Himap Bcs
Himap Bcs
Himap Bcs
HYUNDAI HIMAP-BCS is a multifunction protection relay based on the microprocessors and integrates with the new technology of electrical, electronic, and mechanical field of HYUNDAI. Nowadays our customers have required much more integrated multi protection relay, monitoring and control devices for better and easier maintenance, performance, electrical system analysis and communication according to new trend of switchgear. HiMAP-BCS has a protection function to protect incoming and feeder lines, the motor and the transformer. It also has various kind of measuring function & control function are linked to Power management system with IEC 61850 communication.
Logic editor
Easy and various logic building by using the editor.
C O N T E N T S
Characteristics and Functions Display Configuration Specification Connection Diagram Terminal Block Pin Specification 4 6 8 12 13 Characteristic Curve Order Form View & Dimension Certification 14 18 19 20
HiMAP-BCS
Hyundai Intelligent Measuring and Protection Device - Bay Control for Substation
Fault wave
Vector diagram
Event display
HiMAP-BCS
Protection Object
Incoming Motor Transformer 50/51 (OCR) 37 (UCR) 49 (THR) 64 (OVGR) 67GS (SGR)
Relay Function
50G/51G (OCGR) 27 (UVR) 46 (NSR) 59 (OVR) 66 (NCHR) 67 (DOCR) 47P/47N (VPSR/VNSR) 51LR (Stall/Locked Rotor) 67GD (DGR) 67N (DOCGR)
87T (DFR-TR) 87M (DFR-Motor) 50BF (Breaker Failure) FF (Fuse Failure) 79 (Reclosing) 87G (Restrict Earth Fault) 94 (TCS)
Measuring Function
Measuring
Voltage (Vab, Vbc, Vca, Vo, Vps, Vns, Vavg, Vomax) Current (Ia, Ib, Ic, Io, Ips, Ins, Iavg) Real Power Reactive Power Apparent Power Accumulated Real Energy Accumulated Reactive Energy Power Factor Frequency
Display Range
0-999999V 0-999999A 0-99999999kW 0-99999999kvar 0-99999999kVA 0-99999999kWh 0-99999999kvarh -1.0-1.0PF 50-70Hz
Accuracy (%)
0.2 0.2 0.2 0.5 0.5 1.0 1.0 0.5 0.01Hz
CT/PT ratio will be set by using relay control keys and then displayed via Display window. The values will be saved at flash memory even though the power line will be off.
HiMAP-BCS
Hyundai Intelligent Measuring and Protection Device - Bay Control for Substation
Display Configuration
User Interface Menu
HiMAP-BCS Provides a graphic display with a color LCD and touch panel as a kind of HMI (Human-Machine Interface).
operating status
HiMAP-BCS
Event display
All events (operation, input/output, settings, control, ...) can be recorded. Event lists can be shown also in HiMAP-BCS manager program. HiMAP-BCS records up to 100,000 events. For events detailed information, HiMAP-BCS shows additional information. Events can be sorted by each item. Analysis of events is convenient.
HiMAP-BCS
Specification
General Specification
Item
Current Rating Voltage Frequency Accuracy Measuring
Hyundai Intelligent Measuring and Protection Device - Bay Control for Substation
Specification
1A or 5A, Burden: Below 0.4VA/Phase 110V or 190V, Burden: Below 0.4VA/Phase 50Hz or 60Hz 0.2% 2.0% -10 - 55 -25 - 70 above 10M above 5M above 5M AC 60Hz 2,000V/1Min 1.2/50 5kV Rating Current 3: 3hours / Rating Current 20: 2sec Rating Voltage 3: 3hours Rating Voltage 1.3: 3hours Maximum 300ms AC/DC 95V - 250V 50/60Hz, DC 48V IEC 60255 / KEMC 1120 / IEC 61000-4 / IEC 61850 RS-485 Multi Drop / Fiber Optic MODBUS / IEC61850 220 (W) 272.5 (H) 218.5 (D) 7kg 21W
Protection Relaying Temperature Operation Guarantee Restoration Guarantee Circuits-Ground Insulation Resistance Between Circuits Between Contacts Voltage Withstand Power Frequency Lightning Impulse Current Circuit Overland Withstand Voltage Circuit Control Power Control Power Interruption Control Power Standards Communication Type Protocal Size Weight Consumption Power
I/O Points
Item
AI Voltage AI Current Input DI AI 4 - 20mA AI TCS, CCS Output DO Relay AO 4 - 20mA
Points
4 8 16 4 2 12 4
Remark
Option
HiMAP-BCS
Protection Function
Rated Current AC 1A Instantaneous, Definite: 1.00 - 18.00A (0.01A step) Setting Range OCR (50-1/50-2) (51-1/51-2/51-3) Characteristic Instantaneous: Below 0.05sec Definite: (0.05 - 10sec, 0.01sec step) Inverse, Very inverse, Extremely inverse, Inverse-type D, Inverse-type E, Inverse-type F, Kepco inverse, Kepco very inverse: (Op Level: 0.05 - 10, 0.01 step) Rated Current AC 1A Instantaneous, Definite: 1.00 - 18.00A (0.01A step) Setting Range OCR-Secondary (50S-1/50S-2) (51S-1/51S-2/51S-3 ) Characteristic Instantaneous: Below 0.05sec Definite: (0.05 - 10sec, 0.01sec step) Inverse, Very inverse, Extremely inverse, Inverse-type D, Inverse-type E, Inverse-type F, Kepco inverse, Kepco very inverse: (Op Level: 0.05 - 10, 0.01 step) Rated Current AC 1A Instantaneous, Definite: 0.10 - 12.00A (0.01A step) Setting Range OCGR (50G-1/50G-2) (51G-1/51G-2) Characteristic Instantaneous: Below 0.05sec Definite: (0.05 - 10sec, 0.01sec step) Inverse, Very inverse, Extremely inverse, Inverse-type D, Inverse-type E, Inverse-type F, Kepco inverse, Kepco very inverse: (Op Level: 0.05 - 10, 0.01 step) Rated Voltage UVR (27-1/27-2) Setting Range Characteristic Rated Current UCR (37) Setting Range Characteristic Rated Current Setting Range NSR (46-1/46-2) Characteristic AC 110V 20.0 - 110.0V (0.1V step) Definite (0.05 - 10sec, 0.01sec step) AC 1A 0.04 - 0.50A (0.01A step) Definite (0.05 - 10sec, 0.01sec step) AC 1A 0.10 - 0.50A (0.01A step), 3.0 - 160.0V (0.1V step) Instantaneous: Below 0.05sec Definite: (0.05 - 10sec, 0.01sec step) Inverse, Very inverse, Extremely inverse, Inverse-type D, Inverse-type E, Inverse-type F, Kepco inverse, Kepco very inverse: (Op Level: 0.05 - 10, 0.01 step) Rated Voltage VPSR (47P) Setting Range Characteristic Rated Voltage VNSR (47N) Setting Range Characteristic Rated Current THR (49) Setting Range Characteristic AC 110V 55.0 - 110.0V (0.1V step) Definite (0.05 - 10sec, 0.01sec step) AC 110V 2.0 - 55.0V (0.1V step) Definite (0.05 - 10sec, 0.01sec step) AC 1A 0.10 - 1.20A (0.01A step), Block limit: 0.01 - 4.00A (0.01A step) Hot/Cold limit: 0.5 - 180sec (0.1sec step), tc/th: 0.1 - 20 (0.1 step) 9 Inverse, Very inverse, Extremely inverse, Inverse-type D, Inverse-type E, Inverse-type F, Kepco inverse, Kepco very inverse: 0.02 - 1.00A (0.01A step) Inverse, Very inverse, Extremely inverse, Inverse-type D, Inverse-type E, Inverse-type F, Kepco inverse, Kepco very inverse: 0.20 - 2.40A (0.01A step) Inverse, Very inverse, Extremely inverse, Inverse-type D, Inverse-type E, Inverse-type F, Kepco inverse, Kepco very inverse: 0.20 - 2.40A (0.01A step)
HiMAP-BCS
Specification
Protection Function
Hyundai Intelligent Measuring and Protection Device - Bay Control for Substation
Rated Current 51LR (Stall/Locked Rotor) Characteristic Rated Voltage Setting Range OVR (59-1/59-2) Characteristic Setting Range
AC 1A Starting current: 0.2 - 14.40A (0.01A step) Locked rotor current: 0.20 - 6.00A (0.01A step) Definite: (1 - 10sec, 0.01sec step) Extremely inverse: (1 - 60sec, 0.01sec step) AC 110V 120.0 - 160.0V (0.1V step) Definite: (0.05 - 10sec, 0.01sec step) Inverse, Very inverse, Extremely inverse, Inverse-type D, Inverse-type E, Inverse-type F, Kepco inverse, Kepco very inverse: (Op Level: 0.05 - 10, 0.01 step)
AC 190V 19.0 - 95.0V (0.1V step) Instantaneous: Below 0.05sec Definite: (0.05 - 10sec, 0.01sec step) Inverse, Very inverse, Extremely inverse, Inverse-type D, Inverse-type E, Inverse-type F, Kepco inverse, Kepco very inverse: (Op Level: 0.05 - 10, 0.01 step)
Allowed Start NCHR (66) Thermal State Characteristic Rated Voltage Rated Current DOCR (67) Characteristic Setting Range Time
1 - 50 (1 step) Allow time: 1 - 60min (1min step) Reset time: 1 - 60min (1min step) 40 - 100% (1% step) Instantaneous AC 110V AC 1A 0.20 - 2.40A (0.01A step), 3.0 - 160.0V (0.1V step) (Ref.) 0deg - 359deg (1deg step), (Op) 30 - 90deg (1deg step) Definite: (0.05 - 10sec, 0.01sec step) Inverse, Very inverse, Extremely inverse, Inverse-type D, Inverse-type E, Inverse-type F, Kepco inverse, Kepco very inverse: (Op Level: 0.05 - 10, 0.01 step)
AC 190V AC 1A 0.05 - 10.00A (0.01A step), 19.0 - 95.0V (0.1V step) (Ref.) 0deg - 359deg (1deg step), (Op) 10 - 170deg (1deg step) Definite: (0.05 - 10sec, 0.01sec step) Inverse, Very inverse, Extremely inverse, Inverse-type D, Inverse-type E, Inverse-type F, Kepco inverse, Kepco very inverse: (Op Level: 0.05 - 10, 0.01 step)
Rated Voltage DGR (67GD) Rated Current Setting Range Characteristic Rated Voltage SGR (67GS) Rated Current Setting Range Characteristic
AC 190V AC 1A 0.04 - 0.40A (0.01A step), 19.0 - 38.0V (0.1V step), 10 - 45deg (1deg step) Definite (0.05 - 10sec, 0.01sec step) AC 190V AC 1.5mA 1 - 10mA (1mA step), 19.0 - 38.0V (0.1V step), 45 - 75deg (1deg step) Definite (0.05 - 10sec, 0.01sec step)
10
HiMAP-BCS
Rated Current
AC 1A Primary current: 0.20 - 1.20A (0.01A step) Secondary current: 0.20 - 1.20A (0.01A step) Transformer type: Dy1 - Yy6 (16 type) Zero compensation: Enable/Disable Instantaneous ratio: 500 - 1500% (1% step)
Minimum pickup ratio: 20 - 100% (1% step) Knee point 1: 20 - 500% (1% step) Slope 1: 20 - 100% (1% step) Knee point 2: 20 - 1500% (1% step) Slope 2: 20 - 100% (1% step) 2nd harmonic content: 10 - 30% (1% step) Mode: Instantaneous differential, Percent differential
Characteristic
Rated Current
AC 1A Phase current: 0.10 - 1.50A (0.01A step) Ground current: 0.10 - 1.50A (0.01A step) Instantaneous ratio: 500 - 1500% (1% step)
Minimum pickup ratio: 20 - 100% (1% step) Slope 1: 15 - 100% (1% step) Knee point: 20 - 500% (1% step) Slope 2: 15 - 150% (1% step) Mode: Instantaneous differential, Percent differential
Characteristic
Rated Current DFR-Motor (87M) Characteristic Rated Current Breaker Failure (50BF) Setting Range Characteristic Rated Voltage Fuse Failure (FF) Setting Range Characteristic Reclosing Trials Setting Range
AC 1A 0.04 - 1.00A (0.01A step) Instantaneous: Below 0.05sec Definite: (0.05 - 10sec, 0.01sec step) AC 1A 0.10 - 4.00A (0.01A step) Definite (0.05 - 10sec, 0.01sec step) AC 110V 5.0 - 160.0V (0.1V step) Definite (0.05 - 10sec, 0.01sec step) 1 - 7 (1 step) Prepare time: 1.0 - 300.0sec (0.1sec step)
Reclosing (79)
Setting Time
Reclaim time: 10.0 - 600.0sec (0.1sec step) Reclosing time (1 - 7): 0.1 - 300sec (0.1sec step) Reclose duration: 0.1 - 5.0sec (0.1sec step)
Definite AC/DC 95 - 250V 50/60Hz, DC 48V RS-485 (Rear) x 1, RS-232C (Front) x 1, Fiber optic x 2
11
HiMAP-BCS
Hyundai Intelligent Measuring and Protection Device - Bay Control for Substation
Connection Diagram
12
HiMAP-BCS
X7 Service Port
1 3 5 7 9 11 13 15 17 19 21 23
HiMAP-BCS
Hyundai Intelligent Measuring and Protection Device - Bay Control for Substation
Characteristic Curve
14
HiMAP-BCS
15
HiMAP-BCS
Hyundai Intelligent Measuring and Protection Device - Bay Control for Substation
Characteristic Curve
DGR
SGR
DOCR
Op. Current Ia Ib Ic
16
HiMAP-BCS
DOCGR
DFR-TR
87G REF
17
HiMAP-BCS
Order Form
Hyundai Intelligent Measuring and Protection Device - Bay Control for Substation
HiMAP-BCS
(Option)
Relay Type
A : FI/M/T M : FI/M/ML
Communication Function
I M O X : IEC 61850 : MODBUS-RTU (RS-485) : MODBUS-RTU (Fiber Optic) : N.A
TCS Function
T : TCS Required X : N.A
Logic Function
L : Logic Required X : N.A
TCS (Trip Coil Supervision) Circuit breaker coil disconnection check. Specify followings separately - CT (Secondary): 1 A - 87M: Differential Type or Self Balancing Type - Frequency: 50 Hz - AUX. POWER DC 48V HIMAP-BCS Manager S/W and Communication cable (IEC61850) are sold with separate way.
HIMAP-BCS-M-XCTX
M: Feeder/Incoming, Motor Protection include X: Communication N.A C: Analog Input/Out Required T: TCS required X: Logic N.A
18
HiMAP-BCS
Weight: 7kg
220 20 218.5
272.5
20
176.7
4- 4 4-M4 TAP
Panel Cut-out
5.7
245.5 255.5
3.2
200
240
19
HiMAP-BCS
Hyundai Intelligent Measuring and Protection Device - Bay Control for Substation
Certification [ KERI ]
20
HiMAP-BCS
Certification [ KEMA ]
21
Head Office
140-2, Gye-dong, Jongno-gu, Seoul, Korea Tel: 82-2-746-7579, 7523 Fax: 82-2-746-7648
3452 Lake Lynda Drive, Suite 170, Orlando, Florida 32817, U.S.A. Tel: 1-407-249-7350 Fax: 1-407-275-4940 300 Sylvan Avenue, Englewood Cliffs, NJ 07632, U.S.A. Tel: 1-201-816-0286 Fax: 1-201-816-4083 2nd Floor, The Triangle, 5-17 Hammersmith Grove, London, W6 0LG, UK Tel: 44-20-8741-0501 Fax: 44-20-8741-5620 8th Fl., Yurakucho Denki Bldg.1-7-1, Yuraku-cho, Chiyoda-gu, Tokyo, 100-0006, Japan Tel: 81-3-3212-2076, 3215-7159 Fax: 81-3-3211-2093 I-Room 5th Fl. Nagahori-Plaza Bldg. 2-4-8, Minami Senba, Chuo-Ku, Osaka, 542-0081, Japan Tel: 81-6-6261-5766, 5767 Fax: 81-6-6261-5818 Level 2, Unit 205, Emaar Square-Bldg.4 Sheikh Zayed Road, P.O.Box 252458, Dubai, U.A.E. Tel: 971-4-425-7995 Fax: 971-4-425-7996 1271, Sofia 41, Rojen Blvd., Bulgaria Tel: 359-2-803-3200 Fax: 359-2-803-3203 No. 9 Xiandai Road, Xinba Scientific and Technologic Zone, Yangzhong, Jiangsu, P.R.C. Zip: 212212, China Tel: 86-511-8842-0666, 0212 Fax: 86-511-8842-0668, 0231