Outdoor Type Three-Phase Transformers Up To and Distribution Including 100 kVA 11 Kv-Specification
Outdoor Type Three-Phase Transformers Up To and Distribution Including 100 kVA 11 Kv-Specification
Outdoor Type Three-Phase Transformers Up To and Distribution Including 100 kVA 11 Kv-Specification
( Reaffirmed 2003 )
Indian Standard
OUTDOOR TYPE THREE-PHASE DISTRIBUTION
TRANSFORMERS UP TO AND INCLUDING
100kVA 11 kV- SPECIFICATION
PART 2 SEALED TYPE
1
( First Revision )
..
UDC 621.314.222.6.025.3-213.3 .*
Q BIS 1990
FOREWORD
This Indian Standard ( Part 2) ( First Revision) was adopted by the Bureau of Indian Standards on
30 May 1989, after the draft finalized by the Transformers Sectional Committee had been approved by the
Electrotechnical Division Council.
Sealed type construction for distribution transformers has been developed in view of difficulties in proper
maintenance of a large number of conventional transformers installed in the vast and scattered rural areas
as well as the reduction in the maintenance cost.
This standard was originally published in 1979. This revision has been undertaken to take into account
the experience gained since then.
The major changes in this revision include the reduction of limits of no load and load losses and the
modification of terminal arrangement and temperature rise for top oil, in line generally with REC
Specification on the subjects.
In this standard, for various common requirements, references have been made to IS 2026 ‘Specification
for power transformers’ which is, therefore, a necessary adjunct to this standard.
The requirements of non-sealed type outdoor distribution transformers of similar voltage and kVA ratings
are covered in Part 1 of this standard.
This standard is intended to cover the technical provisions relating to transformers and it does not include
all the necessary provisions of a contact.
In the preparation of this standard, assistance has been derived from REC Specification 11/1976
‘Outdoor type three phase, 11 kV/433-250 V sealed distribution transformers up to and including 100 LVA,
issued by the Rural Electrification Corporation Ltd.
For the purpose of deciding whether a particular requirement of this standard is complied with, the final
value, observed or calculated, expressing the result of a test, shall he rounded off in acctirdance with
IS 2 : 1960 ‘Rules for rounding off numerical values ( revised)‘. The number of significant places retained
in the rounded off value should be the same as that of the specified value in this standard.
IS 118o(Part2):1989
Indian Standard
OUTDOOR TYPE THREE-PHASE DISTRIBUTION
TRANSFORMERS UP TO AND INCLUDING
100kVA 11 kV- SPECIFICATION
PART 2 SEALED TYPE
( First Revision )
1 (SCOPE 5.3 Nominal System Voltage
1.1 This standard (Part 2) specifies the require- Nominal system voltage shall be chosen from the
ments and tests for oil immersed, naturally air-cooled, following:
three-phase, double-wound outdoor distribution
transformers of sealed tank construction up to and 3’3, 6’6 and 11 kV
including 100 kVA, for use on nominal system
voltages up to and including 11 kV. 6 NO-LOAD VOLTAGE RATIOS
2.1 The Indian Standards listed in Annex A are 3 300/433-250, 6 600/433-250 or 11000/433-250
necessary adjuncts to this standard. NOTE - An alternative no-load voltage ratios of 10 450/
433-250 is also permissiblefor 11 kV systems.
3 TERMINOLOGY
7 WINDING CONNECTIONS AND VECTORS
3.1 For the purpose of this standard, the following
definitions. in addition to those given in IS 1885 7.1 The primary winding shall be connected delta
(Part 38 ) : 1977 shall apply. and the secondary winding star [ vector. symbol Dyn
11 in accordance with IS 2026 ( Part 4 ) : 1977 1, so
3.1.1 Sealed Transformers as to produce a positive phase displacement of 30“
from the primary to the secondary vectors of the
A transformer which is non-breathing, that is, so same phase. The neutral of the secondary winding
sealed that there can be no interchange between its shall be brought out to a separate insulated terminal.
contents and the external atmosphere.
8 TAPS
3.1.2 Type Tests
Tests carried out to prove conformity with the 8.1 No taps are required to be provided on these
requirements of the standard. These tests are transformers.
intended to assess the general quality and design of
a given type of transformer. 9 TRANSFORMER TANK
9.2.3 The oil level before sealing the transformer tough insulating material, like epoxy and
shall be made up to the required level while the shall have embedded stem. Metal portion of
transformer filled with oil is maintained at a the internal HV bushing inside the tank shall
temperature of 45°C. Alternatively the tank may remain dipped in oil in all operating
be sealed at any other temperature and free-oil level conditions.
adjusted to meet the requirement of 9.2.2. NOTE -Dimensions of internal bushings are under
consideration.
9.3 The transformer cover and frame shall be such
that it is possible to remove the weld and reweld b) LV Bushing
twice. Where provided, these shall be of porcelain.
2
IS 1180 ( Part 2 ) :1989
L HOLES,+lL,LENGTH 21
PROVIDED IN THE
CHANNELS FIXED TO THE
EASE STRUCTURE OF TANK
\ 75x40 CHANNEL_
17 TOLERANCES 21 TESTS
17.1 The tolerance on electrical performance ( ex-
cluding losses ) shall be as given in 11 of IS 2026 21.1 General
(Part 1) : 1977.
The requirements given in 16.1 of IS 2026 (Part 1) :
18 ABILITY OF TRANSFORMERS TO 1977 shall apply.
WITHSTAND EXTERNAL SHORT-CIRCUIT
18.1 The performance of transformer under external 21.2 All the tests listed under 21.3 and 21.4 shall be
short-circuit conditions shall be in accordance carried out in accordance with the provisions of the
with 8 and 9 of IS 2026 (Part 1) : 1977. clauses and standards given in the parenthesis.
3
Is 118o(Part2):1989
ANNEX A
( Clause 2.1 )
LIST OF REFERRED INDIAN STANDARDS
4
Bukeau of Indian Standards
BIS is a statutory institution established under the Bureau of Indian Standards Act, 1986 to promote
harmonious development of the activities of standardization, marking and quality certification of goods and
attending to connected matters in the country.
Copyright
BIS has the copyright of all its publications. No part of these publications may be reproduced in any form
without the prior permission in writing of BIS. This does not preclude the free use, in the course of
implementing the standard, of necessary details, such as symbols and sizes, type or grade designations.
Enquiries relating to copyright be addressed to the Director (Publication), BIS.
Amendments are issued to standards as the need arises on the basis of comments. Standards are also reviewed
periodically; a standard along with amendments is reaffirmed when such review indicates that no changes are
needed; if the review indicates that changes are needed, it is taken up for revision. Users of Indian Standards
should ascertain that they are in possession of the latest amendments or edition by referring to the latest issue
of”BIS Handbook’ and ‘Standards Monthly Additions’.
This Indian Standard has been developed from Dot: No. ETDC 16 ( 3055 )