7sa5222 Setting Sheet
7sa5222 Setting Sheet
7sa5222 Setting Sheet
5 CT ratio sec : 1 A
7 System frequency : 50 Hz
Line Data's
Details Parameters Actual shortest Longest
Length KM 86 40 157
Relay details
Relay Type : 7SA522
Make : SIEMENS
Rated current : 1A
CT Details
CT Ratio : 600 A
Adopted Ratio : 600
CT Secondary : 1A
System Details
VT Primary : 220kV
VT Secondary : 110V
Voltage Level : 220kV
Frequency : 50Hz
OHL Data:
BASE kV : 220kV
BASE MVA : 230.0 MVA
Line Length : 86.0Km
A separate arc Resistance tolerance can be set for earth faults.An resistance of 4.9 Ohms
and Tower footing resistance of 9.5 Ohms (Primary Values)
Positive Sequence Resistance = ((R1 x 100% of the protected Line) + (R1 x 50% of
the Adjacent shortest Line)+(1/2*Rarc)) x N
R(Z2) 3.292
Set at R(Z2) = 3.292 ohm
Positive Sequence Resistance = ((R1 x 100% of the protected line) + (R1 x 100%
Adjacent longest Line) + (1/2*Rarc)) x N
R(Z3) 6.596
Set at R(Z3) = 6.596 ohm
Positive Sequence Resistance = ((R1 x 100% of the protected Line) + (R1 x 50% of
the Adjacent shortest Line)+(1/2*Rarc)) x N
R(Z1B) 3.292
Set at R(Z1B) = 3.292 ohm
6.877
Set at RE(Z1B) = 6.877 ohm
Set to Z2 and Higher Zones blocked and no trip during Power swing
THE RATIO FOR THE LINE LENGTH ABOVE 25KM = 0.4 (As per Manual)
THE RATIO FOR THE LINE LENGTH BELOW 25KM = 0.6
Line Reactance per Unit Length X' = Positive Seq reactance * CTR/PTR
THE IDMT CURVE SHALL SATURATE 20 TIMES OF PICKUP CURRENT.SO WE HAD TAKEN THIS
CURRENT FOR TMS CALCULATION
20 TIMES OF PICKUP CURRENT = 20*180 A
= 3600 A
TMS = 0.53
Directional Angle = -45˚
T2 Start criteria
MEASURMENT SUPERVISION = ON
IF THE FUSE FAIL FUNCTION OPERATES, IT WILL BLOCK THE DISTANCE PROTECTION.
MINIMUM VOLTAGE THRESHOLD U> = 30 V
MAXIMAM CURRENT THRESHOLD I< = 0.1 A
MINIMUM VOLTAGE THRESHOLD U< = 15 V
DELTA CURRENT THRESHOLD = 0.1 A
VOLTAGE FAILURE SUPERVISION = WITH CURRENT SUPERVISION
DELAY VOLTAGE FAILURE SUPERVISION = 3 SEC
DIRECT TRIP SEND
SYNCHRONIZING SETTINGS
MINIMUM VOLTAGE LIMIT = 99 V (90% OF NOMINAL VOLTAGE)
MAXIMUM VOLTAGE LIMIT = 121 V (110% OF NOMINAL VOLTAGE)
THRESHOLD V1,V2 WITHOUT VOLTAGE = 5.5 V
THRESHOLD V1,V2 WITH VOLTAGE = 88 V (80% OF NOMINAL VOLTAGE)
SWITCHING AT SYNCHRONOUS CONDITION = YES
ON COMMAND AT V1< AND V2> = YES
ON COMMAND AT V1> AND V2< = YES
ON COMMAND AT V1< AND V2< = NO
MAXIMUM VOLTAGE DIFFERENCE = 11 V
MAXIMUM FREQUENCY DIFFERENCE = 0.1 Hz
MAXIMUM ANGLE DIFFERENCE = 10 Deg
RELEASE DELAY AT SYNCH CONDITIONS = 0 Sec
NOTE:
These settings are applicable if the protection is enabled only in the configuration
If the protection is disabled in the configuration menu please ignore.