Tcs 7PA26 - 27 - 30 - Catalog - SIP-2008 - en PDF
Tcs 7PA26 - 27 - 30 - Catalog - SIP-2008 - en PDF
Tcs 7PA26 - 27 - 30 - Catalog - SIP-2008 - en PDF
7PA26/27/30
Auxiliary Relays for Various Applications
Technical data for 7PA26 and 7PA27
Switching contacts
Continuous current 10 A
Overload capability 80 A/200 ms
150 A/10 ms
Switching current/voltage 40 A/0.5 s/110 V DC
LSP2888.tif
LSP2887.tif
Breaking capacity for 105 operating cycles
Non-inductive Inductive, 20 ms
1 contact 2 contacts 1 contact 2 contacts
in series in series
V DC A A A A
24 6.6 12.7 3.2 6.0
60 2.6 4.9 1.4 2.7
LSP2890.tif
LSP2889.tif
Description
Standards
Technical data
Constructions standards (Cont'd) 7PA26 Monostable
Rated voltages and consumption
Immunity test EMC fast-acting relay VN Voltage Consumption
EN 60255-22-1 High frequency 1 MHz burst Description range
disturbance test: V DC V DC mA
Test level: 1 MHz, 400 imp/s, 2 s The monostable 7PA26 has eight change-
Common mode: 2,5 kV 7PA26o20
over contacts.
Differential mode: 1 kV 24/30 20 33 278
EN 61000-4-4 Electrical Fast transient burst: 60 48 66 100
Test level 4 kV, 2.5 kHz,
1 min 2 kV, 5 kHz, 1 min 110/125 88 138 55
EN 61000-4-5 Surge 8/20 s (current) 220 176 242 28
1.2/50 s (voltage) Consumption
Common mode: 2 kV- 7PA26o21 Normal Peak
Differential mode: 1 kV
24/30 19 36 50
EN 61000-4-3 Radiated electromagnetic field: 0.8 A 20 ms
Test level: 80-1000 MHz, 60 42 72 20
10 V/m, 80 % AM (1 kHz)
110/125 77 150 14
EN 61000-4-3 Digital telephones radiated 0.3 A 20 ms
electromagnetic field: Test level: 220 154 264 7
900 5 MHz, 10 V/m, 50 %
(200 Hz) 1.89 GHz 10 MHz,
10 V/m, 50 % (200 Hz) Pick-up time: 7PA26o20 < 20 ms
EN 61000-4-6 Conducted disturbances in- 7PA26o21 < 10 ms
duced by radio frequency fields.
Test level: 0.15-80 MHz, 10 V, Drop-out time: < 40 ms
80 % AM (1kHz)
General description see page 16/5.
EN 61000-4-2 Electrostatic discharges: Test
level: Contact 15 kV; Refer to part 17 for dimension drawings.
Air mode 15 kV
EN 61000-4-8 Power frequency magnetic field:
Fig. 16/6 Connection diagram
Test level: 100 A/m
1 min 1000 A/m 1 s
EN 55011 Emission test: Test level: Cover:
Class A 30-230 MHz, 40 dB(V/m)
(quasi peak)-10 m
230-1000 MHz, 47 dB(V/m)
(quasi peak)-10 m
Power supply:
0.15-0.5 MHz, 79 dB(V)
(quasi peak)/ 66 dB average val.
0.5-5 MHz, 73 dB(V)
(quasi peak)/ 60 dB average val.
5-30 MHz, 73 dB(V)
(quasi peak)/ 60 dB average val.
Selection and ordering data Description Order No.
7PA26 monostable relay with 8 changeover contacts 7PA26o2-oAA00-o
Auxiliary voltage
24 /30 V DC 1
60 V DC 2
110/125 V DC 3
220 V DC 4
Standard, 20 ms 0
Fast, 10 ms 1
Socket
without socket 0
with flush-mounting socket 7XP9010-3 1
with surface-mounting socket 7XP9012-0 2
Technical data
7PA27 Monostable
Rated voltages and consumption
fast-acting relay VN Voltage Consumption
Description range Normal Peak
V DC V DC mA
The monostable 7PA27 is a fast-acting
24/30 19 36 28 1 A/20 ms
relay with four changeover contacts.
60 42 72 12 1 A/20 ms
110/125 77 150 8 0,3 A/20 ms
220 154 264 6 0,3 A/20 ms
Socket
without socket 0
with flush-mounting socket 7XP9011-2 1
with surface-mounting socket 7XP9013-0 2
16
7PA30 Three-phase
Trip circuit supervision
Description
The relay is for supervision of the trip cir-
cuit of a circuit breaker with three selective
trip coils. The trip circuit wiring is super-
vised from the positive supply to the nega-
tive supply whilst the circuit breaker is
open or closed.
Functions
The design, quality and rugged construc-
tion of the relay make it suitable for appli-
cations requiring high levels of reliability/
dependability. The high degree of
protection guarantees reliable operation
over a wide temperature range, even under
extreme environmental conditions.
The relay has been tested in accordance
with IEC, EN and IEEE standards. The re-
lay is CE marked. The supervision current
is always less than 1.4 mA thus avoiding
unwanted operation of the trip coil. Cor-
rect operation is shown via a green LED.
Fig. 16/8 Connection diagram for 3-phase relay
Socket
without socket 0
with flush-mounting socket 7XP9010-4 1
with surface-mounting socket 7XP9012-0 2
7PA30 Single-phase
Trip circuit supervision
Description
The relay is for supervision of the trip cir-
cuit of a circuit breaker with one trip coil.
The trip circuit wiring is supervised from
the positive supply to the negative supply
whilst the circuit breaker is open or closed.
Functions
The design, quality and rugged construc-
tion of the relay make it suitable for appli-
cations requiring high levels of reliability/
dependability. The high degree of
protection guarantees reliable operation
over a wide temperature range, even under
extreme environmental conditions.
The relay has been tested in accordance
with IEC, EN and IEEE standards. The re-
lay is CE marked. The supervision current Fig. 16/9 Connection diagram for 1-phase relay
is always less than 1.4 mA thus avoiding
unwanted operation of the trip coil. Cor-
rect operation is shown via a green LED. Standard voltages and consumption
VN Voltage range Consumption Impedance Pickup
per phase Drop out Voltage
V DC V DC mA k/s V DC
14/30 18 - 33 32 20 between 12 and 18
60 42 - 66 18 44 36 and 42
110/125 77 - 138 18 94 66 and 77
220 154 - 275 13 200 132 and 154
Drop-out time: between 150 ms and 400 ms
Socket
without socket 0
with flush-mounting socket 7XP9011-0 1
with surface-mounting socket 7XP9013-0 2
16
Fig. 17/59
7PA27
Fig. 17/61
7TS16, 7PA30 three-phase
Fig. 17/56
7PA23 auxiliary relay +
flush mounting socket 7XP9011-1
Fig. 17/62
Flush mounting socket 7XP9011-2
for 7PA27 auxiliary relay
Fig. 17/65
7PA26
Fig. 17/66
Flush mounting socket 7XP9010-3
for 7PA26 auxiliary relay
16