Eriteh v0
Eriteh v0
Eriteh v0
Founded in 1903 as the Electric Railway Improvement Company, ERICO developed the CADWELD exothermic welding process in 1938. CADWELD connections have found industry-wide acceptance as the ultimate grounding and bonding connection. During the 1970s, ERICO pioneered the copper-bonded steel ground rod electrode. Today, ERICOs range of facility electrical protection products includes ERITECH ground rods, clamps, grounding and bonding assemblies, ground enhancement material, ground testers, structural lightning protection, equipotential mesh and mats, and signal reference grids; low-voltage TVSS devices; and CADWELD exothermic connections. Facility Electrical Protection Lightning protection, grounding, equipotential bonding and surge protection are all interdependent disciplines and the focus of our Facility Electrical Protection product line. Reliable protection of personnel and structures demands a systematic and comprehensive approach to minimising threats caused by transients and other system disturbances. For instance, no air terminal can safely capture and arrest the lightning energy without a dependable route to ground. Equally, even the most expensive Surge Protection Device (SPD) will not provide optimum protection if a low-impedance electrical connection to the ground is not present. Additionally, a lowimpedance ground system may create hazards to equipment and personnel alike if equipotential bonding is not in place. These interdependent disciplines are best applied when looking at a total facility rather than an individual piece of equipment or a portion of the facility. Since no single technology can eliminate the harmful effects of lightning or induced-surge transients, ERICO has developed the Six Point Plan of Protection. The concept behind this plan is a holistic and coordinated approach that embraces all aspects of effective facility electrical protection. The six interdependent disciplines that form the protection plan are: 1. Capture the lightning strike 2. Convey this energy to ground 3. Dissipate energy into the grounding system 4. Bond all ground points together 5. Protect incoming AC power feeders 6. Protect low voltage data/telecommunications circuits
At ERICO, we offer innovative, efficient grounding and bonding products as well as engineering experience and technical support. With this experience, ERICO is a world-leading authority in the design and construction of permanent, low-impedance grounding systems. ERICO employs a quality-assurance program to help ensure that detailed procedures required for every step of the operation produce the best possible system for our clients. This attention to detail includes design, materials procurement, manufacturing, installation and testing.
Our research and development capabilities provide continuous design improvement with new and improved products that preempt the challenging requirements of everevolving industry applications. Engineering expertise is shared among the other ERICO operations worldwide, to provide a comprehensive global knowledge pool. Trust ERICO for all of your facility electrical protection needs.
www.erico.com
Table of Contents
Technical Information ..................................................................................Pages 4-16 Lightning Protection ..................................................................................Pages 17-29 Conductors ........................................................................................................Pages 30-32 Grounding and Bonding ..........................................................................Pages 33-43 Surge Protection ............................................................................................Pages 44-46 CADWELD/CADWELD PLUS/CADWELD MULTI ..................Pages 47-57 Index ......................................................................................................................Pages 58-59
www.erico.com
CATALOGUE OVERVIEW
LIGHTNING PROTECTION Point 1 - Capture the
lightning strike
PAGES 17 TO 19
PAGES 21 TO 22
PAGES 23 TO 26
PAGES 28 TO 30 PAGES 31 TO 37
2
PAGES 38 TO 41
www.erico.com
CATALOGUE OVERVIEW
1 Capture the lightning strike. Capture the light2 Convey this energy to ground. Conduct the 3
ning strike to a known and preferred attachment point using a purpose-designed air terminal system.
help eliminate ground loops and create an equipotential plane. surges and transients on incoming power lines to help prevent equipment damage and costly operational downtime. Protect low voltage data/telecommunications circuits. Protect equipment from surges and transients on incoming telecommunications and signal lines to help prevent equipment damage and costly operational downtime.
CADWELD PLUS
PAGES 46 TO 48
CADWELD
PAGES 50 TO 56
CADWELD MULTI
PAGES 43 TO 44
www.erico.com
PAGES 43 TO 44
3
PAGE 49
CADWELD
SURGE PROTECTION
CONDUCTORS
LIGHTNING PROTECTION
energy to the ground via a purpose-designed downconductor. Dissipate energy into the grounding system. Dissipate energy into a low impedance grounding system.
TECHNICAL INFORMATION
TECHNICAL INFORMATION
TECHNICAL INFORMATION
ERITECH SYSTEM 3000 PROTECTION OF STRUCTURES AGAINST LIGHTNING
There are 2 types of devices for the protection of structures against lightning: the conventional one, based only on passive components (copper, galvanized steel...), and the active protection system, The latter being based on advanced knowledge and more than 15 years of experience.
AIR TERMINAL
THE ERITECH DYNASPHERE ENHANCED AIR TERMINAL
The patented ERITECH DYNASPHERE is an enhanced air terminal. Non radioactive Not externally powered Has no moving parts Responds dynamically to the approach of a lightning downleader.
ACTIVE PROTECTION
WHAT IS THE SYSTEM?
The ERITECH SYSTEM 3000 is a technically advanced lightningprotection system. The unique features of this system allow the achievement of superior technical performance and hence provide more reliable lightning capture. The ERITECH DYNASPHERE air terminal provides a preferred point for lightning discharges which would otherwise strike and damage an unprotected structure and/or its contents. The ERITECH DYNASPHERE is connected to an ERITECH ERICORE downconductor and the ground system in such a way as to provide a totally integrated system.
PROTECTION LEVEL
Lightning is a statistical phenomena where 100% protection is virtually impossible to achieve, and certainly, is not economically practical. IEC 62305-3 defines 4 protection levels together with associated interception efficiencies. This information is used to determine the appropriate air terminal location and spacing. LEVEL I LEVEL II LEVEL III LEVEL IV 99% 97% 91% 84% Very high risk structures High risk structures Medium risk structures Low risk structures, e.g. Residential
TECHNICAL INFORMATION
PLASTIC FILLER TO INCREASE EFFECTIVE DIAMETER OF CORE CONDUCTOR (Inductance-Skin effect) MAIN CONDUCTOR COPPER TAPE SEMI-CONDUCTIVE STRESS CONTROL LAYER POLYETHYLENE H.V. INSULATION SEMI-CONDUCTIVE STRESS CONTROL LAYER MAIN COPPER TAPE SCREEN SEMI-CONDUCTIVE OUTER SHEATH
Faraday cage
www.erico.com
TECHNICAL INFORMATION
TECHNICAL INFORMATION
TECHNICAL INFORMATION
For the efficient performance of a lightning protection system, it is essential that a low impedance ground be provided to facilitate the dissipation of the lightning energy into the earth mass. Because soil conditions and seasonal patterns vary from site to site, the methods of grounding need to be considered on an individual basis.
Polymeric Cover CADWELD PLUS Package Graphite Mould Tap Hole Conductor Weld Cavity Ignitor Strip
CRUCIBLE
STARTING POWDER
WELD CAVITY
CONDUCTOR CONDUCTOR
www.erico.com
TECHNICAL INFORMATION
GROUND ELECTRODES
The ground electrode is a critical component of the grounding system. Many different types of electrodes are available, some "natural" and some "made. The natural types include metal underground water pipe, the metal frame of a building (if effectively grounded), a copper wire or reinforcing bar in a concrete foundation or underground structures or systems. Consideration should be given to bonding of natural earths to ensure electrical continuity with a facilities other "earths". "Made" electrodes are specifically installed to improve the system grounding or earthing. These earth electrodes must ideally penetrate into the moisture level below the ground level to reduce resistance. They must also consist of metal conductors (or a combination of metal conductor types), which do not corrode excessively for the period of time they are expected to serve. Made electrodes include rods or pipes driven into the earth, metallic plates buried in the earth or a copper wire ring encircling the structure. Underground gas piping or aluminium electrodes are NOT permitted for use as ground electrodes.
GROUND RODS
Which ground rod should be used?
Ground rods are often selected on the basis of their resistance to corrosion. The other major factor is cost. All too often, the cost of a product is seen as the initial up front price, but the real cost is determined by the serviceable life of the ground rod. Galvanised steel rods are one of the cheapest electrodes available. However, they are not the most cost effective since they have a relatively short service life. Solid copper and stainless steel rods have a long service life. However, they are considerably more expensive than galvanised steel rods. In addition to this, solid copper rods are not suited to deep driving or even driving short lengths into hard ground, without bending. As a compromise, steel cored ground rods, swaged in a copper or stainless steel sheath were developed. These ground rods are much less expensive than their solid counterparts. They are capable of being deep driven. However, the sheath of this rod type has been known to slip or tear, particularly the copper version. Once this sheath has been damaged, the integrity of the entire electrode is at risk. Ask for the ERICO White Paper on Ground Rods Copper-bonded vs. Galvanised.
Cost effective long service life Copper-bonded coating: Permanent molecular bond Low resistance performance High fault current capacity (IEEE Std 80) Will not slip or tear when driven Will not crack if rod is bent Carbon Steel core and tip: Greater tensile strength Deep driving capability
Galvanised coating: Relatively short service life May crack if rod is bent Steel core and tip: High tensile strength Deep driving capability
www.erico.com
TECHNICAL INFORMATION
TECHNICAL INFORMATION
TECHNICAL INFORMATION
GROUND ELECTRODES
The copper-bonded ground rod has an electrolytic coating of copper deposited over a layer of nickel. This process ensures a long lasting, molecular bond between the copper layer and the steel core. ERICO recommends copperbonded ground rods because the copper coating will not slip or tear when driven nor will it crack if the rod is bent. The tough, carbon steel core has good characteristics for deep driving. Copper-bonded ground rods have a high resistance to corrosion and provide a low resistance path to ground.
Above photo shows two ground rods subjected to the same pressure load test. The ERITECH copper-bonded ground rod, shown on the left, will bend without tears, cracks or folds, to the outer sheath. The inferior copperclad rod shown on the right, has developed cracks and creases to the outer sheath, which will significantly reduce its serviceable life and put the integrity of the entire electrode at risk.
COMPARATIVE COST
YEARS
Ga lva Zin nis c ed Ste C el opp (10 er mi -bo l/2 nd 54 ed m Ste C ) el opp (13 er mi -bo l/3 nd 30 ed m )
Ga lva Zin nis c ed Ste C el opp (10 er mi -bo l/2 nd 54 ed m Ste C ) el opp (13 er mi -bo l/3 nd 30 ed m )
www.erico.com
TECHNICAL INFORMATION
WHY IS GOOD GROUNDING IMPORTANT ?
The transient nature of lightning with its associated fast rise times and large magnitude currents mean that special consideration needs to be given to grounding, for lightning protection to be effective. Many factors such as soil resistivity variations, installation accessibility, layout and existing physical features are all site specific and tend to affect decisions on grounding methods employed. The primary aim of a direct strike grounding system is to: Efficiently dissipate lightning surge energy into the ground Help ensure safety of equipment and personnel Fig.1-A
Distance from the electrode
Earth Rod
GROUNDING PRINCIPLES
Low impedance is the key to lightning protection. All grounding connections should be as short and direct as possible to minimise inductance and reduce peak voltages induced in the connections. The ground electrode system must efficiently couple lightning surges into the ground by maximising capacitive coupling to the soil. The resistance of the ground itself to lightning currents must also be minimised. Only when all these factors are taken into account will maximum lightning protection be achieved.
Fig.1-B
GROUND IMPEDANCE
Soil resistivity is an important design consideration. It varies markedly for different soil types, moisture content and temperatures and gives rise to variations in ground impedances. Figure 1-B illustrates current flow from the injection point of a single ground electrode. As current flows out from the central injection point, a voltage gradient on the ground surface around the electrode is produced. This gradient levels off to a plateau at some distance from the electrode, as seen in Figure 1-A. The impedance seen by the current is determined by the soil particles in direct contact with the surface of the rod, and by the general impedance of the soil.
www.erico.com
TECHNICAL INFORMATION
TECHNICAL INFORMATION
TECHNICAL INFORMATION
COMPONENTS OF A GROUNDING SYSTEM
A grounding system for lightning protection serves to deliver the lightning current into ground. It consists of one or more ground electrodes (earthing rods) along with any interconnecting conductors. Components include: Ground rods Ground enhancing materials CADWELD exothermic welded connections Ground connectors tapes, stranded cables, rod clamps, mesh, plates etc Ground pits - for access to the ground system Figure 2
DIFFERENCE OF POTENTIAL WITHOUT PROTECTION WITHOUT PROTECTION
Step and Touch Potential. Step potential is the voltage difference between a persons feet caused by the dissipation gradient of a fault entering the earth. Touch potential is similar to step potential except that the fault current passes through the persons arm and torso on the way to the ground.
IEC/EN 62305-3, EN 50164 Series, EN 60364-54, NFC 17-102 NFPA 780, IEEE STD80, IEEE 837, NFPA 70 AS1768
Reducing ground impedance Resistivity of the soil varies markedly for different soil types, moisture content and temperatures, and this gives rise to variations in ground system impedance. The lower the resistivity, the easier it is to achieve an effective grounding system. Measures that can be used for reducing earth impedance include: Connecting additional buried conductors to the ground electrode Use of multiple interconnected ground electrodes Use of flat tape rather than circular conductors Use of spaced conductors connected in parallel Use of equipotential mesh electrodes Use of multiple short interconnected buried conductor Use of ground enhancing compounds Electrically conductive ground enhancing compounds can be applied to help lower ground resistance and impedance. They are particularly useful for rocky ground, areas of moisture variation and sandy soils. These compounds are generally applied around electrodes in oversized drill holes and around horizontal buried conductors. Use of mineral or chemical ground rods Mineral or chemical ground rods are also used to decrease ground impedance. These consist of a perforated hollow copper tube sealed at the bottom. A salt compound is placed inside the tube which gradually leaches out to maintain a conductive environment around the electrode. Use of concrete slabs or footings The use of reinforced concrete slabs and footings is one of the most effective ways to provide a low impedance ground electrode system. If addressed at the design stage this method can provide a very stable, permanent distributed ground electrode system at very little additional cost to the civil works.
Other factors to consider include: The needs and layout of the facility (location and space confinement issues) The ground environment of the facility itself (eg soil resistivity) Existing grounding systems Susceptibility to seasonal variations in soil moisture content and temperature Exposure to pedestrian traffic Step and Touch Potentials While it is clear that a low impedance grounding system will allow the lightning surge energy to be dissipated into the ground, this will not necessarily minimise hazards to personnel in close proximity to the grounding system. High voltage gradients on the surface of the ground give rise to undesirable step and touch potential hazards. In order to reduce the chance of injury to personnel, both step and touch potentials must be minimised. Figure 2 graphically illustrates the danger of such potentials. Selecting the right connections The connections between the conductors and the main grid, and between the grid and ground rods, are as important as the conductors themselves in maintaining a permanent low-resistance path to ground.
10
www.erico.com
TECHNICAL INFORMATION
GROUND POTENTIAL EQUALISATION
Creating an equipotential earth plane under transient conditions is essential for equipment and personnel safety. However, separate earths are sometimes installed for lightning, mains power, computer and communications equipment in buildings and other installations. Although this may be desirable under normal operating conditions, when lightning or other transient voltages occur, potential differences between the separate earths are inevitable. These can enter buildings, destroying equipment and creating dangers for personnel. The PEC (Potential Equalization Clamp) usually operates as an effective open circuit. However, once the earth potential difference exceeds the breakdown voltage of the PEC (under transient conditions), the circuit closes immediately and the earth potentials are equalised, thereby protecting equipment and people.
MAINS POWER EARTH WIRE LIGHTNING DOWNCONDUCTOR
Estimated linear feet of ground conductor covering with each bag of GEM
Total thickness of GEM
Trench Width
EARTH PIT
2, 5 cm (1) 4.3 m (14.0) 2.8 m (9.3) 2.1 m (7.0) 1.7 m (5.6) 1.4 m (4.7)
5, 1 cm (2) 2.1 m (7.0) 1.4 m (4.7) 1.1 m (3.5) 0.9 m (2.8) 0.7 m (2.3)
7, 6 cm (3) 1.4 m (4.7) 0.9 m (3.1) 0.7 m (2.3) 0.6 m (1.9) 0.5 m (1.6)
10, 2 cm (4) 1.1 m (3.5) 0.7 m (2.3) 0.5 m (1.8) 0.4 m (1.4) 0.4 m (1.2)
10 cm 15 cm 20 cm
25 cm (10) 30 cm (12)
TELECOM EARTH MAINS EARTH LP EARTH
Equipotential earth plane created by bonding all earths together with Potential Equalization Clamps (PEC).
Estimated bags of GEM for backfilling around ground rods to a density of 90 lb/cu ft (1442 kg/m3)
Depth of hole (Feet) *
Appropriate depth and separation of electrodes The length, number and placement of ground rods affects the resistivity of the path to ground. The most cost-effective depth to which an electrode should be driven is usually dependent on specific soil conditions. Soils are rarely homogeneous or uniform and it may be advantageous to install electrodes to a particular depth where a low resistivity soil layer, such as a clay base, is encountered. Electrode depths commonly used are in the range of 1 to 4 m. Electrodes should be separated by a distance of at least twice the depth to which they are installed. Equipotential Bonding Potential equalisation ensures that any potential rise due to the injection of lightning current into the impedance of the grounding network, is experienced by all the conductive services in the building. Thus everything rises in potential together and hazardous potential differences are avoided.
Dia. of hole
7.5 cm 10.0 cm 12.5 cm 15.0 cm 17.5 cm 20.0 cm 22.5 cm 25.0 cm (3) (4) (5) (6) (7) (8) (9) (10)
1.8 m 2.1 m 2.4 m 2.7 m 5.2 m 5.8 m 6.1 m (6) (7) (8) (9) (17) (19) (20) 2 2 3 5 6 8 10 12 2 3 4 5 7 9 12 14 2 3 4 6 8 11 13 16 2 3 5 7 9 12 15 18 4 6 9 13 17 22 28 34 4 7 10 14 19 25 31 38 4 7 10 15 20 26 32 40
www.erico.com
11
TECHNICAL INFORMATION
TECHNICAL INFORMATION
TECHNICAL INFORMATION
PROTECTION FROM POWER SURGES
To meet the fundamental requirements of performance, longer service life and greater safety under real world conditions, ERICO has developed a range of technologies covering all aspects of the Six Point Plan of Protection. In the field of surge protection, several technologies play a critical role in the provision of premium performance. The DINLINE Product range offers both shunt or series protection utilising differing technologies in compact DIN rail mounted products. A number of different options are available to suit your individual application or performance requirements.
Data Line Protectors (DLP) / Data Equipment Protectors (DEP) / Local Area Network Protectors (LAN) - Range of connections types available, from DB to RJ45 and KRONE - Wide range of operating voltages and frequencies available - Surge Ratings from 500A to 20kA depending on product and application
12
www.erico.com
TECHNICAL INFORMATION
Transient Discriminating Technology
To meet the fundamental requirements of performance, longer service life and greater safety under real world conditions, ERICO has developed Transient Discriminating (TD) Technology. This quantum leap in technology adds a level of intelligence to the Surge Protection Device enabling it to discriminate between sustained abnormal over-voltage conditions and true transient or surge events. Not only does this help ensure safe operation under practical application, but it also prolongs the life of the protector since permanent disconnects are not required as a means of achieving internal over-voltage protection. which is associated with lightning or switching-induced surges. When the transient frequencies are detected, the patented Quick-Switch within TD activates to allow the robust protection to limit the incoming transient. The frequency discriminating circuit that controls the Quick-Switch helps ensure that the SPD device is immune to the effects of a sustained 50 or 60Hz TOV. This allows the device to keep operating, in order to help provide safe and reliable transient protection, even after an abnormal over-voltage condition has occurred.
TRADITIONAL TECHNOLOGIES
Conventional SPD technologies utilize metal oxide varistors and/or silicon avalanche diodes to clamp or limit transient events. However, these devices are susceptible to sustained 50/60Hz mains over-voltage conditions which often occur during faults to the utility system. Such occurrences present a significant safety hazard when the suppression device attempts to clamp the peak of each half cycle on the mains over-voltage. This condition can cause the device to rapidly accumulate heat and in turn fail with the possibility of inducing a fire hazard.
TD TECHNOLOGY PROVIDES CONTINUED PROTECTION EVEN AFTER OVER-VOLTAGES Typical Supply Problems
1. Transient Impluse 2. Substantial Over-voltage 1. Transient Impluse
Clamping threshold
TD Technology Solution
1. D circu iscrimina tran it detec ting s Quic ient an ts d operak Switch ping ting cla m tran sien t 2. P rote not ction d a clam ttempt oes volta p supply to ge 3. Pro te work ction sti clam ing and ll ps tr ansie nt
www.erico.com
13
2. O vershold voltage tecti exceed threclam on attem ed, pro to lo p, overh pts to fails ng expo eats du e sure and
TECHNICAL INFORMATION
TECHNICAL INFORMATION
TECHNICAL INFORMATION
CADWELD /CADWELD PLUS THE MOLECULAR BOND
CADWELD EXOTHERMIC CONNECTION A welding process that eliminates the connection by forming a molecular bond.
Connections are the weak point of all electrical circuits and especially earthing circuits subjected to ageing and corrosion. The capacity of an earthing circuit to protect the safety of personnel depends on the quality of the connections made.
Weld Cavity
Installation Is Easy!
4 Simple Steps For Permanently Welded Electrical Connections
CADWELD PLUS Control Unit initiates the reaction of the metal crucible. The standard unit includes a 6-foot (1.8 meter) high temperature control unit lead. The lead attaches to the ignition strip using a custom made, purpose-designed termination clip. After the termination clip is installed on the ignition strip, the installer pushes and holds the ignition button to start a charging and discharging sequence. Within a few seconds the control unit sends a predetermined voltage to the ignition strip and the reaction is initiated. Insert CADWELD PLUS package into mould Attach control unit termination clip to ignition strip
Press and hold control unit switch and wait for the ignition
Open the mould and remove the expended steel cup no special disposal required www.erico.com
14
TECHNICAL INFORMATION
THE CADWELD WELD
Will carry more current than the conductor. Will not deteriorate with age. Is a molecular bond that eliminates any risk of loosening or corrosion. Will resist repeated fault currents. Can be quality controlled simply by visual inspection.
RELIABILITY
As the molecular bond eliminates the concept of surface contact, an electrolyte cannot penetrate between the conductors and cause oxidation and deterioration in the course of time.
CORROSIVE ENVIRONMENTS
This reliability is of particular interest for humid or chemical environments or for bonds directly buried in the ground.
CORROSION TEST
This accelerated ageing test, carried out in a saline atmosphere at a controlled temperature, demonstrates that CADWELD welds retain all their electrical properties during the period of the test whereas the resistance of mechanical connections increase with time and this alters their conductive properties. CADWELD'S fine performance is due to its reliability resulting from the molecular bond. Comparison between CADWELD Bonded Connection and Mechanical Connection CADWELD Weld (Metal A) (Metal B). The CADWELD bonded connection provides permanent conductivity over the whole of the section due to molecular bonding between the metal surfaces.
RELATIVE RESISTANCE
MECHANICAL 2 SAMPLES
CONDUCTIVITY
The CADWELD connections form a solid bond around the conductors assuring continuity. The cross sectional area of the weld has greater current carrying capacity than the conductors.
PERFORMANCE
Standard CADWELD welds have a cross section greater than that of the conductors to be joined, which compensates for the difference in resistivity between the conductor and the weld material. Consequently, under fault conditions the weld will always remain cooler than the conductor. If special applications do not allow for the required increase in cross section to be employed, the use of the formula: R = p x l and V= R x l S will make it possible to define precisely the resistance of the CADWELD weld. Comparison between CADWELD Bonded Connection and Mechanical Connection
CADWELD WELD
(Metal A)
(Metal B)
The CADWELD bonded connection provides permanent conductivity over the whole of the section due to molecular bonding between the metal surfaces.
The mechanical connection presents a significant difference between the apparent contact surface and the actual surface.
www.erico.com
15
TECHNICAL INFORMATION
TECHNICAL INFORMATION
TECHNICAL INFORMATION
Nominal Wire Size CADWELD Number Nominal Nominal Nominal Nominal Cross Mould Reference of Strands Diameter of Cable Cable Strand AWG Sectional Strands Diameter Diameter Area Area (mm2) (mm) (mm) (inch) (mm2) #10 1B 7 0.98 2.95 0.12 0.75 6 A7 7 1.04 3.12 0.12 0.85 #8 1E 7 1.23 3.71 0.15 1.19 10 W2 7 1.35 4.05 0.16 1.43 #6 1H 7 1.55 4.67 0.18 1.89 16 W3 7 1.70 5.10 0.20 2.27 #4 1L 7 1.96 5.89 0.23 3.02 25 Y1 7 2.14 6.42 0.25 3.60 #3 1Q 7 2.20 6.60 0.26 3.80 25 Y1 19 1.35 6.75 0.27 1.43 #2 1V 7 2.47 7.42 0.29 4.79 #2 Solid 1T 1 6.54 6.54 0.26 33.62 35 Y2 19 1.53 7.65 0.30 1.84 #1 1Y 19 1.50 8.43 0.33 1.77 #1 Solid 1X 1 7.35 7.35 0.29 42.41 50 Y3 19 1.78 8.90 0.35 2.49 1/0 Solid 2B 1 8.25 8.25 0.32 53.49 1/0 2C 19 1.89 9.46 0.07 2.81 2/0 Solid 2F 1 9.27 9.27 0.36 67.43 2/0 2G 19 2.13 10.65 0.42 3.56 70 Y4 19 2.14 10.70 0.42 3.60 95 Y5 37 1.78 12.46 0.49 2.49 95 Y5 19 2.52 12.60 0.50 4.99 3/0 2L 19 2.59 12.95 0.47 5.27 4/0 Solid 2P 1 11.68 11.68 0.46 107.22 4/0 2Q 19 2.89 13.41 0.53 6.56 120 Y6 37 2.03 14.21 0.56 3.24 250 KCM 2V 37 2.07 14.61 0.58 3.37 150 Y7 37 2.25 15.75 0.62 3.98 300 KCM 3A 37 2.29 16.00 0.63 4.12 350 KCM 3D 37 2.47 17.30 0.68 4.79 185 Y8 37 2.52 17.64 0.69 4.99 400 KCM 3H 37 2.64 18.49 0.73 5.47 240 Y9 61 2.25 20.25 0.80 3.98 500 KCM 3Q 61 2.30 20.65 0.81 4.15 300 Y0 61 2.52 22.68 0.89 4.99 Nominal Wire Cross Sectional Area (mm2) 5.26 5.95 8.32 10.02 13.21 15.89 21.12 25.18 26.61 27.20 33.54 33.62 34.93 33.58 42.41 47.28 53.49 53.43 67.43 67.70 68.34 92.07 94.76 100.10 107.22 124.63 119.75 124.52 147.11 152.39 177.29 184.54 202.53 242.54 253.44 304.24
KCM was previously MCM, ie 1000 circular mils, a measure of the wire cross-sectional area. Note that KCM "overstates" the true cross sectional area (measured in sq. mils) of a conductor by 4/ (i.e. 1.273) 1 mil = 0.001 inch Square Inches x 1273 = KCM Square Millimeters x 1.974 = KCM KCM x 0.5607 = Square Millimeters
16
www.erico.com
The ERITECH SYSTEM 3000 is a technically advanced lightning protection system. The unique Collection Volume Method design (CVM), and features of this system allow the achievement of superior technical performance, and hence more reliable lightning capture. The ERITECH DYNASPHERE air terminal provides a preferred point for lightning discharges which would otherwise strike and damage an unprotected structure and/or its contents. The ERITECH DYNASPHERE is connected to a single insulated downconductor (ERITECH ERICORE) and the ground system in such a way as to provide a totally integrated system.
The ERITECH SYSTEM 1000 SI Interceptor terminal is designed and tested to the French Standard NFC17-102 and Spanish norm UNE-21186. The standards provide simple placement rules and determination of the protected area. The terminals are erected with conductive masts and connected to the ground with two downconductors running on opposite walls.
www.erico.com
17
LIGHTNING PROTECTION
ERITECH SYSTEM 3000
ERITECH DYNASPHERE AIR TERMINAL
702085 702089
70 mm
INLINE COUPLING
LIGHTNING PROTECTION
ALUMINIUM MASTS
68 mm
60 mm
Unit weight kg 1,2 per meter Unit weight kg 1 1 1 1,5 1,5 1,5
Terminations
m 5m 22
225 mm
Factory Upper Termination, outside drum Factory Upper Termination, inside drum Lower Termination
Reference code
Aluminium
INSULATED MASTS
MAST BRACKETS
69,9 mm 61,9 mm
702065
701460
r=38 87 mm
10 mm
90 mm
31 mm 213 mm 195 mm
Fiberglass reinforced
18
www.erico.com
LIGHTNING PROTECTION
ERITECH DYNASPHERE/ERITECH INTERCEPTOR SI ADAPTORS
101925 701840 702296
Reference code
Part No.
Description Adaptor to fix ARC to ER1-xxx-SS* For bare downconductor For SI terminal to FRP SI terminal to 2 pipe. British thread SI terminal to 2 pipe. USA thread SI terminal to 3/4 pipe. USA thread SI terminal to ER2-xxxx-SS* 16mm Conventional Rod to ER2-xxxx-SS* 1 1 1 1 1 1 1 1
ER1-ARCC-SS 101925 THERMLUGCOUPL 701840 INTCPT-ADBUTT INTCPT-ADF2BSPF INTCPT-ADF2NSP 702296 702297 702298
Unit weight kg 2
Unit weight kg 3 3 3
GUY RING
Reference code
Aluminium
in 60
mm
out 91 1
GUYRING
ER3-BASE
GUY KIT
ER2-BASE
Reference code ER1-1000-SS ER1-2000-SS ER2-2000-SS ER2-3000-SS ER2-BASE ER3-2000-SS ER3-3000-SS ER3-BASE
Part No. 702255 702260 702265 702270 702290 702275 702280 702295
Description Upper Section, 1m Upper Section, 2m Mid Section, 2m Mid Section, 3m Base for ER2 mast Lower Section, 2m Lower Section, 3m Base for ER3 mast 1 1 1 1 1 1 1 1
Unit weight kg 3,5 6,2 4,9 7,3 5,2 5,3 7,9 5,6
Stainless Steel
1 1
www.erico.com
19
LIGHTNING PROTECTION
LIGHTNING PROTECTION
Air terminal
What is the ERITECH Isolated Downconductor system? The ERITECH isolated system provides a traditional air terminal fitted to an isolated fiberglass reinforced plastic (FRP) mast. The isolated downconductor internally connects to the air terminal inside the FRP. The FRP mast has natural isolation properties, high strength for windy sites and low weight to minimise mast loading.
Isolated downconductor
Stainless steel connector to conventional lightning protection or grounding system ERITECH Isolated Downconductor ERITECH Isolated System
20
www.erico.com
0.1 kg
MULTIPURPOSE CLAMP CCS-308 (#545170) Stainless Steel Clamp 0.15 kg For connection of lower termination to 25x3 mm, 30x2 mm or 8-10 mm diameter lightning protection or grounding systems.
LIGHTNING EVENT COUNTER LEC-IV (#702050) Lightning Event Counter 2.0 kg Installed upon downconductor to record number of lightning strikes.
ISOLATED MAST BRACKET ISOMMB50 (#702088) 0.4 kg For mounting ISOFRP3M. Use 20 mm stainless steel Fixoband to allow mounting on virtually any mast type/diameter.
MAST BRACKET ALOF-1-GS (#702175) 1.5 kg Galvanised mast bracket providing 190 mm offset. ACF-2-GS (#103100) 2.1 kg Galvanised x mast bracket
ISOLATED DOWNCONDUCTOR ISODC 0.58 kg/m Supplied with factory upper termination fitted and materials for customer lower termination. Order required length in meters.
DUAL DOWNCONDUCTOR ADAPTOR ISODUAL (#702094) 0.2 kg For connecting second parallel ISODC for increased safety distance.
CABLE SADDLE AND SCREWS 2HPS (#400680) Saddle 0.02 kg CONSAD/FX (#701410) Screw 0.01 kg Galvanised steel cable saddle and stainless steel screws for securing ISODC.
ERICO offers a large range of products for lightning and grounding applications. Please contact us should you require additional materials.
Strapping materials and tools for installation of mast mounting bracket ISOMMB50.
www.erico.com
21
LIGHTNING PROTECTION
LIGHTNING PROTECTION
ERITECH SYSTEM 2000
LIGHTNING PROTECTION
The ERITECH SYSTEM 2000 lightning protection system is comprised of these principal components: Air Termination Network Downconductors Grounding System Bonding
This Illustration is not drawn to scale, nor does it portray an actual or typical application. It is designed to illustrate some of the major components of the ERITECH SYSTEM 2000 Lightning Protection System and their relationship with one another.
Air terminal placement is designed using the computer aided design to EN 62305-3, AS 1768, NFPA 780. This ensures the most effective placement of air terminations on the structure. Downconductors are positioned to provide the most direct path from the air termination to a low impedance grounding system, to help ensure safe and effective dissipation of the lightning impulse. Equipotential bonding of all circuits and conductors is necessary to reduce ground potential differences and to limit equipotential damage.
www.erico.com
22
LIGHTNING PROTECTION
AIR TERMINALS AIR TERMINAL TO TAPE COUPLING/BRACKETS
70 mm L 25mm 16.5mm
M16
Reference code
Copper
Part No. 711080 711090 711100 711110 711010 711050 711060 710020 711070
Unit weight kg 0,480 0,750 1,100 1,510 3,000 0,190 0,380 0,265 0,530
TTR Series
27mm
CAR0510 CAR0515 CAR1010 CAR1015 CAR2015 Aluminium AAR0510 AAR1010 AAR0515 AAR1015
Reference code
Part No.
TTRC16 711210 TTRA16 711200 Rod brackets CBR015 711190 ABR015 711180
L 2m
Reference code
Lightning Rod height Chrome - nickel plated copper ASL-240-CC 101700 2,40 m Part No. Reference code ER1-2000 ER2-2000 ER3-2000 Part No. 101920 101930 101940
mm 30 mm 33 36 42
mm L mm 16 500 1
B 800 mm
RSC Part No. 711150 711160 711170 711130 711140 A mm B mm 10 16 16 10 16 25 25 31 25 25 1 1 1 1 1 Unit weight kg 0,500 0,500 1,700 0,160 0,160
385 mm
Reference code
Galvanized steel
Nr of masts 0-3 1
TFS 800
www.erico.com
23
LIGHTNING PROTECTION
LIGHTNING PROTECTION
WATERPROOF CONE/AERIAL SPARK GAP
6-50mm
X-SHAPED BRACKET
LIGHTNING PROTECTION
Reference code Reference code WPC SG-AERIAL-302 Part No. 702230 702285 1 1 Unit weight kg 0,070 0,500 ACF-2-GS
Admissible mm 30 to 50
STRIKING RODS
38-77 mm
Reference code
Part No.
Chrome - nickel plated copper ARC-2205-CNC 101900 ARC-2210-CNC 101910 Stainless steel ARC-2205-SS 102000 ARC-2210-SS 102010
90 mm
120 mm 28-55mm
Reference code
Galvanized steel
102460
102500
702165
ALOF1-GS
Description
Base rod support and cross-over Support plate Angle support plate For flat conductor (30x2) For round conductor (8mm) Cement block support Tape to Mast Clamp
1 1 1 1 1 10 1
24
www.erico.com
LIGHTNING PROTECTION
FASTENERS FOR AIR TERMINAL
102600 102620
w
102610
Description
M10 threaded rod, 100 mm long Supporting anchor bolt* Angle support plate Expanding support pin, M10 85 mm long, drilling depth 60 mm
10 10 10
Reference code
Part No.
Description
l w mm mm 40 69 44.5 15 15 15 25 25 25
Copper TAPC253 711570 for 25x3 bare copper tape clip TAPC506 711590 for 50x6 bare copper tape clip PVC Covered Copper TAPC254 711580 for 25x3 PVC covered copper tape clip Aluminium TAPA253 711550 for 25x3 bare aluminium tape clip
40
15
25
0,100
PUDDLE FLANGES
150 mm
3mm
5/8
Unit weight kg -
Colour Black 50
Reference code
Copper
Part No.
Description
for 25x3 bare copper tape for 25x6 bare copper tape for 31x6 bare copper tape for 50x6 bare copper tape for 25x3 PVC covered Cu tape for 25x6 PVC covered Cu tape for 50x6 PVC covered Cu tape for 25x3 bare aluminium tape for 25x3 PVC covered Al. tape
Unit weight kg Reference code 50 50 25 25 50 50 25 50 25 0,070 0,080 0,090 0,160 0,100 0,130 0,260 0,030 0,040 PDCUC Part No. 711352 Description 8 mm bare/insulated 25 mm x 3 mm bare/insulated 30 mm x 2 mm bare Black adhesive base with hardware Brown adhesive base with hardware Grey adhesive base with hardware Stone adhesive base with hardware White adhesive base with hardware Green adhesive base with hardware Colour Clear 50
DCC253 711220 DCC256 711230 DCC316 711660 DCC506 711240 DCC600 711250 DCC605 711260 DCC610 711270 Aluminium DCA253 711730 DCA600 711760
50 50 50 50 50 50
www.erico.com
25
LIGHTNING PROTECTION
LIGHTNING PROTECTION
SLATE HOLDFAST NON METALLIC DC CLIP & GLAZING BAR HOLDFAST
HF GB
LIGHTNING PROTECTION
Reference code
Part No.
HF250BN 711800 HF250GY 711810 For 25x3 PVC covered tape HFP253BN 711820 HFP253GY 711830 HFP253ST 711840
Unit weight kg -
BI-METALLIC CONNECTORS
711490 711500 711480
GBH C
Aluminium
GBH A
Reference code
Part No.
Description 25x3 mm
round max 8 mm
Stainless Steel
A
BIM800 711490 BIM900 711500 Copper / Aluminium BIM700 711480 mm 8 10 8 10 A mm 28 42 28 42 W mm 10 15 10 15 50 50 50 50 Unit weight kg 0,01 0,01 0,01 0,01
25x3 mm
Reference code
Copper
26 mm
OBC268
Aluminium
Reference code
Copper
Description 26x12 mm
PCT400
26
www.erico.com
LIGHTNING PROTECTION
PROTECTIVE SLEEVE FOR DOWN CONDUCTOR
21mm 40 mm 2m
PCF-40-GS
10 mm
2m 25 mm
PCR-27-GS
AVG3.0
3m 55 mm
Description Protective sleeve for down conductors Protective sleeve for round down conductors Anti vandal guard 1 1 1
Galvanized
80
23
50 mm
Reference code SR
175 35
Reference code
Galvanized
SDH-3-GI
Reference code Reference code CCFR-308 CCS-308 CCG-308 Part No. 545270 545170 545180 Material Brass Stainless steel Galvanized steel 25 25 25 Unit weight kg 0,150 0,150 0,150
Round 8 mm max or tape 30x2 mm max
Description Stainless steel bonding 100 Stainless steel buckle 50 Stainless steel serrated buckle 100 Fixoband Tool 1
www.erico.com
27
LIGHTNING PROTECTION
100 mm
LIGHTNING PROTECTION
SUPPORT FOR HIP OR RIDGE TILES
105400
LIGHTNING PROTECTION
r=93
105300
104980 Part No. 105300 105400 Conductor 6 mm 5-11 mm or 30x2 mm 10 10 Unit weight kg 0,092 0,105 Reference code R6-SRL-40/6 R6-SFT-40 Part No. 104950 104980 Conductor 6 mm 5-11 mm or 30x2 50 50 Unit weight kg 0,069 0,083
107660
25
Conductor 6 mm 8 mm 10 mm 50 50 50
Plastic 16 mm height
106300
18mm
ALD-TAP302 Part No. 711620 711195 100 100 Unit weight kg 0,002 -
28
www.erico.com
LIGHTNING PROTECTION
BLOCKS FOR ROUND OR FLAT CONDUCTORS
80mm
190mm
Part No.
Conductor
Fill 20 20 100
Unit weight kg 0,970 0,982 0,100 Reference code R7-SFT-20 Part No. 702250 10
106030 8 mm Concrete 106080 5-11 mm or 30x2 Concrete 106060 5-10 mm or 30x2 Empty
T CONNECTOR
40 mm 45 mm
150 mm
Unit weight kg Reference code 0,12 HSF Part No. 702240 10 Unit weight kg 0,02
8-10 mm diam.
CROSS CONNECTOR
28 mm 28 mm
Reference code
6-8 mm diam.
www.erico.com
29
LIGHTNING PROTECTION
CONDUCTORS
COPPER CABLE
Reference code
WITHOUT INSULATION
Reference code Part No. SC-EC-25 SC-EC-35 SC-EC-50 SC-EC-70 SC-EC-95 SC-EC-120 SC-EC-150 SC-EC-185 197900 197910 197920 197930 197940 710900 710920 197950 Strand Description 7x2,14 7x2,52 19x1,78 19x2,14 19x2,52 37x2,00 37x2,25 37x2,50 Section mm2 25 35 50 70 95 120 150 185 50 m 50 m 50 m 50 m 50 m 50 m 50 m 50 m Unit weight kg 0,23/m 0,31/m 0,46/m 0,62/m 0,85/m 1,03/m 1,33/m 1,61/m
Width (A)mm 25 25 25 30 38 38 50
25 m 50 m 15 m 30 m 10 m 30 m 20 m
Reference code TC-ECT-2530-30 TC-ECT-3020-30 TC-ECT-3020-75 TC-ECT-4030-30 TC-ECT-4040-35 Unit weight kg 50 m 50 m 50 m 50 m 50 m 50 m 50 m 50 m 50 m 50 m 50 m 0,27/m 0,37/m 0,53/m 0,26/m 0,36/m 0,52/m 0,72/m 0,98/m 1,16/m 1,54/m 2,10/m
Width (A)mm 25 30 30 40 40
30 m 30 m 75 m 30 m 35 m
Strand Description 204x0,395 286x0,395 408x0,395 7x2,14 7x2,52 19x1,78 19x2,14 19x2,52 37x2,03 37x2,25 37x2,52
198000 198010 198020 198050 198060 198070 198080 198090 710980 710990 711000
CT Reference code CTBL253-25 CTBN253-25 CTGN253-25 CTGY253-25 CTST253-25 CTWH253-25 CTYGN253-25 CTGN256-30 CTGN506-20 Part No. 710595 710605 710616 710645 710655 710666 710667 710620 710630 Dimensions AmmxBmm Black 25x3,0 Brown 25x3,0 Green 25x3,0 Grey 25x3,0 Stone 25x3,0 White 25x3,0 Yell./Green 25x3,0 Green 25x6,0 Green 50x6,0 Colour Unit weight kg 0,77/m 0,77/m 0,77/m 0,77/m 0,77/m 0,77/m 0,77/m 1,55/m 2,95/m
25 m 25 m 25 m 25 m 25 m 25 m 25 m 30 m 20 m
30
www.erico.com
CONDUCTORS
LEAD COVERED COPPER TAPE
Reference code LCT-253 Part No. 710625 Width (A)mm 25
50 m
EML
SRGB
Tape = 50 x 0,40 mm Reference code HDB2003 HDB2503 HDB2506 HDB3806 HDB5006 HDB5010 Part No. 710670 710680 710690 710700 710710 550900 Dimensions mm 20x3x4000 25x3x4000 25x6x4000 38x6x4000 50x6x4000 50x10x4000 Unit weight kg 2,14 2,68 5,34 8,00 10,68 17,80
SC
100 m 100 m
50 m 50 m 50 m 50 m
www.erico.com
31
CONDUCTORS
1 1 1 1 1 5
COPPER PLATES
Reference code PC1.5-0606 PC3-0606 PC1.5-0909 PC2.-1020 PC3-0909 Part No. 710190 710200 710210 504550 504590 Dimensions mm 600 x 600 x 1,5 600 x 600 x 3,0 900 x 900 x 1,5 1000 x 2000 x 2 900 x 900 x 3 1 1 1 1 1 Unit weight kg 5,000 9,600 11,510 35,600 21,630
CONDUCTORS
BARE ALUMINIUM TAPE
Width A mm 25 25 50
Thick B mm 3 6 6
50 m 50 m 50 m
D Part No. Cross-section mm2 mm Colours 710840 50,3 8 Black 710850 50,3 8 Brown 710860 50,3 8 Grey 710870 50,3 8 Stone
50 m 50 m 50 m 50 m
Width Thick A mm B mm 25 3 25 3 25 3 25 3 25 3
D mm 8 10
CC5A04 Reference code 30TC-HGSP-3035 Width Thick A mm B mm 30 3,5 Unit weight kg 0,82/m Reference Part No. Code
CC5A05 Description
30 m
Fusing Outside Capacity Diameter Equivalency CC5A04 CC5A04 (1) Tinned Copper, 8.38 mm 100% of (6) Galvanized Steel Strands 16 mm2 CC5A05 CC5A05 (3) Tinned Copper, 8.48 mm 100% of (16) Galvanized Steel Strands 16 mm2 CC5A12 CC5A12 (133) Tinned Copper, 14.53 mm 100% of (24) Galvanized Steel Strands 70 mm2
76 m 76 m 60 m
D mm 8 8
300 m 50 m
32
www.erico.com
GROUNDING SOLUTIONS High strength corrosion resistant ERITECH Ground Rods, clamps and accessories Prefabricated wire mesh Ground Enhancement Material (GEM) greatly improves ground grid resistance and impedance CADWELD molecular bonding connections
RADIAL DESIGN
www.erico.com
33
conditions. Copperbonded rods last longer, drive easier and will not crack.
Copper exteriors, molecularly bonded to nickel-sealed high-strength steel
cores, exceed the requirements of ANSI/UL 467-1984 (ANSI C33.8-1972) and CSA.
Copper Coating: standard copper plating thickness exceeds UL and ANSI specs.
8.3 x 10-4m/m.
Extending rods may be extended with use of threadless couplers.
Manufactured
in Gunmetal (LG2) and Naval Brass to comply with material standards Rod to Cable Lug clamps (threaded and unthreaded) Permits easy connection of ground conductors to both threaded and unthreaded ground rods Type SSR (Stainless steel) A2 grade
Couplers
Earthrod Pigtail
externally coupled ground rods have all the features of standard copperbonded rods plus cold-rolled threads at each end for joining with couplings. The cold-rolled threads of ground rods with their continuous unbroken grain flows are stronger than cut-threads. High-strength couplings are threaded bronze and chamfered at both ends for easy driving. Threaded coupling design allows for full contact of rod point with butt end of preceding rod. These high strength, corrosion-resistant couplings ensure low resistance copper-to-copper connections.
The ERITECH brand of Ground Rod Drivers from ERICO is the simple, effective and affordable way to install ground rods.
The Ground Rod Driver includes driver body with soft rubber grip, insert for driving rods to ground level, and retaining collar which holds insert in place during storage.
14,2 mm (5/8) and 17,2 mm (3/4) inserts are interchangeable with standard driver
Couplers for threaded rods Steel driving studs for sectional ground rods
body to enable easy driving of standard rods. driver will not deform the end of the rod, making connection of the ground conductor quick and easy Integral insert prevents driver from slipping off the rod near ground level. Convenient retaining collar holds the insert in the tool when not in use. Self-contained and easy to store. Saves time and money and dramatically reduces risks of employee injury.
The
34
www.erico.com
Reference Part No. code Non extending 1,2M38 155000 1,5M38 155010 2,1M38 155030 3,0M38 155050 Extending 1,2M12 155060 1,5M12 155070 2,1M12 155090 3,0M12 155110 1,2M58 155240 1,5M58 155250 2,1M58 155270 3,0M58 155290 1,2M34 155420 1,5M34 155430 2,1M34 155450 3,0M34 155470
to standard UL467 Nominal Length Approx. inches mm m feet 3/8 3/8 3/8 3/8 1/2 1/2 1/2 1/2 5/8 5/8 5/8 5/8 3/4 3/4 3/4 3/4 9 9 9 9 12,5 12,5 12,5 12,5 14,2 14,2 14,2 14,2 17,2 17,2 17,2 17,2 1,2 1,5 2,1 3 1,2 1,5 2,1 3 1,2 1,5 2,1 3 1,2 1,5 2,1 3 4 5 7 10 4 5 7 10 4 5 7 10 4 5 7 10 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5
Unit weight kg 0,650 0,800 1,100 1,600 0,800 1,150 1,600 2,300 1,500 1,900 2,650 3,750 2,150 2,750 3,800 5,450 Reference code S1,2M916 S1,5M916 S2,1M916 S3,0M916 S1,2M58 S1,5M58 S2,1M58 S3,0M58 S1,2M34 S1,5M34 S2,1M34 S3,0M34 Part No. 155180 155190 155210 155230 155300 155310 155330 155350 155480 155490 155510 155530
inches 9/16 9/16 9/16 9/16 5/8 5/8 5/8 5/8 3/4 3/4 3/4 3/4
Approx. mm
12,7 12,7 12,7 12,7 14,2 14,2 14,2 14,2 17,2 17,2 17,2 17,2
Nominal Length m feet 1,2 4 1,5 5 2,1 7 3 10 1,2 4 1,5 5 2,1 7 3 10 1,2 4 1,5 5 2,1 7 3 10
5 5 5 5 5 5 5 5 5 5 5 5
Unit weight kg 0,800 1,150 1,600 2,300 1,500 1,900 2,650 3,750 2,150 2,750 3,800 5,450
resistance 6 micro-Ohms
BZT-Copper couplers 99% Cu, typical mechanical
Reference code
Brass
Reference code
Tempered steel
Reference code
Tempered steel
Reference code
Tempered steel
SDT58 SDT34
www.erico.com
35
Reference code
Part No. 1 1 1 1
EST3640 EST3640 EST4610 EST4610 EST4630 EST4630 EST6472 EST6472 Technical data available upon request.
Part Rod Conductor No. Range EHL12FC1K 1/2" 10-16 mm2 str EHL12FC1V 1/2" 22-35 mm2 str* EHL12FC2G 1/2" 50-70 mm2 str** EHL58C1K 5/8" 10-16 mm2 str EHL58C1V 5/8" 22-35 mm2 str* EHL58C2G 5/8" 50-70 mm2 str** EHL34C1K 3/4" 10-16 mm2 str EHL34C1V 3/4" 22-35 mm2 str* EHL34C2G 3/4" 50-70 mm2 str** Dual-Hole (2 Conductors) EHL12FC1K1K 1/2 10-16 mm2 str EHL58C1K1K 5/8 10-16 mm2 str * 6 mm solid ** 8 mm solid
25 25 25 25 25 25 25 25 25 25 25
Unit weight kg 0,137 0,134 0,134 0,129 0,116 0,209 0,213 0,159 0,169 0,134 0,209
36
www.erico.com
SSR16-710010 - Stainless steel Reference code SSR16 Part No. 710010 diam. length mm m 16 1.20 Unit weight kg 1,640
Rod mm 20 5
DT-P137-1-20
CDS15 710090 15 M10 Stainless steel internal coupling Dowel SSD10 710115 10 Driving point for SSR16 SPK15 710120 15
Length m 1,5
mm 20 5
Reference code
Section 50 x 50 x 3
Length m 1 1,5 2 5 5 5
Rod mm 20 5
DT-P11-20-SS
Supplied with splice plate Zinc coating: min 78 micron/ Average min. 86 micron
Reference code
Section 50 x 50 x 5
Length m 1 1,5 2 5 5 5
Rod mm 20-30 5
DH-TR167
www.erico.com
37
Part No.
2
Rod mm 20 5
158440
Description 1,5 m driver body with insert for up to 14,2 mm Replacement insert for 14,2 mm (5/8) Driver body with insert for up to 17,2 Replacement insert for 17,2 mm (3/4) 1 1 1 1
Unit weight kg 10,420 2,720 10,420 2,720 Reference code Part No.
Gunmetal
Unit weight kg 0,040 0,084 0,086 0,085 0,125 0,110 0,04 0,10 0,13
38
www.erico.com
RCC10 SRC15 SRC20 Reference Part No. code Gunmetal RCC10 710420 RCC16 710430 SRC15 710440 SRC20 710450
Description
9,5 mm plain split Clamp 16 mm split Clamp (threaded) 14,2-15 mm plain split Clamp (SCR) for solid copper rod 20 mm plain split Clamp (SCR) for solid copper rod
Reference Part No. Dimensions & code No. of holes Copper BEP25x5x300MM 545140 25x5x300 mm 12 holes BEP25x5x200MM 545135 25x5x200 mm 8 holes BEP25x5x150MM 545530 25x5x150 mm 6 holes
Designed to suit Earth Pit Concrete Earth Pit IP-900-C(103450) Plastic Earth Pit PIT03(710180) Cast Iron Earth Pit IPR193(103470) IP180(103480) 1 1 1
Unit weight kg 11,500 Reference code WGRS200 Part No. 158922 Description Double Flange Earth Rod Seal* 1 Unit weight kg 4,3
PREFABRICATED CROWSFOOT
* Includes PIT05 Heavy Duty Earth Inspection Kit. The Double Flange version is delivered as a kit, which includes a 1,2 m PVC pipe, to be adjusted to site conditions. Kit is assembled with PIT05 (158923).
TAPE METAL SUPPORT FOR FOUNDATIONS OR TRENCHES AND TAPE METAL WALL SUPPORT
INSPECTION PITS
710180 103470 107600 107550
STBF-25-GS STBF-40-GS
100 mm
140 mm
Dimensions mm plastic 250x200x215 concrete 325x325x145 Cast iron 210x140x120 Cast iron 180 Material
1 1 1 1
SSF-6-GS SSF-6-C
www.erico.com
39
INSULATORS
Please see ERIFLEX Catalog.
40 22
Reference code
Copper - 8mm
EQUIPOTENTIAL BARS
SEB
l Cu 50x5mm w
TECLP-8-CU
Aluminium - 8mm
160 mm 5 mm 40 mm 171 mm
TECLP-8-AL
B - BOND
M10x35
173 mm
52 mm
SEB-62-DL
33
25 mm max.
33
Nr of Disconnect L Part No. terminals links mm 545000 1 125 545010 6 0 400 545020 6 1 475 545030 10 0 600 545040 10 1 675 545130 6 2 550 545001 7 x 25 mm2
1 x tape 30 x 3,5 1 x 8 mm
L 94 94 94 94 94 94 1 1 1 1 1 1 10
ABBC
PIPE COLLARS
6-11 mm
Reference code
Part No.
25 mm 10,5 mm
16 connection points
SPC-5080-S 107000 SPC-70120-S 107010 SPC-130180-S 107020 Copper - conductor, 6 to 11 mm SPC-5080-C 107050 SPC-70120-C 107060 SPC-130180-C 107070
Reference code
Tinned copper 100 x 5
SEP
Copper - conductor, 6 to 10 mm
40
www.erico.com
Length mm 50
mm 50
Unit weight kg -
EARTH BLOCKS
20 mm
STATIC EARTHING
EBL08 - 6 x 5,2 mm - 2 x 6,5 mm 165410 165620 198400 198410 198420 5 ft = 1.5 m 10 ft = 3 m 20 ft = 6 m
88 mm
13 mm
B2617A
EBL08
Supporting plate for the connection of round conductors, diameter 10 mm, or flat conductors up to 40 x 4 mm on rebars up to 24 mm .
Description Spring Clamp Aircraft Grounding Clamp Orange Coiled Cable, 5 ft (1.5 m) Orange Coiled Cable, 10 ft (3 m) Orange Coiled Cable, 20 ft (6 m) Cable Reel Assembly 1 1 1 1 1 1
60 40
M10
Part No.
Conductor
Rebar 25
Galvanized steel
FENCE CLAMPS
REBAR CLAMPS
RC EK
Reference code FC073 FC074 FC075 FC076 FC078 FC079 FC080 FC082
Part No. 198401 198402 198403 198404 198406 198407 198408 198411
Conductor Size - Metric 16 mm Str - 70 mm Str 70 mm Str - 120 mm Str 16 mm Str - 70 mm Str 70 mm Str - 120 mm Str 16 mm Str - 120 mm Str 16 mm Str - 70 mm Str 70 mm Str - 120 mm Str 16 mm Str - 120 mm Str
Galvanized steel
www.erico.com
41
B2618B
GROUNDING RECEPTACLES
165180
C
B
mm
J mm
T mm
Unit weight kg
165220 165230
A B
1/2" PIPE FOR TYPE RA & RB CONNECTIONS
These receptacles provide earth connections for the frames of planes, ships, tankers trucks, etc. eliminating their electrostatic charge and obtaining equipotentiality with the surrounding earth. Parts are copper alloy, connections to the earth circuit can be made with CADWELD.
Attachment Cast 3/4 ball Cast 3/4 rod Cast 1-1/2 rod
C 1 1 1
563540 556620 563550 556630 563300 556640 556650 563320 556660 556940 556670 556680 563340 556690 563430 556700 556710 556950 556720 556730 556740 556750 556760 556960 556770 556780 556790 556800 565000 556810 556970 556820 556830 563350 556840 563440 563360 563370 556850 556860 563390 563400 556980 563560
MBJ 16-100-6 MBJ 16-100-8 MBJ 16-150-6 MBJ 16-150-8 MBJ 16-200-6 MBJ 16-200-8 MBJ 16-250-8 MBJ 16-300-6 MBJ 16-300-8 MBJ 16-500-8 MBJ 25-100-10 MBJ 25-150-10 MBJ 25-200-6 MBJ 25-200-10 MBJ 25-200-12 MBJ 25-250-10 MBJ 25-300-10 MBJ 25-500-10 MBJ 30-100-10 MBJ 30-150-10 MBJ 30-200-10 MBJ 30-250-10 MBJ 30-300-10 MBJ 30-500-10 MBJ 35-100-10 MBJ 35-150-10 MBJ 35-200-10 MBJ 35-250-10 MBJ 35-250-25 MBJ 35-300-10 MBJ 35-500-10 MBJ 50-100-10 MBJ 50-150-10 MBJ 50-200-6 MBJ 50-200-10 MBJ 50-200-12 MBJ 50-200-16 MBJ 50-200-18 MBJ 50-250-10 MBJ 50-300-10 MBJ 50-300-16 MBJ 50-300-18 MBJ 50-500-10 MBJ 50-500-12
120 120 120 120 120 120 120 120 120 120 150 150 150 150 150 150 150 150 180 180 180 180 180 180 197 197 197 197 197 197 197 250 250 250 250 250 250 250 250 250 250 250 250 250
1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 2 2 2 2 2 2 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5
16 16 16 16 16 16 16 16 16 16 25 25 25 25 25 25 25 25 30 30 30 30 30 30 35 35 35 35 35 35 35 50 50 50 50 50 50 50 50 50 50 50 50 50
100 100 150 150 200 200 250 300 300 500 100 150 200 200 200 250 300 500 100 150 200 250 300 500 100 150 200 250 250 300 500 100 150 200 200 200 200 200 250 300 300 300 500 500
6,5 8,5 6,5 8,5 6,5 8,5 8,5 6,5 8,5 8,5 10,5 10,5 6,5 10,5 12,5 10,5 10,5 10,5 10,5 10,5 10,5 10,5 10,5 10,5 10,5 10,5 10,5 10,5 25,5 10,5 10,5 10,5 10,5 6,5 10,5 12,5 16,5 18,5 10,5 10,5 16,5 18,5 10,5 12,5
15 15 15 15 15 15 15 15 15 15 23 23 23 23 23 23 23 23 23 23 23 23 23 23 23 23 23 23 40 23 23 28 28 28 28 28 28 28 28 28 28 28 28 28
25 25 25 25 25 25 25 25 25 25 33 33 33 33 33 33 33 33 33 33 33 33 33 33 33 33 33 33 50 33 33 38 38 38 38 38 38 38 38 38 38 38 38 38
10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10
0,018 0,018 0,035 0,035 0,033 0,033 0,040 0,05 0,05 0,082 0,027 0,039 0,052 0,052 0,052 0,064 0,077 0,013 0,032 0,047 0,062 0,075 0,092 0,155 0,037 0,054 0,072 0,089 0,089 0,110 0,180 0,052 0,077 0,12 0,120 0,120 0,11 0,11 0,127 0,153 0,15 0,14 0,255 0,255
42
www.erico.com
TYPE DB
1 4 2
TYPE B162
6 5 8
TYPE DB - Minimum Order Quantity Required
Fig. No. Reference code DB-8A DB-10A DB-12A DB-16A DB-8K DB-10K DB-12K DB-16K DB-8KS DB-10KS DB-12KS DB-16KS DB-10-C5005 DB-10-C501 DB-10-C502 Part No. 166090 166120 166150 166180 166100 166130 166160 166190 166110 166140 166170 166200 166480 166490 166500
7 9
10
11 12
A M8 M10 M12 M16 M8 M10 M12 M16 M8 M10 M12 M16 M10 M10 M10
B
mm
C
mm
D
mm
F
mm
L
mm
B
mm
C
mm
D
mm
F
mm
G
mm
L
mm
65 65 85 65 65 85 65 65 85 65 65 65
42 42 75 42 42 75 42 42 75 -
1 1 1 1 1 1 1 1 1 1 1 1
Unit weight kg 0,435 0,455 0,770 1,980 1,040 1,080 1,980 0,850 1,100 0,840 1,100 1,600
B
mm
C
mm
D
mm
E
mm
F
mm
G
mm
L
mm
45 45 45 45 45 45
85 85 85 85 85 85
75 75 75 75 75 75
5 1 1 1 1 1
www.erico.com
43
30 50 50 50 30 50 50 50 30 50 50 50 50 50 50
50 55 55 55 50 55 55 55 50 55 55 55 55 55 55
500 500 500 500 500 500 500 500 500 1000 2000
5 5 5 5 1 1 1 1 1 1 1 1 1 1 1
Unit weight kg 0,090 0,300 0,305 0,400 0,450 1,520 1,535 1,560 0,440 1,520 1,505 1,540 0,740 0,960 1,440
SURGE PROTECTION
SURGE PROTECTION
COLOUR CODE
Power Protection device Telecommunication and Dataline Protection device.
Power line Telecoms and Data Earthing network
44
www.erico.com
SURGE PROTECTION
DINLINE SURGE DIVERTERS 150kA DINLINE SPARK GAP DIVERTER (SGD)
Reference code DSD160 1SR 275 DSD160 1SR 275M DSD140 1S 75 DSD140 1S 275 DSD140 1SR 275 DSD140 M 275 DSD140 1SR 440 DSD140 M 440 DSD110 1S 275 DSD110 M 275
Part No. 702460 702465 702478 702491 702521 702496 702530 702506 702560 702566
Description 60kA, 275V, Relay 60kA, 275V Module 40kA, 75V 40kA, 275V 40kA, 275V, Relay 40kA, 275V Module 40kA, 440V, Relay 40kA, 440V Module 10kA, 275V 10kA, 275V Module 1 1 1 1 1 1 1 1 1 1
Unit weight kg 0,12 0,10 0,12 0,12 0,12 0,10 0,12 0,10 0,12 0,10
Description 3A, 120V 3A, 240V 10A, 120V 10A, 240V 20A, 120V 20A, 240V 1 1 1 1 1 1
Reference code DSD340 TNC 275 A DSD340 TNS 275 A DSD340 TT 275 A
Description 40kA, 275V TN-C, Modular 40kA, 275V TN-S, Modular 40kA, 275V TT, Modular 1 1 1
www.erico.com
45
SURGE PROTECTION
TRANSIENT PANEL SURGE PROTECTION LOCAL AREA NETWORK PROTECTORS (LAN)
Reference code UTB5SP UTB15SP UTB30SP UTB60SP UTB110SP UTB5DP UTB15DP UTB30DP UTB60DP UTB110DP
Part No. 702861 702862 702863 702864 702866 702886 702887 702888 702889 702891
Description 5V, 1.5A 15V, 1.5A 30V, 1.5A 60V, 1.5A 110V, 1.5A 5V, 8A, 2 Pair 15V, 8A, 2 Pair 30V, 8A, 2 Pair 60V, 8A, 2 Pair 110V, 8A, 2 Pair 1 1 1 1 1 1 1 1 1 1
Unit weight kg 0,100 0,100 0,100 0,100 0,100 0,100 0,100 0,100 0,100 0,100
Description Subscriber line, high speed 12V, high speed 36V, high speed 72V, high speed 230V, high speed 2.5mm2 terminal block 1 1 1 1 1 1
SURGE PROTECTION
Reference code CSP BNC 90 CSP BNC 600 CSP NMF 90 CSP NMF 600 CSP NB 90 CSP NB 600
Description BNC, 90V BNC, 600V NMF, 90V NMF, 600V NB, 90V NB, 600V 1 1 1 1 1 1
46
www.erico.com
XA
PC
BY LE PA
THE CADWELD MOULD NUMBERING SYSTEM
The CADWELD Mould Part Number code gives the complete information of the mould ie: - type of connection, mould price key, and conductor size(s).
PG
Mould type Mould Price Key
BD
TA
XXX-XXXX
EXAMPLES :
TA C - Y6 Y4
Type TA Price Key C 120 mm2 Run 70 mm2 Tap
GT C - P143 Y6
Type GT Price Key C 14,2 mm Copper Clad Ground Rod 120 mm2 Tap
SS C - Y4
Type SS Price Key C 2 x 70 mm2 cables
VS C - Y2 - V76
CADWELD
Type VS Price Key C Cable 35 mm2 Vertical Pipe 76 mm Diameter Pipe
www.erico.com
47
CADWELD PLUS
CADWELD PLUS connections offer all the benefits of conventional CADWELD connections:
Withstand repeated fault currents without failing during operation Exceed requirements of IEEE Std 837- Std. for Qualifying Permanent Connections Used In Substation Grounding Join copper to copper, copper to galvanised or plain steel, copper to copper clad steel, copper to bronze/ brass/stainless steel, steel to steel, etc. Current carrying capacity equal to or greater than that of the conductor Permanent, molecular bond that will not loosen or corrode, resulting in a connection with a lifetime equal to that of the installation No external power or heat source required Quality Assurance Inspection is easy and visual Minimal installation training required Consists of a tamper proof, disposable, moisture-resistant welding material cup. The welding material, disk and ignition source are incorporated into the self-contained package Virtually unlimited shelf life Completes welds at distances of up to 6 ft/1.8 meters (up to 15 ft/4.6 meters with optional lead) Requires minimum components no starting material, no disks, no flint igniters Easy to handle, store and transport by air, land or sea in unlimited quantities Reduces installation time by 20% Has colour-coded welding material containers by size and alloy type for easy identification Has electronic ignition with a CE/UL battery powered controller box that is designed for 600 connections with one set of 8 standard AA batteries (included) requiring no special batteries or chargers
The ultimate welded connection that will never loosen, corrode or increase in resistance just got
BETTER.
CADWELD PLUS is the latest advancement in the continuing evolution of ERICOs exothermic products. Since its development in 1938, CADWELD electrical connections have become recognized as the ultimate connection for rail, cathodic, power and grounding applications. ERICO has established itself as the worldwide connections leader. CADWELD PLUS continues this tradition of technical leadership. The revolutionary CADWELD PLUS System is a simplified method of performing exothermically welded electrical connections. The CADWELD PLUS integrated welding material package has streamlined the installation process by eliminating ignition materials reducing set up time. The tamper proof, integrated welding material package consists of a steel cup containing CADWELD patented welding material alloys and ignition source. This new welding material package is designed for use in all standard CADWELD moulds including CADWELD MULTI. Once placed in the CADWELD mould, the welding material is electronically ignited using a simple battery-powered control unit with six (6) foot lead.
Ignitor Strip
CADWELD PLUS
Feature
Integrated Welding Material Package
Benefits
Simplifies training and set up Saves labour Simplifies cleaning Reduces risk of misapplication Simple visual verification of correct welding material size No starting material required Easy ignition Increased flexibility in hard to reach areas
www.erico.com
Colour Coded Welding Material Electronic Control Unit Six Foot Control Unit Lead
CADWELD
48
CADWELD PLUS
Installation Is Easy!
4 Simple Steps For Permanently Welded Electrical Connections
Press and hold control unit switch and wait for the ignition
Open the mould and remove the expended steel cup no special disposal required
Part No.
165700 165701 165702 165703 165704 165705 165706 165707 165708 165709 165710 165711 165712
Part No.
165713 165714 165715 165716 165717
Accessories
Reference Code Part No.
PLUSCU PLUSCU15L PLUSCULD PLUSCULD15 165738 165745 165739 165746
Description
CADWELD PLUS Control Unit CADWELD PLUS Control Unit with 15 ft. (4.6 meters) Lead CONTROL UNIT Replacement Lead 6 ft. (1.8 meters) CONTROL UNIT Replacement Lead 15 ft. (4.6 meters)
PLUSCU
CADWELD PLUS Patent Numbers
PLUSCULD
6,553,911 6,835,910 6,703,578
CADWELD PLUS Control Unit initiates the reaction of the metal crucible. The standard unit includes a 6-foot (1.8 meter) high temperature control unit lead. The lead attaches to the ignition strip using a custom made, purpose-designed termination clip.
After the termination clip is installed on the ignition strip, the installer pushes and holds the ignition button to start a charging and discharging sequence. Within a few seconds the control unit sends a predetermined voltage to the ignition strip and the reaction is initiated.
www.erico.com
49
CADWELD
Traditional CADWELD
Reference code Part No. Unit Weight kg Disk Type* Reference code
CADWELD PLUS
Part No. Unit Weight kg
F20 Alloy - Clear Cap - Copper/Copper - Copper/Steel - Steel/Steel 15 15 163590 20 0,015 25 25 163000 20 0,025 32 32 163010 20 0,032 45 45 163020 20 0,045 65 65 163030 20 0,065 90 90 163040 10 0,090 115 115 163050 10 0,115 150 150 163060 10 0,150 200 200 163070 10 0,200 250 250 163080 10 0,250 300 use (2) 150 400 use (2) 200 500 500 163090 10 0,500 F33 Alloy - Green Cap - Cathodic protection - Steel pipe 15 25 32 45 65 90 115 150 CA15 CA25 CA32 CA45 CA65 CA90 CA115 CA150 163200 163210 163220 163230 163240 163250 163260 163270 20 20 20 20 20 10 10 10 0,015 0,025 0,032 0,045 0,065 0,090 0,115 0,150
19 19 19 19 19 25 25 38 38 38
38
15PLUSF20 25PLUSF20 32PLUSF20 45PLUSF20 65PLUSF20 90PLUSF20 115PLUSF20 150PLUSF20 200PLUSF20 250PLUSF20 300PLUSF20 400PLUSF20 500PLUSF20
165700 165701 165702 165703 165704 165705 165706 165707 165708 165709 165710 165711 165712
20 20 20 20 20 10 10 10 10 10 10 10 10
0,049 0,063 0,065 0,086 0,104 0,158 0,185 0,217 0,267 0,353 0,376 0,480 0,585
19 19 19 19 19 25 25 38
20 20 20 20 20
CADWELD
50
www.erico.com
CADWELD MULTI
batting and variable Step Layer conductor sizes to be 1 welded into dry mould
Step 2
welding material Step Deposit and tap bottom of 3 container to release starting material
the cover and Step Close ignite with flint ignitor. 4 Open the mould after 10 seconds
The CADWELD MULTI combines a versatile mold block and a range of gaskets (batting) to allow numerous different welded connections to be produced without the need to change the mould for each connection type.
The process is similar to the traditional CADWELD with one distinct difference... there is no need to change the mould for different connection types. The whole process is complete in about one minute. The connection table details the gasket quantities required for each weld.
SS
SC
PA
TA
XA
GG
GJ
TD
TE
TF
Copper concentric conductor sizes up to 25 mm2 (6.6 mm dia.) or #3 AWG (0.26 dia.)
GF
GW
XB
PP
PK
GE
PG
Copper concentric conductor sizes up to 50 mm2 (9.3 mm dia.) or 1/0 AWG (0.37 dia.)
RG
RH
RK
RF
RD
BB
CG
BG
EB
Copper concentric conductor sizes up to 50 mm2 (9.3 mm dia.) or 1/0 AWG (0.37 dia.) Copper or steel strip sizes up to 30 x 3,5 mm (1.2 x 0.14) Rebar sizes up to 10 mm (#3)
BB and CG: Copper strip sizes up to 30 x 3,5 mm (1.2 x 0.14) BG and EB: Copper strip sizes up to 30 x 3,0 mm (1.2 x 0.12)
HA
HC
HS
HT
GL
LA
LJ
LE
BB
CG
Copper concentric conductor sizes up to 50 mm2 (9.3 mm dia.) or 1/0 AWG (0.37 dia.) Copper or steel lug / strip sizes up to 30 x 3,5 mm (1.2 x 0.14)
TG
GT
CN
CP
GR
GT
CN
CP
GR
Copper concentric conductor sizes up to 10 mm2 (4.2 mm dia.) or #6 AWG (0.18 dia.) Copper strip sizes up to 30 x 2,0 mm (1.2 x 0.08)
Copper concentric conductor sizes greater than 10 mm2 (4.2 mm dia.) or #6 AWG (0.18 dia.) Copper strip sizes 30 x (2,5 - 3,0 mm) or 1.2 x (0.10 0.12) Steel strip sizes 30 x (0,5 - 3,5 mm) or 1.2 x (0.02 0.14)
www.erico.com
51
CADWELD
CADWELD
Mould
A
SS
TA
A XA B
A PG B
PT
PC
LJ LW
A HA A LE B
Reference code SSC-W6 SSC-W8 SSC-Y1 SSC-Y2 SSC-Y3 SSC-Y4 SSC-Y5 SSC-Y6 TAC-Y1 TAC-Y2 TAC-Y2-Y1 TAC-Y3 TAC-Y4 TAC-Y4-Y2 TAC-Y5 TAC-Y5-Y6 TAC-Y6 TAC-Y6-Y4 TAC-Y7 TAC-Y8 XAC-Y1 XAC-Y2 XAC-Y3 XAC-Y4 XAC-Y5 XAC-Y6 PGC-Y1 PGC-Y2 PGC-Y3 PGC-Y4 PGC-Y4-Y1 PGC-Y5 PGC-Y6 PTC-Y1 PTC-Y2 PTC-Y3 PTC-Y4 PTC-Y5 PTC-Y6 PCC-Y1 PCC-Y3 PCC-Y6 LJP-Y1-BAK LJP-Y2-BAK LJP-Y3-BAK LJC-Y3-FAM LWP-Y3-BAK HAA-Y1 HAA-Y1-CA HAA-Y2 HAA-A3 HAA-Y3 HAA-Y4 HAA-B3-CA HBA-B3 LEP-Y3-BAK
VGC-Y1 VGC-Y2 VGC-Y3 VGC-Y4 VGC-Y5 VGC-Y6 VSC-Y3 VSC-Y4 VSC-Y5 VSC-Y6 BMP-BAK BMP-CAJ G-BMP-DAJ BMP-CAJ-BAK EBP-BAK EB-BGP-BAK EBP-CAJ G-EBP-DAJ
Part No.
221008 221011 221004 221006 221009 221021 221013 221014 221025 221028 221063 222459 221035 221075 222461 225026 222463 221094 221051 221053 221135 221138 221142 221148 221153 221159 237901 232556 232648 231342 236084 223943 231692 221268 226545 221265 221258 221256 222115 223550 222560 230199 234737 234738 234739 232933 234782 221609 221466 221607 222689 221603 221534 240228 223044 234759 228521 224815 222939 228347 223076 223609 221407 221405 221404 221403 234429 234426 224123 234736 225788 234398 234991 223432
Diameter Amm Bmm 8,0 8,0 10,0 10,0 6,4 6,4 7,6 7,6 9,0 9,0 11,0 11,0 12,5 12,5 14,2 14,2 6,4 6,4 7,6 7,6 7,6 6,4 9,0 9,0 11,0 11,0 11,0 7,6 12,5 12,5 12,5 14,2 14,2 14,2 14,2 11,0 15,9 15,9 17,7 17,7 6,4 6,4 7,6 7,6 9,0 9,0 11,0 11,0 12,5 12,5 14,2 14,2 6,4 6,4 7,6 7,6 9,0 9,0 11,0 11,0 11,0 6,4 12,5 12,5 14,2 14,2 6,4 6,4 7,6 7,6 9,0 9,0 11,0 11,0 12,5 12,5 14,2 14,2 6,4 6,4 9,0 9,0 14,2 14,2 6,4 7,6 9,0 9,0 9,0 6,4 6,4 7,6 8,0 9,0 11,0 4,9 4,9 9,0
6,4 7,6 9,0 11,0 12,5 14,2 9,0 11,0 12,5 14,2
Section Amm2 Bmm2 50 50 78,5 78,5 25 25 35 35 50 50 70 70 95 95 120 120 25 25 35 35 35 25 50 50 70 70 70 35 95 95 95 120 120 120 120 70 150 150 185 185 25 25 35 35 50 50 70 70 95 95 120 120 25 25 35 35 50 50 70 70 70 25 95 95 120 120 25 25 35 35 50 50 70 70 95 95 120 120 25 25 50 50 120 120 25 60 35 60 50 60 50 250 50 60 25 25 35 40 50 70 14,5-16 14,5-16 50 60
25 35 50 70 95 120 50 70 95 120 60 75 87,5 75 60 60 75 87,5
Sizes mm
1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
30x2
Unit weight kg 1,37 1,37 1,37 1,37 1,37 1,37 1,75 1,75 1,37 1,37 1,37 1,37 1,37 1,37 1,37 1,37 1,57 1,57 1,57 1,57 1,37 1,37 1,37 1,37 1,57 1,75 1,37 1,37 1,37 1,37 1,37 1,57 1,57 1,75 1,75 1,75 1,75 1,97 1,97 1,37 1,75 1,97 0,70 0,70 0,70 1,37 0,70 0,31 0,31 0,31 0,31 0,31 0,45 0,19 0,31 0,60
1,37 1,37 1,75 1,75 1,97 1,97 1,57 1,57 1,57 1,57 0,87 0,87 0,87 0,60 0,87 0,85 0,58 0,58
Remarks
Solid core cable horizontal splice Multi -strand cable to cable splice
Horizontal round or cable conductor to flat steel surface or top of horizontal pipe
Sleeve : H105 Tape to cable Cable through connections on vertical flat steel surface
A VG
VS A
CADWELD
BM A EB B
60 75 87,5 60 60 60 75 87,5
52
www.erico.com
CADWELD
Weld metal size required 45 65 32 32 45 65 90 115 32 45 45 90 90 45 115 150 150 90 200 200 45 65 90 115 150 200 45 65 90 115 90 150 200 45 65 90 115 200 250 45 90 200 65 65 90 90 90 45 32F33 45 45 45 65 15F33 25 65
45 45 115 115 150 150 90 90 115 115 65 65 65 90 90 90 65 65
Frame Page 53 L-160 L-160 L-160 L-160 L-160 L-160 L-160 L-160 L-160 L-160 L-160 L-160 L-160 L-160 L-160 L-160 L-160 L-160 L-160 L-160 L-160 L-160 L-160 L-160 L-160 L-160 L-160 L-160 L-160 L-160 L-160 L-160 L-160 L-160 L-160 L-160 L-160 L-160 L-160 L-160 L-160 L-160 L-161 L-161 L-161 L-160 L-161 M-129 M-129 M-129 M-129 M-129 M-129 M-129 M-129 L-161
L-160 L-160 L-160 L-160 L-160 L-160 L-160 L-160 L-160 L-160 L-161 L-161 L-161 L-161 L-161 L-161 L-161 L-161
Toolset Page 55 TS CST TS CST TS CST TS CST TS CST TS CST TS CST TS CST TS CST TS CST TS CST TS CST TS CST TS CST TS CST TS CST TS CST TS CST TS CST TS CST TS CST TS CST TS CST TS CST TS CST TS CST TS CST TS CST TS CST TS CST TS CST TS CST TS CST TS CST TS CST TS CST TS CST TS CST TS CST TS CST TS CST TS CST TS CST TS CST TS CST TS CST TS CST TS CST TS CST TS CST TS CST TS CST TS CST TS CST TS CST TS CST
TS CST TS CST TS CST TS CST TS CST TS CST TS CST TS CST TS CST TS CST TS CST TS CST TS CST TS CST TS CST TS CST TS CST TS CST
Scraper tools Page 55 TP-3B TP-3B TP-3B TP-3B TP-3B TP-3B TP-7A TP-7A TP-3B TP-3B TP-3B TP-7A TP-7A TP-3B TP-7A TP-2A TP-2A TP-7A TP-2A TP-2A TP-3B TP-3B TP-7A TP-7A TP-2A TP-2A TP-3B TP-3B TP-7A TP-7A TP-7A TP-2A TP-2A TP-3B TP-3B TP-7A TP-7A TP-2A TP-2A TP-3B TP-7A TP-2A TP-5B TP-5B TP-5B TP-7A TP-5B TP-3B TP-3B TP-3B TP-3B TP-3B TP-3B TP-3B TP-3B TP-5B
TP-3B TP-3B TP-7A TP-7A TP-2A TP-2A TP-7A TP-7A TP-7A TP-7A TP-5B TP-5B TP-5B TP-2A TP-5B TP-5B TP-5B TP-5B
PLUSCU
Description Control Unit with 1,80 m lead Control Unit with 4,60 m lead Replacement Lead 1,80 m long Replacement Lead 4,60 m long 1 1 1 1
T320
T320A
BRUSHES
T314A T314 KIT-120-3/4 T313
www.erico.com
53
CADWELD
CADWELD
Mould
CH
Part No.
234733 234732 234734 232003 233366 225147 239887 226567 238039 233901 229737 225814 232996 223520 228682 226670 226083 227687 227549 223138 234735 239694 232537 237727 238544 238556 224800 222501 224150 221443 234740 239534 222122 221455 233795 234770 234760 234581 234585 234582 234588 234592 234593 234441 234444 234445 234447 234453 234454
Amm2 60
60 60 60 75 87,5 60
Section Bmm2
Sizes mm 30x2
30x2 30x2 30x2 25x3 25x3,5 30x2
1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
Remarks
Lug or tape to horizontal surface Lug or tape to horizontal surface Lug or tape to vertical surface Lug or tape to vertical surface Lug or tape to vertical surface
CG
CCP-BAK
CC
A
CF BW GR A B
CFP-BAK CFP-CAJ G-CFP-DAJ BWP-BAK GRC-P172-Y3 B-GRC-P143-Y3 GTC-P143-Y1 GTC-P143-Y2 GTC-P143-Y3 GTC-P143-Y4 GTC-P143-Y5 GTC-P172-Y1 GTC-P172-Y2 GTC-P172-Y3 GTC-P172-Y4 GTC-P172-Y5 GTC-P190-2G CPP-P143-BAK CPP-P172-BAK GEC-P128 GEC-P143 GFC-P143-Y3 GFC-P165-G2-B LAC-Y1-BAH LAC-Y1-CAJ LAC-Y2-BAH LAC-Y2-CAJ LAZ-Y3-BAK LAC-Y3-BAH LAC-Y3-BAJ LAC-Y3-CAJ LAC-L9-EAK-A BJC-BAK-CROW BYC-BAK-CROW
17,2 14,2 14,2 14,2 14,2 14,2 14,2 17,2 17,2 17,2 17,2 17,2 19 14,2 17,2 12,8 14,2 14,2 16,5 6,4 6,4 7,6 7,6 9,0 9,0 9,0 9,0 10,0
9,0 9,0 6,4 7,6 9,0 11,0 12,5 6,4 7,6 9,0 11,0 12,5 10,7 12,8 14,2 9,0 9,5
232,4 160,6 160,6 160,6 160,6 160,6 160,6 232,4 232,4 232,4 232,4 232,4 283,5 160,6 232,4 128,7 158 160,6 214 25 25 35 35 50 50 50 50 60 60 60
50 50 25 35 50 70 95 25 35 50 70 95 66,5 60 60 128,7 158 50 50 40 75 40 75 60 40 50 75 120 60 60 25 35 50 70 95 120 25 35 50 70 95 120 20x2 25x3 20x2 25x3 30x2 20x2 25x2 25x3 30x4 30x2 30x2
Single stranded cable to top of ground rod Single stranded cable to top of ground rod
B A
GT B CP A GE A GF
A B
A B B
30x2 30x2
Tape to ground rod Horizontal ground round to ground rod splice Horizontal stranded cable to ground or other rod splice Stranded cable to lug or tape
LA
1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
Crowsfoot with edgewise tape Crowsfoot with flat tape Single stranded cable to rebar
B A
RC B A RT
RCP-Y1 RCP-Y2 RCP-Y3 RCP-Y4 RCP-Y5 RCP-Y6 RTP-Y1 RTP-Y2 RTP-Y3 RTP-Y4 RTP-Y5 RTP-Y6
10-40 10-40 10-40 10-40 10-40 10-40 10-40 10-40 10-40 10-40 10-40 10-40
S-2904B S-2904B S-2904B S-2904B S-2904B S-2904C S-2904B S-2904B S-2904B S-2904B S-2904A S-3121 Batting
CADWELD
54
www.erico.com
CADWELD
Weld metal size required 90
90 90 65 65 65 65 90 115 90 90 90 115 115 90 90 115 115 115 115 90 115 150 150 90 115 32 45 32 45 90 45 45 65 90 115 200 45 45 65 90 90 90 45 45 90 90 90 115
FRAMES
L160 161000 B134 161740
L159
161020
B135
161780
L161
161010
L161A
161090
L160V
161660
SMK21
161080
M129
161030
SKK1
162070
M32
161060
Reference code L160 L159 L161 B134 B135 L161A L160V M129 M32 SMK21 SKK1
Part No. 161000 161020 161010 161740 161780 161090 161660 161030 161060 161080 162070 1 1 1 1 1 1 1 1 1 1 1
www.erico.com
55
CADWELD
Unit weight kg 1,185 1,325 0,380 0,360 0,414 1,010 1,775 0,315 0,880 0,670 0,500
CADWELD
RASP
25 25 25
COPPER SLEEVES
Available on Request
Reference code H101 H102 H103 H104 H105 H107 H108 H109 H113 H115 H117
Part No. 180140 180170 180180 180190 180230 180690 180010 180020 180350 180700 180430
C mm 26 25 25 26 23,5 26 26 26 26 25 25
50 50 50 50 50 50 50 50 50 50 50
Unit weight kg 0,005 0,004 0,006 0,013 0,003 0,008 0,014 0,010 0,007 0,003 0,006
SCRAPER TOOLS
Equivalent Ref. Code TP5A, TP3A, TP5B TP2A, TP6A, TP7A TP4A
1 1 1
11200327
11200300
WRAP SLEEVE
Unit weight kg 0,260 0,100
CADWELD
Dimensions mm 76x25x0,20
25
56
www.erico.com
CADWELD
SLEEVES
TOOLSET
Length + flair B C A
Available on Request
Reference code Reference code H101F H102F H103F H104F H106F H107F H108F H109F H111F H112F H113F H114F H116F H117F H104BF H106AF H109AF H111AF H113AF Part No. 180150 180390 180380 180200 180250 180270 180280 180300 180320 180340 180360 180040 180740 180080 180220 180260 180310 180330 180030 A mm 8 6,4 7,7 19 17 11 20 14 15 12 10 25 13 9 19 17 14 15 10 B C mm mm 6 25 4,3 25 5,3 25 17 25 15 25 9 25 18 25 12 25 13 25 10 25 8 25 21 25 11,5 25 7 25 17 34 15 34 12 34 13 34 8 34 Length + flair 26 26 26 26 26 26 26 26 26 26 26 26 26 26 35 35 35 35 35 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 Unit weight kg 0,005 0,004 0,006 0,013 0,009 0,008 0,014 0,010 0,011 0,008 0,007 0,032 0,007 0,006 0,018 0,012 0,013 0,014 0,009 TS-CSTP
TOOL BOXES
T396
www.erico.com
57
CADWELD
Reference code
CPD-2440 CTR-10 CCR-68-S CCR-68-CU CCR-68-GS ASL-240-CC ARC-2205-CNC ARC-2210-CNC ER1-2000 ER1-ARCC-SS ER2-2000 ER3-2000 TFS 800 ARC-2205-SS ARC-2210-SS ASB-TCA ASP-100-TS ASA-TB ABFF-6530-TC ABFR-6530-TC ASFR-C ATR-10-SS ACB-10-SS AEM-10-SS CCI-70-CA PCF-40-GS PCR-21-GS IP-900-C IP-R193x122MM IP-SQ-180CI SRL23-N6 SRL-23-N8 SRL-23-N10 R1-SRL-25A6 R1-SFT-25 R2-SRL-25 R2-SFT-25 R3SFT-25 R6-SRL-40/6 R6-SFT-40 T1-SRL-25/6 T1-SFT-25 SFR-BC-8 SFT-BE SFT-BC SFRR-SRL-45/6 SFRR-SFT-45 SFRR-SFT-65 SPC-5080-S SPC-70120-S SPC-130180-S SPC-5080-C SPC-70120-C SPC-130180-C SGR-610-2 SDH-3-GI SSF-6-GS SSF-6-C STBF-25-GS STBF-40-GS SFT-23-N SFTP-23-N MPSC404SS FMCDMV01 SCDM01 11200327 11200330 1,2M38 1,5M38 2,1M38 3,0M38 1,2M12 1,5M12 2,1M12 3,0M12 S1,2M916 S1,5M916 S2,1M916 S3,0M916 1,2M58 1,5M58 2,1M58 3,0M58 S1,2M58 S1,5M58 S2,1M58 S3,0M58 1,2M34 1,5M34 2,1M34 3,0M34 S1,2M34 S1,5M34 S2,1M34 S3,0M34 C19 C20 CC12F CC58 CC34 SC916 SC58 SC34 DT12 DT58
Page
41 29 29 29 29 23 24 24 23 19 23 23 23 24 24 24 24 24 24 24 24 25 25 25 27 27 27 39 39 39 28 28 28 27 27 27 27 28 28 28 28 28 29 29 29 28 28 28 40 40 40 40 40 40 40 27 39 39 39 39 28 28 38 51 51 56 56 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 38 38 35 35 35 35 35 35 35 35
Part No.
158080 158090 158100 158110 158120 158130 158140 158155 158160 158165 158170 158175 158185 158250 158260 158290 158380 158400 158410 158440 158450 158500 158510 158520 158530 158540 158550 158610 158675 158690 158710 158720 158730 158760 158770 158780 158810 158922 161000 161010 161020 161030 161060 161080 161090 161660 161740 161780 162070 162230 162630 163000 163010 163020 163030 163040 163050 163060 163070 163080 163090 163200 163210 163220 163230 163240 163250 163260 163270 163590 163670 165000 165010 165020 165040 165130 165180 165220 165230 165260 165270 165280 165400 165410 165610 165620 165700 165700 165701 165701 165702 165702 165703 165703 165704 165704 165705 165705 165706 165706 165707 165707 165708 165708 165709
Reference code
DT34 DS916 DS58 DS34 DH12 DH58 DH34 CP38 C58 CP58 C34 CP34 SP58 C1 C12 PT-58-50/300 DH-TR167 DT-P137-1-20 RTC1 S-136-20 MR127Z/20 EGRD58 EGRD58L EGRD34 EGRD34L 15SS20 DT-P11-20-SS PT-12-25/300 PT-58-25/300 PT-58-35/300 1,0CG50/5 1,5CG50/5 2,0CG50/5 1,0CG50/3 1,5CG50/3 2,0CG50/3 1,5SG20 WGRS200 L160 L161 L159 M129 M32 SMK21 L161A L160V B134 B135 SKK1 B-162-12KS T321C (complete) 25 32 45 65 90 115 150 200 250 500 CA15 CA25 CA32 CA45 CA65 CA90 CA115 CA150 15 GEM T320 T320A B265 T313 T314 B165 B166 B167 KIT-120-3/4 T314A T403 B2618B B2610A B140 B2671A 15PLUSF20 15PLUSF20 25PLUSF20 25PLUSF20 32PLUSF20 32PLUSF20 45PLUSF20 45PLUSF20 65PLUSF20 65PLUSF20 90PLUSF20 90PLUSF20 115PLUSF20 115PLUSF20 150PLUSF20 150PLUSF20 200PLUSF20 200PLUSF20 250PLUSF20
Page
35 35 35 35 35 35 35 38 38 38 38 38 38 38 38 36 37 37 38 38 37 38 38 38 38 37 37 36 36 36 37 37 37 37 37 37 37 39 55 55 55 55 55 55 55 55 55 55 55 43 56 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 39 53 53 56 53 53 42 42 42 53 53 56 41 41 56 41 49 50 49 50 49 50 49 50 49 50 49 50 49 50 49 50 49 50 49
Part No.
165709 165710 165710 165711 165711 165712 165712 165713 165713 165714 165714 165715 165715 165716 165716 165717 165717 165738 165738 165739 165739 165745 165745 165746 165746 166000 166010 166020 166030 166040 166050 166060 166070 166080 166090 166100 166110 166120 166130 166140 166150 166160 166170 166180 166190 166200 166210 166220 166510 166520 166530 166540 166550 166560 167782 167900 167901 167902 167903 167904 167905 167906 180010 180020 180140 180170 180180 180190 180230 180350 180430 180690 180700 182125 182130 182135 185010 185020 185030 197650 197710 197720 197810 197860 197870 197900 197910 197920 197930 197940 197950 197970 197975 198000 198010 198020 198050 198060 198070 198080 198090 198150 198160 198200 198210
Reference code
250PLUSF20 300PLUSF20 300PLUSF20 400PLUSF20 400PLUSF20 500PLUSF20 500PLUSF20 CA15PLUSF33 CA15PLUSF33 CA25PLUSF33 CA25PLUSF33 CA32PLUSF33 CA32PLUSF33 CA45PLUSF33 CA45PLUSF33 CA65PLUSF33 CA65PLUSF33 PLUSCU PLUSCU PLUSCULD PLUSCULD PLUSCU15L PLUSCU15L PLUSCULD15 PLUSCULD15 B161-8A B161-8K B161-8KS B161-10B B161-10KA B161-10KM B164-12A B164-12K B164-12KS DB-8A DB-8K DB-8KS DB-10A DB-10K DB-10KS DB-12A DB-12K DB-12KS DB-16A DB-16K DB-16KS B-162-12A B-162-12K B161-10-C5005 B161-10-C501 B161-10-C502 B-162-12-C5005 B-162-12-C501 B-162-12-C502 KITCDMV01 SRGBC120 SRGBD100 SRGBE100 SRGBF100 SRGBG100 SRGC46 SRGC46BR H108 H109 H101 H102 H103 H104 H105 H113 H117 H107 H115 B136A B136B B136F S2904A S2904B S2904C TC-EC-3020-30 TC-ECT-3020-30 TC-ECT-2530-30 30TC-HGSP-3035 RSCC-8 RSCC-10 SC-EC-25 SC-EC-35 SC-EC-50 SC-EC-70 SC-EC-95 SC-EC-185 TC-ECT-4030-30 TC-ECT-4040-35 IC-EC-25 IC-EC-35 IC-EC-50 IC-ECH-25 IC-ECH-35 IC-ECH-50 IC-ECH-70 IC-ECH-95 RC-EC-6 RC-EC-8 RC-ET-6 RC-ET-8
Page
50 49 50 49 50 49 50 49 50 49 50 49 50 49 50 49 50 49 53 49 53 49 53 49 53 43 43 43 43 43 43 43 43 43 43 43 43 43 43 43 43 43 43 43 43 43 43 43 43 43 43 43 43 43 51 31 31 31 31 31 31 31 56 56 56 56 56 56 56 56 56 56 56 56 56 56 56 56 56 30 30 30 32 32 32 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 31 31 31 31
Part No.
198250 198400 198401 198402 198403 198404 198406 198407 198408 198410 198411 198420 221004 221006 221008 221009 221011 221013 221014 221021 221025 221028 221035 221051 221053 221063 221075 221135 221138 221142 221148 221153 221159 221256 221258 221265 221268 221403 221404 221405 221407 221443 221455 221466 221534 221603 221607 221609 222115 222122 222459 222461 222463 222501 222560 222689 222939 223044 223076 223138 223432 223520 223550 223609 223943 224123 224150 224800 224815 225026 225147 225788 225814 226083 226545 226567 226670 227549 227687 228347 228521 228682 229737 230199 231342 231692 232003 232537 232556 232648 232933 232996 233366 233795 233901 234398 234426 234429 234441 234444 234445 234447 234453 234454 234581
Reference code
RAW-8 A822SA111C-5 FC073 FC074 FC075 FC076 FC078 FC079 FC080 A822SA111C-10 FC082 A822SA111C-20 SSC-Y1 SSC-Y2 SSC-W6 SSC-Y3 SSC-W8 SSC-Y5 SSC-Y6 SSC-Y4 TAC-Y1 TAC-Y2 TAC-Y4 TAC-Y7 TAC-Y8 TAC-Y2-Y1 TAC-Y4-Y2 XAC-Y1 XAC-Y2 XAC-Y3 XAC-Y4 XAC-Y5 XAC-Y6 PTC-Y5 PTC-Y4 PTC-Y3 PTC-Y1 VSC-Y6 VSC-Y5 VSC-Y4 VSC-Y3 LAC-Y2-CAJ LAC-Y3-CAJ HAA-Y1-CA HAA-Y4 HAA-Y3 HAA-Y2 HAA-Y1 PTC-Y6 LAC-Y3-BAJ TAC-Y3 TAC-Y5 TAC-Y6 LAC-Y1-CAJ PCC-Y3 HAA-A3 VGC-Y3 HBA-B3 VGC-Y5 GTC-P190-2G G-EBP-DAJ GTC-P143-Y5 PCC-Y1 VGC-Y6 PGC-Y5 G-BMP-DAJ LAC-Y2-BAH LAC-Y1-BAH VGC-Y2 TAC-Y5-Y6 G-CFZ-DAJ EBP-BAK GTC-P143-Y3 GTC-P172-Y3 PTC-Y2 GRC-P172-Y3 GTC-P172-Y2 GTC-P172-Y5 GTC-P172-Y4 VGC-Y4 VGC-Y1 GTC-P172-Y1 GTC-P143-Y2 PCC-Y6 PGC-Y4 PGC-Y6 CFZ-BAK GEC-P128 PGC-Y2 PGC-Y3 LJP-Y3-FAM GTC-P143-Y4 CFZ-CAJ LAC-L9-EAK-A GTC-P143-Y1 EB-BGP-BAK BMP-CAJ BMP-BAK RTP-Y1 RTP-Y2 RTP-Y3 RTP-Y4 RTP-Y5 RTP-Y6 RCP-Y1
Page
32 41 41 41 41 41 41 41 41 41 41 41 52 52 52 52 52 52 52 52 52 52 52 52 52 52 52 52 52 52 52 52 52 52 52 52 52 52 52 52 52 54 54 52 52 52 52 52 52 54 52 52 52 54 52 52 52 52 52 54 52 54 52 52 52 52 54 54 52 52 54 52 54 54 52 54 54 54 54 52 52 54 54 52 52 52 54 54 52 52 52 54 54 54 54 52 52 52 54 54 54 54 54 54 54
58
www.erico.com
Reference code
RCP-Y3 RCP-Y2 RCP-Y4 RCP-Y5 RCP-Y6 CGP-BAK CHP-BAK CCP-BAK CPP-P143-BAK BMP-CAJ-BAK LJP-Y1-BAK LJP-Y2-BAK LJP-Y3-BAK LAZ-Y3-BAK LEP-Y3-BAK BYC-BAK-CROW BJC-BAK-CROW LWP-Y3-BAK EBP-CAJ PGC-Y4-Y1 GEC-P143 PGC-Y1 B-GRC-P143-Y3 GFC-P143-Y3 GFC-P165-G2-B LAC-Y3-BAH CPZ-P172-BAK BWZ-BAK HAA-B3-CA CDMV0134 CDMV0158 CDMV0112 CDMV01H ALUM 3ME MBMAST3ME GF-302 WM3-2088-B WM2-1030-B WM3-1020-B WM2-1020-B WMS-1030-B PC2.-1020 PC3-0909 DLUNI SEB-GER-08 SEB-06 SEB-06-DL SEB-10 SEB-10-DL SEB-62-DL BEP25x5x200 BEP25x5x300 CCS-308 CCG-308 SEP TC-ECT-3020-75 RC-EC-8-3 SR CCFR-308 BEP25x5x150 HDB5010 MBJ 16-100-8 MBJ 16-150-8 MBJ 16-200-8 MBJ 16-250-8 MBJ 16-300-8 MBJ 25-100-10 MBJ 25-150-10 MBJ 25-200-10 MBJ 25-250-10 MBJ 25-300-10 MBJ 30-100-10 MBJ 30-150-10 MBJ 30-200-10 MBJ 30-250-10 MBJ 30-300-10 MBJ 35-100-10 MBJ 35-150-10 MBJ 35-200-10 MBJ 35-250-10 MBJ 35-300-10 MBJ 50-100-10 MBJ 50-150-10 MBJ 50-200-10 MBJ 50-250-10 MBJ 50-300-10 MBJ 16-500-8 MBJ 25-500-10 MBJ 30-500-10 MBJ 35-500-10 MBJ 50-500-10 MBJ 16-200-6 MBJ 16-300-6 MBJ 25-200-6 MBJ 50-200-6 MBJ 50-200-16 MBJ 50-200-18 MBJ 50-300-16 MBJ 50-300-18 MBJ 25-200-12 MBJ 50-200-12 MBJ 16-100-6 MBJ 16-150-6 MBJ 50-500-12 MBJ 35-250-25
Page
54 54 54 54 54 54 54 54 54 52 52 52 52 54 52 54 54 52 52 52 54 52 54 54 54 54 54 54 52 51 51 51 51 18 18 39 31 31 31 31 31 31 31 40 40 40 40 40 40 40 39 39 27 27 40 30 31 27 27 39 31 42 42 42 42 42 42 42 42 42 42 42 42 42 42 42 42 42 42 42 42 42 42 42 42 42 42 42 42 42 42 42 42 42 42 42 42 42 42 42 42 42 42 42 42
Part No.
591080 591230 591280 591290 700001 700002 700003 700004 700005 700006 700310 700355 700360 700405 700410 700455 700528 700529 700531 700746 700805 700815 700850 700860 701000 701030 701280 701305 701315 701320 701340 701350 701360 701370 701380 701390 701410 701420 701460 701535 701536 701537 701540 701840 701875 701895 701915 701990 702005 702030 702045 702050 702065 702085 702089 702090 702165 702175 702180 702230 702240 702250 702255 702260 702265 702270 702275 702280 702285 702290 702295 702296 702297 702298 702299 702301 702306 702400 702407 702408 702411 702412 702413 702417 702418 702420 702426 702428 702429 702460 702465 702478 702491 702496 702506 702521 702525 702530 702535 702560 702566 702581 702591 702601 702721
Reference code
CEI20 FEI20 BEI20 42014 TDF3A120V TDF3A240V TDF10A120V TDF10A240V TDF20A120V TDF20A240V CSP NMF 90 CSP NMF 600 CSP BNC 90 CSP BNC 600 CSP NB 90 CSP NB 600 LANRJ45C6 LANRJ45POE LANRJ45RAK CATV HF HSP10K36 HSP10K12 HSP10K72 HSP10K230 DSF6A 30V DSF6A 275V GUYRING GUYKIT 4MGRIP GUYKIT 7MGRIP I/LCOUPL MBMAST4M MBMAST5M MBMAST6M ALUM 4M ALUM 5M ALUM 6M CONSAD/FX CABTIE-SS UBOLT SI25 SI40 SI65 SLP10K1F THERMLUGCOUPL ERICORE/PER M ERICORE/TRM/IS ERICORE/TRM/OS CONSAD/E2 ERICORE/LT KITA FRP/2M/BLACK FRP/4.6M/BLACK LEC-IV 7000250S4 D/SMKIV-SS INTMKIV-SS DSF6A 30V TMC-SS ALOF1-GS LSEB 4554 WPC HSF R7-SFT-20 ER1-1000-SS ER1-2000-SS ER2-2000-SS ER2-3000-SS ER3-2000-SS ER3-3000-SS SG-AERIAL-302 ER2-BASE ER3-BASE INTCPT-ADBUTT INTCPT-ADF2BSPF INTCPT-ADF2NSP INTCPT-ADM3/4UNC INTCPT-ADM116UN INTCPT-ADM16 SGD1100 2S NE TDS1501SR277 TDS1501SR560 TDS11002SR240 TDS11002SR277 TDS11002SR560 TDS350TNC277 TDS350TT277 DSD1150 2SR 275 SGD125 1SR NE TDX100M277/480TT TDX200M277/480TT DSD160 1SR 275 DSD160 1SR 275M DSD140 1S 75 DSD140 1S 275 DSD140 M 275 DSD140 M 440 DSD140 1SR 275 CATV MF DSD140 1SR 440 CATV F DSD110 1S 275 DSD110 M 275 DSD340 TNC 275 A DSD340 TNS 275 A DSD340 TT 275 A DLT
Page
27 27 27 27 45 45 45 45 45 45 46 46 46 46 46 46 46 46 46 46 46 46 46 46 45 45 19 19 19 18 18 18 18 18 18 18 19 19 18 19 19 19 46 19 18 18 18 19 18 18 18 19 18 18 18 45 24 24 24 24 29 29 19 19 19 19 19 19 24 19 19 19 19 19 19 19 19 45 46 46 46 46 46 46 46 45 45 46 46 45 45 45 45 45 45 45 46 45 46 45 45 45 45 45 46
Part No.
702861 702862 702863 702864 702866 702886 702887 702888 702889 702891 702900 702901 703000 710010 710020 710030 710040 710050 710060 710070 710080 710090 710090 710100 710110 710115 710120 710120 710130 710140 710150 710160 710170 710180 710190 710200 710210 710220 710230 710240 710250 710260 710290 710295 710300 710305 710325 710335 710345 710350 710355 710360 710365 710370 710380 710390 710400 710410 710420 710430 710440 710450 710510 710515 710535 710555 710560 710580 710595 710605 710615 710616 710620 710625 710630 710645 710655 710666 710667 710670 710680 710690 710700 710710 710730 710740 710750 710760 710770 710780 710790 710800 710810 710820 710830 710840 710850 710860 710870 710900 710920 710960 710965 710980 710990
Reference code
UTB5SP UTB15SP UTB30SP UTB60SP UTB110SP UTB5DP UTB15DP UTB30DP UTB60DP UTB110DP PEC100 PEC150 CCTV 12 SSR16 AAR0515 CTR-8CU CTR-8AL TECLP-8-CU TECLP-8-AL SCR15 SCR20 CDS15 CDS15 CDS20 PBD10 SSD10 SPK15 SPK15 SPK20 EBR-58 EBR-34 500-10-E-BOSS SFO50 PIT03 PC1.5-0606 PC3-0606 PC1.5-0909 OXINH1BCOMP EML663 EML993 ABBC BBBC PFC001 PFA001 GBH C GBH A RC70 RC100 RTC3020 RTC2051 EK16 RTC2526 EK17 UB16 UB20 UB25 GUV16070 GUV70185 RCC10 RCC16 SRC15 SRC20 TC-EC-2530-50 TC-EC-2530-25 TC-EC-2560-15 TC-EC-3850-10 TC-EC-3860-30 TC-EC-5060-20 CTBL253-25 CTBN253-25 LSF-253 CTGN253-25 CTGN256-30 LCT-253 CTGN506-30 CTGY253-25 CTST253-25 CTWH253-25 CTYGN253-25 HDB2003 HDB2503 HDB2506 HDB3806 HDB5006 THDB5060 FAT-253-50 ATBL253 ATBN253 ATGY253 ATST253 ATWH253 SCBL SCBN SCGY SCST SABL SABN SAGY SAST SC-EC-120 SC-EC-150 BAT-2560 BAT-5060 IC-ECH-120 IC-ECH-150
Page
46 46 46 46 46 46 46 46 46 46 42 42 46 37 23 29 29 40 40 36 36 36 36 36 36 37 36 37 36 42 42 41 42 39 31 31 31 42 31 31 40 40 25 25 26 26 41 41 38 38 41 38 41 38 38 38 38 38 39 39 39 39 30 30 30 30 30 30 30 30 30 30 30 31 30 30 30 30 30 31 31 31 31 31 31 32 32 32 32 32 32 31 31 31 31 32 32 32 32 30 30 32 32 30 30
Part No.
711000 711030 711040 711050 711060 711070 711080 711090 711100 711110 711120 711130 711140 711150 711160 711170 711180 711190 711195 711200 711210 711220 711230 711240 711250 711260 711270 711341 711342 711343 711344 711345 711346 711352 711360 711370 711380 711390 711400 711410 711430 711440 711450 711470 711480 711490 711500 711520 711530 711550 711570 711580 711590 711620 711660 711730 711760 711800 711810 711820 711830 711840 CC5A04 CC5A05 CC5A12 EHL12FC1K EHL12FC1K1K EHL12FC1V EHL12FC2G EHL34C1K EHL34C1V EHL34C2G EHL58C1K EHL58C1K1K EHL58C1V EHL58C2G EST3640 EST4610 EST4630 EST6472 IBTB SDT34 SDT58
Reference code
IC-ECH-185 AVG3.0 PC010A AAR0510 AAR1010 AAR1015 CAR0510 CAR0515 CAR1010 CAR1015 CMPR ATBA10 ATBA15 ATBC10 ATBC15 RSC115 ABR015 CBR015 ALD-TAP302 (10x4.8x2) TTRA16 TTRC16 DCC253 DCC256 DCC506 DCC600 DCC605 DCC610 PDCUCABBL PDCUCABBN PDCUCABGY PDCUCABST PDCUCABWH PDCUCABGN PDCUC PDC506BL PC008A PC008C PC010C STA253 STC253 OBA268 OCB268 PCT400 EBL08 BIM700 BIM800 BIM900 DT50 ASCO8 TAPA253 TAPC253 TAPC254 TAPC506 TAPS302 DCC316 DCA253 DCA600 HF250BN HF250GY HFP253BN HFP253GY HFP253ST CC5A04 CC5A05 CC5A12 EHL12FC1K EHL12FC1K1K EHL12FC1V EHL12FC2G EHL34C1K EHL34C1V EHL34C2G EHL58C1K EHL58C1K1K EHL58C1V EHL58C2G EST3640 EST4610 EST4630 EST6472 IBTB SDT34 SDT58
Page
30 27 26 23 23 23 23 23 23 23 23 23 23 23 23 23 23 23 28 23 23 25 25 25 25 25 25 25 25 25 25 25 25 25 25 26 26 26 26 26 26 26 26 41 26 26 26 42 32 25 25 25 25 28 25 25 25 26 26 26 26 26 32 32 32 36 36 36 36 36 36 36 36 36 36 36 36 36 36 36 41 35 35
www.erico.com
59
WARNING ERICO products shall be installed and used only as indicated in ERICO's product instruction sheets and training materials. Instruction sheets are available at www.erico.com and from your ERICO customer service representative. Improper installation, misuse, misapplication or other failure to completely follow ERICO's instructions and warnings may cause product malfunction, property damage, serious bodily injury and death. WARRANTY ERICO products are warranted to be free from defects in material and workmanship at the time of shipment. NO OTHER WARRANTY, WHETHER EXPRESS OR IMPLIED (INCLUDING ANY WARRANTY OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE), SHALL EXIST IN CONNECTION WITH THE SALE OR USE OF ANY ERICO PRODUCTS. Claims for errors, shortages, defects or nonconformities ascertainable upon inspection must be made in writing within 5 days after Buyer's receipt of products. All other claims must be made in writing to ERICO within 6 months from the date of shipment or transport. Products claimed to be nonconforming or defective must, upon ERICO's prior written approval in accordance with its standard terms and procedures governing returns, promptly be returned to ERICO for inspection. Claims not made as provided above and within the applicable time period will be barred. ERICO shall in no event be responsible if the products have not been stored or used in accordance with its specifications and recommended procedures. ERICO will, at its option, either repair or replace nonconforming or defective products for which it is responsible or return the purchase price to the Buyer. THE FOREGOING STATES BUYER'S EXCLUSIVE REMEDY FOR ANY BREACH OF ERICO WARRANTY AND FOR ANY CLAIM, WHETHER SOUNDING IN CONTRACT, TORT OR NEGLIGENCE, FOR LOSS OR INJURY CAUSED BY THE SALE OR USE OF ANY PRODUCT. LIMITATION OF LIABILITY ERICO excludes all liability except such liability that is directly attributable to the willful or gross negligence of ERICO's employees. Should ERICO be held liable its liability shall in no event exceed the total purchase price under the contract. ERICO SHALL IN NO EVENT BE RESPONSIBLE FOR ANY LOSS OF BUSINESS OR PROFITS, DOWNTIME OR DELAY, LABOR, REPAIR OR MATERIAL COSTS OR ANY SIMILAR OR DISSIMILAR CONSEQUENTIAL LOSS OR DAMAGE INCURRED BY BUYER. Due to a policy of continuing product development, specifications are subject to change without notice.
ANSI is a registered trademark of American National Standards Institute CSA is a copyright of Canadian Standard Association International IEEE is a registered trademark of The Institute of Electrical and Electronics Engineers, Inc Krone-LSA is a registered trademark of Krone GmbH. NEC is a registered trademark of, and National Electrical Code (NEC) standard is a copyright of the National Fire Protection Association NFPA is a registered trademark of National Fire Protection Association UL is a registered trademark of Underwriters Laboratories, Inc.
60
www.erico.com
www.erico.com
AUSTRALIA
Phone 1-800-263-508 Fax 1-800-423-091
CHINA
Phone +86-21-3430-4878 Fax +86-21-5831-8177
HUNGARY
Phone 06-800-16538 Fax +39-0244-386-107
NORWAY
Phone 800-100-73 Fax 800-100-66
SWITZERLAND
Phone 0800-55-86-97 Fax 0800-55-96-15
BELGIUM
Phone 0800-757-48 Fax 0800-757-60
DENMARK
Phone 808-89-372 Fax 808-89-373
INDONESIA
Phone +62-21-575-0941 Fax +62-21-575-0942
POLAND
Phone +48-71-349-04-60 Fax +48-71-349-04-61
THAILAND
Phone +66-2-267-5776 Fax +66-2-636-6988
BRAZIL
Phone +55-11-3623-4333 Fax +55-11-3621-4066
FRANCE
Phone 0-800-901-793 Fax 0-800-902-024
ITALY
Phone 800-870-938 Fax 800-873-935
SINGAPORE
Phone +65-6-268-3433 Fax +65-6-268-1389
CANADA
Phone +1-800-677-9089 Fax +1-800-677-8131
GERMANY
Phone 0-800-189-0272 Fax 0-800-189-0274
MEXICO
Phone +52-55-5260-5991 Fax +52-55-5260-3310
SPAIN
Phone 900-993-154 Fax 900-807-333
UNITED KINGDOM
Phone 0808-2344-670 Fax 0808-2344-676
CHILE
Phone +56-2-370-2908 Fax +56-2-369-5657
HONG KONG
Phone +852-2764-8808 Fax +852-2764-4486
NETHERLANDS
Phone 0800-0200-135 Fax 0800-0200-136
SWEDEN
Phone 020-790-908 Fax 020-798-964
UNITED STATES
Phone 1-800-753-9221 Fax +1-440-248-0723
Copyright 2008, 2009, 2010 ERICO International Corporation. All rights reserved. CADDY, CADWELD, CRITEC, ERICO, ERIFLEX, ERITECH, and LENTON are registered trademarks of ERICO International Corporation.
E905C-EUEN
E1197CT10EUEN
6M0910