BEF Calculation - Part 2 PDF
BEF Calculation - Part 2 PDF
The maximum voltage that can appear across the relay circuit can be determined by a simple calculation which
makes the following assumptions:
One current transformer is fully saturated making its excitation current negligible.
The remaining current transformers maintain their ratio.
The resistance of the secondary winding of the saturated CT together with the leads connecting it to the
relay circuit terminals constitute the only burden in parallel with the relay.
The minimum required relay operate voltage setting (Vs) is given by:
VS t IF (RCT RL ) u T (1)
To ensure high speed relay operation the relay circuit operating voltage should be selected in accordance with the
stability requirement above (equation 1), also, the operate voltage should not exceed 0.5 x CT knee point voltage
(Vk).
VK
VS d (2)
2
Rstab
CT
Circuits
NLR
7SR
Non-linear resistors are connected in parallel with the relay circuit to limit the peak voltage developed across the
high impedance components during internal faults to a ‘safe’ level below 3kV peak. Where a Metrosil is not
connected in circuit the peak voltage can be calculated from:
Notwithstanding the above calculation it is recommended that a Metrosil is always fitted in the high impedance
relay circuit.
The use of non-linear resistors manufactured by Metrosil is recommended. The operate characteristic is defined
by:-
Where an external Metrosil is used a single pole 7XG14 can be specified. Metrosils can be specified with a
diameter of 75mm or 150mm and ‘C’ values of 450, 900 or 1000. Metrosils of diameter 75mm have a thermal
rating of 8kJ. Where a higher thermal rating is required Metrosils of 150mm diameter with a thermal rating of 33kJ
should be used.
The 7SG23 relay has an integral 75mm Metrosil with a constant ‘C’ value = 1000.
All Metrosils have a ȕ value = 0.22 to 0.25
A ‘C’ value of 450 can be used where the relay operate voltage is less than 100V, a ‘C’ value of 1000 is
recommended for settings above 100V. These values have a negligible effect on the relay circuit operate
current.
4
P1SEC u IF u T u VK (10)
ʌ
2.2.5 Resistors
When the relay circuit operates for an internal fault the circuit breakers are opened and the flow of fault current
ceases. Where a CB fails to trip then fault current will flow in the high impedance circuit until the fault is cleared by
the operation of CB fail or back up protection. The fault clearance time for failed CB conditions should be
considered when specifying the thermal rating of the relay circuit components.
Alternatively the high impedance circuit can be arranged to short circuit the external components after operation.
Short time rated to withstand IFint for the maximum fault clearance time. For a failed circuit breaker
condition the back up protection clearance time is considered – typically a one second rating is sufficient.
VFint 2
P1SEC t Where: VFint t 4 (VK 3 x R x IFint) x 1.3 (11)
R
Where IFint is not known, the breaking capacity current of the Circuit Breaker can be used.
As stated in section 2.2.3 the 7SR relays have a stabilising resistor connected in series with the REF
current input. 7PG23 relays use a shunt connected resistor to increase the operate current where
required.
Settings Requirements
Rated current = VA / (¥3 x VL)
Rated current = 10 x 106 / (¥3 x 33000) = 175A
Assigned through fault current (rated stability limit) = 16 x rated current = 2.8kA. See section 2.2.1
Required Primary Operate Current
Typically 10 – 25% of protected winding rated current (Irated), or as specified by the user.
POCprov (10 – 25% of Irated) = 17.5 – 43.8A. Say 20A. (0.1A secondary). See section 2.2.2
Metrosil Specification
With reference to section 2.2.4
‘C’ Value
Vs = 48V (i.e. < 100V) so a ‘C’ value of 450 is chosen
PCONT t Is 2 x Rstab
PCONT t 0.08 2 x 600
PCONT t 3.8W
VFint 2
P1SEC t Where: V Fint t 4
(V K 3 x R stab x I Fint ) x 1.3
Rstab
2800
IFint 14A
200
VFint t 4 (VK 3 x Rstab x IFint) x 1.3
VFint t 4 (120 3 x 600 x 14 u 1.3 451V
2
451
P1SEC t 339 W
600