Catalogue - UC600
Catalogue - UC600
Catalogue - UC600
Benefit
An open standard building automation communications protocol which enables connections to other BAS systems and controllers
Schedulingsupports up to 3 weekly schedules Easy to set up and access (3 schedule types supported: Analog, Binary, Multistate) Graphicssupport for up to 10 custom graphics Perform overrides, link directly to alarms, reports, or other graphics directly from with optional TD7 Display. a graphic. Custom data graphs Configurable and fully programmable Total of 19 built-in I/O hardware terminations Expandable up to 120 hardware terminations (with the use of optional expansion modules) Data logging25,000 samples Removable connectors, DIN rail mounting, multiple service tool connections Create and view graphically formatted data logs. Up to 8 custom data graphs can be created with a maximum of 4 data logs per graph. Factory programs available through quick configuration for lowest setup time Programmable for flexibility to meet unique sequence or hardware needs Meets most applied product needs with built-in I/O or with additional custom programming on the controller Flexibility to meet additional equipment needs Easier investigation of equipment, zone, or building problems Ease of installation and service
November 2012
BAS-PRC063-EN
Operating
Temperature: Humidity: Power: Time Clock: Mounting weight of controller: Environmental rating (enclosure): Installation: Pollution -40F to 158F (-40C to 70C) Between 5% to 95% (noncondensing) Input: 20.427.6 Vac (24 Vac, 15% nominal) 50 or 60 Hz, 26 VA Output: (26 VA plus a maximum of 12 VA for each binary output) 24 Vdc, 10%, device max load 600 mA On-board real time clock with 7 day backup Mounting surface must support 1.3 lb. (0.6 kg) NEMA 1 UL 840: Category 3 UL 840: Degree 2
Wiring/Transformer/Communications Protocol
18 AWG is recommended for the circuit between the transformer and the controller. Data link protocol supported: BACnet MS/TP UL listed, Class 2 power transformer, 24 Vac 10%, device max load 26 VA. The transformer must be sized to provide adequate power to the UC600 controller (26 VA) and external device outputs. UC600 requires 26VA: 26VA is for UC600+ IO + two expansion modules (XM30 or XM32).
Agency Compliance
UL916 PAZX, Open Energy Management Equipment UL94-5V, Flammability CE Marked FCC Part 15, Subpart B, Class B Limit BTL MarkAdvanced Application Profile (B-AAC)
BAS-PRC063-EN
30 Nov 2012
Quantity
Types
Thermistor Resistive (setpoint) RTD
Range
10k Type II, 10k Type III, 2252 Type II, 20k Type IV, 100 k 100 1M Balco (Ni-Fe), 1k; 375, 385 (Pt), 1k 020 mA (linear) 020 Vdc (linear) Dry contact Minimum 20 ms, opened or closed
Notes
Configure using any combination of analog or binary inputs/analog outputs Thermistor Resistive (setpoint) RTD 10k Type II, 10k Type III, 2252 Type II, 20k Type IV, 100 k 1001M Balco (Ni-Fe), 1k; 375, 385 (Pt), 1k 20 mA (linear) 020 Vdc (linear) Dry contact Minimum 20 ms, opened or closed
The UC600 provides 600 mA of DC power for 020 mA inputs and/or outputs, and to power expansion modules. See the power budget table in the Tracer UC600 Installation, Operation, and Maintenance guide, BAS-SVX045-EN.
Inputs 6
Current Voltage Outputs Pulse Binary Output Pressure Input Point total 4 1 19 Relay (form A) wet 3-wire
020 mA @16 V 010 Vdc @20 mA 12.5ms to 1 second (12.5ms resolution), 1 second to 60 seconds (0.5 second resolution) 24 VAC, 0.5A maximum 05 in H2O Ranges are given per contact. Pressure input supplied with 5 Vdc. Designed for Kavlico pressure transducers.
BAS-PRC063-EN
30 Nov 2012
Controller dimensions
8.50 in. (215.9 mm) width
IMC
24 VAC XFMR
24 VAC OUT
MBUS
24 VAC OUT
IMC
UI1
1
UI2
UI3
UI4
UI5
UI6
UI7
UI8
P1
UC600
BO1 BO2 BO3 BO4 LINK MBUS IMC
TX RX LINK
SERVICE
ACT
SERVICE TOOL
901
2 3
ADDRESS 901
7 8
2 3
901
2 3
7 8
7 8
x100
x10
AO1 UI9
Trane optimizes the performance of homes and buildings around the world. A business of Ingersoll Rand, the leader in creating and sustaining safe, comfortable and energy efficient environments, Trane offers a broad portfolio of advanced controls and HVAC systems, comprehensive building services, and parts. For more information, visit www.Trane.com.
Trane has a policy of continuous product and product data improvement and reserves the right to change design and specifications without notice. 2012Trane All rights reserved BAS-PRC063-EN 30 Nov 2012 Supersedes BAS-PRC063-EN (26 Sep2012) We are committed to using environmentally conscious print practices that reduce waste.
456
x1 AO2 UI10 AO3 UI11 AO4 UI12 AO5 UI13 AO6 UI14 RELAYS 0.5 A MAX BO1 BO2 BO3 BO4
456
456