CW120 Maintenance and long term monitoring of electrical equipment and electrical system.
CW120
Voltage input
AP240E
CW120/CW121 Input system Instant mode Electric Energy mode Single-phase 2-wire to 3-phase 4-wire (Up to 3 phase 3 wire for CW120) Available Segmented LCD with backlight RS232 or RS485 MODBUS, PC-link, Power-Monitor, Proprietary Available 100 to 240V AC, Supply the power from input. 117 161 51mm 600g
Display
12
Communication
13
Model CW121- -1
In addition to support for a variety of connection types, The CW120 Series can simultaneously measure the loads* (facilities, equipment) on multiple systems sharing a common power supply. CW120 (three-phase 3-wire model): 12W 2 CW121 (three-phase 4-wire model): 12W 2, 3
Load 3 side
(Facility 2) (Facility 1)
Compact design
The CW120 Series is compact in size (117 161 51mm (W H D)), making it ideal for installation in cubicles and inside distribution panels. Installation is even easier with the magnetic case (93023). Although the CW120 Series is small, it has a large backlit LCD. A new addition to the clamp lineup is a small-diameter current clamp (model 96033, capable of measurements in the range of 550 A) for measurements in tight spots and locations where many wires are jumbled together.
Current clamp (96033)
Approximately 70 mm
CF pack 3
Comm. Cable Model 91011
18 mm
CW120
1
PC Media reader
2
Printer Cable Model 91010 Printer Model 97010
* Compact Flash cards with memory capacity up to 128 MB may be used (recommended brand: SanDisk).
Network Communication
Magnetic case (93023)
Measurements
The CW120 Series can be used for voltage measurements up to 495 V. A variety of connection types are supported, from single-phase 2-wire to three-phase 4-wire (CW120: three-phase 3-wire model; CW121: three-phase 4-wire model). Continuous measurement integration (accurate measurements can be obtained even if there are large load fluctuations) Plus/minus signs are shown for reactive power and power factor. The data saving interval can be set in the range of one second to one hour.
CW120 In addition to proprietary communication also supports, MODBUS, PC-link and Power Monitor protocols. PC-link is a protocol for Yokogawa's Temperature controllers and PLCs. Power Monitor protocol is a protocol for Yokogawa's Power Monitors. (PR201)
Internet
Model MV
Model MV
Yokogawa's Recorder
WEB function: Model MV100/200 can be monitored by Internet Browser on PC. E-mail Alarm function: The alarms from Model MV100/200 can be sent to PC as an Email. FTP function: Model MV100/200 can send gathering data as a file to PC by using FTP function. RS485-MODBUS protocol
Remote monitoring
The RS-485 allows multiple use to be connected for remote monitoring.
* RS-485/RS-232 converter is required to connect the CW120/CW121-m-2 (RS485 communication spec) to the RS-232 port on your PC. Recommended brand and model: Yokogawas RS-232/RS-485 Converter Model ML1.
RS-232 Converter PC Monitoring Software
Setting screen
Microsoft, Windows, and Excel are trademarks or registered trademarks of Microsoft Corporation, the United States.
Specifications
CW240
Inputs
Parameter Input type Rated value (range) 150/300/450 V Voltage (V) Resistive potential division Current (A) Clamp detection Clamp 96033: 5/10/20/50 A Clamp 96030: 20/50/100/200 A Clamp 96031: 50/100/200/500 A Clamp 96032: 200/500/1000 A Wiring Input resistance input CW120 CW121 CW120 CW121 Single-phase 2-wire, single-phase 3-wire, three-phase 3-wire Single-phase 2-wire, single-phase 3-wire, three-phase 3-wire, three-phase 4-wire Approximately 1.5 M Approximately 1.3 M Approximately 100 k Clamp 96033: 130 Arms 495 Vrms Clamp 96030: 250 Arms Clamp 96031: 625 Arms Clamp 96032: 1000 Arms A/D converter Voltage/current input simultaneous conversion, 12-bit resolution
Equations
Voltage rms Current rms
Communication Functions
Vrms= 1 T 1 T
T 0
dt = dt =
i
1 T T t=0 1 T T t=0 1
T
T 0
Arms=
Active power
P=
1 T
T 0
dt = T t=0
P = P1 + P2 P = P1 + P2 + P3
Conforms to EIA RS-232 or EIA RS-485. CW120/121 proprietary protocol, Power Monitor protocol (Standard protocol used for YOKOGAWA M&C's Power Monitor) PC link communication (Standard protocol used for YOKOGAWA M&Cs Temperature Controllers) MODBUS communication (ASCII or RTU) Start stop synchronization 1200, 2400, 4800, 9600, 19200, 38400 bps
Single-phase 3-wire, three-phase 3-wire Three-phase 4-wire (t), i(t): Input signals T: One period for input signal
PC card interface
Slot: Compatible card: Function specifications:
Apparent power Power factor (Note 2)
Maximum allowed
PC card slot TYPE II ATA flash memory card Saving measurement data, saving and reading settings data
CW120
Three-phase 3-wire
(Note 3)
Scaling Function
Rated value depends on V and A ranges. Same as for active power. Rated value depends on V and A ranges. Internal computation only; data not displayed or saved.
The VT ratio and CT ratio can be set. Settings ranges VT ratio: 110,000 CT ratio: 110,000 (in increments of 0.01)
External Control I/O (for RS-232 only; not provided for RS-485)
These input and output can be used as signals for starting and stopping integrating measurement. Control input: TTL level or contact Control output: TTL level
Note 1: In the case of distorted waves, there may be differences from other measuring instruments that are based on different measurement principles. Note 2: The polarity of each phase determined by the reactive power meter method is multiplied and the polarity is displayed. Note 3: In the case of three-phase 3-wire and unbalanced inputs, there may be differences from other measuring instruments that are based on different measurement principles, or wiring.
AP240E
Other Functions
Clock (typical precision: 100 ppm), key lock, system reset
General Specifications
Environmental requirements: Indoor usage at an altitude of 2000 meters or less. Usage temperature and humidity ranges: 050C, 585% RH (no condensation) 040C, 585% RH (no condensation) for UL, C-UL Storage temperature and humidity ranges: -2060C, 90% RH (no condensation) Insulating resistance: 500 V DC, 50 MW or greater Between voltage input terminals and case Between voltage input terminals and current input terminals, communication terminals, and control I/O terminals Between power line and case Between power line and current input terminals, communication terminals, and control I/O terminals Insulating withstand voltage: 5550 V AC for one minute Between voltage input terminals and case 3320 V AC for one minute Between voltage input terminals and current input terminals, communication terminals, and control I/O terminals 2300 V AC for one minute Between power line and case Between power line and current input terminals, communication terminals, and control I/O terminals Power supply: 100240 V AC 10%, 50/60 Hz Consumed power: 8 VA maximum External magnetic field effects: Within accuracy levels at 400 A/m External dimensions: Approximately 117 161 51 mm (W H D) Weight: Approximately 0.6 kg Terminals: Voltage input CW120: 3 terminals Banana terminals (safety terminals) CW121: 4 terminals Banana terminals (safety terminals) Current terminals CW120: 2 pairs Banana terminals (safety terminals) (H/L) CW121: 3 pairs Banana terminals (safety terminals) External control I/O 3 terminals (H/L/H) Screwless terminals terminals RS-485 4 terminals (+/-/SG/TM) M3 screw terminals Connectors: RS-232: Mini DIN 8-pin AC power supply: 2-pin Accessories: Voltage input probes: 3 for CW120, 4 for CW121 Power cord, user's manual, operation guide, Toolbox (setting software) Safety standards: Compliant with EN61010-1, EN61010-2-031, UL3111-1 First Edition, CAN C22.2 No. 1010.1-92 Voltage input line Measurement (Overvoltage) category III (Max. input voltage : 600 Vrms) Power line Installation category II (Max. input voltage : 264 Vrms) Pollution degree 2 EMC (emission): Compliant with EN55011, Group1, ClassA; EN61326; EN61000-3-2; EN61000-3-3 EMC (immunity): Compliant with EN61326
Saving items
Saving items: Voltage, current, active power, reactive power, power factor, frequency, active electric energy, regenerative electric energy
Display Functions
Display screen: Backlit segmented LCD Maximum number of displayed digits Electric energy: 6 digits Other parameters: 4 digits Range makeup: (rated values)
Clamp 96032 Clamp 96031 Clamp 96030 Clamp 96033 Voltage Wiring 12W 150.0V 13W 33W 34W 12W 300.0V 13W 33W 34W 12W 450.0V 13W 33W 34W 5.000 A 750.0 W 1.500 kW 1.500 kW 2.250 kW 1.500 kW 3.000 kW 3.000 kW 4.500 kW 2.250 kW 4.500 kW 4.500 kW 6.750 kW 10.00 A 1.500 kW 3.000 kW 3.000 kW 4.500 kW 3.000 kW 6.000 kW 6.000 kW 9.000 kW 4.500 kW 9.000 kW 9.000 kW 13.50 kW 20.00 A 3.000 kW 6.000 kW 6.000 kW 9.000 kW 6.000 kW 12.00 kW 12.00 kW 18.00 kW 9.000 kW 18.00 kW 18.00 kW 27.00 kW 50.00 A 7.500 kW 15.00 kW 15.00 kW 22.50 kW 15.00 kW 30.00 kW 30.00 kW 45.00 kW 22.50 kW 45.00 kW 45.00 kW 67.50 kW 100.0 A 15.00 kW 30.00 kW 30.00 kW 45.00 kW 30.00 kW 60.00 kW 60.00 kW 90.00 kW 45.00 kW 90.00 kW 90.00 kW 135.0 kW 200.0 A 30.00 kW 60.00 kW 60.00 kW 90.00 kW 60.00 kW 120.0 kW 120.0 kW 180.0 kW 90.00 kW 180.0 kW 180.0 kW 270.0 kW 500.0 A 75.00 kW 150.0 kW 150.0 kW 225.0 kW 150.0 kW 300.0 kW 300.0 kW 450.0 kW 225.0 kW 450.0 kW 450.0 kW 675.0 kW 1.000 kA 150.0 kW 300.0 kW 300.0 kW 450.0 kW 300.0 kW 600.0 kW 600.0 kW 900.0 kW 450.0 kW 900.0 kW 900.0 kW 1.350 MW