CSC 101 & CSC 162 Calculator

The document provides input data for setting protection relays for a 132kV transmission line. It includes line parameters such as impedance and length, load current, and required protection zones and settings. Calculations are shown to determine the settings for each protection zone based on the input data according to relay setting principles. The maximum expected load resistance is also calculated.

Uploaded by

Vaneet Gupta
Copyright
© Attribution Non-Commercial (BY-NC)
Available Formats
Download as XLS, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
296 views

CSC 101 & CSC 162 Calculator

The document provides input data for setting protection relays for a 132kV transmission line. It includes line parameters such as impedance and length, load current, and required protection zones and settings. Calculations are shown to determine the settings for each protection zone based on the input data according to relay setting principles. The maximum expected load resistance is also calculated.

Uploaded by

Vaneet Gupta
Copyright
© Attribution Non-Commercial (BY-NC)
Available Formats
Download as XLS, PDF, TXT or read online on Scribd
You are on page 1/ 10

Easun Reyrolle Limited, India

INPUT DATA for CSC 101 / CSC 162 Relays:


1 Voltage Level (KV)
2 PT Ratio
3 CT Ratio
4 Positive seq. Resistance(R1) / Km
5 Positive seq. Reactance(X1) / Km
6 Zero seq. Resistance(R0) / Km
7 Zero seq. Resistance(X0) / Km
8 Line Length (Km)
9 Maximum Load Current (Primary in A)
10 Operating Power Factor
11 Zone 1 Settings required in %
12 Zone 2 Settings required in %
13 Zone 3 Settings required in %
14 Zone 4 Settings required in %
15 Zero Seq. Mutual Reactance (Xm0)

Fill the following Data


132.0000
1200
400.0000
0.1540
0.3870
0.3030
1.4096
7.0000
400.0000
0.8600
80.0000
150.0000
400.0000
25.0000
0.0000

SETTINGS TO BE ADOPTED
(CT Secondary Rated : 1A, PT Secondary : 110V P-P)
1 KV, CTR, LL

( As It Is)

2 Kr

0.323

3 Kx

0.881

4 Km

0.000

5 R_Line

0.359

6 X_Line

0.903

7 R1_PE

0.722

8 X1_PE

0.722

9 R2_PE

1.894

10 X2_PE

1.355

11 R3_PE

5.049

12 X3_PE

3.612

13 R4_PE

0.316

14 X4_PE

0.226

15 R1_PP

0.722

16 X1_PP

0.722

17 R2_PP

1.894

18 X2_PP

1.355

19 R3_PP

5.049

20 X3_PP

3.612

21 R4_PP

0.316

22 X4_PP

0.226

23 Max Load Resistance Observed on Ohms

32.798

Note : Select the Resitance Value of the Z3 or Z4 such


that it should be less than the Max. Load Resistance
Calculated
Created By:
G.Mahendiran
Deputy Manager - Product Management
Easun Reyrolle Limited
Hosur, India - 635 126
Moile : +91 99524 25301.
Email : mahendiran@easunreyrolle.com
All Rights Reserved to M/s. Eaun Reyrolle Limited., Any
form of Reproduction of this copy is prohibited.

EASUN REYROLLE LIMITED, INDIA

INPUT DATA for CSC 101 / CSC 162 Relays:

INPUT

Voltage Level (KV)

132

PT Ratio

1200

CT Ratio

400

Positive seq. Resistance(R1) / Km

0.154

Positive seq. Reactance(X1) / Km

0.387

Zero seq. Resistance(R0) / Km

0.303

Zero seq. Resistance(X0) / Km

1.4096

Line Length (Km)

Maximum Load Current (Primary in A)

400

10

Power Factor

0.86

11

Zone 1 Settings required in %

80

12

Zone 2 Settings required in %

150

13

Zone 3 Settings required in %

400

14

Zone 4 Settings required in %

25

15

Zero Seq. Mutual Reactance (Xm0)

Zone 2 Ph-E Fault:


R2_pe

0.539

X2_pe

1.3545

max(x2_pe/2,25/LZ+R_line)
R2_pe derived (as per Manual)

8.692666667
0.539

X2_pe Rect

0.67725

Min(8*X2_Rect, R2_pe/4)

0.13475

R2_pe Rect

1.3545

R2_pe to be Set

1.8935

Zone 2 Ph-Ph Fault:


R2_pp

0.539

X2_pp

1.3545

max(x2_pp/2,15/LZ+R_line)
R2_pp derived (as per Manual)

5.359333333
0.539

X2_pp Rect

0.67725

Min(8*X2_Rect, R2_pp/4)

0.13475

R2_pp Rect

1.3545

R2_pp to be Set

1.8935

Zone 4 Ph-E Fault:


R4_pe

0.089833333

X4_pe

0.22575

max(x4_pe/2,25/LZ+R_line)

8.692666667

R4_pe derived (as per Manual)

0.089833333

X4_pe Rect
Min(8*X4_Rect, R4_pe/4)
R4_pe Rect
R4_pe to be Set

0.112875
0.022458333
0.22575
0.315583333

Zone 4 Ph-Ph Fault:


R4_pp

0.089833333

X4_pp

0.22575

max(x4_pp/2,15/LZ+R_line)

5.359333333

R4_pp derived (as per Manual)

0.089833333

X4_pp Rect
Min(8*X4_Rect, R4_pp/4)
R4_pp Rect
R4_pp to beSet

0.112875
0.022458333
0.22575
0.315583333

ED, INDIA

COMMON PARAMETERS:
CTR / PTR

0.333333333

Kr

0.322510823

Kx

0.88079242

km
R_Line
X_line

0.359333333
0.903

Zone 1 Ph-E Fault:


R1_pe

0.287466667

X1_pe

0.7224

max(x1_pe/2,25/LZ+R_line)

8.692666667

R1_pe derived (as per Manual)

0.287466667

X1_pe Rect
Min(8*X1_Rect, R1_pe/4)

0.3612
0.071866667

R1_pe Rect

0.7224

R1_pe to be Set

0.7224

Zone 1 Ph-Ph Fault:


R1_pp

0.287466667

X1_pp

0.7224

max(x1_pp/2,15/LZ+R_line)

5.359333333

R1_pp derived (as per Manual)

0.287466667

X1_pp Rect
Min(8*X1_Rect, R1_pp/4)

0.3612
0.071866667

R1_pp Rect

0.7224

R1_pp to be Set

0.7224

Zone 3 Ph-E Fault:


R3_pe

1.437333333

X3_pe

3.612

max(x3_pe/2,25/LZ+R_line)

8.692666667

R3_pe derived (as per Manual)

1.437333333

X3_pe Rect
Min(8*X3_Rect, R3_pe/4)
R3_pe Rect
R3_pe to be Set

1.806
0.359333333
3.612
5.049333333

Zone 3 Ph-Ph Fault:


R3_pp

1.437333333

X3_pp

3.612

max(x3_pp/2,15/LZ+R_line)

5.359333333

R3_pp derived (as per Manual)

1.437333333

X3_pp Rect
Min(8*X3_Rect, R3_pp/4)
R3_pp Rect
R3_pp to be Set

1.806
0.359333333
3.612
5.049333333

Maximum Load Resistance:


Theta (DEGREES(ACOS(PF)))

30.68341711

Factor = (K re * 0.9) / (K rel * K ss* IL max)

0.001370192

Factor * KV

180.8653846

63.4 - Theta

32.71658289

Sin(63.4 - Theta) / Sin 63.4

0.604463783

Load Resistance Primary

109.3265747

Load Resistance Secondary

36.44219156

90% of Load Resistance

32.7979724