50by 1W PDF
50by 1W PDF
50by 1W PDF
Wiring Diagrams
INDEX
UNIT 50BYN V-PH-Hz LABEL DIAGRAM FIG. NUMBER
006 208/230-3-60
008 460-3-60 11720011-C 1
575-3-60
012 208/230-3-60
014 460-3-60 11720960-B 2
016 575-3-60
208/230-3-60
024 460-3-60 1172007-C 3
575-3-60
ACCESSORY WIRING
UNIT 50BYN ACCESSORY DESCRIPTION FIG. NUMBER
Winter Start 4
Evaporator Defrost Thermostat 5
TEMP Thermostat 6
Variable Volume and Temperature (VVTT) and Relay Pack 7
006-024
Airside Economizer 8
Airside Economizer with Indoor Air Quality (IAQ) Sensor 9
Fire and Smoke Control 10
Heater 11
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Book 1 4 PC 111 Catalog No. 535-051 Printed in U.S.A. Form 50BY-1W Pg 1 3-99 Replaces: New
Tab 2b 7a
LEGEND FOR FIG. 1-7
C — Compressor Contactor IFM — Indoor-Fan Motor Field Splice
CB — Circuit Breaker IFP — Indoor-Fan Protector
CLO — Compressor Lockout LPS — Low-Pressure Switch
CR — Control Relay NEC — National Electrical Code Terminal Block Connection
DT — Defrost Thermostat (Evaporator) OFC — Outdoor-Fan Contactor
EQUIP — Equipment OFM — Outdoor-Fan Motor Marked Terminal
FSS — Filter Status OFP — Outdoor-Fan Protector
GND — Ground R — Resistor Unmarked Terminal
HPS — High-Pressure Switch T — Timer Factory Wiring
HS — Humidity Sensor TB — Terminal Block
IAQ — Indoor Air Quality TDR — Time-Delay Relay Field Wiring
IFC — Indoor-Fan Contactor TRAN — Transformer
2
A 5-minute timer (Time-Delay Relay [TDR]) will prevent air and energizes Y1 of the unit. On a call for a second stage
the compressor(s) from restarting for 5 minutes after any com- of cooling (Y2 energized), the actuator energizes Y1 on the
pressor has stopped. unit if the outdoor air enthalpy is acceptable. If the outdoor
If the condenser-fan motor overheats due to motor over- air is unacceptable, the actuator logic module energizes Y2
load or lack of cooling air, the internal fan protector will of the unit. When the system is equipped with a CO2 sensor
open the circuit internally in the motor, and the fan will stop. in a modulating configuration, the following applies: If the
If a safety control in the unit opens, the condenser fan will system is operating in the Cooling mode and the demand for
also stop. fresh air to reduce the carbon dioxide level in the space is
greater than the cooling load demand, the actuator modu-
Accessories — Low ambient control on 50BYN units lates to reduce the carbon dioxide level and does not modu-
is accomplished with a refrigerant operated damper located late towards closed if the leaving-air temperature is below
on the condenser fan discharge. Low ambient operation does 56 F. If, however, the cooling demand is greater than the
not affect operating sequence. demand to reduce the carbon dioxide level, the actuator modu-
lates open and controls to a 56 F leaving-air temperature.
WINTER START (38AE900021) — Since these units are The damper modulates open when the leaving-air tempera-
equipped with a 27 psig low-pressure switch, a 3-minute low- ture demand is greater than the airflow demand required for
pressure switch bypass is recommended for operation below the CO2 sensor to reduce carbon dioxide levels. When the
50 F. Order Winter Start Control accessory no. 38AE900021 CO2 sensor is installed, there is no minimum leaving air tem-
and install according to the instructions supplied with the perature control at the economizer.
kit. See Fig. 4 for low-pressure switch bypass wiring.
USING A CO2 SENSOR WITH THE ECONOMIZER — A
DEFROST THERMOSTAT (50BB-900---001) — This ther- separately ordered carbon dioxide sensor (Fig. 9) can be used
mostat is installed on the evaporator coil and is recom- to signal the economizer to open the outdoor-air dampers to
mended with Winter Start control. Install thermostat accord- admit fresh air and dilute the indoor CO2 level. Sensor de-
ing to instructions supplied with the kit. See Fig. 5 for proper scriptions and part numbers are shown below.
wiring of defrost thermostat.
Economizer CO2 Sensor Accessories
ECONOMIZER SEQUENCE OF OPERATION — When the CO2 SENSOR ACCESSORY DESCRIPTION
thermostat turns the indoor fan on, the economizer relay is PART NUMBERS
energized and the actuator is powered on. The actuator moves CGCDXSEN001A00 Wall Mount Sensor (No Display)
CGCDXSEN002A00 Wall Mount Sensor With Display
the dampers to the minimum position as determined by the CGCDXSEN003A00 Duct Mount Sensor (No Display)
adjustment potentiometer on the actuator. If the system uses CGCDXGAS001A00 Sensor Calibration Service Kit
a CO2 sensor, the minimum position is determined by the CGCDXPRM001A00 User Interface Program (UIP)
potentiometer on the required field-supplied adapter. On a
call for heating from the thermostat (W1 and/or W2 ener- The CO2 sensors listed above are all factory set for a range
gized), the economizer remains at the minimum position. of 0 to 2000 ppm and a linear voltage output of 2 to 10 vdc.
NOTE: If a CO2 sensor is used, the economizer can modu- The relay normally open dry contacts (TB-3 and TB-4) are
late based on the carbon dioxide level in the space. There is factory set to close at 1000 ppm. Refer to the installation
no low leaving-air temperature limit control. Controls to ac- instructions with the CO2 sensor for electrical ratings of con-
complish this must be field-supplied and installed. tacts and information on connecting to power supply. Switch
contacts can be used to set off an alarm or light to indicate
On a call for cooling from the thermostat (Y1 energized), CO2 levels higher than the switch set point. Any changes to
the actuator logic module determines if the outdoor air en- the factory configuration require the purchase of the User
thalpy is acceptable according to the set point on the actua- Interface Program (UIP) or Sensor Calibration Service Kit,
tor. If the outdoor air enthalpy is acceptable, the economizer which also contains the UIP. For correct modulation of the
begins to modulate open and is controlled to maintain a economizer actuator motor, a separately ordered adapter
56 F leaving air temperature. If outdoor air enthalpy is (Honeywell part no. Q769C1007) is required.
unacceptable, the logic module bypasses the use of outdoor
3
4
Fig. 1 — Wiring Schematic and Component Arrangement; 50BYN006-008; 208/230-3-60, 460-3-60, 575-3-60
5
Fig. 2 — Wiring Schematic and Component Arrangement; 50BYN012-016; 208/230-3-60, 460-3-60, 575-3-60
6
Fig. 3 — Wiring Schematic and Component Arrangement; 50BYN024; 208/230-3-60, 460-3-60, 575-3-60
BLK ORN RED
50 BYN UNIT
RED
CB C LOW VOLTAGE WIRING
TRAN
RED A C BRN
3.2 AMPS
24V
BLU
CR IFP
1 3 BLK RED C1 IFC C2
R
TB2 BRN
G BLK
C1 OFC C2
BRN BRN
R1 BLU
T1 ORN
3
LOGIC
2 2 1
Y1 ORN RED LOGIC BRN
1
TDR1 CLO1 OFP
3 LPS1 HPS1
X
X ORN BLU BLU BLU C1 C1 C2
BLU
C BRN
C1 CR C2 BRN
TDR
WINTER
START
7
BLK ORN RED
50 BYN UNIT
RED
CB C LOW VOLTAGE WIRING
TRAN
RED A C BRN
3.2 AMPS
24V
BLU
CR IFP
1 3 BLK RED C1 IFC C2
R
TB2 BRN
G BLK
REMOVE C1 OFC C2
ORN WIRE BRN
BRN
R1 BLU
T1 ORN
3
LOGIC
2 2 1
Y1 RED LOGIC BRN
1
TDR1 CLO1 OFP
3 LPS1 HPS1
X
X ORN BLU BLU BLU C1 C1 C2
BLU
C BRN
C1 CR C2 BRN
DT
8
BLACK
COMMUNICATION RED
BUS GREEN
RED (+)
TO HEATER
REMOTE ROOM BLACK (-) IF USED
SENSOR
SEE NOTE BELOW
FIGURE "A"
HUMIDITY SENSOR
W
R
HS 10
11 WHITE W 13
RED R 12
FILTER STATUS BLUE B 11 FAN
SWITCH 10 HEAT 2
YELLOW Y
FSS 10 GREEN G 9 HEAT 1 NC
1 2 1 2 F R
11 6 A V
8 HEAT 1
IAQ SWITCH N 7 HEAT/FAN COM
7
8
COOL HEAT 6 COOL 2
FAN STATUS SWITCH 5
DX COIL 9 COOL 1
TEMPERATURE 10 FIELD-INSTALLED 4 COOL COM
SEE "A" 3
SENSOR 11 JUMPERS 24 VAC (REQ)
BLACK 2
BLACK 12 24 VAC (COMMON)
BLACK 13 1 GROUND
OUTSIDE AIR RED 14
TEMPERATURE RED 15
RED
JUMPER
SENSOR 16
7 TO 4 TO 3
17
50 BYN UNIT
LOW VOLTAGE WIRING
CB C
TRAN
RED A C BRN
3.2 AMPS
24V
RED
CR IFP
TB2
ORN 1 3 BLK RED C1 IFC C2
R
TB2 BRN
G BLK
BRN C1 OFC C2
BRN BRN
BLU
T1 ORN
3
LOGIC
2 2 1
Y1 ORN RED LOGIC BRN
1
TDR1 CLO1 OFP
3 LPS1 HPS1
X
X ORN BLU BLU BLU C1 C1 C2
BLU
C BRN
C1 CR C2
3
LOGIC BRN
2 2 1 BRN
Y2 BLK RED LOGIC BRN
1
TDR2 CLO2 LPS1 HPS1
X 3
T2 BLK ORN ORN BLU C1 C2 C2
9
BLACK
GREEN
WHITE
RED
COMMUNICATION HUMIDITY SENSOR
BUS WHT WHITE
BLACK BLK RED
RED GRN
BLK BLACK
GREEN ORN GREEN
RED
RED (+) BLK VELOCITY SENSOR
RED
DAMPER BLK
BLACK
RED
ACTUATOR
RED
BLACK (-)
RED DX COIL SENSOR
WHITE
BLUE BLACK
YELLOW MONITOR STAT RED
GREEN
W/TIME CLOCK OUTSIDE AIR SENSOR
TRANSFORMER
DC CONNECTOR HARNESS TO 24 VAC/25VA
DAMPER ACTUATOR BOARD
TO HEATING COIL
REMOTE ROOM (IF USED)
SENSOR (RRS) 24 VAC POWER CONNECTOR
(OPTIONAL) TO ZONE DAMPER BOARD
CHR06 RELAY PACK
(LOCATE IN LOW
VOLTAGE COMPARTMENT) WHITE H1
BROWN H2
YELLOW C1
BLUE C2
GREEN FSN
RED 24 VAC
BLACK (RVH)
ORANGE (RVC)
CR IFP
TB2
ORN 1 3 BLK RED C1 IFC C2
R
TB2 BRN
G BLK
BRN C1 OFC C2
BRN BRN
BLU
T1 ORN
3
LOGIC
2 2 1
Y1 ORN RED LOGIC BRN
1
TDR1 CLO1 OFP
3 LPS1 HPS1
X
X ORN BLU BLU BLU C1 C1 C2
BLU
C BRN
C1 CR C2
3
LOGIC BRN
2 2 1 BRN
Y2 BLK RED LOGIC BRN
1
TDR2 CLO2 LPS1 HPS1
X 3
T2 BLK ORN ORN BLU C1 C2 C2
10
BLK ORN RED
50 BYN UNIT
C
LOW VOLTAGE WIRING
CB ER
TRAN
RED A C BRN
3.2 AMPS
24V
RED
CR IFP
FIELD THERMOSTAT TB2
NEC CLASS II ORN 1 3 BLK RED C1 IFC C2
R
CONT
BRN
G BLK
AUTO BRN C1 OFC C2
BRN BRN
BLU
T1 ORN
COOL TC1 LOGIC
3
2 2 1
Y1 ORN RED LOGIC BRN
1
OFF TDR1 CLO1
3 LPS1 HPS1 OFP
X
X ORN BLU BLU BLU C1 C1 C2
BLU
C BRN
C1 CR C2
3
LOGIC BRN
2 2 1 BRN
TC2 Y2 BLK RED LOGIC BRN
1
TDR2 CLO2 LPS2 HPS2
X 3
T2 BLK ORN ORN BLU C1 C2 C2
TR
ER 24 VAC
WHT WHT TR TR1 TR1
GRN
ENTHALPY
+ +
SO ECONOMIZER
ACTUATOR
S ORN
SENSOR
RESISTOR SR +
SEE NOTE 2
1
YEL S
1K
RED 1 2 1S
2K
BRN 3 4
SENSOR T
SAT MIXED AIR
GRA 1S1
SENSOR
GRA T T1 T1
LEGEND
C — Compressor Contactor SEE NOTE 1
P P1 P1
MINIMUM POSITION MINIMUM
CB — Circuit Breaker ADJUSTMENT POSITION
P
CLO — Compressor Lockout
CR — Control Relay
ER — Economizer Relay T BLU
HPS — High-Pressure Switch
IFC — Indoor-Fan Contactor
IFP — Indoor-Fan Protector
LPS — Low-Pressure Switch
NEC — National Electrical Code
OFC — Outdoor-Fan Contactor
OFP — Outdoor-Fan Protector NOTES:
SAT — Supply-Air Temperature 1. If system has single-stage cooling, disregard and terminate blue wire in
TB — Terminal Block harness. If thermostat is single stage cooling, disregard and terminate
TDR — Time-Delay Relay brown wire.
TR — Terminal 2. Factory installed 620 ohm, 1 watt, 5% resistor should be removed only
TRAN — Transformer if a C7400 enthalpy sensor is added to SR and + for differential enthalpy.
3. Economizer relay closes outside air damper when fan is not powered.
Terminals
Wire Nut or Equivalent Connection
Field Wiring
Factory Wiring
Fig. 8 — Wiring Diagram; Airside Economizer
11
HONEYWELL DAMPER
ACTUATOR M7415 AND
W7459 LOGIC MODULE MINIMUM POSITION POTENTIOMETER
SET TO FULL OPEN POSITION. THIS WILL
ALLOW FOR 100% OUTSIDE AIR AT
2250 PPM
P P1
WHITE BLACK
BLACK
P1 REAR TOP IS "P1"
WHITE
P REAR BOTTOM IS "P"
LEGEND
P — Pressurization Relay
PPM — Parts per Million TB10 TB9
TB — Terminal Block
24V-DO NOT USE HVAC
UNIT TRANSFORMER. PROVIDE CO 2 VENTILATION
24V BY NON-GROUNDING CONTROLLER
TRANSFORMER
NOTES:
1. CO2 Ventilation controller can be mounted in return-air duct or wall
mounted. Locate for best room air sampling. If duct mounted,
install in aspiration box.
2. Damper actuator and logic module ordered separately.
3. The CO2 ventilation controller has a range of 350 to 2250 PPM
and has a hysteresis of 50 PPM.
4. Optional temperature switches can be added to lockout occupied
modes setting for extreme high or low temperatures.
Fig. 9 — Wiring Diagram; Airside Economizer With Indoor Air Quality (IAQ) Sensor
12
BLK ORN RED
50BYN UNIT
C
LOW VOLTAGE WIRING
CB ER
TRAN
RED A C BRN
3.2 AMPS
24V
RED
FIRE OR SMOKE
DETECTOR
CONTACTS
(SHUTS DOWN CR IFP
FIELD THERMOSTAT UNIT) TB2
NEC CLASS II ORN 1 3 BLK RED C1 IFC C2
R
CONT P1 BRN
G BLK
AUTO BRN C1 OFC C2
BRN BRN
BLU
T1 ORN
COOL TC1 LOGIC
3
P2 2 2 1
Y1 ORN RED LOGIC BRN
1
OFF TDR1 CLO1
3 LPS1 HPS1 OFP
X
X ORN BLU BLU BLU C1 C1 C2
BLU
C BRN
C1 CR C2
3
LOGIC BRN
F1 2 2 1 BRN
TC2 Y2 BLK RED LOGIC BRN
1
TDR2 CLO2 LPS2 HPS2
X 3
T2 BLK ORN ORN BLU C1 C2 C2
ER
FROM POWER SUPPLY EXH
FAN
TR
ER 24 VAC
WHT WHT TR TR1 TR1
GRN
ENTHALPY
+ +
SO ECONOMIZER
ACTUATOR
5 ORN
SENSOR
RESISTOR SR +
SEE NOTE 2
1
YEL S
1K
RED 1 2 1S
2K
BRN 3 4
SENSOR T
SAT MIXED AIR
GRA 1S1 ER
SENSOR
GRA T T1 T1
LEGEND
SEE NOTE 1
P P1 P1
C — Compressor Contactor MINIMUM POSITION MINIMUM
CB — Circuit Breaker ADJUSTMENT POSITION
P
CLO — Compressor Lockout
CR — Control Relay
T
ER — Economizer Relay BLU
HPS — High-Pressure Switch
IFC — Indoor-Fan Contactor
IFP — Indoor-Fan Protector
LPS — Low-Pressure Switch
NEC — National Electrical Code
OFC — Outdoor-Fan Contactor
OFP — Outdoor-Fan Protector
P1 — Pressurization Relay NOTES:
R — Resistor 1. If system has single-stage cooling, disregard and terminate blue wire in har-
SAT — Supply-Air Temperature ness. If thermostat is single stage cooling, disregard and terminate brown wire.
TB — Terminal Block 2. Factory installed 620 ohm, 1 watt, 5% resistor should be removed only if a C7400
TDR — Time-Delay Relay enthalpy sensor is added to SR and + for differential enthalpy.
TRAN — Transformer 3. Economizer relay closes outside air damper when fan is not powered.
Terminals
Wire Nut or Equivalent Connection
Field Wiring
Factory Wiring
13
H1
TO 1ST STAGE VALVE
OR CONTACTOR
H2
TO 2ND STAGE VALVE
OR CONTACTOR BLK ORN RED
H1 C
CB
TRAN
RED A C BRN
3.2 AMPS
H2 24V
RED
CR IFP
TB2
ORN 1 3 BLK RED C1 IFC C2
RC R
RH BRN
OFF
HEAT G BLK
ON BRN C1 OFC C2
AUTO FAN G BRN
SW BRN
COOL AUTO BLU
T1 ORN
TH1 AHA 3
LOGIC
2 2 1
Y1 ORN RED LOGIC BRN
W1 1
TDR1 CLO1 OFP
TH2 AHA X 3 LPS1 HPS1
X ORN BLU BLU BLU C1 C1 C2
W2 BLU
X C BRN
C1 CR C2
OFF
L 3
HEAT LOGIC BRN
AUTO 2 2 1 BRN
Y2 BLK RED LOGIC BRN
C 1
COOL TC1 TDR2 CLO2
Y1 X 3 LPS2 HPS2
T2 BLK ORN ORN BLU C1 C2 C2
CC CC
TC2
Y2
FIELD THERMOSTAT
LEGEND
AHA — Adjustable Heat Anticipator R — Resistor
C — Compressor Contactor TB — Terminal Block
CB — Circuit Breaker TDR — Time-Delay Relay
CLO — Compressor Lockout TRAN — Transformer
CR — Control Relay
H1, H2 — Heater Relay Terminal Block Connection
HPS — High-Pressure Switch Marked Terminal
IFC — Indoor-Fan Contactor
IFP — Indoor-Fan Protector Unmarked Terminal
LPS — Low-Pressure Switch Factory Wiring
OFC — Outdoor-Fan Contactor Field Wiring
OFP — Outdoor-Fan Protector
Fig. 11 — Wiring Diagram; Accessory Heater
14
Copyright 1999 Carrier Corporation
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Book 1 4 PC 111 Catalog No. 535-051 Printed in U.S.A. Form 50BY-1W Pg 16 3-99 Replaces: New
Tab 2b 7a