarted by the Diagnostics function (code 08), with sub-function Restart
Communications option (code 00 01).
When that function is used it also places the slave into a Continue on Error or Stop on Error
mode. If it is placed into a Continue on Error mode, the event byte is added to the existing
event log. If the slave is placed into a Stop on Error mode, the byte is added to the log and
the rest of the log is cleared to zeroes.
The event byte is marked by all the bits being set to zeroes.
Force Multiple Coils (function 15)
This function requests that the slave forces each coil in a sequence of coils to either ON or
OFF. When broadcast, the function forces the same coil references in all slaves.
The requested ON/OFF states are specified by the contents of the query data field. A logical
1 in a bit position of the field requests the corresponding coil to be ON. A logical 0
requests it to be OFF.
In addition to the slave address and the function number the query will contain the starting
coil number, the number of coils in the sequence and data on the individual states to which
they are to be forced.
The example below shows the request to force a series of ten coils, starting at coil 20
(addressed as 19, or 13 hex) in slave device 17. Two data bytes are required to cover the
settings for all ten coils: CD 01 hex (1100 1101 0000 0001 binary). The binary bits
correspond to the coils in the following way:
Bit 1 1 0 0 1 1 0 1 0 0 0 0 0 0 0 1
Coil 27 26 25 24 23 22 21 20 29 28
The first byte transmitted (CD hex) addresses coils 27 - 20, with the least significant bit
addressing the lowest coil (20) in the set. The next byte transmitted (01 hex) addresses coils
29 - 28, with the least significant bit addressing the lowest coil (28) in this set. Unused bits in
the data byte should be zero-filled.
FIELD NAME HEX. VALUE RTU
slave address 11 0001 0001
function 0F 0000 1111
coil address MSB 00 0000 0000
coil address LSB 13 0001 0011
number of coils MSB 00 0000 0000
number of coils LSB 0A 0000 1010
byte count 02 0000 0010
force data MSB CD 1100 1101
force data LSB 01 0000 0001
error check - CRC
The normal response returns the slave address, function code, starting address and number of
coils forced. A response to the above query might be:
FIELD NAME HEX. VALUE RTU
slave address 11 0001 0001
function 0F 0000 1111
coil address MSB 00 0000 0000
coil address LSB 13 0001 0011
number of coils MSB 00 0000 0000
number of coils LSB 0A 0000 1010
error check - CRC
DATA & CONTROL FUNCTIONS
20
Preset Multiple Registers (function 16)
This function requests that the slave writes specified data to a range of registers. The range of
registers to be written is identified by the master which indicates the location of the first
register and then the total number of registers to be written - including the first.
Note: The registers must be consecutive for this command to succeed. If the required
registers are not consecutive then multiple commands must be issued.
The example below shows the query required to pre-set or write two registers so that they
both contain the value FF FF. The first register location is 40003 of slave 1. Function 16 is
FIELD NAME HEX. VALUE RTU
slave address 01 0000 0001
function 10 0001 0000
register address MSB 00 0000 0000
register address LSB 02 0000 0010
register number MSB 00 0000 0000
register number LSB 02 0000 0010
byte count 04 0000 0100
1
st
pre-set data MSB FF 1111 1111
1
st
pre-set data LSB FF 1111 1111
2
nd
pre-set data MSB FF 1111 1111
2
nd
pre-set data LSB FF 1111 1111
error check - CRC
The normal response to a PRESET MULTIPLE REGISTERS query comprises the slave
address, an echo of the function code, echoes of the register address and the pre-set data,
and an error check.
A response to the query above would have the following format:
FIELD NAME HEX. VALUE RTU
slave address 01 0000 0001
function 10 0001 0000
register address MSB 00 0000 0000
register address LSB 02 0000 0010
register number MSB 00 0000 0000
register number LSB 02 0000 0010
error check - CRC
Report Slave ID (function 17)
The Report Slave ID function permits the user to obtain information on the slave type and
RUN status.
The query for slave address 1 would simply state the function code 17 (11hex):
FIELD NAME HEX. VALUE RTU
slave address 01 0000 0001
function 11 0001 0000
error check - CRC
A response to the query above would have the following format:
FIELD NAME HEX. VALUE RTU
slave address 01 0000 0001
function 10 0001 0000
number of data bytes returned 02 0000 0010
slave ID 01 0000 0001
run status FF 1111 1111
error check - CRC
DATA & CONTROL FUNCTIONS
21
The above response consists of a 2-byte reply which identifies a) the type of slave fitted
which will depend upon the equipment in use and b) the RUN status00 indicating false and
EXCEPTION RESPONSES
22
Exception Responses
If a slave receives a message correctly (i.e. it passes the error checking) but then finds it is
unable to perform the required operation will issue one of five available exception responses.
The following sections describe the construction of the exception responses in general, then
describes in more detail the ones that are implemented in some of the MTL8000 bus
interfaces..
Construction of exception responses
In a normal response, the slave exactly echoes the function code received from the master. In
an exception response the slave responds similarly, but with the MSB of the function code set
to '1'. The master can therefore identify that an exception response is being returned, and
identify the function code that was received by the slave. This is possible as there are less than
128 (or 80 hex.) function codes defined which, as binary 8-bit numbers, must always have a '0'
as their MSB.
The example below shows the first few bytes of an exception response issued after slave 9
correctly received a function code '01' that it was then unable to perform.
FIELD NAME HEX. VALUE RTU
slave address 09 0000 1001
function (as an exception for 01) 81 1000 0001
Further data is passed to the master via the first bytes of the response's data field. The bytes
returned are referred to as the 'exception code' and these are used to provide the master
with additional information regarding the nature of the exception.
The exception code that is generated by the slave for any particular event, can be determined
by the manufacturer of the device. It is normal, however, to try and use the exception codes
so that the code name is as near as possible, in meaning, to the event that has caused the
exception.
The example below shows the full exception response for the example used earlier - with the
reason for the exception being identified as exception code '02'. This is the 'ILLEGAL DATA
ADDRESS', which would typically be used if the master had requested the slave to read a
non-existent status location.
FIELD NAME HEX. VALUE RTU
slave address 09 0000 1001
function (as an exception for 01) 81 1000 0001
exception code 02 0000 0010
error check - CRC
Exception response types
Some or all of the following exception responses are supported by MTL8000 Series
equipment:
ILLEGAL FUNCTION response 01
ILLEGAL DATA ADDRESS response 02
ILLEGAL DATA VALUE response 03
SLAVE DEVICE FAILURE response 04
ACKNOWLEDGE response 05
SLAVE DEVICE BUSY response 06
NEGATIVE ACKNOWLEDGE response 07
Note that if a slave receives a message which does not pass the error checking employed, it
will discard the message and will not issue a response. This prevents it from carrying out
operations that have either not been translated correctly or which were intended for another
EXCEPTION RESPONSES
23
slave. The master employs a 'time-out' check, and if it has not received a response after a
given time period, it will re-try or take other appropriate action.
Illegal Function (exception code 01)
The ILLEGAL FUNCTION exception code is used to inform the master that the function
code received by the slave is not an allowable function for that particular slave.
An example of such a request would be the function code FORCE SINGLE COILS (function
05). If the master were to send a request containing such a function code, an exception code
'01' would be returned. The example below shows the exception response returned by such
a slave, with address '04' (hex):
FIELD NAME HEX. VALUE RTU
slave address 04 0000 0100
function (as an exception for 05) 85 1000 0101
exception code 01 0000 0000
error check - CRC
Illegal Data Address (exception code 02)
The ILLEGAL DATA ADDRESS exception code is used to inform the master that an address
used in the query is not available within the slave.
An example of such a request would be the function code READ INPUT REGISTERS ('04')
with the number of registers to be read given as 61. The slave has a communication buffer
that is only capable of containing sixty input registers, and a request to read more than this
number could not be handled by the unit. The example below shows the exception response
returned by such a slave, with address '09' (hex):
FIELD NAME HEX. VALUE RTU
slave address 09 0000 1001
function (as an exception for 04) 84 1000 0100
exception code 02 0000 0010
error check - CRC
Illegal Data Value (exception code 03)
The ILLEGAL DATA VALUE exception code is used to inform the master that a value used in
the query is not valid for the function requested form that slave.
An example of such a request would be the function code for DIAGNOSTICS with a
diagnostic sub-code of '01'. If the slave does not support this diagnostic code it would return
the exception code above. The example below shows the exception response returned by
such a slave, with address '06' (hex):
FIELD NAME HEX. VALUE RTU
slave address 06 0000 0110
function (as an exception for 08) 88 1000 1000
exception code 03 0000 0011
error check - CRC
Failure in subsystem (exception code 04)
The FAILURE IN SUBSYSTEM exception code is used when the slave is capable of
responding to the master but elements of it are not responding correctly. This is in
comparison to a slave that is incapable of responding whereupon the user might be given an
exception code 02 (Illegal Data Address) to indicate the effective absence of the slave.
An example of such a request would be the function code READ HOLDING REGISTERS
('03'). If the slave has corrupted configuration information, so that it is unable to respond, it
might return exception code 04 to indicate that it is still able to reply but is incapable of
providing the requested data.
EXCEPTION RESPONSES
24
The following example shows the exception response returned by such a slave, with address
'09' (hex):
FIELD NAME HEX. VALUE RTU
slave address 09 0000 1001
function (as an exception for 03) 83 1000 0100
exception code 04 0000 0100
error check - CRC
Acknowledge (exception code 05)
The ACKNOWLEDGE exception code is used to inform the master that the query has been
received correctly but a delay will be involved in responding as some processing is required to
produce a response. Further polling of the slave while in this condition will produce a rejected
message response - see exception code 06.
An example of such a request would be the function code READ INPUT REGISTERS ('04'). If
a large range of registers is required to be read then the response will be delayed. The
example below shows the exception response returned by such a slave, with address '11'
(hex):
FIELD NAME HEX. VALUE RTU
slave address 11 0001 0001
function (as an exception for 04) 84 1000 0100
exception code 05 0000 0100
error check - CRC
Slave Device Busy (exception code 06)
The SLAVE DEVICE BUSY exception code is used if the slave is involved in processing an
earlier command, or is otherwise occupied. It acknowledges to the master that the query has
been received but it is too busy to respond at present.
An example of such a request would be the function code FORCE SINGLE COIL ('05'). If a
large range of registers is required to be read then the response will be delayed. The
example below shows the exception response returned by such a slave, with address '17'
(hex):
FIELD NAME HEX. VALUE RTU
slave address 17 0001 0001
function (as an exception for 05) 85 1000 0100
exception code 06 0000 0100
error check - CRC
Negative Acknowledge (exception code 07)
The NEGATIVE ACKNOWLEDGE exception code is used to inform the master that the slave
cannot perform the requested function.
An example of such a failure would be attempting to write data in to a register that was 'write
disabled'. If the MODBUS master attempts to write in to such a register, then the exception
code '07' will be returned. The following table shows the exception code returned by such a
slave, with address 04.
FIELD NAME
HEX. VALUE
ASCII RTU
slave address 04 30 33 0000 0011
function (as an exception for 06) 86 38 36 1000 0110
exception code 07 30 37 0000 0111
error check - LRC CRC
MODBUS - PHYSICAL LAYER
25
The Modbus physical layer
The serial interface used by most Modbus masters is RS232C. This interface does not allow
the Modbus network to extend beyond 10 to 20 metres in length, hence, many
manufacturers use other serial interfaces that have longer network capabilities.
RS485 allows simple parallel connection of a number of units. As explained later the RS485
interface supports both 2 and 4 wire connection (plus common), and the latter allows use
with a RS422 host.
Note: when a non-RS232 interface is used with an RS232 master, a data converter must be
inserted in to the network.
The RS485 serial interface standard
The RS485 standard defines the characteristics of the drivers and receivers that are connected
to the bus. It does not define the cabling or connectors used, nor does it specify a particular
data rate or signal format.
RS485 employs differential signalling and therefore requires at least two connectors per signal
and a 'common' line connected between all devices.
RS485 specifies that the two differential signal lines should be marked 'A' and 'B', but this is not
always followed. Many are marked with '+' and '-', which describes the relative voltages of the
signalling lines in their quiescent state.
Note: With RS485, no damage will occur if the signalling lines are connected with the wrong
polarity - but the system will not operate.
RS485 effectively limits the number of addresses supported to 32 units (unless buffers are
used), which in Modbus corresponds to 31 slaves (with 1 master).
Terminations
RS485 interfaces should ideally be provided with a matched termination to prevent
reflections and 'ringing' of the signal on the bus cabling. The termination will normally be a
simple resistive terminator having an impedance that matches the characteristic of the bus -
typically 100. In practice, with low data rates and relatively short networks, it is often
unnecessary to terminate the bus.
Biasing
When no communication is taking place, the bus is in an undefined, floating state and noise on
the bus may be decoded as real characters. Well-written software should discard most of
these characters, but the system can be further protected by biasing the bus to a known state
and thereby reducing any noise that may be present.
2- and 4-wire interconnection
When using RS485, the user can select either two-wire or four-wire interconnection. The two
systems are shown below.
Figure 5 - 2 wire interconnection
MODBUS - PHYSICAL LAYER
26
Figure 6 - 4 wire interconnection
In simple terms, two-wire uses the same pair of wires to transmit queries from the master
and responses from the slave. With four-wire, queries are sent out on one pair of wires and
responses are returned on another set. Note, the nomenclature 'two-' and 'four-wire' ignores
the common wire, which is required to connect to all devices, but it is often not shown on
interconnection diagrams.
With some protocols, with the adoption of 'four-wire' interconnection, the system can be
made to run more quickly, by allowing simultaneous communication of commands and
responses. This is not possible with Modbus, as the 'Query-Response' cycle ensures that
simultaneous communication by both the master and the addressed slave can never occur.
When using Modbus, the decision to use 'two-' or 'four-wire' interconnection is generally
made according to the type of serial data interface that is made available on the host.
Point-to-point and multi-drop connection
Point-to-point and multi-drop are methods of forming the network link between the
master and its slave or slaves. Point-to-point describes the connection between a master and
a single slave, whereas multi-drop allows a number of slaves to be connected to one master.
Linear bus connection is a multi-drop technique for connecting a number of slaves to a single
master. The method is shown below.
Figure 7 - Linear bus connection
Note on RS422: the only direct connection method that is theoretically allowed when using
a Modbus host with an RS422 serial interface is point-to-point. The specification for RS422
indicates that it would be necessary to employ an RS422 to RS485 converter to connect more
than one Modbus slave. However, in practice, RS422 is found to perform well when RS485
slaves are linear bus connected to the RS422 host.
The theory maintains that since RS422 has no tri-state facility it cannot be connected to more
than one slave. However, since the Tx and Rx lines of the host are always ready to transmit to or
receive from a slave, there is no need for the host to adopt a tri-state mode. This then allows
linear BUS connection on an RS422 host with RS485 slaves.
Data converters
Most Modbus hosts will not provide an RS485 serial interface as standard, with RS232 and
RS422 being much more common. Apart from the possibilities of using RS422 as outlined
above, in many applications it will therefore be necessary to use a data converter to allow the
connection of the Modbus RS485 interface to the host's RS232 or RS422 interface.
CRC CALCULATION
27
Appendix - Calculation of the CRC in RTU mode
The Cyclical Redundancy Check (CRC) used for RTU transmission mode is 16-bits long and is
transmitted as two 8-bit bytes. It is calculated by the transmitting device and added to the
message. It is also calculated by the receiving device, from the contents of the message, and
then compared with the value contained in the message. If the two values are not equal, then
an error has occurred in either the transmission or the reception of the message.
The CRC is calculated by carrying out a process of exclusive OR operations. The first byte is
exclusive OR'ed with the value 1111 1111 1111 1111, and the result is used for any
subsequent exclusive OR operations that are required. Only the eight bits of the message data
are used for this operation. Start and stop bits and the parity bit - if one is selected - are not
included in this operation.
Once the first byte has been exclusive OR'ed with the register contents, the least significant
bit is removed, and the register contents are shifted towards the least significant bit position,
with a zero placed in to the vacant position of the most significant bit.
The least significant bit which is extracted is examined and, depending on it's value, one of
two operations is carried out. If the extracted LSB is a '1', the register is exclusive OR'ed with
the hex. value 'A0 01'. If the LSB is a '0', the register contents are left as they are and shifted
again. This shifting and extracting process is repeated until eight shifts have occurred.
The second data byte is exclusive OR'ed with the register contents and the process of shifting,
examining and exclusive OR'ing is repeated another eight times. This process continues until
all the data bytes have been through the operation. The resulting 16-bit CRC is transmitted as
two 8-bit bytes, with the high order bytes transmitted first.
Members of The MTL Instruments Group plc Printed in EU 02/99
The MTL Instruments Group plc
Measurement Technology Limited
Power Court, Luton, Bedfordshire
England LU1 3JJ
Tel: +44 (0)1582 723633 Fax: +44 (0)1582 422283
E-mail: enquiry@mtl-inst.com
MTL Incorporated
9 Merrill Industrial Drive, Hampton, NH 03842
USA
Tel: +1 800 835 7075, +1 603 926 0090 Fax: +1 603 926 1899
Or
8576 Wellington Road
Manassas VA 20109
USA
Tel: +1 703 361 0111 Fax: +1 703 368 1029
E-mail: info@mtlnh.com
MTL Canada Safety Instrumentation
20 Regan Road, Unit 17
Brampton, Ontario L7A 1C3
Canada
Tel: +1 905 840 7850 Fax: +1 905 840 7852
E-mail: cinfo@mtlnh.com
MTL Instruments Limited
MTL Systems Pvt Limited
No.3 Old Mahabalipuram Road
Sholinganallur, Chennai (Madras) 600119
India
Tel: +91 (0)44 496 0552 Telefax: +91 (0)44 496 0477 Fax: +91 (0)44 496 1657
E-mail: mds.engg@mtlindia.sprintrpg.ems.vsnl.net.in
MTL Instruments Pty Limited
9 Vinnicombe Drive
PO Box 1441, Canning Vale
Western Australia 6155
Tel: +61 (0)8 9455 2994 Fax: +61 (0)8 9455 2805
E-mail: enquiry@mtlaus.com.au
MTL Instruments Pte Limited
150 Kampong Ampat
#06-01 KA Centre
Singapore 368324
Tel: +65 487 7887 Fax: +65 487 7997
E-mail: sales@mtlsing.com.sg
MTL Instruments KK
10th Floor, Takanawa Meiko Building
2-15-19 Takanawa, Minato-ku, Tokyo 108
Tel: +81 (0)3 5420 1281 Fax: +81 (0)3 5420 2405
E-mail: sales@mtlkk.co.jp
MTL Instruments GmbH
Hellersbergstrasse 2, D-41460 Neuss
Germany
Tel: +49 (0)2131 168016 Fax: +49 (0)2131 168652
E-mail: info@mtl.de
MTL Instruments sarl
Btiment SILIC 4, 1 rue des Vergers, 69760 Limonest
France
Tel: +33 (0)4 78 64 98 32 Fax: +33 (0)4 78 35 79 41
E-mail: info@mtl-inst.fr
MTL Instruments BV
MTL Systems BV
de Houtakker 33, 6681 CW Bemmel, The Netherlands
Tel: +31 (0)48 1450250 Fax: +31 (0)48 1450260
E-mail: info@mtlbenelux.com
MTL Instruments BVBA
Derbystraat 379 Blok G
9051 Sint-Denijs-Westrem, Gent
Belgium
Tel: +32 (0)9 242 8844 Fax: +32 (0)9 242 8868
E-mail: info@mtlbenelux.com
Group web site: http://www.mtl-inst.com

You might also like