Mfac14-High Impedance Differential Relay

Download as doc, pdf, or txt
Download as doc, pdf, or txt
Download as doc, pdf, or txt
You are on page 1/ 2

Customer Contract

Location #
Project
Contractor
AREVA T&D Site test record RELAY TEST Doc. Ref.

MFAC14- HIGH IMPEDANCE DIFFERENTIAL RELAY


1. GENERAL DATA AND INFORMATION:
Circuit Ref. Designation
Panel No. Serial No.
Make Model No.
Dwg & Sh No. Frequency:
Flag Type No. of Contacts
Setting range:

2. MECHANICAL CHECKS AND VISUAL INSPECTION:


ITEM DESCRIPTION CHECKED
1 Inspect for any physical damage or defects.
2 Verify connections as per approved drawings.
3 Check that serial no. of relay matching with serial no. of case.
4 Relay CT shorting function checked.
5 Test switch checked for correct function.

3. ELECTRICAL TESTS:
3.1 PICKUP / DORP OFF TEST:
Injection done including METROSIL resistor.
Pick up Drop off
Voltage Pick up % Drop off / Pickup current limit
Voltage Voltage
setting (V) current (mA) pick up ratio (mA)
(Volts) (Volts)
25 18-20

50 18-20

75 18-23

100 19-28

125 20-39

150 24-60

175 33-95

Plug removed 33-95


Note : pickup voltage +/-10% setting, D/O and P/U ratio >50%.
3.2 OPERATING TIME TEST:
Setting voltage Applied voltage Measured operating time in
Limits
(V) 2xsetting (V) msec
Between 15-30 msec
(Max. to min. setting respectively)
(Refer graph)

Test performed by Test witnessed by Date of test


AREVA T&D
Name MUSTAFA HAJI

Signature
Customer Contract
Location #
Project
Contractor
AREVA T&D Site test record RELAY TEST Doc. Ref.

MFAC14- HIGH IMPEDANCE DIFFERENTIAL RELAY


3.3 FINAL SETTING TESTS:
3.3.1 PICKUP / DORP OFF TEST:
Pick up current Pick up Voltage Drop off Voltage % Drop off / pick up
Voltage setting (V)
(mA) (Volts) (Volts) ratio

Note : pickup voltage +/-10% setting, D/O and P/U ratio >50%.

3.3.2 OPERATING TIME TEST:


Applied voltage 2xsetting Measured operating time
Setting voltage (V) Limits
(V) in msec
Between 15-30
msec
(Max. to min.
setting respectively)
(Refer graph)

4. FUNCTIONAL TESTS:
Item Description Checked
1 All output contacts resistance measured.
2 Flag operation checked.
3 Check metrosil non-linear resistors connection

Test performed by Test witnessed by Date of test


AREVA T&D
Name MUSTAFA HAJI

Signature