Location via proxy:   [ UP ]  
[Report a bug]   [Manage cookies]                

Himap Bcs

Download as pdf or txt
Download as pdf or txt
You are on page 1of 22
At a glance
Powered by AI
The HiMAP-BCS is a multifunction protection relay that provides various protection, measurement, control and communication capabilities for substations.

The HiMAP-BCS provides 26 different protection functions to protect feeders, motors and transformers including overcurrent, earth fault, over/under voltage, thermal overload and more.

The HiMAP-BCS supports the IEC 61850 communication protocol as well as Modbus RTU via RS-485 or fiber optic connections, allowing it to integrate with various SCADA systems.

IEC 61850 protocol digital multifunctional relay - HiMAP-BCS

HYUNDAI HIMAP-BCS is a multifunction protection relay based on the microprocessors and integrates with the new technology of electrical, electronic, and mechanical field of HYUNDAI. Nowadays our customers have required much more integrated multi protection relay, monitoring and control devices for better and easier maintenance, performance, electrical system analysis and communication according to new trend of switchgear. HiMAP-BCS has a protection function to protect incoming and feeder lines, the motor and the transformer. It also has various kind of measuring function & control function are linked to Power management system with IEC 61850 communication.

We build a better future!

Fault wave record function

Flexible logic building function

IEC 61850 communication protocol

Various kinds of measuring function

Circuit breaker control function

Color touch LCD


Improving operators convenience and displaying various informations

Logic editor
Easy and various logic building by using the editor.

Use of a digital filter


Minimizing the harmonics with a digital filter.

Various monitoring function


Self diagnostic function and fault monitoring of Circuit Breaker & Potential Transformer

C O N T E N T S
Characteristics and Functions Display Configuration Specification Connection Diagram Terminal Block Pin Specification 4 6 8 12 13 Characteristic Curve Order Form View & Dimension Certification 14 18 19 20

HiMAP-BCS

Hyundai Intelligent Measuring and Protection Device - Bay Control for Substation

Characteristics and Functions


Excellent measurement, operation and user interface with 32-bit dual microprocessor Easy access to menu with High density color TFT touchable LCD panel and Display various power status Embodied 26 protective functions in single IED Comply with IEC 61850, new industrial standard Various logic configuration for interlock

Fault Wave and Event Record


HiMAP-BCS saves fault record to removable memory. The saving information includes fault phase and magnitude, point of fault-time, operating time of function, rate of harmonic wave and so on. For recent fault, 300 periodic waves (5 sec) of the current and voltage of each phase are auto-saved as 36-sampling per period. It can record 100 faults and transfer to other system with the communication ports located in the front and back. All records in memory can be analyzed with HiMAPBCS Manager program.

Harmonic Wave Analyzing Function


For the currents of 3-phase, HiMAP-BCS measures amounts of harmonic wave (1st - 13th) of each phase. For the fault-wave of 3-phase, HiMAP-BCS can analyze amounts of harmonic wave (1st - 18th) of each phase. (Using HiMAP-BCS manager program)

Harmonic wave analysis

Fault wave

Vector diagram

Event display

HiMAP-BCS

Protection Relay Function


Type
HiMAPBCS

Protection Object
Incoming Motor Transformer 50/51 (OCR) 37 (UCR) 49 (THR) 64 (OVGR) 67GS (SGR)

Relay Function
50G/51G (OCGR) 27 (UVR) 46 (NSR) 59 (OVR) 66 (NCHR) 67 (DOCR) 47P/47N (VPSR/VNSR) 51LR (Stall/Locked Rotor) 67GD (DGR) 67N (DOCGR)

87T (DFR-TR) 87M (DFR-Motor) 50BF (Breaker Failure) FF (Fuse Failure) 79 (Reclosing) 87G (Restrict Earth Fault) 94 (TCS)

Measuring Function
Measuring
Voltage (Vab, Vbc, Vca, Vo, Vps, Vns, Vavg, Vomax) Current (Ia, Ib, Ic, Io, Ips, Ins, Iavg) Real Power Reactive Power Apparent Power Accumulated Real Energy Accumulated Reactive Energy Power Factor Frequency

Display Range
0-999999V 0-999999A 0-99999999kW 0-99999999kvar 0-99999999kVA 0-99999999kWh 0-99999999kvarh -1.0-1.0PF 50-70Hz

Accuracy (%)
0.2 0.2 0.2 0.5 0.5 1.0 1.0 0.5 0.01Hz

CT/PT ratio will be set by using relay control keys and then displayed via Display window. The values will be saved at flash memory even though the power line will be off.

Remote Control of Circuit Breaker


HiMAP-BCS can control of circuit breaker by order through communication from remote user and it makes remote control of feeder from external communication module. HiMAP-BCS complies with IED 61850 and modbus protocol and can be connected to various SCADA system. And it helps simplify the system. Interlock wiring can be epochally reduced by logic from user definition.
Logic editor

HiMAP-BCS

Hyundai Intelligent Measuring and Protection Device - Bay Control for Substation

Display Configuration
User Interface Menu
HiMAP-BCS Provides a graphic display with a color LCD and touch panel as a kind of HMI (Human-Machine Interface).

Mimic diagram display


User can configure mimic to describe single line and data with mimic-edit program from PC. Normal picture file-format, easy edit and register library are possible.

Vector diagram display


User can recognize magnitude and phase-angle of current or voltage of each phase. The values of data are indicated in numeral text and distinguished by color.

Wave monitoring display in real time


For selected current or voltage phase, up to 2 waves can be plotted for 2 period. With colorful display, easy to recognize wave and their measuring data.

Harmonic graph display


The analysis of harmonic wave from voltage or current is recognized by graph and figure up to the 13th wave.

Status monitoring display (Transformer, motor, re-closer, input/output and so on)


HiMAP-BCS displays every protective function and
6

operating status

HiMAP-BCS

Event display
All events (operation, input/output, settings, control, ...) can be recorded. Event lists can be shown also in HiMAP-BCS manager program. HiMAP-BCS records up to 100,000 events. For events detailed information, HiMAP-BCS shows additional information. Events can be sorted by each item. Analysis of events is convenient.

Digital input/output naming display


For digital input/output, user can name them. The named signal is shown in event display so that user can easily recognize them.

Protection factor setting display


Different setting display for 24 protective functions. With wide screen, various kinds of information can be displayed at a time and advantage of convenience is increased. Easy correct of figures for setting with touch-screen.

Network setting display


For IEC 61850 communication, network setting is displayed. For GPS time setting, user can recognize the IP of NTP server. IP, Gateway, Subnet Mask and Mac address of HiMAP-BCS are directly corrected by touch-screen.

HiMAP-BCS
Specification
General Specification
Item
Current Rating Voltage Frequency Accuracy Measuring

Hyundai Intelligent Measuring and Protection Device - Bay Control for Substation

Specification
1A or 5A, Burden: Below 0.4VA/Phase 110V or 190V, Burden: Below 0.4VA/Phase 50Hz or 60Hz 0.2% 2.0% -10 - 55 -25 - 70 above 10M above 5M above 5M AC 60Hz 2,000V/1Min 1.2/50 5kV Rating Current 3: 3hours / Rating Current 20: 2sec Rating Voltage 3: 3hours Rating Voltage 1.3: 3hours Maximum 300ms AC/DC 95V - 250V 50/60Hz, DC 48V IEC 60255 / KEMC 1120 / IEC 61000-4 / IEC 61850 RS-485 Multi Drop / Fiber Optic MODBUS / IEC61850 220 (W) 272.5 (H) 218.5 (D) 7kg 21W

Protection Relaying Temperature Operation Guarantee Restoration Guarantee Circuits-Ground Insulation Resistance Between Circuits Between Contacts Voltage Withstand Power Frequency Lightning Impulse Current Circuit Overland Withstand Voltage Circuit Control Power Control Power Interruption Control Power Standards Communication Type Protocal Size Weight Consumption Power

I/O Points
Item
AI Voltage AI Current Input DI AI 4 - 20mA AI TCS, CCS Output DO Relay AO 4 - 20mA

Points
4 8 16 4 2 12 4

Remark

Dry Contact Option Option

Option

HiMAP-BCS

Protection Function
Rated Current AC 1A Instantaneous, Definite: 1.00 - 18.00A (0.01A step) Setting Range OCR (50-1/50-2) (51-1/51-2/51-3) Characteristic Instantaneous: Below 0.05sec Definite: (0.05 - 10sec, 0.01sec step) Inverse, Very inverse, Extremely inverse, Inverse-type D, Inverse-type E, Inverse-type F, Kepco inverse, Kepco very inverse: (Op Level: 0.05 - 10, 0.01 step) Rated Current AC 1A Instantaneous, Definite: 1.00 - 18.00A (0.01A step) Setting Range OCR-Secondary (50S-1/50S-2) (51S-1/51S-2/51S-3 ) Characteristic Instantaneous: Below 0.05sec Definite: (0.05 - 10sec, 0.01sec step) Inverse, Very inverse, Extremely inverse, Inverse-type D, Inverse-type E, Inverse-type F, Kepco inverse, Kepco very inverse: (Op Level: 0.05 - 10, 0.01 step) Rated Current AC 1A Instantaneous, Definite: 0.10 - 12.00A (0.01A step) Setting Range OCGR (50G-1/50G-2) (51G-1/51G-2) Characteristic Instantaneous: Below 0.05sec Definite: (0.05 - 10sec, 0.01sec step) Inverse, Very inverse, Extremely inverse, Inverse-type D, Inverse-type E, Inverse-type F, Kepco inverse, Kepco very inverse: (Op Level: 0.05 - 10, 0.01 step) Rated Voltage UVR (27-1/27-2) Setting Range Characteristic Rated Current UCR (37) Setting Range Characteristic Rated Current Setting Range NSR (46-1/46-2) Characteristic AC 110V 20.0 - 110.0V (0.1V step) Definite (0.05 - 10sec, 0.01sec step) AC 1A 0.04 - 0.50A (0.01A step) Definite (0.05 - 10sec, 0.01sec step) AC 1A 0.10 - 0.50A (0.01A step), 3.0 - 160.0V (0.1V step) Instantaneous: Below 0.05sec Definite: (0.05 - 10sec, 0.01sec step) Inverse, Very inverse, Extremely inverse, Inverse-type D, Inverse-type E, Inverse-type F, Kepco inverse, Kepco very inverse: (Op Level: 0.05 - 10, 0.01 step) Rated Voltage VPSR (47P) Setting Range Characteristic Rated Voltage VNSR (47N) Setting Range Characteristic Rated Current THR (49) Setting Range Characteristic AC 110V 55.0 - 110.0V (0.1V step) Definite (0.05 - 10sec, 0.01sec step) AC 110V 2.0 - 55.0V (0.1V step) Definite (0.05 - 10sec, 0.01sec step) AC 1A 0.10 - 1.20A (0.01A step), Block limit: 0.01 - 4.00A (0.01A step) Hot/Cold limit: 0.5 - 180sec (0.1sec step), tc/th: 0.1 - 20 (0.1 step) 9 Inverse, Very inverse, Extremely inverse, Inverse-type D, Inverse-type E, Inverse-type F, Kepco inverse, Kepco very inverse: 0.02 - 1.00A (0.01A step) Inverse, Very inverse, Extremely inverse, Inverse-type D, Inverse-type E, Inverse-type F, Kepco inverse, Kepco very inverse: 0.20 - 2.40A (0.01A step) Inverse, Very inverse, Extremely inverse, Inverse-type D, Inverse-type E, Inverse-type F, Kepco inverse, Kepco very inverse: 0.20 - 2.40A (0.01A step)

HiMAP-BCS
Specification
Protection Function

Hyundai Intelligent Measuring and Protection Device - Bay Control for Substation

Rated Current 51LR (Stall/Locked Rotor) Characteristic Rated Voltage Setting Range OVR (59-1/59-2) Characteristic Setting Range

AC 1A Starting current: 0.2 - 14.40A (0.01A step) Locked rotor current: 0.20 - 6.00A (0.01A step) Definite: (1 - 10sec, 0.01sec step) Extremely inverse: (1 - 60sec, 0.01sec step) AC 110V 120.0 - 160.0V (0.1V step) Definite: (0.05 - 10sec, 0.01sec step) Inverse, Very inverse, Extremely inverse, Inverse-type D, Inverse-type E, Inverse-type F, Kepco inverse, Kepco very inverse: (Op Level: 0.05 - 10, 0.01 step)

Rated Voltage Setting Range OVGR (64-1/64-2/64-3) Characteristic

AC 190V 19.0 - 95.0V (0.1V step) Instantaneous: Below 0.05sec Definite: (0.05 - 10sec, 0.01sec step) Inverse, Very inverse, Extremely inverse, Inverse-type D, Inverse-type E, Inverse-type F, Kepco inverse, Kepco very inverse: (Op Level: 0.05 - 10, 0.01 step)

Allowed Start NCHR (66) Thermal State Characteristic Rated Voltage Rated Current DOCR (67) Characteristic Setting Range Time

1 - 50 (1 step) Allow time: 1 - 60min (1min step) Reset time: 1 - 60min (1min step) 40 - 100% (1% step) Instantaneous AC 110V AC 1A 0.20 - 2.40A (0.01A step), 3.0 - 160.0V (0.1V step) (Ref.) 0deg - 359deg (1deg step), (Op) 30 - 90deg (1deg step) Definite: (0.05 - 10sec, 0.01sec step) Inverse, Very inverse, Extremely inverse, Inverse-type D, Inverse-type E, Inverse-type F, Kepco inverse, Kepco very inverse: (Op Level: 0.05 - 10, 0.01 step)

Rated Voltage Rated Current DOCGR (67N-1/67N-2) Characteristic Setting Range

AC 190V AC 1A 0.05 - 10.00A (0.01A step), 19.0 - 95.0V (0.1V step) (Ref.) 0deg - 359deg (1deg step), (Op) 10 - 170deg (1deg step) Definite: (0.05 - 10sec, 0.01sec step) Inverse, Very inverse, Extremely inverse, Inverse-type D, Inverse-type E, Inverse-type F, Kepco inverse, Kepco very inverse: (Op Level: 0.05 - 10, 0.01 step)

Rated Voltage DGR (67GD) Rated Current Setting Range Characteristic Rated Voltage SGR (67GS) Rated Current Setting Range Characteristic

AC 190V AC 1A 0.04 - 0.40A (0.01A step), 19.0 - 38.0V (0.1V step), 10 - 45deg (1deg step) Definite (0.05 - 10sec, 0.01sec step) AC 190V AC 1.5mA 1 - 10mA (1mA step), 19.0 - 38.0V (0.1V step), 45 - 75deg (1deg step) Definite (0.05 - 10sec, 0.01sec step)

10

HiMAP-BCS

Rated Current

AC 1A Primary current: 0.20 - 1.20A (0.01A step) Secondary current: 0.20 - 1.20A (0.01A step) Transformer type: Dy1 - Yy6 (16 type) Zero compensation: Enable/Disable Instantaneous ratio: 500 - 1500% (1% step)

Setting Range DFR-TR (87T)

Minimum pickup ratio: 20 - 100% (1% step) Knee point 1: 20 - 500% (1% step) Slope 1: 20 - 100% (1% step) Knee point 2: 20 - 1500% (1% step) Slope 2: 20 - 100% (1% step) 2nd harmonic content: 10 - 30% (1% step) Mode: Instantaneous differential, Percent differential

Characteristic

Instantaneous: Below 0.05sec Definite: (0.05 - 10sec, 0.01sec step)

Rated Current

AC 1A Phase current: 0.10 - 1.50A (0.01A step) Ground current: 0.10 - 1.50A (0.01A step) Instantaneous ratio: 500 - 1500% (1% step)

Setting Range REF (87G)

Minimum pickup ratio: 20 - 100% (1% step) Slope 1: 15 - 100% (1% step) Knee point: 20 - 500% (1% step) Slope 2: 15 - 150% (1% step) Mode: Instantaneous differential, Percent differential

Characteristic

Instantaneous: Below 0.05sec Definite: (0.05 - 10sec, 0.01sec step)

Rated Current DFR-Motor (87M) Characteristic Rated Current Breaker Failure (50BF) Setting Range Characteristic Rated Voltage Fuse Failure (FF) Setting Range Characteristic Reclosing Trials Setting Range

AC 1A 0.04 - 1.00A (0.01A step) Instantaneous: Below 0.05sec Definite: (0.05 - 10sec, 0.01sec step) AC 1A 0.10 - 4.00A (0.01A step) Definite (0.05 - 10sec, 0.01sec step) AC 110V 5.0 - 160.0V (0.1V step) Definite (0.05 - 10sec, 0.01sec step) 1 - 7 (1 step) Prepare time: 1.0 - 300.0sec (0.1sec step)

Reclosing (79)

Setting Time

Reclaim time: 10.0 - 600.0sec (0.1sec step) Reclosing time (1 - 7): 0.1 - 300sec (0.1sec step) Reclose duration: 0.1 - 5.0sec (0.1sec step)

Characteristic Auxiliary Power Supply Voltage Communication Port

Definite AC/DC 95 - 250V 50/60Hz, DC 48V RS-485 (Rear) x 1, RS-232C (Front) x 1, Fiber optic x 2

11

HiMAP-BCS

Hyundai Intelligent Measuring and Protection Device - Bay Control for Substation

Connection Diagram

12

HiMAP-BCS

Terminal Block Pin Specification

X2 (DI) Binary Input


31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 DI1 DI2 DI3 DI4 DI-COM1 DI5 DI6 DI7 DI8 DI-COM2 DI9 DI10 DI11 DI12 DI-COM3 DI13 (CB2 CLOSE) DI14 (CB2 OPEN) DI15 (CB1 CLOSE) DI16 (CB1 OPEN) DI-COM4

X3 (DO) Relay Output, CCS/TCS


51 52 53 54 55 56 57 58 59 60 61 62 63 64 65 66 67 68 DO1-NO DO2-NO DO3-NO DO123-COM DO4-NO DO4-COM DO5-NO DO5-COM DO6-NO DO6-COM DO7-NO DO7-COM LOCK-OUT-NO LOCK-OUT-COM CCS+ CCSTCS+ TCS-

X5 (CUR. I/O) 4-20mA Current I/O


77 78 79 80 81 82 83 84 85 86 +24VDC (CI) CUR. IN1 CUR. IN2 CUR. IN3 CUR. IN4 +24VDC (CO) CUR. OUT1 CUR. OUT2 CUR. OUT3 CUR. OUT4

X7 Service Port
1 3 5 7 9 11 13 15 17 19 21 23

X1 (AI) CT, PT Input


Ia-P Ib-P Ic-P Io1 Io2 Ia-S Ib-S Ic-S Va Vb Vc Vo 2 4 6 8 10 12 14 16 18 20 22 24

When using logic building, CB


ON/OFF Input must connects with No.46-49 certainly.

X4 (DO) CB ON/OFF Output


69 70 71 72 73 74 75 76 CB2-ON-NO CB2-ON-COM CB2-OFF-NO CB2-OFF-COM CB1-ON-NO CB1-ON-COM CB1-OFF-NO CB1-OFF-COM

X6 (COMM) Optical Ethernet


FO2 FO1 F.O. LAN 2 F.O. LAN 1

X8 (PWR) Power Port


97 98 99 PWR-P PWR-N FG

Optional X6 (COMM) RS-485


91 92 93 94 95 96 RS-485-V+ RS-485-VShield GND RS-485-V+ RS-485-VShield GND 13

HiMAP-BCS

Hyundai Intelligent Measuring and Protection Device - Bay Control for Substation

Characteristic Curve

Normal Inverse | OP LEVEL 0.05-10.00

Very Inverse | OP LEVEL 0.05-10.00

Extremely Inverse | OP LEVEL 0.05-10.00

Inverse Curve-D | OP LEVEL 0.05-10.00

14

HiMAP-BCS

Inverse Curve-E | OP LEVEL 0.05-10.00

Inverse Curve-F | OP LEVEL 0.05-10.00

Inverse-K (KEPCO) | OP LEVEL 0.05-10.00

Very Inverse-K (KEPCO) | OP LEVEL 0.05-10.00

15

HiMAP-BCS

Hyundai Intelligent Measuring and Protection Device - Bay Control for Substation

Characteristic Curve

THR (49), 51LR Characteristics

DGR

SGR

DOCR

Op. Current Ia Ib Ic

Ref. Volt Vbc Vca Vab

16

HiMAP-BCS

DOCGR

DFR-TR

87G REF

17

HiMAP-BCS
Order Form

Hyundai Intelligent Measuring and Protection Device - Bay Control for Substation

HiMAP-BCS

(Option)

Relay Type
A : FI/M/T M : FI/M/ML

Communication Function
I M O X : IEC 61850 : MODBUS-RTU (RS-485) : MODBUS-RTU (Fiber Optic) : N.A

Current I/O Module


A B C Z : AI (4-20mA 4Ch) : AO (4-20mA 4Ch) : AI with AO : N.A

TCS Function
T : TCS Required X : N.A

Logic Function
L : Logic Required X : N.A

TCS (Trip Coil Supervision) Circuit breaker coil disconnection check. Specify followings separately - CT (Secondary): 1 A - 87M: Differential Type or Self Balancing Type - Frequency: 50 Hz - AUX. POWER DC 48V HIMAP-BCS Manager S/W and Communication cable (IEC61850) are sold with separate way.

Ordering Example HIMAP-BCS-A-IBXL


A: Feeder/Incoming, Motor, Tr Protection include I: IEC 61850 B: Analog Out Required X: TCS N.A L: Logic Required

HIMAP-BCS-M-XCTX
M: Feeder/Incoming, Motor Protection include X: Communication N.A C: Analog Input/Out Required T: TCS required X: Logic N.A

18

HiMAP-BCS

View and Dimension

Weight: 7kg
220 20 218.5

272.5

Side View Front View

20

176.7

Top View Rear View


202 140 120

4- 4 4-M4 TAP

Panel Cut-out

5.7

245.5 255.5

3.2

200

240

19

HiMAP-BCS

Hyundai Intelligent Measuring and Protection Device - Bay Control for Substation

Certification [ KERI ]

20

HiMAP-BCS

Certification [ KEMA ]

21

HHIS-WC-SE-B29-00, 2009.12 Designed by MERMONT

Head Office

1, Jeonha-dong, Dong-gu, Ulsan, Korea Tel: 82-52-202-8101~8 Fax: 82-52-202-8100

Seoul (Sales & Marketing)


Orlando New Jersey London Tokyo Osaka Dubai Sofia Yangzhong

140-2, Gye-dong, Jongno-gu, Seoul, Korea Tel: 82-2-746-7579, 7523 Fax: 82-2-746-7648
3452 Lake Lynda Drive, Suite 170, Orlando, Florida 32817, U.S.A. Tel: 1-407-249-7350 Fax: 1-407-275-4940 300 Sylvan Avenue, Englewood Cliffs, NJ 07632, U.S.A. Tel: 1-201-816-0286 Fax: 1-201-816-4083 2nd Floor, The Triangle, 5-17 Hammersmith Grove, London, W6 0LG, UK Tel: 44-20-8741-0501 Fax: 44-20-8741-5620 8th Fl., Yurakucho Denki Bldg.1-7-1, Yuraku-cho, Chiyoda-gu, Tokyo, 100-0006, Japan Tel: 81-3-3212-2076, 3215-7159 Fax: 81-3-3211-2093 I-Room 5th Fl. Nagahori-Plaza Bldg. 2-4-8, Minami Senba, Chuo-Ku, Osaka, 542-0081, Japan Tel: 81-6-6261-5766, 5767 Fax: 81-6-6261-5818 Level 2, Unit 205, Emaar Square-Bldg.4 Sheikh Zayed Road, P.O.Box 252458, Dubai, U.A.E. Tel: 971-4-425-7995 Fax: 971-4-425-7996 1271, Sofia 41, Rojen Blvd., Bulgaria Tel: 359-2-803-3200 Fax: 359-2-803-3203 No. 9 Xiandai Road, Xinba Scientific and Technologic Zone, Yangzhong, Jiangsu, P.R.C. Zip: 212212, China Tel: 86-511-8842-0666, 0212 Fax: 86-511-8842-0668, 0231

You might also like