Model CW120 Clamp-on Power Meter

CW120 Maintenance and long term monitoring of electrical equipment and electrical system.

Low-cost tools to support your energy conservation efforts


CW240
As energy conservation becomes increasingly important, we are pleased to present low-cost clamp-on power meters designed to meet user needs for simple tools capable of measuring power values and instantaneous values.

Useful features for energy conservation and power measurement wer


Periodically save data as often as once a second
Data can be saved as low as 1-second interval. This capability allows the CW120 Series to respond quickly to load fluctuations and measure transient responses in equipment.

Wiring error check function


This function helps ensure that measurement operations are correct.

Current input (clamp)

Simultaneous measurement of multiple facilities


Multiple CW120 Series units can start and stop integration simultaneously through externally controlled I/O.

CW120

Voltage input

Check equipment operating conditions


The CW120 Series has an instantaneous value filing function (enabling multiple data records to be saved in a single file when multiple measurements are taken) which is useful for determining equipment operating conditions.

Works even with small electric energy values


Easily change the decimal position (the number of digits following the decimal point) and display unit (Wh, kWh, MWh, GWh) on the electric energy display.

AP240E

Details for Models CW120/CW121


Items Measurement Mode
External I/O controller port
(integration start/stop signal: function to start/stop multiple units simultaneously)

CW120/CW121 Input system Instant mode Electric Energy mode Single-phase 2-wire to 3-phase 4-wire (Up to 3 phase 3 wire for CW120) Available Segmented LCD with backlight RS232 or RS485 MODBUS, PC-link, Power-Monitor, Proprietary Available 100 to 240V AC, Supply the power from input. 117 161 51mm 600g

Display

Screen Interface Protocol Monitoring by AP240E

12

RS-232 connector (8-pin)

Communication

13

100-240VAC Power connection PC card slot (flash ATA memory)

Power supply Size (W H D) Weight

Load measurements on multiple systems


Power switch

Model CW121- -1

In addition to support for a variety of connection types, The CW120 Series can simultaneously measure the loads* (facilities, equipment) on multiple systems sharing a common power supply. CW120 (three-phase 3-wire model): 12W 2 CW121 (three-phase 4-wire model): 12W 2, 3

12W Three current systems (example)


Power supply side (Facility 3)
1

Load 3 side

Load 2 side Load 1 side

(Facility 2) (Facility 1)

Easy-to-recognize function icons

Low-cost tools to support your energy conservation efforts

Advanced data management and communication


CW240

Compact design
The CW120 Series is compact in size (117 161 51mm (W H D)), making it ideal for installation in cubicles and inside distribution panels. Installation is even easier with the magnetic case (93023). Although the CW120 Series is small, it has a large backlit LCD. A new addition to the clamp lineup is a small-diameter current clamp (model 96033, capable of measurements in the range of 550 A) for measurements in tight spots and locations where many wires are jumbled together.
Current clamp (96033)
Approximately 70 mm

Data management and communication


1 You can connect CW120 to a PC through dedicated RS-232 cable. 2 A printer (sold separately) can be connected through RS-232 cable to print measurement data. 3 If you have a media reader connected to your PC or card slot in notebook PC, measurement data and settings can be uploaded directly to a PC from CF* pack.
Wiring Method 34W 34W 34W 34W 34W Memory 16MB 16MB 16MB 32MB 32MB Interval Time 1 Second 1 Minute 10 Minutes 1 Second 10 Minutes Stored Period Approx 24 Hours Approx 2 Months More than 1 Year Approx 40 Hours Approx 4 Months

CF pack 3
Comm. Cable Model 91011

18 mm

CW120

1
PC Media reader

2
Printer Cable Model 91010 Printer Model 97010

* Compact Flash cards with memory capacity up to 128 MB may be used (recommended brand: SanDisk).

Network Communication
Magnetic case (93023)

Measurements
The CW120 Series can be used for voltage measurements up to 495 V. A variety of connection types are supported, from single-phase 2-wire to three-phase 4-wire (CW120: three-phase 3-wire model; CW121: three-phase 4-wire model). Continuous measurement integration (accurate measurements can be obtained even if there are large load fluctuations) Plus/minus signs are shown for reactive power and power factor. The data saving interval can be set in the range of one second to one hour.

CW120 In addition to proprietary communication also supports, MODBUS, PC-link and Power Monitor protocols. PC-link is a protocol for Yokogawa's Temperature controllers and PLCs. Power Monitor protocol is a protocol for Yokogawa's Power Monitors. (PR201)

Data Management by DAQLOGGER*


PC

Internet

Model MV

Model MV

Yokogawa's Recorder

WEB function: Model MV100/200 can be monitored by Internet Browser on PC. E-mail Alarm function: The alarms from Model MV100/200 can be sent to PC as an Email. FTP function: Model MV100/200 can send gathering data as a file to PC by using FTP function. RS485-MODBUS protocol

Parameters setting tool (name: Toolbox)


The setting software allows you to set CW120 Series measurement conditions through a PC and save measurement data on a PC when the unit is connected to the PC through RS-232 or RS-485 port.

* DAQLOGGER is Yokogawas communication software for Windows 95/98/ NT4.0/2000/XP

Measurement conditions setting function


This function makes it easy to set basic functions needed for measurement, such as start/stop time and date, wiring method, clamp type, voltage, and current range etc.

Remote monitoring
The RS-485 allows multiple use to be connected for remote monitoring.
* RS-485/RS-232 converter is required to connect the CW120/CW121-m-2 (RS485 communication spec) to the RS-232 port on your PC. Recommended brand and model: Yokogawas RS-232/RS-485 Converter Model ML1.
RS-232 Converter PC Monitoring Software

File transfer function


The data file stored in CF pack can be transfered to PC. Microsoft Excel can read transferred data file.
* Toolbox is included as a standard feature (on two floppy disks).

Setting screen

RS-232 comm. cable


RS-485 Max 31 units, 1.2km

Microsoft, Windows, and Excel are trademarks or registered trademarks of Microsoft Corporation, the United States.

File transfer screen

Specifications
CW240
Inputs
Parameter Input type Rated value (range) 150/300/450 V Voltage (V) Resistive potential division Current (A) Clamp detection Clamp 96033: 5/10/20/50 A Clamp 96030: 20/50/100/200 A Clamp 96031: 50/100/200/500 A Clamp 96032: 200/500/1000 A Wiring Input resistance input CW120 CW121 CW120 CW121 Single-phase 2-wire, single-phase 3-wire, three-phase 3-wire Single-phase 2-wire, single-phase 3-wire, three-phase 3-wire, three-phase 4-wire Approximately 1.5 M Approximately 1.3 M Approximately 100 k Clamp 96033: 130 Arms 495 Vrms Clamp 96030: 250 Arms Clamp 96031: 625 Arms Clamp 96032: 1000 Arms A/D converter Voltage/current input simultaneous conversion, 12-bit resolution

Equations
Voltage rms Current rms

Communication Functions
Vrms= 1 T 1 T
T 0

dt = dt =
i

1 T T t=0 1 T T t=0 1
T

Electrical specifications: Protocols:

T 0

Arms=
Active power
P=

1 T

T 0

dt = T t=0
P = P1 + P2 P = P1 + P2 + P3

Synchronization system: Baud rates:

Conforms to EIA RS-232 or EIA RS-485. CW120/121 proprietary protocol, Power Monitor protocol (Standard protocol used for YOKOGAWA M&C's Power Monitor) PC link communication (Standard protocol used for YOKOGAWA M&Cs Temperature Controllers) MODBUS communication (ASCII or RTU) Start stop synchronization 1200, 2400, 4800, 9600, 19200, 38400 bps

Single-phase 3-wire, three-phase 3-wire Three-phase 4-wire (t), i(t): Input signals T: One period for input signal

PC card interface
Slot: Compatible card: Function specifications:
Apparent power Power factor (Note 2)

Maximum allowed

Reactive power and power factor


Reactive power (Note 2) Single-phase 2-wire Single-phase 3-wire

PC card slot TYPE II ATA flash memory card Saving measurement data, saving and reading settings data

CW120

Faulty Wiring Checking Functions


Check details: Presence/absence of power input; check for frequency measurement range; voltage phase sequence; presence/absence of power input; whether current clamp is reverse-connected

Measurement Input functions


Parameter Method Frequency range Crest factor Active input range Display range Lower limit Upper limit Temperature coefficient Display updating interval Voltage Digital sampling 4565 Hz (reciprocal system), detected from V1 150/300 V range 450 V range 10110% of each range All ranges 1.5 V 130% of each range, except 110% for 450 V range 0.05% rng/C Approximately one second 0.4% of each range 130% of each range 0.07% rng/C (including clamp) Rated input: 2 Rated input: 1.56 Rated input: 3 Current/active power

Three-phase 3-wire
(Note 3)

Scaling Function
Rated value depends on V and A ranges. Same as for active power. Rated value depends on V and A ranges. Internal computation only; data not displayed or saved.

Three-phase 4-wire Computation range Display resolution

The VT ratio and CT ratio can be set. Settings ranges VT ratio: 110,000 CT ratio: 110,000 (in increments of 0.01)

External Control I/O (for RS-232 only; not provided for RS-485)
These input and output can be used as signals for starting and stopping integrating measurement. Control input: TTL level or contact Control output: TTL level

Note 1: In the case of distorted waves, there may be differences from other measuring instruments that are based on different measurement principles. Note 2: The polarity of each phase determined by the reactive power meter method is multiplied and the polarity is displayed. Note 3: In the case of three-phase 3-wire and unbalanced inputs, there may be differences from other measuring instruments that are based on different measurement principles, or wiring.

AP240E

Other Functions
Clock (typical precision: 100 ppm), key lock, system reset

Instantaneous Value Measurement


Voltage rms (V), current rms (A), active power (W), frequency (Hz) Measurement accuracy (at power factor 1, including clamp) Voltage: (0.3% rdg + 0.2% rng) Current/active power: (0.8% rdg + 0.4% rng) when using clamps 96030, 96031, and 96033 (1.2% rdg + 0.8% rng) when using clamp 96032 Frequency: (0.1% rdg + 1% dgt) Computation parameters: Reactive power (Var), power factor Computation accuracy: (value calculated from measurement) 1 dgt Power factor influence: 1.0% rng cos = 0.5 (relative to power factor 1) when using clamp 96030 2.0% rng cos = 0.5 (relative to power factor 1) when using clamps 96031, 96032, and 96033 Reactive factor influence: 1.0% rng sin = 0.5 (relative to reactive factor 1) when using clamp 96030 2.0% rng sin = 0.5 (relative to reactive factor 1) when using clamps 96031, 96032, and 9603 Measurement parameters:

Electric Energy Measurement


Measured parameters: Active electric energy, regenerative electric energy (regenerative electric energy is not displayed on the screen; it is merely saved) Measurement accuracy: Active power measurement accuracy 1 dgt (with standard settings) Integration function settings Start/stop settings: Manual, timer, external trigger (control) Output intervals: 1/2/5/10/15/30 seconds; 1/2/5/10/15/30 minutes; 1 hour Displayed digits: This is set automatically based on the rated power, and the minimum resolution can be set

General Specifications
Environmental requirements: Indoor usage at an altitude of 2000 meters or less. Usage temperature and humidity ranges: 050C, 585% RH (no condensation) 040C, 585% RH (no condensation) for UL, C-UL Storage temperature and humidity ranges: -2060C, 90% RH (no condensation) Insulating resistance: 500 V DC, 50 MW or greater Between voltage input terminals and case Between voltage input terminals and current input terminals, communication terminals, and control I/O terminals Between power line and case Between power line and current input terminals, communication terminals, and control I/O terminals Insulating withstand voltage: 5550 V AC for one minute Between voltage input terminals and case 3320 V AC for one minute Between voltage input terminals and current input terminals, communication terminals, and control I/O terminals 2300 V AC for one minute Between power line and case Between power line and current input terminals, communication terminals, and control I/O terminals Power supply: 100240 V AC 10%, 50/60 Hz Consumed power: 8 VA maximum External magnetic field effects: Within accuracy levels at 400 A/m External dimensions: Approximately 117 161 51 mm (W H D) Weight: Approximately 0.6 kg Terminals: Voltage input CW120: 3 terminals Banana terminals (safety terminals) CW121: 4 terminals Banana terminals (safety terminals) Current terminals CW120: 2 pairs Banana terminals (safety terminals) (H/L) CW121: 3 pairs Banana terminals (safety terminals) External control I/O 3 terminals (H/L/H) Screwless terminals terminals RS-485 4 terminals (+/-/SG/TM) M3 screw terminals Connectors: RS-232: Mini DIN 8-pin AC power supply: 2-pin Accessories: Voltage input probes: 3 for CW120, 4 for CW121 Power cord, user's manual, operation guide, Toolbox (setting software) Safety standards: Compliant with EN61010-1, EN61010-2-031, UL3111-1 First Edition, CAN C22.2 No. 1010.1-92 Voltage input line Measurement (Overvoltage) category III (Max. input voltage : 600 Vrms) Power line Installation category II (Max. input voltage : 264 Vrms) Pollution degree 2 EMC (emission): Compliant with EN55011, Group1, ClassA; EN61326; EN61000-3-2; EN61000-3-3 EMC (immunity): Compliant with EN61326

Saving items
Saving items: Voltage, current, active power, reactive power, power factor, frequency, active electric energy, regenerative electric energy

Display Functions
Display screen: Backlit segmented LCD Maximum number of displayed digits Electric energy: 6 digits Other parameters: 4 digits Range makeup: (rated values)

Clamp 96032 Clamp 96031 Clamp 96030 Clamp 96033 Voltage Wiring 12W 150.0V 13W 33W 34W 12W 300.0V 13W 33W 34W 12W 450.0V 13W 33W 34W 5.000 A 750.0 W 1.500 kW 1.500 kW 2.250 kW 1.500 kW 3.000 kW 3.000 kW 4.500 kW 2.250 kW 4.500 kW 4.500 kW 6.750 kW 10.00 A 1.500 kW 3.000 kW 3.000 kW 4.500 kW 3.000 kW 6.000 kW 6.000 kW 9.000 kW 4.500 kW 9.000 kW 9.000 kW 13.50 kW 20.00 A 3.000 kW 6.000 kW 6.000 kW 9.000 kW 6.000 kW 12.00 kW 12.00 kW 18.00 kW 9.000 kW 18.00 kW 18.00 kW 27.00 kW 50.00 A 7.500 kW 15.00 kW 15.00 kW 22.50 kW 15.00 kW 30.00 kW 30.00 kW 45.00 kW 22.50 kW 45.00 kW 45.00 kW 67.50 kW 100.0 A 15.00 kW 30.00 kW 30.00 kW 45.00 kW 30.00 kW 60.00 kW 60.00 kW 90.00 kW 45.00 kW 90.00 kW 90.00 kW 135.0 kW 200.0 A 30.00 kW 60.00 kW 60.00 kW 90.00 kW 60.00 kW 120.0 kW 120.0 kW 180.0 kW 90.00 kW 180.0 kW 180.0 kW 270.0 kW 500.0 A 75.00 kW 150.0 kW 150.0 kW 225.0 kW 150.0 kW 300.0 kW 300.0 kW 450.0 kW 225.0 kW 450.0 kW 450.0 kW 675.0 kW 1.000 kA 150.0 kW 300.0 kW 300.0 kW 450.0 kW 300.0 kW 600.0 kW 600.0 kW 900.0 kW 450.0 kW 900.0 kW 900.0 kW 1.350 MW