MFAC14 Application Guidance
MFAC14 Application Guidance
Application Guide
High Stability Circulating Current Relay
Publication Reference:
- ALSTOM 2013. All rights reserved. Information contained in this document is indicative only. No representation or warranty is given or should be relied on that it
is complete or correct or will apply to any particular project. This will depend on the technical and commercial circumstances. It is provided without liability and is
subject to change without notice. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.
R6136D
Application Guide
CONTENTS
INTRODUCTION
1.1
The MCAG14/34
3
4
1.1.1
1.1.2
1.1.3
5
6
7
12
12
2.1.1
2.1.2
Voltage setting
Current transformer requirements
12
13
2.2
13
2.2.1
2.2.2
2.2.3
2.2.4
Stability voltage
Stabilising resistor
Current transformer requirements
Metrosil non-linear resistor requirements
13
14
14
15
2.3
16
2.3.1
2.3.2
2.3.3
2.3.4
Stability voltage
Stabilising resistor
Current transformer requirements
Metrosil non-linear resistor requirements
17
17
18
18
R6136D
Application Guide
R6136D
Application Guide
INTRODUCTION
The application of the MCAG14/34 and MFAC14/34 relays to the protection of machines, power
transformers and busbar installations is based on the high impedance differential principle, offering
stability for any type of fault occurring outside the protected zone and satisfactory operation for faults
within the zone
A high impedance relay is defined as a relay or relay circuit whose voltage setting is not less than the
calculated maximum voltage which can appear across its terminals under the assigned maximum
through fault current condition.
It can be seen from Figure 1, that during an external fault the through fault current should circulate
between the current transformer secondaries. The only current that can flow through the relay circuit
is that due to any difference in the current transformer outputs for the same primary current. Magnetic
saturation will reduce the output of a current transformer and the most extreme case for stability will be
if one current transformer is completely saturated and the other unaffected. This condition can be
approached in busbar installations due to the multiplicity of infeeds and extremely high fault level. It is
less likely with machines or power transformers due to the limitation of through fault level by the
protected units impedance, and the fact that the comparison is made between a limited number of
current transformers. Differences in current transformer remanent flux can, however, result in
asymmetric current transformer saturation with all applications.
P4690ENa
RCTB 2 RL , the relay will be prevented from undesirable operation, as most of the current will pass
through the saturated current transformer.
To achieve stability for external faults, the stability voltage for the protection Vs must be determined
in accordance with formula 1 for the MCAG and MFAC. The setting will be dependent upon the
maximum current transformer secondary current for an external fault f and also on the highest
R6136D
Application Guide
loop resistance value between the current transformer common point and any of the current
transformers RCT 2 RL .
Vs f RCT 2 RL
________
RL = maximum lead resistance from the current transformer to the common point
Note:
When high impedance differential protection is applied to motors or reactors, the external fault
current will be low. Therefore, the locked rotor current or starting current of the motor, or reactor
inrush current, should be used in place of the external fault current.
To ensure satisfactory operation of the relay under internal fault conditions the current transformer
kneepoint voltage should not be less than twice the relay voltage setting i.e. VK 2VS for the MCAG
and MFAC.
The kneepoint voltage of a current transformer marks the upper limit of the roughly linear portion of the
secondary winding excitation characteristic and is defined exactly in British practice as that point on
the excitation curve where a 10% increase in exciting voltage produces a 50% increase in exciting
current.
The current transformers should be of equal ratio, of similar magnetising characteristics and of low
reactance construction. In cases where low reactance current transformers are not available and high
reactance ones must be used. It is essential to use in the calculations for the voltage setting, the
reactance of the current transformer and express the current transformer impedance as a complex
number in the form RCT jX CT . It is also necessary to ensure that the exciting impedance of the
current transformer is large in comparison with its secondary ohmic impedance at the relay setting
voltage.
1.1
The MCAG14/34
The MCAG14/34 is an electromechanical current calibrated relay with setting ranges of:
0.025 - 0.100A
0.050 - 0.200A
0.100 - 0.400A
0.200 - 0.800A
0.250 - 1.00A
0.500 - 2.00A
1.00
- 4.00A
The relay has a fixed burden of approximately 1VA at setting current and its impedance varies with the
setting current used. To comply with the definition for a high impedance relay, it is necessary, in most
applications, to utilise an externally mounted stabilising resistor in series with the relay coil.
The standard ratings of the stabilising resistors normally supplied with the relay are 470220and
47for 0.5A, 1A and 5A current transformer secondary respectively. In applications such as busbar
protection, where higher values of stabilising resistor are often required to obtain the desired relay
voltage setting, non-standard resistor values can be supplied. The standard resistors are wire wound,
continuously adjustable and have a continuous rating of 145W.
R6136D
1.1.1
Application Guide
current r , the number of current transformers in parallel with a relay element n and the
magnetising current of each current transformer e at the stability voltage Vs . This relationship
can be expressed in three ways:
To determine the maximum current transformer magnetising current to achieve a specific primary
operating current with a particular relay operating current.
1x op
r
n CT ratio
To determine the maximum relay current setting to achieve a specific primary operating current with a
given current transformer magnetising current.
op
r
n e
CT ratio
To express the protection primary operating current for a particular relay operating current and with a
particular level of magnetising current.
op CT ratio x r n e
To achieve the required primary operating current with the current transformers that are used, a
current setting r must be selected for the high impedance relay, as detailed in the second
RST
Note:
Vs
Rr
Ir
The MCAG14/34 is a fixed burden relay, therefore the ohmic impedance of the relay will vary with
setting. The ohmic impedance
r ; Rr
B
I 2r
The stabilising resistor supplied is continuously adjustable up to its maximum declared resistance. In
some applications, such as generator winding differential protection, the through fault current is low
which results in a low stability voltage setting. In many such cases, a negative stabilising resistor
value can be obtained from the above formula. This negative result indicates that the relay will be
more than stable without a stabilising resistor. When a stabilising resistor is not required, the setting
R6136D
Application Guide
voltage
VSA can be calculated using the following formula and the current transformer kneepoint
VSA
1.1.2
B
Ir
V p 2 2 V K V f V K
V f f RCT 2 RL RST Rr
Where
V = C 0 .25
Where V = instantaneous voltage applied to the non-linear resistor (metrosil)
R6136D
Application Guide
Vsrms x 2 4
rms 0.52
Where Vs rms = rms value of the sinusoidal voltage applied across the metrosil
This is due to the fact that the current waveform through the nonlinear resistor (metrosil) is not
sinusoidal but appreciably distorted. For satisfactory application of a non-linear resistor (metrosil), its
characteristic should be such that it complies with the following requirements:
At the relay voltage setting, the nonlinear resistor (metrosil) current should be as low as possible, but
no greater than approximately 30mA rms for 1A current transformers and approximately 100mA rms
for 5A current transformers.
At the maximum secondary current, the non-linear resistor (metrosil) should limit the voltage to 1500V
rms or 2120V peak for 0.25 second. At higher relay voltage settings, it is not always possible to limit
the fault voltage to 1500V rms, so higher fault voltages may have to be tolerated.
1.1.3
SH
VS
RSH
The increased primary operating current with the shunt resistor connected is:
op CT ratio x r n e I SH
Setting range: 25-175V
R6136D
Setting Voltage
25
50
75
100
125
150
175
Ir (mA)
19
19
20
23
27
36
53
Application Guide
25
75
125
175
225
275
325
Ir (mA)
19
19
20
22
24
31
44
Figures 2 to 8 show how high impedance relays can be applied in a number of different situations.
P4691ENa
Figure 2: Phase and earth fault differential protection for generators, motors or reactors
P4692ENa
Figure 3: Restricted earth fault protection for a 3 phase, 3 wire system-applicable to star
connected generators or power transformer windings
R6136D
Application Guide
P4693ENa
Figure 4: Balanced or restricted earth fault protection for delta winding of a power transformer
with supply system earthed
P4694ENa
Figure 5: Restricted earth fault protection for 3 phase, 4 wire system-applicable to star
connected generators or power transformer windings with neutral earthed at
switchgear
R6136D
Application Guide
P4695ENa
Figure 6: Restricted earth fault protection for 3 phase 4 wire system applicable to star
connected generators or power transformer windings earthed directly at the star
point
P4696ENa
Figure 7: Phase and earth fault differential protection for an auto-transformer with CTs at the
neutral star point
10
R6136D
Application Guide
P4697ENa
Figure 8: Busbar protection - simple single zone phase and earth fault scheme
R6136D
11
Application Guide
2.1
2.1.1
Voltage setting
The power transformer full load current.
1000 x 103
3 x 415
1391A
Maximum through fault level (ignoring source impedance).
100MVA
x 1391
5%
27820 A
Required relay stability voltage (assuming one CT saturated).
f RCT 2 RL
27820 x
5
0.3 0.08
1500
35.2V
The next highest setting should be selected on the MFAC14, this being 50V.
P4698ENa
12
R6136D
2.1.2
Application Guide
VK 2Vs
2 x 50
100V
The exciting current to be drawn by the current transformers at the relay voltage setting, Vs will be:
s r
n
30
5
x 1391 x
100
1500
1.4 A
r relay setting
1A
n number of current transformers in parallel with the relay
4
1.4 0.02
4
0.345 A
e at 50V
As previously stated metrosils are always required with an MFAC. The metrosil type is chosen in
accordance with the maximum secondary current of 27820 x 5/1500 = 93A.
Therefore the metrosil reference is 600A/S2/P with a constant (C) of 620/740. (Please refer to
Metrosil publication for selection chart).
2.2
2.2.1
Stability voltage
The power transformer full load current.
1000 x 103
3 x 415
1391A
Maximum through fault level (ignoring source impedance).
R6136D
13
Application Guide
100MVA
x 1391
5%
27820 A
Required relay stability voltage (assuming one CT saturated).
f RCT 2 RL
27820 x
5
0.3 0.08
1500
35.2V
2.2.2
Stabilising resistor
Assuming that the relay effective setting for a solidly earthed power transformer is approximately 30%
of full load current, we can therefore, choose a relay current setting of 20% of 5A i.e. 1A. On this basis
the required value of stabilising resistor is:
RST
VS B
r 2r
35.2 1
2
1
1
34.2
5A rated MCAG14 relays are supplied with stabilising resistors that are continuously adjustable
between 0 and 47Therefore, a stabilising resistance of 34.2can be set using the standard
resistor.
2.2.3
VK 2Vs
2 x 35.2
70.4V
The exciting current to be drawn by the current transformers at the relay stability voltage, Vs , will be:
s r
n
5
30
x 1391 x
1500
100
1.4 A
r relay setting
1A
14
R6136D
Application Guide
e at 35.2V
2.2.4
V p 2 2 VK V f VK
Where VK = 70.4V (In practice this should be the actual current transformer kneepoint voltage,
obtained from the current transformer magnetisation curve).
V f f RCT 2 RL RST Rr
27820 x
5
x 0.3 0.08 34.2 1
1500
92.7 x 35.58
3298V
R6136D
15
Application Guide
Therefore substituting these values for VK and V f into the main formula, it can be seen that the peak
voltage developed by the current transformer is:
V p 2 2 VK V f VK
2.3
16
R6136D
Application Guide
I r = 0.1A
I f = 7.98A
P4699ENa
2.3.1
Stability voltage
The required relay stability voltage (assuming one CT saturated).
f RCT 2 RL
7.98 0.3 0.02
2.55V
Using the standard formula, this would lead to a CT VK requirement of 2 x 2.55 = 5.1V.
2.3.2
Stabilising resistor
RST
VS B
r 2r
2.55
1
0.1 0.12
74.5
The negative result indicates that the relay is more than stable without any stabilising resistor. With
the relay alone, the actual voltage setting can be calculated as follows:
VSA
B
r
1
0.1
10V
Consequently, if the formulae had been literally applied, a CT with a VK of 5.1V would not have been
sufficient to provide correct operation of the relay under fault conditions.
R6136D
17
Application Guide
2.3.3
VK 2Vs
2 x 10
20V
The exciting current to be drawn by the current transformers at the relay stability voltage, VS , will be
determined by the maximum tolerable protection primary operating current and is defined by:
op CT ratio x r n e
2.3.4
18
R6136D
PXXX
Product Description
Alstom Grid
- ALSTOM 2013. All rights reserved.
Information contained in this document is
indicative only. No representation or warranty
is given or should be relied on that it is
complete or correct or will apply to any
particular project. This will depend on the
technical and commercial circumstances. It is
provided without liability and is subject to
change without notice. Reproduction, use or
disclosure to third parties, without express
written authority, is strictly prohibited.
Alstom Grid Worldwide Contact Centre
www.alstom.com/grid/contactcentre/
Tel: +44 (0) 1785 250 070
www.alstom.com