F FL LO OW W: Vampire - Electronic Indicator
F FL LO OW W: Vampire - Electronic Indicator
F FL LO OW W: Vampire - Electronic Indicator
OPERATING PRINCIPLE
The VAMPIRE is a metal tube variable area flowmeter: as the flow up through the precision machined tapered tube increases, the float rises, reaching an equilibrium position. Electron beam welded within the float casing is a magnet. Two Hall effect magnetic field sensors measure both the vertical and horizontal components on this field. The angle of the magnetic field defines the position of the float in the tapered tube. This solid state measurement eliminates the problems of mechanical hysteresis associated with conventional magnetic pointers. Field angle is also independent of the absolute value of magnet strength, and sensor sensitivity.
FEATURES
4-20mA Transmitter Intrinsically safe approval Liquid or Gas Flow Calibration Built-in Flow Totaliser Operator adjustable High and Low Alarms 1% Accuracy VA meter reliability Program setting password protection
DS1225
Issue 3: 23.02.06
Page 1 of 3
The measurements are compared with a look-up table of field and flow data, stored in the VAMPIRE microprocessor memory on factory flow rig calibration. Flow rate is deduced accurately by interpolation between data points. The micro-processor converts the flow rate to correct Engineering units for the digital display on the LCD, adjusts the display meter pointer and 4-20mA output, sets the Alarm status and increments the totaliser as necessary. Keypads on the VAMPIRE front panel are used to set flow alarm levels, zero the totaliser and select the digital display as rate or total. Via a password entry procedure, the site engineer can reset the display units or even rescale the flowmeter to allow for changes to process conditions. This programme also has selections to define what functions are accessible to the operator (without password), plus zero, span and time constant adjustments. FLOW RANGES
Model Flow Digit Digit Water (L/hr) 160 250 400 600 Air (m3/hr) 5 7.5 12 18 Max P (mBar) 15 30 20 35 GMTX 1 (15mm/1/2 250 Long) 1 2 3 4
1 2 3 4 5 6 1 2 3 4 1 2 3 1
NB Ranges are quoted for Water at 20oC, Air at ATP (1.013 Bar and 20oC). Flow ranges for other fluids or process conditions on application. Units will be calibrated for customers specific conditions. Normally, scales offer 10:1 operating turndown. Pressure drops quoted are at maximum flow rates.
SPECIFICATION
Temperature Ambient GMTX: 50oC GMTA: 70oC Fluid 300oC Polyester coated aluminium. Weatherproof to IP65 4 off suitable for 2-5mm cable. External M6 stud fitted. 85-265V, 50-60Hz, 0-2A max - current consumption 24Vdc loop powered (12V min, 30V max LCD 0-100% analogue scale 90mm long. Digital Display, 4/5 digits 10mm high. Selectable for Flow Rate or Total. 1% FSD GMTXA 20mA into 600 max. GMTXD 4-20mA, 2 wire transmitter. 0.5%on current output, 80mA GMTXA: 2 x 8A SPCO relays @ 230V ac max 100mA, max switched 30V, Internal Impedance 100. GMTXD: 2 x open collector transistors. Display 1-19,999. Pulse output selectable instead of flow alarm output. 50msec pulse length. Max pulse rate 2/sec (GMTXD). GMTXD is intrinsically safe approvded to CENELEC EExia IIBT4. CRN (Contact Sales for details). 28V, 300W for 20mA line. 10V, 50W for alarm signals.
Totaliser
Approvals
Zener Barriers
DISPLAY
Liquid Crystal Display Panel High Alarm Value Flow Rate Meter (% Scale)
KEYPADS
Reset Totaliser (if programme allows) Alarm Messages Flash (when tripped) Programme Prompts Engineering Units Selected for Digital Display Digital Display - Flow Rate or Flow Total Select Rate or Total Display Enter Programme via Password
DS1225
Issue 3: 23.02.06
Page 2 of 3
INSTALLATION
1. Ensure that no ferromagnetic material is situated within 100mm of the indicator. Model GMTXA has output relays de-energised for alarm conditions. Model GMTXD transistor outputs are off for alarm conditions. The negative line is common to the transistor outputs and the loop supply. Intrinsically safe installations of Model GMTXD should be in accordance with BS5345 Part 4. The 4-20mA loop should be protected by an approved standard 28 Volt 300W shunt diode safety barrier. If required, the alarm outputs should be connected via approved 10 Volt 50W safety barriers. It is recommended that the VAMPIRE LCD display is protected from both extremes of freezing and direct sunlight.
2.
3.
4.
5.
FEATURES
Separate Terminal Box Liquid Crystal Display Panel Tapered Flow Tube Solid State Magnetic Field Sensors Float Magnet Inside Electron Beam Welded Casing
Every effort has been made during the preparation of this document to ensure the accuracy of statements and specifications. However, we do not accept liability for damage, injury, loss or expense caused by errors or omissions made. We reserve the right to withdraw or amend products or documentation without notice. Head Office: 2 Downgate Drive, Sheffield, S4 8BT, England Tel: +44(0)114 244 2521 Fax: +44(0)114 243 4838
1-4 Campbell Court, Bramley, Tadley, Hampshire, RG26 5EG, England Tel: +44(0)1256 884901 Fax: +44(0)1256 882986 email: sales@roxspur.com www.roxspur.com
DS1225
Issue 3: 23.02.06
Page 3 of 3