Grounded capacitor banks can interfere with a facilities ground fault protection system and cause the entire facility to lose power (main breaker trip). Harmonic currents in the ground path can cause harmonic interference with control and communication systems. Capacitor discharge currents may damage nearby surge arresters.
Interference with a facilities ground fault protection system is the primary reason for not grounding a capacitor bank or harmonic filter bank. Although this interference can be reduced or eliminated through system modification, it may require protective coordination analysis, relay changes and/or grounding resistor changes. This adds cost and complexity to the installation and may degrade the sensitivity of the existing ground fault protection system. This bulletin describes how a grounded capacitor bank can interfere with a facilities ground fault protection system and suggest that all banks applied on industrial and commercial power systems be left ungrounded.
Figure 1 - Typical industrial facility showing ground fault protection system, failed capacitor, and fault current path for a failed capacitor .
Background
In general, most industrial facilities with 2.4kV through 13.8 kV distribution are resistive grounded through a grounding resistor as shown in Figure 1. The systems are resistive grounded to reduce the fault current and arc damage during line to ground faults. This is particularly true for systems with directly connected motors. The resistor typically has a 10 second ampere rating (continuous and 60 second ratings are also available, but are not typical) that is approximately equal to the ground current that would flow if a line to ground fault should occur. The continuous current rating of a 10 second resistor is much less than the 10 second rating. For example, a 200 amp 10 second resistor may have a continuous rating of 50 amps. For this reason, the ground fault relay, device 51G, is typically set to pick up at approximately 10% of the resistor rating or 20 amps. This protects the resistor from un-cleared feeder faults and other system abnormalities that may damage the resistor.
http://www.nepsi.com/grnd_new.htm
7/17/2008
Page 2 of 4
Solidly Grounded
http://www.nepsi.com/grnd_new.htm
7/17/2008
Page 3 of 4
Systems
Although most commercial and industrial power systems are resistive grounded, there are situations where they may be solidly grounded. This may be due to the design engineers preference or because the facility is directly connected to the utility distribution system. The same possibility as describe above exist for systems that are connected to the utility through a solidly grounded step down transformer, but is less likely because the ground fault currents are much higher, and the current limiting fuse is much quicker at the higher current levels. This can be seen in Figure 2. Typically ground faults would be on the order of 7000 to 20,000 amps on these systems, and coordination could be achieved. Coordination, however should be checked, since a plant shut down can be quite costly.
Figure 3 - Ground fault current path when industrial is connected directly to utility distribution feeder. The facility may or may not have ground fault relays on the service entrance conductors. If relays are present, the ground fault relay would be a residually connected overcurrent relay or a 51N device. These relays are typically not set as low as the 51G device due to error currents in the phase relays. Facilities strive for minimum allowable pickup settings, and therefore coordination should still be checked as was done in Figure 2. For utilities that utilize a uni-grounded system or an ungrounded system, the utility should be consulted to determine if the capacitor bank grounding will interfere with their system. Ground relays on Uni-grounded utility distribution system may be set low enough to pickup. Ungrounded system raise an unrelated concern with overvoltages from uncleared ground faults.
Conclusion
With the forgoing discussion it should be clear that the installation of grounded capacitor banks to industrial and commercial power system can interfere with a facilities ground fault protection system. Proper engineering may be done to overcome these problems, but this adds to the cost and complexity of the installation. The negative issue associated with ungrounded capacitor banks are as follows: Fuse coordination is difficult on smaller banks because a failed capacitor will only draw three times the banks nominal current rating. Overvoltage conditions can occur on the unfaulted capacitors on unbalance banks due to a fuse blowing. This condition can be eliminated by changing the number of capacitors , isolating neutral connections, and/or by adding a neutral unbalance detection scheme to the bank. The above issues can be engineered out of the design by the manufacturer without any regard to the system for which it is being applied to. This puts the responsibility with the manufacturer and not the facilities engineer or design engineer working on the capacitor bank installation. NEPSIs bulletin on Neutral Voltage Unbalance Protection provides further information on the above material.