Fuse Failure Relay
Fuse Failure Relay
S tat i c M o n i to r i n g R e l ay
—
UVT92m is a high speed static
relay intended for continuous
monitoring of fuses against
blowing out or inadvertent
removals. This relay can be used
for one, two or all three phase
fuse failure detection. The plug-in
socket type design for terminals,
supports ease of installation and
maintenance.
tab l e o f c o n t en t s 3
—
Table of contents
004 Features
004 Applications
010 References
4 F u s e failu r e r e lay pr o d u c t g u ide
—
Fuse failure relay
UVT92m
The relay can also be used for supervision of The fuse fail in any phase is indicated by 'Trip'
potential transformer fuses so as to give blocking LED and will remain latched until reset push
signals to voltage operated protection schemes button is pressed and fuse is healthy. After
such as distance protection, under impedance replacing the faulty fuses, the output contacts
and under voltage relays. It can be used for can be reset.
alarming purpose in synchronizing circuits.
The plug in socket design for terminals facilitates
—
Table 1. Application and supported functions ease of installation and maintenance. The relay is
Functionality ANSI IEC suitable for flush mounting on panel and is
Fuse fail supervision 97 FUSEF sufficiently protected against any ingress. A
unique Plug-in PCBA assembly and sheet metal
case makes the relay robust and light weight.
—
Technical data
—
Table 2. Dimensions
Description Value
Width Frame 108.0 mm
Case 088.0 mm
Height Frame 164.0 mm
Case 112.0 mm
Depth Case 145.0 mm (120 mm + 25 mm)
Weight Relay 1.20 kg
—
Table 3. Auxiliary power supply
Description Value
Uaux nominal 24, 30, 48, 110, 220, 250 VDC
Uaux variation 80...110% of Uaux
Burden of auxiliary voltage supply under <3.0W (nominal) / < 4.0 W
Quiescent (Pq)/operating condition
Ripple in the DC auxiliary voltage Max 15% of the DC value (at frequency of 100 Hz)
—
Table 4. Energizing inputs from PT supply and operation time
Description Value
Rated voltage 110V AC
Rated frequency 50 Hz
Burden on energizing input 0.5 VA / Phase
Maximum phase neutral load impedance 2000 ohms
allowable in series with relay input
Relay operation time ≤ 15 msec
—
Table 5. Output contact details
Description Value
Rated voltage 250 V AC/DC
Continuous contact carry 5A
Make and carry for 0.5 sec 10 A
Make and carry for 3.0 sec 8A
Breaking capacity when the control-circuit time 1.0 A/ 0.25 A / 0.15 A
constant L/R<40 ms, at 48 / 110 / 220 V DC
—
Table 6. Degree of protection of relay
Description Value
Front side IP 54
Rear side, connection terminals IP 20
6 F u s e failu r e r e lay pr o d u c t g u ide
—
Table 7. Environmental conditions
Description Value
Operating temperature range -10 0...+550C
Relative humidity < 93%, non-condensing
Atmospheric pressure 86...106kPa
Altitude up to 2000 m
—
Table 8. Environmental tests
—
Table 9. Insulation tests
Description Type test value Reference
Dielectric test
• Test voltage 2 kV, 50 Hz, 1 min IEC 60255-27
—
Table 10. Mechanical tests
Description Type test value Reference
Vibration tests
• Response 10...150 Hz / 0.5 g
• Endurance / Withstand 10...150 Hz, 1.0 g IEC 60255-21-1, class I
Shock tests
• Response 5 g, 11 ms
• Endurance / Withstand 15 g, 11 ms IEC 60255-21-2, class I
Bump tests 10 g, 16 ms 1000 bumps in each IEC 60255-21-2, class I
direction
dimensi o ns and m o u n t ing 7
—
Dimensions and mounting
X2 X1 X2 X1
1 1 1 1
2 2 2 2
3 3 3 3
4 4 4 4
164
164
5 5 5 5
6 6 6 6
7 7 7 7
8 8 8 8
9 9 9 9
10 10 10 10
Ls
18 18 102 25
102 25 108
Rear view Rear view Side view Side view Front vie
1/2’S’ case mounting.
1/2’S’ case mounting.
Ob Ob
ø6 ø6
112 - 0
112 - 0
+1
+1
140±0.3
140±0.3
164
164
Ls Ls
14
14
+1 +1
108 108 88 - 0 88 - 0
25
102 25
Db Db
w Side view Front view Front view Cutout Cutout
Legend
Aa : Socket block
Db : Mounting hole
Ls : Reset button
Ob : Mounting screw
Legend Legend
Aa : Socket block
Aa : Socket block
Db : MountingDb : Mounting hole
hole
Ls : Reset button
Ls : Reset button
Ob : Mounting
Ob screw
: Mounting screw
8 F u s e failu r e r e lay pr o d u c t g u ide
—
Selection and ordering data
—
Table 11: Order code information
# Description
1-7 Product type
Static 1MYN742
8-10 Relay type
UVT92m 844
11 Vacant digit
Vacant -
12 Auxiliary supply
24 V DC A
30 V DC B
48 V DC C
110 V DC D
220 V DC E
250 V DC F
—
Example order code: 1MYN742844-D
—
Connection and terminal diagram
UVT92m - BLOCK DIAGRAM
UVT92m - Block Diagram
R Y B
(+ Ve)
X2-1
X1-1
F A
G
X2-3
X1-2 B
X1-3 X2-5
X2-4
F A
X2-8
X1-4 B X2-6
X1-5 X2-7
D
F A E
X1-6 B
(- Ve)
X2-2
Load
10 F u s e failu r e r e lay pr o d u c t g u ide
References
The http://new.abb.com/medium-
voltage/distribution-automation portal
offers you information about the
medium voltage distribution
automation products and solutions.
Disclaimer
The information in this document is
subject to change without notice and
should not be construed as a commit-
ment by ABB. ABB assumes no responsi-
bility for any errors that may appear in
this document.
www.abb.com/substationautomation
1MDB08202-YN REV A 07.2017
©
Copyright 2017 ABB. All rights reserved.
Specifications subject to change without notice.