Location via proxy:   [ UP ]  
[Report a bug]   [Manage cookies]                

RET615

Download as doc, pdf, or txt
Download as doc, pdf, or txt
You are on page 1of 3

TR2PTDF Group Settings Parameter High operate value Enable high set Low operate value Slope section

2 End section 2 Values (Range) 500...3000 0=False 1=True 5...50 10...50 100...500 Unit %Ir Step 10 Setting 1000 1=True %Ir % %Ir 1 1 1 20 30 150 Description
Instantaneous stage setting Enable high set stage Basic setting for biased operation Slope of the second line of the operating characteristics Turn-point between the second and the third line of the operating characteristics Restraint mode

Restraint mode

Harmonic deblock 2 Start value 2.H Start value 5.H Stop value 5.H Harmonic deblock 5.

-1=2.h + 5.h + wav 5=Waveform 6=2.h + waveform 7=5.h + waveform 0=False 1=True 7...20 10...50 10...50 0=False 1=True % % % 1 1 1

-1=2.h + 5.h + wav

1=True 15 35 35 0=False

2. harmonic deblocking in case of switch on to fault 2. harmonic blocking ratio 5. harmonic blocking ratio 5. harmonic deblocking ratio 5. harmonic deblocking in case of severe over voltage

TR2PTDF Non Group Settings Parameter Operation CT connection type Values (Range) 1=on 5=off 1=Type 1 2=Type 2 Unit Step Setting 1=on 1=Type 1 Description
Operation Off/On

CT connection type. Determined by the directions of the connected current transformers

Winding 1 type

Winding 2 type

Clock number

Zro A elimination

Min winding tap

1=Y 2=YN 3=D 4=Z 5=ZN 1=y 2=yn 3=d 4=z 5=zn 0=Clk Num 0 1=Clk Num 1 2=Clk Num 2 4=Clk Num 4 5=Clk Num 5 6=Clk Num 6 7=Clk Num 7 8=Clk Num 8 10=Clk Num 10 11=Clk Num 11 1=Not eliminated 2=Winding 1 3=Winding 2 4=Winding 1 and 2 -36...36

1=Y

Connection of the HV side windings

1=y

Connection of the LV side windings

0=Clk Num0

Setting the phase shift between HV and LV with clock number for connection group compensation (e.g. Dyn11 -> 11)

Elimination of the zero1=Not eliminat sequence current ed

36

Max winding tap

-36...36

The tap position number resulting the minimum number of effective winding turns on the side of the transformer where the tap changer is. The tap position number resulting the maximum number of effective winding turns on the side of the transformer where the tap changer is. The nominal position of the tap changer resulting the default transformation ratio of the transformer (as if there was no tap changer) The winding where the tap changer is connected

Tap nominal

-36...36

18

Tapped winding

1=Not in use 2=Winding 1

1=Not in use

3=Winding 2 Step of tap 0.60...9.00 % 0.01 1.50

to The percentage change in voltage corresponding one step of the tap changer CT ratio correction, winding 1 CT ratio correction, winding 2

CT ratio Cor Wnd 1 CT ratio Cor Wnd 2

0.40...4.00 0.40...4.00

0.01 0.01

1 1

You might also like